Mitsubishi Electric MU-GA50VB, MU-GA60VB, MU-GA80VB Service Manual

Page 1
SERVICE MANUAL
SPLIT-TYPE, AIR CONDITIONERS
HFC
utilized
R410A
Wireless type Models
No. OB370
MU-GA50VB ­MU-GA60VB ­MU-GA80VB -
Indication of model name
MU-GA50VB -
E1
E1
E1
E1
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················5
3. SPECIFICATION·················································6
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS·························9
6. WIRING DIAGRAM ··········································10
7. REFRIGERANT SYSTEM DIAGRAM··············12
8. PERFORMANCE CURVES······························15
10. DISASSEMBLY INSTRUCTIONS·····················30
11. PARTS LIST······················································36
NOTE:
•This service manual describes technical data of outdoor units. As for indoor units MS-GA50VB - , MS-GA60VB - and MS-GA80VB - , refer to the service manual OB369.
E1E1E1
Page 2
1
Refrigerating
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Depletion Potential : based on CFC-11 w2 :Global Warming Potential : based on CO
2
TECHNICAL CHANGES
MU-A18WV - MU-GA50VB -
1. Oil separator has been removed.
2. Model name has been changed. Indication of capacity has been changed. (BTU➔kW)
MU-A24WV - MU-GA60VB ­MU-A30WV - MU-GA80VB -
1. Model name has been changed. Indication of capacity has been changed. (BTU➔kW)
E1E1
E1E1
E1E1
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410Arefrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
2
Page 3
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
New Specification Current Specification
The incompatible refrigerating oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigerating oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerating oil are compatible each, refrigerating oil backs to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigerating oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigerating oil /Refrigerant
Compressor
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
R410A tools Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm and 15.88 mm
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
3
Page 4
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter
mm
6.35
9.52
12.7
15.88
17 22 26 29
Dimension of flare nut
R22
17 22 24 27
2.Refrigerant piping
Wall thickness
Outside diameter
Pipe
mm
For liquid
For gas
6.35
9.52
12.7
15.88
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88). Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is insufficient.
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
4
Page 5
2
Drainage hose
Piping
Air inlet
Air inlet
Air outlet
Drain outlet
(back and side)
Air outlet
(back and side)
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MU-GA50VB ­MU-GA60VB -
E1 E1
MU-GA80VB -
E1
5
Page 6
3
Outdoor model
Function
Power supply
Capacity Dehumidification Air flow(High) Power outlet Running current Power input Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at 20:) Model Winding resistance(at 20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High) Fan speed regulator Refrigerant filling capacity(R410A) Refrigerating oil (Model)
kW
r/h
K /h
A
A W %
A
A
A
W
"
"
mm
kg
dB
rpm
kg cc
MU-GA50VB -
E1
Cooling
Single phase
230V, 50Hz
5.0
2.5
2,196
15
7.90
1,750
96 37
7.51
0.39
2.76
RN196VHSHT
1,300 C-R 1.80 C-S 3.00
RA6V50-PA WHT-BLK 79.5 BLK-RED 83.0
850o605o290
44 52
828
1
1.45
520 (NEO22)
MU-GA60VB -
E1
Cooling
Single phase
230V, 50Hz
6.5
3.4
2,322
25
10.82 2,420
97 74
10.27
0.55
2.62
NN29VBAHT
1,900 C-R 0.80 C-S 1.64
RA6V60-MA WHT-BLK 71 BLK-RED 89
850o605o290
60 53
873
1
2.00
1,200 (NEO22)
Electrical
data
Compressor
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
SPECIFICATION
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB(24°C)
Indoor-Outdoor piping length : 5m
6
Page 7
Outdoor model
Function
Power supply
Capacity Dehumidification Air flow(High/Low )
Capacity
Power outlet Running current Power input Power factor
Electrical
data
Starting current Compressor motor current Fan motor current
w
kW
R/h
K /h
A A
W
%
A A A
Coefficient of performance(C.O.P)
Model Output Winding resistance(at 20:)
Compressor
W
"
Model Winding
Fan
motor
resistance(at 20:) Dimensions WOHOD Weight Sound level(High/Low ) Fan speed(High/Low )
w
"
mm
kg
w
dB
rpm Fan speed regulator Refrigerant filling capacity(R410A)
Special
remarks
Refrigerating oil (Model) Thermistor RT62(at 25:) Thermistor RT63(at 0:)
kg
cc k" k"
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB(24°C)
Indoor-Outdoor piping length : 5m
w Reference value
E1
MU-GA80VB -
Cooling
Single phase
230V, 50Hz
8.5
4.6
2,940/1,470
w
25
14.42 3,191
96 90
13.85
0.57
2.61
NN37VAAHT
2,500 C-R 0.64 C-S 1.63
RA6V75-AD
WHT-BLK 62.8 BLK-YLW 55.9
YLW-RED 26.0
840o850o330
75
w
55/53
805/435
w
2
2.40
1,300 (NEO 22)
231.44
33.18
7
Page 8
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
52
SPL(dB(A)) LINE
High
FAN SPEED
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
NOISE CRITERIA CURVES
MU-GA50VB -
MU-GA80VB -
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
E1
E1
FAN SPEED
SPL(dB(A)) LINE
High
55
MU-GA60VB -
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
90
E1
FAN SPEED
High
SPL(dB(A)) LINE
53
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
OUTDOOR UNIT
1m
MICROPHONE
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
8
Page 9
5
OUTLINES AND DIMENSIONS
MU-GA50VB - MU-GA60VB -
OUTDOOR UNIT
Drainage hole [16.2
35
90
248
Air in
Drainage 3holes [33
605
292
20
MU-GA80VB -
355
350
20
Air in
Air out
183
500 850
E1
OUTDOOR UNIT
515
299
66
51
34
330
40
E1E1
100mm or more
100mm or more
50
290
30
310
100mm or more
345
500mm or more
Service panel
Unit: mm
350mm or more
Liquid refrigerant pipe joint
Refregerant pipe (flared) [6.35
35-
30-
157
100
161
Gas refregerant pipe joint
Refregerant pipe (flared) [12.7 (MU-GA50VB) [15.88 (MU-GA60VB)
74
Open as a rule 500mm or more if the front and both sides are open
100mm or more
100mm or more
200mm or more if there are obstacles to both sides
360
500 840
121
850
430
Open as a rule
80
500mm or more if the back, both sides and top are open
9
155
90
198
350mm or more
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) [9.52
30-
35-
Gas refrigerant pipe joint Refrigerant pipe (flared) [15.88
Page 10
6
WIRING DIAGRAM
MU-GA50VB -
OUTDOOR UNIT
TO INDOOR UNIT CONNECTING
E1
MODEL WIRING DIAGRAM
TB2
2
WHT
1
BLK
52C
12V
CIRCUIT BREAKER
POWER SUPPLY ~/N 230V 50Hz
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
DSAR
NOTES:
SURGE ABSORBER
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
NAME
: Connector
TB1
L
N
PE
BRN
BLU
GRN/YLW
SYMBOL
MC MF
TB1,TB2
52C
NO COM
COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK
NAME
BRN
WHT WHT
DSAR
C2
SYMBOL
52C
C
C1
RED
BLK
RED
1
ORN
2
WHT
3
BLU
4
COMPRESSOR CONTACTOR
S
RED ORN WHT BLK
MC
R
MF
NAME
MU-GA60VB -
OUTDOOR UNIT
TO INDOOR UNIT CONNECTING 12V
POWER SUPPLY ~/N 230V 50Hz
E1
CIRCUIT BREAKER
MODEL WIRING DIAGRAM
TB2
2
WHT
BRN
BLU
BLU
BRN
X1
DSAR
52C
NO
NO
PE
1
BRN
L
N
BLK
X1
WHT
52C
BRN
GRN/YLW
TB1
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
DSAR
NOTES:
SURGE ABSORBER
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate.
: Terminal block
NAME
: Connector
SYMBOL
MC
MF
TB1,TB2
COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK
10
COM
NAME
COM
C1
C2
SYMBOL
X1
52C
WHT
RED
BLK
ORN WHT
BLU
RELAY COMPRESSOR CONTACTOR
S
1 2 3 4
MC
REDRED ORN WHT BLK
C
R
MF
NAME
Page 11
MU-GA80VB -
OUTDOOR UNIT
E1
MODEL WIRING DIAGRAM
RT62 RT63
LEV
BRN
DSAR
CIRCUIT BREAKER
TB1
L N
N
3
TB2
PE
GRN/YLW
SYMBOL
BLU
MC
MF
NR61
RT62 RT63
SR61
BRN
BLU
BRN
1
WHT
COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DISCHARGE TEMPERATURE THERMIST OR AMBIENT TEMPERA TURE THERMIST OR SOLID STATE RELAY
~ / N 230V 50Hz
POWER SUPPLY
12V
TO INDOOR UNIT CONNECTING
SYMBOL
CZ SURGE ABSORBER
CZ
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
DSAR
F61
LEV
NOTE 1. Use copper conductors only (For field wiring).
SURGE ABSORBER FUSE(3.15A) EXPANSION VALVE COIL
2. Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N).
