Q Corresponding MELSECNET/H
Network System
Reference Manual (PLC to PLC network)
-QJ71LP21
-QJ71LP21-25
-QJ71LP21S-25
-QJ71LP21G
-QJ71LP21GE
-QJ71BR11
-QJ71NT11B
• SAFETY PRECAUTIONS •
(Read these precautions before using this product.)
Before using this product, please read this manual and the relevant manuals carefully and pay full
attention to safety to handle the product correctly.
The instructions given in this manual are concerned with this product. For the safety instructions of the
programmable controller system, please read the CPU module user's manual.
In this manual, the safety precautions are classified into to levels: "WARNING" and "CAUTION".
!!
Under some circumstances, failure to observe the precautions given under "CAUTION" may lead to
serious consequences.
Observe the precautions of both levels because they are important for personal and system safety.
Make sure that the end users read this manual and then keep the manual in a safe place for future
reference.
!
[Design Precautions]
!
WARNING
• For operating status of each communication failure, refer to this manual. Incorrect output or
malfunction due to a communication failure may result in an accident.
• If a coaxial cable is disconnected, this may destabilize the line, and a network communication
error may occur in multiple stations. Provide an interlock circuit in the sequence program so that
the system will operate safely even if the above error occurs. Failure to do so may result in an
accident due to incorrect output or malfunction.
• When changing data of the running programmable controller from a peripheral connected to the
CPU module or from a personal computer connected to an intelligent function module or special
function module, configure an interlock circuit in the sequence program to ensure that the entire
system will always operate safely.
For program modification and operating status change, read relevant manuals carefully and
ensure the safety before operation.
Especially, in the case of a control from an external device to a remote programmable controller,
immediate action cannot be taken for a problem on the programmable controller due to a
communication failure.
To prevent this, configure an interlock circuit in the sequence program, and determine corrective
actions to be taken between the external device and CPU module in case of a communication
failure.
A - 1 A - 1
[Design Precautions]
!
CAUTION
• Do not install the control lines or communication cables together with the main circuit lines or
power cables.
Keep a distance of 100mm or more between them.
Failure to do so may result in malfunction due to noise.
[Installation Precautions]
!
CAUTION
• Use the programmable controller in the operating an environment that meets the general
specifications given in the user's manual for the CPU module used.
Failure to do so may result in electric shock, fire, malfunction, or damage to or deterioration of
the product.
• To mount the module, while pressing the module mounting lever located in the lower part of
module, fully insert the module fixing projection(s) into the hole(s) in the base unit press the
module until it snaps into place.
Incorrect mounting may cause malfunction, failure or drop of the module.
When using the programmable controller in an environment of frequent vibrations, fix the
module a screw.
Tighten the screw within the specified torque range.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
• Shut off the external power supply for the system in all phases before mounting or removing the
module. Failure to do so may result in damage to the product.
• Do not directly touch any conductive part of the module.
Doing so can cause malfunction or failure of the module.
A - 2 A - 2
[Wiring Precautions]
!
WARNING
• Shut off the external power supply (all phases) used in the system before installation and wiring.
Failure to do so may result in electric shock or damage to the product.
!
CAUTION
• Individually ground the FG terminal of the programmable controller with a ground resistance of
100 or less.
Failure to do so may result in electric shock malfunction.
• Check the rated voltage and terminal layout before wiring to the terminal block for the external
power supply, and connect the cable correctly.
Connecting a cable to power supply with a different voltage rating or incorrect wiring may cause
a fire or failure.
• Tighten the terminal screw within the specified torque range.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
• Properly solder the parts of a soldering-type coaxial cable connector. Incomplete soldering may
result in malfunction.
• Crimp the parts of a crimping-type coaxial cable connector with proper force at a proper position.
Failure to do so may cause drop of the cable or malfunction.
• Prevent foreign matter such as dust or wire chips from entering the module.
Such foreign matter can cause a fire, failure, or malfunction.
• A protective film is attached to the top of the module to prevent foreign matter, such as wire
chips, from entering the module during wiring.
Do not remove this film during wiring.
Remove it for heat dissipation before system operation.
• Place the cables in a duct or clamp them.
Failure to do so may cause damage of the module or the cables due to accidental pull or
unintentional shifting of the cables, or malfunctions due to poor contact of the cable.
• Do not install the control lines or communication cables together with the main circuit lines or
power cables.
Keep a distance of 100mm or more between them.
Failure to do so may result in malfunction due to noise.
