Mitsubishi Electronics PEA-RP250 WHA User Manual

Air-Conditioners INDOOR UNIT
PEA-RP250 WHA
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
GB
3
[Fig. 3.2.1]
4
150~200
300
~
B
200
450
A
730
50
50
23 1324 23
470
AE
1100800
C
1350
1034
Keep the service space for the maintenance from the bottom when the heat exchanger is cleaned.
D
1100
more than 100
60
371250
more than 20
more than 20
A Access door B Electrical parts box C Air inlet D Air outlet E Ceiling surface
10
±
30
[Fig. 4.1.1]
235
5
[Fig. 5.1.1] [Fig. 5.1.2] [Fig. 5.3.1]
1034 1324
701494
A
A
A Center of gravity
C
D
D
C
B
C Nuts (field supply)
A Unit body B Lifting machine
D Washers (accessory) E M10 hanging bolt (field supply)
6
E
A
A Indoor unit’s bottom surface
[Fig. 6.2.1]
2
B
D
100 244
C
A
30
E
424
F
165 52
A Air inlet B Refrigerant piping (liquid) C Refrigerant piping (gas) D Control box E Drain pipe F Air outlet
7
[Fig. 7.1.1]
[Fig. 7.1.3]
J
K
[Fig. 7.1.2]
A
A Cool by a wet cloth
A Cut here B Remove brazed cap
A Thermal insulation tubing (small)
A
B
C
E
D
M
G
P
N
O
F
I
20
20
K
H
E
L
20
J
20
M
Q
R
B Caution:
Pull out the thermal insulation on the refrigerant piping at the site, braze the piping, and replace the insulation in its original position.
Ta ke care to ensure that condensation does not form on exposed copper piping.
C Refrigerant piping (liquid) D Refrigerant piping (gas) E Main body F Thermal insulation tubing (large) G Site refrigerant piping H Ensure that there are no gaps between the insulation
and the main body.
I Thermal insulation tubing (small) (supplied) 1 J Ties (large) (supplied) 4 K Ensure that there is no gap here. Place join upwards. L Thermal insulation tubing (medium) (supplied) 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here.
[Fig. 7.2.1]
A
B 1
[Fig. 7.2.2]
I
A
B
525
D
A Indoor unit B Insulation pipe (short) (accessory) C Tie band (accessory) D Band fixing part E Insertion margin F Drain hose (accessory) G Drain pipe (O.D. ø32 PVC TUBE, field supply) H Insulating material (field supply) I Max.145 ± 5 mm
C C C
E
D 2
F
E
G
H
C
A Downward slope 1/100 or more B Drain hose (Accessory) C Indoor unit D Collective piping E Maximize this length to approx. 10 cm
3
8
[Fig. 8.0.1]
D
C
D
C
B
A
A Air inlet B Air filter (supplied at site) C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct-work length 850 mm or more
9
[Fig. 9.1.1] [Fig. 9.2.1]
A Switch 16 A B Overcurrent protection 16 A C Indoor unit
AB
C
[Fig. 9.2.2]
I
E
G
F
H
B
M1M2 21
TB3
B
D
N
L
1
S
M2
M1
DC10~13V
AB 12
A
SM1 M2
TB5 TB15
C
2
A
C
A Te rminal block for indoor
transmission cable
B Te r minal block for outdoor
transmission cable
C Remote controller
A Non-polarized B TB15 C Remote Controller D TB5
4
B
C
A
[Fig. 9.3.1] [Fig. 9.3.2]
B
A
A Screw holding cover (2pcs) B Cover
[Fig. 9.3.3]
E
F
L
L
N
G
M
L
N
M1
M2 S
12
I
J
K
A Te r minal bed box B Knockout hole C Remove
M1
M2
H
O
N
E Use PG bushing to keep the weight of the cable and external force from being
applied to the power supply terminal connector. Use a cable tie to secure the cable. Wind the wire around the cable strap once to keep it from being pulled out.
