Mitsubishi SEZ-KD12NA4,SEZ-KD12NA4.TH,SEZ-KD12NAR1.TH,SEZ-KD12NA4R1.TH SEZ-KD12NA4R1 Data Sheet

Page 1
M-SERIES
SUBMITTAL DATA: SEZ-KD12NA4**
12,000 BTU/H HORIZONTAL-DUCTED INDOOR UNIT FOR MXZ MULTI-ZONE HEAT-PUMP SYSTEMS
Job Name:
System Reference: Date:
**APPLIES TO INDOOR UNIT:
□ SEZ-KD12NA4 □ SEZ-KD12NA4.TH □ SEZ-KD12NAR1.TH □ SEZ-KD12NA4R1.TH
Indoor Unit: SEZ-KD12NA4**
SPECIFICATIONS
Cooling Capacity*............................11,500 Btu/h
* Rating Conditions per AHRI Standard Cooling | Indoor: 80º F (27º C) DB / 67º F (19º C) WB Cooling | Outdoor: 95º F (35º C) DB / 75º F (24º C) WB Heating at 47ºF | Indoor: 70º F (21º C) DB / 60º F (16º C) WB Heating at 47ºF | Outdoor: 47º F (8º C) DB / 43º F (6º C) WB
(For data on specic indoor units [all ducted, all non- ducted, and both ducted and non-ducted] combinations, see the MXZ Technical and Ser vice Manual.)
Electrical Requirements
Power Supply .................... 208 / 230V, 1-Phase, 60 Hz
MCA ...............................................1 A
GENERAL FEATURES
• Horizontal-ducted indoor unit for concealed applications
• Ultra thin body: 7-7/8" high
• Built-in drain mechanism for condensate removal; lifts to 21-11/16"
• Airlterisincludedwithindoorunit
• Quietoperation―aslowas23dBA
• Indoor unit powered from outdoor unit using A-Control
• AUTO fan speed control
• Automatic restart following a power outage
• Limitedwarranty:veyearspartsandsevenyearscompressorss
ACCESSORIES
Indoor Unit
□ Filter Box with MERV 8 Filters (FBL1-2) □ Bottom Return Plate (BRP-2)
Controller Options
□ Wireless Wall-mounted Remote Controller Kit (MHK1)* □ Portable Central Controller (MCCH1)* □ Outdoor Air Sensor (MOS1)* □ Wired Wall-mounted Controller (PAR-31MAA)* □ Simple MA Remote Controller (PAC-YT53CRAU)*
*See Submittal for information on each option.
□ Remote Temperature Sensor (M21-JKO-307) □ Hand-held Wireless Remote Controller
(PAR-FL32MA; req.PAR-FA32MA-E) □ Wireless Signal Receiver PAR-FA32MA (for PAR-FL32MA) □ Lockdown Bracket for Hand-held Controller (RCMKP1CB)
Voltage
Indoor - Outdoor S1-S2 .......................AC 208 / 230V
Indoor - Outdoor S2-S3 ...........................DC ±24V
Blower Motor (ECM).............................0.57 F.L.A.
Airow (Lo - Med - Hi)
Cooling .......................... 247 - 317 - 388 Dry CFM
Heating ..........................247 - 317 - 388 Dry CFM
Sound Pressure Level (Lo - Med - Hi)
Cooling ................................23 - 28 - 33 dB(A)
Heating ................................23 - 28 - 33 dB(A)
DIMENSIONS UNIT INCHES / MM
W 39 / 990 D 27-9/16 / 700 H 7-7/8 / 200
Weight. ....................................50 lbs. / 22 kg
External Finish ......................Galvanized-steel Sheets
Field Drainpipe Size O.D.......................1-1/4" / 32 mm
Refrigerant Type...................................R410A
Refrigerant Pipe Size O.D.
Gas Side .................................3/8" / 9.52 mm
Liquid Side................................1/4" / 6.35 mm
Connection Method ................................Flared
222 - 285 - 349 Wet CFM
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
Page 2
SEZ-KD12NA4** INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW CHARTS
SEZ-KD12NA4
(External static pressure 0.02[in.WG](5Pa)) 208/230V 60Hz
40
[0.16]
30
[0.12]
20
[0.08]
External static pressure [in.WG](Pa)
10
[0.04]
Low
0
678910 11 12
[212] [282][247] [353] [388][318] [424]
Middle
Airflow rate(m
3
/min)[CFM]
High
Rated point
SEZ-KD12NA4
(External static pressure 0.14[in.WG](35Pa)) 208/230V 60Hz
80
[0.32]
70
[0.28]
60
[0.24]
50
[0.20]
40
[0.16]
Middle
3
/min)[CFM]
Rated point
30
[0.12]
External static pressure [in.WG](Pa)
20
[0.08]
10
[0.04]
0
678910 11 12
[212] [282][247] [353] [388][318] [424]
Low
Airflow rate(m
Limit
Limit
High
SEZ-KD12NA4
(External static pressure 0.06[in.WG](15Pa)) 208/230V 60Hz
50
[0.20]
40
[0.16]
30
[0.12]
High
20
[0.08]
External static pressure [in.WG](Pa)
10
[0.04]
0
6789101112
[212] [282][247] [353] [388][318] [424]
Low
Middle
Airflow rate(m
3
/min)[CFM]
Rated point
SEZ-KD12NA4
(External static pressure 0.20[in.WG](50Pa)) 208/230V 60Hz
80
[0.32]
70
[0.28]
60
[0.24]
50
[0.20]
40
[0.16]
30
[0.12]
External static pressure [in.WG](Pa)
20
[0.08]
10
[0.04]
0
6789101112
[212] [282][247] [353] [388][318] [424]
Low
Airflow rate(m
Middle
3
/min)[CFM]
Limit
Rated point
Limit
High
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.
