Mitsubishi Electronics PUH36EK, PUH18EK, PKH30FK, PKH36FK, PUH24EK User Manual

...
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED­ STAND BY DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF AUTO STOP AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
L
I
S
T
E
D
R
A
I
R
S
T
A
N
D
A
R
D
2
1
0
M
A
N
U
F
A
C
T
U
R
E
R
C
E
R
T
I
F
I
E
D
T
O
A
R
I
A
S
C
O
M
P
L
Y
I
N
G
W
I
T
H
C
E
R
T
I
F
I
C
A
T
I
O
N
S
E
C
T
I
O
N
S
O
F
E
Q
U
I
P
M
E
N
T
A
I
R
-
C
O
N
D
I
T
I
O
N
I
N
G
U
N
I
T
A
R
Y
TECHNICAL & SERVICE MANUAL
No. OC120
Series PKH
<Indoor unit>
Models
PKH18FK / PUH18EK PKH24FK / PUH24EK PKH30FK / PUH30EK PKH36FK / PUH36EK
Wall Mounted
Indoor unit
CONTENTS
1. FEATURES ···········································2
2. SPECIFICATIONS·································5
3. DATA·····················································6
4. OUTLINES AND DIMENSIONS··········16
5. WIRING DIAGRAM ·····························22
6.
7. OPERATION FLOW-CHART··············26
8. MICROPROCESSOR CONTROL·······30
9. TROUBLESHOOTING························51
10. SYSTEM CONTROL···························59
11. DISASSEMBLY INSTRUCTIONS ·······64
12. PARTS LIST········································71
13. OPTIONAL PARTS·····························83
······25
REMOTE CONTROLLER
The Slim Line. From Mitsubishi Electric.
1
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED­ STAND BY DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF AUTO STOP AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
FEATURES
Indoor unit
Remote controller
PUH24EK Outdoor unit
Models Cooling capacity / Heating capacity SEER
PKH18FK 18,000 / 18,600 [25,100] Btu/h 11.1 PKH24FK 24,000 / 25,000 [31,500] Btu/h 10.2 PKH30FK 30,000 / 33,000 [40,500] Btu/h 10.6 PKH36FK 34,200 / 38,000 [45,500] Btu/h 10.5
1. COMPACT DESIGN
The PK series models have been downsized and now require such minimal wall space that they can even be installed above windows. For the PKH18/24FK, 13in of wall space between the ceiling and the window allows “above window” installation (14.5in for the PKH30/36FK)
2. A FURTHER REFINEMENT OF COMFORT WITH NOISE SUPPRESSION
Remarkably low-noise operation has been achieved through the development of a “near-silent” fan and a design which minimizes airflow resistance.
3. AUTO FLAP SHUTTER
With a simple flick of the OFF switch the air outlet can be closed off with a shutter. The shutter also functions as a flap during operation to adjust the air flow angle, with “Auto Angle 1” securing a comfortable air flow.
4. INSTALLATION : FAST AND ENDLESSLY ADAPTABLE
(1) External piping
An external piping connection of 24in and a very light body promote trouble-free installation for PKH18FK.
(2) Multi-directional piping
Multi directional drain and refrigerant piping rodically improves flexibility in selecting installation layouts. PKH18FK drain piping can be installed in 5 directions, while PKH30/36FK models boast refrigerant piping in 4 directions and drain piping in 2 directions.
(3) Back plate installation guide
The back plate installation guide gives clear instructions on installation positions. The enlarged back plate secures the unit firmly to the wall, while the support piece which lifts the unit makes left side piping work much easier.
(4) Front power supply box
The front power supply box allows electrical wiring work to be performed easily even after the indoor unit has been fully installed. All the screws for the indoor unit can be tightened from the front side thus ensuring smooth installation. (only for PKH18/24FK)
(5) Easily removable filter
The presence of thumbscrews on the filters means that the filters can be quickly and smoothly removed. (only for PKH30/36FK)
2
5. ADVANCED MICROPROCESSOR
Indoor unit Outdoor unit
Indoor heat exchanger
4•way valve
Accumulator
Compressor
Outdoor heat exchanger
Capillary tubes for heating
Capillary tubes for cooling
Liquid section of piping
HIgh-pressure liquid retrigerant
Restrictor
valve
Restrictor valve
Indoor unit Outdoor unit
Indoor heat exchanger
4•way valve
Accumulator
Compressor
Outdoor heat exchanger
Capillary tubes for cooling
Capillary tubes for heating
Liquid section of piping
Low-pressure two-phase retrigerant
Restrictor
valve
Restrictor valve
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED­ STAND BY DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF AUTO STOP AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
(1) Easy to Use Microprocessor
1) Ultra-Thin Remote Controller
The streamlined, square controller is designed to blend with any kind of interior and the adoption of a sophisticated microprocessor allows you to carry out a wide range of operations easily.
2) Ultra-Thin Remote Controller
Units operation mode, set temperature, room tem- perature, timer setting, fan speed, louver opera­tion, and air flow direction are displayed on the remote controller with the easily understood visual Liquid Crystal Display (LCD).
3) Convenient 24-Hour ON-OFF Timer
The timer allows Mr.SLIM to be switched on or off automatically at the time is shown on the LCD.
4) Self-Diagnostic Feature Indicates Instantly
In the rare case when a problem occurs, the unit stops operating and the set temperature indicator changes to the self-diagnostic indicator, indicating the location of the fault. If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The cause of the most recent problem stored in the memory is displayed on the LCD. This is extremely useful for maintenance purposes.
5) Useful Memory Feature for Storing Instructions
The previous set value is memorized so that constant temperature control can be obtained. This is convenient when, for example, a power failure occurs.
(2) Non-polar Two-Wire Remote Controller Cables
The non-polar, two-wire type remote controller cable is slim, installation is simple and troublefree. Remote controller wire can be extended up to 550 yards.
(3) Automatic Cooling / Heating Changeover Operation
An automatic cooling and heating changeover operation system is provided to ensure easy control and year-round air conditioning. Once the desired temperature is set, unit operation is switched automatically between cooling and heating, in accordance with the room temperatures as low as 23
o
F.
6. REDI-CHARGED REFRIGERANT SYSTEM PRE-CHARGE REFRIGERANT REQUIRED FOR MAXIMUM PIPING LENGTH AT SHIPMENT. PREVENTING TROUBLES DUE TO SHORTAGE OF REFRIGERANT.
The unique refrigerant circuit and a large accumulator always controls the refrigerant to its optimum condition regardless of the length of 164ft maximum or 25ft minimum. The additional refrigerant charging work at the field which often caused uncertain problems heretofore is completely eliminated. This unique system serves to improve the quality of work and reliability, and also helps to speed up the installation work.
With normal circulation systems, a high-pressure refrigerant, condensed for cooling by the outdoor heat exacanger, is reduced in pressure by capillary tubes in the indoor unit after passing through the restrictor valve in the outdoor unit (see Figure 1). With the new circulation system, the direction of the restrictor valve is reversed as shown in Figure 2, and the condensed high pressure refrigerant is reduced in pressure by the capacity tubes in the outdoor unit. This results in a “two­phase refrigerant” of reduced pressure in the liquid section of the piping, The density of this two-phase refrigerant is 1/3~ 1/2 of that of the high pressure liquid refrigerant, and thus is required in smaller amounts (see Figures 1 and 2). As a result, the length of the piping can be extended further, and the effects of height differences are reduced. These new circulation system are also equipped with a large accumulator which allows the refrigerant required for the 100ft piping length to be enclosed in the outdoor unit. The result is an air conditioner that requires no charging unless piping is extended beyond 100ft.
