The PK series models have been downsized and now require such minimal wall space that they can even be installed
above windows. For the PKH18/24FK, 13in of wall space between the ceiling and the window allows “above window”
installation (14.5in for the PKH30/36FK)
2. A FURTHER REFINEMENT OF COMFORT WITH NOISE SUPPRESSION
Remarkably low-noise operation has been achieved through the development of a “near-silent” fan and a design which
minimizes airflow resistance.
3. AUTO FLAP SHUTTER
With a simple flick of the OFF switch the air outlet can be closed off with a shutter. The shutter also functions as a flap
during operation to adjust the air flow angle, with “Auto Angle 1” securing a comfortable air flow.
4. INSTALLATION : FAST AND ENDLESSLY ADAPTABLE
(1) External piping
An external piping connection of 24in and a very light body promote trouble-free installation for PKH18FK.
(2) Multi-directional piping
Multi directional drain and refrigerant piping rodically improves flexibility in selecting installation layouts. PKH18FK drain
piping can be installed in 5 directions, while PKH30/36FK models boast refrigerant piping in 4 directions and drain piping
in 2 directions.
(3) Back plate installation guide
The back plate installation guide gives clear instructions on installation positions. The enlarged back plate secures the
unit firmly to the wall, while the support piece which lifts the unit makes left side piping work much easier.
(4) Front power supply box
The front power supply box allows electrical wiring work to be performed easily even after the indoor unit has been fully
installed. All the screws for the indoor unit can be tightened from the front side thus ensuring smooth installation.
(only for PKH18/24FK)
(5) Easily removable filter
The presence of thumbscrews on the filters means that the filters can be quickly and smoothly removed.
(only for PKH30/36FK)
2
Page 3
5. ADVANCED MICROPROCESSOR
Indoor unitOutdoor unit
Indoor
heat
exchanger
4•way
valve
Accumulator
Compressor
Outdoor
heat
exchanger
Capillary tubes
for heating
Capillary
tubes for
cooling
Liquid section
of piping
HIgh-pressure
liquid
retrigerant
Restrictor
valve
Restrictor valve
Indoor unitOutdoor unit
Indoor
heat
exchanger
4•way
valve
Accumulator
Compressor
Outdoor
heat
exchanger
Capillary tubes
for cooling
Capillary
tubes for
heating
Liquid section
of piping
Low-pressure
two-phase
retrigerant
Restrictor
valve
Restrictor valve
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTOCOOL/DRY
COOLERWARMER
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECKTEST RUN
(1) Easy to Use Microprocessor
1) Ultra-Thin Remote Controller
The streamlined, square controller is designed to
blend with any kind of interior and the adoption of
a sophisticated microprocessor allows you to
carry out a wide range of operations easily.
2) Ultra-Thin Remote Controller
Units operation mode, set temperature, room tem-
perature, timer setting, fan speed, louver operation, and air flow direction are displayed on the
remote controller with the easily understood visual
Liquid Crystal Display (LCD).
3) Convenient 24-Hour ON-OFF Timer
The timer allows Mr.SLIM to be switched on or
off automatically at the time is shown on the LCD.
4) Self-Diagnostic Feature Indicates Instantly
In the rare case when a problem occurs, the unit stops operating and the set temperature indicator changes to the
self-diagnostic indicator, indicating the location of the fault.
If the check switch is pressed twice, the unit stops operating and the check mode is initiated. The cause of the most
recent problem stored in the memory is displayed on the LCD. This is extremely useful for maintenance purposes.
5) Useful Memory Feature for Storing Instructions
The previous set value is memorized so that constant temperature control can be obtained. This is convenient when,
for example, a power failure occurs.
(2) Non-polar Two-Wire Remote Controller Cables
The non-polar, two-wire type remote controller cable is slim, installation is simple and troublefree. Remote controller
wire can be extended up to 550 yards.
An automatic cooling and heating changeover operation system is provided to ensure easy control and year-round air
conditioning.
Once the desired temperature is set, unit operation is switched automatically between cooling and heating, in
accordance with the room temperatures as low as 23
o
F.
6. REDI-CHARGED REFRIGERANT SYSTEM
PRE-CHARGE REFRIGERANT REQUIRED FOR MAXIMUM PIPING LENGTH AT
SHIPMENT. PREVENTING TROUBLES DUE TO SHORTAGE OF REFRIGERANT.
The unique refrigerant circuit and a large accumulator always controls the refrigerant to its optimum condition regardless of
the length of 164ft maximum or 25ft minimum. The additional refrigerant charging work at the field which often caused
uncertain problems heretofore is completely eliminated. This unique system serves to improve the quality of work and
reliability, and also helps to speed up the installation work.
With normal circulation systems, a high-pressure refrigerant, condensed for cooling by the outdoor heat exacanger, is
reduced in pressure by capillary tubes in the indoor unit after passing through the restrictor valve in the outdoor unit (see
Figure 1). With the new circulation system, the direction of the restrictor valve is reversed as shown in Figure 2, and the
condensed high pressure refrigerant is reduced in pressure by the capacity tubes in the outdoor unit. This results in a “twophase refrigerant” of reduced pressure in the liquid section of the piping, The density of this two-phase refrigerant is 1/3~
1/2 of that of the high pressure liquid refrigerant, and thus is required in smaller amounts (see Figures 1 and 2). As a result,
the length of the piping can be extended further, and the effects of height differences are reduced. These new circulation
system are also equipped with a large accumulator which allows the refrigerant required for the 100ft piping length to be
enclosed in the outdoor unit. The result is an air conditioner that requires no charging unless piping is extended beyond
100ft.
3
Page 4
7. HIGH RELIABILITY AND EASY SERVICING
Red
Right
Base
Front
In addition to the self-diagnostic function, units are also equipped with a 3-minute time delay mechanism (cooling), an auto
restart function, an emergency operation function, a test run switch, etc., to assure high reliability and easy servicing.
8. FOUR-WAY PIPING ACCESS MAKES
INSTALLATION LAYOUT EASY
Piping on the outdoor unit may be connected from either of
four directions: front, rear, side or beneath the base.
This easy-access design makes it possible to install a
number of units in a compact arrangement at a single site.
The outdoor unit allows for unheard-of flexibility in
detemining a piping layout, thus greatly simplifying
installation.
9. FRONT-ACCESS FACILITATES
MAINTENANCE
The outdoor unit has been designed with a frontaccess
service panel that allows easy access to all maintenance
point, regardless of the installation layout. What’s more, this
front panel may be removed by loosening only two screws.
It all adds up to greatly simplified maintenance work.
10
. NITROGEN GAS IS CHARGED TO
INDOOR UNIT
Indoor unit and refrigerant pipes are charged with nitrogen
gas (N2) instead of R-22 before shipment from the
factory.
4
Page 5
SPECIFICATIONS2
MODELS : PKH18/24/30/36FK
Model
Item
Capacity
Moisture removal
Power
Consomption
EER
SEER
HSPF
COP
INDOOR UNIT MODELS
External finish
Power supply
Max.fuse size (time dalay)
Min.ampacity
Fan motor
Booster heater
Airflow Hi-Lo
Sound level Hi-Lo
Cond. drain connection OD
Dimensions
Weight
OUTDOOR UNIT MODELS
External finish
Power supply
Max.fuse size (time dalay)
Min.ampacity
Fan motor
Compressor
Crankcase heater
Refrigerant control
Defrost method
Sound level
Dimensions
Weight
REMOTE CONTROLLER
Control voltage (by built-in transformer)
REFRIGERANT PIPING
Pipe size
Connection
method
Between the indoor
& outdoor units
NOTES : *1.Rating conditions (cooling)-indoor : 80˚FDB,67˚FWB outdoor : 95˚FDB,75˚FWB.
(heating)-indoor : 70˚FDB,60˚FWB outdoor : 47˚FDB,43˚FWB.
*2.Rating conditions (heating)-indoor : 70˚FDB,60˚FWB outdoor : 17˚FDB,15˚FWB.
*3.Heating capacity and power consumption in [ ] includes heater operation at 208/230V.
Operating range
Cooling
Heating
Cooling *1
Heating *1
Heating *2
Cooling *1
Heating *1
Heating *2
*1
*1
*2
Dry
Wet
W
D
H
Model (type)
W
D
H
Liquid
Gas
Indoors
Outdoors
Height difference
Piping length
Air flow should be set at HI.
A point on the curve shows the reference point.
<Cooling mode>
PKH36FKPKH36FK
Data is based on the condition of outdoor humidity 75%.
A point on the curve shows the reference point.
<Heating mode>
PKH36FKPKH36FK
13
Page 14
4. STANDARD OPERATION DATA
Models
Item
Electrical circuitRefrigerant circuitIndoor sideOutdoor side
Voltage
Frequency
Total input
Indoor fan current
Booster heater current
Outdoor fan current
Comp. current
Condensing pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Comp.shell bottom temperature
Ref. pipe length
Refrigerant charge
Fan speed
Airflow (High)
Fan speed upper/lower
Airflow
Unit
V
Hz
kW
A
A
A
A
psi.G
psi.G
˚F
˚F
˚F
˚F
ft
˚F
˚F
˚F
˚F
r.p.m.
CFM
˚F
˚F
r.p.m.
CFM
Btu/h
208/230
1.79
0.5
0.75
7.4/6.9
255
81
182
118
66
171
80
67
61
59
95
75
18,000
0.82
60
Cooling
208/230
1.56
0.5
7.6/8.4
0.75
6.1/5.9
202
61
126
102
34
111
70
60
96
68
47
43
18,600
Heating
PKH18FK
208/230
2.36
0.5
0.65+0.65
9.3/8.7
240
75
158
115
46
141
80
67
58
56
95
75
24,000
0.71
60
Cooling
208/230
2.37
0.5
7.6/8.4
0.65+0.65
9.5/8.7
243
63
149
115
35
126
70
60
105
70
47
43
25,000
Heating
PKH24FK
208/230
3.12
0.5
0.75+0.75
12.6/11.8
245
80
158
115
49
138
80
67
59
58
95
75
30,000
0.75
60
Cooling
208/230
3.02
0.5
7.6/8.4
0.75+0.75
12.2/11.4
236
60
159
113
32
130
70
60
103
70
47
43
33,000
Heating
PKH30FK
208/230
3.44
0.5
0.75+0.75
14.3/13.2
243
74
160
115
45
142
80
67
58
56
95
75
34,100
0.71
60
5 lbs 8 oz
1,490
710
1,490
710
1,490
990
1,490
990
790
1,590
750/750
3,170
760/760
3,350
760/760
3,350
25
9 lbs 15 oz
25
10 lbs 2 oz
25
10 lbs 9 oz
Cooling
208/230
3.54
0.5
8.7/9.6
0.75+0.75
14.7/13.7
263
60
170
120
33
148
70
60
109
71
47
43
38,000
Heating
PKH36FK
Intake
air temperature
Discharge
air temperature
Intake
air temperature
Capacity
SHF
DB
WB
DB
WB
DB
WB
14
Page 15
5. OPERATING RANGE
1) POWER SUPPLY
1 Phase 60Hz 208/230V
Guaranteed voltage range
2) OPERATION
Min.Max.
198V208V230V253V
Function
Cooling
Heating
Air intake temperature
Condition
Standard temperature
Maximum temperature
MInimum temperature
Maximum humidity
Standard temperature
Maximum temperature
MInimum temperature
DB(˚F
80
95
67
80
70
80
70
Indoor
)
6. OUTLET AIR SPEED AND COVERAGE RANGE
Model
PKH18FK
PKH24FK
PKH30FK
PKH36FK
Airflow
(
CFM
710
710
990
990
)
Air speed
(
ft/sec
16.1
16.1
17.7
17.7
)
Coverage
range(ft
41
41
50
50
)
Outdoor
WB(˚F
67
71
57
75
60
67
60
)
DB(˚F
95
115
23
80
47
75
17
)
WB(˚F
75
—
—
75
43
65
15
)
The air coverage range is the value up to the position
where the air speed is 0.8ft/sec. when air is blown out
horizontally from the unit at the High notch position.
The coverage range should be used only as a general
guideline since it varies according to the size of the
room and furniture installed inside the room.
