INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D’INSTALLATION
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d’aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
GB
D
F
E
I
NL
SW
INSTALLATIONSMANUAL
Läs denna installationsmanual noga för säkert och korrekt bruk innan luftkonditioneringen installeras.
INSTALLATIONSMANUAL
Læs venligst denne installationsmanual grundigt, før De installerer airconditionanlægget, af hensyn til sikker og korrekt anvendelse.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
РУКОВОДСТВО ПО УСТАНОВКЕ
Для осторожного и правильного использования прибора необходимо тщательно ознакомиться с данным руководством по
установке до выполнения установки кондиционера.
DK
P
GR
TR
RU
2
[Fig. 2.0.1]
1 Pipe cover (For field piping connection)
3
3.2
2 LCD remote controller
[Fig. 3.2.1]
* In case of PEA-200, 250* In case of PEA-400, 500
B
730
200530
A
C
GB
B
7525C
A
200400
1
2
3
D500
Model
A
PEA-200
PEA-500
A
1860
2060
B
1260
1460
C
900
D
400
D
1 When connecting air inlet
2 When installing the suspension fixtures prior to installation of the
indoor unit without inlet duct
3 When hanging the indoor unit directly without inlet duct
A Service space
F
[Fig. 3.2.2]
* In case of PEA-200, 250* In case of PEA-400, 500
F
A
D
B
B
NL
B Air inlet
C Air outlet
20
199200131
C
864
200664
75251095
A
1800
2400
B
C
200400
1
2
3
595500
A
1947
D
F
1840
B
20
203320141
764
SWI
E
P
E
G
I
H
C
Model
D
PEA-200
PEA-500
D Suspension bolt pitch
E Top of the unit
F Suspension bolt holes
A Ceiling board
B Edge beam
C Tie beam
D Square timber for hanging the air conditioner
E Pitch
C
D
E
G
I
H
C
H
F
F Insert: 100 to 150 kg (1 piece) (field supply)
G Hanging bolt (field supply)
PEA-200, 250 : M10
PEA-400, 500 : M12
H Reinforcement
G
D
2
5
[Fig. 5.1.1][Fig. 5.1.2]
5.1
*1
A
B
[Fig. 5.1.3]
A
6
[Fig. 6.2.1]
* In case of PEA-200, 250* In case of PEA-400, 500
E
B
A
C
100
BA
C
D
A Unit body
B Lifting machine
10
A30
B
A Be sure to attach a U-shaped
washer (4 washers in total).
6.2
Model
PEA-200, 250
A
144B145
A Refrigerant pipe (liquid pipe)
B Refrigerant pipe (gas pipe)
C Drain pipe
C
D52E
89
A
B
A
[Fig. 5.2.1]
42
B
45
A
B
A
C
156117 81102
117
5.2
100
A30
B
A Nut
B Washer
A
GB
A Level check
D
F
NL
52
7
[Fig. 7.1.1][Fig. 7.1.2]
A
A Remove the cap
[Fig.7.1.3]
* In case of PEA-200, 250
D
A Brazing
B Gas pipe
C Liquid pipe
D Indoor unit
E Outdoor unit
* Refore to the Outdoor Installation Manual
for connecting to the outdoor unit.
A
B
A
C
7.1
* In case of PEA-400, 500
E
A
B
AG
D
A
D
A
A
C
C
A Thermal insulation
B Pull out insulation
E
F
B
C Wrap with damp cloth
D Return to original position
E Ensure that there is no gap here
F Wrap with insulating tape
G Pipe cover (Accessory part)
(No.2)
B
C
E
(No.1)
E
SWI
E
P
3
7
7.2
GB
D
8
[Fig.7.2.1]
[Fig.8.0.1]
[Fig.8.0.2]
C
F
E
G
D
A
B
H
I
J
GG
E
DC
B
* In case of PEA-200, 250* In case of PEA-400, 500
D
F
E
A
10mm
A Air inlet
B Air outlet
C Access door
D Ceiling surface
E Canvas duct
F Keep duct-work length 850 or more
G Connect common reference potential wire between duct-work to air conditioner
A
A
A Insulator
B Drain pipe R1
C Drain pan
>
D
70 mm
=
>
2 × F
=
>
35 mm
=
>
70 mm
=
10 mm
E
F
G Downward slope 20 mm/m or more
H Drain trap
I The drain pipe should extend below this level.
J Open drain
D
E
F
NL
SWI
E
B
C
A Inlet duct flangeB Inlet temperature sensor
C Sensor protection plateD Sensor fixture
E Inlet duct
[Fig.8.0.3]
* In case of PEA-200, 250
A
12.525~100mm
A
B
C
DG
C
C
1000
7 × 130 (=910)
1618
12 × 130(=1560)
Model
PEA-200
PEA-250
B
A
1102
1302
* In case of PEA-400, 500
B
8 × 130 (=1040)
9 × 130 (=1170)
A
B
C
34
H
F
D
E
330
105
205
F
G45H
31
66
33
29
J
25
K
I35J22K
22
22.5
E
I
2 × 130(=260)
2 × 100(=200)
250
95
4 × 120(=480)
525
12.5
2-
20
25~100 mm
P
C
8 × 130(=1040)
B
1125
42.5
280
2 × 130(=260)
40
188340
A Inlet duct flange
B Outlet duct flange
C Top of the unit
4
9
[Fig.9.0.1]
* In case of PEA-200, 250
ABC
* In case of PEA-400, 500
ABC
S1 S2 S3
I
F
1D2
S1 S2 S3
H
F
1D2
(TB4-1) (TB4-2)
S1 S2 S3 S1 S2 S3S1 S2 S3
H
H
E
PUHZ-200, 250PEA-200, 250
L1 L2 L3 N
G
(No.1 Outdoor)
E
L1 L2 L3 N
I
PUHZ-200, 250PEA-400, 500
G
(No.2 Outdoor)
E
PUHZ-200, 250
L1 L2 L3 N
G
S1 S2 S3
I
L1 L2 L3 N
I
L1 L2 L3 N
CB A
G
CB AABC
I
G
A Power supply
B Earth leakage breaker
C Circuit breaker or local switch
D LCD remote controller
E Outdoor unit
F Indoor unit
G Power cable wiring
H Indoor/Outdoor connection wiring
I Grounding
GB
D
F
[Fig.9.0.2]
* In case of PEA-200, 250* In case of PEA-400, 500
A
B
C
C
B
NL
A For remote controller cables
B For outdoor unit connection cables
C For power supply cables
A
SWI
E
P
5
10
[Fig.10.1.1]
* In case of PEA-200, 250* In case of PEA-400, 500
FG JE
A
C
AABA
2
1
D
22
1
BBB
EF GHIJ
A
No.1ANo.2ANo.1ANo.2
10.1
2
1
D
C
A Outdoor unit
A
A
No.1
No.2
BBB
2
1
B Indoor unit
C Main remote controller
D Subordinate remote controller
E Standard (Refrigerant address = 00)
F Refrigerant address = 01
G Refrigerant address = 02
H Refrigerant address = 03
I Refrigerant address = 14
J Refrigerant address = 15
GB
D
F
NL
11
[Fig.11.1.1]
(1)
D
(3)
<A> For installation in the switch box<B> For direct installation on the wall
C
G
B
A
30120
30
83.5
30
46
C
D
A Remote controller pro-
file
B Required clearances
surrounding the remote controller
C Temperature sensor
D Installation pitch
E
D
11.1
(2)
<A> For installation in the switch box:<B> For direct installation on the wall
D
C
E
F
H
C WallD Conduit
E Lock nutF Bushing
G Switch boxH Remote controller cord
I Seal with putty
H
I
G
select one of the following:
B-1.
B-2.
I
I
SWI
E
P
[Fig.11.2.1]
[Fig.11.3.1]
C Switch box for two piecesD Remote controller cord
E Cross-recessed, pan-head screw
G Seal the remote controller cord service entrance with putty
H Wood screw
5. Installing the unit ......................................................................................... 9
5.1. Hanging the unit body ............................................................... 9
5.2. Confirming the unit’s position and fixing hanging bolts ............. 9
6. Refrigerant pipe and drain pipe specifications .......................................... 10
6.1. Refrigerant pipe and drain pipe specifications ........................ 10
6.2. Refrigerant pipe, drain pipe and filling port ............................. 10
7. Connecting refrigerant pipes and drain pipes ........................................... 10
7.1. Refrigerant piping work ........................................................... 10
7.2. Drain piping work ..................................................................... 10
1. Safety precautions
s Before installing the unit, make sure you read all the “Safety
precautions”.
s The “Safety precautions” provide very important points re-
garding safety. Make sure you follow them.
Symbols used in the text
Warning:
Describes precautions that should be observed to prevent danger of injury
or death to the user.
Caution:
Describes precautions that should be observed to prevent damage to the
unit.
After installation work has been completed, explain the “Safety Precautions”, use,
and maintenance of the unit to the customer according to the information in the
Operation Manual and perform the test run to ensure normal operation. Both the
Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
Symbols put on the unit
: Indicates an action that must be avoided.
: Indicates that important instructions must be followed.
: Indicates a part which must be grounded.
: Beware of electric shock. (This symbol is displayed on the main unit label.)
<Color: yellow>
Warning:
Carefully read the labels affixed to the main unit.
Warning:
• Ask the dealer or an authorized technician to install the air conditioner.
- Improper installation by the user may result in water leakage, electric shock,
or fire.
• Install the unit at a place that can withstand its weight.
- Inadequate strength may cause the unit to fall down, resulting in injuries.
• Use the specified cables for wiring. Make the connections securely so
that the outside force of the cable is not applied to the terminals.
- Inadequate connection and fastening may generate heat and cause a fire.
• Prepare for strong winds and earthquakes and install the unit at the specified place.
- Improper installation may cause the unit to topple and result in injury.
• Always use an filter and other accessories specified by Mitsubishi Electric.
- Ask an authorized technician to install the accessories. Improper installation
by the user may result in water leakage, electric shock, or fire.
• Never repair the unit. If the air conditioner must be repaired, consult the
dealer.
- If the unit is repaired improperly, water leakage, electric shock, or fire may
result.
8. Duct work .................................................................................................. 11
13.1. How to handle problems with the test run ............................... 19
13.2. The following occurrences are not problems or errors ............. 20
• Do not touch the heat exchanger fins.
- Improper handling may result in injury.
• When handling this product, always wear protective equipment.
EG: Gloves, full arm protection namely boiler suit, and safety glasses.
- Improper handling may result in injury.
• If refrigerant gas leaks during installation work, ventilate the room.
- If the refrigerant gas comes into contact with a flame, poisonous gases will
be released.
• Install the air conditioner according to this Installation Manual.
- If the unit is installed improperly, water leakage, electric shock, or fire may
result.
• Have all electric work done by a licensed electrician according to “local
regulations” and the instructions given in this manual.
- If the power source capacity is inadequate or electric work is performed im-
properly, electric shock and fire may result.
• Securely install the outdoor unit terminal cover (panel).
- If the terminal cover (panel) is not installed properly, dust or water may enter
the outdoor unit and fire or electric shock may result.
• When installing or relocating the unit, make sure that no substance other
than the specified refrigerant (R410A) enters the refrigerant circuit.
- Any presence of foreign substance such as air can cause abnormal pres-
sure rise or explosion.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration in the room from exceeding the
safety limit in the event of the refrigerant leakage.
- Consult the dealer regarding the appropriate measures to prevent the safety
limit from being exceeded. Should the refrigerant leak and cause the safety
limit to be exceeded, hazards due to lack of oxygen in the room could result.
• When moving and reinstalling the air conditioner, consult the dealer or
an authorized technician.
- If the air conditioner is installed improperly, water leakage, electric shock, or
fire may result.
• After completing installation work, make sure that refrigerant gas is not
leaking.
- If the refrigerant gas leaks and is exposed to a fan heater, stove, oven, or
other heat source, it may generate noxious gases.
• Do not reconstruct or change the settings of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted
and operated forcibly, or parts other than those specified by Mitsubishi Electric are used, fire or explosion may result.
• To dispose of this product, consult your dealer.
• The installer and system specialist shall secure safety against leakage
according to local regulation or standards.
- Following standards may be applicable if local regulation are not available.
• Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigeration is heavier than the air.
1.1.Before installation
Caution:
• Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
• Do not use the air conditioner where food, pets, plants, precision instruments, or artwork are kept.
- The quality of the food, etc. may deteriorate.
GB
D
DKSWNLIEF
RUTRGRP
7
• Do not use the air conditioner in special environments.
- Oil, steam, sulfuric smoke, etc. can significantly reduce the performance of
the air conditioner or damage its parts.
• When installing the unit in a hospital, communication station, or similar
place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical
equipment, or radio communication equipment may cause the air conditioner
to operate erroneously, or fail to operate. On the other hand, the air conditioner may affect such equipment by creating noise that disturbs medical
treatment or image broadcasting.
• Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80 % or when the drain pipe is clogged,
condensation may drip from the indoor unit. Perform collective drainage work
together with the outdoor unit, as required.
1.2.Before installation (relocation)
• Do not wash the air conditioner units.
- Washing them may cause an electric shock.
• Be careful that the installation base is not damaged by long use.
- If the damage is left uncorrected, the unit may fall and cause personal injury
or property damage.
• Install the drain piping according to this Installation Manual to ensure
proper drainage. Wrap thermal insulation around the pipes to prevent
condensation.
- Improper drain piping may cause water leakage and damage to furniture
GB
and other possessions.
• Be very careful about product transportation.
- Only one person should not carry the product if it weighs more than 20 kg.
- Some products use PP bands for packaging. Do not use any PP bands for a
means of transportation. It is dangerous.
- Do not touch the heat exchanger fins. Doing so may cut your fingers.
• Safely dispose of the packing materials.
- Packing materials, such as nails and other metal or wooden parts, may cause
stabs or other injuries.
- Tear apart and throw away plastic packaging bags so that children will not
play with them. If children play with a plastic bag which was not torn apart,
they face the risk of suffocation.
1.3.Before electrical work
Caution:
• Ground the unit.
- Do not connect the ground wire to gas or water pipes, lightning rods, or
telephone ground lines. Improper grounding may result in electric shock.
• Install the power cable so that tension is not applied to the cable.
- Tension may cause the cable to break and generate heat and cause a fire.
• Install an earth leakage circuit breaker, as required.
- If an leak circuit breaker is not installed, electric shock may result.
• Use power line cables of sufficient current carrying capacity and rating.
- Cables that are too small may leak, generate heat, and cause a fire.
• Use only a circuit breaker and fuse of the specified capacity.
- A fuse or circuit breaker of a larger capacity or a steel or copper wire may
result in a general unit failure or fire.
1.4.Before starting the test run
Caution:
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can
result in severe damage to internal parts. Keep the power switch turned on
during the operational season.
• Do not touch the switches with wet fingers.
- Touching a switch with wet fingers can cause electric shock.
• Do not touch the refrigerant pipes during and immediately after operation.
- During and immediately after operation, the refrigerant pipes are may be hot
and may be cold, depending on the condition of the refrigerant flowing through
the refrigerant piping, compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the refrigerant pipes.
• Do not operate the air conditioner with the panels and guards removed.
- Rotating, hot, or high-voltage parts can cause injuries.
• Do not turn off the power immediately after stopping operation.
- Always wait at least five minutes before turning off the power. Otherwise,
water leakage and trouble may occur.
2. Indoor unit accessories
The unit is provided with the following accessories:
[Fig. 2.0.1](P.2)
Accessory name
Pipe cover (For field piping connection)
• Small diameter
1
• Large diameter
PEA-200, 250PEA-400, 500
12
12
2
3. Selecting an installation site
• Select a site with sturdy fixed surface sufficiently durable against the weight of
unit.
• Before installing unit, the routing to carry in unit to the installation site should
be determined.
• Select a site where the unit is not affected by entering air.
DKSWNLIEFD
• Select a site where the flow of supply and return air is not blocked.
• Select a site where refrigerant piping can easily be led to the outside.
• Select a site which allows the supply air to be distributed fully in room.
• Do not install unit at a site with oil splashing or steam in much quantity.
• Do not install unit at a site where combustible gas may generate, flow in, stagnate or leak.
• Do not install unit at a site where equipment generating high frequency waves
(a high frequency wave welder for example) is provided.
• Do not install unit at a site where fire detecter is located at the supply air side.
(Fire detector may operate erroneously due to the heated air supplied during
heating operation.)
• When special chemical product may scatter around such as site chemical plants
and hospitals, full investigation is required before installing unit. (The plastic
components may be damaged depending on the chemical product applied.)
