Mitsubishi SUZ-KA35VA4, SUZ-KA71VA4, SUZ-KA50VA4, SUZ-KA60VA4, SUZ-KA25VA4.TH Service Manual

...
Page 1
TECHNICAL & SERVICE MANUAL
No.OCH545
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
R410A
Outdoor unit [Model Name]
[Service Ref.]
CONTENTS
1.
COMBINATION OF INDOOR AND OUTDOOR UNITS
.....
2
2. TECHNICAL CHANGES
...................................
3
3. PARTS NAMES AND FUNCTIONS
..................
7
4. SPECIFICATION
................................................
8
5. NOISE CRITERIA CURVES
............................
10
6. OUTLINES AND DIMENSIONS
.......................
11
7. WIRING DIAGRAM
..........................................
13
8. REFRIGERANT SYSTEM DIAGRAM
.............
16
9. ACTUA TOR CONTROL
...................................
19
10. SERVICE FUNCTIONS
....................................
20
11. TROUBLESHOOTING
.....................................
20
12. DISASSEMBLY INSTRUCTIONS
....................
36
Indication of model name
Note:
• This service manual describes technical data of the outdoor units.
HFC
utilized
R410A
SUZ-KA25VA4.TH SUZ-KA35VA4.TH
August 2013
PARTS CATALOG (OCB545)
Page 2
2
1
COMBINATION OF INDOOR AND OUTDOOR UNITS
Heat pump type
Outdoor unit
SUZ-
SLZ-KA25VAL2.TH SLZ-KA35VALR3.TH SLZ-KA50VALR3.TH SLZ-KA25VAQ2.TH SLZ-KA35VAQR2.TH SLZ-KA50VAQR2.TH SEZ-KD25VA(L)R2.TH SEZ-KD35VA(L)R2.TH SEZ-KD50VA(L)R2.TH SEZ-KD60VA(L)R2.TH SEZ-KD71VA(L)R2.TH SEZ-KD25VAQR2.TH SEZ-KD35VAQR2.TH SEZ-KD50VAQR2.TH SEZ-KD60VAQR2.TH SEZ-KD71VAQR2.TH
— —
— —
— — — —
— — — —
— —
— —
— — — —
— — —
— —
— —
— —
— — — —
— —
— — — — — — — — —
— — — —
— — — — — — — — — —
— — — —
OC320
OCH493
Indoor unit
Service
Manual No.
Service Ref.
Heat pump without electric heater
KA25V A4.TH
KA60VA4.TH KA71A4.THKA50VA4.TH
HWE0711
BWE102050
BWE102040
HWE1008
KA35V A4.TH
Note: Please refer to the service manual of indoor unit or the technical data book for the combination data.
INDOOR UNIT SERVICE MANUAL
OCH545
Page 3
3
2
TECHNICAL CHANGES
Refrigerant
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
None None
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
None
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (°C) Steam pressure [25°C](Mpa) Saturated steam density [25°C](Kg/*) Combustibility ODP *1 GWP *2 Refrigerant charge method Additional charge on leakage Kind Color Smell
*1: Ozone Depletion Potential : based on CFC-11 *2: Global Warming Potential : based on CO
2
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners.
As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/materi-
als are required. Refer to the table below.
Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installa-
tion, since it is more susceptible to contaminations than R22.
For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm
2
[Gauge])
New Specification Current Specification
The incompatible refrigerant oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerant oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerant oil are compatible with each other, refrigerant oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerant oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerant oil /Refrigerant
Compressor
OCH545
Page 4
4
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool.
Provided for flaring work (to be used with R22 flare tool). Provided to prevent the back flow of oil. This adapter enables you to use
vacuum pumps. It is difficult to measure R410A with a charging cylinder because the
refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Flare gauge Vacuum pump
adapter
Electronic scale for refrigerant charging
No: Not substitutable for R410A Yes: Substitutable for R410A
No 12.7 mm and 15.88 mm
1. Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
()
NOTE: The unit of pressure has been changed to MPa on the
international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm2 [Gauge])
OCH545
Page 5
5
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe
Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter (mm)
6.35
9.52
12.7
15.88
17 22 26 29
Dimension of flare nut (mm)
R22
17 22 24 27
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.
Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
3. Refrigerant oil
Apply the special refrigerant oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4. Air purge
Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.
Use the vacuum pump for air purging for the purpose of environmental protection.
5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and
the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
2. Refrigerant piping
Specifications
Use the refrigerant pipes that meet the following specifications.
Wall thicknessOutside diameter
Pipe
mm mm
For liquid
For gas
6.35
9.52
9.52
12.7
15.88
0.8
0.8
0.8
0.8
1.0
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
OCH545
Page 6
6
6. Pumping Down
When relocating or disposing of the air conditioner, pump down the system by following the procedure below so that no refrigerant is released into the atmosphere.
1 Turn off the power supply (circuit breaker). 2 Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit. 3 Fully close the stop valve on the liquid pipe side of the outdoor unit. 4 Supply power (circuit breaker). 5 Perform the refrigerant collecting operation (cooling test run).
• For the PAR-31MAA, select “Service” “TestRun” from the main menu to start the test run, and then select the cooling mode.
• For details or for other information about starting the test run when using remote controllers, refer to the installation manual for the indoor unit or the remote controller. 6 Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 0.5 to 0 kgf/cm²) and quickly stop the air conditioner.
