Mitsubishi Melsec-Q, SW1D5C-QTIU-E, Q68TD-G-H01, Q68TD-G-H02 User Manual

Page 1
Page 2
Page 3

SAFETY PRECAUTIONS

(Read these precautions before use.)
Before using this product, please read this manual and the relevant manuals introduced in this manual carefully and pay full attention to safety to handle the product correctly. The instructions given in this manual are concerned with this product. For the safety instructions of the programmable controller system, please read the User's Manual for the CPU module. In this section, the safety precautions are ranked as "DANGER" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
DANGER
CAUTION
Note that the CAUTION level may lead to a serious consequence according to the circumstances.
Always follow the precautions of both levels because they are important to personal safety.
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight personal injury or physical damage.
Please keep this manual accessible when required and always forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
Do not write data into the "system area" of the buffer memory of intelligent function modules. Also, do not use any "prohibited to use" signals as an output signal to an intelligent function module from the programmable controller CPU. Writing data into the "system area" or outputting a signal for "prohibited to use" may cause a malfunction of the programmable controller system.
CAUTION
Do not bunch the control wires or communication cables with the main circuit or power wires, or install them close to each other. They should be installed 100 mm (3.94 inch) or more from each other. Not doing so could result in noise that may cause malfunction.
A - 1
Page 4
[INSTALLATION PRECAUTIONS]
CAUTION
Use the programmable controller in the environment conditions given in the general specifications in the User's Manual for the CPU module. Failure to do so may cause an electric shock, fire, malfunction, or damage to or deterioration of the product.
While pressing the installation lever located at the bottom of the module, fully insert the module fixing projection into the fixing hole in the base unit to mount the module. Incorrect module mounting may cause a malfunction, failure, or drop of the module. Mount the module on the base unit, and then fix the module with a module fixing screw. (Q68TD-G­H02 only) When using the program controller in an environment of frequent vibrations, fix the module with a module fixing screw. (Q68TD-G-H01 only)
The screws must be tightened within the specified torque range. If the screw is too loose, it may cause a drop or malfunction. Excessive tightening may damage the screw and/or the module, resulting in a drop or malfunction.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the module. Failure to do so may cause damage to the product. In the system where a CPU module supporting the online module change is used and on the MELSECNET/H remote I/O stations, modules can be replaced online (during energizing). However, there are some restrictions on replaceable modules and the replacement procedures are predetermined for each module. For details, refer to the chapter of the online module change in this manual.
Do not directly touch any conductive part or electronic part of the module. Doing so may cause a malfunction or failure of the module.
[WIRING PRECAUTIONS]
CAUTION
Always ground the shielded cables for the programmable controller. There is a risk of electric shock or malfunction.
For wiring and connection, properly press, crimp or solder the connector with the tools specified by the manufactures and attach the connector to the module securely.
Be careful to prevent foreign matter such as dust or wire chips from entering the module. Failure to do so may cause a fire, failure or malfunction.
A - 2
Page 5
[WIRING PRECAUTIONS]
CAUTION
A protective film is attached to the module top to prevent foreign matter such as wire chips from entering the module during wiring. Do not remove the film during wiring. Be sure to remove it for heat dissipation before system operation.
Be sure to place the cables connected to the module in a duct or clamp them. If not, dangling cables may swing or inadvertently be pulled, resulting in damage to the module and/ or cables, or malfunctions due to poor cable connection.
When disconnecting the external wiring cable connected to the module, do not pull it by holding the cable part. Disconnect the cable with connector with holding the connector plugged into the module. Pulling the cable part with the cable still connected to the module may cause a malfunction or damage to the module and/or cable.
Always place the thermocouple at least 100mm (3.94inch) away from the main circuit cables and AC control lines. Fully keep it away from highvoltage cables and circuits, which include high frequency waves, such as an inverter's load circuit. Not doing so will cause the module more susceptible to noises, surges and inductions.
Do not place a module near the equipment that generates magnetic noise.
A - 3
Page 6
[STARTING AND MAINTENANCE PRECAUTIONS]
CAUTION
Do not disassemble or modify the modules. Doing so could cause failure, malfunction injury or fire.
Be sure to shut off all phases of the external power supply used by the system before mounting or removing the module. Not doing so may cause damage to the module. In the system where a CPU module supporting the online module change is used and on the MELSECNET/H remote I/O stations, modules can be replaced online (during energizing). However, there are some restrictions on replaceable modules and the replacement procedures are predetermined for each module. For details, refer to the chapter of the online module change in this manual.
Do not install/remove the module to/from the base unit more than 50 times after the first use of the product. (IEC 61131-2 compliant) Failure to do so may cause malfunction.
Do not touch the connector while the power is on. Doing so may cause malfunction.
Switch off all phases of the externally supplied power used in the system when cleaning the module or retightening the terminal or module fixing screws. Not doing so may cause failure or malfunction of the module. If the screws are loose, it may cause the module to fallout, short circuits, or malfunction. If the screws are tightened too much, it may cause damages to the screws and/or the module, resulting in the module falling out, short circuits or malfunction.
Always make sure to touch the grounded metal to discharge the electricity charged in the body, etc., before touching the module. Failure to do so may cause a failure or malfunctions of the module.
[DISPOSAL PRECAUTIONS]
CAUTION
When disposing of this product, treat it as industrial waste.
A - 4
Page 7

REVISIONS

* The manual number is given on the bottom left of the back cover.
Print Date *Manual Number Revision
Nov., 2008 SH(NA)-080795ENG-A First printing
Japanese Manual Version SH-080794-B
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses.
Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
C
2008 MITSUBISHI ELECTRIC CORPORATION
A - 5
Page 8

INTRODUCTION

Thank you for purchasing the MELSEC-Q series Programmable Controller. Before using the equipment, please read this manual carefully to develop full familiarity with the functions and performance of the Q series Programmable Controller you have purchased, so as to ensure correct use. Please forward a copy of this manual to the end user.

CONTENTS

SAFETY PRECAUTIONS •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• A - 1
REVISIONS •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••A - 5
INTRODUCTION •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• A - 6
CONTENTS••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• A - 6
Compliance with the EMC and Low Voltage Directives ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• A - 10
About the Generic Terms and Abbreviations •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• A - 11
Product Lineup ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••A - 12
CHAPTER1 OVERVIEW 1 - 1 to 1 - 3
1.1 Features •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 1 - 2
CHAPTER2 SYSTEM CONFIGURATION 2 - 1 to 2 - 7
2.1 Applicable Systems••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 2 - 1
2.2 About Use of the Q68TD-G-H02 (H01) with the Q12PRH/Q25PRHCPU ••••••••••••••••••••••••••••••••2 - 5
2.3 How to Check the Function Version, Product Information and Software Version ••••••••••••••••••••••2 - 6
CHAPTER3 SPECIFICATIONS 3 - 1 to 3 - 59
3.1 Performance Specifications•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••3 - 1
3.2 Function List •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••3 - 5
3.2.1 Temperature conversion system ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 6
3.2.2 Conversion setting for disconnection detection function(Q68TD-G-H02 only) •••••••••••••••••• 3 - 11
3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only) ••••••••••••••••••••••••••• 3 - 13
3.2.4 Warning output function •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 15
3.2.5 Cold junction temperature compensation resistor disconnection detection function ••••••••••• 3 - 20
3.3 I/O Signals Transferred to/from Programmable Controller CPU ••••••••••••••••••••••••••••••••••••••••• 3 - 21
3.3.1 I/O signal list•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 21
3.3.2 I/O signal details ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 22
3.4 Buffer Memory ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 29
3.4.1 Buffer memory assignment •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 29
3.4.2 Conversion enable/disable setting (Un\G0) •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 35
3.4.3 CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)•••••••••••••••••••• 3 - 36
3.4.4 Conversion completion flag (Un\G10) ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 37
3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)•••••••••••••••••••••••••••••••••••••••••••• 3 - 38
3.4.6 Error code (Un\G19) •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 39
A - 6
Page 9
3.4.7 Setting range 1, 2 (Thermocouple type) (Un\G20,Un\G21) ••••••••••••••••••••••••••••••••••••••••• 3 - 39
3.4.8 Setting range 3 (Offset/gain setting) (Un\G22) •••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 39
3.4.9 Averaging processing selection (Un\G24,Un\G25) ••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 40
3.4.10 Offset/gain setting mode (Un\G26,Un\G27)•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 41
3.4.11 CH[ ] Offset/gain temperature setting values (Un\G28 to Un\G43) •••••••••••••••••••••••••••••••• 3 - 42
3.4.12 Cold junction compensation setting status (Un\G45) (Q68TD-G-H02 only) ••••••••••••••••••••• 3 - 42
3.4.13 Warning output enable/disable setting (Un\G46) ••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 43
3.4.14 Warning output flag (Process alarm/Rate alarm) (Un\G47,Un\G48) •••••••••••••••••••••••••••••• 3 - 44
3.4.15 Disconnection detection flag (Un\G49) (Q68TD-G-H02 only) •••••••••••••••••••••••••••••••••••••• 3 - 45
3.4.16 Disconnection state monitor flag (Un\G49) (Q68TD-G-H01only) •••••••••••••••••••••••••••••••••• 3 - 47
3.4.17 CH[ ] Scaling value (Un\G50 to Un\G57) ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 49
3.4.18 Scaling valid/invalid setting (Un\G58) ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 50
3.4.19 CH[ ] Scaling range upper/lower limit values (Un\G62 to Un\G77) •••••••••••••••••••••••••••••••• 3 - 51
3.4.20 CH[ ] Scaling width upper/lower limit values (Un\G78 to Un\G93)••••••••••••••••••••••••••••••••• 3 - 52
3.4.21 CH[ ] Process alarm upper/lower limit values (Un\G94 to Un\G125)•••••••••••••••••••••••••••••• 3 - 53
3.4.22 CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133) ••••••••••••••••••••••••••••••• 3 - 54
3.4.23 CH[ ] Rate alarm upper/lower limit values (Un\G134 to Un\G149) •••••••••••••••••••••••••••••••• 3 - 54
3.4.24 Mode switching setting (Un\G158, Un\G159) •••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 55
3.4.25 Conversion setting for disconnection detection (Un\G164, Un\G165) (Q68TD-G-H02 only) • 3 - 56
3.4.26 Disconnection state conversion setting (Un\G164, Un\G165) (Q68TD-G-H01only) ••••••••••• 3 - 57
3.4.27 CH[ ] Conversion setting value for disconnection detection (Un\G166 to Un\G173) (Q68TD-G-H02 only)•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 58
3.4.28 CH[ ] Conversion setting value for disconnection state (Un\G166 to Un\G173) (Q68TD-G-H01only)
•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 58
3.4.29 Factory default offset/gain values, User range settings offset/gain values (Un\G190 to Un\G253)
•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 3 - 59
CHAPTER4 SETUP AND PROCEDURES BEFORE OPERATION 4 - 1 to 4 - 17
4.1 Handling Precautions •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 1
4.1.1 Fixing module with module fixing bracket (Q68TD-G-H02 only) ••••••••••••••••••••••••••••••••••••• 4 - 2
4.2 Setup and Procedures before Operation ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 3
4.3 Part Names •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 4
4.4 Wiring ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 6
4.4.1 Wiring precautions •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 6
4.4.2 External wiring •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••4 - 7
4.5 Switch Setting for Intelligent Function Module •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 8
4.6 Offset/Gain Setting ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 4 - 10
4.7 Cold Junction Temperature Compensation with/without Setting •••••••••••••••••••••••••••••••••••••••• 4 - 16
CHAPTER5 UTILITY PACKAGE (GX Configurator-TI) 5 - 1 to 5 - 23
5.1 Utility Package Functions ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 1
5.2 Installing and Uninstalling the Utility Package•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••5 - 3
5.2.1 Handling precautions ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 3
5.2.2 Operating environment ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 5
5.3 Utility Package Operation •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••5 - 7
5.3.1 Common utility package operations ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 7
5.3.2 Operation overview ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 10
A - 7
Page 10
5.3.3 Starting the Intelligent function module utility •••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 12
5.4 Initial Setting ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 14
5.5 Auto Refresh Settings •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 16
5.6 Monitoring/Test •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 18
5.6.1 Monitor/test screen•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 18
5.6.2 Offset/gain setting operation •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 21
5.6.3 OMC (Online Module Change) refresh data ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 5 - 23
CHAPTER6 PROGRAMMING 6 - 1 to 6 - 28
6.1 Programming Procedure ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••6 - 2
6.2 Using Programs in Normal System Configuration ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••6 - 4
6.2.1 Before creating a program ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 6 - 5
6.2.2 Program example when Configurator-TI•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 6 - 7
6.2.3 Program example when GX Configurator-TI is not used •••••••••••••••••••••••••••••••••••••••••••• 6 - 12
6.3 Using Programs on Remote I/O Network •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 6 - 15
6.3.1 Before creating a program ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 6 - 17
6.3.2 Program example when GX Configurator-TI is used ••••••••••••••••••••••••••••••••••••••••••••••••• 6 - 18
6.3.3 Program example when GX Configurator-TI is not used •••••••••••••••••••••••••••••••••••••••••••• 6 - 22
CHAPTER7 ONLINE MODULE CHANGE 7 - 1 to 7 - 35
7.1 Online Module Change Conditions •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 2
7.2 Online Module Change Operations••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••7 - 3
7.3 Online Module Change Procedure ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••7 - 4
7.3.1 When factory default is used and initial setting was made with GX Configurator-TI •••••••••••••7 - 4
7.3.2 When factory default is used and initial setting was made with sequence program ••••••••••••• 7 - 9
7.3.3 When user range setting is used and initial setting was made with GX Configurator-TI (other system is available)••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 13
7.3.4 When user range setting is used and initial setting was made with GX Configurator-TI (other system is unavailable)•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 18
7.3.5 When user range setting is used and initial setting was made with sequence program (other system is available)••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 23
7.3.6 When user range setting is used and initial setting was made with sequence program (other system is unavailable)•••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 28
7.4 Range Reference Table ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 33
7.4.1 Range reference table (Q68TD-G-H02) •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 33
7.4.2 Range reference table (Q68TD-G-H01) •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 34
7.5 Precautions for Online Module Change •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 7 - 35
CHAPTER8 TROUBLESHOOTING 8 - 1 to 8 - 8
8.1 Error Code List ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 1
8.2 Troubleshooting •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 4
8.2.1 "RUN" LED is extinguished••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 4
8.2.2 "RUN" LED flickers••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 4
8.2.3 "ERR" LED flickers ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 4
8.2.4 "ERR" LED is lit ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 4
A - 8
Page 11
8.2.5 "ALM" LED flickers ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 5
8.2.6 "ALM" LED is lit •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 8 - 5
8.2.7 When Disconnection detection signal (XC) (Q68TD-G-H02 only) or Disconnection state monitor signal (XC) (Q68TD-G-H01 only) turns on ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 8 - 5
8.2.8 Measured temperature value cannot be read ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 8 - 5
8.2.9 Measured temperature value is abnormal ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••8 - 6
8.2.10 Checking the Q68TD-G-H02(H01) status using GX Developer system monitor•••••••••••••••••• 8 - 7
APPENDIX App - 1 to App - 14
Appendix 1 Differences of Q68TD-G-H02, Q68TD-G-H01, Q64TD, Q64TDV-GH••••••••••••••••••••••• App - 1
Appendix 2 Dedicated Instruction •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• App - 2
Appendix 2.1 Dedicated Instruction List and Available Device••••••••••••••••••••••••••••••••••••••••••• App - 2 Appendix 2.2 G(P).OFFGAN ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• App - 3 Appendix 2.3 G(P).OGLOAD ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• App - 5 Appendix 2.4 G(P).OGSTOR ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• App - 9
Appendix 3 External Dimension Diagram ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• App - 14
INDEX Index - 1 to Index - 2
A - 9
Page 12

Compliance with the EMC and Low Voltage Directives

(1) For programmable controller system
To configure a system meeting the requirements of the EMC and Low Voltage Directives when incorporating the Mitsubishi programmable controller (EMC and Low Voltage Directives compliant) into other machinery or equipment, refer to Chapter 9 "EMC AND LOW VOLTAGE DIRECTIVES" of the QCPU User's Manual (Hardware Design, Maintenance and Inspection). The CE mark, indicating compliance with the EMC and Low Voltage Directives, is printed on the rating plate of the programmable controller.
(2) For the product
For the compliance of this product with the EMC and Low Voltage Directives, refer to Section 4.4.1 Wiring precautions.
A - 10
Page 13

About the Generic Terms and Abbreviations

Unless otherwise specified, this manual uses the following general terms and abbreviations.
Abbreviation/general terms Description of the abbreviation/general terms
Q68TD-G-H02 Abbreviation for Q68TD-G-H02 channel isolated thermocouple input module
Q68TD-G-H01 Abbreviation for Q68TD-G-H01 channel isolated thermocouple input module
Q68TD-G-H02(H01)
Up scale
Down scale
GX Developer
GX Configurator-TI
QCPU (Q mode)
Process CPU Generic term for Q02PHCPU, Q06PHCPU, Q12PHCPU, Q25PHCPU
Cold junction temperature
compensation resistor
Personal computer
Windows Vista
Windows XP
R
R
Abbreviation for Q68TD-G-H02 or Q68TD-G-H01 channel isolated thermocouple input
module
Maximum value in measured temperature range plus 5% value of measured temperature
range
Minimum value in measured temperature range minus 5% value of measured
temperature range
Generic product name for the SWnD5C-GPPW-E, SWnD5C-GPPW-EA, SWnD5C-
GPPW-EV and SWnD5C-GPPW-EVA. ("n" is 4 or greater.)
"-A" and "-V" denote volume license product and upgraded product respectively.
Generic term for thermocouple input module setting and monitor tool GX Configurator-TI
(SW1D5C-QTIU-E)
Generic term for Q00JCPU, Q00CPU, Q01CPU, Q02CPU, Q02HCPU, Q06HCPU,
Q12HCPU, Q25HCPU, Q02PHCPU, Q06PHCPU, Q12PHCPU, Q25PHCPU,
Q12PRHCPU, Q25PRHCPU, Q00UJCPU, Q00UCPU, Q01UCPU, Q02UCPU,
Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q10UDHCPU, Q13UDHCPU, Q20UDHCPU,
Q26UDHCPU, Q03UDECPU, Q04UDEHCPU, Q06UDEHCPU, Q10UDEHCPU,
Q13UDEHCPU, Q20UDEHCPU, Q26UDEHCPU
Generic term for Resistance Temperature Detector (RTD) used for cold junction
temperature compensation. Pt100 is used.
IBM PC/AT or compatible computer with DOS/V.
R
Generic term for the following:
Microsoft Windows Vista Home Basic Operating System,
Microsoft Windows Vista Home Premium Operating System,
Microsoft Windows Vista Business Operating System,
Microsoft Windows Vista Ultimate Operating System,
Microsoft Windows Vista Enterprise Operating System
R R
R R
R R
R R
R R
Generic term for the following:
Microsoft Windows XP Professional Operating System,
Microsoft Windows XP Home Edition Operating System
R R
R R
A - 11
Page 14