3. Symbols below indicate.
/: Terminal block, : Connector
NAME
CN662
X52
DEICER P.C. BOARD
2
52C
WHT
CZ
CN724
NAME NAME
6
A1 A2BLU
SR62 SR61
T61
YLW
YLW
123
NR61
WHT
52C
MF
WHT
ORN
BLK
21
3456
BLK
WHT
CN711
X52
C1
SYMBOL
SR62
COM
F61
RED
TB1 TB2 T61 X52 52C
RED
RED
ORN
C2
TAB52
NO
CN730
7 5 3 1
C
MC
S
BLK
R
BLU
RED
BLU
SOLID STATE RELAY TERMINAL BLOCK TERMINAL BLOCK TRANSFORMER CONTACTOR COMPRESSOR CONTACTOR
11
Page 12
7
REFRIGERANT SYSTEM DIAGRAM
MU-GA50VB -
OUTDOOR UNIT
E1
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Stop valve (with service port)
Compressor
Stop valve
Capillary tube
[3.0o[1.6o600
Muffler
Strainer
#100
Unit:mm
Outdoor heat exchanger
MU-GA60VB -
OUTDOOR UNIT
E1
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Stop valve (with service port)
Stop valve
Capillary tube [3.0X[1.8X500
Muffler
Muffler
#100
Outdoor heat exchanger
Compressor
Refrigerant flow in cooling
12
Page 13
MU-GA80VB -
Indoor unit
wMax. Height
difference: 10m(MS-GA50/GA60VB)/ 15m(MS-GA80VB)
A
Refrigerant Piping Max. Length
w Height difference should be within 10m(MS-GA50/GA60VB)/ 15m(MS-GA80VB) regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Outdoor heat exchanger
Flared connection
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve (with service port)
Capillary tube [3.6[2.450
Refrigerant flow in cooling
Compressor
Refrigerant pipe [15.88 (with heat insulator)
Refrigerant pipe [9.52 (with heat insulator)
LEV
Muffler
Muffler
Strainer
Ambient temperature thermistor RT63
Capillary tube [4.0[2.4200 (Upper path)
Capillary tube [4.0[2.4100 (Lower path)
Model
Piping size O.D : mm Length of connecting pipe : m
Refrigerant piping
Max. length : m
A
25
30
Indoor unit
Gas 0.43
Liquid 0.5
Gas
12.7
15.88
Liquid
6.35
9.52
MU-GA50VB - E1
MU-GA60VB - E1 MU-GA80VB - E1
Outdoor unit
Gas 0
Liquid 0
OUTDOOR UNIT
E1
Unit:mm
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
13
Page 14
Model
MU-GA50VB -
E1
Refrigerant piping length (one way)
Outdoor unit precharged
1,450
15m
160
20m
260
25m
360
7m
0
10m
60
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
Model
MU-GA60VB -
E1
Refrigerant piping length (one way)
Outdoor unit precharged
2,000
15m
160
20m
260
25m
360
7m
0
10m
60
Outdoor unit
precharged
2,400
0 165 440 715 990 1,165
Refrigerant piping length (one way)
15m10m7m
20m
25m 30m
Model
MU-GA80VB -
E1
Calculation : Xg=20g/m (Refrigerant piping length (m)–7)
Calculation : Xg=20g/m (Refrigerant piping length (m)–7)
Calculation : Xg=55g/mo(Refrigerant piping length(m)-7)
14
Page 15
8
11.6
10.5
7.5
8.5
9.5
12.8
16.3
10.2
13.1
11.6
14.6
18.0
17.4
13.9
12.4
10.8
15.6
19.2
MU-GA50VB - E1
MS-GA60VB - E1
MS-GA50VB - E1
MU-GA60VB - E1
MS-GA80VB - E1
MU-GA80VB - E1
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
PERFORMANCE CURVES
MU-GA50VB - MU-GA60VB - MU-GA80VB -
E1E1E1
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB (4) Total input: W
}
Cooling
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
11
Both indoor and outdoor unit are under the same
temperature/humidity condition.
Dry-bulb temperature
15
Relative humidity(%) 20 25
50 60
30 70
Page 16
18
32
70(%)
230V
15 20
50
25 60
30 35
0.6
0.7
0.8
0.9
1.0
1.1
(:)
6
7
8
9
10
11
18
32
70(%)
230V
15 20
50
25 60
30 35
10
11
12
13
14
15
16
(:)
22
18
32
70(%)
230V
15 20
50
25 60
30 35
0.7
0.8
0.9
1.0
1.1
1.2
(:)
7
8
9
10
11
12
15 20
50
25 60
30 70(%)
35(:)
5
6
9
7
8
18 32
230V
18
32
70(%)
230V
15 20
50
25 60
30 35
0.6
0.7
0.8
0.9
1.0
1.1
(:)
6
7
8
9
10
11
15 20
50
25 60
30 70(%)
35(:)
7
8
12
9
11
10
18 32
230V
Air flow should be set at MAX.
33
The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
(kgf/F[Gauge])(MPa[Gauge])
MU-GA50VB -
MU-GA60VB -
E1
MU-GA50VB -
E1
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
E1
MU-GA60VB -
E1
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
MU-GA80VB -
Ambient temperature(˚C) Ambient humidity(%)
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
E1
MU-GA80VB -
E1
Outdoor unit current(A)
Ambient temperature(˚C) Ambient humidity(%)
16
Page 17
PERFORMANCE DATA COOL operation
MS-GA50VB - : MU-GA50VB - (230V)
CAPACITY : 5.0(kW) SHF : 0.65 INPUT : 1810(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 18 5.88 2.76 0.47 1448 5.63 2.64 0.47 1520 5.40 2.54 0.47 1593 5.20 2.44 0.47 1665 21 20 6.13 2.14 0.35 1520 5.88 2.06 0.35 1611 5.70 2.00 0.35 1647 5.50 1.93 0.35 1720 22 18 5.88 3.00 0.51 1448 5.63 2.87 0.51 1520 5.40 2.75 0.51 1593 5.20 2.65 0.51 1665 22 20 6.13 2.39 0.39 1520 5.88 2.29 0.39 1611 5.70 2.22 0.39 1647 5.50 2.15 0.39 1720 22 22 6.38 1.72 0.27 1575 6.15 1.66 0.27 1674 6.00 1.62 0.27 1720 5.75 1.55 0.27 1792 23 18 5.88 3.23 0.55 1448 5.63 3.09 0.55 1520 5.40 2.97 0.55 1593 5.20 2.86 0.55 1665 23 20 6.13 2.63 0.43 1520 5.88 2.53 0.43 1611 5.70 2.45 0.43 1647 5.50 2.37 0.43 1720 23 22 6.38 1.98 0.31 1575 6.15 1.91 0.31 1674 6.00 1.86 0.31 1720 5.75 1.78 0.31 1792 24 18 5.88 3.47 0.59 1448 5.63 3.32 0.59 1520 5.40 3.19 0.59 1593 5.20 3.07 0.59 1665 24 20 6.13 2.88 0.47 1520 5.88 2.76 0.47 1611 5.70 2.68 0.47 1647 5.50 2.59 0.47 1720 24 22 6.38 2.23 0.35 1575 6.15 2.15 0.35 1674 6.00 2.10 0.35 1720 5.75 2.01 0.35 1792 24 24 6.70 1.54 0.23 1647 6.45 1.48 0.23 1738 6.30 1.45 0.23 1792 6.10 1.40 0.23 1882 25 18 5.88 3.70 0.63 1448 5.63 3.54 0.63 1520 5.40 3.40 0.63 1593 5.20 3.28 0.63 1665 25 20 6.13 3.12 0.51 1520 5.88 3.00 0.51 1611 5.70 2.91 0.51 1647 5.50 2.81 0.51 1720 25 22 6.38 2.49 0.39 1575 6.15 2.40 0.39 1674 6.00 2.34 0.39 1720 5.75 2.24 0.39 1792 25 24 6.70 1.81 0.27 1647 6.45 1.74 0.27 1738 6.30 1.70 0.27 1792 6.10 1.65 0.27 1882 26 18 5.88 3.94 0.67 1448 5.63 3.77 0.67 1520 5.40 3.62 0.67 1593 5.20 3.48 0.67 1665 26 20 6.13 3.37 0.55 1520 5.88 3.23 0.55 1611 5.70 3.14 0.55 1647 5.50 3.03 0.55 1720 26 22 6.38 2.74 0.43 1575 6.15 2.64 0.43 1674 6.00 2.58 0.43 1720 5.75 2.47 0.43 1792 26 24 6.70 2.08 0.31 1647 6.45 2.00 0.31 1738 6.30 1.95 0.31 1792 6.10 1.89 0.31 1882 26 26 6.90 1.31 0.19 1738 6.70 1.27 0.19 1828 6.60 1.25 0.19 1882 6.40 1.22 0.19 1937 27 18 5.88 4.17 0.71 1448 5.63 3.99 0.71 1520 5.40 3.83 0.71 1593 5.20 3.69 0.71 