DATABOOK describes the technical specifications of MITSUBISHI ELECTRIC Corp.'s CITYMULTI air conditioning
system products.
In this DATABOOK for ground source application, information on water-cooled heat source unit PQHY-P Y(S)HM-A/
PQRY-P Y(S)HM-A, with the connection of standard CITY MULTI indoor unit series, Air to Water series, and Close
Control PFD series are specified.
We recommend DATABOOK users to read carefully and take advantage of all the contents inside to design the CITY
MULTI air conditioning system and/or to prepare documents for promotions.
Along with the DATABOOK, MITSUBISHI ELECTRIC provides a Design-Tool software to ensure the users to design
the system correctly and simplify the calculations. Please contact your local distributor for this software.
Please be notified that specifications are subject to change without notice due to continual improvements of the product.
For any inquiries, please contact your local distributor.
i
Contents
I Brine information
1. Brine freezing temperature ........................................................................................................ 1
(3)Center of gravity ......................................................................................................................................24
(6)Capacity tables with indoor units .............................................................................................................30
(6)-1 Cooling capacity with standard indoor units .................................................................................30
(6)-2 Heating capacity with standard indoor units ................................................................................. 43
(7)Correction by total indoor .........................................................................................................................44
(8)Correction by refrigerant piping length ..................................................................................................... 46
(9)Correction by water temperature (For heat source unit) .......................................................................... 49
(9)-1 Connection with standard CITY MULTI indoor units .................................................................... 49
(9)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) ...............................................................49
(9)-3 Connection with PFD-P250/500VM-E .......................................................................................... 50
(10)Correction by water flow rate (For heat source unit) ..............................................................................51
(10)-1 Connection with standard CITY MULTI indoor units .................................................................... 51
(10)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) ............................................................... 51
(10)-3 Connection with PFD-P250/500VM-E .......................................................................................... 51
(11)Correction by indoor temperature .......................................................................................................... 52
(11)-1 Connection with standard CITY MULTI indoor units .................................................................... 52
(11)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) ............................................................... 52
(11)-3 Connection with PFD-P250/500VM-E .......................................................................................... 52
(12)Correction by water flow rate (For PWFY-P100/200VM-E-AU (HEX unit)) ............................................ 53
(12)-1 Connection with PWFY-P100VM-E-AU (HEX unit) ...................................................................... 53
(12)-2 Connection with PWFY-P200VM-E-AU (HEX unit) ...................................................................... 53
(13)Water pressure drop correction by water volume ................................................................................. 54
(13)-1 Heat source unit correction
(Connection with Standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU,
(3)Center of gravity ......................................................................................................................................73
(6)Capacity tables with indoor units .............................................................................................................77
(6)-1 Cooling capacity with standard indoor units .................................................................................77
(6)-2 Heating capacity with standard indoor units ................................................................................. 90
(7)Correction by total indoor .........................................................................................................................91
(8)Correction by refrigerant piping length ..................................................................................................... 92
(9)Correction by port counts of the BC controller ........................................................................................93
(10)Correction by water temperature (For heat source unit) ........................................................................94
(10)-1 Connection with standard CITY MULTI indoor units .................................................................... 94
(10)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) ................................................................ 94
(10)-3 Connection with PWFY-P100VM-E-BU (Booster unit) ................................................................. 95
(10)-4 Connection with PWFY-P100VM-E-BU (Booster unit) + WCB Energy saving mode* ................. 96
(11)Correction by water flow rate (For heat source unit) ..............................................................................97
(11)-1 Connection with standard CITY MULTI indoor units .................................................................... 97
(11)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) ............................................................... 97
(11)-3 Connection with PWFY-P100VM-E-BU (Booster unit) ................................................................. 97
(12)Correction by indoor temperature ..........................................................................................
(12)-1 Connection with standard CITY MULTI indoor units .................................................................... 98
(12)-2 Connection with PWFY-P100/200VM-E-AU (HEX unit) ............................................................... 98
(12)-3 Connection with PWFY-P100VM-E-BU (Booster unit) ................................................................. 98
(13)Correction by water flow rate
(For PWFY-P100/200VM-E-AU (HEX unit) and PWFY-P100VM-E-BU (Booster unit) ........................... 98
(13)-1 Connection with PWFY-P100VM-E-AU (HEX unit) ..................................................................... 98
(13)-2 Connection with PWFY-P200VM-E-AU (HEX unit) ...................................................................... 99
(13)-3 Connection with PWFY-P100VM-E-BU (Booster unit) ................................................................. 99
(14)Water pressure drop correction by water volume ............................................................................... 100
(14)-1 Heat source unit correction
(Connection with Standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU,
The graph was referred from chemical company data.