• When disconnecting the communication and power cables from the module, do not pull the
cable by the cable part. Loosen the screws of connector before disconnecting the cable. When
disconnecting a cable connected to a terminal block, loosen the screws on the terminal block
first before removing the cable.
Failure to do so may result in damage to the module or cable or malfunction due to poor contact.
A - 3 A - 3
[Setup and Maintenance Precautions]
!
CAUTION
• Before performing online operations (especially, program modification, forced output, and
operation status change) for the running CPU module in other station from GX Developer via
MELSECNET/H, read relevant manuals carefully and ensure the safety.
• Do not disassemble or modify the module. Doing so may cause failure, malfunction, injury, or a
fire.
• Use any radio communication device such as a cellular phone or a PHS (Personal Handy-phone
System) more than 25cm (9.85 inches) away in all directions from the programmable controller.
Failure to do so may cause malfunction.
• Shut off the external power supply for the system in all phases before mounting or removing the
module. Failure to do so may cause the module to fail or malfunction.
• Do not touch any terminals while power is on. Doing so will cause electric shock.
• Shut external power supply for the system before cleaning the module or retightening the
terminal screws or module fixing screws.
Failure to do so may cause the module to fail or malfunction.
Undertightening can cause drop of the screw, short circuit or malfunction.
Overtightening can damage the screw and/or module, resulting in drop, short circuit, or
malfunction.
• After the firs use of the product, do not mount/remove the module to/from the base unit more
than 50 times (IEC 61131-2 compliant) respectively.
Exceeding the limit of 50 times may cause malfunction.
• Before handling the module, touch a grounded metal object to discharge the static electricity
from the human body.
Failure to do so may cause the module to fail or malfunction.
[Disposal Precautions]
!
CAUTION
• When disposing of this product, treat it as industrial waste.
A - 4 A - 4
• CONDITIONS OF USE FOR THE PRODUCT •
(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;
i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major
or serious accident; and
ii) where the backup and fail-safe function are systematically or automatically provided outside of
the PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.
(2) The PRODUCT has been designed and manufactured for the purpose of being used in general
industries.
MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT
LIMITED TO ANY AND ALL RESPONSIBILITY OR LIABILITY BASED ON CONTRACT,
WARRANTY, TORT, PRODUCT LIABILITY) FOR ANY INJURY OR DEATH TO PERSONS OR
LOSS OR DAMAGE TO PROPERTY CAUSED BY the PRODUCT THAT ARE OPERATED OR
USED IN APPLICATION NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS,
OR WARNING CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY
MANUALS, TECHNICAL BULLETINS AND GUIDELINES FOR the PRODUCT.
("Prohibited Application")
Prohibited Applications include, but not limited to, the use of the PRODUCT in;
Nuclear Power Plants and any other power plants operated by Power companies, and/or any other
cases in which the public could be affected if any problem or fault occurs in the PRODUCT.
Railway companies or Public service purposes, and/or any other cases in which establishment of
a special quality assurance system is required by the Purchaser or End User.
Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as
Elevator and Escalator, Incineration and Fuel devices, Vehicles, Manned transportation,
Equipment for Recreation and Amusement, and Safety devices, handling of Nuclear or
Hazardous Materials or Chemicals, Mining and Drilling, and/or other applications where there is a
significant risk of injury to the public or property.
Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the
PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT
is limited only for the specific applications agreed to by Mitsubishi and provided further that no
special quality assurance or fail-safe, redundant or other safety features which exceed the general
specifications of the PRODUCTs are required. For details, please contact the Mitsubishi
representative in your region.
A - 5 A - 5
REVISIONS
The manual number is given on the bottom left of the back cover.
Print Date Manual Number Revision
Dec., 1999 SH(NA)-080049-A First printing
Oct., 2000 SH(NA)-080049-B
Correction
Safety Precautions, Contents, About Manuals, About the Generic
Terms and Abbreviations, Chapter 1, Section 1.1, 1.2, Chapter 2,
Section 2.1.3, 2.1.4, 2.2.2, 3.1.1, 3.1.2, 3.2, 3.2.1, 3.2.2, 3.3, 3.3.1,
SAFETY PRECAUTIONS, Compliance with the EMC and Low Voltage
Directives, About the Generic Terms and Abbreviations, DEFINITIONS
OF TERMINOLOGY, Chapter 1, Section 2.1, 2.2, 3.1.1, 3.1.3, 3.2,
The manual number is given on the bottom left of the back cover.