F Power source wiring G Tensile force H Use ordinary bushing
[Fig. 9.3.4]
M2 SM1
B
A
A Te rminal bed B Round terminal C Shield wire D Insulation tape (To keep the earth wire of the shielded cable from coming in contact with the transmis-
D
C
[Fig. 9.5.1]
I Power source terminal bed J Te rminal bed for indoor transmission K Te rminal bed for remote controller L To 1-phase power source M Tr ansmission line DC 30 V N Te rminal bed for outdoor transmission line (TB3) O Tr ansmission line to the remote controller
sion terminal)
SWA
SW5
SW14
SW12
<Indoor controller board>
SW11
SWC
5
Contents
1. Safety precautions ...................................................................................... 6
1.1. Before installation and electric work .......................................... 6
1.2. Precautions for devices that use R410A refrigerant .................. 6
1.3. Before getting installed .............................................................. 7
1.4. Before getting installed (moved) - electrical work ...................... 7
1.5. Before starting the test run ........................................................ 7
2. Indoor unit accessories ............................................................................... 7
3. Selecting an installation site ....................................................................... 7
3.1. Install the indoor unit on a ceiling strong enough to sustain
its weight .................................................................................... 8
3.2. Securing installation and service space .................................... 8
3.3. Combining indoor units with outdoor units ................................. 8
4. Fixing hanging bolts .................................................................................... 8
4.1 Fixing hanging bolts ................................................................... 8
5. Installing the unit ......................................................................................... 8
5.1. Hanging the unit body ................................................................ 8
5.2. Transporting the heat exchanger unit and the fan unit
GBDFEINLPGRRUTR
separately .................................................................................. 8
1. Safety precautions
1.1. Before installation and electric work
s Before installing the unit, make sure you read all the “Safety
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the unit.
Symbols used in the illustrations
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Indicates that caution should be taken with rotating parts. (This symbol is
displayed on the main unit label.) <Color: Yellow>
:Beware of electric shock (This symbol is displayed on the main unit label.)
<Color: Yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock, or fire.
• Install the air unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
• Use the specified cables for wiring. Make the connections securely so that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for typhoons and other strong winds and earthquakes and in­stall the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
•Always use an air cleaner, humidifier, electric heater, and other accesso­ries specified by Mitsubishi Electric.
CZSVHGPO
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
•Never repair the unit. If the air conditioner must be repaired, consult the dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• When handling this product, always wear protective equipment. EG: Gloves, full arm protection namely boiler suit, and safety glasses.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
6
5.3. Confirming the unit’s position and fixing hanging bolts .............. 8
6. Refrigerant pipe and drain pipe specifications ............................................ 8
6.1. Refrigerant pipe and drain pipe specifications ........................... 9
6.2. Refrigerant pipe, drain pipe ....................................................... 9
7. Connecting refrigerant pipes and drain pipes ............................................. 9
7.1. Refrigerant piping work .............................................................. 9
7.2. Drain piping work ....................................................................... 9
8. Duct work .................................................................................................. 10
9. Electrical wiring ......................................................................................... 10
9.1. Power supply wiring ................................................................. 10
9.2. Connecting remote controller, indoor and outdoor
transmission cables ................................................................. 10
9.3. Connecting electrical connections ........................................... 11
9.4. External I/O specifications ....................................................... 11
9.5. Selecting the external static pressure ...................................... 11
9.6. Setting addresses .................................................................... 11
9.7. Sensing room temperature with the built-in sensor in
a remote controller ................................................................... 11
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may result.
•Have all electric work done by a licensed electrician according to “Elec­tric Facility Engineering Standard” and “Interior Wire Regulations”and the instructions given in this manual and always use a special circuit.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
•Keep the electric parts away from water (washing water etc.).
- It might result in electric shock, catching fire or smoke.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
• When installing and moving the air conditioner to another site, do not charge the it with a refrigerant different from the refrigerant specified on the unit.
- If a different refrigerant or air is mixed with the original refrigerant, the refrig-
erant cycle may malfunction and the unit may be damaged.
• If the air conditioner is installed in a small room, measures must be taken to prevent the refrigerant concentration from exceeding the safety limit even if the refrigerant should leak.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or parts other than those specified by Mitsubishi Elec­tric are used, fire or explosion may result.
•To dispose of this product, consult your dealer.
• Do not use a leak detection additive.
1.2. Precautions for devices that use R410A
refrigerant
Caution:
• Do not use the existing refrigerant piping.
- The old refrigerant and refrigerator oil in the existing piping contains a large
amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.
• Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized copper as specified in the JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav­ing particles, oils, moisture, or any other contaminant.
- Contaminants on the inside of the refrigerant piping may cause the refriger-
ant residual oil to deteriorate.
• Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)
- If dust, dir t, or water enters the refrigerant cycle, deterioration of the oil and
compressor trouble may result.
• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.
- The refrigerator oil will degrade if it is mixed with a large amount of mineral oil.
• Use liquid refrigerant to fill the system.
- If gas refrigerant is used to seal the system, the composition of the refriger-
ant in the cylinder will change and performance may drop.
• Do not use a refrigerant other than R410A.
- If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may
cause the refrigerator oil to deteriorate.
• Use a vacuum pump with a reverse flow check valve.
- The vacuum pump oil may flow back into the refrigerant cycle and cause the
refrigerator oil to deteriorate.
• Do not use the following tools that are used with conventional refriger­ants. (Gauge manifold, charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment)
- If the conventional refrigerant and refrigerator oil are mixed in the R410A,
the refrigerant may deteriorated.
- If water is mixed in the R410A, the refrigerator oil may deteriorate.
- Since R410A does not contain any chlorine, gas leak detectors for conven-
tional refrigerants will not react to it.
• Do not use a charging cylinder.
- Using a charging cylinder may cause the refrigerant to deteriorate.
• Be especially careful when managing the tools.
- If dust, dir t, or water gets in the refrigerant cycle, the refrigerant may deterio-
rate.
1.3. Before getting installed
Caution:
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instru­ments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air condi­tioner may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80% or when the drain pipe is clogged,
condensation may drip from the indoor unit. Perform collective drainage work together with the outdoor unit, as required.
• The indoor models should be installed the ceiling over than 2.5 m from floor.
1.4. Before getting installed (moved) - elec-
trical work
Caution:
•Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
-Tension may cause the cable to break and generate heat and cause a fire.
• Install an leak circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
-A fuse or circuit breaker of a larger capacity or a steel or copper wire may result in a general unit failure or fire.
• Do not wash the air conditioner units.
-Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury or property damage.
• Install the drain piping according to this Installation Manual to ensure proper drainage. Wrap thermal insulation around the pipes to prevent condensation.
- Improper drain piping may cause water leakage and damage to furniture
and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
- When transporting the outdoor unit, suspend it at the specified positions on
the unit base. Also support the outdoor unit at four points so that it cannot slip sideways.
• Safely dispose of the packing materials.
-Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
-Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart, they face the risk of suffocation.
1.5. Before starting the test run
Caution:
•Turn on the power at least 12 hours before starting operation.
- Star ting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on during the operational season.
• Do not touch the switches with wet fingers.
-Touching a switch with wet fingers can cause electric shock.
• Do not touch the refrigerant pipes during and immediately after opera­tion.
- During and immediately after operation, the refrigerant pipes are may be hot
and may be cold, depending on the condition of the refrigerant flowing through the refrigerant piping, compressor, and other refrigerant cycle parts. Your hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
GBDFEINLPGRRUTRCZSVHGPO
2. Indoor unit accessories
The unit is provided with the following accessories:
No. Accessories Quantity
1 Insulation pipe 25 mm small diameter 1 2 Insulation pipe 125 mm small diameter 1 3 Insulation pipe 120 mm large diameter 1 4 Tie band (small) 2 5 Tie band (large) 5 6 Drain hose 1 7 Washer 8 8 Wired remote controller 1
3. Selecting an installation site
• Select a site with sturdy fixed surface sufficiently durable against the weight of unit.
• Before installing unit, the routing to carry in unit to the installation site should be determined.
• Select a site where the unit is not affected by entering air.
• Select a site where the flow of supply and return air is not blocked.
• Select a site where refrigerant piping can easily be led to the outside.
• Select a site which allows the supply air to be distributed fully in room.
• Do not install unit at a site with oil splashing or steam in much quantity.
• Do not install unit at a site where combustible gas may generate, flow in, stag­nate or leak.
• Do not install unit at a site where equipment generating high frequency waves (a high frequency wave welder for example) is provided.
7
• At a distance 1 m or more away from your TV and radio (to prevent picture from being distorted or noise from being generated).
• In a place as far away as possible from fluorescent and incandescent lights (so the infrared remote control can operate the air conditioner normally).
• Do not install unit at a site where fire detector is located at the supply air side. (Fire detector may operate erroneously due to the heated air supplied during heating operation.)
