The PK series models have been downsized and now require such minimal wall space that they can even be installed
above windows. For the PKH18/24FK, 13in of wall space between the ceiling and the window allows “above window”
installation (14.5in for the PKH30/36FK)
2. A FURTHER REFINEMENT OF COMFORT WITH NOISE SUPPRESSION
Remarkably low-noise operation has been achieved through the development of a “near-silent” fan and a design which
minimizes airflow resistance.
3. AUTO FLAP SHUTTER
With a simple flick of the OFF switch the air outlet can be closed off with a shutter. The shutter also functions as a flap
during operation to adjust the air flow angle, with “Auto Angle 1” securing a comfortable air flow.
4. INSTALLATION : FAST AND ENDLESSLY ADAPTABLE
(1) External piping
An external piping connection of 24in and a very light body promote trouble-free installation for PKH18FK.
(2) Multi-directional piping
Multi directional drain and refrigerant piping rodically improves flexibility in selecting installation layouts. PKH18FK drain
piping can be installed in 5 directions, while PKH30/36FK models boast refrigerant piping in 4 directions and drain piping
in 2 directions.
(3) Back plate installation guide
The back plate installation guide gives clear instructions on installation positions. The enlarged back plate secures the
unit firmly to the wall, while the support piece which lifts the unit makes left side piping work much easier.
(4) Front power supply box
The front power supply box allows electrical wiring work to be performed easily even after the indoor unit has been fully
installed. All the screws for the indoor unit can be tightened from the front side thus ensuring smooth installation.
(only for PKH18/24FK)
(5) Easily removable filter
The presence of thumbscrews on the filters means that the filters can be quickly and smoothly removed.
(only for PKH30/36FK)
2
5. ADVANCED MICROPROCESSOR
Indoor unitOutdoor unit
Indoor
heat
exchanger
4•way
valve
Accumulator
Compressor
Outdoor
heat
exchanger
Capillary tubes
for heating
Capillary
tubes for
cooling
Liquid section
of piping
HIgh-pressure
liquid
retrigerant
Restrictor
valve
Restrictor valve
Indoor unitOutdoor unit
Indoor
heat
exchanger
4•way
valve
Accumulator
Compressor
Outdoor
heat
exchanger
Capillary tubes
for cooling
Capillary
tubes for
heating
Liquid section
of piping
Low-pressure
two-phase
retrigerant
Restrictor
valve
Restrictor valve
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTOCOOL/DRY
COOLERWARMER
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECKTEST RUN
(1) Easy to Use Microprocessor
1) Ultra-Thin Remote Controller
The streamlined, square controller is designed to
blend with any kind of interior and the adoption of
a sophisticated microprocessor allows you to
carry out a wide range of operations easily.
2) Ultra-Thin Remote Controller
Units operation mode, set temperature, room tem-
perature, timer setting, fan speed, louver operation, and air flow direction are displayed on the
remote controller with the easily understood visual
Liquid Crystal Display (LCD).
3) Convenient 24-Hour ON-OFF Timer
The timer allows Mr.SLIM to be switched on or
off automatically at the time is shown on the LCD.
4) Self-Diagnostic Feature Indicates Instantly
In the rare case when a problem occurs, the unit stops operating and the set temperature indicator changes to the
self-diagnostic indicator, indicating the location of the fault.
If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The cause of the most
recent problem stored in the memory is displayed on the LCD. This is extremely useful for maintenance purposes.
5) Useful Memory Feature for Storing Instructions
The previous set value is memorized so that constant temperature control can be obtained. This is convenient when,
for example, a power failure occurs.
(2) Non-polar Two-Wire Remote Controller Cables
The non-polar, two-wire type remote controller cable is slim, installation is simple and troublefree. Remote controller
wire can be extended up to 550 yards.
An automatic cooling and heating changeover operation system is provided to ensure easy control and year-round air
conditioning.
Once the desired temperature is set, unit operation is switched automatically between cooling and heating, in
accordance with the room temperatures as low as 23
o
F.
6. REDI-CHARGED REFRIGERANT SYSTEM
PRE-CHARGE REFRIGERANT REQUIRED FOR MAXIMUM PIPING LENGTH AT
SHIPMENT. PREVENTING TROUBLES DUE TO SHORTAGE OF REFRIGERANT.