• Push the “ON/OFF” button on the remote controller to stop the air conditioner. Note: When the extension piping is very long with a large refrigerant amount, it may not be possible to perform a pump down operation. In this case, use refrigerant recovery equipment to collect all of the refrigerant in the system. 7 Turn off the power supply (circuit breaker), remove the gauge manifold valve, and then disconnect the refrigerant pipes.
.Warning: When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
• If the refrigerant pipes are disconnected while the compressor is operating and the stop valve (ball valve) is open, the pressure in the refrigeration cycle could become extremely high if air is drawn in, causing the pipes to burst, personal injury, etc.
OCH545
Page 7
77
3
PARTS NAMES AND FUNCTIONS
SUZ-KA25VA4.TH SUZ-KA35VA4.TH
SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
Model SUZ-KA·VA4.TH
Drain socket 1
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
OCH545
Page 8
8
SPECIFICATION
4
NOTE: Test conditions are based on ISO 5151 Cooling : Indoor D.B. 27°C W.B. 19°C Outdoor D.B. 35°C Heating : Indoor D.B. 20°C Outdoor D.B. 7°C W.B. 6°C Refrigerant piping length (one way): 5 m *Measured under rated operating frequency.
Outdoor model
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
Power supply Single phase 230V, 50Hz
Compressor
Model KNB073FKFMC KNB092FFAMC SNB130FGBMT SNB172FEKMT
Output W 550 650 900 1,200
Current*
Cooling
A
2.76 4.06 5.58 6.62 8.02
Heating 3.24 4.09 5.75 6.37 8.13
Refrigeration oil (Model)
L 0.31 (FV50S) 0.27 (FV50S) 0.35 (FV50S) 0.4 (FV50S)
Fan motor
Model RC0J50-FA RC0J60-BD RC0J60-BC
Current*
Cooling
A
0.24 0.29 0.84 0.84 0.83
Heating 0.27 0.28 0.93 0.93 0.82
Dimensions W × H × D mm 800 × 550 × 285 840 × 880 × 330
Weight kg 30 35 54 50 53
Special remarks
Air ow*
Cooling
High
m³/h
1,806 2,868 3,492 3,426
Med. 1,806 2,868 3,066 3,006
Low 1,170 1,038 1,602 1,692 1,512
Heating
High 2,106 2,778 2,952 2,892
Med. 1,806 1,770 2,778 2,952 2,892
Low 1,452 1,326 2,124 2,226 2,280
Sound level*
Cooling
dB(A)
47 49 52 55
Heating 48 50 52 55
Fan speed
Cooling
High
rpm
740 810 840 950
Med. 740 810 840
Low 740 490 480 450
Heating
High 860 900 810
Med. 740 770 810
Low 600 610 620 650
Fan speed regulator 3
Refrigerant fi lling capacity (R410A)
kg 0.80 1.15 1.60 1.80 1.80
OCH545
Page 9
99
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
Specifications and rating conditions of main electric parts
Model
Item
SUZ-KA25VA4.TH SUZKA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
Smoothing capacitor
(C61) 620F 420V
(C62, C63) 620F 420V 620F 420V 620F420V
(CB1, 2, 3) 560F 450V 560F 350V
Diode module (DB61) 15A 600V 15A 600V 25A 600V
Fuse
(F61) T20A L250V T20A L250V T20A L250V
(F62) T20A L250V T20A L250V
(F701, F801, F901)
T3.15A L250V T3.15A L250V T3.15A L250V
(IC700) 15A 600V 15A 600V 20A 600V
Inteligent power module
(IPM) 20A 600V
(IC932) 8A 600V 8A 600V 8A 600V 5A 600V 5A 600V
Power factor controller
(PFC) 20A 600V 20A 600V
(IC820) 20A 600V 20A 600V 20A 600V
Expansion valve coil
(LEV) DC12V
Reactor
(L61) 18mH 23mH 23mH
(L) 340H 20A 340H 20A
Current-Limiting PTC thermistoe
(PTC64, PTC65) 33
Terminal block
(TB1, TB2) 3P 3P
(TB) 5P 5P 5P
Relay
(X63) 3A 250V 3A 250V 3A 250V
(X64) 20A 250V
(X601) 3A 250V 3A 250V
(X602) 3A 250V 3A 250V
R.V. coil (21S4) AC220-240V
OCH545
Page 10
10
NOISE CRITERIA CURVES
5
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
COOLING
FUNCTION
SPL(dB(A))
LINE
High Med.
FAN SPEED
HEATING
47
48
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
NC-10
SUZ-KA25VA4.TH
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
COOLING
FUNCTION
SPL(dB(A))
LINE
FAN SPEED
HEATING
49
50
High
Med.
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
NC-10
SUZ-KA35VA4.TH
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
52
52
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
NC-10
SUZ-KA50VA4.TH
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
SUZ-KA60VA4.TH SUZ-KA71VA4.TH
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
55
55
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
NC-10
OCH545
Page 11
11
6
OUTLINES AND DIMENSIONS
10
69
800
302.5
500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) :6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) :9.52
43
35
2-Oval holes 10×21
REQUIRED SPACE
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
350mm or more
200mm or more
100mm or more
100mm or more
Open two sides of left, right, or rear side.
