Mitsubishi Electric QAHV-N560YA-HPB, QAHV-N560YA-HPB-BS User Manual

Page 1
HOT WATER HEAT PUMP
MODEL
QAHV-N560YA-HPB(-BS)
Page 2

CONTENTS

HOT WATER HEAT PUMP
I.
1-1. Specifications................................................................................................................................... 2
1-2. External Dimensions ........................................................................................................................ 3
1-3. Center of Gravity.............................................................................................................................. 4
1-4. Electrical Wiring Diagrams............................................................................................................... 5
1-5. Optional parts .................................................................................................................................. 7
2. Product Data............................................................................................................................................. 12
2-1. Capacity tables ................................................................................................................................ 12
2-2. Sound pressure levels ..................................................................................................................... 22
2-3. Vibration levels ................................................................................................................................ 23
3. Installation................................................................................................................................................. 24
3-1. Selecting the Installation Site........................................................................................................... 24
3-2. Unit Installation ................................................................................................................................ 28
4. System Design.......................................................................................................................................... 29
4-1. Water Pipe Installation ..................................................................................................................... 29
4-2. QAHV Secondary side control ......................................................................................................... 33
5. Wiring Design............................................................................................................................................ 40
5-1. System Configurations..................................................................................................................... 40
5-2. Electrical Wiring Installation............................................................................................................. 41
6. Controller .................................................................................................................................................. 44
6-1. PAR-W31MAA specifications .......................................................................................................... 44
MEES19K001
1
Page 3

1. Product Specifications

I.1. Product Specifications

1-1. Specifications

Model QAHV-N560YA-HPB
Power Source 3-phase 4-wire 380-400-415V 50Hz
Capacity *1 kW 40
kcal/h 34400
Power input kW 10.31
Current input A 17.8-16.9-16.3
Capacity *2 kW 40
COP(kW/kW) 3.88
QAHV-N-YA-HPB
Power input kW 10.97
Current input A 20.0-19.0-18.3
COP(kW/kW) 3.65
Capacity *3 kW 40
Power input kW 11.6
Current input A 20.4-19.4-18.7
COP(kW/kW) 3.44
Maximum current input A 33.8
Allowable external pump head 77kPa
Temperature range Inlet water temp 5-63°C
Outlet water temp 55–90°C (when the secondary side control is enabled: 55–80ºC)
Outdoor temp D.B. -25~43°C
Sound Pressure level (measured 1m below the unit in an anechoic room) *1 dB(A) 56
Water pipe diameter and type Inlet mm(in.) 19.05(Rc 3/4"), screw pipe
External finish Acrylic painted steel plate
External dimension H x W x D mm 1837(1777 not including legs) x 1220 x 760
Net weight kg(lbs) 400(882)
Design Pressure R744 MPa 14
Heat exchanger Water-side Copper tube coil
Compressor Type Inverter scroll hermetic compressor
FAN Air flow rate m3/min 220
HIC (HIC: Heat inter-changer) circuit Copper pipe
Protection High pressure protection High pres.Sensor & High pres.Switch at 14MPa(643psi)
Defrosting method Auto-defrost mode (Hot gas)
Refrigerant Type x original charge CO2 (R744) 6.5kg
Notes: Unit converter
*1.Under Normal heating conditions at the outdoor temp, 16°CDB/12°CWB(60.8°FDB/53.6°FWB), the outlet water temperature 65°C(149°F), and the inlet water temperature 17°C(62.6°F) *2.Under Normal heating conditions at the outdoor temp, 7°CDB/6°CWB(44.6°FDB/42.8°FWB), the outlet water temperature 65°C(149°F), and the inlet water temperature 9°C(48.2°F) *3.Under Normal heating conditions at the outdoor temp, 7°CDB/6°CWB(44.6°FDB/42.8°FWB), the outlet water temperature 65°C(149°F), and the inlet water temperature 15°C(59.0°F) *Due to continuing improvements, specifications may be subject to change without notice *Do not use steel pipes as water pipes. *Keep the water circulated at all times. Blow the water out of the pipes if the unit will not be used for an extended period time. *Do not use ground water or well wat er *Do not install the unit in an environment where the wet bulb temperature exceeds 32°C *The water circuit must use the closed circuit *There is a possibility that the unit may abnormally stop when it operates outside its operating range. Provide backup (ex.boiler start with error display output signal (blue CN511 1-3)) for abnormal stop.
Outlet mm(in.) 19.05(Rc 3/4"), screw pipe
Water MPa 0.5
Air-side Plate fin and copper tube
Maker MITSUBISHI ELECTRIC CORPORATION
Starting method Inverter
Motor output kW 11.0
Case heater kW 0.045
Lubricant PAG
Type x Quantity Propeller fan
Control, Driving mechanism Inverter-control, Direct-driven by motor
Motor output kW 0.92
Inverter circuit Overheat and overcurrent protection
Compressor Overheat protection
Fan motor Thermal switch
Flow and temperature control LEV
Btu/h 136480
kcal/h 34400
Btu/h 136480
kcal/h 34400
Btu/h 136480
41-145.4ºF
131–194ºF (when the secondary side control is enabled: 131–176ºF)
-13~109.4°F
<MUNSELL 5Y 8/1 or similar>
in. 72.3(69.9 not including legs) x 48.0
L/s 3666
cfm 7768
kcal/h =kW x 860
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
MEES19K001
2
Page 4
1. Product Specifications

1-2. External Dimensions

QAHV-N560YA-HPB(-BS)
Unit: mm
QAHV-N-YA-HPB
54
VENTILATION SPACE
<PLAN>
SERVICE SPACE
145
(908)
MORE THAN 50
MORE THAN 50
VENTILATION • SERVICE SPACE
MORE THAN 300
MORE THAN 500
118
INTAKE
DISCHARGE
AIR
AIR
9
BACK VIEW
145
DRAIN OUTLET(*1)
ø38.1
(60)
26 5454 26
755
(635)
RIGHT SIDE VIEW
The specification of the product is for the improvement
a previous notice and might change.
760
1220
TOP VIEW
304
<SUB>
CONTROL BOX
DISPLAY
<MAIN>
CONTROL BOX
INTAKE
INTAKE
AIR
AIR
1837 1777
19
1472
SERVICE
PAN EL
HOLE TO PASS ROPE
FOR CARRYING
297
85 9085
274
(24)
122
206
60 60
(60)
ANCHOR BOLT HOLE
(WATER PIPE)
DRAIN OUTLET
ø39 KNOCKOUT HOLE
HOLES FOR TRANSMISSION CABLE
FRONT VIEW
(488)
187
199
(755)
(MOUNTING PITCH)
719(716~722)
530
(*1)
2×2-14×20 OVAL HOLE (without REMOVABLE INSTALLATION LEGS)
2×2-14×31 OVAL HOLE
(ANCHOR BOLT HOLE)
18 18
7474
BOTTOM VIEW
1060(MOUNTING PITCH)
MEES19K001
HOLE FOR POWER SUPPLY
ø62 KNOCKOUT HOLE
HOT WATER OUTLET<Rc3/4B>
WATER INLET<Rc3/4B>
REMOVABLE INSTALLATION LEGS
3
Page 5
1. Product Specifications

1-3. Center of Gravity

QAHV-N560YA-HPB(-BS)
QAHV-N-YA-HPB
1777
Unit: mm
1837
1060
1208
600
316497
1874 719
755
MEES19K001
4
Page 6
1. Product Specifications