Model (Qty*)
1LCD remote controller
• If the indoor unit is run in a place subject to high temperatures and humidity
(the dew-point temperature is 26 °C or more inside the ceiling) for a long time,
dew condensation may occur on the indoor unit. When operated under such
condition, add more insulating material (10-20 mm) on the surface of the indoor unit to prevent dew condensation.
3.1.Install the indoor unit on a ceiling strong
enough to sustain its weight
Warning:
The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down causing
injuries.
3.2.Securing installation and service space
• Select the optimum direction of supply airflow according to the configuration of
the room and the installation position.
• As the piping and wiring are connected at the bottom and side surfaces, and
the maintenance is made at the same surfaces, allow a proper space properly.
For the efficient suspension work and safety, provide a space as much as
possible.
RUTRGRP
8
Service space
[Fig. 3.2.1] (P.2)
1 When connecting air inlet
2 When installing the suspension fixtures prior to installation of the indoor unit with-
out inlet duct
3 When hanging the indoor unit directly without inlet duct
A Service spaceB Air inlet
C Air outlet
4. Fixing hanging bolts
Suspension bolt pitch
[Fig. 3.2.2] (P.2)
D Suspension bolt pitchE Top of the unit
F Suspension bolt holes
For combining indoor units with outdoor units, refer to the outdoor unit installation
manual.
4.1.Fixing hanging bolts
Hanging structure
• Ceiling: The ceiling structure varies from building to one another. For detailed
information, consult your construction company.
1 Reinforcing the ceiling with additional members (edge beam, etc.) must be
required to keep the ceiling at level and to prevent the ceiling from vibrations.
2 Cut and remove the ceiling members.
3 Reinforce the ceiling members, and add other members for fixing the ceiling
boards.
For wooden construction
• Use the tie beam (for one story building) or second-floor beam (for two story
building) as strength members.
• To hang the air-conditioner, use a hard square timber of more than 6 cm if the
distance between beams is less than 90 cm and a hard square timber of more
than 9 cm if the distance between beams is less than 180 cm.
5. Installing the unit
5.1.Hanging the unit body
s Bring the indoor unit to an installation site as it is packed.
s To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.
s Install the indoor unit before ceiling work.
[Fig. 5.1.1] (P.3)
A Unit bodyB Lifting machine
* Two installation methods are available
<When hanging the indoor unit directly>
1. Attach a washer and nut(s) to each suspension bolt. (The washers and nuts
are to be supplied locally.)
2. Fit the indoor unit to each suspension bolt.
3. Make sure that the unit is positioned level, then tighten each nut.
[Fig. 5.1.2](P.3)
A NutB Washer
AB
When using inlet duct100 or more130 or more
When not using inlet duct0 or more30 or more
Nut (*1) is not required if distance A is 0.
<When installing the suspension fixture prior to installation of the indoor unit>
1. Loosen each suspension fixture bolt slightly, and remove the fixture and Ushaped washers.
2. Adjust each suspension fixture bolt.
[Fig. 4.1.1](P.2)
A Ceiling boardB Edge beamC Tie beam
D Square timber for hanging the air conditionerE Pitch
For reinforced concrete construction
• As shown in the figure below, fix the hanging bolts, or use square timbers to fix
the hanging bolts.
[Fig. 4.1.2](P.2)
F Insert: 100 to 150 kg (1 piece) (field supply)
G Hanging bolt (field supply)
PEA-200, 250 : M10
PEA-400, 500 : M12
H Reinforcement
Product Weight (kg)
PEA-20070 kg
PEA-25077 kg
PEA-400130 kg
PEA-500133 kg
3. Attach a washer, nut and suspension fixture to each suspension bolt. (The
washers and nuts are to be supplied locally.)
4. Hook the indoor unit to the suspension fixtures.
5. Make sure that the unit is positioned level, then tighten each nut.
[Fig. 5.1.3](P.3)
A Be sure to attach a U-shaped washer (4 washers in total).
When using inlet duct100 or more130 or more
When not using inlet duct25 or more55 or more
AB
5.2.Confirming the unit’s position and fix-
ing hanging bolts
[Fig. 5.2.1] (P.3)
A Level check
s Use the gage supplied with the panel to confirm that the unit body and
hanging bolts are positioned in place. If they are not positioned in place,
it may result in dew drops due to wind leak. Be sure to check the positional
relationship.
s Use a level to check that the surface indicated by A is at level. Ensure
that the hanging bolt nuts are tightened to fix the hanging bolts.
s To ensure that drain is discharged, be sure to hang the unit at level using
a level.
Caution:
Be sure to install the unit body at level.
GB
D
DKSWNLIEF
RUTRGRP
9
6. Refrigerant pipe and drain pipe specifications
To avoid dew drops, provide sufficient antisweating and insulating work to the refrigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commercially available insulating material (with a heat-resisting temperature of more than
100 °C and thickness given below) onto both liquid and gas pipes.
Be also sure to wind commercially available insulating material (with a form
polyethylene’s specific gravity of 0.03 and thickness given below) onto all pipes
which pass through rooms.
1 Select the thickness of insulating material by pipe size.
Pipe sizeInsulating material’s thickness
6.4 mm to 25.4 mmMore than 10 mm
28.6 mm to 38.1 mmMore than 15 mm
2 If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating
material’s thickness more than those given in the table above.
3 If there are customer’s specifications, simply follow them.
7. Connecting refrigerant pipes and drain pipes
GB
7.1.Refrigerant piping work
This piping work must be done in accordance with the installation manuals for
outdoor unit.
• The method of pipe connection is brazing connection.
Cautions on refrigerant piping
s Be sure to use non-oxidative brazing for brazing to ensure that no for-
eign matter or moisture enter into the pipe.
s Provide a metal brace to support the refrigerant pipe so that no load is
imparted to the indoor unit end pipe. This metal brace should be provided 50 cm away from the indoor unit’s brazing connection.
Warning:
When installing or relocating the unit, make sure that no substance other
than the specified refrigerant (R410A) enters the refrigerant circuit.
- Any presence of foreign substance such as air can cause abnormal pressure
rise or explosion.
Caution:
• Install the refrigerant piping for the indoor unit in accordance with the
following.
1. Remove the cap.
[Fig. 7.1.1](P.3)
A Remove the cap
2. Pull out the thermal insulation on the site refrigerant piping, braze the unit
piping, and replace the insulation in its original position.
Wrap the piping with insulating tape.
[Fig. 7.1.2](P.3)
A Thermal insulationB Pull out insulation
C Wrap with damp clothD Return to original position
E Ensure that there is no gap hereF Wrap with insulating tape
DKSWNLIEFD
RUTRGRP
G Pipe cover (Accessory part)
Note:
• Pay strict attention when wrapping the copper piping since wrapping the
piping may cause condensation instead of preventing it.
* Before brazing the refrigerant piping, always wrap the piping on the main
body, and the thermal insulation piping, with damp cloths to prevent heat
shrinkage and burning the thermal insulation tubing. Take care to ensure
that the flame does not come into contact with the main body itself.
Caution:
• Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized
copper as specified in the JIS H3300 “Copper and copper alloy seamless
pipes and tubes”. In addition, be sure that the inner and outer surfaces of
the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shaving particles, oils, moisture, or any other contaminant.
• Never use existing refrigerant piping.
- The large amount of chlorine in conventional refrigerant and refrigerator oil
in the existing piping will cause the new refrigerant to deteriorate.
• Store the piping to be used during installation indoors and keep both
ends of the piping sealed until just before brazing.
- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and
the compressor may fail.
• Do not use a leak detection additive.
6.1.Refrigerant pipe and drain pipe specifications
Item
Refrigerant
pipe
Drain pipe
Model
Liquid pipe
Gas pipe
PEA-200
ø9.52
PEA-250
ø12.7
ø25.4
R1 (Male screw)
PEA-400
ø9.52
PEA-500
ø12.7
6.2.Refrigerant pipe, drain pipe and filling
port
[Fig. 6.2.1] (P.3)
A Refrigerant pipe (liquid pipe)B Refrigerant pipe (gas pipe)
C Drain pipe
Additional refrigerant charge
• Take care not to allow dirt or cutting chips to enter the refrigerant pipes.
• The refrigerant pipes must be kept warm, so take particular care to insulate
between refrigerant pipes and the gas pipe located inside the indoor unit, since
the gas pipe causes condensation during cooling operation.
• When connecting the refrigerant pipes, make sure that the stop valve of the
outdoor unit is fully closed (as it was when shipped from the factory). After
connecting all the refrigerant pipes between the indoor and outdoor units, purge
air from the stop valve service port of the outdoor unit and service port of each
connecting pipe. Check that there is no air leakage from any pipe connection,
then fully open the stop valve of the outdoor unit. This will connect the refrigerant circuit between the indoor and outdoor units.
• The refrigerant pipes must be as short as possible.
• The indoor and outdoor units must be connected with the refrigerant pipes.
[Fig. 7.1.3](P.3)
A BrazingB Gas pipe
C Liquid pipeD Indoor unit
E Outdoor unit
7.2.Drain piping work
[Fig. 7.2.1] (P.4)
A InsulatorB Drain pipe R1
C Drain panD
>
E
G Downward slope 20 mm/m or more H Drain trap
I The drain pipe should extend below this level.
J Open drain
>
2 × F
70 mmF
=
=
>
70 mm
=
>
35 mm
=
10
1. Ensure that the drain piping is downward (pitch of more than 20 mm/m) to the
outdoor (discharge) side.
2. Ensure that any cross-wise drain piping is less than 20 m (excluding the difference of elevation). If the drain piping is long, provide metal braces to prevent it
from waving. Never provide any air vent pipe. Otherwise drain may be ejected.
8. Duct work
3. Use a hard vinyl chloride pipe VP-25 (with an external diameter of 32 mm) for
drain piping.
4. Ensure that collected pipes are 10 cm lower than the unit body’s drain port.
5. Put the end of the drain piping in a position where no odor is generated.
6. Do not put the end of the drain piping in any drain where ionic gases are
generated.
• In connecting duct, insert canvas duct between unit and duct.
• Use incombustible material for duct parts.
• Provide full insulation to inlet duct flange, outlet duct flange and outlet duct to
prevent condensation.
• Be sure to apply the air filter near the air inlet grille.
• Before connecting an inlet duct, remove the air filter, then install that filter in the
inlet grille.
[Fig. 8.0.1](P.4)
A Air inletB Air outlet
C Access doorD Ceiling surface
E Canvas ductF Keep duct-work length 850 or more
G Connect common reference potential wire between duct-work to air conditioner
Caution:
• Outlet duct is 850 mm or more necessary to construct.
• To connect the air conditioner main body and the duct for potential equalization.
• Inlet temperature sensor when an inlet duct is installed.
An inlet temperature sensor is installed on the inlet duct flange. Before connecting an inlet duct, this sensor must be removed and installed in the specified position.
9. Electrical wiring
Precautions on electrical wiring
Warning:
Electrical work should be done by qualified electrical engineers in accordance with “local regulations” and supplied installation manuals. Special circuits should also be used. If the power circuit lacks capacity or has an installation failure, it may cause a risk of electric shock or fire.
1. Be sure to take power from the special branch circuit.
2. Be sure to install an earth leakage breaker to the power.
3. Install the unit to prevent that any of the control circuit cables (remote controller, transmission cables) is brought in direct contact with the power cable outside the unit.
4. Ensure that there is no slack on all wire connections.
5. Some cables (power, remote controller, transmission cables) above the ceiling
may be bitten by mouses. Use as many metal pipes as possible to insert the
cables into them for protection.
6. Never connect the power cable to leads for the transmission cables. Otherwise
the cables would be broken.
7. Be sure to connect control cables to the indoor unit, remote controller, and the
outdoor unit.
8. Put the unit to the ground on the outdoor unit side.
9. Be sure to connect between the control cable terminal block of the outdoor unit
and that of the indoor unit. (Cables have polarity, so make sure that they are
connected according to the terminal numbers.)
10. Fix power source wiring to control box by using buffer bushing for tensible force
(PG connection or the like). Connect control wiring to control terminal bed
through the knockout hole of control box using ordinary bushing.
11. Do not connect the unit in the reverse phase sequence.
If connected in the reverse phase sequence, the indoor unit will not be able to
provide sufficient cooling air. (PEA-200, 250, 400, 500)
[Fig. 8.0.2](P.4)
A Inlet duct flangeB Inlet temperature sensor
C Sensor protection plateD Sensor fixture
E Inlet duct
1 Pull out the sensor, and remove the sensor fixture and protection plate. (The
protection plate must be discarded.)
2 Connect the inlet duct.
3 Drill a sensor hole (ø12.5 dia.) on the side on the duct.
4 Assemble the sensor and fixture.
• When pulling out the sensor, do not pull it by the lead wire. Doing so may result
in wire breakage.
• Before connecting the inlet duct, make sure that the sensor, its fixture and
protection plate are removed.
• The sensor removed in step 1 must be re-installed in the position specified in
the drawing. Installation of the sensor in an incorrect position may result in
malfunction.
Mount holes for outlet duct flange and inlet duct.
[Fig. 8.0.3] (P.4)
A Inlet duct flange
B Outlet duct flange
C Top of the unit
In case of A-control wiring there is high voltage potential on the S3 terminal
caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main
power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit
and outdoor unit, please use 3-potes type.
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not connect the earth cable to any gas pipe, water pipe, lightening rod, or telephone
earth cable. Incomplete grounding may cause a risk of electric shock.
[Fig. 9.0.1] (P.5)
A Power supply
B Earth leakage breaker
C Circuit breaker or local switch
D LCD remote controller
E Outdoor unit
F Indoor unit
G Power cable wiring
H Indoor/Outdoor connection wiring
I Grounding
Caution:
For PEA-400, 500, make sure that refrigerant pipes and wirings be connected
from Outdoor unit No.1 to Indoor unit No.1 and Outdoor unit No.2 to Indoor
unit No.2 respectively.
Wiring from Outdoor unit No.1 must be connected to terminal bed TB4-1, and
wiring from Outdoor unit No.2 must be connected to TB4-2 in Indoor unit
control box.
Any mistakes on those connections may cause an abnormal refrigerant pipe
temperature and etc.
GB
D
DKSWNLIEF
11
RUTRGRP
[Wiring example] (For metal piping)
Earth leakage
breaker *1, *2
PEA-200, 250, 400, 500
Notes:
*1: Connect an earth leakage breaker to the power supply.
*2: Use earth leakage breakers designed exclusively for ground fault protection only in combination with a local switch or a circuit breaker.
*3: The overcurrent protector using a Class-B fuse is shown.
*4: Power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 245 IEC 53 or 227 IEC 53)
*5: Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord (Design 245 IEC 57).
*6: A switch with at least 3 mm contact separation in each pole shall be provided by the Air conditioner installation.
*7: The connection wiring between the outdoor and indoor units can be extended up to a maximum of 50 m.
15 A 30 mA
0.1s. or less
Local switch
Switch
capacity <A>
16
Overcurrent
protector *3
16
Circuit breaker
<A>
Power cable *4
15
1.5 mm2 or more
Earth cable
1.5 mm
2
or more
Indoor and outdoor
connection wiring *5
1.5 mm
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using
fuse, wire or copper wire with too large capacity may cause a risk of malfunction or fire.
Location of cable holes
[Fig. 9.0.2] (P.5)
A For remote controller cablesB For outdoor unit connection cables
GB
C For power supply cables
10. System control
2
or more
Remote controller
wiring
0.3 - 1.25 mm
(max. DC 12V)
2
10.1
Combination of indoor/outdoor unit can be controlled up to a maximum of 16 refrigerant systems.
* Set the refrigerant address using the DIP switch of the outdoor unit.
* Refer to the outdoor unit installation manual for setting method of SW1
1 Wiring from the Remote Control
This wire is connected to TB5 (terminal board for remote controller) of the indoor
unit (non-polar).
2 When a Different Refrigerant System Grouping is Used
Up to 16 refrigerant systems can be controlled as one group using the LCD remote
controller.
Notes:
1. In single refrigerant system, there is no need of wiring 2.
2. LCD remote controller can be installed up to a maximum of 2 units for
SW1
Function table
DKSWNLIEFD
Grouping by using LCD remote controller
[Fig. 10.1.1] (P.6)
A Outdoor unitB Indoor unit
C Main remote controllerD Subordinate remote controller
E Standard (Refrigerant address = 00)
F Refrigerant address = 01G Refrigerant address = 02
H Refrigerant address = 03I Refrigerant address = 14
J Refrigerant address = 15
DIP switch.
one group.