Product Lineup

The product lineup is given in the table below.
(1) Q68TD-G-H02
Model Product name Quantity
Q68TD-G-H02
SW1D5C-QTIU-E GX Configurator-TI Version 1 (Single license product) (CD-ROM) 1
SW1D5C-QTIU-EA GX Configurator-TI Version 1 (Volume license product) (CD-ROM) 1
Q68TD-G-H02 channel isolated thermocouple input module 1
Cold junction temperature compensation resistor (RTD) 1
(2) Q68TD-G-H01
Model Product name Quantity
Q68TD-G-H01
SW1D5C-QTIU-E GX Configurator-TI Version 1 (Single license product) (CD-ROM) 1
SW1D5C-QTIU-EA GX Configurator-TI Version 1 (Volume license product) (CD-ROM) 1
Q68TD-G-H01 channel isolated thermocouple input module 1
Cold junction temperature compensation resistor (RTD) 1
A - 12
Page 15
1
OVERVIEW

CHAPTER1 OVERVIEW

This user's manual provides the specifications, handling instructions, programming procedures and other information of the Q68TD-G-H02 or Q68TD-G-H01 channel isolated thermocouple input module (referred to as the Q68TD-G-H02(H01)), which is designed to use with the MELSEC-Q series CPU module (referred to as the programmable controller CPU).
The Q68TD-G-H02(H01) is a module designed to convert thermocouple input values from outside the programmable controller into 16-bit signed binary measured temperature values and 16-bit signed binary scaling values (ratios).
Programmable controller CPU
Q68TD-G-H02(H01)
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
TO instruction
FROM instruction
(Buffer memory)
Initial setting
Measured
temperature value,
scaling value
reading
Figure 1.1 Overview of Q68TD-G-H02(H01)
* Refer to Section 3.4.17 for details of the scaling values.
Set data
Measured temperature value
Scaling value
Measured temperature value
Scaling value
*
*
Cold junction temperature compensation channel
Channel 1
Temperature measurement
Channel 8
Resistance temperature detector input (by cold junction temperature compensation resistor (RTD))
Thermocouple input
Thermocouple input
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
1 - 1
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 16
1
OVERVIEW
1.1 Features
(1) Channels isolated
Q68TD-G-H02(H01) is channel isolated modules.
(2) 8 channels of temperatures measured by one module
One Q68TD-G-H02(H01) module can measure temperatures of 8 channels. It can also convert the detected temperature values into scaling values (ratios (%)).
(3) Setting of conversion enable/disable
Conversion enable/disable setting for each channel is possible. Disabling conversion for unused channels prevents unnecessary disconnection detection or monitor of disconnection state on unused channels.
(4) Thermocouples conforming to JIS or IEC Standards usable
You can use eight different thermocouples (K, E, J, T, B, R, S, N) conforming to the JIS or IEC Standards. The types of thermocouples can be selected for each channel.
(5) Disconnection detection function (Q68TD-G-H02 only)
Disconnection status of thermocouple or compensating lead wire can be detected for each channel by Disconnection detection flag. Disconnection status can also be detected from the measured temperature value by setting "Up scale", "Down scale" or "Given value" for the Conversion setting for disconnection detection.
(6) Disconnection monitor function (Q68TD-G-H01 only)
Disconnection status of thermocouple or compensating lead wire can be checked on each channel by Disconnection state monitor flag. Disconnection status can also be checked from the measured temperature value by setting "Up scale", "Down scale" or "Given value" for the Conversion setting for disconnection detection.
(7) Selection of sampling processing, time average processing, count
average processing, moving average processing, and primary delay filter
As a conversion processing method, sampling processing, time average processing, count average processing, moving average or primary delay filter can be selected for each channel.
1 - 2
(8) Cold junction temperature compensation by cold junction temperature
compensation resistor (RTD)
Cold junction temperature compensation is possible by connecting the supplied cold junction temperature compensation resistor (RTD) and enabling the cold junction temperature compensation. Resistance temperature detector Pt100 is used for cold junction temperature compensation resistor (RTD).

1.1 Features

Page 17
1
OVERVIEW
(9) Error compensation by offset/gain value setting
Error compensation can be made by setting offset and gain values on each channel. As the offset and gain values, you can make selection from user range setting and factory default setting.
(10)Warning output function
(a) Process alarm warning output
(b) Rate alarm warning output
A warning can be output when the input range set by the user is exceeded. Upper limit value and lower limit value can be set for each channel, and a setting to have a difference (hysteresis) between warning output and warning clear is also possible.
By setting a changing rate, a warning can be output when the changing rate is exceeded.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(11)Online module change
You can perform a module change without stopping the system. Further "inheritance of offset/gain settings to the new Q68TD-G-H02 (H01) after online module change" and "transfer of offset/gain settings to the other Q68TD-G-H02 (H01) mounted on the other slot" can be performed by executing the dedicated instructions (G.OGLOAD, G.OGSTOR) or performing write to buffer memory and turning the Y signal ON. (These functions are limited to between the modules of the same model.)
(12)Easy setting with GX Configurator-TI
The use of GX Configurator-TI sold separately allows you to execute the thermocouple input module setting on screen, resulting in reducing the number of sequence programs. Also, the use of GX Configurator-TI makes it easy to check the setting status and operating status for modules.
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
1.1 Features
1 - 3
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 18
2
SYSTEM CONFIGURATION

CHAPTER2 SYSTEM CONFIGURATION

This chapter explains the system configuration of the Q68TD-G-H02 (H01).
2.1 Applicable Systems
This section describes applicable systems.
(1) Applicable modules and base units, and No. of modules
(a) When mounted with a CPU module
The table below shows the CPU modules and base units applicable to the Q68TD-G-H02 (H01) and quantities for each CPU model. Depending on the combination with other modules or the number of mounted modules, power supply capacity may be insufficient. Pay attention to the power supply capacity before mounting modules, and if the power supply capacity is insufficient, change the combination of the modules.
Programmable controller CPU
Table 2.1 Applicable modules, number of mountable modules, and applicable base units
Applicable CPU module
CPU type CPU model Main base unit Extension base unit
Q00JCPU Up to 16
Basic model QCPU
High Performance model QCPU
Process CPU
Redundant CPU
Universal model QCPU
Safety CPU QS001CPU N/A
Q00CPU
Q01CPU
Q02CPU
Q02HCPU
Q06HCPU
Q12HCPU
Q25HCPU
Q02PHCPU
Q06PHCPU
Q12PHCPU
Q25PHCPU
Q12PRHCPU
Q25PRHCPU
Q00UJCPU Up to 8
Q00UCPU
Q01UCPU
Q02UCPU Up to 36
Q03UDCPU
Q04UDHCPU
Q06UDHCPU
Q10UDHCPU
Q13UDHCPU
Q20UDHCPU
Q26UDHCPU
Q03UDECPU
Q04UDEHCPU
Q06UDEHCPU
Q10UDHCPU
Q13UDEHCPU
Q20UDEHCPU
Q26UDEHCPU
No. of modules
Up to 24
Up to 64
Up to 64
Up to 53
Up to 24
Up to 64
*1
Applicable base unit
*2
*3
2 - 1

2.1 Applicable Systems

Page 19
2
SYSTEM CONFIGURATION
C Controller module
Table 2.1 Applicable modules, number of mountable modules, and applicable base units
Applicable CPU module
CPU type CPU model Main base unit Extension base unit
Q06CCPU-V
Q06CCPU-V-B
Q12DCCPU-V
* 1 Limited within the range of I/O points for the CPU module. * 2 Restrictions apply to mountable slot position. (Refer to (2) in this section) * 3 Connection of extension base units is not available with any safety CPU.
No. of modules
Up to 64
*1
Applicable base unit
*2
:Applicable, :N/A
Remark
When using with a C Controller module, refer to the C Controller Module User's Manual.
(b) Mounting to a MELSECNET/H remote I/O station
The table below shows the network modules and base units applicable to the Q68TD-G-H02 (H01) and quantities for each network module model. Depending on the combination with other modules or the number of mounted modules, power supply capacity may be insufficient. Pay attention to the power supply capacity before mounting modules, and if the power supply capacity is insufficient, change the combination of the modules.
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Table 2.2 Applicable modules, number of mountable modules, and applicable base units
Applicable network module
QJ72LP25-25
QJ72LP25G
QJ72LP25GE
QJ72BR15
* 1 Limited within the range of I/O points for the network module. * 2 Restrictions apply to mountable slot position. (Refer to (2) in this section)
Number of modules
Up to 64
*1
Main base unit of remote I/O
station
Remark
The Basic model QCPU or C Controller module cannot create the MELSECNET/ H remote I/O network.
(2) Restrictions on mountable slot position
(a) Restrictions in using both the Q68TD-G-H02 and Q68TD-G-H01
When mounting the Q68TD-G-H02 and Q68TD-G-H01 on the same base unit, provide one or more than one slot of space between the Q68TD-G-H02 and Q68TD-G-H01.
Base unit
*2
Extension base unit of
remote I/O station
:Applicable, :N/A
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
2.1 Applicable Systems
TROUBLESHOOTING
2 - 2
Page 20
2
SYSTEM CONFIGURATION
(b) Restriction on mountable slot position of the Q68TD-G-H01
The Q68TD-G-H01 has restrictions on mountable slot position. The following describes the restrictions of the slot position when mounting the Q68TD-G-H01 with a combination of the power supply module and the base unit. For the slot that the Q68TD-G-H01 cannot be mounted, leave the slot open or mount a module other than the Q68TD-G-H01. The combination use of modules other than the following power supply modules and the base units does not have restrictions. When using the Q68TD-G-H01 on the remote I/O station, the restriction is the same as for the main base unit. When failing to comply with the following restrictions, the accuracy might not be in the specification range.
Table 2.3 Restriction on mountable slot position
Power supply module
Q63P
Q63RP
Q64P Mount the module to I/O slot No.1 or
Q64RP
No restrictions
later. 1)
Restrictions
Main base unit Extension base unit
Mount the module to I/O slot No.1 or
later. 2) Mount the module to I/O slot No.2 or
later. 3)
1)
Not mountable
Power
supply
OUT
CPU
No.0
I/01 I/01
Slot
Mountable
Slot
No.1
Slot
No.2
Figure 2.1 Mountable slot position of Q68TD-G-H01
2)
Power supply
OUT
IN
Not mountable
Slot
No.0
I/01 I/01
Mountable
Slot
No.1
Slot
No.2
Figure 2.2 Mountable slot position of Q68TD-G-H01
3)
Not mountable Mountable
2 - 3
IN
Figure 2.3 Mountable slot position of Q68TD-G-H01
2.1 Applicable Systems
Power
supply
OUT
Slot
No.0
I/01 I/01
Slot
No.1
Slot
No.2
Page 21
2
SYSTEM CONFIGURATION
(3) Support of the multiple CPU system
The function version of the first released Q68TD-G-H02 (H01) is C, and it supports multiple CPU systems. When using the Q68TD-G-H02 (H01) in a multiple CPU system, refer to the following manual first.
• QCPU User's Manual (Multiple CPU System).
(a) Intelligent function module parameters
Write intelligent function module parameters to only the control CPU of the Q68TD-G-H02 (H01).
(4) Compatibility with online module change
The Q68TD-G-H02 (H01) is compatible with online module change from the initial product with function version C. Refer to CHAPTER 7.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(5) Supported software packages
Relation between the system containing the Q68TD-G-H02 (H01) and software package is shown in the following table. GX Developer is necessary when using the Q68TD-G-H02 (H01).
Table 2.4 Compatible software and software version
System
Q00J/Q00/Q01CPU
Q02/Q02H/Q06H/
Q12H/Q25HCPU
Q02PH/Q06PHCPU
Q12PH/Q25PHCPU
Q00UJ/Q00U/
Q01UCPU
Q12PRH/Q25PRHCPU Redundant system Version 8.45X or later
Q10UDH/Q20UDHCPU
Q02U/Q03UD/
Q04UDH/Q06UDHCPU
Q13UDH/
Q26UDHCPU
Q03UDE/Q04UDEH/
Q06UDEH/
Q13UDEH/
Q26UDEHCPU
Q10UDEH/
Q20UDEHCPU
If installed in a MELSECNET/H remote I/O station Version 6 or later
Single CPU system Version 7 or later
Multiple CPU system Version 8 or later
Single CPU system Version 4 or later
Multiple CPU system Version 6 or later
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
Single CPU system
Multiple CPU system
GX Developer GX Configurator-TI
Version 8.68W or later
Version 7.10L or later
Version 8.76E or later
Version 8.76E or later
Version 8.48A or later
Version 8.62Q or later
Version 8.68W or later
Version 8.76E or later
Software Version
Version 1.28AE or later (Q68TD-G-H02)
Version 1.24AA or later (Q68TD-G-H01)
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
2.1 Applicable Systems
TROUBLESHOOTING
2 - 4
Page 22
2
SYSTEM CONFIGURATION
2.2 About Use of the Q68TD-G-H02 (H01) with the Q12PRH/ Q25PRHCPU
Here, use of the Q68TD-G-H02 (H01) with the Q12PRH/Q25PRHCPU is explained.
(1) Dedicated instruction
The dedicated instruction cannnot be used.
(2) GX Configurator-TI
GX Configurator-TI cannot be used when accessing the Q12PRH/Q25PRHCPU via an intelligent function module on an extension base unit from GX Developer. Connect a personal computer with a communication path indicated below.
12
Main base unit
Extension base unit
(GX Configurator-TI cannot be used.)
Direct connection to use the CPU
1
Connection through an intelligent function module on the main base unit
2
(Through Ethernet module, MELSECNET/H module, or CC-Link module)
Figure 2.4 Communication path available for GX Configurator-TI
2 - 5

2.2 About Use of the Q68TD-G-H02 (H01) with the Q12PRH/Q25PRHCPU

Page 23
2
)
SYSTEM CONFIGURATION
2.3 How to Check the Function Version, Product Information and Software Version
1
This section describes how to check the function version and product information of the Q68TD-G-H02 (H01) and the GX Configuration-TI software version.
(1) Checking on the rating plate on the side of the module
(a) The function version and serial number of the module are printed in the SERIAL
section of the rating plate.
09071
Figure 2.5 Rating plate
Serial No. (first 5 digits
Function version
Relevant regulation standards
(2) Checking through GX Developer
The following explains how to check the function version and serial No. of the module through GX Developer. The function version and serial number can be checked on the "Product Information List" or "Module Detailed Information" screen of GX Developer. The following shows how to check them on the "Product Information List" screen.
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
[Operation procedure]
[Diagnostics] [System monitor] button
Figure 2.6 "Product Information List" screen

2.3 How to Check the Function Version, Product Information and Software Version

Product Inf. List
2 - 6
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 24
2
SYSTEM CONFIGURATION
[Serial No,, Ver., and Product No.]
• The serial No. of the module is displayed in the "Serial No." column.
• The function version of the module is displayed in the "Ver." column.
• The serial No. (Product No.) printed on the rating plate is displayed in the
"Product No." column. For the Q68TD-G-H02 (H01), "-" is displayed since it does not support the Product No. display.
* 1 The "Product No." column appears only when the CPU module is the Universal model QCPU.
POINT
The serial No. on the rating plate may not match the one displayed in the Product Information List of GX Developer.
• The serial No. on the rating plate indicates the management information of the product.
• The serial No. displayed in the Product Information List of GX Developer indicates functional information of the product. The functional information of the product is updated when a new function is added.
*1
(3) Checking the software version of GX Configurator- TI
The software version of GX Configurator- TI can be checked in GX Developer's "Product information" screen.
[Operating procedure]
GX Developer [Help] [Product information]
Software version
2 - 7
("Product information" screen of GX Developer Version 8)
Figure 2.7 How to check the software version of GX Configurator- TI
2.3 How to Check the Function Version, Product Information and Software Version
Page 25
3
SPECIFICATIONS

CHAPTER3 SPECIFICATIONS

3.1 Performance Specifications
The following are the performance specifications of the Q68TD-G-H02 (H01).
(1) List of performance specifications
Table 3.1 List of performance specifications
Item
Number of channels 8 channels
Temperature
Ouput
Thermocouple compliance
standards
Applicable thermocouple and
conversion accuracy
*1
Cold junction compensation
accuracy *1
Accuracy *1 Caluculated with formula *2
Resolution
Conversion speed *3 640ms/8 channels 320ms/8 channels
Sampling period *4 320ms/8 channels
Number of analog input
points
Isolation specifications
Disconnection detection Available (each channel respectively)*5 Not available*6
Maximum number of writes to
flash memory
Number of I/O points
occupied
External connection system 40-pin connector
Applicable wire size
External device connector
(sold separately)
Internal current consumption
(5VDC)
Weight 0.22kg 0.18kg
External dimensions
conversion value
Scaling value 16-bit signed binary
Specific isolated area
Between thermocouple input
channel and programmable
controller power supply
Between thermocouple input
Between cold junction
compensation channel and
programmable controller power
Q68TD-G-H02 Q68TD-G-H01
16-bit signed binary (-2700 to 18200)
JIS C1602-1995,IEC 60584-1(1995),IEC60584-2(1982)
8 channels + cold junction compensation channels/ 1 module
channels
supply
16 points (I/O assignment: Intelligent 16 points)
0.65A 0.49A
102(H) 27.4(W) 130(D)mm 98(H) 27.4(W) 90(D)mm
Specifications
Refer to (2) in this section
1.0
B,R,S,N: 0.3 K,E,J,T: 0.1
Isolation
method
Transfer
isolation
Trasnfer
isolation
No isolation - -
2
0.3mm
Dielectric withstand
voltage
500VACrms for 1min
1000VACrms for 1min
50,000
(AWG#22) or less
A6CON4
Isolation resistance
500VDC 10M or more
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8

