SUBMITTAL DATA: PEAD-A18AA7 & SUZ-KA18NA2
18,000 BTU/H HORIZONT
Job Name:
System Reference: Date:
AL-DUCTED HEAT PUMP SYSTEM
Indoor Unit:
PEAD-A18AA7
Outdoor Unit:
SUZ-KA18NA2
INDOOR UNIT FEATURES
Unobtrusive ceiling-concealed design for short-run ductwork.
•
• Wide ranging external static pressure (0.14-0.60 in. WG)
• Built-in condensate lift mechanism (up to 27-9/16")
• Auto fan speed mode
• Optional FB Series filter boxes for easy access and service
• Ideal for residential homes,retail shopping centers, larger classrooms, office complexes, conference ballrooms, fitness centers, and more
OUTDOOR UNIT FEATURES
• Variable speed INVERTER-driven compressor
• Innovative Joint Lap DC Motor leads to high efficiency and reliability
• Pulse Amplitude Modulation technology
• High-performance grooved piping for increased heat exchange efficiency
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Cooling at 95°F
Cooling at 82°F
Heating at 47°F
Heating at 17°F
Heating at 5°F
Heating at -4°F
Efficiency
Electrical
SPECIFICATIONS: PEAD-A18AA7 & SUZ-KA18NA2
Maximum Capacity BTU/H 18,000
Rated Capacity BTU/H 18,000
Minimum Capacity BTU/H 6,200
1
2
3
4
5
Maximum Power Input W 1,270
Rated Power Input W 1,270
Moisture Removal Pints/h 3.2
Sensible Heat Factor 0.8
Power Factor (208/230V) % 96
Maximum Capacity BTU/H 18,400
Rated Capacity BTU/H 18,400
Minimum Capacity BTU/H 6,800
Maximum Power Input W 1,090
Rated Power Input W 1,090
Maximum Capacity BTU/H 25,600
Rated Capacity BTU/H 21,600
Minimum Capacity BTU/H 8,120
Maximum Power Input W 2,140
Rated Power Input W 1,600
Power Factor % 97
Maximum Capacity BTU/H 1,4000
Rated Capacity BTU/H 14,000
Maximum Power Input W 1,440
Rated Power Input W 1,440
Maximum Capacity BTU/H 12,000
Maximum Power Input W 1,230
Maximum Capacity BTU/H 8,900
SEER 19.8
1
EER
14.1
HSPF (IV) 12.9
COP at 47°F
COP at 17°F in Maximum Capacity
COP at 5°F in Maximum Capacity
ENERGY STAR® certified units (ENERGY ST
2
3
4
AR products are third-party certified
3.90
2.80
2.85
Yes
by an EPA-recognized Certification Body.)
Voltage, Phase, Frequency 208/230V, 1 phase, 60Hz
Guaranteed Voltage Range V AC 187-253
Voltage: Indoor - Outdoor, S1-S2 V AC 208/230
Voltage: Indoor - Outdoor, S2-S3 V DC 24
Short-circuit Current Rating (SCCR) kA 5
Recommended Fuse/Breaker Size (Outdoor) A 15
Recommended Wire Size (Indoor - Outdoor) AWG 14
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Indoor Unit
Indoor Unit Operating
emperature Range
T
Outdoor Unit
SPECIFICATIONS: PEAD-A18AA7 & SUZ-KA18NA2
MCA A 1.69
Fan Motor Full Load Amperage A 1.35
Fan Motor Output W 85
Airflow Rate at Cooling, Dry CFM 600-512-424
