Mitsubishi Electric MUFZ-KJ25VE-E1, MUFZ-KJ25VE-ER1, MUFZ-KJ35VE-E1, MUFZ-KJ35VE-ER1, MUFZ-KJ50VE-E1 Service Manual

...
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ···································3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. NOISE CRITERIA CURVES ······························ 6
5. OUTLINES AND DIMENSIONS ························ 7
7. REFRIGERANT SYSTEM DIAGRAM ············· 10
8. PERFORMANCE CURVES ····························· 12
9. ACTUA TOR CONTROL ··································· 23
10. SERVICE FUNCTIONS ···································· 24
11. TROUBLESHOOTING ····································· 25
12. DISASSEMBLY INSTRUCTIONS ···················· 46
Models
SPLIT-TYPE AIR CONDITIONERS
NOTE: RoHS compliant products have <G> mark on the spec name plate.
HFC
utilized
R410A
No. OBH667
REVISED EDITION-B
OUTDOOR UNIT
Indoor unit service manual MFZ-KJ•VE Series (OBH666)
PARTS CATALOG (OBB667)
MUFZ-KJ25VE
-
E1, ER1
MUFZ-KJ35VE
-
E1, ER1
MUFZ-KJ50VE
-
E1, ER1
MUFZ-KJ25VE MUFZ-KJ35VE
Please void OBH667 REVISED EDITION-A.
Revision B:
MUFZ-KJ25VE -
ER1
, MUFZ-KJ35VE -
ER1
and
MUFZ-KJ50VE -
ER1
have been added.
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
MUFZ-KJ50VE -E1 has been added.
Revision B:
MUFZ-KJ25VE -
ER1
, MUFZ-KJ35VE -
ER1
and MUFZ-KJ50VE -
ER1
have been added.
OBH667B
3
MUFZ-KJ25VE -
E1
,
ER1
MUFZ-KJ35VE -
E1
,
ER1
MUFZ-KJ50VE -
E1
,
ER1
1. New model
TECHNICAL CHANGES
1
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUFZ-KJ25VE MUFZ-KJ35VE
PART NAMES AND FUNCTIONS
2
ACCESSORIES
Model
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
Drain socket 1
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
MUFZ-KJ50VE
OBH667B
4
Outdoor model MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (0.5 - 3.4) 3.5 (0.5 - 3.7) 5.0 (1.6 - 5.7)
Heating 3.4 (1.2 - 4.6) 4.3 (1.2 - 5.5) 6.0 (2.2 - 8.2)
Breaker Capacity A 10 16
Electrical data
Power input 1 (Total)
Cooling
W
540 940 1,410
Heating 770 1,110 1,610
Running current
1
(Total)
Cooling
A
2.7 4.2 6.2
Heating 3.6 5.1 7.1
Power factor
1 (Total)
Cooling
%
87 98
Heating 91 93 98
Starting current
1 (Total) A 3.6 5.1 7.1
Coeffi cient of performance (COP)
1 (Total)
Cooling 4.63 3.72 3.55 Heating 4.42 3.91 3.73
Compressor
Model SNB140FRUMT SNB172FEKMT Output W 950 1,200
Current
1
Cooling
A
2.19 3.69 5.18
Heating 3.16 4.61 5.94
Refrigeration oil (Model) L 0.35 (FV50S) 0.40 (FV50S)
Fan motor
Model RC0J50-CI RC0J60-BC
Current
1
Cooling
A
0.28 0.82
Heating 0.31 0.82 Dimensions W × H × D mm 800 × 550 × 285 840 × 880 × 330 Weight kg 37 55
Special remarks
Dehumidifi cation Cooling L/h 0.6 1.4 2.0
Air fl ow 1
Cooling
Med.
m3/h
1,806 2,748
Low 1,038 1,632
Heating
High 2,016 2,856
Med. 1,710 2,748
Low 1,326 2,274
Sound level
1
Cooling
dB(A)
46 47 49
Heating 51
Fan speed
Cooling
Med.