1-4. Electrical Wiring Diagrams

QAHV-N560YA-HPB(-BS)
M
MP1
4
3
216
4
557611
DC280-340V
Rectifier
circuit
X10
F07
AC250V
6.3A T
CND
red
2
3
4
5
5
2
3
CNMF
BS08S-
power board
4 3 2
CNXB1
1234121
CNXC1
blue
CNXA1
Ref temp Discharge Compressor
Ref temp Gascooler
Ref temp Suction Compressor
Ref temp Air hex inlet
Outdoor temp
Water sensor.3 External
TH17
Water sensor.2 External
TH16
Water sensor.1 External
TH15
temp Water outlet
TH11
temp Water inlet
TH12TH5 TH1TH4TH9 TH2 TH3
Ref temp Air hex outlet
TH19TH18
(secondary circuit) Water sensor External
1~5V/2~10V 4~2~0mA/0~10V Analog input Water temp.setting
*9,10
SV5
654312 7
red
CN33
X37
CN52
CN39
6543 127
213
Relay4-8
board
IT
654312 7
312 4
12
4321
22221111
TB5
6234
30
27 28
3
25 26
34514
1212
TB5
5123
T4
4 321
t° t°
T1 T2
)
-
(
) +
(
12
CNRL
red
CNOUT1
red
CNXC1
CNXA2
blue
CN401
CN402
green
CN404
black
CN405
blue
yellow
CN406
CN407
red
CN408
CN409
CN421
CN4A
black
CN61
green
523 614
TERMINAL
543 12
CN105
black
CNAC2
LED4:Power supply
Control Board
CNPL3
black
GND
2
311212
S1
black
CN2A
2431
12
Flow
sensor.1
Capacity mode 2
(short/cut)
Capacity mode 1
(short/cut)
CN142A
black
LED1
CNPL1
CNPL2
green
+12V+12V+12V
R12
14
16
17
15
S3
S2
Flow
sensor
No-Voltage
contact
input
mode(On/Off)
23-24 Run(Run/Stop)
21-24 Low-noise mode
(low noise/by ordinary)
(Forced/Normal)
21
35
23
TB5
1241243
CN142C
SWP1
UP
32-33 Hot-water storage
24
333132
TB6
165432
A(to be
Fan mode
34
3
CN142B
blue
lit while energized
SWU3
LED3:Remote controller
SWU2
SWS2SWS1
SWU1
Unit address setting
yellow
R11
TB4
13
(secondary
circuit)
blue
CN422
TH14
Shell Ref temp
X03
CN502
12 3
3
1
2
6
4
5
H1
12
H2
123456789
System error(Normal/Error)
19-20 Demand(On/Off)
19
234561
CN142D
blue
SWP3
SWP2
prepared)
B(automatic)
External pump
Emergency signal
(for extra heater)
20
TB6
22334576 1
X08
X09
CN512
yellow
ENTER
ONONON
12345678910
OFFOFFOFF
DOWN
123456789
*11
OFF
LOCAL
REMOTE
X02
CN501
81
SV2 SV1SV4 SV3
X01
123
80
63H1
TB2
PSL1PSH1
40
No-voltage
contact
output
Error display output
(secondary circuit)
TB8
1675432 1675432
X06
X07
CN511
blue
312
yellow
CN801
321
red
CN63LS
33
3
22
2
11
1
12
GND GND+5V +5V
CN63HS
TB9
41
External device
connecting terminal
Operation display output
Optional remote controller
connecting terminal
86
737475
87
X04
CN510
ON
12
SW421
OFF
operation
LED2:CPU in
Control
black
CNTYP1
CNTYP2
1212 33
2
(Non-polarized)
RA
RB
TB5
1
blue
CN3A
Power circuit
black
1
Z21
72
X05
10
SW3 SW2 SW1
10987654321
AC250V
3.15A T
F06
red
CNAC
Flow adjustment device
(secondary circuit)
101112
312
CNVOUT
yellow
12
red
CN52C
564321
CNLVC
312
green
CNLVB2
6 5 4 3
CNLVB
red
2 1
564321
CNLVA
blue
5 4 3
CNIT
red
2 1
6 5 4 3
CN62
green
12
pink
312
CNDC
green
CNWP
TB6
72C
CNIT
CNIT
red
243311542
CN102
21
yellow
CNS2
Transmission
2
M
LEV3
8 7 6 5 4 3 2 1
M
LEV1
supply
LED1:Power
TB7
Central
control
TB3
power circuit
13
CN04
red
MVW1
M
TP2
TP1
S
Upper controller
AE-200 connecting terminals
A/M1 B/M2
A/M1 B/M2
Ter m in a l
between units
(TB3-A/M1,B/M2)
Transmission
power board
QAHV-N-YA-HPB
251346
CN80
CN81
green
513462
1
OFF ON
FAN Board
F121
DC700V
4A T
CNSNR
41325
4321
CN82
6
IPM
RSH01,
C152
C151
CNVDC
2314
12
black
blue
CN83
SW001
LED1:Normal operation(lit)
RSH02
7654321
V
U
M
3~
Fan motor
(Heat exchanger)
/Error(blink)
LED4:CPU in operation
*3
R5
C100
R1
DCL
CNINV
W
black
12
2
34
156
7
yellow
CN43
21
CN6
LED1:Normal operation(lit)
/ Error(blink)
4
2
black
72C
SC-P1
1
3
red
SC-P2
red
CN1
3
1
R05
CN5
red
D1
R04
CN4
blue
123 23
CN2
6 5412
123
234156127
CNTYP
RSH1
1234
-
Z5
U
+
Z4
F01,F02,F03
C31
C30
THHS
IGBT
C33
C35
C37
++++++
C32
C34
C36
Diode
Bridge
Noise
Filter
U
F02
F03
AC250V
6.3A T
black
SC-V
R31
++
R30
F04
C10
F01
Z3
Z2
Z1
R33
R32
AC250V
6.3A T
C6
C5
C4
C9
C3
U
U
U
SC-L1
R35
R34
C8
C2
SC-W
SC-U
red
red
C7
SC-L2
C1
white
white
CT22
black
red white
CT12
SC-L3
CT3
black
blackwhite
red
W
3~
MS
V
Motor
U
(Compressor)
INV Board
321
CN3
green
black
R03
TB24
N
TB23
L3
TB22
L2
TB21
L1
CN1B
1 2 3
R01
R02
4
13 2
CN1A
E
L
ELB1
L1 L2 L3 N
TB1
~
50Hz
380/400/415V
3N
power supply
input
mode
Capacity mode table
*
Max capacity operation
Energy saving operation 1
(factory setting)
Energy saving operation 2
CN2
C1
FT-P
FT-N
P
N
R06
+
C17
DSA
MEES19K001
5
Page 7
1. Product Specifications
QAHV-N-YA-HPB
Ac current sensor
Capacitor (Electrolysis)
DC reactor
Symbol explanation
CT22
CT12
Symbol explanation
CT3
DCL
C100
F01
F02
F03
Fuse
F04
Crankcase heater (for heating the compressor)
F06
Electric heater (Antifreeze)
Electronic expansion valve (Main circuit)
F121
H1
H2
LEV1
F07
Compressor motor
Pump motor
Fan motor
Electronic expansion valve (Injection)
M
MS
MP1
LEV3
Resistance (for Water flow rate sensor 2)
Water flow control valve
MVW1
Resistance (for Water flow rate sensor 3)
Low pressure sensor
High pressure sensor
R11
R12
PSH1
PSL1
Solenoid valve (Defrost)1
Solenoid valve (Defrost)3
Electrical resistance
Solenoid valve (Defrost)2
R1
R5
SV2
SV1
Water flow rate sensor
Solenoid valve (Defrost)4
Solenoid valve (Injection circuit)
SV4
SV5
SV3
S1
Thermistor
High pressure switch
Function setting connector
IGBT temperature
THHS
TH1~5,9,11,12,14
Z21
63H1
Earth leakage breaker
Thermistor
*TH15~18
*S2,3
72C
<ELB1>
Water flow rate sensor
Electromagnetic relay (Inverter main circuit)
* of symbol item is the optional parts, <> is field-supplied parts.
MEES19K001
ON
ONON
OFF
OFFOFF
OFF
OFF
SW421-1 SW421-2
20mA
~5V
~10V
:Terminal block : Connection by cutting the short circuit wire
(no-voltage contact input and remote controller wiring) and wiring of 100V
Press the tab in the middle of the terminals to remove them.
Check that the terminals are securely locked in place after insertion.
3. Faston terminals have a locking function.
4. The symbols of the field connecting terminals are as follows.
1. The broken lines indicate the optional parts,field-supplied parts,and field work.
2. Dashed lines indicate sub box
5. The method of input signal of operation can choose one of optinal remote controller
or greater.Do not place them in the same conduit tube or cabtyre cable as
or no-voltage input.
6. Leave a space of at least 5 cm between the low voltage external wiring
use a separate cabtyre cable for the following wiring.
this will damage the circuit board.
7. When cabtyre cable is used for the control cable wiring,
(a) Optional remote controller wiring
(b) No-voltage contact input wiring
(c) No-voltage contact output wiring
Using the same cabtyre cable may cause malfunctions
and damage to the unit.
(d) Remote water temperature setting
Set the SW421 as shown in the table below.
9. Need to selects either Water temperature setting input signal.
8. Use a contact that takes 12VDC 1mA for no-voltage contact input.
~10V
~
1
0
4
2
Feeding 30mA or more current may damage the circuit board.
10. Use a 4-20mA signal output device with insulation.
11. For prevention of damage of the pump, SWS2 is set in "A"(factory setting).
Note
contact output.
Change the slide switch SWS2 B(automatic) in Test Run.
12. Use a contact that takes 250VAC, 10mA or above, and 1A or below for no-voltage
6
Page 8
1. Product Specifications