But Freezing Temperature condition will be slightly different based on each company.
Please confirm detail data to the chemical company directly.
It is recommended to set the brine concentration to a percentage that will keep the freezing
temperature at -15deg
°C or less.
1.Brine freezing temperature
Brine concentration is decided by the freezing temperature. First, it is necessary to decide the freezing temperature and find
out brine concentration which will correspond to the freezing temperature.
- 1 -
2.Capacity correction by brine concentration (For heat source unit)
Brine concentration [wt%]
Propylene Glycol
Ethylene Glycol
Propylene Glycol
Ethylene Glycol
Ratio of cooling capacity
1
0.95
0.9
0.85
0%20%40%60%80%100%
Brine concentration [wt%]
Propylene Glycol
Ethylene Glycol
Propylene Glycol
Ethylene Glycol
Ratio of cooling input
1.30
1.25
1.20
1.15
1.10
1.05
1.00
0%20%40%60%80%100%
Brine concentration [wt%]
Propylene Glycol
Ethylene Glycol
Propylene Glycol
Ethylene Glycol
Ratio of heating capacity
1.00
0.95
0.90
0.85
0.80
0.75
0.70
0%20%40%60%80%100%
Brine concentration [wt%]
Propylene Glycol
Ethylene Glycol
Propylene Glycol
Ethylene Glycol
Ratio of heating input
1
0.95
0.9
0.85
0.8
0%20%40%60%80%100%
PQHY
PQRY
IU IU
Cooling
Heating
Depending on the freezing temperature and brine concentration, the ratio of unit capacity will change.
As shown in the line diagram, higher the brine concentration, the lower the ratio of capacity becomes.
- 2 -
3.Pressure drop correction by brine concentration (For heat source unit)
*The specification data is
subject to rounding variation.
Wiring
Notes:
Standard attachment
Document
Operating volume range
m3 / h
Inverter
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
17
Joint: CMY-Y102S-G2
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
DrawingExternal
Accessory
Water flow rate
m
3
/ h
L/min
Pressure drop kPa
mm
Compressor
in.
MPa
kg(lbs)
High pressure protection
Net weight
HIC circuit (HIC: Heat Inter-Changer)
Water volume in plate
Water pressure Max.
Compressor
wate
r
Circulating
cfm
96
3.4
MEL32
1,160(1,100 without legs) x 880 x 550
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Installation Manual
Power source
kW
h / lack)lanimoN(*1
6.6-6.2-6.0
PQHY-P200YHM-A(For Ground source)
3-phase 4-wire 380-400-415V 50/60Hz
19,300
22.4
3.92
76,400*1 BTU / h
Indoor unit
Temp. range of
Starting method
Type x Quantit
y
Manufacture
Power input
).ni(mmtnaregirfeR
mm(in.)
Liquid pipe
Gas pipe
Current input
(Nominal)
D.B.
*2
COP
°C
Indoor
Temp. range ofIndoor
Model
External finish
Total capacity
piping diameter
Circulating water
°C
connectable
Model / Quantity
heating
21,500
5.76
Type x original charge
Control
l
Acrylic painted steel plate
Over-heat protection
R410A x 5.0kg (12lbs)
Heat exchangerplate type
-
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
(1)
Specification
(1)-1 Heat source units specification for standard combination
(Standard CITY MULTI indoor units, PWFY-P100/200VM-E-AU)
- 5 -
*1
*2
-
plate type Heat exchanger
Over-heat protection
Acrylic painted steel plate
l
Type x original charge
Control
5.76
27,100
Circulating water
°C
connectable
Model / Quantity
heating
Model
External finish
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range ofIndoor
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
Starting method
Type x Quantit
y
Manufacture
BTU / h
Indoor unit
Temp. range of
*1
28.0
5.45
95,500
9.2-8.7-8.4
PQHY-P250YHM-A(For Ground source)
3-phase 4-wire 380-400-415V 50/60Hz
24,100h / lack)lanimoN(*1
Power source
kW
R410A x 5.0kg (12lbs)
Installation Manual
MEL32
1,160(1,100 without legs) x 880 x 550
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
cfm
96
3.4
Compressor
water
Net weight
HIC circuit (HIC: Heat Inter-Changer)
Water volume in plate
Water pressure Max.
