Mitsubishi Electric MU-GA20VB-E1, MU-GA25VB-E1, MU-GA20VB-E2, MU-GA25VB-E2, MU-GA35VB-E1 Service Manual

HFC
utilized
R410A
SPLIT-TYPE, AIR CONDITIONERS
OUTDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision B:
MU-GA20VB- and MU-GA25VB - have been added.
Please void OB386 REVISED EDITION-A.
No. OB386
REVISED EDITION-B
E2E2
MU-GA20VB­MU-GA20VB­MU-GA25VB­MU-GA25VB­MU-GA35VB-
MU-GA20VB MU-GA25VB MU-GA35VB
E1
E2
E1
E2
E1
Indoor unit service manual
MSC-GAVB Series (OB385) MSC-CAVB Series (OB393)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································3
4. NOISE CRITERIA CURVES·······························5
5. OUTLINES AND DIMENSIONS·························6
6. WIRING DIAGRAM ············································6
7. REFRIGERANT SYSTEM DIAGRAM················7
8. PERFORMANCE CURVES································8
10. DISASSEMBLY INSTRUCTIONS·····················20
11. PARTS LIST······················································22
12. RoHS PARTS LIST···········································24
NOTE:
• This service manual describes technical data of outdoor units.
• RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS Parts List.
Revision A:
11-1. PARTS LIST has been modified. (The parts No. of BACK PANEL has been changed.)
Revision B:
MU-GA20VB- and MU-GA25VB- have been added.