7. ADDITIONAL REFRIGERANT CHARGE (R-22(oz))
Refrigerant piping length (one way)
55ft
70ft
85ft
0
0
0
0
0
0
0
0
0
0
0
0
100ft
0
0
0
0
Model
PKH18FK
PKH24FK
PKH30FK
PKH36FK
Outdoor unit
precharged
(
up to 100ft
5 lbs 8 oz
9 lbs 15 oz
10 lbs 2 oz
10 lbs 9 oz
)
25ft
40ft
0
0
0
0
0
0
0
0
115ft
2
2
5
5
130ft
4
4
10
10
150ft
7
16
16
164ft
9
20
20
15
Page 16
9-1/4
1-25/32
9-1/4
1-25/32
9-1/49-1/4
1-25/32
1/2
13-3/8
7-3/4
Top
Front
Right side
Left side
55-1/8
42-15/16
Air intake
9-1/4
C
Knock out hole for right piping
Refrigerant pipe. Drain pipe
Knock out hole for
left piping
Drain hose for
left-hand side piping
Drain hose
Lower side
Auto vane
(Gas pipe)
Drain hose
Bolt
Gas pipe
19/32
Terminal block for power supply
Terminal block for control
Terminal block for remote controller
(Liquid pipe)
Liquid pipe
Gas pipe
Liquid pipe
A
1-3/16
1-15/32
1-17/32
3-27/322-9/16
2-29/32
5/32
3-15/16
1-17/32
1-3/16
1-15/32
2-29/32
5/32
1-5/32
11-1/32
1-3/16
7-1/4
1-3/16
3-5/32
1-3/18
2-3/8
13/32
1-17/32
1-15/32
2-9/16
3-15/16
A
B
C
Knock out hole for piping
31/32
43-11/16
7-7/32
9-7/16
B
55-1/8
20-9/16
4-23/32
2-5/32
4-1/32
4-3/8
Air outlet
20-9/16
Air outlet
Change vane (manual)
Under panel
Removable at left-hand
side piping
Knock out hole for under-piping
Refrigerant pipe. Drain pipe
Rear piping opening
Range for left rear piping opening
Hole for
tapping screw
66-{1/4 hole for
tapping screw
Wall fixture
Unit center
32-{15/32
hole for bolt
23/32
3-19/32
35-7/16
38-31/32
17-29/32
11-7/32
9-21/32
3/4
9-7/1611-1/3212-3/8
24
Drainage range
on left-hand side
Drainage range
on right-hand side
10x3-19/32=(35-13/16)
7-3/32
2-15/32
8-27/32
7-17/32
23/32
4
OUTLINES AND DIMENSIONS
4.1. Indoor Unit
PKH18/24FK
Unit : mm
16
Page 17
PKH 30/36FK
Unit : mm(inch)
3/4F
Through hole
Liquid pipe1/2F
Gas pipe
1
2
C
3-1/2 3-1/2~ 4
Sleeve >< 1
>< 1 Sleeves are availaable
on the market.
2-15/32
1/2
9-1/4
1-25/32
9-1/4
Right side
for right piping
Knock out hole
7-3/4
19/32
Bolt
or less
2
2-9/32
1-21/32
4-3/8
4-1/32
2-5/32(Gas pipe)
4-23/32(Liquid pipe)
7-7/32
B
9-7/16
1
9-1/4
1-25/32
Front
66-5/32
Top
9-1/4
1-25/32
9-1/4
1-25/32
9-1/4
53-15/16 Alr Intake
13-3/8
Terminal block for control
Terminal block for powar supply
Terminal block for remote controller
Drain hose
43-11/16 (Drain hose)
Lower side
55-1/8
27-5/16 Air outlet27-5/16 Air outlet
louvers(manual)
left-hand piping)
Under panel (Removable at
11-1/32
1-5/32
3-5/32
1-3/16
1-3/16
7-1/413/32
Knock out hole for under-piping
Refrigerant pipe .Drain pipe
Auto vanes
2-3/8
1-3/16
7-17/32
12- 1/4 hole
for tapping screwRear piping hole
Front
or more
1-3/16
Knock out hole
3-15/16
for left piping
5/32
1-17/32
1-15/32
2-29/32
2-9/16
5-/15/16 or less
Left side
Air
outlet
Air
intake
10 or more
A
C
1-3/161-3/16
1-15/32
2-9/163-27/32
31/32
Drain hose for
B
2 or more10 or more
Knock out hole for wiring
A
1-17/32
3-15/16
1-15/32
1-17/32
2-29/32
5/32
9-21/32
Drainage range on
right-hand side
left-handside piping
50
Unit center
Unit out line
Drainage range on
Left hand side
23-7/16
13x3-19/32=(7-3/16)11-7/32
Wall fixture
3/4
3-19/32
35-7/16
23/32
23/32
84- 1/4 hole
for tapping
screw
29-17/32
9-7/167-3/328-27/3211-1/3212-3/8
Range for left
11-5/8
rear piping hole
41- 15/32 hole
for bolt
Range for left rear piping hole
17
Page 18
4.2. Outdoor Unit PUH18EK
Terminal block for indoor and outdoor unit connection
1. Since the indoor fan motor (MF) is connected with 230V power, using 208V power will require a setting change of the dip switch (SW7<I.B>) on the indoor controller board as shown in fig :
fig w1
Indoor fan motor (MF) for 208V.
2. Since the indoor transformer (T) is connected with 230V power if 208V power is used. Change the wiring connection showing fig : w 2.
fig w2
When power supply is
w 1.
230V
SW7
ON
OFF
1
2 3 4
240V
208V
ON
OFF
YELLOW
REDYELLOW
1
2 3 4
3. Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
4. Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers.
5. Symbols used in wiring diagram above are,
6. Emergency operation
¤¤ : Connector, / : Terminal block.
If remote controller or microcomputer fails but there is no other trouble, emergency operation is possible by setting dip switch (SW3<I.B>) on the indoor controller board.
[Check items]
(1)Make sure that no other trouble exist the outdoor unit. Trouble with the outdoor unit prevents emergency operation.
(If any trouble exists the outdoor unit error code "P8" will be displayed on the remote controller and the trouble position will be shown on the outdoor controller
board LED. See electric wiring diagram of the outdoor unit for details.)
(2)Make sure that there is no trouble with the indoor fan.
Emergency operation will be continuous operation mode due to power ON/OFF (ON/OFF with the remote controller is not possible).
[Emergency operation procedure]
(1)Set the dip switch (SW3<I.B>) on the indoor controller board to 1 on and 2 off for cooling and 1 - 2 on for heating.
(2)Turn on outdoor unit side circuit breaker, then indoor unit side circuit breaker.
(3)During emergency operation indoor fan runs at high speed but automatic vane remains stopped.
If the air outlet is blocked up with the vane, Open it with your hands.
(4)Thermostat will not function. Cold air blows out for defrosting during heating thus do not operate defrosting for along time.
(5)Emergency cooling should be limited to 10 hours maximum.
(The indoor unit heat exchanger may freeze).
(6)After every operation, switch the fan connector to FAN1, and set all dip switches (SW3<I.B>) to OFF.
22
BG79N687H01
Page 23
MODELS PUH18EK
LD8
LD7
LD6
LD5
LD4
LD3
LD2
LD1
O.B
SW1
SW2
SW3
OFF
ON
2 1
CN2
RT
LED
1
2
3
TB3
YLW
ORN
BRN
FROM INDOOR UNIT
CONNECTING WIRES
12V DC (polar)
L1
L2
GR
GRN
TB1
POWER SUPPLY
1{ 208/230V
60Hz
3
2
1
CN3
CN4T
4 3 2 1
CN4
4 3 2 1
BRN 12.3V AC
RED 12.3V AC
MF
BLU
BLU
WHT
BLU
WHT
WHT
RED
RED
ORN ORN
C1
MF2
MF1
FC
26C
63H2
63H1
63H1
51CM
5
BRN
BRN
YLW
YLW
YLW
YLW
RED
RED
BLU
63H2
MC
R
C
C
S
21
51C
52C
BLU
BLU
WHT
RED
WHT
UR
TW
RED
RED
RED
ORN
BLK
BLK
T
208V
230V
21R
RED
RED
RED
RED
SV
WHT
WHT
TRF
21
S4
BLK
BLK
BLK
BLK
21S4
52C
GRY
GRY
GRY
GRY
52C
WHT
WHT
CHZNR
R/1
S/2
T/3
BLU BLU
F
HC
WHT
WHT
4
S
A
B
X11X12X13X14
X14
X13 X12 X11
4
3
2
1
C
C1
F<O.B>
FC<O.B>
HC
LD1~LD8
MC
MF
O.B
COMPRESSOR CAPACITOR
FAN CAPACITOR
FUSE<6A>
FAN CONTROLLER
CRANKCASE HEATER
LED<CHECK,SERVICE>
COMPRESSOR
FAN MOTOR<INNER THERMOSTAT>
OUTDOOR CONTROLLER BOARD
w1 In addition, the centralized and remote control can be operated.
w2 The modes which indicate the sources of trouble are listed below.
● EO=Signal transmitting/receiving error
● P1=Room temperature thermistor malfunction
● P2=Indoor coil thermistor malfanction
● P4=Drain sensor malfunction
● P5=Drain over flow
● P6=Coil frost/overheat protection
● P7=System error
● P8=Outdoor unit trouble
w3 The CHECK swich will show if an error has occurred in the past.
w4 Fan runs on low speed for 1 minute in order to remove overheat air.
w5 The 3-minute (6 minutes … heating mode) time-delay functions after compressor stops.
w6 FAN or AUTO mode is selected by the indoor dipswitch setting.
w7 In FAN mode, fan speed and vane operation depend on the remote controller setting. (Compressor is OFF.)
26
Page 27
COOLING OPERATION
COOL operation
Four-way valve/OFF
NO
NO
NO
NO
Vane setting notch
Initial
COOLING
w 8
w 9
YES
Vane intial
setting
Vane
60 deg downward angle
70 deg downward angle
YES
Fan speed
LOW
YES
Downward discharge
1 hour
YES
Vane horizontal
airflow
NO
Compressor
thermostat
ON
NO
Allowance
cancel
NO
YES
YES
NO
w 10
w 11
YES
3-minute
time delay
6-minute
time delay
3-minute
compressor opration
Coil frost
prevention
Cooling area
NO
NO
YES
NO
YES
NO
Aliowance
period
NO
6 minute
time delay
Allowance set
YES
Coil frost protection
YES
10-minute
NO
compressor operation
Allowance cancel
NO
compressor operation
Compressor ON
YES
Coil frost
protection
NO
16-minute
YES
Indoor pipe
temperature is
34¡F or lower
NO
1
YES
YES
Coil frost
prevention
Compressor OFF
Indoor coil
tempreature is
50¡F or higher
YES
3-minute
time delay
Coil frost
prevention release
NO
NO
1 min continue
FAN speed
YES
LOW
FAN speed
LOW 5 min
elapse
NO
YES
Outdoor unit
trouble
w8 When operation stops or changes to cooling or dry mode, the auto vane turns to a horizontal angle. IF opera-
tion changes during auto vane SWING, the auto vane will continue to swing.
w9 When operating TEST RUN, the thermostat will be continuously ON.
w10After 3 minute compressor operation, if the indoor coil thermistor reads -59°F or below for 3 minutes, the com-
pressor will stop for 6 minutes.
w11Cooling area : Indoor coil temperature is more than 9 degrees above the room temperature.
Heating area : Indoor coil temperature is more than 9 degrees below the room temperature.
FAN area : Indoor coil temperature is within 9 degrees either way of the room temperature.
27
Page 28
HEATING OPERATION
Heat operation
Intial
HEATING
YES
Vane intial setting
NO
Defrosting
NO
Four-way valve ON
Hor adjust
in process
NO
Compressor ON
NO
Compressor
thermostat ON
Allowance cancel
Indoor piping
-5¡F or lower
YES
Outdoor unit
trouble
FAN SPEED
Very low airflow
Compressor OFF
1
w 15
2
NO
Vane setting notch
w 9
NO
YES
YES
YES
YES
3 min.restart
prevention
YES
6 min. restart
prevention
NO
Hot adjust start
FAN SPEED very low
Compressor ON
NO
Allowance cancel
w 11
FAN STOP
w 11
20 min.elaspe
YES
w 11
Cooling area
Defrost operation
Four-way valve
10-minute
compressor
operation
YES
Heating
area
Ariflow area
Airflow area
Heating area
NO
Airflow area
YES
START
OFF
w 10
w 11
YES
YES
NO
Heating area
NO
Defrost
30 min. elaspe
YES
Outdoor unit trouble
1
A
Outdoor unit
trouble
YES
Defrost release
NO
131¡F or lower
NO
Auxiliary heater
NO
140¡F or higher
YES
Auxiliary heater OFF
Overheat remote
NO
158¡F or higher
Allowance
Overload protect
2
B
Indoor piping
NO
ON
YES
Indoor piping
START
Indoor unit
YES
period
YES
YES
NO
Auxiliary heater ON
NO
6-minute restart
Allowance set
Compressor OFF
Auxiliary heater
thermostat ON
YES
prevention
YES
Indoor piping
95¡F or higher
NO
HOT adjust
6 min. elapse
YES
FAN SPEED
Low
FAN SPEED
Low 2 min.
elapse
YES
FAN SPEED
setting notch
Hot adjust
release
A
PKH-FK
Type
3-minute
Auxiliary heater
OFF
Indoor coil
thermstor is 60¡C
or higher
FAN speed
Low notti
YES
Airflow 10% up
B
NO
NO
NO
NO
NO
NO
FAN setting notch
Auto COOL/HEAT
operation
NO
w 17
NO
w 16
Initial mode
YES
NO
>
1 T0
T
=
YES
COOL modeHEAT mode
1 < (T0 - 2)
YES
After 15min.
T1<(T0-2)
NO
NO
YES
COOL mode
T
COOL operationHEAT operation
NO
1>(T0 + 2)
T
YES
After 15min.
T1>(T0 + 2)
HEAT operation
11
YES
NO
Cool mode
set
1
w15 (!) Until Low airflow is set while hot adjustment
(@) While defrosting (FAN STOP)
(#) When thermostat is OFF
In the case of(!), (@) and (#) above, airflow is horizontal regardless the VANE setting.
w16 When AUTO operation is started, COOL or HEAT mode is selected automatically.
w17 T1 : Room temperature.
To : Set temperature
28
Page 29
DRY OPERATION
DRY
operation
Four-way valve / OFF
Vane
setting notch
NO
YES
NO
Initial dry
operation
YES
w 8
Vane intial setting
w 12
Room tempereature is
64°F or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
Compressor &
w 9
thermostat ON
YES
NO
NO
YES
3-minute
time delay
NO
Compressor &
thermostat
ON
NO
YES
w 9
Compressor ON
NO
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
w 14
Fan STOP
1
w8 ~ 9 Refer to page 35.
w12When room temperature is 4°F or below, the compressor cannot operate.