The unique refrigerant circuit and a large accumulator always controls the refrigerant to its optimum condition regardless of
the length of 164ft maximum or 25ft minimum. The additional refrigerant charging work at the field which often caused
uncertain problems heretofore is completely eliminated. This unique system serves to improve the quality of work and
reliability, and also helps to speed up the installation work.
With normal circulation systems, a high-pressure refrigerant, condensed for cooling by the outdoor heat exacanger, is
reduced in pressure by capillary tubes in the indoor unit after passing through the restrictor valve in the outdoor unit (see
Figure 1). With the new circulation system, the direction of the restrictor valve is reversed as shown in Figure 2, and the
condensed high pressure refrigerant is reduced in pressure by the capacity tubes in the outdoor unit. This results in a “twophase refrigerant” of reduced pressure in the liquid section of the piping, The density of this two-phase refrigerant is 1/3~
1/2 of that of the high pressure liquid refrigerant, and thus is required in smaller amounts (see Figures 1 and 2). As a result,
the length of the piping can be extended further, and the effects of height differences are reduced. These new circulation
system are also equipped with a large accumulator which allows the refrigerant required for the 100ft piping length to be
enclosed in the outdoor unit. The result is an air conditioner that requires no charging unless piping is extended beyond
100ft.
3
7. HIGH RELIABILITY AND EASY SERVICING
Red
Right
Base
Front
In addition to the self-diagnostic function, units are also equipped with a 3-minute time delay mechanism (cooling), an auto
restart function, an emergency operation function, a test run switch, etc., to assure high reliability and easy servicing.
8. FOUR-WAY PIPING ACCESS MAKES
INSTALLATION LAYOUT EASY
Piping on the outdoor unit may be connected from either of
four directions: front, rear, side or beneath the base.
This easy-access design makes it possible to install a
number of units in a compact arrangement at a single site.
The outdoor unit allows for unheard-of flexibility in
detemining a piping layout, thus greatly simplifying
installation.
9. FRONT-ACCESS FACILITATES
MAINTENANCE
The outdoor unit has been designed with a frontaccess
service panel that allows easy access to all maintenance
point, regardless of the installation layout. What’s more, this
front panel may be removed by loosening only two screws.
It all adds up to greatly simplified maintenance work.
10
. NITROGEN GAS IS CHARGED TO
INDOOR UNIT
Indoor unit and refrigerant pipes are charged with nitrogen
gas (N2) instead of R-22 before shipment from the
factory.
4
SPECIFICATIONS2
MODELS : PKH18/24/30/36FK
Model
Item
Capacity
Moisture removal
Power
Consomption
EER
SEER
HSPF
COP
INDOOR UNIT MODELS
External finish
Power supply
Max.fuse size (time dalay)
Min.ampacity
Fan motor
Booster heater
Airflow Hi-Lo
Sound level Hi-Lo
Cond. drain connection OD
Dimensions
Weight
OUTDOOR UNIT MODELS
External finish
Power supply
Max.fuse size (time dalay)
Min.ampacity
Fan motor
Compressor
Crankcase heater
Refrigerant control
Defrost method
Sound level
Dimensions
Weight
REMOTE CONTROLLER
Control voltage (by built-in transformer)
REFRIGERANT PIPING
Pipe size
Connection
method
Between the indoor
& outdoor units
NOTES : *1.Rating conditions (cooling)-indoor : 80˚FDB,67˚FWB outdoor : 95˚FDB,75˚FWB.
(heating)-indoor : 70˚FDB,60˚FWB outdoor : 47˚FDB,43˚FWB.
*2.Rating conditions (heating)-indoor : 70˚FDB,60˚FWB outdoor : 17˚FDB,15˚FWB.
*3.Heating capacity and power consumption in [ ] includes heater operation at 208/230V.
Operating range
Cooling
Heating
Cooling *1
Heating *1
Heating *2
Cooling *1
Heating *1
Heating *2
*1
*1
*2
Dry
Wet
W
D
H
Model (type)
W
D
H
Liquid
Gas
Indoors
Outdoors
Height difference
Piping length
Air flow should be set at HI.
A point on the curve shows the reference point.
<Cooling mode>
PKH36FKPKH36FK
Data is based on the condition of outdoor humidity 75%.
A point on the curve shows the reference point.