Drain hole :42
Unit: mm
SUZ-KA25VA4.TH SUZ-KA35VA4.TH
OCH545
Page 12
12
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-Oval holes 10 21
840
109
81
880
452
Service panel
99.5
164.5 195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared)
Ø 6.35...(SUZ-KA50/60VA4) Ø 9.52...(SUZ-KA71VA4)
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 12.7...(SUZ-KA50VA4) Ø 15.88...(SUZ-KA60/71VA4)
350 mm or more
100 mm or more
REQUIRED SPACE
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if there are obstacles to both sides
Open as a rule 500mm or more if the back, both sides and top are open
Air in
Bolt pitch for
installation
360
SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
Unit: mm
OCH545
Page 13
1313
7
WIRING DIAGRAM
SUZ-KA25VA4.TH SUZ-KA35VA4.TH
OCH545
Page 14
14
SUZ-KA50VA4.TH
OCH545
Page 15
15
SUZ-KA60VA4.TH SUZ-KA71VA4.TH
OCH545
Page 16
16
REFRIGERANT SYSTEM DIAGRAM
8
Unit: mm
SUZ-KA25VA4.TH
Unit: mm
SUZ-KA35VA4.TH
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Ambient temperature thermistor RT65
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor RT68
Muffler
Outdoor heat exchanger
LEV
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube ø3.0×ø1.8×600(×2)
LEV
Ambient temperature thermistor
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor
Muffler
RT65
RT68
OCH545
Page 17
1717
Unit: mm
SUZ-KA50VA4.TH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
ø
4.0
×
ø
2.4×100 Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Muffler
Unit: mm
SUZ-KA60VA4.TH SUZ-KA71VA4.TH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube
ø
4.0
×
ø
2.4×100 Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe (with heat insulator)
ø
15.88
Refrigerant pipe (with heat insulator)
ø
6.35...(SUZ-KA60VA4)
ø
9.52...(SUZ-KA71VA4)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
OCH545
Page 18
18
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
MAX. REFRIGERANT PIPING LENGTH
Max. Length A
* Height difference limitations are binding regardless of which unit, indoor or outdoor, is position high.
* Max. Height difference B
Indoor unit
Outdoor unit
MAX. HEIGHT DIFFERENCE
Calculation : Xg=20g/m × (Refrigerant piping length(m)–7)
Calculation : Xg=55g/m × (Refrigerant piping length(m)-7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7m 8m 9m 10m 11m 12m 13m 14m 15m 20m
SUZ-KA25VA4.TH 800 0 30 60 90 120 150 180 210 240 390 SUZ-KA35VA4.TH 1,150 0 30 60 90 120 150 180 210 240 390
Calculation: Xg=30g/m×(Refrigerant piping length(m)-7)
Model
Refrigerant piping: m Piping size O.D: mm
Max. Length A
Max. Height difference B
Gas Liquid
SUZ-KA25VA4.TH
20 12 9.52
6.35
SUZ-KA35VA4.TH SUZ-KA50VA4.TH
30 30
12.7
SUZ-KA60VA4.TH
15.88
SUZ-KA71VA4.TH 9.52
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7m 10m 15m 20m 25m 30m
SUZ-KA50VA4.TH 1,600 0 60 160 260 360 460 SUZ-KA60VA4.TH 1,800 0 60 160 260 360 460
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7m 10m 15m 20m 25m 30m
SUZ-KA71VA4.TH 1,800 0 165 440 715 990 1,265
OCH545
Page 19
1919
ACTUATOR CONTROL
9
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH
SUZ-KA71VA4.TH
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds 15 seconds
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
NOTE: The 4-way valve reverses for 5 seconds
right before start-up of the compressor.
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Discharge temperature thermistor
Protection

Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protection

Defrost thermistor Heating: Defrosting

Fin temperature thermistor Protection

Ambient temperature thermistor
Cooling: Low ambient temperature operation

Outdoor heat exchanger temperature thermistor
Cooling: Low ambient temperature operation

Cooling: High pressure protection

OCH545
Page 20
20
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
CHANGE IN DEFROST SETTING
Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 11-6-1.)
11
TROUBLESHOOTING
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the outdoor P.C. board is blinking on and off to indicate an abnormal­ity. To make sure, check how many times the abnormality indication is blinking on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) When troubleshooting, refer to 11-2. and 11-3.
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care the following during servicing.
1)
Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and turn off the breaker.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Housing point
Lead wire
10
SERVICE FUNCTIONS
Jumper wire
Defrost fi nish temperature (°C)
SUZ-KA25VA4.TH SUZ-KA35VA4.TH
SUZ-KA50VA4.TH
SUZ-KA60VA4.TH SUZ-KA71VA4.TH
JS
Soldered (Initial setting) 5 9 10
None (cut) 10 18 18
OCH545
Page 21
2121
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
temperature thermistor, outdoor heat exchanger temperature
No. Symptoms
Abnormal point/
Condition
RemedyCondition
1
Outdoor unit does not op­erate.
1-time flash every
2.5 seconds
Outdoor power sys-
tem
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect connector of compres­sor. Refer to 11-5. "How to check in­verter/compressor". Check stop valve.
2
Outdoor thermistors Discharge temperature thermistor shorts, or opens during compressor running.
defrost thermistor, P.C. board
thermistor or ambient temperature thermistor shorts, or opens during compressor running.
Refer to 11-5.F"Check of outdoor thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly.
Replace inverter P.C. board.
4
6-time flash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
5
11-time flash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current. Check stop valve.