Print Date Manual Number Revision
Jan., 2009 SH(NA)-080049-L
Mode addition
QJ71NT11B
Correction
SAFETY PRECAUTIONS, COMPLIANCE WITH THE EMC AND LOW
VOLTAGE DIRECTIVES, GENERIC TERMS AND ABBREVIATIONS,
PACKING LIST, Section 1.1 to 1.3, 2.1.1, 2.1.2, 2.1.4, 2.2, 2.2.3,
3.1.1 to 3.1.3, 3.2.2, 3.3.2, 3.3.3, 4.1 to 4.3, 4.5, 4.5.1 to 4.5.3, 4.7.1,
GENERIC TERMS AND ABBREVIATIONS, Section 2.2, 8.1.2,
Appendix 1.2
Addition
Section 8.2.4
Section number changed
Section 8.2.4 to Section 8.2.11 Section 8.2.5 to Section 8.2.12
Japanese Manual Version SH-080026-X
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent
licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property
rights which may occur as a result of using the contents noted in this manual.
Thank you for purchasing the Mitsubishi Electric MELSEC-Q series programmable controller.
Before using the product, please read this manual carefully to develop full familiarity with the functions and
performance of the Q series programmable controller to handle the product correctly.
Please forward a copy of this manual to the end user.
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES ............................................................. A- 15
GENERIC TERMS AND ABBREVIATIONS ............................................................................................... A- 16
DEFINITIONS OF TERMINOLOGY ............................................................................................................ A- 18
PACKING LIST ............................................................................................................................................ A- 19
1.2 Features ................................................................................................................................................. 1- 4
1.3 Symbols Used in This Manual ............................................................................................................... 1- 14
3.2 Function Specifications .......................................................................................................................... 3- 14
3.2.1 Cyclic transmission function (periodical communication) .............................................................. 3- 15
3.2.2 RAS function .................................................................................................................................... 3- 18
3.3 Specifications of the Link Data Sending/Receiving Processing Time .................................................. 3- 29
3.3.1 Link data sending/receiving processing ......................................................................................... 3- 29
3.3.2 How to calculate the transmission delay time ................................................................................ 3- 33
A - 10 A - 10
3.3.3 Reducing the link refresh time ........................................................................................................ 3- 47
3.3.4 Reduction of the link scan time ....................................................................................................... 3- 52
3.3.5 Control station shift time .................................................................................................................. 3- 52
4 SETUP AND PROCEDURES BEFORE STARTING THE OPERATION 4- 1 to 4-45
4.1 Procedures Before Starting the Operation ............................................................................................ 4- 1
4.2 Part Names and Settings ....................................................................................................................... 4- 2
4.6.1 Optical loop system ......................................................................................................................... 4- 19
4.6.2 Coaxial bus system ......................................................................................................................... 4- 22
4.6.3 Twisted bus system (when using a shielded twisted pair cable) ................................................... 4- 27
4.6.4 Twisted bus system (when using CC-Link Ver. 1.10-compatible cable) ....................................... 4- 29
4.7 Offline Tests from GX Developer .......................................................................................................... 4- 30
4.7.1 Station-to-station test ...................................................................................................................... 4- 30
4.7.2
Forward loop/reverse loop test (optical loop system only) ............................................................ 4- 36
4.8.1 Loop test (optical loop system only) ............................................................................................... 4- 42
4.8.2 Setup confirmation test (optical loop, coaxial bus system only) .................................................... 4- 43
4.8.3 Station order check test (optical loop system only) ........................................................................ 4- 44
4.8.4 Communication test......................................................................................................................... 4- 45
5 PARAMETER SETTINGS 5- 1 to 5-42
5.1 Setting the Number of Modules (Network Type) .................................................................................. 5- 7
5.5 Control Station Return Setting ............................................................................................................... 5- 20
5.6 Station Inherent Parameters (High Performance model QCPU, Process CPU, Redundant CPU,
and Universal model QCPU) ................................................................................................................. 5- 21
6.1.1 Interlock related signals .................................................................................................................. 6- 1
6.1.2 Program example ............................................................................................................................ 6- 4
6.2.1 32-bit data assurance ...................................................................................................................... 6- 5
6.2.2 Station-based block data assurance for cyclic data ....................................................................... 6- 7
6.2.3 Interlock program example ............................................................................................................. 6- 8