3
7. HIGH RELIABILITY AND EASY SERVICING
Red
Right
Base
Front
In addition to the self-diagnostic function, units are also equipped with a 3-minute time delay mechanism (cooling), an auto restart function, an emergency operation function, a test run switch, etc., to assure high reliability and easy servicing.
8. FOUR-WAY PIPING ACCESS MAKES INSTALLATION LAYOUT EASY
Piping on the outdoor unit may be connected from either of four directions: front, rear, side or beneath the base. This easy-access design makes it possible to install a number of units in a compact arrangement at a single site. The outdoor unit allows for unheard-of flexibility in detemining a piping layout, thus greatly simplifying installation.
9. FRONT-ACCESS FACILITATES MAINTENANCE
The outdoor unit has been designed with a frontaccess service panel that allows easy access to all maintenance point, regardless of the installation layout. What’s more, this front panel may be removed by loosening only two screws. It all adds up to greatly simplified maintenance work.
10
. NITROGEN GAS IS CHARGED TO
INDOOR UNIT
Indoor unit and refrigerant pipes are charged with nitrogen gas (N2) instead of R-22 before shipment from the factory.
4
SPECIFICATIONS2
MODELS : PKH18/24/30/36FK
Model
Item
Capacity
Moisture removal Power
Consomption EER
SEER HSPF
COP INDOOR UNIT MODELS
External finish Power supply Max.fuse size (time dalay) Min.ampacity Fan motor Booster heater
Airflow Hi-Lo Sound level Hi-Lo
Cond. drain connection OD
Dimensions
Weight OUTDOOR UNIT MODELS External finish Power supply Max.fuse size (time dalay) Min.ampacity Fan motor
Compressor
Crankcase heater Refrigerant control Defrost method Sound level
Dimensions
Weight REMOTE CONTROLLER Control voltage (by built-in transformer) REFRIGERANT PIPING
Pipe size Connection
method Between the indoor & outdoor units
NOTES : *1.Rating conditions (cooling)-indoor : 80˚FDB,67˚FWB outdoor : 95˚FDB,75˚FWB. (heating)-indoor : 70˚FDB,60˚FWB outdoor : 47˚FDB,43˚FWB. *2.Rating conditions (heating)-indoor : 70˚FDB,60˚FWB outdoor : 17˚FDB,15˚FWB. *3.Heating capacity and power consumption in [ ] includes heater operation at 208/230V.
Operating range
Cooling
Heating
Cooling *1 Heating *1 Heating *2
Cooling *1 Heating *1 Heating *2 *1
*1 *2
Dry Wet
W D H
Model (type)
W D H
Liquid Gas Indoors Outdoors Height difference Piping length
Maximum
Minimum
Maximum
Minimum
Btu/h Btu/h Btu/h
Pints/h
kW kW kW
V,phase,Hz
V,phase,Hz
A A
F.L.A.
)
A(kW
CFM CFM
)
dB(A
in. in. in. in.
lb
A A
F.L.A.
R.L.A. L.R.A.
)
A(W
)
dB(A
in. in. in.
lb
in. in.
ft ft
Indoor intake air temperature
95˚FDB,71˚FWB 67˚FDB,57˚FWB 80˚FDB,67˚FWB 70˚FDB,68˚FWB
PKH18FK
18,000 18,600[24,100/25,100 10,700[16,200/17,200
5.3
1.79
1.56[3.16/3.46
1.34[2.94/3.24
10.1
11.1
7.2
3.5
2.3
PKH18FK
15 12
0.5
7.6/8.4[1.6/1.9 710-530 640-480
43-35
1
57
PUH18EK
20 16
0.75
RH247NAB
12 37
0.11/0.12[23/28
53
33-1/2
131
Indoor unit-remote controller:DC12V. Indoor unit-outdoor unit:DC12V
130 130
] ]
] ]
]
55-1/8 66-5/32
]
34-1/4 11-5/8
3/8 5/8
Outdoor intake air temperature
PKH24FK
24,000 25,000[30,500/31,500 14,700[20,200/21,200
7.0
2.36
2.37[3.97/4.27
1.92[3.52/3.82
10.2
10.2
6.8
3.1
2.2
PKH24FK
Munsell 3.4Y 7.7/0.8
208/230,1,60
15 12
0.5
7.6/8.4[1.6/1.9 710-530 640-480
43-35
1
57
PUH24EK
Munsell 5Y 7/1
208/230,1,60
20 16
0.65+0.65
NH33NBD
11.5 54
0.16/0.17[33/39 Capillary tube Reverse cycle
55
49-9/16
202
With indoor unit
Not supplied(optional parts)
Flared Flared
115˚FDB
0˚FDB
75˚FDB,65˚FWB 17˚FDB,15˚FWB
PKH30FK
] ]
] ]
]
9-1/4
13-3/8
]
164 164
30,000 33,000[39,100/40,500 19,000[25,100/26,500
9.1
3.12
3.02[4.82/5.22
2.48[4.28/4.68
9.6
10.6
7.1
3.2
2.2
PKH30FK
15 13
0.6
8.7/9.6[1.8/2.2 990-780 890-700
46-41
1
66
PHU30EK
30 20
0.75+0.75
NH41NAD
14.0 73
0.16/0.17[33/39
55
38-3/16 13-9/16 49-9/16
245
1/2 3/4
] ]
]
]
] ]
PKH36FK
34,200 38,000[44,100/45,500 19,600[25,700/27,100
10.5
3.44
3.54[5.34/5.74
2.65[4.45/4.85
PKH36FK
8.7/9.6[1.8/2.2 990-780 890-700
46-41
PUH36EK
0.75+0.75 NH47ND
0.16/0.17[33/39
38-3/16 13-9/16 49-9/16
] ]
9.9
10.5
6.9
3.1
2.2
13
0.6 ]
1
66
30 22
17.5 87
]
246
1/2 3/4
164 164
] ]
5
Models
Models Outdoor intake air DB temperature(˚F
)
PKH18FK
71 67 63
62.5 60 59 71 67 63
62.5 60 59 71 67 63
62.5 60 59 71 67 63
62.5 60 59
TC
21.0
19.5
18.2
18.1
17.2
16.8
27.9
26.1
24.3
24.1
23.0
22.5
34.9
32.6
30.4
30.2
28.8
28.2
39.8
37.1
34.7
34.4
32.8
32.2
SHC
14.4
16.0
17.4
15.5
15.1
14.5
16.1
18.5
20.5
18.0
17.6
17.0
21.5
24.5
26.9
23.8
23.2
22.4
23.0
26.3
29.3
25.8
25.1
24.3
TPC
1.56
1.52
1.49
1.49
1.47
1.46
2.05
2.01
1.97
1.96
1.94
1.93
2.72
2.66
2.60
2.59
2.57
2.56
3.00
2.93
2.87
2.86
2.82
2.81
TC
20.2
18.8
17.5
17.4
16.6
16.2
26.9
25.1
23.4
23.2
22.1
21.7
33.7
31.4
29.2
29.0
27.6
27.0
38.4
35.7
33.3
33.1
31.5
30.8
SHC
13.9
15.4
16.7
14.9
