Mitsubishi Electric PEAD-A24, PEAD-30, PEAD-42AA, PEAD-36 Installation Manual

Air-Conditioners
PEAD-A24,30,36,42AA
FOR INSTALLER
INSTALLATION MANUAL
For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
FOR INSTALLER
English
Veuillez lire le manuel d’installation en entier avant d’installer ce climatiseur pour éviter tout accident et vous assurer d’une utilisation correcte.
POUR L’INSTALLATEUR
Français
2
3
[Fig. 3-1]
4
[Fig. 4-1]
C
D
C
E
D
A Unit body B Lifting machine
5
[Fig. 5-1] [Fig. 5-2] [Fig. 5-3]
A Center of gravity
A Indoor unit’s bottom surface
5.25.1
A Access door B Electrical parts box C Air inlet D Air outlet E Ceiling surface F Service space (viewed from the side) G Service space (viewed from the direction of arrow)
1 600 mm [23-5/8 in] or more 2 100 mm [3-15/16 in] or more 3 10 mm [7/16 in] or more 4 300 mm [11-13/16 in] or more
YX
LW
A
Z
C Nuts (field supply) D Washers (accessory) E M10 hanging bolt (field supply)
B
C
D
A
F
G
3
4
E
A
C B A
D
C
E
1
2
50~150[2~5-15/16] 450[17-3/4]
450[17-
3
/
4
]
49[1-
15
/
16
]
625[24-
5
/
8
]
777[30-
5
/
8
]
20[13/16]
100[3-
15
/16]
23 [15/16]
250[9-
7
/
8
]
B
A
Model PEAD-A24, 30AA PEAD-A36, 42AA
A
1100 [43-5/16]
1400 [55-1/8]
B
1154 [45-7/16]
1454 [57-1/4]
C
1200 [47-1/4]
1500 [59-1/16]
D 1060 [41-23/32] 1360 [53-17/32]
E
1200 [47-1/4]
1500 [59-1/16]
(Unit: mm [in])
4.1
3.1
A
(Unit: mm [in])
3
6
øB
øA
a
b
[Fig. 6-1]
a Indoor unit b Outdoor unit
a
dcbef
90°
d
c
b
a
b
a
a
b
e
b
c
d
c
A
c
b
a
defg h
i
[Fig. 6-9]
A Pipe cover (small) (accessory) B Caution:
Pull out the thermal insulation on the refrigerant piping at the site, insert the flare nut to flare the end, and replace the insu­lation in its original position. Take care to ensure that condensation does not form on ex­posed copper piping.
C Liquid end of refrigerant piping
D Gas end of refrigerant piping E Site refrigerant piping F Main body G Pipe cover (large) (accessory) H Thermal insulation (field supply) I Pull J Flare nut K Return to original position
A
B
C
D
F
G
E
H
H
K
L
J
I
J
O
O
N
N
20
[25/32]
20
[25/32]
20
[25/32]
20
[25/32]
[Fig. 6-3]
[Fig. 6-6]
[Fig. 6-4] [Fig. 6-5]
a Flare nut b Copper tube
a Burr b Copper tube/pipe
c Spare reamer d Pipe cutter
[Fig. 6-7]
[Fig. 6-8]
a Flaring tool b Die c Copper tube
d Flare nut e Yo ke
a Smooth all around b Inside is shining without
any scratches
c Even length all around
d Too much e Tilted f Scratch on
flared plane
g Cracked h Uneven i Bad examples
L Ensure that there is no gap here M Plate on main body N Band (accessory) O Ensure that there is no gap here. Place join upwards.
6.1
6.2
a Copper tubes b Good
c No good d Tilted
e Uneven f Burred
6.3
Model
PEAD-A24, 30, 36, 42AA
A
ø15.88 [5/8]Bø9.52 [3/8]
(Unit: mm [in])
4
[Fig. 6-10]
Correct piping Wrong piping
A Insulation (9 mm [3/8 in] or more) B Downward slope (1/100 or more) C Support metal K Air bleeder L Raised M Odor trap
Grouped piping
D O. D. ø32 mm [1-1/4 in] PVC TUBE E Make it as large as possible. About 10 cm [3-15/16 in]. F Indoor unit G Make the piping size large for grouped piping. H Downward slope (1/100 or more) I O. D. ø38 mm [1-1/2 in] PVC TUBE for grouped piping.
