Mitsubishi Electronics PURY-P72, PURY-P144, P168, P120YTHMU-A, P240YTSHMU-A User Manual

...
Safety Precautions
Before installing the unit, thoroughly read the following safety precautions.Observe these safety precautions for your safety.
WARNING
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or death.
This symbol is intended to alert the user to the presence of important instructions that must be followed to avoid
the risk of serious injury or damage to the unit.
After reading this manual, give it to the user to retain for future reference.Keep this manual for easy reference. When the unit is moved or repaired, give this manual to those who provide these
services. When the user changes, make sure that the new user receives this manual.
WARNING
Ask your dealer or a qualified technician to install the unit.
Improper installation by the user may result in water leak­age, electric shock, smoke, and/or fire.
Properly install the unit on a surface that can with­stand the weight of the unit.
Unit installed on an unstable surface may fall and cause in­jury.
Only use specified cables. Securely connect each ca­ble so that the terminals do not carry the weight of the cable.
Improperly connected or fixed cables may produce heat and start a fire.
Take appropriate safety measures against strong winds and earthquakes to prevent the unit from falling.
If the unit is not installed properly, the unit may fall and cause serious injury to the person or damage to the unit.
Do not make any modifications or alterations to the unit. Consult your dealer for repair.
Improper repair may result in water leakage, electric shock, smoke, and/or fire.
In the event of a refrigerant leak, thoroughly ventilate the room.
If refrigerant gas leaks and comes in contact with an open flame, poisonous gases will be produced.
When installing the All-Fresh type units, take it into consideration that the outside air may be discharged directly into the room when the thermo is turned off.
Direct exposure to outdoor air may have an adverse effect on health. It may also result in food spoilage.
Properly install the unit according to the instructions in the installation manual.
Improper installation may result in water leakage, electric shock, smoke, and/or fire.
Have all electrical work performed by an authorized electrician according to the local regulations and in­structions in this manual, and a dedicated circuit must be used.
Insufficient capacity of the power supply circuit or improper installation may result in malfunctions of the unit, electric shock, smoke, and/or fire.
Do not touch the heat exchanger fins.
The fins are sharp and dangerous.
HWE0803A GB
ii
WARNING
Securely attach the terminal block cover (panel) to the unit.
If the terminal block cover (panel) is not installed properly, dust and/or water may infiltrate and pose a risk of electric shock, smoke, and/or fire.
Only use the type of refrigerant that is indicated on the unit when installing or reinstalling the unit.
Infiltration of any other type of refrigerant or air into the unit may adversely affect the refrigerant cycle and may cause the pipes to burst or explode.
When installing the unit in a small room, exercise cau­tion and take measures against leaked refrigerant reaching the limiting concentration.
Consult your dealer with any questions regarding limiting concentrations and for precautionary measures before in­stalling the unit. Leaked refrigerant gas exceeding the lim­iting concentration causes oxygen deficiency.
Consult your dealer or a specialist when moving or re­installing the unit.
Improper installation may result in water leakage, electric shock, and/or fire.
After completing the service work, check for a gas leak.
If leaked refrigerant is exposed to a heat source, such as a fan heater, stove, or electric grill, poisonous gases may be produced.
Do not try to defeat the safety features of the unit.
Forced operation of the pressure switch or the temperature switch by defeating the safety features of these devices, or the use of accessories other than the ones that are recom­mended by MITSUBISHI may result in smoke, fire, and/or explosion.
Only use accessories recommended by MITSUBISHI.
Ask a qualified technician to install the unit. Improper instal­lation by the user may result in water leakage, electric shock, smoke, and/or fire.
Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it come into contact with any of the internal com­ponents. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
HWE0803A GB
ii
Precautions for handling units for use with R410A
Do not use the existing refrigerant piping.
A large amount of chlorine that is contained in the residual
refrigerant and refrigerator oil in the existing piping may cause the refrigerator oil in the new unit to deteriorate.
R410A is a high-pressure refrigerant and can cause the
existing pipes to burst.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
Store the pipes to be installed indoors, and keep both ends of the pipes sealed until immediately before braz­ing. (Keep elbows and other joints wrapped in plastic.)
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate or cause the unit to malfunction.
Use a small amount of ester oil, ether oil, or alkylben­zene to coat flares and flanges.
Infiltration of a large amount of mineral oil may cause the re­frigerating machine oil to deteriorate.
Charge liquid refrigerant (as opposed to gaseous re­frigerant) into the system.
If gaseous refrigerant is charged into the system, the com­position of the refrigerant in the cylinder will change and may result in performance loss.
Use a vacuum pump with a reverse-flow check valve.
If a vacuum pump that is not equipped with a reverse-flow check valve is used, the vacuum pump oil may flow into the refrigerant cycle and cause the refrigerating machine oil to deteriorate.
Prepare tools for exclusive use with R410A. Do not use the following tools if they have been used with the con­ventional refrigerant (gauge manifold, charging hose, gas leak detector, reverse-flow check valve, refrigerant charge base, vacuum gauge, and refrigerant recovery equipment.).
If the refrigerant or the refrigerating machine oil left on
these tools are mixed in with R410A, it may cause the re­frigerating machine oil to deteriorate.
Infiltration of water may cause the refrigerating machine
oil to deteriorate.
Gas leak detectors for conventional refrigerants will not
detect an R410A leak because R410A is free of chlorine.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of the refrig­erant will change, and the unit may experience power loss.
Exercise special care when handling the tools for use with R410A.
Infiltration of dust, dirt, or water into the refrigerant system may cause the refrigerating machine oil to deteriorate.
Only use refrigerant R410A.
The use of other types of refrigerant that contain chlorine (i.e. R22) may cause the refrigerating machine oil to deteri­orate.
HWE0803A GB
iiiiii
Before installing the unit
WARNING
Do not install the unit where a gas leak may occur.
If gaseous refrigerant leaks and piles up around the unit, it may be ignited.
Do not use the unit to keep food items, animals, plants, artifacts, or for other special purposes.
The unit is not designed to preserve food products.
Do not use the unit in an unusual environment.
Do not install the unit where a large amount of oil or steam
is present or where acidic or alkaline solutions or chemical sprays are used frequently. Doing so may lead to a re­markable drop in performance, electric shock, malfunc­tions, smoke, and/or fire.
The presence of organic solvents or corrosive gas (i.e.
ammonia, sulfur compounds, and acid) may cause gas leakage or water leakage.
When installing the unit in a hospital, take appropriate measures to reduce noise interference.
High-frequency medical equipment may interfere with the normal operation of the air conditioner or vice versa.
Do not install the unit on or over things that cannot get wet.
When the humidity level exceeds 80% or if the drainage system is clogged, the indoor unit may drip water. Drain wa­ter is also discharged from the outdoor unit. Install a central­ized drainage system if necessary.
HWE0803A GB
iv
Before installing the unit (moving and reinstalling the unit) and performing electrical work
Properly ground the unit.
Do not connect the grounding wire to a gas pipe, water pipe, lightning rod, or grounding wire from a telephone pole. Im­proper grounding may result in electric shock, smoke, fire, and/or malfunction due to noise interference.
Do not put tension on the power supply wires.
If tension is put on the wires, they may break and result in excessive heat, smoke, and/or fire.
Install an earth leakage breaker to avoid the risk of electric shock.
Failure to install an earth leakage breaker may result in electric shock, smoke, and/or fire.
Use the kind of power supply wires that are specified in the installation manual.
The use of wrong kind of power supply wires may result in current leak, electric shock, and/or fire.
Use breakers and fuses (current breaker, remote switch <switch + Type-B fuse>, moulded case circuit breaker) with the proper current capacity.
The use of wrong capacity fuses, steel wires, or copper wires may result in malfunctions, smoke, and/or fire.
Periodically check the installation base for damage.
If the unit is left on a damaged platform, it may fall and cause injury.
Properly install the drain pipes according to the in­structions in the installation manual. Keep them insu­lated to avoid dew condensation.
Improper plumbing work may result in water leakage and damage to the furnishings.
Exercise caution when transporting products.
Products weighing more than 20 kg should not be carried
alone.
Do not carry the product by the PP bands that are used on
some products.
Do not touch the heat exchanger fins. They are sharp and
dangerous.
When lifting the unit with a crane, secure all four corners
to prevent the unit from falling.
Properly dispose of the packing materials.
Nails and wood pieces in the package may pose a risk of
injury.
Plastic bags may pose a risk of choking hazard to chil-
dren. Tear plastic bags into pieces before disposing of them.
Do not spray water on the air conditioner or immerse the air conditioner in water.
Otherwise, electric shock and/or fire may result.
When handling units, always wear protective gloves to protect your hands from metal parts and high-tempera­ture parts.
HWE0803A GB
vv
Before the test run
Turn on the unit at least 12 hours before the test run.
Keep the unit turned on throughout the season. If the unit is turned off in the middle of a season, it may result in malfunc­tions.
To avoid the risk of electric shock or malfunction of the unit, do not operate switches with wet hands.
Do not touch the refrigerant pipes with bare hands dur­ing and immediately after operation.
During or immediately after operation, certain parts of the unit such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frost bites and burns, do not touch these parts with bare hands.
Do not operate the unit without panels and safety guards.
Rotating, high-temperature, or high-voltage parts on the unit pose a risk of burns and/or electric shock.
Do not turn off the power immediately after stopping the operation.
Keep the unit on for at least five minutes before turning off the power to prevent water leakage or malfunction.
Do not operate the unit without the air filter.
Dust particles may build up in the system and cause mal­functions.
HWE0803A GB
vi
CONTENTS
I
II
III
IV
V
VI
VII
VIII
Read Before Servicing
[1] Read Before Servicing.............................................................................................................. 3
[2] Necessary Tools and Materials ................................................................................................ 4
[3] Piping Materials ........................................................................................................................ 5
[4] Storage of Piping ...................................................................................................................... 7
[5] Pipe Processing........................................................................................................................ 7
[6] Brazing...................................................................................................................................... 8
[7] Air Tightness Test..................................................................................................................... 9
[8] Vacuum Drying (Evacuation) ..................................................................................................10
[9] Refrigerant Charging .............................................................................................................. 12
[10] Remedies to be taken in case of a Refrigerant Leak............................................................ 12
[11] Characteristics of the Conventional and the New Refrigerants ............................................ 13
[12] Notes on Refrigerating Machine Oil...................................................................................... 14
Restrictions
[1] System configuration .............................................................................................................. 17
[2] Types and Maximum allowable Length of Cables .................................................................. 18
[3] Switch Settings and Address Settings .................................................................................... 19
[4] Sample System Connection ................................................................................................... 25
[5] An Example of a System to which an MA Remote Controller is connected ........................... 26
[6] An Example of a System to which an M-NET Remote Controller is connected ..................... 38
[7] An Example of a System to which both MA Remote Controller and M-NET Remote
Controller are connected ........................................................................................................40
[8] Restrictions on Pipe Length.................................................................................................... 43
Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit ................................................................. 57
[2] Control Box of the Outdoor Unit.............................................................................................. 60
[3] Outdoor Unit Circuit Board...................................................................................................... 64
[4] BC Controller Components..................................................................................................... 74
[5] Control Box of the BC Controller ............................................................................................77
[6] BC Controller Circuit Board .................................................................................................... 78
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers .......................................... 83
[2] Group Settings and Interlock Settings via the ME Remote Controller .................................... 84
[3] Interlock Settings via the MA Remote Controller.................................................................... 88
[4] Using the built-in Temperature Sensor on the Remote Controller.......................................... 89
Electrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit ........................................................................ 93
[2] Electrical Wiring Diagram of the BC Controller....................................................................... 96
[3] Electrical Wiring Diagram of Transmission Booster.............................................................. 105
Refrigerant Circuit
[1] Refrigerant Circuit Diagram .................................................................................................. 109
[2] Principal Parts and Functions ............................................................................................... 116
Control
[1] Functions and Factory Settings of the Dipswitches .............................................................. 125
[2] Controlling the Outdoor Unit ................................................................................................. 132
[3] Controlling BC Controller ...................................................................................................... 145
[4] Operation Flow Chart............................................................................................................ 146
Test Run Mode
[1] Items to be checked before a Test Run................................................................................ 155
[2] Test Run Method .................................................................................................................. 156
[3] Operating Characteristic and Refrigerant Amount................................................................ 157
[4] Adjusting the Refrigerant Amount......................................................................................... 157
[5] Refrigerant Amount Adjust Mode.......................................................................................... 160
[6] The following symptoms are normal. .................................................................................... 162
[7] Standard Operation Data (Reference Data) ......................................................................... 163
HWE0803A GB
CONTENTS
IX
X
Troubleshooting
[1] Error Code Lists.................................................................................................................... 179
[2] Responding to Error Display on the Remote Controller........................................................ 182
[3] Investigation of Transmission Wave Shape/Noise ............................................................... 270
[4] Troubleshooting Principal Parts............................................................................................ 273
[5] Refrigerant Leak ................................................................................................................... 314
[6] Compressor Replacement Instructions................................................................................. 316
[7] Servicing the BC controller ................................................................................................... 327
[8] Troubleshooting Using the Outdoor Unit LED Error Display................................................. 330
LED Monitor Display on the Outdoor Unit Board
[1] How to Read the LED on the Service Monitor ...................................................................... 333
HWE0803A GB
I
Read Before Servicing
[1] Read Before Servicing.......................................................................................................3
[2] Necessary Tools and Materials.......................................................................................... 4
[3] Piping Materials ................................................................................................................. 5
[4] Storage of Piping ...............................................................................................................7
[5] Pipe Processing.................................................................................................................7
[6] Brazing............................................................................................................................... 8
[7] Air Tightness Test..............................................................................................................9
[8] Vacuum Drying (Evacuation) ........................................................................................... 10
[9] Refrigerant Charging........................................................................................................ 12
[10] Remedies to be taken in case of a Refrigerant Leak .......................................................12
[11] Characteristics of the Conventional and the New Refrigerants .......................................13
[12] Notes on Refrigerating Machine Oil ................................................................................. 14
HWE0803A GB
- 1 -
- 2 -
[ I Read Before Servicing ]
IRead Befo re Servicing
[1] Read Before Servicing
1. Check the type of refrigerant used in the system to be serviced. Refrigerant Type
Multi air conditioner for building application CITY MULTI R2 THMU-A, YHMU-A series R410A
2. Check the symptoms exhibited by the unit to be serviced.
Refer to this service handbook for symptoms relating to the refrigerant cycle.
3. Thoroughly read the safety precautions at the beginning of this manual.
4. Preparing necessary tools: Prepare a set of tools to be used exclusively with each type of refrigerant.
Refer to "Necessary Tools and Materials" for information on the use of tools.(page 4)
5. Verification of the connecting pipes: Verify the type of refrigerant used for the unit to be moved or replaced.
Use refrigerant pipes made of phosphorus deoxidized copper. Keep the inner and outer surfaces of the pipes clean and free
of such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil, and water.
These types of contaminants inside the refrigerant pipes may cause the refrigerant oil to deteriorate.
6. If there is a leak of gaseous refrigerant and the remaining refrigerant is exposed to an open flame, a poisonous gas hydrofluoric acid may form. Keep workplace well ventilated.
Install new pipes immediately after removing old ones to keep moisture out of the refrigerant circuit.The use of refrigerant that contains chloride, such as R22, will cause the refrigerating machine oil to deteriorate.
HWE0803A GB
- 3 -
[ I Read Before Servicing ]
[2] Necessary Tools and Materials
Prepare the following tools and materials necessary for installing and servicing the unit.
Tools for use with R410A (Adaptability of tools that are for use with R22 or R407C)
1. To be used exclusively with R410A (not to be used if used with R22 or R407C)
Tools/Materials Use Notes
Gauge Manifold Evacuation and refrigerant charging Higher than 5.09MPa[738psi] on the
Charging Hose Evacuation and refrigerant charging The hose diameter is larger than the
Refrigerant Recovery Cylinder Refrigerant recovery
Refrigerant Cylinder Refrigerant charging The refrigerant type is indicated. The
Charging Port on the Refrigerant Cylinder Refrigerant charging The charge port diameter is larger
Flare Nut Connection of the unit with the pipes Use Type-2 Flare nuts.
2. Tools and materials that may be used with R410A with some restrictions
Tools/Materials Use Notes
Gas Leak Detector Gas leak detection The ones for use with HFC refrigerant
Vacuum Pump Vacuum drying May be used if a check valve adapter
Flare Tool Flare processing Flare processing dimensions for the
Refrigerant Recovery Equipment Refrigerant recovery May be used if compatible with
high-pressure side
conventional model.
cylinder is pink.
than that of the current port.
may be used.
is attached.
piping in the system using the new re­frigerant differ from those of R22. Re­fer to I [3] Piping Materials.
R410A.
3. Tools and materials that are used with R22 or R407C that may also be used with R410A
Tools/Materials Use Notes
Vacuum Pump with a Check Valve Vacuum drying
Bender Bending pipes
Torque Wrench Tightening flare nuts Only the flare processing dimensions
for pipes that have a diameter of ø12.70 (1/2") and ø15.88 (5/8") have been changed.
Pipe Cutter Cutting pipes
Welder and Nitrogen Cylinder Welding pipes
Refrigerant Charging Meter Refrigerant charging
Vacuum Gauge Vacuum level check
4. Tools and materials that must not be used with R410A
Tools/Materials Use Notes
Charging Cylinder Refrigerant charging Prohibited to use
Tools for R410A must be handled with special care to keep moisture and dust from infiltrating the cycle.
HWE0803A GB
- 4 -
[ I Read Before Servicing ]
[3] Piping Materials
Do not use the existing piping!
1. Copper pipe materials
O-material (Annealed) Soft copper pipes (annealed copper pipes). They can easily be bent with hands.
1/2H-material (Drawn) Hard copper pipes (straight pipes). They are stronger than the O-material (Annealed)
The distinction between O-materials (Annealed) and 1/2H-materials (Drawn) is made based on the strength of the pipes them-
selves.
2. Types of copper pipes
Maximum working pressure Refrigerant type
3.45 MPa [500psi] R22, R407C etc.
4.30 MPa [624psi] R410A etc.
3. Piping materials/Radial thickness
Use refrigerant pipes made of phosphorus deoxidized copper. The operation pressure of the units that use R410A is higher than that of the units that use R22. Use pipes that have at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7 mm [28mil] or less may not be used.)
at the same radial thickness.