3.1 Performance Specifications

TROUBLESHOOTING
3 - 1
Page 26
3
SPECIFICATIONS
* 1 To satisfy with the accuracy, a warm-up (power distribution) period of 30 minutes is required. * 2 Calculate the accuracy in the following method.
(Accuracy) = (conversion accuracy) + (temperature characteristic) (operating ambient temperature variation) + (cold junction temperature compensation accuracy) An operating ambient temperature variation indicates a deviation of the operating ambient
temperature from the 25 5 range. Example: When using the thermocouple B (refer to Section 3.1 (2)) with the operating ambient
temperature of 35 and the measured temperature of 1000 , the accuracy is as follows.
( 2.5 )+( 0.4 ) (35 -30 )+( 1 )= 5.5
* 3 The conversion speed indicates the maximum time from when the input temperature changes till
when the measured temperature value of buffer memory is batch-updated.
* 4 The sampling period indicates the period batch-updating the measured temperature value in one
channel.
* 5 When disconnection state is detected, output values are selected from "Up scale", "Down scale" or
Given scale". (Refer to Section 3.2.2)
* 6 The Q68TD-G-H01 does not have the disconnection detection function. However, the
disconnection monitor function is available to select a measured temperature value on a disconnection occurrence from either "Up scale", "Down scale", or "Given value". (Refer to Section
3.2.3) It takes up to 11s to check a disconnection state.
3 - 2
3.1 Performance Specifications
Page 27
3
SPECIFICATIONS
1
(2) Usable Thermocouples and Conversion Accuracies
The following table explains the usable thermocouples and conversion accuracies.
Usable
Thermo
couple
Typ e
B
R
S
K
E
J
T
N
Table 3.2 Usable thermocouples and conversion accuracies
Measured Temperature
Range*1
0 to 600
600 to 800
800 to 1700
1700 to 1820
-50 to 0
0 to 300
300 to 1600
1600 to 1760
-50 to 0
0 to 300
300 to 1600
1600 to 1760
-270 to -200
-200 to 0
0 to 1200
1200 to 1370
-270 to -200
-200 to 0
0 to 900
900 to 1000
-210 to -40
-40 to 750
750 to 1200
-270 to -200
-200 to 0
0 to 350
350 to 400
-270 to -200
-200 to 0
0 to 1250
1250 to 1300
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
Conversion Accuracy (At operating ambient
temperature 25 5 )
------*3 ------*3 ------*3
3.0
2.5 12.5
------*3 ------*3 ------*3
------*3 ------*3 ------*3
2.5 0.4 12.5
2.0 0.3 9.5
------*3 ------*3 ------*3
------*3 ------*3 ------*3
2.5 0.4 12.5
2.0 0.3 9.5
------*3
------*3 ------*3 ------*3
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.25 and
0.5% of measured temperature
------*3 ------*3 ------*3
------*3 ------*3 ------*3
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.5 and
0.25% of measured temperature
------*3 ------*3 ------*3
------*3 ------*3 ------*3
Larger value of 0.5 and
0.25% of measured temperature
------*3 ------*3 ------*3
------*3 ------*3 ------*3
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.5 and
0.25% of measured temperature
------*3 ------*3 ------*3
------*3 ------*3 ------*3
Larger value of 0.5 and
0.5% of measured temperature
Larger value of 0.5 and
0.25% of measured temperature
------*3 ------*3 ------*3
Temperature Characteristic
(Per operating ambient
temperature variation of 1 )
0.4
------*3 ------*3
Larger value of 0.06 and
0.2% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
Larger value of 0.06 and
0.15% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
Larger value of 0.06 and
0.1% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
Larger value of 0.06 and
0.2% of measured temperature
Larger value of 0.06 and
0.02% of measured temperature
Max. Temperature
Error at Ambient
Temperature 55
13.0
11. 0
9.0
8.5
6.75
5.625
6.0
2.625
11. 0
9.375
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
3.1 Performance Specifications
TROUBLESHOOTING
3 - 3
Page 28
3
SPECIFICATIONS
* 1 If a value entered from the thermocouple is outside the measured temperature range given in the
table, it is handled as the maximum/minimum value of the measured temperature range.
* 2 The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995
apply. Also, a warm-up (power distribution) period of 30 minutes is required to satisfy with the accuracy.
* 3 Temperature measurement can be executed, but accuracy is not guaranteed.
3 - 4
3.1 Performance Specifications
Page 29
3
SPECIFICATIONS
3.2 Function List
The following table lists the Q68TD-G-H02 (H01) functions.
1
Table 3.3 Function list
Item Description Refer To
Temperature conversion
function
Temperature conversion
system
Conversion enable/disable
function Thermocouple type
selection function Disconnection detection
function
(Q68TD-G-H02 only) Conversion setting for
disconnection detection
function
(Q68TD-G-H02 only) Disconnection monitor
function
(Q68TD-G-H01 only) Disconnection state
conversion setting function
(Q68TD-G-H01 only)
Cold junction temperature
compensation with/without
setting function
Cold junction temperature
compensation resistor
disconnection detection
function
Warning output function
Scaling function
Offset/gain setting function This function compensates an error of measured temperature value.
Online module change A module change is made without the system being stopped. CHAPTER 7
This function allows temperature data to be imported by connecting a thermocouple.
Temperature data are 16-bit signed binary (-2700 to 18200) and stored into buffer memory. (1) Sampling processing
A temperature input value is converted one by one on each channel and a measured
temperature value is output after every conversion. Then the value is stored into buffer
memory.
(2) Averaging processing
This processing averages a measured temperature value for each channel and the
averaged value is stored into buffer memory.
Averaging processing contains three methods as described below. (a) Time average (b) Count average (c) Moving average
(3) Primary delay filter
Measured temperature values are smoothed by a preset time constant. This function specifies whether temperature conversion is enabled or disabled on each
channel.
This function sets the type of thermocouple on each channel. Section 4.5
This function checks the disconnection of the connected thermocouple on each conversion-
enabled channel.
This function is to select a value to be stored in the CH Measured temperature value
(Un\G11 to Un\G18) from "Up scale", "Down scale" or "Given scale" when disconnection is
detected.
This function checks the disconnection of the connected thermocouple on each conversion-
enabled channel.
This function is to select a value to be stored in the CH Measured temperature value
(Un\G11 to Un\G18) from "Up scale", "Down scale" or "Given scale" when disconnection is
detected. This function determines whether to use cold junction temperature compensation.
Use this function to measure temperatures at high accuracy when the cold junction
temperature compensation accuracy ( 1 ) cannot be taken as a margin of error.
The cold junction temperature compensation accuracy can be improved by disabling the
cold junction temperature compensation and providing a precision ice bath externally.
This function detects a disconnection of connected cold junction temperature compensation
resistor (RTD).
(1)
Process alarm
When measured temperature value exceeds the preset range, a warning is output.
(2)
Rate alarm
When the change of measured temperature value exceeds the preset change, a
warning is output.
This function can convert a measured temperature value into a preset range ratio (%) and
import it into buffer memory.

3.2 Function List

Section 3.4.5
Section 3.2.1
Section 3.4.2
Section 3.4.15
Section 3.2.2
Section 3.4.16
Section 3.2.3
Section 4.7
Section 3.2.5
Section 3.2.4
Section 3.4.17
to
Section 3.4.20 Section 3.4.11
Section 4.6
3 - 5
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
Page 30
3
SPECIFICATIONS
3.2.1 Temperature conversion system
(1) Temperature conversion of Q68TD-G-H02(H01)
(a) Sampling period
The Q68TD-G-H02(H01) measures the temperature from CH1 to CH8 every 40ms per channel. The sampling period indicates the period (320ms) batch-updating the measured temperature value in one channel in the case of that the sampling processing is specified with the Averaging processing selection (Un\G24 and Un\G25). Regardless of the number of conversion-enabled channels, the measured temperature values are stored in the buffer memory every 320ms.
(b) Conversion speed
The conversion speed indicates the maximum time required before the measured temperature values are stored into the buffer memory. The following figure shows the timing of storing the measured temperature values of Q68TD-G-H02 and Q68TD-G-H01 respectively.
Input temperature input
from outside to CH1
Measured temperature
value of CH1 in the
Q68TD-G-H01
Measured temperature
value of CH1 in the
Q68TD-G-H02
Trend of CH1 input
temperature (A)
Sampling period
(320ms)
1) 2)
CH1 CH1 CH1 CH1CH2 CH8
The measured temperature value of 1) is stored
CH1 CH1 CH1 CH1CH2 CH8
Sampling period
(320ms)
The measured temperature value of 2) is stored
Maximum
320ms
The measured temperature value of 1) is stored
Sampling period
(320ms)
3) 4)
The measured temperature value of 3) is stored
The measured temperature value of 2) is stored
Maximum
640ms
Sampling period
(320ms)
The measured temperature value of 4) is stored
The measured temperature value of 3) is stored
At this point, the CH1
measured temperature
value of the buffer memory,
which is measured with
the trend of (A), is stored.
At this point, the CH1
measured temperature
value of the buffer memory,
which is measured with
the trend of (A), is stored.
3 - 6
Figure 3.1 Q68TD-G-H01 and Q68TD-G-H02 conversion speed overview
(2) Sampling processing
Measured temperature value that is measured at every 320ms of sampling period is stored in the buffer memory.
3.2 Function List

3.2.1 Temperature conversion system

Page 31
3
SPECIFICATIONS
(3) Averaging processing
Averaging processing requires at least 2 times of conversion processing excluding the maximum and the minimum values. After the first averaging processing is completed, the corresponding bit for a channel where processing has been completed of the Conversion completion flag (Un\G10) turns ON (changes to "1").
(a) Time average
Conversion is executed for a period of set time, and the total value, which excludes the maximum and the minimum values, is averaged and stored in the buffer memory. The number of processing times within the set time is below.
Number of processing times (times) = set time sampling period (320ms)
Setting range of time average is 1280 to 5000ms.
When setting a value out of the setting range, an error (error code 20 ) occurs.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
[Example] When six channels, channels 1, 2, 3, 4, 5, 6, are enabled for conversion and the set time is 2000ms, measurement is executed for six times and the average value is output.
2000 320 =6.25 (times)...... Drop the fractional part
(b) Count average
Conversion is executed for a preset number of times, and the total value excluding the maximum and the minimum values is averaged and stored in the buffer memory. The processing time is below.
Processing time = set count
Setting range of count average is 4 to 500 times.
When setting a value out of the setting range, an error (error code 30 ) occurs.
[Example] When six channels, channels 1, 2, 3, 4, 5, 6, are enabled for conversion and the count averaging is set to 5 times, the average value is output for every 1600(ms).
5
320 = 1600 (ms)
320(ms)
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
3.2 Function List
3.2.1 Temperature conversion system
3 - 7
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 32
3
SPECIFICATIONS
(c) Moving average
Measured temperature values, which are taken at every sampling period for the specified number of times, are averaged and stored in the buffer memory. The latest measured temperature value can be obtained because the averaging processing is executed moving for each sampling period.
Measured temperature value
10000
8000
CH[] measured temperature value
(Un\G11 to Un\G18)
Conversion completion flag
(Un\G10)
Figure 3.2 Moving average processing for four times settings
Data transition in buffer memory
1st storage
1) + 2) + 3) + 4) 2) + 3) + 4) + 5) 3) + 4) + 5) + 6)
444
Figure 3.3 Buffer memory data change in average processsing
Sampling period (320ms)
3)
2)
1)
0
0
OFF(0)
4)
2nd storage
5)
6)
(a) (b) (c)
8)
7)
ON(1)
3rd storage
9)
11)
10)
1st storage
2nd storage
3rd storage
Time [ms]
12)
3 - 8
3.2 Function List
3.2.1 Temperature conversion system
Page 33
3
)
SPECIFICATIONS
(4) Primary delay filter
By a preset time constant, measured temperature value of which excessive noise is smoothed is output. Depending on the time constant, the degree of smoothness changes. Time constant is the time until the measured temperature value reaches to 63.2% of the steady-state value. The relational expression between the time constant and measured temperature value is shown below.
[When n=1]
Y
n = 0
[When n=2]
Yn = yn-1 +
[When n 3]
Yn = Yn-1 +
t
t + TA
t
t + TA
(yn - yn-
(yn - Yn-
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
1)
SPECIFICATIONS
1
4
Y
n: Current measured
temperature
Y
n-1: Preceding measured
temperature value
n: Number of sampling times
TA: Time constant (320 to
5000ms)
*: Conversion completion flag turns ON(1) when n 2.
Setting range of time constant is 320 to 5000ms. Set the time constant value which is twice as much as the sampling period (320ms). If the time constant value is not twice as much as the sampling period (320ms), the value in which the remainder is rounded down is set.
When setting a value out of the setting range, an error (error code 32 ) occurs.
yn: Measured temperature value before
smoothing
yn-1: Preceding measured temperature
value before smoothing
Conversion time (320ms)
t:
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
3.2 Function List
3.2.1 Temperature conversion system
3 - 9
Page 34
3
SPECIFICATIONS
[Example 1: Measured temperature value when the temperature input value is changed
from 250.0
When the time constant setting is 3200ms (3.2s), the measured temperature value changes as indicated below.
At 3200ms (3.2s) after the temperature input value is changed to 260.0 , the
measured temperature value reaches 63.2% (256.3 )of the value when sampling processing is selected.
to 260.0 ]
262.0 2620
260.0
258.0
256.0
254.0
252.0
Temperture input value ( )
250.0
Figure 3.4 Measured temperature value when the temperature input value is changed from 250.0 to 260.0
Temperture input value
0 3200
Elapsed time (ms)
Measured temperature value
2600
2580
2560
2540
2520
2500
[Example2: Measured temperature value when the change of temperature input value is a waveform with ringing]
The changes of measured temperature values when the time constant setting is 1280ms(1.28s), 640ms(0.64s) or the moving average processing is 4 times are shown below.
Measured temperature value (Time constant setting 640ms)
Measured temperature value (Time constant setting 1280ms)
2620
2600
262.0
260.0
Temperature input value
Measured temperature value (Moving average processing 4 times)
Measured temperature value
7000
2580
2560
2540
2520
Measured temperature value
2500
258.0
256.0
254.0
252.0
Temperture input value ( )
250.0 0
Figure 3.5 Measured temperature value when the change of temperature input value is a waveform with ringing
1000
2000
3000
4000
Elapsed time (ms)
5000
6000
3 - 10
3.2 Function List
3.2.1 Temperature conversion system
Page 35
3
SPECIFICATIONS
3.2.2 Conversion setting for disconnection detection function (Q68TD-G-H02 only)
The conversion setting for disconnection detection function stores specific values into measured temperature values when disconnection is detected. This function can identify the disconnection detection from measured temperature values. This function is only available for channels enable temperature conversion.
(1) Overview of disconnection detection
Maximum 1600msMaximum 640ms
Normal
Disconnection detection signal (XC)
Disconnected
Normal
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
Disconnection detection flag (Un\G49)
CH Measured temperature value
(Un\G11 to Un\G18)
Error clear request (YF)
Figure 3.6 Overview of disconnection detection
Normal(0)
Measured temperature value
Disconnected(1)
Conversion setting value for disconnection detection
Normal(0)
Measured temperature value
(a) It takes up to 640ms till when disconnection is detected.
When disconnection is detected, Disconnection detection flag (Un\G49) and Disconnection detection signal (XC) turn on. Consequently, “ALM” LED blinks.
(b) When disconnection is detected, the value selected from “Up scale”, “Down scale”
or “Given value” in Conversion setting for disconnection detection
(Un\G164,Un\G165) is stored into CH Measured temperature value (Un\G11 to Un\G18). The values specified in Conversion setting for disconnection detection (Un\G164,Un\G165) remains from when disconnection state is restored till when normal measured temperature value is stored.
(c) After disconnection state is restored, the batch-update of measured temperature
value restarts automatically. It takes up to 1600ms from when disconnection state is restored till when
measured temperature value is stored into CH Measured temperature value (Un\G11 to Un\G18).
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
(d) The state of Disconnection detection flag (Un\G49), Disconnection detection
signal (XC), and “ALM” LED, which means the state of disconnection detection, remain even when disconnection state is restored. Turn on Error clear request (YF).
(e) For operating the warning output function in disconnection and restoration, refer
to Section 3.2.4.
3.2 Function List

3.2.2 Conversion setting for disconnection detection function (Q68TD-G-H02 only)

3 - 11
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 36
3
SPECIFICATIONS
(2) Setting methods
When “Up scale”, “Down scale” or “Given value” is selected in Conversion setting for
disconnection detection (Un\G164, Un\G165), the value to be stored into CH Measured temperature value (Un\G11 to Un\G18) in disconnection detection can be specified.
(a) Up scale and down scale
When “Up scale” (0H) or “Down scale” (1H) is selected, an up scale value or down scale value of thermocouple-type to be used is stored into the CH Measured temperature value (Un\G11 to Un\G18).
Thermocouple
type
Thermocouple K 0
Thermocouple E 1
Thermocouple J 2
Thermocouple T 3
Thermocouple B 4
Thermocouple R 5
Thermocouple S 6
Thermocouple N 7
Table 3.4 Upscale and down scale list
Setting value
Measurement
range
-270 to 1370 1452.0 -352.0
-270 to 1000 1063.5 -333.5
-210 to 1200 1270.5 -280.5
-270 to 400 433.5 -303.5
0 to 1820 1911.0 -91.0
-50 to 1760 1850.5 -140.5
-50 to 1760 1850.5 -140.5
-270 to 1300 1378.5 -348.5
Measured temperature value when
disconnection is detected.
Up scale Down scale
(b) Given value
When “Given value” (2H) is selected, set a value in the CH Conversion setting
value for disconnection detection (Un\G166 to Un\G173) in units of 0.1 .
The value set in the buffer memory above is stored into the CH Measured temperature value (Un\G11 to Un\G18) when disconnection is detected.
3 - 12
3.2 Function List
3.2.2 Conversion setting for disconnection detection function (Q68TD-G-H02 only)
Page 37
3
SPECIFICATIONS
3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only)
This disconnection state conversion setting function stores specific values into measured temperature values when disconnection is checked. This function can identify the disconnection detection from measured temperature values. This function is only available for channels enable temperature conversion.
(1) Overview of disconnection monitor
Maximum 11s Maximum 11s
Normal Normal
Disconnection state
monitor signal (XC)
Disconnection state monitor
flag (Un\G49)
Disconnected
Normal(0) Normal(0)Disconnected(1)
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
CH Measured temperature value
(Un\G11 to Un\G18)
Error clear request (YF)
Figure 3.7 Overview of disconnection monitor
Measured temperature value
Measured temperature value (in a gradual decline)
Conversion setting for disconnection state value
Measured temperature value
(a) It takes up to 11s from when line is disconnected till when disconnection is
monitored. The measured temperature value decreases till when disconnection state is checked. When disconnection is checked, Disconnection state monitor flag (Un\G49) and Disconnection state monitor signal (XC) turn on. Consequently, “ALM” LED blinks.
(b) When disconnection is checked, the value selected from “Up scale”, “Down scale”
or “Given value” in Disconnection state conversion setting (Un\G164,Un\G165) is
stored into the CH Measured temperature value (Un\G11 to Un\G18). The values specified in Disconnection state conversion setting (Un\G164,Un\G165) remains from when disconnection state is restored till when normal measured temperature value is stored.
(c) After disconnection state is restored, the batch-update of measured temperature
value restarts automatically. It takes up to 11s from when disconnection state is restored till when measured
temperature value is stored into CH Measured temperature value (Un\G11 to Un\G18).
(d) The state of Disconnection state monitor flag (Un\G49), Disconnection state
signal (XC), and “ALM” LED remains, which means the state of disconnection detection, remains even when disconnection state is restored. Turn on Error clear request (YF).
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
(e) For operating the warning output function in disconnection and restoration, refer
to Section 3.2.4.
3.2 Function List

3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only)