High pressure protection
MPa
kg(lbs)
mm
Compressor
in.
L/min
Pressure drop kPa
Water flow rate
m
3
/ h
Circulating
Accessory
DrawingExternal
Joint: CMY-Y102S-G2, CMY-Y102L-G2
17
Inverter
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Operating volume range
m3 / h
Wiring
Standard attachment
Document
Refrigerant conn. pipe
Header: CMY-Y104/108/1010-G
KE94C317
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Unit converter
*The specification data is
subject to rounding variation.
Notes:
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
- 6 -
*1
*2
-
plate type
Heat exchanger
Over-heat protection
Acrylic painted steel plate
l
Type x original charge
Control
5.76
32,300
Circulating water
°C
connectable
Model / Quantity
heating
Model
External finish
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range ofIndoor
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
Starting method
Type x Quantit
y
Manufacture
BTU / h
Indoor unit
Temp. range of
*1
33.5
7.36
114,300
12.4-11.8-11.3
PQHY-P300YHM-A(For Ground source)
3-phase 4-wire 380-400-415V 50/60Hz
28,800h / lack)lanimoN(*1
Power source
kW
R410A x 5.0kg (12lbs)
Installation Manual
MEL32
1,160(1,100 without legs) x 880 x 550
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
cfm
96
3.4
Compressor
water
Net weight
HIC circuit (HIC: Heat Inter-Changer)
Water volume in plate
Water pressure Max.
High pressure protection
MPa
kg(lbs)
mm
Compressor
in.
L/min
Pressure drop kPa
Water flow rate
m
3
/ h
Circulating
Accessory
DrawingExternal
Joint: CMY-Y102S-G2,CMY-Y102L-G2
17
Inverter
AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Operating volume range
m3 / h
Wiring
Standard attachment
Document
Refrigerant conn. pipe
Header: CMY-Y104/108/1010-G
KE94C317
High pressure sensor, High pressure switch at 4.15MPa (601 psi) Protection
*The specification data is
subject to rounding variation.
Notes:
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Over-heat protection
Acrylic painted steel plate
23LEM23LEM
4.6
)V 042(530.0)V 042(530.0Wkretaeh esaC
6.4Wktuptuo rotoM
Inverter scroll hermetic compressor
Inverter
AC&R Works, MITSUBISHI ELECTRIC CORPORATIONAC&R Works, MITSUBISHI ELECTRIC CORPORATION
Inverter
Inverter scroll hermetic compressor
in.
Over-heat protection
Control
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
195(430)
5.76 + 5.76
43,000
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
45.0
8.25
153,500
13.9-13.2-12.7
PQHY-P400YSHM-A (For Ground source)
3-phase 4-wire 380-400-415V 50/60Hz
38,700h / lack)lanimoN(*1
Power source
kW
Installation Manual
Acrylic painted steel plate
1,160(1,100 without legs) x 880 x 550
cfm
96 + 96
3.4 + 3.4
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
KE94C317
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G2
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
KE94C317
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Refrigerant conn. pipe
Header: CMY-Y104/108/1010-G
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Unit converter
R410A x 5.0kg (12lbs)
Indoor LEV and BC controller
1,160(1,100 without legs) x 880 x 550
PQHY-P200YHM-A(For Ground source)
12.7(1/2) Brazed
28.58(1-1/8) Brazed
epyt etalp epyt etalp
5.0
4.5 + 4.5 ~ 7.2 + 7.2
Lubricant
Type x Quantity
External finish
-
R410A x 5.0kg (12lbs)
195(430)
KB94T223
9.52(3/8) Brazed
170,600
PQHY-P200YHM-A(For Ground source)
8.65
50
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 1~34
-5.0~45.0°C(23~113°F)
7171
Gas pipemm(in.)
dezarB )4/3(50.91dezarB )4/3(50.91
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
50.0
15.0~24.0°C(59~75°F)W.B.
