Mitsubishi PLH-P1.6KAH.UK, PLH-P2KAH.UK, PLH-P2.5KAH.UK, PLH-P1.6KAH1.UK, PLH-P2KAH1.UK Service Manual

...
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
FILTER CHECK MODE TEST RUN
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
TEMP.
Provisional publication
Parts lists for some models are not included in this manual. As soon as they are completed, the manual included the lists for all models will be published.
TECHNICAL & SERVICE MANUAL
Series PLH
Indoor unit [Model names] [Service Ref.]
PLH-P1.6KAH PLH-P1.6KAH.UK
PLH-P2KAH PLH-P2KAH.UK
PLH-P2.5KAH PLH-P2.5KAH.UK
Ceiling Cassettes
PLH-P1.6KAH
PLH-P2KAH
PLH-P2.5KAH
R407C
1.UK
1.UK
1.UK
No. OC235
REVISED EDITION-A
• PLH-P1.6KAH1.UK, PLH­P2KAH1.UK and PLH­P2.5KAH1.UK are added in REVISED EDITION-A. Outdoor units PUH-P1.6, 2,
2.5VGAA.UK and PUH-P1.6, 2,
2.5YGAA.UK which are con­nected to those indoor units are also added in it.
• Please void OC235.
• Refer to the OCT03 REVISED EDITION-C as for control rela­tion. This manual does not cover outdoor units. When serving them, please refer to the ser­vice manual No.OC180 REVISED EDITION-A, OC261 and this manual in a set.
INDOOR UNIT
PLH-P1.6, 2, 2.5KAH.UK PLH-P1.6, 2, 2.5KAH1.UK
REMOTE CONTROLLER
CONTENTS
1. TECHNICAL CHANGES······························2
3. SAFETY PRECAUTION·······························2
4. PART NAMES AND FUNCTIONS ···············4
5. SPECIFICATIONS········································9
6. DATA ··························································15
7. OUTLINES AND DIMENSIONS·················34
8.
WIRING DIAGRAM
9.
REFRIGERANT SYSTEM DIAGRAM
10. TROUBLESHOOTING ·······························37
11. DISASSEMBLY PROCEDURE ··················39
12. PARTS LIST···············································42
13. OPTIONAL PARTS ····································46
·······································35
··············36
Heat pump type
Outdoor unit
PUH-P
Heat pump with electric heater
PLH-P1.6KAH.UK PLH-P1.6KAH1.UK PLH-P2KAH.UK PLH-P2KAH1.UK PLH-P2.5KAH.UK PLH-P2.5KAH1.UK
VGA1
— — — —
YGA1
— — — —
YGA
— —
— — —
VGA
— —
— — —
VGA
— — — — —
YGA
— — — — —
VGAA.UK
— — — —
YGAA.UK
— — — —
VGAA.UK
— —
— —
YGAA.UK
— —
— —
VGAA.UK
— — — —
YGAA.UK
— — — —
1.6 2 2.5
Indoor unit
1
TECHNICAL CHANGES
PLH-P1.6KAH.UK PLH-P1.6KAH1.UK PLH-P2KAH.UK PLH-P2KAH1.UK PLH-P2.5KAH.UK PLH-P2.5KAH1.UK
REMOTE CONTROLLER has changed.(PAR-S27A-E PAR-20MAA-E)
Outdoor units which are connected to PLH-P·KAH.UK and PLH-P·KAH
1.UK have been added.
2
3
COMBINATION OF INDOOR AND OUTDOOR UNITS
SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust / dirt, shaving parti-
cles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant. (Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant
recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is per-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant .
2
Gravimeter
Unit
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
Gauge manifold ·Only for R407C.
1
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
Charge hose ·Only for R407C.
2
·Use pressure performance of 5.10MPa·G or over.
Electronic scale
3
Gas leak detector ·Use the detector for R407C.
4
Adapter for reverse flow check. ·Attach on vacuum pump.