Operation according to switch setting
ONOFF
StartNormal
ClearNormal
Settings for outdoor unit addresses 0 to 15
ON
OFF
<SW1>
123456
SW1
function
settings
Function
1 Compulsory de-
frosting
2 Error history clear
3
Refrigerant sys-
4
tem address set-
5
ting
6
10.2 Examples of refrigerant system address
setting
–
No.1
No.2
Outdoor unit refrigerant
system address
00
00
01~15
Ex.
Indoor unit
PEA-200, 250
1
PEA-400, 500
2
* Set the refrigerant system address of one outdoor unit to 00 for the power supply
to the remote controller.
(The refrigerant system address is set to 00 when shipped from the factory.)
Do not duplicate the refrigerant system address settings within the same system.
Outdoor unit
Remote controller
power supply unit
✕
RUTRGRP
12
11. LCD remote controller
11.1. Installing procedures
(1) Select an installing position for the remote controller (switch box).
Be sure to observe the following precautions.
[Fig.11.1.1] (P.6)
A Remote controller profile
B Required clearances surrounding the remote controller
C Temperature sensorD Installation pitch
1 The temperature sensors are located on both remote controller and indoor
unit. To use the temperature sensor on the remote controller, mainly use the
remote controller for temperature setting or room temperature detection. Install the remote controller in such an area that can detect average room temperatures, free of direct sunlight, airflow from the air conditioner, and other
such heating source.
2 In either case when the remote controller is installed in the switch box or on the
wall, provide the clearances indicated in the diagram.
Note:
Check that there is no electric wire left close to the remote controller sensor.
If any electric wire is near the sensor, the remote controller may fail to detect
a correct room temperature.
3 Procure the following parts locally:
Switch box for two pieces
Thin copper conduit tube
Lock nuts and bushings
(2) Seal the service entrance for the remote controller cord with putty to
prevent possible invasion of dew drops, water, cockroaches or worms.
<A> For installation in the switch box:
• When the remote controller is installed in the switch box, seal the junction
between the switch box and the conduit tube with putty.
<B> For direct installation on the wall select one of the following:
B-1. To lead the remote controller cord from the back of the controller:
• Prepare a hole through the wall to pass the remote controller cord (in order to
run the remote controller cord from the back), then seal the hole with putty.
B-2. To run the remote controller cord through the upper portion:
• Run the remote controller cord through the cut-out upper case, then seal the
cut-out notch with putty similarly as above.
[Fig. 11.1.1](P.6)
C WallD ConduitE Lock nut
F BushingG Switch box
H Remote controller cordI Seal with putty
(3) Install the lower case in the switch box or on the wall.
[Fig. 11.1.1] (P.6)
<A> For installation in the switch box
C Switch box for two piecesD Remote controller cord
E Cross-recessed, pan-head screw
G Seal the remote controller cord service entrance with putty
<B> For direct installation on the wall
H Wood screw
Caution:
Do not over-tighten the screws to possible deformed or broken lower case.
Note:
• Select a flat place for installation.
• Be sure to use two or more locations for securing of the remote controller in the switch box or on the wall.
11.2. Connecting procedures
• The remote controller cord can be extended up to a maximum of 200 m. Use
electric wires or (two-core) cables of 0.3 mm
tion of remote controller. Do not use multi-conductor cables to prevent possible malfunction of the unit.
[Fig. 11.2.1] (P.6)
(1) Connect the remote controller cord to the terminal block at lower case.
A To TB5 on the indoor unit
B Terminal block TB6 in remote controller
No polarity
Caution:
• Do not use crimp-style terminals for connection to the remote controller
terminal block to eliminate contact with the boards and resultant trouble.
• Prevent remote cord chips from getting into the remote controller. Electric shock or malfunction may result.
2
to 1.25 mm2 for making connec-
11.3. Fitting the upper case
[Fig. 11.3.1] (P.6)
(1) To remove the upper case, put a slotted screwdriver tip in the latches as
shown in the diagram then move the screwdriver in the direction of arrow.
(2) To install the upper case, put the upper latches (at two locations) first,
then fit the upper case into the lower case as illustrated.
[Fig. 11.3.2] (P.6)
Note:
Wiring hole for installing directly on the wall (or open wiring)
• Cut off the shaded area from the upper case using a knife, nippers, etc.
• Take out the remote control cord connected to the terminal block via this
portion.
Caution:
• Do not move the screwdriver while inserting the tip far into the latches to
prevent broken latches.
• Be sure to put the upper case securely in the latches by pressing it until
a snap sounds. Loosely inserted, the upper case may fall down.
Note:
The operating section is covered with a protective sheet. Before using the
unit, remember to remove the protective sheet.
GB
D
11.4. Function selection
<Wired remote controller type>
(1) Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed.
Item 1
1.Change Language
(“CHANGE LANGUAGE”)
2.Function limit
(“FUNCTION
SELECTION”)
3.Mode selection
(“MODE SELECTION”)
4.Display change
(“DISP MODE SETTING”)
* This model is not equipped with this function. The setting is invalid.
Language setting to display
(1)
Operation function limit setting (operation lock) (“LOCKING FUNCTION”)
(2) Use of automatic mode setting (“SELECT AUTO MODE”)
(3) Temperature range limit setting (“LIMIT TEMP FUNCTION”)
*(4) Use of automatic filter elevation panel up/down operation mode
• Setting the range of operation limit (operation lock)
• Setting the use or non-use of “automatic” operation mode
• Setting the temperature adjustable range (maximum, minimum)
• Setting the use or non-use of the automatic filter elevation panel up/down operation mode
• Setting the use or non-use of the fixed airflow direction mode
• Selecting main or sub remote controller
*
When two remote controllers are connected to one group, one controller must be set to sub.
• Setting the use or non-use of clock function
• Setting the timer type
• Contact number display in case of error
• Setting the telephone number
• Setting the temperature unit (°C or °F) to display
• Setting the use or non-use of the display of indoor (suction) air temperature
• Setting the use or non-use of the display of “Cooling” or “Heating” display during
operation with automatic mode
Item 3 (Setting content)
DKSWNLIEF
RUTRGRP
13
[Function selection flowchart]
[1] Stop the air conditioner to start remote controller function selection mode. → [2] Select from item1. → [3] Select from item2. → [4] Make the setting. (Details
are specified in item3) → [5] Setting completed. → [6] Change the display to the normal one. (End)
Normal display (Display when the
GB
air condition is not running)
Item 1
Change Language
(“CHANGE LANGUAGE”)
Press the E
button.
Function limit
(“FUNCTION
SELECTION”)
Press the
E button.
Press the
E button.
Mode selection
(“MODE
SELECTION”)
Press the
E button.
Display change
(“DISP MODE
SETTING”)
(Hold down the E button and press the D button for two
seconds.)
* The display cannot be changed during the unit function
selection, the test run and the self diagnosis.
Remote Controller Function
Press the G button.
Press the
G button.
Press the
G button.
Press the
G button.
Operation function limit setting (“LOCKING FUNCTION”)
→
Use of automatic mode setting (“SELECT AUTO MODE”)
Temperature range limit setting (“LIMIT TEMP FUNCTION”)
*
Use of automatic filter elevation panel up/down operation mode setting
(Hold down the E button and press
the D button for two seconds.)
* The remote controller records the
setting that is made in this way.
Press the G button.
Press the G button.
Press the G button.
Press the D
button.
Press the D
button.
Press the D
button.
See [4]-1
Item 3
(Setting content)
See [4]-2. (1)
See [4]-2. (2)
See [4]-2. (3)
See [4]-3. (1)
See [4]-3. (2)
See [4]-3. (3)
See [4]-3. (4)
See [4]-4. (1)
See [4]-4. (2)
See [4]-4. (3)
NOTE
Timer operation stops when the display for
remote controller function selection is changed
to the normal one.
Dot display
The language that is selected in
CHANGE LANGUAGE mode
appears on this display. English is set
in this manual.
F
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
C
ON/OFF
OPERATION
D
E
PAR-21MAA
G
ON/OFF
FILTER
CHECK
CLEAR
I
A
TEST
B
H
* This model is not equipped with this function. The setting is invalid.
[Detailed setting]
[4] -1. CHANGE LANGUAGE setting
The language that appears on the dot display can be selected.
• Press the [
MENU] button to change the language.
1 Japanese (JP), 2 English (GB), 3 German (D), 4 Spanish (E), 5 Russian
(RU), 6 Italian (I), 7 Chinese (CH), 8 French (F)
[4] -2. Function limit
(1) Operation function limit setting (operation lock)
• To switch the setting, press the [
ON/OFF] button.
1 no1: Operation lock setting is made on all buttons other than the [
button.
2 no2: Operation lock setting is made on all buttons.
3 OFF (Initial setting value):
Operation lock setting is not made.
* To make the operation lock setting valid on the normal screen, it is necessary to
press buttons (Press and hold down the [FILTER] and [
ON/OFF] buttons at the
same time for two seconds.) on the normal screen after the above setting is made.
(2) Use of automatic mode setting
When the remote controller is connected to the unit that has automatic operation
mode, the following settings can be made.
• To switch the setting, press the [
1 ON (Initial setting value):
DKSWNLIEFD
The automatic mode is displayed when the operation mode is selected.
ON/OFF] button.
2 OFF:
The automatic mode is not displayed when the operation mode is selected.
(3) Temperature range limit setting
After this setting is made, the temperature can be changed within the set range.
• To switch the setting, press the [
ON/OFF] button.
1 LIMIT TEMP COOL MODE:
The temperature range can be changed on cooling/dry mode.
2 LIMIT TEMP HEAT MODE:
The temperature range can be changed on heating mode.
3 LIMIT TEMP AUTO MODE:
The temperature range can be changed on automatic mode.
4 OFF (initial setting): The temperature range limit is not active.
* When the setting, other than OFF, is made, the temperature range limit setting
on cooling, heating and automatic mode is made at the same time. However, the
range cannot be limited when the set temperature range has not changed.
• To increase or decrease the temperature, press the [
TEMP ( ) or ( )]
button.
• To switch the upper limit setting and the lower limit setting, press the [
button. The selected setting will flash and the temperature can be set.
1 Main: The controller will be the main controller.
2 Sub: The controller will be the sub controller.
(2) Use of clock setting
• To switch the setting, press the [
ON/OFF] button.
1 ON: The clock function can be used.
2 OFF: The clock function cannot be used.
(3) Timer function setting
• To switch the setting, press the [
ON/OFF] button (Choose one of the
followings).
1 WEEKLY TIMER (Initial setting value):
The weekly timer can be used.
2 AUTO OFF TIMER: The auto off timer can be used.
3 SIMPLE TIMER:The simple timer can be used.
4 TIMER MODE OFF: The timer mode cannot be used.
* When the use of clock setting is OFF, the “WEEKLY TIMER” cannot be used.
(4) Contact number setting for error situation
• To switch the setting, press the [
ON/OFF] button.
1 CALL OFF:The set contact numbers are not displayed in case of error.
2 CALL **** *** ****: The set contact numbers are displayed in case of error.
CALL_:The contact number can be set when the display is as shown
on the left.
• Setting the contact numbers
To set the contact numbers, follow the following procedures.
Move the flashing cursor to set numbers. Press the [
button to move the cursor to the right (left). Press the [
TEMP. ( ) and ( )]
CLOCK ( ) and ( )]
button to set the numbers.
[4] -4. Display change setting
(1) Temperature display °C/°F setting
• To switch the setting, press the [
ON/OFF] button.
1 °C: The temperature unit °C is used.
2 °F: The temperature unit °F is used.
(2) Suction air temperature display setting
• To switch the setting, press the [
ON/OFF] button.
1 ON: The suction air temperature is displayed.
2 OFF: The suction air temperature is not displayed.
]
(3) Automatic cooling/heating display setting
• To switch the setting, press the [
ON/OFF] button.
1 ON: One of “Automatic cooling” and “Automatic heating” is displayed under the
automatic mode is running.
2 OFF: Only “Automatic” is displayed under the automatic mode.
(2) Unit Function Selection
Set the functions of each indoor unit from the remote controller, as required. The functions of each indoor unit can be selected only from the remote controller.
Set the functions by selecting the necessary items from Table 1 and Table 2. (Default settings are also shown below)
Table 1. Itemized functions of the entire refrigerant system (select unit number 00 to 15)
Function
Power failure
automatic recovery
Indoor temperature
detection
LOSSNAY
connectivity
Power voltage
Not available
Available
Unit operating average
Set by unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (unit is not equipped with outdoor-air intake)
Supported (unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Settings
Mode no. Setting no.CheckDefault settings
1
01
2
1
022
3
1
032
3
04
1
2
Remarks
Approx. 4-minute wait-period
after power is restored.
Table 2. Itemized functions of the indoor unit (select unit numbers 01 to 04 or AL)
Function
Filter sign
Fan operation
during thermo off
in heating
operation
Fan operation
during thermo off
in cooling
operation
Settings
100 Hr
2500 Hr
No filter sign indicator
Operation (Last set fan speed)
Stop
Operation (Low speed)
Operation (Last set fan speed)
Stop
Mode no. Setting no.CheckDefault settingsRemarks
1
072
3
3
25
2
1
1
27
2
(PEA-400/500)
(PEA-200/250)
When selecting fan operation
“Stop”, set setting no. of Mode
no. “02” in Table 1 to “3”. Be sure
to place the remote controller
inside the room to be air-conditioned so that it can monitor the
room temperature.
Note:
When the indoor unit functions were changed using the function selection after installation is complete, always indicate the set contents by entering 嘷 or other
mark in the appropriate check field of Table 1 and Table 2.
GB
D
[Function selection flow]
First grasp the function selection flow. The following describes setting of “Power voltage” of Table 1 as an example.
(For the actual setting procedure, see [Setting procedure] 1 to 0.)
1 Check the function selection set contents.
2 Switch to the FUNCTION SELECTION mode.
(Press A and B simultaneously in the remote controller OFF state.)
F
3 Refrigerant address specification → 00 (Outdoor unit specification)
4 Unit address No. specification→ 00 (Indoor unit specification)
0 Ending function display (Press buttons A and B simultaneously.)
[Procedure] (Set only when change is necessary.)
1 Check the set contents of each mode. When the set contents of a mode were changed by function selection, the functions of that mode also change.
Check the set contents as described in steps 2 to 7 and change the setting based on the entries in the Table 1 and Table 2. (Refer default settings, when change the
setting)
2 Set the remote controller to Off.
Press and hold down the A [FILTER] and B [TEST] buttons at the same time
for two seconds or longer.
“FUNCTION SELECTION” blinks for a while, then the remote controller display
changes to the display shown below.
3 Set the outdoor unit refrigerant address No.
When the C [
CLOCK ( ) and ( )] buttons are pressed, the refrigerant
address No. decreases and increases between 00 and 15. Set it to the refrigerant address No. whose function you want to select.
(This step is unnecessary for single refrigerant system.)
I
A
B
H
DKSWNLIEF
Refrigerant address display
* If the remote controller enters the OFF state after the “FUNCTION SELECTION” and room temperature displays “
probably abnormal. Make sure there are no noise sources near the transmission line.
Note:
If you make a mistake during operation, end function selection by step ? and repeat selection from step 2.
” have flashes for two seconds, communication is
15
RUTRGRP
4 Set the indoor unit address No.
Press the D [
* When setting mode 01 to 04, set the unit address No. to “00”.
* When setting modes 07, 25, 27:
- When setting for each indoor unit, set the unit address No. to “01-04”.
- When batch setting for all indoor units, set the unit address No. to “AL”.
5 Refrigerant address and unit address No. registration
Press the E [
are registered.
After a while, the mode No. display “– –” flashes.
Mode No. display
* When “
address is not in the system.
When “F” is displayed at the unit address No. display, and when it flashes to-
GB
gether with the refrigerant address display, the selected unit address No. does
not exist. Correctly set the refrigerant address and unit address No. by repeating steps 2 and 3.
ON/OFF] button. The unit address No. display “– –” flashes.
Unit address No. display
] button. The refrigerant address and unit address No.
” flashes at the room temperature display, the selected refrigerant
When the C [
No. changes in 00 → 01 → 02 → 03 → 04 → AL order. Set it to the unit address
No. of the indoor unit whose functions you want to set.
When registered using the E [] button, the registered indoor unit
begins fan operation. When you want to know the location of the indoor units of
the unit address No. whose functions were selected, check here. When the unit
address No. is 00 or AL, all the indoor units of the selected refrigerant address
perform the fan operation.
Ex) When refrigerant address 00, unit address No. = 01 registered
* When grouping by different refrigerant systems and an indoor unit other than
the specified refrigerant address performs the fan operation, the refrigerant
address set here is probably duplicated.