• When special chemical product may scatter around such as site chemical plants and hospitals, full investigation is required before installing unit. (The plastic components may be damaged depending on the chemical product applied.)
• If the unit is run for long hours when the air above the ceiling is at high tem­perature/high humidity (due point above 26 °C), due condensation may be produced in the indoor unit. When operating the units in this condition, add insulation material (10-20 mm) to the entire surface of the indoor unit to avoid due condensation.
• Do not install the unit where ambient temperature exceeds 35 °C [95 °F] DB.
3.1. Install the indoor unit on a ceiling strong
GBDFEINLPGRRUTR
enough to sustain its weight
Warning:
The unit must be securely installed on a structure that can sustain its weight. If the unit is mounted on an unstable structure, it may fall down causing injuries.
4. Fixing hanging bolts
3.2. Securing installation and service space
• Select the optimum direction of supply airflow according to the configuration of the room and the installation position.
• As the piping and wiring are connected at the bottom and side surfaces, and the maintenance is made at the same surfaces, allow a proper space properly. For the efficient suspension work and safety, provide a space as much as possible.
[Fig. 3.2.1] (P.2)
A Access door B Electrical parts box C Air inlet D Air outlet E Ceiling surface
3.3. Combining indoor units with outdoor
units
For combining indoor units with outdoor units, refer to the outdoor unit installation manual.
4.1 Fixing hanging bolts
[Fig. 4.1.1] (P.2)
A Center of gravity
(Give site of suspension strong structure.)
Hanging structure
• Ceiling: The ceiling structure varies from building to one another. For detailed information, consult your construction company.
Center of gravity and Product Weight
Model name
PEA-RP250 WHA
W
1034
L
1324
5. Installing the unit
5.1. Hanging the unit body
ss
s Bring the indoor unit to an installation site as it is packed.
ss ss
s To hang the indoor unit, use a lifting machine to lift and pass through the
ss
hanging bolts.
[Fig. 5.1.1] (P.2)
A Unit body B Lifting machine
[Fig. 5.1.2] (P.2)
C Nuts (field supply) D Washers (accessory) E M10 hanging bolt (field supply)
5.2. Transporting the heat exchanger unit
and the fan unit separately
ss
s Refer to the “Manipulation Details” label on the unit for how to separate
ss
the heat exchanger unit and the fan unit.
Caution:
Heat exchanger unit and the fan unit cannot be installed in separate loca­tions. Doing so will cause water leakage.
CZSVHGPO
• If necessary, reinforce the hanging bolts with anti-quake supporting members as countermeasures against earthquakes. * Use M10 for hanging bolts and anti-quake supporting members (field supply).
X
494
Y
701
235
Z
Product Weight (kg)
108
5.3. Confirming the unit’s position and fix-
ing hanging bolts
ss
s Use the gage supplied with the panel to confirm that the unit body and
ss
hanging bolts are positioned in place. If they are not positioned in place, it may result in dew drops due to wind leak. Be sure to check the positional relationship.
ss
s Use a level to check that the surface indicated by
ss
that the hanging bolt nuts are tightened to fix the hanging bolts.
ss
s To ensure that drain is discharged, be sure to hang the unit at level using
ss
a level.
[Fig. 5.3.1] (P.2)
A Indoor unit’s bottom surface
Caution:
Install the unit in horizontal position. If the side with drain port is installed higher, water leakage may be caused.
AA
A is at level. Ensure
AA
6. Refrigerant pipe and drain pipe specifications
To avoid dew drops, provide sufficient antisweating and insulating work to the re­frigerant and drain pipes. When using commercially available refrigerant pipes, be sure to wind commer­cially available insulating material (with a heat-resisting temperature of more than 100 °C and thickness given below) onto both liquid and gas pipes. Insulate all indoor pipes with form polyethylene insulation with a minimum density of 0.03 and a thickness as specified in the table below.
1 Select the thickness of insulating material by pipe size.
2 If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating material’s thickness more than those given in the table above.
3 If there are customer’s specifications, simply follow them.
8
Pipe size Insulating material’s thickness
6.4 mm to 25.4 mm More than 10 mm
28.6 mm to 38.1 mm More than 15 mm
6.1. Refrigerant pipe and drain pipe specifications
Item
Refrigerant pipe
(Brazing connection)
Model
Liquid pipe ø 9.52
Gas pipe ø 22.2
Drain pipe O.D. ø 32
250
6.2. Refrigerant pipe, drain pipe
[Fig. 6.2.1] (P.2)
A Air inlet B Refrigerant piping (liquid) C Refrigerant piping (gas) D Control box E Drain pipe F Air outlet
7. Connecting refrigerant pipes and drain pipes
7.1. Refrigerant piping work
This piping work must be done in accordance with the installation manuals for both outdoor unit.