14.5
14.0
15.5
17.8
19.7
17.4
16.9
16.4
20.8
23.6
25.8
22.9
22.2
21.5
22.1
25.3
28.1
24.8
24.1
23.2
TPC
1.69
1.65
1.61
1.61
1.58
1.57
2.23
2.18
2.12
2.12
2.09
2.07
2.95
2.88
2.81
2.80
2.77
2.76
3.25
3.17
3.10
3.09
3.04
3.03
TC
19.4
18.0
16.8
16.6
15.8
15.5
25.8
24.0
22.4
22.2
21.1
20.7
32.3
30.0
27.9
27.7
26.3
25.7
36.8
34.2
31.9
31.6
30.1
29.5
SHC
13.3
14.8
16.0
14.3
13.8
13.4
14.9
17.0
18.9
16.6
16.2
15.6
19.9
22.5
24.6
21.9
21.2
20.4
21.2
24.3
26.9
23.7
23.0
22.3
TPC
1.84
1.79
1.74
1.74
1.70
1.69
2.43
2.36
2.30
2.29
2.25
2.24
3.21
3.12
3.04
3.03
2.99
2.98
3.54
3.44
3.35
3.34
3.28
3.26
TC
18.5
17.1
15.9
15.8
15.0
14.6
24.6
22.9
21.3
21.1
20.1
19.7
30.8
28.6
26.6
26.3
24.9
24.4
35.1
32.6
30.3
30.0
28.5
27.9
SHC
12.7
14.0
15.2
13.6
13.1
12.6
14.2
16.3
18.0
15.8
15.4
14.9
19.0
21.5
23.5
20.7
20.1
19.4
20.2
23.1
25.6
22.5
21.8
21.0
TPC
1.99
1.93
1.88
1.87
1.84
1.83
2.63
2.55
2.47
2.47
2.41
2.39
3.48
3.37
3.27
3.26
3.21
3.19
3.83
3.71
3.61
3.59
3.52
3.50
TC
17.6
16.3
15.1
15.0
14.2
13.9
23.4
21.7
20.1
19.9
18.9
18.5
29.3
27.1
25.1
24.9
23.5
22.9
33.4
30.9
28.7
28.4
26.9
26.4
SHC
12.1
13.4
14.4
12.9
12.4
12.0
13.5
15.4
17.0
14.9
14.5
14.0
18.1
20.3
22.2
19.6
18.9
18.2
19.3
21.9
24.2
21.3
20.6
19.9
TPC
2.15
2.07
2.01
2.00
1.96
1.94
2.84
2.73
2.65
2.64
2.58
2.56
3.75
3.61
3.50
3.49
3.43
3.41
4.13
3.98
3.86
3.85
3.76
3.73
IWB
(˚F)
DB 75¡F (50%RH) DB 72¡F (50%RH) DB 70¡F (50%RH)
DB 75¡F (50%RH) DB 72¡F (50%RH) DB 70¡F (50%RH)
DB 75¡F (50%RH) DB 72¡F (50%RH) DB 70¡F (50%RH)
DB 75¡F (50%RH) DB 72¡F (50%RH) DB 70¡F (50%RH)
75 85 95 105 115
710
0.16
Airflow (
CFM
)
B.F
PKH24FK
710
0.16
PKH30FK
990
0.15
PKH36FK
990
0.14
Notes 1. B.F. : Bypass Factor, IWB : Intake air wet-bulb temperature TC : Total Capacity (x10
3
Btu/h), SHC : Sensible Heat Capacity (x10
3
Btu/h)
TPC : Total Power Consumption (kW)
2. SHC is based on 80˚FDB of indoor intake air temperature.
3. Cooling capacity correction factors and Refrigerant piping length (one way) range.
MODEL
Refrigerant piping length (one way)
PKH18FK PKH24FK PKH30FK PKH36FK
1.0
1.0
1.0
1.0
25ft
0.992
0.981
0.981
0.981
40ft
0.983
0.968
0.968
0.968
55ft
0.978
0.952
0.952
0.952
70ft
0.966
0.940
0.940
0.940
85ft
0.959
0.925
0.925
0.925
100ft
0.950
0.913
0.913
0.913
115ft
0.945
0.900
0.900
0.900
130ft
0.886
0.886
0.886
150ft
0.874
0.874
0.874
164ft
3
DATA
MODELS : PKH18/24/30/36FK
1. PERFORMANS DATA
1) COOLING CAPACITY
6
2) HEATING CAPACITY
Models Outdoor intake air WB temperature(˚F
Models
PKH18FK
PKH24FK
PKH30FK
PKH36FK
Notes 1. IDB : Intake air dry-bulb temperature CA : Capacity (x10
2. When booster heater is "on", total capacity and total power consnmption should be added the figures described in booster heater colnmn.
•Booster heater ON : When the set temperature is higher than the room temperature by more than 5.4 deg.
•Booster heater OFF : When the set temperature is higher than the room temperature by less than 3.6 deg.
3. Heating capacity correction factors.
Airflow (CFM)
710
710
990
990
IWB (˚F)
75 70 65 75 70 65 75 70 65 75 70 65
3
Btu/h), PC : Power Consumption (kW)
15 25 35 45 55 65
CA
PC
CA
PC
CA
PC
CA
PC
CA
12.1
1.20
14.1
1.34
16.3
1.49
18.7
1.65
21.4
12.4
1.16
14.4
1.29
16.7
1.44
19.1
1.59
21.8
12.7
1.11
14.7
1.24
17.0
1.38
19.5
1.53
22.2
16.3
1.82
18.9
2.03
21.9
2.27
25.2
2.51
28.8
16.6
1.76
19.4
1.96
22.4
2.19
25.7
2.42
29.3
17.0
1.69
19.8
1.89
22.9
2.10
26.2
2.32
29.9
21.5
2.32
25.0
2.59
28.9
2.89
33.2
3.20
38.0
21.9
2.24
25.5
2.50
29.6
2.78
33.9
3.08
38.6
22.5
2.15
26.1
2.40
30.2
2.68
34.6
2.96
39.4
24.7
2.71
28.7
3.04
33.3
3.39
38.2
3.75
43.7
25.3
2.62
29.4
2.93
34.1
3.26
39.0
3.61
44.5
25.9
2.53
30.1
2.82
34.8
3.14
39.9
3.47
45.4
)
PC
1.83
1.76
1.69
2.77
2.67
2.56
3.53
3.40
3.26
4.14
3.98
3.83
CA
23.7
24.1
24.5
32.8
33.3
33.9
43.2
43.7
44.6
49.6
50.4
51.3
PC
1.99
1.91
1.83
3.01
2.90
2.78
3.86
3.72
3.56
4.49
4.28
4.14
Auxiliary heater
208V 230V
CA
PC
5.5
1.6
6.5
1.9
5.5
1.6
6.5
1.9
6.1
1.8
7.5
2.2
6.1
1.8
7.5
2.2
Models
PKH18FK PKH24FK PKH30FK PKH36FK
Less than 100ft
1.00
1.00
1.00
1.00
Refrigerant piping length (one way)
100~130ft
0.995
0.995
0.995
0.995
130~164ft
0.990
0.990
0.990
0.990
7
2. PERFORMANCE CURVE
Does not include booster heater (1.9kW)
Total power consumption (kW) Total capacity (x10
3
Btu/h)
30
24
18
12
2.5
2.0
1.5
1.0
15 25 35 45 55 65
Total power consumption (kW) Total capacity (x10
3
Btu/h)
Outdoor intake air DB temperature ( F) Outdoor intake air WB temperature ( F)
Indoor intake air DB temperature ( F)
Indoor intake air DB temperature ( F)
65
65
70
70
75
75
30
24
18
12
2.5
2.0
1.5
1.0
63
67
71
63
67
71
SHF=0.82
PKH18FK COOLING CAPACITY
023 32 35
45 55
65
(67)
75 85 95 105 115
Indoor intake air WB temperature ( F)
Indoor intake air WB temperature ( F)
NOTES : Apoint on the curve shows the reference point.