6
7
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time flash
2.5 seconds OFF
Overcurrent protec­tion
Large current flows into intelligent power module.
Reconnect connector of compressor.
Refer to 11-5. "How to check in­verter/compressor". Check stop valve.
 
8
3-time flash
2.5 seconds OFF
Discharge tempera­ture overheat pro­tection
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig­erant amount. Refer to 11-5.  "Check of LEV".
9
4-time flash
2.5 seconds OFF
Fin temperature /P.C. board tem­perature thermistor overheat protection
Temperature of fin temperature thermistor on the heat sink exceeds 72 ~ 86°C or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 72 ~ 85°C.
Check around outdoor unit. Check outdoor unit air passage.
Refer to 11-5. "Check of outdoor
fan motor".
  
10
5-time flash
2.5 seconds OFF
High pressure pro­tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig­erant amount. Check stop valve.
11
8-time flash
2.5 seconds OFF
Compressor syn­chronous abnormal­ity
The waveform of compressor current is distorted.
Reconnect connector of compressor. Refer to 11-5. "How to check in­verter/compressor".
 
12
10-time flash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 11-5. "Check of outdoor fan motor. Refer to 11-5. "Check of inverter P.C. board.
13
12-time flash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally.
Refer to 11-5. "How to check in­verter/compressor".
14
13-time flash
2.5 seconds OFF
DC voltage DC voltage of inverter cannot be detected normally. Refer to 11-5. "How to check in-
verter/compressor".
15
Outdoor unit operates.
1-time flash
2.5 seconds OFF
Frequency drop by current protection
When the input current exceeds approximately 7A(KA25)/ 8A(KA35)/12A(KA50)14A(KA60)/16A(KA71), compressor
The unit is normal, but check the following.
Check if indoor filters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air circulation is short cycled.
  
16
3-time flash
2.5 seconds OFF
Frequency drop by high pressure pro­tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
17
4-time flash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check refrigerant circuit and refrig­erant amount. Refer to 11-5. "Check of LEV". Refer to 11-5. "Check of outdoor thermistors".
 
18
19
7-time flash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check refrigerant circuit and refrig-
erant amount.
 
8-time flash
2.5 seconds OFF
PAM protection PAM: Pulse Ampli­tude Modulation
The overcurrent flows into PFC (Power factor correction : IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases:
1. Instantaneous power voltage drop. (Short time power failure)
2. When the power supply voltage is high.
9-time flash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected. Refer to 11-5. "How to check inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right figure. Refer to 11-6-1.
2. LED is lighted during normal operation. The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the flashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Flashing ĺ
Inverter P.C. board
I
H
H
J
I F
I
Check of indoor/outdoor connecting wire.
Replace indoor or outdoor P.C. board if abnormality is displayed again.
(KA25/35/50)
(KA60/71) Zero cross detecting circuit
Zero cross signal for PAM control cannot be detected.
LED
indication
check
code
UP
U3
U4
FC
E8 E9
UE
Fin temperature thermistor,
/
frequency lowers.
11-2. TROUBLE SHOOTING CHECK TABLE
OCH545
Page 22
22
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Test run Input maintenance info. Function setting Check Self check
kcehc fleS
:tceleS
Ref. address
sserddA
kcehc fleS
Ref. address
Return:
teseR
Error Unt # CI.prG
Self check
Contact
Return:
Reset
M-NET address
Error Grp.
---- ---
When there is no error history
Self check
Delete error history?
Ref. address
Cancel OK
Self check
Return:
Ref. address
Error history deleted
2
With theF1or
F2
button, enter the refrigerant address, and press the button.
Select "Self check" with the F1 or F2 button, and press the button.
1
Select "Service" from the Main menu, and press the button.
3
Error code, unit number, attribute will appear.
"-" will appear if no error history is available.
4
Resetting the error history.
Press the
F4
button (Reset) on the screen that shows the error history.
A confi rmation screen will appear asking if you want to delete the error history.
Press the
F4
button (OK) to delete the error history.
If deletion fails, "Request rejected" will appear. "Unit not exist" will appear if no indoor units that are correspond to the entered address are found.
Navigating through the screens
• To go back to the Main menu ..........
button
• To return to the previous screen .......
button
11-3. HOW TO PROCEED "SELF-DIAGNOSIS"
11-3-1. Self-diagnosis <PAR-30MAA> <PAR-31MAA>
As this air conditioner has a function to memorize all the failures that had occured, the latest failure detail can be recalled by following the procedure below. Use this function when the check code is not displayed with wired remote controller or the remote controller at use is wireless type.
OCH545
Page 23
23
If operations cannot be completed with the remote controller, diagnose the remote controller with this function.
F1 F2 F3 F4
unem ecivreS
rosruC
:unem niaM
Maintenance password Remote controller check
F1 F2 F3 F4
Remote controller check
:nigeB
Start checking?
Remote controller check
:nigeB
Start checking?
1
Select "Service" from the Main menu, and press the button.
Select "Remote controller check" with the F1
or F2 button, and press
the
button.
2
Select "Remote controller check" from the Service menu, and press the but-
ton to start the remote controller check and see the check results.
To cancel the remote controller check and exit the Remote controller check menu screen, press the
or the button.
The remote controller will not reboot itself.
Check the remote controller display and see if anything is displayed (including lines). Nothing will appear on the remote controller display if the correct voltage (8.5 – 12 VDC) is not supplied to the remote con­troller. If this is the case, check the remote controller wiring and indoor units.
