MITSUBISHI
,8'IELECTRIC
Air-Con i ioners
PKA-A.
PKA-A.FAL
=r,$LIII I
INSTALLATION MANUAL
For safe and correct use, read this manual and the outdoor unit installation manual thoroughly before installing
the air-conditioner unit.
MANUAL DE INSTALACI6N
Para un use correcto y seguro, lea detalladamente este manual y el manual de instalaci6n de la unidad exterior
antes de instalar la unidad de aire acondicionado.
Contents
1. Safety precautions ................................................................................... 2 5. Drainage piping work (Fig. 5-1) ................................................................ 6
2. Installation location .................................................................................. 3 6. Electricalwork .......................................................................................... 7
3. Installing the indoor unit ........................................................................... 3 7. Test run .................................................................................................. 12
4. Installing the refrigerant piping ................................................................. 5 8. Easy maintenance function (Option) ...................................................... 15
1. Safety precautions
Before installing the unit, make sure you read all the "Safety precau-
tions".
Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Z_ Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
z_ Caution:
Describes precautions that must be observed to prevent damage to the unit.
Z_ Warning:
= Ask a dealer or an authorized technician to install the unit.
= For installation work, follow the instructions in the Installation Manual and
use tools and pipe components specifically made for use with refrigerant
specified in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
= The unit must be securely installed on a structure that can sustain its weight.
= if the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Should the refrigerant leak and cause
the concentration limit to be exceeded, hazards due to lack of oxygen in the
room may result.
1.1. Before installation (Environment)
Caution:
• Do not use the unit in an unusual environment, if the air conditioner is in-
stalled in areas exposed to steam, volatile oil (including machine oil), or sulfuric
gas, areas exposed to high salt content such as the seaside, the performance
can be significantly reduced and the internal parts can be damaged.
• Do not install the unit where combustible gases may leak, be produced, flow,
or accumulate, if combustible gas accumulates around the unit, fire or explo-
sion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in the
direct airflow of the indoor unit or too close to the unit, as these items can be
damaged by temperature changes or dripping water.
1.2. Before installation or relocation
Z_ Caution:
• Be extremely careful when transporting the units.Two or more persons are
needed to handle the unit, as it weighs 20 kg, 44 Ibs or more. Do not grasp
the packaging bands. Wear protective gloves as you can injure your hands
on the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials,
such as nails and other metal or wooden parts may cause stabs or other
injuries.
1.3. Before electric work
Z_ Caution:
= Be sure to install circuit breakers, if not installed, electric shock may result.
= For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
= When installing the power lines, do not apply tension to the cables.
After installation work has been completed, explain the 'Safety Precautions," use,
and maintenance of the unit to the customer according to the information in the Op-
eration Manual and perform the test run to ensure normal operation. Both the Instal-
lation Manual and Operation Manual must be given to the user for keeping. These
manuals must be passed on to subsequent users.
a
(_: Indicates which must be
part grounded.
Z_ Warning:
Carefully read the labels affixed to the main unit,
• Ventilate the room if refrigerant leaks during operation, if refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual.
• Use only specified cables for wiring.
• The terminal block cover panel of the unit must be firmly attached.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or
an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another loca-
tion.
• After installation has been completed, check for refrigerant leaks, if refriger-
ant leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.
• When the room humidity exceeds 80% or when the drainpipe is clogged, wa-
ter may drip from the indoor unit. Do not install the indoor unit where such
dripping can cause damage.
• When installing the unit in a hospital or communications office, be prepared
for noise and electronic interference. Inverters, home appliances, high-fre-
quency medical equipment, and radio communications equipment can cause
the air conditioner to malfunction or breakdown.The air conditioner may also
affect medical equipment, disturbing medical care, and communications equip-
ment, harming the screen display quality.
• Thermal insulation of the refrigerant pipe is necessary to prevent condensa-
tion. if the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation, if the drain-
pipe is installed incorrectly, water leakage and damage to the ceiling, floor,
furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench, if tightened too
much, the flare nut can break after an extended period.
• Be sure to ground the unit. if the unit is not properly grounded, electric shock
may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse), and
molded case circuit breaker) with the specified capacity, if the circuit breaker
capacity is larger than the specified capacity, breakdown or fire may result.
1.4. Before starting the test run
Z_ Caution:
= Turn on the main power switch more than 12 hours before starting operation.
Starting operation just after turning on the power switch can severely dam-
age the internal parts.
• Before starting operation, check that all panels, guards and other protective
parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.
2
= Do not operate the air conditioner without the air filter set in place, if the air
filter is not installed, dust may accumulate and breakdown may result.
= Do not touch any switch with wet hands. Electric shock may result.
= Do not touch the refrigerant pipes with bare hands during operation.
• After stopping operation, be sure to wait at least five minutes before turning off
the main power switch. Otherwise, water leakage or breakdown may result.
