Mitsubishi SUZ-KA35VA, SUZ-KA35VAH, SUZ-KA50VA, SUZ-KA25VA.TH, SUZ-KA25VAR1.TH Service Manual

...
Page 1
TECHNICAL & SERVICE MANUAL
No.OC322
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
R410A
Outdoor unit [model names]
[Service Ref.]
SUZ-KA25VAHR1.TH
SUZ-KA35VAH SUZ-KA35VAH.TH
SUZ-KA35VAHR1.TH
SUZ-KA50VA SUZ-KA50VA.TH SUZ-KA50VA1.TH
SUZ-KA50VAR2.TH
SUZ-KA60VA SUZ-KA60VA.TH SUZ-KA60VA1.TH
SUZ-KA60VAR2.TH
SUZ-KA71VA SUZ-KA71VA.TH
SUZ-KA71VA1.TH
CONTENTS
1.
COMBINATION OF INDOOR AND OUTDOOR UNITS
.......
2
2. TECHNICAL CHANGES
....................................
3
3. PART NAMES AND FUNCTIONS
......................
7
4. SPECIFICATION
.................................................
8
5. NOISE CRITERIA CURVES
..............................
12
6. OUTLINES AND DIMENSIONS
........................
13
7. WIRING DIAGRAM
...........................................
15
8. REFRIGERANT SYSTEM DIAGRAM
..............
23
9. PERFORMANCE CURVES
..............................
29
10. ACTUA TOR CONTROL
....................................
57
11. SERVICE FUNCTIONS
.....................................
58
12. TROUBLESHOOTING
......................................
58
13. DISASSEMBLY INSTRUCTIONS
...................
103
14. PARTS LIST
....................................................
113
15. RoHS PARTS LIST
.........................................
119
Indication of model name
NOTE: This service manual describes technical data of the outdoor units. RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS Parts List.
HFC
utilized
R410A
SUZ-KA25VA(H).TH SUZ-KA25VA(H)R1.TH SUZ-KA35VA(H).TH SUZ-KA35VA(H)R1.TH
April 2009
REVISED EDITION-E
Revision:
SUZ-KA25/35VA(H)R1.TH are added in REVISED EDITION-E.
• Some descriptions
have been modified.
• Please void OC322
REVISED EDITION-D.
Page 2
2
1
COMBINATION OF INDOOR AND OUTDOOR UNITS
Heat pump type
Outdoor unit
SUZ-
SLZ-KA25V A(L).TH SLZ-KA35V A(L).TH SLZ-KA50V A(L).TH SEZ-KC25V A.W SEZ-KA35V A.TH SEZ-KA50V A.TH SEZ-KA60V A.TH SEZ-KA71V A.TH SEZ-KD25V A(L).TH SEZ-KD35V A(L).TH SEZ-KD50V A(L).TH SEZ-KD60V A(L).TH SEZ-KD71V A(L).TH MFZ-KA25V A-E1 MFZ-KA35V A-E1 MFZ-KA50V A-E1
— —
— — — —
— — — —
— —
— —
— — — —
— — — —
— —
— —
— — — —
— — — —
— — — — — —
— — — —
— — — —
— — — — — — —
— — — —
— — —
OC320
OC321
OB409
Indoor unit
Service
Manual No.
Service Ref.
Heat pump without electric heater
KA25V A(H).TH KA25V A(H)R1.TH
KA60VA
(1)
.TH
KA60VAR2.TH
KA71VA
(1)
.TH
KA50VA
(1)
.TH
KA50VAR2.TH
HWE0711
KA35V A(H).TH KA35V A(H)R1.TH
(NOTE) • Please refer to the service manual of indoor unit or the technical data book for the combination data.
• Only MFZ-KA·VA series can be connected to SUZ-KA·VAH series.
1-1. INDOOR UNIT SERVICE MANUAL
1-2. TECHNICAL DATA BOOK
OCS03
Page 3
3
2
TECHNICAL CHANGES
SUZ-KA50VA1.TH SUZ-KA50VAR2.TH SUZ-KA60VA
1.TH SUZ-KA60VAR2.TH
1. OUTDOOR ELECTRONIC CONTROL P.C. BOARD has been changed.
2. Compressor has been changed. (SNB130FLDH(1)
→ SNB130FGBH)
3. High pressure switch has been added. (SUZ-KA60VAR2.TH)
4. Thermistors (RT61, 62, 64, 65, 68) have been changed. (SUZ-KA50VAR2.TH)
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
1. OUTDOOR ELECTRONIC CONTROL P.C. BOARD has been changed.
2. Max. height difference 15m
30m (Except when combined with MFZ).
3. Guaranteed operating range Lower limit (Cooling/Outdoor) -10:DB
-15:DB (Except when combined with MFZ)
SUZ-KA25VA.TH SUZ-KA35VA.TH
Lower limit (Heating/Outdoor) -10:DB → -15:DB.
SUZ-KA35VAH.TH
Defrost finish temperature has been changed (Refer to 11).
SUZ-KA25VA.TH SUZ-KA25VAR1.TH SUZ-KA25VAH.TH SUZ-KA25VAHR1.TH SUZ-KA35VA.TH SUZ-KA35VAR1.TH SUZ-KA35VAH.TH SUZ-KA35VAHR1.TH
1. Inverter P.C. board and Power P.C. board have been changed.
2. Refrigerant circuit has been changed.
• Compressor has been changed. (KNB073FDVH(C) KNB073FFDHC : SUZ-KA25VA(H)R1.TH) (KNB092FCAH KNB092FFAHC : SUZ-KA35VA(H)R1.TH)
• Muffler of liquid pipe side has been deleted.
• Muffler of gas pipe side has been changed.
• Capillary tube of liquid pipe side has been added. (SUZ-KA35VA(H)R1.TH)
• 4-way valve and R.V. coil have been changed.
• Specification of LEV body has been changed.
• Stop valve has been changed.
3. Precharged refrigerant amount has been changed. (900g 800g : SUZ-KA25VA(H)R1.TH)
4. Fan motor has been changed. (RC0J50-AL RC0J50-DB)
5. Outdoor heat exchanger temperature thermistor (RT68) has been added.
SUZ-A09VR.TH SUZ-KA25VA.TH SUZ-A12VR.TH SUZ-KA35VA.TH
1. Indication of capacity has been changed.(BTU base kW base)
2. Control method between indoor and outdoor unit has been changed.
3. Power supply method has been changed (change to supply from outdoor unit).
4. Terminal block for power supply has been added.
5. Power P.C.board has been changed.
6. Inverter P.C. board has been changed.
7. Refrigerant circuit has been changed.
Compressor has been changed.(KNB073FBVH KNB073FDVH:SUZ-KA25VA) (KNB092FAAH KNB092FCAH:SUZ-KA35VA)
• Specification and position of muffler have been changed.
• Path of outdoor heat exchanger has been changed.
• 4-way valve and R.V. coil have been changed.
• Stop valve has been changed.
8. Fan motor has been changed.(AC DC)
9. Shape of grille has been changed.
10. Shape of service panel has been changed.
11. Shape of propeller has been changed.
12. Symbol on terminal block has been changed (to S1/S2/S3).
Page 4
4
Refrigerant
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
None None
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
None
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point () Steam pressure [25](Mpa) Saturated steam density [25](Kg/*) Combustibility ODP +1 GWP +2 Refrigerant charge method Additional charge on leakage Kind Color Smell
+1: Ozone Depletion Potential : based on CFC-11 +2: Global Warming Potential : based on CO
2
SUZ-A18VR SUZ-KA50VA.TH SUZ-A24VR SUZ-KA60VA.TH
1. Indication of capacity has been changed.(BTU base kW base)
2. Power supply method has been changed (change to supply from outdoor unit).
3. Outdoor electronic control P.C. board has been changed.
4. Noise filter P.C. board has been changed.
5. Length of fan motor lead wire has been changed.
6. Shape of relay panel has been changed.
7. Symbol on terminal block has been changed (to S1/S2/S3).
8. Control method between indoor and outdoor unit has been changed.
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/ materials are required. Refer to the table below. 2 Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installation, since it is more susceptible to contaminations than R22. 3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant piping.) 4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent composition change.
Page 5
5
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
()
NOTE: The unit of pressure has been changed to MPa on the
international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm2 [Gauge])
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No: Not substitutable for R410A Yes: Substitutable for R410A
No 12.7 mm and 15.88 mm
1. Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system).
The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm2 [Gauge])
New Specification Current Specification
The incompatible refrigerant oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerant oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerant oil are compatible with each other, refrigerant oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerant oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerant oil /Refrigerant
Compressor
Page 6
6
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter (mm)
6.35
9.52
12.7
15.88
17 22 26 29
Dimension of flare nut (mm)
R22
17 22 24 27
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient. 2 Flaring work and flare nut Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
3. Refrigerant oil
Apply the special refrigerant oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4. Air purge
Do not discharge the refrigerant into the atmosphere. Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit. Use the vacuum pump for air purging for the purpose of environmental protection.
5. Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
2. Refrigerant piping
1 Specifications Use the refrigerant pipes that meet the following specifications.
Wall thicknessOutside diameter
Pipe
mm mm
For liquid
For gas
6.35
9.52
9.52
12.7
15.88
0.8
0.8
0.8
0.8
1.0
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
Page 7
77
3
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
Air inlet
Air outlet
Drain outlet
Piping
Drain hose
(back and side)
ACCESSORIES
Drain socket
1
SUZ-KA25VAR1.TH SUZ-KA35VAR1.TH
SUZ-KA25VA.TH SUZ-KA35VA.TH
SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH
OUTDOOR UNIT
Air inlet
Piping
Air outlet
(back and side)
Drain hose
Drain outlet
ACCESSORIES
Drain socket Drain cap :33
1 2
SUZ-KA50VA
(1).TH
SUZ-KA60VA(1).TH SUZ-KA71VA
(1).TH
SUZ-KA50VAR2.TH SUZ-KA60VAR2.TH
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA50VAR2.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH SUZ-KA60VAR2.TH
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
SUZ-KA25VAR1.TH SUZ-KA35VAR1.TH SUZ-KA25VAHR1.TH SUZ-KA35VAHR1.TH
Page 8
8
SPECIFICATION
4
Function
Power supply
Outdoor Service Ref.
Starting current *1 Compressor motor current *1 Fan motor current *1 Model Output Winding resistance (at 20) Model
Winding resistance(at 20)
Air flow(High/Low+) Dimensions WHD
Weight Sound level
*1 Fan speed(High+/Low+, High+/Med+/Low+) Fan speed regulator Refrigerant filling capacity(R410A) Refrigerating oil (Model)
A A A
W
*/h
mm
kg dB
rpm
kg cc
Single phase
230V, 50Hz
3.65
KNB073FDVH(C)
550
U-V 1.53 U-W 1.53
V-W 1.53
RC0J50-AL
WHT-BLK 37.5
BLK-RED 37.5
RED-WHT 37.5
800%550%285
33
46
0.90
320 (NEO22)
Cooling
2.74
0.31
2,058
810+/650
+
2
880+/810+/650
+
3
810+/650
+
2
880+/810+/650
+
3
Heating
3.37
0.28
1,938
SUZ-KA25VA(H).TH
Compressor
Fan
motor
Special
remarks
Electrical
data
SUZ-KA25VA(H)R1.TH
Single phase
230V, 50Hz
3.65
KNB073FFDH(C)
550
U-V 1.70 U-W 1.70
V-W 1.70
RC0J50-DB
WHT-BLK 37.0
BLK-RED 37.0
RED-WHT 37.0
800%550%285
30 46
0.80
320 (NEO22)
Cooling
2.74
0.31
2,058
Heating
3.37
0.28
1,938
SUZ-KA50VA.TH
SUZ-KA50VA
1.TH
Single phase
230V, 50Hz
6.75
0.30
SNB130FLDH or SNB130FLDH1
850
U-V 0.45 U-W 0.45
V-W 0.45
RC0J60-AA
WHT-BLK 15.2
BLK-RED 15.2
RED-WHT 15.2
840%850%330
53
2
1.60
FLDH: 450/FLDH1: 600(NEO22)
Cooling
6.45
2,940/1,650
+
53/51
+
800/480
+
Heating
6.05
2,940/2,210
+
55/53
+
800/620
+
Capa-
city
SUZ-KA35VA(H)R1.TH
840+/760
+
2
880+/800+/630
+
3
SUZ-KA35VA(H).TH
Single phase
230V, 50Hz
4.75
KNB092FCAH
650
U-V 0.49 U-W 0.49
V-W 0.49
RC0J50-AL
WHT-BLK 37.5
BLK-RED 37.5
RED-WHT 37.5
2,004
800%550%285
37
1.05
320 (NEO22)
Cooling
4.22
0.33
47
Heating
4.42
0.33
48
840+/760
+
2
880+/800+/630
+
3
Single phase
230V, 50Hz
4.75
KNB092FFAH(C)
650
U-V 1.91 U-W 1.91
V-W 1.91
RC0J50-DB
WHT-BLK 37.0
BLK-RED 37.0
RED-WHT 37.0
2,004
800%550%285
33
1.05
320 (NEO22)
Cooling
4.22
0.33
47
Heating
4.42
0.33
48
NOTE : Test conditions are based on ISO 5151 Cooling : Indoor D.B. 27: W.B. 19 : Outdoor D.B. 35: W.B. 24: Heating : Indoor D.B. 20: W.B. 15: Outdoor D.B. 7: W.B. 6: Refrigerant piping length (one way): 5m *1 Measured under rated operating frequency. w Reference value
Page 9
99
SUZ-KA50VAR2.TH
SUZ-KA60VA.TH
SUZ-KA60VA
1.TH
SUZ-KA71VA.TH
SUZ-KA71VA
1.TH
SUZ-KA60VAR2.TH
Function
Power supply
Outdoor Service Ref.
Starting current *1 Compressor motor current *1 Fan motor current *1 Model Output Winding resistance (at 20) Model
Winding resistance(at 20)
Air flow(High/Low+) Dimensions WHD
Weight Sound level
*1 Fan speed(High+/Low+, High+/Med+/Low+) Fan speed regulator Refrigerant filling capacity(R410A) Refrigerating oil (Model)
A A A
W
* /h
mm
kg
dB
rpm
kg cc
Compressor
Fan
motor
Special
remarks
Electrical
data
Single phase
230V, 50Hz
10.30
0.30
TNB220FMCH(T)
1300
U-V 1.41 U-W 1.41
V-W 1.41
RC0J60-AA
WHT-BLK 15.2
BLK-RED 15.2
RED-WHT 15.2
840%850%330
58
2
2.00
870 (NEO22)
Cooling
10.00
2,940/1650
+
53/51
+
800/480
+
Heating
9.60
2,940/2,210
+
55/53
+
800/620
+
Capa-
city
Single phase
230V, 50Hz
6.75
0.30
SNB130FGBH(T)
900
U-V 0.98 U-W 0.98
V-W 0.98
RC0J60-AA
WHT-BLK 15.2
BLK-RED 15.2
RED-WHT 15.2
840%850%330
53
2
1.60
450 (NEO22)
Cooling
6.45
2,940/1,650
+
53/51
+
800/480
+
Heating
6.05
2,940/2,210
+
55/53
+
800/620
+
Single phase
230V, 50Hz
9.75
0.30
SNB130FLDH or SNB130FLDH1
850
U-V 0.45 U-W 0.45
V-W 0.45
RC0J60-AA
WHT-BLK 15.2
BLK-RED 15.2
RED-WHT 15.2
840%850%330
53
2
1.80
FLDH: 450/FLDH1: 600 (NEO22)
Cooling
8.05
2,940/1650
+
53/51
+
800/480
+
Heating
9.45
2,940/2,210
+
55/53
+
800/620
+
Single phase
230V, 50Hz
9.75
0.30
SNB130FGBH(T)
900
U-V 0.98 U-W 0.98
V-W 0.98
RC0J60-AA
WHT-BLK 15.2
BLK-RED 15.2
RED-WHT 15.2
840%850%330
53
2
1.80
450 (NEO22)
Cooling
8.05
2,940/1650
+
53/51
+
800/480
+
Heating
9.45
2,940/2,210
+
55/53
+
800/620
+
NOTE : Test conditions are based on ISO 5151 Cooling : Indoor D.B. 27: W.B. 19 : Outdoor D.B. 35: W.B. 24: Heating : Indoor D.B. 20: W.B. 15: Outdoor D.B. 7: W.B. 6: Refrigerant piping length (one way): 5m *1 Measured under rated operating frequency. w Reference value
Page 10
10
Model
Item Current transformer Current transformer Smoothing capacitor Diode module Fuse Fuse Defrost heater Intelligent power module Expansion valve coil Reactor Current-detecting resistor Current-detecting resistor Current-limiting resistor Terminal block Relay Relay Relay R.V. coil Heater protector
SUZ-KA25VA.TH
(CT) (CT761, CT781) (
C63A, C63B, C63C
)
(DB61, DB65)
(F61)
(F71, F801, F901)
(H)
(IPM)
(LEV)
(L61)
(R61)
(R831)
(
R64A, R64B
)
(TB1,TB2)
(X63) (X64) (X66)
(21S4)
(26H)
SUZ-KA25VAH.TH SUZ-KA35VA.TH SUZ-KA35VAH.TH
ETA19Z59BZ
ETQ19Z71AY
620420V
D25×B60
250V 20A
250V 3.15A
PS21244-A-203
CAD-MD12ME 12VDC
10A 23.0mH
25m 5W
5.1 5W 3P
G5NB-1a
G4A-1A-PS
STF-01AJ503
230V 130W
G5NB-1a
Open 45
230V 130W
G5NB-1a
Open 45
45m 5W (1 element) 50m 5W (2 elements)
Specifications and rating conditions of main electric parts
Model
Item
Smoothing capacitor Current transformer Current transformer Fuse Fuse Fuse Intelligent power module High pressure switch Intelligent power module Reactor Expansion valve coil Power factor controller Resistor Resistor Resistor Solenoid coil relay Terminal block Terminal block Relay R.V. coil
(CB1,2,3)
(CT1,2)
(CT61)
(F64)
(F801)
(F911)
(HC930)
(HPS)
(IPM)
(L)
(LEV)
(PFC)
(R64A,B)
(R937A,B)
(RS1~4)
(SSR61)
(TB1) (TB2)
(X64)
(21S4)
560 450V ETQ19Z68AY ETQ19Z53AY
250V 2A
250V 3.15A
250V 1A
PS21661-RZ
PS21244-A 340μH 20A
DC12V
PS51259-A
1010W
1.12W 2%
0.04 7W TLP3506
3P 3P
G4A
AC 220 - 240V
SUZ-KA50VA.TH
SUZ-KA50VA
1.TH
SUZ-KA60VA.TH
SUZ-KA60VA
1.TH
SUZ-KA60VAR2.TH
SUZ-KA71VA.TH
SUZ-KA71VA
1.TH
ACB-DB156ACB-DB156 (for R2)
SUZ-KA25VA.TH SUZ-KA25VAH.TH SUZ-KA35VA.TH SUZ-KA35VAH.TH
SUZ-KA50VA.TH SUZ-KA50VA
1.TH
SUZ-KA60VA.TH SUZ-KA60VA
1.TH SUZ-KA60VAR2.TH
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
Page 11
11
SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH
SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
SUZ-KA50VAR2.TH
Model
Item Current
transformer
20 A(CT) 15 A(CT761, CT781)
Smoothing capacitor
620 μF 420 V
(C61)
Diode module
25 A 600 V15 A 600 V(DB61)
(DB65)
Fuse
T20AL250V(F61)
(F701, F801,
F901)
T3.15AL250V
Defrost heater
230 V
130 W
230 V
130 W
Intelligent power module
(IPM)
Expansion valve coil
DC 12 V(LEV)
23 mH(L61)Reactor
Current­detecting resistor
(R61)
45 mΩ 5 W
(1 element) (2 elements)
(R61,R62)
(2 elements)
(R825)
(R937, R938,
R939)
(R937A, R937B)
Current-limiting PTC thermistor
(PTC64,
PTC65)
3 P(TB1, TB2)Terminal block
Relay
(X63) (X64)
(21S4)R.V. coil
(TR821)IGBT
(H)
(X66)
Heater protector
(26H)
25 A 600 V
15 A 600 V 20 A 600 V
100 mΩ 5 W
180 mΩ 5 W
25 mΩ 5 W
430 mΩ 2 W
1.1 Ω 2 W
33 Ω
3 A 250 V
20 A 250 V
AC 220 - 240 V
30 A 600 V
(C62, C63)
620 μF 420 V
——
3 A 250 V
3 A 250 V
——
Open 45°C
Open 45°C
——
SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH SUZ-KA50VAR2.TH
Page 12
12
NOISE CRITERIA CURVES
5
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
SPL(dB(A))
LINE
High
Med.
FAN SPEED
HEATING
46 46
Test conditions, Cooling : Dry-bulb temperature 35Wet-bulb temperature (24)
Heating : Dry-bulb temperature 7Wet-bulb temperature 6
SUZ-KA25VA.TH SUZ-KA25VAH.TH
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
COOLING
FUNCTION
SPL(dB(A))
LINE
FAN SPEED
HEATING
47 48
Test conditions, Cooling : Dry-bulb temperature 35Wet-bulb temperature (24)
Heating : Dry-bulb temperature 7Wet-bulb temperature 6
OUTDOORUNIT
MICROPHONE
1m
High Med.
SUZ-KA35VA.TH SUZ-KA35VAH.TH
COOLING
FUNCTION
SPL(dB(A)) LINE
High
FAN SPEED
HEATING
53 55
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 35Wet-bulb temperature (24)
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Heating : Dry-bulb temperature 7Wet-bulb temperature 6
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA50VAR2.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH SUZ-KA60VAR2.TH
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH
SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
Page 13
13
6
OUTLINES AND DIMENSIONS
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) :6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) :9.52
43
35
2 holes 10×21
Drain hole :33 (SUZ-KA25/KA35VAH)
REQUIRED SPACE
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
350mm or more
200mm or more
100mm or more
100mm or more
Open two sides of left, right, or rear side.
Drain hole :42 (SUZ-KA25/KA35VA)
Unit: mm
OUTDOOR UNIT
SUZ-KA25VA.TH SUZ-KA25VAH.TH SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH SUZ-KA35VA.TH SUZ-KA35VAH.TH SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
Page 14
14
Unit: mm
30
35
155
90
198
40
515
299
66
34
51
330
360
850
430
500
80
121
840
Open as a rule 500mm or more if the front and both sides are open
100mm or more 200mm or more if there are obstacles to both sides
Open as a rule 500mm or more if the back, both sides and top are open
350mm or more
100mm or more
Service panel
Gas refrigerant pipe joint Refrigerant pipe(flared)
:12.7·····(SUZ-KA50VA) :15.88···(SUZ-KA60/KA71VA)
Liquid refrigerant pipe joint Refrigerant pipe(flared)
:6.35·····(SUZ-KA50/KA60VA) :9.52·····(SUZ-KA71VA)
REQUIRED SPACE
Drain holes :33
OUTDOOR UNIT
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA50VAR2.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH SUZ-KA60VAR2.TH
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
Page 15
1515
7
WIRING DIAGRAM
OUTDOOR UNIT
SUZ-KA25VA.TH SUZ-KA35VA.TH
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
DB61,DB65
DSA61
F61
F71
F801,F901
IC801
IPM,IC932
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
SYMBOL
R61,R831
R64A,R64B
TB1,TB2
TR821
T801
X63,X64
21S4
LEV
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
NAME
CURRENT-DETECTING RESISTOR
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
REVERSING VALVE COIL
EXPANSION VALVE COIL
NOTES:1. About the indoor side electric wiring, refer to
the indoor unit electric wiring diagram for
servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
MODELS WIRING DIAGRAM
+++
F61
GRN
~/N
230V~
12-24V
230V 50Hz
CIRCUIT BREAKER
PE
RED
BLU
WHITE
GRN/YLW
TB1
POWER
SUPPLY
L
N
TB2
S3
S1
TO INDDOR UNIT
CONNECTING
S2
RED
BLU
WHT
NR63
LDE
4
6
CN726
CN727
TB800
C63B
POWER P.C. BOARD
INVERTER P.C. BOARD
21S4
X63
CN721
1
2
L61
TAB63
3
LD69
RT61 RT62 RT64RT65
CN642
CN641
CN643
21213412
GRN
231
CN601
45
IC801
F901
IC932
CN931
315
42
1
2
3
CN932
5 42
13
MF
LD-V
LD-W
LD-U
3
1
WHT
BLK
RED
RED
V
BLK
WHT
W
U
wc
CN61
IPM
CT781
CT761
2
CN724
LEV
6
R61
N
U
V
W
P
F801
C63C
R831
DB65
DB61
TR821
C63A
T801
LDY
CN725
BLK
LD70
BLK
L63
NR64
DSA61
CT
TAB61
L62
X64
4
F71
TAB62
BLK
BLU
R64AR64B
WHT
Page 16
16
OUTDOOR UNIT
SUZ-KA25VAR1.TH SUZ-KA35VAR1.TH
NOTES:1. About the indoor side electric wiring, refer to
the indoor unit electric wiring diagram for
servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
: Terminal block
Page 17
17
OUTDOOR UNIT
SUZ-KA25VAH.TH SUZ-KA35VAH.TH
SYMBOL
CT,CT761,CT781
C63A,C63B,C63C
DB61,DB65
DSA61
F61
F71
F801,F901
IC801
IPM,IC932
LEV
SYMBOL
L61
L62,L63MCMF
NR63,NR64
RT61
RT62
RT64
RT65
R61,R831
SYMBOL
R64A,R64B
TB1,TB2
TR821
T801
X63,X64,X66
21S4H26H
NAME
CURRENT TRANSFORMER
SMOOTHING CAPACITOR
DIODE MODULE
SURGE ABSORBER
FUSE (T20AL250V)
FUSE (T3.15AL250V)
FUSE (T3.15AL250V)