1
TECHNICAL CHANGES
MU-A07YV- MU-GA20VB-
1. Indication of capacity has been changed.(BTU base kW base)
2. Unit size has been changed. (W780mm x H540mm x D255mm W800mm x H550mm x D285mm)
3. Outdoor fan motor has been changed. (RC6V20-AC RA6V21-AC)
4. Stop valve cover has been added.
5. Outdoor fan capacitor has been changed.
6. Compressor capacitor has been changed.
MU-A09YV- MU-GA25VB-
1. Indication of capacity has been changed.(BTU base kW base)
2. Unit size has been changed. (W780mm x H540mm x D255mm W800mm x H550mm x D285mm)
3. Outdoor fan motor has been changed. (RC6V20-AC RA6V21-AC)
4. Stop valve cover has been added.
5. Outdoor fan capacitor has been changed.
6. Compressor capacitor has been changed.
7. Compressor has been changed. (RN099VHSHT RN092VHSHT)
MU-A12YV- MU-GA35VB-
1. Indication of capacity has been changed.(BTU base kW base)
2. Unit size has been changed. (W780mm x H540mm x D255mm W800mm x H550mm x D285mm)
3. Outdoor fan motor has been changed. (RC6V33-AC RA6V33-KA)
4. Stop valve cover has been added.
5. Outdoor fan capacitor has been changed.
6. Compressor capacitor has been changed.
7. Compressor has been changed. (RN135VHSHT 5PS132DAH01)
8. Stop valve (Gas) has been changed from [12.7 to [9.52.
9. Fuse for compressor protection has been added.
E2E2
E1E1
E1E1
E1E1
MU-GA20VB- MU-GA20VB­MU-GA25VB- MU-GA25VB-
1. Compressor has been changed. (RN092VHST KN092VDMHC)
2. Compressor capacitor has been changed.
3. Capillary tube has been changed. ([3.0x[1.4x700 [3.0x[1.4x900)
E2E1 E2E1
2
2
Air outlet
Drain outlet
Piping
Drain hose
( )
Air inlet
back : MU-GA20VB
MU-GA25VB
back and side : MU-GA35VB
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at 20:) Model Winding resistance(at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigeration oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg
dB
rpm
kg cc
MU-GA20VB -
E1
Single phase
230V,50Hz
2.3
0.9
1,800
10
3.17 715
– 98 21
2.76
0.245
3.22
RN092VHSHT
600 C-R 3.87 C-S 6.14
RA6V21-AC
WHT-BLK 366
BLK-RED 274 800o550o285
31 45
745
1
0.60
350 (NEO22 )
MU-GA20VB -
E2
Single phase
230V,50Hz
2.3
0.9
1,800
10
3.17 715
98
15.5
2.76
0.245
3.22
KN092VDMHC
650
C-R 3.62 C-S 5.40
RA6V21-AC WHT-BLK 366 BLK-RED 274
800o550o285
27 45
745
1
0.60
350 (NEO22 )
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Outdoor unit power supply
Outdoor model
PART NAMES AND FUNCTIONS
OUTDOOR UNIT
MU-GA20VB MU-GA25VB MU-GA35VB
3
NOTE: Test conditions are based on ISO 5151.
SPECIFICATION
Cooling : Indoor DB27°C WB19°C Indoor-Outdoor piping length : 5m
Outdoor DB35°C WB24°C
3
Capacity Dehumidification Outdoor air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at 20:) Model Winding resistance(at 20:) Dimensions WOHOD Weight Sound level Fan speed Fan speed regulator Refrigerant filling capacity (R410A) Refrigeration oil (Model)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
mm
kg dB
rpm
kg
cc
MU-GA25VB -
E2
Single phase
230V,50Hz
10
KN092VDMHC
650 C-R 3.62 C-S 5.40
RA6V21-AC WHT-BLK 366 BLK-RED 274
800o550o285
27 45
745
1
0.60
350 (NEO22 )
2.5
1.1
1,800
3.40 775
99
15.5
2.99
0.245
3.23
MU-GA25VB -
E1
Single phase
230V,50Hz
10
RN092VHSHT
600 C-R 3.87 C-S 6.14
RA6V21-AC
WHT-BLK 366
BLK-RED 274 800o550o285
31 45
745
1
0.60
350 (NEO22 )
2.5
1.1
1,800
3.40 775
– 99 21
2.99
0.245
3.23
MU-GA35VB -
E1
Single phase
230V,50Hz
1.7
10
5PS132DAH01
900 C-R 2.80 C-S 5.43
RA6V33-KA WHT-BLK 215 BLK-RED 307
800o550o285
30 49
855
1
0.70
350 (RB68A)
3.45
1,902
5.02
1,120
– 97 21
4.50
0.33
3.08
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Outdoor unit power supply
Outdoor model
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB24°C
Indoor-Outdoor piping length : 5m
4
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling :DB35: WB24:
MU-GA35VB
COOL
FUNCTION
49
SPL(dB(A)) LINE
OUTDOOR UNIT
MICROPHONE
1m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27: WB19:
MU-GA20VB MU-GA25VB
COOL
FUNCTION
45
SPL(dB(A)) LINE
NOISE CRITERIA CURVES
5
5
C2
C1
WHT
POWER SUPPLY
~/N 230V 50Hz
CIRCUIT BREAKER
BLU
BRN
WHT
RED
BLU
WHT
BLK
RED
12V
TO INDOOR
UNIT
CONNECTING
WHT
BLK
DSAR
52C
TB2
2
1
C
R
S
GRN/YLW
PE
N
L
BRN
TB1
COM
52C
NO
MC
1
3 2
BLK
RED
WHT
MF
SYMBOL
TB2 52C
SYMBOL
MC MF
TB1
SYMBOL
C1 C2
DSAR
NAME
NAME NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER
COMPRESSOR(INNER PROTECTOR)
TERMINAL BLOCK COMPRESSOR CONTACTOR
OUTDOOR FAN MOTOR(INNER FUSE) TERMINAL BLOCK
OUTLINES AND DIMENSIONS
MU-GA20VB MU-GA25VB MU-GA35VB
OUTDOOR UNIT
344.5
285
550
44
Air in
(MU-GA35VB)
2 holes 10X21
22.3
Handle
280
10
400
Air in
Air out
150
302.5 500 Bolt pitch for installation
Drain hole [42
40
17.5
164.5
69
800
installation
Bolt pitch for
23
99.5 Service port
REQUIRED SPACE
100mm or more
304~325
Service panel
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
35-
Gas refrigerant pipe joint Refrigerant pipe (flared) [9.52
170.5
ore
or m
m
200m
Open two sides of left, right, or rear side.