When room temperature rises over 64°F, the compressor starts after a 3-minute time delay.
w13Compressor ON time is decided by room temperature. Refer to page 35.
w14In dry operation, compressor ON makes the fan speed LOW and compressor OFF stops the fan.
It is not possible to set the fan speed with the remote controller
w System control operation.
w Emergency operation.
w Set by dipswitch on indoor controller board.
● Transmits the power to remote controller.
1 2 3
Polar three-wire cable
Outdoor unit
OUTPUT to outdoor unit
12VDC
1
2
3
● Compressor and
outdoor fan : ONOFF
● Operation mode
change :COOLHEAT.
Page 31
2. INDOOR UNIT CONTROL
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECKTEST RUN
2-1 COOL operation
<COOL operation time chart>
Operation starts by
POWER button
ON.
ON
Thermostat
OFF
<How to operate>
1 Press POWER ON/OFF button.
2 Press COOL / DRY button to set operation mode to Cool.
NOTE :"Cool" and "DRY" are alternately displayed each time
COOL / DRY button is pressed.
3 To set desired temperature, press WARMER or COOLER
button.
NOTE :Set temperature changes by 2˚F in the range 66~86˚F,
each time WARMER or COOLER button is pressed.
The room temperature
displayed on Remote
controller becomes equal
to set temperature.
The room temperature
displayed on Remote
controller rises above
set temperature.
Operation stops by
POWER button
OFF.
LOW or HIGH
Indoor fan
ON
OFF
LOW or HIGH
Initally 10 degrees
(Changeable by remote controller setting)
Auto vane
Booster heater
CLOSECLOSE
ON
OFF
OFF
ON
Compressor
OFF
Minimum 3 minutes 1
W
w1 Even if the room temperature displayed on remote controller rises above the set temperature during this period, the compressor will not start until this period
has ended.
31
Page 32
(1) Compressor control
5 minutes
SET
LOW
5 minutes
SET
LOW
OFF
1 3-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2 The compressor runs when the room temperature displayed on remote controller is higher than set temperature.
The compressor stops when the room temperature displayed on remote controller is equal to or lower than the set temperature.
3 The compressor stops in check mode or during protective functions.
4 Coil frost preventionTo prevent indoor coil frost, the compressor will stop when the indoor coil thermistor (RT2) reads 34°F
or below after the compressor has been continuously operated for at least 16 minutes or more. When the indoor coil temperature rises to 50°F or above, the compressor will start after a 3-minute time delay.
NOTE : The start temperature of coil frost prevention changes 34°F to - 27°F.
5 Coil frost protection
When indoor coil temperature becomes 5°F or below, coil frost protection will proceed as follows.
<Start condition>
After the compressor has been continuously operated for 3 minutes or more,and the indoor coil temperature has been
5°F or below for 3 minutes,the coil frost protection will start.
<Coil frost protection>
Compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again during the first 10 minutes of compressor operation, both the indoor and outdoor
units stop, displaying a check code of “P8” on the remote controller.
<Termination conditions>
Coil frost protection is released when the start condition is not satisfied again during the allowance, or when the COOL
mode stops or changes to another mode.
(2) Indoor fan control
Indoor fan speed LOW/HIGH depends on the remote controller setting.
However, if an outdoor unit abnormality is detected, the indoor fan speed will be LOW, regardless of the remote controller
setting.
When the outdoor unit abnormality detection is released and the fan speed returns to the set speed, the quiet cycle control
will work.
(a) Normal control
(i ) Fan speed LOW/HIGH depends on the remote controller setting regardless of the thermostat ON/OFF.
(ii) Fan speed will remain on LOW if an abnormality in outdoor unit is detected. (5 minutes)
When the abnormality detection is released, the fan speed returns to the set speed.
1 Start-up of outdoor unit abnormality detec-
tion.
2 Release of outdoor unit abnormality detec-
tion.
3 Unit stop due to outdoor unit abnormality
with P8 indication.
NOTE 1 : Fan stops immediately if the unit stops or the check mode is started.
32
Page 33
(3) Auto vane control
Auto vane position is set to 10degrees discharge at the start-up of COOL operation. It can then be changed by the remote
controller.
(a) Stop mode (fixed operation)
(
!) At start-up of COOL operation, the auto vane is set to 10 degrees discharge direction.
(@) Discharge direction can be changed with AIR DISCHARGE UP/DOWN botton.
1 Fan speed : LOW
10°
discharge
2 Fan speed : HIGH
10°
discharge
(b) SWING mode
(!) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
(@) When SWING mode is changed to STOP mode, the discharge direction returns to the position of the last STOP mode.
<AUTO RETURN>
1 Fan speed : LOW
10°
discharge
30°
discharge
60°
discharge
60°
discharge
60°
discharge
70°
discharge
70°
discharge
70°
discharge
AUTO
RETURN
2 Fan speed : HIGH
10°
discharge
When 60 degrees or 70 degrees discharge is selected with the LOW fan speed in COOL operation, “Auto RETURN” will
appear below the temperature display. One hour later, the discharge direction returns to 10 degrees automatically and
“AUTO RETURN” will disappear. If the discharge direction is set to 10 degrees during “AUTO RETURN” indication, the
time counting for AUTO RETURN is cancelled.
30°
discharge
60°
discharge
AUTO
RETURN
70°
discharge
33
Page 34
<Auto vane drive>
(a) The vane is driven by DC12V motor.
(b) Air discharge direction is selected depends on the number of pulse were sended.
(c) Before start driving the auto vane, detect the standard position first, output the number of pulse to each air discharge.
(d) The speed of the auto vane drive for both open and close are setted at 200 pulse/sec.
(e) Method of driving the auto vane.
1 Detecting the standard position:
Output 1600 pulse to the opening direction.
2 Position setting:Output the number of pulse indicated no below chart to the closing direction.
The number of pulse outputed after
detecting the standard position
Close
Horizontal
Downward A
Downward B
Downward C113
(4) Detecting abnormalities in the outdoor unit
After the compressor has been continuously operated for 3 minutes, if the difference between the indoor coil temperature
and room temperature is out of RANGE C for 1 minute, the indoor fan speed will turn to LOW. Five minutes later, if the difference is still out of
RANGE C,the outdoor unit is functioning abnormally. Thus, the compressor stops and check code “P8” appears on remote
controler.
RANGE A: Indoor coil temperature is more than 9 degrees above room temperature.
RANGE B : Indoor coil temperature is within 5 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 9 degrees below room tempetature.
1600
680
578
283
Indoor coil temperature
minus room temperature
(degree)
+9
0
-9
RANGE A
RANGE B
RANGE C
34
Page 35
Minimum 3 minutes 1
ON
30
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
ON
Initally 10 degrees discharge
(
Changeable by remote controller setting
)
LOW speedLOW speed
ON
ON
OFF
OFF
CLOSE
CLOSE
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
30
The room temperature
dislayed on remote controller becomes equal to
set temperature.
The room temperature
dislayed on remote controller rises above set
temperature.
w
2-2 DRY operation
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
<DRY operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press COOL / DRY button to set operation mode to DRY.
NOTE :"Cool" and "DRY" are alternately displayed each time
COOL / DRY button is pressed.
3 To set desired temperature, press WARMER or COOLER
button.
NOTE :Set temperature changes by 2˚F in the range 66~86˚F,
each time WARMER or COOLER button is pressed.
w1 Even if the room temperature dispayed on remote controller above the set temperature during this period, the compressor will not start until this period
has ended.
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor runs when the room temperature displayed on remote controller
is higher than the set temperature.
The compressor stops when the room temperature displayed on remote controller
is equal to or lower than the set temperature.
3The compressor stops in check mode or during protective functions.
4The compressor will not start when the room temperature displayed on remote controller
is below 64°F.
The compressor starts intermittent operation when the power is turned ON with room temperature above 64°F. The compressor ON/OFF time depends on the thermostat ON/OFF and the following room temperatures.After 3-minute compressor operation,
● If the room temperature thermistor reads above 82°F with thermostat ON, the compressor will operate for 6 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 79°F—82°F with thermostat ON, the compressor will operate for 4 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads 75°F—79°F with thermostat ON, the compressor will operate for 2 more minutes and then stop for 3 minutes.
● If the room temperature thermistor reads below 75°F with thermostat ON, the compressor will stop for 3 minutes.
● If the thermostat is OFF regardless of room temperature, the compressor will stop for 10 minutes.
5Coil frost protection in DRY operation is the same as in COOL operation.
6Coil frost prevention does not operate in DRY operation.
(2) Indoor fan control
The indoor fan runs on LOW speed during compressor operation. The fan speed cannot be changed with the remote con-
troller. Also, the indoor fan does not run during compressor OFF.
(3) Auto vane & drain pump controls
Same as in COOL operation
(4) Detecting abnormalities in the outdoor unit
An abnormality in the outdoor unit can not be detected in DRY operation.
35
Page 36
Minimum 3 minutes 2
ON
Thermostat
Indoor fan
Auto vane
Booster heater
Compressor
Power ON lamp
STAND BY lamp
ON
ON
LOW or HIGHLOW or HIGH
ON
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Extra LOW 1Extra LOW 1
Hot adjustment
10¡
Close
10¡Close
From POWER ON until
warm begins to blow
Hot adjustment
Depends on remote
controller setting
Depends on remote
controller setting
1 Changeable by indoor
dipswitch J1 - 7 and
J1 - 8.
OFF during thermostat OFF
hot adjustment
defrosting
LOW
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
The room temperature
displayed on remote controller becomes equal to
set temperature.
The room temperature
displayed on remote controller falls below set
tem-
w
ww
w
2-3 HEAT operation
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
<HEAT operation time chart>
<How to operate>
1 Press POWER ON/OFF button.
2 Press HEAT button to set operation mode to HEAT.
3 To set desired temperature, press WARMER or COOLER
button.
<Display in HEAT operate>
"STAND BY" is displayed from HEAT operation start until warm
air begins to blow.
"DEFROST" is displayed during defrosting.
w2 Even if the room temperature displayed on remote controller rise above the set temperature during this period, the compressor will not start until this period has
ended.
36
Page 37
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 6, minutes after stop.
2The compressor runs when the the room temperature displayed on remote controller is lower than the set temperature.
The compressor stops when the the room temperature displayed on remote controller is equal to or higher than the set
temperature.
3The compressor stops in check mode or during protective functions.
4Overheat protection
<Start condition>
When the indoor coil thermistor reads 158°F or above, the overheat protection will start.
<Overheat protection>
The compressor stops for 6 minutes, and then restarts.
If the start condition is satisfied again within 10 minutes of compressor operation, both the indoor and outdoor units stop,
displaying a check code of “P6” on the remote controller.
<Termination conditions>
Overheat protection is terminated when the start condition is not satisfied again during the allowance (10-minute compressor operation), when operation mode changes to other mode, or when thermostat turns OFF.
(2) Indoor fan control
(a) Nomal control
(!)The indoor fan runs on EXTRA-LOW speed during the thermostat OFF.
EXTRA-LOW speed can be changed to LOW or HIGH speed by setting the (J1-7, J1-8) If the indoor coil temperature becomes more than 9 degrees below the room temperature during the thermostat OFF, the indoor fan will stop.
After, when the indoor coil temperature becomes within 9 degrees of room temperature, the indoor fan will run on
EXTRA-LOW speed.
(@)Hot adjustment Hot adjustment is a warm-up for HEAT operation
<Start conditions>
The hot adjustment works under any of the follwing conditions.
● HEAT operation starts.
● Defrosting ends.
● Thermostat turns ON.[Hot adjustment]
Initially, the indoor fan runs on EXTRA-LOW speed. When 5 minutes have passed or the indoor coil temperature
exceeds 95°F, the fan speed changes to LOW. Two minutes later, the hot adjustment ends. Then, the fan speed
depends on the remote controller setting.
(#)The indoor fan stops when the indoor coil temperature is within 9 degrees either way of room temperature.
($)To eliminate the remaining heat, the indoor fan runs for the first 1 minute after the booster heater is turned OFF.
37
Page 38
(3) Auto vane control
(a) STOP mode (fixed operation)
(!) The discharge direction at the start-up of HEAT operation is the same as that of the previous operation.
(@) The discharge direction can be charged by the remote controller setting.
10°
discharge
In the following cases, discharge direction becomes 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW
2 During defrosting with indoor fan OFF
3 During the thermostat OFF
(b) SWING mode
(!) The vane motor turns ON when the SWING mode is selected.
The vane motor is continuously ON during SWING mode.
(@) In the following cases, the discharge direction is 10° regardless of the remote controller setting.
1 During the hot adjustment with fan speed at EXTRA-LOW
2 During defrosting with indoor fan OFF
3 During thermostat OFF
(4) Booster heater control
When the room temperature is 5 degrees below the set temperature, the booster heater will turn ON.
When the room temperature is equal to the set temperature, booster heater will turn OFF.
During the hot adjustment, the booster heater will not work.
<Overheat prevention>
When the indoor coil thermistor rises to 140°F or above, the booster heater cannot work.
When the indoor coil thermistor falls to 131°F or below, the booster heater can work.
