Make sure that the inside and outside of refrigerant piping is clean and it has no contamination
such as sulfur hazardous for use, oxides, dirt,
shaving particles, etc.
In addition, use pipes with specified thickness.
Store the piping to be used during installation
indoors and keep both ends of the piping sealed
until just before brazing. (Leave elbow joints, etc.
in their packaging.)
Use ester oil, ether oil or alkylbenzene oil (small
amount) as the refrigerant oil applied to flares
and flange connections.
In case of using the existing pipes for R22, be careful with
the followings.
· Be sure to clean the pipes and make sure that the insides
of the pipes are clean.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
Do not use refrigerant other than R410A.
If other refrigerant (R22 etc.) is used, chlorine in refrigerant can cause deterioration of refrigerant oil etc.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil etc.
Use the following tools specifically designed for
use with R410A refrigerant.
The following tools are necessary to use R410A refrigerant.
Keep the tools with care.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigerant will change and the efficiency will be lowered.
Flare tool
Electronic refrigerant
charging scale
Vacuum pump adaptor
Size adjustment gauge
Gauge manifold
Torque wrench
Gas leak detector
Charge hose
Tools for R410A
Contamination inside refrigerant piping can cause deterioration of refrigerant oil etc.
If dirt, dust or moisture enter into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of compressor.
If large amount of mineral oil enter, that can cause deterioration of refrigerant oil etc.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
3-1. CAUTIONS RELATED TO NEW REFRIGERANT
Cautions for units utilizing refrigerant R410A
[1] Cautions for service
(1) Perform service after collecting the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) When performing service, install a filter drier simultaneously.
Be sure to use a filter drier for new refrigerant.
[2] Additional refrigerant charge
When charging directly from cylinder
· Check that cylinder for R410A on the market is syphon type.
· Charging should be performed with the cylinder of syphon stood vertically. (Refrigerant is charged from liquid phase.)
3
Unit
Gravimeter
[3] Service tools
Use the below service tools as exclusive tools for R410A refrigerant.
No.Specifications
1Gauge manifold·Only for R410A
·Use the existing fitting
·Use high-tension side pressure of 5.3MPa·G or over.
2Charge hose·Only for R410A
·Use pressure performance of 5.09MPa·G or over.
3Electronic scale
4Gas leak detector·Use the detector for R134a, R407C or R410A.
5Adaptor for reverse flow check·Attach on vacuum pump.
6Refrigerant charge base
7Refrigerant cylinder·Only for R410ATop of cylinder (Pink)
Bender
Pipe cutter
Welder and nitrogen gas cylinder
Refrigerant charging scale
Vacuum gauge or thermistor vacuum gauge and
vacuum valve
Charging cylinder
Air purge, refrigerant charge and
Operation check
Gas leak check
Collection of refrigerant
Refrigerant charge
Apply to flared section
Prevent compressor malfunction
when charging refrigerant by
spraying liquid refrigerant
Prevent gas from blowing out
when detaching charge hose
Vacuum drying and air
purge
Flaring work of piping
Bend the pipes
Cut the pipes
Weld the pipes
Charge refrigerant
Check the degree of vacuum. (Vacuum
valve prevents back flow of oil and refrigerant to thermistor vacuum gauge)
Charge refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Tool for HFC refrigerant
Tool exclusive for R410A
Tool exclusive for R410A
Ester oil and alkylbenzene
oil (minimum amount)
Tool exclusive for R410A
Tool exclusive for R410A
Tools for other refrigerants can
be used if equipped with adopter for reverse flow check
Tools for other refrigerants
can be used by adjusting
flaring dimension
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants can be used
Tools for other refrigerants
can be used
Tool exclusive for R410A
Tools and materialsUseR410A toolsCan R22 tools be used?
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
Can R407C tools be used?
Ester oil:
Alkylbenzene oil: minimum amount
(Usable if equipped
with adopter for rever se flow)
(Usable by adjusting
flaring dimension)
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.
New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same
as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working
pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
1Thickness of pipes
Because the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness
shown below. (Never use pipes of 0.7mm or below.)
2Dimensions of flare cutting and flare nut
The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that,
R410A is a refrigerant, which has higher risk of leakage because of its working pressure higher than that of other refriger-
ants. Therefore, to enhance airtightness and intensity, flare cutting dimension of copper pipe for R410A have been specified separately from the dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also
have partly been changed to increase intensity as shown below. Set copper pipe correctly referring to copper pipe flaring
dimensions for R410A below. For 1/2” and 5/8”, the dimension B changes.
Use torque wrench corresponding to each dimension.
Dimension A
3Tools for R410A (The following table shows whether conventional tools can be used or not.)
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
(Max.30m)
The refrigerant circuit with LEV(Linear Expansion Valve) and Accumlator always control the optimal refrigerant
level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done. It also helps to speed up the installation time.
(1).UKPUH-P71YHA(1).UK
(1).UK PUH-P100VHA(1).UK
(1).UK PUH-P100YHA(1).UK
(1).UK
6
5SPECIFICATIONS
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
FanFan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Mode
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Service Ref.
PUH-P71VHA/YHA
(1).UKPUH-P100VHA/YHA(1).UK
Cooling
12.03/4.29
25.5
NN33VAAMT/ NN33YCAMT
2.2
(V) Internal thermostat
HP switch
Discharge thermo
25
0.070
55(1940)
49
50
93(205)
3.6(7.9)
30.5
NN40VAAMT/ NN40YCAMT
2.7
(Y) Thermal relay
HP switch
Discharge thermo
25
0.110
65(2290)
50
52
94(207)
4.4(9.7)
Propeller fan o 1
943(37-1/8)
1.30(MEL56)
Max. 50m
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
Plate fin coil
Reverse cycle
950(37-3/8)
330+30(13+1-3/16)
R410A
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 50m
Heating
11.98/4.28
Cooling
15.07/5.39
Heating
14.48/5.18
Single, 50Hz, 230V/ 3Phase, 50Hz, 400V(4wires)
OUTDOOR UNIT
REFRIGERANT PIPING
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Power supply (phase, cycle, voltage)
Running current
Max. current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
FanFan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
Mode
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Service Ref.
