GB
WT04936X01
Air-Conditioners For Building Application
Remote ON/OFF <input> signal adapter PAC-SC36NA-E
Installation Manual
This installation manual describes only the connection of the Remote ON/OFF <output> signal adapter to the outdoor unit of CITY
MULTI air conditioner series.
This part is a wiring member to connect the external circuit (locally procured) to the board on the outdoor unit. Depending on the
connection, Demand, Night mode, Snow sensor etc. can be controlled.
For details of compatible models, connection method and setting method, refer to the CITY MULTI DATA BOOK, Electrical Wiring
Diagram etc.
For your safety, be sure to read firstly “ 1 Safety Precaution ” described below thoroughly and then install the PAC-SC36NA-E.
1 Safety Precaution
● The following two symbols are used to denote dangers that may be caused by incorrect use.
WARNING
CAUTION
● After reading this instruction manual, keep it in a place where the end user can find it anytime he or she wants to it. When someone
moves, repairs or uses the PAC-SC36NA-E, make sure that this manual is forwarded to the final user.
■ Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric shock or fire.
■ Ensure that installation work is done correctly following this
instruction manual.
Any deficiency caused by installation may result in an electric shock
or fire.
■ Firmly connect the wiring using the specified cables.
Carefully check that the cables do not exert any forces on the
terminals.
Improper wiring connections may produce heat and possibly a fire.
■ Never modify or repair the PAC-SC36NA-E.
Any deficiency caused by your modification or repair may result in
an electric shock or fire. Consult with your dealer about repair.
■ Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PAC-SC36NA-E
may cause an explosion.
■ Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and
sulfuric gas may deteriorate the performance significantly or give
damage to the component parts.
■ Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
■ Do not install in any place at a temperature of more than 40
°F) or less than 0 °C (32 °F) or exposed to direct sunlight.
(104
2 Parts list
Make sure that the following items are included in the package.
• Remote ON/OFF <input> signal adapter 3 m (9-3/4 ft) ...........1 pcs.
This symbol denotes what could lead to serious injury or death if your misuse the PAC-SC36NA-E.
This symbol denotes what could lead to a personal injury or property damage if you misuse the PAC-SC36NA-E.
WARNING
■ All electrical work must be performed by a licensed technician,
according to local regulations and the instructions given in this
manual.
Any lack of electric circuit or any deficiency caused by installation
may result in an electric shock or fire.
■ Do not move and re-install the PAC-SC36NA-E yourself.
Any deficiency caused by installation may result in an electric shock or
fire. Ask your distributor or special vendor for moving and installation.
■ Stop the operation if any malfunction occurs.
If malfunction occurs (burning smell, etc.) stop the operation and
turn off the power supply. Contact your dealer or technical representative. If the controller continues to operate after a malfunction occurs, this may cause damage, electric shock or fire.
■ Do not turn on the main power until installation has been completed.
Doing so may result in electric shock or fire.
CAUTION
■ Do not install in any place where acidic or alkaline solution or
special spray are often used.
Doing so may cause an electric shock or malfunction.
■ Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew.
Doing so may cause an electric shock or malfunction.
■ Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
■ Do not wash with water.
Doing so may cause an electric shock or malfunction.
°C
3 Connection to the Outdoor Unit
Connect the connector side of the Remote ON/OFF <input> signal adapter to the connector CN3D, CN3N and CN3S of the outdoor unit
control board as necessary. The connector can only be connected in one direction only. Do not force the connection.
4 Locally Procured Parts
All parts other than the Remote ON/OFF <input> signal adapter (PAC-SC36NA-E) are procured locally.
The items required will depend on the connection method. Refer to the example of use shown below.
(Example)
1 External timer ....... No voltage contact out put timer (with separate circuits for power supply and switch).
2 Switch ................... Single pole, single action swich.
CAUTION: Choose the parts for the contact for minute electric current.
The timer and the contact of the switch will require degrees of 5 VDC, 12 V or 1 mA load. Choosing the wrong parts may cause
stoppage of the adapter.
3 Transit relay .......... When the wiring work as described in
4 Control cable ........ The length of the electrical wiring for the PAC-SC37SA is 3 meters (9-3/4 ft).
CAUTION:
1. Wiring should be covered by insulation tube with supplementary insulation.
2. Use relays or switches with IEC or equivalent standard.
3. The electric strength between accessible parts and control circuit should have 2750 V or more.
To extend this length, use sheathed 2-core cable
Control cable type: CVV, CVS, CPEV or equivalent
Cable size: 0.5 mm
Don’t extend the cable more than 10 meters (32 ft).
2
~ 1.25 mm2 (16 to 22 AWG)
6. Wiring Restrictions
is required, this relay is used.
5 Locally Procured Wiring
Basic connection methods for following models are shown below as examples.
For details and the connection method with another models, refer to the CITY MULTI DATA BOOK, Electrical Wiring Diagram etc.
(1) PUHY, PUY, PURY-P200, 250, 300, 350YGM
PUHY, PURY-P400, 450, 500, 550, 600, 650YGM
PUHY-P700, 750, 800, 850, 900, 950, 1000, 1050, 1100, 1150, 1200, 1250YSGM
1 Step demand (CN3D + DipSW4-7 ON)
Power supply
of relay
X Y
SW2
SW1
Preparations in the field
2 Night mode (CN3D + DipSW4-7 OFF)
Insulate this point securely as
this is not used.
