13. PARTS LIST······················································30
14. RoHS PARTS LIST···········································32
NOTE:
• This service manual describes technical data of outdoor units.
• RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS Parts List.
Revision A:
• MUH-GA20VB-and MUH-GA25VB-have been added.
E2E2
Revision B:
• MUH-GA35VB-has been added.
1
MUH-A07YV-➔MUH-GA20VB-
1. Indication of capacity has been changed. (BTU base ➔ kw)
2. Dimension of outdoor unit has been changed. (W780mm x H540mm x D255mm ➔ W800mm x H550mm x D285mm)
3. Stop valve cover has been added.
4. Outdoor fan motor has been changed. (RC6V20-AB ➔ RA6V21-AD)
5. Outdoor fan motor capacitor has been changed.
6. Compressor capacitor has been changed.
7. Outdoor heat exchanger has been changed. (L-BEND ➔ FLAT)
MUH-A09YV-➔MUH-GA25VB-
1. Indication of capacity has been changed. (BTU base ➔ kw)
2. Dimension of outdoor unit has been changed. (W780mm x H540mm x D255mm ➔ W800mm x H550mm x D285mm)
3. Stop valve cover has been added.
4. Outdoor fan motor has been changed. (RA6V33-FB ➔ RA6V33-KB)
5. Outdoor fan motor capacitor has been changed.
6. Compressor capacitor has been changed.
7. Outdoor heat exchanger has been changed. (2 Row ➔ 1 Row)
E3
TECHNICAL CHANGES
E1E1
E1E1
MUH-A12YV-➔MUH-GA35VB-
1. Indication of capacity has been changed. (BTU base ➔ kw)
2. Dimension of outdoor unit has been changed. (W780mm x H540mm x D255mm ➔ W800mm x H550mm x D285mm)
3. Stop valve cover has been added.
4. Outdoor fan motor has been changed. (RA6V33-FB ➔ RA6V33-KB)
5. Outdoor fan motor capacitor has been changed.
6. Compressor capacitor has been changed.
7. Size of stop valve (gas) has been changed.([12.7 ➔ [9.52)
8. Outdoor heat exchanger has been changed. (2 Row ➔ 1 Row)
MUH-GA20VB-➔MUH-GA20VB-
1. Compressor has been changed. (BN092VHST ➔ KN092VDMHC)
2. Compressor capacitor has been changed.
3. Capillary tube has been changed.
4. Refrigerant filling capacity has been changed.
5. Deicer P.C. board has been changed.
MUH-GA25VB-➔MUH-GA25VB-
1. Compressor has been changed. (RN104VHSHT ➔ KN104VTMHC)
2. Compressor capacitor has been changed.
3. Capillary tube has been changed.
4. Refrigerant filling capacity has been changed.
5. Deicer P.C. board has been changed.
MUH-GA35VB-➔MUH-GA35VB-
1. Outdoor heat exchanger has been changed. (1 row ➔ 2 row)
2. Refrigerant filling capacity has been changed.
3. Outdoor unit weight has been changed. (35 kg ➔ 39 kg)
E1E1
E2E1
E2E1
E3E1
2
2
( )
Air inlet
Air outlet
Drain outlet
Piping
Drain hose
back : MUH-GA20VB
back and side : MUH-GA25VB
MUH-GA35VB
Drain socket
1
<Outdoor unit: MUH type>
1
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance (at 20:)
Model
Winding
resistance (at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigeration oil (Model)
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance (at 20:)
Model
Winding
resistance (at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigeration oil (Model)
RT61
Refrigerant flow in cooling
Refrigerant flow in heating
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping : m
Model
Max. lengthAMax. height
B
Piping size O.D : mm
Gas
Liquid
Length of connecting pipe : m
Indoor unit
Outdoor unit
MUH-GA20VB
MUH-GA25VB
MUH-GA35VB
20
25
10
9.52
MAX. HEIGHT DIFFERENCE
Indoor
unit