OK: No problems are found with the remote controller. Check other
parts for problems.
E3, 6832: There is noise on the transmission line, or the indoor unit or another
remote controller is faulty. Check the transmission line and the other remote controllers.
NG (ALL0, ALL1):
Send-receive circuit fault. Remote controller needs replacing.
ERC:
The number of data errors is the discrepancy between the number of bits in the data transmitted from the remote controller and that of the data that was actually transmitted over the transmission line. If data errors are found, check the transmission line for external noise inter­ference.
Remote controller check results screen
If the button is pressed after the remote controller check results are dis­played, remote controller check will end, and the remote controller will automati-
cally reboot itself.
11-3-2. Remote controller check <PAR-30MAA> <PAR-31MAA>
3
OCH545
Page 24
24
When a problem occurs to the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below.
1 (If the outdoor unit is malfunctioning, the unit number will be "00".) 2 In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the unit that first experienced trouble (i.e., the unit that transmitted the error code) will be displayed.
3 To clear the error code, press the
ON/OFF
button.
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During central control by a MELANS controller, cancel the error code by pressing the
ON/OFF
button.
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote controller or power is turned off.
Check the error code history for each unit using the remote controller.
1
Switch to self-diagnosis mode. Press the
CHECK
button (
H in the picture above)
twice within 3 seconds.
The display content will change as shown below.
2
Set the unit number or refrigerant address you want to diagnose.
Press the [TEMP] buttons (
and ) (
F in the picture above)
to select the desired number or address. The number (address) changes between [01] and [50] or [00] and [15].
3
Display self-diagnosis results. <When there is error code history> (For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
4
Reset the error history. Display the error history in the diagnosis result display screen (see step
3
).
F
E
G
C
D
H
B
A
I
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
The refrigerant address will begin to blink approximately 3 seconds after being selected and the self-diagnosis process will begin.
Unit number or refrigerant address to be diagnosed
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
<When there is no error code history> <When there is no corresponding unit>
11-3-3. Self-diagnosis <PAR-21MAA>
11-3-4. Self-Diagnosis During Maintenance or Service <PAR-21MAA>
OCH545
Page 25
25
Transmission data from remote controller
Transmission data on transmission path
When the number of data errors is "02":
Press the
ON/OFF
button ( in the picture in the previous page) twice
within 3 seconds. The self-diagnosis address or refrigerant address will blink.
When the error history is reset, the display will look like the one shown below. However, if you fail to reset the error history, the error content will be displayed again.
Cancel self-diagnosis.
Self-diagnosis can be cancelled by the following 2 methods.
Press the
CHECK
button ( in the picture in the previous page) Self-diagnosis will be cancelled and the screen will return to the previous state in effect
before the start of self-diagnosis.
Press the
ON/OFF
button ( in the picture in the previous page). Self-diagnosis will be cancelled and the indoor unit will stop.
10-3-3. Remote Controller Diagnosis
If the air conditioner cannot be operated from the remote controller, diagnose the remote controller as explained below.
First, check that the power-on indicator is lit.
If the correct voltage (DC12 V) is not supplied to the remote controller, the indicator will not light. If this occurs, check the remote controller's wiring and the indoor unit.
Switch to the remote controller self-diagnosis mode.
Press the
CHECK
button ( in the picture in the previous page)
for 5 seconds or more. The display content will change as shown below.
Press the
FILTER
button ( in the picture in the previous page)
Remote controller self-diagnosis result
[When the remote controller is functioning correctly]
Check for other possible causes, as there is no problem with the remote controller.
[When the remote controller malfunctions] (Error display 1) "NG" blinks. The remote controller's transmitting-receiv-
ing circuit is defective.
The remote controller must be replaced with a new one.
[Where the remote controller is not defective, but cannot be operated.] (Error display 2) [E3], [6833] or [6832] blinks.
Transmission is not possible.
There might be noise or interference on the transmission path, or the indoor unit or other remote controllers are defective. Check the transmission path and other controllers.
(Error display 3)
"ERC" and the number of data errors are displayed. Data error has occurred.
The number of data errors is the difference between the number of bits sent from the remote controller and the number actually transmitted through the transmis­sion path. If such a problem is occurring, the transmitted data is affected by noise, etc. Check the transmission path.
To cancel remote controller diagnosis
Press the
CHECK
button ( in the picture in the previous page) for 5 seconds or more. Remote controller diagnosis will be cancelled,
"PLEASE WAIT" and operation lamp will blink. Afterapproximately 30 seconds, the state in effect before the diagnosis will be restored.
Power on indicator
twice within 3 seconds.
to start self-diagnosis.
11-3-5. Remote controller check <PAR-21MAA>
OCH545
Page 26
26
• "CHECK" lights, and refrigerant address "00" flashes.
• Check that the remote controller's display has stopped before continuing.
• Select the refrigerant address of the indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit’s DIP switch (SW1). (For more information, see the outdoor unit installation manual.)
• If an air conditioner error occurs, the indoor unit's sensor emits an intermittent buzzer sound, the operation light flashes, and the error code is output. (It takes 3 seconds at most for error code to appear.)
• The check mode is cancelled.