Recheck the refrigerant address at the outdoor unit DIP switches.
CLOCK ( ) and ( )] buttons are pressed, the unit address
Refrigerant address 00
Outdoor unit
Indoor unit
Registration
Unit address
No. 01
Fan operation
Remote Controller
6 Mode No. selection
Select the mode No. you want to set with the F [
Mode No. display
7 Select the setting contents of the selected mode.
When the G [ MENU] button is pressed, the current setting No. flashes.
Use this to check the currently set contents.
Setting No. display
Setting No. 1 = 240 V
8 The contents set at steps 3 to 7 are registered.
When the E [
and setting ends.
* When “– –” appears at the mode No. and setting No. displays and “
Make sure there are no noise sources near the transmission line.
DKSWNLIEFD
9 To select more functions, repeat steps 3 to 8.
0 End function selection.
Press and hold down the A [FILTER] and B [TEST] buttons at the same time for two seconds or longer.
After a while, the function selection display disappears and the remote controller returns to the air conditioner off display.
] button is pressed, the mode No. and setting No. flash and registration begins. The flashing mode No. and setting No. change to a steady light
TEMP. ( ) and ( )] buttons. (Only the settable mode numbers can be selected.)
Mode No. 04 = Power voltage
Select the setting No. using the F [TEMP. ( ) and ( )] buttons.
” flashes at the room temperature display, communication is probably abnormal.
Setting No. 2 = 220 V, 230 V
* Do not operate the air conditioner from the remote controller for 30 seconds after the end of function selection.
Note:
When the functions of an indoor unit were changed by function selection after the end of installation, always indicate the set contents by entering a 嘷 or other
mark in the appropriate check field of Table 1 and Table 2.
RUTRGRP
16
12. Test run
12.1. Before test run
The test run can be carried out either from the outdoor unit or the indoor unit.
For the test run from outdoor unit, please check the outdoor unit installation manual.
1. Checklist
• After the installation, piping setup, and wiring of the indoor and outdoor units is
complete, check that refrigerant is not leaking, the power and control wires are
not loose, and the poles are not reversed.
• Use a 500 V insulation resistance tester to make sure that the resistance between the power terminal and the ground is 1.0 MΩ or more. If it is less than
1.0 MΩ, do not operate the unit. * Absolutely do not touch the tester to indoor/
outdoor connection terminals S1, S2, and S3. An accident could occur.
• Before turning the power ON, make sure that test run switch (SW4) of outdoor
controller board is OFF.
• Check the electrical power phase. If the phase is reversed, the fan may rotate
in the wrong direction or stop, or unusual sounds may be produced. (PEA200, 250, 400, 500)
• Starting at least 12 hours before the test run, send current through the
crankcase heater. (If the current is running for a shorter period of time,
damage to the compressor could result.)
• For specific models requiring changing of settings for higher ceilings or selection of power supply ON/OFF capability, make proper changes referring to the
description for Selection of Functions through Remote Controller.
After the above checks are complete, carry out the test run as indicated in the
following outline.
12.2. Test run procedures
1 Turn on the main power supply
While the display on the remote controller indicates “
is disabled. Turn off the “
“CENTRALLY CONTROLLED”
indicator
” indicator before using the remote controller.
TEMP.
2 Press the [TEST] button twice successively within three seconds. Test
run starts.
“TEST RUN” and “OPERATION MODE” are displayed alternately.
3 Press [] button
Cooling/drying mode: Cool air should start to blow.
Heating mode: Warm air should start to blow (after a while).
4 Check the outdoor unit fan for correct running
The outdoor unit features automatic capacity control to provide optimum fan
speeds. The fan keeps running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power. Then, in actuality,
the fan may stop or run in the reverse direction depending on the outside air,
which does not mean malfunction.
”, the remote controller
˚C
˚C
ON/OFF
5 Press the [
ON/OFF] button to reset the test run in progress
• The test run will be automatically shut down after two hours in response to the
AUTO STOP setting of two hours on the timer.
• During the test run, the room temperature display shows the indoor unit tubing
temperatures.
• In the case of the test run, the OFF timer will activate, and the test run will
automatically stop after two hours.
• The room temperature display section shows the control temperature for the
indoor units during the test run.
• Check that all the indoor units are running properly for simultaneous twin and
triple operation.
Malfunctions may not be displayed even if the wiring is incorrect.
6 Register a telephone number
The telephone number of the repair shop, sales office, etc., to contact if an
error occurs can be registered in the remote controller. The telephone number
will be displayed when an error occurs.
For registration procedures, refer to 11.4 Function selection of remote controller.
Operation mode display
“TEST RUN” and “OPERATION MODE” are
displayed alternately.
Timer stops test run after two hours.
MENU
BACKDAY
MONITOR/SET
PAR-21MAA
TEMP.
˚C
ON/OFF
ON/OFF
CLOCK
OPERATION
FILTER
CHECK
CLEAR
Piping temperature display
Stop test run by pressing the [ ON/OFF] button.
During test run, the RUN lamp remains on.
TEST
[TEST] button
[
] button
(*1)
After turning ON the power, the system will go into startup mode, and the remote
controller operation lamp (green) and the display section’s “PLEASE WAIT” will
flash. Also, in the case of the indoor substrate LEDs, LED 1 and LED 2 light up
(when address is 0) or become dim (when address is not 0), and LED 3 flashes. In
the case of the outdoor substrate LED display,
and are displayed
alternatively at 1-second intervals.
• If one of the above operations does not function correctly, the following causes
should be considered, and if applicable, dealt with. (The following symptoms
have been determined under test run mode. Note that “startup” in the chart
means the *1 display above.)
GB
D
Symptoms
Remote Controller DisplayOutdoor Substrate LED Display
Remote controller is displaying “PLEASE WAIT”, and
operation is not possible.
After power is turned ON, “PLEASE WAIT” is displayed for 3 mins., then error code is displayed.
Power is turned ON, and “EE” or “EF” are displayed
after “PLEASE WAIT” is displayed.
Display messages do not appear even when remote
controller operation switch is turned ON (operation
lamp does not light up).
Operation display appears but soon disappears even
when remote controller operations are executed.
After “startup” display, “00” is displayed (correct operation).
After “startup” display, error code is
displayed.
After “startup” display, “F1” (negative
phase) is displayed.
After “startup” display, “00” or “EE” is
displayed (“EE” is displayed when a
test run is made).
After “startup” display, “EA” (error for
number of units) or “Eb” (unit number
error) is displayed.
After “startup” display, “00” is displayed (correct operation).
After “startup” display, “00” is displayed (correct operation).
After “startup” display, “00” is displayed (correct operation).
Cause
• After power is turned ON, system startup lasts for about 2 mins., and
“PLEASE WAIT” is displayed (correct operation).
• Outdoor unit’s safeguard installation connector is open.
• Negative phase and open phase of outdoor unit’s power terminal board
(Single phase: L, N,
/triple phase: L1, L2, L3, N, )
• Incorrect connection of outdoor terminal board (Single phase: L, N,
triple phase: L1, L2, L3, N,
grounding and S1, S2, S3)
• Outdoor unit and indoor unit construction differ.
• Wiring for the indoor and outdoor unit is not connected correctly. (Polarity
is wrong for S1, S2, S3)
• Remote controller transmission wire short
• There is no outdoor unit for address 0 (address is something other than
0).
• Remote controller transmission wire burnout
• After cancellation of function selection, operation is not possible for about
30 secs. (correct operation).
17
DKSWNLIEF
/
RUTRGRP
* Press the remote controller’s “CHECK” button twice consecutively to be able to run a self-check. See the chart below for content of error code displays.
See the chart below for details of the LED displays (LED 1, 2, 3) on the indoor substrate.
LED 1 (microcomputer power supply)Displays the ON/OFF of power for control. Check that this is lit during normal use.
LED 2 (remote controller feed)Displays the ON/OFF of feed to wired remote controller. Is only lit for indoor unit linked to outdoor unit with address “00”.
LED 3 (indoor and outdoor signals)Displays signal between indoor and outdoor units. Check that this is flashing during normal use.
LCDNonconformity ContentLCDNonconformity Content
P8Tube temperature error
P9
U0 ~ UP Outdoor unit nonconformity
F1 ~ FA Outdoor unit nonconformity
E0 ~ E5 Signal error between remote controller and
Open/short in condenser/evaporater temp thermistor
indoor unit
E6 ~ EFSignal error between indoor and outdoor
units
- - - -No error history
FFFFNo relevant unit
12.3. Self-check
Retrieve the error history of each unit using the remote controller.
1 Switch to the self check mode.
When the H [CHECK] button is pressed twice successively within three seconds, the display shown below appears.
2 Set the address or refrigerant address No. you want to self check.
When the F [
creases and increases between 01 and 50 or 00 and 15. Set it to the address
No. or refrigerant address No. you want to self check.
TEMP. ( ) and ( )] buttons are pressed, the address de-
GB
Self check address or self check refrigerant address
3 Self check result display <Error history> (For the contents of the error code, refer to 13. Troubleshooting, error code list.)
ERROR CODE
Approximately three seconds after the change operation, the self check refrigerant address changes from flashing to a steady light and self check begins.
Error code 4 digits or error code 2 digits
4 Error history reset
The error history is displayed in 3 Self check results display.
When the D [MENU] button is pressed twice successively within three seconds, the self check address or refrigerant address flashes.
5 Self check reset
There are the following two ways of resetting self check.
Press the H [CHECK] button twice successively within three seconds → Resets self check and returns to the state before self check.
Press the I [
ON/OFF] button → Self check resets and indoor units stop.
<When there is no error history>
ERROR CODEERROR CODE
ERROR CODEERROR CODE
(When operation is prohibited, this operation is ineffective.)
<When opposite side does not exist>
When the error history was reset, the display shown below appears.
When error history reset failed, the error contents are displayed again.
Address 3 digits or unit address No. 2 digits
ERROR CODE
12.4. Remote controller check
DKSWNLIEFD
If operation cannot be carried out from the remote controller, use this function to diagnose the remote controller.
1 First check the power mark.
When normal voltage (DC12 V) is not applied to the remote controller, the power
mark goes off.
When the power mark is off, check the remote controller wiring and the indoor
unit.
2 Switch to the remote controller check mode.
When the H [CHECK] button is held down for five seconds or longer, the display shown below appears.
When the A [FILTER] button is pressed, remote controller check begins.
Power mark
RUTRGRP
18
3 Remote controller check result
When remote controller is normal
When remote controller is faulty
(Error display 1) “NG” flashes → Remote controller send/receive circuit abnormal
Since there is no problem at the remote controller, check for other causes.
When the problem is other than the checked remote controller
(Error code 2) “E3” “6833” “6832” flash → Cannot send
ERROR CODE
There is noise on the transmission line, or the indoor unit or another remote controller is faulty. Check the transmission line and the other remote controllers.
4 Remote controller check reset
When the H [CHECK] button is held down for five seconds or longer, remote controller check resets and the “PLEASE WAIT” and RUN lamp flash. Approximately 30
seconds later, the remote controller returns to the state before remote controller check.
Remote controller switching is necessary.
(Error display 3) “ERC” and data error count are displayed → Data error generation
“Data error count” is the difference between the number of bits of remote controller
send data and the number of bits actually sent to the transmission line. In this case,
the send data was disturbed by the noise, etc. Check the transmission line.
When data error count is 02
Remote controller send data
Send data on transmission line
13. Troubleshooting
13.1. How to handle problems with the test run
Error code list: details
Remote controller
display
E0
E1, E2
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
F1
F8
A0
A2
A3
A6
A7
A8
EF
U2
U2
U3
U4
U6
UE
UL
F8
P1
P2
P4
P5
P5
P6
P6
P8
P9
Remote controller communication – reception error
Remote controller board error
Remote controller communication – transmission error
Remote controller communication – reception error
Remote controller communication – transmission error
Communication between indoor and outdoor units – reception error
Communication between indoor and outdoor units – transmission error
Communication between indoor and outdoor units – reception error
Communication between indoor and outdoor units – transmission error
Indoor/outdoor connection wiring error, indoor unit overload (5 units or more)
Indoor/outdoor connection wiring error (interference, loose)
Excessive time in use
Serial communication error
Serial communication error
Reverse phase, out of phase verification
Faulty input circuit
Duplicated M-NET address setting
M-NET error in PH/W transmission
M-NET bus busy
M-NET communication error with P transmission
M-NET error – no ACK
M-NET error- no response
Undefined error code
Outlet temperature error
CN23 Short-circuit Connector Unplugged
Open/short in discharge temp thermistor
Open/short in liquid temp thermistor
Compressor overcurrent interruption (51C operation)
High pressure error (63H1 operation)
Low pressure error (63L operation)
Power synchronous idle circuit error
Inlet sensor error
Open/short in liquid temp thermistor
Drain sensor error
Drain overflow protector operation
Water leak error (PDH only)
Freeze prevention operation
Surge prevention operation
Piping temperature error
Open/short in condenser/evaporater temp thermistor
–
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
GB
D
DKSWNLIEF
RUTRGRP
19
13.2. The following occurrences are not problems or errors
Problem
The fan setting changes during heating.
(PEA-200, 250)
The fan stops during heating.
When the switch is turned ON, the fan does
not begin to operate. (PEA-200, 250)
The outdoor unit fan turns in reverse or stops,
and an unusual sound is heard.
Note:
If the fan in the indoor unit does not operate, check the over-current relay on the fan motor to determine whether it has been tripped.
If the over-current relay has been tripped, reset it after eliminating the cause of the problem (e.g. motor lock).
To reset the over-current relay, open the control box and press the green claw on bottom-right of the relay until a click is heard. Release the claw and check that
it returns to its original position.
Note that if it is pressed too hard it will not return to its original position.
Remote controller display
Ordinary display
Defrosting display
Heating preparations
underway
Ordinary display
Cause
During thermostat OFF mode, low speed air operation will take place.
During thermostat ON mode, low speed air will switch automatically to set notch (fan
speed) on the basis of time or piping temperature.
During defrosting, the fan will stop.
After the switch is turned ON, low speed air will take place, for 7 minutes (or after pipe
temperature reaches 35°C, 2 minutes) before automatically switch to set notch (fan
speed).
(Hot adjustment)
There is a risk of the power to the outdoor unit being connected in reverse phase. Be
sure to check that the phase is correct.
6.1. Technische Daten der Kältemittel- und Auslaufrohrleitung ...... 24
6.2. Kältemittelrohr, Auslaufrohr und Einfüllöffnung ....................... 24
7.1. Verrohrung der Kältemittelleitung ............................................ 24
7.2. Verrohrung des Auslaufs/der Dränage .................................... 25
1. Sicherheitsvorkehrungen
s Vor dem Einbau der Anlage vergewissern, daß Sie alle Infor-
mationen über “Sicherheitsvorkehrungen” gelesen haben.
s Die “Sicherheitsvorkehrungen” enthalten sehr wichtige
Sicherheitsgesichtspunkte. Sie sollten sie unbedingt befolgen.
Im Text verwendete Symbole
Warnung:
Beschreibt Vorkehrungen, die beachtet werden sollten, um den Benutzer vor
der Gefahr von Verletzungen oder tödlicher Unfälle zu bewahren.
Vorsicht:
Beschreibt Vorkehrungen, die beachtet werden sollten, um die Anlage vor
Schäden zu bewahren.
Wenn die Installationsarbeit fertig ist, erkören Sie dem Kunden die “Sicherheitsvorkehrungen” und die Wartung der Anlage entsprechend den Angaben im Betriebshandbuch und führen den Probelauf aus, um normalen Betrieb sicherzustellen.
Sowohl das Installationshandbuch als auch das Betriebshandbuch müssen dem
Benutzer zur Aufbewahrung übergeben werden. Diese Handbücher müssen an
zukünftige Benutzer weitergereicht werden.
An der Anlage angebrachte Zeichen
: Verweist auf eine Handlung, die unterbleiben muß.
: Verweist auf wichtige Anweisungen, die befolgt werden müssen.
: Verweist auf ein Teil, das geerdet werden muß.
: Gefahr von elektrischem Schlag. (Dieses Symbol findet sich als Aufkleber
auf der Hauptanlage.) <Farbe: gelb>
Warnung:
Die auf der Hauptanlage angebrachten Aufkleber sorgfältig lesen.
Warnung:
• Bitten Sie Ihren Fachhändler oder einen geprüften Fachtechniker, die Installation der Anlage vorzunehmen.
- Unsachgemäße Installation durch den Benutzer kann Wasseraustritt, Strom-
schläge oder Brände verursachen.
• Die Anlage an einem Ort installieren, der genügend Tragkraft für deren
Gewicht besitzt.