6.3 Link Dedicated Instruction List ............................................................................................................... 6- 9
6.4 Using the Link Special Relays (SB)/Link Special Registers (SW) ....................................................... 6- 13
7 APPLICATION FUNCTIONS 7- 1 to 7-160
7.1 Direct Access to the Link Devices ......................................................................................................... 7- 2
7.2 Inter-Link Data Transfer Function (High Performance model QCPU, Process CPU,
Redundant CPU, and Universal model QCPU) .................................................................................... 7- 6
7.3 Low-Speed Cyclic Transmission Function (High Performance model QCPU, Process CPU,
Redundant CPU, and Universal model QCPU) .................................................................................... 7- 9
7.3.1 Send range settings ........................................................................................................................ 7- 10
7.4 Transient Transmission Function (Non-Periodical Communication) .................................................... 7- 16
7.4.1 Communication function.................................................................................................................. 7- 17
7.4.2 Routing function ............................................................................................................................... 7- 20
7.4.3 Group function ................................................................................................................................. 7- 27
7.4.4 Message sending function using the logical channel numbers ..................................................... 7- 28
7.5.6 Application example ........................................................................................................................ 7- 121
7.6 Multiplex Transmission Function (Optical Loop System) ..................................................................... 7- 123
7.7 Simple Dual-Structured Network (High Performance model QCPU and Process CPU) .................... 7- 124
7.8 Stopping/Restarting the Cyclic Transmission and Stopping Link Refreshing (Network Test) ............ 7- 129
7.9 Increasing the Number of Send Points by Installing Multiple Modules with the Same Network
(High Performance model QCPU, Process CPU, Redundant CPU, and Universal model QCPU) ... 7- 132
7.10 Configuring a Network with a Redundant System .............................................................................. 7- 134
7.10.1 Outline of the redundant system operation .................................................................................. 7- 134
7.10.2 Precautions for network configuration including a redundant system ......................................... 7- 137
7.10.3 Pairing setting in a redundant system .......................................................................................... 7- 145
7.10.4 Redundant settings in a redundant system ..................................................................................
7.10.5 System switching request to the control system CPU ................................................................. 7- 150
7.10.6 Function for returning to control station in a redundant system .................................................. 7- 152
7.10.7 Data retention time for system switching ...................................................................................... 7- 153
7.10.8 Routing via a redundant system ................................................................................................... 7- 159
8.2.1 Items to be checked first ................................................................................................................. 8- 23
8.2.2 Data link failure on the entire system ............................................................................................. 8- 24
8.2.3 Data link failure caused by reset or power-off of each station ....................................................... 8- 24
8.2.4 Cyclic data is 0 caused by reset or power-on of each station ....................................................... 8- 26
8.2.5 Data link failure of a specific station ............................................................................................... 8- 27
8.2.6 Data link failure in MELSECNET/H Extended mode ..................................................................... 8- 27
8.2.7 Data link failure in MELSECNET/H twisted bus system ................................................................ 8- 28
8.2.8 Data link in a redundant system ..................................................................................................... 8- 28
8.2.9 Send/received data failure .............................................................................................................. 8- 29
8.2.10 Link dedicated instruction not complete ....................................................................................... 8- 30
The following manuals are also relevant to this product.
Order each manual as needed, referring to the following list.
Relevant manuals
Manual name
Q corresponding MELSECNET/H Network System Reference Manual (Remote I/O network)
Specifications, setup and procedures before starting the operation, parameter setting, programming and
troubleshooting of the remote I/O network of the MELSECNET/H network system. (Sold separately)
Type MELSECNET/10 Network system (PLC to PLC network) Reference Manual
System configuration, performance, specifications and programming of MELSECNET/10 network system
(PLC to PLC network). (Sold separately)
For QnA/Q4AR MELSECNET/10 Network System Reference Manual
System configuration, performance, specifications and programming of MELSECNET/10 network system
(PLC to PLC network). (Sold separately)
COMPLIANCE WITH EMC AND LOW VOLTAGE DIRECTIVES
(1) Method of ensuring compliance
To ensure that Mitsubishi Electric programmable controllers maintain EMC and
Low Voltage Directives when incorporated into other machinery or equipment,
certain measures may be necessary. Please refer to one of the following
manuals.
• QCPU User's Manual (Hardware Design, Maintenance and Inspection)
Manual number
(Model code)
SH-080124
(13JF96)
IB-66440
(13JE33)
IB-66690
(13JF78)
• Safety Guidelines
(This manual is included with the CPU module or base unit.)
The CE mark on the side of the programmable controller indicates compliance
with EMC and Low Voltage Directives.