1665 27 20 6.13 3.61 0.59 1520 5.88 3.47 0.59 1611 5.70 3.36 0.59 1647 5.50 3.25 0.59 1720 27 22 6.38 3.00 0.47 1575 6.15 2.89 0.47 1674 6.00 2.82 0.47 1720 5.75 2.70 0.47 1792 27 24 6.70 2.35 0.35 1647 6.45 2.26 0.35 1738 6.30 2.21 0.35 1792 6.10 2.14 0.35 1882 27 26 6.90 1.59 0.23 1738 6.70 1.54 0.23 1828 6.60 1.52 0.23 1882 6.40 1.47 0.23 1937 28 18 5.88 4.41 0.75 1448 5.63 4.22 0.75 1520 5.40 4.05 0.75 1593 5.20 3.90 0.75 1665 28 20 6.13 3.86 0.63 1520 5.88 3.70 0.63 1611 5.70 3.59 0.63 1647 5.50 3.47 0.63 1720 28 22 6.38 3.25 0.51 1575 6.15 3.14 0.51 1674 6.00 3.06 0.51 1720 5.75 2.93 0.51 1792 28 24 6.70 2.61 0.39 1647 6.45 2.52 0.39 1738 6.30 2.46 0.39 1792 6.10 2.38 0.39 1882 28 26 6.90 1.86 0.27 1738 6.70 1.81 0.27 1828 6.60 1.78 0.27 1882 6.40 1.73 0.27 1937 29 18 5.88 4.64 0.79 1448 5.63 4.44 0.79 1520 5.40 4.27 0.79 1593 5.20 4.11 0.79 1665 29 20 6.13 4.10 0.67 1520 5.88 3.94 0.67 1611 5.70 3.82 0.67 1647 5.50 3.69 0.67 1720 29 22 6.38 3.51 0.55 1575 6.15 3.38 0.55 1674 6.00 3.30 0.55 1720 5.75 3.16 0.55 1792 29 24 6.70 2.88 0.43 1647 6.45 2.77 0.43 1738 6.30 2.71 0.43 1792 6.10 2.62 0.43 1882 29 26 6.90 2.14 0.31 1738 6.70 2.08 0.31 1828 6.60 2.05 0.31 1882 6.40 1.98 0.31 1937 30 18 5.88 4.88 0.83 1448 5.63 4.67 0.83 1520 5.40 4.48 0.83 1593 5.20 4.32 0.83 1665 30 20 6.13 4.35 0.71 1520 5.88 4.17 0.71 1611 5.70 4.05 0.71 1647 5.50 3.91 0.71 1720 30 22 6.38 3.76 0.59 1575 6.15 3.63 0.59 1674 6.00 3.54 0.59 1720 5.75 3.39 0.59 1792 30 24 6.70 3.15 0.47 1647 6.45 3.03 0.47 1738 6.30 2.96 0.47 1792 6.10 2.87 0.47 1882 30 26 6.90 2.42 0.35 1738 6.70 2.35 0.35 1828 6.60 2.31 0.35 1882 6.40 2.24 0.35 1937 31 18 5.88 5.11 0.87 1448 5.63 4.89 0.87 1520 5.40 4.70 0.87 1593 5.20 4.52 0.87 1665 31 20 6.13 4.59 0.75 1520 5.88 4.41 0.75 1611 5.70 4.28 0.75 1647 5.50 4.13 0.75 1720 31 22 6.38 4.02 0.63 1575 6.15 3.87 0.63 1674 6.00 3.78 0.63 1720 5.75 3.62 0.63 1792 31 24 6.70 3.42 0.51 1647 6.45 3.29 0.51 1738 6.30 3.21 0.51 1792 6.10 3.11 0.51 1882 31 26 6.90 2.69 0.39 1738 6.70 2.61 0.39 1828 6.60 2.57 0.39 1882 6.40 2.50 0.39 1937 32 18 5.88 5.35 0.91 1448 5.63 5.12 0.91 1520 5.40 4.91 0.91 1593 5.20 4.73 0.91 1665 32 20 6.13 4.84 0.79 1520 5.88 4.64 0.79 1611 5.70 4.50 0.79 1647 5.50 4.35 0.79 1720 32 22 6.38 4.27 0.67 1575 6.15 4.12 0.67 1674 6.00 4.02 0.67 1720 5.75 3.85 0.67 1792 32 24 6.70 3.69 0.55 1647 6.45 3.55 0.55 1738 6.30 3.47 0.55 1792 6.10 3.36 0.55 1882 32 26 6.90 2.97 0.43 1738 6.70 2.88 0.43 1828 6.60 2.84 0.43 1882 6.40 2.75 0.43 1937
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
21 2725
E1E1
OUTDOOR DB(:)
17
Page 18
21 18 4.90 2.30 0.47 1774 4.50 2.12 0.47 1882 4.33 2.03 0.47 1919 21 20 5.15 1.80 0.35 1846 4.80 1.68 0.35 1937 4.63 1.62 0.35 1991 22 18 4.90 2.50 0.51 1774 4.50 2.30 0.51 1882 4.33 2.21 0.51 1919 22 20 5.15 2.01 0.39 1846 4.80 1.87 0.39 1937 4.63 1.80 0.39 1991 22 22 5.45 1.47 0.27 1919 5.10 1.38 0.27 2027 4.93 1.33 0.27 2063 23 18 4.90 2.70 0.55 1774 4.50 2.48 0.55 1882 4.33 2.38 0.55 1919 23 20 5.15 2.21 0.43 1846 4.80 2.06 0.43 1937 4.63 1.99 0.43 1991 23 22 5.45 1.69 0.31 1919 5.10 1.58 0.31 2027 4.93 1.53 0.31 2063 24 18 4.90 2.89 0.59 1774 4.50 2.66 0.59 1882 4.33 2.55 0.59 1919 24 20 5.15 2.42 0.47 1846 4.80 2.26 0.47 1937 4.63 2.17 0.47 1991 24 22 5.45 1.91 0.35 1919 5.10 1.79 0.35 2027 4.93 1.72 0.35 2063 24 24 5.75 1.32 0.23 1991 5.40 1.24 0.23 2082 5.25 1.21 0.23 2127 25 18 4.90 3.09 0.63 1774 4.50 2.84 0.63 1882 4.33 2.72 0.63 1919 25 20 5.15 2.63 0.51 1846 4.80 2.45 0.51 1937 4.63 2.36 0.51 1991 25 22 5.45 2.13 0.39 1919 5.10 1.99 0.39 2027 4.93 1.92 0.39 2063 25 24 5.75 1.55 0.27 1991 5.40 1.46 0.27 2082 5.25 1.42 0.27 2127 26 18 4.90 3.28 0.67 1774 4.50 3.02 0.67 1882 4.33 2.90 0.67 1919 26 20 5.15 2.83 0.55 1846 4.80 2.64 0.55 1937 4.63 2.54 0.55 1991 26 22 5.45 2.34 0.43 1919 5.10 2.19 0.43 2027 4.93 2.12 0.43 2063 26 24 5.75 1.78 0.31 1991 5.40 1.67 0.31 2082 5.25 1.63 0.31 2127 26 26 6.05 1.15 0.19 2063 5.70 1.08 0.19 2154 5.53 1.05 0.19 2199 27 18 4.90 3.48 0.71 1774 4.50 3.20 0.71 1882 4.33 3.07 0.71 1919 27 20 5.15 3.04 0.59 1846 4.80 2.83 0.59 1937 4.63 2.73 0.59 1991 27 22 5.45 2.56 0.47 1919 5.10 2.40 0.47 2027 4.93 2.31 0.47 2063 27 24 5.75 2.01 0.35 1991 5.40 1.89 0.35 2082 5.25 1.84 0.35 2127 27 26 6.05 1.39 0.23 2063 5.70 1.31 0.23 2154 5.53 1.27 0.23 2199 28 18 4.90 3.68 0.75 1774 4.50 3.38 0.75 1882 4.33 3.24 0.75 1919 28 20 5.15 3.24 0.63 1846 4.80 3.02 0.63 1937 4.63 2.91 0.63 1991 28 22 5.45 2.78 0.51 1919 5.10 2.60 0.51 2027 4.93 2.51 0.51 2063 28 24 5.75 2.24 0.39 1991 5.40 2.11 0.39 2082 5.25 2.05 0.39 2127 28 26 6.05 1.63 0.27 2063 5.70 1.54 0.27 2154 5.53 1.49 0.27 2199 29 18 4.90 3.87 0.79 1774 4.50 3.56 0.79 1882 4.33 3.42 0.79 1919 29 20 5.15 3.45 0.67 1846 4.80 3.22 0.67 1937 4.63 3.10 0.67 1991 29 22 5.45 3.00 0.55 1919 5.10 2.81 0.55 2027 4.93 2.71 0.55 2063 29 24 5.75 2.47 0.43 1991 5.40 2.32 0.43 2082 5.25 2.26 0.43 2127 29 26 6.05 1.88 0.31 2063 5.70 1.77 0.31 2154 5.53 1.71 0.31 2199 30 18 4.90 4.07 0.83 1774 4.50 3.74 0.83 1882 4.33 3.59 0.83 1919 30 20 5.15 3.66 0.71 1846 4.80 3.41 0.71 1937 4.63 3.28 0.71 1991 30 22 5.45 3.22 0.59 1919 5.10 3.01 0.59 2027 4.93 2.91 0.59 2063 30 24 5.75 2.70 0.47 1991 5.40 2.54 0.47 2082 5.25 2.47 0.47 2127 30 26 6.05 2.12 0.35 2063 5.70 2.00 0.35 2154 5.53 1.93 0.35 2199 31 18 4.90 4.26 0.87 1774 4.50 3.92 0.87 1882 4.33 3.76 0.87 1919 31 20 5.15 3.86 0.75 1846 4.80 3.60 0.75 1937 4.63 3.47 0.75 1991 31 22 5.45 3.43 0.63 1919 5.10 3.21 0.63 2027 4.93 3.10 0.63 2063 31 24 5.75 2.93 0.51 1991 5.40 2.75 0.51 2082 5.25 2.68 0.51 2127 31 26 6.05 2.36 0.39 2063 5.70 2.22 0.39 2154 5.53 2.15 0.39 2199 32 18 4.90 4.46 0.91 1774 4.50 4.10 0.91 1882 4.33 3.94 0.91 1919 32 20 5.15 4.07 0.79 1846 4.80 3.79 0.79 1937 4.63 3.65 0.79 1991 32 22 5.45 3.65 0.67 1919 5.10 3.42 0.67 2027 4.93 3.30 0.67 2063 32 24 5.75 3.16 0.55 1991 5.40 2.97 0.55 2082 5.25 2.89 0.55 2127 32 26 6.05 2.60 0.43 2063 5.70 2.45 0.43 2154 5.53 2.38 0.43 2199
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
35 4340
Q SHC SHF INPUT
Q
SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 5.0(kW) SHF : 0.65 INPUT : 1810(W)
PERFORMANCE DATA COOL operation
MS-GA50VB - : MU-GA50VB - (230V)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
E1E1
18
Page 19
PERFORMANCE DATA COOL operation
MS-GA60VB - : MU-GA60VB - (230V)
CAPACITY : 6.5(kW) SHF : 0.63 INPUT : 2480(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 18 7.64 3.44 0.45 1984 7.31 3.29 0.45 2083 7.02 3.16 0.45 2182 6.76 3.04 0.45 21 20 7.96 2.63 0.33 2083 7.64 2.52 0.33 2207 7.41 2.45 0.33 2257 7.15 2.36 0.33 22 18 7.64 3.74 0.49 1984 7.31 3.58 0.49 2083 7.02 3.44 0.49 2182 6.76 3.31 0.49 22 20 7.96 2.95 0.37 2083 7.64 2.83 0.37 2207 7.41 2.74 0.37 2257 7.15 2.65 0.37 22 22 8.29 2.07 0.25 2158 8.00 2.00 0.25 2294 7.80 1.95 0.25 2356 7.48 1.87 0.25 23 18 7.64 4.05 0.53 1984 7.31 3.88 0.53 2083 7.02 3.72 0.53 2182 6.76 3.58 0.53 23 20 7.96 3.26 0.41 2083 7.64 3.13 0.41 2207 7.41 3.04 0.41 2257 7.15 2.93 0.41 23 22 8.29 2.40 0.29 2158 8.00 2.32 0.29 2294 7.80 2.26 0.29 2356 7.48 2.17 0.29 24 18 7.64 4.35 0.57 1984 7.31 4.17 0.57 2083 7.02 4.00 0.57 2182 6.76 3.85 0.57 24 20 7.96 3.58 0.45 2083 7.64 3.44 0.45 2207 7.41 3.33 0.45 2257 7.15 3.22 0.45 24 22 8.29 2.73 0.33 2158 8.00 2.64 0.33 2294 7.80 2.57 0.33 2356 7.48 2.47 0.33 24 24 8.71 1.83 0.21 2257 8.39 1.76 0.21 2381 8.19 1.72 0.21 2455 7.93 1.67 0.21 25 18 7.64 4.66 0.61 1984 7.31 4.46 0.61 2083 7.02 4.28 0.61 2182 6.76 4.12 0.61 25 20 7.96 3.90 0.49 2083 7.64 3.74 0.49 2207 7.41 3.63 0.49 2257 7.15 3.50 0.49 25 22 8.29 3.07 0.37 2158 8.00 2.96 0.37 2294 7.80 2.89 0.37 2356 7.48 2.77 0.37 25 24 8.71 2.18 0.25 2257 8.39 2.10 0.25 2381 8.19 2.05 0.25 2455 7.93 1.98 0.25 26 18 7.64 4.96 0.65 1984 7.31 4.75 0.65 2083 7.02 4.56 0.65 2182 6.76 4.39 0.65 26 20 7.96 4.22 0.53 2083 7.64 4.05 0.53 2207 7.41 3.93 0.53 2257 7.15 3.79 0.53 26 22 8.29 3.40 0.41 2158 8.00 3.28 0.41 2294 7.80 3.20 0.41 2356 7.48 3.06 0.41 26 24 8.71 2.53 0.29 2257 8.39 2.43 0.29 2381 8.19 2.38 0.29 2455 7.93 2.30 0.29 26 26 8.97 1.52 0.17 2381 8.71 1.48 0.17 2505 8.58 1.46 0.17 2579 8.32 1.41 0.17 27 18 7.64 5.27 0.69 1984 7.31 5.05 0.69 2083 7.02 4.84 0.69 2182 6.76 4.66 0.69 27 20 7.96 4.54 0.57 2083 7.64 4.35 0.57 2207 7.41 4.22 0.57 2257 7.15 4.08 0.57 27 22 8.29 3.73 0.45 2158 8.00 3.60 0.45 2294 7.80 3.51 0.45 2356 7.48 3.36 0.45 27 24 8.71 2.87 0.33 2257 8.39 2.77 0.33 2381 8.19 2.70 0.33 2455 7.93 2.62 0.33 27 26 8.97 1.88 0.21 2381 8.71 1.83 0.21 2505 8.58 1.80 0.21 2579 8.32 1.75 0.21 28 18 7.64 5.58 0.73 1984 7.31 5.34 0.73 2083 7.02 5.12 0.73 2182 6.76 4.93 0.73 28 20 7.96 4.86 0.61 2083 7.64 4.66 0.61 2207 7.41 4.52 0.61 2257 7.15 4.36 0.61 28 22 8.29 4.06 0.49 2158 8.00 3.92 0.49 2294 7.80 3.82 0.49 2356 7.48 3.66 0.49 28 24 8.71 3.22 0.37 2257 8.39 3.10 0.37 2381 8.19 3.03 0.37 2455 7.93 2.93 0.37 28 26 8.97 2.24 0.25 2381 8.71 2.18 0.25 2505 8.58 2.15 0.25 2579 8.32 2.08 0.25 29 18 7.64 5.88 0.77 1984 7.31 5.63 0.77 2083 7.02 5.41 0.77 2182 6.76 5.21 0.77 29 20 7.96 5.18 0.65 2083 7.64 4.96 0.65 2207 7.41 4.82 0.65 2257 7.15 4.65 0.65 29 22 8.29 4.39 0.53 2158 8.00 4.24 0.53 2294 7.80 4.13 0.53 2356 7.48 3.96 0.53 29 24 8.71 3.57 0.41 2257 8.39 3.44 0.41 2381 8.19 3.36 0.41 2455 7.93 3.25 0.41 29 26 8.97 2.60 0.29 2381 8.71 2.53 0.29 2505 8.58 2.49 0.29 2579 8.32 2.41 0.29 30 18 7.64 6.19 0.81 1984 7.31 5.92 0.81 2083 7.02 5.69 0.81 2182 6.76 5.48 0.81 30 20 7.96 5.49 0.69 2083 7.64 5.27 0.69 2207 7.41 5.11 0.69 2257 7.15 4.93 0.69 30 22 8.29 4.72 0.57 2158 8.00 4.56 0.57 2294 7.80 4.45 0.57 2356 7.48 4.26 0.57 30 24 8.71 3.92 0.45 2257 8.39 3.77 0.45 2381 8.19 3.69 0.45 2455 7.93 3.57 0.45 30 26 8.97 2.96 0.33 2381 8.71 2.87 0.33 2505 8.58 2.83 0.33 2579 8.32 2.75 0.33 31 18 7.64 6.49 0.85 1984 7.31 6.22 0.85 2083 7.02 5.97 0.85 2182 6.76 5.75 0.85 31 20 7.96 5.81 0.73 2083 7.64 5.58 0.73 2207 7.41 5.41 0.73 2257 7.15 5.22 0.73 31 22 8.29 5.06 0.61 2158 8.00 4.88 0.61 2294 7.80 4.76 0.61 2356 7.48 4.56 0.61 31 24 8.71 4.27 0.49 2257 8.39 4.11 0.49 2381 8.19 4.01 0.49 2455 7.93 3.89 0.49 31 26 8.97 3.32 0.37 2381 8.71 3.22 0.37 2505 8.58 3.17 0.37 2579 8.32 3.08 0.37 32 18 7.64 6.80 0.89 1984 7.31 6.51 0.89 2083 7.02 6.25 0.89 2182 6.76 6.02 0.89 32 20 7.96 6.13 0.77 2083 7.64 5.88 0.77 2207 7.41 5.71 0.77 2257 7.15 5.51 0.77 32 22 8.29 5.39 0.65 2158 8.00 5.20 0.65 2294 7.80 5.07 0.65 2356 7.48 4.86 0.65 32 24 8.71 4.62 0.53 2257 8.39 4.44 0.53 2381 8.19 4.34 0.53 2455 7.93 4.20 0.53 32 26 8.97 3.68 0.41 2381 8.71 3.57 0.41 2505 8.58 3.52 0.41 2579 8.32 3.41 0.41
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q
21 2725
E1E1
OUTDOOR DB(:)
SHC
SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
19
2282 2356 2282 2356 2455 2282 2356 2455 2282 2356 2455 2579 2282 2356 2455 2579 2282 2356 2455 2579 2654 2282 2356 2455 2579 2654 2282 2356 2455 2579 2654 2282 2356 2455 2579 2654 2282 2356 2455 2579 2654 2282 2356 2455 2579 2654 2282 2356 2455 2579 2654
Page 20
21 18 6.37 2.87 0.45 2430 5.85 2.63 0.45 2579 5.62 2.53 0.45 2629 21 20 6.70 2.21 0.33 2530 6.24 2.06 0.33 2654 6.01 1.98 0.33 2728 22 18 6.37 3.12 0.49 2430 5.85 2.87 0.49 2579 5.62 2.76 0.49 2629 22 20 6.70 2.48 0.37 2530 6.24 2.31 0.37 2654 6.01 2.22 0.37 2728 22 22 7.09 1.77 0.25 2629 6.63 1.66 0.25 2778 6.40 1.60 0.25 2827 23 18 6.37 3.38 0.53 2430 5.85 3.10 0.53 2579 5.62 2.98 0.53 2629 23 20 6.70 2.74 0.41 2530 6.24 2.56 0.41 2654 6.01 2.47 0.41 2728 23 22 7.09 2.05 0.29 2629 6.63 1.92 0.29 2778 6.40 1.86 0.29 2827 24 18 6.37 3.63 0.57 2430 5.85 3.33 0.57 2579 5.62 3.20 0.57 2629 24 20 6.70 3.01 0.45 2530 6.24 2.81 0.45 2654 6.01 2.71 0.45 2728 24 22 7.09 2.34 0.33 2629 6.63 2.19 0.33 2778 6.40 2.11 0.33 2827 24 24 7.48 1.57 0.21 2728 7.02 1.47 0.21 2852 6.83 1.43 0.21 2914 25 18 6.37 3.89 0.61 2430 5.85 3.57 0.61 2579 5.62 3.43 0.61 2629 25 20 6.70 3.28 0.49 2530 6.24 3.06 0.49 2654 6.01 2.95 0.49 2728 25 22 7.09 2.62 0.37 2629 6.63 2.45 0.37 2778 6.40 2.37 0.37 2827 25 24 7.48 1.87 0.25 2728 7.02 1.76 0.25 2852 6.83 1.71 0.25 2914 26 18 6.37 4.14 0.65 2430 5.85 3.80 0.65 2579 5.62 3.65 0.65 2629 26 20 6.70 3.55 0.53 2530 6.24 