- Bei ungenügender Tragkraft kann das Anlage herunterfallen und Verletzun-
gen verursachen.
• Zur Verdrahtung die angegebenen Kabel verwenden. Die Anschlüsse so
sichern, daß Zugspannung von außen nicht auf die Klemmen wirken kann.
- Falscher Anschluß und falsche Befestigung führen zu Wärmebildung und
verursachen Brände.
• Vorsorge gegen heftige Windstöße und Erdbeben treffen, und die Anlage
8.Arbeiten am Strömungskanal ....................................................................... 25
13.1. Handhabung von Problemen beim Testlauf ............................. 35
13.2. Die folgenden Erscheinungen stellen keine Probleme oder
Fehler dar ................................................................................ 35
an dem angegebenen Ort installieren.
- Durch unsachgemäße Installation kann die Anlage herunterfallen und Verletzungen verursachen.
• Stets einen Filter und sonstiges Zubehör gemäß Angaben von Mitsubishi
Electric verwenden.
- Einen geprüften Techniker bitten, die Zusatzeinrichtungen zu installieren.
Unsachgemäße Installation durch den Benutzer kann zu Wasseraustritt,
Stromschlägen oder Bränden führen.
• Die Anlage niemals selbst reparieren. Wenn die Anlage repariert werden
muß, wenden Sie bitte sich an den Fachhändler.
- Wenn die Anlage unsachgemäß repariert wird, kann dies zu Wasseraustritt,
Stromschlägen oder Bränden führen.
• Nicht die Wärmetauscherleitung berühren.
- Unsachgemäße Handhabung kann zu Verletzungen führen.
• Tragen Sie bei der Handhabung dieses Erzeugnisses immer Schutzausrüstung, d.h. Handschuhe, vollen Armschutz wie einen Overall und eine
Schutzbrille.
- Unsachgemäße Handhabung kann zu Verletzungen führen.
• Wenn Kältemittelgas während der Installationsarbeiten austritt, den Raum
gründlich lüften.
- Wenn das Kältemittelgas auf offenes Feuer trifft, wird giftiges Gas freige-
setzt.
• Die Anlage gemäß Anweisungen in diesem Installations-handbuch installieren.
- Bei unsachgemäßer Installation kann dies zu Wasseraustritt, Stromschlägen
oder Bränden führen.
• Elektroarbeiten durch einen zugelassenen Fachelektriker in Übereinstimmung mit den “örtlichen Vorschriften” und den Anweisungen in diesem
Handbuch ausführen lassen.
- Wenn die Leistung der Stromquelle ungenügend ist oder die Elektroarbeiten
unsachgemäß ausgeführt wurden, kann dies zu Stromschlägen und zu Bränden führen.
• Die Abdeckung der Elektroanschlüsse der Außenanlage (Abdeckplatte)
fest anbringen.
- Wenn die Abdeckung der Elektroanschlüsse (Abdeckplatte) nicht sachge-
mäß angebracht wurde, kann Staub oder Wasser in die Außenanlage eindringen und Brände oder Stromschläge verursachen.
• Beim Installieren und Verlegen der Anlage kein anderes Kältemittel als
das auf der Anlage angegebene Kältemittel (R410A) einfüllen.
- Jedes Vorhandensein von Fremdmaterialiien wie Luft kann anormalen Druck-
anstieg oder Explosion zur Folge haben.
• Wenn die Klimaanlage in einem kleinen Raum aufgestellt wird, müssen
Maßnahmen ergriffen werden, um zu verhindern, dass die Kältemittelkonzentration selbst bei austretendem Kältemittel den Sicherheitsgrenzwert übersteigt.
- Befragen Sie einen Fachhändler bezüglich geeigneter Maßnahmen zur Ver-
hinderung des Überschreitens des Grenzwertes. Wenn Kältemittel austritt
und dadurch der Sicherheitsgrenzwert überschritten wird, können wegen
des daraus resultierenden Sauerstoffmangels im Raum Gefahren entstehen.
• Beim Verbringen der Anlage an einen anderen Ort einen Fachhändler
oder einen geprüften Techniker zur Neuaufstellung hinzuziehen.
- Bei unsachgemäßer Installation der Anlage kann Wasser austreten, und es
GB
D
DKSWNLIEF
RUTRGRP
21
können Stromschlage oder Brände verursacht werden.
• Nach Abschluß der Installationsarbeiten sicherstellen, daß kein
Kältemittelgas austritt.
- Wenn Kältemittelgas austritt und mit einem Heizgebläse, einem Ofen oder
sonstigen Wärmequellen in Berührung kommt, kann giftiges Gas erzeugt
werden.
• Die Einstellungen der Schutzvorrichtungen nicht neu einrichten oder
ändern.
- Wenn Druckschalter, Thermoschalter oder eine andere Schutzvorrichtung
kurzgeschlossen oder mit Gewalt betätigt wird oder wenn andere als die von
Mitsubishi Electric angegebenen Teile verwendet werden, besteht Brandoder Explosionsgefahr.
• Zum Entsorgen dieses Gerätes wenden Sie sich an Ihren Fachhändler.
• Der Installateur und der Systemfachmann müssen für die Sicherung gegen Wasseraustritt gemäß den örtlichen Bestimmungen und Normen
sorgen.
- Falls keine örtlichen Bestimmungen bestehen, sind die nachstehenden Nor-
men anzuwenden.
• Besondere Beachtung ist den örtlichen Verhältnissen wie etwa dem Kellergeschoß etc. zu schenken, wo sich Kältemittelgas ansammeln kann, da
Kältemittel schwerer als Luft ist.
1.1.Vor der Installation
Vorsicht:
• Anlage nicht an Orten installieren, wo brennbares Gas austreten kann.
GB
- Wenn Gas austritt und sich um die Anlage herum ansammelt, kann dies zu
einer Explosion führen.
• Anlage nicht an Orten verwenden, wo sich Lebensmittel, Tiere, Pflanzen,
Präzisionswerkzeuge oder Kunstgegenstände befinden.
D
- Die Qualität von Lebensmitteln etc. kann beeinträchtigt werden.
• Anlage nicht unter besonderen Umfeldbedingungen einsetzen.
- Dichter Öldampf, Dampf oder schwefelhaltiger Rauch können die Leistung
der Klimageräte erheblich beeinträchtigen oder Teile der Anlage beschädigen.
• Bei Installation der Anlage in einem Krankenhaus, einer Rundfunkstation oder an ähnlichen Orten für ausreichend Lärmschutz sorgen.
- Der Betrieb der Anlage kann gestört oder unterbrochen werden, wenn sie
durch Aufnahmegeräte, private Stromerzeugungseinrichtungen, medizinische
Hochfrequenzgeräte oder Rundfunkeinrichtungen beeinflußt wird. Umgekehrt
kann der Betrieb der Anlage die Funktion dieser Geräte und Einrichtungen
beeinträchtigen und Lärm erzeugen, der ärztliche Behandlungen stört oder
Bildübertragungen beeinträchtigt.
• Die Anlage nicht auf Baueinrichtungen installieren, die Wasseraustritt
verursachen können.
- Wenn die Luftfeuchtigkeit 80 % übersteigt oder wenn die Abwasserleitung
verstopft ist, kann Kondenswasser aus der Innenanlage tropfen. Daher die
vorgesehene Sammelabwasserleitung der Außenanlage einrichten.
1.2.Vor der Installation (Verlegung)
• Klimageräte nicht waschen.
- Waschen der Anlage kann Stromschläge verursachen.
• Sorgfältig darauf achten, daß die Installationsplatte durch langen Gebrauch nicht beschädigt wird.
- Wenn der Schaden nicht behoben wird, kann die Anlage herunterfallen und
Personenschäden oder Sachschäden hervorrufen.
• Zur Gewährleistung eines ordnungsgemäßen Wasserablaufs die Abwasserleitung gemäß Anweisungen in diesem Installationshandbuch installieren. Rohrleitungen mit Wärmeisolierung versehen, um
Kondenswasserbildung zu verhindern.
DKSWNLIEF
- Unsachgemäß angebrachte Abwasserleitungen können Wasseraustritt ver-
ursachen und Schäden an Möbeln oder sonstigen Einrichtungsgegenständen nach sich ziehen.
• Beim Transport der Anlage sehr sorgfältig vorgehen.
- Wenn der Gegenstand mehr als 20 kg wiegt, nicht nur eine Person zum
Tragen einsetzen.
- Bei einigen Produkten werden PP-Bänder zur Verschnürung eingesetzt. Verwenden Sie keine PP-Bänder zum Transport. Dies ist gefährlich.
- Nicht die Wärmetauscherrippen berühren. Man kann sich dadurch die Finger verletzen.
• Verpackungsmaterial sicher entsorgen
- Verpackungsmaterial, wie Nägel und andere Metall- oder Holzteile, können
Stichwunden oder sonstige Verletzungen verursachen.
- Kunststoffbeutel zerreißen und entsorgen, damit Kinder nicht mit ihnen spielen. Wenn Kinder mit Kunstoffbeuteln spielen, die nicht zerrissen wurden,
besteht Erstickungsgefahr.
1.3.Vor Durchführung von Elektroarbeiten
Vorsicht:
• Erdung der Anlage.
- Die Erdungsleitung nicht an Gas- oder Wasserrohre, Blitzableiter oder an
die Erdleitungen von Telefonen anschließen. Unsachgemäße Erdung kann
zu Stromschlägen führen.
• Netzstromleitungen so anbringen, daß keine Zugspannung auf die Kabel
ausgeübt wird.
- Zugspannung Kabelbruch, Wärmebildung und Brände verursachen.
• Einen Erdschlußunterbrecher wie vorgesehen anbringen.
- Wenn kein Fehlerstromschutzschalter angebracht wird, können Stromschlä-
ge verursacht werden.
• Netzstromkabel mit ausreichender Stromstärke und Nennwertauslegung
verwenden.
- Zu kleine Kabel können Fehlstrom verursachen, Wärme erzeugen und Brand
ausbrechen lassen.
• Nur Stromunterbrecher und Sicherungen der angegebenen Leistung verwenden.
- Eine Sicherung oder ein Stromunterbrecher von größerer Stärke oder Stahl-
oder Kupferdraht können zum Ausfall der Anlage oder zum Ausbruch von
Bränden führen.
1.4.Vor Installationsbeginn
Vorsicht:
• Strom mindestens 12 Stunden vor Betriebsbeginn einschalten.
- Betriebsbeginn unmittelbar nach Einschalten des Netzschalters kann zu
schwerwiegenden Schäden der Innenteile führen. Während der Saison Netzschalter eingeschaltet lassen.
• Schalter nicht mit nassen Fingern berühren.
- Berühren eines Schalters mit nassen Fingern kann einen Stromschlag ver-
ursachen.
• Kältemittelrohrleitung nicht während oder unmittelbar nach Betrieb berühren.
- Während und unmittelbar nach Betrieb sind die Kältemittelrohrleitungen, je
nach Durchfluß des Kältemittels durch die Kältemittelrohrleitung, den Kompressor und andere Teile des Kältemittelkreislaufs, manchmal heiß und
manchmal kalt. Sie können sich die Hände verbrennen oder Frostverletzungen
erleiden, wenn Sie die Kältemittelrohrleitung berühren.
• Klimageräte nicht bei abgenommenen Verkleidungen und Schutzabdeckungen betreiben.
- Drehende, heiße oder unter Hochspannung stehende Teile können Verlet-
zungen verursachen.
• Netzstrom nicht unmittelbar nach Betriebsbeendigung ausschalten.
- Vor Ausschalten des Netzstroms immer mindestens 5 Minuten warten. An-
derenfalls kann es zu Wasseraustritt oder sonstigen Störungen kommen.
2. Versorgungseinrichtungen der Innenanlage
Die Anlage ist mit folgenden Versorgungseinrichtungen versehen:
[Fig. 2.0.1](P.2)
Zubehörbezeichnung
Rohrabdeckung (für Leitungsverbindung vor Ort)
• Kleiner Durchmesser
1
• Großer Durchmesser
2
PEA-200, 250PEA-400, 500
Modell (Anzahl*)
12
12
1LCD-Fernbedienung
RUTRGRP
22
3. Einen Aufstellort wählen
• Einen Aufstellort mit stabiler, fester Fläche, die für das Gewicht der Anlage
haltbar genug ist, wählen.
• Vor Einbau der Anlage muß der Weg zum Transport der Anlage an den Aufstellort festgelegt werden.
• Einen Aufstellort wählen wo die Anlage nicht durch eindringende Luft beeinflußt wird.
• Einen Aufstellort wählen wo der Strom der Zu- und Abluft nicht behindert ist.
• Einen Aufstellort wählen wo die Kältemittelrohrleitung problemlos nach außen
geleitet werden kann.
• Einen Aufstellort wählen wo die Luft aus der Anlage sich vollständig im Raum
verteilen kann.
• Die Anlage nicht an einem Ort aufstellen, wo in größeren Mengen Öl verspritzt
oder Dampf erzeugt wird.
• Die Anlage nicht an einem Ort aufstellen, wo brennbares Gas erzeugt werden,
hereinströmen, verbleiben oder austreten kann.
• Die Anlage nicht an einem Ort aufstellen, wo durch Einrichtungen Hochfrequenzwellen entstehen können (z.B. durch ein Hochfrequenz-Schweißgerät).
• Die Anlage nicht an einem Ort aufstellen, wo sich an derSeite, wo die Luftaustritt, ein Feuermelder befindet. (Der Feuermelder kann versehentlich in Gang
gesetzt werden, wenn während des Heizbetriebs Warmluft austritt)
• Wo spezielle chemische Produkte im Raum verteilt sein können, wie in chemischen Anlagen und Krankenhäusern, ist vor Aufstellung der Anlage eine umfassende Untersuchung erforderlich. (Die Kunststoffteile können je nach Art
der chemischen Produkte, denen sie ausgesetzt sind, beschädigt werden)
• Wenn die Innenanlage längere Zeit an einem Ort mit hohen Temperaturen und
Luftfeuchtigkeit betrieben wird (die Taupunkttemperatur beträgt 26°C oder mehr
innerhalb der Decke), kann Kondenswasserbildung an der Innenanlage auftreten. Bei Betrieb unter solchen Bedingungen mehr Isolierungsmaterial (10 20 mm) über die gesamte Oberfläche der Innenanlage zufügen, um
Kondenswasserbildung zu verhindern.
3.1.Die Innenanlage an einer Decke mon-
tieren, die stark genug ist, um das Gewicht zu halten
3.2.Sicherstellen des Freiraums für Montage und Wartung/Bedienung
• Entsprechend der Raumanordnung und der Aufstellposition die optimale
Strömungsrichtung der Luft aus der Anlage feststellen und auswählen.
• Wenn Rohrleitungen und Elektroleitungen an den Boden- und Seitenflächen
angeschlossen sind und die Bedienung und Wartung an der gleichen Fläche
vorgenommen wird, genügend Freiraum vorsehen. Zur effizienten Vornahme
der Aufhängungsarbeiten und zur Sicherheit soviel Freiraum wie möglich vorsehen.
Raum für Bedienung und Wartung
[Fig. 3.2.1] (P.2)
1 Beim Anschluß des Lufteingangs
2 Bei Anbringung der Aufhängungsbefestigungen vor Aufstellung der Innenanlage
ohne Eingangsströmungskanal
3 Bei unmittelbarem Aufhängen der Innenanlage ohne Eingangsströmungskanal
A Freiraum für Bedienung und Wartung
B LufteingangC Luftausgang
Abstand der Aufhängungsbolzen
[Fig. 3.2.2] (P.2)
D Hängebolzen-SteigungE Oberseite der Anlage
F Hängebolzen-Löcher
Zum Verbinden der Innenanlagen mit Außenanlagen im Montagehandbuch der
Außenanlagen nachschlagen.
GB
D
Warnung:
Die Anlage muß an einem Gebäudeteil, der das Gewicht tragen kann, sicher
angebracht werden. Wenn die Anlage an einem Gebäudeteil mit ungenügender Tragkraft montiert wird, kann sie herunterfallen und Personenschäden
verursachen.
4. Befestigung der Hängebolzen
4.1.Befestigung der Hängebolzen
Baustruktur für die Aufhängung
• Decke: Die Deckenstruktur ist von Gebäude zu Gebäude unterschiedlich. Holen Sie nähere Informationen bei der jeweiligen Bauunternehmung ein.
1 Verstärkung der Decken durch zusätzliche Stützglieder (Deckenträger etc.) ist
erforderlich, um die Decke in der Waagerechten zu halten und um Schwingungen der Decke zu vermeiden.