INTELLIGENT POWER DEVICE
INTELLIGENT POWER MODULE
EXPANSION VALVE COIL
NAME
REACTOR
CMC COIL
COMPRESSOR
OUTDOOR FAN MOTOR
VARISTOR
DEFROST THERMISTOR
DISCHARGE TEMPERATURE THERMIST OR
FIN TEMPERATURE THERMIST OR
AMBIENT TEMPERA TURE THERMIST OR
CURRENT-DETECTING RESISTOR
NAME
CURRENT-LIMITING RESISTOR
TERMINAL BLOCK
SWITCHING POWER TRANSISTOR
TRANSFORMER
RELAY
REVERSING VALVE COIL
DEFROST HEATER
HEATER PROTECTOR
NOTES:1. About the indoor side electric wiring, refer to
the indoor unit electric wiring diagram for
servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
MODELS WIRING DIAGRAM
IC932
F901
CT
4
3
NR64 NR63
GRN
DSA61
LDE
23145
CN601
LDY
GRN
MF
RT65 RT64RT62RT61
3 12 4
5
21
3
212 4
5
1
3
CN931
CN932
431212
CN643
CN641 CN642
312
X66
CN722
1
2
YLW
BLK BLK
BLKBLK
BLK
BLK
1
2
BLK
RED
CN725
6
4
CN727
CN726
TB800
POWER P.C. BOARD
INVERTER P.C. BOARD
21S4
X63
CN721
1
2
IC801
F801
C63C
LD-V
LD-W
LD-U
3
1
WHT
BLK
RED
RED
V
BLK
WHT
W
U
MC
CN61
IPM
CT781
CT761
2
CN724
LEV
6
R61
N
U
V
W
P
L61
BLK
R831
TAB63
LD69
DB65
DB61
LD70
TR821
C63B
C63A
BLK
T801
L63
F61
TAB61
L62
X64
F71
TAB62
BLK
BLU
H
26H
+++
12-24V
TO INDDOR UNIT
CONNECTING
PE
CIRCUIT BREAKER
~/N
230V 50Hz
POWER
SUPPLY
230V
~
RED
BLU
WHITE
GRN/YLW
TB1
L
N
R64A
TB2
S3S1S2
RED
BLU
WHT
R64B
WHT
Page 18
18
OUTDOOR UNIT
SUZ-KA25VAHR1.TH SUZ-KA35VAHR1.TH
NOTES:1. About the indoor side electric wiring, refer to
the indoor unit electric wiring diagram for
servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
: Terminal block
Page 19
19
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH
R64B
YLW
230V~
12-24V
CN912
CN663
WHT
BLU
NOISE
FILTER
P.C.BOARD
BRN
TO INDOOR
UNIT
CONNECTING
RED
S3
RT65
21
CN61
13
GRN/YLW
5
PFC
GRN
LD9
POWER
BOARD
RT64
21
CN3
RED
WHT
RS2
RS1
R64A
RS3
RS4
F801
CN901
NR64
ELECTRONIC
CONTROL
P.C.BOARD
CB1
CB2
CB3
HC930
IPM
NF
BLK
BLK
BLK
BLK
WHT
RED
YLW
BLU
ORN
PNK
GRY
BLU
WHT
GRN
GRN
BLU BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK BLK
BLK
RED
BLU
L
CT2
CT1
SSR61
U
6
CN7954123 78
CN661
W
CN4
TB2
S1
1
CN601
3
S2
1567
CN702
5321
CN781
13
CN701
12
12
CN931
LD1LD2
T801
R937A
R937B
CN801
231 34512
MF
CN932
3X64
5123
LDE2
12
CT61
TAB1
F64
F911
LDE1
21S4
POWER SUPPLY
~/N 230V 50Hz
TAB2
N
PE
L
TB1
CIRCUIT
BREAKER
4
1
RED
YLW
3
2
RED
S
R
21
CN903
21
CN902
21
CN5
6543 1
CN2
27
TAB4
V
MC
W
U
V
WHT
RT61 RT62 RT68
LEV
MODELS WIRING DIAGRAM
OUTDOOR UNIT
:Terminal block :Connector
3. Symbols below indicate.
2. Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1. About the indoor side electric wiring,NOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE COIL
L
REACTOR
IPM
INTELLIGENT POWER MODULE
CT61
FUSE (T2AL 250V)
F64
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGENT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
SMOOTHING CAPACITOR
CB1~3
OUTDOOR FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMPERATURE THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B
RESISTOR
PFC
NF
NR64
VARISTOR
AMBIENT TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
21S4
REVERSING VALVE COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT65
FIN TEMPERATURE THERMISTOR
RT64
T801
TRANSFORMER
SSR61
RT68
OUTDOOR HEAT EXCHANGER
TEMPERATURE THERMISTOR
DEFROST THERMISTOR
RT62
NAME
SYMBOL
Page 20
20
SUZ-KA50VAR2.TH
POWER SUPPLY
~/N 230V 50Hz
CIRCUIT
BREAKER
TO INDOOR
UNIT
CONNECTING
230V~
12-24V
S3S1S2
TB2
BRN
BLU
RED
L
N
GRN/YLW
TB1
BLK
BRN BLU
F61
BRN
LD-E1
LD-S
LD62
LD61
L62
DSA
PTC65
PTC64
LD63
CT
F701
X64
U
U
U
6
14
12
1 3
12
1
1
3
5
1
3
5
CN724
CN641CN643CN644CN642
RT62
RT61RT65
RT68
RT64
CN932
CN931
MS
3~
INVERTER P.C. BOARD
HC930
R937B
F901
R937A
IC802
T801
F801
C61 C62C63
R61
LD66LD70
DB61
DB65
R825
TR821
IPM
LDU
LDV
LDW
N
P
U
V
W
1
1
3
3
BLKBLK
WHT
RED
WHT
RED
MS
3~
MC
U
V
W
ORN YLW
L61
X63
1 2
CN721
21S4
M
LEV
6
2. Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1. About the indoor side electric wiring,NOTES:
SYMBOL
NAME
SYMBOL
NAME
SMOOTHING CAPACITOR
FUSE (T20AL 250V)
LEV
EXPANSION VALVE COIL
L61
REACTOR
HC930,IPM
INTELLIGENT POWER DEVICE
C61,62,63
DIODE MODULE
DB61,DB65
CT
CURRENT TRANSFORMER
F701,F801,F901
INTELLIGENT POWER MODULE
F61
DSA
SURGE ABSORBER
FAN MOTOR
CIRCUIT PROTECTION
RT61
DISCHARGE TEMP. THERMISTOR
R937A, B
MF
MC
COMPRESSOR
R825
PTC64,PTC65
R61
CURRENT-DETECTING RESISTOR
AMBIENT TEMP. THERMISTOR
SWITCHING POWER TRANSISTOR
21S4
REVERSING VALVE COIL
X63,X64
RELAY
TB1,TB52
TERMINAL BLOCK
RT65
FIN TEMP. THERMISTOR
RT64
T801
TRANSFORMER
TR821
RT68
OUTDOOR HEAT EXCHANGER
TEMP. THERMISTOR
DEFROST THERMISTOR
RT62
NAME
SYMBOL
FUSE (T3.15AL 250V)
IC802
L62
REACTOR
CURRENT-DETECTING RESISTOR
CURRENT-DETECTING RESISTOR
MF
:Terminal block
3. Symbols below indicate.
OUTDOOR UNIT
Page 21
21
SUZ-KA60VAR2.TH
:Terminal block
3. Symbols below indicate.
2. Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1. About the indoor side electric wiringNOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE
L
REACTOR
IPM
INTELLIGENT POWER MODULE
CT61
FUSE (T2AL 250V)
F64
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGENT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
SMOOTHING CAPACITOR
CB1~3
FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMP. THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B
RESISTOR
PFC
NF
NR64
VARISTOR
AMBIENT TEMP. THERMISTOR
SOLENOID COIL RELAY
21S4
REVERSING VALVE COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT65
FIN TEMP. THERMISTOR
RT64
T801
TRANSFORMER
SSR61
RT68
OUTDOOR HEAT EXCHANGER TEMP. THERMISTOR
DEFROST THERMISTOR
RT62
NAME
SYMBOL
HPS
HIGH PRESSURE SWITCH
OUTDOOR UNIT
Page 22
22
SUZ-KA71VA.TH SUZ-KA71VA1.TH
BLK
CN902
12
CN903
12
TAB4
X64 3
R64A R64B
RED
2
3
1
4
L
YLW
YLW
RED
230V~
12-24V
CN912
CN663
WHT
BLU
NOISE
FILTER
P.C.BOARD
BRN
TO INDOOR
UNIT
CONNECTING
RED
S3
RT65
21
CN61
13
GRN/YLW
5
PFC
GRN
LD9
POWER
BOARD
RT64
21
CN3
HPS
RED
RED
RED
WHT
RS2
RS1 RS3
RS4
F801
CN901
NR64
CN681
ELECTRONIC
CONTROL
P.C.BOARD
CB1
CB2
CB3
HC930
IPM
NF
BLK
BLK
BLK
BLK
WHT
RED
YLW
BLU
ORN
PNK
GRY
BLU
WHT
GRN
GRN
BLU BLU
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK BLK
BLK
RED
BLU
CT2
CT1
SSR61
U
6
CN7954123 78
CN661
12
W
CN4
TB2
S1
1
CN601
3
S2
1567
CN702
5321
CN781
13
CN701
12
12
CN931
LD1LD2
T801
R937A
R937B
CN801
23134512
MF
CN932
5123
LDE2
12
CT61
TAB1
F64
F911
LDE1
21S4
POWER SUPPLY
~/N 230V 50Hz
TAB2
N
PE
L
TB1
CIRCUIT
BREAKER
S
R
21
CN5
6543 1
CN2
27
V
MC
W
U
V
WHT
RT61RT62 RT68
LEV
MODEL WIRING DIAGRAM
OUTDOOR UNIT
:Terminal block :Connector
3. Symbols below indicate.
2. Use copper conductors only (for field wiring).
diagram for servicing.
refer to the indoor unit electric wiring
1. About the indoor side electric wiring,NOTES:
SYMBOL
NAME
SYMBOL
NAME
CURRENT TRANSFORMER
FUSE (T1AL 250V)
LEV
EXPANSION VALVE COIL
L
REACTOR
IPM
INTELLIGENT POWER MODULE
HPS
HIGH PRESSURE SWITCH
CT61
CT1, 2
CURRENT TRANSFORMER
HC930
INTELLIGENT POWER MODULE
F911
F801
FUSE (T3.15AL 250V)
F64
FUSE (T2AL 250V)
SMOOTHING CAPACITORCB1~3
OUTDOOR FAN MOTOR
POWER FACTOR CONTROLLER
NOISE FILTER
RT61
DISCHARGE TEMPERATURE THERMISTOR
RS1~4
RESISTOR
R937A, B
RESISTOR
MF
MC
COMPRESSOR
R64A,B RESISTOR
PFC
NF
NR64
VARISTOR
FIN TEMPERATURE THERMISTOR
SOLENOID COIL RELAY
21S4
REVERSING VALVE COIL
X64
RELAY
TB1
TERMINAL BLOCK
TB2
TERMINAL BLOCK
RT64
T801
TRANSFORMER
SSR61
AMBIENT TEMPERATURE THERMISTOR
RT65
RT68
OUTDOOR HEAT EXCHANGER
TEMPERATURE THERMISTOR
DEFROST THERMISTOR
RT62
NAME
SYMBOL
Page 23
2323
REFRIGERANT SYSTEM DIAGRAM
8
OUTDOOR UNIT
Unit: mm
SUZ-KA25VA.TH SUZ-KA25VAH.TH
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Capillary tube :3.0×:2.0×240
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe :9.52 (with heat insulator)
Refrigerant pipe :6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Strainer #100
Muffler
Muffler
Ambient temperature thermistor RT65
Muffler
OUTDOOR UNIT
SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Ambient temperature thermistor RT65
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor RT68
Muffler
Outdoor heat exchanger
LEV
Page 24
24
OUTDOOR UNIT
SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
Unit: mm
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube ø3.0×ø1.8×600(×2)
LEV
Ambient temperature thermistor
Muffler
Capillary tube ø3.0×ø2.0×240
Outdoor heat exchanger temperature thermistor
Muffler
RT65
RT68
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe :9.52 (with heat insulator)
Refrigerant pipe :6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
Capillary tube :3.0×:1.8×600(×2)
LEV
Ambient temperature thermistor RT65
Muffler
Muffler
Muffler
OUTDOOR UNIT
SUZ-KA35VA.TH SUZ-KA35VAH.TH
Page 25
25
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH
OUTDOOR UNIT
Unit: mm
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube :3.6
×:2.4×50
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe :12.7 (SUZ-KA50VA) (with heat insulator) :15.88 (SUZ-KA60V A)
Refrigerant pipe :6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Unit: mm
SUZ-KA50VAR2.TH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainer)
Stop valve (with service port)
Capillary tube ø3.6×ø2.4×50
Compressor
4-way valve
Refrigerant pipe ø12.7 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
Muffler
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
Refrigerant flow in cooling Refrigerant flow in heating
R.V. coil heating ON cooling OFF
OUTDOOR UNIT
Page 26
26
SUZ-KA71VA.TH SUZ-KA71VA1.TH
OUTDOOR UNIT
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube :3.6×:2.4×50
Capillary tube :1.8
×:0.6×1000
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe :15.88 (with heat insulator)
Refrigerant pipe :9.52 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Oil separator
High-pressure switch
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Strainer
#100
Strainer
#100
Ambient temperature thermistor RT65
Unit:mm
Unit:mm
SUZ-KA60VAR2.TH
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube :3.6:2.450
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe :15.88 (with heat insulator)
Refrigerant pipe :6.35 (with heat insulator)
LEV
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Receiver
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
High-pressure switch
OUTDOOR UNIT
Page 27
27
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Outdoor unit
precharged
900
800
1,050
14m
270
270
7m
0
0
6m
0
0
5m
0
0
11m
180
180
Models
Refrigerant piping length (one way)
Calculation : Xg=30g/m%(Refrigerant piping length(m) - 5)
8m
90
90
9m
120
120
10m
150
150
12m
210
210
13m
240
240
15m
300
300
20m
450
450
SUZ-KA25VA.TH SUZ-KA25VAH.TH
SUZ-KA35VA.TH SUZ-KA35VAH.TH SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH
Refrigerant Piping Max. length A
+ Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
+ Max. Height
difference 12m
Indoor unit
(SLZ/SEZ)
Outdoor unit
MAX. HEIGHT DIFFERENCE
Refrigerant piping
Max. length: m
A
20
Gas
9.52
Liquid
6.35
Piping size O.D: mm
Models
SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH SUZ-KA25VAR1.TH SUZ-KA35VAR1.TH SUZ-KA25VAHR1.TH SUZ-KA35VAHR1.TH
SUZ-KA25VA.TH SUZ-KA25VAH.TH SUZ-KA25VAR1.TH SUZ-KA25VAHR1.TH SUZ-KA35VA.TH SUZ-KA35VAH.TH SUZ-KA35VAR1.TH SUZ-KA35VAHR1.TH
MAX. REFRIGERANT PIPING LENGTH
Page 28
28
Refrigerant Piping Max. length A
+ Height difference should be within 30m regardless of which unit, indoor or outdoor position is high. Max. Height difference of SUZ-KA50/60/71VA.TH : 15m
SUZ-KA50/60/71VA
1.TH : 30m
SUZ-KA50/60VAR2.TH : 30m
+ Max. Height difference 30m
Indoor unit
Outdoor unit
(SLZ/SEZ)
MAX. HEIGHT DIFFERENCE
Refrigerant piping
Max. length: m
A
30
Gas
12.7
15.88
Liquid
6.35
9.52
SUZ-KA50VA.TH
SUZ-KA50VA
1.TH
SUZ-KA50VAR2.TH
SUZ-KA60VA.TH
SUZ-KA60VA
1.TH
SUZ-KA60VAR2.TH
SUZ-KA71VA.TH
SUZ-KA71VA
1.TH
Model
Piping size O.D: mm
Refrigerant piping length (one way)
Outdoor unit
precharged
15m
160
160
20m
260
260
25m
360
360
30m
460
460
7m
0
0
10m
60
60
Model
SUZ-KA50VA.TH
SUZ-KA50VA
1.TH
SUZ-KA50VAR2.TH
SUZ-KA60VA.TH
SUZ-KA60VA
1.TH
SUZ-KA60VAR2.TH
1,600
1,800
ADDITIONAL REFRIGERANT CHARGE(R410A: g)
Calculation : Xg=20g/m o (Refrigerant piping length(m)–7)
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA50VAR2.TH SUZ-KA60VA.TH SUZ-KA60VA
1.TH SUZ-KA60VAR2.TH
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
MAX. REFRIGERANT PIPING LENGTH
Outdoor unit
precharged
2,000
0 165 440 715 990 1,265
Refrigerant piping length (one way)
15m10m7m
Model
SUZ-KA71VA.TH SUZ-KA71VA
1.TH
20m
25m 30m
Calculation : Xg=55g/m o (Refrigerant piping length(m)-7)
Page 29
2929
PERFORMANCE CURVES
9
Model
SLZ-KA25VA(L)/SUZ-KA25VA SLZ-KA35VA(L)/SUZ-KA35VA SLZ-KA50VA(L)/SUZ-KA50VA
The standard data contained in these specifications applies only to the operation of the air conditioner under normal condition. Operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage: ±10% (207~253V), 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
COOLING HEATING (1) Indoor intake air wet-bulb temperature: W.B. ˚C (1) Indoor intake air dry-bulb temperature: D.B. ˚C (2) Indoor outlet air wet-bulb temperature: W.B. ˚C (2) Indoor outlet air dry-bulb temperature: D.B. ˚C (3) Outdoor intake air dry-bulb temperature: D.B. ˚C (3) Outdoor intake air wet-bulb temperature: W.B. ˚C (4) Total input: W (4) Total input: W
Indoor air wet/dry-bulb temperature difference on the side of the chart on page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and-dry-bulb thermometers to the indoor air inlet as shown in the figure, and at least 2 sets of wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and-dry-bulb thermometers to the outdoor air inlet.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
Wet-and dry-bulb thermometers
BACK VIEW
INDOOR UNIT
OUTDOOR UNIT
Page 30
30
Indoor air Wet-bulb temperature
difference (degree)
10.8
10.0
9.2
8.5
7.7
6.9
SUZ-KA50VA
at Rated frequency
Outdoor intake air Dry-bulb temperature ()
-10-15 -5 0 5 101520253035404546
Outdoor intake air Dry-bulb temperature ()
Indoor intake air Wet-bulb temperature(
)
-15 -10 -5 0 5 10 15 20 25 30 35 40 4546
Indoor air Wet-bulb temperature
difference (degree)
8.4
7.8
7.2
6.6
6.0
5.4
SUZ-KA35VA(H)
at Rated frequency
Outdoor intake air Dry-bulb temperature ()
-10-5 0 5 101520253035404546
Outdoor intake air Dry-bulb temperature ()
Indoor intake air Wet-bulb temperature(
)
-10-5 0 5 101520253035404546
Indoor air Wet-bulb temperature
difference (degree)
SUZ-KA25VA(H)
6.4
5.9
5.4
5.0
4.5
4.1
at Rated frequency
Outdoor intake air Dry-bulb temperature () Outdoor intake air Dry-bulb temperature ()
Indoor intake air Wet-bulb temperature(
)
Indoor intake air Wet-bulb temperature()
Indoor intake air Wet-bulb temperature()
Indoor intake air Wet-bulb temperature()
-10-5 0 5 101520253035404546
-10-5 0 5 101520253035404546
Page 31
31
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0
Input correction factors
The operational frequency of compressor
Correction of Cooling total input
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0
Input correction factors
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.5
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
SUZ-KA25VA(H)
SUZ-KA35VA(H) SUZ-KA35VA(H) SUZ-KA35VA(H) SUZ-KA35VA(H)
SUZ-KA25VA(H) SUZ-KA25VA(H) SUZ-KA25VA(H)
SUZ-KA50VA SUZ-KA50VA SUZ-KA50VA SUZ-KA50VA
<How to operate fixed-frequency operation (Test run operation)>
1. Press the EMERGENCY OPERATION switch or the Test button to COOL or HEAT mode.
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor starts at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts.
6. To cancel test run operation (EMERGENCY OPERATION), press the EMERGENCY OPERATION switch or the ON/OFF button on remote controller.
NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system). The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm
2
[Gauge])
20.8
19.2
17.6
16.0
14.4
12.8
11.2
9.6
23.9
22.1
20.2
18.4
16.5
14.7
12.9
11.0
Indoor air Dry-bulb temperature
difference (degree)
Indoor intake air Dry-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Indoor intake air Dry-bulb temperature ()
SUZ-KA25VA(H)
at Rated frequency
SUZ-KA35VA(H)
at Rated frequency
28.2
26.0
23.9
21.7
19.5
17.4
15.2
13.0
SUZ-KA50VA
at Rated frequency
NOTE: The above curves are for the heating operation without any frost.
Page 32
32
Outdoor unit current(A)
15 2050256030
70 (%)
35(°C)
3
3.5
4
4.5
5
32
18
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA35VA(H)
15 205025
60
30 70 (%)
35(°C)
2
2.5
3
3.5
4
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA25VA(H)
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
2
4
6
8
10
12
14
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA25VA(H)
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA35VA(H)
2
4
6
8
10
12
14
Outdoor unit current(A)
15 2050256030
70 (%)
35(°C)
5.0
6.0
7.0
8.0
9.0
32
18
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA50VA
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA50VA
2
4
6
8
10
12
14
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
1 Both indoor and outdoor unit are under the same temperature/humidity condition.
2 Air flow : High speed 3 Operation: TEST RUN OPERATION
Dry-bulb temperature
Relative humidity(%)
20
50
25
60
30
70
HEAT operation
Condition indoor: Dry bulb temperature 20.0°C Wet bulb temperature 14.5°C Condition outdoor: Dry bulb temperature 2,7,15,20.0°C Wet bulb temperature 1,6,12,14.5°C
SUZ-KA25VA(H)
Outdoor unit current (A)
Ambient temperature(°C)
3.0
2.5
2.0
1.5
1.0
0.5
0.0 2 5 10 15 20 25()
SUZ-KA35VA(H)
Outdoor unit current (A)
Ambient temperature(°C)
4.0
3.5
3.0
2.5
2.0
1.5
1.0 2 5 10 15 20 25()
SUZ-KA50VA
Outdoor unit current (A)
Ambient temperature(°C)
7.0
6.0
5.0
4.0
3.0
2.0
1.0 2 5 10 15 20 25()
Page 33
33
Model
SEZ-KC25VA/SUZ-KA25VA SEZ-KA35VA/SUZ-KA35VA SEZ-KA50VA/SUZ-KA50VA SEZ-KA60VA/SUZ-KA60VA SEZ-KA71VA/SUZ-KA71VA
The standard data contained in these specifications applies only to the operation of the air conditioner under normal condition. Operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
Rated voltage: ±10% (207~253V), 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
COOLING HEATING (1) Indoor intake air wet-bulb temperature: W.B.˚C (1) Indoor intake air dry-bulb temperature: D.B.˚C (2) Indoor outlet air wet-bulb temperature: W.B.˚C (2) Indoor outlet air dry-bulb temperature: D.B.˚C (3) Outdoor intake air dry-bulb temperature: D.B.˚C (3) Outdoor intake air wet-bulb temperature: W.B.˚C (4) Total input: W (4) Total input: W
Indoor air wet/dry-bulb temperature difference on the side of the chart on page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and-dry-bulb thermometers to the indoor air inlet as shown in the figure, and at least 2 sets of wet-and-dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet-and-dry-bulb thermometers to the outdoor air inlet.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the TEST button twice to start the COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
Air outlet
Air inlet
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
BACK VIEW
INDOOR UNIT
OUTDOOR UNIT
w The picture is SEZ-KA35, 50, 60, 71VA. SEZ-KC25VA is similar to SEZ-KA35, 50, 60, 71VA.
Page 34
34
8.4
7.8
7.2
6.6
6.0
5.4
8.6
8.0
7.4
6.8
6.2
5.5
10.5
9.6
8.8
7.9
7.1
6.3
8.4
7.8
7.2
6.6
6.0
5.4
7.9
7.3
6.7
6.2
5.6
5.1
Indoor air Wet-bulb temperature
difference (degree)
SUZ-KA50VA
at Rated frequency
SUZ-KA60VA
at Rated frequency
SUZ-KA71VA
at Rated frequency
Outdoor intake air Dry-bulb temperature ()
-10-15 -5 0 5 101520253035404546
Outdoor intake air Dry-bulb temperature ()
Indoor intake air Wet-bulb temperature(
)
-15 -10 -5 0 5 10 15 20 25 30 35 40 4546
Indoor air Wet-bulb temperature
difference (degree)
SUZ-KA35VA(H)
at Rated frequency
Outdoor intake air Dry-bulb temperature ()
-10-5 0 5 101520253035404546
Outdoor intake air Dry-bulb temperature ()
Indoor intake air Wet-bulb temperature(
)
-10-5 0 5 101520253035404546
Indoor air Wet-bulb temperature
difference (degree)
SUZ-KA25VA(H)
at Rated frequency
Outdoor intake air Dry-bulb temperature () Outdoor intake air Dry-bulb temperature ()
Indoor intake air Wet-bulb temperature(
)
-10-5 0 5 101520253035404546
-10-5 0 5 101520253035404546
Indoor intake air Wet-bulb temperature()
Indoor intake air Wet-bulb temperature(
)
Indoor intake air Wet-bulb temperature()
Page 35
35
25.2
23.2
21.3
19.4
17.4
15.5
13.6
11.6
Indoor air Dry-bulb temperature
difference (degree)
Indoor intake air Dry-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Indoor intake air Dry-bulb temperature ()
SUZ-KA25VA(H)
at Rated frequency
22.7
20.9
19.2
17.4
15.7
14.0
12.2
10.5
SUZ-KA35VA(H)
at Rated frequency
24.5
22.6
20.7
18.9
17.0
15.1
13.2
11.3
SUZ-KA50VA
at Rated frequency
25.3
23.3
21.4
19.4
17.5
15.5
13.6
11.7
SUZ-KA60VA
at Rated frequency
Indoor air Dry-bulb temperature
difference (degree)
Indoor intake air Dry-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Outdoor intake air Wet-bulb temperature ()
Indoor intake air Dry-bulb temperature ()
25.3
23.3
21.4
19.4
17.5
15.5
13.6
11.7
SUZ-KA71VA
at Rated frequency
Heating capacity
Heating capacity
Total input (heating)
Total input (heating)
NOTE: The above curves are for the heating operation without any frost.
Page 36
36
SUZ-KA25VA(H)
SUZ-KA25VA(H) SUZ-KA25VA(H) SUZ-KA25VA(H)
SUZ-KA35VA(H)
SUZ-KA35VA(H) SUZ-KA35VA(H) SUZ-KA35VA(H)
SUZ-KA50VA
SUZ-KA50VA SUZ-KA50VA SUZ-KA50VA
SUZ-KA60VA
SUZ-KA60VA SUZ-KA60VA SUZ-KA60VA
SUZ-KA71VA
SUZ-KA71VA SUZ-KA71VA SUZ-KA71VA
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
Correction of Cooling capacity
Capacity correction factors
The operational frequency of compressor
Correction of Cooling total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
0.0
0.5
1.0
1.5
2.0
1.5
1.0
0.5
0.0
Correction of
Heating total input
Input correction factors
The operational frequency of compressor
0 50 100 150(Hz)
2.0
1.5
1.0
0.5
0.0 0 50 100 150(Hz)
Correction of Heating capacity
Capacity correction factors
The operational frequency of compressor
Page 37
37
15 205025
60
30 70 (%)
35(°C)
6
7
8
9
10
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA50VA
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA50VA
2
4
6
8
10
12
14
15 205025
60
30 70 (%)
35(°C)
3
3.5
4
4.5
5
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA35VA(H)
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA35VA(H)
2
4
6
8
10
12
14
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA25VA(H)
2
4
6
8
10
12
14
15 205025
60
30 70 (%)
35(°C)
4
6
8
10
12
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA60VA
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA60VA
2
4
6
8
10
12
14
15 205025
60
30 70 (%)
35(°C)
2
2.5
3
3.5
4
32
18
Outdoor unit current(A)
Ambient temperature(°C) Ambient humidity(%)
SUZ-KA25VA(H)
(MPa [Gauge])
(kgf/% [Gauge])
18 32
15 2050256030
70 (%)
35(°C)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
SUZ-KA71VA
2
4
6
8
10
12
14
Ambient temperature(°C) Ambient humidity(%)
15 205025
60
30 70 (%)
35(°C)
4
6
8
10
12
32
18
Outdoor unit current(A)
SUZ-KA71VA
Dry-bulb temperature
Relative humidity(%)
20
50
25
60
30 70
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
<How to operate fixed-frequency operation (Test run operation)>
1. Press the TEST button to COOL or HEAT mode.
2. Test run operation starts and continue to operate for 30 minutes.
3. Compressor starts at rated frequency in COOL mode or 58Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts.
6. To cancel test run operation (EMERGENCY OPERATION), press the ON/OFF button on remote controller. NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system). The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm
2
[Gauge])