1-5. Optional parts

1-5-1. Remote controller PAR-W31MAA
Refer to 6-1. PAR-W31MAA specifications.
QAHV-N-YA-HPB
MEES19K001
7
Page 9
1. Product Specifications
External water temperature sensor TW-TH16-E
Parts Shape Quantity
Thermistor
ABC
D
A: 157 mm B: 42 mm C: 54 mm D: 48 mm
1 pc
Flow sensor kit
Parts Shape Quantity
Flow sensor
A
B
A: 71.5 mm * 129 mm including the
coupler B: ø30 mm Wiring length: 1.9 m
1 pc
O-ring
A
B
C
A: 15.8 mm B: 2.4 mm C: 20.6 mm
2 pcs
Quick fastener
A
B
C
A: 38.6 mm B: 15 mm C: 14 mm
2 pcs
Coupler 1 (IN-side)
A
Thread: R3/4 Hex 30 A: 36 mm
1 pc
Coupler 2 (OUT-side)
A
Thread: R3/4 Hex 30 A: 43.2 mm
1 pc
Cable tie (2 types)
A
B
Long cable tie A: 380 mm B: 4.7 mm
2 pcs
+
1 spare
Short cable tie A: 100 mm B: 2.5 mm
1 pc
+
1 spare
IN-side
OUT-side
* The size and length noted are approximate.
1
1
2
3
4
5
6
Specification
Specification
1-5-2. Secondary circuit kit Q-1SCK
This kit contains External water temperature sensor TW-TH16-E and Flow sensor kit for use on the secondary side of hot
water heat pump (QAHV) units. Make sure the following parts are included.
QAHV-N-YA-HPB
MEES19K001
8
Page 10
1. Product Specifications
External water temperature sensor TW-TH16
1. Parts that are required to install an external water temperature sensor
A) External water temperature sensor B) Wiring to connect the sensor and the unit* C) Wiring terminals to connect the wiring to the sensor and the terminal block
on the unit (Four for M4 screws)* * Items B) and C) are field supplied.
2. Installing the external water temperature sensor
Install the external water temperature sensor where the water pipes merge or on the load-side tank.Install horizontally or vertically on top of the pipe.When installing horizontally, make sure the wiring faces down.
Wiring specifications
Size
Type
Maximum length
2-core cable (Min.1.25 mm2)
CVVS or CPEVS
20 m
QAHV-N-YA-HPB
Vertical installation
Horizontal installation
3. Wiring the external water temperature sensor
Connect the external water temperature sensor wiring to the terminal block in the control box on the unit as shown in the figure below.
External water temperature sensor
Sensor wiring
ø6
Sensor Sensor properties
· Resistance: R = 15 kΩ ± 3% (0°C)
· B-constant: 3460 K
Note
R 1/2
12-pin terminal block in the control box on the unit
(Note) Run the sensor wiring at least 5 cm away from any wiring that carries a voltage of 100 V or more, and do not put the sensor wiring in the same conduit tube with it.
T2T1
Control box
5442157
20
12
ø10
48
A
Unit
ø78
M4 screw × 3
Terminal screws
A
BB
50
f)
Terminal block for connection to the sensor
e)
MEES19K001
Connect the sensor wiring to terminals T1 and T2 of the 12-pin terminal block in the control box on the unit.
Connect the shield to the earth terminal.
Thread the wiring to the external water temperature sensor through parts b) through d) as shown in the figure at right. Attach M4 terminals (not supplied) to the wirings, and connect them to e) and f) (terminals A and B).
After the wiring is connected, securely tighten the tightening screw d), and then caulk the gap between the wiring a) and the tightening screw to keep water from entering.
b) Water-sealing rubber
(Internal diameter ø11)
c) Washer (Internal diameter ø12)
d) Tightening screw
(Internal diameter ø15)
Shield (to be cut)
a) Wiring (not supplied)
Detailed view of the area labeled “A” in the figure above
9
Page 11
1. Product Specifications
Flow sensor kit
1. Tools and materials needed for an installation of the flow sensor
Have the following tools and materials ready before starting.
1 Flow sensor 1 Tightening torque: 50 N·m ± 10% 2 O-ring 2 *2 Only use silicon grease. 3 Quick fastener 2 *3 Select the following type of extension wiring. 4 Coupler 1 (IN-side) 1 Wiring diameter 0.812 mm or larger 5 Coupler 2 (OUT-side) 1 Type CVVS or CPEVS 6 Cable tie (short) 1 Maximum length 20 m 7 Cable tie (long) 1 to 2 *4 Select the type of terminal block that meets the following.
QAHV-N-YA-HPB
1 Screwdriver - Terminal screw diameter of M3.5 or M4 2 Torque wrench (spanner) *1 3 Grease *2 4 Extension wiring *3 5 Terminal block *4
2. Flow sensor installation
Install the flow sensor on the pipe by following steps (1) through (3) below. Install the flow sensor between the secondary-side pump and the heat exchanger. Refer to the Installation/Operation Manual of QAHV-N560YA-HPB for details.
(1) Install an O-ring on the flow sensor and coupler 2 (OUT-side).
OUT-side
Materials Quantity *1 Size: HEX 30
Tools and locally procured materials - Usable at or above 15 V
O-ring
IN-side*
- Water-proof
O-ring
Both of the parts shown at left have a groove on the smaller end. Apply grease to the O-rings, and then fit them into the groove.
Flow sensor
Coupler 2 (OUT-side)
(2) Connect a coupler to the pipe, and connect the flow sensor.
The degree of incline should be less than 5 degrees.
Pipe
Screw in.
Coupler 1
Flow sensor
installation
position
(IN-side)
Coupler 2 (OUT-side)
Screw in.
Pipe
Up
The IN-side of the coupler must face up.
Flow direction
Down
No more than 5 degrees of incline allowed
(3) Install the quick fastener on the pipe.
Quick fastener installation
Quick fastener
When installing the quick fastener, use caution not to let it come in contact with the wiring.
Quick fastener
Hold the wiring with a cable tie.
Place a cable tie over the protective tube to hold the wiring on the pipe.
Thread the cable tie through the hole on the quick fastener, and hold the wiring in place.
* The end with a smaller bore is the IN-side. Be sure to install
them in the correct orientation.
Attach the coupler to the pipe so that
Coupler 1
(IN-side)
Insert
Flow direction
Insert
Coupler 2
(OUT-side)
the IN-side of the coupler faces up
and the OUT-side of the coupler
faces down. (Water flows from top
to bottom.) The incline of the pipe
should not exceed 5 degrees.
Keep the sensor away from water.
The flow sensor is 71.5 mm long.
Keep an appropriate distance
between the couplers.
Fit the flow sensor to the coupler.
Insert the flow sensor into the couplers, and then fit the quick fasteners where the flow sensor and the couplers are connected to each other. Keep the quick fasteners out of contact with the wiring so as not to damage the wiring. Hold the wiring to the quick fastener with a (short) cable tie as shown in the figure to keep the wiring from being damaged. Extend the length of the wiring as necessary, using a terminal block. Keep the wiring and the terminal block dry.
MEES19K001
10
Page 12
1. Product Specifications
3. Flow sensor wiring connection
Connect the wiring by following steps (1) through (4) below.
(1) Open the panel.
Using a screwdriver, remove the SERVICE PANEL and the CONTROL BOX (SUB) cover.
SERVICE PANEL
(2) Thread the wiring into the unit.
B
C
CONTROL BOX (SUB)
1
Thread the flow sensor wiring through A in the figure.
2
Hold the wiring with the cable strap inside the unit indicated as B in the figure to keep it out of contact with the pipes and other components.
3
Thread the wiring through the rubber bush indicated as C in the figure (second one from the left).
QAHV-N-YA-HPB
A
(3) Connect the wiring.
1
2
1
Flow sensorTerminal block box
Wiring (not supplied)
Black
15 14 13
White
Terminal block (not supplied)
Red
* Refer to the Installation/Operation Manual of QAHV-
N560YA-HPB for the detailed explanation on how to open the part indicated as A and how to route the wiring indicated as B in the figure.
* Perform wiring work for the flow output adjustment
device and the thermistor at the same time.
2
Flow adjusting device (Reference)
0-10V
+10V
GND
Connect the flow sensor wiring to the terminal block inside the BOX. The numbers on the wirings correspond to the numbers on the terminal block. Connect each wiring to the correct terminal. When done, hold the excess wiring with the supplied cable tie (long). Also, hold the wirings in place with a cable tie (long) where indicated as B in the figure to keep them out of contact with the pipes and other components.
(4) Close the panel.
Using a screwdriver, re-place the SERVICE PANEL and the CONTROL BOX (SUB) cover.
4. Cautionary notes
Note the following when performing wiring work.
Turn off the power before performing wiring work to avoid electrocution.Watch for sharp edges of sheet metal.Keep external wiring at least 5 cm away from wiring that carries 100 V or higher.Do not bundle the wiring together with strong current wiring.Connect wiring in a way that minimizes electrical noise interference. Shield the wiring to minimize external effects.Install the flow sensor indoors, and insulate it as necessary to keep it from being exposed to subzero temperatures.Keep the wiring and the terminal block dry.
MEES19K001
11
Page 13