PKH18FK COOLING CAPACITY PKH18FK HEATING CAPACITY
36
Btu/h)
3
30
24
18
12
3.0
2.5
2.0
1.5
Total power consumption (kW) Total capacity (x10
023 32 35
8
PKH24FK COOLING CAPACITY PKH24FK HEATING CAPACITY
SHF=0.71V
Indoor intake air WB temperature ( F)
71 67 63
35
Btu/h)
3
Indoor intake air DB temperature ( F)
30
24
18
Does not include booster heater (1.9kW)
12
71 67 63
Indoor intake air WB temperature ( F)
45 55
Outdoor intake air DB temperature ( F)
(67)
65
75 85 95 105 115
3.0
2.5
2.0
1.5
Total power consumption (kW) Total capacity (x10
15 25 35 45 55 65
Indoor intake air DB temperature ( F)
Outdoor intake air WB temperature ( F)
65 70 75
75 70 65
NOTES : Apoint on the curve shows the reference point.
71 67 63
71 67 63
42
36
30
24
4.0
3.5
3.0
2.5
2.0
SHF=0.75
Total capacity(x10 Btu/h)
3
Total power consumption(kW)
Outdoor intake air DB temperature(¡F)
0 23 32 35 45 55 65 (67) 75 85 95 105 115
indoor intake air WB temperature(¡F)
indoor intake air WB temperature(¡F)
48 42 36 30 24 18
4.0
3.5
3.0
2.5
2.0
1.5 15 25 35 45 55 65
Outdoor intake air WB temperature(¡F)
indoor intake air DB temperature(¡F)
indoor intake air DB temperature(¡F)
Does not include booster heater(2.2kW)
65 70 75
75 70 65
Total capacity(x10 Btu/h)
3
Total power consumption(kW)
42
36
30
24
4.5
4.0
3.5
3.0
2.5
Total capacity(x10 Btu/h)
3
indoor intake air WB temperature(¡F)
SHF=0.71
Total power consumption(kW)
Outdoor intake air DB temperature(¡F)
indoor intake air WB temperature(¡F)
0 23 32 35 45 55 65 (67) 75 85 95 105 115
71 67 63
71 67 63
54
48
32
36
30
24
4.5
4.0
3.5
3.0
2.5
2.0 15 25 35 45 55 65
Outdoor intake air WB temperature(¡F)
indoor intake air DB temperature(¡F)
indoor intake air DB temperature(¡F)
Does not include booster heater(2.2kW)
65 70 75
75 70 65
Total capacity(x10 Btu/h)
3
Total power consumption(kW)
PKH30FK COOLING CAPACITY PKH30FK HEATING CAPACITY
PKH36FK COOLING CAPACITY PKH36FK HEATING CAPACITY
9
3. CONDENSING PRESSURE AND SUCTION PRESSURE
350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150
(psi.G)
Condensing pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
Indoor DB
temperature( F)
86 80 75 70
100
90 80 70 60 50 40 30 20
(psi.G)
Suction pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
86 80 75 70
Indoor DB temperature( F)
350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150
(psi.G)
Condensing pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
80 70 60 50 40 30 20 10
(psi.G)
Suction pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
Data is based on the condition of indoor humidity 50%. Air flow should be set at HI. A point on the curve shows the reference point.
<Cooling mode>
PKH18FK PKH18FK
Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point.
<Heating mode>
PKH18FK PKH18FK
10
Data is based on the condition of indoor humidity 50%.
360 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160
(psi.G)
Condensing pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
Indoor DB
temperature( F)
86 80 75 70
100
90 80 70 60 50 40 30 20
(psi.G)
Suction pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
86 80 75 70
Indoor DB temperature( F)
350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150
(psi.G)
Condensing pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
80 70 60 50 40 30 20 10
(psi.G)
Suction pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
Air flow should be set at HI. A point on the curve shows the reference point.
<Cooling mode>
PKH24FK PKH24FK
Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point.
<Heating mode>
PKH24FK PKH24FK
11
Data is based on the condition of indoor humidity 50%.
350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150
(psi.G)
Condensing pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
86 80 75 70
110 100
90 80 70 60 50 40 30
(psi.G)
Suction pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
86 80 75 70
Indoor DB temperature( F)
Indoor DB temperature( F)
340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150 140
(psi.G)
Condensing pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
80 70 60 50 40 30 20 10
(psi.G)
Suction pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
Air flow should be set at HI. A point on the curve shows the reference point.
<Cooling mode>
PKH30FK PKH30FK
Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point.
<Heating mode>
PKH30FK PKH30FK
12
Data is based on the condition of indoor humidity 50%.
350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190 180 170 160 150
(psi.G)
Condensing pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
86 80 75 70
90 80 70 60 50 40 30 20
(psi.G)
Suction pressure
30 40 50 60 70 80 90 100 110
Outdoor ambient temperature
DB( F)
86 80 75 70
Indoor DB temperature( F)
Indoor DB temperature( F)
390 380 370 360 350 340 330 320 310 300 290 280 270 260 250 240 230 220 210 200 190
(psi.G)
Condensing pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
80 70 60 50 40 30 20 10
(psi.G)
Suction pressure
30 3520 25 45 55 6540 50 60 70
Outdoor ambient temperature
DB( F)
75 70 65
Indoor DB temperature( F)
Air flow should be set at HI. A point on the curve shows the reference point.
<Cooling mode>
PKH36FK PKH36FK
Data is based on the condition of outdoor humidity 75%. A point on the curve shows the reference point.
<Heating mode>
PKH36FK PKH36FK
13
4. STANDARD OPERATION DATA
Models
Item
Electrical circuitRefrigerant circuitIndoor sideOutdoor side
Voltage Frequency Total input Indoor fan current Booster heater current Outdoor fan current Comp. current Condensing pressure Suction pressure Discharge temperature Condensing temperature Suction temperature Comp.shell bottom temperature Ref. pipe length Refrigerant charge
Fan speed Airflow (High)
Fan speed upper/lower Airflow
Unit
V
Hz
kW
A A A
A psi.G psi.G
˚F ˚F ˚F ˚F
ft
˚F ˚F ˚F
˚F r.p.m. CFM
˚F
˚F r.p.m. CFM Btu/h
208/230
1.79
0.5
0.75
7.4/6.9 255
81 182 118
66 171
80
67
61
59
95
75
18,000
0.82
60
Cooling
208/230
1.56
0.5
7.6/8.4
0.75
6.1/5.9 202
61 126 102
34
111
70
60
96
68
47
43
18,600
Heating
PKH18FK
208/230
2.36
0.5
0.65+0.65
9.3/8.7 240
75
158
115
46
141
80 67 58 56
95 75
24,000
0.71
60
Cooling
208/230
2.37
0.5
7.6/8.4
0.65+0.65
9.5/8.7 243
63 149 115
35 126
70
60 105
70
47
43
25,000
Heating
PKH24FK
208/230
3.12
0.5
0.75+0.75
12.6/11.8 245
80 158 115
49 138
80
67
59
58
95
75
30,000
0.75
60
Cooling
208/230
3.02
0.5
7.6/8.4
0.75+0.75
12.2/11.4 236
60 159 113
32 130
70
60 103
70
47
43
33,000
Heating
PKH30FK
208/230
3.44
0.5
0.75+0.75
14.3/13.2 243
74 160 115
45 142
80
67
58
56
95
75
34,100
0.71
60
5 lbs 8 oz
1,490
710
1,490
710
1,490
990
1,490
990
790
1,590
750/750
3,170
760/760
3,350
760/760
3,350
25
9 lbs 15 oz
25
10 lbs 2 oz
25
10 lbs 9 oz
Cooling
208/230
3.54
0.5
8.7/9.6
0.75+0.75
14.7/13.7 263
60 170 120
33 148
70
60 109
71
47
43
38,000
Heating
PKH36FK
Intake air temperature
Discharge air temperature
Intake air temperature
Capacity SHF
DB
WB
DB
WB
DB
WB
14
5. OPERATING RANGE
1) POWER SUPPLY
1 Phase 60Hz 208/230V Guaranteed voltage range
2) OPERATION
Min. Max. 198V 208V 230V 253V
Function
Cooling
Heating
Air intake temperature
Condition
Standard temperature Maximum temperature MInimum temperature Maximum humidity Standard temperature Maximum temperature MInimum temperature
DB(˚F
80 95 67 80 70 80 70
Indoor
)
6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
PKH18FK PKH24FK PKH30FK PKH36FK
Airflow (
CFM
710 710 990 990
)
Air speed
(
ft/sec
16.1
16.1
17.7
17.7
)
Coverage
range(ft
41 41 50 50
)
Outdoor
WB(˚F
67 71 57 75 60 67 60
)
DB(˚F
95
115
23 80 47 75 17
)
WB(˚F
75 — — 75 43 65 15
)
The air coverage range is the value up to the position where the air speed is 0.8ft/sec. when air is blown out horizontally from the unit at the High notch position. The coverage range should be used only as a general guideline since it varies according to the size of the room and furniture installed inside the room.