Airflow Rate at Cooling, Wet CFM 540-461-382
Sound Pressure Level (Cooling) dB(A) 37-33-30
Sound Pressure Level (Heating) dB(A) 37-33-30
External Static Pressure in.WG 0.14-0.20-0.28-0.40-0.60
Drain Pipe Size In. (mm) 1-1/4 (32)
Condensate Lift Mechanism, Maximum Distance In. (mm) 27-9/16 (700)
Heat Exchanger Type Plate fin coil
External Finish Color Galvanized
W: In. (mm) 35-7/16 (900)
Unit Dimensions
Package Dimensions
Unit Weight Lbs. (kg) 62 (28)
Package Weight Lbs. (kg) 71 (32)
Cooling Intake Air Temp (Maximum / Minimum)* °F 90F D.B / 71F W.B // 67F D.B / 57F W.B
Heating Intake Air Temp (Maximum / Minimum) °F 80F D.B // 70F D.B
MCA A 14
MOCP A 24
Fan Motor Full Load Amperage A 0.67
Fan Motor Output W 77
Airflow Rate CFM 1,691 / 1,691
Refrigerant Control LEV
Defrost Method Reverse cycle
Heat Exchanger Type Plate fin coil
Sound Pressure Level, Cooling
Sound Pressure Level, Heating
Compressor Type DC INVERTER-driven Twin Rotary
Compressor Model SNB130FQBMT
Compressor Rated Load Amps A 10.0
Compressor Locked Rotor Amps A 12.5
Compressor Oil Type // Charge oz. FV50S//11.8
External Finish Color Ivory Munsell 3Y 7.8/1.1
Base Pan Heater Optional
Unit Dimensions
1
2
D: In. (mm) 28-7/8 (732)
H: In. (mm) 9-7/8 (250)
W: In. (mm) 45-5/16 (1,150)
D: In. (mm) 34-11/16 (880)
H: In. (mm) 13-7/16 (380)
dB(A) 54
dB(A) 55
W: In. (mm) 33-1/16 (840)
D: In. (mm) 13 (330)
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Outdoor Unit Operating
emperature Range
T
Refrigerant
Piping
SPECIFICATIONS: PEAD-A18AA7 & SUZ-KA18NA2
H: In. (mm) 34-5/8 (880)
W: In. (mm) 38-9/16 (980)
Package Dimensions
Unit Weight Lbs. (kg) 127 (58)
Package Weight Lbs. (kg) 145 (66)
Cooling Air Temp (Maximum / Minimum)* °F 115 / 14
Cooling Thermal Lock-out / Re-start Temperatures** °F -1 / 3
Heating Air Temp (Maximum / Minimum) °F 75 / -4
Heating Thermal Lock-out / Re-start Temperatures** °F -9 / -4
Type R410A
Charge Lbs, oz 3, 9
Gas Pipe Size O.D. (Flared) In.(mm) 1/2 (12.7)
Liquid Pipe Size O.D. (Flared) In.(mm) 1/4 (6.35)
Maximum Piping Length Ft. (m) 100
Maximum Height Difference Ft. (m) 50
Maximum Number of Bends 10
D: In. (mm) 16-9/16 (420)
H: In. (mm) 39 (990)
Notes
1
AHRI Rated Conditions
(Rated data is
determined at a fixed
compressor speed)
Conditions
Cooling (Indoor // Outdoor) °F 80 DB, 67 WB // 95 DB, 75 WB
2
Heating at 47°F (Indoor // Outdoor) °F 70 DB, 60 WB // 47 DB, 43 WB
3
Heating at 17°F (Indoor // Outdoor) °F 70 DB, 60 WB // 17 DB, 15 WB
4
Heating at 5°F (Indoor // Outdoor) °F 70 DB, 60 WB // 5 DB, 4 WB
5
Heating at -4°F (Indoor // Outdoor) °F 70 DB, 60 WB // -4 DB, -5 WB
*Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures.