2. Product Data

2. Product Data

2-1. Capacity tables

2-1-1. Correction by temperature
Outlet water temperature 60~70°C Energy saving operation 1 mode
QAHV-N560YA-HPB(-BS)
QAHV-N-YA-HPB
65
60
55
50
45
40
35
Capacity
Inlet water temperature 5°C, 400V, unit with a snow hood
Inlet water temperature
5°C~29°C
30
Capacity (kW), Power input (kW)
25
20
15
10
Inlet water temperature 5°C, 9°C, 17°C, 24°C, 29°C starting from the bottom
5
0
-30 -20 -10 0 10 20 30 40 50
Inlet water temperature 29°C, 24°C, 17°C, 9°C, 5°C starting from the bottom
Power input
5°C
9°C
17°C
Inlet water temperature
24°C
29°C
29°C 24°C
17°C
9°C 5°C
MEES19K001
Intake air temperature (°C D.B.)
12
Page 14
2. Product Data
Outlet water temperature 80°C Energy saving operation 1 mode
65
60
55
50
45
QAHV-N-YA-HPB
40
35
30
Capacity (kW), Power input (kW)
25
20
15
10
Inlet water temperature 5°C, 9°C, 17°C, 24°C, 29°C starting from the bottom
Capacity
Inlet water temperature 29°C, 24°C, 17°C, 9°C, 5°C starting from the bottom
Power input
5°C
9°C
Inlet water temperature
Inlet water temperature
24°C
17°C
5°C~29°C
29°C
29°C 24°C
17°C
5°C 9°C
MEES19K001
5
0
-30 -20 -10 0 10 20 30 40 50
Intake air temperature (°C D.B.)
13
Page 15
2. Product Data
Outlet water temperature 90°C Energy saving operation 1 mode
65
60
QAHV-N-YA-HPB
55
50
45
40
Inlet water temperature 24°C, 17°C, 9°C, 5°C starting from the bottom
35
30
Capacity (kW), Power input (kW)
25
20
15
Inlet water temperature
10
24°C, 5°C, 9°C, 17°C starting from the bottom
Capacity
Power input
9°C
5°C
24°C
Inlet water temperature
5°C 9°C
17°C
24°C
Inlet water temperature
17°C
9°C
5°C 17°C 24°C
MEES19K001
5
0
-30 -20 -10 0 10 20 30 40 50
Intake air temperature (°C D.B.)
14
Page 16
2. Product Data
Outlet water temperature 60~70°C Max capacity operation mode
65
60
55
50
45
40
35
Capacity
Inlet water temperature 5°C, 400V, unit with a snow hood
Inlet water temperature
5°C 9°C
17°C
24°C
29°C
QAHV-N-YA-HPB
30
Capacity (kW), Power input (kW)
25
20
15
Inlet water temperature 5°C, 9°C, 17°C, 24°C, 29°C starting from the bottom
10
5
0
-30 -20 -10 0 10 20 30 40 50
Power input
MEES19K001
Intake air temperature (°C D.B.)
15
Page 17
2. Product Data
Outlet water temperature 80°C Max capacity operation mode
65
60
QAHV-N-YA-HPB
Inlet water temperature
55
50
45
40
35
30
Capacity (kW), Power input (kW)
25
Capacity
5°C
9°C
17°C
24°C
29°C
Power input
20
Inlet water temperature
29°C 24°C
15
17°C 9°C 5°C
5°C 9°C
17°C 24°C 29°C
10
5
0
-30 -20 -10 0 10 20 30 40 50
Intake air temperature (°C D.B.)
MEES19K001
16
Page 18
2. Product Data
Outlet water temperature 90°C Max capacity operation mode
65
60
55
50
QAHV-N-YA-HPB
45
40
Inlet water temperature
35
29°C, 24°C, 17°C, 9°C, 5°C starting from the bottom
30
Capacity (kW), Power input (kW)
25
20
15
10
Inlet water temperature 29°C, 24°C, 5°C, 9°C, 17°C starting from the bottom
5
Capacity
Power input
9°C
17°C
5°C
24°C
Inlet water temperature
Inlet water temperature
29°C
5°C
9°C
17°C
24°C
29°C
5°C 9°C
17°C 29°C 24°C
MEES19K001
0
-30 -20 -10 0 10 20 30 40 50
Intake air temperature (°C D.B.)
17
Page 19
2. Product Data
Outlet water temperature 60~70°C Energy saving operation 2 mode
QAHV-N-YA-HPB
65
60
55
50
45
40
35
Inlet water temperature 5°C, 400V, unit with a snow hood
Inlet water temperature
5°C
9°C
Capacity
17~29°C
30
Capacity (kW), Power input (kW)
25
20
15
10
Inlet water temperature 5°C, 9°C, 17°C, 24°C, 29°C starting from the bottom
5
0
-30 -20 -10 0 10 20 30 40 50
Power input
5°C
Inlet water temperature 29°C, 24°C, 17°C, 9°C, 5°C starting from the bottom
9°C
17°C
Inlet water temperature
9°C
24°C
5°C
29°C
MEES19K001
Intake air temperature (°C D.B.)
18
Page 20
2. Product Data
Outlet water temperature 80°C Energy saving operation 2 mode
65
60
55
QAHV-N-YA-HPB
50
45
40
35
30
Capacity (kW), Power input (kW)
25
20
Capacity
Inlet water temperature 29°C, 24°C, 17°C, 9°C, 5°C starting from the bottom
Power input
Inlet water temperature
5°C
9°C
17~29°C
MEES19K001
15
Inlet water temperature
5°C 29°C
24°C
10
Inlet water temperature
9°C
17°C 5°C, 9°C, 17°C, 24°C, 29°C starting from the bottom
5
0
-30 -20 -10 0 10 20 30 40 50
Intake air temperature (°C D.B.)
19
Page 21
2. Product Data
Outlet water temperature 90°C Energy saving operation 2 mode
65
60
QAHV-N-YA-HPB
55
50
45
Capacity
Inlet water temperature
5°C
40
Inlet water temperature
35
29°C, 24°C, 17°C, 9°C, 5°C starting from the bottom
30
Capacity (kW), Power input (kW)
25
20
15
10
Inlet water temperature 29°C, 24°C, 5°C, 9°C, 17°C starting from the bottom
Power input
9°C
24°C
5°C
29°C
Inlet water temperature
17°C
9°C
17°C
24°C
29°C
29°C 24°C 17°C 9°C 5°C
MEES19K001
5
Inlet water temperature
0
-30 -20 -10 0 10 20 30 40 50
Intake air temperature (°C D.B.)
20
Page 22
2. Product Data
2-1-2. Correction by relative humidity
1.05
RH (%)
90
85 90
QAHV-N-YA-HPB
1.00
85
70
80
0.95
70
60
40
50
80
30
0.90
Capacity correction factor
30
40
50
0.85
60
0.80
-15 -10 -5 0 5 10 15 20 25 30
Outside air temperature (°C D.B.)
35 40
MEES19K001
21
Page 23
2. Product Data

2-2. Sound pressure levels

Measurement condition
QAHV-N560YA-HPB(-BS)
QAHV-N-YA-HPB
1m
Measurement location
1.5m
Sound Pressure Level: 56.0 / 58.0 dB (Spring, Autumn/Winter)
Opetation condition… Spring, Autumn: Outdoor temp.: 16°CDB/12°CWB, Inlet water temp.: 17°C, Outlet water temp.: 65°C
Winter: Outdoor temp.: 7°CDB/6°CWB, Inlet water temp.: 9°C, Outlet water temp.: 65°C
Winter
90
80
70
60
50
40
Octave band sound level (0dB=20μPa)
30
Spring, Autumn
NC-70
NC-60
NC-50
NC-40
NC-30
MEES19K001
20
Approximate minimum audible limit on continuous noise
10
63Hz 125Hz 250Hz 500Hz 1000Hz 2000Hz 4000Hz 8000Hz
Octave band central frequency (Hz)
NC-20
22
Page 24
2. Product Data

2-3. Vibration levels

QAHV-N-YA-HPB
Measurement location
Concrete
Model Vibration Levels [dB]
QAHV-N560YA-HPB(-BS) 47 or less
10cm
20cm
MEES19K001
23
Page 25

3. Installation

Wind
Wind
• Install the outdoor unit in a place where it is not exposed to direct wind, such as behind a building.
• Install the outdoor unit so that the outlet/ inlet faces away from the wind.
Wind
3. Installation