Pipe size (mm[in.]) Radial thickness (mm [mil]) Type
ø6.35 [1/4"] 0.8t [32t]
ø9.52 [3/8"] 0.8t [32t]
ø12.7 [1/2"] 0.8t [32t]
ø15.88 [5/8"] 1.0t [40t]
ø19.05 [3/4"] 1.0t [40t]
ø22.2 [7/8"] 1.0t [40t]
ø25.4 [1"] 1.0t [40t]
ø28.58 [1-1/8"] 1.0t [40t]
ø31.75 [1-1/4"] 1.1t [44t]
ø34.93 [1-3/8"] 1.2t [48t]
ø41.28 [1-5/8"] 1.4t [56t]
The pipes in the system that uses the refrigerant currently on the market are made with O-material (Annealed), even if the
pipe diameter is less than ø19.05 (3/4"). For a system that uses R410A, use pipes that are made with 1/2H-material (Drawn) unless the pipe diameter is at least ø19.05 (3/4") and the radial thickness is at least 1.2t.
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes
that meet the local standards.
O-material (Annealed)
1/2H-material,
H-material (Drawn)
HWE0803A GB
- 5 -
[ I Read Before Servicing ]
4. Thickness and refrigerant type indicated on the piping materials
Ask the pipe manufacturer for the symbols indicated on the piping material for new refrigerant.
5. Flare processing (O-material (Annealed) and OL-material only)
The flare processing dimensions for the pipes that are used in the R410A system are larger than those in the R22 system.
Flare processing dimensions (mm[in.])
A dimension (mm)
Pipe size (mm[in.])
R410A R22, R407C
ø6.35 [1/4"] 9.1 9.0
ø9.52 [3/8"] 13.2 13.0
ø12.7 [1/2"] 16.6 16.2
Dimension A
ø15.88 [5/8"] 19.7 19.4
ø19.05 [3/4"] 24.0 23.3
(ø19.05 pipes should have a radial thickness of 1.2 t and be made of annealed materials.) If a clutch-type flare tool is used to flare the pipes in the system using R410A, the length of the pipes must be between 1.0 and 1.5 mm. For margin adjustment, a copper pipe gauge is necessary.
6. Flare nut
The flare nut type has been changed to increase the strength. The size of some of the flare nuts have also been changed.
Flare nut dimensions (mm[in.])
B dimension (mm)
Pipe size (mm[in.])
R410A R22, R407C
ø6.35 [1/4"] 17.0 17.0
ø9.52 [3/8"] 22.0 22.0
ø12.7 [1/2"] 26.0 24.0
Dimension B
ø15.88 [5/8"] 29.0 27.0
ø19.05 [3/4"] 36.0 36.0
The figures in the radial thickness column are based on the Japanese standards and provided only as a reference. Use pipes that meet the local standards.
HWE0803A GB
- 6 -
[ I Read Before Servicing ]
[4] Storage of Piping
1. Storage location
Store the pipes to be used indoors. (Warehouse at site or owner's warehouse) If they are left outdoors, dust, dirt, or moisture may infiltrate and contaminate the pipe.
2. Sealing the pipe ends
Both ends of the pipes should be sealed until just before brazing. Keep elbow pipes and T-joints in plastic bags.
The new refrigerator oil is 10 times as hygroscopic as the conventional refrigerating machine oil (such as Suniso) and, if not handled with care, could easily introduce moisture into the system. Keep moisture out of the pipes, for it will cause the oil to deteriorate and cause a compressor failure.
[5] Pipe Processing
Use a small amount of ester oil, ether oil, or alkylbenzene to coat flares and flanges.
Use a minimum amount of oil. Use only ester oil, ether oil, and alkylbenzene.
HWE0803A GB
- 7 -
[ I Read Before Servicing ]
[6] Brazing
No changes have been made in the brazing procedures. Perform brazing with special care to keep foreign objects (such as oxide scale, water, and dust) out of the refrigerant system.
Example: Inside the brazed connection
Use of oxidized solder for brazing Use of non-oxidized solder for brazing
1. Items to be strictly observed
Do not conduct refrigerant piping work outdoors if raining.Use non-oxidized solder.Use a brazing material (BCuP-3) that requires no flux when brazing between copper pipes or between a copper pipe and
copper coupling.
If installed refrigerant pipes are not immediately connected to the equipment, then braze and seal both ends.
2. Reasons
The new refrigerating machine oil is 10 times as hygroscopic as the conventional oil and is more likely to cause unit failure if
water infiltrates into the system.
Flux generally contains chloride. Residual flux in the refrigerant circuit will cause sludge to form.
3. Notes
Do not use commercially available antioxidants because they may cause the pipes to corrode or refrigerating machine oil to deteriorate.
HWE0803A GB
- 8 -
[ I Read Before Servicing ]
[7] Air Tightness Test
No changes have been made in the detection method. Note that a refrigerant leak detector for R22 will not detect an R410A leak.
Halide torch R22 leakage detector
1. Items to be strictly observed
Pressurize the equipment with nitrogen up to the design pressure (4.15MPa[601psi]), and then judge the equipment's air tight-
ness, taking temperature variations into account.
Refrigerant R410A must be charged in its liquid state (vs. gaseous state).
2. Reasons
Oxygen, if used for an air tightness test, poses a risk of explosion. (Only use nitrogen to check air tightness.)Refrigerant R410A must be charged in its liquid state. If gaseous refrigerant in the cylinder is drawn out first, the composition
of the remaining refrigerant in the cylinder will change and become unsuitable for use.
3. Notes
Procure a leak detector that is specifically designed to detect an HFC leak. A leak detector for R22 will not detect an HFC(R410A) leak.
HWE0803A GB
- 9 -
[ I Read Before Servicing ]
[8] Vacuum Drying (Evacuation)
(Photo1) 15010H (Photo2) 14010
Recommended vacuum gauge: ROBINAIR 14010 Thermistor Vacuum Gauge
1. Vacuum pump with a reverse-flow check valve (Photo1)
To prevent the vacuum pump oil from flowing into the refrigerant circuit during power OFF or power failure, use a vacuum pump with a reverse-flow check valve. A reverse-flow check valve may also be added to the vacuum pump currently in use.
2. Standard of vacuum degree (Photo 2)
Use a vacuum pump that attains 0.5Torr(65Pa) or lower degree of vacuum after 5 minutes of operation, and connect it directly to the vacuum gauge. Use a pump well-maintained with an appropriate lubricant. A poorly maintained vacuum pump may not be able to attain the desired degree of vacuum.
3. Required precision of vacuum gauge
Use a vacuum gauge that registers a vacuum degree of 5Torr(650Pa) and measures at intervals of 1Torr(130Pa). (A recom­mended vacuum gauge is shown in Photo2.) Do not use a commonly used gauge manifold because it cannot register a vacuum degree of 5Torr(650Pa).
4. Evacuation time
After the degree of vacuum has reached 5Torr(650Pa), evacuate for an additional 1 hour. (A thorough vacuum drying re-
moves moisture in the pipes.)
Verify that the vacuum degree has not risen by more than 1Torr(130Pa) 1hour after evacuation. A rise by less than
1Torr(130Pa) is acceptable.
If the vacuum is lost by more than 1Torr(130Pa), conduct evacuation, following the instructions in section 6. Special vacuum
drying.
5. Procedures for stopping vacuum pump
To prevent the reverse flow of vacuum pump oil, open the relief valve on the vacuum pump side, or draw in air by loosening the charge hose, and then stop the operation. The same procedures should be followed when stopping a vacuum pump with a reverse-flow check valve.
6. Special vacuum drying
When 5Torr(650Pa) or lower degree of vacuum cannot be attained after 3 hours of evacuation, it is likely that water has pen-
etrated the system or that there is a leak.
If water infiltrates the system, break the vacuum with nitrogen. Pressurize the system with nitrogen gas to
0.5kgf/cm
2
G(0.05MPa) and evacuate again. Repeat this cycle of pressurizing and evacuation either until the degree of vac-
uum below 5Torr(650Pa) is attained or until the pressure stops rising.
Only use nitrogen gas for vacuum breaking. (The use of oxygen may result in an explosion.)
HWE0803A GB
- 10 -
[ I Read Before Servicing ]
7. Notes
To evacuate air from the entire system Applying a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) is not enough to attain the desired vacuum pressure. Be sure to apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2) and also through the check joints on the high and low pressure sides (CJ1 and 2).
To evacuate air only from the outdoor units Apply a vacuum through the check joints on the high and low pressure sides (CJ1, and 2).
To evacuate air from the indoor units and extension pipes Apply a vacuum through the check joints at the refrigerant service valve on the high and low pressure sides (BV1 and 2).
HWE0803A GB
- 11 -
[ I Read Before Servicing ]
[9] Refrigerant Charging
Cylinder with a siphon
Cylinder without a siphon
Cylin-
Cylin-
der
der
Cylinder color R410A is pink. Refrigerant charging in the liquid state
Valve Valve
liquid
liquid
1. Reasons
R410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F], R125=-49°C[-52°F]) and can almost be handled the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and be­come unsuitable for use.
2. Notes
When using a cylinder with a siphon, refrigerant is charged in the liquid state without the need for turning it upside down. Check the type of the cylinder on the label before use.
[10] Remedies to be taken in case of a Refrigerant Leak
If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced. (Charge refrigerant in the liquid state.) Refer to "IX [5] Refrigerant Leak".(page 314)
HWE0803A GB
- 12 -
[ I Read Before Servicing ]
[11] Characteristics of the Conventional and the New Refrigerants
1. Chemical property
As with R22, the new refrigerant (R410A) is low in toxicity and chemically stable nonflammable refrigerant. However, because the specific gravity of vapor refrigerant is greater than that of air, leaked refrigerant in a closed room will accumulate at the bottom of the room and may cause hypoxia. If exposed to an open flame, refrigerant will generate poisonous gases. Do not perform installation or service work in a con­fined area.
New Refrigerant (HFC type) Conventional Refriger-
ant (HCFC type)
R410A R407C R22
R32/R125 R32/R125/R134a R22
Composition (wt%) (50/50) (23/25/52) (100)
Type of Refrigerant Pseudo-azeotropic
Refrigerant
Non-azeotropic
Refrigerant
Single Refrigerant
Chloride Not included Not included Included
Safety Class A1/A1 A1/A1 A1
Molecular Weight 72.6 86.2 86.5
Boiling Point (°C/°F) -51.4/-60.5 -43.6/-46.4 -40.8/-41.4
Steam Pressure
1.557/226 0.9177/133 0.94/136
(25°C,MPa/77°F,psi) (gauge)
Saturated Steam Density (25°C,kg/m
3
/77°F,psi)
64.0 42.5 44.4
Flammability Nonflammable Nonflammable Nonflammable
Ozone Depletion Coefficient (ODP)
Global Warming Coefficient (GWP)
Refrigerant Charging Method Refrigerant charging in
Replenishment of Refrigerant after a Refrigerant
*1
*2
0 0 0.055
1730 1530 1700
the liquid state
Refrigerant charging in
the liquid state
Refrigerant charging in
the gaseous state
Available Available Available
Leak
*1 When CFC11 is used as a reference *2 When CO
is used as a reference
2
2. Refrigerant composition
R410A is a pseudo-azeotropic HFC blend and can almost be handled the same way as a single refrigerant, such as R22. To be safe, however, draw out the refrigerant from the cylinder in the liquid phase. If the refrigerant in the gaseous phase is drawn out, the composition of the remaining refrigerant will change and become unsuitable for use. If the refrigerant leaks out, it may be replenished. The entire refrigerant does not need to be replaced.
3. Pressure characteristics
The pressure in the system using R410A is 1.6 times as great as that in the system using R22.
Pressure (gauge)
Temperature (°C/°F)
R410A R407C R22
MPa/psi MPa/psi MPa/psi
-20/-4 0.30/44 0.18/26 0.14/20
0/32 0.70/102 0.47/68 0.40/58
20/68 1.34/194 0.94/136 0.81/117
40/104 2.31/335 1.44/209 1.44/209
60/140 3.73/541 2.44/354 2.33/338
65/149 4.17/605 2.75/399 2.60/377
HWE0803A GB
- 13 -
[ I Read Before Servicing ]
[12] Notes on Refrigerating Machine Oil
1. Refrigerating machine oil in the HFC refrigerant system
HFC type refrigerants use a refrigerating machine oil different from that used in the R22 system. Note that the ester oil used in the system has properties that are different from commercially available ester oil.
Refrigerant Refrigerating machine oil
R22 Mineral oil
R407C Ester oil
R410A Ester oil
2. Effects of contaminants
*1
Refrigerating machine oil used in the HFC system must be handled with special care to keep contaminants out. The table below shows the effect of contaminants in the refrigerating machine oil on the refrigeration cycle.
3. The effects of contaminants in the refrigerating machine oil on the refrigeration cycle.
Cause Symptoms Effects on the refrigerant cycle
Water infiltration Frozen expansion valve
and capillary tubes
Clogged expansion valve and capillary tubes Poor cooling performance Compressor overheat Motor insulation failure Burnt motor Coppering of the orbiting scroll Lock Burn-in on the orbiting scroll
Clogged expansion valve, capillary tubes, and drier Poor cooling performance Compressor overheat
Burn-in on the orbiting scroll
Hydrolysis
Air infiltration Oxidization
Adhesion to expansion valve and capillary tubes
Dust, dirt
Infiltration of contaminants
Infiltration of contaminants into the com­pressor
Sludge formation and ad­hesion Acid generation Oxidization Oil degradation
Sludge formation and adhesion Clogged expansion valve and capillary tubes
Mineral oil etc.
Poor cooling performance Compressor overheat
Oil degradation Burn-in on the orbiting scroll
*1. Contaminants is defined as moisture, air, processing oil, dust/dirt, wrong types of refrigerant, and refrigerating machine oil.
HWE0803A GB
- 14 -
II
Restrictions
[1] System configuration ....................................................................................................... 17
[2] Types and Maximum allowable Length of Cables ...........................................................18
[3] Switch Settings and Address Settings ............................................................................. 19
[4] Sample System Connection.............................................................................................25
[5] An Example of a System to which an MA Remote Controller is connected.....................26
[6] An Example of a System to which an M-NET Remote Controller is connected...............38
[7] An Example of a System to which both MA Remote Controller and M-NET Remote
Controller are connected.................................................................................................. 40
[8] Restrictions on Pipe Length............................................................................................. 43
HWE0803A GB
- 15 -
- 16 -
[ II Restrictions ]
IIRestrictions
[1] System configuration
1. Table of compatible indoor units
The table below summarizes the types of indoor units that are compatible with different types of outdoor units.
Outdoor
units
Composing units Maximum total capacity
of connectable indoor
units
Maximum number of connectable in-
door units
Types of connectable in-
door units
72 - - 36 - 108 18 P06 - P96 models
96 - - 48 - 144 24
R410A series indoor units
120 - - 60 - 180 30
144 72 72 72 - 216 36
168 96 72 84 - 252 42
192 96 96 96 - 288 48
216 120 96 108 - 324 50
240 120 120 120 - 360 50
1) "Maximum total capacity of connectable indoor units" refers to the sum of the numeric values in the indoor unit model names.
2) If the total capacity of the indoor units that are connected to a given outdoor unit exceeds the capacity of the outdoor unit, the indoor units will not be able to perform at the rated capacity when they are operated simultaneously. Select a combination of units so that the total capacity of the connected indoor units is at or below the capacity of the outdoor unit whenever possible.
HWE0803A GB
- 17 -
[ II Restrictions ]
[2] Types and Maximum allowable Length of Cables
1. Wiring work
(1) Notes
1) Have all electrical work performed by an authorized electrician according to the local regulations and instructions in this man­ual.
2) Install external transmission cables at least 5cm [1-31/32"] away from the power supply cable to avoid noise interference. (Do not put the control cable and power supply cable in the same conduit tube.)
3) Provide grounding for the outdoor unit as required.
4) Run the cable from the electric box of the indoor or outdoor unit in such way that the box is accessible for servicing.
5) Do not connect power supply wiring to the terminal block for transmission line. Doing so will damage the electronic compo­nents on the terminal block.
6) Use 2-core shielded cables as transmission cables. Use a separate 2-core control cable for each refrigerant system. Do not use a single multiple-core cable to connect indoor
units that belong to different refrigerant systems. The use of a multiple-core cable may result in signal transmission errors and malfunctions.
Outdoor unit
TB3TB7TB3TB
2-core shielded cable
TB3TB7TB3TB
2-core shielded cable
7
7
BC Controller
Indoor unit
Remote Controller
Outdoor unit
TB3TB7TB3TB
TB3TB7TB3TB
BC Controller
7
multiple-core cable
7
Indoor unit
Remote Controller
TB3: Terminal block for indoor-outdoor transmission line TB7: Terminal block for centralized control
(2) Control wiring
Different types of control wiring are used for different systems. Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work.
Types and maximum allowable length of cables
Control lines are categorized into 2 types: transmission line and remote controller line. Use the appropriate type of cables and observe the maximum allowable length specified for a given system. If a given system
has a long transmission line or if a noise source is located near the unit, place the unit away from the noise source to reduce noise interference.
1) M-NET transmission line
Facility type
All facility types
Type Shielded cable CVVS, CPEVS, MVVS
Cable type
Number of cores
Cable size Larger than 1.25mm
2-core cable
2
[AWG16]
Maximum transmission line distance between the outdoor unit and the far-
200 m [656ft] max.
thest indoor unit
Maximum transmission line distance for central­ized control and Indoor/ outdoor transmission line (Maximum line distance
500 m [1640ft] max. *The maximum overall line length from the power supply unit on the transmission lines for centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
via outdoor unit)
HWE0803A GB
- 18 -
[ II Restrictions ]
2) Remote controller wiring
MA remote controller
*1
M-NET remote controller
*2
Type VCTF, VCTFK, CVV, CVS, VVR, VVF, VCT Shielded cable MVVS
Number of cores
Cable type
Cable size
Maximum overall line length
2-core cable 2-core cable
0.3 to 1.25mm [AWG22 to 16] (0.75 to 1.25mm [AWG18 to 16]
2 *3
2) *4
0.3 to 1.25mm [AWG22 to 16] (0.75 to 1.25mm [AWG18 to 16]
The section of the cable that exceeds 10m
200 m [656ft] max.
[32ft] must be included in the maximum in­door-outdoor transmission line distance.