rpm
810 780
Low 490 480
Heating
High 900 810
Med. 770 780
Low 610 650 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 1.10 1.50
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
SPECIFICATION
3
OBH667B
5
Specifi cations and rated conditions of main electric parts
Model
Item
MUFZ-KJ25VE MUFZ-KJ35VE
Smoothing capacitor
(C61, C62) 600 μF/ 620 μF 420 V
Diode module (DB61) 15 A 600 V
Fuse
(F61) T20AL250V
(F701, F801, F901)
T3.15AL250V
Power module
(IC700) 15 A 600 V
(IC932) 8A600V
Expansion valve coil
(LEV) 12 V DC
Reactor (L61) 23 mH
Power factor controller
(IC820) 20A 600V
Circuit protection
(PTC64, PTC65) 33 Ω
Terminal block (TB) 5 P
Relay
(X63) 3 A 250 V
(X64) 20 A 250 V
(X69) 10A 250V
R.V.coil (21S4) 220 - 240 V AC
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-KJ50VE
Smoothing capacitor
(CB1, CB2, CB3)
560 μF 450 V
Fuse
(F601, F880, F901)
T3.15AL250 V
IGBT module
(IC932) 5 A 600 V
(IC700) 20 A 600 V
Expansion valve coil
(LEV) 12 V DC
Reactor (L) 340 μH Diode module (IC820) 20 A 600 V
Circuit protection
(PTC64, PTC65) 33 Ω
Terminal block (TB1, TB2) 3 P
Relay
(X64) 20 A 250 V (X65) 20 A 250 V
(X69) 10 A 250 V (X601) 3 A 250 V (X602) 3 A 250 V
R.V. coil (21S4) 220 - 240 V AC
OBH667B
6
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
46 51
NC-10
MUFZ-KJ25VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
47 51
NC-10
MUFZ-KJ35VE
NOISE CRITERIA CURVES
4
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
NC-10
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
49 51
MUFZ-KJ50VE
OBH667B
7
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
43
35
2 holes 10 X 21
Drain hole ø42
REQUIRED SPACE
350 mm or more
100 mm or more
100 mm or more
*1 100 mm or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
Clear *1
200 mm or
more *2
Unit: mm
MUFZ-KJ25VE MUFZ-KJ35VE
OUTLINES AND DIMENSIONS
5
MUFZ-KJ50VE
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-holes 10 21
360
840
109
81
880
452
Service panel
99.5
164.5 195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared)
Ø 6.35
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 12.7
350 mm or more
100 mm or more
REQUIRED SPACE
100 mm or more
500 mm
or more *2
*1 500 mm or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
Clear *1
OBH667B
8
WIRING DIAGRAM
6
MUFZ-KJ25VE MUFZ-KJ35VE
OBH667B
9
MUFZ-KJ50VE
OBH667B
10
Unit: mm
MUFZ-KJ25VE MUFZ-KJ35VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø4.0×ø2.4×240
Outdoor heat exchanger temperature thermistor RT68
Capillary tube ø3.0×ø2.0×210
Muffler
REFRIGERANT SYSTEM DIAGRAM
7
MUFZ-KJ50VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve
Capillary tube
ø
4.0
×
ø
2.4×100 Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
Muffler
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
OBH667B
11
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m Piping size O.D: mm
Max. Length A Max. Height difference B Gas Liquid
MUFZ-KJ25/35 20 12 9.52 6.35 MUFZ-KJ50 30 15 12.7 6.35
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUFZ-KJ25/35 1,100
0 30 60 90 120 150 180 210 240 390
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 10 m 15 m 20 m 25 m 30 m
MUFZ-KJ50 1,500 0 60 160 260 360 460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
OBH667B
12
PERFORMANCE CURVES8
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB]
}
Cooling
(2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
}
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB] (7) Total input: W Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
INDOOR UNIT OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature(°C)
Capacity correction factors
26
24
20 18
22
Indoor intake air Wet-bulb temperature( )