•For constraints on pipe length and allowable difference of elevation, refer to the outdoor unit manual.
• The method of pipe connection is brazing connection.
Caution:
• Install the refrigerant piping for the indoor unit in accordance with the following.
1. Cut the tip of the indoor unit piping, remove the gas, and then remove the brazed cap.
[Fig. 7.1.1] (P.3)
A Cut here B Remove brazed cap
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit piping, and replace the insulation in its original position. Wrap the piping with insulating tape.
Note:
• When blazing the refrigerant pipes, be sure to blaze, after covering a wet cloth to the pipes of the units in order to prevent it from burning and shrinking by heat.
[Fig. 7.1.2] (P.3)
A Cool by a wet cloth
•Pay strict attention when wrapping the copper piping since wrapping the piping may cause condensation instead of preventing it.
[Fig. 7.1.3] (P.3)
A Thermal insulation tubing (small) B Caution:
Pull out the thermal insulation on the refrigerant piping at the site, braze the pip­ing, and replace the insulation in its original position.
Ta ke care to ensure that condensation does not form on exposed copper piping.
C Refrigerant piping (liquid) D Refrigerant piping (gas) E Main body F Thermal insulation tubing (large) G Site refrigerant piping H Ensure that there are no gaps between the insulation and the main body. I Thermal insulation tubing (small) (supplied) 1 J Ties (large) (supplied) 4 K Ensure that there is no gap here. Place join upwards. L Thermal insulation tubing (medium) (supplied) 2 M Thermal insulation N Pull O Flared pipe end P Wrap with damp cloth Q Return to original position R Ensure that there is no gap here.
Cautions On Refrigerant Piping
ss
s Be sure to use non-oxidative brazing for brazing to ensure that no for-
ss
eign matter or moisture enter into the pipe.
ss
s Be sure to apply refrigerating machine oil over the flare connection seat-
ss
ing surface and tighten the connection using a double spanner.
ss
s Provide a metal brace to support the refrigerant pipe so that no load is
ss
imparted to the indoor unit end pipe. This metal brace should be pro­vided 50 cm away from the indoor unit’s flare connection.
When installing and moving the unit, do not charge it with refrigerant other than the refrigerant specified on the unit.
- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal­function and result in severe damage.
• Use refrigerant piping made of C1220 (Cu-DHP) phosphorus deoxidized
•Never use existing refrigerant piping.
• Store the piping to be used during installation indoors and keep both
7.2. Drain piping work
• Ensure that the drain piping is downward (pitch of more than 1/100) to the
• Ensure that any cross-wise drain piping is less than 20 m (excluding the differ-
• Use a hard vinyl chloride pipe O.D. ø32 for drain piping.
• Ensure that collected pipes are 10 cm lower than the unit body’s drain port.
• Do not provide any odor trap at the drain discharge port.
• Put the end of the drain piping in a position where no odor is generated.
1. Insert the drain hose (accessory) into the drain port.
2. Attach the drain pipe (O.D. ø32 PVC TUBE, field supply).
3. Perform insulation work on the drain pipe (O.D. ø32 PVC TUBE) and on the
Warning:
GBDFEINLPGRRUTRCZSVHGPO
Caution:
copper as specified in the JIS H3300 “Copper and copper alloy seamless pipes and tubes”. In addition, be sure that the inner and outer surfaces of the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav­ing particles, oils, moisture, or any other contaminant.
- The large amount of chlorine in conventional refrigerant and refrigerator oil in the existing piping will cause the new refrigerant to deteriorate.
ends of the piping sealed until just before brazing.
- If dust, dir t, or water gets into the refrigerant cycle, the oil will deteriorate and the compressor may fail.
outdoor (discharge) side. Do not provide any trap or irregularity on the way.
ence of elevation). If the drain piping is long, provide metal braces to prevent it from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
Do not put the end of the drain piping in any drain where ionic gases are generated.