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
1 Both indoor and outdoor unit are under the same temperature/humidity condition.
2 Air flow : High speed 3 Operation: TEST RUN OPERATION
Page 38
38
HEAT operation
Condition indoor: Dry bulb temperature 20.0°C Wet bulb temperature 14.5°C Condition outdoor: Dry bulb temperature 2,7,15,20.0°C Wet bulb temperature 1,6,12,14.5°C
SUZ-KA25VA(H)
Outdoor unit current (A)
Ambient temperature(°C)
4.0
3.5
3.0
2.5
2.0
1.5
1.0 2 5 10 15 20 25()
SUZ-KA71VA
Outdoor unit current (A)
Ambient temperature(°C)
13.0
12.0
11.0
10.0
9.0
8.0
7.0
2 5 10 15 20 25()
SUZ-KA35VA(H)
Outdoor unit current (A)
Ambient temperature(°C)
4.0
3.5
3.0
2.5
2.0
1.5
1.0 2 5 10 15 20 25()
SUZ-KA50VA
Outdoor unit current (A)
Ambient temperature(°C)
7.0
6.0
5.0
4.0
3.0
2.0
1.0 2 5 10 15 20 25()
SUZ-KA60VA
Outdoor unit current (A)
Ambient temperature(°C)
7.0
6.0
5.0
4.0
3.0
2.0
1.0 2 5 10 15 20 25(
)
Page 39
39
2.94 2.00 0.68 552 2.81 1.91 0.68 580 2.70 1.84 0.68 607 2.60 1.77 0.68 635
3.06 1.72 0.56 580 2.94 1.65 0.56 614 2.85 1.60 0.56 628 2.75 1.54 0.56 656
2.94 2.12 0.72 552 2.81 2.03 0.72 580 2.70 1.94 0.72 607 2.60 1.87 0.72 635
3.06 1.84 0.60 580 2.94 1.76 0.60 614 2.85 1.71 0.60 628 2.75 1.65 0.60 656
3.19 1.53 0.48 600 3.08 1.48 0.48 638 3.00 1.44 0.48 656 2.88 1.38 0.48 683
2.94 2.23 0.76 552 2.81 2.14 0.76 580 2.70 2.05 0.76 607 2.60 1.98 0.76 635
3.06 1.96 0.64 580 2.94 1.88 0.64 614 2.85 1.82 0.64 628 2.75 1.76 0.64 656
3.19 1.66 0.52 600 3.08 1.60 0.52 638 3.00 1.56 0.52 656 2.88 1.50 0.52 683
2.94 2.35 0.80 552 2.81 2.25 0.80 580 2.70 2.16 0.80 607 2.60 2.08 0.80 635
3.06 2.08 0.68 580 2.94 2.00 0.68 614 2.85 1.94 0.68 628 2.75 1.87 0.68 656
3.19 1.79 0.56 600 3.08 1.72 0.56 638 3.00 1.68 0.56 656 2.88 1.61 0.56 683
3.35 1.47 0.44 628 3.23 1.42 0.44 662 3.15 1.39 0.44 683 3.05 1.34 0.44 718
3.06 2.21 0.72 580 2.94 2.12 0.72 614 2.85 2.05 0.72 628 2.75 1.98 0.72 656
3.19 1.91 0.60 600 3.08 1.85 0.60 638 3.00 1.80 0.60 656 2.88 1.73 0.60 683
3.35 1.61 0.48 628 3.23 1.55 0.48 662 3.15 1.51 0.48 683 3.05 1.46 0.48 718
2.94 2.59 0.88 552 2.81 2.48 0.88 580 2.70 2.38 0.88 607 2.60 2.29 0.88 635
3.06 2.33 0.76 580 2.94 2.23 0.76 614 2.85 2.17 0.76 628 2.75 2.09 0.76 656
3.19 2.04 0.64 600 3.08 1.97 0.64 638 3.00 1.92 0.64 656 2.88 1.84 0.64 683
3.35 1.74 0.52 628 3.23 1.68 0.52 662 3.15 1.64 0.52 683 3.05 1.59 0.52 718
3.45 1.38 0.40 662 3.35 1.34 0.40 697 3.30 1.32 0.40 718 3.20 1.28 0.40 738
2.94 2.70 0.92 552 2.81 2.59 0.92 580 2.70 2.48 0.92 607 2.60 2.39 0.92 635
3.06 2.45 0.80 580 2.94 2.35 0.80 614 2.85 2.28 0.80 628 2.75 2.20 0.80 656
3.19 2.17 0.68 600 3.08 2.09 0.68 638 3.00 2.04 0.68 656 2.88 1.96 0.68 683
3.35 1.88 0.56 628 3.23 1.81 0.56 662 3.15 1.76 0.56 683 3.05 1.71 0.56 718
3.45 1.52 0.44 662 3.35 1.47 0.44 697 3.30 1.45 0.44 718 3.20 1.41 0.44 738
2.94 2.82 0.96 552 2.81 2.70 0.96 580 2.70 2.59 0.96 607 2.60 2.50 0.96 635
3.06 2.57 0.84 580 2.94 2.47 0.84 614 2.85 2.39 0.84 628 2.75 2.31 0.84 656
3.19 2.30 0.72 600 3.08 2.21 0.72 638 3.00 2.16 0.72 656 2.88 2.07 0.72 683
3.35 2.01 0.60 628 3.23 1.94 0.60 662 3.15 1.89 0.60 683 3.05 1.83 0.60 718
3.45 1.66 0.48 662 3.35 1.61 0.48 697 3.30 1.58 0.48 718 3.20 1.54 0.48 738
2.94 2.94 1.00 552 2.81 2.81 1.00 580 2.70 2.70 1.00 607 2.60 2.60 1.00 635
3.06 2.70 0.88 580 2.94 2.59 0.88 614 2.85 2.51 0.88 628 2.75 2.42 0.88 656
3.19 2.42 0.76 600 3.08 2.34 0.76 638 3.00 2.28 0.76 656 2.88 2.19 0.76 683
3.35 2.14 0.64 628 3.23 2.06 0.64 662 3.15 2.02 0.64 683 3.05 1.95 0.64 718
3.45 1.79 0.52 662 3.35 1.74 0.52 697 3.30 1.72 0.52 718 3.20 1.66 0.52 738
2.94 2.94 1.00 552 2.81 2.81 1.00 580 2.70 2.70 1.00 607 2.60 2.60 1.00 635
3.06 2.82 0.92 580 2.94 2.70 0.92 614 2.85 2.62 0.92 628 2.75 2.53 0.92 656
3.19 2.55 0.80 600 3.08 2.46 0.80 638 3.00 2.40 0.80 656 2.88 2.30 0.80 683
3.35 2.28 0.68 628 3.23 2.19 0.68 662 3.15 2.14 0.68 683 3.05 2.07 0.68 718
3.45 1.93 0.56 662 3.35 1.88 0.56 697 3.30 1.85 0.56 718 3.20 1.79 0.56 738
2.94 2.94 1.00 552 2.81 2.81 1.00 580 2.70 2.70 1.00 607 2.60 2.60 1.00 635
3.06 2.94 0.96 580 2.94 2.82 0.96 614 2.85 2.74 0.96 628 2.75 2.64 0.96 656
3.19 2.68 0.84 600 3.08 2.58 0.84 638 3.00 2.52 0.84 656 2.88 2.42 0.84 683
3.35 2.41 0.72 628 3.23 2.32 0.72 662 3.15 2.27 0.72 683 3.05 2.20 0.72 718
3.45 2.07 0.60 662 3.35 2.01 0.60 697 3.30 1.98 0.60 718 3.20 1.92 0.60 738
2.94 2.94 1.00 552 2.81 2.81 1.00 580 2.70 2.70 1.00 607 2.60 2.60 1.00 635
3.06 3.06 1.00 580 2.94 2.94 1.00 614 2.85 2.85 1.00 628 2.75 2.75 1.00 656
3.19 2.81 0.88 600 3.08 2.71 0.88 638 3.00 2.64 0.88 656 2.88 2.53 0.88 683
3.35 2.55 0.76 628 3.23 2.45 0.76 662 3.15 2.39 0.76 683 3.05 2.32 0.76 718
3.45 2.21 0.64 662 3.35 2.14 0.64 697 3.30 2.11 0.64 718 3.20 2.05 0.64 738
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SLZ-KA25VA(L)/SUZ-KA25VA(H)
CAPACITY : 2.5(kW) INPUT : 690(W) SHF : 0.86
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 40
40
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SLZ-KA25VA(L)/SUZ-KA25VA(H)
CAPACITY : 2.5(kW) INPUT : 690(W) SHF : 0.86
2.45 1.67 0.68 676 2.25 1.53 0.68 718 2.08 1.41 0.68 745
2.58 1.44 0.56 704 2.40 1.34 0.56 738 2.23 1.25 0.56 780
2.45 1.76 0.72 676 2.25 1.62 0.72 718 2.08 1.49 0.72 745
2.58 1.55 0.60 704 2.40 1.44 0.60 738 2.23 1.34 0.60 780
2.73 1.31 0.48 731 2.55 1.22 0.48 773 2.38 1.14 0.48 800
2.45 1.86 0.76 676 2.25 1.71 0.76 718 2.08 1.58 0.76 745
2.58 1.65 0.64 704 2.40 1.54 0.64 738 2.23 1.42 0.64 780
2.73 1.42 0.52 731 2.55 1.33 0.52 773 2.38 1.24 0.52 800
2.45 1.96 0.80 676 2.25 1.80 0.80 718 2.08 1.66 0.80 745
2.58 1.75 0.68 704 2.40 1.63 0.68 738 2.23 1.51 0.68 780
2.73 1.53 0.56 731 2.55 1.43 0.56 773 2.38 1.33 0.56 800
2.88 1.27 0.44 759 2.70 1.19 0.44 794 2.55 1.12 0.44 828
2.58 1.85 0.72 704 2.40 1.73 0.72 738 2.23 1.60 0.72 780
2.73 1.64 0.60 731 2.55 1.53 0.60 773 2.38 1.43 0.60 800
2.88 1.38 0.48 759 2.70 1.30 0.48 794 2.55 1.22 0.48 828
2.45 2.16 0.88 676 2.25 1.98 0.88 718 2.08 1.83 0.88 745
2.58 1.96 0.76 704 2.40 1.82 0.76 738 2.23 1.69 0.76 780
2.73 1.74 0.64 731 2.55 1.63 0.64 773 2.38 1.52 0.64 800
2.88 1.50 0.52 759 2.70 1.40 0.52 794 2.55 1.33 0.52 828
3.03 1.21 0.40 787 2.85 1.14 0.40 821 2.68 1.07 0.40 856
2.45 2.25 0.92 676 2.25 2.07 0.92 718 2.08 1.91 0.92 745
2.58 2.06 0.80 704 2.40 1.92 0.80 738 2.23 1.78 0.80 780
2.73 1.85 0.68 731 2.55 1.73 0.68 773 2.38 1.62 0.68 800
2.88 1.61 0.56 759 2.70 1.51 0.56 794 2.55 1.43 0.56 828
3.03 1.33 0.44 787 2.85 1.25 0.44 821 2.68 1.18 0.44 856
2.45 2.35 0.96 676 2.25 2.16 0.96 718 2.08 1.99 0.96 745
2.58 2.16 0.84 704 2.40 2.02 0.84 738 2.23 1.87 0.84 780
2.73 1.96 0.72 731 2.55 1.84 0.72 773 2.38 1.71 0.72 800
2.88 1.73 0.60 759 2.70 1.62 0.60 794 2.55 1.53 0.60 828
3.03 1.45 0.48 787 2.85 1.37 0.48 821 2.68 1.28 0.48 856
2.45 2.45 1.00 676 2.25 2.25 1.00 718 2.08 2.08 1.00 745
2.58 2.27 0.88 704 2.40 2.11 0.88 738 2.23 1.96 0.88 780
2.73 2.07 0.76 731 2.55 1.94 0.76 773 2.38 1.81 0.76 800
2.88 1.84 0.64 759 2.70 1.73 0.64 794 2.55 1.63 0.64 828
3.03 1.57 0.52 787 2.85 1.48 0.52 821 2.68 1.39 0.52 856
2.45 2.45 1.00 676 2.25 2.25 1.00 718 2.08 2.08 1.00 745
2.58 2.37 0.92 704 2.40 2.21 0.92 738 2.23 2.05 0.92 780
2.73 2.18 0.80 731 2.55 2.04 0.80 773 2.38 1.90 0.80 800
2.88 1.96 0.68 759 2.70 1.84 0.68 794 2.55 1.73 0.68 828
3.03 1.69 0.56 787 2.85 1.60 0.56 821 2.68 1.50 0.56 856
2.45 2.45 1.00 676 2.25 2.25 1.00 718 2.08 2.08 1.00 745
2.58 2.47 0.96 704 2.40 2.30 0.96 738 2.23 2.14 0.96 780
2.73 2.29 0.84 731 2.55 2.14 0.84 773 2.38 2.00 0.84 800
2.88 2.07 0.72 759 2.70 1.94 0.72 794 2.55 1.84 0.72 828
3.03 1.82 0.60 787 2.85 1.71 0.60 821 2.68 1.61 0.60 856
2.45 2.45 1.00 676 2.25 2.25 1.00 718 2.08 2.08 1.00 745
2.58 2.58 1.00 704 2.40 2.40 1.00 738 2.23 2.23 1.00 780
2.73 2.40 0.88 731 2.55 2.24 0.88 773 2.38 2.09 0.88 800
2.88 2.19 0.76 759 2.70 2.05 0.76 794 2.55 1.94 0.76 828
3.03 1.94 0.64 787 2.85 1.82 0.64 821 2.68 1.71 0.64 856
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 41
41
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SLZ-KA35VA(L)/SUZ-KA35VA(H)
CAPACITY : 3.5(kW) INPUT : 1060(W) SHF : 0.77
4.11 2.43 0.59 848 3.94 2.32 0.59 890 3.78 2.23 0.59 933 3.64 2.15 0.59 975
4.29 2.02 0.47 890 4.11 1.93 0.47 943 3.99 1.88 0.47 965 3.85 1.81 0.47 1007
4.11 2.59 0.63 848 3.94 2.48 0.63 890 3.78 2.38 0.63 933 3.64 2.29 0.63 975
4.29 2.19 0.51 890 4.11 2.10 0.51 943 3.99 2.03 0.51 965 3.85 1.96 0.51 1007
4.46 1.74 0.39 922 4.31 1.68 0.39 981 4.20 1.64 0.39 1007 4.03 1.57 0.39 1049
4.11 2.76 0.67 848 3.94 2.64 0.67 890 3.78 2.53 0.67 933 3.64 2.44 0.67 975
4.29 2.36 0.55 890 4.11 2.26 0.55 943 3.99 2.19 0.55 965 3.85 2.12 0.55 1007
4.46 1.92 0.43 922 4.31 1.85 0.43 981 4.20 1.81 0.43 1007 4.03 1.73 0.43 1049
4.11 2.92 0.71 848 3.94 2.80 0.71 890 3.78 2.68 0.71 933 3.64 2.58 0.71 975
4.29 2.53 0.59 890 4.11 2.43 0.59 943 3.99 2.35 0.59 965 3.85 2.27 0.59 1007
4.46 2.10 0.47 922 4.31 2.02 0.47 981 4.20 1.97 0.47 1007 4.03 1.89 0.47 1049
4.69 1.64 0.35 965 4.52 1.58 0.35 1018 4.41 1.54 0.35 1049 4.27 1.49 0.35 1102
4.29 2.70 0.63 890 4.11 2.59 0.63 943 3.99 2.51 0.63 965 3.85 2.43 0.63 1007
4.46 2.28 0.51 922 4.31 2.20 0.51 981 4.20 2.14 0.51 1007 4.03 2.05 0.51 1049
4.69 1.83 0.39 965 4.52 1.76 0.39 1018 4.41 1.72 0.39 1049 4.27 1.67 0.39 1102
4.11 3.25 0.79 848 3.94 3.11 0.79 890 3.78 2.99 0.79 933 3.64 2.88 0.79 975
4.29 2.87 0.67 890 4.11 2.76 0.67 943 3.99 2.67 0.67 965 3.85 2.58 0.67 1007
4.46 2.45 0.55 922 4.31 2.37 0.55 981 4.20 2.31 0.55 1007 4.03 2.21 0.55 1049
4.69 2.02 0.43 965 4.52 1.94 0.43 1018 4.41 1.90 0.43 1049 4.27 1.84 0.43 1102
4.83 1.50 0.31 1018 4.69 1.45 0.31 1071 4.62 1.43 0.31 1102 4.48 1.39 0.31 1134
4.11 3.41 0.83 848 3.94 3.27 0.83 890 3.78 3.14 0.83 933 3.64 3.02 0.83 975
4.29 3.04 0.71 890 4.11 2.92 0.71 943 3.99 2.83 0.71 965 3.85 2.73 0.71 1007
4.46 2.63 0.59 922 4.31 2.54 0.59 981 4.20 2.48 0.59 1007 4.03 2.37 0.59 1049
4.69 2.20 0.47 965 4.52 2.12 0.47 1018 4.41 2.07 0.47 1049 4.27 2.01 0.47 1102
4.83 1.69 0.35 1018 4.69 1.64 0.35 1071 4.62 1.62 0.35 1102 4.48 1.57 0.35 1134
4.11 3.58 0.87 848 3.94 3.43 0.87 890 3.78 3.29 0.87 933 3.64 3.17 0.87 975
4.29 3.22 0.75 890 4.11 3.08 0.75 943 3.99 2.99 0.75 965 3.85 2.89 0.75 1007
4.46 2.81 0.63 922 4.31 2.71 0.63 981 4.20 2.65 0.63 1007 4.03 2.54 0.63 1049
4.69 2.39 0.51 965 4.52 2.30 0.51 1018 4.41 2.25 0.51 1049 4.27 2.18 0.51 1102
4.83 1.88 0.39 1018 4.69 1.83 0.39 1071 4.62 1.80 0.39 1102 4.48 1.75 0.39 1134
4.11 3.74 0.91 848 3.94 3.58 0.91 890 3.78 3.44 0.91 933 3.64 3.31 0.91 975
4.29 3.39 0.79 890 4.11 3.25 0.79 943 3.99 3.15 0.79 965 3.85 3.04 0.79 1007
4.46 2.99 0.67 922 4.31 2.88 0.67 981 4.20 2.81 0.67 1007 4.03 2.70 0.67 1049
4.69 2.58 0.55 965 4.52 2.48 0.55 1018 4.41 2.43 0.55 1049 4.27 2.35 0.55 1102
4.83 2.08 0.43 1018 4.69 2.02 0.43 1071 4.62 1.99 0.43 1102 4.48 1.93 0.43 1134
4.11 3.91 0.95 848 3.94 3.74 0.95 890 3.78 3.59 0.95 933 3.64 3.46 0.95 975
4.29 3.56 0.83 890 4.11 3.41 0.83 943 3.99 3.31 0.83 965 3.85 3.20 0.83 1007
4.46 3.17 0.71 922 4.31 3.06 0.71 981 4.20 2.98 0.71 1007 4.03 2.86 0.71 1049
4.69 2.77 0.59 965 4.52 2.66 0.59 1018 4.41 2.60 0.59 1049 4.27 2.52 0.59 1102
4.83 2.27 0.47 1018 4.69 2.20 0.47 1071 4.62 2.17 0.47 1102 4.48 2.11 0.47 1134
4.11 4.07 0.99 848 3.94 3.90 0.99 890 3.78 3.74 0.99 933 3.64 3.60 0.99 975
4.29 3.73 0.87 890 4.11 3.58 0.87 943 3.99 3.47 0.87 965 3.85 3.35 0.87 1007
4.46 3.35 0.75 922 4.31 3.23 0.75 981 4.20 3.15 0.75 1007 4.03 3.02 0.75 1049
4.69 2.95 0.63 965 4.52 2.84 0.63 1018 4.41 2.78 0.63 1049 4.27 2.69 0.63 1102
4.83 2.46 0.51 1018 4.69 2.39 0.51 1071 4.62 2.36 0.51 1102 4.48 2.28 0.51 1134
4.11 4.11 1.00 848 3.94 3.94 1.00 890 3.78 3.78 1.00 933 3.64 3.64 1.00 975
4.29 3.90 0.91 890 4.11 3.74 0.91 943 3.99 3.63 0.91 965 3.85 3.50 0.91 1007
4.46 3.53 0.79 922 4.31 3.40 0.79 981 4.20 3.32 0.79 1007 4.03 3.18 0.79 1049
4.69 3.14 0.67 965 4.52 3.03 0.67 1018 4.41 2.95 0.67 1049 4.27 2.86 0.67 1102
4.83 2.66 0.55 1018 4.69 2.58 0.55 1071 4.62 2.54 0.55 1102 4.48 2.46 0.55 1134
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 42
42
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SLZ-KA35VA(L)/SUZ-KA35VA(H)
CAPACITY : 3.5(kW) INPUT : 1060(W) SHF : 0.77
3.43 2.02 0.59 1039 3.15 1.86 0.59 1102 2.91 1.71 0.59 1145
3.61 1.69 0.47 1081 3.36 1.58 0.47 1134 3.12 1.46 0.47 1198
3.43 2.16 0.63 1039 3.15 1.98 0.63 1102 2.91 1.83 0.63 1145
3.61 1.84 0.51 1081 3.36 1.71 0.51 1134 3.12 1.59 0.51 1198
3.82 1.49 0.39 1124 3.57 1.39 0.39 1187 3.33 1.30 0.39 1230
3.43 2.30 0.67 1039 3.15 2.11 0.67 1102 2.91 1.95 0.67 1145
3.61 1.98 0.55 1081 3.36 1.85 0.55 1134 3.12 1.71 0.55 1198
3.82 1.64 0.43 1124 3.57 1.54 0.43 1187 3.33 1.43 0.43 1230
3.43 2.44 0.71 1039 3.15 2.24 0.71 1102 2.91 2.06 0.71 1145
3.61 2.13 0.59 1081 3.36 1.98 0.59 1134 3.12 1.84 0.59 1198
3.82 1.79 0.47 1124 3.57 1.68 0.47 1187 3.33 1.56 0.47 1230
4.03 1.41 0.35 1166 3.78 1.32 0.35 1219 3.57 1.25 0.35 1272
3.61 2.27 0.63 1081 3.36 2.12 0.63 1134 3.12 1.96 0.63 1198
3.82 1.95 0.51 1124 3.57 1.82 0.51 1187 3.33 1.70 0.51 1230
4.03 1.57 0.39 1166 3.78 1.47 0.39 1219 3.57 1.39 0.39 1272
3.43 2.71 0.79 1039 3.15 2.49 0.79 1102 2.91 2.29 0.79 1145
3.61 2.42 0.67 1081 3.36 2.25 0.67 1134 3.12 2.09 0.67 1198
3.82 2.10 0.55 1124 3.57 1.96 0.55 1187 3.33 1.83 0.55 1230
4.03 1.73 0.43 1166 3.78 1.63 0.43 1219 3.57 1.54 0.43 1272
4.24 1.31 0.31 1208 3.99 1.24 0.31 1261 3.75 1.16 0.31 1314
3.43 2.85 0.83 1039 3.15 2.61 0.83 1102 2.91 2.41 0.83 1145
3.61 2.56 0.71 1081 3.36 2.39 0.71 1134 3.12 2.21 0.71 1198
3.82 2.25 0.59 1124 3.57 2.11 0.59 1187 3.33 1.96 0.59 1230
4.03 1.89 0.47 1166 3.78 1.78 0.47 1219 3.57 1.68 0.47 1272
4.24 1.48 0.35 1208 3.99 1.40 0.35 1261 3.75 1.31 0.35 1314
3.43 2.98 0.87 1039 3.15 2.74 0.87 1102 2.91 2.53 0.87 1145
3.61 2.70 0.75 1081 3.36 2.52 0.75 1134 3.12 2.34 0.75 1198
3.82 2.40 0.63 1124 3.57 2.25 0.63 1187 3.33 2.09 0.63 1230
4.03 2.05 0.51 1166 3.78 1.93 0.51 1219 3.57 1.82 0.51 1272
4.24 1.65 0.39 1208 3.99 1.56 0.39 1261 3.75 1.46 0.39 1314
3.43 3.12 0.91 1039 3.15 2.87 0.91 1102 2.91 2.64 0.91 1145
3.61 2.85 0.79 1081 3.36 2.65 0.79 1134 3.12 2.46 0.79 1198
3.82 2.56 0.67 1124 3.57 2.39 0.67 1187 3.33 2.23 0.67 1230
4.03 2.21 0.55 1166 3.78 2.08 0.55 1219 3.57 1.96 0.55 1272
4.24 1.82 0.43 1208 3.99 1.72 0.43 1261 3.75 1.61 0.43 1314
3.43 3.26 0.95 1039 3.15 2.99 0.95 1102 2.91 2.76 0.95 1145
3.61 2.99 0.83 1081 3.36 2.79 0.83 1134 3.12 2.59 0.83 1198
3.82 2.71 0.71 1124 3.57 2.53 0.71 1187 3.33 2.36 0.71 1230
4.03 2.37 0.59 1166 3.78 2.23 0.59 1219 3.57 2.11 0.59 1272
4.24 1.99 0.47 1208 3.99 1.88 0.47 1261 3.75 1.76 0.47 1314
3.43 3.40 0.99 1039 3.15 3.12 0.99 1102 2.91 2.88 0.99 1145
3.61 3.14 0.87 1081 3.36 2.92 0.87 1134 3.12 2.71 0.87 1198
3.82 2.86 0.75 1124 3.57 2.68 0.75 1187 3.33 2.49 0.75 1230
4.03 2.54 0.63 1166 3.78 2.38 0.63 1219 3.57 2.25 0.63 1272
4.24 2.16 0.51 1208 3.99 2.03 0.51 1261 3.75 1.91 0.51 1314
3.43 3.43 1.00 1039 3.15 3.15 1.00 1102 2.91 2.91 1.00 1145
3.61 3.28 0.91 1081 3.36 3.06 0.91 1134 3.12 2.83 0.91 1198
3.82 3.01 0.79 1124 3.57 2.82 0.79 1187 3.33 2.63 0.79 1230
4.03 2.70 0.67 1166 3.78 2.53 0.67 1219 3.57 2.39 0.67 1272
4.24 2.33 0.55 1208 3.99 2.19 0.55 1261 3.75 2.06 0.55 1314
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 43
43
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
5.41
5.64
5.41
5.64
5.87
5.41
5.64
5.87
5.41
5.64
5.87
6.16
5.64
5.87
6.16
5.41
5.64
5.87
6.16
6.35
5.41
5.64
5.87
6.16
6.35
5.41
5.64
5.87
6.16
6.35
5.41
5.64
5.87
6.16
6.35
5.41
5.64
5.87
6.16
6.35
5.41
5.64
5.87
6.16
6.35
5.41
5.64
5.87
6.16
6.35
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1304 1369 1304 1369 1418 1304 1369 1418 1304 1369 1418 1483 1369 1418 1483 1304 1369 1418 1483 1565 1304 1369 1418 1483 1565 1304 1369 1418 1483 1565 1304 1369 1418 1483 1565 1304 1369 1418 1483 1565 1304 1369 1418 1483 1565 1304 1369 1418 1483 1565
2.70
2.14
2.92
2.37
1.76
3.13
2.59
1.99
3.35
2.82
2.23
1.60
3.04
2.46
1.85
3.78
3.27
2.70
2.10
1.40
4.00
3.49
2.93
2.34
1.65
4.22
3.72
3.17
2.59
1.90
4.43
3.94
3.40
2.84
2.16
4.65
4.17
3.64
3.08
2.41
4.86
4.40
3.87
3.33
2.67
5.08
4.62
4.11
3.58
2.92
5.18
5.41
5.18
5.41
5.66
5.18
5.41
5.66
5.18
5.41
5.66
5.93
5.41
5.66
5.93
5.18
5.41
5.66
5.93
6.16
5.18
5.41
5.66
5.93
6.16
5.18
5.41
5.66
5.93
6.16
5.18
5.41
5.66
5.93
6.16
5.18
5.41
5.66
5.93
6.16
5.18
5.41
5.66
5.93
6.16
5.18
5.41
5.66
5.93
6.16
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1369 1451 1369 1451 1508 1369 1451 1508 1369 1451 1508 1565 1451 1508 1565 1369 1451 1508 1565 1646 1369 1451 1508 1565 1646 1369 1451 1508 1565 1646 1369 1451 1508 1565 1646 1369 1451 1508 1565 1646 1369 1451 1508 1565 1646 1369 1451 1508 1565 1646
2.59
2.05
2.79
2.27
1.70
3.00
2.49
1.92
3.21
2.70
2.15
1.54
2.92
2.38
1.78
3.62
3.13
2.60
2.02
1.36
3.83
3.35
2.83
2.25
1.60
4.04
3.57
3.06
2.49
1.85
4.24
3.78
3.28
2.73
2.10
4.45
4.00
3.51
2.97
2.34
4.66
4.22
3.73
3.20
2.59
4.86
4.43
3.96
3.44
2.84
4.97
5.24
4.97
5.24
5.52
4.97
5.24
5.52
4.97
5.24
5.52
5.80
5.24
5.52
5.80
4.97
5.24
5.52
5.80
6.07
4.97
5.24
5.52
5.80
6.07
4.97
5.24
5.52
5.80
6.07
4.97
5.24
5.52
5.80
6.07
4.97
5.24
5.52
5.80
6.07
4.97
5.24
5.52
5.80
6.07
4.97
5.24
5.52
5.80
6.07
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1434 1483 1434 1483 1549 1434 1483 1549 1434 1483 1549 1614 1483 1549 1614 1434 1483 1549 1614 1695 1434 1483 1549 1614 1695 1434 1483 1549 1614 1695 1434 1483 1549 1614 1695 1434 1483 1549 1614 1695 1434 1483 1549 1614 1695 1434 1483 1549 1614 1695
2.48
1.99
2.68
2.20
1.66
2.88
2.41
1.88
3.08
2.62
2.10
1.51
2.83
2.32
1.74
3.48
3.04
2.54
1.97
1.34
3.68
3.25
2.76
2.20
1.58
3.88
3.46
2.98
2.43
1.82
4.07
3.67
3.20
2.67
2.06
4.27
3.88
3.42
2.90
2.31
4.47
4.09
3.64
3.13
2.55
4.67
4.30
3.86
3.36
2.79
4.78
5.06
4.78
5.06
5.29
4.78
5.06
5.29
4.78
5.06
5.29
5.61
5.06
5.29
5.61
4.78
5.06
5.29
5.61
5.89
4.78
5.06
5.29
5.61
5.89
4.78
5.06
5.29
5.61
5.89
4.78
5.06
5.29
5.61
5.89
4.78
5.06
5.29
5.61
5.89
4.78
5.06
5.29
5.61
5.89
4.78
5.06
5.29
5.61
5.89
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1500 1549 1500 1549 1614 1500 1549 1614 1500 1549 1614 1695 1549 1614 1695 1500 1549 1614 1695 1744 1500 1549 1614 1695 1744 1500 1549 1614 1695 1744 1500 1549 1614 1695 1744 1500 1549 1614 1695 1744 1500 1549 1614 1695 1744 1500 1549 1614 1695 1744
2.39
1.92
2.58
2.13
1.59
2.77
2.33
1.80
2.97
2.53
2.01
1.46
2.73
2.22
1.68
3.35
2.93
2.43
1.91
1.30
3.54
3.14
2.65
2.13
1.53
3.73
3.34
2.86
2.36
1.77
3.92
3.54
3.07
2.58
2.00
4.11
3.74
3.28
2.81
2.24
4.31
3.95
3.49
3.03
2.47
4.50
4.15
3.70
3.25
2.71
PERFORMANCE DATA COOLING operation at Rated frequency SLZ-KA50VA(L)/SUZ-KA50VA
CAPACITY : 4.6(kW) INPUT : 1630(W) SHF : 0.68
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 44
44
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
4.51
4.74
4.51
4.74
5.01
4.51
4.74
5.01
4.51
4.74
5.01
5.29
4.74
5.01
5.29
4.51
4.74
5.01
5.29
5.57
4.51
4.74
5.01
5.29
5.57
4.51
4.74
5.01
5.29
5.57
4.51
4.74
5.01
5.29
5.57
4.51
4.74
5.01
5.29
5.57
4.51
4.74
5.01
5.29
5.57
4.51
4.74
5.01
5.29
5.57
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1597 1663 1597 1663 1728 1597 1663 1728 1597 1663 1728 1793 1663 1728 1793 1597 1663 1728 1793 1858 1597 1663 1728 1793 1858 1597 1663 1728 1793 1858 1597 1663 1728 1793 1858 1597 1663 1728 1793 1858 1597 1663 1728 1793 1858 1597 1663 1728 1793 1858
2.25
1.80
2.43
1.99
1.50
2.61
2.18
1.70
2.79
2.37
1.91
1.38
2.56
2.11
1.59
3.16
2.75
2.31
1.80
1.22
3.34
2.94
2.51
2.01
1.45
3.52
3.13
2.71
2.22
1.67
3.70
3.32
2.91
2.43
1.89
3.88
3.51
3.11
2.65
2.12
4.06
3.70
3.31
2.86
2.34
4.24
3.89
3.51
3.07
2.56
4.14
4.42
4.14
4.42
4.69
4.14
4.42
4.69
4.14
4.42
4.69
4.97
4.42
4.69
4.97
4.14
4.42
4.69
4.97
5.24
4.14
4.42
4.69
4.97
5.24
4.14
4.42
4.69
4.97
5.24
4.14
4.42
4.69
4.97
5.24
4.14
4.42
4.69
4.97
5.24
4.14
4.42
4.69
4.97
5.24
4.14
4.42
4.69
4.97
5.24
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1695 1744 1695 1744 1826 1695 1744 1826 1695 1744 1826 1875 1744 1826 1875 1695 1744 1826 1875 1940 1695 1744 1826 1875 1940 1695 1744 1826 1875 1940 1695 1744 1826 1875 1940 1695 1744 1826 1875 1940 1695 1744 1826 1875 1940 1695 1744 1826 1875 1940
2.07
1.68
2.24
1.85
1.41
2.40
2.03
1.60
2.57
2.21
1.78
1.29
2.38
1.97
1.49
2.90