5
Refrigerant charge base.
6
Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
7
·Cylinder with syphon
Refrigerant recovery equipment.
8
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant.
3
4
Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.
Grille
Filters Remove dust and pollutants from inhaled air
Horizontal Air Outlet Sets airflow horizontal automatically during cooling or dehumidifying.
Air Intake Inhales air from room.
PART NAMES AND FUNCTIONS
Indoor (Main) Unit PLH-P1.6KAH.UK, PLH-P2KAH.UK, PLH-P2.5KAH.UK
PLH-P1.6KAH1.UK, PLH-P2KAH1.UK, PLH-P2.5KAH1.UK
4
Remote controller
Once the controls are set, the same operation mode can
be repeated by simply pressing the ON/OFF button.
PLH-P1.6KAH.UK, PLH-P2KAH.UK, PLH-P2.5KAH.UK
Operation buttons [ PAR-S27A-E ]
TIME SETTING button
TIMER button
This switches between continuous operation and the timer operation.
This sets of switches the current time. start time and stop time.
AIR SPEED button
This sets the fan speed.
OPERATION SWITCH button
Press this button to switch the cooler elec­tronic dry (dehumidify) automatic and heater modes.
TEMP. ADJUSTMENT button
This sets the room tempera­ture The temperature setting can be performed in 1°C units
Setting range
Cooler 19°C to 30°C Heater 17°C to 28°C
TIMER ADJUSTMENT button
This adjust the current time, start time and stop time.
LOUVER button
This switches the hori­zontal fan motion ON and OFF.
(This button does not operate in this model)
ON/OFF button
This switches between the operation and stop modes each time it is pressed. The lamp on this button lights dur­ing operation.
AIR DIRECTION button
This adjusts the vertical angle of the ventilation.
FILTER button
This resets the filter cleaning indication display.
CHECK-TEST RUN button
Only press this button to per­form an inspection check or test operation Do not use it for normal operation.
VENTILA TION button
This sets the ventilation fan speed.
5
Display
CENTRALLY CONTROLLED display
This indicates when the unit is con­trolled by optional features such as central control type remote controller.
TIMER display
This indicates when the continuous operation and time operation modes are set. It also display the time for the timer operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby mode is set from the time the sleep operation starts until the heating air is discharged.
DEFROST display
This indicates when the defrost oper­ation is performed.
CLOCK display
The current time , start time and stop time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
In this display example on the bot­tom left, a condition where all dis­play lamps light is shown for expla­nation purposes although this differs from actual operation.
AIR DIRECTION display
This displays the air direction.
FAN SPEED display
The selected fan speed is displayed.
ROOM TEMPERATURE display
The temperature of the suction air is displayed during operation. The dis­play range is 8° to 39°C. The display flashes 8°C when the actual temper­ature is less than 8° and flashes 39°C when the actual temperature is greater than 39°C.
Operation lamp
This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.
CHECK MODE
TEST RUN
This display lights in the check mode or when a test operation is per­formed.
display
FILTER display
CHECK display
This indicates when a malfunction has occurred in the unit which should be checked.
SET TEMPERATURE display
This displays the selected setting temperature.
Caution
Only the Power display lights when the unit is stopped and power supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.
“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.
POWER display
This lamp lights when electricity is supplied to the unit.
This lamp lights when the filter need to be cleaned.
6
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
Press this button to switch the cooler, electronic dry (dehumidify), automatic and heater modes.
OPERATION SWITCH button
This sets the room temperature. The temperature setting can be performed in 1: units Setting range Cooler 19: to 30: Heater 17: to 28:
TEMP. ADJUSTMENT button
This switches between continuous operation and the timer operation.
TIMER button
This switches between the operation and stop modes each time it is pressed. The lamp on this button lights during operation.
ON/OFF button
Only press this button to perform an inspection check or test operation. Do not use it for normal operation.