[Fig. 7.2.1] (P.3)
A Downward slope 1/100 or more B Drain hose (Accessory) C Indoor unit D Collective piping E Maximize this length to approx. 10 cm
(The drain hose must not be bent more than 45° to prevent the hose from breaking or clogging.) The connecting part between the indoor unit and the drain hose may be dis­connected at the maintenance. Fix the part with the accessory band, not be adhered.
(Attach the pipe with glue for the hard vinyl chloride pipe, and fix it with the band (small, accessory).)
socket (including elbow).
[Fig. 7.2.2] (P.3)
A Indoor unit B Insulation pipe (short) (accessory) C Tie band (accessory) D Band fixing part E Insertion margin F Drain hose (accessory) G Drain pipe (O.D. ø32 PVC TUBE, field supply) H Insulating material (field supply) I Max.145 ± 5 mm
9
8. Duct work
• When connecting ducts, insert a canvas duct between the main body and the duct.
• Use non-combustible duct components.
• Install sufficient thermal insulation to prevent condensation forming on outlet duct flanges and outlet ducts.
Caution:
•Keep the distance between the inlet grille and the fan over 850 mm. If it is less than 850 mm, install a safety guard not to touch the fan.
9. Electrical wiring
Precautions on electrical wiring
Warning:
Electrical work should be done by qualified electrical engineers in accord-
GBDFEINLPGRRUTR
ance with “Engineering Standards For Electrical Installation” and supplied installation manuals. Special circuits should also be used. If the power cir­cuit lacks capacity or has an installation failure, it may cause a risk of elec­tric shock or fire.
1. Be sure to install an earth leakage breaker to the power.
2. Install the unit to prevent that any of the control circuit cables (remote control­ler, transmission cables) is brought in direct contact with the power cable out­side the unit.
3. Ensure that there is no slack on all wire connections.
4. Some cables (power, remote controller, transmission cables) above the ceiling may be bitten by mouses. Use as many metal pipes as possible to insert the cables into them for protection.
5. Never connect the power cable to leads for the transmission cables. Otherwise the cables would be broken.
[Fig. 8.0.1] (P.4)
A Air inlet B Air filter (supplied at site) C Duct D Canvas duct E Access door F Ceiling G Ensure sufficient length to prevent short cycling H Air outlet I Keep duct-work length 850 mm or more
6. Be sure to connect control cables to the indoor unit, remote controller, and the outdoor unit.
7. Put the unit to the ground on the outdoor unit side.
8. Select control cables from the conditions given in page
11
.
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not con­nect the earth cable to any gas pipe, water pipe, lightening rod, or telephone earth cable. Incomplete grounding may cause a risk of electric shock.
Types of control cables
1. Wiring transmission cables
•Types of transmission cables
Design wiring in accordance with the following table <Table 1>.
• Cable diameter
More than 1.25 mm
2
<Table 1>
Tr ansmission cable length Less than 80 m
Facility example
(for noise judgment)
Types of transmission
cables
2. Remote controller cables
Types of cables
Cable diameter
Length
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
Less than 200 m
Residence or independent store without noise
VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT or shielding wire CVVS or CPEVS
MA remote controller
2
Building, clinic, hospital or communications station without noise supposedly generated from inverter equipment, private power gen­erator, high-frequency medical equipment, radio-used communications equipment and so on
9.1. Power supply wiring
•Power supply cords of appliances shall not be lighter than design 245 IEC 57 or 227 IEC 57.
•A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
Power cable size: more than 2.0 mm
[Fig. 9.1.1] (P.4)
CZSVHGPO
A Switch 16 A B Overcurrent protection 16 A C Indoor unit
[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)]
To select NF or NV instead of a combination of Class B fuse with switch, use the following:
• In the case of Class B fuse rated 15 A or 20 A,
NF model name (MITSUBISHI): NF30-CS (15 A) (20 A) NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)
Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1 s.
2
Shielding wire CVVS or CPEVS
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large capacity may cause a risk of mal­function or fire.
9.2. Connecting remote controller, indoor and outdoor transmission cables
• Connect indoor unit TB5 and outdoor unit TB3. (Non-polarized 2-wire)
The “S” on indoor unit TB5 is a shielding wire connection. For specifications about the connecting cables, refer to the outdoor unit installation manual.
• Install a remote controller following the manual supplied with the remote con-
troller.