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
ACCESSORIES: PEAD-A18AA7
Filter Box with MERV 13 Filters □ FBM2-2-A
Wireless Signal Receiver □ PAR-SA9CA-E
Wireless Signal Receiver □ PAR-FA32MA-W
Wireless Signal Receiver □ PAR-FA32MA-E
Wireless Remote Controller □ PAR-FL32MA-E
kumo touch™ RedLINK™ Wireless Controller □ MHK2
Deluxe MA Remote Controller □ PAR-40MAAU
Simple MA Controller □ PAC-YT53CRAU-J
Touch MA Controller □ PAR-CT01MAU-SB
Airzone ZBS Wired Blueface Principal Controller White □ AZZBSBLUEFACECB
Airzone ZBS Wired Think Controller White □ AZZBSTHINKCB
Airzone ZBS Wireless Think Controller White □ AZZBSTHINKRB
Airzone ZBS Wired Lite Controller White □ AZZBSLITECB
Airzone ZBS Wireless Lite Controller White □ AZZBSLITERB
Wired Remote Sensor □ PAC-SE41TS-E
Wireless Temperature and Humidity Sensor □ PAC-USWHS003-TH-1
Flush Mount Remote Temperature Sensor □ PAC-USSEN001-FM-1
Wireless Interface 2 □ PAC-USWHS002-WF-2
Thermostat Interface □ PAC-US444CN-1
kumo station
USNAP Interface □ PAC-WHS01UP-E
IT Extender □ PAC-WHS01IE-E
BACnet® and MODBUS® Interface □ PAC-UKPRC001-CN-1
External Fan / Heater Control Relay Adapter □ CN24RELAY-KIT-CM3
Connector cable for remote display □ PAC-SA88HA-EP
Connector for CN32 (remote on/off) □ PAC-SE55RA-E
Lockdown Bracket for Hand-held Remote Controllers □ RCMKP1CB
Remote Operation Adapter
Blue Diamond Sensor Extension Cable — 15 Ft. □ C13-103
MegaBlue Advanced Blue Diamond Condensate Pump w/ Reservoir & Sensor □ X87-835 - 110 to 250V
Advanced Blue Diamond Mini Condensate Pump w/ Reservoir & Sensor (208/230V) [recommended] □ X87-721 - 208/230V
(30A/600V/UL) [fits 2" X 4" utility box] - Black □ TAZ-MS303
(30A/600V/UL) [fits 2" X 4" utility box] - White □ TAZ-MS303W
1
Unable to use with wireless remote controller
®
1
□ PAC-WHS01HC-E
□ PAC-SF40RM-E
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
ACCESSORIES: SUZ-KA18NA2
Air Outlet Guide □ MAC-886SG-E
Optional Defrost Heater □ MAC-642BH-U1
Hail Guard □ HG-A7
Outdoor Unit 3-1/4 inch Mounting Base (Pair) - Plastic □ DSD-400P
Condensing Unit Mounting Pad 16" x 36" x 3" □ ULTRILITE1
Outdoor Unit Stand — 12" High □ QSMS1201M
Outdoor Unit Stand — 18" High □ QSMS1801M
Outdoor Unit Stand — 24" High □ QSMS2401M
Heavy Duty Wall Mounting Bracket— Coated Steel □ QSWB2000M-1
Heavy Duty Wall Mounting Bracket — 316 Series Stainless Steel □ QSWBSS
15' x 1/4" x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-15
30' x 1/4" x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-30
50' x 1/4" x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-50
65' x 1/4" x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-65
100' x 1/4" x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MLS141212T-100
10' x 3/8" x 10' x 5/8" Lineset (Twin-Tube Insulation) □ MPLS385812T-10
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
200(7-7/8)
120°
120°
ø125
135
378(14-15/16) 153(6-1/16)
B(Suspension bolt pitch) 23(15/16)
C
A
40(1-5/8)
15(5/8)
40(1-5/8)
H±3(H±1/8)