(5) Detecting abnormalities in the outdoor unit
When the outdoor unit is determined to be abnormal by the following causes, the compressor will stop and the check code
“ P8 ” will appear on the remote controller display.
1 During compressor ON after hot adjustment
1 If the difference between the indoor coil temperature and room temperature is in the RANGE B, the indoor fan will
stop.
2 Within 20 minutes after entering RANGE B (except for the first 10 seconds),
a) If the temperature difference enters RANGE A, the hot adjustment stasrts,
b) If the temperature difference is still in RANGE B, the outdoor unit is deemed abnormal.
c) If the temperature difference enters RANGE C, defrosting starts.
Within 30 minutes after entering RANGE C,
●If the temperature difference does not return to RANGE B,the outdoor unit is deemed abnormal.
●If the temperature difference returns to RANGE B, the next 20 minutes is an allowance period. If the difference enter
RANGE Aduring the allowance, defrosting ends and the hot adjustment starts. If the difference does not enter
RANGE Aduring the allowance, the outdoor unit is deemed abnormal.
2 During compressor ON in hot adjustment
After 30 minutes of defrosting in hot adjustment, if the temperature difference is still in RANGE C, the outdoor unit is
determined to be abnormal.
3 During compressor OFF
After 20 minutes of thermostat OFF, if the indoor coil thermistor reads -13°F or below, the outdoor unit is determined to
be abnormal.
30°
discharge
60°
discharge
70°
discharge
(only for New models)
(SWING)
(SW5-3:OFF/ON)
w1 (See the next page.)
38
Page 39
(6) Indoor coil thermistor abnormality detection
An abnormality can be detected during compressor ON, except for the following.
●For the first 30 minutes after the temperature difference between the indoor coil temperature and room temperature
enters the RANGE C.
●When the temperature difference enters the RANGE C until it moves to the RANGE B.
(7) Defrosting operation
After the outdoor unit starts the defrosting operation, when the temperature difference between the indoor coil temperature
and room temperature gets out of RANGE Aand into RANGE B, the indoor unit starts the defrosting mode. After the outdoor unit stops the defrosting operation, when the temperature difference returns to the RANGE A, the indoor unit stops
the defrosting mode. While the indoor unit is in the defrosting mode, the indoor fan and the booster heater stop.
w1 RANGE A: Indoor coil temperature is more than 9 degrees above room temperataure.
RANGE B : Indoor coil temperature is within 9 degrees either way of room temperature.
RANGE C : Indoor coil temperature is more than 9 below room temperature
Indoor coil temperature
minus room temperature
(degree)
+9
-9
RANGE A
0
RANGE B
RANGE C
39
Page 40
Mode change (HEAT COOL)
When the room temperature displayed remote controller becomes2degrees above the set temperature,
the operation mode can not be changed for 15 minutes.
(degree)
To+4
To:Set temperature (19 28 )
To+2
To
To-2
To-4
Compressor
Start
HEAT modeHEAT mode
Mode change
15 minutes
Mininum 3 minutes
15 minutes
Mininum 3 minutes
COOL mode
(COOL HEAT)
ON
OFF
-15.832506886104115¡F
-17¡F
Cooling range
(Outside air temperature)
Heating range
10¡F
2-4 AUTO operation (Automatic COOL/HEAT change over operation)
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMER MODE HOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECK TEST RUN
<How to operate>
1 Press POWER ON/OFF button.
2 Press AUTO button to set operation mode to AUTO.
3 To set desired temperature, press WARMER or COOLER
button.
NOTE :Set temperature changes by 2˚F in the range 66~86˚F,
each time WARMER or COOLER button is pressed.
Once the desired temperature is set, operation mode is
switched automatically between COOL and HEAT
according to room temperature.
(1) Initial mode
1 When AUTO operation starts after unit OFF.
● If the room temperature displayed on remote controller is higher than the set temperature, operation starts in COOL
mode.
● If the room temperature displayed on remote controller is equal to or lower than the set temperature, operation starts
HEAT mode.
2 When AUTO operation starts after COOL or HEAT operation, the previous mode continues.
(2)Mode change
1 HEAT mode changes to cool mode when 15 minutes have passed since the room temperature became 2 degrees
above the set temperature.
2 COOL mode changes to HEAT mode when 15 minutes have passed since the room temperature became 2 degrees
below the set temperature.
(3)Temperature range
AUTO operation is available under the outside air temperatures as follows.
40
Page 41
discharge
1
downward discharge
2
downward discharge
3
downward discharge
4
2-5 Auto vane control
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECKTEST RUN
<How to operate>
To change the air flow direction, press AIR DISCHARGE UP/DOWN button.
<Remote controller display>
1
10°
2
30°
3
60°
4
70°
Available in COOL operation with fan speed on HIGH or
in HEAT operation.
Unavailable in DRY operation.
If fan speed changes from LOW to HIGH during 30°
downward discharge in COOL mode, the direction automatically changes to 10°.
Changes by pressing
the AIR DISCHARGE
UP/DOWN button.
(1) COOL/DRY operation
(2) HEAT operation
At the start-up of COOL or DRY operation, the discharge direction in automatically set to 10°. After, it can be changed to
another direction with AIR DISCHARGE UP/DOWN button on the remote controller.
<Auto return>
When 60° or 70° discharge is set with fan speed on LOW, “AUTO RETURN” appears below the room temperature display.
One hour later the direction changes to 10° degrees, automatically and “AUTO RETURN” disappears.
At the start-up of HEAT operation, discharge direction depends on the setting of the last operation.
After, it can be changed to another direction with AIR DISCHARGE UP/DOWN button. The discharge direction shifts to 10°
regardless of the remote controller settings under any of the following conditions.
● Thermostat OFF
● Defrosting
● Indoor fan speed EXTRA-LOW in hot adjustment
41
Page 42
2-6 TIMER operation
-CENTRALLY CONTROLLED STAND BY
ON
DEFROST
CHECK DRY
HEAT
COOL
CHECK
F
SET TEMP
TIMER OFF
AUTO STOP
HR
AUTO START
LOW HIGH
F
AUTO RETURN
CHECK TEST RUN
<Timer setting example>
POWER
AUTO COOL/DRY
HEAT
SET
TEMPERATURE
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
UP/DOWN
DISCHARGE
CHECKTEST RUN
MITSUBISHI ELECTRIC
ON/OFF
COOLERWARMER
SWING
STOP
<Timer function>
AUTO STOP ·········The air conditioner stops after the set time lapses.
AUTO START ········The air conditioner starts after the set time lapses.
AUTO OFF ············Timer is not active.
<How to operate>
1. Press POWER ON/OFF button.
2. Press TIMER HOURS button to select AUTO STOP or AUTO
START.
3. Press TIMER HOURS button to set desired time.
Time setting is in 1 hour units for up to 24 hours.
Each time HOURS button is pressed, set time increases by 1 hour.
When HOURS button is pressed and held, the set time increases
by 1 hour every 0.5 seconds.
4. To cancel the timer operation, press POWER ON / OFF button.
AUTO STOP
8
HR
This setting will stop the air conditioner in 8 hours.
With the lapes of time, time display changes in 1 hour units, showing remaining time.
2-7 Test run
<Before test run>
● After installing, wiring, and piping the indoor and outdoor units, check for refrigerant leakage, looseness in power supply or
control wiring, and mistaken polarity.
● Use a 500-volt megger to check the resistance between the power supply teminal block and ground to make sure that it is
at least 1.0MΩ.
Attention:
Do not use the air conditioner if resistance is less than 1.0MΩ.
<How to operate>
-CENTRALLY CONTROLLED STAND BY
ON
DEFROST
CHECK DRY
HEAT
COOL
CHECK
F
SET TEMP
TIMER OFF
AUTO STOP
HR
AUTO START
LOW HIGH
F
AUTO RETURN
CHECK TEST RUN
POWER
AUTO COOL/DRY
HEAT
SET
TEMPERATURE
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
UP/DOWN
DISCHARGE
CHECKTEST RUN
MITSUBISHI ELECTRIC
ON/OFF
COOLERWARMER
SWING
STOP
1. Turn ON main breaker.
2. Press TEST RUN button twice. “TEST RUN” is displayed on
remote controller.
3. Press COOL / DRY button to check that cool air is being
discharged.
4. Press AIR DISCHARGE UP / DOWN button to check auto
vane operation.
5. Check outdoor fan operation.
6. Check compressor operation referring to the indoor coil
temperature code displayed on the remote controller. (See
next page.)
7. The test run works for 2 hours and stops automatically. To
cancel the test run, press POWER ON / OFF button or
TEST RUN button
TIMER MODE button.
8. After checking, turn OFF the main breaker.
Displayed during test run
Indoor coil temperaure code Display
42
Page 43
(1) Indoor coil temperature code
Code1
~40~34¡F
9
~113¡F
2
~50¡F
10
~122¡F
3
~59¡F
11
~131¡F
4
~68¡F
12
~140¡F
5
~77¡F
13
~158¡F
6
~86¡F
14
7
~95¡F
15
Thermistor
abnormality
8
104¡F
Indoor coil
temperature
Code
Indoor coil
temperature
1 ON
1
2
1.2 ON
1
2
1-2 OFF
1
2
During the test run, the indoor coil temperature code from 1 to 15 is displayed on the remote controller instead of room
temperature. The code should fall with the lapse of time in normal COOL operation, and should rise in normal HEAT
operation.
(2) Trouble during test run
● If the unit malfunctions during the test run, refer to section 10 in this manual entitled “TROUBLESHOOTING.”
● When the optional program timer is connected to the conditioner, refer to its operating instructions.
2-8 Emergency operation
When the remote controller or microprocessor malfunctions but all other parts are normal, emergency operation is started
by setting the dipswitch SW3 on the indoor controller board.
<Before emergency operation>
1. Make sure the compressor and the indoor fan are operating normally.
2. Locate the defect with the self-diagnostic function. When the self-diagnostic function indicates “protective function is
working”, release the protective function before starting the emergency operation.
CAUTION: When the self-diagnostic function indicates a check code of “P5” (drain pump malfunction), DO NOT start
the emergency operation because the drain may overflow.
<How to operate>
1. For emergency cooling, set the dipswitch SW3-1 to ON and SW3-2 to OFF.
For emergency heating, set the dipswitch SW3-1,2 to ON.
Emergency
cooling
Emergency
heating
Nomal
operation
Microcessor board
2. Turn ON the outdoor unit breaker and then turn ON the indoor unit breaker.
Emergency operation will now start.
3. During emergency operation, the indoor fan operates on high speed, but the swing louvers and the auto vanes do not
operate.
4. To stop emergency operation, turn OFF the indoor unit breaker.
NOTE: The remote controller POWER ON/OFF button can not start/stop emergency operations.
CAUTION: Do not use emergency cooling for more than 10 hours, as the indoor coil may freeze.
43
Page 44
2-9 Interlock with ventilation system (LOSSNAY)
Relay box
Relay box (PZ-12RB-E)
LOSSNAY
LOSSNAY
LOSSNAY control switch (PZ-05SLB2-E)LOSSNAY control switch
(PZ-05SLB
2-E)
Mr. SLIM
Mr. SLIM
Remote
controller
Remote
controller
Remote display
adapter
(PAC-SA88HA-E)
Power
supply
Power supply
Relay box
LOSSNAY
ABLN HIGH N
Terminal block
Terminal block
Mr.SLIM
CN51
12V DC
Power supply
220 240V AC
Circuit
breaker
WHT
WHT
N
DAMPER
DAMPER
RED
LOW
HIGH
ORN
ORN
RED
(PZ-12RB-E)
L
N
Mr. SLIM/LOSSNAY interlock operation is available by using the optional parts listed below.
(1) System organization
(2) Required parts are:
● Relay box (PZ-12RB-E) ••• Contact capacity 10A
● Remote display adapter (PAC-SA88HA-E)…An optional part for Mr. SLIM
● LOSSNAY control switch (PZ-05SLB-2-E)…For LOSSNAY individual operation
(3) Operation
1LOSSNAY turns ON/OFF according to Mr. SLIM ON/OFF
2While Mr. SLIM is OFF, LOSSNAY individual operation is available by using the LOSSNAY control switch.
When Mr. SLIM turns OFF with the LOSSNAY control switch at ON, LOSSNAY will continue to operate.
(4) Wiring.
Remote
controller
Insulation
is needed
10m
Connecting wire
2
0.13mm or over
Connecting wire
solid wire,
1.6 or 2.0
(field supplied)
Circuit breaker
(field supplied)
L
Power
supply
N
50Hz
220 240V
PL
HIGH
N
LOSSNAY control switch
(PZ-05SLB
Indoor controller
N
L
LOW
DAMPER
2-E)
Mr. SLIM
board
Connector
CN51
ORN
RED
BRN
GRN
YLW
Junction box
(field supplied)
Power supply
for Mr. SLIM
220 240V AC
Relay box
(PZ-12RB-E)
YLW
A
ORN
B
RED
L
WHT
N
RED
HIGH
N
WHT
LOSSNAY
Terminal
block
ORN
LOW
RED
HIGH
WHT
N
RED
DAMPER
ORN
DAMPER
WHT
2When the LOSSNAY control switch is not used:1When the LOSSNAY control switch is used:
8
7
4
6
2
5
3
1
NOTE: For further information, refer to the
LOSSNAY technical & service manual.
44
Page 45
2-10 Dip switch and jumper connector functions
Each figure shows the initial factory setting.