3.31 0.53 2654 6.01 3.19 0.53 2728 26 22 7.09 2.90 0.41 2629 6.63 2.72 0.41 2778 6.40 2.63 0.41 2827 26 24 7.48 2.17 0.29 2728 7.02 2.04 0.29 2852 6.83 1.98 0.29 2914 26 26 7.87 1.34 0.17 2827 7.41 1.26 0.17 2951 7.18 1.22 0.17 3013 27 18 6.37 4.40 0.69 2430 5.85 4.04 0.69 2579 5.62 3.88 0.69 2629 27 20 6.70 3.82 0.57 2530 6.24 3.56 0.57 2654 6.01 3.43 0.57 2728 27 22 7.09 3.19 0.45 2629 6.63 2.98 0.45 2778 6.40 2.88 0.45 2827 27 24 7.48 2.47 0.33 2728 7.02 2.32 0.33 2852 6.83 2.25 0.33 2914 27 26 7.87 1.65 0.21 2827 7.41 1.56 0.21 2951 7.18 1.51 0.21 3013 28 18 6.37 4.65 0.73 2430 5.85 4.27 0.73 2579 5.62 4.10 0.73 2629 28 20 6.70 4.08 0.61 2530 6.24 3.81 0.61 2654 6.01 3.67 0.61 2728 28 22 7.09 3.47 0.49 2629 6.63 3.25 0.49 2778 6.40 3.14 0.49 2827 28 24 7.48 2.77 0.37 2728 7.02 2.60 0.37 2852 6.83 2.53 0.37 2914 28 26 7.87 1.97 0.25 2827 7.41 1.85 0.25 2951 7.18 1.80 0.25 3013 29 18 6.37 4.90 0.77 2430 5.85 4.50 0.77 2579 5.62 4.33 0.77 2629 29 20 6.70 4.35 0.65 2530 6.24 4.06 0.65 2654 6.01 3.91 0.65 2728 29 22 7.09 3.76 0.53 2629 6.63 3.51 0.53 2778 6.40 3.39 0.53 2827 29 24 7.48 3.06 0.41 2728 7.02 2.88 0.41 2852 6.83 2.80 0.41 2914 29 26 7.87 2.28 0.29 2827 7.41 2.15 0.29 2951 7.18 2.08 0.29 3013 30 18 6.37 5.16 0.81 2430 5.85 4.74 0.81 2579 5.62 4.55 0.81 2629 30 20 6.70 4.62 0.69 2530 6.24 4.31 0.69 2654 6.01 4.15 0.69 2728 30 22 7.09 4.04 0.57 2629 6.63 3.78 0.57 2778 6.40 3.65 0.57 2827 30 24 7.48 3.36 0.45 2728 7.02 3.16 0.45 2852 6.83 3.07 0.45 2914 30 26 7.87 2.60 0.33 2827 7.41 2.45 0.33 2951 7.18 2.37 0.33 3013 31 18 6.37 5.41 0.85 2430 5.85 4.97 0.85 2579 5.62 4.78 0.85 2629 31 20 6.70 4.89 0.73 2530 6.24 4.56 0.73 2654 6.01 4.39 0.73 2728 31 22 7.09 4.32 0.61 2629 6.63 4.04 0.61 2778 6.40 3.91 0.61 2827 31 24 7.48 3.66 0.49 2728 7.02 3.44 0.49 2852 6.83 3.34 0.49 2914 31 26 7.87 2.91 0.37 2827 7.41 2.74 0.37 2951 7.18 2.66 0.37 3013 32 18 6.37 5.67 0.89 2430 5.85 5.21 0.89 2579 5.62 5.00 0.89 2629 32 20 6.70 5.16 0.77 2530 6.24 4.80 0.77 2654 6.01 4.63 0.77 2728 32 22 7.09 4.61 0.65 2629 6.63 4.31 0.65 2778 6.40 4.16 0.65 2827 32 24 7.48 3.96 0.53 2728 7.02 3.72 0.53 2852 6.83 3.62 0.53 2914 32 26 7.87 3.22 0.41 2827 7.41 3.04 0.41 2951 7.18 2.94 0.41 3013
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
35 4340
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 6.5(kW) SHF : 0.63 INPUT : 2480(W)
PERFORMANCE DATA COOL operation
MS-GA60VB - : MU-GA60VB - (230V)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
E1E1
20
Page 21
PERFORMANCE DATA COOL operation
MS-GA80VB - : MU-GA80VB - (230V)
CAPACITY : 8.5(kW) SHF : 0.62 INPUT : 3260(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 18 9.99 2608 9.56 4.21 0.44 2738 9.18 4.04 0.44 2869 8.84 3.89 0.44 2999 21 20 10.41 2738 9.99 3.20 0.32 2901 9.69 3.10 0.32 2967 9.35 2.99 0.32 3097 22 18 9.99 2608 9.56 4.59 0.48 2738 9.18 4.41 0.48 2869 8.84 4.24 0.48 2999 22 20 10.41 2738 9.99 3.60 0.36 2901 9.69 3.49 0.36 2967 9.35 3.37 0.36 3097 22 22 10.84 2836 10.46 2.51 0.24 3016 10.20 2.45 0.24 3097 9.78 2.35 0.24 3227 23 18 9.99 2608 9.56 4.97 0.52 2738 9.18 4.77 0.52 2869 8.84 4.60 0.52 2999 23 20 10.41 2738 9.99 4.00 0.40 2901 9.69 3.88 0.40 2967 9.35 3.74 0.40 3097 23 22 10.84 2836 10.46 2.93 0.28 3016 10.20 2.86 0.28 3097 9.78 2.74 0.28 3227 24 18 9.99 2608 9.56 5.36 0.56 2738 9.18 5.14 0.56 2869 8.84 4.95 0.56 2999 24 20 10.41 2738 9.99 4.39 0.44 2901 9.69 4.26 0.44 2967 9.35 4.11 0.44 3097 24 22 10.84 2836 10.46 3.35 0.32 3016 10.20 3.26 0.32 3097 9.78 3.13 0.32 3227 24 24 11.39 2967 10.97 2.19 0.20 3130 10.71 2.14 0.20 3227 10.37 2.07 0.20 3390 25 18 9.99 2608 9.56 5.74 0.60 2738 9.18 5.51 0.60 2869 8.84 5.30 0.60 2999 25 20 10.41 2738 9.99 4.79 0.48 2901 9.69 4.65 0.48 2967 9.35 4.49 0.48 3097 25 22 10.84 2836 10.46 3.76 0.36 3016 10.20 3.67 0.36 3097 9.78 3.52 0.36 3227 25 24 11.39 2967 10.97 2.63 0.24 3130 10.71 2.57 0.24 3227 10.37 2.49 0.24 3390 26 18 9.99 2608 9.56 6.12 0.64 2738 9.18 5.88 0.64 2869 8.84 5.66 0.64 2999 26 20 10.41 2738 9.99 5.19 0.52 2901 9.69 5.04 0.52 2967 9.35 4.86 0.52 3097 26 22 10.84 2836 10.46 4.18 0.40 3016 10.20 4.08 0.40 3097 9.78 3.91 0.40 3227 26 24 11.39 2967 10.97 3.07 0.28 3130 10.71 3.00 0.28 3227 10.37 2.90 0.28 3390 26 26 11.73 3130 11.39 1.82 0.16 3293 11.22 1.80 0.16 3390 10.88 1.74 0.16 3488 27 18 9.99 2608 9.56 6.50 0.68 2738 9.18 6.24 0.68 2869 8.84 6.01 0.68 2999 27 20 10.41 2738 9.99 5.59 0.56 2901 9.69 5.43 0.56 2967 9.35 5.24 0.56 3097 27 22 10.84 2836 10.46 4.60 0.44 3016 10.20 4.49 0.44 3097 9.78 4.30 0.44 3227 27 24 11.39 2967 10.97 3.51 0.32 3130 10.71 3.43 0.32 3227 10.37 3.32 0.32 3390 27 26 11.73 3130 11.39 2.28 0.20 3293 11.22 2.24 0.20 3390 10.88 2.18 0.20 3488 28 18 9.99 2608 9.56 6.89 0.72 2738 9.18 6.61 0.72 2869 8.84 6.36 0.72 2999 28 20 10.41 2738 9.99 5.99 0.60 2901 9.69 5.81 0.60 2967 9.35 5.61 0.60 3097 28 22 10.84 2836 10.46 5.02 0.48 3016 10.20 4.90 0.48 3097 9.78 4.69 0.48 3227 28 24 11.39 2967 10.97 3.95 0.36 3130 10.71 3.86 0.36 3227 10.37 3.73 0.36 3390 28 26 11.73 3130 11.39 2.73 0.24 3293 11.22 2.69 0.24 3390 10.88 2.61 0.24 3488 29 18 9.99 2608 9.56 7.27 0.76 2738 9.18 6.98 0.76 2869 8.84 6.72 0.76 2999 29 20 10.41 2738 9.99 6.39 0.64 2901 9.69 6.20 0.64 2967 9.35 5.98 0.64 3097 29 22 10.84 2836 10.46 5.44 0.52 3016 10.20 5.30 0.52 3097 9.78 5.08 0.52 3227 29 24 11.39 2967 10.97 4.39 0.40 3130 10.71 4.28 0.40 3227 10.37 4.15 0.40 3390 29 26 11.73 3130 11.39 3.19 0.28 3293 11.22 3.14 0.28 3390 10.88 3.05 0.28 3488 30 18 9.99 2608 9.56 7.65 0.80 2738 9.18 7.34 0.80 2869 8.84 7.07 0.80 2999 30 20 10.41 2738 9.99 6.79 0.68 2901 9.69 6.59 0.68 2967 9.35 6.36 0.68 3097 30 22 10.84 2836 10.46 5.85 0.56 3016 10.20 5.71 0.56 3097 9.78 5.47 0.56 3227 30 24 11.39 2967 10.97 4.82 0.44 3130 10.71 4.71 0.44 3227 10.37 4.56 0.44 3390 30 26 11.73 3130 11.39 3.64 0.32 3293 11.22 3.59 0.32 3390 10.88 3.48 0.32 3488 31 18 9.99 2608 9.56 8.03 0.84 2738 9.18 7.71 0.84 2869 8.84 7.43 0.84 2999 31 20 10.41 2738 9.99 7.19 0.72 2901 9.69 6.98 0.72 2967 9.35 6.73 0.72 3097 31 22 10.84 2836 10.46 6.27 0.60 3016 10.20 6.12 0.60 3097 9.78 5.87 0.60 3227 31 24 11.39 2967 10.97 5.26 0.48 3130 10.71 5.14 0.48 3227 10.37 4.98 0.48 3390 31 26 11.73 3130 11.39 4.10 0.36 3293 11.22 4.04 0.36 3390 10.88 3.92 0.36 3488 32 18 9.99 2608 9.56 8.42 0.88 2738 9.18 8.08 0.88 2869 8.84 7.78 0.88 2999 32 20 10.41 2738 9.99 7.59 0.76 2901 9.69 7.36 0.76 2967 9.35 7.11 0.76 3097 32 22 10.84 2836 10.46 6.69 0.64 3016 10.20 6.53 0.64 3097 9.78 6.26 0.64 3227 32 24 11.39 2967 10.97 5.70 0.52 3130 10.71 5.57 0.52 3227 10.37 5.39 0.52 3390 32 26 11.73