<Heating mode>
PKH36FKPKH36FK
13
4. STANDARD OPERATION DATA
Models
Item
Electrical circuitRefrigerant circuitIndoor sideOutdoor side
Voltage
Frequency
Total input
Indoor fan current
Booster heater current
Outdoor fan current
Comp. current
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Comp.shell bottom temperature
Ref. pipe length
Refrigerant charge
Fan speed
Airflow (High)
Fan speed upper/lower
Airflow
Unit
V
Hz
kW
A
A
A
A
psi.G
psi.G
˚F
˚F
˚F
˚F
ft
˚F
˚F
˚F
˚F
r.p.m.
CFM
˚F
˚F
r.p.m.
CFM
Btu/h
208/230
1.79
0.5
0.75
7.4/6.9
255
81
182
118
66
171
80
67
61
59
95
75
18,000
0.82
60
Cooling
208/230
1.56
0.5
7.6/8.4
0.75
6.1/5.9
202
61
126
102
34
111
70
60
96
68
47
43
18,600
Heating
PKH18FK
208/230
2.36
0.5
0.65+0.65
9.3/8.7
240
75
158
115
46
141
80
67
58
56
95
75
24,000
0.71
60
Cooling
208/230
2.37
0.5
7.6/8.4
0.65+0.65
9.5/8.7
243
63
149
115
35
126
70
60
105
70
47
43
25,000
Heating
PKH24FK
208/230
3.12
0.5
0.75+0.75
12.6/11.8
245
80
158
115
49
138
80
67
59
58
95
75
30,000
0.75
60
Cooling
208/230
3.02
0.5
7.6/8.4
0.75+0.75
12.2/11.4
236
60
159
113
32
130
70
60
103
70
47
43
33,000
Heating
PKH30FK
208/230
3.44
0.5
0.75+0.75
14.3/13.2
243
74
160
115
45
142
80
67
58
56
95
75
34,100
0.71
60
5 lbs 8 oz
1,490
710
1,490
710
1,490
990
1,490
990
790
1,590
750/750
3,170
760/760
3,350
760/760
3,350
25
9 lbs 15 oz
25
10 lbs 2 oz
25
10 lbs 9 oz
Cooling
208/230
3.54
0.5
8.7/9.6
0.75+0.75
14.7/13.7
263
60
170
120
33
148
70
60
109
71
47
43
38,000
Heating
PKH36FK
Intake
air temperature
Discharge
air temperature
Intake
air temperature
Capacity
SHF
DB
WB
DB
WB
DB
WB
14
5. OPERATING RANGE
1) POWER SUPPLY
1 Phase 60Hz 208/230V
Guaranteed voltage range
2) OPERATION
Min.Max.
198V208V230V253V
Function
Cooling
Heating
Air intake temperature
Condition
Standard temperature
Maximum temperature
MInimum temperature
Maximum humidity
Standard temperature
Maximum temperature
MInimum temperature
DB(˚F
80
95
67
80
70
80
70
Indoor
)
6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
PKH18FK
PKH24FK
PKH30FK
PKH36FK
Airflow
(
CFM
710
710
990
990
)
Air speed
(
ft/sec
16.1
16.1
17.7
17.7
)
Coverage
range(ft
41
41
50
50
)
Outdoor
WB(˚F
67
71
57
75
60
67
60
)
DB(˚F
95
115
23
80
47
75
17
)
WB(˚F
75
—
—
75
43
65
15
)
The air coverage range is the value up to the position
where the air speed is 0.8ft/sec. when air is blown out
horizontally from the unit at the High notch position.
The coverage range should be used only as a general
guideline since it varies according to the size of the
room and furniture installed inside the room.