J±3(J±1/8)
58(2-5/16)
20(13/16) D(Duct)
30(1-3/16) 100(3-15/16)X(E-1)=F
100(3-15/16)
10(7/16)
57(2-1/4)
643(25-3/8)
18(3/4) 210(8-5/16)
21(7/8)
G
732(28-7/8)
32(1-5/16)
700(27-9/16)
238(9-3/8)
10(7/16)
33(1-5/16)
40(1-5/8)
100(3-15/16)
122(4-13/16)
178(7-1/16)
136 67
356(14-1/16)
217(8-9/16)
41(1-5/8)
250(9-7/8)
23(15/16)
(4-15/16)
(5-3/8)
3-ø2.9(1/8) mount hole
Drain pipe(O.D ø32(1-1/4)
Fresh air intake ø100(3-15/16)
knock out hole
2XE-ø2.9(1/8)
(Suspension bolt pitch)
Air filter
Drain pipe
(Integral lift pump outlet)
Drain pump
(DUCT)
2X2-ø2.9(1/8)
1 Refrigerant piping (gas)
(5-3/8)
(2-11/16)
(Emergency drain)
2 Refrigerant piping(liquid)
Drain pipe(O.Dø32(1-1/4))(Gravity drain)
Terminal block(Power source)
Terminal block(Transmission)
Note 4
Control box
(O.Dø32(1-1/4))
Top
Top
Bottom
view
Top
Bottom
Inlet air
side view
Outlet air
side view
Opposite piping
side view
Piping
side view
(43-5/16)
(55-1/8)
(45-7/16)
(57-1/4) (59-1/16) (53-9/16)
(47-1/4) (41-3/4) (39-3/8)
(51-3/16)
(41-11/16)
(53-1/2)
2Liquid pipe
1Gas pipe
1058
1358 1300
Model
1200
11
1060 1100 1154
1400
ø15.88
(5/8)
1454
1500
ø9.52
(3/8)
1360
14
1000
PEAD-A24,30AA7
PEAD-A36,42AA7
Unit:mm(in.)
Air
inlet
Air
outlet
Note 1.Use an M10 screw for the suspension bolt
(field supply).
2.Keep the service space for maintenance
at the bottom.
3.This drawing is for PEAD-A24·30·36·42
AA7 models,which have 2 fans. PEAD-A09·
12·15·18AA7 models have 1 fan.
4.If the inlet duct is used,remove the air
filter (supplied with the unit), then
install the filter (field supply) at the
suction side.
5.Heat air to 0°C (32°F) or higher when
taking fresh air with a fresh air intake.
PEAD-A24,30AA7
PEAD-A36,42AA7
PEAD-A12,15,
18AA7
Model A E D C B F
G
Unit:mm(in.)
(35-7/16) (37-9/16) (39-3/8) (33-7/8) (31-1/2) (33-13/16)
858
1000
9
860 900 954 800
PEAD-A09,12,
15,18AA7
ø12.7
(1/2)
ø6.35
(1/4)
(3-1/8)
78
H
(2-7/8)
72
J
66
(2-5/8)
62
(2-1/2)
PEAD-A09AA7
ø9.52
(3/8)
ø6.35
(1/4)
62
(2-1/2)
DIMENSIONS: PEAD-A18AA7
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
Unit: inch
16-7/16
1-9/16
1-5/8
Drain hole
6-7/8
19-11/16
13
2
Air in
Air in
Air out
2-holes 13/32 13/16
14-3/16
33-1/16
4-5/16
3-3/16
34-5/8
17-25/32
Service panel
6-1/2
7-11/16
35
44
Liquid refrigerant pipe joint
Refrigerant pipe (flared) Ø 1/4 (18 K BTU/H )
Refrigerant pipe (flared) Ø 3/8 (24/30/36 K BTU/H )
Gas refrigerant pipe joint
Refrigerant pipe (flared) Ø 1/2 (18 KBTU/H)
Refrigerant pipe (flared) Ø 5/8 (24/30/36 KBTU/H )
*1 20 in. (500 mm) or more when front
and sides of the unit are clear
14 in. (350 mm)
or more
4 in. (100 mm)
or more
REQUIRED SPACE
Clear *1
4 in. (100 mm)
or more
20 in. (500 mm)
or more *2
*2 When any 2 sides of left, right
and rear of the unit are clear
DIMENSIONS: SUZ-KA18NA2
FORM# PEAD-A18AA7 / SUZ-KA18NA2 - 202004
Specifications are subject to change without notice. © 2020 Mitsubishi Electric Trane HVAC US LLC. All rights reserved.
1340 Satellite Boulevard, Suwanee, GA 30024
oll Free: 800-433-4822 www.mehvac.com