3-1. Selecting the Installation Site

3-1-1. Installation Conditions
Select the installation site in consultation with the client.
Select a site to install the outdoor unit that meets the following conditions:
The unit will not be subject to heat from other heat sources.The noise from the unit will not be a problem.The unit will not be exposed to strong winds.Water from the unit can be drained properly.The space requirements as shown in 3-1-2. Installation Space Requirements.
QAHV-N-YA-HPB
1. Protection against winds
Using the figures at right as a reference, provide adequate protection against winds. A unit installed alone is vulnerable to strong winds. Select the installation site carefully to minimize the effect of winds. When installing a unit in a place where the wind always blows from the same direction, install the unit so that the outlet faces away from the direction of the wind.
2. Cold Climate Installation
Observe the following when installing the units in areas where snow or strong winds prevail.
Avoid direct exposure to rain, winds, and snow.Icicles that may form under the foundation can fall and inflict personal injury or property damage. Select the installation site
carefully to reduce these risks, especially when installing the unit on a roof.
If the units are installed in the direct line of rain, winds, or snow, install the optional snow hood (on both the discharge and
suction ducts). Use a snow net or snow fence as necessary to protect the unit.
Install the unit on a base approximately twice as high as the expected snowfall.If the unit is continuously operated for a long time with the outside air temperature below the freezing point, install a heater
at the base of the unit to prevent the water from freezing at the unit bottom.
When using the unit in an outdoor temperature of -15ºC or below, install a drain pan (with heater whose capacity is 320 W
or more) at the bottom surface of the unit.
MEES19K001
24
Page 26
3. Installation
3-1-2. Installation Space Requirements
Provide sufficient space around the unit for effective operation, efficient air movement, and ease of access for maintenance.
1. Single unit installation
(1) When all walls are within their height limits*.
QAHV-N-YA-HPB
[mm]
≤ Unit height
≤ 500
L2
L3
L3
≤ Unit height
When the distance behind the unit (L2) needs to be small 500 300 50
L1
* Height limit
Front/Right/Left Same height or lower than the overall height of the unit
Rear 500 mm or lower from the unit bottom
Required minimum distance [mm]
L1 (Front) L2 (Rear) L3 (Right/Left)
(2) When one or more walls exceed their height limits*.
When the wall(s) at the front and/or the right/left exceed(s) their height
When the wall at the rear exceeds its height limit
When all walls exceed their height limits
limits
L3
h1
Unit height
h3
≤ 500
Unit height
L3
L1
L2
L3
≤ Unit height
L3
≤ Unit height
L1
h2
500
L2
h3
h1
L3
Unit height
L3
Unit height
L1
h2
500
L2
Add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2, and L3 as shown in the table below.
Required minimum distance [mm]
L1 (Front) L2 (Rear) L3 (Right/Left)
When the distance behind the unit (L2) needs to be small 500 + h1 300 + h2 50 + h3
MEES19K001
25
Page 27
3. Installation
2. Multiple unit installation
When installing multiple units, make sure to take into consideration factors such as providing enough space for people to pass through, ample space between blocks of units, and sufficient space for airflow. (The areas marked
A
with in the figures below must be left open.)
In the same way as with the single unit installation, add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2, and L3 as shown in the tables below.
QAHV-N-YA-HPB
(1) Side-by-side installation
A
L4
h1
Unit height
Required minimum distance [mm]
L1 (Front) L2 (Rear) L4 (Between)
500 + h1 300 + h2 100
A
Leave open in two directions.
A
L1
(2) Face-to-face installation
When there are walls in the front and rear of the block of units
[mm]
h2
500
L2
When there is a wall on either the right or left side of the block of units
A
h1
Unit height
L1
Required minimum distance [mm]
L1 (Front) L2 (Rear) L4 (Between)
500 300 500
A
Leave open in two directions.
A
L4
h2
500
L2
L4
h3
Unit height
L3
Required minimum distance [mm]
L3 (Right/Left) L4 (Between)
50 + h3 500
L4
L4
MEES19K001
26
Page 28
3. Installation
3. Combination of face-to-face and side-by-side installations
When there are walls in the front and rear of the block of units
A
L4
h2’
500
Required minimum distance [mm]
L2 (Right) L2’ (Left) L4 (Between)
300 + h2 300 + h2’ 1000
A
Leave open in two directions.
L2’
A
When there are two walls in an L-shape
h3
Unit height
h2
500
L2
L3
A
Required minimum distance [mm]
L2 (Right) L3 (Right/Left) L4 (Between)
300 + h2 1000 + h3 1000
[mm]
L2
A
L4
QAHV-N-YA-HPB
h2
500
3-1-3. System installation restrictions
Piping length restrictions
The maximum piping length is 60 m. Select appropriate diameter pipes to prevent negative pressure from the pumping head and the pressure loss in the pipes. Pumping head (when maximum flow rate is 17 /min): 77 kPa
Installation height restrictions
• When the unit is installed above the storage tank Decide the height so that the unit inlet water pressure will not be negative for the tank pressure.
Heat
pump
unit
Unit inlet water pressure > 0 MPa
Storage
tank
• When the unit is installed below the storage tank Decide the height so that the unit inlet water pressure will be 0.5 MPa or below for the tank pressure.
Storage
tank
Unit inlet water pressure < 0.5 MPa
Heat
pump
unit
MEES19K001
27
Page 29
3. Installation

3-2. Unit Installation

Units should be installed only by personnel certified by Mitsubishi Electric.
Securely fix the unit with bolts to keep the unit from falling down during earthquakes or due to strong winds.Install the unit on a foundation made of concrete or iron.Noise and vibrations from the unit may be transmitted through the floor and walls. Provide adequate protection against
noise and vibration.
Build the foundation in such way that the corners of the installation legs are securely supported as shown in the figure
below. When using rubber vibration isolators, make sure they are large enough to cover the entire width of the unit's
QAHV-N-YA-HPB
legs. If the corners of the legs are not firmly seated, the legs may bend.
The projecting length of the anchor bolt should be less than 30 mm.This unit is not designed to be installed using hole-in anchor bolts unless brackets are used to support the four corners
of the unit.
The legs on the unit are detachable.Detaching the legs
Loosen the three screws on the legs to detach each leg (two each in the front and back). If the finish coat becomes damaged when detaching the legs, be sure to touch it up.
Be sure to install the unit on a surface strong enough to withstand its weight to keep the unit from falling down
and causing injury.
Provide adequate protection against strong winds and earthquakes. Improper installation may cause the unit
to fall down, resulting in personal injury.
When building the foundation, take the floor strength, water drainage during operation, and piping and wiring routes into consideration.
Precautions for routing the pipes and wires underneath the unit without detachable legs When routing the pipes and wires underneath the unit, make sure that the foundation will not block the piping access holes. Also, make sure the foundation is at least 100 mm high so that the piping can pass under the unit.
≤ 30 mm
A: M10 anchor bolt (field supply)
B
A
C
≤ 30 mm
A
B
B: Corner is not seated. C: Detachable leg D: Screws
D
MEES19K001
28
Page 30