CHECK-TEST RUN button
This switch the horizontal fan motion ON and OFF.
(Not available for this model.)
LOUVER button
This sets the ventilation fan speed.
VENTILATION button
This adjusts the vertical angle of the ventilation.
AIR DIRECTION button
This resets the filter service indication display
FILTER button
This sets the current time, start time and stop time.
TIME SETTING button
This sets the ventilation fan speed.
AIR SPEED button
PLH-P1.6KAH1.UK, PLH-P2KAH1.UK, PLH-P2.5KAH1.UK
Operation buttons [ PAR-20MAA-E ]
7
Display
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
CENTRALLY CONTROLLED display
This indicates when the unit is con­trolled by optional features such as central control type remote controller.
TIMER display
This indicates when the continuous operation and time operation modes are set. It also display the time for the timer operation at the same time as when it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
The [STANDBY] symbol is only dis­played from the time the heating operation starts unit the heated air begins to blow.
DEFROST display
This indicates when the defrost oper­ation is performed.
CLOCK display
The current time , start time and stop time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.
In this display example on the bot-
tom left, a condition where all dis­play lamps light is shown for expla­nation purposes although this differs from actual operation.
AIR DIRECTION display
This displays the air direction.
AIR SPEED display
The selected fan speed is displayed.
ROOM TEMPERATURE display
The temperature of the suction air is displayed during operation. The display range is 8°C to 39°C. The display flashes 8°C when the actual temperature is less than 8°C and flashes 39°C when the actual tem­perature is greater than 39°C.
Operation lamp
This lamp lights during operation,
This display lights in the check mode
goes off when the unit stops and flashes when a malfunction occurs.
CHECK MODE
TEST RUN
or when a test operation is per­formed.
display
FILTER display
CHECK display
This indicates when a malfunction has occurred in the unit which should be checked.
SET TEMPERATURE display
This displays the selected setting temperature.
Caution
Only the Power display lights when the unit is stopped and power supplied to the unit.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.
“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.
When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.
POWER display
This lamp lights when electricity is supplied to the unit.
This lamp lights when the filter need to be cleaned.
8
5 SPECIFICATIONS
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min (CFM)
Pa (mmAq)
kW
dB mm (in.) mm (in.) mm (in.) mm (in.)
kg (lbs)
A A
kW
W
kW
K
/min (CFM
)
dB
dB mm (in.) mm (in.) mm (in.)
kg (lbs) kg (lbs)
L mm (in.) mm (in.)
Function Capacity w1
Total input w1
Service Ref.
Power supply (phase, cycle, voltage)
Input w2 Running current w2
Starting current w2 External finish Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure Booster heater w2 Operation control & Thermostat Noise level (Lo-Mi2-Mi1-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PLH-P1.6KAH.UK
Cooling
15,000
4,400
1.86
0.15
0.64
0.70
7.66 / 2.67
Heating
17,100 (21,800)
5,000 (6,400)
1.93 (3.33)
0.10 <1.40>
0.45 <5.83>
0.50 <5.83>
8.19 / 2.86
W
D H
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
PLH-P1.6KAH.UK
Single phase, 50Hz, 220-230-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
13-14-15-16 (459-494-530-565)
0 (direct blow)
<1.4>
Remote controller & built-in
32-34-35.5-37
32 (1-1/4)
PUH-P1.6VGA / PUH-P1.6YGA
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
36 / 20
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
RE277VHSM / RE277YFKM
1.3
Line start
Inner thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
30
Plate fin coil
Propeller (direct) x 1
0.070
45 (1,590)
Reverse cycle
46 48
900 (35-7/16)
330+20 (13+3/4)
650 (25-5/8)
55 (121)
R407C
2.6 (5.7)
0.57 (Ester) MEL56
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 40m Max. 40m
w1 : ( ) Shows the total rating. w2 : < > Shows the only booster heater rating.