1 On remote controller board
(1) SW17(Address selector)
1 2 3 4 5 6 7 8 9
ON
OFF
SW17-1 ~ 6) For address setting
SW17-7) When two remote controllers are used, this switch sets the controller function.
OFF: The remote controller is set as a main controller.
ON: The remote controller is set as a sub controller.
SW17-8) Switch for system back-up
OFF: Without back-up
ON: With back-up
SW17-9) Switch for temperature unit
OFF: °C ( Celsius)
ON: °F (Fahrenheit)
SW17-0) Switch for louvers
OFF: Unit with louvers
ON: Unit without louvers
3. On indoor controller boaed
(1) J1 (Mode selector)
0
1456789
J1-1) Switch that changes between FAN mode and AUTO mode.
Provided: Fan mode for models without heat pump.
Not provided: AUTO mode for models without heat pump.
J1-4) Switch for drain pump
Provided: The drain pump works in only COOL operation
Not provided: The drain pump works in both COOL and HEAT operation
J1-5) Switch to change the temperature to start coil frost prevention
Provided : 34°F (For all current models)
Not provided: -27°F (For previous special models)
J1-6) Switch for set temperature adjustment in HEAT mode
During HEAT operation, warm air collects near the ceiling. When the indoor unit is installed near the ceiling, the
temperature read by room temperature thermistor differs from the actual living-space temperature by about 7
degrees. Therfore, the room temperature read by room temperature thermistor must be lowered by 4 degrees.
Provided : 7-degree adjustment
Not provided : No adjustment
10
45
Page 46
J1-7) Switch for fan speed during thermostat OFF in HEAT operation
J1-8) Switch for fan speed during thermostat OFF in HEAT operation.
J1-9) Switch for detecting abnormalities in the outdoor unit abnormality detection.
J1-10) Switch for auto restart function
Provided : EXTRA LOW
Not provided : LOW
Provided : EXTRA LOW or LOW (set with J1-7)
Not provided : Low or HIGH (set with remote controller)
Provided : When an abnormality occurs, it is detected.
Not provided : Even if an abnormality occurs, it can not be detected.
Previded : This function does not work
Not provided : This function works.
The room temperature displayed on remote controller
becomes equal to set temperature.
The room temperature displayed on remote controller
becomes different from set
temperature.
3-1 Outdoor fan control
The rotational frequency of outdoor fan is phase-controlled according to the outdoor coil temperature. This control allows the
cooling operation even with the low outside-air temperature and the heating operation even with the high outside-air temperature.
3-2 Outdoor unit control
The outdoor unit turns ON/OFF the cooling/heating operation according to orders given from the indoor unit.
3-3 Protective functions
1 If an reversed-phase, an open phase, or an indoor controller abnormality is detected, the outdoor unit will stop operation and
the check mode will start. (For the check mode details, see page 48.)
2 If a protective function works, the compressor will stop running. Three minutes later, the compressor will restart. If the protec-
tive function works again, the compressor will stop running and the check mode will start.
3 The protective function is memorized.
4 The memory is cleared when the POWER ON/OFF button on the remote controller is turned OFF. However, the check mode
display continues until the outdoor unit receives the “operation ON” command from the indoor unit.
3-4 COOL/HEAT operation time chart
w1 If compressor restarts within 10 minuteas, 4-way valve remains ON.
47
Page 48
ON
Outdoor fan
Compressor
4-way valve
Bypass valve
Auto vane
Indoor fan
35degrees(SW5-3 OFF)or 20degrees(SW5-3:ON)discharge direction
(Remote controller still displays set direction.)
Outdoor unit
Indoor unit
ON
Set direction
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
Set direction
Defrosting
starts.
Defrosting
stops.
3-5 Defrosting in HEAT mode
<Defrosting time chart>
(1) Start conditions
A. When all of the following conditions are satisfied, defrosting will start. However, when the bypass valve turns OFF,
defrosting starts 10 minutes later.
(a) More than seven minutes have passed since the compressor start-up.
(b) The outdoor coil thermistor reads 23˚F or below.
(c) The outdoor fan motor output step is 100%
(d) Total time of compressor operation exceeds 30 minutes, and the outdoor coil temperature has fallen by 14 degrees
or more in comparison with that of 10 minutes after the compressor start-up.
NOTE: The outdoor coil temperature 10 minutes after the compressor start-up is memorized until the defrosting
operation has ended.
B. When all of the following conditions are satisfied, defrosting will start.
(a) ~ (c) The same as above (a) ~ (c) in item A
(d) Total time of compressor operation exceeds “defrost interval”.
Further information on the defrost interval is described in (3).
C. After the total time of compressor operation exceeds the defrost interval, the thermostat repeats ON/OFF three times.
Two minutes after the fourth “ON” of the thermostat, if the outdoor coil thermistor reads 23˚F or below and the fan output output is 100%, defrosting will start.
NOTE: The count of the thermostat ON/OFF is cleared by the compressor-OFF command or defrosting start-up.
(2) During defrosting
● Even if the thermostat turns OFF, defrosting continues.
● The 4-way valve, bypass valve, outdoor fan, and indoor fan are OFF.
48
Page 49
(3) Defrost interval
The defrost interval time is determined as follows.
● Initial defrost interval is 50 minutes.
● The defrost interval after defrosting depends on the preceding defrosting time as shown below.
Defrosting operation timeNext defrost interval
3 minutes or below120 minutes
3 to 7 minutes80 minutes
7 to 10 minutes60 minutes
10 to 15 minutes40 minutes
15 minutes (Maximum)30 minutes
NOTE1:If the unit stops during defrosting , the next defrost interval will be 50 minutes.
NOTE2:If a protection function works for the first time during defrosting, the compressor will stop.
After a 3-minute time delay, defrosting will restart. In this case, a 3-minute time delay is included with the defrosting
time.
If the protection function works for the second time, the unit stops operation and displays the check code.
The next defrost interval will be 30 mimutes.
NOTE3:When the defrosting has ended, the total time of the compressor operation is cleard.
(4) Termination conditions
Defrosting finishes when any of the following conditions are satisfied.
1Defrosting has continued for 15 munites.
2Outdoor coil thermistor reads 72˚F or above for the first 75 seconds after defrosting start-up.
3Outdoor coil thermistor reads 46˚F or above after the 75-second defrosting.
4Power ON/OFF button is turned OFF during defrosting.
3-6 Actuators
(1) Bypass valve control
<Cooling mode>
1When the unit stops due to the coil frost prevention, the bypass valve turns ON. When one hour has passed since the
compressor stopped, the bypass valve returns to OFF.
2When the compressor operates with the bypass valve at ON for more than 30 minutes, the bypass valve turns OFF.
3When the compressor stops with the bypass valve at OFF, the bypass valve turns ON and remains ON for three min-
utes.
<Heating mode>
1When the unit starts for the first time after the circuit breaker has been turned ON, or when it starts after the compressor
OFF of 30 minutes or more, if the outdoor coil thermistor reads 54˚F or more, the bypass valve turns ON.
2When the high pressure switch (63H1) works, the bypass valve turns ON.
3When the bypass has been ON for 30 minutes:
● If the high pressure switch has already returned, the bypass valve turns to OFF.
● If not, the fan output step keeps 70 for three minutes. Meanwhile, if the high pressure switch returns, the bypass valve
turns OFF. Otherwise the normal fan control starts.
4When the operation mode changes or stops, the bypass valve turns ON and remains ON for three minutes.
<Defrosting operation>
1The bypass valve is OFF.
(2) Crankcase heater control
1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hour
after the compressor stops.
2Without jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and
1-hour OFF.
49
Page 50
3-7 Service functions
(1) Compulsory defrositng
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.
● During HEAT mode
● The compressor is ON.
● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)
● The outdoor coil thermistor reads 46°F or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normal
defrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-output
While the compressor is operating (exept during defrosting) and the fan output step is indicated by LED, pressing SW2
fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.
1SW2 is pressed again.
2SW3 setting is changed.
3The compressor stops.
4Defrosting operation starts.
(3) Function of switches on the outdoor controller board
SW1: Clears the check code memory (push-button switch)
SW2: Switches the output state indication and the check code display (push-button switch)
SW3-1,2: Switches the output state indication items (dip swtich)
For further information, refer to page 50.
(4) 100% fan output
Fan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting.
Open-circuit of CN22 restarts the normal fan control.
(5) Time shorterning
Short circuit of the connector CN21 shortens the time as follows
1Fan control period: 30 seconds → 3 seconds
2Three-minutes time delay function : 3 minites → 3 seconds
3Max. time of defrosting : 15 minites → 15 seconds
4Defrost interval : 30 ~ 120 minutes → 3 ~ 12 seconds
5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes → 3 seconds
6Compressor ON time to start other functions : x minutes → x seconds
7Crankcase heater operation : 1 hour → 6 seconds
50
Page 51
9
TROUBLESHOOTING
1.TROUBLE IN TEST RUN
SymptomCauseCheck points
The display “CENTRALLY
CONTROLLED” on remote
controller does not disappear.
When remote controller
POWER button is turned
ON, the check code
“EO”appears.
1) Wrong address setting of remote controller/indoor controller board.
2) Timer adapter is connected to the
remote controller.
3) Signal transmission error between
indoor unit and remote controller.
1) Signal transmission error between
indoor unit and remote controller
1) Check the address setting of remote controller
and indoor controller.
2) Make sure the timer adapter is used correctly.
3) 1 Turn another remote controller’s DIP SW17-
7 ON to make it sub controller.
2 Connect the sub controller to the unit, and
turn circuit breaker ON.
● If the display “centrally controlled” disappears, replace the original remote controller.
● If the display remains the same, replace the
indoor controller board.
1) 1 Connect a sub remote controller.
2 Turn circuit breaker ON.
If the display “centrally controlled” remains,
replace the indoor controller board.
3 If the display disappears, turn the remote
controller POWER button ON and check as
follows.
Remote controller
1
Operating Display
2
Operating Display
3
NO Display
4
NO Display
Sub remote controller
EO Display
Operating Display
EO Display
Operating Display
Malfunction of
indoor Unit
Malfunction of
Remote controller
Malfunction of
indoor Unit and
Remote Controller
Malfunction of
Remote controller
Malfunction
When remote controller
POWER button is turned
ON, operating display
appears, but disappears
soon.
Despite turning POWER
button ON, the remote
controller display does not
appear.
1) Short circuit of indoor/outdoor connecting wire
2) Short circuit of transmission wire.
3) Short circuit of drain sensor heater circuit.
4) Wrong operation of remote controller
due to noise wave emitted by other
appliances.
1) Damaged remote controller.
2) Short circuit of transmission wire.
3) Bad contact of indoor CN40.
4) CN40 is attached to a sub unit.
5) Damaged transformer.
6) Bad contact of CN4T.
7) Blown fuse.
8) Circuit breaker OFF.
1), 2) Check the wire
3) Measure the resistance of the drain sensor
connector CN50 1 - 3. Normal resistance
should be 82Ω.
4) Turn the circuit breaker OFF, and then turn
ON.
If the remote controller remains abnormal,
despite the above measures, replace the indoor
controller board.
1) Measure the voltage between terminals of
remote controller. If no voltage, remove the
wire from the terminals and measure the voltage between wires. If the voltage is between
6VDC and 12V, replace the remote controller.
2) ~ 8) Check each point.
If it is not defective, replace the indoor
controller board.
51
Page 52
2. SELF DIAGNOSTIC FUNCTION WITH REMOTE CONTROLLER
MITSUBISHI ELECTRIC
-CENTRALLY CONTROLLED STAND BY
DEFROST
ON
CHECK DRY
COOL
HEAT
CHECK
SET TEMP
TIMER OFF
AUTO STOP
AUTO START
F
HR
F
LOW HIGH
AUTO RETURN
CHECK TEST RUN
POWER
ON/OFF
HEAT
SET
TEMPERATURE
AUTO COOL/DRY
COOLERWARMER
TIMERMODEHOURS
FAN SPEED LOW/HIOGH
AIR
DISCHARGE
UP/DOWN
SWING
STOP
CHECKTEST RUN
2-1 When malfunction occurs during operation
When a malfunction occurs, the indoor and outdoor units stop and the malfunction is displayed on the LCD of the remote
controller.
(A) ON the set temperature display part, “CHECK” appears, and
the unit address and the check code are displayed alternately
at one-second intervals. (Check mode)
Example
CHECK
0
°F
Alternately
displayed
CHECK
p1
CHECK mode
°F
(2) When one remote controller controls several units in the group control,
the LCD shows the unit address and check code of the first malfunctioning unit.
(3) To cancel the check mode, press the POWER button. In
ON/OFF
remote ON/OFF control, press the remote ON/OFF switch. In centralized control, turn OFF the POWER ON/OFF button of centralized controller.
CHECK button
NOTE: The latest check code is memorized, even if the check mode is cancelled by the way mentioned above. It takes
60 seconds maximum to display the memorized check code.
2-2 How to use the self diagnostic function for service
A. For normal control with one unit and one remote controller
(1) Pressing the CHECK button on the remote controller twice starts the self diagnostic function.
(2) During the self diagnostic function, “CHECK” appears at two positions on the remote controller display. Then, at least
10 seconds later, the unit address and the check code is alternately displayed at one-second intervals.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
2-3 For group control using one remote controller
(1) Press the WARMER or COOLER button on the remote controller to advance or go back to the unit address. Each time
WARMER button is pressed, the unit address advances by one. Each time COOLER button is pressed, the unit
address goes back by one.