2.56
2.16
1.69
1.15
3.06
2.74
2.35
1.89
1.36
3.23
2.91
2.53
2.09
1.57
3.39
3.09
2.72
2.29
1.78
3.56
3.27
2.91
2.48
1.99
3.73
3.44
3.10
2.68
2.20
3.89
3.62
3.28
2.88
2.41
3.82
4.09
3.82
4.09
4.37
3.82
4.09
4.37
3.82
4.09
4.37
4.69
4.09
4.37
4.69
3.82
4.09
4.37
4.69
4.92
3.82
4.09
4.37
4.69
4.92
3.82
4.09
4.37
4.69
4.92
3.82
4.09
4.37
4.69
4.92
3.82
4.09
4.37
4.69
4.92
3.82
4.09
4.37
4.69
4.92
3.82
4.09
4.37
4.69
4.92
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1760 1842 1760 1842 1891 1760 1842 1891 1760 1842 1891 1956 1842 1891 1956 1760 1842 1891 1956 2021 1760 1842 1891 1956 2021 1760 1842 1891 1956 2021 1760 1842 1891 1956 2021 1760 1842 1891 1956 2021 1760 1842 1891 1956 2021 1760 1842 1891 1956 2021
1.91
1.56
2.06
1.72
1.31
2.21
1.88
1.49
2.37
2.05
1.66
1.22
2.21
1.84
1.41
2.67
2.37
2.01
1.60
1.08
2.83
2.54
2.19
1.78
1.28
2.98
2.70
2.36
1.97
1.48
3.13
2.87
2.53
2.16
1.67
3.28
3.03
2.71
2.35
1.87
3.44
3.19
2.88
2.53
2.07
3.59
3.36
3.06
2.72
2.26
PERFORMANCE DATA COOLING operation at Rated frequency SLZ-KA50VA(L)/SUZ-KA50VA
CAPACITY : 4.6(kW) INPUT : 1630(W) SHF : 0.68
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 45
45
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KC25VA/SUZ-KA25VA(H)
CAPACITY : 2.5(kW) INPUT : 730(W) SHF : 0.74
2.94 1.65 0.56 584 2.81 1.58 0.56 613 2.70 1.51 0.56 642 2.60 1.46 0.56 672
3.06 1.35 0.44 613 2.94 1.29 0.44 650 2.85 1.25 0.44 664 2.75 1.21 0.44 694
2.94 1.76 0.60 584 2.81 1.69 0.60 613 2.70 1.62 0.60 642 2.60 1.56 0.60 672
3.06 1.47 0.48 613 2.94 1.41 0.48 650 2.85 1.37 0.48 664 2.75 1.32 0.48 694
3.19 1.15 0.36 635 3.08 1.11 0.36 675 3.00 1.08 0.36 694 2.88 1.04 0.36 723
2.94 1.88 0.64 584 2.81 1.80 0.64 613 2.70 1.73 0.64 642 2.60 1.66 0.64 672
3.06 1.59 0.52 613 2.94 1.53 0.52 650 2.85 1.48 0.52 664 2.75 1.43 0.52 694
3.19 1.28 0.40 635 3.08 1.23 0.40 675 3.00 1.20 0.40 694 2.88 1.15 0.40 723
2.94 2.00 0.68 584 2.81 1.91 0.68 613 2.70 1.84 0.68 642 2.60 1.77 0.68 672
3.06 1.72 0.56 613 2.94 1.65 0.56 650 2.85 1.60 0.56 664 2.75 1.54 0.56 694
3.19 1.40 0.44 635 3.08 1.35 0.44 675 3.00 1.32 0.44 694 2.88 1.27 0.44 723
3.35 1.07 0.32 664 3.23 1.03 0.32 701 3.15 1.01 0.32 723 3.05 0.98 0.32 759
3.06 1.84 0.60 613 2.94 1.76 0.60 650 2.85 1.71 0.60 664 2.75 1.65 0.60 694
3.19 1.53 0.48 635 3.08 1.48 0.48 675 3.00 1.44 0.48 694 2.88 1.38 0.48 723
3.35 1.21 0.36 664 3.23 1.16 0.36 701 3.15 1.13 0.36 723 3.05 1.10 0.36 759
2.94 2.23 0.76 584 2.81 2.14 0.76 613 2.70 2.05 0.76 642 2.60 1.98 0.76 672
3.06 1.96 0.64 613 2.94 1.88 0.64 650 2.85 1.82 0.64 664 2.75 1.76 0.64 694
3.19 1.66 0.52 635 3.08 1.60 0.52 675 3.00 1.56 0.52 694 2.88 1.50 0.52 723
3.35 1.34 0.40 664 3.23 1.29 0.40 701 3.15 1.26 0.40 723 3.05 1.22 0.40 759
3.45 0.97 0.28 701 3.35 0.94 0.28 737 3.30 0.92 0.28 759 3.20 0.90 0.28 781
2.94 2.35 0.80 584 2.81 2.25 0.80 613 2.70 2.16 0.80 642 2.60 2.08 0.80 672
3.06 2.08 0.68 613 2.94 2.00 0.68 650 2.85 1.94 0.68 664 2.75 1.87 0.68 694
3.19 1.79 0.56 635 3.08 1.72 0.56 675 3.00 1.68 0.56 694 2.88 1.61 0.56 723
3.35 1.47 0.44 664 3.23 1.42 0.44 701 3.15 1.39 0.44 723 3.05 1.34 0.44 759
3.45 1.10 0.32 701 3.35 1.07 0.32 737 3.30 1.06 0.32 759 3.20 1.02 0.32 781
2.94 2.47 0.84 584 2.81 2.36 0.84 613 2.70 2.27 0.84 642 2.60 2.18 0.84 672
3.06 2.21 0.72 613 2.94 2.12 0.72 650 2.85 2.05 0.72 664 2.75 1.98 0.72 694
3.19 1.91 0.60 635 3.08 1.85 0.60 675 3.00 1.80 0.60 694 2.88 1.73 0.60 723
3.35 1.61 0.48 664 3.23 1.55 0.48 701 3.15 1.51 0.48 723 3.05 1.46 0.48 759
3.45 1.24 0.36 701 3.35 1.21 0.36 737 3.30 1.19 0.36 759 3.20 1.15 0.36 781
2.94 2.59 0.88 584 2.81 2.48 0.88 613 2.70 2.38 0.88 642 2.60 2.29 0.88 672
3.06 2.33 0.76 613 2.94 2.23 0.76 650 2.85 2.17 0.76 664 2.75 2.09 0.76 694
3.19 2.04 0.64 635 3.08 1.97 0.64 675 3.00 1.92 0.64 694 2.88 1.84 0.64 723
3.35 1.74 0.52 664 3.23 1.68 0.52 701 3.15 1.64 0.52 723 3.05 1.59 0.52 759
3.45 1.38 0.40 701 3.35 1.34 0.40 737 3.30 1.32 0.40 759 3.20 1.28 0.40 781
2.94 2.70 0.92 584 2.81 2.59 0.92 613 2.70 2.48 0.92 642 2.60 2.39 0.92 672
3.06 2.45 0.80 613 2.94 2.35 0.80 650 2.85 2.28 0.80 664 2.75 2.20 0.80 694
3.19 2.17 0.68 635 3.08 2.09 0.68 675 3.00 2.04 0.68 694 2.88 1.96 0.68 723
3.35 1.88 0.56 664 3.23 1.81 0.56 701 3.15 1.76 0.56 723 3.05 1.71 0.56 759
3.45 1.52 0.44 701 3.35 1.47 0.44 737 3.30 1.45 0.44 759 3.20 1.41 0.44 781
2.94 2.82 0.96 584 2.81 2.70 0.96 613 2.70 2.59 0.96 642 2.60 2.50 0.96 672
3.06 2.57 0.84 613 2.94 2.47 0.84 650 2.85 2.39 0.84 664 2.75 2.31 0.84 694
3.19 2.30 0.72 635 3.08 2.21 0.72 675 3.00 2.16 0.72 694 2.88 2.07 0.72 723
3.35 2.01 0.60 664 3.23 1.94 0.60 701 3.15 1.89 0.60 723 3.05 1.83 0.60 759
3.45 1.66 0.48 701 3.35 1.61 0.48 737 3.30 1.58 0.48 759 3.20 1.54 0.48 781
2.94 2.94 1.00 584 2.81 2.81 1.00 613 2.70 2.70 1.00 642 2.60 2.60 1.00 672
3.06 2.70 0.88 613 2.94 2.59 0.88 650 2.85 2.51 0.88 664 2.75 2.42 0.88 694
3.19 2.42 0.76 635 3.08 2.34 0.76 675 3.00 2.28 0.76 694 2.88 2.19 0.76 723
3.35 2.14 0.64 664 3.23 2.06 0.64 701 3.15 2.02 0.64 723 3.05 1.95 0.64 759
3.45 1.79 0.52 701 3.35 1.74 0.52 737 3.30 1.72 0.52 759 3.20 1.66 0.52 781
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 46
46
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KC25VA/SUZ-KA25VA(H)
CAPACITY : 2.5(kW) INPUT : 730(W) SHF : 0.74
2.45 1.37 0.56 715 2.25 1.26 0.56 759 2.08 1.16 0.56 788
2.58 1.13 0.44 745 2.40 1.06 0.44 781 2.23 0.98 0.44 825
2.45 1.47 0.60 715 2.25 1.35 0.60 759 2.08 1.25 0.60 788
2.58 1.24 0.48 745 2.40 1.15 0.48 781 2.23 1.07 0.48 825
2.73 0.98 0.36 774 2.55 0.92 0.36 818 2.38 0.86 0.36 847
2.45 1.57 0.64 715 2.25 1.44 0.64 759 2.08 1.33 0.64 788
2.58 1.34 0.52 745 2.40 1.25 0.52 781 2.23 1.16 0.52 825
2.73 1.09 0.40 774 2.55 1.02 0.40 818 2.38 0.95 0.40 847
2.45 1.67 0.68 715 2.25 1.53 0.68 759 2.08 1.41 0.68 788
2.58 1.44 0.56 745 2.40 1.34 0.56 781 2.23 1.25 0.56 825
2.73 1.20 0.44 774 2.55 1.12 0.44 818 2.38 1.05 0.44 847
2.88 0.92 0.32 803 2.70 0.86 0.32 840 2.55 0.82 0.32 876
2.58 1.55 0.60 745 2.40 1.44 0.60 781 2.23 1.34 0.60 825
2.73 1.31 0.48 774 2.55 1.22 0.48 818 2.38 1.14 0.48 847
2.88 1.04 0.36 803 2.70 0.97 0.36 840 2.55 0.92 0.36 876
2.45 1.86 0.76 715 2.25 1.71 0.76 759 2.08 1.58 0.76 788
2.58 1.65 0.64 745 2.40 1.54 0.64 781 2.23 1.42 0.64 825
2.73 1.42 0.52 774 2.55 1.33 0.52 818 2.38 1.24 0.52 847
2.88 1.15 0.40 803 2.70 1.08 0.40 840 2.55 1.02 0.40 876
3.03 0.85 0.28 832 2.85 0.80 0.28 869 2.68 0.75 0.28 905
2.45 1.96 0.80 715 2.25 1.80 0.80 759 2.08 1.66 0.80 788
2.58 1.75 0.68 745 2.40 1.63 0.68 781 2.23 1.51 0.68 825
2.73 1.53 0.56 774 2.55 1.43 0.56 818 2.38 1.33 0.56 847
2.88 1.27 0.44 803 2.70 1.19 0.44 840 2.55 1.12 0.44 876
3.03 0.97 0.32 832 2.85 0.91 0.32 869 2.68 0.86 0.32 905
2.45 2.06 0.84 715 2.25 1.89 0.84 759 2.08 1.74 0.84 788
2.58 1.85 0.72 745 2.40 1.73 0.72 781 2.23 1.60 0.72 825
2.73 1.64 0.60 774 2.55 1.53 0.60 818 2.38 1.43 0.60 847
2.88 1.38 0.48 803 2.70 1.30 0.48 840 2.55 1.22 0.48 876
3.03 1.09 0.36 832 2.85 1.03 0.36 869 2.68 0.96 0.36 905
2.45 2.16 0.88 715 2.25 1.98 0.88 759 2.08 1.83 0.88 788
2.58 1.96 0.76 745 2.40 1.82 0.76 781 2.23 1.69 0.76 825
2.73 1.74 0.64 774 2.55 1.63 0.64 818 2.38 1.52 0.64 847
2.88 1.50 0.52 803 2.70 1.40 0.52 840 2.55 1.33 0.52 876
3.03 1.21 0.40 832 2.85 1.14 0.40 869 2.68 1.07 0.40 905
2.45 2.25 0.92 715 2.25 2.07 0.92 759 2.08 1.91 0.92 788
2.58 2.06 0.80 745 2.40 1.92 0.80 781 2.23 1.78 0.80 825
2.73 1.85 0.68 774 2.55 1.73 0.68 818 2.38 1.62 0.68 847
2.88 1.61 0.56 803 2.70 1.51 0.56 840 2.55 1.43 0.56 876
3.03 1.33 0.44 832 2.85 1.25 0.44 869 2.68 1.18 0.44 905
2.45 2.35 0.96 715 2.25 2.16 0.96 759 2.08 1.99 0.96 788
2.58 2.16 0.84 745 2.40 2.02 0.84 781 2.23 1.87 0.84 825
2.73 1.96 0.72 774 2.55 1.84 0.72 818 2.38 1.71 0.72 847
2.88 1.73 0.60 803 2.70 1.62 0.60 840 2.55 1.53 0.60 876
3.03 1.45 0.48 832 2.85 1.37 0.48 869 2.68 1.28 0.48 905
2.45 2.45 1.00 715 2.25 2.25 1.00 759 2.08 2.08 1.00 788
2.58 2.27 0.88 745 2.40 2.11 0.88 781 2.23 1.96 0.88 825
2.73 2.07 0.76 774 2.55 1.94 0.76 818 2.38 1.81 0.76 847
2.88 1.84 0.64 803 2.70 1.73 0.64 840 2.55 1.63 0.64 876
3.03 1.57 0.52 832 2.85 1.48 0.52 869 2.68 1.39 0.52 905
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 47
47
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA35VA/SUZ-KA35VA(H)
CAPACITY : 3.5(kW) INPUT : 1060(W) SHF : 0.77
4.11 2.43 0.59 848 3.94 2.32 0.59 890 3.78 2.23 0.59 933 3.64 2.15 0.59 975
4.29 2.02 0.47 890 4.11 1.93 0.47 943 3.99 1.88 0.47 965 3.85 1.81 0.47 1007
4.11 2.59 0.63 848 3.94 2.48 0.63 890 3.78 2.38 0.63 933 3.64 2.29 0.63 975
4.29 2.19 0.51 890 4.11 2.10 0.51 943 3.99 2.03 0.51 965 3.85 1.96 0.51 1007
4.46 1.74 0.39 922 4.31 1.68 0.39 981 4.20 1.64 0.39 1007 4.03 1.57 0.39 1049
4.11 2.76 0.67 848 3.94 2.64 0.67 890 3.78 2.53 0.67 933 3.64 2.44 0.67 975
4.29 2.36 0.55 890 4.11 2.26 0.55 943 3.99 2.19 0.55 965 3.85 2.12 0.55 1007
4.46 1.92 0.43 922 4.31 1.85 0.43 981 4.20 1.81 0.43 1007 4.03 1.73 0.43 1049
4.11 2.92 0.71 848 3.94 2.80 0.71 890 3.78 2.68 0.71 933 3.64 2.58 0.71 975
4.29 2.53 0.59 890 4.11 2.43 0.59 943 3.99 2.35 0.59 965 3.85 2.27 0.59 1007
4.46 2.10 0.47 922 4.31 2.02 0.47 981 4.20 1.97 0.47 1007 4.03 1.89 0.47 1049
4.69 1.64 0.35 965 4.52 1.58 0.35 1018 4.41 1.54 0.35 1049 4.27 1.49 0.35 1102
4.29 2.70 0.63 890 4.11 2.59 0.63 943 3.99 2.51 0.63 965 3.85 2.43 0.63 1007
4.46 2.28 0.51 922 4.31 2.20 0.51 981 4.20 2.14 0.51 1007 4.03 2.05 0.51 1049
4.69 1.83 0.39 965 4.52 1.76 0.39 1018 4.41 1.72 0.39 1049 4.27 1.67 0.39 1102
4.11 3.25 0.79 848 3.94 3.11 0.79 890 3.78 2.99 0.79 933 3.64 2.88 0.79 975
4.29 2.87 0.67 890 4.11 2.76 0.67 943 3.99 2.67 0.67 965 3.85 2.58 0.67 1007
4.46 2.45 0.55 922 4.31 2.37 0.55 981 4.20 2.31 0.55 1007 4.03 2.21 0.55 1049
4.69 2.02 0.43 965 4.52 1.94 0.43 1018 4.41 1.90 0.43 1049 4.27 1.84 0.43 1102
4.83 1.50 0.31 1018 4.69 1.45 0.31 1071 4.62 1.43 0.31 1102 4.48 1.39 0.31 1134
4.11 3.41 0.83 848 3.94 3.27 0.83 890 3.78 3.14 0.83 933 3.64 3.02 0.83 975
4.29 3.04 0.71 890 4.11 2.92 0.71 943 3.99 2.83 0.71 965 3.85 2.73 0.71 1007
4.46 2.63 0.59 922 4.31 2.54 0.59 981 4.20 2.48 0.59 1007 4.03 2.37 0.59 1049
4.69 2.20 0.47 965 4.52 2.12 0.47 1018 4.41 2.07 0.47 1049 4.27 2.01 0.47 1102
4.83 1.69 0.35 1018 4.69 1.64 0.35 1071 4.62 1.62 0.35 1102 4.48 1.57 0.35 1134
4.11 3.58 0.87 848 3.94 3.43 0.87 890 3.78 3.29 0.87 933 3.64 3.17 0.87 975
4.29 3.22 0.75 890 4.11 3.08 0.75 943 3.99 2.99 0.75 965 3.85 2.89 0.75 1007
4.46 2.81 0.63 922 4.31 2.71 0.63 981 4.20 2.65 0.63 1007 4.03 2.54 0.63 1049
4.69 2.39 0.51 965 4.52 2.30 0.51 1018 4.41 2.25 0.51 1049 4.27 2.18 0.51 1102
4.83 1.88 0.39 1018 4.69 1.83 0.39 1071 4.62 1.80 0.39 1102 4.48 1.75 0.39 1134
4.11 3.74 0.91 848 3.94 3.58 0.91 890 3.78 3.44 0.91 933 3.64 3.31 0.91 975
4.29 3.39 0.79 890 4.11 3.25 0.79 943 3.99 3.15 0.79 965 3.85 3.04 0.79 1007
4.46 2.99 0.67 922 4.31 2.88 0.67 981 4.20 2.81 0.67 1007 4.03 2.70 0.67 1049
4.69 2.58 0.55 965 4.52 2.48 0.55 1018 4.41 2.43 0.55 1049 4.27 2.35 0.55 1102
4.83 2.08 0.43 1018 4.69 2.02 0.43 1071 4.62 1.99 0.43 1102 4.48 1.93 0.43 1134
4.11 3.91 0.95 848 3.94 3.74 0.95 890 3.78 3.59 0.95 933 3.64 3.46 0.95 975
4.29 3.56 0.83 890 4.11 3.41 0.83 943 3.99 3.31 0.83 965 3.85 3.20 0.83 1007
4.46 3.17 0.71 922 4.31 3.06 0.71 981 4.20 2.98 0.71 1007 4.03 2.86 0.71 1049
4.69 2.77 0.59 965 4.52 2.66 0.59 1018 4.41 2.60 0.59 1049 4.27 2.52 0.59 1102
4.83 2.27 0.47 1018 4.69 2.20 0.47 1071 4.62 2.17 0.47 1102 4.48 2.11 0.47 1134
4.11 4.07 0.99 848 3.94 3.90 0.99 890 3.78 3.74 0.99 933 3.64 3.60 0.99 975
4.29 3.73 0.87 890 4.11 3.58 0.87 943 3.99 3.47 0.87 965 3.85 3.35 0.87 1007
4.46 3.35 0.75 922 4.31 3.23 0.75 981 4.20 3.15 0.75 1007 4.03 3.02 0.75 1049
4.69 2.95 0.63 965 4.52 2.84 0.63 1018 4.41 2.78 0.63 1049 4.27 2.69 0.63 1102
4.83 2.46 0.51 1018 4.69 2.39 0.51 1071 4.62 2.36 0.51 1102 4.48 2.28 0.51 1134
4.11 4.11 1.00 848 3.94 3.94 1.00 890 3.78 3.78 1.00 933 3.64 3.64 1.00 975
4.29 3.90 0.91 890 4.11 3.74 0.91 943 3.99 3.63 0.91 965 3.85 3.50 0.91 1007
4.46 3.53 0.79 922 4.31 3.40 0.79 981 4.20 3.32 0.79 1007 4.03 3.18 0.79 1049
4.69 3.14 0.67 965 4.52 3.03 0.67 1018 4.41 2.95 0.67 1049 4.27 2.86 0.67 1102
4.83 2.66 0.55 1018 4.69 2.58 0.55 1071 4.62 2.54 0.55 1102 4.48 2.46 0.55 1134
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 48
48
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA35VA/SUZ-KA35VA(H)
CAPACITY : 3.5(kW) INPUT : 1060(W) SHF : 0.77
3.43 2.02 0.59 1039 3.15 1.86 0.59 1102 2.91 1.71 0.59 1145
3.61 1.69 0.47 1081 3.36 1.58 0.47 1134 3.12 1.46 0.47 1198
3.43 2.16 0.63 1039 3.15 1.98 0.63 1102 2.91 1.83 0.63 1145
3.61 1.84 0.51 1081 3.36 1.71 0.51 1134 3.12 1.59 0.51 1198
3.82 1.49 0.39 1124 3.57 1.39 0.39 1187 3.33 1.30 0.39 1230
3.43 2.30 0.67 1039 3.15 2.11 0.67 1102 2.91 1.95 0.67 1145
3.61 1.98 0.55 1081 3.36 1.85 0.55 1134 3.12 1.71 0.55 1198
3.82 1.64 0.43 1124 3.57 1.54 0.43 1187 3.33 1.43 0.43 1230
3.43 2.44 0.71 1039 3.15 2.24 0.71 1102 2.91 2.06 0.71 1145
3.61 2.13 0.59 1081 3.36 1.98 0.59 1134 3.12 1.84 0.59 1198
3.82 1.79 0.47 1124 3.57 1.68 0.47 1187 3.33 1.56 0.47 1230
4.03 1.41 0.35 1166 3.78 1.32 0.35 1219 3.57 1.25 0.35 1272
3.61 2.27 0.63 1081 3.36 2.12 0.63 1134 3.12 1.96 0.63 1198
3.82 1.95 0.51 1124 3.57 1.82 0.51 1187 3.33 1.70 0.51 1230
4.03 1.57 0.39 1166 3.78 1.47 0.39 1219 3.57 1.39 0.39 1272
3.43 2.71 0.79 1039 3.15 2.49 0.79 1102 2.91 2.29 0.79 1145
3.61 2.42 0.67 1081 3.36 2.25 0.67 1134 3.12 2.09 0.67 1198
3.82 2.10 0.55 1124 3.57 1.96 0.55 1187 3.33 1.83 0.55 1230
4.03 1.73 0.43 1166 3.78 1.63 0.43 1219 3.57 1.54 0.43 1272
4.24 1.31 0.31 1208 3.99 1.24 0.31 1261 3.75 1.16 0.31 1314
3.43 2.85 0.83 1039 3.15 2.61 0.83 1102 2.91 2.41 0.83 1145
3.61 2.56 0.71 1081 3.36 2.39 0.71 1134 3.12 2.21 0.71 1198
3.82 2.25 0.59 1124 3.57 2.11 0.59 1187 3.33 1.96 0.59 1230
4.03 1.89 0.47 1166 3.78 1.78 0.47 1219 3.57 1.68 0.47 1272
4.24 1.48 0.35 1208 3.99 1.40 0.35 1261 3.75 1.31 0.35 1314
3.43 2.98 0.87 1039 3.15 2.74 0.87 1102 2.91 2.53 0.87 1145
3.61 2.70 0.75 1081 3.36 2.52 0.75 1134 3.12 2.34 0.75 1198
3.82 2.40 0.63 1124 3.57 2.25 0.63 1187 3.33 2.09 0.63 1230
4.03 2.05 0.51 1166 3.78 1.93 0.51 1219 3.57 1.82 0.51 1272
4.24 1.65 0.39 1208 3.99 1.56 0.39 1261 3.75 1.46 0.39 1314
3.43 3.12 0.91 1039 3.15 2.87 0.91 1102 2.91 2.64 0.91 1145
3.61 2.85 0.79 1081 3.36 2.65 0.79 1134 3.12 2.46 0.79 1198
3.82 2.56 0.67 1124 3.57 2.39 0.67 1187 3.33 2.23 0.67 1230
4.03 2.21 0.55 1166 3.78 2.08 0.55 1219 3.57 1.96 0.55 1272
4.24 1.82 0.43 1208 3.99 1.72 0.43 1261 3.75 1.61 0.43 1314
3.43 3.26 0.95 1039 3.15 2.99 0.95 1102 2.91 2.76 0.95 1145
3.61 2.99 0.83 1081 3.36 2.79 0.83 1134 3.12 2.59 0.83 1198
3.82 2.71 0.71 1124 3.57 2.53 0.71 1187 3.33 2.36 0.71 1230
4.03 2.37 0.59 1166 3.78 2.23 0.59 1219 3.57 2.11 0.59 1272
4.24 1.99 0.47 1208 3.99 1.88 0.47 1261 3.75 1.76 0.47 1314
3.43 3.40 0.99 1039 3.15 3.12 0.99 1102 2.91 2.88 0.99 1145
3.61 3.14 0.87 1081 3.36 2.92 0.87 1134 3.12 2.71 0.87 1198
3.82 2.86 0.75 1124 3.57 2.68 0.75 1187 3.33 2.49 0.75 1230
4.03 2.54 0.63 1166 3.78 2.38 0.63 1219 3.57 2.25 0.63 1272
4.24 2.16 0.51 1208 3.99 2.03 0.51 1261 3.75 1.91 0.51 1314
3.43 3.43 1.00 1039 3.15 3.15 1.00 1102 2.91 2.91 1.00 1145
3.61 3.28 0.91 1081 3.36 3.06 0.91 1134 3.12 2.83 0.91 1198
3.82 3.01 0.79 1124 3.57 2.82 0.79 1187 3.33 2.63 0.79 1230
4.03 2.70 0.67 1166 3.78 2.53 0.67 1219 3.57 2.39 0.67 1272
4.24 2.33 0.55 1208 3.99 2.19 0.55 1261 3.75 2.06 0.55 1314
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 49
49
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
5.88
6.13
5.88
6.13
6.38
5.88
6.13
6.38
5.88
6.13
6.38
6.70
6.13
6.38
6.70
5.88
6.13
6.38
6.70
6.90
5.88
6.13
6.38
6.70
6.90
5.88
6.13
6.38
6.70
6.90
5.88
6.13
6.38
6.70
6.90
5.88
6.13
6.38
6.70
6.90
5.88
6.13
6.38
6.70
6.90
5.88
6.13
6.38
6.70
6.90
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1424 1495 1424 1495 1549 1424 1495 1549 1424 1495 1549 1620 1495 1549 1620 1424 1495 1549 1620 1709 1424 1495 1549 1620 1709 1424 1495 1549 1620 1709 1424 1495 1549 1620 1709 1424 1495 1549 1620 1709 1424 1495 1549 1620 1709 1424 1495 1549 1620 1709
3.35
2.76
3.58
3.00
2.36
3.82
3.25
2.61
4.05
3.49
2.87
2.21
3.74
3.12
2.48
4.52
3.98
3.38
2.75
2.00
4.76
4.23
3.63
3.02
2.28
4.99
4.47
3.89
3.28
2.55
5.23
4.72
4.14
3.55
2.83
5.46
4.96
4.40
3.82
3.11
5.70
5.21
4.65
4.09
3.38
5.88
5.45
4.91
4.36
3.66
5.63
5.88
5.63
5.88
6.15
5.63
5.88
6.15
5.63
5.88
6.15
6.45
5.88
6.15
6.45
5.63
5.88
6.15
6.45
6.70
5.63
5.88
6.15
6.45
6.70
5.63
5.88
6.15
6.45
6.70
5.63
5.88
6.15
6.45
6.70
5.63
5.88
6.15
6.45
6.70
5.63
5.88
6.15
6.45
6.70
5.63
5.88
6.15
6.45
6.70
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1495 1584 1495 1584 1647 1495 1584 1647 1495 1584 1647 1709 1584 1647 1709 1495 1584 1647 1709 1798 1495 1584 1647 1709 1798 1495 1584 1647 1709 1798 1495 1584 1647 1709 1798 1495 1584 1647 1709 1798 1495 1584 1647 1709 1798 1495 1584 1647 1709 1798
3.21
2.64
3.43
2.88
2.28
3.66
3.11
2.52
3.88
3.35
2.77
2.13
3.58
3.01
2.39
4.33
3.82
3.26
2.64
1.94
4.56
4.05
3.51
2.90
2.21
4.78
4.29
3.75
3.16
2.48
5.01
4.52
4.00
3.42
2.75
5.23
4.76
4.24
3.68
3.02
5.46
4.99
4.49
3.93
3.28
5.63
5.23
4.74
4.19
3.55
5.40
5.70
5.40
5.70
6.00
5.40
5.70
6.00
5.40
5.70
6.00
6.30
5.70
6.00
6.30
5.40
5.70
6.00
6.30
6.60
5.40
5.70
6.00
6.30
6.60
5.40
5.70
6.00
6.30
6.60
5.40
5.70
6.00
6.30
6.60
5.40
5.70
6.00
6.30
6.60
5.40
5.70
6.00
6.30
6.60
5.40
5.70
6.00
6.30
6.60
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1566 1620 1566 1620 1691 1566 1620 1691 1566 1620 1691 1762 1620 1691 1762 1566 1620 1691 1762 1851 1566 1620 1691 1762 1851 1566 1620 1691 1762 1851 1566 1620 1691 1762 1851 1566 1620 1691 1762 1851 1566 1620 1691 1762 1851 1566 1620 1691 1762 1851
3.08
2.57
3.29
2.79
2.22
3.51
3.02
2.46
3.73
3.25
2.70
2.08
3.48
2.94
2.33
4.16
3.71
3.18
2.58
1.91
4.37
3.93
3.42
2.84
2.18
4.59
4.16
3.66
3.09
2.44
4.81
4.39
3.90
3.34
2.71
5.02
4.62
4.14
3.59
2.97
5.24
4.85
4.38
3.84
3.23
5.40
5.07
4.62
4.10
3.50
5.20
5.50
5.20
5.50
5.75
5.20
5.50
5.75
5.20
5.50
5.75
6.10
5.50
5.75
6.10
5.20
5.50
5.75
6.10
6.40
5.20
5.50
5.75
6.10
6.40
5.20
5.50
5.75
6.10
6.40
5.20
5.50
5.75
6.10
6.40
5.20
5.50
5.75
6.10
6.40
5.20
5.50
5.75
6.10
6.40
5.20
5.50
5.75
6.10
6.40
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1638 1691 1638 1691 1762 1638 1691 1762 1638 1691 1762 1851 1691 1762 1851 1638 1691 1762 1851 1905 1638 1691 1762 1851 1905 1638 1691 1762 1851 1905 1638 1691 1762 1851 1905 1638 1691 1762 1851 1905 1638 1691 1762 1851 1905 1638 1691 1762 1851 1905
2.96
2.48
3.17
2.70
2.13
3.38
2.92
2.36
3.59
3.14
2.59
2.01
3.36
2.82
2.26
4.00
3.58
3.05
2.50
1.86
4.21
3.80
3.28
2.75
2.11
4.42
4.02
3.51
2.99
2.37
4.63
4.24
3.74
3.23
2.62
4.84
4.46
3.97
3.48
2.88
5.04
4.68
4.20
3.72
3.14
5.20
4.90
4.43
3.97
3.39
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA50VA/SUZ-KA50VA
CAPACITY : 5.0(kW) INPUT : 1780(W) SHF : 0.75
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 50
50
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
4.90
5.15
4.90
5.15
5.45
4.90
5.15
5.45
4.90
5.15
5.45
5.75
5.15
5.45
5.75
4.90
5.15
5.45
5.75
6.05
4.90
5.15
5.45
5.75
6.05
4.90
5.15
5.45
5.75
6.05
4.90
5.15
5.45
5.75
6.05
4.90
5.15
5.45
5.75
6.05
4.90
5.15
5.45
5.75
6.05
4.90
5.15
5.45
5.75
6.05
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1744 1816 1744 1816 1887 1744 1816 1887 1744 1816 1887 1958 1816 1887 1958 1744 1816 1887 1958 2029 1744 1816 1887 1958 2029 1744 1816 1887 1958 2029 1744 1816 1887 1958 2029 1744 1816 1887 1958 2029 1744 1816 1887 1958 2029 1744 1816 1887 1958 2029
2.79
2.32
2.99
2.52
2.02
3.19
2.73
2.23
3.38
2.94
2.45
1.90
3.14
2.67
2.13
3.77
3.35
2.89
2.36
1.75
3.97
3.55
3.11
2.59
2.00
4.17
3.76
3.32
2.82
2.24
4.36
3.97
3.54
3.05
2.48
4.56
4.17
3.76
3.28
2.72
4.75
4.38
3.98
3.51
2.96
4.90
4.58
4.20
3.74
3.21
4.50
4.80
4.50
4.80
5.10
4.50
4.80
5.10
4.50
4.80
5.10
5.40
4.80
5.10
5.40
4.50
4.80
5.10
5.40
5.70
4.50
4.80
5.10
5.40
5.70
4.50
4.80
5.10
5.40
5.70
4.50
4.80
5.10
5.40
5.70
4.50
4.80
5.10
5.40
5.70
4.50
4.80
5.10
5.40
5.70
4.50
4.80
5.10
5.40
5.70
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1851 1905 1851 1905 1994 1851 1905 1994 1851 1905 1994 2047 1905 1994 2047 1851 1905 1994 2047 2118 1851 1905 1994 2047 2118 1851 1905 1994 2047 2118 1851 1905 1994 2047 2118 1851 1905 1994 2047 2118 1851 1905 1994 2047 2118 1851 1905 1994 2047 2118