5.45
-5.0~45.0°C(23~113°F)
kW / kW
kcal / h
*2 BTU / h
Power input
kW
14.6-13.8-13.3
87.5POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
- 8 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
Over-heat protection
Acrylic painted steel plate
23LEM23LEM
6.3
)V 042(530.0)V 042(530.0
3.6
Inverter scroll hermetic compressor
Inverter
AC&R Works, MITSUBISHI ELECTRIC CORPORATION AC&R Works, MITSUBISHI ELECTRIC CORPORATION
Inverter
Inverter scroll hermetic compressor
Over-heat protection
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
195(430)
5.76 + 5.76
54,200
56.0
11.45
191,100
19.3-18.3-17.6
PQHY-P500YSHM-A(For Ground source)
3-phase 4-wire 380-400-415V 50/60Hz
48,200
Installation Manual
Acrylic painted steel plate
1,160(1,100 without legs) x 880 x 550
96 + 96
3.4 + 3.4
KE94C317
Joint: CMY-Y102S-G2, CMY-Y102L-G2, CMY-Y202-G
2
KE94C317
Refrigerant conn. pipe
Header: CMY-Y104/108/1010-G
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
R410A x 5.0kg (12lbs)
Indoor LEV and BC controller
1,160(1,100 without legs) x 880 x 550
PQHY-P250YHM-A(For Ground source)
15.88(5/8) Brazed
28.58(1-1/8) Brazed
epyt etalp epyt etalp
5.0
4.5 + 4.5 ~ 7.2 + 7.2
-
R410A x 5.0kg (12lbs)
195(430)
KB94T223
9.52(3/8) Brazed
215,000
PQHY-P250YHM-A(For Ground source)
12.06
52
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 1~43
-5.0~45.0°C(23~113°F)
7171
dezarB )8/7(2.22dezarB )8/7(2.22
63.0
15.0~24.0°C(59~75°F)
4.89
-5.0~45.0°C(23~113°F)
20.3-19.3-18.6
22.5
- 10 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
R410A x 5.0kg (12lbs)
Indoor LEV and BC controller
1,160(1,100 without legs) x 880 x 550
PQHY-P300YHM-A(For Ground source)
15.88(5/8) Brazed
28.58(1-1/8) Brazed
epyt etalp epyt etalp
5.0
4.5 + 4.5 ~ 7.2 + 7.2
-
R410A x 5.0kg (12lbs)
195(430)
KB94T223
12.7(1/2) Brazed
235,400
PQHY-P250YHM-A(For Ground source)
14.65
52.5
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 2~47
-5.0~45.0°C(23~113°F)
7171
22.2(7/8) BrazeddezarB )8/7(2.22
69.0
15.0~24.0°C(59~75°F)
4.68
-5.0~45.0°C(23~113°F)
24.7-23.4-22.6
07.4
- 11 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
R410A x 5.0kg (12lbs)
Indoor LEV and BC controller
1,160(1,100 without legs) x 880 x 550
PQHY-P300YHM-A(For Ground source)
15.88(5/8) Brazed
28.58(1-1/8) Brazed
epyt etalpepyt etalp
5.0
4.5 + 4.5 ~ 7.2 + 7.2
-
R410A x 5.0kg (12lbs)
195(430)
KB94T223
12.7(1/2) Brazed
261,000
PQHY-P300YHM-A(For Ground source)
17.12
53
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 2~50
-5.0~45.0°C(23~113°F)
7171
22.2(7/8) Brazed22.2(7/8) Brazed
76.5
15.0~24.0°C(59~75°F)
4.45
-5.0~45.0°C(23~113°F)
28.9-27.4-26.4
64.4
- 12 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
25.5
24.8-23.6-22.7
5.22
-5.0~45.0°C(23~113°F)
81.5
15.0~24.0°C(59~75°F)
53
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 2~50
-5.0~45.0°C(23~113°F)
12.7(1/2) Brazed
278,100
14.74
195(430)
KB94T659
Over-heat protection
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection
195(430)
epyt etalp
Copper pipe,tube-in-tube structure
1.0
5.0
1.0
Copper pipe,tube-in-tube structure
12.7(1/2) Brazed
22.2(7/8) Brazed
Heat Source Twinning kit: CMY-Y300VBK2
12.7(1/2) Brazed
19.05(3/4) Brazed19.05(3/4) Brazed
Copper pipe,tube-in-tube structure
195(430)
- 13 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
33.5
27.8-26.4-25.5
5.13
-5.0~45.0°C(23~113°F)
88.0
15.0~24.0°C(59~75°F)
53.5