MUFZ-KJ35VE
MUFZ-KJ25VE
Indoor air Wet-bulb temperature
difference (°C)
8.5
7.9
7.2
6.6
6.0
5.4
4.8
12.9
11.8
10.8
9.8
8.8
7.9
7.0
14.6
13.4
12.2
11.0
9.9
8.9
7.8
MUFZ-KJ50VE
8-1. CAPACITY AND INPUT CURVES
OBH667B
13
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
0.8
0.9
1.0
1.1
1.2
1.3
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature (°C)
Input correction factors
26
24
22 20 18
Indoor intake air Wet-bulb temperature( )
Indoor air Wet-bulb temperature
difference (°C)
7.2
6.6
6.0
5.4
4.8
4.2
10.8
9.8
8.8
7.9
7.0
6.1
MUFZ-KJ35VE
12.2
11.0
9.9
8.9
7.8
6.8
MUFZ-KJ50VE
MUFZ-KJ25VE
Total input (Cooling :
at Rated frequency
)
Indoor air Dry-bulb temperature
difference (°C)
22.9
21.2
19.4
17.6
15.9
14.1
12.3
10.6
8.8
7.1
MUFZ-KJ25VE
29.0
26.8
24.5
22.3
20.1
17.8
15.6
13.4
11.1
8.9
MUFZ-KJ35VE
28.0
25.9
23.7
21.6
19.4
17.2
15.1
12.9
10.8
8.6
MUFZ-KJ50VE
Outdoor intake air Wet-bulb temperature (°C)
-15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity (
at Rated frequency)
Capacity correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Indoor air Dry-bulb temperature
difference (°C)
22.9
21.2
19.4
17.6
15.9
14.1
12.3
10.6
8.8
7.1
MUFZ-KJ25VE
29.0
26.8
24.5
22.3
20.1
17.8
15.6
13.4
11.1
8.9
MUFZ-KJ35VE
28.0
25.9
23.7
21.6
19.4
17.2
15.1
12.9
10.8
8.6
MUFZ-KJ50VE
Outdoor intake air Wet-bulb temperature (°C)
-15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Heating :
at Rated frequency
)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
OBH667B
14
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
1
2
3
0 50 100
150
0.5
1.0
1.5
2.0
050100
150
1
2
3
0 50 100
150
0.5
1.0
1.5
2.0
050100
150
1
2
3
MUFZ-KJ25VE
MUFZ-KJ35VE
Correction of Coolin g capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operationalfrequency of compressor (Hz)
Input correction factors
Correction of Heating capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heati nginput
The operational frequency of compressor (Hz)
Input correction factors
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Heati ngcapacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heati nginput
The operational frequenc y of compressor (Hz)
Input correction factors
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUFZ-KJ50VE
Correction of Heating input
Capacity correction factors
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (H z)
The operational frequency of compressor (Hz)
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100 150
0.5
1.0
1.5
2.0
0 50 100 150
0.5
1.0
1.5
2.0
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
OBH667B
15
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
0.9
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
Ambient temperature(°C) Ambient humidity(%)
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
0.8
(kgf/cm2[Gauge])(MPa [Gauge])
6
5
4
7
8
9
(kgf/cm2[Gauge])(MPa [Gauge])
4
6
5
7
8
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
MUFZ-KJ25VE MUFZ-KJ35VE
MUFZ-KJ50VE
(kgf/cm2[Gauge])(MPa [Gauge])
50 60 70
3
5
4
6
7
8
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm2 [Gauge])
15 20 25 30 35
1.5
2.0
2.5
3.0
15 20 25 30 35
2.5
3.0
3.5
4.0
4.5
Ambient temperature (°C) Ambient humidity(%)
50 60 70 50 60 70 50 60 70
Outdoor current (A)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
MUFZ-KJ35VEMUFZ-KJ25VE
Outdoor unit current
15 20 25 30 35
3
4
5
6
7
8
MUFZ-KJ50VE
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
0510
15 20 25
2.5
3.0
3.5
4.0
4.5
0 5 10 15 20 25
4
5
6
7
8
9
0510
15 20 25
4.0
4.5
5.0
5.5
6.0
Ambient temperature (°C)
Outdoor current (A)
MUFZ-KJ35VEMUFZ-KJ25VE
Outdoor unit current
MUFZ-KJ50VE
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