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q
21 2725
0.44
4.39
0.32
3.33
0.48
4.79
0.36
3.75
0.24
2.60
0.52
5.19
0.40
4.17
0.28
3.03
0.56
5.59
0.44
4.58
0.32
3.47
0.20
2.28
0.60
5.99
0.48
5.00
0.36
3.90
0.24
2.73
0.64
6.39
0.52
5.41
0.40
4.34
0.28
3.19
0.16
1.88
0.68
6.79
0.56
5.83
0.44
4.77
0.32
3.64
0.20
2.35
0.72
7.19
0.60
6.25
0.48
5.20
0.36
4.10
0.24
2.82
0.76
7.59
0.64
6.66
0.52
5.64
0.40
4.56
0.28
3.28
0.80
7.99
0.68
7.08
0.56
6.07
0.44
5.01
0.32
3.75
0.84
8.39
0.72
7.50
0.60
6.50
0.48
5.47
0.36
4.22
0.88
8.79
0.76
7.91
0.64
6.94
0.52
5.92
0.40 3130 11.39 4.56 0.40 3293 11.22 4.49 0.40 3390 10.88 4.35 0.40 3488
4.69
E1E1
OUTDOOR DB(:)
SHC
SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
21
Page 22
21 18 8.33 3.67 0.44 3195 7.65 3.37 0.44 3390 7.35 3.24 0.44 3456 21 20 8.76 2.80 0.32 3325 8.16 2.61 0.32 3488 7.86 2.52 0.32 3586 22 18 8.33 4.00 0.48 3195 7.65 3.67 0.48 3390 7.35 3.53 0.48 3456 22 20 8.76 3.15 0.36 3325 8.16 2.94 0.36 3488 7.86 2.83 0.36 3586 22 22 9.27 2.22 0.24 3456 8.67 2.08 0.24 3651 8.37 2.01 0.24 3716 23 18 8.33 4.33 0.52 3195 7.65 3.98 0.52 3390 7.35 3.82 0.52 3456 23 20 8.76 3.50 0.40 3325 8.16 3.26 0.40 3488 7.86 3.15 0.40 3586 23 22 9.27 2.59 0.28 3456 8.67 2.43 0.28 3651 8.37 2.34 0.28 3716 24 18 8.33 4.66 0.56 3195 7.65 4.28 0.56 3390 7.35 4.12 0.56 3456 24 20 8.76 3.85 0.44 3325 8.16 3.59 0.44 3488 7.86 3.46 0.44 3586 24 22 9.27 2.96 0.32 3456 8.67 2.77 0.32 3651 8.37 2.68 0.32 3716 24 24 9.78 1.96 0.20 3586 9.18 1.84 0.20 3749 8.93 1.79 0.20 3831 25 18 8.33 5.00 0.60 3195 7.65 4.59 0.60 3390 7.35 4.41 0.60 3456 25 20 8.76 4.20 0.48 3325 8.16 3.92 0.48 3488 7.86 3.77 0.48 3586 25 22 9.27 3.34 0.36 3456 8.67 3.12 0.36 3651 8.37 3.01 0.36 3716 25 24 9.78 2.35 0.24 3586 9.18 2.20 0.24 3749 8.93 2.14 0.24 3831 26 18 8.33 5.33 0.64 3195 7.65 4.90 0.64 3390 7.35 4.71 0.64 3456 26 20 8.76 4.55 0.52 3325 8.16 4.24 0.52 3488 7.86 4.09 0.52 3586 26 22 9.27 3.71 0.40 3456 8.67 3.47 0.40 3651 8.37 3.35 0.40 3716 26 24 9.78 2.74 0.28 3586 9.18 2.57 0.28 3749 8.93 2.50 0.28 3831 26 26 10.29 1.65 0.16 3716 9.69 1.55 0.16 3879 9.39 1.50 0.16 3961 27 18 8.33 5.66 0.68 3195 7.65 5.20 0.68 3390 7.35 5.00 0.68 3456 27 20 8.76 4.90 0.56 3325 8.16 4.57 0.56 3488 7.86 4.40 0.56 3586 27 22 9.27 4.08 0.44 3456 8.67 3.81 0.44 3651 8.37 3.68 0.44 3716 27 24 9.78 3.13 0.32 3586 9.18 2.94 0.32 3749 8.93 2.86 0.32 3831 27 26 10.29 2.06 0.20 3716 9.69 1.94 0.20 3879 9.39 1.88 0.20 3961 28 18 8.33 6.00 0.72 3195 7.65 5.51 0.72 3390 7.35 5.29 0.72 3456 28 20 8.76 5.25 0.60 3325 8.16 4.90 0.60 3488 7.86 4.72 0.60 3586 28 22 9.27 4.45 0.48 3456 8.67 4.16 0.48 3651 8.37 4.02 0.48 3716 28 24 9.78 3.52 0.36 3586 9.18 3.30 0.36 3749 8.93 3.21 0.36 3831 28 26 10.29 2.47 0.24 3716 9.69 2.33 0.24 3879 9.39 2.25 0.24 3961 29 18 8.33 6.33 0.76 3195 7.65 5.81 0.76 3390 7.35 5.59 0.76 3456 29 20 8.76 5.60 0.64 3325 8.16 5.22 0.64 3488 7.86 5.03 0.64 3586 29 22 9.27 4.82 0.52 3456 8.67 4.51 0.52 3651 8.37 4.35 0.52 3716 29 24 9.78 3.91 0.40 3586 9.18 3.67 0.40 3749 8.93 3.57 0.40 3831 29 26 10.29 2.88 0.28 3716 9.69 2.71 0.28 3879 9.39 2.63 0.28 3961 30 18 8.33 6.66 0.80 3195 7.65 6.12 0.80 3390 7.35 5.88 0.80 3456 30 20 8.76 5.95 0.68 3325 8.16 5.55 0.68 3488 7.86 5.35 0.68 3586 30 22 9.27 5.19 0.56 3456 8.67 4.86 0.56 3651 8.37 4.69 0.56 3716 30 24 9.78 4.30 0.44 3586 9.18 4.04 0.44 3749 8.93 3.93 0.44 3831 30 26 10.29 3.29 0.32 3716 9.69 3.10 0.32 3879 9.39 3.01 0.32 3961 31 18 8.33 7.00 0.84 3195 7.65 6.43 0.84 3390 7.35 6.18 0.84 3456 31 20 8.76 6.30 0.72 3325 8.16 5.88 0.72 3488 7.86 5.66 0.72 3586 31 22 9.27 5.56 0.60 3456 8.67 5.20 0.60 3651 8.37 5.02 0.60 3716 31 24 9.78 4.69 0.48 3586 9.18 4.41 0.48 3749 8.93 4.28 0.48 3831 31 26 10.29 3.70 0.36 3716 9.69 3.49 0.36 3879 9.39 3.38 0.36 3961 32 18 8.33 7.33 0.88 3195 7.65 6.73 0.88 3390 7.35 6.47 0.88 3456 32 20 8.76 6.65 0.76 3325 8.16 6.20 0.76 3488 7.86 5.98 0.76 3586 32 22 9.27 5.93 0.64 3456 8.67 5.55 0.64 3651 8.37 5.36 0.64 3716 32 24 9.78 5.08 0.52 3586 9.18 4.77 0.52 3749 8.93 4.64 0.52 3831 32 26 10.29 4.11 0.40 3716 9.69 3.88 0.40 3879 9.39 3.76 0.40 3961
INDOOR
DB(:)
INDOOR
WB(:)
OUTDOOR DB(:)
35 4340
Q
SHC
SHF
INPUT
Q
SHC SHF INPUT Q SHC SHF INPUT
CAPACITY : 8.5(kW) SHF : 0.62 INPUT : 3260(W)
PERFORMANCE DATA COOL operation
MS-GA80VB - : MU-GA80VB - (230V)
E1E1
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
22
Page 23
9
TROUBLESHOOTING
MU-GA50VB ­MU-GA60VB ­MU-GA80VB -
E1 E1 E1
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
(1) Check the power supply voltage. (2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
(2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the com-
ponents.
(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To
make sure, check how many times the abnormality indication is flashing on and off before starting service work. (2)Before servicing that the connector and terminal are connected properly. (3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration. (4) When troubleshooting, refer to 9-2..
23
Page 24
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
Indoor unit operates. Outdoor unit doesn't operate normally.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage".
MU-GA80VB
Refer to 9-4. A "Check of outdoor unit".
Refer to "Check of remote controller and receiver P.C. board".
MU-GA80VB
Flash on and off at 0.5­second intervals Cause: Indoor/ Outdoor unit
• Mis-wiring
Refer to 9-4. C "How to check mis-wiring (When outdoor unit doesn't work)".
2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage".