4. System Design

4. System Design

4-1. Water Pipe Installation

4-1-1. Schematic Piping Diagram and Piping System Components
indicates the direction of the water flow.
Heat pump unit
QAHV-N-YA-HPB
2
T
1
6
T
2
1
7
3
4
P
5
P
3
5
4
10
8
9
11
Water piping diagram
1
Union joints/flange joints
2
Thermometer
Water pressure gauge
3
4
Valve
5
Flexible joint
Drain pipe
6
7
Strainer
8
Air vent valve
9
Water pipe
10
Drain valve Install drain valves so that water can be drained for servicing.
11
Expansion tank
Required to allow for a replacement of equipment.
Required to check the performance and monitor the operation of the units.
Recommended for checking the operation status.
Required to allow for a replacement or cleaning of the flow adjuster.
Recommended to prevent the noise and vibration from the pump from being transmitted.
Install the drain pipe with a downward inclination of between 1/100 and 1/200. To prevent drain water from freezing in winter, install the drain pipe as steep an angle as practically possible and minimize the straight line. For cold climate installation, take an appropriate measure (e.g., drain heater) to prevent the drain water from freezing.
Install a strainer near the unit to keep foreign materials from entering the water-side head exchanger (supplied).
Install air venting valves to the places where air can accumulate. Automatic air vent valves are effective.
Use pipes that allow for easy air purging, and provide adequate insulation.
Select an expansion tank that is suitable for the system.
To storage tank
From storage tank
* Installing a freezing prevention heater
(1) In cold areas (where the outside temperature drops below freezing), provide a freezing prevention heater at all local
pipes to prevent spontaneous freezing.
(2) After the heater is installed, check outside temperature +25ºC is ensured at the EcoCute inlet/outlet pipe joint section
(at outside temperature -25ºC, joint section 0ºC or higher).
(3) Depending on the local piping material, prevent overheating by selecting a self temperature adjustment type heater or
other method.
Heater installation example
Heater
Piping
Joint section 0ºC or higher
Piping
Heater
250 mm
Tape
Heat insulator
MEES19K001
29
Page 31
4. System Design
* 3-way valve installation
Please connect 3-way valve on the lower part of the storage tank except when the unit is in operation. Anti-freezing operation will keep the water in the tank circulated and water storage tanks can become thermally stratified.
QAHV-N-YA-HPB
: Anti-freezing operation Residual running of the pump
: Hot water storage operation
3-way valve (field supply)
MEES19K001
30
Page 32
4. System Design
4-1-2. Notes on pipe Corrosion
Water treatment and water quality control
Poor-quality circulating water can cause the water-side heat exchanger to scale up or corrode, reducing heat exchange performance. Properly control the quality of the circulating water.
Removing foreign objects and impurities in the pipes
During installation, keep foreign objects, such as welding and sealant fragments and rust, out of the pipes.
Water Quality Control
(1) Poor-quality water can corrode or scale up the heat exchanger. Regular water treatment is recommended.
Water circulation systems using open heat storage tanks are particularly prone to corrosion. When using an open heat storage tank, install a water-to-water heat exchanger, and use a closed-loop circuit on the air-conditioner side. If a water supply tank is installed, keep contact with air to a minimum, and keep the level of dissolved oxygen in the water no higher than 1 mg/ℓ.
(2) Water quality standard
Higher mid-range temperature Make-up water criteria
Items
pH (25°C) 6.5 ~ 8.0 6.5 ~ 8.0
Electric conductivity (mS/m) (25°C) 30 or less 30 or less
(µs/cm) (25°C) [300 or less] [300 or less]
-
Chloride ion (mg Cl
Standard items
Reference items
Reference: Guideline of Water Quality for Refrigeration and Air Conditioning Equipment. (JRA GL02E-1994)
Sulfate ion (mg SO42-/) 30 or less 30 or less
Acid consumption
(pH4.8) (mg CaCO3/)
Calcium hardness (mg CaCO
Ionic silica (mg SiO
Iron (mg Fe/) 0.3 or less 0.3 or less
Copper (mg Cu/) 0.1 or less 0.1 or less
Sulfide ion (mg S2-/) Not to be detected Not to be detected
Ammonium ion (mg NH
Residual chlorine (mg Cl/ ) 0.1 or less 0.1 or less
Free carbon dioxide (mg CO2/) 10.0 or less 10.0 or less
/) 30 or less 30 or less
/)
3
/) 30 or less 30 or less
2
+
/) 0.1 or less 0.1 or less
4
Water Temp. > 60°C Water Temp. > 60°C
Recirculating water Recirculating water Corrosive Scale-forming
50 or less 50 or less
6.5 pH 7.5: 90 or less
7.5 pH 8.0: 50 or less
250 or less
Tendencywater system (with secondary side control enabled)
OO
OO
O
O
OO
O
O
O
O
O
QAHV-N-YA-HPB
O
O
O
(3) Please consult with a water quality control specialist about water quality control methods and water quality
calculations before using anti-corrosive solutions for water quality management.
(4) When replacing an air conditioner (including when only the heat exchanger is replaced), first analyze the water
quality and check for possible corrosion. Corrosion can occur in water systems in which there has been no signs of corrosion. If the water quality level has dropped, adjust the water quality before replacing the unit.
(5) Suspended solids in the water
Sand, pebbles, suspended solids, and corrosion products in water can damage the heating surface of the heat exchanger and cause corrosion. Install a good quality strainer (60 mesh or better) at the inlet of the unit to filter out suspended solids.
(6) Connecting pipes made from different materials
If different types of metals are placed in direct contact with each other, the contact surface will corrode. Install an insulating material between pipes that are made of different materials to keep them out of direct contact with each other.
MEES19K001
31
Page 33
4. System Design
4-1-3. Pipe gradient and air venting valve (Outlet hot water pipe)
During the hot water storage operation, the air dissolved in the water is discharged in the form of bubbling from the outlet hot water pipe to quickly raise low-temperature water to the required temperature. When the air accumulates in the pipe, the resistance of the water circuit will increase and the flow rate will extremely decrease. Because of this, an installation of automatic air venting valves is required when there is a pipe that slopes down in the outlet hot water pipe. Install the pipe with an upward gradient of 1/200 or more toward the air vent to prevent air accumulation in the pipe.Also, install air venting valves to the places where air can accumulate. The installation example is shown below.
QAHV-N-YA-HPB
If the crosscut pipe is located lower than the hot water outlet of the heat pump unit, raise the pipe near the unit and install
an automatic air venting valve.
Automatic air venting valve
Automatic air venting valve
Heat pump unit
Upward gradient 1/200
Air separator
Base
Air venting valve installation example
4-1-4. Outlet check valve (When installing multiple units)
When connecting multiple units with pipes in parallel, install a check valve at the outlet pipe of each unit. If a check valve is not installed, a circuit in which warm water flows back will be created in some units during the defrost cycle or abnormal stop, and other units will come to an abnormal stop due to sudden change of the inlet water temperature.
4-1-5. Water Pipe Hole Size and Location
Automatic air venting valve
Hot water outlet
Crosscut pipe
Hot water outlet (Bronze Rc3/4, female screw)
85 9085
274
297
Water inlet (Bronze Rc3/4, female screw)
206
122
199
Service panel
19
9
26 5454 26
755
Front view Side view
MEES19K001
32
Page 34
4. System Design