Page 3
DIMENSIONS: SEZ-KD12NA4**
25(1)
15(19/32)
2XE- ø2.9(1/8)
D (Duct)
57(2-1/4)
20(13/16)
Drain pipe(O.D. ø32(1-1/4))
23(29/32)
(5-29/32)
150(Duct)
2X2- ø2.9(1/8)
1
Refrigerant piping are connection (gas)
159(6-9/32)
Air outlet
100(3-15/16)X(E-1)=F
100(3-15/16)
49
30(1-3/16)
57(2-1/4)
(1-15/16) (24-5/8)
23(29/32)
10(13/32)
116
100 25(1)
(3-15/16)
2
345(13-19/32)
10(13/32)
625(Suspension bolt pitch)
700(27-9/16) 677(26-21/32)
Control box
70
(2-25/32)(4-19/32)
270(10-21/32)
Refrigerant piping are connection (liquid)
Drain pipe(O.D. ø32(1-1/4))
(Emergency draining)
Suspension bolt hole 4-14X30(9/16X1-3/16) Slot
L- ø2.9(1/8)
88(3-15/32)
A
C
Air inlet
170(6-23/32)
102(4-1/32)
90
M
N
B (Suspension bolt pitch)23(29/32)
(3-9/16)
Knockout hole ø27(1-3/32)
(Indoor/outdoor connecting line)
200(7-7/8)
88(3-15/32)
Knockout hole ø27(1-3/32)
(Remote controller transmission line)
Terminal block (Indoor/outdoor connecting line)
Terminal block (Remote controller transmission line)
Drain pipe(O.D. ø32(1-1/4))
(Spontaneous draining)
12(1/2)
H
100(3-15/16)XJ=K
100(3-15/16)
12(1/2)
20(13/16)
37(1-15/32)
100(3-15/16)
157.5 (6-7/32)20(13/16) 37(1-15/32)
Unit : mm(in.)
Air lter
450
777
(30-19/32)
450
(17-23/32)
More than 300
(11-13/16)
Note2
50(1-31/32)
50(1-31/32)
G
(1-31/32 ~ 5-29/32)
50 ~ 150
(17-23/32)
Required space for service and maintenance
ModelA
SEZ-KD09NA4**
SEZ-KD12NA4**
SEZ-KD15NA4**
SEZ-KD18NA4**
Note1.Use M10 screw for the suspension bolt (eld supply).
2.Keep the service space for the maintenance at the bottom.
3.This chart indicates for SEZ-KD15NA4** model,which has 3 fans. SEZ-KD09,12NA4** models have 2 fans. SEZ-KD18NA4** models have 4 fans.
4.In case an inlet duct is used,remove the air lter(supply with the unit), then install the lter(eld supply) at suction side.
700
(27-9/16)
900 952 998 860
(35-7/16)
1100B1152
(43-5/16)
(29-5/8)
(37-1/2)
(45-3/8)
(31-7/16)
(39-5/16)
1198
(47-3/16)
C
660798752
(26)
(33-7/8)
1060
(41-3/4)
Access door
F
E11D
7
(23-5/8)
800 1000 860
9
(31-1/2)
1000
(39-3/8)
175±5(6-29/32 ±7/32)
(Actual length)
J
H
G
800600
660
5
(26)
(31-1/2)
7
(33-7/8)
(39-3/8)
1060
1200
(47-1/4)
(41-3/4)
9
Less than 300
K
500
(19-11/16)
700
(27-9/16)
900
(35-7/16)
(11-13/16)
Drain hose (I.D. ø32(1-1/4))
<accessory>
1
N
M
L
790
839
16
(31-1/8)
20
24
(33-1/16)
1039
(40-29/32)
1239
(48-25/32)
990
(39)
1190
(46-7/8)
ø9.52(3/8)
ø12.7(1/2)
(13/32)
(21-21/32)
Less than 550
More than 10
More than 20
mm(in.)
2
Gas pipe Liquid pipe
ø6.35(1/4)
Ceiling surface
(13/16)
Make the access door at the appointed position properly for service maintenance.
Access door
FORM# SEZ-KD12NA4** FOR MXZ MULTI-ZONE SYSTEMS - 201411
Specications are subject to change without notice.
© 2014 Mitsubishi Electric US, Inc.