[Procedure]
1. Press the CHECK button twice.
2. Press the temperature buttons.
3. Point the remote controller at the sensor on the indoor unit and press the HOUR button.
4. Point the remote controller at the sensor on the indoor unit and press the ON/OFF button.
<Malfunction-diagnosis method at maintenance service>
11-3-6. Self-diagnosis <Wireless remote controller>
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop.
ON/OFF
TEMP
FAN
VAN E
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
CHECK
CHECK display
Temperature button
CHECK button
Refrigerant address display
HOUR button
ON/OFF button
OCH545
Page 27
27
[Output pattern A] Errors detected by indoor unit
[Output pattern B]
E9
1. If the beeper does not sound again after the initial
2 beeps to confirm the self-check start signal was received and
the OPERATION INDICATOR lamp does not come on,
there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATION INDICATOR lamp flash pattern
Beep Beep Beep Beep Beep
Beep Beep
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
[Output pattern B]
OPERATION INDICATOR lamp flash pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
· · · Repeated
Number of blinks/beeps in pattern indicates the check code in the following table (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates the check code in the following table
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
Refer to the following tables for details on the check codes. [Output pattern A]
Notes:
*The check code in the parenthesis indicates PAR-30MAA model.
Beeper sounds/OPERATION
INDICATOR lamp flashes Check code
Symptom Remark
(Number of times)
Wireless remote controller
Wired remote controller
Beeper sounds/OPERATION
INDICATOR lamp flashes Check code
(Number of times)
Wireless remote controller
Wired remote controller
1P1
Intake sensor error
P9 Pipe (TH5) sensor error
2
P2 Pipe (TH2) sensor error
3E6,E7
Indoor/outdoor unit communication error
4 P4 Drain sensor error/Float switch connector (CN4F) open 5
P5 Drain pump error
PA Forced compressor stop (due to water leakage abnormality) 6 P6 Freezing/Overheating protection operation 7 EE Communication error between indoor and outdoor units
9 E4, E5 Remote controller signal receiving error
Errors detected by unit other than indoor unit (outdoor unit, etc.)
Symptom
1
Indoor/outdoor unit communication error
2
(Transmitting error) (Outdoor unit)
3
Open/short of outdoor unit thermistors
UP U3,U4 Others
14
Other errors (Refer to the technical manual for the outdoor unit.)
12 14
Fb (FB)*
PL
Indoor unit control system error (memory error, etc.)
E0, E3 – E1, E2 Remote controller control board error
Remote controller transmission error
Abnormality of refrigerant circuit
Compressor overcurrent interruption
As for indoor unit, refer to indoor unit's service manual.
OCH545
Page 28
28
11-4. TROUBLE CRITERION OF MAIN PARTS
Parts name
Figure
Check method and criterion
Outdoor fan motor
R.V. coil (21S4)
Expansion valve coil (LEV)
Measure the resistance between terminals with a tester. (Temperature: -10°C ~ 40°C)
WHT - BLK
BLK - RED
RED - WHT
Normal
Measure the resistance between terminals with a tester. (Temperature : -10°C ~ 40°C)
Normal
WHT - RED
RED - ORN YLW - BRN BRN - BLU
Normal
37  ~ 54 
Measure the resistance with a tester. (Temperature : -10°C ~ 40°C)
Measure the resistance with a tester. Refer to 11-6. “Test point diagram and voltage”, 11-6-1. (KA25/35/50) or
11-6-2. (KA60/71) “Inverter P.C. board”, for the chart of thermistor.
Color of the lead wire
Color of the lead wire
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. Refer to 11-6. “Test point diagram and voltage”, 11-6-1. (KA25/35/50) or 11-6-2. (KA60/71) “Inverter P.C. board”, for the chart of thermistor.
Defrost thermistor (RT61) Fin temperature
thermistor (RT64)
29  ~ 42 
Measure the resistance between terminals with a tester. (Temperature: -10°C ~ 40°C)
Compressor
U-V U-W V-W
Normal
W
U
V
WHT
RED BLK
W
U
V
WHT
RED BLK
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor(RT68)
SUZ-KA25VA4.TH
1.36  ~ 1.93 
SUZ-KA35VA4.TH
1.52 ~ 2.17
1.19 k ~ 1.78 k
SUZ-KA50/60VA4.TH
0.78  ~ 1.11 
SUZ-KA71VA4.TH
0.92  ~ 1.12 
SUZ-KA25/35VA4.TH SUZ-KA50/60/71VA4.TH
12 ~ 17
SUZ-KA25/35VA4.TH
LEV
WHT
RED
YLW
ORN
BLU
Measure the resistance with a tester. (Temperature : -10°C ~ 40°C)
RED - ORN
RED - WHT
RED - BLU
RED - YLW
Normal
37  ~ 54 
Color of the lead wire
SUZ-KA50/60/71VA4.TH
LEV
WHT
RED ORN
YLW
BRN
BLU
SUZ-KA25VA4.TH SUZ-KA35VA4.THSUZ-KA50VA4.TH SUZ-KA60VA4.TH SUZ-KA71VA4.TH
OCH545
Page 29
29
A How to check inverter/compressor
Are the voltages balanced?
Disconnect the connector between the compressor and the intelligent power module (KA25/35/50: IC700, KA60/71: IPM) .
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See 11-5. “Check of compressor”.
No
Yes
See 11-5. “Check of open phase”.
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the voltage balance between the terminals.
Output voltage is 50 - 130V. (The voltage may differ according to the tester.)