2 Die Stützglieder der Decke abtrennen und herausnehmen.
3 Die Stützglieder der Decke verstärken und weitere Bauelemente zur Befesti-
gung der Deckenplatten hinzufügen.
Bei Holzkonstruktionen
• Verwenden Sie den Dachbalken (bei eingeschossigen Gebäuden) oder den
Deckenträger (bei zweigeschossigen Gebäuden) als verstärkende Bauelemente.
• Zum Aufhängen der Klimaanlage Vierkanthartholz von mehr als 6 cm Seitenlänge verwenden, wenn der Abstand zwischen den Trägern weniger als 90 cm
und Vierkanthartholz von mehr als 9 cm Seitenlänge verwenden, wenn der
Abstand zwischen den Trägern weniger als 180 cm beträgt.
[Fig. 4.1.1](P.2)
A DeckenplatteB EckenträgerC Dachbalken
D Vierkantholz zur Aufhängung der KlimaanlageE Abstand
Zur Verstärkung von Betonkonstruktionen
• Die Hängebolzen, wie in der nachstehenden Darstellung gezeigt, befestigen
oder die Hängebolzen mit Vierkantholz befestigen.
[Fig. 4.1.2](P.2)
F Einschub: 100 bis 150 kg (1 Stück) (Vor Ort zu beschaffen)
G Hängebolzen (vor Ort zu beschaffen)
PEA-200, 250 : M10
PEA-400, 500 : M12
H Verstärkung
Produktgewicht (kg)
PEA-20070 kg
PEA-25077 kg
PEA-400130 kg
PEA-500133 kg
DKSWNLIEF
23
RUTRGRP
5. Aufstellen der Anlage
5.1.Aufhängen des Anlagenkörpers
s Die Innenanlage in der Verpackung an den Aufstellungsort bringen.
s Zum Aufhängen der Innenanlage diese mit einer Hebevorrichtung anhe-
ben und durch die Hängebolzen führen.
s Innenanlage vor Vornahme der Deckenarbeiten anbringen.
[Fig. 5.1.1] (P.3)
A AnlagenkörperB Hebevorrichtung
* Zwei Installationsmethoden stehen zur Verfügung
<Bei direktem Aufhängen der Innenanlage>
1. Jede Aufhängungsschraube mit einer Unterlegscheibe und Mutter(n) versehen. (Unterlegscheiben und Muttern vor Ort beschaffen.)
2. Innenanlage an jedem Aufhängungsbolzen anbringen.
3. Dafür sorgen, daß die Anlage waagerecht angeordnet ist, dann die einzelnen
Muttern anziehen.
[Fig. 5.1.2](P.3)
A MutterB Unterlegscheibe
GB
Bei Verwendung des Einlaßkanals
Bei Nichtverwendung des Einlaßkanals
Mutter (*1) ist nicht erforderlich, wenn der Abstand A die Länge 0 hat.
AB
100 oder mehr130 oder mehr
0 oder mehr30 oder mehr
D
<Bei Installation der Aufhängungshalterung vor der Installation der Innenanlage>
1. Jeden Aufhängungshalterungsbolzen leicht lösen, und die Halterung und Uförmigen Unterlegscheiben entfernen.
2. Jeden Aufhängungshalterungsbolzen einstellen.
3. Eine Unterlegscheibe, Mutter und Aufhängungsbefestigung an jedem
Aufhängungsbolzen anbringen. (Die Unterlegscheiben und Muttern werden
vor Ort beschafft.)
4. Die Innenanlage auf die Aufhängungsbefestigungen haken.
5. Sicherstellen, dass die Einheit eben positioniert ist und dann jede Mutter festziehen.
[Fig. 5.1.3](P.3)
A Immer eine U-förmige Unterlegscheibe anbringen (insgesamt 4 Unterlegscheiben).
Bei Verwendung des Einlaßkanals
Bei Nichtverwendung des Einlaßkanals
AB
100 oder mehr130 oder mehr
25 oder mehr55 oder mehr
5.2.Sich über die richtige Lage der Anlage
vergewissern und die Hängebolzen befestigen
[Fig. 5.2.1] (P.3)
A Überprüfung der Waagerechten
s Mit der mit der Füllplatte gelieferten Lehre vergewissern, daß der An-
lagenkörper und die Hängebolzen sich in der richtigen Lage befinden.
Wenn sie nicht richtig angeordnet sind, kann dies aufgrund von Luftdurchgangsöffnungen zur Tropfenbildung führen. Vergewissern, daß das
Lageverhältnis genau überprüft wird.
s Mit einer Wasserwaage vergewissern, daß sich die mit
nete Fläche in der Waagerechten befindet. Auch dafür sorgen, daß die
Muttern der Hängebolzen fest angezogen sind, um die Hängebolzen zu
sichern.
s Um zu gewährleisten, daß der Wasserauslauf stattfindet, mit einer Was-
serwaage sicherstellen, daß die Anlage in der Waagerechten hängt.
Vorsicht:
Dafür sorgen, daß der Anlagenkörper waagerecht angebracht wird.
AA
A gekennzeich-
AA
6. Technische Daten der Kältemittel- und Auslaufrohrleitung
Um Tropfenbildung zu vermeiden, die Kältemittel- und Auslaufrohrleitung ausreichend gegen Schwitzwasserbildung sichern und mit Isoliermaterial ausstatten.
Bei Einsatz von handelsüblichen Kältemittelrohren dafür sorgen, daß handelsübliches Isoliermaterial (mit einer Hitzebeständigkeit von mehr als 100°C und der nachstehend angegebenen Stärke) sowohl um die Flüssigkeits- als auch um die Gasrohre gewickelt wird.
Auch dafür sorgen, daß handelsübliches Isoliermaterial (mit einem spezifischen
Gewicht für Schaumpolyäthylen von 0,03 und der nachstehend angegebenen Stärke) um alle Rohre, die durch Räume verlaufen, gewickelt wird.
1 Auswahl der Stärke des Isoliermaterials nach Rohrgrößen.
RohrgrößeStärke des Isoliermaterials
6,4 mm bis 25,4 mmMehr als 10 mm
28,6 mm bis 38,1 mmMehr als 15 mm
2 Wenn die Anlage im obersten Stockwerk eines Gebäudes und unter
Umgebungsbedingungen mit hoher Temperatur und hoher Luftfeuchtigkeit eingesetzt wird, ist es notwendig, Rohrgrößen und Isoliermaterialstärken zu ver-
DKSWNLIEF
wenden, die über den in der Tabelle angegebenen liegen.
3 Wenn technische Angaben seitens des Kunden vorliegen, diese einfach befolgen.
6.1.Technische Daten der Kältemittel- und
Auslaufrohrleitung
Position
Kältemittel-
rohr
Auslaufrohr
Flüssigkeitsrohr
Gasrohr
6.2.Kältemittelrohr, Auslaufrohr und Einfüll-
öffnung
[Fig. 6.2.1] (P.3)
A Kältemittelrohrleitung (Flüssigkeitsrohrleitung)
B Kältemittelrohrleitung (Gasrohrleitung)C Auslaufrohr
7. Kältemittel- und Auslaufrohrleitungen anschließen
7.1.Verrohrung der Kältemittelleitung
Die Verrohrung muß gemäß Anweisungen im Aufstellungshandbuch für die Außenanlage vorgenommen werden.
• Der Rohranschluß erfolgt mittels Hartlöt-Verfahren.
Vorsichtsmaßregeln bei Kältemittelrohrleitungen
s Dafür sorgen, daß zum Hartlöten nichtoxidierende Hartlötverfahren an-
gewendet werden, um zu gewährleisten, daß keine Fremdstoffe oder
Feuchtigkeit in die Rohrleitung eindringen.
s Die Kältemittelrohrleitung mit einer Metallklammer stützen, damit das
Endrohr der Innenanlage keiner Belastung ausgesetzt wird. Diese Me-
RUTRGRP
tallklammer muß 50 cm von der hartgelöteten Verbindung der Innenanlage entfernt angebracht werden.
Warnung:
Beim Installieren und Verlegen der Anlage kein anderes Kältemittel als das
auf der Anlage angegebene Kältemittel (R410A) einfüllen.
- Jedes Vorhandensein von Fremdmaterialiien wie Luft kann anormalen Druckan-
stieg oder Explosion zur Folge haben.
Vorsicht:
• Die Kältemittelrohre für die Innenanlage gemäfl der folgenden Angaben
installieren.
1. Die Kappe abnehmen.
[Fig. 7.1.1](P.3)
A Kappe abnehmen
2. Die Wärmeisolierung an der Seite des Kältemittelrohres herausziehen, die Rohrleitungen der Anlage löten, und die Isolierung wieder an der ursprünglichen
Stelle anbringen.
Die Rohrleitung mit Isolierband umwickeln.
24
Modell
PEA-200
ø9,52
PEA-250
ø12,7
R1 (Schraubenspindel)
PEA-400
ø9,52
ø25,4
PEA-500
ø12,7
[Fig. 7.1.2] (P.3)
A WärmeisolierungB Isolierung abziehen
C Mit feuchtem Tuch umwickeln
D Wieder an ursprünglicher Stelle anbringen
E Dafür sorgen, dafl an dieser Stelle keine Lücke ist
F Mit Isolierband umwickelnG Rohrabdeckung (Zubehör)
Hinweis:
• Beim Umwickeln der Kupferrohre größte Vorsicht walten lassen, da sich
durch das Umwickeln der Rohrleitung Kondenswasser bilden kann, anstatt dies zu verhindern.
* Vor dem Löten der Kältemittelrohre die Rohre am Anlagenkörper und die
Wärmeisolierungsrohre immer mit feuchten Tüchern umwickeln, um
Wärmeschrumpfen und Verbrennen der Wärmeisolierungsrohre zu vermeiden. Dafür sorgen, dafl die Flamme nicht mit dem Anlagenkörper in Be-
rührung kommt.
Vorsicht:
• Kältemittelrohrleitungen aus phosphor-deoxidiertem Kupfer C1220 (CUDHP) gemäß Angaben in JIS H3300 “Nahtlose Rohrleitungen und Rohre
aus Kupfer und Kupferlegierung” verwenden. Außerdem vergewissern,
daß die Innen- und Außenflächen der Rohrleitungen sauber und frei von
gefährlichem Kupfer, Oxyden, Staub/Schmutz, Metallbearbeitungsrückständen, Ölen, Feuchtigkeit oder anderen Verunreinigungen sind.
- Die große Menge Chlor in herkömmlichen Kältemitteln und Kältemaschinenöl
in der vorhandenen Rohrleitung führt zu einer Qualitätsminderung des neuen Kältemittels.
• Die zu verwendende Rohrleitung während der Installation in einem geschlossenen Raum aufbewahren und beide Enden der Rohrleitung bis
unmittelbar vor dem Hartlöten abgedichtet lassen.
- Wenn Staub, Schmutz oder Wasser in den Kältemittelkreislauf gelangen,
wird die Qualität des Öls gemindert, was zum Ausfall des Kompressors füh-
ren kann.
• Keine Additive zur Erkennung von undichten Stellen verwenden.
Zusätzliche Kältemittelfüllung
• Dafür sorgen, daß weder Schmutz noch Schneidrückstände in die Rohrleitungen
gelangen.
• Die Kältemittelrohrleitungen müssen warm gehalten werden. Daher besonders
auf die Isolierung zwischen Kältemittelrohrleitungen und Gasrohrleitung im
Inneren der Innenanlage achten, da die Gasrohrleitung während des Kühl-
betriebs Kondenswasser bildet.
• Beim Anschluß der Kältemittelrohrleitungen dafür sorgen, daß die Absperrarmatur der Außenanlage vollständig geschlossen ist (wie dies bei Versand ab
Werk der Fall war). Nach Anschluß der Kältemittelrohrleitungen zwischen Innen- und Außenanlagen von der Wartungseinheit der Außenanlage und der
Wartungseinheit von jeder Anschlußrohrleitung aus eine Luftreinigung vornehmen. Vergewissern, daß an den Rohranschlüssen keine Luft austritt, dann die
Absperrarmatur der Außenanlage vollständig öffnen. Dadurch wird der
Kältemittelkreislauf zwischen Innen- und Außenanlagen angeschlossen.
• Die Kältemittelrohrleitungen müssen so kurz wie möglich sein.
• Die Innen- und Außenanlagen müssen mit Kältemittelrohrleitungen verbun-
den werden.
[Fig. 7.1.3](P.3)
A HartlötenB Gasrohrleitung
C FlüssigkeitsrohrleitungD Innenanlage
E Außenanlage
7.2.Verrohrung des Auslaufs/der Dränage
[Fig. 7.2.1] (P.4)
A IsolatorB Ablassrohr R1
C AblassschaleD
>
E
G Abwärtsneigung 20 mm/m oder mehr
H Geruchverschluss
I Das Ablassrohr sollte bis unter diesen Pegel reichen.
J Offener Ablass
1. Dafür sorgen, daß die Auslaufrohrleitung in Richtung Außenanlage (Abwasserauslauf) geneigt ist (Verhältnis von mehr als 20 mm/m).
2. Dafür sorgen, daß abzweigende Auslaufrohrleitungen weniger als 20 m lang
sind (unabhängig vom Steigungsunterschied). Bei langen Dränagerohren Metallklammern (Rohrschellen) anbringen, um Schwingungen zu verhindern. Niemals Luftabzugsrohre anbringen, da sonst Abwasser ausgestoßen wird.
3. Ein Hartvinylchlorid-Rohr VP-25 (mit einem Außendurchmesser von 32 mm)
als Auslaufrohr verwenden.
4. Dafür sorgen, daß zusammengefaßte Rohre 10 cm niedriger als die Wartungseinheit des Anlagekörpers angebracht sind.
5. Das Ende des Auslaufrohrs an einer Stelle anbringen, an der kein Geruch
entstehen kann.
6. Das Ende der Auslaufleitung nicht in einen Ablauf verlegen, in dem sich IonenGase bilden können.
>
2 × F
70 mmF
=
=
>
70 mm
=
>
35 mm
=
GB
D
8. Arbeiten am Strömungskanal
• Beim Anschluß des Strömungskanals zwischen Anlage und Strömungskanal
ein Zwischenstück aus Segeltuch einsetzen.
• Für die einzelnen Teile des Strömungskanals nichtbrennbares Material ver-
wenden.
• Die Flansche am Eingang des Strömungskanals, am Ausgang des Strömungskanals und den Ausgangsströmungskanal selbst vollständig isolieren, um
Kondenswasserbildung zu verhindern.
• Dafür sorgen, daß der Luftfilter in der Nähe des Lufteinganggitters angebracht
wird.
• Vor Anschluß eines Eingangsströmungskanals Luftfilter (mit der Anlage geliefert) abnehmen, dann diesen Filter im Einlaßgitter anbringen.
[Fig. 8.0.1](P.4)
A LufteingangB LuftausgangC Zugangstür
D DeckenflächeE Teilstück des Strömungskanals aus Segeltuch
F Länge des Strömungskanals bei 850 mm oder mehr halten
G Strömungskanal und Klimaanlage mit Spannungsleitung der üblichen Art verbin-
den
Vorsicht:
• Der Ausgangsströmungskanal muß auf 850 mm oder mehr ausgelegt
werden.
• Den Hauptkörper der Klimaanlage und den Strömungskanal zum potentiellen Ausgleich miteinander verbinden.
• Eingangstemperaturfühler, wenn ein Eingangsströmungskanal installiert wurde.
Am Flansch des Eingangsströmungskanals ist ein Eingangstemperaturfühler
installiert. Vor Anbringung eines Eingangsströmungskanals muß der Fühler
abgenommen und an der angegebenen Stelle installiert werden.
[Fig. 8.0.2](P.4)
A Flansch des Eingangsströmungskanals
B EingangstemperaturfühlerC Fühlerschutzplatte
D FühlerbefestigungE Eingangsströmungskanal
1 Fühler herausziehen und Fühlerbefestigung und Schutzplatte abnehmen. (Die
Schutzplatte muß beseitigt werden.)
2 Den Eingangsströmungskanal anschließen.
3 An der Seite des Strömungskanals ein Fühlerloch (Durchmesser ø12,5) boh-
ren.
4 Fühler zusammen mit der Befestigung anbringen.
• Fühler nicht an der Elektroleitung herausziehen, da sonst die Leitung brechen
kann.
• Vor Anschluß des Eingangsströmungskanals vergewissern, daß der Fühler,
seine Befestigung und die Schutzplatte abgenommen wurden.
• Der in Schritt 1 abgenommene Fühler muß an der in der Zeichnung angegebenen Stelle wieder angebracht werden. Wird der Fühler an der falschen Stelle angebracht, kann dies zu Fehlfunktionen führen.