UNIT : 660 (26) PANEL : 760 (30) UNIT : 660 (26) PANEL : 760 (30) UNIT : 253 (10) PANEL : 30 (1-1/8) UNIT : 20 (44) PANEL : 3.7 (8)
Upper limit Lower limit Upper limit Lower limit
Indoor
Outdoor
Cooling
Heating
D.B. 35˚C W.B. 22.5˚C D.B. 19˚C W.B. 15˚C D.B. 28˚C D.B. 17˚C
D.B. 46˚C D.B. -5˚C D.B. 24˚C W.B. 18˚C D.B. -11˚C W.B. -12˚C
Notes 1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C (80˚F) W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C (95˚F) W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C (68˚F) Outdoor : D.B. 7˚C (45˚F) W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
9
Cooling
18,400
5,400
2.62
0.14
0.65
0.72
11.11 / 3.88
Heating
21,300 (26,100)
6,250 (7,650)
2.67 (4.07)
0.10 <1.40>
0.45 <5.83>
0.50 <5.83>
11.51 / 4.02
PLH-P2KAH.UK
Single phase, 50Hz, 220-230-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
13-14-15-16 (459-494-530-565)
0 (direct blow)
<1.4>
Remote controller & built-in
32-34-35.5-37
32 (1-1/4)
PUH-P2VGA / PUH-P2YGA
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
74 / 30
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
NE38VMJM / NE38YEJM
1.7
Line start
Inner thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
38
Plate fin coil
Propeller (direct) x 1
0.070
55 (1,940)
Reverse cycle
48 49
900 (35-7/16)
330+20 (13+3/4)
855 (33-5/8)
71 (157)
R407C
3.1 (6.8)
1.2 (Ester) MEL56
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 40m Max. 40m
UNIT : 660 (26) PANEL : 760 (30) UNIT : 660 (26) PANEL : 760 (30) UNIT : 253 (10) PANEL : 30 (1-1/8) UNIT : 20 (44) PANEL : 3.7 (8)
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min (CFM)
Pa (mmAq)
kW
dB mm (in.) mm (in.) mm (in.) mm (in.)
kg (lbs)
A A
kW
W
kW
K
/min (CFM
)
dB
dB mm (in.) mm (in.) mm (in.)
kg (lbs) kg (lbs)
L mm (in.) mm (in.)
Function Capacity w1
Total input w1
Service Ref.
Power supply (phase, cycle, voltage)
Input w2 Running current w2
Starting current w2 External finish Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure Booster heater w2 Operation control & Thermostat Noise level (Lo-Mi2-Mi1-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PLH-P2KAH.UK
W
D H
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
w1 : ( ) Shows the total rating. w2 : < > Shows the only booster heater rating.
Upper limit Lower limit Upper limit Lower limit
Indoor
Outdoor
Cooling
Heating
D.B. 35˚C W.B. 22.5˚C D.B. 19˚C W.B. 15˚C D.B. 28˚C D.B. 17˚C
D.B. 46˚C D.B. -5˚C D.B. 24˚C W.B. 18˚C D.B. -11˚C W.B. -12˚C
Notes 1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C (80˚F) W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C (95˚F) W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C (68˚F) Outdoor : D.B. 7˚C (45˚F) W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
10
Item
Function Capacity w1
Total input w1
Service Ref.
Power supply (phase, cycle,voltage)
External finish Heat exchanger Fan Fan (drive) x No.
Booster heater w2
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level (Lo-Mi2-Mi1-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger Fan Fan (drive) x No.
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D. Connection method Between the indoor &
REFRIGERANT PIPING
outdoor unit
Notes 1. Rating Conditions (ISO T1)
Input w2 Running current w2 Starting current w2
Fan motor output Airflow (Lo-Mi2-Mi1-Hi) External static pressure
Running current Starting current
Model Motor output Starter type Protection devices Crankcase heater
Fan motor output Airflow
Charge Oil (Model)
Cooling : Indoor : D.B. 27˚C (80˚F) W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C (95˚F) W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C (68˚F) Outdoor : D.B. 7˚C (45˚F) W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Cooling
Heating
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C W.B. 22.5˚C D.B. 19˚C W.B. 15˚C D.B. 28˚C D.B. 17˚C
Service Ref.