2 *3
2) *4
*1 MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and
wireless remote controller. *2 M-NET remote controller refers to ME remote controller and ME simple remote controller. *3 The use of cables that are smaller than 0.75mm
2
[AWG18] is recommended for easy handling.
*4 When connected to the terminal block on the Simple remote controller, use cables that meet the cable size specifi-
cations shown in the parenthesis.
[3] Switch Settings and Address Settings
1. Switch setting
Refer to section "[5] An Example of a System to which an MA Remote Controller is connected - [7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected" before performing wiring work. Set the switches while the power is turned off. If the switch settings are changed while the unit is being powered, those changes will not take effect, and the unit will not function properly.
Units on which to set the switches Symbol Units to which the power must be shut off
CITY MULTI indoor unit Main/sub unit IC Outdoor units
LOSSNAY, OA processing unit
*1
M-NET remote controller Main/sub remote
LC Outdoor units
RC Outdoor units
*3
and Indoor units
*3
and LOSSNAY
*3
controller
MA remote controller Main/sub remote
MA Indoor units
controller
CITY MULTI outdoor unit
*2
OC,OS Outdoor units
BC controller Main BC Outdoor units
Sub1, 2 BS1, BS2 Outdoor units
*3
*3
and BC controller
*3
and BC controller
*1. Applicable when LOSSNAY units are connected to the indoor-outdoor transmission line. *2. The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity
from large to small (if two or more units have the same capacity, in the order of address from small to large).
*3. Turn off the power to all the outdoor units in the same refrigerant circuit.
HWE0803A GB
- 19 -
[ II Restrictions ]
2. M-NET Address settings (1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
Unit or controller Sym-
bol
Address setting
Setting method Factory
range
CITY MULTI indoor unit
M-NET adapter
M-NET con­trol interface
Free Plan adapter
LOSSNAY, OA processing unit LC 0, 01 to
M-NET re­mote con­troller
Main/sub unit IC 0, 01 to
Main remote
RC 101 to
controller
Sub remote
RC 151 to
controller
50
50
150
200
*1 *4 *6
*1 *4 *6
*3
Assign the smallest address to the main indoor unit in the group, and assign sequential address numbers to the rest of the indoor units in the same group. In an R2 system with a sub BC controller, make the set­tings for the indoor units in the following order. (i) Indoor unit to be connected to the main BC controller (ii) Indoor unit to be connected to sub BC controller 1 (iii) Indoor unit to be connected to sub BC controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
Add 100 to the smallest address of all the indoor units in the same group.
Add 150 to the smallest address of all the indoor units in the same group.
MA remote controller MA No address settings required. (The main/sub setting must be made if
2 remote controllers are connected to the system.)
CITY MULTI outdoor unit OCOS0, 51 to
100
*6
Auxiliary outdoor unit
BC controller (main)
BC 0, 51 to
100
*6
Assign an address that equals the lowest address of the in-
*1 *2
*1 *2
door units in the same refrigerant circuit plus 50.
Assign sequential addresses to the outdoor units in the
same refrigerant circuit. The outdoor units in the same re­frigerant circuit are automatically designated as OC and
*5
OS.
Assign an address that equals the address of the outdoor
unit in the same refrigerant system plus 1.
If a given address overlaps any of the addresses that are
assigned to the outdoor units or to the sub BC controller, use a different, unused address within the setting range.
BC controller (sub1, 2)
BS1 BS2
51 to 100
Assign an address to both the sub BC controller 1 and 2
*2
that equals the lowest address of the indoor units that are connected to each of them plus 50.
If a sub BC controller is connected, the automatic startup
function is not available.
System controller
Group remote con-
GRSC201 to
troller
System remote con­troller
ON/OFF remote con­troller
SR SC
AN SC
Schedule timer (com­patible with M-NET)STSC
Central controller
TRSC0, 201 to
G(B)-50A
250
250
Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range listed on the left to each unit.
Assign an address that equals the sum of the smallest group number of the group to be controlled and 200.
Assign an arbitrary but unique address within the range listed on the left to each unit.
Assign an arbitrary but unique address within the range listed on the left to each unit. The address must be set to "0" to control the K-control unit.
LM adapter SC 201 to
250
Assign an arbitrary but unique address within the range listed on the left to each unit.
address
setting
00
00
101
Main
00
00
201
202
000
247
*1. If a given address overlaps any of the addresses that are assigned to other units, use a different, unused address within the
setting range.
*2. To set the outdoor unit address or the auxiliary outdoor unit address to "100," set the rotary switches to "50." *3. To set the M-NET remote controller address to "200," set the rotary switches to "00." *4. Some models of indoor units have two or three control boards.
Assign an address to the No.1, No. 2, and No. 3 control boards so that the No. 2 control board address equals the No. 1 control board address plus 1, and that the No. 3 control board address equals the No. 1 control board address plus 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, and OS. They are designated as OC,
and OS in the descending order of capacity (ascending order of address if the capacities are the same).
*6. No address settings are required for units in a system with a single outdoor unit (with some exceptions).
Address setting is required if a sub BC controller is connected.
HWE0803A GB
- 20 -
[ II Restrictions ]
(2) Power supply switch connector connection on the outdoor unit
(Factory setting: The male power supply switch connector is connected to CN41.)
There are limitations on the total number of units that are connectable to each refrigerant system. Refer to the System Design Manual for details.
System configura­tion
Connection to the system con­troller
Power supply unit for transmission lines
Group operation of units in a sys­tem with multiple
Power supply switch connector connection
outdoor units
System with one outdoor unit
System with multi­ple outdoor units
_ _ _ Leave CN41 as it is
(Factory setting)
Not connected _ Not grouped
Grouped Disconnect the male connector from the fe-
With connection to the indoor unit system
With connection to the central­ized control sys­tem
Not required Grouped/not
grouped
Not required (Powered from
*1
Grouped/not grouped
the outdoor unit)
Required *1 Grouped/not
grouped
male power supply switch connector (CN41) and connect it to the female power supply switch connector (CN40) on only one of the outdoor units.
*Connect the S (shielded) terminal on the
terminal block (TB7) on the outdoor unit whose CN41 was replaced with CN40 to the ground terminal ( ) on the electric box.
Leave CN41 as it is (Factory setting)
*2
*1 The need for a power supply unit for transmission lines depends on the system configuration. *2 The replacement of the power jumper connector from CN41 to CN40 must be performed on only one outdoor unit in the
system.
(3) Settings for the centralized control switch for the outdoor unit (Factory setting: SW2-1 are set to OFF.)
System configuration Centralized control switch settings
*1
Connection to the system controller Not connected Leave it to OFF. (Factory setting)
Connection to the system controller Connected
*2
ON
*1. Set SW2-1 on all outdoor units in the same refrigerant circuit to the same setting. *2. When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
(4) Selecting the position of temperature detection for the indoor unit (Factory setting: SW1-1 set to "OFF".)
To stop the fan during heating Thermo-OFF (SW1-7 and 1-8 on the indoor units to be set to ON), use the built-in thermistor on the remote controller or an optional thermistor.
1) To use the built-in sensor on the remote controller, set the SW1-1 to ON. Some models of remote controllers are not equipped with a built-in temperature sensor.
Use the built-in temperature sensor on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
(Note) Factory setting for SW1-1 on the indoor unit of the All-Fresh Models is ON.
2) When an optional temperature sensor is used, set SW1-1 to OFF, and set SW3-8 to ON. When using an optional temperature sensor, install it where room temperature can be detected.
HWE0803A GB
- 21 -
[ II Restrictions ]
(5) Various start-stop controls (Indoor unit settings)
Each indoor unit (or group of indoor units) can be controlled individually by setting SW 1-9 and 1-10.
Function
Power ON/OFF by the
*1,*2,*3
plug
Automatic restoration after power failure
Operation of the indoor unit when the operation is resumed after the unit
was stopped
Indoor unit will go into operation regardless of its operation status before power off (power failure). (In approx. 5 minutes)
Indoor unit will go into operation if it was in operation when the power was turned off (or cut off due to power failure). (In approx. 5 minutes)
Indoor unit will remain stopped regardless of its operation status before
Setting (SW1)
910
OFF ON
ON OFF
OFF ON
power off (power failure).
*1. Do not cut off power to the outdoor unit. Cutting off the power supply to the outdoor unit will cut off the power supply to the
crankcase heater and may cause the compressor to malfunction when the unit is put back into operation. *2. Not applicable to units with a built-in drain pump or humidifier. *3. Models with a built-in drain pump cannot be turned on/off by the plug individually. All the units in the same refrigerant cir-
cuits will be turned on or off by the plug. *4. Requires that the dipswitch settings for all the units in the group be made. *5. To control the external input to and output from the air conditioners with the PLC software for general equipment via the
G(B)-50A, set SW1-9 and SW1-10 to ON. With these settings made, the power start-stop function becomes disabled. To
use the auto recovery function after power failure while these settings are made, set SW1-5 to ON.
(6) Miscellaneous settings
Cooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 "OFF.") When using indoor unit as a cooling-only unit, set SW3-1 to ON.
(7) Various types of control using input-output signal connector on the outdoor unit (various connection options)
*4 *5
Type Usage Function
Input Prohibiting cooling/heating operation (thermo OFF) by an external
DEMAND (level) CN3D
input to the outdoor unit.
Performs a low level noise operation of the outdoor unit by an ex­ternal input to the outdoor unit.
Low-noise mode
*3 *4
(level)
Terminal
to be
*1
used
*2
Option
Adapter for external input (PAC­SC36NA-E)
* It can be used as the silent operation device for each refrigerant system.
Forces the outdoor unit to perform a fan operation by receiving sig­nals from the snow sensor.
*5
Cooling/heating operation can be changed by an external input to
Snow sensor signal input (level)
Auto-changeover CN3N
CN3S
the outdoor unit.
Out-
How to extract signals from the outdoor unit
put
*It can be used as an operation status display device. *It can be used for an interlock operation with external devices.
Operation status of the compressor
Error status
*5
*6
CN51 Adapter for
external out­put (PAC­SC37SA-E)
*1. For detailed drawing, refer to "Example of wiring connection". *2. For details, refer to 1) through 4) shown below. *3. Low-noise mode is valid when Dip SW4-4 on the outdoor unit is set to OFF. When DIP SW4-4 is set to ON, 4 levels of
on-DEMAND are possible, using different configurations of low-noise mode input and DEMAND input settings.When 2 or more outdoor units exist in one refrigerant circuit system, 8 levels of on-DEMAND are possible.
*4. By setting Dip SW5-5, the Low-noise mode can be switched between the Capacity priority mode and the Low-noise pri-
ority mode. When SW5-5 is set to ON: The low-noise mode always remains effective. When SW5-5 is set to OFF: The low noise mode is cancelled when certain outside temperature or pressure criteria are met, and the unit goes into normal operation (capacity priority mode).
Low-noise mod is effective. Capacity priority mode becomes effective.
Cooling Heating Cooling Heating
TH7<30°C[86°F] and 63HS1<32kg/cm
2
TH7>3°C[37°F] and 63LS>4.6kg/cm
2
TH7>35°C[95°F] or 63HS1>35kg/cm
2
TH7<0°C[32°F] or 63LS<3.9kg/cm
2
*5. Each outdoor unit in the system with multiple outdoor units requires the signal input/output setting to be made. *6. Take out signals from the outdoor unit (OC) if multiple outdoor units exist in a single system.
HWE0803A GB
- 22 -
[ II Restrictions ]
1) Wiring should be covered by insulation tube with supplementary insulation.
2) Use relays or switches with IEC or equivalent standard.
3) The electric strength between accessible parts and control circuit should have 2750V or more.
Example of wiring connection
(1) CN51
Distant control board
ecruosrewoppmaL
1
L
L
2
L1 : Outdoor unit error display lamp L2 : Compressor operation lamp (compressor running state) X, Y : Relay (coil =<0.9W : DC12V)
1. Optional part : PAC-SC37SA-E or field supply.
Relay circuit Adapter
X Y
Y
X
Preparations
in the field
Maximum cable length is 10m
1
5 4 3
(3) CN3N
Relay circuit
X
Y
Preparations
in the field
Adapter
2
1 2
3
Maximum cable length is 10m
Outdoor unit control board
CN3N
Y
X : Cooling / Heating Y : Validity / Invalidity of X X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Outdoor unit control board
CN51
OFF
ON
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
(2) CN3S
Relay circuit
Preparations
X : Relay
Snow sensor : The outdoor fan runs when X is closed
X
OFF
Normal
CoolingONHeating
Outdoor unit
1 2
3
2
control board
Adapter
X
in the field
2. Optional part : PAC-SC36NA-E or field supply.
Maximum cable length is 10m
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
in stop mode or thermostat mode.
CN3S
(4) CN3D
Relay circuit
Preparations
in the field
X : Low-noise mode Y : Compressor ON/OFF X,Y : Relay
2. Optional part : PAC-SC36NA-E or field supply.
Adapter
X
Y
Maximum cable length is 10m
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum appicable load =< 1mA at DC
1 2
3
Outdoor unit
2
control board
CN3D
1 2
3
Outdoor unit
2
control board
CN3D
Relay circuit
X
Preparations
in the field
X : Low-noise mode X : Relay
Low-noise mode : The noise level is reduced by controlling the maximum
Contact rating voltage >= DC15V Contact rating current >= 0.1A Minimum applicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
Adapter
Maximum cable length is 10m
fan frequency and maximum compressor frequency.
HWE0803A GB
- 23 -
[ II Restrictions ]
1) SW4-4: OFF (Compressor ON/OFF, Low-noise mode)
CN3D 1-3P Compressor ON/OFF
Open Compressor ON
Short-circuit Compressor OFF
*1
CN3D 1-2P Low-noise mode
*2
Open OFF
Short-circuit ON
*1. When SW4-4 on the outdoor unit in one refrigerant circuit system is set to ON , this function cannot be used. *2. This function can be enabled when the 4-step demand control is enabled. Input the order to CN3D 1-2P on the outdoor unit
whose SW4-4 is set to OFF.
2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND)
(*3)
CN3D 1-2P
CN3D 1-3P Open Short-circuit
Open 100% (No DEMAND) 75%
Short-circuit 0% (Compressor OFF) 50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON.
Note the following steps to be taken when using the STEP DEMAND (Example) When switching from 100% to 50%
Demand control steps
If the step listed as the wrong example above is taken, thermo may go off. The percentage of the demand listed in the table above is an approximate value based on the compressor volume and does not necessarily correspond with the capacity. When this function is enabled, the night mode cannot be enabled.
(Wrong)
(Correct)
100%
100%
0%
75%
50%
50%
3) When SW4-4 on the two outdoor units in one refrigerant circuit system is set to ON (8 levels of on-DEMAND)
8 levels of on-DEMAND No.2 CN3D
1-2P Open Short-circuit
No.1 CN3D 1-2P 1-3P Open Short-circuit Open Short-circuit
Open Open 100% 50% 88% 75%
Short-circuit 50% 0% 38% 25%
Short-circuit Open 88% 38% 75% 63%
Short-circuit 75% 25% 63% 50%
*3. Input the order to CN3D on the outdoor unit whose SW4-4 is set to ON. *4. CN3D of No. 1, 2, 3 can be selected arbitrary with the outdoor unit whose SW4-4 is set to ON.
(*3, *4)
HWE0803A GB
- 24 -
[ II Restrictions ]
[4] Sample System Connection
Examples of typical system connection are shown on pages [5] to [7]. Refer to the Installation Manual that came with each device or controller for details.
(1) An example of a system to which an MA remote controller is connected
System
configuration
System with one out-
1
2
door unit
System with one out-
door unit
Connection to the system controller
NO
NO
Address start up for in-
door and outdoor units
address setup
address setup
Grouping of units in a
3
system with multiple
outdoor units
System with one out-
4
5
6
door unit
System with one out-
door unit
System with one out-
door unit
With connection to transmission line
for centralized control
With connection to indoor-outdoor
With connection to transmission line
for centralized control
NO
transmission line
address setup
address setup
address setup
address setup
(2) An example of a system to which an M-NET remote controller is connected
System
configuration
System with one out-
1
door unit
Connection to the system controller
With connection to transmission line
for centralized control
Address start up for indoor
and outdoor units
address setup
Automatic
Manual
Manual
Manual
Manual
Manual
Manual
Notes
Connection of multiple LOSS­NAY units
Connection of multiple LOSS­NAY units
Notes
(3) An example of a system to which both MA remote controller and M-NET remote controller are connected
System
configuration
System with one out-
1
door unit
Connection to the system controller
With connection to transmission
line for centralized control
Address start up for in­door and outdoor units
Manual
address setup
Notes
HWE0803A GB
- 25 -
[ II Restrictions ]
[5] An Example of a System to which an MA Remote Controller is connected
1. System with one outdoor unit (automatic address setup for both indoor and outdoor units) (1) Sample control wiring
Leave the male connector on CN41 as it is. SW2-1 OFF
OS
00
TB3
M1 M2 M1 M2 M1 M2
TB7
S
Leave the male connector on CN41 as it is. SW2-1 OFF
OC
00
TB3
M1 M2
TB7
L3L1 L2
BC
00
TB02
S
M1 M2
S
M1
TB5
M2
IC
00
S
L4 L5
15
TB
12
m1
GroupGroup
00
TB5STB
M1
M2
IC
15
12
Interlock operation with the ventilation unit
LC
00
TB5
M1
M2
S
*1
S
M1M2
TB02
00
BS
*1. When BS is connected to the system, automatic address setup is not available.
L11
m4
A1 B2
MA
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) re­quired
1 unit 2 units
When the P72 and P96 models are not included in the connect­ed indoor units
When the P72 and P96 models are included in the connected indoor units
27 - 50 units -
21 - 39 units 40 - 50 units
The table above shows the number of transmission
boosters that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
M1
A1 B2
MA
TB5
M2
A1 B2
MA
L12 L13
IC
15
TB
12
S
m5
A1 B2
MA
A1 B2
RC
GroupGroup
0000
TB5STB
M1
M2
IC
A1 B2
15
12
A1 B2
MA
MA
IC
00
15
TB5STB
M1
M2
12
m2
m3
4) Automatic address setup is not available if start-stop in­put(CN32, CN51, CN41) is used for a group operation of indoor units. Refer to "[5] 2. Manual address setup for both indoor and outdoor units"
5) To connect more than 2 LOSSNAY units to indoor units in the same system, refer to the next section "[5] 2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected".