(2) Additional measures
(a) When using QJ71LP21 and QJ71NT11B
No additional measures are necessary for the compliance of this product
with EMC and Low Voltage Directives.
(b) When using QJ71BR11
To ensure that this product maintains EMC and Low Voltage Directives,
please refer to one of the manuals listed under (1).
A - 15 A - 15
GENERIC TERMS AND ABBREVIATIONS
Generic term/abbreviation Description of generic term/abbreviation
Abbreviation for the QJ71LP21, QJ71LP21-25, QJ71LP21S-25, QJ71LP21G, and QJ71LP21GE
QJ71LP21
QJ71BR11 Abbreviation for the QJ71BR11 MELSECNET/H network module
QJ71NT11B Abbreviation for the QJ71NT11B MELSECNET/H network module
Network modules Generic term for the QJ71LP21, QJ71BR11, and QJ71NT11B
CC-Link IE Controller Network
module
CC-Link IE Field Network module Abbreviation for the QJ71GF11-T2 CC-Link IE Field Network master/local modules
MELSECNET/H Abbreviation for the Q corresponding MELSECNET/H network system
MELSECNET/10 Abbreviation for the AnU and QnA/Q4AR corresponding MELSECNET/10 network system
QCPU
Basic model QCPU Generic term for the Q00JCPU, Q00CPU, and Q01CPU
High Performance model QCPU Generic term for the Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU, and Q25HCPU
Process CPU Generic term for the Q02PHCPU, Q06PHCPU, Q12PHCPU, and Q25PHCPU
Redundant CPU Generic term for the Q12PRHCPU and Q25PRHCPU
Universal model QCPU
Built-in Ethernet port QCPU
Safety CPU Generic term for the QS001CPU
C Controller module
Control CPU
System A CPU
System B CPU
Control system CPU A CPU module that controls operations in a redundant system
Standby system CPU A CPU module that stands by in case the control system fails in a redundant system
GX Developer
GX Works2 Generic product name for SWnDND-GXW2 and SWnDNC-GXW2 (n: version)
CC-Link Ver. 1.10-compatible cable Abbreviation for the CC-Link Version. 1.10-compatible dedicated cable
MELSECNET/H network modules. However, QJ71LP21, QJ71LP21-25, QJ71LP21S-25,
QJ71LP21G, and QJ71LP21GE are used in this manual to indicate special machine types
Abbreviation for the QJ71GP21-SX and QJ71GP21S-SX CC-Link IE Controller Network modules
Generic term for the Basic model QCPU, High Performance model QCPU, Process CPU,
Redundant CPU, and Universal model QCPU
Generic term for the Q00UJCPU, Q00UCPU, Q01UCPU, Q02UCPU, Q03UDCPU, Q03UDVCPU,
*1: The QJ71LP21 is discontinued in October, 2000.
1
1
1
1
1
1
1
REMARKS
For the coaxial bus system, terminating resistors (75 ) are required in the network
terminal stations.
Terminating resistors are not supplied with the QJ71BR11; they must be purchased
separately.
For a list of the model names and how to use the terminating resistors, refer to
Section 4.6.2.
A - 19 A - 19
1 OVERVIEW
1 OVERVIEW
MELSEC-Q
1
1.1 Overview
The MELSECNET/H network system includes a PLC to PLC network for
communicating between the control station and normal stations, and a remote I/O
network for communicating between the remote master station and remote I/O stations.
This manual is used for configuring PLC to PLC networks on MELSECNET/H network
systems (hereinafter abbreviated as MESECNET/H.)
When configuring a remote I/O network using MELSECNET/H, refer to Q
corresponding MELSECNET/H Network System Reference Manual (Remote I/O
network).
REMARKS
Networks known as MELSECNET/10H are hereinafter abbreviated as
MELSECNET/H.
The PLC to PLC network system of MELSECNET/H provides more functionality,
higher processing speed and more capacity than the conventional PLC to PLC network
system of MELSECNET/10 network system.
In addition, in pursuit of the maximum ease of use of the MELSECNET/10 network
system, the FA system can be networked easily by combining with GX Developer.
The MELSECNET/H system supports the MELSECNET/H and MELSECNET/H
Extended modes (high functionality and high-speed mode) and the MELSECNET/10
mode (functional and performance compatibility mode) to achieve the network
performance improvement and upward compatibility of MELSECNET/10.
Unless otherwise categorized, this is abbreviated as MELSECNET/H for explanatory
purposes in this manual.
