DCA125USI
Ultra-Silent Series
WhisperWatt
TM
125
Prime Rating: 100 kW (125 kVA) Standby Rating: 110 kW (137 kVA)
60 Hertz
Heavy duty, 4-cycle, direct injection, turbocharged, air to air intercooled diesel engine provides maximum
reliability.
Brushless alternator reduces service and maintenance requirements and meets temperature rise standards for Class F insulation systems.
Open delta alternator design provides virtually unlimited excitation for maximum motor starting capability.
Automatic voltage regulator (AVR) provides precise regulation.
Electronic governor system maintains frequency to ±0.25%.
Full load acceptance of standby nameplate rating in one step (NFPA 110, para 5-13.2.6).
Sound attenuated, weather resistant, steel housing
provides operation at 65 dB(A) at 23 feet. Fully lockable enclosure allows safe unattended operation.
Internal fuel tank with direct reading fuel gauges are standard.
Seven stage powder coat paint provides durability and weather protection.
Complete engine analog instrumentation includes DC ammeter, oil pressure gauge, water temp. gauge, fuel level gauge, tachometer/hour meter, manual engine speed control, and emergency shutdown monitors.
Complete generator analog instrumentation includes voltage regulator control, ammeter phase selector switch, voltmeter phase selector switch, AC voltmeter, AC ammeter, frequency meter, panel light, and circuit breaker.
Automatic safety shutdown system monitors the water temperature, engine oil pressure, overspeed, and overcrank. Warning lights indicate abnormal conditions.
Auto start/stop control allows generator to start automatically in the event of a commercial power failure.
Complete power panel. Fully covered; three-phase terminals and single phase receptacles allow fast and convenient hookup for most applications including temporary power boxes, tools and lighting equipment. All are NEMA standard.
Fuel/water separator removes condensation from fuel for extended engine life.
EPA emissions certified - Tier 3 emissions compliant.
DCA125USI Rev 2
Page 2
Specifications
DCA125USI
Ultra-Silent Series
Generator Specifications
Design
No. of Poles 4-pole
Excitation Brushless with AVR
Standby Output 110 KW (137 KVA)
Prime Output 100 KW (125 KVA)
Generator RPM 1800
Voltage — 3Ø 208, 220, 240, 416, 440, 480V Switchable
Voltage — 1Ø 120, 127, 139, 240, 254, 277V Switchable
Armature Connection Star with neutral / Zig Zag
Voltage Regulation (No load to full load)
Power Factor 0.8
Frequency 60 Hz
Frequency Regulation: No Load to Full Load
Frequency Regulation: Steady State
Insulation Class F
Sound Level dB(A) Full load at 23 feet
Revolving field, Self-ventilated
Drip-proof, Single bearing
±0.5%
Isochronous under varying loads from
no load to 100% rated load
±0.25% of mean value for constant loads
from no load to full load
65
Engine Specifications
Make/Model Isuzu / 4HK1X
Emissions EPA Tier 3 Certified
Starting System Electric
Design
Displacement 5193 cc
No. cylinders 4
Bore x Stroke (mm) 115 x 125
Gross Engine Power Output 170.3 hp (127 kW)
HP at Rated Speed 152.3 hp (113.6 kW)
BMEP 212 psi (1458 kPa)
Piston Speed 1480 ft/min (7.50 m/s)
Compression Ratio 17.5 : 1
Engine Speed 1800 rpm
Overspeed Limit 2070 rpm
Oil capacity gallons (liters) 6.1 (23.4)
Battery 12V 128 Ah x 1
4-cycle, watercooled, direct injection,
turbocharged, air to air intercooled
Fuel System
Recommended Fuel ASTM-D975-No.1 and No. 2-D
Maximum Fuel Flow (per hour) 19.0 gal (71.0 L)
Maximum Inlet Restriction (Hg) 8.9 in (225 mm)
Fuel Tank Capacity 169 gal (640 L)
Fuel Consumption gph lph
at full load 7.3 27.6
at 3/4 load 5.7 21.7
at 1/2 load 4.0 15.1
DCA125USI Rev 2
at 1/4 load 2.4 9.1
Cooling System
Fan Load 4.4 hp (3.3 kW)
Coolant Capacity (with radiator) 5.2 gal (19.7 L)
Coolant Flow Rate (per minute) 48 gal (180 L)
Heat Rejection to Coolant (per minute) 3500 Btu (3.7 MJ)
