DCA600SSK
WhisperWatt Generator
WhisperWatt
600
Prime Rating: 480 kW (600 kVA)
Standby Rating: 528 kW (660 kVA)
60 Hertz
™
WhisperWattWhisperWatt
WhisperWatt
WhisperWattWhisperWatt
■
Heavy duty, turbocharged, aftercooled, direct
injection diesel engine provides maximum reliability.
■
Brushless alternator reduces service and maintenance
requirements and meets temperature rise standards for
Class F insulation systems.
■
Open delta alternator design provides virtually
unlimited excitation for maximum motor starting capability.
■
Automatic voltage regulator (AVR) provides precise
regulation.
■
Electronic governor system maintains frequency to
±0.25%.
■
Full load acceptance of standby nameplate rating in
one step (NFPA 110, para 5-13.2.6).
■
Sound attenuated, weather resistant, steel housing
provides operation at 75 dB(A) at 23 feet. Fully lockable
enclosure allows safe unattended operation.
■
Internal fuel tank with direct reading fuel gauges are
standard.
■
Seven-stage powder coat paint provides durability and
weather protection.
■
EPA-MOH emissions certified.
™
Standard Features Standard Features
Standard Features
Standard Features Standard Features
■
■
■
■
■
■
■
Complete engine analog instrumentation includes DC
ammeter, oil pressure gauge, water temp. gauge,
tachometer/hour meter, preheat indicator, manual engine
speed control, emergency shutdown monitors, and
emergency stop button.
Complete generator analog instrumentation includes
voltage regulator control, ammeter phase selector switch,
voltmeter phase selector switch, AC voltmeter, AC
ammeter, frequency meter, panel light, and circuit breaker.
Automatic safety shutdown system monitors the water
temperature, engine oil pressure, overspeed, and
overcrank. Warning lights indicate abnormal conditions.
Auto start/stop control allows generator to start
automatically in the event of a commercial power failure.
Complete power panel. Fully covered; three-phase
terminals and single phase receptacles allow fast and
convenient hookup for most applications including
temporary power boxes, tools and lighting equipment. All
are NEMA standard.
Simultaneous single and three phase power.
Emergency stop switch

SpecificationsSpecifications
Specifications
SpecificationsSpecifications
Generator Specifications
Design
No. of Poles 4-pole
Excitation Brushless with AVR
Standby Output 528 KW (660 KVA)
Prime Output 480 KW (600 KVA)
Generator RPM 1800
Voltage — 3Ø
Voltage — 1Ø 120, 127, 139, 240, 254, 277V Adjustable
Armature Connection Star with neutral
Voltage Regulation
(No load to full load)
Power Factor 0.8
Frequency 60 Hz
Frequency Regulation:
No Load to Full Load
Frequency Regulation:
Steady State
Insulation Class F
Sound Level dB(A)
Full load at 23 feet
Revolving field, self-ventilated,
drip-proof, single bearing
208, 220, 240, 416, 440, 480V
Reconnectable
±1.0%
Isochronous under varying loads from no
load to 100% rated load
±0.25% of mean value for constant loads
from no load to full load
75
DCA600SSK
WhisperWatt Generator
Cooling System
Fan Load 18.8 hp (14 kW)
Coolant Capacity (with radiator) 29.6 gallons (112 liters)
Coolant Flow Rate (per minute) 197 gallons (744 liters)
Heat Rejection to Coolant (per minute)
Heat Radiated to Room (per minute)
Maximum Coolant Friction Head 5.0 psi (34 kPa)
Maximum Coolant Static Head 45 feet (14 meters)
Ambient Temperature Rating 95°F (35°C)
Air
Combustion Air
Maximum Air Cleaner Restriction 30 in. H
Alternator Cooling Air 3023 cfm (86 m
Radiator Cooling Air 18891 scfm (535 m
Minimum Air Opening to Room 46 sq.ft (4.26 sq.m)
Minimum Discharge Opening 16.5 sq.ft (1.5 sq.m)
Standby: 19715 Btu (20.8 MJ)
Prime: 17535 Btu (18.5 MJ)
Standby: 4151 Btu (4.38 MJ)
Prime: 3697 Btu (3.90 MJ)
3
/min)
3
3
/min)
3
/min)
/min)
Standby: 1815 cfm (51 m
Prime: 1776 cfm (50 m
O (7.0 kPa)
2
Engine Specifications
Make / Model Komatsu / SA6D170AE-1
Emissions EPA Tier 2 Certified
Starting System Electric
Design
Displacement 23,150 cc
No. cylinders 6
Bore x Stroke (mm) 170 x 170
Gross Engine Power Output
BMEP
Piston Speed 2008 ft./min. (10 m/s)
Compression Ratio 14:1
Engine Speed 1800 rpm
Overspeed Limit 2100 rpm
Oil capacity gallons (liters) 16.1 (60.9)
Battery 12V 200Ah x 2 (24V System)
Direct Injection,
Turbocharged, Aftercooled
539 bhp (402 kWm) Standby
490 bhp (365 kWm) Prime
257 psi (1773 kPa)
234 psi (1612 kPa)
Fuel System
Maximum Fuel Flow (per hour) Standby: 41 gallons (37 liters)
Maximum Inlet Restriction (Hg) 0.4 in. (9.8 mm)
Maximum Return Restriction (Hg) 3.9 in. (98 mm)
Fuel Tank Capacity 129.5 gallons (490 liters)
Fuel Consumption
full load gph (lph)
75% load gph (lph)
50% load gph (lph)
25% load gph (lph)
33.9 (128.3)
26.7 (101.1)
17.4 (65.9)
10.6 (40.1)
Exhaust System
Gas Flow (full load)
Gas Temperature
Maximum Back Pressure 40 in. H
4555 cfm (129 m
4449 cfm (126 m
858°F (459°C) Standby
822°F (439°C) Prime
3
/min) Standby
3
/min) Prime
O (10 kPa)
2
Amperage
Rated Voltage Maximum Amps
1Ø 120 Volt 1333.3 amps (4 wire)
1Ø 240 Volt 666.7 amps (4 wire)
3Ø 240 Volt 1443.4 amps
3Ø 480 Volt 721.7 amps
Warranty*
Komatsu Engine
12 months from date of purchase or 1000 hours (whichever
occurs first).
Generator
12 months from date of purchase or 1000 hours (whichever
occurs first).
*Refer to the express written, one-year limited warranty sheet for additional
information.
Backfeed to a utility system can cause electrocution and/or property damage. Do
not connect to any building’s electrical system except through an approved device.
Specifications are subject to change without notice.