• Connect the “1” and “2” on indoor unit TB15 to a MA remote controller. (Non-
polarized 2-wire)
10
• Connect the remote controller’s transmission cable within 10 m using a 0.75 mm core cable. If the distance is more than 10 m, use a 1.25 mm2 junction cable.
[Fig. 9.2.1] (P.4) MA Remote controller
A Te r minal block for indoor transmission cable B Te r minal block for outdoor transmission cable C Remote controller
• DC 9 to 13 V between 1 and 2 (MA remote controller)
[Fig. 9.2.2] (P.4) MA Remote controller
A Non-polarized B TB15 C Remote Controller D TB5
Caution:
Install wiring so that it is not tight and under tension. Wiring under tension may break, or overheat and burn.
9.3. Connecting electrical connections
Please identify the model name of the operation manual attached on the terminal bed box cover with that shown on the rating name plate.
1. Remove the screw (2pcs) holding the cover to dismount the cover.
[Fig. 9.3.1] (P.5)
A Screw holding cover (2pcs) B Cover
2. Open knockout holes (Recommend to use a screwdriver or the like for this work.)
[Fig. 9.3.2] (P.5)
A Te r minal bed box B Knockout hole C Remove
3. Fix power source wiring to terminal bed box by using buffer bushing for tensile force. (PG connection or the like.) Connect transmission wiring to transmission terminal bed through the knockout hole of terminal bed box using ordinary bushing.
Connect the power source, Earth, transmission and remote controller wiring. The dismounting of the terminal bed box is not needed.
[Fig. 9.3.3] (P.5)
E Use PG bushing to keep the weight of the cable and external force from being
applied to the power supply terminal connector. Use a cable tie to secure the cable. Wind the wire around the cable strap once to keep it from being pulled out.
F Power source wiring G Tensile force H Use ordinary bushing I Power source terminal bed J Te r minal bed for indoor transmission K Te r minal bed for remote controller L To 1-phase power source M Tr ansmission line DC 30 V N Te r minal bed for outdoor transmission line (TB3) O Tr ansmission line to the remote controller
[Shield wire connection]
[Fig. 9.3.4] (P.5)
A Te r minal bed B Round terminal C Shield wire D Insulation tape (To keep the earth wire of the shielded cable from coming in con-
tact with the transmission terminal)
5. After wiring is complete, make sure again that there is no slack on the connec­tions, and attach the cover onto the terminal bed box in the reverse order of removal.
Notes:
• Do not pinch the cables or wires when attaching the terminal bed box cover. Doing so may cause a risk of disconnection.
• When accommodating the terminal bed box, make sure that the connec­tors on the box side are not removed. If removed, it cannot operate nor­mally.
2
9.4. External I/O specifications
Caution:
1. Wiring should be covered by insulation tube with supplementary insula­tion.
2. Use relays or switches with IEC or equivalent standard.
3. The electric strength between accessible parts and control circuit should have 2750 V or more.
9.5. Selecting the external static pressure
As the factory setting is for use under an external static pressure of 150 Pa, no switch operation is needed when using under the standard condition.
External static pressure Switch operation
SWA
60 Pa
75 Pa
100 Pa
150 Pa
3 2 1
SWA
3 2 1
SWA
3 2 1
SWA
3 2 1
9.6. Setting addresses
(Be sure to operate with the main power turned OFF.)
• There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch numbers. 1 How to set addresses
Example: If Address is “1”, remain SW12 (for over 10) at “0”, and match SW11(for 1 to 9) with “1”.
• The rotary switches are all set to “0” when shipped from the factory. These switches can be used to set unit addresses and branch numbers at will.
9.7. Sensing room temperature with the
built-in sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote control­ler, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF.
Note:
•To perform the auto cooling/heating operation, use the built-in sensor in a remote controller or the optional remote sensor.
SWC
SWC
SWC
SWC
2
1
2
1
2
1
2
1
GBDFEINLPGRRUTRCZSVHGPO
11
This product is designed and intended for use in the residential, commer-
cial and light-industrial environment.
The product at hand is based on the following EU regulations:
Low Voltage Directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC
WT05750X01
Please be sure to put the contact address/telephone number on
this manual before handing it to the customer.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
Authorized representative in EU: MITSUBISHI ELECTRIC EUROPE B.V.
HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX UB8 1QQ, U.K.
Loading...