Heat Rejection from Engine (per minute) 1040 Btu (1.1 MJ)
Maximum Coolant Friction Head 6.5 psi (45.0 kPa)
Maximum Coolant Static Head 29.5 ft (9.0 m)
Ambient Temperature Rating 104°F (40°C)
Air
Combustion Air 297 cfm (8.4 m3/min)
Maximum Air Cleaner Restriction
Alternator Cooling Air 1352 cfm (38.3 m
Radiator Cooling Air 2944 cfm (83 m
25.0 in H
O (6.25 kPa)
2
3
/min)
3
/min)
Exhaust System
Gas Flow (full load) 738 cfm (20.9 m3/min)
Gas Temperature 986°F (530°C)
Maximum Back Pressure 53.2 in/H
O (13.3 kPa)
2
Amperage
Rated Voltage Maximum Amps
1Ø 120 Volt 277.8 Amps (4 wire)
1Ø 240 Volt 138.9 Amps (4 wire)
3Ø 240 Volt 300 Amps
3Ø 480 Volt 150 Amps
Main Line Circuit Breaker Rating 300 Amps
Over Current Relay Trip Set Point 152 Amps
Warranty*
Isuzu Engine
12 months from date of purchase with unlimited hours or 24 months from date of purchase with 2000 hours (whichever comes first).
Generator
24 months from date of purchase or 2000 hours (whichever occurs first).
Trailer
12 months excluding normal wear items.
*Refer to the express written, one-year limited warranty sheet for additional information.
Generator is not intended for use in enclosed areas or where free flow of air is restricted.
Backfeed to a utility system can cause electrocution and/or property damage. Do not connect to any building’s electrical system except through an approved device.
Specifications are subject to change without notice.
Page 3
Ultra-Silent Features
DCA125USI
Ultra-Silent Series
Generator Output Panel
Low Noise Muffler— Large capacity low noise muffler minimizes exhaust sound.
Soundproof Casing— The new design divides the cabinet into three sections, separating the engine, muffler and radiator for more efficient cooling and reduces noise from the engine and fans.
New Cooling System— An advanced design uses two separate air intake systems to cool the generator. The engine fan draws air in to cool the engine and generator housing while a second electric fan directly cools the radiator. With less air being drawn into the generator through each fan, considerably less noise is produced through the top of the generator.
Environmental Design — Constructed using an integrated environmental skid and fuel tank. This design fully contains fuel leakage and any liquid that might leak from the engine such as lube oil or radiator coolant. All potentially hazardous liquids are contained without contaminating the surrounding area.
Outside Air
Electric Fan Radiator
Diesel engine
Control
box
Outside air
Optional Control Features
Audible alarm alerts operator of abnormal conditions.
Low coolant level shutdown system provides
protection from critically low coolant levels. Includes control panel warning light.
Emergency stop switch
Optional Generator Features
Battery charger — provides fully automatic and self-
adjusting charging to the generator's battery system.
Jacket water heater — for easy starting in cold weather climates.
Special batteries — long life batteries provide extra engine cranking power.
Spring isolaters — provides extra vibration protection for standby applications.
Trailer mounted package — highway legal, double axle trailer with electronic or surge brakes.
Optional Output Connections
Flow of Cooling Air
AC generator
Cam-Loks — provides quick disconnect alternative to bolt-on connectors.
Pin and Sleeve Connectors — provides industry standard connectors for all voltage requirements.
Output Cable — available in any custom length and size configuration.
DCA125USI Rev 2
Page 4
Dimensions
DCA125USI
Ultra-Silent Series
Weight
Dry Weight 5689 lb (2580 kg)
Wet Weight 7012 lb (3180 kg)
Max. Lifting Point
Capacity
Manufactured by Denyo Co.
Your MQ Power dealer is:
14050 lb (6370 kg)
© COPYRIGHT 2010 MQ POWER Rev 2 (10-10) DCA125USI
MQ POWER
POST OFFICE BOX 6254 CARSON, CA 90749 310-537-3700 • 800-883-2551 FAX: 310-604-3831 E-MAIL: mqpower@multiquip.com WEBSITE: www.mqpower.com