<< Operation method (Test run operation)>>
• For the PAR-31MAA, select “Service” “Test Run” from the main menu to start the test run, and then select the cooling
mode.
• For details or for other information about starting the test run when using remote controllers, refer to the installation manual for the indoor unit or the remote controller.
<<Measurement point>> At 3 points BLK (U) - WHT (V) BLK (U) - RED (W) WHT (V) - RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (KA25/35/50: Refer to 11-6-1, KA60/71: 11-6-2)
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
OK
No
Yes
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
C Check of compressor
B Check of open phase
11-5. TROUBLESHOOTING FLOW
* Measure AC voltage between the lead wires at 3 points.
Is the compressor
operation time more than
10 seconds?
Replace the compressor.
No
Yes
Check the refrigerant circuit
OCH545
Page 30
30
D Check of compressor winding
Disconnect the connector between the compressor and intelligent power module, and measure the resistance between the
compressor terminals. <<Measurement point>> at 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 11-4. 0 [] ················Abnormal [short] Infinite [] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
* Measure the resistance between the lead wires at 3 points.
E Check of compressor operation time
Compressor starts
Abnormal (IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second
1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
Connect the compressor and activate the inverter. Then measure the
time until the inverter stops due to over current. <<Operation method>> Start heating or cooling test run. (TEST RUN OPERATION : Refer to 11-5
.) <<Measurement>> Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
Is the resistance of thermistor normal?
(KA25/35/50: Refer to 11-6-1, KA60/71: 11-6-2.)
Disconnect the connector of thermistor in the outdoor P.C. board (see below table), and measure the resistance of thermistor.
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
No
Yes
F Check of outdoor thermistors
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
Yes
OK. (Cause is poor contact.)
No
Replace the inverter P.C. board.
Thermistor Symbol
Connector, Pin No.
Board
SUZ-KA25/35/50VA4.TH SUZ-KA60/71VA4.TH
Defrost RT61 Between CN641 pin1 and pin2 Between CN671 pin1 and pin2
Inverter
P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Between CN671 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Between CN673 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Between CN672 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3 Between CN671 pin5 and pin6
OCH545
Page 31
31
G Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721(KA25/35/50)/CN602(KA60/71) is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector although any signal is not being transmitted to R.V. coil. Check if CN721(KA25/35/50)/CN602(KA60/71) is connected.
Is there 230 VAC between CN721 (KA25/35/50)/CN602(KA60/71)
and on the inverter P.C. board 3 minutes after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 (KA25/35/50)/CN602(KA60/71)
and on the inverter P.C. board 3 minutes after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the intelligent power module. Turn ON the power supply and start heating test run. (TEST RUN OPERATION: Refer to 11-5
)
Disconnect connector between the compressor and the intelligent power module. Turn ON the power supply and start cooling test run. (TEST RUN OPERATION: Refer to 11-5
)
H Check of outdoor fan motor
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 11-4.)
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
Disconnect CN932 from the inverter
P.C. board, and turn on the power sup-
ply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
OCH545
Page 32
32
I Check of LEV
Turn on power supply to the outdoor unit after checking LEV coil is fi xed to the LEV body securely.
Yes
Disconnect the connector CN724 is there nor­mal resistance to LEV coil?
No
Replace the inverter P.C. board.
Replace the LEV coil.
No
Normal
Start
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
Yes
Check the outdoor fan motor. (Refer to .)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan mo­tor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 11-3.)
Yes
No
Yes (10-time fl ash)
No
J Check of inverter P.C. board
OCH545
Page 33
33
Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
K
OCH545
Page 34
34
11-6. TEST POINT DIAGRAM AND VOLTAGE
11-6-1. Inverter P.C. board
SUZ-KA25VA4.TH SUZ-KA35VA4.TH SUZ-KA50VA4.TH
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
DB61 260 - 370 VDC
Front side of unit
230 VAC
Smoothing capacitor (C62)
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) T3.15AL250V
Smoothing capacitor (C61)
Smoothing capacitor (C63)
Fuse (F901) T3.15AL250V
R.V.coil (CN721) 230 VAC
Jumper wire for changing defrost setting (JS)
Signal of outdoor
fan motor (CN931)
230 VAC
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Jumper wire for pre-heat control setting (JK)
Heater connector (CN722)
Fuse (F801) T3.15AL250V
Back side of unit
LEV connector
(CN724)
Output to drive outdoor fan motor (CN932)
LED
OCH545
Page 35
35
11-6-2. Inverter P.C. board SUZ-KA60VA4.TH SUZ-KA71VA4.TH
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
Fin temperature thermistor/RT64 (CN673)
Ambient temperature thermistor/RT65
(CN672)
Discharge temperature thermistor/RT62 (CN671)
Defrost thermistor /RT61 (CN671)
Output to drive outdoor fan motor (CN932)
Outdoor heat exchanger temperature thermistor /RT68 (CN671)
Fuse (F901) T3.15AL250V
Fuse (F880) T3.15AL250V
LEV connector (CN724)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
Fuse (F62) T2.0AL250V
Fuse (F601) T3.15AL250V
Signal of out­door fan motor (CN931)
R.V. coil (CN602) 230VAC
325 - 370 VDC
JP715 (+)
JP30 (-)
LED
OCH545
Page 36
36
12
DISASSEMBLY INSTRUCTIONS
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Slide the sleeve.Pull the terminal while
pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
The terminal which has the locking mechanism can be detached as shown below. There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
NOTE: Turn OFF power supply before disassembling.