PUH-P140YHA
(1).UKPUH-P125YHA(1).UK
Cooling
6.79
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
Line start
Discharge thermo, HP switch
Thermal relay
Plate fin coil
Propeller fan o 2
0.070+0.070
100(3,530)
Reverse cycle
950(37-3/8)
330+30(13+1-3/16)
1,350(53-1/8)
131(289)
R410A
5.0(11.0)
2.10(MEL56)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 50m
Max. 50m
Heating
6.57
Cooling
8.55
18.7
BN65YEGMT
4.6
25
51
53
15.1
BN52YEGMT
3.7
25
50
52
Heating
8.45
3Phase, 50Hz, 400V
OUTDOOR UNIT
REFRIGERANT PIPING
7
Service Ref.
Mode
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Crankcase heater
Heat exchanger
FanFan(drive) o No.
OUTDOOR UNIT
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Max. current
Model
Motor output
Starter type
Protection devices
Fan motor output
Airflow
Charge
Oil (Model)
/min(CFM
K
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
A
A
kW
W
kW
dB
dB
L
PU-P71VHA/YHA
Cooling
Single, 50Hz, 230V / 3Phase, 50Hz, 400V(4wires)
12.03/4.29
NN33VAAMT/ NN33YCAMT
(V) Internal thermostat
HP switch
Discharge thermo
0.070
)
55(1940)
93(205)
3.6(7.9)
(1).UKPU-P100VHA/YHA(1).UK
25.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NN40VAAMT/ NN40YCAMT
2.2
Line start
(Y) Thermal relay
Discharge thermo
25
Plate fin coil
Propeller fan o 1
–
49
–
950(37-3/8)
330+30(13+1-3/16)
943(37-1/8)
R410A
1.30(MEL56)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 50m
Max. 50m
Cooling
15.07/5.18
30.5
2.7
HP switch
25
0.110
65(2290)
50
–
94(207)
4.4(9.7)
Service Ref.
Mode
Power supply (phase, cycle, voltage)
External finish
Refrigerant control
Compressor
Crankcase heater
Heat exchanger
FanFan(drive) o No.
OUTDOOR UNIT
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
REFRIGERANT PIPING
Running current
Max. current
Model
Motor output
Starter type
Protection devices
Fan motor output
Airflow
Charge
Oil (Model)
/min(CFM
K
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
mm(in.)
mm(in.)
A
A
kW
W
kW
dB
dB
L
PU-P140YHA
Cooling
6.79
15.1
BN52YEGMT
3.7
25
)
50
–
3Phase, 50Hz, 400V
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
BN65YEGMT
Line start
Discharge thermo, HP switch
Thermal relay
Plate fin coil
Propeller fan o 2
0.070+0.070
100(3,530)
–
950(37-3/8)
330+30(13+1-3/16)
1,350(53-1/8)
131(289)
R410A
5.0(11.0)
2.10(MEL56)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 50m
Max. 50m
(1).UKPU-P125YHA(1).UK
Cooling
8.55
18.7
4.6
25
51
–
8
6DATA
Piping length (one way)
10m
20m
30m
40m
50m
Factory
charged
3.4
4.2
4.8
3.5
4.3
4.9
3.6
4.4
5.0
4.2
5.0
5.6
4.8
5.6
6.2
3.6
4.4
5.0
Service Ref.
PUH-P71VHA/YHA(1).UK
PU-P71VHA/YHA
(1).UK
PUH-P100VHA/YHA
(1).UK
PU-P100VHA/YHA
(1).UK
PUH-P125/140YHA
(1).UK
PU-P125/140YHA
(1).UK
U-V
(R-C)
U-W
(S-C)
W-V
Unit
Compressor model
Winding
Resistance
( " )
NN33YCAMT
(at 20°C)
4.64
4.64
4.64
0.63
1.55
–
3.32
3.32
3.32
NN33VAAMT
0.68
1.80
–
PUH-P71VHA
(1).UK
PU-P71VHA
(1).UK
PUH-P71YHA
(1).UK
PU-P71YHA
(1).UK
NN40YCAMT
NN40VAAMT
PUH-P100VHA
(1).UK
PU-P100VHA
(1).UK
PUH-P100YHA
(1).UK
PU-P100YHA
(1).UK
U-V
U-W
W-V
Unit
Compressor model
Winding
Resistance
( " )
(at 20°C)
2.149
2.149
2.149
1.794
1.794
1.794
BN65YEGMT
BN52YEGMT
PUH-P125YHA
(1).UK
PU-P125YHA
(1).UK
PUH-P140YHA
(1).UK
PU-P140YHA
(1).UK
6-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
6-2. COMPRESSOR TECHNICAL DATA
PRE-CHARGED REFRIGERANT IS
SUPPLIED FOR PIPING LENGTH AT
SHIPMENT.