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger) L1 +L2+L3+L4+L5 200m[656ft] L1 +L2+L3+L11+L12+L13 200m[656ft]
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft] m4+m5 200m [656ft]
- 26 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-out­door transmission line (TB02) on the main BC controller (BC), and of the terminal block for indoor-outdoor trans­mission line (TB5) on each indoor unit (IC). (Non-polar­ized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC and OS in the order of ca­pacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC controller (BC), and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Connect terminals 1 and 2 on the terminal block for MA
remote controller line (TB15) on the indoor unit (IC) to the terminal block on the MA remote controller (MA). (Non-polarized two-wire)
When 2 remote controllers are connected to the sys­tem
When 2 remote controllers are connected to the system, connect terminals 1 and 2 of the terminal block (TB15) on the indoor unit (IC) to the terminal block on the two MA remote controllers.
Set one of the MA remote controllers as a sub controller.
(Refer to the Instruction Manual for the MA remote con­troller for the setting method.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy­chain terminals 1 and 2 on the terminal block (TB15) on all indoor units (IC) in the same group, and then connect terminals 1 and 2 on the terminal block (TB15) on the in­door unit on one end to the terminal block on the MA re­motecontroller. (Non-polarized two-wire)
When performing a group operation of indoor units that
have different functions, "Automatic indoor/outdoor ad­dresssetup" is not available.
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal
block(TB5) on the indoor unit (IC) to the appropriate ter­minals on the terminal block (TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Interlock operation setting with all the indoor units in the
same system will automatically be made. (It is required that the Lossnay unit be turned on before the outdoo­runit.)
When performing an interlocked operation of part of the
indoor units in the system with a LOSSNAY unit, using a LOSSNAY unit alone without interlocking it with any units, performing an interlock operation of more than 16 indoor units with a LOSSNAY unit, or connecting two or more LOSSNAY units to the same refrigerant system, the automatic IC/OC address setup function is not avail­able.
5) Switch setting No address settings required.
(5) Address setting method
Proce-
dures
Unit or controller
1 Indoor unit Main unit IC No settings
2 LOSSNAY LC No settings
3MA
remote con­troller
4 Outdoor unit OCOSNo settings
5 Auxiliary
outdoor unit BCcontroller
Sub unit IC
Main
MA No settings remote con­troller
Sub
MA Sub remote con­troller
BC No settings
Address set-
ting range
required.
required.
required.
remote con­troller
required.
required.
Setting method Notes
- Port number setting is re-
Factory
setting
00 quired To perform a group opera­tion of indoor units that fea­ture different functions, the automatic IC/OC address setup function is not avail­able.
-00
-Main
Settings to be made with the Sub/Main switch
-00
-00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
27- 27 -
[ II Restrictions ]
2. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address setup for both indoor and outdoor units)
(1) Sample control wiring
Interlock operation with the ventilation unit
Leave the male connector on CN41 as it is. SW2-1 OFF
OS
52
TB3
M1 M2
L1 L2
Leave the male connector on CN41 as it is. SW2-1 OFF
TB7
M1 M2
S
TB3
M1 M2
L3
OC
51
TB7
M1 M2
BC
53
TB02
S
M1 M2
S
IC
01
TB5STB
M1M2 M1 M2 M1 M2
L4 L5
GroupGroup
15
12
IC
02
TB5STB
15
12
TB5
LC
05
S
M1 M2
TB02
57
BS
A1 B2
MA
S
L11
Group
IC
TB5
S
IC
L12 L13
15
TB
12
A1 B2
MA
IC
0403
TB5STB
IC
A1 B2
MA
15
12
LC
06
TB5
M1M2M1M2M1M2
S
0807
TB5
15
TB
12
S
A1 B2
TB5STB
M1M2M1M2
15
12
A1 B2
* If the BC address overlaps any of the addresses that are assigned to either the OC, OS, or BS, use a different, unused address. OC, OS, and BS addresses (lowest indoor unit address in the group plus +50) have higher priority than the BS address.
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) required
1 unit 2 units
When the P72 and P96 models are not in­cluded in the connected indoor units
When the P72 and P96 models are includ­ed in the connected indoor units
27 - 50 units
21 - 39 units
40 - 50 units
-
MA
MA
The table above shows the number of transmission
boosters that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 1.
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Same as [5] 1.
- 28 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Daisy-chain terminals M1 and M2 of the terminal block
for indoor-outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-out­door transmission line (TB02) on the main and sub BC controllers (BC and BS), and of the terminal block for in­door-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC and OS in the order of ca­pacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on BC and BS, and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.
(5) Address setting method
Proce-
dures
1 Indoor
Unit or controller
Main unit IC 01 to 50
Address
setting
range
unit
Sub unit
2 LOSSNAY LC 01 to 50
3MA
remote controller
Main remote controller
Sub remote controller
MA No set-
tings re­quired.
MA Sub
remote controller
4 Outdoor unit OCOS51 to 100
5 Auxiliary
outdoor
BCcon­troller (Sub)
BS 51 to 100
unit
BC control­ler (Main)
BC OC (or OS if it exists) +1
2) Transmission line for centralized control No connection is required.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block (TB5) on LOSSNAY (LC). (Non-po­larized two-wire)
Interlock setting between the indoor units and LOSS-
NAY units must be entered on the remote controller. (Re­fer to "IV [3] Interlock Settings via the MA Remote Controller" or the installation manual for the MA remote controller for the setting method.)
5) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main
unit in the group.
In a system with a sub BC controller,
make the settings for the indoor units in the following order.
(i) Indoor unit to be connected to the main
BC controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these units after assigning an ad­dress to all indoor units.
-Main
Settings to be made with the Sub/ Main switch
Assign sequential address to the out door
units in the same refrigerant circuit.
The outdoor units are automatically des-
ignated as OC and OS.(Note)
Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the indoor unit addresses.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con­troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif­ferent, unused address with­in the setting range.
The use of a sub BC control-
ler requires the connection of a main BC controller.
Fac-
tory set­ting
00
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
29- 29 -
[ II Restrictions ]
3. Group operation of units in a system with multiple outdoor units (1) Sample control wiring
L12
IC
01
15
12
m2
A1 B2
Leave the male connector on CN41 as it is. SW2-1 OFF
OS
52
TB3
M1 M2
TB7
M1 M2
L11
CN41 CN40 Replace
SW2-1 OFF
OC
51
TB3
M1 M2
TB7
S
Not Connect
M1 M2
S
Connect
BC
53
TB02
M1 M2
TB5STB
S
M1 M2 M1 M2
Group
TB5STB
Interlock operation with the ventilation unit
GroupGroup
TB5
M1 M2
LC
07
S
IC
03
15
12
A1 B2
TB5STB
M1 M2
IC
06
15
12
A1 B2
L31
Leave the male connector on CN41 as it is. SW2-1 OFF
M1 M2
M1 M2
TB3
TB7
L21
Leave the male connector on CN41 as it is. SW2-1 OFF
Not Connect
M1 M2
TB3
TB7
OC
55
S
Not Connect
M1 M2M1 M2
BC
57
TB02
S
M1 M2
OS
56
S
(2) Cautions
1) M-NET remote controller and MA remote controller can­not both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be performed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for transmission line for centralized control (TB7) on only one of the outdoor units.
6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) re­quired
1 unit 2 units
When the P72 and P96 mod­els are not included in the connected indoor units
When the P72 and P96 mod­els are included in the con­nected indoor units
27 - 50 units -
21 - 39 units 40 - 50 units
TB5
MA
m3
L22
IC
MA
Group
IC
0402
TB5STB
15
TB
S
12
15
M1 M2
12 12
A1 B2
MA
The left table shows the number of transmission boost-
ers that is required by the system with three BC control­lers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
(3) Maximum allowable length
1) Indoor/outdoor transmission line Maximum distance (1.25mm
L11+L12 200m [656ft] L21+L22 200m [656ft]
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger)
L12+L31+L22 500m [1640ft] L11+L31+L21 500m [1640ft]
3) MA remote controller wiring Same as [5] 1.
MA
IC
05
TB5 TB15
S
M1 M2
2
[AWG16] or larger)
- 30 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 2.
Shielded cable connection
Same as [5] 2.
2) Transmission line for centralized control Daisy-chain terminals M1 and M2 on the terminal block
for transmission line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC and OS in the same refrigerant circuit If a power supply unit is not connected to the transmis­sion line for centralized control, replace the power jump­er connector on the control board from CN41 to CN40 on only one of the outdoor units.
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC and OS in the order of ca­pacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Only use shielded cables.
(5) Address setting method
Proce-
dures
1 Indoor
Unit or controller
Main unit IC 01 to 50
Address
setting
range
unit
Sub unit
2 LOSSNAY LC 01 to 50
3MA
remote controller
Main remote controller
Sub remote controller
MA No set-
tings re­quired.
MA Sub
remote controller
4 Outdoor unit OCOS51 to 100
5 Auxiliary
outdoor
BCcon­troller (Sub)
BS 51 to 100
unit
BC control­ler (Main)
BC OC (or OS if it exists) +1
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the outdoor units (OC, OS) with the shield wire of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 2.
4) LOSSNAY connection Same as [5] 2.
5) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main
unit in the group.
In a system with a sub BC controller,
make the settings for the indoor units in the following order.
(i) Indoor unit to be connected to the main
BC controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these units after assigning an ad­dress to all indoor units.
-Main
Settings to be made with the Sub/ Main switch
Assign sequential address to the out door
units in the same refrigerant circuit.
The outdoor units are automatically des-
ignated as OC and OS.(Note)
Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the indoor unit addresses.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con­troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif­ferent, unused address with­in the setting range.
The use of a sub BC control-
ler requires the connection of a main BC controller.
Fac-
tory set­ting
00
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
31- 31 -
[ II Restrictions ]
4. A system in which a system controller is connected to the transmission line for centralized control and which is pow­ered from an outdoor unit
(1) Sample control wiring
Interlock operation with
IC
12
the ventilation unit
15
IC
03
TB5STB
15
12
TB5
M1 M2
LC
07
S
L11
Leave the male connector on CN41 as it is. SW2-1 OFF
OS
52
TB3
M1 M2 M1M2
CN41 CN40 Replace
SW2-1 OFF
OC
51
TB3
TB02
M1 M2
L12
BC
53
Group
IC
01
15
S
TB5STB
M1 M2
12
Group Group
02
TB5STB
M1 M2 M1M2
Not Connect
L21
Not Connect
TB7
M1 M2
S
Leave the male connector on CN41 as it is. SW2-1 OFF
OC
55
TB3
M1 M2M1 M2
TB7
S
Connect
Not Connect
L32
Note1
System controller
ABS
TB02
M1 M2
A1B
2
MA
L22
BC
Group
IC
57
TB5
M1 M2
TB
12
S
A1B
MA
S
TB5STB
15
m2 m1
2
m3
Note1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). Note2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
A1B
2
MA
IC
Group
0504
15
12
IC
06
TB5STB
15
12
A1B
MA
2
A1B
2
MA
LC
08
TB5
S
M1 M2M1 M2M1 M2
TB7
M1 M2
S
Leave the male connector on CN41 as it is. SW2-1 OFF
L31
OS
56
TB3
TB7
M1 M2 M1M2
S
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be per­formed only on one of the outdoor units.
5) Short-circuit the shield terminal (S terminal) and the earth terminal (
) on the terminal block for transmission line for centralized control (TB7) on the outdoor unit whose power jumper connector is mated with CN40.
6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) required
1 unit 2 units
When the P72 and P96 models are not included in the connected in­door units
When the P72 and P96 models are included in the connected indoor units
27 - 50 units -
21 - 39 units 40 - 50 units
The left table shows the number of transmission boosters
that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-men­tioned system, two additional indoor units can be connected.
7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec­tor on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 3.
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft]
3) MA remote controller wiring Same as [5] 1.
- 32 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 2. Only use shielded cables.
Shielded cable connection
Same as [5] 2.
2) Transmission line for centralized control
Daisy-chain terminals A and B on the system controller, ter­minals M1 and M2 on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in dif­ferent refrigerant circuits and on the outdoor units (OC and OS) in the same refrigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper con­nector on the control board from CN41 to CN40 on only one of the outdoor units. If a system controller is connected, set the central control switch (SW2-1) on the control board of all outdoor units to "ON."
The outdoor units in the same refrigerant circuit are au­tomatically designated as OC, OS1, and OS2 in the or­der of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Only use shielded cables.
Shielded cable connection
(5) Address setting method
Ad-
Proce-
dures
Unit or controller
dress
setting
range
1 Indoor
unit
Main unit IC 01 to
50
Sub unit
2 LOSSNAY LC 01 to
50
3MA
remote controller
Main remote con­troller
Sub remote con­troller
4 Outdoor unit (Note) OC
No set-
MA
tings re­quired.
Sub
MA
remote controller
51 to 100 Assign sequential address to the outdoor
OS
5 Auxiliary
outdoor
BCcon­troller (Sub)
51 to 100 Assign an address that equals the sum of the
BS
unit
BC control­ler (Main)
BC OC (or OS if it exists) +1
Daisy-chain the S terminal of the terminal block (TB7) on the system controller, OC, and OS with the shield of the shielded cable. Short-circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection Connect terminals M1 and M2 on the terminal block
(TB5) on the indoor unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-polarized two-wire)
Indoor units must be interlocked with the LOSSNAY unit
using the system controller. (Refer to the operation man­ual for the system controller for the setting method.) In­terlock setting from the remote controller is required if the ON/OFF remote controller alone or the LM adapter alone is connected.
5) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main unit
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the fol­lowing order.
(i) Indoor unit to be connected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
-
Settings to be made with the Sub/ Main switch
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
smallest address of the indoor units that are connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the indoor unit addresses.
Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con­troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif­ferent, unused address with­in the setting range.
The use of a sub BC control-
ler requires the connection of a main BC controller.
Fac-
tory set­ting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
33- 33 -
[ II Restrictions ]
5. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter)
(1) Sample control wiring
Interlock operation with
IC
12
the ventilation unit
15
GroupGroupGroup
IC
03
TB5STB
M2M1 M2M1
15
12
TB5
LC
07
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS
52
TB3
M2M1 M2M1
L11
CN41 CN40 Replace SW2-1 OFF ON
51
TB3
L12
OC
BC
53
TB02
M2M1
IC
01
15
S
TB5STB
M2M1 M2M1
12
02
TB5STB
L21
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
TB7
55
TB3
TB7
M2M1
OC
M2M1
M2M1
S
S
Not Connect
Connect
L25
BC
57
TB02
M2M1
S
Note1
System controller
ABS
Group Group
L31
TB7
M2M1
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS
56
TB3
M2M1
TB7
M2M1
S
Not Connect
S
Not Connect
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be per­formed only on one of the outdoor units.
5) Provide grounding to S terminal on the terminal block for transmis­sion line for centralized control (TB7) on only one of the outdoor units.
6) A maximum of 3 system controllers can be connected to the indoor­outdoor transmission line, with the exception that only one G(B)-50A may be connected.
7) When the total number of indoor units exceeds 20 (12 if one or more indoor units of the 72 model or above is connected), it may not be possible to connect a system controller to the indoor-outdoor trans­mission line.
8) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
TB5
A1B
2
MA
L22
IC
15
TB
S
12
A1B
MA
TB5STB
M2M1M2M1
m2 m1
2
m3
When the P72 and P96 models are not in­cluded in the connected indoor units
When the P72 and P96 models are includ­ed in the connected indoor units
The table above shows the number of transmission boosters that is
required by the system with three BC controllers. For each BC con­troller that is subtracted from the above-mentioned system, two ad­ditional indoor units can be connected.
A1B
2
MA
IC
0504
15
12
Note1 LM adapters cannot be connected to the indoor-outdoor transmission line.
IC
06
TB5STB
M2M1
(3) Maximum allowable length
1) Indoor/outdoor transmission line Maximum distance (1.25mm
L11+L12 200m [656ft] L21+L22 200m [656ft] L25 200m [656ft]
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger) L25+L31+L12(L11) 500m [1640ft] L12(L11)+L31+L22(L21) 500m [1640ft]
3) MA remote controller wiring Same as [5] 1.
A1B
2
MA
LC
08
TB5
15
12
A1B
MA
S
M2M1
2
Number of transmission booster (sold separately) required
1 unit 2 units
27 - 50 units
21 - 39 units
2
[AWG16] or larger)
40 - 50 units
-
- 34 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block for indoor­outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC controllers (BC and BS), of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC), and the S terminal of the system controller.(Non-polarized two-wire)
Only use shielded cables.
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC and BS, and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.
2) Transmission line for centralized control
Daisy-chain terminals M1 and M2 on the terminal block for transmis­sion line for centralized control (TB7) on the outdoor units (OC) in different refrigerant circuits and on the OC and OS in the same re­frigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the con­trol board from CN41 to CN40 on only one of the outdoor units. Set the central control switch (SW2-1) on the control board of all out­door units to "ON."
(5) Address setting method
Ad-
Proce-
dures
Unit or controller
dress
setting
range
1 Indoor
unit
Main unit IC 01 to
50
Sub unit
2 LOSSNAY LC 01 to
50
3MA
remote controller
Main remote con­troller
Sub remote con­troller
4 Outdoor unit OC
No set-
MA
tings re­quired.
Sub
MA
remote controller
51 to 100 Assign sequential address to the outdoor
OS
5 Auxiliary
outdoor
BCcon­troller (Sub)
51 to 100 Assign an address that equals the sum of the
BS
unit
BC control­ler (Main)
BC OC (or OS if it exists) +1
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal on the terminal block (TB7) on the out­door units (OC, OS) with the shield wire of the shielded cable. Short­circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the sys­tem
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5) on the in­door units (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po­larized two-wire)
Indoor units must be interlocked with the LOSSNAY unit using the
system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock setting from the remote controller is required if the ON/OFF remote controller alone is con­nected.
5) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main unit
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the fol­lowing order.
(i) Indoor unit to be connected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
-
Settings to be made with the Sub/ Main switch
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
smallest address of the indoor units that are connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the indoor unit addresses.
Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con­troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif­ferent, unused address with­in the setting range.
The use of a sub BC control-
ler requires the connection of a main BC controller.