4-2. QAHV Secondary side control

4-2-1. General description and purpose of secondary side control
Secondary side control is a control method to raise the hot water temperature in the tank by using another heat exchanger
added between the tank and the existing heat exchanger. By incorporating the secondary side control to the QAHV, the need to assemble a pump control on-site is eliminated, and the system construction in cases where water exceeding the QAHV water quality standard is used is now easier.
(1) System diagram
Secondary side control system
[2] Secondary side circuit [3] Hot water supply circuit[1] Unit heating circuit
Temperature sensor
T
Flow sensor
System overview The system using the secondary side control is roughly split into the following three elements: [1] Unit heating circuit, [2]
Secondary side circuit, and [3] Hot water supply circuit. The hot water heated in the unit heating circuit [1] and the cold water from the lower section of the tank are heat-exchanged in the secondary side circuit [2], and then the high-tempera­ture water flows into the hot water storage tank. The heated hot water in the hot water storage tank is supplied to the customer via the hot water supply circuit [3].
QAHV-N-YA-HPB
Control target
Based on the data of the flow rate sensor and temperature thermistor installed on the secondary side, the output of secondary side pump is adjusted by QAHV (adjusts by 0-10 V output).
Purpose
Adjusting the pump output on the secondary side maintains the target outlet hot water temp. and prevents acute rising of water inlet temp. to QAHV.
Overview on pump operation in different operation modes (○: operated, ×: stopped)
Operation modes Primary side Secondary side
Hot water storage mode
Defrost operation mode
Anti freezing operation
At the end of hot water storage mode, before and after defrost operation (*)
○○
××
○○ ○○
(2) Difference between systems with and without secondary side control
Without secondary side control
Unit Tank Unit
Diagram
With secondary side control
Secondary side heat exchanger
Tank
MEES19K001
Water quality standard Calcium hardness (mg CaCO3/ℓ)
Hot water supply temperature range
Control target
6.5 ≤ pH ≤ 7.5: 90 or less
7.5 ≤ pH ≤ 8.0: 50 or less
55-90°C
Unit
pH ≤ 250 or less
Unit: 55-90°C Secondary side: 55-80°C
Unit, secondary side pump, and
secondary side flow adjusting device
33
Page 35
4. System Design
4-2-2. Schematic Piping Diagram and Piping System Components
Secondary side control system
[2] Secondary side circuit [3] Hot water supply circuit[1] Unit heating circuit
Temperature sensor
T
QAHV-N-YA-HPB
Flow sensor
(1) Notes on configuring and selecting components
1) Points to note for secondary side water piping [1] Details on components in the unit heating circuit
* For details, refer to page 29. [2] Details on components in heat exchanger heating circuit Schematic Piping Diagram and Piping System Components for secondary circuit
No.
Flow sensor
1
(Optional parts)
Temperature
2
sensor (Optional parts)
Plate heat
3
exchanger
Pump + Flow
4
rate adjustment device
5
Water piping
Anti-freeze
6
heater
7
Union joint
8
Val ve
9
Strainer
10
Air vent valve
11
Flexible joint
Water pressure
12
gauge
13
Expansion tank
14
Drain valve
15
Safety valve
From heat pump unit
To heat pump unit
Component
3
2
T
7
7
14
Application
Measures and controls the secondary side flow rate.
Measures and controls the secondary side outlet hot water temperature.
Exchanges heat between hot water output from the unit and water input from the tank.
Outputs hot water from the secondary side and adjusts the flow rate.
Water flow channel
Prevents pipe damage due to freezing of the water circuit.
Improves the workability of replacing equipment.
Improves the workability of cleaning the heat exchanger and replacing parts.
Prevents foreign materials from entering into the heat exchanger.
Bleeds air from the pipe.
Prevents the propagation of vibration.
Used to check the operation status.
Absorbs excessive water pressure due to expansion caused by a rise in temperature.
Improves workability of replacing equipment.
Prevents rupturing of the water circuit.
14
8
Be sure to install this component between the downstream of the flow rate adjustment device and the heat exchanger.
Install this component at the outlet of the heat exchanger.
Select a heat exchanger that is appropriate for the capacity.
Select a pump and flow rate adjustment device that are suitable for the system. Install them at the lower outlet of the tank.
Be sure to perform insulation work. Select pipes that allow for easy air bleeding.
This component needs to be installed in a location where an ambient temperature may fall to 0˚C or less.
Install these components in the two places of the chilled water passage section and the high temperature water passage section to enable replacement.
Install these components in the two places of the chilled water passage section and the high temperature water passage section to enable replacement.
Install a strainer with 60 mesh or better near the heat exchanger.
Install air vents in places where there is a risk of air accumulating.
These components need to be installed in consideration of the pipe load as pipes are easily damaged by bending.
Attach this component to each piping section to check the water pressure.
Select an expansion tank that is suitable for the system.
Install these components in the two places of the chilled water passage section and the high temperature water passage section to enable replacement.
Be sure to provide an escape pipe to prevent discharged water from spraying on passersby.
12
P
8
12
P
11
15
4
1
P
Remarks and notes on selecting and installing components
10
To storage tank
5 6
From storage tank
9
11
13
5 6
MEES19K001
34
Page 36
4. System Design
4-2-3. Selection criteria for heat exchanger
Step 1 Determination of prerequisites for selection
1. Heat exchanger capacity 40000 W
2. Estimation of outlet hot water and inlet water temperatures As a guide, select a heat exchanger of which the temperature difference between the high temperature section and the low temperature section will be 5°C or below.
2-1. Outlet hot water temperature (when secondary side outlet hot water temperature is set to 65°C (setting at the
time of shipment))
Secondary side circuit outlet hot water temperature: 65°C Unit outlet hot water temperature: 70°C
2-2. Inlet water temperature
Secondary side inlet water temperature: 10°C Unit inlet water temperature: 15°C
3. Used flow rate (40000 W/(70-15)°C/4200 J/kg•K) × 60 s = 10.4 kg/min 10.4 ℓ/min
Step 2 Determination of model
Notes on selection
Select a heat exchanger that allows water to pass through both of the flow channels. Select a heat exchanger so that the pressure applied to the heat exchanger in the on-site system will not
exceed the maximum operating pressure of the heat exchanger.
Select a heat exchanger that allows flowing at a flow rate of maximum 30 /min. Select a heat exchanger with a capacity of at least 40000 W. Ensure that the shearing stress at the flow rate to be used will be 16 Pa or more. (Refer to step 4.)
* To increase the shearing stress:
When the area per plate is equal, select a vertically long heat exchanger. Select a heat exchanger of which NTU is high (although the heat transfer capacity improves as NTU
increases, the pressure loss becomes high).
QAHV-N-YA-HPB
Step 3 Determination of specifications of the heat exchanger
Determine the model of heat exchanger and number of plates in consultation with the heat exchanger manufacturer based on the above requirements. * To determine the number of plates, calculate the number of plates while referring to the example below.
Values to use when determining the number of plates:
1) Overall heat transfer coefficient of corresponding heat exchanger
2) Heat transfer area per plate
Calculation method
a) Obtain the data of 1) and 2) from the heat exchanger manufacturer. b) Estimate the number of plates of the heat exchanger. c) Check that the number of transfer units for the corresponding number of plates matches between NTU1 and
NTU2 (NTU1=NTU2). If they are matched, select a heat exchanger having the corresponding number of plates. If they are not matched, change the number of plates and then return to B to perform the calculation again.
∆T1: Temperature difference between inlet and
NTU 1
= NTU 2
ΔT ΔT
K×A
=
V×C
outlet
∆T: Temperature difference of high temperature
part (low temperature part)
2
K: Overall heat transfer coefficient (W/m
K)
A: Total heat transfer area (m2) G: Total mass flow rate (kg/s) C: Specific heat (J/kg•K)
MEES19K001
35
Page 37
4. System Design
Step 4 Calculation of the shearing stress
Calculate the shearing stress using the following method. Values required for calculation
Relationship between flow rate and pressure loss of corresponding heat exchanger (Obtain the data from the
heat exchanger manufacturer.)
Calculation method Calculate the shearing stress using the following formula.
QAHV-N-YA-HPB
Representative length of 1 channel
Effective length
Front of heat exchanger
Side of heat exchanger
Distance between plates
Effective length: Length between water inlet and water outlet (refer to the figure on the right)
Representative length of 1 channel: Distance between plates (refer to the figure on the right) × 2
Effective length
∆P: Pressure loss
A shearing stress of 16 Pa or higher is required to reduce the amount of scale that adheres. If the shearing stress is low:
Select a vertically short shape. Change the shape of the plates.
Reselect a heat exchanger that will increase the shearing stress by following methods described above.
MEES19K001
36
Page 38
4. System Design
4-2-4. Configuration method and selection criteria of flow rate adjustment device
In this system, a flow rate adjustment device is installed in the secondary side circuit to perform secondary side flow rate adjustment control by outputting 0 to 10 V from the unit. * 10-V power supply is not supplied. The following shows a system configuration example of the flow rate adjustment device and notes on the system configuration. The following three system types are recommended as flow rate adjustment devices:
1. System using a three-way valve
2. System using a two-way valve
3. System using an inverter
1. System using a three-way valve
Overview of system
ON/OFF signal
0 to 10 V output
Three-way valve
Pump
This system has a pump provided at the outlet of the tank and a three-way valve provided downstream of the pump, and adjusts the flow rate by controlling the opening and closing of the three-way valve.
Flow rate
output device
Pump
Wiring connection places
1-3 of CN512 of
control board
(ON/OFF output)
QAHV-N-YA-HPB
Flow rate
adjustment
device
Three-way valve
Sub box
terminal block
No. 10, 11, 12
Notes on selection method and system configuration
Notes on pump selection and connection
Calculate the total pump head according to the system at the site and then select a pump capable of outputting
the minimum flow rate of about 3 /min and maximum flow rate of about 30 /min with the necessary pump head for the piping at the site.
When selecting the pump, please note that output at a high flow rate will not occur if the flow rate with the
pump head of the system at the site is low, and output at a low flow rate will not occur if the flow rate is too high.
Be sure to check that the flow rate becomes 20 to 30 ℓ/min at the maximum output during a flow rate
adjustment test run.
* If the flow rate is not within the range of 20 to 30 /min, select a different pump or adjust the maximum
frequency using an inverter, etc. so that the maximum flow rate of 20 to 30 /min is achieved.
* To select a proper pump, first select a pump that supports slightly high flow rate, and then adjust the frequency
with an inverter so that the flow rate becomes 20 to 30 /min at the maximum output. (In that case, an inverter is necessary to be prepared separately.)
Notes on three-way valve selection and connection
Use a valve that is capable of adjusting the flow rate with a 0 to 10 V input. Calculate the Cv value and select a valve that supports an appropriate rate. Select a valve of which the ratio of the maximum flow rate and the minimum flow rate will be at least 1:10. Place the three-way valve downstream of the pump. Connect one outlet to the heat exchanger.
Connect the other outlet to the lower part of the tank.
Carefully read the instruction manual and use the three-way valve in accordance with the usage procedures.
MEES19K001
37
Page 39
4. System Design
2. System using a two-way valve
QAHV-N-YA-HPB
ON/OFF signal
Overview of system This system has a pump provided at the outlet of the
0 to 10 V output
tank and a two-way valve provided downstream of the pump, and adjusts the flow rate by controlling the opening and closing of the two-way valve.
Flow rate
output device
Two-way valve
Notes on pump selection and connection Select a pump in the same way as for a system with a three-way valve. Notes on two-way valve selection and connection
Use a valve that is capable of adjusting the flow rate with a 0 to 10 V input. Calculate the Cv value and select a valve that supports an appropriate rate. Select a valve of which the ratio of the maximum flow rate and the minimum flow rate will be at least 1:10. There are various kinds of two-way valve (such as ball valve, butterfly valve, and globe valve), and there are
valves suitable for flow rate adjustment and valves that are not suitable for flow rate adjustment. Therefore be sure to select a two-way valve of a kind capable of precisely controlling the flow rate, such as a butterfly valve or globe valve.
Place the two-way valve downstream of the pump. Carefully read the instruction manual and use the two-way valve in accordance with the usage procedures.
Pump
Wiring connection places
Pump
1-3 of CN512 of
control board
(ON/OFF output)
Flow rate
adjustment device
Two-way valve
Sub box
terminal block
No. 10, 11, 12
3. System using an inverter
Overview of system This system has a pump provided at the outlet
0 to 10 V output
Pump
Inverter
Notes on pump selection and connection Select a pump in basically the same way as for a system with a three-way valve or two-way valve.
Select a pump that can be used also at a low frequency (6 Hz or less).
(The motor may be seized depending on the pump selected as this control is performed at a low frequency.)
Select a pump of which flow rate at 100% output is between 20 to 30 ℓ/min.
Notes on inverter selection and connection
The inverter needs to be able to adjust output with a 0 to 10 input. Select an inverter that will not cause the seizing of the motor. Configure the settings so that the flow rate on the secondary side will become 0 /min when the unit is not
operating.
Carefully read the instruction manual and use the inverter in accordance with the usage procedures.
of the tank and an inverter connected to the pump, and adjusts the flow rate by changing the frequency of the inverter.
Wiring connection places
Flow rate
output
device
Pump
-
Flow rate
adjustment
device
Inverter
Sub box terminal block No. 10, 11, 12
MEES19K001
38
Page 40
4. System Design
4-2-5. When connecting multiple units
To connect multiple units, configure one secondary side circuit system for each unit as shown in the figure below.
(Install a heat exchanger, flow sensor, and thermistor for each unit.)
QAHV-N560YA-HPB
QAHV-N560YA-HPB
Storage tank
QAHV-N560YA-HPB
QAHV-N560YA-HPB
Storage tank
QAHV-N-YA-HPB
MEES19K001
39
Page 41