1 - 1 1 - 1
1 OVERVIEW
GX Developer
Q25HCPU
MELSEC-Q
Control station (MELSECNET/10 mode)
Control station (MELSECNET/H mode)
Remote master station
1
MELSECNET/10
Q25HCPU Normal station
QnACPU
MELSECNET/H (25Mbps) PLC to PLC network
Q25HCPU
PLC to PLC network
Normal
station
AnUCPU
Normal station
Normal
station
Q25HCPU
REMARKS
MELSECNET/H (25Mbps)
remote I/O network
MELSECNET/H (10Mbps)
PLC to PLC network
Q25HCPU
Normal station
Normal station
Remote I/O
station
This manual is written assuming that MELSECNET/H is used in the MELSECNET/H
or MELSECNET/H Extended mode. Thus, if MELSECNET/H is to be used in the
MELSECNET/10 mode, please refer to the "For QnA/Q4AR MELSECNET/10
Network System Reference Manual".
POINT
(1) Select a QCPU as a programmable controller of the MELSECNET/H for PLC
to PLC network system.
(2) When any of the conventional series QnA, AnU and ACPUs exist in the same
network, select the MELSEC NET/10 mode, which is compatible with the
MELSECNET/10.
(3) Set the control station and normal stations within the same network to the
same network type.
Stations of different network types cannot be used together within the same
network.
1 - 2 1 - 2
1 OVERVIEW
module
QCPU
AnUCPU MELSECNET/10
QnACPU MELSECNET/10
MELSEC-Q
The table below shows the CPU modules that can be combined for use on each
network.
CPU
Type of networks that can
be used with CPU
MELSECNET/H
(10 Mbps)
MELSECNET/H
(25 Mbps)
MELSECNET/H
(Twisted bus)
MELSECNET/10 MELSECNET/H
PLC to PLC network PLC to PLC network
(MESLECNET/10 mode)
Network to be connected
(MESLECNET/H mode,
MELSECNET/H Extended mode)
: Use possible : Use not possible
REMARKS
What is network type?
The network type is a parameter set for specifying the network where the network
module is used.
Set the network type of the network module in the Network parameter of GX
Developer.
There are the following network types.
Network type Description
MELSECNET/H mode Set this mode when all CPUs within the network are QCPUs.
The maximum number of link points per station has been increased
MELSECNET/H Extended
mode
MELSECNET/10 mode
compared with the MELSECNET/H mode.
In excess of 2000 bytes, a maximum of 35840 bytes can be set.
Set this mode when the system uses many link points per station.
This mode is used to operate the network module on a
MELSECNET/10 network where the QnA/AnU exists.
1 - 3 1 - 3
1 OVERVIEW
1.2 Features
The MELSECNET/H is designed to provide higher processing speed, more capacity,
and more functionality while maintaining the connectivity with the MELSECNET/10; it is
easier to use than ever in combination with GX Developer. Furthermore, the
MELSECNET/H has the following features that were not available with the conventional
MELSECNET (II) and MELSECNET/B data link systems.
(1) Achievement of a high-speed communication system
(a) The MELSECNET/H enables high-speed communications with 25Mbps
and 10Mbps communication speeds.
Item
Link device transfer 8 16 64
SB/SW transfer 1 for each
Basic model QCPU
Safety CPU
Refresh range
Communication speeds vary depending on the network system.
Network system Communication speed
Optical loop 10Mbps or 25Mbps 1
Coaxial bus 10Mbps
Twisted bus 156kbps to 10Mbps
1: QJ71LP21-25 and QJ71LP21S-25 only
(b) The link scan time has become even faster through the use of processors
specifically designed for linking.
(c) Refresh parameter area can be subdivided
By subdividing ranges refresh parameter ranges, refreshing of the areas
not used for the sequence program can be eliminated and the refresh time
can be reduced by refreshing only those required. (Refer to Section 5.7
"Refresh Parameters.")
The number of refresh parameter settings per module is shown below.
Number of settings
Q00UJCPU
Q00UCPU
Q01UCPU
Universal model QCPU other than listed in the left column.
High Performance model QCPU
Process CPU
Redundant CPU
Also, because the bus speed between a QCPU and a network module has
been improved, the refresh time has been reduced.
QCPU
device (B)
Network module
link device (LB)
Station
No. 1
(Host)
Station
No. 2
MELSEC-Q
Each station's
total send range
Station
No. 3
High-speed bus
Fragmentation
(d) The optical loop system enables even faster levels of data communication
with multiplex transmission (refer to Multiplex Transmission Function in
section 7.6.)