Fac-
tory set­ting
00
00
Main
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
35- 35 -
[ II Restrictions ]
6. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (except LM adapter)
(1) Sample control wiring
L31
L11
Leave the male connector on CN41 as it is. SW2-1 OFF ON
M1M2
M1M2
Leave the male connector on CN41 as it is. SW2-1 OFF ON
M1M2
M1M2 M1M2
OS1
52
TB3
TB7
OS1
55
TB3
TB7
S
S
CN41 CN40 Replace SW2-1 OFF ON
Not Connect
L21
Leave the male connector on CN41 as it is. SW2-1 OFF ON
Not Connect
L32
OC
BC
51
TB3
M1M2 M1M2
TB7
S
M1M2
Connect
OC
BC
54
TB3
M1M2
TB7
M1M2
S
Not Connect
System controller
ABS
L12
Group
IC
1 1 2 1 222 12
53 57
TB02
01
15
TB5STB
S
M1M2
12
M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2 M1M2
m2
A1 B2
MA
m3
Group Group Group
IC
02
TB5STB
12
15
TB5STB
BS
IC
04
57
15
TB02
12
A1 B2
MA
L22
IC
07
15
TB5STB
S
12
A1 B2
MA
Group Group Group
IC
1 1 2 1 1
56 59
TB5
TB02
S
Note1
TB
15
S
12
M1M2 M1M2
A1 B2
MA
*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is).
IC
0503
TB5STB
m1
12
A1 B2
IC
06
15
TB5STB
M1M2
MA
323 1
15
12
M1M2
TB02
BS
IC
09
15
TB5STB
S
12
M1M2
A1 B2
MA
Numbers in the square indicate port numbers. Connection to BC controllers Interlock operation with the ventilation unit
*2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
TB5STB
TB5STB
M1M2
12
LC
13
15
TB5
S
BS
IC
08
61
15
TB02
12
IC
10
TB5
15
12
M1M2
IC
12
11
15
TB5STB
S
LC
14
S
12
A1 B2
MA
IC
1 2
12
TB5STB
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 2 MA remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replacement of male power jumper connector (CN41) must be per­formed only on one of the outdoor units.
5) Short-circuit the S (shield) terminal of the terminal block for the cen­tral control unit (TB7) and the ground terminal ( ) on the outdoor unit whose power jumper was moved from CN41 to CN40.
6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) required
1 unit 2 units
When the P72 and P96 models are not in­cluded in the connected indoor units
When the P72 and P96 models are includ­ed in the connected indoor units
27 - 50 units
21 - 39 units
40 - 50 units
-
The table above shows the number of transmission boost-
ers that is required by the system with three BC controllers. For each BC controller that is subtracted from the above­mentioned system, two additional indoor units can be con­nected.
7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec­tor on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line
2
Maximum distance (1.25mm
[AWG16] or larger) L11+L12 200m [656ft] L21+L22 200m [656ft]
2) Transmission line for centralized control Maximum line distance via outdoor unit
(1.25mm
2
[AWG16] or larger) L32+L31+L12(L11) 500m [1640ft] L32+L22(L21) 500m [1640ft] L12(L11)+L31+L22(L21) 500m[1640ft]
3) MA remote controller wiring Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16]) m1 200m [656ft] m2+m3 200m [656ft]
- 36 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 of the terminal block for indoor­outdoor transmission line (TB3) on the outdoor units (OC and OS), of the terminal block for indoor-outdoor transmission line (TB02) on the main and sub BC controllers (BC and BS), and of the terminal block for indoor-outdoor transmission line (TB5) on each indoor unit (IC). (Non-polarized two-wire)
Shielded cable connection
Daisy-chain the ground terminal ( ) on the outdoor units (OC and OS), the S terminal of the terminal block (TB02) on the BC (BS), and the S terminal of the terminal block (TB5) on the indoor unit (IC) with the shield of the shielded cable.
The outdoor units in the same refrigerant circuit are auto­matically designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have the same capacity, in the order of address from small to large).
Only use shielded cables.
2) Transmission line for centralized control
Daisy-chain terminals A and B on the terminal block for transmission line for centralized control (TB7) on the outdoor units (OC) in differ­ent refrigerant circuits and on the OC and OS in the same refrigerant circuit. If a power supply unit is not connected to the transmission line for centralized control, replace the power jumper connector on the con­trol board from CN41 to CN40 on only one of the outdoor units. Set the central control switch (SW2-1) on the control board of all out-
(5) Address setting method
Pro ce­du­res
1 Indoor
Unit or controller
Main unit IC 01 to 50
Address
setting
range
unit
Sub unit
2 LOSSNAY LC 01 to 50
3MA
remote controller
Main remote controller
Sub remote controller
4 Outdoor unit OC
No settings
MA
required.
Sub re-
MA
mote con­troller
51 to 100 The sum of the smallest address of the indoor units
OS
5 Auxiliary
outdoor unit
BC controller (Sub)
BC control­ler (Main)
51 to 100 Assign an address that equals the sum of the smallest
BS
BC 51 to 100 OC (or OS if it exists) +1
door units to "ON."
Only use shielded cables.
Shielded cable connection
Daisy-chain the S terminal of the terminal block (TB7) on the system controller, OC, and OS with the shield of the shielded cable. Short­circuit the earth terminal ( ) and the S terminal on the terminal block (TB7) on the outdoor unit whose power jumper connector is mated with CN40.
3) MA remote controller wiring Same as [5] 1.
When 2 remote controllers are connected to the system
Same as [5] 1.
Group operation of indoor units
Same as [5] 1.
4) LOSSNAY connection
Connect terminals M1 and M2 on the terminal block (TB5) on the in­door unit (IC) to the appropriate terminals on the terminal block for indoor-outdoor transmission line (TB5) on LOSSNAY (LC). (Non-po­larized two-wire)
Indoor units must be interlocked with the LOSSNAY unit us-
ing the system controller. (Refer to the operation manual for the system controller for the setting method.) Interlock set­ting from the remote controller is required if the ON/OFF re­mote controller alone or the LM adapter alone is connected.
5) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main unit in the
group.
In a system with a sub BC controller, make the set-
tings for the indoor units in the following order.
(i) Indoor unit to be connected to the main BC con-
troller (ii) Indoor unit to be connected to sub BC controller 1 (iii) Indoor unit to be connected to sub BC controller 2
Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit ad­dress +1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
-
Settings to be made with the Sub/Main switch
in the same system and 50.
Assign sequential address to the outdoor units in
the same refrigerant circuit.
The outdoor units are automatically designated as
OC and OS.(Note)
address of the indoor units that are connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units that feature different functions, designate the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the indoor unit addresses.
Make the same indoor unit group settings with the system controller as the ones that were made with the MA remote controller.
To set the address to 100,
set the rotary switches to 50.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con­troller overlaps any of the addresses that are assigne d to the outdoor units or to the sub BC controller, use a dif­ferent, unused address with­in the setting range.
The use of a sub BC control-
ler requires the connection of a main BC controller.
Fact
ory set­ting
00
00
Mai
n
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
37- 37 -
[ II Restrictions ]
[6] An Example of a System to which an M-NET Remote Controller is connected
(1) Sample control wiring
L11
Not Connect
L21
Not Connect
CN41 CN40 Replace SW2-1 OFF ON
OC
51
TB3
TB7
M1 M2
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OC
55
TB3
TB7
S
System controller
ABS
Connect
Not Connect
L32
Note1
Group
IC
01
Group
TB5STB
M1M2
A1 B2
101 RC
S
TB02
M1M2
BC
53
BC
57
TB02
M1M2
S
m3
A1 B2
154
RC
*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS
52
TB3
M1M2 M1M2
TB7
M1M2
S
Leave the male connector on CN41 as it is.
L31
SW2-1 OFF ON
OS
56
TB3
M1M2 M1M2
TB7
M1M2 M1M2
S
L12
Group Group
02
15
12
m1
L22
TB5STB
M1M2
A1 B2
102
RC
IC
0504
TB5
M1M2 M1M2 M1M2 M1 M2
A1 B2
104
RC
TB5STB
15
TB
12
S
m2
Interlock operation with the ventilation unit
IC
IC
03
15
12
IC
Group
TB5STB
A1 B2
103
RC
IC
06
15
12
TB5STB
A1 B2
106
RC
15
12
15
12
TB5
LC
07
TB5
S
M1M2M1M2
LC
08
S
(2) Cautions
1) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
2) No more than 3 M-NET remote controllers can be connected to a group of indoor units.
3) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
4) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units.
5) Provide an electrical path to ground for the S terminal on the terminal block for centralized control on only one of the out­door units.
6) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in par­allel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) required
1 unit 2 units 3 units
When the P72 and P96 models are not included in the connected indoor units
When the P72 and P96 models are included in the connected in­door units
15 - 34 units
11 - 26 units
35 - 50
units
27 - 42 units
-
43 - 50 units
The left table shows the number of transmission boosters
that is required by the system with three BC controllers. For each BC controller that is subtracted from the above-men­tioned system, two additional indoor units can be connected.
7) When a power supply unit is connected to the transmission line for centralized control, leave the power jumper connec­tor on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 3.
2) Transmission line for centralized control Same as [5] 4.
3) M-NET remote controller wiring Maximum overall line length
(0.3 to 1.25mm
2
[AWG22 to 16]) m1 10m [32ft] m2+m3 10m [32ft] If the standard-supplied cable must be extended, use a cable with a diameter of 1.25mm
2
[AWG16]. The section of the cable that exceeds 10m [32ft] must be included in the maximum indoor-outdoor transmission line distance described in (1). When connected to the terminal block on the Simple re­mote controller, use cables that meet the following cable size specifications: 0.75 - 1.25 mm
2
[AWG18-16].
- 38 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) M-NET remote controller wiring M-NET remote controller is connectable anywhere on
the indoor-outdoor transmission line.
(5) Address setting method
Ad-
Proce-
dures
Unit or controller
dress
setting
range
1 Indoor
unit
Main unit IC 01 to
50
Sub unit
2 LOSSNAY LC 01 to
50
3 M-NET
remote controller
Main remote con­troller
Sub remote con­troller
4 Outdoor unit OC
RC 101 to
150
RC 151 to
200
51 to 100 Assign sequential address to the outdoor
OS
5 Auxiliary
outdoor
BCcon­troller (Sub)
51 to 100 Assign an address that equals the sum of the
BS
unit
BC control­ler (Main)
BC OC (or OS if it exists) +1
When 2 remote controllers are connected to the sys­tem
Refer to the section on Switch Setting.
Performing a group operation (including the group operation of units in different refrigerant circuits).
Refer to the section on Switch Setting.
4) LOSSNAY connection Same as [5] 4.
5) Switch setting Address setting is required as follows.
Setting method Notes
Assign the smallest address to the main unit
in the group.
In a system with a sub BC controller, make
the settings for the indoor units in the fol­lowing order.
(i) Indoor unit to be connected to the main BC
controller
(ii) Indoor unit to be connected to sub BC
controller 1
(iii) Indoor unit to be connected to sub BC
controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Assign an arbitrary but unique address to each of these units after assigning an address to all indoor units.
Add 100 to the main unit address in the group
Add 150 to the main unit address in the group
units in the same refrigerant circuit.
The outdoor units are automatically desig-
nated as OC and OS.(Note)
smallest address of the indoor units that are connected to the sub BC controller and 50.
Port number setting is
required
To perform a group op-
eration of indoor units that have different func­tions, set the indoor unit in the group with the greatest number of functions as the main unit.
None of these addresses may overlap any of the indoor unit addresses.
It is not necessary to set the
100s digit.
To set the address to 200,
set the rotary switches to 00.
To set the address to 100,
set the rotary switches to 50.
If the addresses that is as-
signed to the main BC con­troller overlaps any of the addresses that are assigned to the outdoor units or to the sub BC controller, use a dif­ferent, unused address with­in the setting range.
The use of a sub BC control-
ler requires the connection of a main BC controller.
Fac-
tory set­ting
00
00
101
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
HWE0803A GB
39- 39 -
[ II Restrictions ]
[7] An Example of a System to which both MA Remote Controller and M-NET Remote Controller are connected
(1) Sample control wiring
L12
Group Group
IC
01
TB5STB
15
M1M2 M1M2 M1M2
12
IC
02
TB5STB
15
12
IC
06
TB5STB
15
12
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OS
52
TB3
M1M2
L11
CN41 CN40 Replace SW2-1 OFF ON
M1M2
51
TB3
OC
BC
53
TB02
M1M2
S
TB7
M1M2
S
Not Connect
Leave the male connector on CN41 as it is.
L31
SW2-1 OFF ON
OS
55
TB3
TB7
S
Not Connect
L21
TB7
M1M2
S
Leave the male connector on CN41 as it is.
SW2-1 OFF ON
OC
54
TB3
TB7
S
M1 M2M1 M2
Connect
Not Connect
L32
Note1
System controller
ABS
M1 M2M1 M2M1 M2
BC
56
TB02
S
(2) Cautions
1) Be sure to connect a system controller.
2) M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units.
3) Assign to the indoor units connected to the MA remote controller ad­dresses that are smaller than those of the indoor units that are con­nected to the M-NET remote controller.
4) No more than 2 M-NET remote controllers can be connected to a group of indoor units.
5) No more than 2 MA remote controllers can be connected to a group of indoor units.
6) Do not connect the terminal blocks (TB5) on the indoor units that are connected to different outdoor units with each other.
7) Replace the power jumper connector of the control board from CN41 to CN40 on only one of the outdoor units.
8) Provide an electrical path to grou nd for the S terminal on the terminal block for centralized control on only one of the outdoor units.
9) When the number of the connected indoor units is as shown in the table below, one or more transmission boosters (sold separately) are required. To connect two transmission boosters, connect them in parallel. (Observe the maximum number of connectable indoor units that are listed in the specifications for each outdoor unit.)
Number of transmission booster (sold separately) required
1 unit 2 units 3 units
When the P72 and P96 models are not included in the connected indoor units
When the P72and P96 models are included in the connected in­door units
15 - 34 units
11 - 26 units
35 - 50
units
27 - 42 units
-
43 - 50 units
A1 B2
A1 B2
106
MA
L22
IC
GroupGroup
IC
0403
TB5
TB
15
12
S
A1 B2
MA
*1 When only the LM adapter is connected, leave SW2-1 to OFF (as it is). *2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
TB5STB
A1 B2
104
RC
15
12
TB5STB
M1M2M1M2M1M2
RC
IC
05
15
12
The left table shows the number of transmission boost-
ers that is required by the system with three BC control­lers. For each BC controller that is subtracted from the above-mentioned system, two additional indoor units can be connected.
10) When a power supply unit is connected to the transmis­sion line for centralized control, leave the power jumper connector on CN41 as it is (factory setting).
(3) Maximum allowable length
1) Indoor/outdoor transmission line Same as [5] 3.
2) Transmission line for centralized control Same as [5] 4.
3) MA remote controller wiring Same as [5] 1.
4) M-NET remote controller wiring Same as [6]
- 40 -
GBHWE0803A
[ II Restrictions ]
(4) Wiring method
1) Indoor/outdoor transmission line Same as [5] 3.
Shielded cable connection
Same as [5] 1.
2) Transmission line for centralized control Same as [5] 4.
Shielded cable connection
Same as [5] 4.
3) MA remote controller wiring
When 2 remote controllers are connected to the sys­tem
Group operation of indoor units
Same as [5] 1.
4) M-NET remote controller wiring
When 2 remote controllers are connected to the sys­tem
Group operation of indoor units
Same as [6]
5) LOSSNAY connection Same as [5] 4.
6) Switch setting Address setting is required as follows.
HWE0803A GB
41- 41 -
[ II Restrictions ]
(5) Address setting method
Pro-
ce-
dure
Unit or controller
s
1 Opera-
tion with the
In­door unit
Main unit
IC 01 to
50
MA re­mote controller
2 Opera-
tion with the M-NET remote
MA re­mote con­troller
In­door unit
Sub unit
Main re­mote control­ler
Sub remote control­ler
Main unit
Sub unit
IC 01 to
50
No
MA
set­tings re­quired.
Sub
MA
remote control­ler
IC 01 to 50Assign the smallest address
IC 01 to
50
controller
M­NET re­mote con­troller
Main re­mote control­ler
Sub remote control­ler
RC 101 to
150
RC 151 to
200
3 LOSSNAY LC 01 to
50
4 Outdoor unit OCOS51 to
100
5 Auxiliary
outdoor
BCcontroller (Sub)
BS 51 to
100
unit
BC controller (Main)
BC OC (or OS if it exists) +1
Ad-
dress
set-
ting
range
Setting method Notes
Assign the smallest address to
the main unit in the group.
In a system with a sub BC con-
troller, make the settings for the indoor units in the following or­der.
(i) Indoor unit to be connected to
the main BC controller
(ii) Indoor unit to be connected to
sub BC controller 1
(iii) Indoor unit to be connected to
sub BC controller 2 Make the settings for the indoor units in the way that the formula "(i) < (ii) < (iii)" is true.
Assign sequential numbers start­ing with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Assign an address smaller than that of
the indoor unit that is connected to the M-NET remote controller.
Enter the same indoor unit group set-
tings on the system controller as the ones that were entered on the MA re­mote controller.
To perform a group operation of indoor
units that have different functions, des­ignate the indoor unit in the group with the greatest number of
Port number setting is required
-
Settings to be made according to the remote controller func­tion selection
Assign an address higher than those of
to the main unit in the group.
Assign sequential numbers starting with the address of the main unit in the same group +1. (Main unit address +1, main unit address +2, main unit address +3, etc.)
Add 100 to the main unit ad­dress in the group.
the indoor units that are connected to the MA remote controller.
Make the initial settings for the indoor
unit group settings via the system con­troller.
To perform a group operation of indoor
units that have different functions, des­ignate the indoor unit in the group with the greatest number of functions as the main unit.
Port number setting is required. Addresses that are assigned to the in-
door units that are connected to t he sub BC controller should be higher than the addresses that are assigned to the in­door units that are connected to the main BC controller.
It is not necessary to set the 100s
digit.
To set the address to 200, set it to
00.
Add 150 to the main unit ad­dress in the group.
Assign an arbitrary but unique address to each of these units
None of these addresses may over-
lap any of the indoor unit addresses. after assigning an address to all indoor units.
Assign sequential address to the
outdoor units in the same refrig­erant circuit.
The outdoor units are automati-
cally designated as OC and OS.(Note)
Assign an address that equals the sum of the smallest address of the indoor units that are connected to the sub BC controller and 50.