The check code and the unit address, appear alternately.
(2) The check code “U8” means no malfunction has occurred since installation.
The check code “EO” means the following conditions:
● The unit address displayed on the remote controller does not apply to any unit.
● power is not supplied to the unit.
● Signal transmitting / receiving circuit is abnormal.
(3) Check and repair the unit according to the check code. (Refer to the next page.)
52
Page 53
Check
code
EO
Diagnosis of malfunctionCauseCheck points
Signal transmitting/receiving
error
(Indoor controller does not
respond to remote controller
signal.)
During individual unit control
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
1) Check the transmission wire.
2) Check with another remote controller. If “EO” is
still indicated, replace the indoor controller
board.
If other check code appears. replace the original remote controller.
Abnormality of room temper-
P1
ature thermistor (RT1)
Abnormality of indoor coil
P2
thermistor (RT2)
Signal transmission error
P3
(Remote controller does not
respond to indoor controller
signal.)
Abnormality of drain sensor1) Bad contact of transmission
P4
1) Bad contact of thermistor
2) Damaged thermistor
1) Bad contact of transmission
wire
2) Signal transmitting/receiving circuit is abnormal.
3) Wrong operation due to noise
wave emitted by other appliances
wire
2) Damaged thermistor
1) Check the thermistor.
2) Measure the resistance of the thermistor.
Normal resistance should be as follows.
32˚F ····15kΩ86˚F···4.3kΩ
50˚F ······9.6kΩ 104˚F···3.0kΩ
68˚F ······6.3kΩ
If the resistance is normal, replace the indoor
controller board.
1) Check the transmission wire.
2) Check with another remote controller.
If “P3” is still indicated, replace the indoor
board.
If other check code appears, replace the original remote controller.
3) Short-circuit between 1 and 2 of CN40 and
attach CN40 to the following units.
● Second unit in twin control
● Second and third units in triple control
● Sub units in group control
1) Check the connector.
2) Measure the resistance of the thermistor 4 - 5.
As for the normal resistance, refer to the case
of P1.
If the resistance is normal, replace the indoor controller board.
Malfunction of drain pump1) Malfunction of drain pump
P5
Coil frost protection is work-
P6
ing.
P7
System error
Abnormality in outdoor unit1) Wrong wiring of indoor/outdoor
P8
2) Damaged drain sensor
1) Short cycle of air cycle
2) Dirty air filter
3) Damaged fan
4) Abnormal refrigerant
1) Wrong address-setting
2) Signal transmitting/receiving circuit of remote controller is
abnormal.
3) Wrong SW6-setting
connecting wire
2) Reversed phase
3) Protection device is working
4) Damaged outdoor coil thermistor
1) Check the drain pump.
2) ● Check the drain sensor.
● Check the drain sensor heater. Normal resistance should be 82Ω.
If the resistance is normal, replace the indoor controller board.
1) Clear obstructions from the air cycle.
2) Clean the air filter
3) Check the fan.
4) Check the refrigerant temperature and pressure.
1) Check the address-setting.
2) Check with another remote controller. If check
code other than “P7” appears, replace the original remote controller.
3) Check SW6 setting.
1) Check the indoor/outdoor connecting wire.
2) Change the connection of electric wiring.
3) Check the protection device.
4) Measure the resistance of the outdoor coil thermistor. If the resistance is normal, replace the
outdoor controller board.
53
Page 54
3.SERVICE DATA INDICATION BY SWITCHES ON OUTDOOR CONTROLLER BOARD
SW3-1
SW3-2
OFF
OFF
Check codeOutput state
Outdoor coil
temperature
(
bit
)
Fan output
step
(
bit
)
Total time of
compressor
operation(Hr
)
OFF
OFF
OFF
ON
ON
OFF
ON
ON
LED
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
Blinking
Reversed phase
Open phase
63H2 function
51C function
26C function
Overheat protection
During 63H1 function
Compressor ON
Outdoor fan ON
4-way valve ON
Bypass valve ON
Crankcase heater ON
Lighting
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
256
512
1024
2048
4096
8192
16384
32768
Outdoor coil thermistor
is abnomal.
Heating operation command from
indoor controller
Compressor ON command from
indoor controller
Input circuit on controller
board is abnormal
Setting dip switchs SW2 and SW3 on the outdoor controller board enables LED to show the output state and check code.
Output state is shown by LED lighting, and check code by blinking.
SW1 : Turning SW1 ON clears the check code. If SW1 is turned ON while the check code is blinking , the indication
changes to output state indication.
NOTE : SW1 is usually available independant of SW3 setting. As an exception, when the check code shows a
reversed phase or an open phase during the power-on-reset state, SW1 is not available.
SW2 : SW2 is turned ON by pressing, and OFF by releasing.
When SW3-1 and SW3-2 are OFF, pressing SW2 changes indication between output state and check code alternately.
When SW2 is turned On with SW3-1 OFF and SW3-2 ON, the compulsory defrosting starts.
SW3 : Output state indication items depend on the combination of SW3-1 ON/OFF and SW3-2 ON/OFF.
Changed alternately by pressing SW2.
54
Page 55
3-1 Outdoor coil temperature
50
Fan output step (bit)
Fan rotational frequency (rpm)
100150200250
800
600
400
200
0
50
Fan output step (bit)
Type
Fan rotational frequency (rpm)
100150200250
800
600
400
200
0
Type
212
˚F
Temperature
176
140
104
68
32
0
(Open 8 bits)(Open 8 bits)(Open 8 bits)
(Short 238 bits)(Short 238 bits)(Short 238 bits)
Number of bits
50100150200255
-4
-40
To obtain data on the outdoor coil temperature, add the number of bits of lighting
LEDs, and see the graph below to find the
temperature.
3-2 Fan output step
To obtain data on the fan output step, add the number of bits of lighting LEDs, and see the graph below to find the fan
rotational frequency.
1PUH18/24EK
2PUH30/36EK
3-3 Total time of compressor operation
Compressor operation time is indicated in 256 hour units. To obtain the compressor operation time, add the hours of lighting LEDs. During the compressor operation time indication, SW2 is not available.
3-4 Check code indication
● When a protection function works for the first time during operation, the operation stops and restarts after the 3-minutes
time delay mode. When the protection function works again, the operation stops. (Check mode) When both SW3-1 and
SW3-2 are OFF, the check code is indicated.
● If the outdoor controller board receives the compressor ON command from the indoor controller board during check
mode the indication changes to output state indication.
● By pressing SW2 duirng normal operation. operation will continue.
● The latest check code is indicated.
55
Page 56
4. TROUBLESHOOTING ACCORDING TO CHECK CODE
Blinking
LED
LD1
LD2
LD3
LD4
LD5
LD6
Diagnosis of malfunctionCauseCheck point
Reversed phasePhases A1, A2, and A3are con-
Open phase● Phase A2is open.
Outdoor coil thermistor is
abnormal. (Open circuit or short
circuit)
High pressure switch (63H2)
function
Thermal relay (51C) function● 51C was connected incor-
Thermal switch (26C) function.● 26C was connected incor-
nected improperly.
● Contact of protector, such as
thermal switch, opened when
power was turned on.
● Outdoor coil thermistor is
broken.
● Thermistor was connected
incorrectly.
● 62H2 was badly connected.
● 63H2 was working.
rectly.
● 51C was working.
rectly.
● 26C is working.
Check the power supply connection.
● Check the power supply.
● Check each protector.
● Measure the resistance of the thermistor.
● Check the thermistor. If normal, replace the out-
● Check 63H2 and the outdoor fan motor.
● Check if refrigerant supply is low.
● Check if air cycle is short-cycled.
● Check 51C, the compressor, and power supply.
● Check 26C.
● Check if refrigerant supply is low.
● Check if the capillary tube is clogged.
door controller board.
LD7
Over heat protection ● The thermistor is broken.
LD8
Input circuit of outdoor controller board is abnormal.
● Coil temperature is over
153˚F.
● Pulse input is abnormal.● Replace the outdoor controller board.
5.WHEN OUTDOOR UNIT DOES NOT WORK
Cause
1) Indoor/outdoor connecting wires are poorly connected.
(Refer to next page.)
2) Power supply is poorly connected.
3) Connector or transformer is broken.
4) Fuse (6A) in the outdoor controller board is blown.
● Measure the resistance of the thermistor.
● Check the outdoor fan motor.
● Check if air cycle is short-cycled.
Check points
1) Check the connecting wires.
2) Check the power supply.
3) Check connectors and transformers.
4) Check the fuse.
56
Page 57
6. WRONG WIRING ON SITE
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
OutdoorIndoor
1
2
3
1
2
3
6-1 Between remote controller and indoor unit
If the wire is disconnected between the remote controller and the indoor unit, nothing is displayed on the remote controller
when the POWER button is pressed. The beep sound will also not be heard.
6-2 Phenomenon due to wrong wiring between indoor and outdoor units
Cooling operation. Several minutes later, check code “P8” appears
on remote controller display.
ONNormal operation.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops, 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOutdoor unit stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops.
Operation stops. 9 minutes later, check code “P8” appears on
ON
remote controller display.
OFFOperation stops. 4-way valve turns OFF.
27 minutes later, check code “P8” appears on remote controller
ON
display.
Disconnection between 3 and 3.
COOL
HEAT
Normal operation.
–
OFFOperation stops. 4-way valve turns ON.
Operation stops. 27 minutes later, check code “P8” appears on
ON
remote controller display.
57
Page 58
7. OTHER TROUBLES AND CAUSES
Vanes do not work.
Unit stops after 5 to
20 seconds operation
Air discharge display
is OFF and air discharge UP/DOWN
button does not operate.
In this case, remote
controller is normal.
Power ON/OFF button
is not available.
t
t
t
Vane motor does not work.
Limit swtich does not work.
Connector is poorly connected.
Vane motor is poorly assembled.
Indoor controller board is damaged.
Protection function is working.
Indoor controller board
deems the auto vanes
are not attached to the
unit.
Horizontal anlgle can
not be detected.
Beep sound is heard,
but display is turned
OFF.
Beep sound is not
heard, and display
remains OFF.
t
t
t
t
“CENTRALLY CONTROLLED” is displayed.
t
Indoor controller is
damaged.
Dip switch setting is
wrong.
Indoor controller is
damaged.
Vane motor is damaged.
Vane motor limit switch
is poorly connected.
Auto vane is wired after
power is turned to ON.
Indoor/outdoor connecting wire is connected
incorrectly.
Indoor/outdoor connecting wire shorts.
Compressor protector is
damaged.
Deicer is broken.
Remote controller is
damaged.
Transmission wire is
poorly connected
Vane motor is damaged.
t
t
Refer to check code on remote controller display.
See page 52.
Vane motor relay is damaged.
Limit switch is damaged.
The size of the cam is wrong.
t
t
t
Vane motor limit switch
is damaged.
Vane motor is damaged.
Poorly connected
Disconnected
Transmission wire is
damaged.
Connector is poorly
connected.
Indoor terminal block is
poorly connected.
Remote controller terminal block is poorly
connected.
8.MR. SLIM/LOSSNAY INTERLOCK OPERATION
<Symptoms that are not malfunctions>
If any of the following symptoms occur, they are not malfunctions.
Symptom
LOSSNAY control switch can not work during interlock operation.
LOSSNAY control switch does not work.
LOSSNAY air speed can not be controlled in interlock operation.
For LOSSNAY, troubleshooting refer to the LOSSNAY technical & service manual.
58
LOSSNAY control switch is effective only while Mr. SLIM is not operating.
LOSSNAY fan speed is fixed to HIGH during interlock operation.
LOSSNAY fan speed LOW/HIGH can be switched only during LOSSNAY individual operation with the LOSSNAY contorl switch.
Cause
Page 59
10
Unit
Remote
controller
UnitUnit
Unit
Remote
controller
UnitUnit
Unit
Remote
controller
UnitUnit
Unit
Remote controll
display board
Remote
controller
UnitUnit
SYSTEM CONTROL
1. VARIETY OF SYSTEM CONTROL FUNCTIONS
1 Group control with
a single remote
controller
(See page 59.)
2 Control using two
remote controllers
(See page 60.)
3 Individual control
by grouping
remote controllers
(See page 61.)
4 Multiple remote
control display
(See page 62.)
❋ Multiple display
adapter
(PAC-SA88HA-E)
is needed.
Many units, installed at different locations, can be started
and controlled with a single remote controller. The remote
controller can be mounted in a different location using a
non-polar two-wire cable, which can be extended up to
500m. Amaximum of 50 units can be controlled with a
single remote controller. All units operate in the same
mode.
Two remote controllers can be used to control either one
unit or a group of units. Units can then be controlled from
a distance or at close range. Units operate according to
the latest command from either remote controller.
By grouping the remote controllers in one place, several
units installed at different locations can be controlled individually, and operation conditions of all units are visible
without a special control board. The control method is the
same as that of the single unit with a single remote controller.
Several units can be controlled with a remote control display board. Operation conditions of all the units are visible with the remote control display board.
Individual control by each remote controller is also possible.
59
Page 60
2. GROUP CONTROL WITH A SINGLE REMOTE CONTROLLER
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
To remote
controller
To next
unit
To next unit
The last unit
dose not have
this wire.
Next unit
electrical box
Master unit
electrical box
123ANE
123ANE
Master
unit
No.1 unitNo.2 unitLast unit
2-wire cable
A maximum of 50 units can be started in order according to the dip switch settings
2-1 How to wire
(1) Connect the remote controller to the double terminal block
on the indoor controller board of the master unit (No.0 unit).