Befestigungslöcher für Flansch des Ausgangsführungskanals und Eingangsströmungskanals.
[Fig. 8.0.3] (P.4)
A Einlasskanalflansch
B Auslaßkanalflansch
C Oberseite der Anlage
DKSWNLIEF
RUTRGRP
25
9. Elektroverdrahtung
Vorsichtsmaßnahmen bei der elektrischen Verdrahtung
Warnung:
Elektroarbeiten sollen nur durch qualifizierte Fachelektriker gemäß “ör tlichen
Vorschriften” und den Anweisungen in den mitgelieferten Handbüchern ausgeführt werden. Es sollen eigens eingerichtete Stromkreise verwendet werden. Wenn der Stromkreis zu schwach ausgelegt ist oder Installationsfehler
aufweist, besteht die Gefahr von Stromschlägen oder Brand.
1. Dafür sorgen, daß die Netzstromversorgung über einen gesonderten Strom-
kreis erfolgt.
2. Dafür sorgen, daß ein Erdschlußstromunterbrecher in den Stromkreis instal-
liert wird.
3. Die Anlage so installieren, daß verhindert wird, daß eines der Steuerkreis-
kabel (Fernbedienung, Übertragungskabel) in direkten Kontakt mit dem Netzstromkabel außerhalb der Anlage gebracht werden kann.
4. Dafür sorgen, daß keiner der Elektroleitungsanschlüsse zu lose gespannt ist
oder einen Wackelkontakt aufweist.
5. Einige Kabel (für Netzstrom-, Fernbedienungs-Übertragungskabel), die ober-
halb der Decke angeordnet sind, können Mäuseverbiß ausgesetzt sein. Daher
Kabel zum Schutz soweit wie möglich in Metallrohre verlegen.
6. Netzstromkabel niemals an die Zuleitung für die Übertragungskabel anschlie-
GB
ßen, da sonst die Kabel brechen können.
7. Dafür sorgen, daß die Innenanlage, die Fernbedienung und die Außenanlage
mit Steuerkabeln verbunden sind.
8. Die Anlage auf der Seite der Außenanlage erden.
D
9. Für Anschluß zwischen Klemmleiste des Steuerkabels, der Außenanlage und
dem der Innenanlage sorgen. (Kabel besitzen Polarität. Daher dafür sorgen,
daß sie entsprechend den Anschlußnummern angeschlossen werden.)
10. Bei Befestigung der Netzstromleitung an den Steuerkasten darauf achten, daß
eine Pufferbuchse gegen Zugspannung angebracht wird (PG-Anschluß oder
ähnliches). Steuerleitung an das Steuerklemmbrett durch die ausgebrochenen Öffnungen im Steuerkasten mit normalen Buchsen anschließen.
11. Nicht die Anlage in umgekehrter Phasensequenz anschließen.
Bei Anschluß in umgekehrter Phasensequenz kann die Innenanlage nicht ausreichend Kühlluft zuführen. (PEA-200, 250, 400, 500)
Im Falle von A-Steuerungs-Verkabelung besteht ein Hochspannungspotential
am Anschluss S3 auf Grund der Auslegung des elektrischen Schaltkreises,
das keine Isolierung zwischen Netzstrom und Kommunikationssignalleitung
vorsieht. Daher trennen Sie das Gerät bei Arbeiten vollständig vom Netzstrom. Berühren Sie außerdem die Anschlüsse S1, S2 und S3 nicht, wenn
das Gerät am Netzstrom angeschlossen ist. Wenn zwischen Innen- und Außenanlage ein Trennschalter verwendet werden soll, verwenden Sie einen
dreipoligen Typ.
Vorsicht:
Dafür sorgen, daß die Anlage zur Seite der Außenanlage hin geerdet wird.
Die Erdleitung nicht an Gasrohre, Wasserrohre, Beleuchtungsstäbe oder
Telefonerdleitungen anschließen. Unsachgemäße Erdung kann zu Stromschlägen führen.
[Fig. 9.0.1] (P.5)
A Betriebsstrom:
B Erdschlußunterbrecher
C Stromunterbrecher oder örtlicher Schalter
D LCD-Fernbedienung
E Außenanlage
F Innenanlage
G Netzstromkabelverdrahtung
H Verbindungsverdrahtung außen/innen
I Erdung
Vorsicht:
Für PEA-400, 500 sicherstellen, daß die Kältemittelleitungen und
Verdrahtungen jeweils von der Außenanlage Nr. 1 zur Innenanlage Nr. 1 und
der Außenanlage Nr. 2 zur Innenanlage Nr. 2 ausgeführt werden.
Die Verdrahtung von der Außenanlage Nr. 1 muß am Klemmbrettkasten TB41 vorgenommen werden, und die Verdrahtung von der Außenanlage Nr. 2
muß an TB4-2 am Schaltkasten der Innenanlage vorgenommen werden.
Werden bei Vornahme dieser Anschlüsse Fehler gemacht, führt dies zu
unnormalen Kühlmittelleitungstemperaturen usw.
[Verdrahtungsbeispiel] (Für Metallrohre)
Erdschlußunterbrecher
*1, *2
PEA-200, 250, 400, 500
Hinweise:
*1: Einen Erdschlußstromunterbrecher in der Stromversorgung installieren.
*2: Erdschlußstromunterbrecher verwenden, die speziell für Erdschlußschutz in Kombination mit einem örtlichen Schalter oder Stromunterbrecher konstruiert
sind.
*3: Der Überstromschutz unter Verwendung einer Sicherung der Klasse B wird gezeigt.
*4: Netzstromkabel dürfen nicht leichter als polychloropren-beschichtete flexible Kabel sein (Design 245 IEC 53 oder 227 IEC 53).
*5: Verbindungskabel für Innenanlage/Außenanlage dürfen nicht leichter als polychloropren-beschichtete flexible Kabel sein (Design 245 IEC 57).
*6: Bei der Installierung der Klimaanlage ist ein Schalter mit einem Kontaktabstand von mindestens 3 mm für jeden Pol vorzusehen.
*7: Die Verbindungsverdrahtung zwischen Außenanlage und Innenanlage kann bis zu maximal 50 m erweitert werden.
DKSWNLIEF
Vorsicht:
Nur Unterbrecher und Sicherungen mit der richtigen Kapazität verwenden.
Bei Verwendung von Sicherungen, Leitungen oder Kupferleitungen mit zu
großer Leistungsaufnahme besteht die Gefahr der Fehlfunktion oder Brandgefahr.
Lage der Kabelöffnungen
[Fig. 9.0.2] (P.5)
A Für Fernbedienungskabel
B Für Anschlusskabel der AußenanlageC For Stromversorgungskabel
15 A 30 mA
0,1 s. oder weniger
Örtlicher Schalter
Schalter-
kapazität <A>
16
Überstrom-
schutz *3 <A>
16
Stromunter-
brecher
15
Netzstromkabel
*4
1,5 mm2 oder mehr
Erdkabel
1,5 mm2 oder mehr
Verbindungsverdrahtung
innen/außen *5
2
oder mehr
1,5 mm
Fernbedienungsverdrahtung
0,3 - 1,25 mm
(max. DC 12V)
2
RUTRGRP
26
10. Systemsteuerung
10.1.
Gruppierung mit LCD-Fernbedienung
Kombination von Innenanlage/Außenanlage zur Steuerung von maximal 16
Kältemittelsystemen.
[Fig. 10.1.1](P.6)
A AußenanlageB Innenanlage
C Haupt-FernbedienungD Neben-Fernbedienung
E Standard (Kältemitteladresse = 00) F Kältemitteladresse = 01
G Kältemitteladresse = 02H Kältemitteladresse = 03
I Kältemitteladresse = 14J Kältemitteladresse = 15
* Die Kältemitteladresse mit dem DIP-Schalter an der Außenanlage einstellen.
* Einstellmethode von SW1 siehe Installationshandbuch der Außenanlage
DIP-Schalter.
1 Verdrahtung von der Fernbedienung
Dieser Draht ist an TB5 (Klemmenbrett für Fernbedienung) der Innenanlage angeschlossen (nichtpolar).
2 Bei Verwendung einer anderen Kältemittelsystem-Gruppierung
Bis zu 16 Kältemittel-Systeme können als eine Gruppe mit der LCD-Fernbedienung gesteuert werden.
Hinweise:
1. Bei Einzel-Kältemittelanlagen ist Verdrahtung 2 nicht erforderlich.
2. LCD-Fernbedienung kann für maximal 2 Anlagen für eine Gruppe installiert werden.
10.2. Beispiele für Kältemittelsystemadressen-Einstellung
Z.B.
Innenanlage
1
PEA-200, 250
2
PEA-400, 500
* Die Kältemittelsystem-Adresse einer Außenanlage auf 00 für die Stromversor-
gung zur Fernbedienung stellen.
(Die Kältemittelsystem-Adresse ist werkseitig auf 00 gestellt.)
Nicht die Kältemittelsystemadressen-Einstellungen innerhalb des gleichen Systems duplizieren.
Außenanlage
–
Nr. 1
Nr. 2
Außenanlage-
Kältemittelsystemadresse
00
00
01~15
Fernbedienung-
Stromversorgungseinheit
✕
GB
SW1
Funktionstabelle
<SW1>
ON
OFF
123456
SW1
Funktionseinstellungen
Funktion
1 Vorgeschriebene
Entfrostung
2
Fehlerverlauf löschen
3
K ä ltemittel-
4
systemadresse-
5
Einstellung
6
Betrieb entsprechend der
Schaltereinstellung
ON (EIN)OFF (AUS)
StartNormal
LöschenNormal
Einstellungen für Außenanlage-Adressen 0 bis 15
11. LCD-Fernbedienung
11.1. Installationsabläufe
(1) Aufstellungsort für Fernbedienung (Schaltkasten) auwählen.
Dabei nachstehende Vorsichtsmaßnahmen beachten.
[Fig. 11.1.1] (P.6)
A Form der Fernbedienung
B Erforderliche Freiräume um die Fernbedienung herum
C TemperaturfühlerD Installationsteilung
1 Die Temperaturfühler befinden sich sowohl an der Fernbedienung als auch an
der Innenanlage. Den Temperaturfühler an der Fernbedienung hauptsächlich
zur Temperatureinstellung oder zur Ermittlug der Raumtemperatur verwenden.
Die Fernbedienung an einer Stelle anbringen, an der die durchschnittliche
Raumtemperatur festgestellt werden kann, ohne daß sie durch direktes Sonnenlicht, Luftstrom aus der Klimaanlage oder sonstige Heizquellen beeinflußt wird.
2 In jedem Falle, ob nun die Fernbedienung im Schaltkasten oder an der Wand
befestigt wird, dafür sorgen, daß die in der Zeichnung angegebenen Freiräume
eingehalten werden.
Hinweis:
Vergewissern, daß sich in der Nähe des Fühlers der Fernbedienung keine
Elektroleitung befindet. Wenn sich eine Elektroleitung nahe dem Fühler befindet, kann die Fernbedienung u.U. die richtige Raumtemperatur nicht feststellen.
3 Folgende Teile vor Ort beschaffen:
Schaltkasten für zwei Teile
Dünnes Kupferleitungsrohr
Kontermuttern und Buchsen/Leitungsdurchführungen
(2) Den Wartungszugang des Fernbedienungskabel mit Kitt oder Dichtungs-
mittel abdichten, um das mögliche Eindringen von Tau, Wasser, Kakerlaken oder Würmern und Raupen zu verhindern.
<A> Zur Installation des Schaltkasten:
• Wenn die Fernbedienung im Schaltkasten installiert wird, die Verbindung zwischen Schaltkasten und Leitungsrohrdurchführung mit Kitt abdichten.
<B> Bei Installation direkt an der Wand wie folgt vorgehen:
B-1. Zur Führung des Fernbedienungskabels von der Rückseite der Steue-
rung:
• Ein Loch für das Anschlußkabel der Fernbedienung durch die Wand brechen
(damit das Kabel der Fernbedienung von hinten durchgeführt werden kann),
dann das Loch mit Kitt abdichten.
B-2. Zur Führung des Fernbedienungskabels durch die Oberseite:
• Das Fernbedienungskabel durch einen Einschnitt im oberen Gehäuse führen,
dann den Einschnitt in ähnlicher Weise wie oben mit Kitt abdichten.
[Fig. 11.1.1](P.6)
C Wand/MauerD RohrleitungE Kontermutter
F Buchse/RohrleitungsführungG Schaltkasten
H Kabel der FernbedienungI Mit Kitt abdichten
(3) Den unteren Kasten im Schaltkasten oder an der Wand befestigen.
[Fig. 11.1.1] (P.6)
<A> Bei Installation im Schaltkasten
C Schaltkasten für zwei StückD Kabel der Fernbedienung
E Zylinderkopfschraube mit Kreuzschlitz
G Bedienungszugang des Kabels der Fernbedienung mit Kitt abdichten.
<B> Bei Installation direkt an der Wand
H Holzschraube
Vorsicht:
Die Schrauben nicht zu stark anziehen, damit der untere Kasten nicht deformiert wird oder bricht.
Hinweis:
• Zur Installation einen ebenen Platz auswählen.
• Darauf achten, daß zur Sicherung der Fernbedienung im Schaltkasten
oder an der Wand zwei oder mehr Plätze vorgesehen werden.
D
DKSWNLIEF
RUTRGRP
27
11.2. Anschlußverfahren
• Das Kabel der Fernbedienung kann auf max. 200 m verlängert werden. Verwenden Sie zum Anschluss einer Fernbedienung Elektroleitungen oder (2adrige) Kabel von 0,3 mm
licher Fehlfunktionen der Anlage keine mehradrigen Kabel.
[Fig. 11.2.1] (P.6)
(1) Schließen Sie das Fernbedienungskabel an die Klemmleiste im unteren
Gehäuse an.
A Zu TB5 an der Innenanlage
B Klemmleiste TB6 auf der Fernbedienung
Keine Polarität
Vorsicht:
• Zum Anschluß an die Klemmleiste der Fernbedienung keine Quetschkontakte verwenden, um unerwünschte Kontakte mit der Tafel und daraus resultierende Störungen zu vermeiden.
• Achten Sie darauf, dass keine metallenen Schnipsel in die Fernbedienung gelangen. Dies kann zu einem elektrischen Schlag oder zu Fehlfunktionen führen.
2
bis 1,25 mm2. Verwenden Sie zur Vermeidung mög-
(2) Zur Installierung des oberen Gehäuses bringen Sie zunächst die oberen
Verriegelungen (an 2 Stellen) an, und fügen Sie dann, wie abgebildet, das
obere Gehäuse in das untere Gehäuse ein.
[Fig. 11.3.2] (P.6)
Hinweis:
Kabelloch für die direkte Wandinstallation (oder offene Verkabelung)
• Schneiden Sie mit einem Messer, einer Kneifzange usw. den schattierten
Teil vom oberen Gehäuse ab.
• Ziehen Sie das Kabel der Fernbedienung heraus, das an den Anschlußblock über diesen Ausschnitt angeschlossen ist.
Vorsicht:
• Den Schraubenzieher nicht drehen, wenn die Spitze weit in die Verriegelungen hineinreicht, damit diese nicht brechen.
• Achten Sie bitte darauf, das obere Gehäuse sicher in den Verriegelungen
anzubringen, indem Sie es nach unten drücken, bis ein hörbares Einrasten erfolgt. Locker eingefügt kann das obere Gehäuse herunterfallen.
Hinweis:
Der Arbeitsbereich ist mit einem Schutzblech abgedeckt. Vor Benutzung der
Anlage daran denken, das Schutzblech abzunehmen.
11.3. Anbringung des oberen Kastens
[Fig. 11.3.1] (P.6)
GB
(1) Zum Abnehmen des oberen Kastens die Spitze eines flachen Schrau-
benziehers, wie auf der Zeichnung dargestellt, in der Verriegelung ansetzen, dann den Schraubenzieher in Pfeilrichtung drehen.
D
11.4. Funktionswahl
<Typ verdrahtete Fernbedienung>
(1) Funktionsauswahl an der Fernbedienung
Die Einstellung der folgenden Fernbedienungsfunktionen kann mit dem Auswahlmodus der Fernbedienungsfunktion geändert werden. Ändern Sie die Einstellung nach Bedarf.
Eintrag 1
1.Sprache ändern
(“CHANGE LANGUAGE”)
2.Funktionsgrenzen
(“Funktion auswahlen”)
3.