To set the address to 100, set it to 50.If the addresses that is assigned to the
main BC controller overlaps any of the addresses that are assigned to the out­door units or to the sub BC controller, use a different, unused address within the setting range.
The use of a sub BC controller requires
the connection of a main BC controller.
Facto­ry set-
ting
00
Main
00
101
00
00
The outdoor units in the same refrigerant circuit are automatically designated as OC and OS. They are designated as OC and OS in the descending order of capacity (ascending order of address if the capacities are the same).
- 42 -
GBHWE0803A
[ II Restrictions ]
[8] Restrictions on Pipe Length
(1) System that requires 16 BC controller ports or fewer <System with only the main BC controller or standard BC con-
troller>
Outdoor unit
*Use a main BC controller when connecting the outdoor units of P144 model or above.
Branch joint (CMY-Y102S-G2)
b
B
c
Maximum of 3 units per port Total capacity of P54 or below
Indoor
d
h2
HH'
h1
Reducer (P06 - P18 models) (Supplied with the BC Controller)
a
Indoor Indoor Indoor
(P06 - P54 models) (P72 or P96 models)
A
BC controller
Junction pipe (CMY-R160-J)
Unit: m [ft]
Operation Pipe sections Allowable length of pipes
Length Total pipe length A+B+a+b+c+d Refer to the restrictions on the total piping
length in the graph on the next page.
Total pipe length from the outdoor unit to the farthest indoor unit
Between outdoor unit and BC control-
A+B+d 165 [541] or less
(Equivalent length 190 [623] or less)
A 110 [360] or less
ler
*1
Height difference
Between BC controller and indoor unit B+d 40 [131] or less
Between indoor and outdoor units
Outdoor unit above indoor unit
Outdoor unit be-
H 50 [164] or less
H' 40 [131] or less
low indoor unit
Between indoor unit and BC controller h1 15[49](10[32]) or less
Between indoor units h2 15[49](10[32]) or less
*2
*2
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
1) To connect the P72 or P96 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J).
2) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
3) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
HWE0803A GB
- 43 -
[ II Restrictions ]
Restrictions on pipe length [PURY-P72, P96THMU-A, PURY-P72, P96YHMU-A]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
Aggregate length of all pipes(m[ft])
200
[656]
10 20 30 40 50 60 70 80 90
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
100 110
The height difference and the pipe length between BC controller and indoor units
70
[229]
60
[196]
50
[164]
40
[131]
30
[98]
20
[64]
Pipe length between main BC
10
controller and farthest indoor unit (m[ft])
[32]
0
0 5 10 15
Height difference between main BC controller and farthest indoor unit (m[ft])
[16] [32] [49]
HWE0803A GB
- 44 -
[ II Restrictions ]
(2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P120 model or
below.>
Outdoor unit
HH'
h1
BC controller (main)
Reducer (P06 - P18 models) (Supplied with the BC Controller)
Junction pipe
a
(CMY-R160-J)
Indoor Indoor Indoor Indoor
(P06 - P54 models) (P72 or P96 models)
Branch joint (CMY-Y202-G2)
A
b
(CMY-Y102L-G2) (CMY-Y102S-G2)
C
Branch joint (
CMY-Y102S-G2)
B
c
Maximum of 3 units per port Total capacity of P54 or below
d
BC controller (sub)
D
BC controller (sub)
E
Indoor
e
Indoor
h1
h3
h2
h1
f
Unit: m [ft]
Operation Pipe sections Allowable length of pipes
Length Total pipe length A+B+C+D+E+a+b+c+d+e+f Refer to the restrictions on the total pip-
ing length in the graphon the next page.
Total pipe length from the out­door unit to the farthest indoor
A+C+E+f 165 [541] or less
(Equivalent length 190 [623] or less)
unit
Between outdoor unit and BC
A 110 [360] or less
controller
*1
Height differ­ence
Between BC controller and in­door unit
Outdoor unit above in-
Between indoor and outdoor units
door unit
Outdoor unit
B+d or C+D+e
40 [131] or less
or C+E+f
H 50 [164] or less
H' 40 [131] or less below in­door unit
Between indoor unit and BC
h1 15 [49](10[32]) or less
*2
controller
Between indoor units h2 15 [49](10[32]) or less
*2
Between the BC controller (main or sub) and the sub BC
h3 15 [49] or less
controller
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
HWE0803A GB
- 45 -
[ II Restrictions ]
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers.
2) When connecting two sub BC controllers, observe the maximum allowable length in the table above.
3) When connecting two sub BC controllers, install them in parallel.
4) To connect the P36 through P54 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J) and merge the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.) It is also possible to connect the P36 through P54 models of units to a port, although the cooling performance will somewhat decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.) (The factory setting for DIP SW4-6 is OFF. )
5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
6) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or below (when two GB type controllers are connected P126 or below for both combined). The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below. If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with two sub controllers is P168 or below.
Restrictions on pipe length [PURY-P120THMU-A, PURY-P120YHMU-A]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
Aggregate length of all pipes(m[ft])
200
[656]
10 20 30 40 50 60 70 80 90
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
100 110
The height difference and the pipe length between BC controller and indoor units
70
[229]
60
[196]
50
[164]
40
[131]
30
[98]
20
[64]
Pipe length between main BC
10
controller and farthest indoor unit (m[ft])
[32]
0
0 5 10 15
Height difference between main BC controller and farthest indoor unit (m[ft])
[16] [32] [49]
HWE0803A GB
- 46 -
[ II Restrictions ]
(3) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144 model or
above.>
Branch joint (CMY-R100VBK) The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity
2
index of the two, regardless of the relative positions of the outdoor units or their addresses. If the distributor is placed in the outdoor unit that has a smaller capacity, refrigerant will not be properly distributed and compressor failure may result. (If outdoor units that have the same capacity are used in combination, the distributor can be placed in either outdoor unit.)
Branch joint (CMY-Y202-G2) (CMY-Y102L-G2)
A
BC controller (main)
Junction pipe
a
(CMY-R160-J)
Indoor Indoor Indoor Indoor
b
C
B
(CMY-Y102S-G2)
Branch joint (
CMY-Y102S-G2)
cd
Maximum of 3 units per port Total capacity of P54 or below
D
E
BC controller (sub)
BC controller (sub)
Indoor
e
Indoor
h1
h3
h2
f
h1
h4
HH'
Outdoor unit
1
Outdoor unit
F
Reducer (P06 - P18 models) (Supplied with the BC Controller)
h1
G
(P06 - P54 models) (P72 - P96 models)
Unit: m [ft]
Operation Pipe sections Allowable length of pipes
Length Total pipe length F+G+A+B+C+D+E+a+b+c+d+e+fRefer to the restrictions on the total pip-
ing length in the graph on the next page.
Total pipe length from the out­door unit to the farthest indoor
F(G)+A+C+E+f 165 [541] or less
(Equivalent length 190 [623] or less)
unit
Between outdoor unit and BC
F(G)+A 110 [360] or less
controller
Between BC controller and in­door unit
B+d or C+D+e
or C+E+f
40 [131] or less
*1
Between indoor units F+G 5 [16] or less
Height differ­ence
Between indoor
Outdoor unit above in­door unit
H 50 [164] or less
and outdoor units
Outdoor unit below in-
H' 40 [131] or less
door unit
Between indoor unit and BC
h1 15 [49](10[32]) or less
*2
controller
Between indoor units h2 15 [49](10[32]) or less
*2
Between the BC controller (main or sub) and the sub BC
h3 15 [49] or less
controller
Between outdoor units h4 0.1 [0.3] or less
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe
the restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
HWE0803A GB
- 47 -
[ II Restrictions ]
1) A system that requires more than 16 BC controller ports requires two or three BC controllers (main and sub), and three pipes will be used between the main and the sub BC controllers.
2) When connecting two sub BC controllers, observe the maximum allowable length in the table above.
3) When connecting two sub BC controllers, install them in parallel.
4) To connect the P36 through P54 models of indoor units, use an optional junction pipe kit (Model: CMY-R160-J) and merge the two ports before connecting them. (In that case, set DIP SW4-6 on the BC controller to ON.) It is also possible to connect the P36 through P54 models of units to a port, although the cooling performance will somewhat decrease. (In that case, set DIP SW4-6 on the BC controller to OFF.) (The factory setting for DIP SW4-6 is OFF.)
5) Do not connect the P72 or P96 models of indoor units and other models of indoor units at the same port.
6) Note the following when connecting multiple indoor units to a single port.
Those indoor units connected to the same port must be installed in the same room.Set the indoor temperature via the connected remote controller, and when connecting multiple remote controllers, configure
these controllers as a group by making appropriate settings. These indoor units can only be operated in the same mode.
7) The maximum capacity of the indoor units that is connectable to the CMB-P-NU-GB types of sub BC controllers is P126 or below (when two GB type controllers are connected P126 or below for both combined) . The maximum total capacity of indoor units that is connectable to the sub BC controller CMB-P1016NU-HB is P126 or below. If at least one CMB-P1016NU-HB unit is connected, the maximum total capacity of connectable indoor units to a system with two sub controllers is P168 or below.
HWE0803A GB
- 48 -
[ II Restrictions ]
Restrictions on pipe length
[PURY-P144, P168TSHMU-A] [PURY-P144, P168YSHMU-A]
[PURY-P216, P240TSHMU-A] [PURY-P216, P240YSHMU-A]
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
Aggregate length of all pipes(m[ft])
200
[656]
10 20 30 40 50 60 70 80 90
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
Aggregate length of all pipes(m[ft])
200
[656]
10 20 30 40 50 60 70 80 90
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
100
100
[PURY-P192TSHMU-A] [PURY-P192YSHMU-A]
110
110
1000
[3280]
900
[2952]
800
[2624]
700
[2296]
600
[1968]
500
[1640]
400
[1312]
300
[984]
Aggregate length of all pipes(m[ft])
200
[656]
10 20 30 40 50 60 70 80 90
[32] [64] [98] [131] [164] [196] [229] [262] [295] [328] [360]
Pipe length between outdoor unit and BC controller (m[ft])
100
110
The height difference and the pipe length between BC controller and indoor units
70
[229]
60
[196]
50
[164]
40
[131]
30
[98]
20
[64]
Pipe length between main BC
10
controller and farthest indoor unit (m[ft])
[32]
0
0 5 10 15
Height difference between main BC controller and farthest indoor unit (m[ft])
[16] [32] [49]
HWE0803A GB
- 49 -
[ II Restrictions ]
1. Refrigerant pipe size
(1) Between outdoor unit and the first twinning pipe (Part A)
Refrigerant pipe size Connection to outdoor unit and BC controller
Outdoor units
Low-pressure pipe High-pressure pipe Low-pressure pipe High-pressure pipe
72 ø19.05 [3/4"] ø15.88 [5/8"] ø19.05 [3/4"] ø15.88 [5/8"]
96 ø22.2 [7/8"]
120
ø19.05 [3/4"]
144
ø22.2[7/8"] ø22.2 [7/8"]168
192
216
ø28.58 [1-1/8"] ø28.58 [1-1/8"]
ø28.58 [1-1/8"] ø28.58 [1-1/8"]
240
(2) Between BC controller and indoor unit (Sections a, b, c, d, e, and f )
Refrigerant pipe size Indoor unit connection
Indoor unit
Liquid pipe Gas pipe Liquid pipe Gas pipe
P06, P08, P12, P15, P18 ø6.35 [1/4"] ø12.7 [1/2"] ø6.35 [1/4"] ø12.7 [1/2"]
P24, P27, P30
P36, P48, P54
P72
P96 ø22.2
ø9.52 [3/8"] ø15.88 [5/8"] ø9.52 [3/8"] ø15.88 [5/8"]
ø19.05 [3/4"]
ø12.7 [1/2"]
[7/8"]
Unit : mm [inch]
ø22.2 [7/8"]
ø19.05 [3/4"]
Unit : mm [inch]
(Flare connection for all models)
ø19.05 [3/4"]
ø12.7 [1/2"]
ø22.2
[7/8"]
(3) Between the main and sub BC controllers (Section C)
Unit : mm [inch]
Refrigerant pipe size (Brazed connection on all models )
Indoor unit
Liquid pipe High-pressure gas pipe Low-pressure gas pipe
- P72
P73 - P108
ø9.52 [3/8"]
ø15.88 [5/8"] ø19.05 [3/4"]
ø22.2 [7/8"]
ø19.05 [3/4"]
P109 - P126
ø12.7 [1/2"]
ø28.58 [1-1/8"]P127 - P144
P145 - P168 ø15.88 [5/8"]
ø22.2 [7/8"]
Select the proper size pipes for the main unit based on the total capacity of the indoor units that are connected to both sub BC controllers. Select the proper size pipes for the sub controller side based on the total capacity of the indoor units that are connected to the sub controller.
HWE0803A GB
- 50 -
[ II Restrictions ]
2. Connecting the BC controller
(1) Size of the pipe that fits the standard BC controller ports
P72 - P120 models
Connection: Brazed connection
To outdoor unit
*1 Reducer (Standard supplied parts)
P18 model or below
P24 - P54 models P72 or P96 models
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.
BC controller
IndoorIndoor
*2
Junction pipe kit (Model name: CMY-R160-J) (Optional accessory)
Indoor
Operation
Outdoor unit side PURY-P72THMU-A
PURY-P72YHMU-A
PURY-P96THMU-A PURY-P96YHMU-A
PURY-P120THMU-A PURY-P120YHMU-A
Indoor unit side ø9.52 [3/8"] (Flare connection)
Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)
A
B
IndoorIndoorIndoor
3*
Maximum of 3 units per port Total capacity of P30 or below (All units connected to the same port must be in the same operating mode.)
Unit : mm [inch]
Pipe sections
High-pressure side (gas) Low-pressure side (gas)
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
ø19.05 [3/4"]
(Brazed connection)
(Brazed connection)
ø28.58 [1-1/8"]
(Brazed connection)
ø15.88 [5/8"]
(Flare connection)
* BC controllers can only be connected to P72 - P120 models of outdoor units.
HWE0803A GB
- 51 -
[ II Restrictions ]
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect P36 - P96 models of indoor units (or when the total capacity of indoor units exceeds P31), use a junction pipe kit and merge the two nozzles.
50 [1-31/32"]
Liquid pipe side:3/8F (Flare connection)
Gas pipe side:5/8F
Liquid pipe side: 6.35[1/4"]ID Gas pipe side: 12.7[1/2"]ID
(Flare connection)
Liquid pipe side:3/8F (Flare connection)
Gas pipe side:5/8F (Flare connection)
234 [9-7/32"]
Liquid pipe side: 9.52[3/8”]ID
Gas pipe side: 19.05[3/4”]ID(*1)
Supplied with a thermal insulation cover
Note) Use the flare nut that is supplied with the BC controller.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P30 or below (in a system with a junction pipe: P96 or below)Maximum number of connectable indoor units: 3 unitsBranch joint: Use CMY-Y102S-G2 (optional accessory).Refrigerant pipe selection (size of the pipes A and B in the previous page) : Select the proper size pipes based
on the total capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units Liquid pipe Gas pipe
P54 or below ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]
Unit : mm [inch]
HWE0803A GB
- 52 -
[ II Restrictions ]
(2) Size of the pipe that fits the main BC controller ports
P72 - P240 models
Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)
To outdoor unit
Connection: Brazed connection
BC controller (main)
*1 Reducer (Standard supplied parts)
Indoor Indoor Indoor
P18 model or below
P24 - P54 models P72 or P96 models
*2 Junction pipe kit (Model name:CMY-R160-J) (Optional accessory)
A B
Indoor Indoor Indoor
3*
Maximum of 3 units per port Total capacity of P54 or below (All units connected to the same port must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use a junction pipe kit and merge the two nozzles.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)Maximum number of connectable indoor units: 3 unitsBranch joint: Use CMY-Y102S-G2 (optional accessory).Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units Liquid pipe Gas pipe
P54 or below ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]
Pipe sections
Outdoor unit side
Operation
PURY-P72THMU-A PURY-P72YHMU-A
High pressure side (Liquid) Low-pressure side (Gas)
ø15.88 [5/8"]
(Brazed connection)
PURY-P96THMU-A PURY-P96YHMU-A
PURY-P120THMU-A
ø19.05 [3/4"]
(Brazed connection)
PURY-P120YHMU-A
PURY-P144TSHMU-A PURY-P144YSHMU-A
PURY-P168TSHMU-A PURY-P168YSHMU-A
ø22.2 [7/8"]
(Brazed connection)
PURY-P192TSHMU-A PURY-P192YSHMU-A
PURY-P216TSHMU-A PURY-P216YSHMU-A
PURY-P240TSHMU-A
ø28.58 [1-1/8"]
(Brazed connection)
PURY-P240YSHMU-A
Indoor unit side ø9.52 [3/8"] (Flare connection) ø15.88 [5/8"] (Flare connection)
Unit : mm [inch]
Unit : mm [inch]
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
ø28.58 [1-1/8"]
(Brazed connection)
HWE0803A GB
- 53 -
[ II Restrictions ]
(3) Size of the pipe that fits the sub BC controller ports
Branch joint (Model name:CMY-Y102S-G2) (Optional accessory)
A B
Indoor Indoor Indoor
3*
Maximum of 3 units per port
To Main BC controller
*1 Reducer (Standard supplied parts)
Indoor Indoor Indoor
P18 model or below
Connection: Brazed connection
*2
BC controller (sub)
Junction pipe kit (Model name: CMY-R160-J) (Optional accessory)
P24 - P54 models P72 or P96 models
Total capacity of P54 or below (All units connected to the same port must be in the same operating mode.)
The ports of the BC controller accommodates the pipes on P24 - P54 models of indoor units. To connect other types of indoor units, follow the procedure below.
1) To connect P06 - P18 models of indoor units use the reducer that is supplied with the BC controller.
2) To connect the units between the P72 and P96 models of indoor units (or when the total capacity of indoor units is P55 or above), use a junction pipe kit and merge the two nozzles.
3) To connect multiple indoor units to a port (or to a junction pipe)
Maximum total capacity of connected indoor units: P54 or below (in a system with a junction pipe: P96 or below)Maximum number of connectable indoor units: 3 unitsBranch joint: Use CMY-Y102S-G2 (optional accessory).Refrigerant pipe selection (size of the pipes in sections A and B in the figure above): Select the proper based on the total
capacity of the downstream indoor units, using the table below as a reference.