(See Figure 1.)
(2) Connect the double terminal block of the master unit to the
double terminal block of No.1 unit.
(3) Connect the double terminal block of No.1 unit to the dou-
ble terminal block of No.2 unit.
(4) Continue the process until all the units are connected with
two-wire cables. (See Figure 2.)
(5) Remove the connector CN40 from the indoor controller
board of each unit except the master unit. (See Figure 3.)
(6) Set the unit-address of each unit with SW2 on the indoor
controller board following the instructions below.
2-2 How to set unit-address
The unit-address also serves as a successive-start timer which
starts each unit at intervals of 1 second. If two or more units
have the same unit-address in a group control, operation stops
due to system error. Be sure to set SW2 correctly following the
instructions below.
(1) Each lever of SW2 shows the number as follows.
(2) Total number of levers turned to ON shows the address of
the unit.
For example, to set No.3 unit, turn ON SW2-1 and SW2-2.
(3) In this way, set from the. master unit to the last unit.
Do not forget to set the master (No. 0) unit.
Figure 1
Figure 2
Figure 3
Indoor controller board CN40
Should be removed from
all units other than unit
No.0:(Master Unit)
Setting examples
Unit address & start
delay in seconds.
2-3 Unit control
The remote controller can control all units ON/OFF, temperature,air flow, and swing louver. However, the thermostat in
each unit turns ON or OFF individually to adjust to the room temperature.
60
SW2
Master (No. 0) unit
ALL OFF
0
No. 1 unit
1 ON
1
No. 2 unit
2 ON
2
No. 4 unit
3 ON
4
No. 8 unit
4 ON
8
No. 16 unit
5 ON
16
No. 32 unit
6 ON
32
Page 61
Remote
controller
power supply of
control circuit
Remote
ON/OFF
switch
2-wire
remote
controller
cable
Figure 6
Relay box
Timer adapter cables
Timer adapter
PAC-SA89TA-E
3. CONTROL USING TWO REMOTE CONTROLLERS : OPTIONAL REMOTE CONTROLLER
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Individual
operation
Multiple operation
Main remote controllerSub remote controller
Turn SW17-7 ON
(PAC-SK47RC)
Two remote controllers can be used to control either one unit or a group of units. Units operate according to the latest command from either of the two remote controllers.
Before operation, be sure to set one remote controller as the "main controller" and the other as the "sub controller", using dipswitch SW17-7 of the remote controller.
3-1 How to set SW17-7 (See Figure 5.)
(1) For the main remote controller, turn SW17-7 OFF.
(2) For the sub remote controller, turn SW17-7 ON.
3-2 Remote controller LCD indication
(1) The same indications always appear on both the main and sub remote con-
trollers, except during the timer operations.
(2) Timer operations can be set with either of the two remote controllers.
However, LCD indication appears only on the remote controller used for timer
settings.
(3) If both remote controllers are set for timer operation with different time-set-
tings, the timer operation with the shorter remaining-time is effective.
(4) Self-diagnostic function is available with either of the two remote controllers.
If one of the remote controllers is used for the self-diagnostic function, the
other remote controller displays the check mode.
If the self-diagnostic function is reset by either of the two remote controllers,
both remote controllers are reset.
4. REMOTE ON-OFF AND INDIVIDUAL REMOTE CONTROLS
This method is auailable to control one unit or any number of units.
The following operations are available by connecting a relay, a timer adapter (PAC-SA89TA-E), and a remote ON/OFF switch
to the system. Timer adapter is an optional part. Other parts are available on the market.
(A) To start all units in order by remote ON-OFF switch
(B) To stop all units simultaneously by remote ON-OFF switch
(C) To switch between the remote ON-OFF control and the individual remote control
4-1 System
Figure 6 shows the case of three units.The same is the case with any number of units.
61
Page 62
NOTE1 : Install the relay box where it can be serviced easily.
Power
supply
Remote
ON/OFF
switch
No.1 unit
relay box
No.2 unit
relay box
Next unit
T
X2X2
T
Glow switch or pilot lamp can be
combined to easily identify the
on-off mode of SW1 and SW2.
To
No.1
unit
To
No.2
unit
Timer adapter cables
Remote controller
T
X2
SW
1
SW2
T
X2
Remote
controller cable (2-core)
Remote controller
NOTE2 : For control circuit wiring, use a wire of No. 14 AWG or a control cable according to the power supply of control
circuit.
NOTE3 : When the power supply of the control circuit is 220/240V AC,
● Do not connect the control circuit wire to the remote controller cable directly.
● Do not place the control circuit wire and the remote controller cable into the same conduit.
4-2 Basic wiring
Caution : Before starting all units simultaneously by the remote ON-OFF switch, be sure to connect a sequence-start timer
into the remote ON-OFF circuit. Otherwise, a rush of starting current may damage the power supply.
4-3 Switch function of remote ON-OFF switch
SW2
(Switches between remote ON-OFF and individual control)
SW1
(Switches between
remote ON and OFF.)
ON
(Start)
OFF
(Stop)
ON
(Remote ON-OFF control)
All units start together.
w1
Individual control is not available.
All units stop together.
w2
Individual control is not available.
Each unit can be controlled by each
remote controller.
Remote ON-OFF switch is not available.
OFF
(Individual control)
w1 After all units start together, if SW2 is turned OFF, each unit can be individually stopped by each remote controller.
w2 After all units stop together, if SW2 is turned OFF, each unit can be individually started by each remote controller.
5. INDIVIDUAL CONTROL BY GROUPING THE REMOTE CON-
TROLLERS
● Grouping the remote controllers allows individual control and cen-
tralized monitoring of units installed in different places without a
special control board.
● Remote control cables are extendable up to 500m. When the cable
length exceeds 12m, use the double-insulated two-core cable such
as Belden 9407. Also, the cable thickness must be No. 22 AWG or
above.
● When gathering the power ON/OFF switches of air conditioners
near the remote controllers, you should also install the power
ON/OFF switch near each unit to prevent electric trouble during
servicing.
62
Page 63
6. MULTIPLE REMOTE CONTROL DISPLAY
CN51
connector(5P)
GREEN
Power
supply
Electrical insulation is needed.
Wiring at the actual place
Optional multiple display
adapter
The maximumdistance between
indoor board and relay is 10m.
YELLOW
ORANGE
RED
BROWN
5
X1
X1
RL
GL
X2
X2
1
<Wiring >
Power
supply
Remote
controller
cable
Relay box
(Field supply)
Remote
controller
Remote
controller
Remote
controller
3wires
3wires
3wires
2wires
No.1 unitNo.2 unitNo.3 unit
Muitiple remote control
ON-OFF display
(Field supply)
(Operation check)
<System>
Power
supply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote
controller adapter
connect to
the connector CN51
Relay box
5
X1-1
X2-1
1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1
X2
5
1
No.2 unit
X1
X2
5
1
No.3 unit
X1
X2
X1-2
X2-2
X1-3
X2-3
You can control serveral units with a multiple remote control display,by
wiring an optional multipe display adapter (PAC-SA88HA-E) with relays
and lamps on the market.
6-1 How to wire
(1) Connect the multipe display adapter to the connector CN51 on the
indoor controller board.
(2) Wire three of the five wires from the multiple display adapter as shown
1. Removing the lower side of the indoor unit from the installation plate
(1) Remove the 2 screws.
Hang the indoor unit hangers to the catches on the installation plate.
Figure 1
2. Removing the right side panel
(1) Remove the 2 screws of the right side panel:one on the
bottom and the other on the upper right-hand side.
(2) Disconnect the connector from the adapter case.
(3) Sliding the right side panel to the right, pull it out toward
you.
3. Removing the indoor controller board
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Disconnect the connectors on the indoor controller board.
(4) To unhook the catches on the right-hand side of the indoor
controller board, pull the left-hand side toward you and lift
up the cover to the right. Then the indoor controller board
can be removed.
Figure 2
Photo 1
Indoor controller
board
Electrical parts
box cover
Catches
4. Removing the ielectrical parts box
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the room temperature thermistor and the indoor
coil thermistor.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
(5) Remove the 2 screws of the electrical parts box.
(6) Disconnect the connector of the heater lead wire connec-
tor.
(7) Disconnect the connector of the fan motor lead wire.
(8) Remove the electrical parts box.
64
Photo 2
Room temperature thermister
Indoor coil thermister
Screws
Electrical parts
box
Page 65
OPERATING PROCEDUREPHOTOS&ILLUSTRATION
Catch on the left side panel
Catch on
the unit
(8) Remove the screws of the indoor controller board case,
and pull out the indoor controller board case.
Then the transformer and the capacitor and relay can be
serviced.
5. Removing the vane motor
(1) Remove the right side panel.
(2) Remove the screw of the electrical parts box cover, and
remove the cover.
(3) Remove the 2 screws of the vane motor, and remove the
motor from the shaft.
(4) Disconnect the vane motor connector on the indoor con-
troller board.
Photo 3
Capacitor
Indoor controller
board case
Photo 4
Vane motor
Relay
Transformer
Electrical parts box
Screws
Indoor controller board
6 Removing the intake grills
(1) Remove the right side panel.
(2) To remove the left side panel, remove the screw on the
bottom and the screw on the upper left-hand side. (See
Figure 3.)
1. Press up this side of the left side panel to unhook the
catch on the panel from the catch on the unit.
2. Slide the left side panel to the left to remove the panel.
Note: Fix the unit to the metal fixture securely
(3) Remove the air filters.
(4) Hold and press the center cover to remove.
(5) Remove the screws of the grills.
(6) Pull the lower side of the grill toward you and slide the
upper to the right to remove the grills.
7. Removing the drain pan
(1) Remove the left and right side panels.
(2) Remove the grills.
(3) Remove the electrical parts box cover.
(4) Loosen the drain hose band to remove.
(5) Remove the 3 screws of the drain pan, and slide the drain
pan toward you to remove.
Figure 3
Photo 5
Left side panel
Photo 6
Slide to the
right
Screws for grills
Drain pan
Screws
Grills
Drain hose
band
Drain hose
65
Page 66
OPERATING PROCEDUREPHOTOS
8. Removing the lineflow fan and the fan motor
(1) Remove the left and right side panels.
(2) Remove the grills.
(3) Remove the electrical parts box.
(4) Remove the drain pan.
(5) Loosen the screw that fixes the lineflow fan to the fan
motor. (See Photo 7. )
(6) Remove the 4 screws of the motor fixture, and remove the
fan motor and the motor fixture at a time (See Photo 8.)
(7) Remove the screws of the left and right motor supports,
and remove the motor supports and the fan motor. (See
Photo 9.)
(8) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(9) Remove the screw of the center support, and remove the
support. (See Photo 10. )
(10) Pull the left-hand side of the heat exchanger toward you,
and remove the lineflow fan.
Photo 11
Heat exchanger
Bearing support
Photo 7
Photo 8
Photo 9
Screw
Motor support
Lineflow fan
Fan motor
Screw
Fan motor
Screw
Fan motor
Motor fixture
Screw
Lineflow fan
9. Removing the electrical heater.
(1) Remove the left and right side panels.
(2) Remove the grills.
(3) Remove the drain pan.
(4) Loosen the screw that fixes the lineflow fan to the fan
motor.(See Photo 7.)
(5) Remove the screw of the center support, and remove the
support. (See Photo 10.)
(6) Remove the 2 screws on the left and right sides of the heat
exchanger, and pull the bearing support toward you. (See
Photo 11.)
(7) Pull the left-hard side of the heat exchanger toward you,
and remove the lineflow fan.
(8) Remove the heater fixing screws (1 screw each on right
and left sides), and slide the heater element to the left to
remove the heater.
Photo 10
Photo 12
Heat exchanger
Lineflow fan
Heater element
Motor
support
ScrewCenter support
Heater fixing screws
66
Page 67
13-4 Outdoor unit (PUH18EK)
Outdoor
controller
board
Transformer
Capacitor
Contactor
Terminal block
Screws
Propeller
Motor support
Separator support plate
High-pressure switch
Lead
connectors
Valve bed
Crankcase heater
Propeller nut
Screws
Top panel
Service
panel
Cover
panel
Front panel
OPERATING PROCEDUREPHOTOS
1. Electrical parts
(1) Remove top panel (3 screws in front, 2 screws in rear)
(2) Remove cover panel (1 screw).
The panel is anchored by clicks to the side panel.
Remove by pulling towards you.
(3) Remove cover panel (1 screw).
The panel is anchored by clicks on the right and left sides.
After removing the screw, pull the panel down and remove it
by pulling towards you.
Photo 1
Photo 2
2. Fan motor
(1) Remove front panel (3 screws).
Open the panel to a 45 degree angle and lift to remove. The
panel is clasped at three points on the left side.
(2) Remove propeller (1 set nut).
(3) Remove fan motor (3 screws).
Remove lead connectors.
Photo 3
67
Page 68
OPERATING PROCEDUREPHOTOS
Heat exchanger
Accumulator
Charge plug
Ball valve
Compressor
3. Heat Exchanger, Compressor
(1) Remove the rear panel (2 screws in front, 1 screw on the
side, 3 screws in the rear). Remove the valve bed, and open
the rear panel to the rear to remove.
NOTE :
All panels are clasped, and must be removed by shifting up
and down.
(2) Remove right side panel (4 screws).
(3) Remove rear guard (3 screws).