K/min (CFM)
Pa (mmAq)
mm (in.)
K
Indoor
mm (in.) mm (in.) mm (in.)
kg (lbs)
/min (CFM
mm (in.) mm (in.) mm (in.)
kg (lbs) kg (lbs)
mm (in.) mm (in.)
W
D H
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Btu/h
W
kW
kW
A A
kW
kW
dB
A A
kW
W
kW
dB dB
L
PLH-P2.5KAH.UK
Cooling
21,500
6,300
2.77
0.14
0.61
0.67 Galvanized sheets with gray heat insulation
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
11.78 / 4.11
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
)
Outdoor D.B. 46˚C D.B. -5˚C D.B. 24˚C W.B. 18˚C D.B. -11˚C W.B. -12˚C
PLH-P2.5KAH.UK
Single phase, 50Hz, 220-230-240V
Plate fin coil
Turbo fan (direct) x 1
14-15-16-17 (494-530-565-600)
Remote controller & built-in
UNIT : 660 (26) PANEL : 760 (30) UNIT : 660 (26) PANEL : 760 (30) UNIT : 253 (10) PANEL : 30 (1-1/8) UNIT : 21 (46) PANEL : 3.7 (8)
PUH-P2.5VGA
Linear Expansion Valve
NE41VMJM / NE41YEJM
0.030
0 (direct blow)
<2.1>
35-36.5-38-39.5
32 (1-1/4)
1 / PUH-P2.5YGA1
77 / 32
Munsell 5Y 8/1
Hermetic
1.9
Line start
38
Plate fin coil
Propeller (direct) x 1
0.070
50 (1,770)
Reverse cycle
48 50
900 (35-7/16)
330+20 (13+3/4)
855 (33-5/8)
82 (181)
R407C
3.3 (7.3)
1.2 (Ester) MEL56
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 50m Max. 50m
w1 : ( ) Shows the total rating. w2 : < > Shows the only booster heater rating.
Heating
25,200 (32,400)
7,400 (9,500)
2.68 (4.78)
0.10 <2.10>
0.45 <8.75>
0.50 <8.75>
11.55 / 4.03
11
Cooling
15,000
4,400
1.82
0.15
0.64
0.70
7.36 / 2.94
Heating
17,100 (21,800)
5,000 (6,400)
1.89 (3.29)
0.10 <1.40>
0.45 <5.83>
0.50 <5.83>
7.59 / 2.56
PLH-P1.6KAH.UK / PLH-P1.6KAH
1.UK
Single phase, 50Hz, 220-230-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
13-14-15-16 (459-494-530-565)
0 (direct blow)
<1.4>
Remote controller & built-in
32-34-35.5-37
32 (1-1/4)
PUH-P1.6VGAA.UK / PUH-P1.6YGAA.UK
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
36 / 20
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
RE277VHSMT / RE277YFKM
1.3
Line start
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, HP switch, Discharge thermo.
30
Plate fin coil
Propeller (direct) x 1
0.070
45 (1,590)
Reverse cycle
47 49
900 (35-7/16)
330+20 (13+3/4)
650 (25-5/8)
55 (121)
R407C
2.5 (5.5)
0.57 (Ester) MEL56
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 40m Max. 40m
UNIT : 660 (26) PANEL : 760 (30) UNIT : 660 (26) PANEL : 760 (30) UNIT : 253 (10) PANEL : 30 (1-3/16) UNIT : 20 (44) PANEL : 3.7 (8)
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min (CFM)
Pa (mmAq)
kW
dB mm (in.) mm (in.) mm (in.) mm (in.)
kg (lbs)
A A
kW
W
kW
K
/min (CFM
)
dB
dB mm (in.) mm (in.) mm (in.)
kg (lbs) kg (lbs)
L mm (in.) mm (in.)