Power supply
of relay
Preparations in the field
SW1
X
X
Orange
XYBrown
Red
Adapter
Orange
Brown
Red
Maximum cable
length is 10 m
Adapter
1
2
3
Maximum cable
length is 10 m
1
2
3
Outdoor unit
control board
CN3D
Outdoor unit
control board
X, Y: Relay (Point of contact rating: DC1 mA)
CN3D
Y (SW2)
OPEN
SHORT
X (SW1)
OPEN
100 %
0 % (Stop)
SHORT
* They are rough values.
X: Relay (Point of contact rating: DC1 mA)
X (SW1)
SHORT
Night mode: The noise level is reduced by limiting the
Night mode
OPEN
OFF
ON
maximum fan frequency under the following condition.
Cooling mode: outdoor temp. (TH6) < 30 °C
Heating mode: outdoor temp. (TH6) > 3 °C
75 %
50 %
21
Preparations in the field
Adapter
CN3D
2
1
3
XYBrown
Red
X Y
SW1
SW2
Outdoor unit
control board
Maximum cable
length is 10 m
Orange
Power supply
of relay
Preparations in the field
Adapter
CN3N
2
1
3
XYBrown
Red
X Y
SW1
SW2
Outdoor unit
control board
Maximum cable
length is 10 m
Orange
Power supply
of relay
3 Demand and Night mode (CN3D + DipSW4-7 OFF)
Power supply
of relay
X Y
SW2
SW1
Preparations in the field
XYBrown
4 Snow sensor (CN3S)
Insulate this point securely as
Power supply
of relay
this is not used.
X
SW1
Preparations in the field
X
Adapter
Orange
Brown
Red
Maximum cable
length is 10 m
5 Auto change over (CN3N) (PUHY, PUY only)
Power supply
of relay
X Y
SW2
SW1
Preparations in the field
XYBrown
Adapter
Orange
Red
Maximum cable
length is 10 m
1
2
3
Adapter
Orange
Red
Maximum cable
length is 10 m
1
2
3
Outdoor unit
control board
1
2
3
CN3S
Outdoor unit
control board
Outdoor unit
control board
X, Y: Relay (Point of contact rating: DC1 mA)
CN3D
X: Relay (Point of contact rating: DC1 mA)
Snow sensor: The outdoor fun runs when X is closed
CN3N
Night mode
X (SW1)
SHORT
OPEN
ON/OFF
OFF
ON
in stop mode or thermostat mode.
SW1: Cool/Heat
SW2: Validity/Invalidity of SW1
X, Y: Relay (Point of contact rating: DC1 mA)
OPEN
(Auto change over: OFF)
Y (SW2)
SHORT
(Auto change over: ON)
Y (SW2)
OPEN
SHORT
Compressor
ON/OFF
OFF
ON
X (SW1)
OPEN
SHORT
NORMAL
COOL HEAT
(3) PUMY-P100, 125, 140YHM
1 Step demand (CN3D + DipSW8-1 ON)
2 Night mode (CN3D + DipSW8-1 OFF)
Insulate this point securely as
this is not used.
Power supply
of relay
Preparations in the field
5 Auto change over (CN3N)
X
SW1
X, Y: Relay (Point of contact rating: DC1 mA)
X (SW1)
OPEN
SHORT
Y (SW2)
OPEN
SHORT
100 %
0 % (Stop)
75 %
50 %
* They are rough values.
Adapter
Orange
1
Brown
Red
Maximum cable
length is 10 m
2
3
X
Outdoor unit
control board
X: Relay (Point of contact rating: DC1 mA)
X (SW1)
CN3D
SHORT
Night mode: The noise level is reduced by limiting the
Night mode
OPEN
OFF
ON
maximum fan frequency under the following condition.
Cooling mode: outdoor temp. (TH6) < 30 °C
Heating mode: outdoor temp. (TH6) > 3 °C
SW1: Cool/Heat
SW2: Validity/Invalidity of SW1
X, Y: Relay (Point of contact rating: DC1 mA)
X (SW1)
OPEN
OPEN
(Auto change over: OFF)
Y (SW2)
SHORT
(Auto change over: ON)
SHORT
NORMAL
COOL HEAT
(2) PQHY, PQRY-P200, 250YGM-A
PQHY, PQRY-P400, 500YSGM-A
1 Demand (CN3D)
Power supply
of relay
Preparations in the field
Insulate this point securely as
this is not used.
X
SW1
X
Orange
Brown
Red
Maximum cable
length is 10 m
Adapter
1
2
3
Outdoor unit
control board
X: Relay (Point of contact rating: DC1 mA)
CN3D
OPEN
SHORT
ON/OFF
ON
OFF
Compressor
X (SW1)
Demand: The compressor is stopped when X is closed.
6 Wiring Restrictions
Keep the length of the cable connecting to the circuit board of the indoor unit shorter than 10 meters (32 ft).
Longer than 10 meters (32 ft) could cause improper operation.
Use a transit relay when extending wiring such as remote wiring.
43