11. PARTS LIST······················································22
12. RoHS PARTS LIST···········································24
NOTE:
• This service manual describes technical data of outdoor units.
• RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS Parts List.
Revision A:
• 11-1. PARTS LIST has been modified. (The parts No. of BACK PANEL has been changed.)
Revision B:
• MU-GA20VB-and MU-GA25VB-have been added.
1
TECHNICAL CHANGES
MU-A07YV-➔MU-GA20VB-
1. Indication of capacity has been changed.(BTU base ➔ kW base)
2. Unit size has been changed. (W780mm x H540mm x D255mm ➔ W800mm x H550mm x D285mm)
3. Outdoor fan motor has been changed. (RC6V20-AC ➔ RA6V21-AC)
4. Stop valve cover has been added.
5. Outdoor fan capacitor has been changed.
6. Compressor capacitor has been changed.
MU-A09YV-➔MU-GA25VB-
1. Indication of capacity has been changed.(BTU base ➔ kW base)
2. Unit size has been changed. (W780mm x H540mm x D255mm ➔ W800mm x H550mm x D285mm)
3. Outdoor fan motor has been changed. (RC6V20-AC ➔ RA6V21-AC)
4. Stop valve cover has been added.
5. Outdoor fan capacitor has been changed.
6. Compressor capacitor has been changed.
7. Compressor has been changed. (RN099VHSHT ➔ RN092VHSHT)
MU-A12YV-➔MU-GA35VB-
1. Indication of capacity has been changed.(BTU base ➔ kW base)
2. Unit size has been changed. (W780mm x H540mm x D255mm ➔ W800mm x H550mm x D285mm)
3. Outdoor fan motor has been changed. (RC6V33-AC ➔ RA6V33-KA)
4. Stop valve cover has been added.
5. Outdoor fan capacitor has been changed.
6. Compressor capacitor has been changed.
7. Compressor has been changed. (RN135VHSHT ➔ 5PS132DAH01)
8. Stop valve (Gas) has been changed from [12.7 to [9.52.
9. Fuse for compressor protection has been added.
E2E2
E1E1
E1E1
E1E1
MU-GA20VB-➔MU-GA20VBMU-GA25VB-➔MU-GA25VB-
1. Compressor has been changed. (RN092VHST ➔ KN092VDMHC)
2. Compressor capacitor has been changed.
3. Capillary tube has been changed. ([3.0x[1.4x700 ➔ [3.0x[1.4x900)
E2E1
E2E1
2
2
Air outlet
Drain outlet
Piping
Drain hose
( )
Air inlet
back : MU-GA20VB
MU-GA25VB
back and side : MU-GA35VB
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at 20:)
Model
Winding
resistance(at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigeration oil (Model)
Capacity
Dehumidification
Outdoor air flow
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at 20:)
Model
Winding
resistance(at 20:)
Dimensions WOHOD
Weight
Sound level
Fan speed
Fan speed regulator
Refrigerant filling
capacity (R410A)
Refrigeration oil (Model)
kW
R/h
K /h
A
A
W
A(kW)
%
A
A
A
W
"
"
mm
kg
dB
rpm
kg
cc
MU-GA25VB -
E2
Single phase
230V,50Hz
10
KN092VDMHC
650
C-R 3.62
C-S 5.40
RA6V21-AC
WHT-BLK 366
BLK-RED 274
800o550o285
27
45
745
1
0.60
350 (NEO22 )
2.5
1.1
1,800
3.40
775
–
99
15.5
2.99
0.245
3.23
MU-GA25VB -
E1
Single phase
230V,50Hz
10
RN092VHSHT
600
C-R 3.87
C-S 6.14
RA6V21-AC
WHT-BLK 366
BLK-RED 274
800o550o285
31
45
745
1
0.60
350 (NEO22 )
2.5
1.1
1,800
3.40
775
–
99
21
2.99
0.245
3.23
MU-GA35VB -
E1
Single phase
230V,50Hz
1.7
10
5PS132DAH01
900
C-R 2.80
C-S 5.43
RA6V33-KA
WHT-BLK 215
BLK-RED 307
800o550o285
30
49
855
1
0.70
350 (RB68A)
3.45
1,902
5.02
1,120
–
97
21
4.50
0.33
3.08
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Outdoor unit power supply
Outdoor model
NOTE: Test conditions are based on ISO 5151.
Cooling : IndoorDB27°C WB19°C
Outdoor DB35°C WB24°C
Indoor-Outdoor piping length : 5m
4
4
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling :DB35:WB24:
MU-GA35VB
COOL
FUNCTION
49
SPL(dB(A))LINE
OUTDOOR UNIT
MICROPHONE
1m
90
80
70
60
50
40
30
20
10
631252505001000 2000 4000 8000
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions,
Cooling : DB27:WB19:
MU-GA20VB
MU-GA25VB
COOL
FUNCTION
45
SPL(dB(A))LINE
NOISE CRITERIA CURVES
5
5
C2
C1
WHT
POWER SUPPLY
~/N 230V 50Hz
CIRCUIT
BREAKER
BLU
BRN
WHT
RED
BLU
WHT
BLK
RED
12V
TO INDOOR
UNIT
CONNECTING
WHT
BLK
DSAR
52C
TB2
2
1
C
R
S
GRN/YLW
PE
N
L
BRN
TB1
COM
52C
NO
MC
1
3
2
BLK
RED
WHT
MF
SYMBOL
TB2
52C
SYMBOL
MC
MF
TB1
SYMBOL
C1
C2
DSAR
NAME
NAMENAME
COMPRESSOR CAPACITOR
OUTDOOR FAN CAPACITOR
SURGE ABSORBER
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB
(2) Indoor outlet air wet-bulb temperature :°CWB
(3) Outdoor intake air dry-bulb temperature :°CDB
(4) Total input:W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on next page shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets
of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air
speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once to start the EMERGENCY COOL MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
Cooling
}
8
INDOOR UNIT
1832
230V
1520
50
25
6030 70
(%)
35(:)
0.7
0.8
0.9
1.0
1.1
1.2
1.3
7
8
9
10
11
12
13
1520
50
25
60
30
70(%)
35(:)
1
2
4
3
1832
230V
OUTDOOR UNIT
Wet-and dry-bulb
thermometers
Wet-and dry-bulb
thermometers
8-1.CAPACITY AND THE INPUT CURVES
9.6
8.5
7.8
7.1
6.4
5.8
5.1
MSC-GA20VB
11.0
8.8
10.0
8.0
7.2
6.5
5.7
MU-GA20VB
MU-GA25VB
MSC-GA25VB
9.1
8.2
7.4
6.5
MU-GA35VB
MSC-GA35VB
8-2.OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
COOL operation
① Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20
25
3070
Relative humidity(%)
50
60
➁ Air flow should be set at MAX.
③ The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa[Gauge]) =10.2(kgf/ff[Gauge] )