Refer to "Check of indoor fan motor".
4-time flash Cause: Indoor unit
• Trouble of indoor unit control system
Replace the indoor electronic control P.C. board.
1. Check indoor / outdoor connecting wire.
2. Refer to "Check of indoor electronic control P.C. board".
Outdoor unit doesn't stop even if indoor unit stops.
MU-GA50/GA60VB
Check of wiring diagram of outdoor unit on page 10.
MU-GA80VB
Refer to 9-4. B "Check of outdoor unit".
As for indoor unit, refer to service manual OB369.
MU-GA80VB
6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
MU-GA80VB
7-time flash Cause: Outdoor unit
• Trouble of outdoor control system
Refer to 9-4. E "Check of outdoor thermistor".
Replace the deicer P.C. board.
MU-GA80VB
10-time flash Cause: Outdoor unit
• Trouble of low discharge temperature protection
Refer to 9-4. D "Check of LEV".
9-2. Instruction of troubleshooting
24
Page 25
9-3. Trouble criterion of main parts
Part name FigureCheck method and criterion
Measure the resistance between the terminals with a tester. (Part temperature –10˚C ~ 40˚C)
Compressor (MC) INNER PROTECTOR 160i 5: OPEN 90i10: CLOSE
Normal
MU-GA50VB
Terminal
C – R C – S
1.59 " ~ 1.95 "
2.65 " ~ 3.24 "
MU-GA60VB
0.71 " ~ 0.87 "
1.45 " ~ 1.77 "
MU-GA80VB
0.56 " ~ 0.71 "
1.43 " ~ 1.76 "
Abnormal
Open or
short-circuit
LEV(Expansion valve)
MU-GA80VB
Color of lead wire
WHT – RED RED – ORN
YLW – BRN BRN – BLU
Abnormal
Open or
short-circuit
Normal
41.0 " ~ 49.0 "
Measure the resistance with a tester. (Part temperature : –10˚C ~ 40˚C)
Measure the resistance with a tester. (Part temperature –10˚C ~ 40˚C)
Discharge temperature thermistor(RT62)
MU-GA80VB
Ambient temperature thermistor(RT63)
MU-GA80VB
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up. (Part temperature 0˚C ~ 40˚C)
Normal
120 k" ~ 800k"
Abnormal
Open or short-circuit
Normal
5 k" ~ 60 k"
Abnormal
Open or short-circuit
w Reference value
MU-GA50VB MU-GA60VB MU-GA80VB
Measure the resistance between the terminals with a tester. (Part temperature –10˚C ~ 40˚C)
Color of
lead wire
WHT – BLK
BLK – RED BLK – YLW
YLW – RED
Open or
short-circuit
70.4 " ~ 85.5 "
73.6 " ~ 89.3 " – –
63 " ~ 77 " 79 " ~ 96 "
– –
55 " ~ 68 "
– 49 " ~ 61 " 22 " ~ 29 "
Normal
Abnormal
Outdoor fan motor(MF) INNER PROTECTOR
MU-GA50VB MU-GA60VB
130i 5: OPEN ( 83i15: CLOSE
w
)
MU-GA80VB
135i 5: OPEN ( 87i15: CLOSE
w
)
REDORN WHT
YLW
BLK
MAIN
AUX.1AUX.2
C
P
P
~
BLK
R
MAIN
AUX.
RED
S
C
WHT
MAIN
AUX.
BLK
MU-GA50VB/GA60VB
MU-GA80VB
RED
WHTORN
P
LEV
WHT
6
RED1
ORN4
YLW5
BRN2
BLU3
:INNER PROTECTOR
P
MU-GA50VB - MU-GA60VB - MU-GA80VB -
E1E1E1
25
Page 26
Is there 230V AC to between
L-N on the
outdoor terminal block
?
No
Check the outdoor power supply and connection of wiring.
Yes
Compressor does not operate.
Yes
3minutes after the power supply turns ON, is there 230V AC between A1-A2 on the compressor contactor (52C)?
Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch.
Outdoor fan motor does not operate.
No
Rectify the connecting wire.
Rectify the connecting wire.
Rectify the connecting wire.
Check the compressor. Refer to page 25.
Replace the compressor contactor(52C).
Turn ON the power supply.
Yes
Is there 230V AC between 2/T1 on the compressor contactor(52C) and N on the outdoor terminal block?
Yes
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
Yes
No
Is there 230V AC between 1/L1 on the compressor contactor(52C) and N on the outdoor terminal block?
No
No
Yes
Yes
Yes
Is there 230V AC between CN711 1-3 or 2-3 on the deicer P.C. board? w
Operate the unit in COOL mode by pressing the EMERGENCY OPERATION switch.
No
Check the outdoor fan motor. Refer to page 25.
Yes
Is there 230V AC CN730 1-3 on the deicer P.C. board? w
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
No
Is there 5V DC between J101 - J401 on the deicer P.C. board? w
Is there 230V AC between CN730 1-3 on the deicer P.C. board? w
+
Is there 5V DC between J101 - J401 on the deicer P.C. board? w
+
w Refer to page 29.
9-4. Troubleshoot flow
Compressor and/or outdoor fan motor doesn’t operate.
A
Check of outdoor unit
MU-GA80VB
26
Page 27
Compressor and/or outdoor fan motor doesn’t stop.
B
Check of outdoor unit
1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL mode by pressing the
EMERGENCY OPERATION switch. 4 Operate the unit for 1 minute or more and stop it by pressing the EMERGENCY OPERATION switch again.
After 30 seconds, does compressor stop?
Ok
After 30 seconds, does outdoor fan motor stop?
Yes
MU-GA80VB
Is there 230V AC between
No
A1-A2 on the compressor contactor (52C)?
No
Yes
Replace the deicer P.C. board.
Replace the deicer P.C. board.
Is there 230V AC between
No
2/T1 on the compressor contactor (52C) and N on the outdoor terminal block?
Replace the compressor contactor (52C).
Yes
Ok
When OPERATION INDICATOR lamp flashes ON and OFF in every 0.5-second. Outdoor unit doesn’t operate.
How to check mis-wiring
C
• Turn ON the power supply. (indoor/ outdoor unit)
• Press once EMERGENCY OPERATION switch.
MU-GA80VB
Start
After 3 minutes, mis-wiring is indicated (0.5-second ON, 0.5-second OFF) on OPERATION INDICATOR lamp on indoor unit.w
w Short circuit of JPG and JPS on the indoor electronic control P.C. board enables self -check to be displayed in 3 seconds.
Yes
No
Rectify the connecting wire.
Make them sure.
1. Turn OFF the power supply (indoor/ outdoor unit) and disconnect indoor and outdoor connecting wire at the terminal block 3 of the indoor unit.
2. Short-circuit terminal block N-3 of indoor unit by lead wire.
Turn ON the power supply (indoor unit) and press once EMERGENCY OPERATION switch.
3.
Yes
Is this mis-wiring, poor contact, or wire disconnection?
No
Is there 20V DC between both ends of R132 on the indoor electronic control P.C. board ? ( By tester, the stylus is between 0 ~ 20V. )
• Turn OFF the power supply. (indoor unit) Disconnect the lead wire that terminal block N-3 of the indoor unit is short-circuited.
• Connect ON indoor/ outdoor connecting wire.
Turn ON the power supply. (outdoor unit)
Is there 230V AC between L-N on the outdoor terminal block?
Is there 5V DC between J101 + -J401 - on the deicer P.C. board? Refer to page 29.
During EMERGENCY OPERATION, is there 10V DC between both ends of R601on the deicer P.C. board? Refer to page 29. (By tester, the stylus is between 5 ~10V.)
Replace the deicer P.C. board.
Yes
Yes
Yes
Yes
27
No
Replace the indoor electronic control P.C. board.
No
Check the outdoor power supply and connection of wiring.
No
Replace the deicer P.C. board.
Make the wiring between CN730
No
on the deicer P.C. board and outdoor terminal block correct. Refer to page 29.
As for indoor unit, refer to service manual OB369.
Page 28
When OPERATION INDICATOR lamp flashes 10-time.
Replace the LEV.
With remote controller set toward the indoor unit, press OPERATE/ STOP(ON/ OFF) button and confirm one beep tone.
LEV operates in full-opening direction.
Is LEV properly fixed to the expansion valve?
Ok
Do you hear the expansion valve "click,click·······"? Do you feel the expansion valve vibrate on touching it?
Does the resistance of LEV have the characterictics on page 25?
No
Yes
Yes
Yes
No
No
Properly fix the LEV to the expansion valve.
Replace the deicer P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON again.
2. Press the RESET button on the remote controller.
Turn ON the power supply. 1 During pressing both the OPERATION SELECT button and the TOO COOL button on the
remote controller at the same time, press the RESET button. 2 First, release the RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
1 During pressing both the OPERATION SELECT button and the TOO COOL button on the
remote controller at the same time, press the RESET button. 2 First, release the RESET button. And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.
AMPM
CLOCK
˚C
AMPM
Cooling doesn't operate.
Check of LEV (Expansion valve)
D
MU-GA80VB
When OPERATION INDICATOR lamp flashes 6-time. Thermistors in the outdoor unit are abnormal.
E
Check of outdoor thermistor
w Disconnect the connectors CN662 from the deicer P.C. board.
(Check the characteristics of each thermistor.)
Discharge temperature thermistor(RT62)
Measure resistance between CN 662 1 and 2.
Turn OFF the power supply.
Ambient temperature thermistor(RT63)
Measure resistance between CN 662 3 and 4.
MU-GA80VB
Does the resistancs of thermistor have the characteristics on page 29?
Replace the thermistor.
No
28
Connect CN662. Turn ON the power
Yes
supply and press the EMERGENCY OPERATION switch.
W It is thought defective contact of the connector.
Replace the deicer P.C.
board.
No
Does the unit operate 10 minutes or more?
Yes
Ok W.