2.57
2.16
2.75
2.35
1.89
2.93
2.54
2.09
3.11
2.74
2.30
1.78
2.93
2.50
2.00
3.47
3.12
2.70
2.21
1.65
3.65
3.31
2.91
2.43
1.88
3.83
3.50
3.11
2.65
2.11
4.01
3.70
3.32
2.86
2.34
4.19
3.89
3.52
3.08
2.57
4.37
4.08
3.72
3.29
2.79
4.50
4.27
3.93
3.51
3.02
4.15
4.45
4.15
4.45
4.75
4.15
4.45
4.75
4.15
4.45
4.75
5.10
4.45
4.75
5.10
4.15
4.45
4.75
5.10
5.35
4.15
4.45
4.75
5.10
5.35
4.15
4.45
4.75
5.10
5.35
4.15
4.45
4.75
5.10
5.35
4.15
4.45
4.75
5.10
5.35
4.15
4.45
4.75
5.10
5.35
4.15
4.45
4.75
5.10
5.35
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1922 2011 1922 2011 2065 1922 2011 2065 1922 2011 2065 2136 2011 2065 2136 1922 2011 2065 2136 2207 1922 2011 2065 2136 2207 1922 2011 2065 2136 2207 1922 2011 2065 2136 2207 1922 2011 2065 2136 2207 1922 2011 2065 2136 2207 1922 2011 2065 2136 2207
2.37
2.00
2.53
2.18
1.76
2.70
2.36
1.95
2.86
2.54
2.14
1.68
2.71
2.33
1.89
3.20
2.89
2.52
2.09
1.55
3.36
3.07
2.71
2.30
1.77
3.53
3.25
2.90
2.50
1.98
3.69
3.43
3.09
2.70
2.19
3.86
3.60
3.28
2.91
2.41
4.03
3.78
3.47
3.11
2.62
4.15
3.96
3.66
3.32
2.84
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA50VA/SUZ-KA50VA
CAPACITY : 5.0(kW) INPUT : 1780(W) SHF : 0.75
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 51
51
OUTDOOR D.B.()
INDOOR INDOOR
21 25 27 30
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
6.46
6.74
6.46
6.74
7.01
6.46
6.74
7.01
6.46
6.74
7.01
7.37
6.74
7.01
7.37
6.46
6.74
7.01
7.37
7.59
6.46
6.74
7.01
7.37
7.59
6.46
6.74
7.01
7.37
7.59
6.46
6.74
7.01
7.37
7.59
6.46
6.74
7.01
7.37
7.59
6.46
6.74
7.01
7.37
7.59
6.46
6.74
7.01
7.37
7.59
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1568 1646 1568 1646 1705 1568 1646 1705 1568 1646 1705 1784 1646 1705 1784 1568 1646 1705 1784 1882 1568 1646 1705 1784 1882 1568 1646 1705 1784 1882 1568 1646 1705 1784 1882 1568 1646 1705 1784 1882 1568 1646 1705 1784 1882 1568 1646 1705 1784 1882
3.68
3.03
3.94
3.30
2.59
4.20
3.57
2.88
4.46
3.84
3.16
2.43
4.11
3.44
2.73
4.98
4.38
3.72
3.02
2.20
5.23
4.65
4.00
3.32
2.50
5.49
4.92
4.28
3.61
2.81
5.75
5.19
4.56
3.91
3.11
6.01
5.46
4.84
4.20
3.42
6.27
5.73
5.12
4.50
3.72
6.46
6.00
5.40
4.79
4.02
6.19
6.46
6.19
6.46
6.77
6.19
6.46
6.77
6.19
6.46
6.77
7.10
6.46
6.77
7.10
6.19
6.46
6.77
7.10
7.37
6.19
6.46
6.77
7.10
7.37
6.19
6.46
6.77
7.10
7.37
6.19
6.46
6.77
7.10
7.37
6.19
6.46
6.77
7.10
7.37
6.19
6.46
6.77
7.10
7.37
6.19
6.46
6.77
7.10
7.37
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1646 1744 1646 1744 1813 1646 1744 1813 1646 1744 1813 1882 1744 1813 1882 1646 1744 1813 1882 1980 1646 1744 1813 1882 1980 1646 1744 1813 1882 1980 1646 1744 1813 1882 1980 1646 1744 1813 1882 1980 1646 1744 1813 1882 1980 1646 1744 1813 1882 1980
3.53
2.91
3.77
3.17
2.50
4.02
3.43
2.77
4.27
3.68
3.04
2.34
3.94
3.31
2.63
4.76
4.20
3.59
2.91
2.14
5.01
4.46
3.86
3.19
2.43
5.26
4.72
4.13
3.48
2.73
5.51
4.98
4.40
3.76
3.02
5.75
5.23
4.67
4.04
3.32
6.00
5.49
4.94
4.33
3.61
6.19
5.75
5.21
4.61
3.91
5.94
6.27
5.94
6.27
6.60
5.94
6.27
6.60
5.94
6.27
6.60
6.93
6.27
6.60
6.93
5.94
6.27
6.60
6.93
7.26
5.94
6.27
6.60
6.93
7.26
5.94
6.27
6.60
6.93
7.26
5.94
6.27
6.60
6.93
7.26
5.94
6.27
6.60
6.93
7.26
5.94
6.27
6.60
6.93
7.26
5.94
6.27
6.60
6.93
7.26
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1725 1784 1725 1784 1862 1725 1784 1862 1725 1784 1862 1940 1784 1862 1940 1725 1784 1862 1940 2038 1725 1784 1862 1940 2038 1725 1784 1862 1940 2038 1725 1784 1862 1940 2038 1725 1784 1862 1940 2038 1725 1784 1862 1940 2038 1725 1784 1862 1940 2038
3.39
2.82
3.62
3.07
2.44
3.86
3.32
2.71
4.10
3.57
2.97
2.29
3.82
3.23
2.56
4.57
4.08
3.50
2.84
2.11
4.81
4.33
3.76
3.12
2.40
5.05
4.58
4.03
3.40
2.69
5.29
4.83
4.29
3.67
2.98
5.52
5.08
4.55
3.95
3.27
5.76
5.33
4.82
4.23
3.56
5.94
5.58
5.08
4.50
3.85
5.72
6.05
5.72
6.05
6.33
5.72
6.05
6.33
5.72
6.05
6.33
6.71
6.05
6.33
6.71
5.72
6.05
6.33
6.71
7.04
5.72
6.05
6.33
6.71
7.04
5.72
6.05
6.33
6.71
7.04
5.72
6.05
6.33
6.71
7.04
5.72
6.05
6.33
6.71
7.04
5.72
6.05
6.33
6.71
7.04
5.72
6.05
6.33
6.71
7.04
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1803 1862 1803 1862 1940 1803 1862 1940 1803 1862 1940 2038 1862 1940 2038 1803 1862 1940 2038 2097 1803 1862 1940 2038 2097 1803 1862 1940 2038 2097 1803 1862 1940 2038 2097 1803 1862 1940 2038 2097 1803 1862 1940 2038 2097 1803 1862 1940 2038 2097
3.26
2.72
3.49
2.96
2.34
3.72
3.21
2.59
3.95
3.45
2.85
2.21
3.69
3.10
2.48
4.40
3.93
3.35
2.75
2.04
4.63
4.17
3.61
3.02
2.32
4.86
4.42
3.86
3.29
2.60
5.09
4.66
4.11
3.56
2.89
5.32
4.90
4.36
3.82
3.17
5.55
5.14
4.62
4.09
3.45
5.72
5.38
4.87
4.36
3.73
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA60VA/SUZ-KA60VA
CAPACITY : 5.5(kW) INPUT : 1960(W) SHF : 0.75
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 52
52
OUTDOOR D.B.()
INDOOR INDOOR
35 40 46
D.B.() W.B.()
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
5.39
5.67
5.39
5.67
6.00
5.39
5.67
6.00
5.39
5.67
6.00
6.33
5.67
6.00
6.33
5.39
5.67
6.00
6.33
6.66
5.39
5.67
6.00
6.33
6.66
5.39
5.67
6.00
6.33
6.66
5.39
5.67
6.00
6.33
6.66
5.39
5.67
6.00
6.33
6.66
5.39
5.67
6.00
6.33
6.66
5.39
5.67
6.00
6.33
6.66
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
1921 1999 1921 1999 2078 1921 1999 2078 1921 1999 2078 2156 1999 2078 2156 1921 1999 2078 2156 2234 1921 1999 2078 2156 2234 1921 1999 2078 2156 2234 1921 1999 2078 2156 2234 1921 1999 2078 2156 2234 1921 1999 2078 2156 2234 1921 1999 2078 2156 2234
3.07
2.55
3.29
2.78
2.22
3.50
3.00
2.46
3.72
3.23
2.70
2.09
3.46
2.94
2.34
4.15
3.68
3.18
2.59
1.93
4.37
3.91
3.42
2.85
2.20
4.58
4.14
3.66
3.10
2.46
4.80
4.36
3.90
3.35
2.73
5.01
4.59
4.14
3.61
2.99
5.23
4.82
4.38
3.86
3.26
5.39
5.04
4.62
4.11
3.53
4.95
5.28
4.95
5.28
5.61
4.95
5.28
5.61
4.95
5.28
5.61
5.94
5.28
5.61
5.94
4.95
5.28
5.61
5.94
6.27
4.95
5.28
5.61
5.94
6.27
4.95
5.28
5.61
5.94
6.27
4.95
5.28
5.61
5.94
6.27
4.95
5.28
5.61
5.94
6.27
4.95
5.28
5.61
5.94
6.27
4.95
5.28
5.61
5.94
6.27
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
2038 2097 2038 2097 2195 2038 2097 2195 2038 2097 2195 2254 2097 2195 2254 2038 2097 2195 2254 2332 2038 2097 2195 2254 2332 2038 2097 2195 2254 2332 2038 2097 2195 2254 2332 2038 2097 2195 2254 2332 2038 2097 2195 2254 2332 2038 2097 2195 2254 2332
2.82
2.38
3.02
2.59
2.08
3.22
2.80
2.30
3.42
3.01
2.52
1.96
3.22
2.75
2.20
3.81
3.43
2.97
2.44
1.82
4.01
3.64
3.20
2.67
2.07
4.21
3.85
3.42
2.91
2.32
4.41
4.07
3.65
3.15
2.57
4.60
4.28
3.87
3.39
2.82
4.80
4.49
4.10
3.62
3.07
4.95
4.70
4.32
3.86
3.32
4.57
4.90
4.57
4.90
5.23
4.57
4.90
5.23
4.57
4.90
5.23
5.61
4.90
5.23
5.61
4.57
4.90
5.23
5.61
5.89
4.57
4.90
5.23
5.61
5.89
4.57
4.90
5.23
5.61
5.89
4.57
4.90
5.23
5.61
5.89
4.57
4.90
5.23
5.61
5.89
4.57
4.90
5.23
5.61
5.89
4.57
4.90
5.23
5.61
5.89
0.57
0.45
0.61
0.49
0.37
0.65
0.53
0.41
0.69
0.57
0.45
0.33
0.61
0.49
0.37
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
0.97
0.85
0.73
0.61
0.49
1.00
0.89
0.77
0.65
0.53
2117 2215 2117 2215 2274 2117 2215 2274 2117 2215 2274 2352 2215 2274 2352 2117 2215 2274 2352 2430 2117 2215 2274 2352 2430 2117 2215 2274 2352 2430 2117 2215 2274 2352 2430 2117 2215 2274 2352 2430 2117 2215 2274 2352 2430 2117 2215 2274 2352 2430
2.60
2.20
2.78
2.40
1.93
2.97
2.59
2.14
3.15
2.79
2.35
1.85
2.99
2.56
2.08
3.52
3.18
2.77
2.30
1.71
3.70
3.38
2.98
2.52
1.94
3.88
3.57
3.19
2.75
2.18
4.06
3.77
3.40
2.97
2.41
4.25
3.96
3.61
3.20
2.65
4.43
4.16
3.81
3.42
2.88
4.57
4.36
4.02
3.65
3.12
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA60VA/SUZ-KA60VA
CAPACITY : 5.5(kW) INPUT : 1960(W) SHF : 0.75
NOTE
Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 53
53
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA71VA/SUZ-KA71VA
CAPACITY : 7.1(kW) INPUT : 2460(W) SHF : 0.74
21 25 27
OUTDOOR D.B.()
30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21
INDOOR
D.B.()
INDOOR
W.B.()
18 8.34 4.67 0.56 1968 7.99 4.47 0.56 2066 7.67 4.29 0.56 2165 7.38 4.14 0.56 2263 21 20 8.70 3.83 0.44 2066 8.34 3.67 0.44 2189 8.09 3.56 0.44 2239 7.81 3.44 0.44 2337 22 18 8.34 5.01 0.60 1968 7.99 4.79 0.60 2066 7.67 4.60 0.60 2165 7.38 4.43 0.60 2263 22 20 8.70 4.17 0.48 2066 8.34 4.00 0.48 2189 8.09 3.89 0.48 2239 7.81 3.75 0.48 2337 22 22 9.05 3.26 0.36 2140 8.73 3.14 0.36 2276 8.52 3.07 0.36 2337 8.17 2.94 0.36 2435 23 18 8.34 5.34 0.64 1968 7.99 5.11 0.64 2066 7.67 4.91 0.64 2165 7.38 4.73 0.64 2263 23 20 8.70 4.52 0.52 2066 8.34 4.34 0.52 2189 8.09 4.21 0.52 2239 7.81 4.06 0.52 2337 23 22 9.05 3.62 0.40 2140 8.73 3.49 0.40 2276 8.52 3.41 0.40 2337 8.17 3.27 0.40 2435 24 18 8.34 5.67 0.68 1968 7.99 5.43 0.68 2066 7.67 5.21 0.68 2165 7.38 5.02 0.68 2263 24 20 8.70 4.87 0.56 2066 8.34 4.67 0.56 2189 8.09 4.53 0.56 2239 7.81 4.37 0.56 2337 24 22 9.05 3.98 0.44 2140 8.73 3.84 0.44 2276 8.52 3.75 0.44 2337 8.17 3.59 0.44 2435 24 24 9.51 3.04 0.32 2239 9.16 2.93 0.32 2362 8.95 2.86 0.32 2435 8.66 2.77 0.32 2558 25 20 8.70 5.22 0.60 2066 8.34 5.01 0.60 2189 8.09 4.86 0.60 2239 7.81 4.69 0.60 2337 25 22 9.05 4.35 0.48 2140 8.73 4.19 0.48 2276 8.52 4.09 0.48 2337 8.17 3.92 0.48 2435 25 24 9.51 3.43 0.36 2239 9.16 3.30 0.36 2362 8.95 3.22 0.36 2435 8.66 3.12 0.36 2558 26 18 8.34 6.34 0.76 1968 7.99 6.07 0.76 2066 7.67 5.83 0.76 2165 7.38 5.61 0.76 2263 26 20 8.70 5.57 0.64 2066 8.34 5.34 0.64 2189 8.09 5.18 0.64 2239 7.81 5.00 0.64 2337 26 22 9.05 4.71 0.52 2140 8.73 4.54 0.52 2276 8.52 4.43 0.52 2337 8.17 4.25 0.52 2435 26 24 9.51 3.81 0.40 2239 9.16 3.66 0.40 2362 8.95 3.58 0.40 2435 8.66 3.46 0.40 2558 26 26 9.80 2.74 0.28 2362 9.51 2.66 0.28 2485 9.37 2.62 0.28 2558 9.09 2.54 0.28 2632 27 18 8.34 6.67 0.80 1968 7.99 6.39 0.80 2066 7.67 6.13 0.80 2165 7.38 5.91 0.80 2263 27 20 8.70 5.91 0.68 2066 8.34 5.67 0.68 2189 8.09 5.50 0.68 2239 7.81 5.31 0.68 2337 27 22 9.05 5.07 0.56 2140 8.73 4.89 0.56 2276 8.52 4.77 0.56 2337 8.17 4.57 0.56 2435 27 24 9.51 4.19 0.44 2239 9.16 4.03 0.44 2362 8.95 3.94 0.44 2435 8.66 3.81 0.44 2558 27 26 9.80 3.14 0.32 2362 9.51 3.04 0.32 2485 9.37 3.00 0.32 2558 9.09 2.91 0.32 2632 28 18 8.34 7.01 0.84 1968 7.99 6.71 0.84 2066 7.67 6.44 0.84 2165 7.38 6.20 0.84 2263 28 20 8.70 6.26 0.72 2066 8.34 6.01 0.72 2189 8.09 5.83 0.72 2239 7.81 5.62 0.72 2337 28 22 9.05 5.43 0.60 2140 8.73 5.24 0.60 2276 8.52 5.11 0.60 2337 8.17 4.90 0.60 2435 28 24 9.51 4.57 0.48 2239 9.16 4.40 0.48 2362 8.95 4.29 0.48 2435 8.66 4.16 0.48 2558 28 26 9.80 3.53 0.36 2362 9.51 3.43 0.36 2485 9.37 3.37 0.36 2558 9.09 3.27 0.36 2632 29 18 8.34 7.34 0.88 1968 7.99 7.03 0.88 2066 7.67 6.75 0.88 2165 7.38 6.50 0.88 2263 29 20 8.70 6.61 0.76 2066 8.34 6.34 0.76 2189 8.09 6.15 0.76 2239 7.81 5.94 0.76 2337 29 22 9.05 5.79 0.64 2140 8.73 5.59 0.64 2276 8.52 5.45 0.64 2337 8.17 5.23 0.64 2435 29 24 9.51 4.95 0.52 2239 9.16 4.76 0.52 2362 8.95 4.65 0.52 2435 8.66 4.50 0.52 2558 29 26 9.80 3.92 0.40 2362 9.51 3.81 0.40 2485 9.37 3.75 0.40 2558 9.09 3.64 0.40 2632 30 18 8.34 7.68 0.92 1968 7.99 7.35 0.92 2066 7.67 7.05 0.92 2165 7.38 6.79 0.92 2263 30 20 8.70 6.96 0.80 2066 8.34 6.67 0.80 2189 8.09 6.48 0.80 2239 7.81 6.25 0.80 2337 30 22 9.05 6.16 0.68 2140 8.73 5.94 0.68 2276 8.52 5.79 0.68 2337 8.17 5.55 0.68 2435 30 24 9.51 5.33 0.56 2239 9.16 5.13 0.56 2362 8.95 5.01 0.56 2435 8.66 4.85 0.56 2558 30 26 9.80 4.31 0.44 2362 9.51 4.19 0.44 2485 9.37 4.12 0.44 2558 9.09 4.00 0.44 2632 31 18 8.34 8.01 0.96 1968 7.99 7.67 0.96 2066 7.67 7.36 0.96 2165 7.38 7.09 0.96 2263 31 20 8.70 7.31 0.84 2066 8.34 7.01 0.84 2189 8.09 6.80 0.84 2239 7.81 6.56 0.84 2337 31 22 9.05 6.52 0.72 2140 8.73 6.29 0.72 2276 8.52 6.13 0.72 2337 8.17 5.88 0.72 2435 31 24 9.51 5.71 0.60 2239 9.16 5.50 0.60 2362 8.95 5.37 0.60 2435 8.66 5.20 0.60 2558 31 26 9.80 4.70 0.48 2362 9.51 4.57 0.48 2485 9.37 4.50 0.48 2558 9.09 4.36 0.48 2632 32 18 8.34 8.34 1.00 1968 7.99 7.99 1.00 2066 7.67 7.67 1.00 2165 7.38 7.38 1.00 2263 32 20 8.70 7.65 0.88 2066 8.34 7.34 0.88 2189 8.09 7.12 0.88 2239 7.81 6.87 0.88 2337 32 22 9.05 6.88 0.76 2140 8.73 6.64 0.76 2276 8.52 6.48 0.76 2337 8.17 6.21 0.76 2435 32 24 9.51 6.09 0.64 2239 9.16 5.86 0.64 2362 8.95 5.73 0.64 2435 8.66 5.54 0.64 2558 32 26 9.80 5.09 0.52 2362 9.51 4.95 0.52 2485 9.37 4.87 0.52 2558 9.09 4.73 0.52 2632
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 54
54
PERFORMANCE DATA COOLING operation at Rated frequency SEZ-KA71VA/SUZ-KA71VA
CAPACITY : 7.1(kW) INPUT : 2460(W) SHF : 0.74
OUTDOOR D.B.()
INDOOR
D.B.()
INDOOR
W.B.()
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT 21 18 6.96 3.90 0.56 2411 6.39 3.58 0.56 2558 5.89 3.30 0.56 2657 21 20 7.31 3.22 0.44 2509 6.82 3.00 0.44 2632 6.32 2.78 0.44 2780 22 18 6.96 4.17 0.60 2411 6.39 3.83 0.60 2558 5.89 3.54 0.60 2657 22 20 7.31 3.51 0.48 2509 6.82 3.27 0.48 2632 6.32 3.03 0.48 2780 22 22 7.74 2.79 0.36 2608 7.24 2.61 0.36 2755 6.75 2.43 0.36 2854 23 18 6.96 4.45 0.64 2411 6.39 4.09 0.64 2558 5.89 3.77 0.64 2657 23 20 7.31 3.80 0.52 2509 6.82 3.54 0.52 2632 6.32 3.29 0.52 2780 23 22 7.74 3.10 0.40 2608 7.24 2.90 0.40 2755 6.75 2.70 0.40 2854 24 18 6.96 4.73 0.68 2411 6.39 4.35 0.68 2558 5.89 4.01 0.68 2657 24 20 7.31 4.10 0.56 2509 6.82 3.82 0.56 2632 6.32 3.54 0.56 2780 24 22 7.74 3.41 0.44 2608 7.24 3.19 0.44 2755 6.75 2.97 0.44 2854 24 24 8.17 2.61 0.32 2706 7.67 2.45 0.32 2829 7.24 2.32 0.32 2952 25 20 7.31 4.39 0.60 2509 6.82 4.09 0.60 2632 6.32 3.79 0.60 2780 25 22 7.74 3.71 0.48 2608 7.24 3.48 0.48 2755 6.75 3.24 0.48 2854 25 24 8.17 2.94 0.36 2706 7.67 2.76 0.36 2829 7.24 2.61 0.36 2952 26 18 6.96 5.29 0.76 2411 6.39 4.86 0.76 2558 5.89 4.48 0.76 2657 26 20 7.31 4.68 0.64 2509 6.82 4.36 0.64 2632 6.32 4.04 0.64 2780 26 22 7.74 4.02 0.52 2608 7.24 3.77 0.52 2755 6.75 3.51 0.52 2854 26 24 8.17 3.27 0.40 2706 7.67 3.07 0.40 2829 7.24 2.90 0.40 2952 26 26 8.59 2.41 0.28 2804 8.09 2.27 0.28 2927 7.60 2.13 0.28 3050 27 18 6.96 5.57 0.80 2411 6.39 5.11 0.80 2558 5.89 4.71 0.80 2657 27 20 7.31 4.97 0.68 2509 6.82 4.63 0.68 2632 6.32 4.30 0.68 2780 27 22 7.74 4.33 0.56 2608 7.24 4.06 0.56 2755 6.75 3.78 0.56 2854 27 24 8.17 3.59 0.44 2706 7.67 3.37 0.44 2829 7.24 3.19 0.44 2952 27 26 8.59 2.75 0.32 2804 8.09 2.59 0.32 2927 7.60 2.43 0.32 3050 28 18 6.96 5.84 0.84 2411 6.39 5.37 0.84 2558 5.89 4.95 0.84 2657 28 20 7.31 5.27 0.72 2509 6.82 4.91 0.72 2632 6.32 4.55 0.72 2780 28 22 7.74 4.64 0.60 2608 7.24 4.35 0.60 2755 6.75 4.05 0.60 2854 28 24 8.17 3.92 0.48 2706 7.67 3.68 0.48 2829 7.24 3.48 0.48 2952 28 26 8.59 3.09 0.36 2804 8.09 2.91 0.36 2927 7.60 2.73 0.36 3050 29 18 6.96 6.12 0.88 2411 6.39 5.62 0.88 2558 5.89 5.19 0.88 2657 29 20 7.31 5.56 0.76 2509 6.82 5.18 0.76 2632 6.32 4.80 0.76 2780 29 22 7.74 4.95 0.64 2608 7.24 4.63 0.64 2755 6.75 4.32 0.64 2854 29 24 8.17 4.25 0.52 2706 7.67 3.99 0.52 2829 7.24 3.77 0.52 2952 29 26 8.59 3.44 0.40 2804 8.09 3.24 0.40 2927 7.60 3.04 0.40 3050 30 18 6.96 6.40 0.92 2411 6.39 5.88 0.92 2558 5.89 5.42 0.92 2657 30 20 7.31 5.85 0.80 2509 6.82 5.45 0.80 2632 6.32 5.06 0.80 2780 30 22 7.74 5.26 0.68 2608 7.24 4.92 0.68 2755 6.75 4.59 0.68 2854 30 24 8.17 4.57 0.56 2706 7.67 4.29 0.56 2829 7.24 4.06 0.56 2952 30 26 8.59 3.78 0.44 2804 8.09 3.56 0.44 2927 7.60 3.34 0.44 3050 31 18 6.96 6.68 0.96 2411 6.39 6.13 0.96 2558 5.89 5.66 0.96 2657 31 20 7.31 6.14 0.84 2509 6.82 5.73 0.84 2632 6.32 5.31 0.84 2780 31 22 7.74 5.57 0.72 2608 7.24 5.21 0.72 2755 6.75 4.86 0.72 2854 31 24 8.17 4.90 0.60 2706 7.67 4.60 0.60 2829 7.24 4.35 0.60 2952 31 26 8.59 4.12 0.48 2804 8.09 3.89 0.48 2927 7.60 3.65 0.48 3050 32 18 6.96 6.96 1.00 2411 6.39 6.39 1.00 2558 5.89 5.89 1.00 2657 32 20 7.31 6.44 0.88 2509 6.82 6.00 0.88 2632 6.32 5.56 0.88 2780 32 22 7.74 5.88 0.76 2608 7.24 5.50 0.76 2755 6.75 5.13 0.76 2854 32 24 8.17 5.23 0.64 2706 7.67 4.91 0.64 2829 7.24 4.63 0.64 2952 32 26 8.59 4.47 0.52 2804 8.09 4.21 0.52 2927 7.60 3.95 0.52 3050
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Page 55
55
OUTDOOR W.B.()
INDOOR
-10
D.B.()
Q INPUT-5Q INPUT0Q INPUT5Q INPUT10Q INPUT15Q INPUT20Q INPUT 15 21 26
1.89
1.80
1.62
540 581 623
-15
Q INPUT
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUTQ INPUT
Q INPUT
Q
INPUT Q INPUT Q INPUT Q INPUT Q INPUTQ INPUT
1.50
1.41
1.23
432 460 498
-15
2.00
1.88
1.64
572 609 660
2.28
2.16
2.01
647 689 730
2.67
2.55
2.37
730 764 805
3.06
2.91
2.76
789 822 863
3.45
3.30
3.15
838 863 905
3.81
3.66
3.51
863 888 930
4.20
4.04
3.90
880 921 955
PERFORMANCE DATA HEATING operation SLZ-KA25VA(L)/SUZ-KA25VA(H) at Rated frequency
CAPACITY : 3.0(kW) INPUT : 830(W)
SLZ-KA35VA(L)/SUZ-KA35VA(H) at Rated frequency
CAPACITY : 4.0(kW) INPUT : 1100(W)
SLZ-KA50VA(L)/SUZ-KA50VA at Rated frequency
CAPACITY : 5.0(kW) INPUT : 1550(W)
OUTDOOR W.B.()
INDOOR
-10
D.B.()
-5 0 5 10 15 20
15 21 26
OUTDOOR W.B.()
INDOOR
-10
D.B.()
-5 0 5 10 15 20
15 21 26
3.15
3.00
2.70
1008 1085 1163
3.80
3.60
3.35
1209 1287 1364
4.45
4.25
3.95
1364 1426 1504
5.10
4.85
4.60
1473 1535 1612
5.75
5.50
5.25
1566 1612 1690
6.35
6.10
5.85
1612 1659 1739
7.00
6.73
6.50
1643 1721 1783
2.52 715 3.04 858 3.56 968 4.08 1045 4.60 1111 5.08 1144 5.60 1166
2.40 770 2.88 913 3.40 1012 3.88 1089 4.40 1144 4.88 1177 5.38 1221
2.16 825 2.68 968 3.16 1067 3.68 1144 4.20 1199 4.68 1232 5.20 1265
Page 56
56
SEZ-KA50VA/SUZ-KA50VA at Rated frequency
CAPACITY : 5.9(kW) INPUT : 1840(W)
SEZ-KA60VA/SUZ-KA60VA at Rated frequency
CAPACITY : 6.9(kW) INPUT : 2450(W)
OUTDOOR W.B.()
INDOOR
-10
D.B.()
Q INPUT-5Q INPUT0Q INPUT5Q INPUT10Q INPUT15Q INPUT20Q INPUT 15 21 26
3.72
3.54
3.19
1196 1288 1380
4.48
4.25
3.95
1435 1527 1619
5.25
5.02
4.66
1619 1693 1785
6.02
5.72
5.43
1748 1822 1914
6.79
6.49
6.20
1858 1914 2006
7.49
7.20
6.90
1914 1969 2061
8.26
7.94
7.67
1950 2042
2116
OUTDOOR W.B.()
INDOOR
-10
D.B.()
Q INPUT-5Q INPUT0Q INPUT5Q INPUT10Q INPUT15Q INPUT20Q INPUT 15 21 26
4.35
4.14
3.73
1593 1715 1838
5.24
4.97
4.62
1911 2034 2156
6.14
5.87
5.45
2156 2254 2377
7.04
6.69
6.35
2328 2426 2548
7.94
7.59
7.25
2475 2548 2671
8.76
8.42
8.07
2548 2622 2744
9.66
9.28
8.97
2597 2720 2818
SEZ-KA71VA/SUZ-KA71VA at Rated frequency
CAPACITY : 8.1(kW) INPUT : 2360(W)
OUTDOOR W.B.()
INDOOR
-10
D.B.()
Q INPUT-5Q INPUT0Q INPUT5Q INPUT10Q INPUT15Q INPUT20Q INPUT 15 21 26
5.10
4.86
4.37
1534 1652 1770
6.16
5.83
5.43
1841 1959 2077
7.21
6.89
6.40
2077 2171 2289
8.26
7.86
7.45
2242 2336 2454
9.32
8.91
8.51
2384 2454 2572
10.29
9.88
9.48
2454 2525 2643
11.34
10.89
10.53
2502 2620 2714
SEZ-KC25VA/SUZ-KA25VA(H) at Rated frequency
CAPACITY : 3.0(kW) INPUT : 830(W)
SEZ-KA35VA/SUZ-KA35VA(H) at Rated frequency
CAPACITY : 4.0(kW) INPUT : 1100(W)
OUTDOOR W.B.()
INDOOR
-10
D.B.()
Q INPUT-5Q INPUT0Q INPUT5Q INPUT10Q INPUT15Q INPUT20Q INPUT 15 21 26
OUTDOOR W.B.()
INDOOR
-10
D.B.()
Q INPUT-5Q INPUT0Q INPUT5Q INPUT10Q INPUT15Q INPUT20Q INPUT 15 21 26
2.52 715 3.04 858 3.56 968 4.08 1045 4.60 1111 5.08 1144 5.60 1166
2.40 770 2.88 913 3.40 1012 3.88 1089 4.40 1144 4.88 1177 5.38 1221
2.16 825 2.68 968 3.16 1067 3.68 1144 4.20 1199 4.68 1232 5.20 1265
-15
Q INPUT
Q INPUT
1.50
1.41
1.23
432 460 498
-15
2.00
1.88
1.64
572 609 660
1.89 540 2.28 647 2.67 730 3.06 789 3.45 838 3.81 863 4.20 880
1.80 581 2.16 689 2.55 764 2.91 822 3.30 863 3.66 888 4.04 921
1.62 623 2.01 730 2.37 805 2.76 863 3.15 905 3.51 930 3.90 955
Page 57
5757
ACTUATOR CONTROL
10
SUZ-KA25VA(H) SUZ-KA35VA(H) SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
Discharge temperature thermistor Indoor pipe temperature thermistor
Defrost thermistor
Fin temperature thermistor
Ambient temperature thermistor
Purpose
Protection Cooling: Coil frost prevention Heating: High pressure protection Cooling: High pressure protection Heating: Defrosting Protection Cooling: Low ambient temperature operation Heating: Defrosting (Heater)
Compressor
LEV
Outdoor
fan motor
Indoor
fan motor
Defrost
heater
RV-coil
Sensor
Actuator
10-3. Relation between main sensor and actuator
SUZ-KA25VA(H).TH SUZ-KA35VA(H).TH
10-2. R.V. coil control
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling . . . . . . . . . . . . . . . . . OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
ON
OFF
ON
OFF
Outdoor fan
Compressor
5 seconds 15 seconds
ON OFF
Compressor
Outdoor fan motor
R.V.coil
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
ON or OFF
ON or OFF
10-1. Outdoor fan motor control