Refrigerant Piping
Max. height
B
Max. length
A
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Model
MUH-GA20VB -
MUH-GA20VB -
MUH-GA25VB MUH-GA25VB -
MUH-GA35VB MUH-GA35VB -
Outdoor unit precharged
E1
E2
E1
E2
E1
E3
650
600
800
650
800
1050
7m
0
Gas 0.43
6.35
Liquid 0.5
Outdoor unit
Refrigerant piping length (one way)
10m
60
15m
160
Calculation : Xg = 20g/m x (A-7)m
20m
260
Gas 0
Liquid 0
25m
360
8
PERFORMANCE CURVES
MUH-GA20VB MUH-GA25VB MUH-GA35VB
The standard specifications apply only to the operation of the air conditioner under normal conditions, since operating condi-
tions vary according to the areas where these units are installed. The following information has been provided to clarify the
operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB
(2) Indoor outlet air wet-bulb temperature :°CWB
(3) Outdoor intake air dry-bulb temperature :°CDB
(4) Total input:W
(5) Indoor intake air dry-bulb temperature :°CDB
(6) Outdoor intake air wet-bulb temperature :°CWB
(7) Total input :W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 10 shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
Cooling
}
Heating
}
9
MSC-GA20VB
MUH-GA20VB
MUH-GA35VB
MSC-GA35VB
MUH-GA25VB
MSC-GA25VB
8.5
7.8
7.1
6.4
5.8
5.1
10.0
9.2
8.3
7.5
6.8
6.0
11.0
10.0
9.1
8.2
7.4
6.5
20.0
18.5
16.9
15.4
13.9
12.3
10.8
9.2
19.2
17.8
16.3
14.8
13.3
11.8
10.4
8.9
MSC-GA20VB
MUH-GA20VB
MUH-GA25VB
MSC-GA25VB
MUH-GA35VB
MSC-GA35VB
24.0
22.1
20.3
18.4
16.6
14.7
12.9
11.1
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL
(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
Wet-and dry-bulb
thermometers
8-1.CAPACITY AND THE INPUT CURVES
OUTDOOR UNIT
Wet-and dry-bulb
thermometers
NOTE:The above curves are for the heating operation without any frost.
10
8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
1832
7
8
9
10
11
12
13
230V
1520
50
25
6030 70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1520
50
25
60
30
70(%)
35(:)
1
2
4
3
1832
230V
1832
230V
1520
50
25
6030 70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
1520
50
25
60
30
70(%)
35(:)
1
2
4
3
1832
230V
1832
230V
1520
50
25
60
30
70(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
1520
50
25
6030 70(%)
35(:)
3
4
5
6
1832
230V
COOL operation
① Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20
25
Relative humidity(%)
50
60
3070
➁ Air flow should be set at MAX.
③ The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge] )
NOTEQ :Total capacity (kW)SHF :Sensible heat factorDB :Dry-bulb temperature
SHC :Sensible heat capacity (kW)INPUT :Total power input (W)WB :Wet-bulb temperature
18
PERFORMANCE DATA
OUTDOOR WB(:)
INDOOR
-10-505101520
DB(:)
QINPUTQINPUTQINPUTQINPUTQINPUTQINPUTQINPUT
CAPACITY : 2.5(kW)
INPUT : 690(W)
15
21
26
1.58
1.50
1.35
449
483
518
1.90
1.80
1.68
538
573
607
2.23
2.13
1.98
607
635
669
2.55
2.43
2.30
656
683
718
2.88
2.75
2.63
697
718
752
3.18
3.05
2.93
718
738
773
3.50
3.36
3.25
731
766
794
OUTDOOR WB(:)
INDOOR
-10-505101520
DB(:)
QINPUTQINPUTQINPUTQINPUTQINPUTQINPUTQINPUT
CAPACITY : 3.0(kW)
INPUT : 820(W)
15
21
26
1.89
1.80
1.62
533
574
615
2.28
2.16
2.01
640
681
722
2.67
2.55
2.37
722
754
795
3.06
2.91
2.76
779
812
853
3.45
3.30
3.15
828
853
894
3.81
3.66
3.51
853
877
918
4.20
4.04
3.90
869
910
943
OUTDOOR WB(:)
INDOOR
-10-505101520
DB(:)
QINPUTQINPUTQINPUTQINPUTQINPUTQINPUTQINPUT