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 2~50
-5.0~45.0°C(23~113°F)
12.7(1/2) Brazed
300,300
16.51
195(430)
KB94T659
Over-heat protection
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection
195(430)
epyt etalp
Copper pipe,tube-in-tube structure
1.0
5.0
1.0
Copper pipe,tube-in-tube structure
12.7(1/2) Brazed
22.2(7/8) Brazed
Heat Source Twinning kit: CMY-Y300VBK2
12.7(1/2) Brazed
22.2(7/8) Brazed19.05(3/4) Brazed
Copper pipe,tube-in-tube structure
195(430)
- 14 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection
195(430)
epyt etalp
Copper pipe,tube-in-tube structure
1.0
5.0
1.0
Copper pipe,tube-in-tube structure
12.7(1/2) Brazed
22.2(7/8) Brazed
Heat Source Twinning kit: CMY-Y300VBK2
12.7(1/2) Brazed
22.2(7/8) Brazed22.2(7/8) Brazed
Copper pipe,tube-in-tube structure
195(430)
- 15 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
28.4
35.0-33.2-32.0
4.69
-5.0~45.0°C(23~113°F)
100.0
15.0~24.0°C(59~75°F)
54
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 2~50
-5.0~45.0°C(23~113°F)
12.7(1/2) Brazed
341,200
20.74
195(430)
KB94T659
Over-heat protection
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection
195(430)
epyt etalp
Copper pipe,tube-in-tube structure
1.0
5.0
1.0
Copper pipe,tube-in-tube structure
12.7(1/2) Brazed
22.2(7/8) Brazed
Heat Source Twinning kit: CMY-Y300VBK2
12.7(1/2) Brazed
22.2(7/8) Brazed 22.2(7/8) Brazed
Copper pipe,tube-in-tube structure
195(430)
- 16 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Over-heat protection
195(430)
epyt etalp
Copper pipe,tube-in-tube structure
1.0
5.0
1.0
Copper pipe,tube-in-tube structure
12.7(1/2) Brazed
22.2(7/8) Brazed
Heat Source Twinning kit: CMY-Y300VBK2
12.7(1/2) Brazed
22.2(7/8) Brazed22.2(7/8) Brazed
Copper pipe,tube-in-tube structure
195(430)
- 17 -
*1
*2
Wkretaeh esaC
Wktuptuo rotoM
in.
Control
Circulating water
°C
Set Model
Model
connectable
Model / Quantity
heating
Model
Total capacity
piping diameter
D.B.
*2
COP
°C
Indoor
Temp. range of
Current input
(Nominal)
mm(in.)
mm(in.)
Liquid pipe
Gas pipe
Power input
Refrigerant
BTU / h
Indoor unit
Temp. range of
*1
h / lack)lanimoN(*1
Power source
kW
cfm
l
Water volume in plate
wate r
HIC circuit (HIC: Heat Inter-Changer)
Heat exchanger
Water pressure Max.
Protection
mm
External dimension HxWxD
Type x original charge
)sbl(gkthgiew teN
MPa
High pressure protection
Inverter circuit (COMP.)
Manufacture
Starting method
L/min
Water flow rate
m
3
/ h
Circulating
Compressor
Accessory
Drawing
distributor
Remarks
●Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be refer
●Turn DipSW 3-9 ON before power ON.
red to the Installation Manual.
●Due to continuing improvement, above specifications may be subject to change without notice.
●The ambient temperature of the heat source unit needs to be kept below 40 °C D.B.
●The ambient relative humidity of the heat source unit needs to be kept below 80%.
●The heat source unit should not be installed at outdoor.
●Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
●Be sure to provide interlocking for the unit operation and water circuit.
●Add brine to circulating water when a unit is operating at water temperature below 10°C.
●Twinning kit is required.
kPaPressure drop
Operating volume range
m3 / h
Notes:
Standard attachment
Document
Wiring
External
*The specification data is
subject to rounding variation.
Unit converter
Lubricant
Type x Quantity
External finish
Gas pipemm(in.)