(4) Remove separator support plate (4 screws).
(5) Remove motor support (2 screws).
(6) Remove valve bed (5 screws). The valve bed is clasped on
the right and left sides. Lift to remove.
(7) Remove the electrical parts box.
Remove the respective connectors from highpressure
switch, crank case heater, shell thermo, and fan motor lead.
(8) Remove separator (2 screws).
(9) Remove heat exchanger (2 screws).
Disconnect the welded section of pipe.
(10) Remove compressor (3 set nuts).
Remove the weldment of the compressor suction pipe and
discharge pipe.
Photo 4
Screws
Photo 5
Screws
68
Photo 6
Page 69
13-5 Outdoor unit (PUH24EK)
Screws
Panel cover
Compressor protector
Run capacitor
52C relay
Terminal block
Screws
Motor support
Separator support place
High-pressure
switch
Valve bed
Crank case heater
Propeller fan
Propeller
nut
OPERATING PROCEDUREPHOTOS
1. Electrical parts
(1) Remove top panel (3 screws in front, 2 screws in rear)
(2) Remove cover panel (1 screw).
The panel is anchored by clicks to the side panel.
Remove by pulling towards you.
(3) Remove cover panel (1 screw).
The panel is clasped on the right and left sides. After removing the screw, pull the panel down and remove it by pulling
towards you.
Photo 1
Photo 2
2. Fan motor
(1) Remove front panel (3 screws).
Open the panel to a 45 degree angle and lift to remove. The
panel is clasped at three points on the left side.
(2) Remove propeller (1 set nut).
(3) Remove fan motor (3 screws).
Remove lead connectors.
Photo 3
69
Page 70
OPERATING PROCEDUREPHOTOS
Heat exchanger
Accumulator
Charge plug
Ball valve
Compressor
3. Heat Exchanger, Compressor
(1) Remove the rear / right side panel (2 screws in front, 1 screw
on the side, 3 screws in the rear).
Remove the electrical box, valve bed, and open to the rear
to remove (anchors attached).
(2) Remove right side panel (4 screws).
(3) Remove rear guard (3 screws).
(4) Remove separator support plate (4 screws).
(5) Remove motor support (2 screws).
(6) Remove valve bed (5 screws). The valve bed is clasped on
the right and left sides. Lift to remove.
(7) Remove the electrical parts box.
Remove the respective connectors from highpressure
switch, Low-pressure switch, crank case heater, shell ther-
mo, and fan motor lead.
(8) Remove separator (2 screws).
(9) Remove heat exchanger (2 screws).
Remove piping weld zone.
(10) Remove compressor (3 set nuts).
Remove the weldment of the compressor suction pipe and
discharge pipe.
NOTE :
All panels are clasped, and must be removed by shifting up
and down.
Screws
Photo 4
Screws
Photo 5
70
Photo 6
Page 71
PART LIST12
No.
Parts No.Parts NameSpecifications
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Q'ty / set
PKH
24FK 30FK18FK
Part number that are circled not shown in the figure.
TOP PANEL
FRONT PANEL
FAN GUARD
SERVICE PANEL
SIDE PANEL (LEFT)
REAR PANEL
PANEL COVER
REAR GUARD
BASE ASSEMBLY
30EK
1
1
2
1
1
1
1
1
1
Q'ty / set
PUH
36EK
1
1
2
1
1
1
1
1
1
Remarks
(Drawing No.)
Wiring
Diagram
Symbol
Page 83
13
Part No
Pipe length
Pipe size OD
Connection method
PAC-05FFS-E
5m
PAC-07FFS-E
7m
Liquid : 3/8 Gas : 5/8
Indoor unit : Flared Outdoor unit : Flared
PAC-10FFS-E
10m
PAC-15FFS-E
15m
28˚C
26
˚C
8:00
Normal
operation
23:00
Setback
operation
8:00
Normal
operation
Part No
Pipe length
Pipe size OD
Connection method
PAC-SC51PI-E
5m
PAC-SC52PI-E
7m
Liquid : 1/2 Gas : 3/4
Indoor unit : Flared Outdoor unit : Flared
PAC-SC53PI-E
10m
PAC-SC54PI-E
15m
OPTIONAL PARTS
1. REFRIGERANT PIPES
FOR model: PKH18/24FK
FOR model : PKH30/36FK
Note 1. How to connect refrigerant pipes.
Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as the
connection takes no more than 5 minutes, no air will enter, and there will be no need for air purging. Remove the blind
caps and make the connections within 5 minutes. After the connections for the indoor and outdoor units are made,
open the stop valve on the outdoor unit to allow refrigerant gas to flow.
If piping length exceeds 5m,an additional charge of refrigerant is needed.
Note 2. The following main parts are contained in the optional refrigerant piping kit.
When using a program timer, PAC-SK65PT, a program timer adapter (PAC-825AD) is also needed.
Part No.PAC-SK65PT (with set back function)
Model NameProgram timer
2-1 Program timer specifications
Part nameProgram timer
Part No.PAC-SK65PT
Exterior dimensions120 o 120 o 15mm
InstallationWall mount
Type of clockQuartz
Clock accuracy± 50s / month
Display — Time
— Week
— Timer setting
Program cycle24 hours
Timer setting unit30 minutes
No. of set points48 / day
Power rating5V DC
Se back functionProvided
2-2 Feature of program timer
(1) Daily timer function
Daily timer can be set in 30 minutes units for up to 24 hours.
Each unit can be set for unit ON, unit OFF, or setback operation.
(2) Setback operation (PAC-SK65PT)
Set back operation is useful for reducing running costs
e.g. At a hotel with a 24-hour system
8:00~23:00 Cooling operation with set temperature at 26°C
23:00~8:00 Setback operation with 2 degrees of setback
As shown in the chart on the right, the set temperature rises 2 degrees
automatically during the setback operation. When the setback operation
ends, nomal operation will begin.
(3) Weekly timer function
Daily timer function can apply to each day of the week.
(1) Install the program timer next to the remote controller the same way as the remote controller is installed.
(2) Connect the program timer and the remote controller with a 6-wire cable as shown in the figure below
NOTE:While the program timer is connected to the remote controller, the
24hour ON/OFF timer on the remote controller will not operate.
2-4 Names and functions
<PAC-SK65PT>
Mode selector button :Using this button to select ¨MONITOR¨ or
¨SET¨ mode.
¨MONITOR¨ : Indicates the current timer setting. All buttons
SET / MONITOR
except will not work. This is the
normal status.
¨SET¨ : ¨SET¨ is used to set the time, change the day of the
week, and program the daily and weekly timer.
Mode dispay
Current time
Current day
Weekly timer
Daily timer dislay
NOTE : Display above
is only an exanple
display
display
display
Set back
display
Clock adjustment button : Used to adjust the current time. Press
AHEAD
Each time the button is pressed the time
advances by 1 minute. Pressing continuously advances 1 minute in a 0.5 second
interval. When the lower digit of minute
becomes 0 the indication advances in 10
minutes unit. button is used for
reversing the time. Each time the button
is pressed the time reverses by 1 minute.
Pressing continuously reverses the time
by 1 minute in a 0.5 second interval.
When the lower digit of minute becomes 0
the indication reverses in 10 minutes unit.
Day setting button : Used to adjust the day of the week.
Pressing button moves the day
BACK
light display in the order of S
Weekly timer button : Used to set the weekly timer.
Set back button : Used to set the set back amount.
Set back can bee set in the range of 1 to 48˚F
in 34˚F unit.
Daily timer button : Used to set the timer settings in units of 30
minutes.
button to advance the time.
BACK
➛M➛T➛W
3. TIMER ADAPTER
This adapter is needed for system control and for operation via external contacts. Adapter connection is described on page
57.
84
Part No.PAC-SA89TA-E
ORN1
BRN
RED
2
3
Page 85
4. MULTIPLE REMOTE CONTROLLER ADAPTER
This adapter is needed for remote indication (operation/check). Adapter connection is described on page 69.
Part No.PAC-SA88HA-E
1
2
3
4
5
BRN
RED
ORN
YLW
GRN
5. CENTRALIZED REMOTE CONTROLLER
Allows individual or combined control of up to 16 units. When using the PAC-805RC, the program timer adapter (PAC825AD)is also needed. See page 90.
Part No.PAC-805RC
5-1. Dimensions
12
113
56.3
11
23.5
Unit : mm
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
117
POWER
ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
8
113
ENGAGED
GROUP
12345678910
GROUP
SELECTION
117
ACTIVE BYPASS
DUAL CENTRAL
PROGRAM
TIMER
CONTROLLER
OPERATION
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
5-2. Functions
"ENGAGED" indicator
When this indicator is lit, transmission is in
progress and all switches are inoperative.
DUAL/CENTRAL switch
This change-over switch governing the
operation of the accessory remote controller.
"DUAL"
Instructions from both the accessory
remote controller and the centralized
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
remote controller are valid. (Priority given
to the last instruction received.)
"CENTRAL"
ON/OFF switching by the accessory
remote controller is invalidated. Controll is
by the centralized remote controller only.
Initial setting is "DUAL".
LCD Matrix Display
This display indicates the operational status of all connected units either by steady
lighting or by flashing.
Independent “DUAL / CENTRAL” and “ACTIVE / BYPASS” setting of all the groups is
possible. When the power supply to the centralized remote controller is cut due to
power failure, all settings will return to original “DUAL” and “BYPASS”.
POWER
ON/OFF
AHEAD
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
MITSUBISHI ELECTRIC
POWER ON/OFF switch
Operation ON/OFF switch.
▲BACK ▼AHEAD buttons
These buttons are used to designate
the attached unit(s). (They designate
the unit that is centrally controlled.)
●When group “00” is designated; collective ON/OFF instruction is sent to all
units.
●When group “01”-“16“ is designated;
ON/OFF instruction is sent to the designated units only.
ACTIVE/BYPASS switch
This is a change-over switch for the
program timer.
(It selects timer operation on the program timer.)
Use “BYPASS” when a program timer
is not connected.
“ACTIVE”
The switch tums ON/OFF operational
instructions from the program timer
automatically.
“BYPASS”
ON/OFF Operation is by the centralized remote controller only.
Initial setting is “BYPASS”.
85
Page 86
5-3 Connection method
(1) Connections in the power supply cord.
1. Connect the power supply cord to the power supply terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V AV (220, 230, 240V) to
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap. Use a Ø1.6
(AWG 14) or above two-wire cable for the transmission line.
CAUTION : Never connect the power supply cord to the transmission terminal-block.
TERMINAL-BLOCK
FOR TRANSMISSION
TERMINAL-BLOCK
OF POWER SUPPLY
A N.
Transmission
Tie-wrap
TRANSFORMER
A N E
Fuse(5A)
Tie-wrap
(W)(R) (O)
(BR)
200
220
230
T
(Y)
240
5A
A
N
E
Wiring has to be changed when
a 200,230 or 240V power is used.
(2) Connection method of centralized remote controller and power supply board.
1. Connect the centralized remote controller and power supply board with a non-polar, two-wire cable.
To adaptor's
terminal-block
Centralized remote
controller
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
Non-polar,
two-wire cable
Power supply board box
To adaptor's
terminal-block
POWER
SUPPLY
86
2. Wiring diagram3. Be sure to set the maximum address number with the
dipswitch SW17 on the centralized remote controller.
BACK
ACTIVE
BYPASS
DUAL
CENTRAL
10 9 8 7 6 5 4 3 2 1
POWER
ON/OFF
AHEAD
Dip switch
SW17
Centralized
remote controller
Power supply
board
ENGAGED
GROUP
12345678910
ACTIVE BYPASS
DUAL CENTRAL
GROUP
SELECTION
PROGRAM
TIMER
CONTROLLER
OPERATION
Page 87
6. PROGRAM TIMER ADAPTER
Length : 2m (6' 7")
Length : 2m (6' 7")
Length : 2m (6' 7")
This adapter is needed when a program timer(PAC-SK65PT)or a centralized remote controller(PAC-805RC)is used.
6-2 Connection method
Connection and wiring methods differ with the type of the indoor unit used. Confirm the type before carrying out
the work.
(1) Connections in the adapter box
1. Connect the power supply cord to the terminal-block and fix it in-place with a tie-wrap.
Connect a single phase 200V (220, 230, 240V) AV to A N.
As E is the GND terminal, be sure to ground the earth wire.
2. Connect the transmission line to the transmission terminal-block and fix it in-place with a tie-wrap (when a
centralized remote controller is being used).
CAUTION : Never connect the power supply cord to the transmission terminal-block
Fig-1Fig-2
TERMINAL-BLOCK
FOR
TRANSMISSION
Tie-wrap
Transmission cord
CN22
Dip switch
TRANS
CN1 CN21 CN51 CN30CN42 CN50 CN40
Fuse(5A)
TRANSFORMER
(AG)
SW1
A N E
POWER SUPPLY CORD
TERMINAL-BLOCK
FOR POWER
SUPPLY
Tie-wrap
Terminal block for
transmission to
program timer or
centralized remote
controller
Wiring has to be changed when 200V power supply is used.
(W)
CN22
TRANS
(B)
200
SW1
T
(Y)
240
220
5A
A
POWER
SUPPLY
N
E
(2) When the centralized remote controller is used, set the address number with the dipswitch SW1 of the pro-
gram timer adapter.
87
Page 88
cCopyright 1997 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD.
Issued in Jun. 1997. No. OC120 5020
New publication, effective Jun. 1997
Specifications subject to change without notice