5. Wiring Design

5. Wiring Design

5-1. System Configurations

1. Types of control cables
Remote controller cable
QAHV-N-YA-HPB
Control cable wiring
*1. Use a CVVS or CPEVS cable (Max. total length of 200 m) if there is a source of electrical interference near by (e.g., factory) or the total length of control
*2. When the wiring length exceeds 10 m, use wire of 1.25 mm².
2. System Configuration (1) Individual system
M-NET cable between units *1
External input wire size Min. 0.3 mm²
External output wire size 1.25 mm²
wiring exceeds 120 m.
* Each unit is operated individually by connecting a dry contact switch/relay to each unit.
Size 0.3 - 1.25 mm² (Max. 200 m total) *2
Recommended cable types CVV
Size More than 1.25 mm² (Max. 120 m total)
Recommended cable types Shielding wire CVVS, CPEVS or MVVS
External
temperature
sensor
Field-supplied dry contact switch/relay or remote controller (PAR-W31MAA) or centralized controller (AE-200)
Unit (MAIN circuit)
PCB PCB
External
temperature
sensor
Field-supplied dry contact switch/relay or remote controller (PAR-W31MAA) or centralized controller (AE-200)
Unit (MAIN circuit)
(2) Multiple system (2-16 units)
* A group of unit that consists of one main unit and up to 15 sub units is operated collectively by connecting an external
water temperature sensor and a dry contact switch/relay to the main unit.
External
temperature
sensor
Field-supplied dry contact switch/relay or remote controller (PAR-W31MAA) or centralized controller (AE-200)
Unit (MAIN circuit)
PCB PCB PCB
MAIN unit
Inter-unit wiring
(M-NET line)
Unit (MAIN circuit) Unit (MAIN circuit)
SUB unit
Inter-unit wiring
(M-NET line)
SUB unit(s)
n units
MEES19K001
40
Page 42
5. Wiring Design

5-2. Electrical Wiring Installation

5-2-1. Main Power Supply Wiring and Switch Capacity
Schematic Drawing of Wiring (Example)
<A> Switch (with current breaking capability)
<B> Current leakage breaker
<C> Outdoor unit
3N~380–415V
1
, L2, L3, N
L
<A><B>
<C>
PE
Main power supply wire size, switch capacities, and system impedance
Model
QAHV-N560YA-HPB 10 - 10 63 A 100 mA 0.1 sec. or less 63 63 63 0.21
1) Use a dedicated power supply for each unit. Ensure that each unit is wired individually.
2) When installing wiring, consider ambient conditions (e.g., temperature, sunlight, rain).
3) The wire size is the minimum value for metal conduit wiring. If voltage drop is a problem, use a wire that is one size thicker. Make sure the power-supply voltage does not drop more than 10%.
4) Specific wiring requirements should adhere to the wiring regulations of the region.
5) Power supply cords of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57).
6) A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.
7) Do not install a phase advancing capacitor on the motor. Doing so may damage the capacitor and result in fire.
Be sure to use specified wires and ensure no external force is imparted to terminal connections.
Loose connections may cause overheating and fire.
Be sure to use the appropriate type of overcurrent protection switch. Note that overcurrent may include direct current.
Minimum wire thickness (mm²)
Main cable Branch Ground Capacity Fuse
Current leakage breaker
Local switch (A)
No-fuse breaker
(A)
Max. Permissive
System Impedance
QAHV-N-YA-HPB
Some installation sites may require an installation of an earth leakage breaker for the inverter. If no earth leakage breaker is installed,
there is a danger of electric shock.
Only use properly rated breakers and fuses. Using a fuse or wire of the wrong capacity may cause malfunction or fire.
This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above
table at the interface point (power service box) of the user’s supply.
Ensure that this device is connected only to a power supply system that fulfills the requirements above.
If necessary, consult the public power supply company for the system impedance at the interface point.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*2) at the
interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, in consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*2).
Ssc(*2)
Ssc (MVA)
2.62
MEES19K001
41
Page 43
5. Wiring Design
5-2-2. Cable Connections
1. Schematic Diagram of a Unit and Terminal Block Arrangement
To remove the front panel of the control box, unscrew the four screws and pull the panel forward and then down.
QAHV-N-YA-HPB
Control terminal block
Power supply terminal block
Cable strap
Power wire
Transmission cable
Cable strap
Transmission cablePower wire
Fix in place with a cable tie.
Important: Power supply cables larger than 25 mm2 in diameter are not connectable to the power supply terminal block
(TB2). Use a pull box to connect them.
2. Installing the conduit tube
Punch out the knockout hole for wire routing at the bottom of the front panel
with a hammer.
When putting wires through knockout holes without protecting them with a
Knockout hole
conduit tube, deburr the holes and protect the wires with protective tape.
If damage from animals is a concern, use a conduit tube to narrow the
opening.
Burr
MEES19K001
42
Page 44
5. Wiring Design
Note:
• Make sure the cables are not coming out of the rubber bushing cut.
Top view
Cut
Rubber bushing (oval part)
Rubber bushing (oval part)
Cables are coming out of the rubber bushing.
Wiring
Cross-sectional view
Top view
Wiring
Rubber bushing
Wiring
• When threading the wiring through the rubber bushing, make sure the rubber bushing will not come off the sheet metal on the control box guard.
QAHV-N-YA-HPB
Sheet metal on the guard
Rubber bushing Rubber bushing
Sheet metal on the guard
• When tying the supplied tie band around the rubber bushing, make sure to leave no gap between the ends.
<<Important>>
Tie band
Overlapped rubber bushing
Approx. 20 mm (13/16 in)
Cut on the rubber bushing
There is a gap in the rubber bushing.
Cut on the rubber bushing
When putting the tie band on the rubber bushing, make sure the ends of the rubber bushing overlap each other as shown in the figure at left. * If there is a gap, water from snow or rain may enter, resulting in equipment damage.
A power wire exceeding the specified power wire thickness cannot be connected to the power terminal block (TB2). Use a separate pull box. To ensure that the transmission cable is not affected by electrical noise from the power cable, route the power cable away from the transmission cable (distance of at least 5 cm).
MEES19K001
43
Page 45

6. Controller

Item Description Operations Display
ON/OFF
Runs and stops the operation of a group of units
Operation mode switching
Switches between Mode 1/Mode 2/Mode 3 * Available operation modes vary depending on the unit to be connected. * Switching limit setting can be made via a remote controller.
Water temperature setting
Temperature can be set within the ranges below. (in increments of 0.5°C or 0.5°F) 40°C ~ 90°C
* The settable range varies depending on the unit to be connected.
Water temperature display
10°C ~ 90°C (in increments of 0.5°C or 0.5°F) * The settable range varies depending on the unit to be connected.
Permit/Prohibit
local operation
Individually prohibits operations of each local remote control function: ON/OFF, Operation modes, water temperature setting, Circulating water replacement warning reset. * Upper level controller may not be connected depending on the unit to be connected.
Weekly scheduler
ON/OFF/Water temperature setting can be done up to 8 times one day in the week. (in increments of a minute)
Error
When an error is currently occurring on a unit, the afflicted unit and the error code are displayed.
Self check (Error history)
Searches the latest error history by selecting "CHECK" from the Main menu.
LANGUAGE setting
The language on the dot matrix LCD can be changed. (11 languages) English/French/German/Swedish/Spanish/Italian/Danish/Dutch/Finnish /Norwegian/Portuguese
(Front view) (Side view) (Rear view)
Unit: mm
120
46
19
83.5
120
6. Controller

6-1. PAR-W31MAA specifications

QAHV-N-YA-HPB
MEES19K001
44
Page 46
MEES19K001
Warning
Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate.
- Doing so may cause the unit or pipes to burst, or result in explosion or fire during use, repair, or at the time of disposal of the unit.
- It may also be in violation of applicable laws.
- MITSUBISHI ELECTRIC CORPORATION cannot be held responsible for malfunctions or accidents resulting from the use of the wrong type of refrigerant.
New publication effective Aug. 2019
Specifications subject to change without notice
Loading...