Cooling capacity
devices
Compressor
cooling
Circulating water
Indoor
Heating capacity
=kW x 860
=kW x 3,412
=m
3
/min x 35.31
=kg / 0.4536
kcal
BTU/h
cfm
lb
Pipe between unit and
Liquid pipemm(in.)
Sound pressure level (measured in anechoic room)
dB <A>
W.B.
kW / kW
kcal / h
*2 BTU / h
Power input
kW
POCkW / kW
kW
Current inputkWA
A
Optional parts
Refri gerant
1.<Standard CITY MULTI indoor unit>
Nominal cooling conditions(subject to JIS B8615-1)
Indoor:27°CDB/19°CWB(81°FDB/66°FWB)
Water temperature:30°C(86°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
2.<PWFY-P100/200VM-E-AU>
Nominal cooling conditions
Circulating water Temp. : 30°C (86°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 23°C
Water flow rate : 1.93m
3
/h (P100) / 3.86m3/h (P200)
Brine concentration 0%
Nominal heating conditions(subject to JIS B8615-1)
Indoor:20°CDB(68°FDB)
Water temperature:20°C(68°F)
Pipe length:7.5m(24-9/16ft.), Level difference:0m(0ft.)
Brine concentration 0%
Nominal heating conditions
Circulating water Temp. : 20°C (68°F)
Pipe length : 7.5 m (24-9/16 ft)
Level difference : 0m (0ft)
Inlet water Temp 30°C
Water flow rate : 2.15m
3
/h (P100) / 4.30m3/h (P200)
Brine concentration 0%
04.4
43.3-41.1-39.6
4.34
-5.0~45.0°C(23~113°F)
113.0
15.0~24.0°C(59~75°F)
55
15.0~27.0°C(59~81°F)
50~130 % of heat source unit capacity
P15~P250 / 2~50
-5.0~45.0°C(23~113°F)
12.7(1/2) Brazed
385,600
25.67
195(430)
KB94T659
Over-heat protection
Over-heat protection, Over-current protection
Over-heat protection
5.0
19.05(3/4) Brazed
41.28(1-5/8) Brazed
4.5 + 4.5 + 4.5 ~ 7.2 + 7.2 + 7.2
LEV and HIC circuit
epyt etalpepyt etalp
5.0
1.0
17
45-11/16(43-5/16 without legs) x 34-11/16 x 21-11/16
2. The noise level is measured in an anechoic room.
3. Heating can be used only by the indoor warming-up.
4. Works not included : Installation / foundation work, electric connection work,
duct work, insulation work, The power source switch and other items are
not specified in the specifications.
5.
Add brine to circulating water for heat source unit when operating at water temperature below 10°C.
2. The noise level is measured in an anechoic room.
3. Heating can be used only by the indoor warming-up.
Note
4. Works not included : Installation / foundation work, electric connection work,
duct work, insulation work, The power source switch and other items are
not specified in the specifications.
At factory shipment, this model of indoor unit is designed and set to accommodate a single refrigerant
circuit. Connection of two refrigerant circuits to the indoor unit requires setting change and pipe work.
5.
Add brine to circulating water for heat source unit when operating at water temperature below 10°C.
- 20 -
(2)External dimension
Service space
(front side)
Service space
(front side)
Top view
550
60
60
20
74
116 0
(60)
The space for
control box
replacement
450
600
170
350
725
600
450
170
110 0
550
(530)
(102)
(53)
506 (503~509)
470 (467~473)
834
720
110 0
141
213
240
2 x 2-14 x 20 Oval hole
140
75
608
563
584
83
58
121 226
234
18
78
168
433
548
(550)
2222
4040
550
880
2 x 2-14 x 20 Oval hole
(Installation support hole)
(880)
8080
2323
Control box
Service
panel
(Installation support hole pitch)
(Mounting pitch)
(Installation support
hole pitch)
(Mounting pitch)
88
7
6
5
4
3
2
Refrigerant service
valve <Gas>
Refrigerant service
valve <Liquid>
1
(front and back, 2 points)
Note 8*
Detachable leg
880
ø
22.2 Brazed
ø9.52 Brazed
ø
19.05 Brazed
GasLiquid
PQHY-P300YHM-A
PQHY-P250YHM-A
PQHY-P200YHM-A
*1
*1
*1
Fig. BFig. A
Note 1. Close a hole of the water piping, the refrigerant piping,
the power supply, and the control wiring and unused knockout
holes with the putty etc. so as not to infiltrate rain water
etc. (field erection work)
Note 2. At the time of product shipment, the front side piping
specification serves as the local drainage connection.
