Mitsubishi PEFY-P71VMA-E, PEFY-P63VMA-E, PEFY-P80VMA-E, PEAD-RP71JA, PEFY-P100VMA-E Technical Manual

...
AIR CONDITIONERS
AIR VOLUME CONTROL TECHNICAL MANUAL
2009
Models
PEAD-RP60JA(L) PEAD-RP71JA(L) PEAD-RP100JA(L) PEAD-RP125JA(L) PEAD-RP140JA(L)
PEFY-P63VMA(L)-E PEFY-P71VMA(L)-E PEFY-P80VMA(L)-E PEFY-P100VMA(L)-E PEFY-P125VMA(L)-E PEFY-P140VMA(L)-E
CONTENTS
1. Air volume control by analog input ......................2
2. Air volume control by contact input .....................5
3. Fan characteristic curves ....................................7
4. Restrictions .......................................................17
5. Wiring ...............................................................18
6. Function settings ...............................................20
1
2
Air volume control technical manual
Indoor unit air volume can be controlled with a opening-closing of a damper by either an analog input (CN2A) or a contact input (CN105) to the air conditioning unit. With the PEAD series, it is possible to cut energy consumption by controlling not only the air volume but also the compressor capacity.
Corresponding model
Air volume can be controlled with the following models. (
1) PEAD-RP60,71,100,125,140JA(L)
(2) PEFY-P63,71,80,100,125,140VMA(L)-E
NOTE:
Air volume control with analog input 0-10V is not available with the following models. (
a) PEAD-RP35,50JA(L)
(b) PEFY-P20,25,32,40,50VMA(L)-E
System conguration
PEAD
Damper System Remote controller
Damper System Controller
Indoor unit
Air inlet
Bypass damper
Damper
Outdoor unit
Field supply
MA Remote controller
MAC-397IF-E *
Analog input Contact input
CN2A
CN105
Supply connectors to CN2A and CN105 on site. (Refer to 5) * MAC-397IF-E:MA & Contact terminal interface (optional)
PEFY
Damper System Remote controller
Damper System Controller
Indoor unit
Air inlet
Bypass damper
Damper
Outdoor unit
Field supply
MA Remote controller
MAC-397IF-E *
Analog input Contact input
M-NET
CN2A
M-NET
CN105
Damper System Remote controller
Damper System Controller
Indoor unit
Air inlet
Bypass damper
Damper
Field supply
MA Remote controller
MAC-397IF-E *
Analog input Contact input
CN2A
CN105
Centralized controller (AG-150A)(optional)
Supply connectors to CN2A and CN105 on site. * MAC-397IF-E:MA & Contact terminal interface (optional)
2
1-1. Air volume control
Indoor air volume can be controlled in 10 different stages from V1 to V10 with analog input 0-10V from the damper system controller supplied on site.
0
10
20
30
40
50
60
70
80
90
100
V1 V2 V3 V4 V5 V6 V7 V8 V9 V10
Air volume stage (0-10V analog input)
Air volume rate (%)
PEAD-RP60,71JA(L) PEFY-P63,71,80VMA(L)-E
PEAD-RP100,125,140JA(L) PEFY-P100,125,140VMA(L)-E
*Air volume rate shows the value without change in the external static pressure. For values in different external static pressure, refer to 3. Fan characteristic curves for details.
1-2. Outdoor unit capacity control
With the PEAD series, compressor capacity is controlled in accordance with air volume level in 10 stages from V1 to V10. With the PEFY series, compressor capacity will not be controlled because numbers of indoor units are connected. However, it is possible to reduce energy consumption with a change in the air volume leading to compressor capacity control due to a change in condensing temperature.
0
10
20
30
40
50
60
70
80
90
100
V1 V2 V3 V4 V5 V6 V7 V8 V9 V10
Air volume stage (0-10V analog input)
Outdoor unit capacity rate (%)
* Outdoor unit capacity rate may change depending on the outdoor temperature.
PEAD-RP60,71,100,125,140JA(L)
1. Air volume control by analog input
3
4
1-3. Analog input of voltage
With analog input of voltage, fan rotation and air volume in 10 stages from V1 to V10 can be controlled.