CAPACITY : 3.7(kW)
INPUT : 1020(W)
15
21
26
2.33
2.22
2.00
663
714
765
2.81
2.66
2.48
796
847
898
3.29
3.15
2.92
898
938
989
3.77
3.59
3.40
969
1010
1061
4.26
4.07
3.89
1030
1061
1112
4.70
4.51
4.33
1061
1091
1142
5.18
4.98
4.81
1081
1132
1173
HEAT operation (230V)
MSC-GA20VB : MUH-GA20VB
MSC-GA25VB : MUH-GA25VB
MSC-GA35VB : MUH-GA35VB
NOTEQ:Total capacity (kW) INPUT:Total power input (W) DB:Dry-bulb temperature WB:Wet-bulb temperature
9
R.V. coil control
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ACTUATOR CONTROL
Heating · · · · · ON
Cooling · · · · · OFF
Dry · · · · · · · · OFF
Compressor
R.V. coil
Outdoor fan
ON
OFF
ON
OFF
ON
OFF
(COOL / DRY)
5 seconds
(HEAT)
5 seconds
ON
OFF
ON
OFF
ON
OFF
19
Lead wiring
Housing point
10
Jumper wire
JRF
JRG
MODELChange point
Defrost interval time changes from 40 minutes to 15 minutes.
Defrost start temperature changes from -3: to 0:.
MUH-GA20VB
MUH-GA25VB
MUH-GA35VB
SERVICE FUNCTIONS
MUH-GA20VB
MUH-GA25VB
MUH-GA35VB
10-1. COMPULSORY DEFROSTING MODE FOR SERVICE
By short circuit of the connector JPDS and JPSG on the outdoor deicer P.C. board, defrosting mode can be accomplished regardless of the defrost interval restriction. (Refer to 11-5.)
Defrost thermistor RT61 must read below -3°C.
10-2. CHANGE IN DEFROST SETTING
<JRF> When the JRF wire of the deicer P.C. board is cut, the defrost interval time will be changed.
<JRG> When the JRG wire of the deicer P.C. board is cut, the defrost temperature will be changed.(Refer to 11-5.)
11
TROUBLESHOOTING
MUH-GA20VB
MUH-GA25VB
MUH-GA35VB
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
1) Before servicing the air conditioner, be sure to turn off the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn off the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to 11-2. “Instruction of troubleshooting”.
20
11-2. Instruction of troubleshooting
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
operates.
Outdoor unit
doesn't operate
normally.
OPERATION
INDICATOR
lamp on the
indoor unit is
flashing on
and off.
Outdoor unit
operates in
only T est Run
operation.
Outdoor unit
doesn't
operate
even in
Test Run
operation.
Indoor unit
operates,
when the
EMERGENCY
OPERATION
switch is
pressed.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is
pressed.
Check room
temperature
thermistor.
Refer to 11-5.
"Test point
diagram and
voltage".
Refer to 11-4.
A "Check of
outdoor unit".
Refer to
"Check of
remote
controller
and receiver
P.C. board".
Cause:
Indoor/Outdoor unit
• Mis-wiring or
trouble of serial
signal
2-time flash
Cause:
Indoor unit
• T roub le of
room temp erature/
indoor coil
thermistor
3-time flash
Cause:
Indoor unit
• T roub le of
indoor fan
motor
6-time flash
Cause:
Outdoor unit
• T roub le of
thermistor
in outdoor
unit
7-time flash
Cause:
Outdoor unit
• T roub le of
outdoor
control
system
Check room
temperature
thermistor
and indoor
coil thermistor.
Refer to 11-5.
"Test point
diagram and
voltage".
Refer to
"Check of
indoor fan
motor".
Refer to 11-4.
E"Check of
outdoor
thermistor".
Replace the
deicer
P.C. board.
Refer to 11-4. D
"How to check
mis-wiring and
serial signal
error (When
outdoor unit
doesn't work)".
W1
1. Check indoor /
outdoor
connecting wire.
2. Refer to
"Check of indoor
electronic control
P.C. board".
Outdoor unit
doesn't
stop even
if indoor unit
stops.