Page 29
Temperature(:)
Discharge temperature thermistor(RT62)
Resistance(k")
0 102030405060708090100110120
0
100
200
300
400
500
600
700
800
900
Ambient temperature thermistor (RT63)
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Resistance(k")
9-5. Test point diagram and voltage
MU-GA80VB -
E1
Outdoor deicer P.C. board
J101
+
}
5V
DC
J401 (Refer to page 26 or 27.)
CN662 1-2 Discharge temper­ature thermistor (RT62) (Refer to page 28.)
CN662 3-4 Ambient temperature thermistor (RT63)
(Refer to page 28.)
29
LEV connector (CN724)
Fan motor connector (CN711)
}
R601 10V DC (Refer to page 27.)
Varistor (NR62)
+
+
12V DC
}
Fuse
3.15A / 250V Varistor
(NR61)
CN7301-3
}
230V AC
(Refer to page 26 or
27.)
Page 30
10
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
<"Terminal with lock mechanism" Detaching points>
Connector
Sleeve
Locking lever
DISASSEMBLY INSTRUCTIONS
10-1. MU-GA50VB -
E1
OUTDOOR UNIT
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the down of the cabinet on the both side and remove
the cabinet.
Photo 2
Screws of the cabinet
2. Removing the electrical parts
(1) Remove the service panel and the cabinet. (2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block (TB1, TB2)
•Compressor contactor (52C)
Photo 1
Service panel
Photo 3
PHOTOS
Outdoor fan capacitor(C2)
Connector
Screws of the cabinet
Compressor contactor(52C)
Compressor capacitor(C1)
30
Terminal blocks (TB1, TB2)
Page 31
OPERATING PROCEDURE
PHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.) (2) Disconnect the connector and remove the hooked lead
wire from the fan motor. (3) Remove the propeller nut and remove the propeller. (4) Remove screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor. (5) Disconnect lead wires from the glass terminal of the com-
pressor. (6) Recover gas from the refrigerant circuit. (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor. (10)
Remove the compressor.
Photo 4
Propeller
Photo 5
Discharge pipe
Hook
Propeller nut
Soundproof felt
NOTE
Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm
Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat.
2
(MPa).
Suction pipe
Compressor
Compressor set nuts
31
Page 32
10-2. MU-GA60VB -
OUTDOOR UNIT
E1
OPERATING PROCEDURE
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the bottom of the cabinet on the both side to remove
the cabinet.
PHOTOS
Photo 1
Screws
Service panel
Photo 2
2. Removing the electrical parts
(1) Remove the cabinet . (Refer to 1.) (2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block(TB1, TB2)
•Relay (X1)
•Compressor contactor (52C)
Screws
Photo 3
Compressor capacitor (C1)
Outdoor fan capacitor (C2)
Connector
Compressor contactor (52C)
Relay (X1)
Terminal blocks (TB1, TB2)
32
Page 33
OPERATING PROCEDURE
PHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.) (2) Disconnect the connector and remove the hocked lead
wire from the fan motor. (3) Remove the propeller nut and remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the outdoor fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor. (4) Disconnect the lead wires from the glass terminal of the
compressor. (5) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm (6) Disconnect the welded part of the discharge pipe. (7) Disconnect the welded part of the suction pipe. (8) Remove nuts fixing the compressor. (9) Remove the compressor.
2
(0MPa).
Photo 4
Propeller
Photo 5
Discharge pipe
Hook
Propeller nut
Suction pipe
Compressor
Compressor set nuts
33
Page 34
10-3. MU-GA80VB -
OUTDOOR UNIT
E1
OPERATING PROCEDURE
1.Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Remove the screws of the front panel. (8) Remove the front panel. (9) Remove the screws of the back panel.
(10)
Remove the back panel.
Photo 3
Screw of the motor support
Screws of the back panel
Photo 1
Screws of the cabinet
Photo 2
Screws of the front panel
PHOTOS
Screw of the top panel
Screws of the cabinet
Screw of the service panel
Screws of the top panel
Set screws of the back panel
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
34
Photo 4
Screws of the relay panel
Deicer P.C. board
Screw of the valve cover
Terminal
blocks
Screws of the relay panel
Page 35
OPERATING PROCEDURE
PHOTOS
3. Removing the propeller and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the propeller nut and the propeller.
NOTE : Loose the propeller in the rotating direction for
removal.
When attaching the propeller, align the mark on the propeller and the motor shaft cut section. Set the propeller in position by using the cut on the shaft and the mark on the propeller.
(3) Remove the clamp of outdoor fan motor lead wire and
disconnect the outdoor fan motor connector. (4) Remove the screws fixing the outdoor fan motor. (5) Remove the outdoor fan motor.
Photo 5
Set screws of the outdoor fan motor
Propeller
nut
Propeller
Set screws of the outdoor fan motor
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.) (2) Remove the relay panel. (3) Remove the soundproof felt. (4) Remove the terminal cover on the compressor. (5) Disconnect lead wires from the compressor. (6) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm (7) Disconnect the welded part of the discharge pipe. (8) Disconnect the welded part of the suction pipe. (9) Remove nuts fixing the compressor.
)
(
Remove the compressor.
10
2
(0MPa).
Photo 6
Discharge pipe
Suction pipe
Terminal cover
Compressor set nuts
35
Page 36
11
PARTS LIST
MU-GA50VB ­MU-GA60VB -
E1 E1
11-1. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
22
1
2
3
21
20
19
18 17
16
15 14 13
12
11
10
9
4
56
7
8
36
Page 37
MU-GA50VB -
MU-GA50VB - E1MU-GA60VB -
E1
Symbol
in Wiring
Diagram
Q'ty/unit
Remarks
Part No. Part Name
No.
E02 817 233 E02 817 232 E02 817 521 E02 141 501 E02 139 515 E02 075 506 E02 527 506 E02 817 900 E02 821 900 E02 817 290 E02 818 290 E02 817 661 E02 818 661 E02 817 662 E02 817 245 E02 816 301 E02 818 301 E02 817 630 E02 818 630 E02 890 383 E02 895 383 E02 818 374 E02 817 374 E02 466 340 E02 466 340 E07 012 340 E02 895 351 E02 888 353 E02 889 353 E02 817 009 E02 412 936 E02 217 936
1 2 3 4 5
6
7
8
9
10 11
12
13
14 15
16 17 18 19 20
21 22 23
BACK PANEL CABINET GRILLE PROPELLER MOTOR SUPPORT COMPRESSOR RUBBER SET COMPRESSOR RUBBER SET COMPRESSOR COMPRESSOR BASE BASE STOP VALVE(GAS) STOP VALVE(GAS) STOP VALVE(LIQUID) SERVICE PANEL OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER SURGE ABSORBER SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK COMPRESSOR CONTACTOR RELAY COMPRESSOR CONTACTOR OUTDOOR FAN CAPACITOR COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR HANDLE CAPILLARY TUBE CAPILLARY TUBE
1 1 1 1 1 3
1
1
1
1 1 1
1
1
1 1 1
1 1
1 1
1 1 1 1 1
4
1
1
1 1 1
1
1
1 1 1
1 1 1
1 1
1
3RUBBERS/SET 4RUBBERS/SET RN196VHSHT NN29VBAHT
{12.7 {15.88 { 6.35
RA6V50 ­RA6V60 -
2P 3P
3.0+/440V AC 40+/440V AC 55+/440V AC
{3.0o{1.6o600 {3.0o{1.8o500
MC MC
MF MF
DSAR DSAR
TB2 TB1 52C
X1
52C
C2 C1 C1
MU-GA60VB -
E1 E1
11-1. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
Part numbers that is circled is not shown in the illustration.
37
Page 38
MU-GA80VB -
E1
11-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
22232425
21
20 19
1
2 3
18 17
16
4
15 14
6 7
8
15
5
13
9
38
1210 11
Page 39
MU-GA80VB -
E1
11-2. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Q'ty/unit
MU-GA80VB -
1 1 1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
No.
Part No.
E02 819 297
1 2
E02 819 630
3
E02 819 301
4
E02 214 501
5
E02 819 290
6
E02 819 232
7
E02 819 009
8
E02 819 521
9
E02 527 506
10
E02 819 900
11
E02 819 661
12
E02 819 662
13
E02 819 650
14
E02 819 245
15
E02 819 309
16
E02 890 383
17
E02 821 374
18
E02 817 374
19
E02 890 351
20
E02 896 451
21
E02 890 340
22
E02 890 353
23
E02 819 233
24
E02 817 009
25
E02 726 515
26
E02 822 640
27
E02 819 493
28
E02 127 382
29
E02 336 385
30
E02 214 386
31
E02 819 936 E02 262 936
32
E02 527 936
Part Name
TOP PANEL OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR PROPELLER BASE CABINET HANDLE FAN GUARD COMPRESSOR RUBBER SET COMPRESSOR STOP VALVE(GAS) STOP VALVE(LIQUID) VALVE COVER SERVICE PANEL THERMISTOR SURGE ABSORBER TERMINAL BLOCK TERMINAL BLOCK OUTDOOR FAN CAPACITOR DEICER P.C. BOARD COMPRESSOR CONTACTOR COMPRESSOR CAPACITOR BACK PANEL(OUT) HANDLE MOTOR SUPPORT EXPANSION VALVE EXPANSION VALVE COIL FUSE VARISTOR CZ SURGE ABSORBER CAPILLARY TUBE(TAPER PIPE) CAPILLARY TUBE CAPILLARY TUBE
Symbol in Wiring Diagram
MF
MC
RT62, RT63
DSAR
TB2 TB1
C2
52C
C1
LEV F61
NR61
CZ
E1
Remarks
RA6V75-
4RUBBERS/SET NN37VAAHT
{15.88 {9.52
DISCHARGE, AMBIENT
2P 3P
4.0+/440V AC
60+/440V AC
250V/3.15A
{3.6x{2.4x50 {4.0x{2.4x200 {4.0x{2.4x100
39
Page 40
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Oct. 2004. No.OB370 6 Made in Japan
New publication, effective Oct. 2004 Specifications subject to change without notice.
Loading...