(9 mm [3/8 in] or more insulation)
J Up to 550 mm [21-11/16 in] N Drain hose (accessory) O Horizontal or slightly upgradient
[Fig. 6-11]
C
B
A
L
D
D
D
E
K
M
B
H
I
Max. 20m [65ft]
1.5-2m [5-7ft]
G
F
FF
A Indoor unit B Tie band (accessory) C Visible part D Insertion margin E Drain hose (accessory) F Drain pipe (O.D. ø32 mm [1-1/4 in] PVC TUBE, field supply) G Insulating material (field supply) H Tie band (accessory) I To be gap free. The joint section of the insulation material meet must be at the top.
6
6.5
[Fig. 6-12]
A Insert pump's end 2 to 4 cm [13/16 to 1-5/8 in]. B Remove the water supply port. C About 2500 cc D Water E Filling port F Screw
A
B
F
C
D
E
B
J
O
N
F
Max. 300mm [11-13/16in]
I
B
CD D
G
F
E
H
A
32
[1-
1
/4]
35
[1-
7
/16]
25 [1]
(Unit: mm [in])
5
8
[Fig. 8-1]
8.1
7
7.1
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords F Remote controller G Indoor unit
S1
S2
L1 L2 G
1 2
S1
S2
S3
S3
AB C
D
E
F
G
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords F Remote controller G Indoor unit
S1
S2
1 2
S1
S2
S3
1 2
S1
S2
S3
S3
1 2
S1
S2
S3
1 2
S1
S2
S3
ABC
D
E
F
GGGG
L1 L2
G
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply
S1 S2
1 2
S1 S2 S3
S3
A
CB
D
JEB
C
F
G
H
L1 L2
G
L1 L2
G
A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords F Remote controller G Indoor unit H Option J Indoor unit power supply
S1 S2
1 2
S1 S2 S3
1 2
S1 S2 S3
1 2
S1 S2 S3
1 2
S1 S2 S3
S3
ABC
D
E
JBC
F
H
GGGG
L1 L2
G
L1 L2 G
L1 L2 G
L1 L2 G
L1 L2 G
[Fig. 8-2]
[Fig. 8-3] [Fig. 8-4]
[Fig. 7-1]
[Fig. 7-2]
[Fig. 7-3]
[Fig. 7-4]
Duct
Air inlet
Access door
Canvas duct
Ceiling surface
Air outlet
Leave distance enough to pre­vent short cycle
<A> In case of rear inlet
A
B
G
F
A
A B C D E F G
D
CE
<B> In case of bottom inlet
A
B
G
C
E
A
F
D
A
B
A Filter B Bottom plate
C
D
6
8.2
F Use PG bushing to keep the weight of the cable and external force from being applied to
the power supply terminal connector. Use a cable tie to secure the cable.
G Power source wiring H Use ordinary bushing I Transmission wiring J Conduit K Side frame L Knockout hole (for power source wiring) M Washer (accessory)
N Ter minal block for power source and indoor transmission O Ter minal block for remote controller
[Fig. 8-2-3] [Fig. 8-2-4]
C Ter minal box D Knockout hole E Remove
A Screw holding cover (1pc) B Cover
[Fig. 8-2-1]
[Fig. 8-2-2]
8
A
B
D
E
C
H
I
J
G
F
O
N
L
K
J
M
7
A For installation in the switch box: B For direct installation on the wall select one of the following:
• Prepare a hole through the wall to pass the remote controller cord (in order to run the remote controller cord from the back), then seal the hole with putty.
• Run the remote controller cord through the cut-out upper case, then seal the cut-out notch with putty similarly as above.
C Wall D Conduit E Lock nut F Bushing G Switch box H Remote controller cord I Seal with putty J Wood screw
F
A
H
C
D
E
G
I
I
I
H
B
J
H
B-1. B-2.
[Fig. 8-5]
8
A
AB TB6
B
A To the ter minal block on the indoor unit B TB6 (No polarity)
[Fig. 8-6]
8.2
46 [1-13/16]
30
[1-3/16]
120 [4-3/4]
83.5 [3-5/16]
A
B
C
30
[1-3/16]
30
[1-3/16]
A Remote controller profile B Required clearances surrounding the remote controller C Installation pitch
[Fig. 8-4]
[Fig. 8-3]
A Indoor terminal block B Earth wire (green/yellow) C Indoor/outdoor unit connecting wire 3-
core 1.5 mm
2
[AWG 16] or more
D Outdoor terminal block 1 Connecting cable
Cable 3-core 1.5 mm
2
[AWG 16], in con-
formity with Design 245 IEC 57.