Total capacity of indoor units Liquid pipe Gas pipe
P54 or below ø9.52 [3/8"] ø15.88 [5/8"]
P55 - P72 ø9.52 [3/8"] ø19.05 [3/4"]
P73 - P96 ø9.52 [3/8"] ø22.2 [7/8"]
Operation Pipe sections
Total capacity of the in­door units that are con­nected to the BC
High-pressure side
(liquid)
Low-pressure side
(gas)
controller
On the BC controller side
P72 model or below
P73 - P108
ø15.88 [5/8"]
(Brazed connection)
ø19.05 [3/4"]
ø19.05 [3/4"]
(Brazed connection)
ø22.2 [7/8"]
(Brazed connection)
(Brazed connection)
P109 - P126
P127 - P144
P145 - P168
ø22.2 [7/8"]
(Brazed connection)
ø28.58 [1-1/8"]
(Brazed connection)
Unit : mm [inch]
Unit : mm [inch]
Liquid pipe side
ø9.52 [3/8"]
(Brazed connection)
ø12.7 [1/2"]
(Brazed connection)
ø15.88 [5/8"]
(Brazed connection)
HWE0803A GB
- 54 -
III
Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit ..........................................................57
[2] Control Box of the Outdoor Unit.......................................................................................60
[3] Outdoor Unit Circuit Board............................................................................................... 64
[4] BC Controller Components.............................................................................................. 74
[5] Control Box of the BC Controller......................................................................................77
[6] BC Controller Circuit Board.............................................................................................. 78
HWE0803A GB
- 55 -
- 56 -
[ III Outdoor Unit Components ]
III Outdoor Unit Components
[1] Outdoor Unit Components and Refrigerant Circuit
1. Front view of a outdoor unit (1) PURY-P72, P96, P120THMU-A
PURY-P72, P96, P120YHMU-A
Fan guard
Fan
Fin guard
Heat exchanger
Front panel
Control Box
HWE0803A GB
- 57 -
[ III Outdoor Unit Components ]
2. Refrigerant circuit (1) PURY-P72THMU-A
PURY-P72YHMU-A
Check valve(CV7a)
4-way valve(21S4a)
Solenoid valve(SV2)
High-pressure switch (63H1)
Low pressure sensor (63LS)
High pressure sensor (63HS1)
Transformer box (YHMU-A only)
Accumulator (ACC)
Compressor cover
Solenoid valve(SV9)
Check valve(CV5a)
Solenoid valve block (SV4a, SV4b, SV4d)
Check valve (CV4a)
Check valve (CV3a)
Check valve (CV6a)
Check valve (CV10a)
Check valve (CV9a)
Check valve (CV8a)
Check valve block assembly (CV2a)
Solenoid valve(SV5b)
Solenoid valve (SV1a)
Oil separator (O/S)
Compressor (COMP)
High pressure check joint(CJ1)
Low pressure check joint(CJ2)
Refrigerant service valve on the low pressure side (BV1)
Solenoid valve(SV5c)
Refrigerant service valve on the high pressure side(BV2)
HWE0803A GB
- 58 -
[ III Outdoor Unit Components ]
(2) PURY-P96, P120THMU-A
PURY-P96, P120YHMU-A
Solenoid valve(SV2)
Low pressure sensor(63LS)
High-pressure switch (63H1)
High pressure sensor (63HS1)
Check valve(CV7a)
4-way valve(21S4a)
Solenoid valve(SV9)
Check valve(CV5a)
Solenoid valve block
(SV4a, SV4b, SV4c, SV4d)
Check valve
(CV6a) Check valve (CV3a)
Solenoid valve(SV5b)
Check valve (CV4a)
High pressure check joint(CJ1)
Refrigerant service valve on the low pressure side(BV1)
Solenoid valve(SV5c)
Refrigerant service valve on the high pressure side (BV2)
Check valve block assembly (CV2a)
Low pressure check joint(CJ2)
Transformer box (YHMU-A only)
Accumulator (ACC)
Compressor cover
Solenoid valve (SV1a)
Compressor(COMP)
Oil separator (O/S)
Check valve (CV10a)
Check valve (CV9a)
Check valve (CV8a)
HWE0803A GB
- 59 -
[ III Outdoor Unit Components ]
[2] Control Box of the Outdoor Unit
<HIGH VOLTAGE WARNING>
Control box houses high-voltage parts. When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components. Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and Check that the voltage across terminals FT-P and FT-N (YHMU) on the INV board or the voltage at both ends of the main capacitor (C1) (THMU) is 20VDC or below. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
1. PURY-P72THMU-A
DC reactor (DCL)
Electromagnetic relay(72C)
Rush current protection resistor (R1) Note.2
Noise filter
Note.2
Terminal block for
power supply
(TB1)
Note.1
Ground terminal
Fan board
INV board
Smoothing capacitor(C1)
Control board
M-NET board
Terminal block for transmission line (TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water­proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE0803A GB
- 60 -
[ III Outdoor Unit Components ]
2. PURY-P96, P120THMU-A
DC reactor (DCL)
Electromagnetic relay
(72C)
Diode stack
Noise filter
Current sensor
(ACCT3)
Current sensor
(DCCT1)
Terminal block for
power supply
(TB1)
Ground terminal
Smoothing capacitor(C1)
Note.2
Note.1
Fan board
Current sensor (ACCT2)
INV board Control board
IPM
Current sensor (ACCT1)
Terminal block for transmission line (TB3, TB7)
M-NET board
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water­proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE0803A GB
- 61 -
[ III Outdoor Unit Components ]
3. PURY-P72, P96, P120YHMU-A
Electromagnetic relay(72C)
DC reactor (DCL)
Noise filter
Terminal block for power supply
(TB1)
Fuse(F4)
Capacitor(C100)
Rush current protection resistor (R1,R5) Note.2
Fan board
Control board
M-NET board
Fuse(F5)
Ground
terminal
Note.1
INV board
Terminal block for transmission line (TB3, TB7)
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water­proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE0803A GB
- 62 -
[ III Outdoor Unit Components ]
4. Transformer Box (PURY-P72, P96, P120Y(T)HMU-A)
Transformer (T03)
Transformer (T02)
HWE0803A GB
- 63 -
[ III Outdoor Unit Components ]
[3] Outdoor Unit Circuit Board
1. Outdoor unit control board
CNAC2 L1 L2
CN505 72C driving output (THMU)
CN51
Output 12VDC Compressor ON/OFF output
Error output
Actuator driving output
CN72 72C driving output (YHMU)
CNDC Bus voltage input P N
CN2
Serial communication signal input GND
INV board
Output 17VDC
CN801 Pressure switch connection
CN332 Output 18VDC GND (Fan board)
CN4 GND Serial communication signal output
LEV driving output
LED1 Service LED
SWU1,2 Address switch
SW1-5
switch
Dip
Sensor input
LED3 Lit when powered
LED2 Lit during normal CPU operation
HWE0803A GB
CNAC L1 L2
LED3 Lit when powered
F01 Fuse 250V AC/3.15A
External signal input (contact input)
CN102
Power supply input for centralized control system (30VDC) Indoor/outdoor transmission line input/output (30VDC)
- 64 -
CN41 Power supply for
CN40
centralized control OFF Power supply for centralized control ON
CNVCC2 Output 12VDC Output 5VDC
CNIT Output 12VDC GND Output 5VDC Power supply detection input
Power supply ON/OFF signal output CNS2 Transmission line input/output for centralized control system (30VDC)
GND
[ III Outdoor Unit Components ]
2. M-NET board
(THMU only) F01 250V
3.15A
Grounding
CN03(THMU only) Bus voltage input P N
CN04 Bus voltage input (YHMU only) Bus voltage output (THMU only) P N
CN102
Power supply output for centralized control system (30VDC) Indoor/outdoor transmission line input/output (30VDC)
Grounding
Grounding
TB3 Indoor/outdoor transmission block
Ground terminal for transmission line
CNS2 Transmission line input/output for centralized control system (30VDC)
TB7 Terminal block for transmission line for centralized control
CNIT Input 12VDC GND Input 5VDC Power supply detection output Power supply ON/OFF signal input
LED1 Power supply for indoor transmission line
TP1,2 Check pins for indoor/outdoor transmission line
HWE0803A GB
- 65 -
[ III Outdoor Unit Components ]
3. INV board (1) PURY-P72THMU-A
SC-P1 Rectifier diode output (P)
C30,31,32 Smoothing capacitor
RSH1,2 Overcurrent detection resistor
CN6 Open: No-load operation setting Short-circuited: Normal setting
IGBT (Rear)
CN5V GND Output 5VDC
LED1 Lit: Inverter in normal operation Blink: Inverter error
CN4 GND
Serial communication signal output
CNDC Bus voltage output P N
(INV Boar)
CN2
S
erial communication signal output
SC-P2 Bus voltage Input(
TB-P(Note) Bus voltage output(P
P)
)
TB-N(Note) Bus voltage output
(N)
SC-T Input(L3)
CT3 Current sensor(
L3)
SC-S Input(L2)
CT12 Current sensor
SC-R Input(L1)
CT22 Current sensor
(U)
SC-U Inverter output(U)
GND Input 17VDC
SC-V Inverter output(V)
SC-W Inverter output(W)
(W)
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE0803A GB
- 66 -
[ III Outdoor Unit Components ]
(2) PURY-P96, P120THMU-A
CNCT2 Current (AC) sensor input ACCT1 ACCT2
CNCT Current (DC) sensor input
FT-N(Note) BUS voltage output
SC-P1 Bus voltage input/output(P)
(N)
IPM-P BUS voltage output (IPM input)
CNTH Thermistor input (THHS)
CNTYP Function setting input (Z26)
(P)
IPM-N BUS voltage input/output(N) (IPM input)
CNCT3 Current (AC) sensor input (ACCT3)
LED1 Inverter in normal operation
CNIPM
IPM driving power supply output and signal output
IPM error signal input (IPM output)
CNDC1 BUS voltage output P N
LED2 Inverter error
LED4 Lit during normal CPU operation
SW1 ON: No-load operation setting OFF: Normal setting : Fixed to OFF
CN5V GND Output 5VDC
CN2 Serial communication
signal output GND Output 17VDC
CN4 GND (Fan board) Serial communication
signal input
LED3 Lit while charging
CNFG Functional earth
F02 Fuse 250VAC 3.15A
CNDC2 BUS voltage input P N
CNDC3 BUS voltage output P N
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter­minals to remove them.
HWE0803A GB
- 67 -
[ III Outdoor Unit Components ]
(3) PURY-P72, P96, P120YHMU-A
Bus voltage check terminal (P) Note
IGBT (Rear)
CN1 Bus voltage output N
P Bus voltage check terminal (N) Note 1
SC-L1 Input(L1)
SC-L2 Input(L2)
SC-P1
SC-P2 Bus voltage Input(P)
Rectifier diode output (P)
CN6 Open: No-load operation setting
LED1 Lit: Inverter in normal operation Blink: Inverter error
Short-circuited: Normal setting
CN5V GND Output 5VDC
RSH1 Overcurrent detection resistor
CN4 GND
CNTYP Inverter board type
SC-V Inverter output(V)
SC-W Inverter output(W)
SC-U Inverter output(U)
(INV Board) Serial communication signal output
CN2
S
erial communication signal output GND Input 17VDC
SC-L3 Input(L3)
CT22 Current sensor(W)
CT3 Current sensor(L3)
CT12 Current sensor(U)
C30 C37 Smoothing capacitor
1) Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. (It takes about 10 minutes to discharge electricity after the power supply is turned off.)
HWE0803A GB
- 68 -
[ III Outdoor Unit Components ]
4. Fan board
(1) PURY-P72, P96, P120THMU-A
CNVDC Bus voltage input
NP
F01 Fuse 250VAC 15A
LED3 Lit during normal CPU operation
CN18V
Input 18VDC GND
CN4
GNDSerial communication signal output GND(Control boardSerial communication signal output
CN22
GND(INV boardInput 5VDC
Serial communication signal input
GND(INV boardInput 17VDC
CN21
Serial communication signal output
GND(INV boardInput 17VDC
R630 Overcurrent detection resistor
CNINV Inverter output
WVU
DIP IPM(Rear)
THBOX Thermistor (Control box internal temperature detection)
LED1 Inverter in normal operation
LED2 Inverter error
HWE0803A GB
- 69 -
[ III Outdoor Unit Components ]
(2) PURY-P72, P96, P120YHMU-A
CNVDC Bus voltage input N P
CNINV Inverter output W V U
R630,R631 Overcurrent detection resistor
DIP IPM Rear
CN18V Input 18VDC GND
LED3 Lit during normal CPU operation
CN4 GND Serial communication signal output
CN5
GND(Control board)
Serial communication signal output
CN21 Serial communication signal output GND(INV board) Input 17VDC
CN22 GND(INV board) Input 5VDC Serial communication signal input GND(INV board) Output 17VDC
THBOX Thermistor (Control box internal temperature detection)
LED1 Inverter in normal operation LED2 Inverter error
HWE0803A GB
- 70 -
[ III Outdoor Unit Components ]
5. Noise Filter
(1) PURY-P72THMU-A
F2 Fuse 250VAC 6.3A
F1 Fuse 250VAC 6.3A
Grounding
TB21 Input/output(L1)
CN02 Output
L1L2
TB22 Input/output(L2)
TB23 Input/output(L3)
CN01 Input
L3L2L1
HWE0803A GB
- 71 -
[ III Outdoor Unit Components ]
(2) PURY-P96, P120THMU-A
R1,2 Rush current protection resistor
F3 Fuse 250VAC 6.3A
Grounding
CN02 Output
L1L2
F1 Fuse 250VAC 6.3A
F2 Fuse 250VAC 6.3A
TB42 Bus voltage output(N)
TB31 Bus voltage output(P)
CN03 72C drive input
Electromagnetic relay
72C
Diode stack rectified voltage input (Diode stack output)
Output
Diode stack input
TB23 Input
L3) TB22
Input
L2
TB21 Input
L1
CN01 Input
L3L2L1
HWE0803A GB
- 72 -
[ III Outdoor Unit Components ]
(3) PURY-P72, P96, P120YHMU-A
CN4 Output (Rectified L2-L3 current) P N
CN2 Surge absorber circuit Surge absorber circuit Short circuit Short circuit
F1,F2,F3,F4 Fuse 250VAC 6.3A
Grounding
CN1A Input L1
CN5 Output (Rectified L2-L3 current) P N
CN6 Input L2 L3
Grounding
CN1B Input L3 L2
HWE0803A GB
TB21 Input/output(L1)
TB22 Input/output(L2)
- 73 -
TB23 Input/output(L3)
[ III Outdoor Unit Components ]
[4] BC Controller Components
1. CMB-P NU-G, GA
(1) Front
Liquid pipe (Indoor unit side)
Gas pipe (Indoor unit side)
(2) Rear view <G type>
Gas/Liquid separator
Tube in tube heat exchanger
TH12
PS1
TH11
SVM1 LEV3
LEV1
PS3
TH16
TH15
HWE0803A GB
- 74 -
[ III Outdoor Unit Components ]
(3) Rear view <GA type>
Gas/Liquid separator
Tube in tube heat exchanger
TH11
TH12
LEV2
TH16
PS3
TH15
PS1
LEV3
LEV1
SVM2
SVM1
HWE0803A GB
- 75 -
[ III Outdoor Unit Components ]
2. CMB-P NU-GB, HB
(1) Front
(2) Rear view
Liquid pipe (Indoor unit side)
Gas pipe (Indoor unit side)
TH12
LEV3
TH15
HWE0803A GB
- 76 -
[ III Outdoor Unit Components ]
[5] Control Box of the BC Controller
1. CMB-P1016NU-G, GA
Transformer
Terminal block for power supply
Terminal block for transmission line
Relay board
BC controller board
HWE0803A GB
- 77 -
[ III Outdoor Unit Components ]
[6] BC Controller Circuit Board
1. BC controller circuit board (BC board)
SW4
HWE0803A GB
SW5
SW6
- 78 -
SW1SW2
[ III Outdoor Unit Components ]
2. RELAY BOARD (RELAY 4 board)
3. RELAY BOARD (RELAY 10 board)
HWE0803A GB
- 79 -
- 80 -
IV
Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers ...................................83
[2] Group Settings and Interlock Settings via the ME Remote Controller .............................84
[3] Interlock Settings via the MA Remote Controller .............................................................88
[4] Using the built-in Temperature Sensor on the Remote Controller ...................................89
HWE0803A GB
- 81 -
- 82 -
[ IV Remote Controller ]
IV Remote Controller
[1] Functions and Specifications of MA and ME Remote Controllers
There are two types of remote controllers: M-NET (ME) remote controller, which is connected on the indoor-outdoor transmission line, and MA remote controller, which is connected to each indoor unit.
1. Comparison of functions and specifications between MA and ME remote controllers
Functions/specifications MA remote controller
*1*2
M-NET (ME) remote controller
*2*3
Remote controller address settings Not required Required
Indoor/outdoor unit address set­tings
Wiring method Non-polarized 2-core cable
Not required (required only by a system with one outdoor unit)
*4
Required
Non-polarized 2-core cable
To perform a group operation, daisy-
chain the indoor units using non-polar­ized 2-core cables.
Remote controller connection Connectable to any indoor unit in the
group
Interlock with the ventilation unit Each indoor unit can individually be in-
terlocked with a ventilation unit. (Set up via remote controller in the group.)
Changes to be made upon group­ing change
MA remote controller wiring between in­door units requires rewiring.
Connectable anywhere on the indoor-out­door transmission line
Each indoor unit can individually be inter­locked with a ventilation unit. (Set up via remote controller.)
Either the indoor unit address and remote controller address must both be changed, or the registration information must be changed via MELANS.
*1. MA remote controller refers to MA remote controller (PAR-20MAA, PAR-21MAA), MA simple remote controller, and wire-
less remote controller.
*2. Either the MA remote controller or the M-NET remote controller can be connected when a group operation of units in a
system with multiple outdoor units is conducted or when a system controller is connected. *3. M-NET remote controller refers to ME remote controller and ME simple remote controller. *4. Depending on the system configuration, some systems with one outdoor unit may require address settings.
2. Remote controller selection criteria
MA remote controller and M-NET remote controller have different functions and characteristics. Choose the one that better suits the requirements of a given system. Use the following criteria as a reference.
MA remote controller
*1*2
There is little likelihood of system expansion and group-
ing changes.