Air volume stages Analog input voltage(V)
Air volume
standard setting
(Damper System OFF) *1
V1 0.0~1.5
-
V2 1.0~2.5 V3 2.0~3.5 V4 3.0~4.5 V5 4.0~5.5 V6 5.0~6.5 V7 6.0~7.5 Low V8 7.0~8.5
Middle
V9 8.0~9.5
V10 9.0~10.0 High
NOTE: *1 In case of PEAD-RP JA(L) Dip SW 1-1 OFF, PEFY-P VMA(L)-E Dip SW 3-6 OFF, refer to 6-1.
Differentials of air volume stages V1 to V10
V2 V1
0
V6 V5 V4 V3
V10
V9 V8 V7
9.0 10.07.0 8.03.0 4.0 5.0 6.01.0 2.0
1.5 2.5 3.5 4.5 5.5 6.5 7.5 8.5 9.5
Air
Volume
stage
Input Voltage [V]
Example of analog input of voltage
When analog input changes
1
7.2V→27.5V→37.2V→47.0V→56.3V→66.0V→76.3V→
8
6.5V,
air volume stages are decided as
1
V7→2V8→3V8→4V7→5V7→6V6→7V6→
8
V7.
See drawing below for details.
V6
V8
V7
7.06.0
6.5 7.5
14
8
5
76
3 2
Air
Volume
stage
Input Voltage [V]
4
1-4. Example of air volume control 1
Air volume can be selected in the following order.
Condition:
1. R1- R4 indicates the air outlet of each indoor unit.
2. R4 fully open at all times.
3. Air volume designed as R1: 5m
3
/min, R2: 5m3/min, R3: 7m3/min, R4:17m3/min.
4. Rated air volume measured when R1 - R3 is fully open. (External static pressure set as 100Pa)
[Fig.1-4-1] Example of duct system
Damper System Remote controller
Damper System Controller
Indoor unit
Air inlet
Bypass damper
Damper
Air outlet
R4
17m3/min 7m3/min 5m3/min 5m3/min
R3 R2 R1
Field supply
MAC-397IF-E *
Analog input Contact input
CN105
CN2A
Selecting air volume stage V1~V10
Depending on the damper opening pattern R1-R3, patterns
1~8
as in the below chart is available. The air volume stage is selected from the fan characteristic curve. (Refer to [Fig. 1-4-3]) Choose the pattern closest to the required air volume and which the diagram exceeds. Duct pressure drop depends on the site conditions. Shown here are temporarily numbers in case of external static pressure 100Pa.
Air Outlet R1 R2 R3 R4
Total Air volume
[m3/min]
Selected
Stage
Air Volume
[m3/min] 5 5 7 17 34 -
Air volume pattern
1
Open Open Open Open 34 V10
2
Close Open Open Open 29 V9
3
Open Close Open Open 29 V9
4
Close Close Open Open 24 V7
5
Open Open Close Open 27 V8
6
Close Open Close Open 22 V7
7
Open Close Close Open 22 V7
8
Close Close Close Open 17 V5
[Fig.1-4-2] Air volume pattern
*1~8in the below diagram [Fig.1-4-3] indicates the air volume pattern1~8shown in this chart [Fig. 1-4-2]
10 15 20 25 30 35 40 45
Airflow rate(m3/min)
External static pressure (Pa)
[Fig.1-4-3] Duct damper open/close
PEAD-RP100JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
0
20
40
60
80
100
120
140
160
V1
V4
V5
V6
V7
V8
V9
V10
V3 V2
8 6 7 2 3 14 5
Limit
Limit
5
6
Example of system ow
The following explains the system ow for duct damper open/close pattern
1~6
shown in [Fig.1-4-3].
Condition: Voltage decrease from 10.0V to 3.7V when duct damper changes from full-open to R1,R3 close.
ޓ
On site
............<Section1-3>
.............<Section1-3>
........<Section1,3>
CN21 0-10V Analog input
10.0V→3.7V
Damper System Remote Controller R1,R3
close
Operation signal ON→OFF
Damper System Remote Controller
R1,R2,R3,R4 full-open operation
Air volume step
V10→V4
Damper System Controller Analog output 10.0V→3.7V
Air volume
34m3/min→22m3/min
Outdoor unit capacity rate
100%→65%
2-1. Function control by MAC-397IF-E (CN105)
Following functions can be controlled from damper system controller by using MAC-397IF-E.
1. ON/OFF
2. Cooling/ Heating/ Fan mode
3. Air volume rate change (Hi-Mid-Lo)
PRECAUTION:
Multistage air volume control is not available via MAC-397IF-E. In order to control multistage air volume and compressor capacity (PEAD series), use 0-10V analog input (CN2A).