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
SUZ-KA25VA(H)R1.TH SUZ-KA35VA(H)R1.TH
esopruProsneS
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater
Discharge temperature thermistor
Protection
Indoor coil temperature thermistor
Cooling: Coil frost prevention Heating: High pressure protec-
tion Defrost thermistor Heating: Defrosting Fin temperature thermistor Protection
Ambient temperature thermistor
Cooling: Low ambient tempera-
ture operation
Heating: Defrosting (Heater)
Outdoor heat exchanger tem­perature thermistor
Cooling: Low ambient tempera-
ture operation
Cooling: High pressure protec-
tion
○○ ○
○○ ○○○○○
○○ ○○○
○○○ ○○○
NOTE: The 4-way valve reverses for 5 seconds
right before start-up of the compressor.
Page 58
58
Jumper wire
Defrost finish temperature
JS
none
(cut)
Serial No.
soldered
(Initial setting)
SUZ-KA35VA
8
~67P00330 68P00331~
5
SUZ-KA25VAH SUZ-KA35VAHSUZ-KA25VA
15
8
13
10
13
10
15
13
SUZ-KA25VA(H) SUZ-KA35VA(H)
CHANGE IN DEFROST SETTING
<JS> When the JS wire of the outdoor Inverter P.C. board is cut/ soldered, the defrost finish temperature is changed.
(Refer to 12-6-1 SUZ-KA25/35VA(H).TH) (Refer to 12-6-3 SUZ-KA25/35VA(H)R1.TH)
12
TROUBLESHOOTING
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp is blinking on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is blinking on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
4) When troubleshooting, refer to 12-2. and 12-3.
SUZ-KA25VA(H) SUZ-KA35VA(H) SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA
12-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care the following during servicing.
1)
Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and turn off the breaker.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Housing point
Lead wire
11
SERVICE FUNCTIONS
Discharge temperature thermistor Indoor pipe temperature thermistor
Defrost thermistor Fin temperature thermistor Ambient temperature thermistor Outdoor heat exchanger temperature
Purpose
Protection Cooling: Coil frost prevention Heating: High pressure protection
Heating: Defrosting
Protection
Protection Cooling: High pressure protection
Compressor LEV
Outdoor fan motor
4-way
valve
Sensor
Actuator
SUZ-KA50VA/VA1/VAR2.TH SUZ-KA60VA/VA1/VAR2.TH SUZ-KA71VA/VA1.TH
Page 59
59
12-2. Failure mode recall function
As this air conditioner has a function to memorize all the failures that had happened, the latest failure detail can be recalled by following the procedures below. Use this function when the check code is not displayed with wired remote controller or the remote controller at use is wireless type.
12-2-1. Flow chart of the indoor/outdoor unit failure mode recall function
Operational procedure (For wireless remote controller)
Yes
(Blinks)
No
(OFF)
Yes
No
Releasing the failure mode recall function
1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
Note1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
2. Blinking pattern when the indoor unit is abnormal:[Output pattern A]
3.Blinking pattern when the outdoor unit is abnormal:[Output pattern B]
Does OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep sounds are emitted at the same timing of the blinking of OPERATION INDICA T OR lamp. 2
Setting up the failure mode recall function
Before blinking, does POWER lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point. Make sure to check at least two consecutive blinking cycles. 2
Turn ON the power supply. While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
Repair the defective parts.
Release the failure mode recall function by the following procedures. With the remote controller headed towards the indoor unit, press any button that is not used in this failure mode recall function (e.g. TIMER button) . OR
Turn OFF the power supply and turn ON it again.Press RESET button of the remote controller.
Judgment of indoor/outdoor abnormality
1 Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed).
The outdoor unit is abnormal. Check the blinking pattern, and confirm the abnormal point(12-2.3.). Make sure to check at least two consecutive blinking cycles. 3
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
Indoor unit is normal. There is a possibility that the plasma or outdoor unit is abnormal. Confirm the failure detail on the LED display of the outdoor controller board.(refer to 12-2-4.)
OPERATION INDICATOR lamp blink pattern
Beep
Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
On
0.5 sec.
Off
Approx. 2.5 sec.On0.5 sec.On0.5 sec.
··· Repeated
Number of blinks/beeps in pattern indicates the check code in the next page (i.e., n=5 for “P5”)
Number of blinks/beeps in pattern indicates the check code in the next page
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
OPERATION INDICATOR lamp blink pattern
Beep Beep Beep Beep Beep Beep Beep
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.On0.5 sec.On0.5 sec.
Off
Approx. 2.5 sec.OnApprox. 3 sec.On0.5 sec.On0.5 sec.
··· Repeated
Number of blinks/beeps in pattern indicates the check code in the next page (i.e., n=5 for “U2”)
Number of blinks/beeps in pattern indicates the check code in the next page
n
th
1st2nd3
rd
1st2
nd
Self-check starts (Start signal received)
Beeper sounds
OPERATION INDICATOR lamp
RE
SET
TOO
TO
O
COOL
AUTO COOL
DRY
HEAT
F
AN
VANE
SELECT
TIME
ON/OFF
TOO
WARM
TOO
COOL
h
Page 60
60
12-2-2. Wired remote controller
12-2-3. Failure mode table (Wireless remote controller/Wired remote controller)
Turn on the power.Press the [CHECK] button twice.Set refrigerant address with [TEMP] button
if system control is used.
Press the [ON/OFF] button to stop the self-check.
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
 
CHECK buttonRefrigerant addressTEMP. buttonIC: Indoor unit
OC: Outdoor unit
Check code
[Output pattern A]Errors detected by indoor unit
Beeper sounds/OPERATION INDICATOR
lamp blinks
Wireless remote controller
Check code
Wired remote controller
Symptom Remark
(Number of times)
1
P1
Intake sensor error
2
P2 P9
Pipe (TH2) sensor error Pipe (TH5) sensor error
3
E6,E7
Indoor/outdoor unit communication error
4
P4
Drain sensor error/Float switch connector open
5
P5
Drain pump error
6
P6
Freezing/Overheating protection operation
7
EE
Communication error between indoor and outdoor units
8
P8
Pipe temperature error
9
E4, E5
Remote controller signal receiving error
10
11
– –
– –
– –
12
Fb
Indoor unit control system error (memory error, etc.)
E1, E2
Remote controller control board error
E0, E3
Remote controller transmission error
[Output pattern B]Errors detected by unit other than indoor unit (outdoor unit, etc.)
Check code
Symptom Remark
1E9
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) 2UP Compressor overcurrent interruption 3U3,U4 Open/short of outdoor unit thermistors 4UF Compressor overcurrent interruption (When compressor locked) 5U2 Abnormal high discharging temperature/insufficient refrigerant 6U1,Ud Abnormal high pressure (63H worked)/Overheating protection operation 7U5 Abnormal temperature of heat sink 8U8 Outdoor unit fan protection stop 9U6 Compressor overcurrent interruption/Abnormal of power module
10U7 Abnormality of super heat due to low discharge temperature 11
U9,UH
Abnormality such as overvoltage or voltage shortage and abnormal
synchronous signal to main circuit/Current sensor error
12 13 14Others Other errors
• If the beeper does not sound again after the initial
two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp
does not come on,
there are no error records.
• If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
For details, check the LED display of the outdoor controller board.
• On wireless remote controller The continuous buzzer sounds from receiving section of indoor unit. Blink of operation lamp
• On wired remote controller Check code displayed in the LCD.
Beeper sounds/OPERATION INDICATOR
lamp blinks
Wireless remote controller
Wired remote controller
(Number of times)
Page 61
61
1-time flash every
2.5 seconds 2-time flash
2.5 seconds OFF 3-time flash
2.5 seconds OFF 4-time flash
2.5 seconds OFF 5-time flash
2.5 seconds OFF 7-time flash
2.5 seconds OFF
8-time flash
2.5 seconds OFF 9-time flash
2.5 seconds OFF 10-time flash
2.5 seconds OFF
11-time flash
2.5 seconds OFF 12-time flash
2.5 seconds OFF
Lighting
Outdoor thermistors
Outdoor control system
Fin temperature/P.C. board temperature overheat
Converter control system
Overcurrent protection
Overcurrent protection
Refrigerant system
High pressure protection
Low discharge temperature
Outdoor fan
Outdoor power system (+)
Discharge temperature Defrost thermistor Ambient temperature thermistor
Fin temperature thermistor P.C. board temperature thermistor Nonvolatile memory data
Fin temperature/P.C. board temperature overheat protection
DC voltage Compressor each phase
current Compressor open-phase
protection
Overcurrent protection
Compressor synchronous abnormality (Compressor start-up failure protection) Discharge temperature overheat protection
High pressure protection (Overheat protection)
Low discharge temperature protection
Outdoor fan protection
Outdoor power system
When thermistors short or open during compressor running.
When nonvolatile memory data cannot be read properly, unit stops.
When fin temperature exceeds 83
(SUZ-KA25VA(H))/82 (SUZ-KA35VA(H)), or P.C. board temperature exceeds 85 (SUZ-KA25VA(H))/81 (SUZ-KA35VA(H)).
When DC voltage of inverter cannot be detected normally. When compressor each phase current cannot be detected normally.
When 14A (SUZ-KA25VA(H))/24A (SUZ-KA35VA(H)) current flow into intelligent power module (IPM). When the open-phase protection of compressor is detected. When the interphase short out occurs in the output of the intelligent power module (IPM). When the compressor winding shorts out.
When 14A (SUZ-KA25VA(H))/24A (SUZ­KA35VA(H)) current flow into intelligent power module (IPM).
When waveform of compressor current is distorted.
When discharge temperature exceeds 116
.
When the indoor coil themistor (TH5) exceeds 70 in HEAT mode. When the defrost thermistor exceeds 70
in COOL mode. When discharge temperature has been 50
or less for 20 minutes.
When outdoor fan has stopped within 30 seconds 3 times in a row after outdoor fan start-up, unit stops.
When it consecutively occurs 3 times that the compressor stops for overcurrent protection or start-up failure protection within 1 minute after start-up.
•Check the outdoor thermistors
+
Defective outdoor thermistors can be identified by checking the blinking
pattern of LED.
•Replace the inverter P.C. board.
•Check around outdoor unit.
•Check outdoor unit air passage.
•Check the outdoor fan motor.
•Check the inverter/compressor.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Check the stop valve.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Check the refrigerant circuit and refrigerant amount.
•Check the LEV.
•Check the outdoor thermistors.
•Check refrigerant circuit and refrigerant amount.
•Check the stop valve.
•Check the refrigerant circuit and refrigerant amount.
•Check the LEV.
•Check the outdoor fan motor.
•Check the inverter P.C. board.
•Reconnect compressor connector.
•Check the inverter/compressor.
•Check the stop valve.
LED indication
(Outdoor unit)
Abnormal point
(Failure mode)
Details of abnormal
Detection method
Check point
+ Operation indicator lamp of the indoor unit (only the wireless remote controller use model) blinks twice. Refer to 12-2-1. +3 and 12-2-3. [Outdoor pattern B].
12-2-4. Outdoor unit failure mode table SUZ-KA25VA(H) SUZ-KA35VA(H)
(Except for SUZ-KA25/35VA(H)R1.TH)
Page 62
62
Lighting
5 times
6 times
Once
Twice
3 times 4 times 9 times
5 times 6 times
7 times
Goes out
Goes out
Discharge temperature thermistor
Defrost thermistor
Ambient temperature thermistor
Fin temperature thermistor P.C. board temperature
thermistor Outdoor heat exchanger
temperature thermistor
EEPROM Communication error
between P.C. boards
Communication between P.C. boards protection
Current sensor Current sensor protection
Zero cross detecting circuit
Zero cross detecting circuit protection
Converter protection
Bus-bar voltage protection (1)
Bus-bar voltage protection (2) +Even if this protection stop is performed continuously 3 times, it does not mean the abnormality in outdoor power system.
Outdoor thermistors
Outdoor control system Converter control
system
Outdoor LED indication
LED1 LED2
Abnormal point
(Failure mode)
Details of abnormal Detecting method Check point
When a short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 10 minutes of compressor start-up. When a short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 5 minutes of compressor start-up. When a short or open circuit is detected in the thermistor during operation.
When a short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 5 minutes (in cooling) and 10 minutes (in heating) of compressor start-up. When nonvolatile memory data cannot be read properly, unit stops. When the communication between boards protection stop is continuously performed twice.
Communication error occurs between the electronic control P.C.board and power board for more than 10 seconds. Current sensor protection stop is continuously performed twice. When a short or open circuit is detected in the current sensor during compressor operating. The protection stop of the zero cross detecting circuit is continuously performed 10 times.
When zero cross signal cannot be detected while the compressor is operating. When a failure is detected in the operation of the converter during operation. When the bus-bar voltage exceeds 400V or falls to 200V or below during compressor operating.
When the bus-bar voltage exceeds 400V or falls to 50V or below during compressor operating.
• Check the outdoor thermistors.
• Replace the outdoor electronic control P.C. board.
• Check the outdoor thermistors.
• Replace the outdoor electronic control P.C. board.
• Check the connecting wire between outdoor electronic control P.C. board and power board.
• Replace the power board.
• Check the connecting wire among electronic control P.C. board, noise filter P.C. board and power board.
• Replace the power board.
SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA (Except for SUZ-KA50VAR2.TH)
Page 63
63
Once
3 times
4 times
Lighting
Goes out
Goes out
Goes out
Lighting
IPM protection Lock protection
Fin temperature overheat protection
P.C.boad temperature overheat protection
Discharge temperature overheat protection
HPS protection High pressure protection
(Overheat protection)
Low discharge temperature protection
Outdoor fan protection
Outdoor power system
Overcurrent protection
Fin temperature/P.C. board temperature overheat
Refrigerant system
High pressure protection
Low discharge temperature
Outdoor fan
Outdoor power system
Outdoor LED indication
LED1 LED2
Abnormal point
(Failure mode)
Details of abnormal Detecting method Check point
When overcurrent is detected after 30 seconds of compressor start-up. When overcurrent is detected within 30 seconds after the compressor gets started. When the fin temperature exceeds 87 during operation.
When the P.C. board temperature exceeds 70 during operation.
When discharge temperature exceeds 116.
When high-pressure is detected with the high-pressure switch (HPS) during operation. When the indoor coil thermistor (TH5) exceeds 70 in HEAT mode. When the outdoor heat exchanger thermistor exceeds 70 in COOL mode. When the frequency of the compressor is kept 80Hz or more and discharge temperature is kept under 39 for more than 20 minutes. When outdoor fan has stopped within 30 seconds 3 times in a row after outdoor fan start -up,unit stops. When IPM protection stop or lock protection stop is continuously performed 3 times within 1 minute after the compressor get started, or when converter protection stop or bus-bar voltage protection stop is continuously performed 3 times within 3 minutes after start-up.
• Check the connection of the compressor connecting wire.
• Check the inverter/ compressor.
• Check the stop valve.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Check the outdoor fan motor.
• Check refrigerant circuit and refrigerant amount.
• Check the LEV.
• Check the outdoor thermistors.
• Check refrigerant circuit and refrigerant amount.
• Check the stop valve.
• Check refrigerant circuit and refrigerant amount.
• Check the LEV.
• Check the outdoor fan motor.
• Reconnect compressor connector.
• Check the inverter/ compressor.
• Check the stop valve.
• Check the PAM module.
Page 64
64
Refer to 12-5./ "How
Refer to 12-5./ "How
Refer to 12-5.9 "Check
Refer to 11-5.< "Check
Refer to 12-5.7 "Check
Refer to 12-5.9 "Check
Refer to 12-5./ "How
Refer to 12-5./ "How
Refer to 12-5.5 "Check
Refer to 12-5./ "How
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition
)lamroN(enoN
Outdoor power system
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started.
Reconnect connectors. to check inverter/
compressor". Check stop valve.
Discharge temperature thermistor
1-time flash every
2.5 seconds
Thermistor shorts or opens during compressor running. of outdoor thermistors".
Defective outdoor thermistors can be identified by checking the blinking pattern of LED.
Defrost thermistor Fin temperature thermistor 3-time flash
2.5 seconds OFF
P.C. board temperature thermistor
4-time flash
2.5 seconds OFF
Ambient temperature thermistor
2-time flash
2.5 seconds OFF
Overcurrent 11-time flash
2.5 seconds OFF
Large current fl ows into intelligent power module.
Reconnect compressor connector.
to check inverter/ compressor". Check stop valve.
Compressor synchronous abnormality (Compressor start­up failure protection)
12-time flash
2.5 seconds OFF
Waveform of compressor current is distorted.
Reconnect compressor connector.
to check inverter/ compressor".
Discharge temperature
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrigerant amount.
of LEV".
High pressure
Temperature indoor coil thermistor exceeds 70°C in HEAT mode. Temperature defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrigerant amount. Check stop valve.
Fin temperature/P.C. board temperature
7-time flash
2.5 seconds OFF
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 80°C, or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 70 ~ 75°C.
Check around outdoor unit. Check outdoor unit air passage.
of outdoor fan motor".
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Refer to 12-5.7 "Check of outdoor fan motor".
of inverter P.C. board".
Nonvolatile memory data 5-tme flash
2.5 seconds OFF
Nonvolatile memory data cannot be read properly.
Replace the inverter P.C. board.
Discharge temperature
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
of LEV". Check refrigerant circuit and refrigerant amount.
DC voltage 8-ti m e f l ash
2.5 seconds OFF
DC voltage of inverter cannot be detected normally. to check inverter/
compressor".
Each phase current of compressor
9-time flash
2.5 seconds OFF
Each phase current of compressor cannot be detected normally.
Overcurrent Compressor open­phase
10-time flash
2.5 seconds OFF
Large current fl ows into intelligent power module (IPM). The open-phase operation of compressor is detected. The interphase short out occurs in the output of the intelligent power module (IPM). The compressor winding shorts out.
Reconnect compressor connector.
to check inverter/ compressor".
Stop valve (Closed valve) 14-time flash
2.5 seconds OFF
Closed valve is detected by compressor current.
Check stop valve
NOTE: Blinking patterns of this mode differ from the ones of Troubleshooting check table (12-3.).
Correspondence
SUZ-KA25VA(H)R1.TH SUZ-KA35VA(H)R1.TH SUZ-KA50VAR2.TH
Page 65
65
Abnormal point/ Condition
When it consecutively occurs 3times that the compressor stops for overcurrent protection or start-up failure protection within 1minute start-up.
When discharge temperature thermistor, fin temperature thermistor, defrost thermistor, P.C. board temperature thermistor or ambient temperature thermistor shorts or opens during compressor running.When discharge temperature
When nonvolatile memory data cannot be read properly, compressor stops.
When 14A (SUZ-KA25VA(H))/24A (SUZ-KA35VA(H)) current flows into intelligent power module.