Function Capacity w1
Total input w1
Service Ref.
Power supply (phase, cycle,voltage)
Input w2 Running current w2
Starting current w2 External finish Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure Booster heater w2 Operation control & Thermostat Noise level (Lo-Mi2-Mi1-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PLH-P1.6KAH.UK / PLH-P1.6KAH1.UK
W D H
Cooling Heating
W D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Notes 1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C (80˚F) W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C (95˚F) W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C (68˚F) Outdoor : D.B. 7˚C (45˚F) W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
w1 : ( ) Shows the total rating. w2 : < > Shows the only booster heater rating.
Upper limit Lower limit Upper limit Lower limit
Indoor
Outdoor
Cooling
Heating
D.B. 35˚C W.B. 22.5˚C D.B. 19˚C W.B. 15˚C D.B. 28˚C D.B. 17˚C
D.B. 46˚C D.B. -5˚C D.B. 24˚C W.B. 18˚C D.B. -11˚C W.B. -12˚C
12
Item
Function Capacity w1
Total input w1
Service Ref.
Power supply (phase, cycle,voltage)
External finish Heat exchanger Fan Fan (drive) x No.
Booster heater w2
INDOOR UNITOUTDOOR UNIT
Operation control & Thermostat Noise level (Lo-Mi2-Mi1-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
External finish Refrigerant control Compressor
Heat exchanger Fan Fan (drive) x No.
Defrost method Noise level
Dimensions
Weight Refrigerant
Pipe size O.D. Connection method Between the indoor &
REFRIGERANT PIPING
outdoor unit
Notes 1. Rating Conditions (ISO T1)
Input w2 Running current w2 Starting current w2
Fan motor output Airflow (Lo-Mi2-Mi1-Hi) External static pressure
Running current Starting current
Model Motor output Starter type Protection devices Crankcase heater
Fan motor output Airflow
Charge Oil (Model)
Cooling : Indoor : D.B. 27˚C (80˚F) W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C (95˚F) W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C (68˚F) Outdoor : D.B. 7˚C (45˚F) W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Cooling
Heating
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
Upper limit Lower limit Upper limit Lower limit
D.B. 35˚C W.B. 22.5˚C D.B. 19˚C W.B. 15˚C D.B. 28˚C D.B. 17˚C
Service Ref.
K/min (CFM)
Pa (mmAq)
mm (in.)
K
Indoor
mm (in.) mm (in.) mm (in.)
kg (lbs)
/min (CFM
mm (in.) mm (in.) mm (in.)
kg (lbs) kg (lbs)
mm (in.) mm (in.)
W
D H
Cooling
Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Btu/h
W
kW
kW
A A
kW
kW
dB
A A
kW
W
kW
dB dB
L
PLH-P2KAH.UK / PLH-P2KAH1.UK
Cooling
18,000
5,300
2.44
PLH-P2KAH.UK / PLH-P2KAH
Single phase, 50Hz, 220-230-240V
0.14
0.65
0.72 Galvanized sheets with gray heat insulation
13-14-15-16 (459-494-530-565)
UNIT : 660 (26) PANEL : 760 (30) UNIT : 660 (26) PANEL : 760 (30) UNIT : 253 (10) PANEL : 30 (1-3/16) UNIT : 20 (44) PANEL : 3.7 (8)
PUH-P2VGAA.UK / PUH-P2YGAA.UK
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
10.26 / 3.70
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, HP switch, Discharge thermo.
