Mr. Steam MS400EE3X, MS400ED3X Specifications

®
mr.steam
Technical Specifications
______________________________________________________ Model MS 400E
Serial Number 9000000 and higher
ater Inlet
W
Mr.Steam Standard Features
Stainless steel tank
• Industrial, large diameter, serviceable heating element
• Modular Plug and Play connections
• Electronic water-levelcontrol system
• Full-port drain valve.
• Limited lifetime steam generator parts warranty
Control & Acces­sory Connections
Steam Outlet
afety Valve
S
Manual Drain Valve
ptional
O
AutoFlush
Safety Features
• Built-in, low-voltage 24-volt control
• ASME safety valve
Locating and Installing the Steam Generator Unit
• Select a location as near as practical to the steam room, within 60 feet. Typical locations include: closet, van­ity cabinet, heated attic or basement
• Do not install steambath generator inside the steam room.
• Do not install steambath generator outdoors or wherever environmental conditions may affect the safety and/ or performance of the generator
• Do not install steambath generator or plumbing lines in unheated attic or any locations where water could freeze
• Do not install steambath generator near flammable or corrosive materials
• 60-minute electronic countdown shutdown with 75-minute limiting safety back-up
or chemicals or in areas having a high con-
centration of chlorine
• Install steambath generator on a solid and level surface or securely mounted to a wall using the keyhole slots provided.
• Install steambath generator in an upright position only
• Provide a minimum of 12 inches inches at both ends and top of the steam generator or as required for servicing. Alternately provide unions to facilitate installation and disconnection of the steam generator.
• The minimum clearance from com­bustible surfaces is zero all around.
Electrical
All electrical wiring to be installed by a qualified licensed electrician in accordance with National Electrical Code and local electrical code.
Power Wiring
1. Check power voltage.
2. Use minimum 90˚ C/600V rated insulated copper
conductors only, type THHN or equal sized in accordance with National Electrical Code and local electrical code for the Amps in Ampere Chart.
If allowed by code, NM cable may require a larger
wire size than as listed on the chart.
3. Connect suitably sized equipment grounding wire to ground terminal provided.
4. Install a separate circuit breaker between supply and unit. Provide a power supply disconnect within sight of the steam generator or one that is capable of being locked in the open position.
A M P E R E C H A R T
Required Plumbing
Steam Outlet (1/2" NPT) Safety Valve (3/4" NPT) Drain (1/2" NPT) Steam Head (1/2" NPT)
MODEL NO. VOL. CU.M. KW 3 PH AMPS (AWG)
MS 400E 10.1 9.0 380 14 12
MAX ROOM VOLTS WIRE SIZE
415 13 12
Water Supply (3/8" NPT)
FOR ILLUSTRATIVE PURPOSES ONLY. IMPORTANT NOTE: FOR SAFE AND TROUBLE FREE INSTALLATION
visit mrsteam.com or scan the QR code before installation to download the Installation, Operation and Maintenance Manual or refer to the manual provided with the unit.
MODEL VOLTAGE* PHASE OPTIONS PROJECT INFORMATION
MS400E
Notes:
Required Equipment: iSteam, iTempoPlus or iTempo Control
mr.steam
43-20 34th Street, Long Island City, NY 11101 TEL: 800 76 STEAM FAX: 718 472 3256 / 9410 S. La Cienega Blvd. Inglewood CA 90301 TEL:800 72 STEAM FAX: 310 216 2944
D=380

E=415
*
Contact Mr. Steam for other voltages
®
Sussman-Automatic Corp
3-Three Phase
Optional Equipment: iGenie, AudioWizard, ChromaSteam, HomeWizard, Recessed Light, MS Light, MS Wallseat, AutoFlush, Drip Pan, AromaSteam, Chlorine Filter, FORM Shower Systems
®
hello@mrsteam.com www.mrsteam.com
Express Steam
Location:
Architect:
Engineer:
Contractor:
Submitted By:
Date:
TS0041-400EX REV 8.15
Loading...