When discharge temperature thermistor exceeds 116, compressor stops. Compressor can restart if discharge temperature thermistor reads 100 or less 3 minutes later.
When temperature of fin temperature thermistor on the heat sink exceeds 83 (SUZ-KA25VA(H))/82 (SUZ-KA35VA(H)) or temperature of P.C. board temperature thermistor exceeds 85 (SUZ-KA25VA(H))/81 (SUZ-KA35VA(H)), compressor stops and restarts 3 minutes later.
When indoor coil thermistor exceeds 70 in HEAT mode. When the defrost thermistor exceeds 70 in COOL mode.
When current from power outlet exceeds 6.1A (SUZ-KA25VA(H))/9.2A (SUZ-KA35VA(H)), compressor frequency lowers.
When indoor coil thermistor exceeds 55 in HEAT mode, compressor frequency lowers.
When indoor coil thermistor reads 8 or less in COOL mode, compressor frequency lowers.
When discharge temperature thermistor exceeds 111, compressor frequency lowers.
When discharge temperature has been 50 or less for 20 minutes.
No.
1
2
3
6
7
8
9
14
15
16
17
18
Symptom
LED indication
Detection method
Check point
Outdoor unit does not operate
'Outdoor unit stops and restarts 3 minutes later' is repeated
Outdoor unit operates
Outdoor unit operates
1-time flash every
2.5 seconds
2-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
5-time flash
2.5 seconds OFF
1-time flash
2.5 seconds OFF
3-time flash
2.5 seconds OFF
4-time flash
2.5 seconds OFF
7-time flash
2.5 seconds OFF
Outdoor power system
Outdoor thermistors
Outdoor control system
Overcurrent protection
Discharge temperature overheat protection
Fin temperature /P.C. board temperature thermistor overheat protection
High pressure protection
Frequency drop by current protection
Frequency drop by high pressure protection
Frequency drop by defrosting in COOL mode
Frequency drop by discharge temperature protection
Low discharge temperature protection
· Check stop valve.
·
Reconnect connector of compressor.
· Refer to 12-5. "How to check inverter/ compressor".
· Refer to 12-5. "Check of outdoor thermistors".
· Check stop valve.
·
Reconnect connector of compressor.
· Refer to 12-5. "How to check
inverter/compressor".
Replace inverter P.C. board.
· Check refrigerant circuit and refrigerant amount.
· Refer to 12-5. "Check of LEV".
· Check around outdoor unit.
· Check outdoor unit air passage.
· Refer to 12-5. "Check of outdoor fan motor".
· Check refrigerant circuit and refrigerant amount.
· Check stop valve.
The unit is normal, but check the following.
· Check if indoor filters are clogged.
· Check if refrigerant is short.
· Check if indoor/outdoor unit air circulation is short cycled.
· Refer to 12-5. "Check of LEV".
· Check refrigerant circuit and refrigerant amount.
Inverter P.C. board (Parts side)
LED
Flashing
Refer to 12-5." "How to check mis-wiring and serial signal error.
Refer to 12-2-3. Check [output pattern B]
When the communication failure between the indoor and outdoor unit for 3 minutes.
Serial signal
8-time flash
2.5 seconds OFF
Compressor synchronous abnormality
When the waveform of compressor current is distorted.
·
Reconnect connector of compressor.
· Refer to 12-5. "How to check inverter/compressor".
8-time flash
2.5 seconds OFF
PAM protection PAM:
Pulse Amplitude Modulation
When the overcurrent flows into IGBT (Insulated Gate Bipolar transistor : TR821) or when the bus-bar voltage reaches 320V or more, PAM stops and restarts.
This is not malfunction. PAM protection will be activated in the following cases; Instantaneous power voltage drop (Short time power failure) When the power supply voltage is high.
9-time flash
2.5 seconds OFF
Inverter check mode
When the connector of compressor is disconnected, inverter check mode starts.
Check if the connector of the compressor is correctly connected. Refer to 12-5. "How to check inverter/ compressor".
4
10
19
10-time flash
2.5 seconds OFF
Outdoor fan
6-time flash
2.5 seconds OFF
When outdoor fan has stopped within 30 seconds 3 times a row after outdoor fan start-up, unit stops.
· Refer to 12-5. "Check of outdoor
fan motor.
· Refer to 12-5.! "Check of inverter
P.C. board.
11
12
13
12-time flash
2.5 seconds OFF
Each phase current of compressor
When compressor each phase current cannot be detected normally
· Refer to 12-5. "How to check
inverter/compressor".
13-time flash
2.5 seconds OFF
DC voltage
When DC voltage of inverter cannot be detected normally.
· Refer to 12-5. "How to check inverter/compressor".
· Check refrigerant circuit and refrigerant amount.
· Refer to 12-5. "Check of LEV".
· Refer to 12-5. "Check of outdoor thermistors".
When outdoor unit is defective.
Outdoor unit (Other abnormality)
5
14-time flash
2.5 seconds OFF
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the flashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
12-3. Troubleshooting check table SUZ-KA25VA(H) SUZ-KA35VA(H)
(Except for SUZ-KA25/35VA(H)R1.TH)
NOTE 1. The location of LED is illustrated at the right figure. Refer to 12-6-1.
2. LED lights up during normal operation.
Page 66
66
LED1 (Red)
LED2 (Yellow)
Lightning Twice Outdoor power system
• Check the connection of the compressor connecting wire.
Refer to 12-5.( "How to check inverter/compressor".
• Check the stop valve.
Lightning 3 times
Discharge temperature thermistor
• Refer to 12-5.) "Check of outdoor thirmistor".
• Refer to 12-5.) "Check of outdoor thirmistor".
Outdoor heat exchanger temperature thermistor
Defrost thermistor
Lightning 7 times Nonvolatile memory data • Replace the outdoor electronic control P.C. board.
Lightning 8 times Current sensor • Replace the power board.
Lightning 11 times
Communication error between P.C. boards
• Check the connecting wire between outdoor electronic control P.C. board and power board.
Lightning 12 times
Zero cross detecting circuit
• Check the connecting wire among outdoor electronic control P.C. board, noise filter P.C. board and power board.
Abnormal point/Condition Correspondence
When a short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 5 minutes (in cooling) and 10 minutes (in heating) of compressor start-up.
When a short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 5 minutes of compressor start-up.
• Refer to 12-5.) "Check of outdoor thirmistor".
• Replace the outdoor electronic control P.C. board.
Indication
When IPM protection stop or lock protection stop is continuously performed three times within 1 minute after the compressor gets started, or when converter protection stop or bus-bar voltage protection stop is continuously performed three times within 3 minutes after start-up.
When a short circuit is detected in the thermistor during operation, or when an open circuit is detected in the thermistor after 10 minutes of compressor start-up.
Condition
When the nonvolatile memory data cannot be read properly.
Lightning 6 times Serial signal
Fin temperature thermistor
P.C board temperature thermistor
Lightning 4 times
Ambient temperature thermistor
Current sensor protection stop is continuously performed twice. When the communication protection stop between boards is
continuously performed twice. The protection stop of the zero cross detecting circuit is continuously
performed 10 times.
When a short or open circuit is detected in the thermistor during operation.
When a short or open circuit is detected in the thermistor during operation.
5 timesLightning
Outdoor electronic control P.C. board (Parts side)
Lighting
IPM protection
Lock protection
3 times Goes out
Discharge temperature protection
• Check the amount of gas and refrigerant circuit.
• Refer to 12-5.'"Check of LEV".
Fin temperature protection P.C. board temperature protection
High-pressure protection
8 times Goes out
Converter protection
• Replace the power board.
Bus-bar voltage protection (1)
• Replace the power board.
Bus-bar voltage protection (2)
13 times Goes out Outdoor fan motor • Refer to 12-5.* "Check of outdoor fan motor".
Lighting 8 times
Current sensor protection
• Replace the power board.
Lighting 11 times
Communication between P.C. boards protection
• Check the connecting wire between outdoor electronic control P.C. board and power board.
Lighting 12 times
Zero cross detecting circuit protection
• Check the connecting wire among outdoor electronic control P.C. board, noise filter P.C. board and power board.
•Check refrigerant circuit and refrigerant amount.
•Refer to 12-5.' "Check of LEV".
• Check around of gas and the refrigerant circuit.
• Check of stop valve.
• Reconnect compressor connector.
• Refer to 12-5.( "How to check inverter/compressor".
• Check the stop valve.
• Check the power module (PAM module).
Twice Goes out
4 times Goes out
5 times Goes out
9 times Goes out
When over-current is detected after 30 minutes of compressor start-up.
When over-current is detected within 30 minutes of compressor start-up
When the bus-bar voltage exceeds 400V or falls to 200V or below during compressor operating.
When the bus-bar voltage exceeds 400V or falls to 50V or below during compressor operating.
When temperature of discharge temperature thermistor exceeds 116:, compressor stops. Compressor can restart if discharge temperature thermistor reads 100 or less 3 minutes later.
When the fin temperature exceeds 87 during operation.
When the P.C. board temperature exceeds 70 during operation. When high-pressure is detected with the high-pressure switch (HPS)
during operation.
When failure occurs continuously three times within 30 seconds after the fan gets started.
When a short or open circuit is detected in the current sensor during compressor operating.
Communication error occurs between the outdoor electronic control P.C. board and power board for more than 10 seconds.
When zero cross signal cannot be detected while the compressor is operating.
When the outdoor heat exchanger temperature exceeds 70 during cooling or when indoor gas pipe temperature exceeds 70 during heating.
When a failure is detected in the operation of the converter during operation.
Outdoor unit does not operate.
LED2
LED1
Refer to 12-5.% "How to check mis-wiring and serial signal error.
When the communication fails between the indoor and outdoor unit for 3 minutes.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Symptom
'Outdoor unit stops and restarts 3 minutes later' is repeated.
SUZ-KA50VA SUZ-KA60VA SUZ-KA71VA (Except for SUZ-KA50VAR2.TH)
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the flashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
NOTE 1. The location of LED is illustrated at the right figure.
2. LED is lighted during normal operation.
Page 67
67
Primary current protection Secondary current protection
High-pressure protection Defrosting in cooling
3 times
Lighting
Discharge temperature protection
• Check refrigerant circuit and refrigerant amount.
• Refer to 12-5.' "Check of LEV".
• Refer to 12-5.) "Check of outdoor thermistors".
4 times
Lighting
Low discharge temperature protection
• Refer to 12-5.' "Check of LEV".
• Check refrigerant circuit and refrigerant amount.
5 times
Lighting
Cooling high-pressure protection
This symptom does not mean any abnormality of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
-
-
These symptoms do not mean any abnormality of the product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
Twice Lighting
Once Lighting
When the discharge temperature exceeds 100 during operation.
When the frequency of the compressor is kept 80Hz or more and the discharge temperature is kept under 39 for more than 20 minutes.
When the outdoor heat exchanger temperature exceeds 58 during operation.
9 times
Lighting
Inverter check mode
Lighting
Lighting
Normal
When the unit is operated with emergency operation switch.
-
When the input current exceeds 15A.
When the current of the compressor exceeds 15A. When the indoor gas pipe temperature exceeds 45 during heating.
When the indoor gas pipe temperature falls 3 or below during cooling.
LED1 (Red)
LED2 (Yellow)
Abnormal point/Condition Correspondence
Indication
Condition
Outdoor unit operates.
Outdoor unit operates
No.
Symptom
20
21
22
23
24
25
26
Page 68
68
SUZ-KA25VA(H)R1.TH SUZ-KA35VA(H)R1.TH SUZ-KA50VAR2.TH
Refer to 12-5./ "How to check in-
Refer to 12-5.9 "Check of LEV".
Refer to 12-5.5 "Check of outdoor
DC voltage DC voltage of inverter cannot be detected normally. Refer to 12-5. / "How to check in-
Refer to 12-5./ "How to check in-
Refer to 12-5.< "Check of inverter
Refer to 12-5./ "How to check in-
Refer to 12-5.7 "Check of outdoor
Refer to 12-5.9 "Check of LEV".
Refer to 12-5./ "How to check in-
Refer to 11-5.> "How to check mis-
Refer to 12-5.5 "Check of outdoor
Refer to 12-5./ "How to check in-
No. Symptom LED indication
Abnormal point/ Con-
dition
ecnednopserroCnoitidnoC
1
Outdoor unit does not oper­ate.
1-time flash every
2.5 seconds
Outdoor power sys­tem
Overcurrent protection stop is continuously performed 3 times within 1 minute after the compressor gets started, or failure of restart of compressor has repeated 24 times.
Reconnect connector of compres­sor.
verter/compressor". Check stop valve.
2
Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor,
defrost thermistor, P.C. board temperature thermistor or ambi­ent temperature thermistor shorts or opens during compressor running.
thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly. (The left lamp of OPERATION INDICATOR lamp of the indoor
unit lights up or fl ashes 7-time.)
Replace inverter P.C. board.
4
6-time flash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes. wiring and serial signal error.
5
11-time fl ash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current. Check stop valve.
6
14-time flash
2.5 seconds OFF
Outdoor unit (Other abnormality)
ehtfotrahcwolF".1.2-21otrefeR.evitcefedsitinuroodtuO detailed outdoor unit failure mode recall function".
7
'Outdoor unit stops and restarts 3 min­utes later' is repeated.
2-time flash
2.5 seconds OFF
Overcurrent protec­tion
Large current fl ows into intelligent power module, or compres­sor repeats after 15 seconds when overcurrent protection oc­curs within 10 seconds after compressor starts. (Repeated 24 times at Maximum)
Reconnect connector of compres­sor.
verter/compressor". Check stop valve.
8
3-time ?ash
2.5 seconds OFF
Discharge tempera­ture overheat protec­tion
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check refrigerant circuit and refrig­erant amount.
9
4-time flash
2.5 seconds OFF
Fin temperature/P.C. board temperature thermistor overheat protection
Temperature of fin temperature thermistor on the heat sink exceeds 75 ~ 80°C or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 70 ~ 75°C.
Check around outdoor unit. Check outdoor unit air passage.
fan motor".
10
5-time flash
2.5 seconds OFF
High pressure protec­tion
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check refrigerant circuit and refrig­erant amount. Check stop valve.
11
8-time flash
2.5 seconds OFF
Compressor synchro­nous abnormality
The waveform of compressor current is distorted. Reconnect connector of compres-
sor. verter/compressor".
12
10-time flash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 12-5.7 "Check of outdoor fan motor.
P.C. board.
13
12-time flash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally
verter/compressor".
14
13-time flash
2.5 seconds OFF verter/compressor".
15
Outdoor unit operates.
1-time flash
2.5 seconds OFF
Frequency drop by current protection
Current from power outlet reaches the protection current, and compressor frequency lowers.
The unit is normal, but check the following. Check if indoor fi lters are clogged. Check if refrigerant is short. Check if indoor/outdoor unit air cir­culation is short cycled.
16
3-time flash
2.5 seconds OFF
Frequency drop by high pressure protec­tion
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
17
4-time flash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check refrigerant circuit and refrig­erant amount. Refer to 12-5.9 "Check of LEV".
thermistors".
18
Outdoor unit operates.
7-time flash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes. Check refrigerant circuit and refrig-
erant amount.
19
8-time flash
2.5 seconds OFF
PAM protection PAM: Pulse Amplitude Modulation
The overcurrent fl ows into IGBT (Insulated Gate Bipolar tran­sistor : TR821) or when the bus-bar voltage reaches 320 V or more, PAM stops and restarts.
This is not malfunction. PAM protec­tion will be activated in the following cases; 1 Instantaneous power voltage drop (Short time power failure) 2 When the power supply voltage is high.
20
9-time flash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected.
verter/ compressor".
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 12-6-3. or 12-6-7.
2. LED is lighted during normal operation.
The flashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Flashing
Inverter P.C. board(Parts side)
Page 69
69
12-4. Trouble criterion of main parts (1)
Part name
Figure
Check method and criterion
Outdoor fan motor
R.V. coil
Expansion valve coil (LEV)
Measure the resistance between the terminals with a tester. (Part temperature -20°C ~ 40°C)
WHT - BLK BLK - RED
RED - WHT
Normal
Measure the resistance between the terminals with a tester. (Part temperature -20°C ~ 40°C)
Normal
1.20 k ~ 1.55 k
WHT - RED RED - ORN
YLW - BRN
BRN - BLU
Normal
37  ~ 54 
Measure the resistance with a tester. (Part temperature : -20°C ~ 40°C)
Measure the resistance with a tester. Refer to 12-6. “Test point diagram and voltage”, 12-6-1. or 12-6-3.
“Inverter P.C. board”, for the chart of thermistor.
Color of the lead wire
Color of the lead wire
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. Refer to 12-6. “Test point diagram and voltage”, 12-6-1. or 12-6-3. “Inverter P.C. board”, for the chart of thermistor.
Defrost thermistor (RT61) Fin temperature
thermistor (RT64)
31  ~ 41 
Measure the resistance between the terminals with a tester. (Part temperature -20°C ~ 40°C)
Compressor
Defrost heater SUZ-KA·VAH
Measure the resistance with a tester. (Part temperature -20°C ~ 40°C)
Normal
333 ~ 428
U-V
U-W
V-W
Normal
SUZ-KA35VA(H).TH
0.41  ~ 0.53 
SUZ-KA25VA(H).TH
1.28  ~ 1.66 
23
W
U
V
1
WHT
RED BLK
23
W
U
V
1
WHT
RED BLK
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor(RT68) (SUZ-KA25/35VA(H)R1.TH)
SUZ-KA25VA(H)R1.TH
1.36 ~ 1.93
SUZ-KA35VA(H)R1.TH
1.52  ~ 2.17 
SUZ-KA25/35VA(H).TH
SUZ-KA25/35VA(H)R1.TH
29  ~ 42 
SUZ-KA25/35VA(H).TH
SUZ-KA25/35VA(H)R1.TH
1.19 k ~ 1.78 k
LEV
WHT
RED
ORN
YLW
BRN
BLU
SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAR1.TH SUZ-KA35VAR1.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH SUZ-KA25VAHR1.TH SUZ-KA35VAHR1.TH
Page 70
70
SUZ-KA50VA.TH SUZ-KA50VA1.TH SUZ-KA50VAR2.TH SUZ-KA60VA.TH SUZ-KA60VA1.TH SUZ-KA60VAR2.TH SUZ-KA71VA.TH SUZ-KA71VA1.TH
12-4. Trouble criterion of main parts (2)
Part name
Figure
Check method and criterion
Outdoor fan motor
R.V. coil
Expansion valve coil (LEV)
Measure the resistance between lead wires with a tester. (Part temperature -10°C ~ 40°C)
RED - BLK BLK - WHT WHT - RED
Normal
Measure the resistance with a tester. (Part temperature -10°C ~ 40°C)
Normal
SUZ-KA50/60VAR2.TH
1.32 k ~ 1.62 k
Other models
2.6 k ~ 3.3 k
WHT - RED RED - ORN YLW - BRN
BRN - BLU
Normal
37.4  ~ 53.9 
Measure the resistance with a tester. (Part temperature : -10°C ~ 40°C)
Measure the resistance with a tester. Refer to 12-6. “Test point diagram and voltage”, 12-6-4. “Outdoor
electronic control P.C. board” or 12-6-7. “Inverter P.C. board”, for the chart of thermistor.
Color of the lead wire
Color of the lead wire
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 12-6. “Test point diagram and voltage”, 12-6-4. “Outdoor electronic control P.C. board” or 12-6-7. “Inverter P.C. board”, for the chart of thermistor.
Defrost thermistor (RT61)
Fin temperature thermistor (RT64)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor (RT68)
13.4  ~ 16.4 
Measure the resistance between the terminals with a tester. (Part temperature -10°C ~ 40°C)
Compressor
High pressure switch (HPS)
SUZ-KA60VAR2.TH SUZ-KA71VA
(1).TH
Pressure
3.7 ± 0.15 MPa
4.8 MPa
Close
Open
Normal
SUZ-KA50/60VAR2.TH
0.86 ~ 1.06
SUZ-KA50/60VA(1).TH
0.40 ~ 0.49
SUZ-KA71VA(1).TH
1.29 ~ 1.49
W
U
V
WHT
RED
BLK
U
RED
WHT
BLK
V
W
(W)
(V)
(U)
LEV
WHT
RED
YLW
BRN
ORN
BLU
+ 0.05
- 0.1
Page 71
71
[SUZ-KA25/35VA(H).TH]
Check of open phase
B
Check of intelligent power module
C
How to check inverter/compressor
A
Check the voltage between terminals.
Check the compressor.
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Check the resistance of the intelligent power module.
See D “Check of compressor”.
No
See B “Check of open phase”.
See C 'Check of intelligent power module'.
Is the resistance
infinite?
Yes
Replace the inverter P.C. board.
No (0~several
")
Yes
Are the voltages balanced?
Replace the inverter P.C. board and compressor.
With the connector between compressor and the intelligent power
module disconnected, activate the inverter and check if the inverter is normal by measuring the balance of voltage between terminals.
<< Operation method>> Start cooling or heating operation by pressing the EMERGENCY OPERATION switch
on the indoor unit. (test-run mode : refer to page 31 for SLZ/SUZ and 37 for SEZ/SUZ.)
<<Measurement point>> + Measure AC voltage between the lead wires at 3 points.
BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of inverter P.C. board flashes 9 times.
Measure the resistance between terminals on the intelligent
power module. <<Measurement point>> at 6 points BLK-WHT, WHT-BLK BLK-RED, RED-BLK WHT-RED, RED-WHT
<<Judgement>> Infinite []···········Normal 0~dozens of ······Abnormal (short)
Output voltage [V]
115V
ohmmeter indication
Normal (infinite)
Abnormal (0~dozens of )
X1
X1
LED
Inverter P.C. board
9-time flash
2.5-second OFF
Flashing
12-5. Troubleshooting flow
Outdoor unit does not operate.
Page 72
72
Check of compressor
D
Check of compressor winding
E
Check of compressor operation time
F
Disconnect the connector (CN61) between compressor and intelligent
power module, and measure the resistance between the compressor terminals. Measurement point at 3 points of lead wire. BLK-WHT BLK-RED WHT-RED
<<Judgment>>
Refer to 12-4.. 0[] ······················Abnormal [short] Infinite[] ·············Abnormal [open] NOTE 1. Be sure to zero the ohmmeter before measurement.
2. Winding resistance for each phase at 20. Refer to 4. SPECIFICATION.
Normal (1~several )
Abnormal (0······ s h o r t )
Abnormal (infinite······ o p e n )
Ohmmeter indication
Ok
Replace the compressor.
"Check of compressor winding". Is the compressor normal?
No
Replace the compressor.
No
Yes
X1
X1
X1
23
W
U
V
1
WHT
Compressor motor
RED BLK
Yes
"Check of compressor operation time". Does the
compressor operate continuously?
Is the compressor operation time more than 10 seconds?
No
Check the refrigerant circuit.
Yes
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current. <<Operation method>>
[For wireless remote controller use model] Start heating or cooling operation by pressing the EMERGENCY OPERATION switch on the indoor unit. (Test-run mode) [For wired remote controller use model] Start heating or cooling operation by pressing the TEST button
twice on the remote controller. (Test-run mode) <<Measurement>> Measure the time from the start of outdoor fan running to the stop of
compressor due to over current. <<Judgment>>
For reference
0~10 seconds······················Abnormal (compressor short or poor contact)
(compressor lock-out)
10 seconds~5 minutes········Abnormal (refrigerant circuit defect)
more than 5 minutes············Normal
Outdoor fan starts Abnormal (Compressor winding short or layer short) (compressor connector poor contact) (compressor lock-out)
Abnormal (Refrigerant circuit defect, etc.)
Normal
0 second
10 seconds
5 min.
[SUZ-KA25/35VA(H).TH]
Page 73
73
Check of R.V. coil
H
Is there 230V AC between CN721 and on the power P.C. board 3 minutes after
the power supply is turned ON?
Yes
No
Replace the power P.C. board.
Replace the 4-way valve.
CN721
Power P.C. board (soldered side)
Disconnect connector (CN61) between compressor and intelligent power module. [
For wireless remote controller use model
] Turn ON the power supply and press the EMERGENCY OPERATION switch (COOL switch). [For wired remote controller use model] Turn ON the power supply and press the TEST button twice (COOL mode).
Is there 230V AC between CN721 and on the power P.C.board 3 minutes after the power supply is turned ON?
No
Yes
Disconnect connector (CN61) between compressor and intelligent power module. [
For wireless remote controller use model
] Turn ON the power supply and press the EMERGENCY OPERATION switch (HEAT switch). [For wired remote controller use model] Turn ON the power supply and press the TEST button twice (HEAT mode).
Replace the power P.C. board.
• Defective R.V. coil
• Defective 4-way valve
+First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4.. +In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector although no
signal is being transmitted to R.V. coil. Check if CN721 is connected.
Unit operates COOL mode even if it is set to HEAT mode.
Unit operates HEAT mode even if it is set to COOL mode.
The thermistors in the outdoor unit are abnormal.
Check of outdoor thermistors
G
[SUZ-KA25/35VA(H).TH]
Measure the resistance between CN641 and .
Measure the resistance between CN642 and .
No
Yes
Replace the thermistor except RT64. In case that RT64 is abnormal, replace the inverter P.C. board, since RT64 is combined with the inverter P.C. board.
Replace the inverter
P.C. board.
Disconnect the connectors CN641, CN642 and CN643 from the inverter P.C. board.
(Check the characteristics of each thermistor.)
Defrost thermistor RT61
Measure the resistance between CN641 and .
Reconnect the connectors CN641, CN642 and CN643. Turn ON the power supply and press EMERGENCY OPERATION switch (For wireless remote controller use model)./TEST button twice (For wired remote controller use model).
Discharge temperature thermistor RT62
Fin temperature thermistor RT64
Is the resistance of thermistor normal? (Refer to 12-6.1.)
No
Yes
Does the unit operate 10 minutes or more?
OK. (Cause is poor contact.)
Measure the resistance between CN643 and .
Ambient temperature thermistor RT65
Page 74
74
[SUZ-KA25/35VA(H).TH]
Check of power supply
J
Inverter does not operate.
Check of outdoor fan motor
I
Outdoor fan motor does not operate.
Disconnect the connector (CN61) between compressor and intelligent power module. [
For wireless remote controller use model
] Turn ON power supply and press EMERGENCY OPERATION switch. [
For wired remote controller use model
] Turn ON the power supply and press the TEST button twice.
Check the electric parts in main circuit.
Ok. If flash, refer to 12-3.
Is there voltage 280V ~ 370V DC between DB61 (+) and DB61 (-) on the inverter P.C. board? Refer to 12-6.1.
Dose LED on the inverter P.C. board light up or flash? Refer to 12-6-1.
Outdoor terminal block
S3 S2 S1
Yes
Yes
Yes
No
No
Replace the indoor
electronic control P.C. board.
No
Yes
No
Indoor/outdoor connecting wire
Replace the inverter P.C. board.
DB61
280V~370V DC
Inverter P.C. board (Solder side)
Is there voltage 230V AC
between the indoor terminal block S1 and S2?
Rectify indoor/outdoor connecting wire.
Does POWER lamp on the indoor unit light up?
Does the voltage between each terminal repeat 5V and 0V DC by turns?
Does the outdoor fan rotate smoothly?
Check the inverter P.C. board. (Refer to 12-5.!)
No
Yes
Yes
No ( Fixed to either 5V or 0V DC)
Yes
No
Rotate the outdoor fan slowly by hand, and measure the voltage of CN931 (Measurement of feedback output). Between (+) and (-) Between (+) and (-) Between (+) and (-)
Is the resistance between each terminal of outdoor fan motor normal? (Refer to 12-4.)
Disconnect CN932 from the inverter P.C. board.
Replace the outdoor fan motor.
CN931
CN932
Inverter P.C. board (Solder side)
Turn ON the power supply.
Page 75
75
Check of current limiting resistor
K
Outdoor unit does not operate at all or stops immediately due to over current.
Check other electric parts in the main circuit together in the case of the defective current-limiting resistor.
Turn ON the power supply and press EMERGENCY OPERATION switch of the indoor unit.
Replace the power P.C. board or the compressor.
Replace the power P.C. board or the inverter P.C. board.
Does the rush current limiting relay (X64) work properly? (Normally it close 1 minutes after outdoor unit power ON.)
Yes
No
No
No
Yes
Yes
Does the current-limiting resistor (R64A or R64B) on the power P.C. board short out? (Normal resistance : 5
5% )
Replace the power P.C.board.
Replace the power P.C. board.
Does LED on the inverter P.C. board light up?
Check of LEV (Expansion valve)
L
Heating/Cooling does not work sufficiently.
[SUZ-KA25/35VA(H).TH]
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
(For wireless remote controller use model)
Replace the LEV.
Expansion valve operates in full-opening direction.
Is LEV properly fixed to the expansion valve?
OK
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Does the resistance of LEV have the characteristics? (Refer to 12-4.)
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1.Pin(-) Pin(+)
2.Pin(-) Pin(+)
3.Pin(-) Pin(+)
4.Pin(-) Pin(+) Is there about 3~5V AC between each? NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Replace the expansion valve.
Yes
No
No
Properly fix the LEV to the expansion valve.
Replace the inverter P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON again.
2. Press the RESET button on the remote controller.
1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.