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Refer to 11-4.
B "Check of
outdoor unit".
Refer to 11-4.
C "Check of
R.V. coil".
W
1.<The case of the trouble of the serial signal>
When the power is turned off and then turned on again, the indication shows “the trouble of mis-wiring”.
W
"Test run operation"
means the
operation
within 30 minutes
after
EMERGENCY
OPERATION
switch is pressed.
Flash on and off at
0.5
-
second intervals
4-time flash
Cause:
Indoor unit
• T roub le of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
Refer to indoor
unit service
manual.
W
W
MUH-GA20VB MUH-GA25VB MUH-GA35VB
21
Yes
Compressor
doesn't operate.
Yes
Yes
Is there 230V AC between 3 on the
compressor contactor (52C) and N
on the outdoor terminal block (TB1)?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch.
3-minute time delay works.
Test run operation operates for 30 minutes.
Outdoor fan motor
doesn't operate.
No
Rectify the indoor and
outdoor connecting wire.
Rectify the connecting wire.
Check the compressor and compressor
capacitor, and rectify the connecting wire.
Start
Yes
Is there 230V AC between 4 on the
compressor contactor (52C) and
TAB20 on the deicer P.C. board?
Is there 230V AC between L–N
on the outdoor terminal block (TB1)?
Replace the
deicer P.C. board.
Replace the
deicer P.C.
board.
No
No
Yes
Yes
No
Check the outdoor fan motor
and rectify the connecting
wire.
Is there 230V AC between 4 on the
compressor contactor (52C) and
TAB 20 on the deicer P.C. board?
Replace the
deicer P.C. board.
No
Yes
Rectify the indoor and
outdoor connecting wire.
Rectify the connecting wire.
Is there 230V AC between L–N on
the outdoor terminal block (TB1)?
No
No
Is the switch SW2-2 on the
indoor electronic control
P.C. board set to MUH type?
No
Change the switch SW-2-2
on the indoor electronic control
P.C. board to MUH type.
Yes
+
–
Is there 5V DC between J205 –J101 on
the deicer P.C. board?
+
–
Is there 5V DC between J205 –J101 on
the deicer P.C. board?
P
R
C
S
RED
BLK
WHT
MAINAUX.
WHTRED
BLK
MAIN
AUX.
FUSE
11-3. Trouble criterion of main parts
MUH-GA20VB MUH-GA25VB MUH-GA35VB
Part name
Defrost
thermistor
(RT63)
Measure the resistance with a tester.
(Part temperature –10°C ~ 40°C)
Refer to 11-5. “Test point diagram and voltage”, “Outdoor deicer
P.C. board”, the chart of thermistor.
Check method and criterion
Figure
Compressor
(MC)
INNER
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
PROTECTOR
MUHGA20/GA25VB
150i 5°C OPEN
90i10°C CLOSE
MUHGA20/GA25VB
E1
-
E2
-
C-R
C-S
MUH-GA20VB
3.41~4.18Ω
5.41~6.63Ω
E1
-
MUH-GA20VB
-
3.19~3.91Ω
4.76~5.83Ω
E2
160i5°C OPEN
90i10°C CLOSE
MUH-GA35VB
155i 5°C OPEN
90i10°C CLOSE
Measure the resistance between the terminals with a tester.
(Coil wiring temperature –10°C ~ 40°C)
Outdoor fan
motor
(MF)
INNER FUSE
145i 2°C
Color of
lead wire
WHT-BLK
BLK-RED
MUH-GA20VB
323 ~ 396 Ω
241 ~ 296 Ω
CUT OFF
11-4. Troubleshooting flow
Compressor and/or outdoor fan motor doesn’t operate.
Normal
MUH-GA25VB
2.99~3.67Ω
4.02~4.92Ω
Normal
E1
-
MUH-GA25VB
E2
-
3.19~3.91Ω
4.76~5.83Ω
MUH-GA25/GA35VB
189 ~ 233 Ω
270 ~ 332 Ω
MUH-GA35VB
2.46~3.01Ω
2.96~3.63Ω
P INNER PROTECTOR
AA
Check of outdoor unit
22
Compressor and/or outdoor fan motor doesn’t stop.