)
Outdoor D.B. 46˚C D.B. -5˚C D.B. 24˚C W.B. 18˚C D.B. -11˚C W.B. -12˚C
Plate fin coil
Turbo fan (direct) x 1
0.030
0 (direct blow)
<1.4>
Remote controller & built-in
32-34-35.5-37
32 (1-1/4)
62 / 31
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE36VMJMT / NE36YEKMT
1.6
Line start
38
Plate fin coil
Propeller (direct) x 1
0.070
55 (1,940)
Reverse cycle
48 49
900 (35-7/16)
330+20 (13+3/4)
855 (33-5/8)
71 (157)
R407C
2.6 (5.7)
1.2 (Ester) MEL56
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 40m Max. 40m
w1 : ( ) Shows the total rating. w2 : < > Shows the only booster heater rating.
Heating
20,300 (25,100)
5,950 (7,350)
2.40 (3.80)
1.UK
0.10 <1.40>
0.45 <5.83>
0.50 <5.83>
10.57 / 3.82
13
Cooling
21,500
6,300
2.63
0.14
0.61
0.67
11.90 / 4.48
Heating
25,200 (32,400)
7,400 (9,500)
2.57 (4.67)
0.10 <2.10>
0.45 <8.75>
0.50 <8.75>
11.51 / 4.34
PLH-P2.5KAH.UK / PLH-P2.5KAH
1.UK
Single phase, 50Hz, 220-230-240V
Galvanized sheets with gray heat insulation
Plate fin coil
Turbo fan (direct) x 1
0.030
14-15-16-17 (494-530-565-600)
0 (direct blow)
<2.1>
Remote controller & built-in
35-36.5-38-39.5
32 (1-1/4)
PUH-P2.5VGAA.UK / PUH-P2.5YGAA.UK
Single phase, 50Hz, 220-230-240V / 3 phases, 50Hz, 380-400-415V (4wires)
77 / 35
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE41VMJMT / NE41YEKMT
1.9
Line start
Internal thermostat, HP switch, Discharge thermo. / Thermal relay, HP switch, Discharge thermo.
38
Plate fin coil
Propeller (direct) x 1
0.070
50 (1,770)
Reverse cycle
48 50
900 (35-7/16)
330+20 (13+3/4)
855 (33-5/8)
82 (181)
R407C
3.1 (6.8)
1.2 (Ester) MEL56
9.52 (3/8)
15.88 (5/8) Flared Flared
Max. 50m Max. 50m
UNIT : 660 (26) PANEL : 760 (30) UNIT : 660 (26) PANEL : 760 (30) UNIT : 253 (10) PANEL : 30 (1-3/16) UNIT : 21 (46) PANEL : 3.7 (8)
Service Ref.
Item
Btu/h
W
kW
kW
A A
kW
K/min (CFM)
Pa (mmAq)
kW
dB mm (in.) mm (in.) mm (in.) mm (in.)
kg (lbs)
A A
kW
W
kW
K
/min (CFM
)
dB
dB mm (in.) mm (in.) mm (in.)
kg (lbs) kg (lbs)
L mm (in.) mm (in.)
Function Capacity w1
Total input w1
Service Ref.
Power supply (phase, cycle,voltage)
Input w2 Running current w2
Starting current w2 External finish Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow (Lo-Mi2-Mi1-Hi)
External static pressure Booster heater w2 Operation control & Thermostat Noise level (Lo-Mi2-Mi1-Hi) Unit drain pipe I.D. Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current External finish Refrigerant control Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater Heat exchanger Fan Fan (drive) x No.
Fan motor output
Airflow Defrost method Noise level
Dimensions
Weight Refrigerant
Charge
Oil (Model) Pipe size O.D.
Connection method Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PLH-P2.5KAH.UK / PLH-P2.5KAH1.UK
W
D H
Cooling Heating
W
D H
Liquid
Gas Indoor side Outdoor side Height difference Piping length
Notes 1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C (80˚F) W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C (95˚F) W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C (68˚F) Outdoor : D.B. 7˚C (45˚F) W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
w1 : ( ) Shows the total rating. w2 : < > Shows the only booster heater rating.