3 - 13
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 38
3
SPECIFICATIONS
(2) Setting methods
When “Up scale”, “Down scale” or “Given value” is selected in Disconnection state
conversion setting (Un\G164,Un\G165), the value to be stored into the CH Measured temperature value (Un\G11 to Un\G18) in disconnection check can be specified.
(a) Up-scale and down-scale
When “Up scale” (0H) or “Down scale” (1H) is selected, an up-scale value or down-scale value of thermocouple-type to be used is stored into the CH Measured temperature value (Un\G11 to Un\G18).
Thermocouple
type
Thermocouple K 0
Thermocouple E 1
Thermocouple J 2
Thermocouple T 3
Thermocouple B 4
Thermocouple R 5
Thermocouple S 6
Thermocouple N 7
Table 3.5 Up-scale and down-scale list
Setting value
Measurement
range
-270 to 1370 1452.0 -352.0
-270 to 1000 1063.5 -333.5
-210 to 1200 1270.5 -280.5
-270 to 400 433.5 -303.5
0 to 1820 1911.0 -91.0
-50 to 1760 1850.5 -140.5
-50 to 1760 1850.5 -140.5
-270 to 1300 1378.5 -348.5
Measured temperature value when
disconnection is detected
Up scale Down scale
(b) Given value
When “Given value” (2H) is selected, set a value in the CH CH1 Conversion
setting value for disconnection state (Un\G166 to Un\G173) in units of 0.1 .
The value set in the buffer memory above is stored in the CH Measured temperature value (Un\G11 to Un\G18) during disconnection state.
3 - 14
3.2 Function List
3.2.3 Disconnection state conversion setting function (Q68TD-G-H01 only)
Page 39
3
SPECIFICATIONS
1
3.2.4 Warning output function
(1) Process alarm
(a) Warning occurrence
When the detected measured temperature value is higher than or equal to the process alarm upper upper limit value or lower than or equal to the process alarm lower lower limit value and falls in the warning output range, a warning occurs. When a warning occurs, it is notified by storing "1" in the bit position corresponding to the channel of the warning output flag (process alarm)(Un\G47), and turning ON the warning output signal (XD) and the [ALM] LED.
(b) Warning clearance
After a warning occurrence, when the temperature value falls lower than the process alarm upper lower limit value or rises higher than the process alarm lower upper limit value and returns to within the setting range, the warning is cleared. When the warning is cleared, "0" is stored in the bit position corresponding to the channel of the warning output flag (process alarm)(Un\G47). The warning output signal (XD) turns OFF and the "ALM" LED turns off only when the process alarm and rate alarm warnings for all channels do not occur or are in clearance state.
Warning output range section
Temperature
Upper upper
limit value
Upper lower
limit value
CH1 measured
temperature value
Lower upper
limit value
CH2 measured
temperature value
Lower lower
limit value
Warning occurence
Warning occurence
Warning clearance
Warning clearance
Out of warning output range section Included
Warning clearance
Warning clearance
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
CH1 Process alarm upper limit value (Un\G47,b0)
CH1 Process alarm lower limit value (Un\G47,b1)
CH2 Process alarm upper limit value (Un\G47,b2)
Warning output signal (XD)
Figure 3.8 Warning output occurence and clearance (Process alarm)
3.2 Function List

3.2.4 Warning output function

Time
3 - 15
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 40
3
SPECIFICATIONS
(c) Settable range and default value differ according to the thermocouple type.
Set it in unit of 0.1 .
Thermocouple
type
Thermocouple K -2000 12000 -2700 to 13700 (-2000 to 12000)
Thermocouple E -2000 9000 -2700 to 10000 (-2000 to 9000)
Thermocouple J -400 7500 -2100 to 12000 (-400 to 7500)
Thermocouple T -2000 3500 -2700 to 4000 (-2000 to 3500)
Thermocouple B 6000 17000 0 to 18200 (6000 to 17000)
Thermocouple R 0 16000 -500 to 17600 (0 to 16000)
Thermocouple S 0 16000 -500 to 17600 (0 to 16000)
Thermocouple N -2000 12500 -2700 to 13000 (-2000 to 12500)
Table 3.6 Settable range and default value of process alarm
Default value
Process
alarm lower
upper
limit
value
Process
alarm lower lower
limit
value
Process
alarm upper upper
limit
value
Process
alarm
upper
lower
limit
value
Settable temperature range
(Accuracy guarantee range)
(d) When time average or count average is specified, process-alarm processing is
executed for each preset time or count. When other temperature conversion system (sampling processing, moving average, or primary delay filter) is specified, process-alarm processing is executed at every sampling time.
(e) When the value of the Conversion setting for disconnection detection
(Un\G164,Un\G165) or Disconnection state conversion setting (Un\G164,Un\G165) is set for disconnection detection or disconnection check as follows, a warning occur.
• The lower or equal value to the value set in the process alarm lower lower limit is set.
• The higher or equal value to the value set in the process alarm upper upper limit is set.
(2) Rate alarm
(a) Warning occurrence
When the measured temperature value is monitored at every rate alarm warning detection period and the changed portion from the preceding value is larger than or equal to the rate alarm upper limit value or smaller than or equal to the rate alarm lower limit value, a warning occurs. When a warning occurs, it is notified by storing "1" in the bit position corresponding to the channel of the warning output flag (rate alarm)(Un\G48), and turning ON the warning output signal (XD) and the [ALM] LED.
3 - 16
3.2 Function List
3.2.4 Warning output function
Page 41
3
SPECIFICATIONS
(b) Warning clearance
After a warning occurrence, when the changed portion of the measured temperature value falls lower than the rate alarm upper limit value or rises higher than the rate alarm lower limit value, and returns to within the setting range, the warning is cleared. When the warning is cleared, "0" is stored in the bit position corresponding to the channel of the warning output flag (rate alarm)(Un\G48). The warning output signal (XD) turns OFF and the "ALM" LED turns off only when the process alarm and rate alarm warings for all channels do not occur or are in clearance state.
Measured temperature value
Rate alarm warning detection period
CH1 measured temperature value
CH2 measured temperature value
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Rate alarm warning detection
Change of measured temperature value ( C)
CH1 Rate alarm upper limit value (Un\G48,b0)
CH1 Rate alarm lower limit value (Un\G48,b1)
CH2 Rate alarm upper limit value (Un\G48,b2)
Warning output signal (XD)
Figure 3.9 Warning output occurence and clearance (Rate alarm)
period
Change of CH2 measured temperature value
Rate alarm upper limit value
Rate alarm lower limit value
Change of CH1 measured temperature value
Time
Time
(c) Set the rate alarm upper limit/lower limit values in units of 0.1 for the measured
temperature range.
Setting range is -32768 to 32767 (-3276.8 to 3276.7 ). Initial value is set to "0".
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
3.2 Function List
3.2.4 Warning output function
TROUBLESHOOTING
3 - 17
Page 42
3
SPECIFICATIONS
(d) The rate alarm warning detection period is set based on the period batch-updating
measured temperature values and the number of the periods. Setting range is 1 to 6000 (times). Calculation method of the rate alarm warning detection period is below.
(Rate alarm warning detection period) = (Setting value of the rate alarm warning detection period) (Temperature measurement value update period)
[Example 1: When setting the rate alarm warning detection period to 150 times with sampling processing]
Rate alarm warning detection period = 150 times
[Example 2: When setting the rate alarm warning detection period to 150 times with 2000ms of time average for the averaging processing)]
2000
320 = 6.25 (times) Drop the fractional part
The batch-updated period of 2000ms of time average is same as the period of 1920ms (320ms 6 times) Rate alarm warning detection period = 150 times
320ms = 48000ms = 48s
1920ms=288000ms = 288s
[Example 3: When setting the rate alarm warning detection period to 150 times with 10 times of count average for the averaging processing]
Rate alarm warning detection period = 150 times 480s
[Example 4: When setting the rate alarm warning detection period to 150 times with 4 times of moving average for the averaging processing)]
Rate alarm warning detection period = 150 times
(e) Rate alarm is effective to monitor a change of measured temperature values
within a limited range.
1) Setting example of the rate alarm upper limit/lower limit values for monitoring that a measured temperature value rises within the specified range
Change of measured temperature value ( C)
20.0
10.0
C
C
0
Rate alarm upper limit value
Rate alarm lower limit value
10 times 320ms = 480000ms =
320ms=48000ms = 48s
3 - 18
Time
Figure 3.10 Setting example of rate alarm upper limit or lower limit
3.2 Function List
3.2.4 Warning output function
Page 43
3
SPECIFICATIONS
2) Setting example of rate alarm upper limit/lower limit values for monitoring that
a measured temperature value drops within the specified range
Change of measured temperature value ( C)
Figure 3.11 Setting example of rate alarm upper limit or lower limit
3) Setting example of rate alarm upper limit/lower limit values for monitoring that
a measured temperature value changes within the specified range
Change of measured temperature value ( C)
-10.0
-20.0
C
C
1
OVERVIEW
2
0
Rate alarm upper limit value
SYSTEM
CONFIGURATION
3
Rate alarm lower limit value
Time
SPECIFICATIONS
4
Rate alarm upper limit value
C
10.0
0
C
-10.0
Rate alarm lower limit value
Time
Figure 3.12 Setting example of rate alarm upper limit or lower limit
(f) When the value of the Conversion setting for disconnection detection
(Un\G164,Un\G165) or Disconnection state conversion setting (Un\G164,Un\G165) is set for disconnection detection or disconnection check as follows, a warning occur.
• The changed portion from the preceding value is smaller than or equal to the rate alarm lower limit value.
• The changed portion from the preceding value is larger than or equal to the rate alarm upper limit value.
(g) After connection is restored, preceding values required for rate alarm occurence
are cleared. Therefore, a warning does not occur even though the changed portion of measured temperature values before and after temperature conversion exceeds the setting range when temperature conversion is restarted.
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
3.2 Function List
3.2.4 Warning output function
TROUBLESHOOTING
3 - 19
Page 44
3
SPECIFICATIONS
3.2.5 Cold junction temperature compensation resistor disconnection detection function
This function detects disconnection of cold junction compensation resistor (RTD). When a cold junction compensation resistor (RTD) connected with a relay terminal block is disconnected, an error (error code 800) occurs. Consequently, the Error flag (XF) turns on and the “ERR” LED blinks to notify the error.
(1) Condition for detecting disconnection of cold junction compensation
resistor (RTD)
Disconnection of the cold junction temperature compensation can be detected only when the switch setting 4 of the intelligent function modules is set to “with cold junction compensation”. The following shows the conditions in which the disconnection of the cold junction temperature compensation resistor (RTD) can be detected.
Table 3.7 Disconnection detection of cold junction temperature compensation resistor
Connection state
Cold junction temperature
with/without setting
Error flag
RTD
Without disconnection
RTD
With disconnection
Without connection
(2) Operation for detecting disconnection of cold junction compensation
resistor (RTD)
When disconnection of cold junction temperature compensation resistor (RTD) is detected, conversion for every conversion-enabled channel stops. The measured temperature value for cold junction temperature compensation resistor (RTD) disconnection remains the same as the measured value prior to the disconnection detection.
+
-
GND
+
-
GND
+
-
GND
with
OFF
without
with ON
without OFF
with ON
without OFF
3 - 20
(3) Operation and processing for restoring disconnection of cold junction
compensation resistor (RTD)
Conversion processing does not restart even after the disconnection of the cold junction temperature compensation resistor (RTD) is restored. To restart the conversion processing, turn off the Error clear request (YF).
3.2 Function List

3.2.5 Cold junction temperature compensation resistor disconnection detection function

Page 45
3
SPECIFICATIONS
3.3 I/O Signals Transferred to/from Programmable Controller CPU
This section describes the I/O signal assignment and signal functions.
1
3.3.1 I/O signal list
The following are the I/O signals of the Q68TD-G-H02 (H01). The I/O numbers (X/Y) given in this chapter and later assume that the first I/O number of the Q68TD-G-H02 (H01) is set to 0.
Table 3.8 I/O signal list
Input signal
(Signal direction:
Programmable controller CPU Q68TD-G-H02 (H01))
Device No. Signal name Device No. Signal name
X0 Module ready Y0
X1
X2 Y2
X3 Y3
X4 Y4
X5 Y5
X6 Y6
X7 Y7
X8 Y8
X9 Operating condition setting completion flag Y9 Operating condition setting request
XA Offset/gain setting mode status flag YA User range write request
XB Channel change completion flag YB Channel change request
XC
XD Warning output signal YD
XE Conversion completion flag YE
XF Error flag YF Error clear request
Reserved
Disconnection detection signal (Q68TD-G-H02 only)
Disconnection state monitor signal (Q68TD-G-H01
only)
*
Programmable controller CPU Q68TD-G-H02 (H01))
Y1
Reserved
YC
Reserved
Output signal
(Signal direction:
*
*
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
POINT
The reserved signals marked * are used by the system and are unavailable for the user. Should they be turned on/off in a sequence program, we cannot guarantee the functions of the Q68TD-G-H02 (H01).

3.3 I/O Signals Transferred to/from Programmable Controller CPU

3.3.1 I/O signal list

3 - 21
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 46
3
SPECIFICATIONS
3.3.2 I/O signal details
The following are details of the Q68TD-G-H02 (H01) I/O signals.
(1) Module ready (X0)
(a) If the module is in the normal mode at power-on or resetting of the programmable
controller CPU, this signal turns on to start conversion processing as soon as it gets ready for conversion.
(b) When this signal (X0) is off in the normal mode, conversion processing is not
performed. In the offset/gain setting mode, conversion processing is performed if this signal (X0) is off.
(c) This signal (X0) turns off when:
• The module is in the offset/gain setting mode
• The Q68TD-G-H02 (H01) is in a watchdog timer error *1
* 1 Occurs if program operation is not completed within the intended time due to errors such as a
hardware fault of the Q68TD-G-H02 (H01). The RUN LED of the Q68TD-G-H02 (H01) goes off when a watchdog timer error occurs.
(2) Operation condition setting completion flag (X9)
(a) When the following settings are changed, this signal is used as an interlock
condition to turn ON/OFF the operation condition setting request (Y9).
• Conversion enable/disable setting (Un\G0)
• CH Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)
• Averaging processing selection (Un\G24,Un\G25)
• Warning output enable/disable setting (Un\G46)
• Scaling valid/invalid setting (Un\G58)
• CH Scaling range upper/lower limit value (Un\G62 to Un\G77)
• CH Scaling width upper/lower limit value (Un\G78 to Un\G93)
• CH Process alarm upper/lower limit value (Un\G94 to Un\G125)
• CH Rate alarm warning detection period (Un\126 to Un\G133)
• CH Rate alarm upper/lower limit value (Un\G134 to Un\G149)
• Conversion setting for disconnection detection (Un\G164,Un\G165) (Q68TD­G-H02 only)
• Disconnection state conversion setting (Un\G164,Un\G165) (Q68TD-G-H01 only)
• CH Conversion setting value for disconnection detection (Un\G166 to Un\G173) (Q68TD-G-H02 only)
• CH Conversion setting value for disconnection state (Un\G166 to Un\G173) (Q68TD-G-H01 only)
3 - 22
(b) When Operation condition setting completion flag (X9) is OFF, conversion
processing is not carried out.
3.3 I/O Signals Transferred to/from Programmable Controller CPU