9
6-3. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
PUH-P100VHA(1).UK
PUH-P100YHA
(1).UK
PU-P100VHA
(1).UK
PU-P100YHA
(1).UK
COOLING
MODE
HEATING
50
SPL(dB)
52
LINE
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
PUH-P125YHA(1).UK
PU-P125YHA
(1).UK
COOLING
MODE
HEATING
50
SPL(dB)
52
LINE
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
BAND CENTER FREQUENCIES, Hz
PUH-P71VHA(1).UK
PUH-P71YHA
(1).UK
PU-P71VHA
(1).UK
PU-P71YHA
(1).UK
COOLING
MODE
HEATING
49
SPL(dB)
51
LINE
10
PUH-P140YHA(1).UK
PU-P140YHA
90
80
(1).UK
MODE
COOLING
HEATING
SPL(dB)
51
53
LINE
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
HEARING FOR
CONTINUOUS
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
NOISE
10
631252505001000 2000 4000 8000
MICROPHONE
1.5m
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
BAND CENTER FREQUENCIES, Hz
1m
UNIT
GROUND
11
6-4. STANDARD OPERATION DATA
TotalElectrical circuitRefrigerant circuitIndoor side
Outdoor
side
Representative matching
SHF
BF
W
kW
Mode
Capacity
Input
PLA-RP71AAPLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
PLA-RP71AAPLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
Cooling
8,000
2.83
Heating
9,000
2.82
Cooling
10,000
3.53
Heating
11,500
3.40
Cooling
12,300
4.36
Heating
14,300
4.23
Cooling
14,200
5.41
Heating
17,000
5.35
12.03/4.29
2.99
(30.4)
0.79
(8.0)
76.9
49.7
3.8
5
27
19
12.8
35
24
0.74
0.11
11.98/4.28
2.55
(26.0)
0.53
(5.4)
85.1
41.0
6.5
5
20
15
44.5
7
6
—
—
15.07/5.39
3.16
(32.2)
0.91
(9.3)
78.2
49.9
4.2
5
27
19
13.4
35
24
0.78
0.06
14.48/5.18
2.67
(27.2)
0.74
(7.5)
81.4
40.9
4.0
5
20
15
42.2
7
6
—
—
6.79
3.00
(30.6)
0.75
(7.7)
80.5
38.7
2.4
5
27
19
12.3
35
24
0.74
0.05
6.57
2.97
(30.3)
0.74
(7.5)
78.1
46.2
-0.5
5
20
15
46.1
7
6
—
—
8.55
3.05
(31.1)
0.94
(9.6)
78.0
49.9
-0.8
5
27
19
11.2
35
24
0.70
0.08
8.45
3.68
(37.5)
0.61
(6.2)
82.4
56.3
-1.2
5
20
15
51.6
7
6
—
—
1 , 50
230
0.79
1/3 , 50
230/400
1 , 50
230
0.92
1/3 , 50
230/400
1 , 50
230
0.92
3 , 50
400
1 , 50
230
0.92
3 , 50
400
Phase , Hz
Volts
Amperes
Outdoor unit
Phase , Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
A
V
A
MPa
(Of/F)
MPa
(Of/F)
°C
°C
°C
m
°C
°C
°C
°C
°C
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
PUH-P71VHA
PUH-P71YHA
PUH-P100VHA
PUH-P100YHA
PUH-P125YHA
PUH-P140YHA
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/ff)
12
TotalElectrical circuitRefrigerant circuitIndoor side
Outdoor
side
SHF
BF
W
kW
V
A
V
A
MPa
(Of/F)
MPa
(Of/F)
°C
°C
°C
m
°C
°C
°C
°C
°C
Mode
Capacity
Input
Indoor unit
Phase , Hz
Volts
Amperes
Outdoor unit
Phase , Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Cooling
8,000
2.83
1 , 50
230
0.79
1/3 , 50
230/400
12.03/4.29
2.99
(30.4)
0.79
(8.0)
76.9
49.7
3.8
5
27
19
12.8
35
24
0.74
0.11
Cooling
10,000
3.53
1 , 50
230
0.92
1/3 , 50
230/400
15.07/5.39
3.16
(32.2)
0.91
(9.3)
78.2
49.9
4.2
5
27
19
13.4
35
24
0.78
0.06
Cooling
12,300
4.36
1 , 50
230
0.92
3 , 50
400
6.79
3.00
(30.6)
0.75
(7.7)
80.5
38.7
2.4
5
27
19
12.3
35
24
0.74
0.05
Cooling
14,200
5.41
1 , 50
230
0.92
3 , 50
400
8.55
3.05
(31.1)
0.94
(9.6)
78.0
49.9
-0.8
5
27
19
11.2
35
24
0.70
0.08
D.B.
W.B.
D.B.
D.B.
W.B.
PLA-RP71AAPLA-RP100AA2
PU-P71VHA
PU-P71YHA
PU-P100VHA
PU-P100YHA
PU-P125YHAPU-P140YHA
PLA-RP125AA2
PLA-RP140AA2
PLA-RP71AAPLA-RP100AA2
PLA-RP125AA2
PLA-RP140AA2
Representative matching
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/ff)
13
7OUTLINES AND DIMENSIONS
417
6642
45
56
(19)37028
53
175600175
330
2-12o36 oval holes
(Foundation Bolt M10)
Air Discharge
Rear Air Intake
Side Air Intake
2-U Shaped notched holes
(Foundfation Bolt M10)
Installation Feet
,,,
,
,
,
,,
,,,,
,
,
,,
,
,
,,
,,,
,
,
,,
30
Over
Over
Less than
Piping and wiring connections
can be made from 4 directions:
FRONT,Right,Rear and Below.