2. Installation location
A
D
w
Fig. 2=1
2.1. Outline dimensions (indoor unit) (Fig. 2=1)
Select a proper position allowing the following clearances for installation and mainte-
nance. (mm)
Models D H A B C E F
A24, A30 9-1/4 13-3/8 Min,5-15/1( Min. 2 Min.l-3/16 Max. 10 Min,5-15/16
A36
z_ Warning:
Mount the indoor unit on a ceiling strong enough to withstand the weight of the
unit.
W
235 340 Min. 150 Min. 50 Min. 30 Max. 250 Max. 150
1400
55-1/8
235 340 Min. 150 Min. 50 Min. 30 Max. 250 Max. 150
1680
9-1/4 13-3/8 Min,5-15/1( Min. 2 Min. l-3/16 Max. 10 Min, 5-15/16
66-5/32
2.2. Outline dimensions (Outdoor unit)
3. Installing the indoor unit Refer to the outdoor unit installation manual.
3.1. Check the indoor unit accessories (Fig. 3=1)
The indoor unit should be supplied with the following accessories.
PARTNUMBER ACCESSORY
11@ Wall-fixing bracket
C2_ Tapping screw 4 x 35
Insulation material
(_) Band
1@ Felt tape
1@ Drain socket
C7_ Wireless remote controller
@ ®
Fig. 3=1
1@ Remote controller holder
1@ Alkali batteries
_) Wired remote controller
1@ Drain adaptor
(_)- _) are
stored in a cut-out section of the packing material (styrofoam).
QUANTITY
1
12
2
4 (large)+ 5 (small)
3
1
1
1
2
1
1
(inch)
LOCATIONOFSETTING
Fixatthebackoftheunit
Set inside the unit
for PKA-A.FAL
for PKA-A. FA
[] A24, A30
[] A36
• _,_2 .... _2
®
Fig. 3=2
d)
(inch)
3.2. Installing the wall mounting fixture (Fig. 3=2)
1) Setting the wall mounting fixture and piping positions
_. Using the wall mounting fixture, determine the unit's installation position
and the locations of the piping holes to be drilled.
z./_ Warning:
Before drilling a hole in the wall, you must consult the building contractor,
_A_Indoor unit center line
(B_Left drain range
@ Right drain range
@ Hole for tapping screw
(_ Bolt hole
(_ Hole for tapping screw
Contour of the unit
Knockout hole for left rear piping
(i) Rear piping access hole (90-100 mm, 3-9/16 to 4 inch dia.)
2) Drilling the piping hole (Fig. 3-3)
_. Use a core drill to make a hole of 90-100 ram, 3-9/16 to 4 inch diameter in the
wall in the piping direction, at the position shown in the diagram to the left.
_. The hole should incline so that the outside opening is lower than the inside
opening.
_" insert a sleeve (with a 90 mm, 3-9/f6 inch diameter and purchased locally)
through the hole.
Note:
The purpose of the hole's inclination is to promote drain flow.
_A_Sleeve
_B_Hole
(C) (Indoors)
_ Wall
(_ (Outdoors)
©
®
©
Fig. 3=3
3
3. Installing the indoor unit
A24, A30 (inch) 3) InstaMng the wall mounting fixture
\\\\\
=, =,IM,n231
Min.G1/2
A36
Max. 19/32
Fig. 3=5
...........................................f .....................................
M}n.GI/2
Since the indoor unit weighs near 30 kg, 66 Ibs, selection of the mounting
location requires thorough consideration. If the wall does not seem to be
strong enough, reinforce it with boards or beams before installation.
The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(if possible, secure the fixture at all the positions marked with a bold arrow.)
(Fig. 3-4)
Secure the wall mounting fixture through its middle row of 12-mm, t/2
inch-dia, holes using locally purchased bolts (through bolts, bolt anchor
and nut anchor) of Mr0 or W3/6 threading.The bolt tip must not protrude by
more than 15 ram, 9/32 inch from the wall surface. (Fig. 3-5)
Use at least two bolts for a concrete wall, and at least four bolts for a foamed
concrete wail
_A_Wall-fixing bracket _B_Mounting bolt _C_Wall
Z_ Warning:
if possible, secure the fixture at all the positions marked with a bold arrow.
Z_ Caution:
The unit body must be mounted horizontally,
Fig. 3=4
3.3. Preparation for piping connection
Remove the vinyl band that holds the drain piping.
• This vinyl band can be used to temporarily attach the pipes to the wall mounting
fixture while connecting the left pipe.
1) Rear, right and lower piping (Fig. 3-6)
1® Remove the right side panel.
2) Left and left rear piping
® Remove the side panel.
When embedding pipes into the wall (Fig. 3=7)
When the refrigerant pipe, drain pipes, internal/external connection lines, etc., are to
be embedded into the wall in advance, the extruding pipes, etc., may have to be bent
and have their length modified to the unit.