3.3.2 I/O signal details

Page 47
3
SPECIFICATIONS
(c) Operating condition setting completion flag (X9) turns OFF in the following status.
• When Operating condition setting request (Y9) is ON.
Module ready (X0)
Operating condition setting completion flag (X9)
Operating condition setting request (Y9)
Conversion enable/disable setting (Un\G0)
Conversion completion flag (XE)
Figure 3.13 When Operating condition setting request (Y9) is ON
(3) Offset/gain setting mode status flag (XA)
Executed in Q68TD-G-H02(H01) Executed in sequence program
Conversion disabled
Conversion enabled
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(a) In offset/gain setting mode
1) This signal is used as an interlock condition to turn ON/OFF the user range write request (YA) when the value at completion of offset/gain setting adjustment is registered.
2) See Section 4.6 regarding the offset/gain settings.
Executed in Q68TD-G-H02(H01)
Executed in sequence program
OFF
Module ready (X0)
Offset/gain setting mode status flag (XA)
User range write request (YA)
Figure 3.14 Offset/gain setting mode status flag (XA) during offset/gain setting mode
(b) In normal mode
1) This signal is used as an interlock condition to turn ON/OFF the user range write request (YA) when the user range is restored.
2) Refer to CHAPTER 7 for the user range restoration.
Executed in Q68TD-G-H02(H01) Executed in sequence program
ON
Module ready (X0)
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
Offset/gain setting mode status flag (XA)
User range write request (YA)
Figure 3.15 Offset/gain setting mode status flag (XA) during normal mode
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
3 - 23
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 48
3
SPECIFICATIONS
(4) Channel change completion flag (XB)
(a) This signal is used as an interlock condition to turn ON/OFF the channel change
request (YB) when changing the channel for the offset/gain setting.
(b) For offset/gain setting, refer to Section 4.6.
Executed in Q68TD-G-H02(H01) Executed in sequence program
Offset/gain setting mode offset/gain specification (Un\G26, Un\G27)
Channel change completion flag (XB)
Channel change request (YB)
Figure 3.16 Channel change completion flag (XB)
(5) Disconnection detection signal (XC) (Q68TD-G-H02 only)
(a) This signal turns on when any input signal line including a thermocouple in the
input circuit of the conversion-enabled channel is disconnected. To identify the disconnected channel, check Disconnection detection flag (Un\G49). When this signal turns on, conversion update for the conversion-enabled channels stops.
(b) Measured temperature value when this signal turns on can be selected from "Up
scale", "Down scale", or "Given scale". (Refer to Section 3.2.2)
(c) This signal turns off after eliminating the cause of disconnection and turning on
Error clear request (YF).
(d) When connection is restored, the measured temperature value update is restarted
regardless of the reset of this signal.
(6) Disconnection state monitor signal (XC) (Q68TD-G-H01 only)
(a) The thermocouple input circuit of the conversion-enabled channel turns ON the
disconnection state monitor signal (XC) when any input signal line including the thermocouple is disconnected. To identify the disconnected channel, check with the disconnection state monitor flag (Un\G49). In addition, conversion update for the conversion-enabled channels stops.
3 - 24
(b) For measured temperature values to be stored when the disconnection state
monitor signal (XC) turns ON, any of "Up scale", "Down scale", or "Given value" can be selected (refer to Section 3.2.3).
(c) Removing the cause of disconnection and turning ON the error clear request (YF)
turns OFF the disconnection state monitor signal (XC).
(d) When the line connection is recovered, the temperature conversion value update
is restarted regardless of the disconnection state monitor signal (XC) reset.
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
Page 49
3
SPECIFICATIONS
(7) Warning output signal (XD)
(a) The warning output signal (XD) turns ON when a process alarm or rate alarm is
detected.
1) Process alarm
• This signal turns ON when the process alarm is enabled and a measured
• For every conversion-enabled channel, the signal automatically turns OFF
2) Rate alarm
• This signal turns ON when the rate alarm is enabled and the change of
• For every conversion-enabled channel, the signal automatically turns OFF
temperature value exceeds the preset range of the process alarm upper/ lower limit value (Un\G94 to Un\G125) in a conversion-enabled channel.
when the measured temperature value returns to within the setting range, and the "ALM" LED also turns off.
measured temperature value exceeds the preset range of the rate alarm upper/lower limit value (Un\G134 to Un\G149) in a conversion-enabled channel.
when the change of measured temperature values return to within the setting range, and the "ALM" LED also turns off.
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Executed in Q68TD-G-H02(H01)
Warning output flag (Un\G47, Un\G48)
Warning output signal (XD)
Figure 3.17 On or off for warning output signal (XD)
0
Warning occurrence (process alarm, rate alarm)
0
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
3 - 25
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 50
3
SPECIFICATIONS
(8) Conversion completion flag (XE)
(a) Conversion completion flag (XE) turns ON when the measured temperature
values of all conversion-enabled channels are stored into buffer memory after power-on or hardware reset.
(b) When averaging processing is performed, this signal also turns ON when the
converted measured temperature value is stored into buffer memory after completion of averaging processing.
(c) When Operating condition setting completion flag (X9) turns on (stop
conversion)
1) After the measured temperature value is stored into buffer memory, the bit of corresponding channel in Conversion completion flag (Un\G10) turns on (changes to "1").
2) After the measured temperature values of all conversion-enabled channels are stored into buffer memory, this flag turns on.
(d) When Operating condition setting completion flag (X9) turns off (conversion
stop)
1) The bits of all channels in Conversion completion flag (Un\G10) are turned off (changes to "0").
2) This flag (XE) turns off. Note that even though conversion has been stopped, the data immediately before the stop are held in the Measured temperature values stored in the buffer memory.
(e) This flag (XE) does not turn on when all channels are set to conversion-disabled.
(9) Error Flag (XF)
(a) Error flag (XF) turns ON when a writing error occurs.
(b) To clear the error code, turn ON Error clear request (YF).
Executed in Q68TD-G-H02(H01) Executed in sequence program
Error code (Un\G19)
Error occurrence
3 - 26
Error flag (XF)
Error clear request (YF)
Figure 3.18 On or off for Error flag (XF)
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
Page 51
3
SPECIFICATIONS
(10)Operating condition setting request (Y9)
(a) This signal is turned ON when enabling the following setting contents.
• Conversion enable/disable setting (Un\G0)
• CH Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)
• Averaging processing selection (Un\G24,Un\G25)
• Warning output enable/disable setting (Un\G46)
• Scaling valid/invalid setting (Un\G58)
• CH Scaling range upper/lower limit value (Un\G62 to Un\G77)
• CH Scaling width upper/lower limit value (Un\G78 to Un\G93)
• CH Process alarm upper/lower limit value (Un\G94 to Un\G125)
• CH Rate alarm warning detection period (Un\G126 to Un\G133)
• CH Rate alarm upper/lower limit value (Un\G134 to Un\G149)
• Conversion setting for disconnection detection (Un\G164,Un\G165) (Q68TD­G-H02 only)
• Disconnection state conversion setting (Un\G164,Un\G165) (Q68TD-G-H01 only)
• CH Conversion setting value for disconnection detection (Un\G166 to Un\G173) (Q68TD-G-H02 only)
• CH Conversion setting value for disconnection state (Un\G166 to Un\G173) (Q68TD-G-H01 only)
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
(b) When this signal is turned on, Disconnection detection signal (XC) and Warning
output signal (XD) turn off.
(c) For the ON/OFF timing, refer to the field of the operating condition setting
completion flag (X9).
(11)User range write request (YA)
(a) In offset/gain setting mode
1) This signal turns ON when registering the adjusted value of offset/gain setting to the flash memory.
2) For the ON/OFF timing, refer to the field of the offset/gain setting mode status flag (XA). For offset/gain settings, refer to Section 4.6.
(b) In normal mode
1) This signal turns ON when the user range is restored.
2) For the ON/OFF timing, refer to the field of the offset/gain setting mode status flag (XA). For user range restoration, refer to CHAPTER 7.
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
TROUBLESHOOTING
3 - 27
Page 52
3
SPECIFICATIONS
(12)Channel change request (YB)
(a) This signal turns ON when changing the channel for executing the offset/gain
setting.
(b) For the ON/OFF timing, refer to the field of the channel change completion flag
(XB). For the offset/gain setting, refer to Section 4.6.
(13)Error clear request (YF)
(a) This signal turns ON when clearing Error flag (XF) and Disconnection state
monitor signal (XC). However, the setting value error of the intelligent function module switch setting cannot be cleared. Correct the setting value.
(b) For the ON/OFF timing, refer to the filed of Disconnection state monitor signal
(XC) and Error flag (XF)
3 - 28
3.3 I/O Signals Transferred to/from Programmable Controller CPU
3.3.2 I/O signal details
Page 53
3
SPECIFICATIONS
3.4 Buffer Memory
3.4.1 Buffer memory assignment
This section describes the assignment of the Q68TD-G-H02 (H01) buffer memory.
POINT
Do not write data from system area or sequence program to the buffer memory area where writing is disabled. Doing so may cause malfunction.
Addresses
Hex. Dec.
00H 0 Conversion enable/disable setting 00FFH
01H 1 CH1 Time/Count/Moving average/Time constant setting 0
02H 2 CH2 Time/Count/Moving average/Time constant setting 0
03H 3 CH3 Time/Count/Moving average/Time constant setting 0
04H 4 CH4 Time/Count/Moving average/Time constant setting 0
05H 5 CH5 Time/Count/Moving average/Time constant setting 0
06H 6 CH6 Time/Count/Moving average/Time constant setting 0
07H 7 CH7 Time/Count/Moving average/Time constant setting 0
08H 8 CH8 Time/Count/Moving average/Time constant setting 0
09H 9 System area - -
0AH 10 Conversion completion flag 0 R
0BH 11 CH1 Measured temperature value 0 R
0CH 12 CH2 Measured temperature value 0 R
0DH 13 CH3 Measured temperature value 0 R
0EH 14 CH4 Measured temperature value 0 R
0FH 15 CH5 Measured temperature value 0 R
10H 16 CH6 Measured temperature value 0 R
11H 17 CH7 Measured temperature value 0 R
12H 18 CH8 Measured temperature value 0 R
13H 19 Error code 0 R
14H 20 Setting range 1(Thermocouple type CH1-CH4) 0 R
15H 21 Setting range 2(Thermocouple type CH5-CH8) 0 R
16H 22 Setting range 3(Offset/gain setting CH1-CH8) 0 R
17H 23 System area - -
18H 24 Averaging processing selection (CH1-CH4) 0
19H 25 Averaging processing selection (CH5-CH8) 0
1AH 26 Offset/gain setting mode(Offset specification) 0
1BH 27 Offset/gain setting mode(Gain specification) 0
1CH 28 CH1 Offset temperature setting value 0
1DH 29 CH1 Gain temperature setting value 0
1EH 30 CH2 Offset temperature setting value 0
1FH 31 CH2 Gain temperature setting value 0
20H 32 CH3 Offset temperature setting value 0
21H 33 CH3 Gain temperature setting value 0
22H 34 CH4 Offset temperature setting value 0
23H 35 CH4 Gain temperature setting value 0
Table 3.9 Buffer memory assignment
Description Default value

3.4 Buffer Memory

3.4.1 Buffer memory assignment

Read/Write
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
3 - 29
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
*1
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
Page 54
3
SPECIFICATIONS
Table 3.9 Buffer memory assignment
Addresses
Hex. Dec.
24H 36 CH5 Offset temperature setting value 0
25H 37 CH5 Gain temperature setting value 0
26H 38 CH6 Offset temperature setting value 0
27H 39 CH6 Gain temperature setting value 0
28H 40 CH7 Offset temperature setting value 0
29H 41 CH7 Gain temperature setting value 0
2AH 42 CH8 Offset temperature setting value 0
2BH 43 CH8 Gain temperature setting value 0
2CH 44 System area - -
2DH 45
Cold junction compensation setting state (Q68TD-G-H02 only) 0 R
System area (Q68TD-G-H01 only) - -
2EH 46 Warning output enable/disable setting FFFFH
2FH 47 Warning output flag(Process alarm) 0 R
30H 48 Warning output flag(Rate alarm) 0 R
31H 49
Disconnection detection flag (Q68TD-G-H02 only)
Disconnection state monitor flag (Q68TD-G-H01 only)
32H 50 CH1 Scaling value 0 R
33H 51 CH2 Scaling value 0 R
34H 52 CH3 Scaling value 0 R
35H 53 CH4 Scaling value 0 R
36H 54 CH5 Scaling value 0 R
37H 55 CH6 Scaling value 0 R
38H 56 CH7 Scaling value 0 R
39H 57 CH8 Scaling value 0 R
3AH 58 Scaling valid/invalid setting 00FFH
3BH 59
to to
System area - -
3DH 61
3EH 62 CH1 Scaling range lower limit value 0
3FH 63 CH1 Scaling range upper limit value 0
40H 64 CH2 Scaling range lower limit value 0
41H 65 CH2 Scaling range upper limit value 0
42H 66 CH3 Scaling range lower limit value 0
43H 67 CH3 Scaling range upper limit value 0
44H 68 CH4 Scaling range lower limit value 0
45H 69 CH4 Scaling range upper limit value 0
46H 70 CH5 Scaling range lower limit value 0
47H 71 CH5 Scaling range upper limit value 0
48H 72 CH6 Scaling range lower limit value 0
49H 73 CH6 Scaling range upper limit value 0
4AH 74 CH7 Scaling range lower limit value 0
4BH 75 CH7 Scaling range upper limit value 0
4CH 76 CH8 Scaling range lower limit value 0
4DH 77 CH8 Scaling range upper limit value 0
4EH 78 CH1 Scaling width lower limit value 0
4FH 79 CH1 Scaling width upper limit value 0
50H 80 CH2 Scaling width lower limit value 0
51H 81 CH2 Scaling width upper limit value 0
52H 82 CH3 Scaling width lower limit value 0
Description Default value
0R
Read/Write
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
*1
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
3 - 30
3.4 Buffer Memory
3.4.1 Buffer memory assignment
Page 55
3
SPECIFICATIONS
Table 3.9 Buffer memory assignment
Addresses
Hex. Dec.
53H 83 CH3 Scaling width upper limit value 0
54H 84 CH4 Scaling width lower limit value 0
55H 85 CH4 Scaling width upper limit value 0
56H 86 CH5 Scaling width lower limit value 0
57H 87 CH5 Scaling width upper limit value 0
58H 88 CH6 Scaling width lower limit value 0
59H 89 CH6 Scaling width upper limit value 0
5AH 90 CH7 Scaling width lower limit value 0
5BH 91 CH7 Scaling width upper limit value 0
5CH 92 CH8 Scaling width lower limit value 0
5DH 93 CH8 Scaling width upper limit value 0
5EH 94 CH1 Process alarm lower lower limit value -2000
5FH 95 CH1 Process alarm lower upper limit value -2000
60H 96 CH1 Process alarm upper lower limit value 12000
61H 97 CH1 Process alarm upper upper limit value 12000
62H 98 CH2 Process alarm lower lower limit value -2000
63H 99 CH2 Process alarm lower upper limit value -2000
64H 100 CH2 Process alarm upper lower limit value 12000
65H 101 CH2 Process alarm upper upper limit value 12000
66H 102 CH3 Process alarm lower lower limit value -2000
67H 103 CH3 Process alarm lower upper limit value -2000
68H 104 CH3 Process alarm upper lower limit value 12000
69H 105 CH3 Process alarm upper upper limit value 12000
6AH 106 CH4 Process alarm lower lower limit value -2000
6BH 107 CH4 Process alarm lower upper limit value -2000
6CH 108 CH4 Process alarm upper lower limit value 12000
6DH 109 CH4 Process alarm upper upper limit value 12000
6EH 110 CH5 Process alarm lower lower limit value -2000
6FH 111 CH5 Process alarm lower upper limit value -2000
70H 112 CH5 Process alarm upper lower limit value 12000
71H 113 CH5 Process alarm upper upper limit value 12000
72H 114 CH6 Process alarm lower lower limit value -2000
73H 115 CH6 Process alarm lower upper limit value -2000
74H 116 CH6 Process alarm upper lower limit value 12000
75H 117 CH6 Process alarm upper upper limit value 12000
76H 118 CH7 Process alarm lower lower limit value -2000
77H 119 CH7 Process alarm lower upper limit value -2000
78H 120 CH7 Process alarm upper lower limit value 12000
79H 121 CH7 Process alarm upper upper limit value 12000
7AH 122 CH8 Process alarm lower lower limit value -2000
7BH 123 CH8 Process alarm lower upper limit value -2000
7CH 124 CH8 Process alarm upper lower limit value 12000
7DH 125 CH8 Process alarm upper upper limit value 12000
7EH 126 CH1 Rate alarm warning detection period 0
7FH 127 CH2 Rate alarm warning detection period 0
80H 128 CH3 Rate alarm warning detection period 0
81H 129 CH4 Rate alarm warning detection period 0
Description Default value
3.4 Buffer Memory
3.4.1 Buffer memory assignment
Read/Write
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
3 - 31
1
*1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
Page 56
3
SPECIFICATIONS
Table 3.9 Buffer memory assignment
Addresses
Hex. Dec.
82H 130 CH5 Rate alarm warning detection period 0
83H 131 CH6 Rate alarm warning detection period 0
84H 132 CH7 Rate alarm warning detection period 0
85H 133 CH8 Rate alarm warning detection period 0
86H 134 CH1 Rate alarm upper limit value 0
87H 135 CH1 Rate alarm lower limit value 0
88H 136 CH2 Rate alarm upper limit value 0
89H 137 CH2 Rate alarm lower limit value 0
8AH 138 CH3 Rate alarm upper limit value 0
8BH 139 CH3 Rate alarm lower limit value 0
8CH 140 CH4 Rate alarm upper limit value 0
8DH 141 CH4 Rate alarm lower limit value 0
8EH 142 CH5 Rate alarm upper limit value 0
8FH 143 CH5 Rate alarm lower limit value 0
90H 144 CH6 Rate alarm upper limit value 0
91H 145 CH6 Rate alarm lower limit value 0
92H 146 CH7 Rate alarm upper limit value 0
93H 147 CH7 Rate alarm lower limit value 0
94H 148 CH8 Rate alarm upper limit value 0
95H 149 CH8 Rate alarm lower limit value 0
96H 150
to to
9DH 157
9EH 158
9FH 159
A0H 160
to to
A3H 163
A4H 164
A5H 165
A6H 166
A7H 167
A8H 168
System area - -
Mode switching setting 0
System area - -
Conversion setting for disconnection detection (CH1-CH4)(Q68TD-
G-H02 only)
Disconnection state conversion setting (CH1-CH4)(Q68TD-G-H01
only)
Conversion setting for disconnection detection (CH5-CH8)(Q68TD-
G-H02 only)
Disconnection state conversion setting (CH5-CH8)(Q68TD-G-H01
only)
CH1 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH1 Conversion setting value for disconnection state (Q68TD-G-
H01 only)
CH2 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH2 Conversion setting value for disconnection state (Q68TD-G-
H01 only)
CH3 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH3 Conversion setting value for disconnection state (Q68TD-G-
H01 only)
Description Default value
1111H
1111
0
0
0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
*1
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
Read/Write
H
3 - 32
3.4 Buffer Memory
3.4.1 Buffer memory assignment
Page 57
3
SPECIFICATIONS
Addresses
Hex. Dec.
A9H 169
AAH 170
ABH 171
ACH 172
ADH 173
AEH 174
to to
BDH 189
BE
BF
C0
C1
C2
C3
C4
C5
C6
C7
C8
C9
CA
CB
CC
CD
CE
CF
D0
D1
D2
D3
D4
D5
D6
D7
D8
190
H
191
H
192
H
193
H
194
H
195
H
196
H
197
H
198
H
199
H
200
H
201
H
202
H
203
H
204
H
205
H
206
H
207
H
208
H
209
H
210
H
211
H
212
H
213
H
214
H
215
H
216
H
Table 3.9 Buffer memory assignment
Description Default value
Read/Write
CH4 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH4 Conversion setting value for disconnection state (Q68TD-G-
0
R/W
H01 only)
CH5 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH5 Conversion setting value for disconnection state (Q68TD-G-
0
R/W
H01 only)
CH6 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH6 Conversion setting value for disconnection state (Q68TD-G-
0
R/W
H01 only)
CH7 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH7 Conversion setting value for disconnection state (Q68TD-G-
0
R/W
H01 only)
CH8 Conversion setting value for disconnection detection (Q68TD-
G-H02 only)
CH8 Conversion setting value for disconnection state (Q68TD-G-
0
R/W
H01 only)
System area - -
CH1 Factory default offset value
CH1 Factory default gain value
CH1 User range settings offset value
CH1 User range settings gain value
*3
*3
*3
*3
CH1 User range settings thermal EMF offset value(L)
CH1 User range settings thermal EMF offset value(H)
CH1 User range settings thermal EMF gain value(L)
CH1 User range settings thermal EMF gain value(H)
CH2 Factory default offset value
CH2 Factory default gain value
CH2 User range settings offset value
CH2 User range settings gain value
*3
*3
*3
*3
CH2 User range settings thermal EMF offset value(L)
CH2 User range settings thermal EMF offset value(H)
CH2 User range settings thermal EMF gain value(L)
CH2 User range settings thermal EMF gain value(H)
CH3 Factory default offset value
CH3 Factory default gain value
CH3 User range settings offset value
CH3 User range settings gain value
*3
*3
*3
*3
CH3 User range settings thermal EMF offset value(L)
CH3 User range settings thermal EMF offset value(H)
CH3 User range settings thermal EMF gain value(L)
CH3 User range settings thermal EMF gain value(H)
CH4 Factory default offset value
CH4 Factory default gain value
CH4 User range settings offset value
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
1
*1
*2
OVERVIEW
2
*2
*2
SYSTEM
CONFIGURATION
3
*2
*2
SPECIFICATIONS
4
*2
*2
SETUP AND
PROCEDURES BEFORE
5
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
OPERATION
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
*2
3.4 Buffer Memory
3.4.1 Buffer memory assignment
TROUBLESHOOTING
3 - 33
Page 58
3
SPECIFICATIONS
Addresses
Hex. Dec.
D9
DA
DB
DC
DD
DE
DF
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
EF
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
217
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
H
CH4 User range settings gain value
218
CH4 User range settings thermal EMF offset value(L)
219
CH4 User range settings thermal EMF offset value(H)
220
CH4 User range settings thermal EMF gain value(L)
221
CH4 User range settings thermal EMF gain value(H)
222
CH5 Factory default offset value
223
CH5 Factory default gain value
224
CH5 User range settings offset value
225
CH5 User range settings gain value
226
CH5 User range settings thermal EMF offset value(L)
227
CH5 User range settings thermal EMF offset value(H)
228
CH5 User range settings thermal EMF gain value(L)
229
CH5 User range settings thermal EMF gain value(H)
230
CH6 Factory default offset value
231
CH6 Factory default gain value
232
CH6 User range settings offset value
233
CH6 User range settings gain value
234
CH6 User range settings thermal EMF offset value(L)
235
CH6 User range settings thermal EMF offset value(H)
236
CH6 User range settings thermal EMF gain value(L)
237
CH6 User range settings thermal EMF gain value(H)
238
CH7 Factory default offset value
239
CH7 Factory default gain value
240
CH7 User range settings offset value
241
CH7 User range settings gain value
242
CH7 User range settings thermal EMF offset value(L)
243
CH7 User range settings thermal EMF offset value(H)
244
CH7 User range settings thermal EMF gain value(L)
245
CH7 User range settings thermal EMF gain value(H)
246
CH8 Factory default offset value
247
CH8 Factory default gain value
248
CH8 User range settings offset value
249
CH8 User range settings gain value
250
CH8 User range settings thermal EMF offset value(L)
251
CH8 User range settings thermal EMF offset value(H)
252
CH8 User range settings thermal EMF gain value(L)
253
CH8 User range settings thermal EMF gain value(H)
* 1 Indicates whether reading from and writing to a sequence program are enabled.
R : Read enabled W : Write enabled
* 2 Data must be written to buffer memory under the interlock conditions (buffer memory write
conditions) of the following I/O signals.
• Operating condition setting
Buffer memory write condition
Write request
Operating condition setting request
* 3 This area is related with the user range save/restore function and allows users to re-set the offset/
gain values easily in the case of online module change.
Table 3.9 Buffer memory assignment
Description Default value
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
Y9 X9
Operating condition setting completion flag
Figure 3.19 Setting of interlock conditions
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
MOV
Read/Write
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*2
R/W
*1
3 - 34
3.4 Buffer Memory
3.4.1 Buffer memory assignment
Page 59
3
SPECIFICATIONS
1
3.4.2 Conversion enable/disable setting (Un\G0)
Temperature conversion enable/disable status is set for each channel.
(1) Setting methods
(a) Set enable/disable status for each channel in buffer memory.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 are fixed to "0"
Figure 3.20 Setting of enable/disable status (Un\G0)
[Setting example] Setting enable status for channel 1 and 2
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1111110000000000
Figure 3.21 Setting example of enable/disable status (Un\G0)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
0: Conversion enabled 1: Conversion disabled
(2) Default value
The default value is set to “Disable” (00FFH) for all channels.
POINT
Setting “Disable” (1) for unused channels can prevent unnecessary disconnection detection or monitoring disconnection state.
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
3.4 Buffer Memory