7. ADDITIONAL REFRIGERANT CHARGE (R-22(oz))
Refrigerant piping length (one way)
55ft
70ft
85ft
0
0
0
0
0
0
0
0
0
0
0
0
100ft
0 0 0 0
Model
PKH18FK PKH24FK PKH30FK PKH36FK
Outdoor unit
precharged
(
up to 100ft
5 lbs 8 oz 9 lbs 15 oz 10 lbs 2 oz 10 lbs 9 oz
)
25ft
40ft
0
0
0
0
0
0
0
0
115ft
2 2 5 5
130ft
4
4 10 10
150ft
7 16 16
164ft
9 20 20
15
9-1/4
1-25/32
9-1/4
1-25/32
9-1/4 9-1/4
1-25/32
1/2
13-3/8
7-3/4
Top
Front
Right side
Left side
55-1/8
42-15/16
Air intake
9-1/4
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose
Bolt
Gas pipe
19/32
Terminal block for power supply
Terminal block for control
Terminal block for remote controller
(Liquid pipe)
Liquid pipe
Gas pipe
Liquid pipe
A
1-3/16
1-15/32
1-17/32
3-27/32 2-9/16
2-29/32
5/32
3-15/16
1-17/32
1-3/16
1-15/32
2-29/32
5/32
1-5/32
11-1/32
1-3/16
7-1/4
1-3/16
3-5/32
1-3/18
2-3/8
13/32
1-17/32
1-15/32
2-9/16
3-15/16
A
B
C
Knock out hole for piping
31/32
43-11/16
7-7/32
9-7/16
B
55-1/8
20-9/16
4-23/32
2-5/32
4-1/32
4-3/8
Air outlet
20-9/16
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
Hole for
tapping screw
66-{1/4 hole for
tapping screw
Wall fixture
Unit center
32-{15/32
hole for bolt
23/32
3-19/32
35-7/16
38-31/32
17-29/32
11-7/32
9-21/32
3/4
9-7/16 11-1/32 12-3/8
24
Drainage range
on left-hand side
Drainage range
on right-hand side
10x3-19/32=(35-13/16)
7-3/32
2-15/32
8-27/32
7-17/32
23/32
4
OUTLINES AND DIMENSIONS
4.1. Indoor Unit PKH18/24FK
Unit : mm
16
PKH 30/36FK
Unit : mm(inch)
3/4F
Through hole
Liquid pipe 1/2F
Gas pipe
1
2
C
3-1/2 3-1/2~ 4
Sleeve >< 1
>< 1 Sleeves are availaable
on the market.
2-15/32
1/2
9-1/4
1-25/32
9-1/4
Right side
for right piping
Knock out hole
7-3/4
19/32
Bolt
or less
2
2-9/32
1-21/32
4-3/8
4-1/32
2-5/32(Gas pipe)
4-23/32(Liquid pipe)
7-7/32
B
9-7/16
1
9-1/4
1-25/32
Front
66-5/32
Top
9-1/4
1-25/32
9-1/4
1-25/32
9-1/4
53-15/16 Alr Intake
13-3/8
Terminal block for control
Terminal block for powar supply
Terminal block for remote controller
Drain hose
43-11/16 (Drain hose)
Lower side
55-1/8
27-5/16 Air outlet 27-5/16 Air outlet
louvers(manual)
left-hand piping)
Under panel (Removable at
11-1/32
1-5/32
3-5/32
1-3/16
1-3/16 7-1/4 13/32
Knock out hole for under-piping
Refrigerant pipe .Drain pipe
Auto vanes
2-3/8
1-3/16
7-17/32
12- 1/4 hole
for tapping screwRear piping hole
Front
or more 1-3/16
Knock out hole
3-15/16
for left piping
5/32
1-17/32
1-15/32
2-29/32
2-9/16
5-/15/16 or less
Left side
Air
outlet
Air
intake
10 or more
A
C
1-3/161-3/16
1-15/32
2-9/163-27/32
31/32
Drain hose for
B
2 or more 10 or more
Knock out hole for wiring
A
1-17/32 3-15/16
1-15/32
1-17/32
2-29/32
5/32
9-21/32
Drainage range on
right-hand side
left-handside piping
50
Unit center
Unit out line
Drainage range on
Left hand side
23-7/16
13x3-19/32=(7-3/16) 11-7/32
Wall fixture
3/4
3-19/32
35-7/16
23/32
23/32
84- 1/4 hole
for tapping
screw
29-17/32
9-7/16 7-3/328-27/32 11-1/32 12-3/8
Range for left
11-5/8
rear piping hole
41- 15/32 hole
for bolt
Range for left rear piping hole
17
4.2. Outdoor Unit PUH18EK
Terminal block for indoor and outdoor unit connection
Terminal block for power line
Ground
terminal
Handie for moving
Service panel
Refrigerant pipe
(Flared) 5/8
Knock out hole
for front piping
4-3/4
(refrigerant. drainage
and wiring)
4-1/8
Drain hole
Drain hole
2-U-shaped
notched
holes
1-5/8
1-3/4
1/5/16
Bottom piping hole
2-9/16
3-1/8
R13/16
Front right piping holes-
detail figures
Standard bolt length
1 max.
1/2
1/2x7/8 Oval hoies
(standard bolt W3/8(M10)
Knock out hole for
right piping
(refrigerant. drainage
and wiring)
15-7/8
7-1/18 20-5/18
17-3/18
1
2
13-7/4
13-7/8
21-3/4
2-3/820-5/81-9/16
33-9/16
34-1/4
11-7/8
7-9/32 7-9/32
Front opening
Service space
(for N.E.C)
1/2
36
36
4
Note:Allow adequate
upper clearance.
1/2
8
1/2
1-9/161-1/16
13
14-1/4
11/169/16
19-11/16
Refrigerant pipe
(Flared) 3/8
Outlet guide
installation hole
1
40
1/2
Outdoor Unit-Necessary surrouding clearance
(Concentrated installation)
The upper side must be open.