4 PIPING-WIRING DIRECTIONS
3 FOUNDATION BOLTS2 SERVICE SPACE
1 FREE SPACE (Around the unit)
Piping Knock-Out Hole Details
Example of Notes
···Refrigerant GAS pipe connction (FLARE){15.88(5/8F)
FUSE (6.3A 250V)
FUSE (6.3A 250V)
FUSE (6.3A 250V)
FUSE (6.3A 250V)
MC/CH RELAY
21S4 RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
JUMPER WIRE
MODEL SELECTION w2
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
O.B
321 12345
CNVMNT
(WHT)
CNMNT
(WHT)
LED1(GRN)
LED2(RED)
1011121314
SW1SW4
J1J2J3J4J5
S1
S2
S3
w2
J6
CNLEV
(WHT)
123456789
(WHT)
TH3/TH6
JA
JB
(RED)
T
634
TH4
121223145
NAME
COMPRESSOR(INNER THERMOSTAT)
FAN MOTOR(INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND./EVA.TEMP
MF CAPACITOR
MC CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
4-WAY VALVE SOLENOID COIL
HIGH PRESSURE PROTECT SWITCH
INNER THERMOSTAT FOR MC
TERMINAL BLOCK
LINEAR EXPANSION VALVE
OUTDOOR CONTROLLER BOARD
49C
MC
A1A1A2A2B1
B1
S
C
R
R
W
B
E
H
C5
L
D
T
U
6
2
/
/
T
T
3
1
1
5
/
/
L
L
1
3
C3
CH
52C
52C
21S4
MF
a
b
63H
BLU
RED
MF3
(WHT)
13
52C
(PNK)
313131
CH
(BLU)
21S4
(GRN)
w1
4/SR
X51
X52
FUSE2
LEV
TH4
TH6
TH3
R
B
E
L
D
U
TB1
NL
POWER SUPPLY
~/N
230V 50Hz
Y
O
B
L
R
R
W
N
N
w1 PUH-P71/P100VHA MODEL ONLY
S3S2S1
S3
INDOOR
UNIT
S2
S1
TB4
w2 MODEL SELECTION
J1
J2
J4
MODEL
PUH-P71VHA
PUH-P100VHA
PU-P71VHA
PU-P100VHA
: with jumper wire O : without jumper wire
O
O
O
OJ3O
O
O
J5 J6
O
O
O
O
O
O
O
<Notes when servicing>
Some fastening terminals have a lock mechanism:When removing the fastening terminal, push the projection (locking lever)on a
terminal with your finger and pull it out.
400V 50Hz
<Notes when servicing>
Some fastening terminals have a lock mechanism:When removing the fastening terminal, push the projection(locking lever)on a terminal with
your finger and pull it out.
MC
MF
TH3
TH4
TH6
C3
C4
CH
52C
21S4
SV
63H
51C
TB1
LEV
TB2
63L
O.B
FUSE (6.3A 250V)
FUSE (6.3A 250V)
FUSE (6.3A 250V)
FUSE (6.3A 250V)
MC/CH RELAY
21S4 RELAY
SV RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
JUMPER WIRE
MODEL SELECTION w4
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
NAME
MODEL
J1 J2
O
O
O
O
J3
O
O
O
O
J4
O
O
O
O
J5
O
O
J6
O
O
O
O
O
O
PUH-P71YHA
PU-P71YHA
PUH-P100YHA
PU-P100YHA
PUH-P125YHA
PU-P125YHA
PUH-P140YHA
PU-P140YHA
: with jumper wire O : without jumper wire
w1 PU(H)-P125/140YHA MODEL ONLY
w2 PUH-P71/P100/P125/P140YHA MODEL ONLY
w3 PU(H)-P71/100YHA MODEL ONLY
w4 MODEL SELECTION
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
B
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
L
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
B
B Earth leakage breaker
C wiring circuit breaker or
isolating switch
C
1
2
1
2
1
2
S1
S2
S3
S1
S2
S3
S1
S2
S3
S1
S2
S3
Indoor/outdoor
connection cable
Indoor
unit
Unit
power
supply
Indoor
unit
Indoor
unit
Outdoor
unit
Remote
controller
L
N
9-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
Outdoor unit Power supply
Outdoor unit input capacity
Main switch (Breaker)
Max. Permissive System Impedance (")
Outdoor unit power supply
)
2
Outdoor unit power supply earth
Indoor unit-Outdoor unit*2
Wiring
Indoor unit-Outdoor unit earth
Wire No. o
size (mm
Remote controller-Indoor unit*3
Outdoor unit L-N
Outdoor unit L1-N, L2-N, L3-N
Indoor unit-Outdoor unit S1-S2*4
rating
Circuit
Indoor unit-Outdoor unit S2-S3*4
Remote controller-Indoor unit*4
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 45 m
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2
used, Max. 50 m
If 2.5 mm
2
If 2.5 mm
used and S3 separated, Max. 80 m
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulataed by the transformer or other device.
2. Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
3. Install an earth longer than other cables.
*1
*4
P71VP100VP71YP100YP125YP140Y
~/N (single), 50 Hz, 230 V3N~(3phase), 50 Hz, 400 V
32 A16 A25 A
0.060.230.220.140.12
2 o Min. 44 o Min. 1.54 o Min. 2.5
1 o Min. 41 o Min. 1.51 o Min. 2.5
3 o 1.5 (polar)
1 o Min. 1.5
2 o 0.3 (Non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 12 V
Caution:
Do not push the contactor button (52C) on the outdoor unit, otherwise the compressor may be damaged.
Power supply
Isolator
3 poles isolator
A-Control
Outdoor Unit
S1
S2
S3
S1
S2
S3
A-Control
Indoor Unit
1:1 systemSynchronized twin and triple system Electrical wiring
• Synchronized twin
• Synchronized triple
18
9-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES
The following connection patterns are available.
