Mitsubishi MU-GE50VB-E1, MUH-GE50VB-E1 Service Manual

SPLIT-TYPE AIR CONDITIONERS
OUTDOOR UNIT
SERVICE MANUAL
Models
MU-GE50VB­MUH-GE50VB-
E1
E1
HFC
utilized
R410A
Indoor unit service manual MS/MSH-GE
No. OBH530
VB Series (OBH529)
CONTENTS
10. SERVICE FUNCTIONS ···································· 17
11. TROUBLESHOOTING ····································· 17
12. DISASSEMBLY INSTRUCTIONS ···················· 23
NOTE:
• This service manual describes technical data of outdoor units.
1. TECHNICAL CHANGES ··································· 2
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 3
4. NOISE CRITERIA CURVES ······························ 4
5. OUTLINES AND DIMENSIONS ························ 5
6. WIRING DIAGRAM ············································ 6
7. REFRIGERANT SYSTEM DIAGRAM ··············· 7
9. ACTUA TOR CONTROL ··································· 16
PARTS CATALOG (OBB530)
1
MU-GA50VB-
1. Unit size has been changed. (W 850 mm × H 605 mm × D 290 mm W 800 mm × H 550 mm × D 285 mm)
2. Outdoor fan motor has been changed. (RA6V50-PA RA6V33-KA)
MUH-GA50VB-
1. Unit size has been changed. (W 850 mm × H 605 mm × D 290 mm W 800 mm × H 550 mm × D 285 mm)
2. Outdoor fan motor has been changed. (RA6V60-MA RA6V33-KB)
TECHNICAL CHANGES
E1
MU-GE50VB-
E1
MUH-GE50VB-
E1
E1
2
2
PART NAMES AND FUNCTIONS
MU-GE50VB MUH-GE50VB
Air inlet back and side
Piping
Drain hose
Air outlet
Drain outlet
3
Outdoor model MU-GE50VB MUH-GE50VB Function Cooling Cooling Heating
Power supply Capacity kW 5.0 5.0 5.2
Electrical
Coeffi cient of performance (C.O.P) (Total)
Fan
Dimensions W H D mm 800 Weight kg 38 40
Special
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Wet-bulb temperature 24°C Heating: Indoor Dry-bulb temperature 20°C Wet-bulb temperature -°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Indoor-Outdoor piping length: 5 m
SPECIFICATION
Single phase 230 V, 50 Hz
Breaker capacity A 15 15 Running current (Total) Power input (Total) W 1,810 1,780 1,610
data
Power factor (Total) % 96 94 Starting current (Total)
Model RN196VHSHT RN196VHSHT Output W 1,300 1,300
Compressor
Compressor motor current Model RA6V33-KA RA6V33-KB Fan motor current A 0.33 0.33
motor
Dehumidifi cation /h 2.5 2.5 Air fl ow /h 1,902 1,902 Sound level dB 52 52 Fan speed rpm 855 855 Fan speed regulator 1 1
remarks
Refrigerant fi lling capacity (R410A)
Refrigeration oil (Model)
A 8.20 8.23 7.53
A37 37
2.76 2.81 3.23
A 7.57 7.60 6.90
550 285 800 550 285
kg 1.35 1.45 cc 520 (NEO 22) 520 (NEO 22)
MUH-GE50VB
ACCESSORIES
<Outdoor unit: MUH type>
Drain socket
Single phase 230 V, 50 Hz
-
1
3
4
MU-GE50VB
NOISE CRITERIA CURVES
COOL
SPL(dB(A))LINE
52
FUNCTION
Test conditions, Cooling :Dry-bulb temperature35°C Wet-bulb temperature24°C
90
MUH-GE50VB
FUNCTION
COOLING
HEATING
SPL(dB
Test conditions, Cooling :Dry-bulb temperature35°C Wet-bulb temperature24°C Heating :Dry-bulb temperature 7°C Wet-bulb temperature 6°C
90
(A))LINE
52
80
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
20
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
80
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
NC-10 NC-10
70
60
50
40
30
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
20
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OUTDOOR UNIT
1m
MICROPHONE
4
5
OUTLINES AND DIMENSIONS
MU-GE50VB MUH-GE50VB
OUTDOOR UNIT
344.5
285
550
Air in
22.3
Handle
280
400
Air in
44
2 holes 10×21
Air out
10
150
302.5 500 Bolt pitch for installation
Drain hole ø42
800
Unit: mm
REQUIRED SPACE
100mm or more
304~325
installation
Bolt pitch for
40
17.5 23
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
35°
164.5
69
99.5
170.5
Service port
Gas refrigerant pipe joint Refrigerant pipe (flared) ø12.7
200mm or more
Open two sides of left, right, or rear side.