Grouping (floor plan) has been set at the time of instal-
lation.
M-NET (ME) remote controller
There is a likelihood of centralized installation of remote
controllers, system expansion, and grouping changes.
Grouping (floor plan) has not been set at the time of in-
stallation.
*1*2
To connect the remote controller directly to the OA pro-
cessing unit.
*1. M-NET remote controller and MA remote controller cannot both be connected to the same group of indoor units. *2. A system controller must be connected to a system to which both MA remote controller and M-NET remote controller are
connected.
<System with MA remote controller> <System with M-NET remote controllers>
Outdoor unit
M-NET transmission line (indoor/outdoor transmission line)
groupgroup
Outdoor unit
M-NET transmission line (indoor/outdoor transmission line)
groupgroup
BC
controller
MA remote controller
HWE0803A GB
Indoor unit
- 83 -
BC
controller
M-NET remote controller
Indoor unit
[ IV Remote Controller ]
[2] Group Settings and Interlock Settings via the ME Remote Controller
1. Group settings/interlock settings
Make the following settings to perform a group operation of units that are connected to different outdoor units or to manually set up the indoor/outdoor unit address.
(A) Group settings...........Registration of the indoor units to be controlled with the remote controller,
and search and deletion of registered information.
(B) Interlock settings........Registration of LOSSNAY units to be interlocked with the indoor units,
and search and deletion of registered information
[Operation Procedures]
(1) Address settings
Register the indoor unit to be controlled with the remote controller.
1
Bring up either the blinking display of HO by turning on the unit or the
normal display by pressing the ON/OFF button.
The display window must look like one of the two figures below to proceed to the next step.
C
G
E
STAND BY DEFROST
PAR-F27MEA
CENTRALLY CONTROLLED
DAILY
AUTO OFF
CLOCK
REMAINDER
˚C
TEMP.
CLOCKON→OFF
TIMER SET
ON OFF
1Hr.
NOT AVAILABLE
˚C
CHECK MODE TEST RUN LIMIT TEMP.
ON/OFF
FILTER
FILTER
CHECK TEST
F
?
A
D
[Blinking display of HO ]
Bring up the Group Setting window.
2
-Press and hold buttons [FILTER] and [ ] simultaneously for 2 seconds to bring up the display as
A
B
[Normal display]
shown below.
Indoor unit address display window
3
Select the unit address.
-
Select the address of the indoor unit to be registered by pressing
button
through the addresses.
4
Register the indoor unit whose address appears on the
C
[TEMP. ( ) or ( )] to advance or go back
display.
- Press button [TEST] to register the indoor unit address
D
whose address appears on the display.
- If registration is successfully completed, unit type will appear
on the display as shown in the figure below.
- If the selected address does not have a corresponding indoor
unit, an error message will appear on the display. Check the address, and try again.
<Successful completion of registration>
Unit type (Indoor unit in this case)
<Deletion error>
H
B
(B) Interlock Settings (A) Group Settings
6
Bring up the Interlock Setting window.
-Press button [ ] to bring up the following display.
G
Press again to go back to the Group Setting window as shown under step .
Indoor unit address display window
7
Bring up the address of the indoor unit and the address of the
2
Interlocked unit address display window
Both the indoor unit address and interlocked unit address will be displayed together.
To search for an address, go to section (2) Address Search.
LOSSNAY to be interlocked on the display.
- Select the address of the indoor unit to be registered by pressing button [TEMP. ( ) or ( )] to advance or go back through
C
the addresses.
- Select the address of the LOSSNAY unit to be interlocked by pressing button [TIMER SET ( ) or ( )] to advance or go back through the interlocked unit addresses.
8
Make the settings to interlock LOSSNAY units with indoor units.
- Press button [TEST] while both the indoor unit address and
H
D
the address of the LOSSNAY units to be interlocked are displayed to enter the interlock setting.
- Interlock setting can also be made by bringing up the LOSSNAY address in the indoor unit address display window and the indoor unit address in the interlocked unit address display window.
If registration is successfully
blinks to indicate a registration error. (Indicates that selected address does not have a corresponding unit.)
5
To register the addresses for multiple indoor units, repeat steps and above.
3
4
(Displayed alternately)
completed, the two displays as shown on the left will appear alternately. If the registration fails, will blink on the display. (Indicates that the selected address does not have a corresponding unit.)
To search for an address, go to section (2) Address Search.
NOTE : Interlock all the indoor units in the group with the LOSSNAY units; otherwise, the LOSSNAY units will not operate.
To next page.
HWE0803A GB
- 84 -
[ IV Remote Controller ]
(C) To return to the normal display When all the group settings and interlock settings are made, take the following step to go back to the normal display.
10
Press and hold buttons [FILTER] and [ ] simultaneously for 2 seconds to go back to the window as shown in step .
A
1
B
(2) Address search
To search for the address of indoor units that have been entered into the remote controller, follow steps and .
1
2
(A) To search group settings
11
Bring up the Group Setting window.
- Each pressing of button [ ] will bring up the address of a
E
registered indoor unit and its unit type on the display.
<Entry found>
Unit type (Indoor unit in this case)
<No entries found>
- When only one unit address is registered, the same address will remain on the display regardless of how many times the button is pressed.
- When the address of multiple units are registered (i.e. 011, 012, 013 ), they will be displayed one at a time in an ascending order with each pressing of button [ ] .
E
Repeat steps and in the previous page to interlock
9
all the indoor units in a group with the LOSSNAY unit.
To go back to the normal display, follow step .
7
8
To search for an address,
10
go to section (2) Address Search.
(B) Interlock setting search
After performing step , proceed as follows:
12
Bring up the address of the indoor unit to be searched on
6
the display.
- Select the address of the indoor unit to be searched by pressing
H
button [TIMER SET ( ) or ( )] to advance or go back through the interlocked addresses.
LOSSNAY can be searched in the same manner by bringing up the LOSSNAY address in the Interlocked unit address display window.
13
Bring up on the display the address of the LOSSNAY unit that was interlocked with the indoor unit in step .
- With each pressing of button [ ], the address of the
E
LOSSNAY and indoor unit that is interlocked with it will be displayed alternately.
Address of an interlocked LOSSNAY unit
(Displayed alternately)
12
14
To delete an address, go to section (3) Address Deletion.
Bring up the address of another registered unit on the display.
- After completing step , a subsequent pressing of button
E
[ ] will bring up the address of another registered
13
unit. (The display method is the same as the one in step .)
To go back to the normal display, follow step .
10
Address of another interlocked unit
(Displayed alternately)
To delete an address,
(3) Address deletion
go to section (3) Address Deletion .
The addresses of the indoor units that have been entered into the remote controller can be deleted by deleting the group settings. The interlock settings between units can be deleted by deleting the interlock settings. Follow the steps in section (2) Address Search to find the address to be deleted and perform deletion with the address being displayed in the display window. To delete an address, the address must first be bought up on the display.
15
Delete the registered indoor unit address or the interlock setting between units.
- Press button ? [CLOCK ON OFF] twice while either the indoor unit address or the address of the interlocked unit is displayed on the
F
display to delete the interlock setting.
13
HWE0803A GB
- 85 -
[ IV Remote Controller ]
(A) To delete group settings
(B) To delete interlock settings
<Successful completion of deletion>
will be displayed in the room temperature display window.
(Displayed alternately)
- If a transmission error occurs, the selected setting will not be deleted, and the display will appear as shown below. In this case, repeat the steps above.
<Deletion error>
will be displayed in the room temperature display window.
To go back to the normal display, follow step .
10
(4) Making (A) Group settings and (B) Interlock settings of a group from any arbitrary remote controller
(A) Group settings and (B) Interlock settings of a group can be made from any arbitrary remote controller. Refer to (B) Interlock Settings under section 1 Group Settings/Interlock Settings for operation procedures. Set the address as shown below.
(A) To make group settings Interlocked unit address display window...Remote controller address
Indoor unit address display window...........The address of the indoor unit to be controlled with the remote controller
(B) To make interlock settings Interlocked unit address display window...LOSSNAY address
Indoor unit address display window..........The address of the indoor unit to be interlocked with the LOSSNAY
If deletion is successfully completed, will appear in the unit type display window. If the deletion fails, will appear in the unit type display window. In this case, repeat the steps above.
- -
2. Remote controller function selection via the ME remote controller
In the remote controller function selection mode, the settings for four types of functions can be made or changed as necessary.
1) Skip-Auto-Mode setting The automatic operation mode that is supported by some simultaneous cooling/heating type units can be made unselectable via the ME remote controller.
2) Operation mode display selection mode (Display or non-display of COOL/HEAT during automatic operation mode) When the automatic operation mode is selected, the indoor unit will automatically perform a cooling or heating operation based on the room temperature. In this case, or will appear on the remote controller display. This setting can be changed so that only will appear on the display.
3) Room temperature display selection mode (Display or non-display of room temperature) Although the suction temperature is normally displayed on the remote controller, the setting can be changed so that it will not appear on the remote controller.
4) Narrowed preset temperature range mode The default temperature ranges are 19 C to 30 C in the cooling/dry mode and 17 C to 28 C in the heating mode and 19 C to 28 C in the auto mode.
By changing these ranges (raising the lower limit for the cooling/dry mode and lowering the upper limit for the heating mode), energy can be saved.
NOTE
When making the temperature range setting on the simultaneous cooling/heating type units that supports the automatic operation mode to save on energy consumption, enable the Skip-Auto-Mode setting to make the automatic operation mode unselectable. If the automatic operation mode is selected, the energy-saving function may not work properly.
When connected to the air conditioning units that do not support the automatic operation mode, the setting for the Skip-Auto-Mode, restricted preset temperature range mode (AUTO), and operation mode display selection mode are invalid. If an attempt is made to change the preset temperature range, “LIMIT TEMP.” appears on the display.
PAR-F27MEA
TEMP.
TIMER SET
CLOCKĺONĺOFF
ON/OFF
FILTER
CHECK TEST
Normal display
1 1
Remote controller function selection mode
Skip-Auto-Mode setting
Temperature range setting mode (AUTO)
Operation mode display selection mode (Display or non-display of the automatic mode)
5
Restricted preset temperature range mode (Cooling)
4
Restricted preset temperature range mode (Heating)
Room temperature display selection mode
[Function selection mode sequence on the remote controller]
*2
3
2
3
2
*2
3
2
3
2
3
2
3
*1 *1
2
[Normal display]
1
: Press and hold the [CHECK] and [ ] buttons simultaneously for two seconds.
2
: [SET TEMP.
3
: [SET TEMP.
2
3
*1 : Skip-Auto-Mode is enabled *2 : Skip-Auto-Mode is disabled
( ) ] ( ) ]
button button
HWE0803A GB
- 86 -
[ IV Remote Controller ]
[Operation Procedures]
1. Press the [ON/OFF] button on the remote controller to bring the unit to a stop. The display will appear as shown in the previous page (Normal display).
2. Press buttons [CHECK] and [ ] simultaneously for 2 seconds to go into the “Skip-Auto-Mode setting.” under the remote controller function selection mode. Press button [SET TEMP. ( )] or [SET TEMP. ( )] to go into the other four modes
1
2
3
under the remote controller function selection mode.
Skip-Auto-Mode setting (Making the automatic operation mode unselectable)
This setting is valid only when the controller is connected to the simultaneous cooling/heating type air conditioning units that support the automatic operation mode.
“ ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button switches
4
between “ON” and “OFF.”
[TIMER SET ( ) (( ))] button
When set to “ON,” the automatic operation mode is available for selection in the function selection mode. When set to “OFF,” the automatic operation mode is not available for selection in the function selection mode, and an automatic operation cannot be performed. (The automatic operation mode is skipped in the function selection mode sequence.)
Operation mode display selection mode (Changing the type of display that appears during the automatic mode operation)
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
will blink, and either
switch between “ON” and “OFF.”
“ON”or“
OFF” will light up.
Press button [TIMER SET ( ) or ( )] in this state to
4
[TIMER SET ( ) (( ))] button
When it is set to ON, will appear on the display during automatic operation mode. When it is set to OFF, only will appear on the display during automatic operation mode.
Restricted preset temperature range mode (The range of preset temperature can be changed.)
1) Temperature range setting for the cooling/dry mode
will light up in the display window, and the temperature range for the cooling/dry mode will appear on the display. [Lower limit temperature]: Appears in the preset temperature display window [Upper limit temperature: Appears in the time display window Switch between the Lower and Upper limit temperature setting by pressing the [CLOCK-ON-OFF] button. The selected temperature setting blinks.
[TIMER SET ( ) (( ))] button
[The left figure shows the display that appears when the current temperature range setting is between 19 C and 30 C in the Cool/Dry mode, and the lower limit temperature is selected to be set.]
Press button [TIMER SET ( ) or ( )] to set the lower limit temperature to the desired temperature.
4
[Settable range for the lower limit temperature] : 19 C 30 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 30 C 19 C (Settable up to the lower limit temperature that is shown on the display)
2) Temperature range setting for heating “ ” and the settable temperature range for heating appear on the display.
As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range.
5
[Settable range for the lower limit temperature] : 17 C 28 C (Settable up to the upper limit temperature that is shown on the display) [Settable range for the upper limit temperature] : 28 C 17 C (Settable up to the lower limit temperature that is shown on the display)
3) Temperature range setting for the automatic mode
When connected to the air conditioning units that do not support the automatic operation mode, the setting for this mode is invalid.
“ ” and the temperature range for the automatic operation mode appear on the display. As with the Cool/Dry mode, use the [CLOCK-ON-OFF] button and the [TIMER SET ( ) or ( )] to set the temperature range. [Settable range for the lower limit temperature] : 19 C
5
28 C (Settable up to the upper limit temperature that is shown on the display)
[Settable range for the upper limit temperature] : 28 C 19 C (Settable up to the lower limit temperature that is shown on the display)
5
4
4
Room temperature display selection mode (Switching between the display or non-display of room temperature on the controller)
“ 88 C ” blinks and either “ON” or “OFF” lights up on the controller. Pressing the [TIMER SET ( ) or ( )] button
4
switches between “ON” and “OFF.”
˚C ˚C
[TIMER SET ( ) (( ))] button
When set to “ON,” room temperature always appears on the display during operation. When set to “OFF,” room temperature does not appear on the display during operation.
HWE0803A GB
- 87 -
[ IV Remote Controller ]
[3] Interlock Settings via the MA Remote Controller
1. LOSSNAY interlock setting (Make this setting only when making an interlock settings between the LOSSNAY units and the Freeplan model of units.)
Make this setting only when necessary.
Perform this operation to enter the interlock setting between the LOSSNAY and the indoor units to which the remote controller is connected, or to search and delete registered information.
In the following example, the address of the indoor unit is 05 and the address of the LOSSNAY unit is 30.
[Operation Procedures]
Press the [ON/OFF] button on the remote controller to bring the unit to a stop.
1
The display window on the remote controller must look like the figure below to proceed to step .
Press and hold the [FILTER] and [ ] buttons simultaneously for two seconds to perform a search for the LOSSNAY that is interlocked with the
2
indoor unit to which the remote controller is connected.
Search result
3
- The indoor unit address and the interlocked LOSSNAY address will appear alternately.
<Indoor unit address and indoor unit> <LOSSNAY address and LOSSNAY>
- Without interlocked LOSSNAY settings
2
4
If no settings are necessary, exit the window by pressing and holding the [FILTER] and [ ] buttons simultaneously for 2 seconds. Go to step 1. Registration Procedures to make the interlock settings with LOSSNAY units, or go to step 2. Search Procedures to search for a particular LOSSNAY unit. Go to step 3. Deletion Procedures to delete any LOSSNAY settings.
< 1. Registration Procedures >
5
To interlock an indoor unit with a LOSSNAY unit, press the [ TEMP. ( ) or ( )] button on the remote controller that is connected to the indoor unit, and select its address (01 to 50).
6
Press the [ CLOCK ( ) or ( )] button to select the address of the LOSSNAY to be interlocked (01 to 50).
Indoor unit address LOSSNAY address
7
Press the [TEST] button to register the address of the selected indoor unit and the interlocked LOSSNAY unit.
- Registration completed The registered indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Registration error If the registration fails, the indoor unit address and the LOSSNAY address will be displayed alternately.
Registration cannot be completed: The selected unit address does not have a corresponding indoor unit or a LOSSNAY unit. Registration cannot be completed: Another LOSSNAY has already been interlocked with the selected indoor unit.
HWE0803A GB
- 88 -
[ IV Remote Controller ]
< 2. Search Procedures >
8
To search for the LOSSNAY unit that is interlocked with a particular indoor unit, enter the address of the indoor unit into the remote controller that is connected to it.
<Indoor unit address>
9
Press the [ MENU] button to search for the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
- Search completed (With a LOSSNAY connection) The indoor unit address and IC, and the interlocked LOSSNAY address and LC will appear alternately.
- Search completed (No interlocked settings with a LOSSNAY exist.)
- The selected address does not have a corresponding indoor unit.
< 3. Deletion Procedures >
Take the following steps to delete the interlock setting between a LOSSNAY unit and the interlocked indoor unit from the remote controller that is connected to the indoor unit. Find the address of the LOSSNAY to be deleted (See section 2. Search Procedures. ), and bring up the result of the search for both the
10
indoor unit and LOSSNAY on the display.
11
Press the [ ON/OFF] button twice to delete the address of the LOSSNAY unit that is interlocked with the selected indoor unit.
- Registration completed The indoor unit address and , and the interlocked LOSSNAY address and will appear alternately.
-Deletion error If the deletion fails
[4] Using the built-in Temperature Sensor on the Remote Controller
1. Selecting the position of temperature detection (Factory setting: SW1-1 on the controller board on the indoor unit is set to OFF.)
To use the built-in sensor on the remote controller, set the SW1-1 on the controller board on the indoor unit to ON.
Some models of remote controllers are not equipped with a built-in temperature sensor. Use the built-in temperature sensor
on the indoor unit instead.
When using the built-in sensor on the remote controller, install the remote controller where room temperature can be detected.
HWE0803A GB
- 89 -
- 90 -
V
Electrical Wiring Diagram
[1] Electrical Wiring Diagram of the Outdoor Unit .................................................................93
[2] Electrical Wiring Diagram of the BC Controller................................................................96
[3] Electrical Wiring Diagram of Transmission Booster.......................................................105
HWE0803A GB
- 91 -
Loading...