2 Indoor terminal block 3 Outdoor terminal block
A Indoor terminal block
4 Always install an earth wire (1-core 1.5 mm
2
[AWG 16]) longer than other cables
5 Remote controller cable
Wire No × size (mm
2
) : Cable 2C × 0.3 This wire accessory of remote controller (wire length : 10 m [32 ft], non-polar. Max. 500 m [1640 ft])
6 Wired remote controller
C Indoor/outdoor unit
connecting wire 3-core 1.5 mm
2
[AWG 16] or more
D Outdoor terminal block
B Earth wire (green/yellow)
8.3
12
6
5
2
4
3
1
(Unit: mm [in])
8
A
B
C
D
E
G
H
F
A Signal receiving unit external B Center of Switch box C Switch box D Installation pitch E 6.5 mm (1/4 inch) F 70 mm (2 - 3/4 inch) G 83.5 ± 0.4 mm (3 - 9/32 inch) H Protrusion (pillar, etc)
[Fig. 8-9]
A
B
C
A Remote controller wire B Hole (drill a hole on the ceiling to pass the remote controller wire.) C Signal Receiving Unit
Ceiling cassette type, Ceiling concealed type
[Fig. 8-10]
A
B
C
A Fix tightly with tape. B Remote controller wire C Order wire
Indoor unit
[Fig. 8-8]
[Fig. 8-11]
H
J
I
When using the switch box
When installing directly on the wall
A 150 mm (5 - 15/16 inch) B Remote controller wire (Accessory) C Wiring pipe D Locknut
H Seal around here with putty I Remote controller wire J Seal around here with putty
E Bushing F Switch box G Seal around here with putty
C
D
B
F
E
G
A
Wall
8
8.4
IC
OC(00)
CN90
TB1
TB4
1
D
C
A
B
Standard 1:1
[Fig. 8-7]
A Outdoor unit B Refrigerant address C Indoor unit D Signal receiving unit
Indoor/outdoor wiring
Signal receiving unit wiring
9
8
8.4
[Fig. 8-12]
[Fig. 8-13]
AB
C
D
A Thin-wall portion B Bottom case C Remote controller wire D Conducting wire
[Fig. 8-14]
A
A Screw (M4 x 30)
* When installing the lower case directly on the wall or the ceiling,
use wood screws.
Insert the minus screwdriver toward the arrow pointed and wrench it to remove the cover. A flat screwdriver whose width of blade is between 4 and 7mm (5/32 - 9/32inch) must be used.
[Fig. 8-15]
1
1
2
A
1 Hang the cover to the upper hooks (2 places). 2 Mount the cover to the lower case
A Cross-section of upper hooks
10
8
8.4
[Fig. 8-16]
IC IC IC IC
CN90 CN90 CN90 CN90
Pair number: 0
[Fig. 8-17]
IC
CN90
IC
CN90
Pair number: 0 Pair number: 0
Pair number: 0 Pair number: 0
IC IC IC IC
CN90 CN90 CN90 CN90
[Fig. 8-19]
[Fig. 8-18]
Pair number: 0 Pair number: 1 Pair number: 2 Pair number: 3
Pair number: 0 Pair number: 1 Pair number: 2 Pair number: 3
Pair number: 0 Pair number: 0 Pair number: 0 Pair number: 0
A
CN2A
CN3C
SW2
SW1
JP1
JP2
JP3
JP41
JP42
CN22
CN2L
CNXA2
CN32
SWE
CN20
CN90
CN105
CN41
CN4F
CN51
CNXB2
CNXC2
CN44
ON
OFF
<Indoor controller board>
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
CHECK
2,4
3
A
[Fig. 8-20]
11
9
[Fig. 9-1] [Fig. 9-2]
9.2
A ON/OFF button B Test run display C Indoor temperature liquid line
temperature display
D ON/OFF lamp E Power display
A CHECK button B Refrigerant address C TEMP. button D IC: Indoor unit
OC: Outdoor unit
E Check code
F Error code display
Test run remaining time display
G Set temperature button H Mode selection button I Fan speed button M TEST button
8
8.5
[Fig. 8-21]
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
A B
DC
G
E
F
4
1
213 4
1 2
A Filter button (<Enter> button) B TEST button C Set Time button D Timer On/Off button (Set Day button) E Mode selection button F Set temperature button G Timer Menu button (Monitor/Set button)
Mode numberSetting numberRefrigerant addressUnit number
1
2
3
4
3
12
CHECK CHECK
CHECKCHECK
4
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
CHECK
E
F
D
C
A B
A Hour button B Minute button C TEMP button D TEMP button E ON/OFF button F CHECK button
[Fig.8-22]
[Fig. 9-3]
A TEST RUN button B MODE button C FAN button D VANE button
9.3
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
TEST RUN
B
A
C D
˚F
˚F
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN COOL, HEAT
A
FCEDB
MIH G
˚C
˚F
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK DAY
MONITOR/SET
CLOCK
ON/OFF
B
C
A
E D
Loading...
+ 25 hidden pages