SOTOPERUDECORP GNITAREPO
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply and indoor/outdoor con-
necting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Photo 2
Back panel
Screws of the back panel
Service
panel
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the
service panel
Direction to remove
Screws of the cabinet
Hooks
Screw of the cabinet
H
SUZ-KA25VA4.TH SUZ-KA35VA4.TH OUTDOOR UNIT
OCH545
Page 37
3737
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the relay panel. (Photo 3) (5) Remove the inverter assembly. (Photo 4) (6) Remove the screw of the earth wire and screw of the
T.B.support. (Photo 4)
(7) Remove the relay panel from the inverter assembly. (8) Remove the inverter P.C. board from the relay panel.
Photo 3
Photo 4 (Inverter assembly)
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil. (Photo 5)
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder.
(Photo 5) (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6) (6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
R.V. coil
Screws of the relay panel
Heat sink
Inverter P.C. board
Screw of the earth wire
T.B.support
Screw of the T.B.support
Relay panel
OCH545
Page 38
38
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN932 (Fan motor) (3) Remove the propeller nut. (Photo 7) (4) Remove the propeller. (Photo 7) (5) Remove the screws fixing the fan motor. (Photo 7) (6) Remove the fan motor.
Photo 6
Photo 7
Photo 8
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Remove the inverter assembly. (Refer to procedure 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm² (0 MPa).
(4) Detach the welded part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the welded part of pipes connected with 4-way valve.
(Photo 8)
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Propeller nut
Screws of the outdoor fan motor
Propeller
Welded parts of 4-way valve
OCH545
Page 39
39
SUZ-KA50VA4.TH
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 1
Photo 2
Screws of the cabinet
Screws of the top panel
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Screws of the cabinet
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
Screws of the cabinet
OCH545
Page 40
40
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly. (7) Remove the screw of the earth wire, screw of the P.C. board
cover and screws of the terminal block support.
(8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and the inverter
P.C. board from the P.C. board support.
Photo 3
Photo 4
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
Screw of the heat sink support and the separator
Brazed parts of 4-way valve
Screw of the R.V. coil
Heat sink
Screw of the inverter P.C. board
Screw of the earth wire
Screws of the terminal block support
Screw of the P.C. board cover
Screw of the terminal block support and the back panel
P.C. board support
Heat sink support
OCH545
Page 41
41
OPERATING PROCEDURE PHOTOS
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3)
Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder.
(6) Pull out the ambient temperature thermistor from its holder.
Photo 6
Photo 7
Photo 8
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to
procedure
1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor) (3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to
procedure
1.) (2) Remove the back panel. (Refer to procedure 1.) (3) Remove the inverter assembly. (Refer to procedure 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm² (0 MPa).
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the rieCONNECTOR: Yellow nuts. (7) Remove the compressor. (8) Detach the brazed part of 4-way valve and pipe. (Photo 5)
Screws of the outdoor fan motor
Brazed part of the discharge pipe
Brazed part of the suction pipe
Discharge temperature thermistor
Outdoor heat exchanger tempera­ture thermistor
Ambient tem-
perature
thermistor
Defrost thermistor
Propeller nut
OCH545
Page 42
42
NOTE: Turn OFF power supply before disassembling.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 1
Photo 2
Screws of the cabinet
Screws of the top panel
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Screws of the cabinet
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
SUZ-KA60VA4.TH SUZ-KA71VA4.TH
OCH545
Page 43
43
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN602 (R.V. coil) CN931, CN932 (Fan motor) CN671 (Defrost thermistor, discharge temperature thermistor
and outdoor heat exchanger temperature thermistor) CN672 (Ambient temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screws fixing the relay panel. (5) Remove the relay panel. (6) Remove the earth wires and the lead wires of the inverter P.C.
board.
(7) Remove the screw of the PB support. (8) Remove the inverter P.C. board from the relay panel.
Photo 3
Photo 4
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN602 (R.V. coil)
(3) Remove the R.V. coil.
Screws of the PB support
Screws of the relay panel
Inverter P.C board
Earth wires
Screw of the
relay panel
Screws of the PB support
Welded parts of 4-way valve
Screw of the R.V. coil
OCH545
Page 44
44
OPERATING PROCEDURE PHOTOS
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to procedure 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board> CN671 (Defrost thermistor, discharge temperature thermis-
tor and outdoor heart exchanger temperature ther­mistor)
CN672 (Ambient temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er. (Photo 7) (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (6) Pull out the ambient temperature thermistor from its holder.
Photo 5
Photo 6
Photo 7
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to
procedure
1.) (2) Remove the back panel. (Refer to procedure 1.) (3) Remove the inverter assembly. (Refer to procedure 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm² (0 MPa).
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the welded part of 4-way valve and pipe. (Photo 4)
Screws of the outdoor fan motor
Welded part of the discharge pipe
Welded part of the suction pipe
Discharge temperature thermistor
Outdoor heat exchanger tempera­ture thermistor
Ambient tem­perature thermistor
Defrost thermistor
OCH545
Page 45
45
OCH545
Page 46
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
Copyright 2013 MITSUBISHI ELECTRIC CORPORATION
Distributed in Aug. 2013 No.OCH545 Made in Japan
New publication, effective Aug. 2013 Specifications are subject to change without notice.