7. ADDITIONAL REFRIGERANT CHARGE (R-22(oz))
Refrigerant piping length (one way)
55ft
70ft
85ft
0
0
0
0
0
0
0
0
0
0
0
0
100ft
0
0
0
0
Model
PKH18FK
PKH24FK
PKH30FK
PKH36FK
Outdoor unit
precharged
(
up to 100ft
5 lbs 8 oz
9 lbs 15 oz
10 lbs 2 oz
10 lbs 9 oz
)
25ft
40ft
0
0
0
0
0
0
0
0
115ft
2
2
5
5
130ft
4
4
10
10
150ft
7
16
16
164ft
9
20
20
15
9-1/4
1-25/32
9-1/4
1-25/32
9-1/49-1/4
1-25/32
1/2
13-3/8
7-3/4
Top
Front
Right side
Left side
55-1/8
42-15/16
Air intake
9-1/4
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose
Bolt
Gas pipe
19/32
Terminal block for power supply
Terminal block for control
Terminal block for remote controller
(Liquid pipe)
Liquid pipe
Gas pipe
Liquid pipe
A
1-3/16
1-15/32
1-17/32
3-27/322-9/16
2-29/32
5/32
3-15/16
1-17/32
1-3/16
1-15/32
2-29/32
5/32
1-5/32
11-1/32
1-3/16
7-1/4
1-3/16
3-5/32
1-3/18
2-3/8
13/32
1-17/32
1-15/32
2-9/16
3-15/16
A
B
C
Knock out hole for piping
31/32
43-11/16
7-7/32
9-7/16
B
55-1/8
20-9/16
4-23/32
2-5/32
4-1/32
4-3/8
Air outlet
20-9/16
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
Hole for
tapping screw
66-{1/4 hole for
tapping screw
Wall fixture
Unit center
32-{15/32
hole for bolt
23/32
3-19/32
35-7/16
38-31/32
17-29/32
11-7/32
9-21/32
3/4
9-7/1611-1/3212-3/8
24
Drainage range
on left-hand side
Drainage range
on right-hand side
10x3-19/32=(35-13/16)
7-3/32
2-15/32
8-27/32
7-17/32
23/32
4
OUTLINES AND DIMENSIONS
4.1. Indoor Unit
PKH18/24FK
Unit : mm
16
PKH 30/36FK
Unit : mm(inch)
3/4F
Through hole
Liquid pipe1/2F
Gas pipe
1
2
C
3-1/2 3-1/2~ 4
Sleeve >< 1
>< 1 Sleeves are availaable
on the market.
2-15/32
1/2
9-1/4
1-25/32
9-1/4
Right side
for right piping
Knock out hole
7-3/4
19/32
Bolt
or less
2
2-9/32
1-21/32
4-3/8
4-1/32
2-5/32(Gas pipe)
4-23/32(Liquid pipe)
7-7/32
B
9-7/16
1
9-1/4
1-25/32
Front
66-5/32
Top
9-1/4
1-25/32
9-1/4
1-25/32
9-1/4
53-15/16 Alr Intake
13-3/8
Terminal block for control
Terminal block for powar supply
Terminal block for remote controller
Drain hose
43-11/16 (Drain hose)
Lower side
55-1/8
27-5/16 Air outlet27-5/16 Air outlet
louvers(manual)
left-hand piping)
Under panel (Removable at
11-1/32
1-5/32
3-5/32
1-3/16
1-3/16
7-1/413/32
Knock out hole for under-piping
Refrigerant pipe .Drain pipe
Auto vanes
2-3/8
1-3/16
7-17/32
12- 1/4 hole
for tapping screwRear piping hole
Front
or more
1-3/16
Knock out hole
3-15/16
for left piping
5/32
1-17/32
1-15/32
2-29/32
2-9/16
5-/15/16 or less
Left side
Air
outlet
Air
intake
10 or more
A
C
1-3/161-3/16
1-15/32
2-9/163-27/32
31/32
Drain hose for
B
2 or more10 or more
Knock out hole for wiring
A
1-17/32
3-15/16
1-15/32
1-17/32
2-29/32
5/32
9-21/32
Drainage range on
right-hand side
left-handside piping
50
Unit center
Unit out line
Drainage range on
Left hand side
23-7/16
13x3-19/32=(7-3/16)11-7/32
Wall fixture
3/4
3-19/32
35-7/16
23/32
23/32
84- 1/4 hole
for tapping
screw
29-17/32
9-7/167-3/328-27/3211-1/3212-3/8
Range for left
11-5/8
rear piping hole
41- 15/32 hole
for bolt
Range for left rear piping hole
17
4.2. Outdoor Unit PUH18EK
Terminal block for indoor and outdoor unit connection
1. Since the indoor fan motor (MF) is connected with 230V power, using 208V power will require a setting change of the dip switch (SW7<I.B>) on the indoor controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 208V.