4
8
For 10 units or less
11-5/8
Side air intake
Handle for
moving
Rear fresh
air intake
Rear piping hole
Handle for moving
3-3/4
5-7/16
2-3/8
Knock out holes for
power line 1-1/16
1-3/4
2-1/16
Air intake
Air intake
Air outlet
11/16
R1/4
R13/16
Unit : mm
18
Outdoor Unit PUH24EK
Terminal block for
indoor and outdoor
unit connection
Terminal block for power line
Ground
terminal
Handie
for moving
Service panel
Refrigerant pipe
(Flared) 5/8F
Knock out hole
for front piping
4-3/4
(refrigerant. drainage
and wiring)
4-1/8
Drain hole
Drain hole
2-U-shaped
notched
holes
2-1/16
2-1/4
1/9/16
Bottom
piping hole
2-9/16
3-1/8
R13/16
Front right piping holes-
detail figures
Standard bolt length
1 max.
1/2
2-1/2x7/8 Oval hoies
(standard bolt M10)W3/8(M10)
Knock out hole
for right piping
(refrigerant.
drainage and wiring)
3-1/4
20-5/8 20-5/82-3/8
13-9/16 23-1/16
1
2
15-1/16
37-34
2-3/820-5/81-9/16
49-1/2
34-1/4
11-7/8
7-9/32 7-9/32
Front opening
Service space
(for N.E.C)
3/8
36
36
4
Note:Allow adequate
upper clearance.
Outdoor Unit - necessary surrounding clearance
1/2
12
1/2
1-9/161-1/16
13
14-1/4
11/169/16
19-11/16
Refrigerant pipe
(Flared) 3/8F
Outlet guide
installation hole
1
40
1/2
Outdoor Unit-Necessary surrouding clearance
(Concentrated installation)
The upper side must be open.
6
12
For 10 units or less
11-5/81/4
Side air intake
Handle
formoving
Rear fresh
air intake
Rear piping hole
Handle for moving
3-3/4
5-7/16
2-3/8
Knock out holes for
power line 1-1/16
1-3/4
2-1/16
Air intake
Air intake
Air outlet
11/16
R1/4
R13/16
15-7/8
Unit : mm
19
Outdoor Unit PUH30/36EK
Unit : mm
12
Outdoor Unit - necessary surrounding clearance
6
upper clearance.
Note:Allow adequate
1/2
Front opening
1/2
11/169/16
Air intake
23-5/8
7-9/32 7-9/32
36
1/2
Terminal block for
16-1/4
14-31/32
1-9/16 1-1/16
Air intake
Service space
indoor and outdoor
Air outlet
(for N.E.C)
36
unit connection
Terminal block for power line
38-3/16
13-7/8
Service panel
Ground
Handie
terminal
49-1/2
for moving
Refrigerant pipe
(Flared)
(PUH30/36EK) 3/4
(PUH42EK)7/8F
37-3/4
20-5/8 20-5/82-3/8
1-3/4
Refrigerant pipe
(Flared) 3/8F
15-7/8
15-1/16
3-1/4
13-9/16 23-1/16
2-1/16
Knock out holes for
power line 1-1/16
4-3/4
2-3/8
Knock out hole
for front piping
(refrigerant. drainage
and wiring)
2-3/820-5/81-9/16
1/9/16
4-1/8
2-1/2x7/8 Oval hoies
(standard bolt W3/8(M10)
R13/16
Knock out hole
for right piping
(refrigerant.
2-1/4 2-1/16
Bottom
Drain hole
Standard bolt length
1 max.
3-1/8
R13/16
drainage and wiring)
R1/4
piping hole
2-U-shaped
notched
holes
Drain hole
2-9/16
Front right piping holes-
detail figures
11/16
1/2
20
12
40
The upper side must be open.
For 10 units or less
1/2
Outdoor Unit-Necessary surrouding clearance
(Concentrated installation)
6
Outlet guide
installation hole
1
13-9/161/4
Side air intake
Handle
formoving
Handle for moving
Rear fresh
air intake
1-5/16
7/8
Rear piping hole
3-3/4
5-7/16
Remote controller (PKH series)
2-3/4
CENTRALLY CONTROLLED STAND BY DEFROST
AUTO DRY
HEAT COOL
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
LOW HIGH
F
ON
AIR SWEEP
HEAT AUTO COOL/DR Y
F
SET
TEMPERATURE
TIMER MODE HOURS
HR
FAN SPEED LOW/HIGH
AIR DISCHARGE
3-5/8 3-5/8 5/8
ON/OFFPOWER
WARMER COOLER\
4-3/4
4-1/4
UP/DOWN SWING/STOP
Unit : mm
A
3-9/32
CHECK TEST RUN
CHECK TEST RUN
4-3/4 4-3/4
1/2
5/32
Rear side wiring arrangement opening
Side wiring arrangement opening
5/16
Fixing holes
3/16
3/8
1/2
1/4
2
VIEW A
21
5
WIRING DIAGRAM
MODELS PKH18/24/30/36FK
MF
C
I.B
RED
WHT
BLK
FAN1
X4
X4
SW2
ON OFF
123456
POWER SUPPLY ~(1 PHASE) AC208/230V 60Hz
SYMBOL
C
FAN MOTOR CAPACITOR CN1<R.B> PROGRAM TIMER CONNECTOR CN2<R.B> REMOTE SWITCH CONNECTOR CN21<I.B> LOSSNAY CONNECTOR CN27<I.B> DRAIN LIFT-UP MECHANISM CONNECTOR CN51<I.B> CENTRALLY CONTROL CONNECTOR F1,2<I.B> FUSE (6A250V) FS1,2 THERMAL FUSE <243°F / 18, 24FK : 10A. 30.36FK : 16A> H HEATER I.B INDOOR CONTROLLER BOARD J1 MODE SELECTOR JUMPER RESISTORS J5 MODE SELECTOR JUMPER RESISTORS J9 MODE SELECTOR JUMPER RESISTORS LCD<R.B> LIQUID CRYSTALDISPLAY LED1<I.B> LED (DC 12V POWER) LED2<I.B> LED (DC 5V POWER) MF FAN MOTOR MV VANE MOTOR
L1 L2
GR
WIRING DIAGRAM
RED
BLE
WHT
F1
SW3SW7
ON OFF
12
J1J9J5
456789
88H
563
4
YLW YLW
LED1 12V POWER
REDRED BLU
ZNR
CN27
D.U.M
CND
POWER
SW6
12342 4
TB2
NAME
F2
1234
RED BLU
GRN/YLWGROUND
230V 208V
RED
CNT
TRANS
LED2 5V POWER
HEATER
CN24
L1
POWER SUPPLY ~(1 PHASE)
L2
AC208/230V 60Hz
TB2
MODELS
TB5
BLU 2 BLU 1
TB4
BRN 3 ORN 2 YLW
RT2
RT1
5 6
78
GR
GROUND
18.24FK 30.36FK
ON
SW7
OFF
1234
TRANSMISSON WIRES DC12V
TO OUTDOOR UNIT CONNECTING WIRES-POLAR DC12V
1
R.B
1 2 3
CN2
LCD
CN1
1 2 3 4 5 6
GRY
26H
GRY
ON OFF
1234
TB6
SW17
09876542321
NAME
1 2
OFF ON
661
CNGV
VANE
CENTRALLY
CONTROL
DRAIN
CN50
FS2HFS1
T
POWER
CN51
10VAC
14.3VAC
RED
4 3 2 1
4 3 2 1
REMOCON
CN40
5 4 3 2 1
INTAKE
CN24
HEATER
RT1
RT2
RED
BRN
PEMOCON
CN21
PIPE
CN20
SYMBOL
GRN/YLW
MV
BRN
CN4T
TRANS
TO
CN22 CN30
OUTDOOR
3 2 12 1
2 1 2 1
LOSSNAY
CN21
I.B
88H
BWN YLW
1 2
ROOM TEMP. THERMISTOR (32°F / 15K, 77°F / 5.4KDETECT)
INDOOR COIL THERMISTOR
(32°F / 15K, 77°F / 5.4KDETECT) SW2<I.B> ADDRESS SELECTOR SW3<I.B> EMERGENCY OPERATION SW6<I.B> MODEL SELECTOR SW7<I.B> MODEL SELECTOR SW17<I.B> ADDRESS SELECTOR T TRANSFORMER TB2 POWER TERMINAL BLOCK TB4 INDOOR / OUTDOOR CONNECTING LINE TERMINAL BLOCK TB5 REMOTE CONTROLLER TERMINAL BLOCK TB6 TRANSMISSION LINE X4<I.B> FAN MOTOR RELAY ZNR VARISTOR 26H HEATER THERMALSWITCH 88H HEATER CONTACTOR
R.B REMOTE CONTROLLER BOARD
NOTES :
1. Since the indoor fan motor (MF) is connected with 230V power, using 208V power will require a setting change of the dip switch (SW7<I.B>) on the indoor con­troller board as shown in fig :
fig w1
Indoor fan motor (MF) for 208V.