Auswahl der Betriebsart
(“Betriebsart wahlen”)
4.Änderung der Anzeige
(“Anzeige betriebsart”)
* Dieses Modell ist nicht mit dieser Funktion ausgestattet. Die Einstellung ist ungültig.
Einstellung der angezeigten Sprache
(1) Einstellung der Funktionsgrenzen bei der Bedienung (Operation
Lock) (“Sperr-Funktion”)
(2)
Einstellung der Benutzung der Betriebsar t Automatisch (“Auswahl autobetrieb”)
(3) Einstellung der Temperaturgrenzen (“Limit temp Funktion”)
*
(4) Verwendung der automatischen Filteranheberpanel Auf/Ab-
Betriebsmodus-Einstellung
*
(5) Verwendung der Festluftstromrichtungsmodus-Einstellung
(1) Haupt-/Nebenfunktion der Fernbedienung (“Haupt/Neben
controller”)
(2) Benutzung der Uhreinstellung (“Uhr”)
(3) Einstellung der Timer-Funktion (“Wochenzeit schalt uhr”)
(4) Kontaktnummer für den Fall von Fehlfunktionen (“CALL.”)
(1) Temperatureinstellung in °C/°F (“Wechsel °C/°F”)
(2)
Einstellung der Anzeige der Luftansaugtemperatur (“Raum TEMP gewahlt”)
(3)
Einstellung der automatischen Kühl-/Heizanzeige (“Auto Betrieb C/H”)
Eintrag 2
• Anzeige in mehreren Sprachen ist möglich.
• Einstellung der Funktionsgrenzen bei der Bedienung (Operation Lock)
• Einstellung, ob die Betriebsart “Automatisch” benutzt wird oder nicht
• Einstellung des Temperaturbereichs (maximum, minimum)
• Einstellung der Verwendung oder Nichtverwendung des automatischen Filteranheberpanel Auf/Ab-Betriebsmodus
•
Einstellung der Verwendung oder Nichtverwendung des Festluftstromrichtungsmodus
• Auswahl der Funktion als Haupt-/Nebenfernbedienung
* Wenn zwei Fernbedienungen in einer Gruppe angeschlossen sind, muss eine
der beiden als Nebengerät arbeiten.
• Einstellung, ob die Zeitfunktionen benutzt werden oder nicht
• Einstellen des Timer-Typs
• Anzeige der Kontaktnummer für den Fall von Fehlfunktionen
• Einstellen der Telefonnummer
• Einstellen der Temperaturanlage der Anzeige (°C oder °F)
•
Einstellung, ob die Temperatur der (angesaugten) Innenluft angezeigt wird oder nicht
• Einstellung, ob “Cooling” oder “Heating” (Kühlen/Heizen) in der Betriebsart Automatisch angezeigt werden oder nicht
Eintrag 3 (Inhalt der Einstellungen)
DKSWNLIEF
RUTRGRP
28
[Flussdiagramm der Funktionsauswahl]
[1] Stoppen Sie die Klimaanlage, um den Funktionsauswahlmodus der Fernbedienung zu starten → [2] Wählen Sie aus Eintrag 1 aus. → [3] Wählen Sie aus
Eintrag 2 aus. → [4] Nehmen Sie die Einstellung vor. (Einzelheiten werden in Eintrag 3 angegeben) → [5] Einstellung abgeschlossen. → [6] Umschaltung der
Anzeige auf Normalbetrieb. (Ende)
Normalbetriebsanzeige (Anzeige
bei deaktivierter Klimaanlage)
(Halten Sie die Taste E gedrückt und drücken Sie Taste
zwei Sekunden lang.)
* Die Anzeige lässt sich während der Funktionsauswahl,
Eintrag 1
Sprache ändern
(“CHANGE LANGUAGE”)
Drücken Sie
Taste E.
Funktionsgrenzen
(“Funktion
auswahlen”)
Drücken Sie
Taste E.
Drücken Sie
Taste E.
Auswahl der
Betriebsart
(“Betriebsart
wahlen”)
Drücken Sie
Taste E.
Änderung der
Anzeige
(“Anzeige
betriebsart”)
des Testlaufs und der Selbstdiagnose nicht ändern.
Funktionsauswahlmodus der
Drücken Sie Taste G.
→
Drücken Sie
Taste G.
→
Drücken Sie
Taste G.
Drücken Sie
Taste G.
→
Einstellung der Funktionsgrenzen bei der Bedienung (“Sperr-Funktion”)
Einstellung der Benutzung der Betriebsart Automatisch (“Auswahl autobetrieb”)
Einstellung der Temperaturgrenzen (“Limit temp Funktion”)
*
Verwendung der automatischen Filteranheberpanel Auf/Ab-Betriebsmodus-Einstellung
[ ]
*
Verwendung der Festluftstromrichtungsmodus-Einstellung
[ ]
Haupt-/Nebenfunktion der Fernbedienung (“Haupt/Neben controller”)
Benutzung der Uhreinstellung (“Uhr”)
Einstellung der Timer-Funktion (“Wochenzeit schalt uhr”)
Kontaktnummer für den Fall von Fehlfunktionen (“CALL.”)
Temperatureinstellung in °C/°F (“Wechsel °C/°F”)
Einstellung der Anzeige der Luftansaugtemperatur (“Raum TEMP gewahlt”)
Einstellung der automatischen Kühl-/Heizanzeige (“Auto Betrieb C/H”)
Fernbedienung
Eintrag 2
→
→
→
→
→→→→→
D
(Halten Sie die Taste E gedrückt und drükken Sie Taste D zwei Sekunden lang.)
* Die Fernbedienung speichert die
vorgenommenen Änderungen.
Drücken Sie Taste G.
Drücken Sie Taste G.
Drücken Sie Taste G.
Drücken Sie
Taste D.
Drücken Sie
Taste D.
Drücken Sie
Taste D.
Siehe [4]-1
Eintrag 3 (Inhalt
der Einstellungen)
Siehe [4]-2. (1)
Siehe [4]-2. (2)
Siehe [4]-2. (3)
Siehe [4]-3. (1)
Siehe [4]-3. (2)
Siehe [4]-3. (3)
Siehe [4]-3. (4)
Siehe [4]-4. (1)
Siehe [4]-4. (2)
Siehe [4]-4. (3)
HINWEIS
Der Timer-Betrieb stoppt, wenn die Anzeige des
Funktionsauswahlmodus auf die Normalbetriebsanzeige umschaltet.
Punktmatrixanzeige
Die mit CHANGE LANGUAGE
(Sprache einstellen) eingestellte
Sprache wird hier angezeigt. In den
Darstellungen dieser Anleitung ist
Englisch ausgewählt.
F
TEMP.
MENU
BACKDAY
MONITOR/SET
CLOCK
C
ON/OFF
E
PAR-21MAA
G
OPERATION
D
ON/OFF
FILTER
CHECK
CLEAR
TEST
I
A
GB
B
H
D
* Dieses Modell ist nicht mit dieser Funktion ausgestattet. Die Einstellung ist ungültig.
[Genaue Einstellung]
[4] -1. Einstellung CHANGE LANGUAGE (Sprache ändern)
Die Sprache des Punktmatrix-Displays kann eingestellt werden.
[4] -2. Funktionsgrenzen
(1) Einstellung der Funktionsgrenzen bei der Bedienung (Operation Lock)
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 no1: Die Einstellung der Bedienungssperre (Operation Lock) gilt für alle Tasten
außer der [
ON/OFF]-Taste.
2 no2: Die Einstellung der Bedienungssperre gilt für alle Tasten.
3 OFF (Anfängliche Einstellungswert):
Die Einstellung der Bedienungssperre wird nicht vorgenommen.
* Damit die Bedienungssperre (Operation Lock) in der normalen Anzeige gültig
ist, müssen Sie die [FILTER]-Taste gedrückt halten und währenddessen die Taste [
ON/OFF] zwei Sekunden lang drücken, nachdem Sie die obige Einstel-
lung durchgeführt haben.
(2) Einstellung der Benutzung der Betriebsart Automatisch
Wenn die Fernbedienung an einem Anlage angeschlossen ist, bei dem ein automatischer Betrieb möglich ist, können die folgenden Einstellungen vorgenommen
werden.
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 ON (Anfängliche Einstellungswert):
Die Betriebsart Automatisch wird angezeigt, wenn diese Betriebsart ausgewählt wird.
2 OFF:
Die Betriebsart Automatisch wird nicht angezeigt, wenn diese Betriebsart ausgewählt wird.
(3) Einstellung der Temperaturgrenzen
Nach dieser Einstellung kann die Temperatur im eingestellten Bereich verändert werden.
• Zur Umschaltung der Einstellung drücken Sie die Taste [ON/OFF].1 Limit Kuhl Temp:
Der Temperaturbereich kann in der Betriebsart Kühlen/Trocknen geändert werden.
2 Limit Heiz Temp:
Der Temperaturbereich kann in der Betriebsart Heizen geändert werden.
3 Limit Auto Temp:
Der Temperaturbereich kann in der Betriebsart Automatisch geändert werden.
4 OFF (Anfangseinstellung):
Die Temperaturbereichsgrenzen sind nicht aktiv.
* Wenn eine andere Einstellung als OFF gewählt wird, werden die Temperatur-
bereichsgrenzen für Kühlen, Heizen und automatischen Betrieb gleichzeitig eingestellt. Der Bereich kann jedoch nicht begrenzt werden, wenn der eingestellte
Temperaturbereich sich nicht geändert hat.
• Um die Temperatur zu erhöhen oder zu verringern, drücken Sie die Taste
[
TEMP ( ) oder ( )].
• Um die Obergrenze und die Untergrenze einzustellen, drücken Sie die Taste
[
] (Gebläsegeschwindigkeit). Die ausgewählte Einstellung blinkt, und die
Temperatur kann eingestellt werden.
• Einstellbarer Bereich
Betriebsart Kühlen/Trocknen: Untergrenze: 19°C bis 30°C Obergrenze: 30°C bis 19°C
Betriebsart Heizen:Untergrenze: 17°C bis 28°C Obergrenze: 28°C bis 17°C
Betriebsart Automatisch:Untergrenze: 19°C bis 28°C Obergrenze: 28°C bis 19°C
* Der einstellbare Bereich hängt vom angeschlossenen Anlage ab (Mr.-Slim-An-
lage, Free-Plan-Anlage und Zwischentemperaturanlage).
[4] -3. Einstellen der Auswahl der Betriebsart
(1) Haupt-/Nebenfunktion der Fernbedienung
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 Haupt: Die Fernbedienung fungiert als Hauptfernbedienung.
2 Neben: Die Fernbedienung fungiert als Nebenfernbedienung.
(2) Benutzung der Uhreinstellung
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 ON : Die Clock-Funktion kann benutzt werden.
2 OFF : Die Clock-Funktion kann nicht benutzt werden.
(3) Einstellung der Timer-Funktion
• Zur Umschaltung der Einstellung drücken Sie die Taste [
2 Auto Zeit funktion Aus: Der Auto-Off-Timer kann benutzt werden.
3 Einfnche zeit funktion: Der einfache Timer kann benutzt werden.
4 Zeitschaltuhr Aus:Der Timer-Modus kann nicht benutzt werden.
* Wenn die Verwendung der Clock-Einstellung auf OFF steht, kann “Wochenzeit
schalt uhr” nicht benutzt werden.
(4) Kontaktnummer für den Fall von Fehlfunktionen
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 CALL OFF:Die eingestellten Kontaktnummern werden im Falle von Fehl-
funktionen nicht angezeigt.
2 CALL **** *** **** : Die eingestellten Kontaktnummern werden im Falle von Fehl-
funktionen angezeigt.
CALL_:Die Kontaktnummer kann eingegeben werden, wenn das
Display so aussieht wie links gezeigt.
DKSWNLIEF
RUTRGRP
29
• Eingabe der Kontaktnummern
Zur Eingabe der Kontaktnummern gehen Sie wie folgt vor.
Bewegen Sie den blinkenden Cursor auf die eingestellten Nummern. Drücken Sie
die Taste [
Drücken Sie die Taste [
TEMP. ( ) Und ( )] um den Cursor nach rechts (links) zu bewegen.
CLOCK ( ) Und ( )] um die Nummern einzustellen.
[4] -4. Einstellung der Anzeige
(1) Temperatureinstellung in °C/°F
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 °C: Für die Temperatur wird die Anlage Celsius °C verwendet.
(2) Einstellung der Anzeige der Luftansaugtemperatur
• Zur Umschaltung der Einstellung drücken Sie die Taste [
ON/OFF].
1 ON: Die Temperatur der Ansaugluft wird angezeigt.
2 OFF: Die Temperatur der Ansaugluft wird nicht angezeigt.
(3) Einstellung der automatischen Kühl-/Heizanzeige
• Zur Umschaltung der Einstellung drücken Sie die Taste [
1 ON:
Entweder “Automatic cooling” (Automatisches Kühlen) oder “Automatic heating”
ON/OFF].
(Automatisches Heizen) wird in der Betriebsart Automatisch angezeigt.
2 OFF: Nur “Automatic” wird in der Betriebsart Automatisch angezeigt.
2 °F: Für die Temperatur wird die Anlage Fahrenheit °F verwendet.
(2) Anlagenfunktionsauswahl
Stellen Sie, wenn erforderlich, die Funktionen jeder Innenanlage von der Fernbedienung aus ein. Die Funktionen jeder Innenanlage können nur an der Fernbedienung eingestellt werden.
Stellen Sie die Funktionen durch Wahl der notwendigen Positionen aus Tabelle 1 und Tabelle 2 ein. (Standardeinstellungen sind unten ebenfalls dargestellt.)
Tabelle 1. In Einzelpunkten aufgeführte Funktionen des gesamten Kältemittelsystems (wählen Sie Anlage Nummer 00 bis 15)
Automatische
Wiederherstellung
nach Netzstromausfall
Erkennung der
Innentemperatur
GB
LOSSNAYVerbindung
Netzstrom
D
Funktion
Nicht verfügbar
Verfügbar
Betriebsdurchschnitt der Anlage
Einstellung durch Fernbedienung der Anlage
Interner Sensor der Fernbedienung
Nicht unterstützt
Unterstützt (Anlage nicht mit Außen-Lufteinlaß ausgestattet)
Unterstützt (Anlage mit Außen-Lufteinlaß ausgestattet)
240 V
220 V, 230 V
Einstellungen
Betriebsart Nr.
01
022
032
04
Einstellung Nr.
1
2
1
3
1
3
1
2
Prüfen
Standardeinstellungen
Etwa 4 Minuten nach dem Wiederherstellen des Netzstroms warten.
Bemerkungen
Tabelle 2. In Einzelpunkten aufgeführte Funktionen der Innenanlage (wählen Sie die Anlagenummern 01 bis 04 oder AL)
Funktion
Filterzeichen
Gebläsebetrieb bei
Thermo aus im
Heizbetrieb
Gebläsebetrieb
während ausgeschalteter Heizung
im Kühlbetrieb
100 Std.
Einstellungen
2500 Std.
Keine Filterzeichenanzeige
Betrieb (Zuletzt eingestellte Gebläsegeschwindigkeit)
Stop
Betrieb (niedrige Geschwindigkeit)
Betrieb (Zuletzt eingestellte Gebläsegeschwindigkeit)
Stop
Betriebsart Nr.
072
25
27
Einstellung Nr.
1
3
3
2
1
1
2
Prüfen
Standardeinstellungen
(PEA-400/500)
Beim Wählen des Gebläsebetriebs“Stopp” stellen Sie die Einstell-
(PEA-200/250)
nummer von Betriebsart Nr. “02” in
Tabelle 1 to “3”. Stellen Sie sicher,
daß sich die Fernbedienung innerhalb des zu klimatisierenden Raums
befindet, so daß sie die Raumtemperatur überwachen kann.
Bemerkungen
Hinweis:
Wenn die Funktionen der Innenanlage nach abgeschlossener Installation mit der Funktionswahl geändert worden sind, geben Sie stets durch Eingabe von 嘷
oder einer anderen Kennzeichnung im zugehörigen Prüffeld von Tabelle 1 oder Tabelle 2 den Inhalt der Einstellungen an.
[Funktion Auswahlablauf]
Sehen Sie sich zuerst den Funktionsablauf an. Als Beispiel wird nachfolgend die Einstellung der “Netzstrom” in Tabelle 1 gezeigt.
(Den aktuellen Einstellvorgang sehen Sie in [Einstellverfahren] 1 bis 0.)
1 Prüfung der Inhalte der Funktionsauswahl.
2 Schalten Sie in den FUNKTIONSAUSWAHL-Betrieb.
(Drücken Sie gleichzeitig im AUS-Status der Fernbedienung die Tasten A und B.)