After 3 minutes, does the unit
operate in HEAT mode?
Ok
No
Is there 230V AC between
CN7211 – 2 on the deicer
P.C. board?
Replace the
deicer P.C. board.
Yes
Yes
Yes
No
Replace the R.V. coil.
Turn ON the power supply and operate
the indoor unit in COOL mode by pressing
the EMERGENCY OPERATION switch.
BB
Check of outdoor unit
Start
Turn OFF the power supply.
After 1 minute, turn ON
power supply again.
Is there 230V AC between 3 on the
Does compressor stop?
Yes
OK
No
compressor contactor (52C) and N on the
outdoor terminal block (TB1)?
Yes
Replace the
deicer P.C. board.
No
Rectify the connecting wire.
Does outdoor fan motor stop?
Yes
OK
No
Replace the
deicer P.C. board.
Unit operates COOL mode even if it is set to HEAT mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
CC
Check of R.V. coil
Turn ON the power supply and operate
the indoor unit in HEAT mode by pressing
the EMERGENCY OPERATION switch.
After 3 minutes, does the unit
operate in COOL mode?
Yes
Is there 230V AC between
CN7211 – 2 on the deicer P.C.
board?
Yes
Replace the R.V. coil.
No
OK
No
Replace the
deicer P.C. board
Unit operates HEAT mode even if it is set to COOL mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
CC
Check of R.V. coil
23
When OPERATION INDICATOR lamp flashes 0.5-second intervals.
Outdoor unit does not operate.
DD
How to check mis-wiring and serial signal error
w 1 Set the switch(SW2-2) on indoor electronic control P.C. board to
MU or MUX type, when the outdoor unit is MU or MUX type.
Start
Turn OFF the power supply(indoor/outdoor unit).
Is the outdoor unit "MUH" type?
•Turn ON the power supply(indoor/outdoor unit).
•Press once EMERGENCY OPERATION switch.
•3 min. later, check the self-check result
displayed on OPERATION INDICATOR
lamp on indoor unit.
Correct them.
1. Turn OFF the power supply(indoor/outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side.
2. Short-circuit between indoor terminal block N and 3.
3. Turn ON the power supply
Yes
(indoor unit) and press EMERGENCY OPERATION switch once.
Is this mis-wiring, poor contact,
or disconnection of wire?
Yes
w 2
Serial signal error is indicated.
(0.5-sec. ON, 0.5-sec. OFF)
No
If the setting is MUH or MXZ type, the unit does not work.
w 2 Short circuit of JPG and JPS on the indoor electronic control
P.C. board enables self-check to be displayed in 3 seconds.
No
Set the switch(SW2-2) on the indoor electronic
control P.C. board to MU or MUX type.
Does the unit operate?
No
Refer to the
"Instruction of
troubleshooting."
Yes
w1
OK
Is there 20V DC between both ends of
R132 on indoor electronic control P.C.
board ?
( By tester, the stylus is between 0 ~ 20V. )
•Turn OFF the power supply(indoor unit).
•Connect indoor and outdoor connecting wire.
Turn ON the power supply(outdoor unit).
Is there 230V AC between outdoor terminal
block L-N (TB1)?
Is there 5V DC between J205 + –J101 - on the deicer P.C. board?
Turn ON the power supply(indoor unit).
During EMERGENCY OPERATION,
is there 10V DC between both ends
of R601?
(By tester, the stylus is between 5 ~10V)
Replace the deicer P.C. board.
Refer to indoor unit service manual.
Yes
Yes
Yes
Yes
No
Replace the indoor electronic
control P.C. board.
Check the outdoor power supply,
No
power supply cord and
connection.
No
Replace the deicer P.C. board.
Make the wiring between CN730
No
on the deicer P.C. board and
outdoor terminal block correct.
24
When OPERATION INDICATOR lamp flashes 6-time.
Thermistors in the outdoor unit are abnormal.
EE
Check of outdoor thermistor
Start
Turn OFF the
power supply.
Defrost thermistor (RT61)
Measure
resistance
between CN 661
1 and 2.