2. Since the indoor transformer (T) is connected with 230V power if 208V power is used. Change the wiring connection showing fig : w 2.
fig w2
When power supply is
w 1.
230V
SW7
ON OFF
1
2 3 4
240V 208V
ON OFF
YELLOW REDYELLOW
1
2 3 4
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are,
6. Emergency operation
¤¤ : Connector, / : Terminal block.
If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor con­troller board.
[Check items] (1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code "P8" will be displayed on the remote controller and the trouble position will be shown on the outdoor controller board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure] (1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating. (2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker. (3)During emergency operation indoor fan runs at high speed but automatic vane remains stopped.
If the air outlet is blocked up with the vane, Open it with your hands.
(4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time. (5)Emergency cooling should be limited to 10 hours maximum. (The indoor unit heat exchanger may freeze). (6)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
22
BG79N687H01
MODELS PUH18EK
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
O.B
SW1 SW2 SW3
OFF ON
2 1
CN2
RT
LED
1 2 3
TB3
YLW ORN BRN
FROM INDOOR UNIT CONNECTING WIRES
12V DC (polar)
L1 L2 GR
GRN
TB1 POWER SUPPLY 1{ 208/230V 60Hz
3 2 1
CN3
CN4T
4 3 2 1
CN4
4 3 2 1
BRN 12.3V AC
RED 12.3V AC
MF
BLU
BLU
WHT
BLU
WHT
WHT
RED
RED
ORN ORN
C1
MF2
MF1
FC
26C
63H2
63H1
63H1
51CM
5
BRN
BRN
YLW
YLW
YLW
YLW
RED
RED
BLU
63H2
MC
R
C
C
S
2 1
51C
52C
BLU
BLU
WHT
RED
WHT
UR
T W
RED
RED
RED
ORN
BLK
BLK
T
208V
230V
21R
RED
RED
RED
RED
SV
WHT
WHT
TRF
21 S4
BLK
BLK
BLK
BLK
21S4
52C
GRY
GRY
GRY
GRY
52C
WHT
WHT
CH ZNR
R/1
S/2
T/3
BLU BLU
F
HC
WHT WHT
4
S
A
B
X11X12X13X14
X14
X13 X12 X11
4 3 2 1
C C1 F<O.B> FC<O.B> HC LD1~LD8 MC MF O.B
COMPRESSOR CAPACITOR FAN CAPACITOR FUSE<6A> FAN CONTROLLER CRANKCASE HEATER LED<CHECK,SERVICE> COMPRESSOR FAN MOTOR<INNER THERMOSTAT> OUTDOOR CONTROLLER BOARD
WIRING DIAGRAM
RT
SW1•2•3<0.B> T TB1,3 X11<O.B> X12<O.B> X13<O.B>
OUTDOOR COIL THERMSTOR <32˚F/15k,77˚F/5.4k> SELECTOR<CHECK,SERVICE> TRANSFORMER TERMINAL BLOCK CRANKCASE HEATER RELAY COMPRESSOR RELAY R.V RELAY
X14<O.B> ZNR<O.B> 21R 21S4 51C 52C 63H1 63H2
BYPASS VALVE RELAY VARISTOR BYPASS VALVE COIL R.V COIL OVERCURRENT RELAY CONTACTOR
CONTROL HIGH PRESSURE SWITCH
PROTECT HIGH PRESSURE SWITCH
SW3
How to use SW1 and 2
Pressing erases the past check contents
SW1
loaded on the microcomputer.
The output display (light) remains during opera­tion but pressing displays the past check
SW2
contents in flashing mode. Pressing the switch again retums to output display (light).
White connector
When Power Supply is 208V
w
RED WHITE
ORANGE
208V 230V
Main function of LED(when both Nos.1 and 2 of are "OFF")
LED NO. Output display (light) Check display (flash)
LD1 Compressor indoor command — LD2 Heating indoor command — LD3 63H1 ON RT short/open LD4 Compressor ON 63H2 funcitons LD5 Outdoor fan ON — LD6 R.V.coil ON — LD7 Bypass valve ON RT overheat protection LD8 Crankcase heater ON Defective input
NOTES : 1. If the operation stops to function of the protection device, the check display flashes.
CAUTION FOR SERVICING
The connector marked The compressor stops by disconnecting the white connector as shown at the right.
CAUTIONS FOR POWER SUPPLY WIRING
2. Symbols used in wiring diagram above are. / :Terminal block, ¤¤¤ :Connector, ¤ :PC board insertion tab.
Since LD8 lights when normal power is turned "ON", check the power supply with the "ON" or "OFF" LD8.
w Since the indoor transformer (T) is connected with 230V power, if 208V power is used,
change the wiring connection as shown in the right figure.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
s
¤— is to turn the compressor ON-OFF during servicing.
23
MODELS PUH24/30/36EK
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
O.B
SW1 SW2 SW3
OFF ON
2 1
CN2
RT
LED
1 2 3
TB3
YLW ORN BRN
FROM INDOOR UNIT CONNECTING WIRES
12V DC (poler)
L1 L2 GR
GRN
TB1 POWER SUPPLY 1[ 208/230V 60Hz
3 2 1
CN3
CN4T
4 3 2 1
CN4
4 3 2 1
BRN 12.3V AC
RED 12.3V AC
MF1
BLU
BLU
WHT
WHT
BLU WHT
RED
RED
ORN ORN
C1
MF2
YLW YLW
BLU
WHT
BRN
WHT WHT
BRN
BLU BLU
C1
MF2
MF1
FC
26C
63H2
63H1
63H1
51CM
5
BRN
BRN
YLW
YLW
YLW
YLW
RED
RED
BLU
63H2
MC
R
C
C
S
52C
BLU
BLU
WHT
RED
WHT
UR
T W
RED
RED
RED
ORN
BLK
BLK
T
208V
230V
21R
RED
RED
RED
RED
SV
WHT
WHT
TRF
21 S4
BLK
BLK
BLK
BLK
21S4
52C
GRY
GRY
GRY
GRY
52C
WHT
WHT
CH ZNR
R/1
S/2
T/3
BLU BLU
F
HC
WHT WHT
4
S
A
B
X11X12X13X14
X14
X13 X12 X11
4 3 2 1
1 2 3 4
C C1,2 C5 F<O.B> FC<O.B> HC LD1~LD8 MC MF1,2
COMPRESSOR CAPACITOR FAN CAPACITOR COMPRESSOR STARTCAPACITOR FUSE<6A> FAN CONTROLLER CRANKCASE HEATER LED<CHECK,SERVICE> COMPRESSOR<INNER THERMOSTAT> FAN MOTOR<INNER THERMOSTAT>
WIRING DIAGRAM
O.B R
RT SW1•2•3<O.B>
T TB1,3 X11<O.B> X12<O.B>
OUTDOOR CONTROLLER BOARD
RESISTOR OUTDOOR COIL THERMISTOR <32˚F/15k, 77˚F/5.4k> SELECTOR<CHECK,SERVICE> TRANSFORMER TERMINAL BLOCK CRANKCASE HEATER RELAY COMPRESSOR RELAY
X13<O.B> X14<O.B> ZNR<O.B> 19 21R 21S4 52C 63H1 63H2
R.V RELAY BYPASS VALVE RELAY VARISTOR COMPRESSOR STARTRELAY BYPASS VALVE COIL R.V COIL CONTACTOR CONTROL HIGH PRESSURE SWITCH PROTECT HIGH PRESSURE SWITCH
NOTES : Symbols used in wiring diagram above are. / :Terminal block, ¤¤¤ :Connector, ¤ :PC board insertion tab.