The outdoor unit power supply patterns vary on models.
1:1 System
<For models without heater>
* The optional indoor power supply terminal kit is required.
D
L
N
A
CB
JEB
S1
S2
S3
G
L
N
C
F
H
S1
S2
S3
1
2
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Simultaneous twin/triple system
<For models without heater>
* The optional indoor power supply terminal kits are required.
AB
D
L
N
C
JBC
S1
S2
S3
E
GGHG
L
N
S1
S2
S3
1
F
2
L
L
N
N
S1
S1
S2
S2
S3
S3
1
1
2
2
A Outdoor unit power supply
B Earth leakage breaker
C Wiring circuit breaker or isolating switch
D Outdoor unit
E Indoor unit/outdoor unit connecting cords
F Remote controller
G Indoor unit
H Option
J
A
B
C
D
E
F
G
H
J
Indoor unit power supply
Outdoor unit power supply
Earth leakage breaker
Wiring circuit breaker or isolating switch
Outdoor unit
Indoor unit/outdoor unit connecting cords
Remote controller
Indoor unit
Option
Indoor unit power supply
* Affix a label B that is included with the manuals near each wiring diagram for the indoor and outdoor units.
Indoor unit model
Indoor unit power supply
Indoor unit input capacity
Main switch (Breaker)
Indoor unit power supply
Indoor unit power supply earth
)
2
Indoor unit-Outdoor unit
(mm
Wiring
Indoor unit-Outdoor unit earth
Wire No. o size
Remote controller-Indoor unit*3
Indoor unit L-N*4
Indoor unit-Outdoor unit S1-S2*4
Indoor unit-Outdoor unit S2-S3*4
rating
Circuit
Remote controller-Indoor unit*4
*1
*2
RP35~140
~/N (single), 50 Hz, 230 V
16 A
2 o Min. 1.5
1 o Min. 1.5
2 o Min. 0.3
–
2 o 0.3 (Non-polar)
AC 230 V
–
DC24 V
DC12 V
*1. A breaker with at least 3 mm contact separation in each pole shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
*2. Max. 120 m
*3.The 10 m wire is attached in the remote controller accessory. Max. 500 m
*4.The figures are NOT always against the ground.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords and indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord.
(Design 60245 IEC 57)
3. Install an earth longer than other cables.
If the indoor and outdoor units have separate power supplies, refer to the table
below. Change the indoor unit electrical box wiring referring to the figure in the
right and the Jumper wire JB settings of the outdoor unit control board.
Indoor unit specifications
Indoor unit electrical box connector
connection change
Label affixed near each wiring diagram
for the indoor and outdoor units
Outdoor unit jumper wire (when using
separate indoor unit/outdoor unit
power supplies only)
Required
Required
Jumper wire JB is cut.
L1
L2
GR
S1
S2
S3
Indoor unit power supplied from outdoor unit
(when shipped from factory)
* There are three types of labels (labels A, B, and C). Affix the appropriate labels to
the units according to the wiring method.
Please turn on the power supply of the outdoor unit first. Afterward, please turn on
the power supply of the indoor unit.
Connectors (connections when shipped
from the factory are for indoor unit power
supplied from outdoor unit)
BLUE
BLUE
YELLOW
YELLOW
ORANGE
CND
CND
Indoor unit
control board
L1
L2
GR
S1
S2
S3
Separate indoor unit/outdoor unit power
supplies
If the indoor and
outdoor units have
separate power
supplies, change the
connections of the
connectors as shown
in the following
figure.
YELLOW
BLUE
YELLOW
BLUE
Connectors
ORANGE
CND
CND
Indoor unit
control board
19
9-3. INDOOR – OUTDOOR CONNECTING CABLE
✽1 : In case that cable with stripe of yellow and green is available.
✽2 : In the flat cables are connected as this picture, they can be used up to 80m.
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm
2
.
✽4 : In case of regular polarity connection (S1-S2-S3).
✽5 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, humidity or materials, etc.
The cable length may vary depending on the condition of installation, humidity or materials, etc.
The cable shall not be lighter than design 60245 IEC or 227 IEC.
Cross section
of cable
Round
2.5
2.5
1.5
2.5
3
3
4
4
50
✽1
45
✽3
60
✽4
Not
applicable
✽2
Flat
Flat
Round
Wire size
(mm
2
)
Number
of wires
Clockwise : S1-S2-S3
Clockwise : S1-S2-S3-Open
Connect S1 and S3 to the opposite angle
Not applicable
(Because center wire has no cover finish)
From left to right : S1-Open-S2-S3
PolarityL(m) ✽5
(3C Flat cable ✕ 2)
S1 S2 S3
w The Max. cable length may vary depending on the condition of installation, humidity or materials, etc.
Indoor unit-Outdoor unit
Outdoor power supply
Max. 45m
3 o 1.5 (polar)
1 o Min. 1.5
Max. 50m
3 o 2.5 (polar)
1 o Min. 2.5
Max. 80m
3 o 2.5 (polar) and S3 separated
1 o Min. 2.5
Indoor unit-Outdoor unit earth
Wire No. o Size (E)
Be sure to connect the indoor-outdoor connecting cables directly to the units (no intermediate connections).
Intermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to
ground or a poor electrical contact at the intermediate connection point.