43-
Unit: mm
Basically open 100mm or more without any obstruction in front and on both sides of the unit.
100mm or more
350m
m
or m
ore
6
WIRING DIAGRAM
MU-GA20VB MU-GA25VB
OUTDOOR UNIT
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
6
MU-GA35VB
PE
N
L
TB1
1
2
TB2
C1
C2
WHT
CIRCUIT BREAKER
WHT
51C
41
BRN
F
BLU
BRN
WHT
RED
BLU
WHT
BLK
RED
POWER SUPPLY
~/N 230V 50Hz
12V
TO INDOOR
UNIT
CONNECTING
WHT
BLK
DSAR
52C
C
R
S
GRN/YLW
BRN
COM
52C
NO
MC
1
3 2
BLK
RED
WHT
MF
OUTDOOR UNIT
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
DSAR
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
7
SURGE ABSORBER
F
FUSE (T20AL250V)
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate. /: Terminal block, : Connector
REFRIGERANT SYSTEM DIAGRAM
NAME
SYMBOL
MC
MF TB1 TB2
NAME NAME COMPRESSOR OUTDOOR FAN MOTOR (INNER FUSE) TERMINAL BLOCK TERMINAL BLOCK
MU-GA20VB MU-GA25VB MU-GA35VB
OUTDOOR UNIT
Flared connection
Refrigerant pipe [9.52 (with heat insulator)
Stop valve (with service port)
SYMBOL
51C 52C
Muffler
OVERLOAD RELAY COMPRESSOR CONTACTOR
Unit:mm
Outdoor heat exchanger
Refrigerant pipe [6.35 (with heat insulator)
Flared connection
Stop valve
Capillary tube
[3.0x[1.4x700 (MU-GA20VB [3.0x[1.4x900 (MU-GA20VB [3.0x[1.4x450 (MU-GA35VB)
7
Compressor
Strainer #100
- , MU-GA25VB- )
- , MU-GA25VB- )
E1E1 E2E2
Refrigerant flow in cooling
Piping size O.D : mm Length of connecting pipe : m
Model
Refrigerant piping : m
Max. length
A
20
25
Max. height
B
10
Indoor unit
Gas 0.43
Liquid 0.5
Liquid
6.35
Gas
9.52
Outdoor unit
Gas 0
Liquid 0
MU-GA20VB MU-GA25VB
MU-GA35VB
Indoor unit
Max. Height B
Outdoor unit
Refrigerant Piping
Max. length
A
Model
Refrigerant piping length (one way)
Outdoor unit precharged
600 700
25m
360
7m
0
10m
60
15m
160
20m
260
Calculation : Xg=20g/m x(A-7)m
MU-GA20VB MU-GA25VB
MU-GA35VB
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R410A : g)
8
PERFORMANCE CURVES
MU-GA20VB MU-GA25VB MU-A35VB
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB (4) Total input: W Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
Cooling
}
8
INDOOR UNIT
18 32
230V
15 20
50
25 6030 70
(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
15 20
50
25 60
30 70(%)
35(:)
1
2
4
3
18 32
230V
OUTDOOR UNIT
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
8-1.CAPACITY AND THE INPUT CURVES
9.6
8.5
7.8
7.1
6.4
5.8
5.1
MSC-GA20VB
11.0
8.8
10.0
8.0
7.2
6.5
5.7
MU-GA20VB
MU-GA25VB
MSC-GA25VB
9.1
8.2
7.4
6.5
MU-GA35VB
MSC-GA35VB
8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25 30 70
Relative humidity(%)
50 60
Air flow should be set at MAX.The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge] )
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%) Ambient temperature(˚C) Ambient humidity(%)
MU-GA20VB MU-GA20VB
Outdoor unit current (A)
9