No.
Function change from Damper
system controller
MAC-397IF-E use
Indoor unit control board
switch setting
PEAD PEFY SW1-1 SW3-6
1
ON / OFF
Ο
OFF
2
Cooling/ Heating/ Fan
Ο
OFF
3
Air volume rate change
(Hi-Mid-Lo)
Ο
OFF
NOTE*1 In order to change functions1~3from MAC-397IF-E, contact input from damper system controller is required. Only one of the functions1~3is
available one at a time because setting is made by switching DIP-SW of MAC-397IF-E. Refer to the MAC-397IF-E manual for DIP-SW setting and wiring.
*2 When not using MAC-397IF-E,
1~3
functions only available from MA remote controller.
*3 Combination of function
3
and analog input is not available.
2. Air volume control by contact input
6
2-2. Example of air volume control by contact input and analog input
Supply connecters to CN2A and CN105 on site. (Refer to 5). * MAC-397IF-E:MA & Contact terminal interface (optional)
Refer to the MAC-397IF-E manual for DIP-SW setting and wiring.
MAC-397IF-E input
Damper System Remote controller
Damper System Controller
Indoor unit
Bypass damper
Damper
Outdoor unit
Field supply
MA Remote controller
CN2A
MAC-397IF-E *
CN105
CN105 CN560
Indoor unit MAC-397IF-E
Lead wires
Contact point a (about 10mA)
Damper System Controller
1. Contact input When either of the damper open/close with damper system controller, ON/OFF signal via MAC-397IF-E.
2. Analog input Air volume controllable with analog input to CN2A, controlling open/close of duct damper.
* It is possible to directly command CN105 without MAC-397IF-E with serial communication. For further details, contact your nearest distributor.
1 2 3 5 64
■Dip switch (SW500) setting
(1) Contact input
ON
2 43 5 6 7 81
Air inlet
←(2) Analog input
CN591
2-3. Example of air volume control with xed static pressure
This example shows how to keep duct static pressure at a constant level with analog input.
Damper System Remote controller
Damper System Controller
Indoor unit
Air inlet
Bypass damper
Damper
air outlet
R4
17m3/min 7m3/min 5m3/min 5m3/min
R3 R2 R1
Field supply
MAC-397IF-E *
Analog input
Contact input
CN105
CN2A
Check air volume at each air outlet when R1-R4 is full open and set static pressure as target value. Then, analog input to keep the static pressure at this target value even when either of the damper closes. With MAC-397IF-E as in section 2-2, it is also possible to stop the indoor unit when all duct damper closes.
*Refer to the 1-3 for air volume differentials to prevent hunting.
7
8
With an analog input of 0-10V, indoor air volume can be controlled in 10 steps from V1 to V10.
Rated point
V1~4
V5
V6
V7
V8
V9
V10
Limit
Airflow rate(m3/min)
External static pressure (Pa)
10 15 20 25 30
0
20
40
60
PEAD-RP60JA(L)
(External static pressure 35Pa) 220-240V 50/60Hz
V1,2
V3
V4
V5
V6
V7
V8
V9
V10
Limit
Limit
Rated point
Airflow rate(m3/min)
External static pressure (Pa)
10 15 20 25 30
20
40
60
120
100
80
PEAD-RP60JA(L)
(External static pressure 100Pa) 220-240V 50/60Hz
Airflow rate(m3/min)
External static pressure (Pa)
10 15 20 25 30
0
40
20
60
80
PEAD-RP60JA(L)
(External static pressure 50Pa) 220-240V 50/60Hz
Rated point
V1,2
V3
V4
V5
V6
V7
V8
V9
V10
Limit
Airflow rate(m3/min)
External static pressure (Pa)
10 15 20 25 30
50
150
100
PEAD-RP60JA(L)
(External static pressure 150Pa) 220-240V 50/60Hz
Rated point
V1,2
V3
V4
V5
V6
V7
V8
V9
V10
Limit
Limit
Airflow rate(m3/min)
External static pressure (Pa)
10 15 20 25 30
0
100
20
40
60
80
PEAD-RP60JA(L)
(External static pressure 70Pa) 220-240V 50/60Hz
Rated point
V1,2
V3
V4
V5
V6
V7
V8
V9
V10
Limit
Limit
3. Fan characteristic curves
Loading...
+ 16 hidden pages