3.4.2 Conversion enable/disable setting (Un\G0)

3 - 35
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 60
3
SPECIFICATIONS
3.4.3 CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)
When the averaging processing (1H to 4H) is specified with Averaging processing selection (Un\G24, Un\G25), time average, count average, moving average or time constant for primary delay filter is set. (Refer to Section 3.2.1)
(1) Setting methods
(a) Set the following setting range in buffer memory.
Table 3.10 Settable range
Processing method Setting value
Time average
Count average 4 to 500(times)
Moving average 2 to 60(times)
Primary delay filter
* 1 Set the values in units of 320ms.
For the details of the setting values, refer to Section 3.2.1 (3) Averaging processing or Section
3.2.1 (4) Primary delay filter.
1280 to 5000(ms)
320 to 5000(ms)
*1
*1
(b) Turn on Operating condition setting request (Y9) to activate the setting. (Refer to
Section 3.3.2)
(2) Default value
All channels are set to “0”.
POINT
(1) When a value out of the setting range in Table 3.10 is written, an error occurs
and the following also occurs.
• The error codes (20 , 30 , 31 , 32 ) are stored to the error code (Un\G19). (Refer to Section 8.1)
• Error flag (XF) turns on.
• Conversion processing is performed with the setting before the error occurence.
(2) When a value is set on the channels set sampling processing (0
Averaging processing selection (Un\G24, Un\G25), the setting value of CH Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8) is ignored.
H) to
3 - 36
3.4 Buffer Memory

3.4.3 CH[ ] Time/Count/Moving average/Time constant setting (Un\G1 to Un\G8)

Page 61
3
SPECIFICATIONS
1
3.4.4 Conversion completion flag (Un\G10)
Conversion state can be checked for each channel.
(1) Data storage
(a) The bit of the corresponding channel in Conversion completion flag turns on
(changes to “1”) when conversion of conversion-enabled channels is completed.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 are fixed to "0".
Figure 3.22 Storage of Conversion completion flag (Un\G10)
(b) Conversion completion flag (XE) turns on when conversion of all conversion-
enabled channels is completed.
0: During conversion or unused 1: Conversion completed
(2) How to clear stored data
When Operating condition setting request (Y)) is turned on, the bit of all channels in the Conversion completion flag returns to default value (“0”).
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
3.4 Buffer Memory

3.4.4 Conversion completion flag (Un\G10)

3 - 37
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 62
3
SPECIFICATIONS
3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)
“Thermal electromotive force values” input from thermocouples are converted into “temperature values” to check values of detected temperature.
(1) Data storage
The measured temperature value rounded off to one decimal place is multiplied by 10 and the result is stored into buffer memory in 16-bit signed binary. (Drop the second decimal place and later.)
[Setting example 1]
When the measured temperature value is 123.025 1230 is stored.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1100111000000100
Figure 3.23 Storage example 1 of CH Measured temperature value (Un\G11 to Un\G18)
When the measured temperature value is -123.0 -1230 is stored.
b15 b14 b13
11111011
Figure 3.24 Storage example 2 of CH Measured temperature value (Un\G11 to Un\G18)
b12b11b10b9b8b7b6b5b4b3b2b1b0
00110010
POINT
(1) When disconnection is detected or checked with a monitor, the values set in
Conversion setting for disconnection detection (Un\G164, Un\G165) or Disconnection state conversion setting (Un\G164, Un\G165) are stored into
the CH Measured temperature value (Un\G11 to Un\G18). (Refer to Section
3.4.25, Section 3.4.26)
(2) After the disconnection recovery, normal measured temperature value is
automatically stored.
3 - 38
3.4 Buffer Memory

3.4.5 CH[ ] Measured temperature value (Un\G11 to Un\G18)

Page 63
3
SPECIFICATIONS
3.4.6 Error code (Un\G19)
Error codes that are detected by the Q68TD-G-H02(H01) are stored. (Refer to Section
8.1)

3.4.7 Setting range 1, 2 (Thermocouple type) (Un\G20,Un\G21)

This area is for checking thermocouple type of the Q68TD-G-H02(H01). which is set with Switch 1 and 2 in the intelligent function module switch setting. (Refer to Section 4.5)
(1) Data storage
(a) The setting value of thermocouple type is stored into the position shown in the
following figure for each channel.
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
Un\G20 (Setting range CH1 to CH4)
Un\G21 (Setting range CH5 to CH8)
Figure 3.25 Storage of setting range 1,2 (thermocouple type) (Un\G20,Un\G21)
b15
to
b12 b11
CH4 CH3 CH1
CH8 CH7 CH6 CH5
to
b8 b7
to
CH2
(b) The following table shows the setting value for each thermocouple type.
Table 3.11 Thermocouple and setting value
Themocouple type Setting value
Thermocouple K 0H
Thermocouple E 1H
Thermocouple J 2H
Thermocouple T 3H
Thermocouple B 4H
Thermocouple R 5H
Thermocouple S 6H
Thermocouple N 7H

3.4.8 Setting range 3 (Offset/gain setting) (Un\G22)

b4 b3
to
b0
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
This area is for checking offset/gain setting of the Q68TD-G-H02(H01). which is set with Switch 3 in the intelligent function module switch setting. (Refer to Section 4.5)
(1) Data storage
The setting value of offset/gain setting is stored into the position corresponding to the channels shown in the following figure.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 are fixed to "0".
Figure 3.26 Storage of setting range 3 (Offset/gain setting) (Un\G22)

3.4.6 Error code (Un\G19)

0: Factory default setting 1: User range setting
3.4 Buffer Memory
3 - 39
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 64
3
SPECIFICATIONS
3.4.9 Averaging processing selection (Un\G24,Un\G25)
Averaging processing is selected for each channel.
(1) Setting methods
(a) The Averaging processing selection is set in the position corresponding to each
channel of buffer memory shown in the following figure.
Un\G24 (Averaging processing selection CH1 to CH4)
b15 b12 b11 b8 b7 b4 b3 b0
to
CH4 CH3 CH2 CH1
to
to to
Un\G25 (Averaging processing selection CH5 to CH8)
Figure 3.27 Setting of Averaging processing selection (Un\G24,Un\G25)
(b) The following table shows the setting value.
Table 3.12 Processing method and setting value
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to sampling processing (0000H).
[Setting example]
• CH1 Count average (2H)
• CH2 Time average (1
• CH3 Primary delay filter (4
• CH4 Sampling processing (0
Set “0412 setting.
CH8 CH7 CH6 CH5
Processing method Setting value
Samplling processing 0H
Time average 1H
Count average 2H
Moving average 3H
Primary delay filter 4H
H)
H)
H)
H” for Un\G24 as shown in the following figure in the case of the above
3 - 40
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G24 (Averaging processing selection CH1 to CH4)
Figure 3.28 Setting example of Averaging processing selection (Un\G24,Un\G25)
POINT
If a value out of the setting range is set, sampling processing is performed.
3.4 Buffer Memory

3.4.9 Averaging processing selection (Un\G24,Un\G25)

0001001000000100
Page 65
3
SPECIFICATIONS
3.4.10 Offset/gain setting mode (Un\G26,Un\G27)
A channel targeted for adjusting offset/gain setting values in the offset/gain setting mode is specified. (Refer to Section 4.6)
(1) Setting methods
Set a channel targeted for adjusting offset setting in Un\G26, and a channel for gain setting in Un\G27.
b7 b6 b5 b4 b3 b2 b1 b0
Un\G26 (Offset specification)
Un\G27 (Gain specification)
Figure 3.29 Setting of Averaging processing selection (Un\G24,Un\G25)
b15 b14 b13 b12 b11 b10 b9 b8
00000000
00000000
Data for b8 to b15 are fixed to "0". 1: Setting channel
CH4 CH3 CH2 CH1CH8 CH7 CH6 CH5
CH4 CH3 CH2 CH1CH8 CH7 CH6 CH5
0: disable
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(2) Default value
All channels are set to “Disable” (0000H).
POINT
Setting multiple channels at the same time is possible, however, set offset and gain values separately (set “0” in either Un\G26 or Un\G27). When both values are set at the same time, an error (error code: 500) occurs.
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
3.4 Buffer Memory

3.4.10 Offset/gain setting mode (Un\G26,Un\G27)

3 - 41
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 66
3
SPECIFICATIONS
3.4.11 CH[ ] Offset/gain temperature setting values (Un\G28 to Un\G43)
Measured temperature values equivalent to the input from the sensor are set during the offset/gain setting mode.
(1) Setting methods
(a) Input a value used as an offset value or gain value in 16-bit signed binary (units of
0.1 ) to the channel set in the Offset/gain setting mode (Un\G26,Un\G27).
(b) When Channel change request (YB) is turned on, measured temperature value is
compensated for the value written in this area.
(2) Default value
All channels are set to “0”.
POINT
(1) High accuracy is ensured for Offset/gain temperature setting values when the
minimum or maximum temperature of the operating range is used to compensate errors.
(2) Set Offset/gain temperature setting values while reading measured
temperature values.
(3) Always set Offset/gain temperature setting values to satisfy the following
conditions. An error (error code: 41 ) occurs if the conditions are not satisfied.
• Condition 1: Within the input enabled range
• Condition 2: (Gain temperature setting value) - (Offset temperature
setting value) > 0.1[ ]
(4) Offset/gain temperature setting values are stored into the flash memory of the
Q68TD-G-H02(H01) turning on User range write request (YA), and the values are not erased at power-off.
3 - 42
3.4.12 Cold junction compensation setting status (Un\G45) (Q68TD-G­H02 only)
The Cold junction compensation setting status of the Q68TD-G-H02, set with Switch 4 in the intelligent function module, can be checked.
(1) Data storage
Table 3.13 Cold junction compensation setting state (Un\G45)
Cold junction
Storage value
0000H Available
0001H Not available
3.4 Buffer Memory

3.4.11 CH[ ] Offset/gain temperature setting values (Un\G28 to Un\G43)

compensation
setting state
Page 67
3
SPECIFICATIONS
3.4.13 Warning output enable/disable setting (Un\G46)
Enable/disable state of warning output for process alarm or rate alarm is set for each channel.
(1) Setting methods
(a) Warning output enable/disable setting is set for the corresponding channels in the
following figure.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
1
OVERVIEW
2
CH4 CH3 CH2 CH1CH8 CH7 CH6 CH5CH4 CH3 CH2 CH1CH8 CH7 CH6 CH5
Rate alaram setting
0: Enable,
Figure 3.30 Setting of Warning output enable/disable setting (Un\G46)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
1: Disable
Process alarm setting
(2) Default value
Both process alarm and rate alarm are set to “Disable” for all channels (FFFFH).
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
3.4 Buffer Memory

3.4.13 Warning output enable/disable setting (Un\G46)

3 - 43
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 68
3
SPECIFICATIONS
3.4.14 Warning output flag (Process alarm/Rate alarm) (Un\G47,Un\G48)
For both process alarm and rate alarm, whether the warning is for the upper limit value or lower limit value can be checked for each channel.
(1) Data storage
(a) When a measured temperature value is out of the setting range of the CH
Process alarm upper/lower limit values (Un\G94 to Un\G125) or CH Rate alarm upper/lower limit values (Un\G134 to Un\G149), the bit of the corresponding channels turns on (changes to “1”).
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G47 (Process alarm)
CH8 lower
limit value
CH7 lower
limit value
CH8 upper
limit value
CH6 lower
CH7 upper
limit value
limit value
CH6 upper
limit value
CH5 lower
limit value
CH5 upper
CH4 lower
limit value
limit value
CH3 lower
CH4 upper
limit value
limit value
CH3 upper
limit value
CH2 lower
limit value
CH2 upper
CH1 lower
limit value
limit value
0: Normal 1: Alarm ON
CH1 upper
limit value
Un\G48 (Rate alarm)
Figure 3.31 Storage of Warning output flag (Process alarm/Rate alarm) (Un\G47,Un\G48)
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH6 lower
CH8 lower
limit value
CH8 upper
CH7 lower
limit value
limit value
limit value
CH7 upper
limit value
CH5 lower
CH6 upper
limit value
limit value
CH5 upper
limit value
CH4 lower
limit value
CH4 upper
limit value
CH3 upper
CH3 lower
limit value
limit value
CH2 lower
limit value
CH1 lower
limit value
CH2 upper
limit value
0: Normal 1: Alarm ON
CH1 upper
(b) When the measured temperature value or the change of measured temperature
values returns to within the setting range, this flag will be automatically reset.
(c) When Operating condition setting request (Y9) is turned on, this flag will be
cleared.
(d) If a warning is detected on any of channels for the conditions described below,
Warning output signal (XD) also turns on.
1) Conversion enable (“0”) is set in Conversion enable/disable setting (Un\G0).
2) Process alarm setting or rate alarm setting are set to “Enable”(“0”) in the Warning output enable/disable (Un\G46).
limit value
3 - 44
3.4 Buffer Memory

3.4.14 Warning output flag (Process alarm/Rate alarm) (Un\G47,Un\G48)

Page 69
3
SPECIFICATIONS
1
3.4.15 Disconnection detection flag (Un\G49) (Q68TD-G-H02 only)
Disconnection state is detectable for each channel.
(1) Data storage
(a) The bit of the corresponding channel turns on (changes to “1”) when the
disconnection state of a thermocouple or compensating lead wire is detected.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 is fixed to "0".
Figure 3.32 Storage of Disconnection detection flag (Un\G49)
(b) Conversion for the channels not disconnected is continued.
0: Normal 1: Disconnected
(2) How to clear flag
(a) Check the sensor connection state of disconnection detection channels.
(b) When Operating condition setting request (Y9) or Error clear request (YF) is
turned on, this flag will be cleared. When the signal turns on in disconnection state, the bit of the corresponding channel turns on (changes to “1”) again.
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
3.4 Buffer Memory

3.4.15 Disconnection detection flag (Un\G49) (Q68TD-G-H02 only)

3 - 45
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 70
3
SPECIFICATIONS
(3) Relationship between the Disconnection detection flag and conversion
enable/disable setting.
The following table shows the relationship between the Disconnection detection flag and conversion enable/disable setting.
Table 3.14 Relationship between conversion enable/disable setting and Disconnection detection flag
Connection state
Conversion enable/disable
setting
Disconnection detection
flag
Enable
Disable
Enable ON
Disable OFF
Enable ON
Disable OFF
Without disconnection
With disconnection
Without connection
+
-
+
-
+
-
POINT
(1) Always set “Disable” for any channel where no thermocouple or
compensating lead wire is connected. If “Enable” is set, the bit of the corresponding channel in the Disconnection
detection flag (Un\G49) turns on (changes to “1”). (2) For wiring of a thermocouple or compensating lead wire, refer to Section 4.4. (3) For troubleshooting of disconnection detection, refer to Section 8.2.7.
OFF
3 - 46
3.4 Buffer Memory
3.4.15 Disconnection detection flag (Un\G49) (Q68TD-G-H02 only)
Page 71
3
SPECIFICATIONS
1
3.4.16 Disconnection state monitor flag (Un\G49) (Q68TD-G-H01only)
Disconnection state is detectable for each channel.
(1) Data storage
(a) The bit of the corresponding channel turns on (changes to “1”) when the
disconnection state of a thermocouple or compensating lead wire is checked.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 is fixed to "0".
Figure 3.33 Storage of Disconnection state monitor flag (Un\G49)
(b) Conversion for the channels not disconnected is continued.
0: Normal 1: Disconnected
(2) How to clear flag
(a) Check the sensor connection state of disconnection detection channels.
(b) When Operating condition setting request (Y9) or Error clear request (YF) is
turned on, this flag will be cleared. When the signal turns on in disconnection state, the bit of the corresponding channel turns on (changes to “1”) again.
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
3.4 Buffer Memory

3.4.16 Disconnection state monitor flag (Un\G49) (Q68TD-G-H01only)

3 - 47
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 72
3
SPECIFICATIONS
(3) Relationship between the Disconnection state monitor flag and
conversion enable/disable setting.
The following table shows the relationship between the Disconnection state monitor flag and conversion enable/disable setting.
Table 3.15 Relationship between conversion enable/disable setting and Disconnection detection flag
Connection state
Conversion enable/disable
setting
Disconnection state
monitor flag
Enable
Disable
Enable ON
Disable OFF
Enable ON
Disable OFF
Without disconnection
With disconnection
Without connection
+
-
+
-
+
-
POINT
(1) Always set “Disable” for any channel where no thermocouple or
compensating lead wire is connected.
If “Enable” is set, the bit of the corresponding channel in Disconnection
detection flag (Un\G49) turns on (changes to “1”). (2) For wiring of a thermocouple or compensating lead wire, refer to Section 4.4. (3) For troubleshooting of disconnection state check, refer to Section 8.2.7.
OFF
3 - 48
3.4 Buffer Memory
3.4.16 Disconnection state monitor flag (Un\G49) (Q68TD-G-H01only)
Page 73
3
SPECIFICATIONS
1
3.4.17 CH[ ] Scaling value (Un\G50 to Un\G57)
The result of scaling measured temperature values is stored.
(1) Data storage
Measured temperature values within the scaling range set in CH Scaling range upper/lower limit values (Un\G62 to Un\G77) are scaled to the scaling width set in
CH Scaling width upper/lower limit values (Un\G78 to Un\G93), and then the result is stored.
(2) How to calculate the scaling value.
The following is how to calculate the scaling value.
Scaling value =
(scaling width upper limit value - scaling width lower limit value)
measured temperature value - scaling range lower limit value
scaling range upper limit value - scaling range lower limit value
Figure 3.34 How to caluculate the scaling value
[Setting example] To scale a temperature to percent (for the use of thermocouple K)
(a) Setting value
• Scaling range: -100 to 500 (lower limit value = -1000, upper limit value = 5000)
• Scaling width: 0 to 100% (lower limit value = 0, upper limit value = 100)
(b) Input value
CH1 measured temperature value: 360 (Measured temperature value = 3600)
Scaling value =
(100 - 0)
3600 - (-1000)
5000 - (-1000)
Figure 3.35 Setting example of scaling value
+ 0 =
76.666666
= 77[%]
Fractional portion is rounded off.
Stores into buffer memory address 50.
+ scaling width lower limit value
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
POINT
(1) If the upper limit value is less than the lower limit value in the settings of CH
Scaling range upper/lower limit values (Un\G62 to Un\G77) or CH Scaling width upper/lower limit values (Un\G78 to Un\G93), it will not result in an error and the scaling value calculated with the expression above will be output.
(2) When the measured temperature is out of the range set in Scaling range
uppr/lower limit values, the value set in Scaling width upper limit value or lower limit value is stored into this buffer memory.
3.4 Buffer Memory

