When using the product where it is exposed to high temperatures and humidity (30℃ or higher, RH 80% or higher), or fogs
occur frequently, moisture is likely to condense in the core, resulting in the dripping of condensation water. The product
should not be used under such conditions.
Outdoor air may be introduced into the product owing to the pressure difference between indoor and outdoor or external winds
even when the product is not operated. It is recommended to install also an electrically operated damper to block the outdoor air.
In a cold weather area, an area with strong external winds or where fogs occur frequently, cold outdoor air, external winds or
fog may be introduced into the product when its operation is stopped. It is recommended to install also an electrically
operated damper to shut them out.
In a cold weather area, or others, dewing or freezing could occur on the main unit, where the duct is connected, or other sections,
depending on the conditions of outdoor air and indoor temperature and moisture, even if they are within the range of operating conditions.
Make sure to confirm the operating conditions and other precautions, and do not use the product if dewing or freezing is anticipated.
*Example of dewing condition – Outdoor air: -5˚C or lower, dew-point temperature at installation place: 10˚C or higher
(When the indoor temperature is 22˚C or higher with the relative humidity higher than 50%, or other)
When using the product in an environment where there is a window, or opening near the outdoor louvre , where insects are
likely to gather around the light , take note that small insects may intrude into the product
.
Do not install the product near a bedroom.
Provide heat insulation to all ducts to prevent moisture condensation.
Do not use vent caps or round hoods in places directly exposed to rain.
Do not install the Lossnay unit in the ceiling of bedroom.
OA intake should be placed where it is not exposed to rain.
CAUTION
Unit (mm)
Outline Drawings
Trial Operation
Sample installation
Attention
After the product has been installed, carry out a trial operation.
If an error code should be flash, refer to the following table and take the required action.
1. Trial operation with the remote controller (PZ-45SLJ-E)
OA
(Outside air)
EA
(Exhaust air)
OA
(Outside air)
Hood or Louvre
(to prevent rain water
from seeping in)
Downward gradient of duct:
1/30 or more (toward wall side, provide 1m or more )
(to prevent rain water from seeping in)
EA
(Exhaust air)
RA
(Return air)
RA
(Return air)
SA
(
Supply air)
SA
(
Supply air)
Anchor bolt, nut
(Not included)
Supply air grille
(Not included)
Return air grille
(Not included)
Anchor bolt, nut
(Not included)
φ
200 Duct
(Not included)
Function setting
Configure the function setting using the function selection switch (SW-2) in the control box.
The setting can be changed at any time.
Configuring function selection switch (SW-2)
Ventilation stop by low SA temperature / high SA temperature and automatic recovery
When Lossnay detects low or high temperatures out of the
SA temperature setting range, it stops ventilation. Lossnay
checks the SA temperature every two hours. When it
detects a temperature within the setting range, it starts
operating again at the fan speed used before stopping.
※"STby"(Standby) is displayed on the remote controller if
Lossnay does not operate due to the above function.
※"Lo" is displayed on the remote controller when the
temperature is -10
℃ or lower.
OFF ON
SW2
Operation
7
8
Lossnay stops when the SA temperature is
detected 8
℃ or lower.
7
8
Lossnay stops when the SA temperature is
detected 10
℃ or lower.
7
8
Lossnay stops when the SA temperature is
detected 12
℃ or lower.
7
8
Invalid
9
10
9
10
9
10
9
10
Lossnay stops when the SA temperature is
detected 31
℃ or higher.
Lossnay stops when the SA temperature is
detected 28
℃ or higher.
Lossnay stops when the SA temperature is
detected 25
℃ or higher.
Invalid
Relevant button
Relevant display items
Sequence
1
2
3
4
5
Initiate the supply of power to the Lossnay unit. (The [HO]
display will flash for approximately 40 seconds)
Press the ON/OFF button. The Operation lamp will turn on and
the Lossnay unit will begin to operate.
Press the DISPLAY ℃button to select the display of SA or IA
temperature.
Press the Fan Speed Adjustment button to select low, middle,
or high fan speed.
Press the ON/OFF button. The Operation lamp will turn off and
the Lossnay unit will stop operating.
A circuit abnormality has occurred in the Lossnay unit.
Error code
4116
Cause Remedy
A breakdown has occurred in the Lossnay thermistor (OA side).
5101
A breakdown has occurred in the Lossnay thermistor (SA side).
5105
A breakdown has occurred in the remote controller thermistor.
Communication error
Turn off the power supply and
contact the retail outlet from
where this product was
purchased for further instructions.
Turn off the main switch and turn it
back on. If the error still continues,
contact the retail outlet.
5106
6608
- 2 - - 7 -
Built-in IA (Indoor Air) thermistor
Remote controller (included with the product)
Accessory parts
Mounting screw⋯×12 Duct connecting flange⋯×3
Control
box
EA
(exhaust air)
(supply air)
SA
(return air)
RA
(outside air)
OA
Air supply fan
Heat exchanger
(Lossnay core)
Air filter
Power cord opening
fixture
OA Maintenance cover
Air exhaust fan
Ceiling suspension
Maintenance
cover
Inspection space
420
184
262
871
30262
544
19
256
58
202
95
424
85
85
544
φ192
φ192
φ192
φ192
φ208
φ208
φ208
φ208
142
142
415
142
391
More than 700
More than 830
More than 600
How to remove the RA chamber form the Lossnay unit
The RA duct can be installed on the opposite side. Remove the RA chamber from the
unit by removing the screws, then rotate the RA chamber 180 degrees and reinstall.
Remove the RA chamber from the unit by removing the
mounting screws.
Maintenance
cover
Mounting
screw
Mounting
screw
RA chamber
RA chamber
Mounting screw