43°
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
100mm or more
350mm or more
5
6
MU-GE50VB
WIRING DIAGRAM
MUH-GE50VB
6
7
REFRIGERANT SYSTEM DIAGRAM
MU-GE50VB
OUTDOOR UNIT
Refrigerant pipe 12.7 (with heat insulator)
Flared connection
Flared connection
Stop valve (with service port)
Stop valve
Unit :mm
Muffler
Outdoor heat exchanger
Compressor
Strainer #100
Refrigerant pipe 6.35 (with heat insulator)
MUH-GE50VB
OUTDOOR UNIT
Refrigerant pipe ø12.7 (with heat insulator)
Flared connection
Flared connection
Stop valve (with service port)
Strainer #100
Capillary tube
3.0 x 1.6 x 450
4-way valve
Muffler
Compressor
Check valve
Outdoor heat exchanger
Capillary tube ø3.0 × ø1.8 × 600 (2 pcs)
Capillary tube ø3.0 × ø1.6 × 500
Refrigerant pipe ø6.35 (with heat insulator)
Stop valve
Capillary tube ø3.0 × ø1.6 × 300
7
R.V. coil heating ON cooling OFF
Defrost thermistor RT61
Refrigerant flow in cooling Refrigerant flow in heating
MAX. REFRIGERANT PIPING LENGTH
Model
MU-GE50VB MUH-GE50VB
Refrigerant piping: m
Max. lengthAMax. height
B
25
10
Piping size O.D: mm
Gas
12.7
MAX. HEIGHT DIFFERENCE
Indoor unit
Refrigerant Piping
Max. height B
Max. length
A
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
MU-GE50VB
MUH-GE50VB
Outdoor unit precharged
1350 1450
7 m
0
Length of connecting pipe: m
Liquid
6.35
Outdoor unit
Refrigerant piping length (one way)
10 m
60
Indoor unit
Gas 0.43
Liquid 0.5
15 m
160
Calculation : Xg = 20 g/m × (A-7)m
20 m
260
Outdoor unit
Gas 0
Liquid 0
25 m
360
8
PERFORMANCE CURVES
MU-GE50VB MUH-GE50VB
The standard specifications apply only to the operation of the air conditioner under normal conditions, since operating condi­tions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264 V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °CWB (2) Indoor outlet air wet-bulb temperature: °CWB (3) Outdoor intake air dry-bulb temperature: °CDB (4) Total input: W (5) Indoor intake air dry-bulb temperature: °CDB (6) Outdoor intake air wet-bulb temperature: °CWB (7) Total input: W
Indoor air wet/dry-bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
8
Cooling
}
Heating (MUH-GE50VB)
}
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL
[HEAT (MUH-GE50VB)]
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MODE.
INDOOR UNIT
Wet and dry-bulb thermometers
8-1. CAPACITY AND THE INPUT CURVES
11.6
10.6
9.6
8.6
7.7
difference(degree)
6.9
Indoor air Wet-bulb temperature
Indoor intake air Wet-bulb temperature
OUTDOOR UNIT
Wet and dry-bulb thermometers
ulb temperature
t-b
Indoor intake air
We
MUH-GE50VB
MU-GE50VB
26.6
24.5
22.5
20.4
18.4
16.3
difference(degree)
14.3
Indoor air Dry-bulb temperature
12.3
MUH-GE50VB
Outdoor intake air Dry-bulb temperature
lb temperature
oor intake air Dry-bu
Ind
Outdoor intake air Wet-bulb temperature
NOTE: The above curves are for the heating operation without any frost.
Outdoor intake air Dry-bulb temperature
intake air Dry-bulb temperature
oor
Ind
Outdoor intake air Wet-bulb temperature
9
Loading...