3.4.17 CH[ ] Scaling value (Un\G50 to Un\G57)

3 - 49
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 74
3
SPECIFICATIONS
3.4.18 Scaling valid/invalid setting (Un\G58)
This area is for checking the scaling function valid/invalid status for each channel.
(1) Setting methods
(a) Scaling valid/invalid setting is set for each channel.
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH100000000
Data for b8 to b15 is fixed to "0".
Figure 3.36 Setting of Scaling valid/invalid setting (Un\G58)
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “Invalid” (00FFH).
[Program example]
Program example with a condition of the following is below.
• Scaling range: -100 to 500 (lower limit value = -1000, upper limit value = 5000)
• Scaling width: 0 to 100.0% (lower limit value = 0, upper limit value = 100)
Sets CH1 scaling function to "enable"
Sets CH1 scaling range lower limit value
Sets CH1 scaling range upper limit value
Sets CH1 scaling width lower limit value
Sets CH1 scaling width upper limit value
0: Valid
1: Invalid
3 - 50
Turns ON operating condition seting request (Y9)
Turns OFF operating condition setting request (Y9)
Figure 3.37 Program example of scaling function
3.4 Buffer Memory

3.4.18 Scaling valid/invalid setting (Un\G58)

Page 75
3
SPECIFICATIONS
1
3.4.19 CH[ ] Scaling range upper/lower limit values (Un\G62 to Un\G77)
A scaling range of measured temperature values is set for each channel in units of 0.1 .
(1) Setting methods
(a) For use of the scaling function, change the setting value.
(b) Set the scaling range value in buffer memory.
• Settable scaling range: -32768 to 32767
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "0".
POINT
(1) When the measured temperature is out of the range set in Scaling range
uppr/lower limit values, the value set in Scaling width upper limit value or
lower limit value is stored into CH Scaling value (Un\G50 to Un\G57).
(2) Set “Valid” (“1”) in Scaling valid/invalid setting (Un\G58). When “Invalid” (“0”)
is set in the setting of the Scaling valid/invalid setting (Un\G58), CH Scaling range upper/lower limit values (Un\G62 to Un\G77) is ignored.
(3) If the same value is set for the upper limit and the lower limit, an error (error
code: 91 ) occurs on the corresponding channel. Then, the following occurs.
• Error code (91 ) is stored into Error code (Un\G19). (Refer to Section
8.1).
• Error flag (XF) turns on.
• The module operates with setting before the error occurence.
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
3.4 Buffer Memory

3.4.19 CH[ ] Scaling range upper/lower limit values (Un\G62 to Un\G77)

3 - 51
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 76
3
SPECIFICATIONS
3.4.20 CH[ ] Scaling width upper/lower limit values (Un\G78 to Un\G93)
A width for scaling conversion is set.
(1) Setting methods
(a) For use of the scaling function, change the setting value.
(b) Set the scaling range value in buffer memory.
• Settable scaling range: -32768 to 32767
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "0".
POINT
(1) When “Invalid” (“0”) is set in Scaling valid/invalid setting (Un\G58), the setting
of CH Scaling width upper/lower limit values (Un\G78 to Un\G93) is ignored. (2) If the same value is set for the upper limit and the lower limit, an error (error
code: 91 ) occurs on the corresponding channel. Then, the following occurs.
• Error code (91 ) is stored into Error code (Un\G19). (Refer to Section
8.1).
• Error flag (XF) turns on.
• The module operates with setting before the error occurence.
3 - 52
3.4 Buffer Memory

3.4.20 CH[ ] Scaling width upper/lower limit values (Un\G78 to Un\G93)

Page 77
3
SPECIFICATIONS
3.4.21 CH[ ] Process alarm upper/lower limit values (Un\G94 to Un\G125)
Process alarm upper upper limit value, upper lower limit value, lower upper limit value, and lower lower limit value can be set. (Refer to Section 3.2.4)
(1) Setting methods
(a) A scaling range of measured temperature values is set for each channel in units of
0.1 . Settable range and default value differ according to the thermocouple type. The following table shows settable range and default value for each thermocouple type.
Table 3.16 Process alarm settable range and default value
Default value
Process
Thermocouple
type
Thermocouple K -2000 12000 -2700 to 13700 (-2000 to 12000)
Thermocouple E -2000 9000 -2700 to10000 (-2000 to 9000)
Thermocouple J -400 7500 -2100 to12000 (-400 to 7500)
Thermocouple T -2000 3500 -2700 to 4000 (-2000 to 3500)
Thermocouple B 6000 17000 0 to18200 (6000 to17000)
Thermocouple R 0 16000 -500 to17600 (0 to16000)
Thermocouple S 0 16000 -500 to17600 (0 to16000)
Thermocouple N -2000 12500 -2700 to13000 (-2000 to12500)
alarm lower lower
limit
value
Process
alarm lower upper
limit
value
Process
alarm
upper
lower
limit
value
Process
alarm upper upper
limit
value
Settable temperature range (Accuracy
gurantee range)
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
(b) Turn on Operating condition setting request (Y9) to activate the setting.
POINT
(1) If any of the following values are set, an error (error code: 6 ) occurs.
Then, Error flag (XF) turns on.
• A value out of the above settable range:
• A value that does not satisfy the following condition:
Process alarm lower lower limit value lower upper limit value upper lower limit value
upper upper limit value
(2) When “Disable” (“0”) is set in the Warning output enable/disable setting
(Un\G46), the setting of CH Process alarm upper/lower limit values (Un\G94 to Un\G125) is ignored.
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
3.4 Buffer Memory

3.4.21 CH[ ] Process alarm upper/lower limit values (Un\G94 to Un\G125)

TROUBLESHOOTING
3 - 53
Page 78
3
SPECIFICATIONS
3.4.22 CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133)
The number of conversion periods to check a change in measured temperature values is set for each channel. (Refer to Section 3.2.4)
(1) Setting methods
(a) For use of the rate alarm, change the setting value.
(b) Set the number of conversion periods in buffer memory.
• Settable range: 1 to 6000(times)
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “0”.
POINT
(1) When a value out of the above setting range is set, an error (error code: 70 )
occurs on the corresponding channel. Then, the following occurs.
• Error code (71 ) is stored into the Error code (Un\G19). (Refer to Section
8.1).
• Error flag (XF) turns on.
• The module operates with setting before the error occurence.
(2) Set “Enable” in Warning output enable/disable (Un\G46). When “Disable” is
set, the settings of CH Rate alarm warning detection period (Un\G126 to Un\G133) is ignored.

3.4.23 CH[ ] Rate alarm upper/lower limit values (Un\G134 to Un\G149)

A scaling range of measured temperature values is set for each channel in units of
0.1 .(Refer to Section 3.2.4)
(1) Setting methods
(a) For use of the rate alarm, change the setting value.
(b) Set the range in buffer memory.
• Settable range:-32768 to 32767
(c) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to "0".
3 - 54
3.4 Buffer Memory

3.4.22 CH[ ] Rate alarm warning detection period (Un\G126 to Un\G133)

Page 79
3
SPECIFICATIONS
3.4.24 Mode switching setting (Un\G158, Un\G159)
This area is used to switch the mode between normal mode and offset/gain setting mode. This mode can be switched without resetting the programmable controller CPU.
Setting methods
(a) Set the setting value of the switching target mode.
Table 3.17 Switching target mode and setting value
Switching target mode
Normal mode 0964H 4144H
Offset/gain setting value mode 4144H 0964H
(b) To switch the mode, turning on Operating condition setting request (Y9) after
setting the value is required.
Un\G158 Un\G159
Setting value
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(c) When the mode is switched completely, this area for Un\G158 and Un\G159 is
cleared to “0”.
POINT
If a value other than the setting values in Table 3.17 is written, mode switching is not performed.
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
3.4 Buffer Memory

3.4.24 Mode switching setting (Un\G158, Un\G159)

3 - 55
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 80
3
SPECIFICATIONS
3.4.25 Conversion setting for disconnection detection (Un\G164,
When disconnection is detected, a value stored into CH Measured temperature value (Un\G11toUn\G18) is set. (Refer to Section 3.2.2) The value to be stored is selected from “Up scale”, “Down scale” or “Given value”.
(1) Setting methods
Un\G164 (Conversion setting for disconnection detection CH1-4)
Un\G165) (Q68TD-G-H02 only)
(a) Set the value to be stored into buffer memory.
b15 b12 b11 b8 b7 b4 b3 b0
to
CH4 CH3 CH2 CH1
to
to
to
Un\G165 (Conversion setting for disconnection detection CH5-8)
Figure 3.38 Setting of Conversion setting for disconnection detection (Un\G164, Un\G165)
The value to be stored into CH Measured temperature value (Un\G11toUn\G18) changes as follows, depending on the setting value.
1) Up scale (0
2) Down scale (1
3) Given value (2
CH8 CH7 CH6 CH5
Measured temperature value at the time of disconnection detection
Up scale
Down scale Given value
H)
Setting value
0
H
1
H
2
H
Up-scale of the range currently set is stored.
H)
Down-scale of the range currently set is stored.
H)
The value set in CH Conversion setting value for disconnection detection (Un\G166toUn\G173) is stored.
3 - 56
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “Down scale” (1111H).
POINT
If a value out of the setting range is set, the module operates with the default setting, “Down scale”(1
3.4 Buffer Memory

3.4.25 Conversion setting for disconnection detection (Un\G164, Un\G165) (Q68TD-G-H02 only)

H).
Page 81
3
SPECIFICATIONS
1
3.4.26 Disconnection state conversion setting (Un\G164, Un\G165) (Q68TD-G-H01only)
When disconnection state is checked, a value stored into CH Measured temperature value (Un\G11toUn\G18) is set. (Refer to Section 3.2.3) The value to be stored is selected from “Up scale”, “Down scale” or “Given value”.
(1) Setting methods
(a) Set the value to be stored in buffer memory.
Un\G164 (Disconnection state conversion setting CH1 to CH4)
Un\G165 (Disconnection state conversion setting CH5 to CH8)
Figure 3.39 Setting of Disconnection state conversion setting (Un\G164, Un\G165)
The value to be stored into CH Measured temperature value (Un\G11toUn\G18) in the disconnection state check changes as follows, depending on the setting value.
b15 b12 b11 b8 b7 b4 b3 b0
to
CH4 CH3 CH2 CH1
CH8 CH7 CH6 CH5
to
Measured temperature value when confirming disconnection state
to
Up scale Down scale Given value
to
Setting value
0
H
1
H
2
H
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
1) Up scale (0
H)
Up-scale of the range currently set is stored.
2) Down scale (1
H)
Down-scale of the range currently set is stored.
3) Given value (2
H)
The value set in CH Conversion setting for disconnection state value (Un\G166toUn\G173) is stored.
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “Down scale” (1111H).
POINT
If a value out of the setting range is set, the module operates with the default setting, “Down scale”(1H).
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
3.4 Buffer Memory

3.4.26 Disconnection state conversion setting (Un\G164, Un\G165) (Q68TD-G-H01only)

TROUBLESHOOTING
3 - 57
Page 82
3
SPECIFICATIONS

3.4.27 CH[ ] Conversion setting value for disconnection detection (Un\G166 to Un\G173) (Q68TD-G-H02 only)

When “Give value” (2H) is set in Conversion setting for disconnection detection
(Un\G164,Un\G165), the value to be stored into CH Measured temperature value (Un\G11toUn\G18) can be set by user. (Refer to Section 3.2.2)
(1) Setting methods
(a) Set the value to be stored in buffer memory in units of 0.1 .
• Settable range:-32768 to 32767
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to “0”.
[Setting example] When the value of 800 is stored into CH1 Measured temperature value for disconnection detection.
1) Set the following in buffer memory.
• Conversion setting for disconnection detection (Un\G164):2
• CH1 Conversion setting value for disconnection detection(Un\G166):8000
2) Turn on Operating condition setting request (Y9).

3.4.28 CH[ ] Conversion setting value for disconnection state (Un\G166 to Un\G173) (Q68TD-G-H01only)

When “Give value” (2H) is set in the Disconnection state conversion setting
(Un\G164,Un\G165), the value to be stored into CH Measured temperature value (Un\G11toUn\G18) can be set by user in the disconnection state check. (Refer to Section
3.2.3)
(1) Setting methods
(a) Set the valuetobe stored in buffer memory in units of 0.1 .
• Settable range:-32768 to 32767
(b) Turn on Operating condition setting request (Y9) to activate the setting.
(2) Default value
All channels are set to“0”.
H
3 - 58
[Setting example] When the value of 800 is stored into CH1 Measured temperature value for the check of disconnection state
1) Set the following in buffer memory.
• Disconnection state conversion setting (Un\G164):2
• CH1 Conversion setting value for disconnection state (Un\G166):8000
2) Turn on Operating condition setting request (Y9) to activate the setting.
3.4 Buffer Memory
3.4.27 CH[ ] Conversion setting value for disconnection detection (Un\G166 to Un\G173) (Q68TD-G-H02
H
Page 83
3
SPECIFICATIONS
3.4.29 Factory default offset/gain values, User range settings offset/gain values (Un\G190 to Un\G253)
This area is used to reset the offset/gain easily at online module change. (Refer to CHAPTER 7)
(1) Purpose of this buffer memory
(a) When the offset/gain setting values of the user range setting are restored, the
data to be used are stored. The data are stored (saved) in the following cases.
• When writing default setting by the utility
• When setting the operating condition (Y9 turns from off to on
• When writing the offset/gain values in the offset/gain setting mode (YA turns from off to on)
* 1 The data are not saved when a setting value has been written in the Mode switching setting
(Un\G158,Un\G159).
*1
)
1
2
3
OVERVIEW
SYSTEM
CONFIGURATION
(b) To restore the offset/gain values of the user range setting, set the data saved in
this area to the corresponding area of the restoring target module.
(2) How to save data during online module change
Save buffer memory data during online module change in the following procedure.
1) Turn on Operating condition setting request (Y9).
2) Compare the values of the Factory default offset/gain values, the User range settings offset/gain values, and the User range settings resistance offset/gain values (Un\G190 to Un\G253) to the values in the range reference table. (Refer to Section 7.4)
3) When the values are appropriate, take down the buffer memory data compared.
POINT
This area is not used for offset/gain setting. For offset/gain setting, refer to Section 4.6.
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
3.4 Buffer Memory

3.4.29 Factory default offset/gain values, User range settings offset/gain values (Un\G190 to Un\G253)

3 - 59
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 84
4
SETUP AND PROCEDURES BEFORE OPERATION
CHAPTER4 SETUP AND PROCEDURES BEFORE
OPERATION
4.1 Handling Precautions
(1) Do not drop or give a strong impact to the case.
(2) Do not remove the printed-circuit board of the module from the case.
Doing so may cause a failure.
(3) Be careful to prevent foreign matters such as cutting chips or wire chips
from entering the module. Failure to do so may cause a fire, failure or malfunction.
(4) A protective film is attached to the module top to prevent foreign matter
such as wire chips from entering the module during wiring. Do not remove the film during wiring. Be sure to remove it for heat dissipation before system operation.
(5) Tighten the screws such as module fixing screws within the following
ranges. Undertigtening can cause drop of the screw, short circuit or malfunction.
Table 4.1 Tightening torque
Screw location Tightening torque range
Module fixing screw (M3 screw)
Connector screw (M2.6 screw) 0.20 to 0.29N•m
* 1 The module can be easily fixed onto the base unit using the hook at the top of the module.
When using the Q68TD-G-H02(H01) in an environment of frequent vibrations, fix the module with a module fixing screw.
(6) When mounting the module to the base unit, insert the module fixing
projection into the fixing hole in the base unit, and mount the module with using the hole as a supporting point. Incorrect module mounting may cause a malfunction, failure, or drop of the module. After mounting the module to the base unit, fix the module with a module fixing bracket. (Q68TD-G-H02 only) (Refer to Section 4.1.1) When using the Q68TD-G-H01 in an environment of frequent vibrations, fix the module with a module fixing screw. (Q68TD-G-H01 only)
*1
0.36 to 0.48N•m
4 - 1
(7) Always make sure to touch the grounded metal to discharge the
electricity charged in the body, etc., before touching the module. Failure to do so may cause a failure or malfunctions of the module.

4.1 Handling Precautions

Page 85
4
SETUP AND PROCEDURES BEFORE OPERATION
4.1.1 Fixing module with module fixing bracket (Q68TD-G-H02 only)
After mounting the Q68TD-G-H02 to the base unit, fix the Q68TD-G-H02 module with a module fixing bracket.
POINT
Make sure that the module fixing bracket is hooked on the third slit viewed from the front of the Q68TD-G-H02. Then, tighten the module fixing screw within the specified torque range.
1
OVERVIEW
2
Module fixing bracket
Module fixing screw
Q68TD-G-H02
Figure 4.1 Fixing module with module fixing bracket
3rd slit
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
4.1 Handling Precautions

4.1.1 Fixing module with module fixing bracket (Q68TD-G-H02 only)

4 - 2
7
8
ONLINE MODULE
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 86
4
SETUP AND PROCEDURES BEFORE OPERATION
4.2 Setup and Procedures before Operation
Start
Module mounting Mount the Q68TD-G-H02(H01) in the specified slot.
Wiring
Wire the thermocouple and cold junction temperature compensation resistor to the Q68TD-G-H02(H01). If the terminal block is used, connect the thermocouple and cold junction temperature compensation resistor to it. Then wire the terminal block to the Q68TD-G-H02(H01).
Intelligent function module switch settings Perform settings using GX Developer.
Use user range settings?
Use user range settings
Offset/gain setting If user range settings are used, perform the offset and gain settings.
Use the utility package?
YES
Initial setting and automatic refresh setting
The program can be simplified if the utility package is used for setting.
Programming and debugging Create and check the sequence program.
Figure 4.2 Procedures and setting before system operation
(Refer to CHAPTER 5).
Use factory default settings
NO
4 - 3

4.2 Setup and Procedures before Operation

Page 87
4
r
r
SETUP AND PROCEDURES BEFORE OPERATION
4.3 Part Names
The following explains the part names of the Q68TD-G-H02(H01). The part names and signal names of the Q68TD-G-H02 and Q68TD-G-H01 are same.
(1) Q68TD-G-H02
1
OVERVIEW
2
Module fixing screw
(2) Q68TD-G-H01
Module fixing bracket
1)
2)
(Connector
terminal
number)
A1
A20
(Connecto
terminal
number)
B1
B20
3)
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
2)
(Connector
terminal
number)
A1
A20