When connecting on the rear side, please remove the
rear side plug sealing corks, and attach a front side.
Ensure there is no leak after the attachment has been fitted.
Note 3. Take notice of service space as Fig. A. (In case of single
installation, 600mm or more of back space as front space
makes easier access when servicing the unit from rear side)
Note 4. If water pipes or refrigerant pipes stretch upward,
required space for service and maintenance due to
replacement of control box is shown in Fig. B.
Note 5. In case the temperature around the heat source unit has
possibility to drop under 0°C or the inlet-water temp. drops
under 10°C, be careful for the following point to prevent the
pipe burst by the water pipe freeze-up.
· Circulate the water all the time even if the heat source
· Add brine to water circuit.
unit is not in operation.
· Drain the water from inside of the heat source unit when
the heat source unit will not operate for a long term.
Note 6. Ensure that the drain piping is downward with a pitch of
more than 1/100.
Note 7. The detachable leg can be removed at site.
Note 8. At brazing of pipes, wrap the refrigerant service valve
with wet cloth and keep the temperature of
refrigerant service valve under 120°C.
ø45 Knockout hole
ø34 Knockout hole
ø52 or ø27 Knockout hole
For pipes
For wires
For transmission cables
Front through hole
Front through hole
Front through hole
Front through hole
140 x 77 Knockout hole
ø65 or ø40 Knockout hole
Front through hole
Water pipe
Drain pipe
inlet
outlet
Rc1-1/2 Screw
Rc1-1/2 Screw
Rc3/4 Screw
Specifications
Usage
NO.
Connection specifications for
the refrigerant service valve
Model
Connecting pipe specifications
*1. Connect by using the connecting pipes that are supplied.
<Accessories>
· Refrigerant (Liquid) conn. pipe ·····1 pc.
(P200/P250/P300 ; Packaged in the accessory kit)
· Refrigerant (Gas) conn. pipe ·····1 pc.
(P200/P250/P300 ; Packaged in the accessory kit)
Unit : mm
PQHY-P200,250,300YHM-A
- 21 -
PQHY-P400,450,500,550,600YSHM-A
110 0
550
1780
88088020
d
c
e
f
To indoor unit
Liquid Twinning pipe <optional parts>
Gas Twinning pipe <optional parts>
a
b
To indoor unit
Detachable leg
(front and back, 2 points)
ø28.58
ø15.88
ø12.7
ø12.7
ø9.52
ø9.52
ø22.2
ø22.2
f
e
Twinning pipe ~
Heat Source unit 2
Liquid
Gas
d
c
Twinning pipe ~
Heat Source unit 1
Liquid
Gas
CMY-Y100VBK2
PQHY-P600YSHM-A
PQHY-P300YHM-A
PQHY-P300YHM-A
Note 1. Connect the pipes as shown in the figure above. Refer to the table below for the pipe size.
2. The detachable leg can be removed at site.
3. Twinning pipe should not be tilted more than 15 degrees from the ground.
4. See the Installation Manual for the details of Twinning pipe installation.
5. The length of the straight part of pipe connected in front of the twinning pipe must be 500mm (19inch) or longer.
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
631252505001k2k4k8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
631252505001k2k4k8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.
10
20
30
40
50
60
70
80
90
631252505001k2k4k8k
NC-40
NC-30
NC-20
NC-60
NC-50
NC-70
Octave band central frequency (Hz)
Octave band sound level (dB)
Approximate minimum
audible limit on
continuous noise
Stand 50/60Hz
Low 50/60Hz
Sound level of PQHY-P250YHM-A
Sound level of PQHY-P300YHM-A
90
80
Stand 50/60Hz
Low 50/60Hz
70
60
50
40
Octave band sound level (dB)
30
Approximate minimum
20
audible limit on
continuous noise
10
631252505001k2k4k8k
Octave band central frequency (Hz)
Standard
Low noise mode
When Low noise mode is set,the A/C system's capacity is limited. The system could return to normal operation
from Low noise mode automatically in the case that the operation condition is severe.