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)
Indoor unit-Outdoor unit
Indoor/Outdoor separate
power supply
Max. 120m
2 o Min. 0.3
—
Indoor unit-Outdoor unit earth
Wire No. o Size (E)
w The optional indoor power supply terminal kit is necessary
20
9-4. M-NET WIRING METHOD
Group
remote
controller
Refrigerant
address 00
M-NET
address 01
A-control
remote
controller
A-control
remote
controller
A-control
remote
controller
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 00
M-NET
address 03
Power
supply
unit for
transmission
wire
Central
remote
controller
M-NET transmission wire
✕ Bad example (Multi spot grounding of shield wire)
Good example 1 (Single spot grounding of shield wire)
Power
supply
appliance
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Central
remote
controller
Power
supply
appliance
M-NET type
outdoor unit
M-NET transmission wire
M-NET type
outdoor unit
M-NET type
outdoor unit
Good example 2 (Single spot grounding of shield wire)
(Points to notice)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET p.c. board may be burn out.
(3) Use 2-core x 1.25mm2shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Ground only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
“Ed” error will appear on the LED display of outdoor unit.
“0403” error will appear on the central-control remote controller.
If there are more than two grounding spots on the shield wire, noise may enter into the shield wire because the ground
wire and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among
grounding spots. In case of single spot grounding, noise does not enter into the shield wire because the ground wire and
shield wire do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot grounding method described in the
installation manual.
21
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
12
~
50
M-NET Address No.
<Setting example>
Switch
setting
SW11
ones
digit
SW12
tens
digit
OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
0
Refrigerant
address
OFF
ON
8
OFF
ON
1
OFF
ON
9
OFF
ON
10
OFF
ON
11
OFF
ON
12
OFF
ON
13
OFF
ON
14
OFF
ON
15
OFF
ON
2
OFF
ON
3
OFF
ON
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
System
controller
A-control
remote
controller
Group AGroup BGroup C
A-control
remote
controller
TB5
A-control
remote
controller
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 00
M-NET
address 02
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 00
M-NET
address 04
Power
supply
unit for
transmission
wire
A-control
remote
controller
A-control
remote
controller
TB5
Group AGroup B
Refrigerant
address 00
M-NET
address 01
Refrigerant
address 01
M-NET
address 02
Refrigerant
address 00
M-NET
address 04
Refrigerant
address 01
M-NET
address 03
Refrigerant
address 02
M-NET
address 05
System
controller
Power
supply
unit for
transmission
wire
● M-NET wiring
(1) Use 2-core x 1.25mm
2
shield wire for electric wires.
(Excluding the case connecting to system controller.)
(2) Connect the wire to the M-NET terminal block.Connect one core of the
transmission wire (non-polar) to Aterminal and the other to B. Peel the
shield wire, twist the shield part to a string and connect it to S terminal.
(3) In the system which several outdoor units are being connected, the terminal
(A, B, S) on M-NET terminal block should be individually wired to the other
M-NET
terminal
block
ABS
Transmission
wire
Ground
wire
Shield
part
outdoor unit’s terminal, i.e. Ato A, B to B and S to S.In this case, choose one of those outdoor units and drive a screw
to fix an ground wire on the plate as shown on the right figure.
9-4-1. M-NET address setting
In A-control models, M-NET address and refrigerant address should be set only for the outdoor unit. Similar to Free Combo
system, there is no need to set the address of outdoor unit and remote controller. To construct a central control system, the
setting of M-NET address should be conducted only upon the outdoor unit. The setting range should be 1 to 50 (the same as
that of the indoor unit in Free Combo system), and the address number should be consecutively set in a same group.
Address number can be set by using rotary switches
(SW11 for ones digit and SW12 for tens digit), which
is located on the M-NET board of outdoor unit.
(Factory setting: all addresses are set to “0”.)
9-4-2. Refrigerant address setting
In case of multiple grouping system (multiple refrigerant circuits in one group), indoor units should be connected by remote
controller wiring (TB5) and the refrigerant address needs to be set. Leave the refrigerant addresses to “00” if the group setting is not conducted. Set the refrigerant address by using DIP SW1-3 to -6 on the outdoor controller board. [Factory setting:
all switches are OFF. (All refrigerant addresses are “00”.)]
9-4-3. Regulations in address settings
In case of multiple grouping system, M-NET and refrigerant address settings should be done as explained in the above section. Set the lowest number in the group for the outdoor unit whose refrigerant address is “00” as its M-NET address.
w Refrigerant addresses can be overlapped if they are in the different group.
w In group B, M-NET address of the outdoor unit whose refrigerant address is “00” is not set to the minimum in the group. As
“3” is right for this situation, the setting is wrong. Taking group A as a good sample, set the minimum M-NET address in
the group for the outdoor unit whose refrigerant address is “00”.
22
10REFRIGERANT SYSTEM DIAGRAM
Outdoor heat exchanger
Thermistor
(TH3)
Thermistor
(TH6)
Distributor
Service
port
(check)
Accumulator
Compressor
Refrigerant GAS pipe
15.88A({5/8")
Refrigerant LIQUID pipe
9.52A({3/8")
Stop valve
(with service port)
4-way valve
Service port
(check)
High pressure
protect switch
Refrigerant flow in cooling
Refrigerant flow in heating
Linear expansion valve
Thermistor
(TH4)
Muffler
Ball valve
(#50)
Strainer
(#100)
Strainer
Strainer
(#40)
(#100)
Strainer
Bypass valve
Service
port
(check)
Accumulator
Compressor
Refrigerant GAS pipe
15.88A({5/8")
Refrigerant LIQUID pipe
9.52A({3/8")
4-way
valve
Service port (check)
High pressure protect switch
Linear expansion valve
Muffler
Thermistor
(TH4)
Refrigerant flow in cooling
Refrigerant flow in heating
Judge what is wrong and take a corrective action according
to “11-4. Self-diagnosis action table”.
Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “11-5. Troubleshooting
by inferior phenomena”.