2. Since the indoor transformer (T) is connected with 230V power if 208V power is used. Change the wiring connection showing fig : w 2.
fig w2
When power supply is
w 1.
230V
SW7
ON
OFF
1
2 3 4
240V
208V
ON
OFF
YELLOW
REDYELLOW
1
2 3 4
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are,
6. Emergency operation
¤¤ : Connector, / : Terminal block.
If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code "P8" will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stopped.
If the air outlet is blocked up with the vane, Open it with your hands.
(4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
22
BG79N687H01
MODELS PUH18EK
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
O.B
SW1
SW2
SW3
OFF
ON
2 1
CN2
RT
LED
1
2
3
TB3
YLW
ORN
BRN
FROM INDOOR UNIT
CONNECTING WIRES
12V DC (polar)
L1
L2
GR
GRN
TB1
POWER SUPPLY
1{ 208/230V
60Hz
3
2
1
CN3
CN4T
4 3 2 1
CN4
4 3 2 1
BRN 12.3V AC
RED 12.3V AC
MF
BLU
BLU
WHT
BLU
WHT
WHT
RED
RED
ORN ORN
C1
MF2
MF1
FC
26C
63H2
63H1
63H1
51CM
5
BRN
BRN
YLW
YLW
YLW
YLW
RED
RED
BLU
63H2
MC
R
C
C
S
21
51C
52C
BLU
BLU
WHT
RED
WHT
UR
TW
RED
RED
RED
ORN
BLK
BLK
T
208V
230V
21R
RED
RED
RED
RED
SV
WHT
WHT
TRF
21
S4
BLK
BLK
BLK
BLK
21S4
52C
GRY
GRY
GRY
GRY
52C
WHT
WHT
CHZNR
R/1
S/2
T/3
BLU BLU
F
HC
WHT
WHT
4
S
A
B
X11X12X13X14
X14
X13 X12 X11
4
3
2
1
C
C1
F<O.B>
FC<O.B>
HC
LD1~LD8
MC
MF
O.B
COMPRESSOR CAPACITOR
FAN CAPACITOR
FUSE<6A>
FAN CONTROLLER
CRANKCASE HEATER
LED<CHECK,SERVICE>
COMPRESSOR
FAN MOTOR<INNER THERMOSTAT>
OUTDOOR CONTROLLER BOARD
w1 In addition, the centralized and remote control can be operated.
w2 The modes which indicate the sources of trouble are listed below.
● EO=Signal transmitting/receiving error
● P1=Room temperature thermistor malfunction
● P2=Indoor coil thermistor malfanction
● P4=Drain sensor malfunction
● P5=Drain over flow
● P6=Coil frost/overheat protection
● P7=System error
● P8=Outdoor unit trouble
w3 The CHECK swich will show if an error has occurred in the past.
w4 Fan runs on low speed for 1 minute in order to remove overheat air.
w5 The 3-minute (6 minutes … heating mode) time-delay functions after compressor stops.
w6 FAN or AUTO mode is selected by the indoor dipswitch setting.
w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
26
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
NO
Vane setting notch
Initial
COOLING
w 8
w 9
YES
Vane intial
setting
Vane
60 deg downward angle
70 deg downward angle
YES
Fan speed
LOW
YES
Downward discharge
1 hour
YES
Vane horizontal
airflow
NO
Compressor
thermostat
ON
NO
Allowance
cancel
NO
YES
YES
NO
w 10
w 11
YES
3-minute
time delay
6-minute
time delay
3-minute
compressor opration
Coil frost
prevention
Cooling area
NO
NO
YES
NO
YES
NO
Aliowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
YES
10-minute
NO
compressor operation
Allowance cancel
NO
compressor operation
Compressor ON
YES
Coil frost
protection
NO
16-minute
YES
Indoor pipe
temperature is
34¡F or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
tempreature is
50¡F or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
YES
LOW
FAN speed
LOW 5 min
elapse
NO
YES
Outdoor unit
trouble
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. IF opera-
tion changes during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10After 3 minute compressor operation, if the indoor coil thermistor reads -59°F or below for 3 minutes, the com-
pressor will stop for 6 minutes.
w11Cooling area : Indoor coil temperature is more than 9 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 9 degrees below the room temperature.
FAN area : Indoor coil temperature is within 9 degrees either way of the room temperature.
27
Loading...
+ 62 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.