Is the resistance of
thermistor normal?
No
Replace the
thermistor.
Reconnect CN661.
Turn ON the power
Yes
supply and press
the EMERGENCY
OPERATION switch.
Replace the deicer P.C.
board.
No
Does the unit operate
10 minutes or more?
Yes
OK ❈
❈ Defective contact of the connector is considered.
Defrost interval time
short pin
(JPDS, JPSG)
(Refer to 10-1.)
Jumper wire for
change in
}
}
CN661 1-2
Defrost thermistor RT61
+
--
defrost setting
(JRF,JRG)
(Refer to 10-2.)
12V DC
J204
+
J101
--
26
12
(1) Slide the sleeve and check if there is a locking lever or not.
(2) The terminal with this connector has the locking
mechanism.
1Slide the sleeve.
2Pull the terminal while
pushing the locking
lever.
1Hold the sleeve, and
pull out the terminal
slowly.
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
<"Terminal with locking mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
MUH-GA20VB MUH-GA25VB MUH-GA35VB
OUTDOOR UNIT
OPERATING PROCEDUREPHOTOS
1. Removing the cabinet
(1) Remove the screws of the top panel.
(2) Remove the screw of the service panel.
(3) Remove the screws of the cabinet.
(4) Remove the screws of the front panel and motor support.
(5) Remove the service panel, and remove the screw from
the insides.
(6) Remove the top panel.
(7) Remove the cabinet.
Photo 3
Screws of the
top panel
Screw of the
Service panel
Photo 1
Screw of the front panel and motor support
Screws of the cabinet
Photo 2
MUH-GA20VB
Screws of the
top panel
Screw of the cabinet
27
Screws of the
cabinet
OPERATING PROCEDUREPHOTOS
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the propeller nut.
(3) Remove the propeller.
NOTE : Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the
propeller and the motor shaft cut section.
Set the propeller in position by using the cut on the
shaft and the mark on the propeller.
(4) Disconnect the outdoor fan motor connector.
(5) Remove screws fixing the fan motor.
(6) Remove the outdoor fan motor.
Photo 4
Screw of the
relay panel
Photo 5
MUH-GA20VB
Screw of the
outdoor fan motor
Propeller
Deicer
P.C. board
Surge absorber
Relay panel
Terminal
cover
Terminal
block
Screws of
the relay
panel
28
Propeller
nut
Sound proof felt
R.V. coil
OPERATING PROCEDUREPHOTOS
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
NOTE : Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
)
(
Remove the compressor.
10
2
(0 MPa).
Photo 6
Glass
terminal
Compressor
Discharge pipe
Compressor nuts
4-Way valve
Suction
pipe
29
13
PARTS LIST (non-RoHS compliant)
MUH-GA20VB MUH-GA25VB MUH-GA35VB
13-1. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
OUTDOOR HEAT EXCHANGER
OUTDOOR HEAT EXCHANGER
OUTDOOR HEAT EXCHANGER
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
CABINET
CABINET
GRILLE
PROPELLER
BASE
BASE
COMPRESSOR RUBBER SET
COMPRESSOR
COMPRESSOR
COMPRESSOR
STOP VALVE (GAS)
STOP VALVE (LIQUID)
BACK PANEL
BACK PANEL
SERVICE PANEL
DRAIN SOCKET
TERMINAL BLOCK
TERMINAL BLOCK
4-WAY VALVE
4-WAY VALVE
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
COMPRESSOR CAPACITOR
SURGE ABSORBER
DEICER P.C. BOARD
DEICER P.C. BOARD
DEFROST THERMISTOR
CONDENSER NET
CONDENSER NET
TOP PANEL
SEPARATOR
MOTOR SUPPORT
R. V. COIL
R. V. COIL
FUSE
VARISTOR
CHECK VALVE
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
CAPILLARY TUBE
HEAD OFFICE: TOKYO BLDG.,2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2005 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in May 2007. No.OB387 REVISED EDITION-B 6
Distributed in May 2006. No.OB387 REVISED EDITION-A 6
Distributed in Feb. 2005. No.OB387 6
Made in Japan
New publication, effective May 2007
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.