• Make the pipes to be embedded slightly longer than necessary, and install.
_A)Right side panel (C)On-site piping
_) Through hole CD)Wall-fixing bracket _
® Remove the five screws indicated by the arrows in the diagram. (Fig. 3-8)
® Remove the left side panel, then the lower panel.
1. While pushing up the front lower portion of the side panel (to disengage the side
panel catch from the unit catch), slide the upper portion of the side panel to the
left.
• When the indoor unit is already mounted, be sure the unit does not fall from the wall
mounting fixture.
• For reassembly, put the catch at the front lower portion of the side panel over the
unit body and push it to the right.
_A)Grille (_ Catch
_) Left side panel _) Side panel
(C) Lower panel (_ Unit body
_: Structure of the side panel and the unit body (Fig. 3-9)
1. Panel catch engages the unit body catch.
2. Panel catch is put in the unit body hole.
3. Panel catch engages the unit body catch.
4. Sheet metal of the unit body enters the panel.
5. Panel catch enters the unit body hole.
®
The drain hose can be connected at two different positions. Use the most conven-
ient position and, if necessary, exchange the position of the drain pan, rubber plug
and the drain hose. (Fig. 3-10)
@ Drain pan
_) Band
Plug
_J)Drain hose
(© Screwdriver
®
Fig. 3=6
Fig. 3=7
® ®
Fig. 3=8
Fig. 3=10
4
3. Installing the indoor unit
d)
®
Fig. 3=11
4. Installing the refrigerant piping
4.1. Precautions
3.4. Mounting the indoor unit (Fig. 3-11)
(j) Make sure to hang the metal catches of the indoor unit over the hooks of the wall
mounting fixture.
When the piping has been completed, use the securing screws to fix the indoor
unit on the wall mounting fixture.
Note:
Check that the catches of the indoor unit securely fit over the hooks of the wall
mounting fixture.
3_ The screw indicated by the bold arrow is used only during transportation and
should be removed. Remove the screw before installation if there is not enough
space at the left side to remove it once the unit has been installed.
_A_Indoor unit
(B_Wall fixing bracket _
(C) Hook
_ Metal catch of the indoor unit
(9 Securing screws
4.1.1. For devices that use R410A refrigerant
= Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration oil
applied to the flared sections.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. Use refrigerant pipes with the thicknesses
specified in the table to the below. Make sure the insides of the pipes are
clean and do not contain any harmful contaminants such as sulfuric com-
pounds, oxidants, debris, or dust.
z_ Warning:
When installing or moving the air conditioner, use only the specified refriger-
ant (R4t 0A) to charge the refrigerant lines. Do not mix it with any other refriger-
ant and do not allow air to remain in the lines. Air enclosed in the lines can
cause pressure peaks resulting in a rupture and other hazards.
(_) 45o±2 ° (_
® Flare cutting dimensions
Copper pipe O.D. Flare dimensions
(mm, inch) _A dimensions (ram, inch)
e6.35, 1/4" 8.7- 9.1, 11/32-23/64
e9.52, 3/8" 12.8 - 13.2, 1/2-33/64
o12.7, 1/2" 16.2 - 16.6, 41/64-21/32
e15.88, 5/8" 19.3 - 19.7, 49/64-25/32
Fig. 4-1
Liquid pipe e9.52 mm, 3/8 inch thickness 0.8 mm, 1/32 inch
Gas pipe o15.88 mm, 5/8 inch thickness 1.0 mm, 3/64 inch
= Do not use pipes thinner than those specified above.
A24, A30, A36
(inch) 4.2. Connecting pipes (Fig. 4-1)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C, 212 °F or
more, thickness of 12 mm, 1/2 inch or more).
The indoor parts of the drain pipe should be wrapped with polyethylene foam insu-
lation materials (specific gravity of 0.03, thickness of 9 mm, 23/64 inch or more).
(_ • Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening
flare nut.
Use two wrenches to tighten piping connections.
Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-
late carefully.
(_) Flare nut tightening torque
Copper pipe O.D.
(mm, inch)
06.35, 1/4"
09.52, 3/8"
o12.7, 1/2"
o15.88, 5/8"
(c) Apply refrigerating machine oil over the entire flare seat surface.
_ Use correct flare nuts meeting the pipe size of the outdoor unit.
Available pipe size
Liquid side
Gas side
O : Factory flare nut attachment to the heat-exchanger.
Flare nut O.D. Tightening torque
(mm, inch) (N.m, ft.lbs)
17, 43/64 14- 18, 10-13
22, 7/8 34 - 42, 25-30
26, 1-3/64 49 - 61,35-44
29, 1-9/64 68 - 82, 49-59
A24, A30, A36
09.52
e15.88
5