Turn ON the power supply. <Preparation of the remote controller> While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button. And release the other two buttons after all LCD except the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
ON/OFF
RESET
TOO WARM
TOO COOL
MODE
AUTO COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
ON/OFF
TOO
WARM
TOO
COOL
h
Page 76
76
[SUZ-KA25/35VA(H).TH]
Check of defrost heater
M
Replace the inverter P.C. board.
Is there 230V AC between CN722 and on the power P.C. board? Refer to 12-6-2.
Yes
No
No problem of the power P.C. board.
Is the voltage between CN726 (+)-(-)on the power P.C. board 0V DC? Refer to 12-6-2.
Yes
No
Replace the power P.C. board.
NOTE: In case both thermistors are more than the above temperature, cool them with cold water etc...
In HEAT mode, for more than 5 minutes, let the ambient temperature thermistor continue to read 5 or less, and let the defrost thermistor continue to read -1 or less.
3 2 1
230V AC
Check the following points before checking electric continuity.
1) Does the resistance of ambient temperature thermistor have the characteristics? Refer to 12-6-1.
2) Is the resistance of defrost heater normal? Refer to 12-4.
3) Does the heater protector remain conducted (not open)?
4) Are both ambient temperature thermistor and circuit of defrost heater securely connected to connectors?
26H
CN726
CN722
H
2
1
2
1
23
Outdoor base gets frozen.
<SUZ-KA25VAH SUZ-KA35VAH>
Check of LEV (Expansion valve)
L
Start
Replace the inverter P.C. board.
Replace the LEV coil.
Disconnect the connector CN724 is there normal resistance to LEV coil?
Yes
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
No
Normal
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
Yes
No
(For wired remote controller use model)
Page 77
77
[SUZ-KA25/35VA(H).TH]
Check of inverter P.C. board
N
Outdoor fan motor does not operate, or stops immediately after starting up.
Yes (10-time blink)
Yes
Check the LED indication on the inverter P.C. board. Does the LED blink 10-time?
No
No
Is the fuse (F901) blown on the inverter P.C. board?
Replace the inverter P.C. board.
CN931
CN932
Inverter P.C.board (Solder side)
Check the corresponding parts following LED indication. (Refer to 12-3.)
Operate the outdoor unit by starting EMERGENCY OPERA TION.
Check the connection of the connectors (CN931, CN932) of outdoor fan motor. If the connection is poor, make it correct.
Check the outdoor fan motor. Refer to12-5..
Page 78
78
[SUZ-KA25/35VA(H).TH]
(For wireless remote controller use model)
How to check miswiring and serial signal error (when outdoor unit does not work)
O
Is there rated voltage in the power supply?
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
2 Be careful of the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
No
No
Yes
No
Yes
Yes
Yes
No
Yes
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does the lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power supply.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block is S2 and S3. 1
B
Turn ON the power supply.
Check the wiring.
Make them correct.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C.board. 2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
Is serial signal error indicated 6 minutes later?
No
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.board repeat "3.6-second-OFF and 0.8-second­quick blinking"?
3
As for indoor unit.
Inverter P.C.board (Parts side)
LED
Blinking
Is serial signal error indicated 6 minutes later?
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON it again.
· Press EMERGENCY OPERATION switch.
·
Reinstall the
unit apart from inverter-contro lled lighting equipment.
·
Attach a filter
on receiving section of the indoor unit.
Yes
B
A
Page 79
79
[SUZ-KA25/35VA(H).TH]
(For wired remote controller use model)
How to check miswiring and serial signal error (when outdoor unit does not work)
O
Is serial signal error indicated 6 minutes later?
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON it again.
· Press TEST button twice.
·
Reinstall the
unit apart from inverter-contro lled lighting equipment.
·
Attach a filter
on receiving section of the indoor unit.
Yes
B
A
Is there rated voltage in the power supply?
Is there any mis wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
No
Yes
No
Yes
Yes
No
No
Yes
No
Yes
Serial signal error display
As for indoor unit.
Inverter P.C.board (Parts side)
LED
Blinking
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does POWER lamp on remote controller light up? <Confirmation of the power to the indoor unit>
Press TEST button twice.
Check the power supply.
Is the self-check of the remote controller displayed 6 minutes after?
POWER lamp blinks.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring. Short-circuit outdoor terminal block is S2 and S3. 1
B
Check the wiring.
Make them sure.
1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or not lighted)
No
Yes
No
Yes
2 Be careful of the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
Yes
Yes
No
Yes
Turn ON the power supply.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C.board. 2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
No
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.board repeat "3.6-second-OFF and 0.8-second­quick blinking"?
3
Page 80
80
Replace or repair the antenna. Replace or repair the coaxial cable.
No
No
No
Yes
Yes
No
No
Yes
Yes
Yes
Is the distance between the antennas and the indoor unit within 3m, or is the distance between the antennas and the outdoor unit within 3m?
Is the distance between the TV sets or radios and the indoor unit within 1m, or is the distance between the TV sets or radios and the outdoor unit within 3m?
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the antenna wiring?
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Even if all of the above conditions are fulfilled, the electromagnetic noise may enter, depending on the electric field strength or the installation condition (combination of specific conditions such as antennas or wiring). Check the followings before asking for service.
1.Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2.Channel, frequency, broadcast station affected by the electromagnetic noise
3.Channel, frequency, broadcast station unaffected by the electromagnetic noise
4.Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, grounding wire, antennas, wiring from antennas, receiver
5.Electric field intensity of the broadcast station affected by the electromagnetic noise
6.Presence or absence of amplifier such as booster
7.Operation condition of air conditioner when the electromagnetic noise enters in.
1)Turn OFF the power supply once, and then turn ON the power supply. In this situation check for the electromagnetic noise.
2)Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3)After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4)Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation check for the electromagnetic noise.
After checking the above, consult the service representative.
Is the unit earthed?
Earth the unit.
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas.
[
SUZ-KA25/35VA(H).TH SUZ-KA50/60/71VA(1).TH
SUZ-KA60VAR2.TH]
Electromagnetic noise enters into TV sets or radios
P
Page 81
81
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
Check of power supply
Outdoor unit does not operate. (LED display: display OFF)
Turn on power supply.
No
Yes
Yes
No
No
Yes
No
Yes
Yes
No
Replace the power board.
Start
Check the connecting of parts of main power supply circuit.
Is there voltage of 230V AC in the power supply terminal block?
Is the output voltage from the noise filter P.C. board 230V AC?
Is the input voltage to the outdoor electronic control P.C. board 325V DC?
Check the power supply cable.
Replace the outdoor electronic control P.C. board.
Replace the noise filter P.C. board.
Is fuse (F64) blown?
Is the input voltage to the power board 230V AC?
Replace the fuse.
Replace the reactor.
Q
Page 82
82
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
Is there rated voltage in the power supply?
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or not lighted)
No
Yes
No
Yes
Yes
No
Yes
No
Yes
2 Be careful of the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
No
No
Yes
No
Yes
Yes
Yes
No
Yes
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does the lamp of OPERATION INDICATOR lamp light up? <Confirmation of the power to the indoor unit>
Press EMERGENCY OPERATION switch once.
Check the power supply.
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block is S2 and S3. 1
B
Turn ON the power supply.
Check the wiring.
Make them correct.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C.board. 2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
Is serial signal error indicated 6 minutes later?
No
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.board repeat "3.6-second-OFF and 0.8-second­quick blinking"?
3
Is serial signal error indicated 6 minutes later?
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON it again.
· Press EMERGENCY OPERATION switch.
·
Reinstall the unit apart from inverter-contro lled lighting equipment.
·
Attach a filter on receiving section of the indoor unit.
Yes
B
A
Outdoor electronic control P.C. board
Blinking
(Parts side)
LED2
LED1
As for indoor unit.
How to check miswiring and serial signal error (when outdoor unit does not work)
When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Indoor unit does not operate.
Outdoor unit does not operate.
(For wireless remote controller use model)
R
Page 83
83
When unit cannot operate neither by the remote controller.
Indoor unit does not operate.
Outdoor unit does not operate.
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
Is serial signal error indicated 6 minutes later?
No
· Turn OFF inverter-controlled lighting equipment.
· Turn OFF the power supply and then turn ON it again.
· Press TEST button twice.
·
Reinstall the
unit apart from inverter-contro lled lighting equipment.
·
Attach a filter
on receiving section of the indoor unit.
Yes
B
A
Is there rated voltage in the power supply?
Is there any mis wiring, poor contact, or wire disconnection of the indoor/outdoor connecting wire?
No
Yes
No
Yes
Yes
No
No
Yes
No
Yes
Serial signal error display
As for indoor unit.
Turn OFF the power supply.
Turn ON the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Does the left lamp of OPERATION INDICATOR lamp on remote controller light up? <Confirmation of the power to the indoor unit>
Press TEST button twice.
Check the power supply.
Is the self-check of the remote controller displayed 6 minutes after?
The left lamp of OPERATION INDICATOR lamp blinks.
A
Check the wiring.
Make them sure.
Outdoor electronic control P.C. board
Blinking
(Parts side)
LED2
LED1
1. Miswiring may damage indoor electronic control P.C. board during the operation. Be sure to confirm the wiring is correct before the operation starts. 3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C.board or the outdoor electronic control P.C.board is normal, LED blinks 6 times after 3 minutes.
(Lighted or OFF)
No
Yes
No
Yes
2 Be careful of the residual voltage of smoothing capacitor.
Be sure to release the failure-mode recall function after checking.
Yes
Yes
No
Yes
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not mis-wiring.
Short-circuit outdoor terminal block is S2 and S3. 1
B
Turn ON the power supply.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20V DC between outdoor terminal block S2 and S3? <Confirmation of serial signal>
Is there rated voltage between indoor terminal block S1 and S2? <Confirmation of power voltage>
Replace the indoor electronic control P.C. board.
Replace the inverter P.C. board or the outdoor electronic control P.C.board. 2
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Is there any error of the indoor/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
No
Replace the indoor/outdoor connecting wire.
Replace the indoor/outdoor connecting wire.
No
Does the LED on the inverter P.C. board or the outdoor electronic control P.C.board repeat "3.6-second-OFF and 0.8-second­quick blinking"?
3
How to check miswiring and serial signal error (when outdoor unit does not work)
(For wired remote controller use model)
R
Page 84
84
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
Check of R.V. coil
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power supply, start EMERGENCY OPERATION in HEAT mode.
Is there voltage of 230V AC between pin1 and pin 2 at connector CN912?
Turn off power supply of indoor and outdoor unit.
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.
2. 3 minutes after turning on the power supply, start EMERGENCY OPERATION in HEAT mode.
Replace the 4-way valve.
Replace the noise filter P.C. board.
Replace the R.V. coil.
Is there voltage 12V DC between the connector CN781 pin 5 (+) and pin 3 (-)?
Replace the electronic control P.C. board.
Disconnect the connector CN912 in noise filter P. C. board. Is there normal resistance to R.V. coil?
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning on the power supply, start EMERGENCY OPERATION in COOL mode.
Is there voltage of 230V AC between pin1 and pin 2 at connector CN912?
1. Turn off power supply of indoor and outdoor unit, and disconnect the connector CN781 in the outdoor electronic control P.C. board.
2. 3 minutes after turning on the power supply, start EMERGENCY OPERATION in COOL mode.
Replace the 4-way valve.
Replace the noise filter P.C. board.
Is there voltage 12V DC between the connector CN781 pin 5 (+) and pin 3 (-)?
Replace the outdoor electronic control P.C. board.
If the connector CN912 is not connected or R.V. coil is open, voltage occurs between terminals even when the control is OFF.
• When heating operation does not work.
• When cooling operation does not work.
The cooling operation or heating operation does not operate. (LED display: Both LED1 and LED2 lighting)
S
Page 85
85
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
How to check inverter/ compressor
When heating, room does not get warm. When cooling, room does not get cool.
LED display:
LED1
LED2 Lighting Lighting Lighting
Twice
Twice
Goes out
Check of LEV
No
Yes
No
Yes
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the LEV body securely.
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
Disconnect the connector CN795. Is there normal resistance to LEV coil?
Normal
Replace the outdoor electronic control P.C. board.
Replace the LEV coil.
When cooling, heat exchanger of non-operating indoor unit frosts. When heating, non-operating indoor unit get warm.
LED display:
LED1 LED2
Lighting
Lighting
6 time Goes out
No
No
Yes
Yes
Yes
No
Yes
No
Disconnect the terminal of the compressor. 3 minutes after turning on the power supply, start
EMERGENCY OPERATION.
Is output balanced?
Clarify the causes by counting time until the inverter stops. 0 to 10 seconds: compressor rare short 10 to 60 seconds: compressor lock 60 seconds to 5minutes: refrigerant circuit defective 5 minutes or more: normal
Measure the voltage between each lead wire leading to the compressor. U (BLK) - V (WHT) V (WHT) - W (RED) W (RED) - U (BLK) Is voltage output on right table?
Turn off power supply of indoor and outdoor unit, and measure the compressor winding resistance between the compressor terminals. Is the resistance between each terminal normal?
Is the input voltage to the outdoor electronic control P.C. board 370V or more?
Reconnect the lead wire of compressor, and turn on power supply to indoor and outdoor unit. 3 minutes later, starts EMERGENCY OPERATION.
Replace the compressor.
Replace the power board.
COOL HEAT
150V
(48Hz)
170V
(64Hz)
• After the outdoor fan starts running, wait for 1 minutes or more before measuring the voltage.
• The output voltage values have the tolerance of $20%.
T
U
Page 86
86
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
Check of outdoor thermistors
When thermistor is abnormal.
No
Yes
No
Yes
Reconnect the connector CN661 on the outdoor electronic control P.C. board and CN3 on the power board, and disconnect the lead wire leading to the compressor. 3 minutes after turning on the power supply, start (EMERGENCY) OPERATION.
Thermistor Defrost thermistor Discharge temperature thermistor Outdoor heat exchanger temperature thermistor Fin temperature thermistor Ambient temperature thermistor
Symbol
RT61 RT62 RT68 RT64 RT65
Connector, Pin No. Between CN661 pin1 and pin2 on the outdoor electronic control P.C. board Between CN661 pin3 and pin4 on the outdoor electronic control P.C. board Between CN661 pin7 and pin8 on the outdoor electronic control P.C. board Between CN3 pin1 and pin2 on the outdoor power board Between CN663 pin1 and pin2 on the outdoor electronic control P.C. board
Disconnect the connector in the outdoor electronic control P.C. board or the outdoor power board (see below table), and measure the resistance of thermistor. Is the thermistor normal?
Does thermistor operate 10 minutes or more though the thermistor abnormality is not displayed?
Replace the thermistor.
Normal
Replace the outdoor electronic control P.C. board.
Check of outdoor fan motor
Fan motor does not operate or stops operating shortly after starting the operation.
Yes
Yes
Yes
No
No (Fixed to either 5V or 0V DC)
Start
Check the connection between the connector CN931 and CN932.
Disconnect CN932 from outdoor electronic control P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between (+) and (-) Between (+) and (-) Between (+) and (-)
Is the resistance between each terminal of outdoor fan motor normal?
Does the outdoor fan motor rotates smoothly?
Does the voltage between each terminal become 5V DC and 0V DC repeatedly?
Replace the outdoor DC fan motor.
Replace the outdoor electronic control P.C. board.
V
W
Page 87
87
[SUZ-KA50/60/71VA(1).TH SUZ-KA60VAR2.TH]
X Check of HPS
Infinity
0
Yes
No
1. Disconnect the connector CN681 in the electronic control P.C. board.
2. Check the resistance of HPS after 1 minutes have passed since the outdoor unit power supply was turned off.
Check the resistance between each terminal.
Reconnect CN681. Turn on power supply to the indoor and outdoor unit. 3 minutes later, starts EMERGENCY OPERATION.
Is HPS protection displayed immediately after compressor starts?
Replace HPS.
Replace the electronic control P.C. board.
Normal
When the operation frequency does not go up from lowest frequency.
SUZ-KA60VAR2.TH SUZ-KA71VA
(1).TH
Outdoor unit does not operate at all, or stops immediately due to overcurrent.
Check of current-limiting resistor
Y
Turn ON the power supply and press EMERGENCY OPERATION switch.
Replace the outdoor electronic control P.C. board or power P.C.board or the compressor.
Replace the noise filter P.C. board or the outdoor electronic control P.C. board.
Does the rush current limiting relay(X64) work properly?
Open
Not open
No
No
Yes
Yes
Is the resistance of current-limiting resistor (R64A or R64B) on the noise filter P.C. board normal? (Normal resistance : 5$5%)
Replace the noise filter P.C.board.
Replace the power P.C. board.
Does LED on the outdoor electronic control P.C. board light up?
When the current-limiting resistor is open, the rush current limiting relay (X64) may not work properly.
Page 88
88
a How to check inverter/compressor
Are the voltages balanced?
Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See
d
“Check of compressor”.
No
Yes
See b “Check of open phase”.
With the connector between the compressor and the intelligent power module disconnected, activate the inverter and check if
the inverter is normal by measuring the balance of voltage between the terminals. The output voltage values have the tolerance of ± 20%. << Operation method>>
Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION
: Refer to page 31 for SLZ/SUZ and page 37 for SEZ/SUZ.) <<Measurement point>> At 3 points BLK (U) - WHT (V) BLK (U) - RED (W) WHT (V) - RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 12-6-3. (KA25/35VA) or 12-6-7.)
Refer to
f “Check of compressor operation
time”. Does the compressor operate continuously?
Check the refrigerant circuit.
OK.
No
Yes
Refer to e “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
d Check of compressor
b Check of open phase
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
9-time flash
2.5-second OFF
Is the compressor operation time more than 10 seconds?
No
Replace the compressor.
Yes
Page 89
89
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
e Check of compressor winding
Disconnect the connector (CN61) between the compressor and intelligent power module, and measure the resistance between
the compressor terminals. <<Measurement point>> at 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 12-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
f Check of compressor operation time
Compressor starts Abnormal
(IPM failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact,) (Outdoor P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second 1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board or the outdoor power board.
Replace the inverter P.C. board or the outdoor power board.
No
No
Is the thermistor normal? (Refer to 12-6-3. or 12-6-7. )
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
OK. (Cause is poor contact.)
Yes
Yes
g Check of outdoor thermistors
Disconnect the connector of thermistor in the outdoor P.C. board (see
below table), and measure the resistance of thermistor.
Connect the compressor and activate the inverter. Then measure the
time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY
OPERATION switch on the indoor unit. (TEST RUN OPERATION : Refer to page 31 for SLZ/SUZ and page 37 SEZ/SUZ.) <<Measurement>> Measure the time from the start of compressor to the stop of
compressor due to overcurrent.
Page 90
90
h Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 12-4. In case CN721 is not connected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although any signal is not being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721
and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector (CN61) between the compressor and the intelligent power module. Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 12-4.)
Check the connection between the connector CN931 and CN932.
Disconnect CN932 from outdoor electronic control P.C. board or the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the outdoor electronic control P.C. board or the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
i Check of outdoor fan motor
Page 91
91
j Check of power supply
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
No
Yes
Replace the indoor electronic control P.C. board.
Rectify indoor/outdoor connecting wire.
Yes
If light up, OK. If fl ash, refer to 12-3.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit light up?
Dose LED on the inverter P.C. board light up or fl ash? (Refer to 12-6-3. or 12-6-7.)
No
Replace the inverter P.C. board.
Is there voltage 280 - 370 VDC between DB61 (+) and DB61 (–) on the inverter P.C. board? (Refer to 12-6-3. or 12-6-7.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector (CN61) between compressor and intelligent power module. Turn ON power supply and press EMERGENCY OPERATION switch.
Inverter P.C. board (Solder side)
DB61
280 - 370 VDC
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
k Check of LEV
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin
(+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 ~ 5 VAC between each? NOTE: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to the expansion valve?
Does the resistance of LEV coil have the characteristics? (Refer to 12-4.)
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button. First, release RESET button.
And release the other two buttons after all LCD except
the set temperature in operation display section of the remote controller is displayed after 3 seconds.
Yes
No
No
Yes
No
Yes
Yes
ON/OFF
RESET
TOO WARM
TOO COOL
MODE
AUTO
COOL
DRY
HEAT
FAN
VANE
SELECT
TIME
ON/OFF
TOO
WARM
TOO
COOL
h
(For wireless remote controller use model)
Page 92
92
m Check of LEV (Expasion valve)
(For wired remote controller use model)
Turn on power supply to the outdoor unit after checking LEV coil is fi xed to the LEV body securely.
Yes
Disconnect the connector CN724 is there nor­mal resistance to LEV coil?
No
Replace the inverter P.C. board.
Replace the LEV coil.
No
Normal
Start
Is "click - click" sound heard? Or, do you feel vibration of the LEV coil with a hand?
Yes
Check the outdoor fan motor. (Refer to i.)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan mo­tor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 12-3.)
Yes
No
Yes (10-time fl ash)
No
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
n Check of inverter P.C. board
Page 93
93
p How to check miswiring and serial signal error
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
(For wireless remote controller use model)
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between outdoor termi­nal block S1 and S2?
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICA­TOR lamp light up? <Confi rmation of the power to the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connect­ing wire?
Yes
Correct them.
No
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3.
1
B
1. Miswiring may damage indoor electronic control P.C. board during the operation.
Be sure to confi rm the wiring is correct before the operation
starts.
3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
Turn ON the power supply.
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second­ON quick blinking"? 3
Yes
No (Lighted or not lighted)
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
2
2. Be careful of the residual voltage of smoothing capacitor.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between outdoor terminal block S2 and S3? <Confi rmation of serial signal>
Yes
No
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Yes
Replace the indoor/ outdoor connecting wire.
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiv­ing section of the indoor unit.
No
Is there rated voltage between indoor terminal block S1 and S2? <Confi rmation of power voltage>
No
No
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Yes
Replace the indoor/ outdoor connecting wire.
No
Replace the indoor electronic control P.C. board.
Yes
Be sure to release the failure-mode recall function after checking.
Yes
As for indoor unit.
Page 94
94
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
q How to check miswiring and serial signal error
(For wired remote controller use model)
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between outdoor termi­nal block S1 and S2?
No
Check the wiring.
Press TEST button once.
Does the left lamp of OPERATION INDICA­TOR lamp light up? <Confi rmation of the power to the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring, poor contact, or wire disconnection of the indoor/outdoor connect­ing wire?
Yes
Correct them.
No
A
Turn OFF the power supply. Check once more if the indoor/outdoor connecting wire is not miswiring. Short-circuit outdoor terminal block S2 and S3. 1
B
1. Miswiring may damage indoor electronic control P.C. board during the operation.
Be sure to confi rm the wiring is correct before the operation
starts.
3. Be sure to check this within 3 minutes after turning ON. After 3 minutes, LED blinks 6 times. Even when the inverter P.C. board or the outdoor electronic control P.C. board is normal, LED blinks 6 times after 3 minutes.
Turn ON the power supply.
Does the LED on the inverter P.C. board or the outdoor electronic control P.C. board repeat "3.6-second-OFF and 0.8-second­ON quick blinking"? 3
Yes
No (Lighted or not lighted)
Replace the inverter P.C. board or the outdoor electronic control P.C. board.
2
2. Be careful of the residual voltage of smoothing capacitor.
Turn OFF the power supply. Remove the short-circuit between outdoor terminal block S2 and S3. Turn ON the power supply. Is there amplitude of 10 to 20 VDC between outdoor terminal block S2 and S3? <Confi rmation of serial signal>
Yes
No
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other . Attach a fi lter on remote control receiv­ing section of the indoor unit.
No
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Yes
Replace the indoor/ outdoor connecting wire.
Is there rated voltage between indoor terminal block S1 and S2? <Confi rmation of power voltage>
No
As for indoor unit.
No
Is there any error of the in­door/outdoor connecting wire, such as the damage of the wire, intermediate connection, poor contact to the terminal block?
Yes
Replace the indoor/ outdoor connecting wire.
No
Replace the indoor electronic control P.C. board.
Yes
Be sure to release the failure-mode recall function after checking.
Yes
Page 95
95
r Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of ; indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
[SUZ-KA25/35VA(H)R1.TH SUZ-KA50VAR2.TH]
Page 96
96
Back side of unit
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature()
Ambient temperature thermistor(RT65)
Defrost thermistor(RT61)
Temperature()
Discharge temperature thermistor(RT62)
0 10 20 30 40 50 60 70 80 90 100 110 120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(
)
Fin temperature thermistor(RT64)
Resistance(k)
Resistance(k)
Resistance(k)
Output to drive outdoor fan motor (CN932)
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor /RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor/RT61
(CN641)
LEV connector (CN724)
230V AC DB61
Connecting wire with power P.C. board (CN725)
Jumper wire for change in defrost setting (JS)
Front side of unit
DB61 280V ~ 370V DC
Smoothing capacitor (C63C)
Smoothing capacitor (C63A)
Smoothing capacitor (C63B)
Rotational frequency
feedback signal of outdoor fan motor
(CN931)
1(+) 2(+) 3(+) 45V 5GND
Output to drive compressor (LDW, LDV, LDU)
LED monitor lamp
Connector for indoor/ outdoor communication (CN601)
(+)
(-)
12-6. Test point diagram and voltage 12-6-1. Inverter P.C. board SUZ-KA25VA.TH SUZ-KA35VA.TH
SUZ-KA25VAH.TH SUZ-KA35VAH.TH
Fuse (F801)
Fuse (F901)
Page 97
97
12-6-2. Power P.C. board
Heater connector (CN722) Refer to 12-5.M
R.V. coil (CN721) 230V AC
230V AC
Back side of unit
SUZ-KA25VAH SUZ-KA35VAH
}
SUZ-KA25VA.TH SUZ-KA35VA.TH SUZ-KA25VAH.TH SUZ-KA35VAH.TH
Front side of unit
Connecting wire with inverter P.C.board (CN726) Refer to 12-5.M
230V AC
Varistor (NR63)
Varistor (NR62)
Varistor (NR64)
Page 98
98
12-6-3. Inverter P.C. board SUZ-KA25VAR1.TH SUZ-KA35VAR1.TH SUZ-KA25VAHR1.TH SUZ-KA35VAHR1.TH
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(°C)
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature(°C)
Discharge temperature thermistor(RT62)
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature(°C)
Fin temperature thermistor(RT64)
Resistance(kΩ)
Resistance(kΩ)
Resistance(kΩ)
Back side of unit
Fin temperature
thermistor /RT64
(CN642)
Ambient temperature
thermistor /RT65
(CN643)
Discharge temperature
thermistor /RT62
(CN641)
Defrost thermistor
/RT61(CN641)
LEV connector (CN724)
DB61 DC 260 - 300 V
Front side of unit
AC 230 V
Smoothing capacitor (C62)
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) 250 V 3.15 A
Smoothing capacitor (C61)
Smoothing capacitor (C63)
Fuse (F901) 250 V 3.15 A
R.V.coil (CN721) 230 VAC
Jumper wire for changing defrost setting (JS)
Output to drive outdoor
fan motor (CN932)
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Heater connector (CN722)
SUZ-KA25/35 VAHR1.TH
Fuse (F801) 250 V 3.15 A
0 102030405060708090100110120
0
100
200
300
400
500
600
700
AC 230 V
LED monitor lamp
Page 99
99
12-6-4. Outdoor electronic control P.C. board SUZ-KA50VA
(1).TH SUZ-KA60VA(1).TH SUZ-KA60VAR2.TH SUZ-KA71VA(1).TH
LED 1 LED 2
CN801
325V DC
~
370V DC
Input
(
(
CN932
20-90V AC
GND
5V
5V DC
pulse wave
(
To fan
motor
Defrost thermistor (RT61)
Discharge temperature thermistor (RT62)
Outdoor heat exchanger
temperature thermistor (RT68)
(
(
(+)
(–)
(+)
Rush current relay
(–)
R.V. coil (–)
(
12V
DC
15V
15V
CN931
(+)
(–)
(
CN661
CN701
Signal transmission
(To power board)
5V DC pulse wave
(+)
(–)
(
GND
CN702
Signal reception
(From power board)
5V DC pulse wave
GND (power board)
CN781
CN795
12V DC
pulse wave
LEV
(
(
(
(
(
-20-10 0 10203040
100
90 80 70 60 50 40 30 20 10
0
0 1020304050607080
200 180 160 140 120 100
80 60 40 20
0
Resistance (k)
Resistance (k)
Temperature ()
Temperature ()
Defrost thermistor (RT61) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)
Fin temperature thermistor (RT64
)
0 102030405060708090100110120
700 600 500 400 300 200 100
0
Resistance (k)
Temperature ()
Discharge temperature thermistor (RT62)
F801
FUSE
3.15A/250V
(
Ambient temperature
thermistor (RT65)
CN663
Serial signal Room A
5~10V DC
CN601 230V AC
50 Hz Input
High pressure switch
SUZ-KA60VAR2 SUZ-KA71VA
CN681
(
(
Page 100
100
{
CN912 R.V. coil 230V AC
230V AC 50Hz Input
230V AC 50Hz Output
{
CN901 To electronic control P.C. board
F64 FUSE 2A/250V
F911 FUSE 1A/250V
12-6-5. Noise filter P.C. board SUZ-KA50VA
(1).TH SUZ-KA60VA(1).TH SUZ-KA60VAR2.TH SUZ-KA71VA(1).TH
CN902 To power board
{
CN903 To power board
{
230V AC 50Hz Output
NR64 VARISTOR