1 - 4 1 - 4
1 OVERVIEW
MELSEC-Q
(2) Large-scale and flexible system configuration
(a) The link device has a larger capacity: 16384 points for the link relay (LB)
and 16384 points for the link register (LW). (Refer to Section 3.1.1)
(b) The maximum number of link points per station has been increased.
By selecting the network type, the maximum number of link points per
station can be increased.
1) MELSECNET/H Extended mode
By selecting the MELSECNET/H Extended mode as the network type,
the maximum number of link points per station can be set up to 35840
bytes in excess of 2000 bytes.
It is not necessary to install multiple network modules for a single CPU
module to increase the number of transmission points.
2) MELSECNET/H mode
1
By selecting the MELSECNET/H mode as the network type, the
maximum number of link points per station can be set up to 2000 bytes.
Furthermore, by installing multiple network modules with the same
network number for the same CPU module, the link points of "number
of modules
maximum number of link points per station" can be sent.
(High Performance model QCPU, Process CPU, Redundant CPU, and
Universal model QCPU) (Refer to Section 7.9 "Increasing the Number
of Send Points by Installing Multiple Modules Having the Same
Network Number.")
1: The link scan time varies depending on the network type.
Refer to Section 3.3.2 for details.
(c) The commands for transmitting and receiving data with other stations on
the MELSECNET/H network system (SEND, RECV, RECVS, READ,
SREAD, WRITE, SWRITE) enable a maximum of 960 words of data to be
transmitted and received (refer to Programming in section 7.4.5.)
(d) A system can be expanded to contain a maximum of 239 networks. (Refer
to Section 2.1.4, "A Network System Containing Multiple Networks.")
(e) By using the inter-link data transfer function, data (LB/LW) can be transferred
to another network without creating a sequence program. (High Performance
model QCPU, Process CPU, Redundant CPU, and Universal model QCPU)
(Refer to Section 7.2, "Inter-link Data Transfer Function.")
Q25HCPU
Network
module 1
LBLB
0
Network
module 2
1
0
Inter-link data
Q25H
CPU
Network
module
Data of network No. 2
Network No. 1
3FFF
transfer
H
3FFF
Data of network No. 1
Q25H
CPU
H
Network No. 2
Network
module
1 - 5 1 - 5
1 OVERVIEW
GX Developer
Transient transmission
possible.
Q25H
CPU
MELSEC-Q
(f) By installing multiple network modules, N:N communication (transient
transmission) with destination stations on eight network systems that use
the programmable controllers as relay stations can be performed using the
routing function.
(Refer to Section 7.4.2, "Routing Function.")
Transient transmission using the routing function can be performed not only
in a system composed of MELSECNET/H networks but also in a system
that contains CC-Link IE Controller Network, CC-Link IE Field Network
and/or MELSECNET/10 networks.
QJ71
LP21
No.1
Q25H
CPU
MELSECNET/H
QJ71
LP21
QJ71
LP21
Request destination
MELSECNET/H
Q25H
QJ71
CPU
LP21
No.3
No.2
QJ71
LP21
Q25H
CPU
Q25H
CPU
QJ71
LP21
QJ71
LP21
QJ71
LP21
QJ71
LP21
MELSECNET/HMELSECNET/H
Q25H
CPU
QJ71
LP21
No.4
QJ71
LP21
Request
source
MELSECNET/ HMELSECNET/H
Q25H
CPU
QJ71
LP21
Q25H
CPU
QJ71
LP21
QJ71
LP21
Q25H
QJ71
LP21
No.7No.8
QJ71
LP21
CPU
MELSECNET/HMELSECNET/H
No.5No.6
: Only the High Performance model QCPU, Process CPU, Redundant
CPU, and Universal model QCPU accept multiple network modules.
(g) The following three types of network systems can be configured
according to applications of each user.
1) Loop system that is more resistant to noise and provides longer distance
in total and between stations. (Up to 30km in total length)
2) Coaxial bus system that allows easier wiring (Up to 500m in total length)
3) Twisted bus system that allows the use of general-purpose cables (Up to
1200m in total length)
(Refer to Section 3.1, "Performance Specifications.")
(h) The following functions facilitate network connection:
1) Any station to be connected in the future can be specified as a reserved
station.
Specifying a station not actually connected as a reserved station
prevents a communication error. (Refer to Section 5.3.4 "Specification of
the reserved station.")
2) It is not necessary to connect stations in order of the station Nos. in the
network. (Refer to Section 4.2 "Part Names and Settings.")