s
White connector
w
When Power Supply is 208V
RED WHITE
ORANGE
208V 230V
CAUTION FOR SERVICING
The connector marked The compressor stops by disconnecting the white connector as shown at the right.
CAUTION FOR POWER SUPPLY WIRING
Since LD8 lights when normal power is turned "ON", check the power supply with the "ON" or "OFF" LD8.
w Since the indoor transformer (T) is connected with 230V power, if 208V power is used,
change the wiring connection as shown in the right figure.
¤— is to turn the compressor ON-OFF during servicing.
CAUTION FOR INDOOR AND OUTDOOR CONNECTING WIRES
Since the indoor and outdoor connecting wires has polarity, make sure to connect the same terminal numbers (1,2,3) for indoor and outdoor units.
24
6
Indoor unit Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
Outdoor unit
Indoor coil thermistor RT2
Distributor
Restrictor valve
Capillary tube
({0.126x{0.071x15.7)
({0.126x{0.071x9.8)
PKH30FK({0.157x{0.079x11.4) PKH36FK({0.157x{0.079x11.4)
Capillary tubesize:(ODxIDxLength) The symbol { indicates diameter.
Capillary tube ({0.157x{0.079 x33.5)
Refrigerant pipe (option) {3/8" (with heat insulator)
Refrigerant pipe (option) {5/8" (with heat insulator)
Ball valve (with service port)
Ball valve
Strainer
Strainer
Strainer
Flared connection
Accumulator
Muffler
Flexible tube
Compressor
Service port (check)
Service port (check)
Fusible plug
Bypass valve
Oil separator
4-way valve
Control high pressure switch
Protect high pressure switch
Outdoor coil thermistor RT
Restrictor valve
Indoor coil thermistor RT2
Distributor
Restrictor valve
Capillary tube
Capillary tube ({0.126x{0.063 x17.3)x2
Refrigerant pipe (option) {3/8" (with heat insulator)
Refrigerant pipe (option) {5/8" (with heat insulator)
Ball valve (with service port)
Ball valve
Strainer
Strainer
Strainer
Flared connection
Accumulator
Muffler
Flexible tube
Compressor
Service port (check)
Service port (check)
Fusible plug
Bypass valve
Oil separator
4-way valve
Control high pressure switch
Protect high pressure switch
Outdoor coil thermistor RT
Restrictor valve
Indoor coil thermistor RT2
Distributor
Restrictor valve
Capillary tube
Capillary tube PUH30EK ({0.157x{0.079 x23.6)x2 PUH36EK ({0.157x{0.079 x17.7)x2
Capillary tube
Refrigerant pipe (option) {1/2" (with heat insulator)
Refrigerant pipe (option) {3/4 (with heat insulator)
Ball valve (with service port)
Ball valve
Strainer
Strainer
Strainer
Flared connection
Accumulator
Muffler
Flexible tube
Compressor
Service port (check)
Service port (check)
Fusible plug
Bypass valve
Oil separator
4-way valve
Control high pressure switch
Protect high pressure switch
Outdoor coil thermistor RT
Restrictor valve
COOL HEAT
w
PKH18FK
REFRIGERANT SYSTEM DIAGRAM
PKH24FK
PKH-30/36FK
25
7 OPERATION FLOW-CHART
START
Power circuit
breaker
Check SW
ON twice
Operation SW
ON
“OFF” timer
“ON” timer
STOP
Set time complete
Set time complete
1
NO
NO
NO NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
w 1
w 2
w 3
w 4
w 5
w 7
w 6
PROTECTION DEVICE SELF HOLD RELEASE
Remote controller
indicator lamp OFF
Trouble STOP
Remote controller
operation display
Operating mode
(COOL)
Operating mode
(DRY)
Operating mode
(HEAT)
Operating mode
(FAN)
Auto COOL/HEAT
operation
COOL operation
DRY operation
HEAT operation
FAN operation
Trouble
PROTECTION DEVICE
SELF HOLD
Remote controller
trouble display
Indoor side
Outdoor side
Fan STOP
Auxiliary heater OFF
Compressor OFF
Fan STOP
Four-way valve OFF
MAIN OPERATION
w1 In addition, the centralized and remote control can be operated. w2 The modes which indicate the sources of trouble are listed below.
EO=Signal transmitting/receiving error
P1=Room temperature thermistor malfunction
P2=Indoor coil thermistor malfanction
P4=Drain sensor malfunction
P5=Drain over flow
P6=Coil frost/overheat protection
P7=System error
P8=Outdoor unit trouble
w3 The CHECK swich will show if an error has occurred in the past. w4 Fan runs on low speed for 1 minute in order to remove overheat air. w5 The 3-minute (6 minutes … heating mode) time-delay functions after compressor stops. w6 FAN or AUTO mode is selected by the indoor dipswitch setting. w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
26
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
NO
Vane setting notch
Initial
COOLING
w 8
w 9
YES
Vane intial
setting
Vane 60 deg downward angle 70 deg downward angle
YES
Fan speed
LOW
YES
Downward discharge
1 hour
YES
Vane horizontal
airflow
NO
Compressor
thermostat
ON
NO
Allowance
cancel
NO
YES
YES
NO
w 10
w 11
YES
3-minute
time delay
6-minute
time delay
3-minute
compressor opration
Coil frost
prevention
Cooling area
NO
NO
YES
NO
YES
NO
Aliowance
period
NO
6 minute time delay
Allowance set
YES
Coil frost protection
YES
10-minute
NO
compressor operation
Allowance cancel
NO
compressor operation
Compressor ON
YES
Coil frost
protection
NO
16-minute
YES
Indoor pipe
temperature is
34¡F or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
tempreature is
50¡F or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
YES
LOW
FAN speed LOW 5 min
elapse
NO
YES
Outdoor unit
trouble
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. IF opera-
tion changes during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON. w10After 3 minute compressor operation, if the indoor coil thermistor reads -59°F or below for 3 minutes, the com-
pressor will stop for 6 minutes.
w11Cooling area : Indoor coil temperature is more than 9 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 9 degrees below the room temperature. FAN area : Indoor coil temperature is within 9 degrees either way of the room temperature.
27
Loading...
+ 62 hidden pages