The inferior phenomenon is
not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise and etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
inferior phenomenon occurred, matters related to wiring
and etc.
2Reset error code logs and restart the unit after finishing
service.
3There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
1Re-check the abnormal symptom.
2Conduct trouble shooting and ascertain the cause of the
inferior phenomenon according to “11-5. Troubleshooting
by inferior phenomena”.
3Continue to operate unit for the time being if the cause
is not ascertained.
4There is no abnormality concerning of parts such as
electrical component, controller board, remote controller
and etc.
11-1. TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>
Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit.
Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are summarized in the table below. Check the contents below before investigating details.
11-2. CHECK POINT UNDER TEST RUN
(1) Before test run
• After installation of indoor and outdoor units, piping work and electric wiring work, re-check that there is no refrigerant leak-
age, loosened connections and incorrect polarity.
• Measure impedance between the ground and the power supply terminal block(L, N) on the outdoor unit by 500V Megger and
check that it is 1.0M" or over.
wDon’t use 500V Megger to indoor/outdoor connecting wire terminal block(S1, S2, S3) and remote controller terminal block
(1, 2). This may cause malfunction.
• Make sure that test run switch (SW4) is set to OFF before turning on power supply.
• Turn on power supply 12 hours before test run in order to protect compressor.
• For specific models which requires higher ceiling settings or auto-recovery feature from power failure, make proper changes
of settings referring to the description of “Selection of Functions through Remote Controller”.
Make sure to read operation manual before test run. (Especially items to secure safety.)
24
"TEST RUN" and the currently selected
LCD
Contents of inferior phenomena
P1
P2
P4
P5
P6
P8
P9
Fb
Abnormality of room temperature thermistor
Abnormality of pipe temperature thermistor/Liquid
Abnormality of drain sensor/Float switch connector open
Drain overflow protection is working.
Freezing/overheating protection is working.
Abnormality of pipe temperature
Abnormality of pipe temperature thermistor/Cond./Eva
Abnormality of indoor controller board
LCD
Contents of inferior phenomena
U1~UP
F3~F9
E0~E5
E6~EF
----
FFFF
Malfunction outdoor unit
Malfunction
outdoor unit
Remote controller transmitting error
Indoor/outdoor unit communication error
No error history
No applied unit
LED1
(microcomputer power supply)
LED2
(remote controller)
LED3
(indoor/outdoor communication)
Lits when power is supplied.
Lits when power is supplied for wired remote controller.
The indoor unit should be connected to the outdoor unit with address “0” setting.
Flash when indoor and outdoor unit are communicating.
operation mode are displayed altemately.
Displays the remaining
test run time.
B
C
[TEST] button
A
Pipe (liquid) temperature
Operating procedures
1. Turn on the main power supply.
2. Press TEST button twice.
3. Press OPERATION SWITCH
button.
4. Press AIR DIRECTION button.
5. Check the outdoor unit fan for
correct running.
6. Press the ON/OFF button to reset the test run in progress.
7. Register the contact number.
A
B
C
While the room temperature display on the remote
controller is “PLEASE WAIT”, the remote controller is disabled.
Wait until “PLEASE WAIT” disappears before using remote controller.
“PLEASE WAIT” appears for about 2 minutes after power
supply is turned on. w1
The TEST RUN appears on the screen.
Cooling mode:
Heating mode: Check if warm air blows. (It takes a little
while until warm air blows.)
Check for correct motion of auto-vanes.
The outdoor unit features automatic capacity control to
provide optimum fan speeds. Therefore, the fan keeps
running at a low speed to meet the current outside air
condition unless it exceeds its available maximum power.
Then, in actuality, the fan may stop or run in the reverse
direction depending on the outside air, but this does not
mean malfunction.
Check if cool air blows and water is drained.
• In case of test run, the OFF timer will be activated, and the test run will automatically stop after two hours.
• The room temperature display section shows the pipe temperature of indoor units during the test run.
• Check that all the indoor units are running properly in case of simultaneous twin and triple operation. Malfunctions may not
be displayed regardless of incorrect wiring.
w1 After turning on the power supply, the system will go into startup mode, “PLEASE WAIT” will blink on the display section of
the room temperature, and lamp(green) of the remote controller will flash.
As to INDOOR BOARD LED, LED1 will be lit up, LED2 will either be lit up in case the address is 0 or turned off in case the
address is not 0. LED3 will blink.
As to OUTDOOR BOARD LED, LED1(green) and LED2(red) will light up. (After the startup mode of the system finishes,
LED2(red) will be turned off.)
In case OUTDOOR BOARD LED is digital display, — and —will be displayed alternately every second.
• If one of the above operations doesn’t function correctly, the causes written below should be considered. Find causes from
the symptoms.
The below symptoms are under test run mode. “startup” in the table means the display status of w1 written above.
Symptoms in test run mode
Remote Controller Display
Remote controller displays “PLEASE
WAIT”, and
After power is turned on, “PLEASE WAIT”
is displayed for 3 minutes, then error code
is displayed.
No display appears even when remote
controller operation switch is turned on.
(Operation lamp does not light up.)
Display appears but soon disappears
even when remote controller is operated.
cannot be operated.
OUTDOOR BOARD LED Display
< > indicates digital display.
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed,
green(once) and red(once) blink
alternately. <F1>
After “startup” is displayed,
green(once) and red(twice) blink
alternately. <F3, F5, F9>
After “startup” is displayed,
green(twice) and red(once) blink
alternately. <EA. Eb>
After “startup” is displayed, only
green lights up. <00>
After “startup” is displayed, only
green lights up. <00>
• After power is turned on, “PLEASE WAIT” is displayed for 2
minutes during
• Outdoor unit’s safeguard installation connector is open.