Upper limit Lower limit Upper limit Lower limit
Indoor
Outdoor
Cooling
Heating
D.B. 35˚C W.B. 22.5˚C D.B. 19˚C W.B. 15˚C D.B. 28˚C D.B. 17˚C
D.B. 46˚C D.B. -5˚C D.B. 24˚C W.B. 18˚C D.B. -11˚C W.B. -12˚C
14
DATA6
Outdoor intake air D.B.(°C)
20 25 30
Indoor
Intake air
D.B.(°C)
Indoor
Intake air
W.B.(°C) 20 20 20 22 22 22 24 24 24 24 26 26 26 26 28 28 28 28 30 30 30 30 32 32 32 32 34 34 34 34
16 18 20 16 18 20 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22 16 18 20 22
CA 4356 4664 5016 4356 4664 5016 4356 4664 5016 5346 4356 4664 5016 5346 4356 4664 5016 5346 4356 4664 5016 5346 4356 4664 5016 5346 4356 4664 5016 5346
SHC(W)
3049 2705 2307 3398 3078 2709 3746 3451 3110 2673 4095 3824 3511 3101 4356 4198 3912 3528 4356 4571 4314 3956 4356 4664 4715 4384 4356 4664 5016 4811
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
1.00
1.00
1.00
0.90
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
1.00
1.00
1.00
0.90
SHF
0.70
0.58
0.46
0.78
0.66
0.54
0.86
0.74
0.62
0.50
0.94
0.82
0.70
0.58
1.00
0.90
0.78
0.66
1.00
0.98
0.86
0.74
1.00
1.00
0.94
0.82
1.00
1.00
1.00
0.90
P.C.
1.49
1.52
1.56
1.49
1.52
1.56
1.49
1.52
1.56
1.60
1.49
1.52
1.56
1.60
1.49
1.52
1.56
1.60
1.49
1.52
1.56
1.60
1.49
1.52
1.56
1.60
1.49
1.52
1.56
1.60
CA 4224 4532 4906 4224 4532 4906 4224 4532 4906 5236 4224 4532 4906 5236 4224 4532 4906 5236 4224 4532 4906 5236 4224 4532 4906 5236 4224 4532 4906 5236
SHC(W)
2957 2629 2257 3296 2991 2649 3633 3354 3042 2618 3971 3716 3434 3037 4224 4079 3827 3456 4224 4441 4219 3875 4224 4532 4612 4294 4224 4532 4906 4712
P.C.
1.57
1.60
1.64
1.57
1.60
1.64
1.57
1.60
1.64
1.69
1.57
1.60
1.64
1.69
1.57
1.60
1.64
1.69
1.57
1.60
1.64
1.69
1.57
1.60
1.64
1.69
1.57
1.60
1.64
1.69
CA 4092 4378 4774 4092 4378 4774 4092 4378 4774 5104 4092 4378 4774 5104 4092 4378 4774 5104 4092 4378 4774 5104 4092 4378 4774 5104 4092 4378 4774 5104
SHC(W)
2864 2539 2196 3192 2889 2578 3519 3240 2960 2552 3846 3590 3342 2960 4092 3940 3724 3369 4092 4290 4106 3777 4092 4378 4488 4185 4092 4378 4774 4594
P.C.
1.66
1.71
1.75
1.66
1.71
1.75
1.66
1.71
1.75
1.80
1.66
1.71
1.75
1.80
1.66
1.71
1.75
1.80
1.66
1.71
1.75
1.80
1.66
1.71
1.75
1.80
1.66
1.71
1.75
1.80
1. PERFORMANCE DATA
1) COOLING CAPACITY(1) PLH-P1.6KAH.UK / PUH-P1.6VGA, PUH-P1.6YGA
(240V)
Note CA : Capacity (W)
P.C. : Power consumption (kW)
SHC(W) : Sensible heat capacity
SHF : Sensible heat factor
15
Loading...
+ 33 hidden pages