1 - 6 1 - 6
1 OVERVIEW
a
n
i
t
s
e
Network module
e
n
n
a
h
c
n
o
i
t
QCPU
Send
J.SEND
D
(3) Providing various communication services
(a) Transient transmission can be performed by designating a channel
number (1 to 64) of the receiving station. This function allows to set
(change) the channel numbers arbitrarily with the sequence programs and
to perform transmission to multiple stations with the same channel number
at one time.
(Refer to Section 7.4.4, "Message sending function using the logical
channel numbers.")
Receiver
channel
unmatched
Sender
9
.
o
N
l
Discard
Discard
Receiver
channel
No. 9
Received
Received
Received
MELSECNET/H
Receiver
channel
No. 9
QCPU
Channel 1
Channel
No.1
No.2
No.3
MELSEC-Q
2
3
7
8
Channel
No.9
No.20
Network module
Receive
J.RECV
Receiver
channel
unmatched
Receiver
channel
No. 9
(b) By using the low-speed cyclic transmission function, it is possible to
cyclically send data that does not require high-speed transmission in a
batch mode, separately from the normal cyclic transmission (LB/LW). Highspeed transmission can be achieved by efficiently dividing the data to
transmit into data that requires high-speed transmission, which is sent by
the normal cyclic transmission, and other data that is sent by low-speed
cyclic transmission.
There are three types of transmission method depending on how the
transmission is activated.
1) "Transmission of data for one station in one link scan" (default)
2) "Periodical cycle interval" which transmits in a set time cycle
(hour/minute/second)
3) "System times" which transmits data at the specified timing
(year/month/day/hour/minute/second)
(High Performance model QCPU, Process CPU, Redundant CPU,
and Universal model QCPU)
(Refer to Section 7.3, "Low-Speed Cyclic Transmission Function.")
MELSECNET/H
T
g
i
s
e
d
e
h
t
e
m
i
t
d
e
t
a
n
t
a
n
o
i
s
s
i
m
s
n
a
r
Low-speed cyclic
transmission data
1 - 7 1 - 7
1 OVERVIEW
I50
Interrupt
sequence
program
MELSEC-Q
(c) The interrupt sequence program of the host's CPU module can be started
up using the event issue function. This function reduces the response time
of the system and process real-time data receiving. (Refer to Section 7.5,
"Starting Up the Interrupt Sequence Program.")
CPU module
IRET
MAIN
Normal
sequence
program
END
Conditions
matched
Network module
Condition check
Interrupt condition
parameters
• Relay information
• Register data
• Arrival at a channel
• Network status
MELSECNET/H
Transient transmission
from other station
Cyclic transmission
(4) Enhanced RAS functions (Refer to Section 3.2.2, "RAS function.")
(a) By using the control station switch function, if the control station of the
network is down, a normal station is substituted for the control station,
enabling to continue the network communication.
(b) When a faulty station recovers and can resume normal operation, it
automatically returns to the network to resume the data communication
using the automatic return function.
(c) The automatic return control function allows a failed control station to be
reconnected to the network as a normal station, reducing network downtime.
(d) The loopback function (in the optical loop system) isolates a faulty part,
where a fault such as cable disconnection or a station error has occurred,
and enables data communications among operable stations.
(e) Preventing station failure using external power supply
When two or more stations are faulty and halted in the optical loop system,
stations between these faulty stations can continue the data link.
Because the loop back is prevented, the link scan time will be stabilized.
(The QJ71LP21S-25 is the network module where external power can be
supplied.)
1 - 8 1 - 8
1 OVERVIEW
MELSEC-Q
(f) By using the station detach function (coaxial bus system and twisted bus
system), even when some of the connected stations are down due to power
off, etc., the normal communication can be continued among other
operational stations.
(g) W hen an error occurs in a normal network due to disconnection, etc. the
data link can be continued by switching to link data refresh on the standby
network if two network modules, a regular module and a standby module,
are installed for each programmable controller CPU (High Performance
model QCPU and Process CPU)
(h) The network module can continue the transient transmission even if an
error that stops the CPU module while the system is operating occurs.
(i) It is possible to check the time when a transient error occurred.
REMARKS
The following faults make the RAS functions valid.
Break in cable
Power-off of slave station
Network setting error
Fault detectable by self-diagnostics of CPU module
If the network module has become faulty, the RAS functions may not be activated
depending on the fault.
1 - 9 1 - 9
Loading...
+ 458 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.