• Incorrect wiring between the indoor and outdoor unit (Polarity
is wrong for S1, S2, S3.)
• Remote controller transmission wire short.
• There is no outdoor unit of address 0.
(Address is other than 0.)
• Remote controller transmission wire burnout.
• After canceling function selection, operation is not possible for
about 30 seconds. (Normal)
system startup. (Normal)
Cause
1, L2, L3 and
w Press the remote controller’s CHECK button twice to perform self-diagnosis. See the table below for the contents of LCD
display.
See the table below for details of the LED display (LED 1, 2, 3) on the indoor controller board.
25
7
MODE
MODE
COOL
HEAT
TEST RUN
FAN
VANE
TEST RUN
ON
SW4
12
A Stop
B Cooling
C Operation
D Heating
A
CD
B
(Factory setting)
3,4
2
ON/OFF
MODE
CHECK
TEST RUN
SET
TEST RUN
FAN
VANE
LOUVER
RESET
CLOCK
TEMP
AUTO STOP
AUTO START
h
min
5
6
Test run [for wireless remote controller]
Measure an impedance between the power supply terminal block on
the outdoor unit and ground with a 500V Megger and check that it is
equal to or greater than 1.0M".
1 Turn on the main power to the unit.
2 Press the button twice continuously.
(Start this operation from the status of remote controller display
turned off.)
Aand current operation mode are displayed.
3 Press the ( ) button to activate mode, then
check whether cool air is blown out from the unit.
4 Press the ( ) button to activate mode, then
check whether warm air is blown out from the unit.
5 Press the button and check whether strong air is blown out
from the unit.
6 Press the button and check whether the auto vane operates
properly.
7 Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver
while following steps
• It is not possible to run the in FAN, DRY or AUTO mode.
22
to 77.
(2) Outdoor Unit
1) Check Items
• After installation of indoor and outdoor units, and tubing and electric wiring work, check that the unit is free from leaks of refrigerant, loosened
connections, and incorrect polarity.
• Check that there is no negative phase and open phase. (The F1 message for negative phase and the F2 message for open phase will flash
at digital indicator LED 1 on the outdoor substrate. If this happens, rewire correctly.)
• Measure the impedance between power terminals (Single phase: L,N,;;/ triple phase: L1,L2,L3,;;) and the ground with a 500V Megger and
check that it is 1.0MΩ or more. Do not operate the equipment if measurement is less than 1.0mΩ. *Never conduct this operation on the out-
door connection wiring terminals (S1,S2,S3) as this causes damage.
• When there is no error at the outdoor unit.
(If there is an error at the outdoor unit, it can be evaluated at LED 1 [digital display] of the outdoor substrate.)
• The stop valves are open both the liquid and gas sides.
After checking the above, execute the test run in accordance with the following.
2) Test run start and finish
• Operation from the indoor unit
Execute the test run using the installation manual for the indoor unit.
• Operation from the outdoor unit.
Execute settings for test run start, finish and operation mode (cooling, heating) using the DIP switch SW 4 on the outdoor substrate.
1 Set the operation mode (cooling, heating) using SW4-2.
2 Turn ON SW 4-1, The operation mode for SW 4-2 will be adhered to, and the test run will commence.
3 Turn OFF SW 4-1 to finish the test run.
• There may be a faint knocking noise emitted from the proximity of the fan during the test run. This is torque
fluctuation occurring due to control of fan revolutions. There is no problem with the product.
Note:
The SW 4-2 operation mode cannot be changed during the test run. (To change run mode, stop the equipment with SW 4-1, change
the operation mode, then restart test run with SW 4-1.)
26
11-3. HOW TO PROCEED "SELF-DIAGNOSIS"
11-3-1. When a Problem Occurs During Operation
If a problem occurs in the air conditioner, the indoor and outdoor units will stop,
and the problem is shown in the remote controller display.
[CHECK] and the refrigerant address are displayed on the temperature
display, and the error code and unit number are displayed alternately as
shown below.
1 If the outdoor unit is malfunctioning, the unit number will be "00".
2 In the case of group control, for which one remote controller controls
multiple refrigerant systems, the refrigerant address and error code of the
unit that first experienced trouble (i.e., the unit that transmitted the error
code) will be displayed.
3 To clear the error code, press the
button.
When using remote-/local-controller combined operation, cancel the error code after turning off remote operation. During
central control by a MELANS controller, cancel the error code by pressing the
button.
11-3-2. Self-Diagnosis During Maintenance or Service
Since each unit has a function that stores error codes, the latest check code can be recalled even if it is cancelled by the remote
controller or power is shut off.
Check the error code history for each unit using the remote controller.
1
Switch to self-diagnosis mode.
H
Press the
button twice within 3 seconds. The display content
will change as shown below.
2
Set the unit number or refrigerant address you want to diagnose.
F
Press the [TEMP] buttons ( and ) to select the desired number
or address. The number (address) changes between [01] and [50] or [00]
3
Display self-diagnosis results.
<When there is error code history>
(For the definition of each error code, refer to the indoor unit's installation manual or service handbook.)
4
Reset the error history.
Display the error history in the diagnosis result display screen (see step
3
).
E
B
A
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
The refrigerant address will begin to flash
approximately 3 seconds after being
selected and the self-diagnosis process will begin.
Unit number or refrigerant address
to be diagnosed
Error code (2 or 4 digits)
(Alternating Display)
Address (3 digits) or unit number (2 digits)
<When there is no error code history><When there is no corresponding unit>
and
[15].
ON/OFF
I
F
G
H
C
D
ON/OFF
CHECK
27
Loading...
+ 63 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.