4.3 Part Names

3)1)
(Connecto
terminal
number)
B1
B20
4 - 4
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE
TROUBLESHOOTING
Page 88
4
SETUP AND PROCEDURES BEFORE OPERATION
Table 4.2 Part names
Number Name Description
Displays the operating status of the Q68TD-G-H02(H01).
On : Normal operation
1) RUN LED
2) ERR. LED
3) ALM LED
Flashing : During offset/gain setting mode
Off :
5V power supply interrupted, watchdog timer error occurred, or online module
change enabled.
Displays the error status of the Q68TD-G-H02(H01).
On : Error
Flashing : Error in switch settings
Switch No. 5 of the intelligent function module has been set to a value other
than zero.
Off : Normal operation
Displays the warning status of the Q68TD-G-H02(H01).
On : Warning (process alarm, rate alarm) occurring (Refer to Section 3.4.13)
Flashing :
Disconnection detected (Q68TD-G-H02)
Checking a disconnection status (Q68TD-G-H01)
Off : Normal operation
A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20
Seen from the front
of the module
B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16 B17 B18 B19 B20
Figure 4.3 Terminal
number
Table 4.3 Signal name
Term in al
number
Signal name
Terminal
number
Signal name
A1 CH1+ B1 CH1-
A2 --- B2 ---
A3 CH2+ B3 CH2-
A4 --- B4 ---
A5 CH3+ B5 CH3-
A6 --- B6 ---
A7 CH4+ B7 CH4-
A8 --- B8 ---
A9 CH5+ B9 CH5-
A10 --- B10 ---
A11 CH6+ B11 CH6-
A12 --- B12 ---
A13 CH7+ B13 CH7-
A14 --- B14 ---
A15 CH8+ B15 CH8-
A16 --- B16 ---
A17 --- B17 ---
A18 --- B18 ---
A19 --- B19 RTD+
A20 RTDG B20 RTD-
4 - 5
* For actual wiring, refer to Section 4.4.2 External Wiring.
4.3 Part Names
Page 89
4
SETUP AND PROCEDURES BEFORE OPERATION
4.4 Wiring
1
The following explains the wiring precautions and module connection example.
4.4.1 Wiring precautions
External wiring that is less susceptible to noise is required as a condition of enabling a highly reliable system and making full use of the capabilities of the Q68TD-G-H02(H01).
(1) Use separate cables for the AC control circuit and the external input
signals of the Q68TD-G-H02(H01) to avoid the influence of the AC side surges and inductions.
(2) Always place the thermocouple at least 100mm away from the main
circuit cables and AC control circuit lines. Fully keep it away from high­voltage cables and circuits, which include high frequency waves, such as an inverter's load circuit. Not doing so will cause the module more susceptible to noises, surges and inductions.
(3) The following wiring is required for the product to comply with the EMC
and Low Voltage Directives.
Q68TD-G-H02(H01)
A6CON4
In a control panel
AD75CK
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
Relay terminal block
20(7.87) to 30cm
(11.81 inch)
Figure 4.4 Wiring complying with EMC and LOW Voltage Directives
(a) Use shielded cables for every external wiring and use the AD75CK cable clamp to
ground to the panel. AD75CK can ground four cables together when using cables
with outer diameter of about 7mm.
(b) For wiring between A6CON4 and a relay terminal block, use shielded cables to
ground to the panel. In addition, keep the wiring distance within 3m.
(c) Before touching the relay terminal block, always touch the grounded metal to
discharge the electricity charged in the body.
Strip off the outer sheath
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE

4.4 Wiring

4.4.1 Wiring precautions

TROUBLESHOOTING
4 - 6
Page 90
4
SETUP AND PROCEDURES BEFORE OPERATION
4.4.2 External wiring
(1) Wiring procedure
1) Install a relay terminal block for wiring.
2) Connect the thermocouple and the compensation conductors to the relay terminal block.
3) When setting the Q68TD-G-H02(H01) to "With cold junction temperature compensation", connect the cold junction temperature compensation resistor (RTD), which is supplied with Q68TD-G-H02(H01), to the relay terminal block.
4) Use A6CON4 to wire between the relay terminal block and Q68TD-G­H02(H01).
Q68TD-G-H02(-H01)
Compensation
conductors
(*2)
RTD
(*3)
(*4)
Relay
terminal block
CH1
+
­Cable(*1)
CH8
+
-
RTD
+
-
G
Figure 4.5 Wiring example using relay terminal block
*1 Always use shielded cabled. In addition, always ground the shield. *2 Always use shielded compensation conductors. In addition always ground the shield. *3 When setting the Q68TD-G-H02(H01) to "With cold junction temperature compensation", always connect the cold junction temperature compensation resistor (RTD). *4 When connecting the RTD, always connect the terminals between RTD- and RTD G.
Connector (A6CON4)
CH1
+
-
CH8
+
-
RTD
+
-
G
A1
B1
A15
B15
B19
B20
A20
Modulator
Modulator
Filter
Demodulator
Demodulator
Input amplifer
4 - 7
4.4 Wiring

4.4.2 External wiring

Page 91
4
SETUP AND PROCEDURES BEFORE OPERATION
4.5 Switch Setting for Intelligent Function Module
The settings for the intelligent function module are performed using the I/O assignment settings for GX Developer.
(1) Setting item
Intelligent function module switch has switches 1 to 5.The setting is executed with 16­bit data. When not setting the intelligent function module switch, the default of switches 1 to 5 is 0.
Table 4.4 Intelligent Function Module Switch Settings
Setting Item
Switch 1
Switch 2
Thermocouple type
settings
(CH1 to CH4)
H
CH4 CH3 CH2 CH1
Thermocouple type
settings
(CH5 to CH8)
H
CH8 CH7 CH6 CH5
Thermocouple type Setting value
Thermocouple K 0
Thermocouple E 1
Thermocouple J 2
Thermocouple T 3
Thermocouple B 4
Thermocouple R 5
Thermocouple S 6
Thermocouple N 7
Setting a value other than 0 to 7 results in a range
setting error (error code: 10 ) and the measured
temperature is not converted. ( indicates the error
corresponding channel number.)
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
Switch 3
Switch 4
Switch 5
Offset/gain setting mode
00
Fixed to 0
H
H
b7 b6 b5 b4 b3 b2 b1 b0
CH8 CH7 CH6 CH5CH4 CH3 CH2 CH1
0: Factory default setting 1: User range setting
Mode setting, Cold junction compensation setting
00
H
Fixed to 0
H
0
: With cold junction temperature compensation
1 to FH*1
: Without cold junction temperature compensation
0
: Normal mode
H
1 to FH*1
: offset/gain setting mode
0 : Fixed *2
* 1 Setting any value within the setting range will provide the same operation.
When the setting range is 1 to FH, set 1 for example.
* 2 Setting a value other than "0" results in an error.
6
7
8
UTILITY PACKAGE (GX
ONLINE MODULE
CONFIGURATOR-TI)
PROGRAMMING
CHANGE

4.5 Switch Setting for Intelligent Function Module

TROUBLESHOOTING
4 - 8
Page 92
4
SETUP AND PROCEDURES BEFORE OPERATION
(2) Operating procedure
Start the settings with GX Developer assignment setting screen.
(a) I/O assignment setting screen
Set the following for the slot in which the Q68TD-G-H02(H01) is mounted. The type setting is required; set other items as needed. Type : Select "intelli." Model name : Enter the module model name. Points : Select 16 points. Start XY : Enter the start I/O number for the Q68TD-G-H02(H01). Detail setting: Specify the control PLC for the Q68TD-G-H02(H01). It is unnecessary to set the "Error time output mode" or "H/W error time PLC operation mode" since these settings are invalid for the Q68TD-G-H02(H01).
Figure 4.6 I/O assignment tab
(b) Switch setting for intelligent function module screen
Click on [Switch setting] on the I/O assignment setting screen to display the screen shown at left, then set switches 1 to 5. The switches can easily be set if values are entered in hexadecimal. Change the entry format to hexadecimal and then enter the values.
Figure 4.7 Switch setting for intelligent function module screen
4 - 9
4.5 Switch Setting for Intelligent Function Module
Page 93
4
SETUP AND PROCEDURES BEFORE OPERATION
4.6 Offset/Gain Setting
Execute offset/gain settings in the following procedure. When the factory shipped setting is used, offset/gain setting is not necessary. If the utility package is installed, execute the offset/gain setting according to the procedure in Section 5.6.2.
(1) Setting procedure
With the intelligent function module swich setting, set the input type setting value to a type for executing error compensation. In the cold junction temperature compensation setting, set it to "with cold junction temperature compensation". *1
2)
Switch to the offset/gain setting mode. *2
Check that "RUN" LED is flashing to indicate the offset/gain setting mode.
1)
Set the conversion enable/disable setting (Un\G0) of the channel for executing the offset/gain setting to "enable" and turnY9 from ON to OFF. *3
Check the disconnection detection flag (Un\G49) (Q68TD-G-H02 only) or disconnection state monitor flag (Un\G49) (Q68TD-G-H01 only), and identify the channel for the disconnection. Then review the wiring of the channel and turn YF from ON to OFF.
YES
Enter the value, to be used as a offset value in the termocouple or standard DC voltage generator, to channel for adjusting.
START
Is the disconnection
detection signal (XC)
(Q68TD-G-H02 only) or disconnection
state monitor signal (XC)
(Q68TD-G-H01 only)
ON?
NO
Set the gain setting channel in the offset/gain setting mode (Gain specification)(Un\G27). Set the offset/gain setting mode (Offset specification)(Un\G26) to "0".
Write the temperature setting value (digital) equivalent to the analog input value to the CH gain temperature setting value (Un\G29)*4 of the channel to be adjusted.
Turn ON the channel change request (YB).
Confirm that the channel change completion flag (XB) is turned ON.
Turn OFF the channel change request (YB).
Do you want to adjust other channels?
YES
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
1)
Set the offset setting channel in the offset/gain setting mode (Offset specification)(Un\G26). Set the offset/gain setting mode (Gain specification) (Un\G27) to "0".
Write the temperature setting value (digital) equivalent to the analog input value to the CH offset temperature setting value (Un\G28)*4 of the channel to be adjusted.
Turn ON the channel change request (YB).
Confirm that the channel change completion flag (XB) is turned ON.
Turn OFF the channel change request (YB).
Enter the value, to be used as gain value in the termocouple or standard DC voltage generator, to channel for adjusting.
Turn ON the user range write request (YA).
Confirm that the offset/gain setting mode status flag (XA) is turned OFF.
Turn OFF the user range write request (YA).
Switch to normal mode.
Figure 4.8 Setting procedure for offset/gain setting

4.6 Offset/Gain Setting

NO
Is the "ERR." LED on?
NO
FINISH
YES
4 - 10
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
2)
7
ONLINE MODULE
CHANGE
8
TROUBLESHOOTING
Page 94
4
SETUP AND PROCEDURES BEFORE OPERATION
* 1 When inputting a value using such as a standard DC voltage generator, or using without cold
junction temperature compensation on actual use, set it to "without cold junction compensation".
* 2 The mode switching (normal mode to offset/gain setting mode to normal mode) method is indicated
below.
Table 4.5 Mode switching method
Mode switching method Refer to
Dedicated instruction (G(P).OFFGAN)
Setting the mode switching setting (Un\G158, Un\G159) and turning from
OFF to ON the operating condition setting request (Y9).
Intelligent function module switch setting
(After setting the intelligent function module switch, reset or turn from OFF
to ON the programmabel controller CPU.)
* 3 For the conversion enable/disable setting of unused channels or channels not executing the offset/
gain setting, always set it to "disable". If all channels are set to "Enable", Disconnection detection flag (Disconnection state monitor flag) (Un\G49) of channels that are not connecting a thermocouple turns on (changes to "1")
* 4 Buffer memory address of channel 1 only is indicated in the chart. For buffer memory address of
other channels, refer to Section 3.4.1 Buffer memory assignment.
(2)(a) in this
section
(2)(b) in this
section
Section 4.5,
(2)(c) in this
section
4 - 11
4.6 Offset/Gain Setting
Page 95
4
SETUP AND PROCEDURES BEFORE OPERATION
POINT
(1) Execute the offset/gain settings in the actual operating status. (2) Offset value and gain value are stored in the Flash memory of the Q68TD-G-
H02(H01) by turning ON the user range write request (YA), and the values are not erased at power-off. To prevent unnecessary write to Flash memory, an error (error code 162) occures if writing is performed 26 times continuously.
(3) Execute the offset/gain setting within the measured temperature guarantee
range (refer to shaded area of Section 3.1 (2) Table 3.2). If the setting exceeds the measrued temperature guarantee range, resolution and accuracy may not be within the ranges of the performance specifications.
(4) Set the offset and gain values within the ranges where the following
conditions are satisfied.
(Gain value) - (offset value) > 0.1[ ] Set the offset temperature setting value and gain temperature setting value within the range where the following conditions are satisfied.
(Gain temperarure setting value) - (offset temperature setting value) > 0.1[ ]
(5) When the user range write request (YA) is turned ON, consistency check for
offset value and gain value, and offset temperature setting value and gain temperature setting value is executed. If an error occurs on any channel, offset/gain values are not written to the module. Check the value of error code (Un\G19) and take an appropriate measure. Then, execute offset/gaing setting again.
(6) Offset/gain setting can be exectued on multiple channels at the same time;
however, set the offset and gain separately. Setting the offset and gain for channels at the same time results in an error, and the [ERR.] LED turns on.
(7) It takes approximately seven seconds from when Channel change request
(YB) turns on till when Channel change completion flag (XB) turns on. During this period, input to channels targeted for offset/gain setting must be constant. In addition, if disconnection is detected or checked during this period, Channel change completion flag (XB) turns on earlier and an error (error
code: 51 ) occurs simultaneously. If this occurs, perform offset/gain setting again after connection is restored.
(8) If an error (error code: 51 ) described at (7) occurs while performing offset/
gain setting simultaneously on multiple channels, values are not set only for the channel of which disconnection is detected or checked but also normally­connected channels. Therefore, perform offset/gain setting again for all adjusting target channels after connection is restored.
(9) The Module ready (X0) turns from OFF to ON when the offset/gain setting
mode is switched to the normal mode by the setting of the dedicated instruction (G(P).OFFGAN) or mode switch settings (Un\G158, Un\G159). Note that initial setting processing will be executed if there is a sequence program that will execute initial setting when the Module ready (X0) turns ON.
(10)Warm-up (power distribution) period of 30 minutes is required to satisfy with
accuracy before the offset/gain setting is performed.
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
4.6 Offset/Gain Setting
TROUBLESHOOTING
4 - 12
Page 96
4
SETUP AND PROCEDURES BEFORE OPERATION
(2) Program examples
(a) The program in dotted area of (a) is common to (a),(b) and (c). In this example, the I/O numbers for the Q68TD-G-H02(H01) are X/Y0 to X/YF.
Table 4.6 List of devices
Device Function
M0 Mode switching
M1 Channel selection
M2 Channel conversion enabling
M3 Offset setting
M4 Gain setting
M5 Channel change instruction
M6 Offset/gain setting value write command to module
M50 Switching to the offset/gain setting mode
M51 Switching to the normal mode
D0 Dedicated instruction (G(P).OFFGAN) setting value storage device
D1
D2
D3 Offset temperature setting value storage device
D4 Gain temperature setting value storage device
Channel specification storage device
4 - 13
4.6 Offset/Gain Setting
Page 97
4
SETUP AND PROCEDURES BEFORE OPERATION
(a) When switching the mode using dedicated instruction (G(P).OFFGAN)
The following program example is for switching to the offset/gain setting mode with the dedicated instruction (G(P).OFFGAN) and changing the channel for the offset/gain setting, then writing the offset/gain values to the Q68TD-G-H02(H01) and then switching to the normal mode.
1
OVERVIEW
2
*1
Dedicated instruction (G.OFFGAN)
Stores offset/gain setting target channel.
Copies data of D1 into D2.
Inverts bit for conversion enable/disable setting.
Sets conversion enable/disable.
Turns ON Operating condition setting request (Y9).
Turns OFF Operating condition setting request (Y9).
Stores offset temperature setting value into D3.
Writes value to Offset temperature setting value.
Specifies offset setting channel.
Sets "0" for gain setting channel.
Stores gain temperature setting value into D4.
Writes value to Gain temperature setting value.
Sets "0" for offset setting channel.
Specifies gain setting channel.
Turns ON Channel change request (YB).
Turns OFF Channel change request (YB).
Turns ON User range write request (YA).
Turns OFF User range write request (YA).
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
Processing in normal mode
Figure 4.9 When switching the mode using dedicated instruction (G(P).OFFGAN)
* 1 The program in the dotted area is a common program.
4.6 Offset/Gain Setting
4 - 14
8
ONLINE MODULE
CHANGE
TROUBLESHOOTING
Page 98
4
SETUP AND PROCEDURES BEFORE OPERATION
(b) When switching the mode using the the mode switching setting (Un\G158,
Un\G159) and the operating condition setting request (Y9)
Stores "H4144" in Un\G1
Stores "H0964" in Un\G1
Common program
Stores "H0964" in Un\G1
Stores "H4144" in Un\G1
Processing in normal mode
Figure 4.10 When switching the mode using the setting in the Mode switching setting (Un\G158,Un\G159) and Operating condition
setting request (Y9)
(c) When switching the mode by making intelligent function module switch setting
Only the common program is necessary.
4 - 15
4.6 Offset/Gain Setting
Page 99
4
SETUP AND PROCEDURES BEFORE OPERATION
4.7 Cold Junction Temperature Compensation with/without Setting
The Q68TD-G-H02(H01) can execute the following two different cold junction temperature compensations by setting the inteligent function module switch setting (switch 4) to whether to carry out the cold junction temperature compensation using the cold junction temperature compensation resistor (RTD) or not.
(1) Executing cold junction temperature compensation with the cold
junction temperature compensation resistor (RTD) (set to "with cold junction temperature compensation")
Cold junction temperature compensation is possible by connecting the supplied cold junction temperature compensation resistor (RTD) and setting it to "with cold junction temperature compensation". Always connect the supplied cold junction temperature compensation resistor (RTD) to the terminal block. (For connection, refer to Section 4.4.2.)
Q68TD-G-H02(H01)
Terminal block
RTD
Compensation conductor
Object whose temperature is to be measured
Thermocouple
1
2
3
4
OVERVIEW
SYSTEM
CONFIGURATION
SPECIFICATIONS
Figure 4.11 Connection between a cold junction compensation resistor (RTD) and a relay terminal block
(2) Executing cold junction temperatuer compensation externally (set to
"without cold junction temperature compensation")
Use this function to measure temperatures at high accuracy when the cold junction temperature compensation accuracy ( 1 ) of supplied cold junction temperature compensation resistor (RTD) cannot be taken as a margin of error. Connecting a cold junction temperature compensation resistor (RTD) to the terminal block is unnecessary.
By providing a precision ice bath externally, the thermoelectromotive force generated at the tip of the thermocouple can be led to this module without any change, improving the cold junction temperature compensation accuracy.
Q68TD-G-H02(H01)
Terminal block
Conductor
Compensation conductor
Object whose temperature is to be measured
Thermocouple
SETUP AND
PROCEDURES BEFORE
OPERATION
5
UTILITY PACKAGE (GX
CONFIGURATOR-TI)
6
PROGRAMMING
7
ONLINE MODULE
CHANGE
8
Ice bath
Figure 4.12 Connection between an ice bath and a relay terminal block

4.7 Cold Junction Temperature Compensation with/without Setting

TROUBLESHOOTING
4 - 16
Page 100
4
SETUP AND PROCEDURES BEFORE OPERATION
POINT
The ice bath is designed to connect the thermocouple/compensation conductor and conductor in the pot whose internal temperature is controlled to be 0 . Hence, the thermoelectromotive force at the contact portion of the thermocouple/ compensation conductor and conductor will be 0mV, preventing the generation of extra thermoelectromotive force which can cause errors.
4 - 17
4.7 Cold Junction Temperature Compensation with/without Setting
Loading...