Condition:
Operation: Test run operation (Refer to 8-3.)
HEAT operation
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
OBH667B
16
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ25VE
CAPACITY: 2.5 kW SHF: 0.85 INPUT: 540 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.94 1.97 0.67 432 2.81 1.88 0.67 454 2.70 1.81 0.67 475 2.60 1.74 0.67 497
21 20 3.06 1.68 0.55 454 2.94 1.62 0.55 481 2.85 1.57 0.55 491 2.75 1.51 0.55 513
22 18 2.94 2.09 0.71 432 2.81 2.00 0.71 454 2.70 1.92 0.71 475 2.60 1.85 0.71 497
22 20 3.06 1.81 0.59 454 2.94 1.73 0.59 481 2.85 1.68 0.59 491 2.75 1.62 0.59 513
22 22 3.19 1.50 0.47 470 3.08 1.45 0.47 500 3.00 1.41 0.47 513 2.88 1.35 0.47 535
23 18 2.94 2.20 0.75 432 2.81 2.11 0.75 454 2.70 2.03 0.75 475 2.60 1.95 0.75 497
23 20 3.06 1.93 0.63 454 2.94 1.85 0.63 481 2.85 1.80 0.63 491 2.75 1.73 0.63 513
23 22 3.19 1.63 0.51 470 3.08 1.57 0.51 500 3.00 1.53 0.51 513 2.88 1.47 0.51 535
24 18 2.94 2.32 0.79 432 2.81 2.22 0.79 454 2.70 2.13 0.79 475 2.60 2.05 0.79 497
24 20 3.06 2.05 0.67 454 2.94 1.97 0.67 481 2.85 1.91 0.67 491 2.75 1.84 0.67 513
24 22 3.19 1.75 0.55 470 3.08 1.69 0.55 500 3.00 1.65 0.55 513 2.88 1.58 0.55 535
24 24 3.35 1.44 0.43 491 3.23 1.39 0.43 518 3.15 1.35 0.43 535 3.05 1.31 0.43 562
25 18 2.94 2.44 0.83 432 2.81 2.33 0.83 454 2.70 2.24 0.83 475 2.60 2.16 0.83 497
25 20 3.06 2.17 0.71 454 2.94 2.09 0.71 481 2.85 2.02 0.71 491 2.75 1.95 0.71 513
25 22 3.19 1.88 0.59 470 3.08 1.81 0.59 500 3.00 1.77 0.59 513 2.88 1.70 0.59 535
25 24 3.35 1.57 0.47 491 3.23 1.52 0.47 518 3.15 1.48 0.47 535 3.05 1.43 0.47 562
26 18 2.94 2.56 0.87 432 2.81 2.45 0.87 454 2.70 2.35 0.87 475 2.60 2.26 0.87 497
26 20 3.06 2.30 0.75 454 2.94 2.20 0.75 481 2.85 2.14 0.75 491 2.75 2.06 0.75 513
26 22 3.19 2.01 0.63 470 3.08 1.94 0.63 500 3.00 1.89 0.63 513 2.88 1.81 0.63 535
26 24 3.35 1.71 0.51 491 3.23 1.64 0.51 518 3.15 1.61 0.51 535 3.05 1.56 0.51 562
26 26 3.45 1.35 0.39 518 3.35 1.31 0.39 545 3.30 1.29 0.39 562 3.20 1.25 0.39 578
27 18 2.94 2.67 0.91 432 2.81 2.56 0.91 454 2.70 2.46 0.91 475 2.60 2.37 0.91 497
27 20 3.06 2.42 0.79 454 2.94 2.32 0.79 481 2.85 2.25 0.79 491 2.75 2.17 0.79 513
27 22 3.19 2.14 0.67 470 3.08 2.06 0.67 500 3.00 2.01 0.67 513 2.88 1.93 0.67 535
27 24 3.35 1.84 0.55 491 3.23 1.77 0.55 518 3.15 1.73 0.55 535 3.05 1.68 0.55 562
27 26 3.45 1.48 0.43 518 3.35 1.44 0.43 545 3.30 1.42 0.43 562 3.20 1.38 0.43 578
28 18 2.94 2.79 0.95 432 2.81 2.67 0.95 454 2.70 2.57 0.95 475 2.60 2.47 0.95 497
28 20 3.06 2.54 0.83 454 2.94 2.44 0.83 481 2.85 2.37 0.83 491 2.75 2.28 0.83 513
28 22 3.19 2.26 0.71 470 3.08 2.18 0.71 500 3.00 2.13 0.71 513 2.88 2.04 0.71 535
28 24 3.35 1.98 0.59 491 3.23 1.90 0.59 518 3.15 1.86 0.59 535 3.05 1.80 0.59 562
28 26 3.45 1.62 0.47 518 3.35 1.57 0.47 545 3.30 1.55 0.47 562 3.20 1.50 0.47 578
29 18 2.94 2.91 0.99 432 2.81 2.78 0.99 454 2.70 2.67 0.99 475 2.60 2.57 0.99 497
29 20 3.06 2.66 0.87 454 2.94 2.56 0.87 481 2.85 2.48 0.87 491 2.75 2.39 0.87 513
29 22 3.19 2.39 0.75 470 3.08 2.31 0.75 500 3.00 2.25 0.75 513 2.88 2.16 0.75 535
29 24 3.35 2.11 0.63 491 3.23 2.03 0.63 518 3.15 1.98 0.63 535 3.05 1.92 0.63 562
29 26 3.45 1.76 0.51 518 3.35 1.71 0.51 545 3.30 1.68 0.51 562 3.20 1.63 0.51 578
30 18 2.94 2.94 1.00 432 2.81 2.81 1.00 454 2.70 2.70 1.00 475 2.60 2.60 1.00 497
30 20 3.06 2.79 0.91 454 2.94 2.67 0.91 481 2.85 2.59 0.91 491 2.75 2.50 0.91 513
30 22 3.19 2.52 0.79 470 3.08 2.43 0.79 500 3.00 2.37 0.79 513 2.88 2.27 0.79 535
30 24 3.35 2.24 0.67 491 3.23 2.16 0.67 518 3.15 2.11 0.67 535 3.05 2.04 0.67 562
30 26 3.45 1.90 0.55 518 3.35 1.84 0.55 545 3.30 1.82 0.55 562 3.20 1.76 0.55 578
31 18 2.94 2.94 1.00 432 2.81 2.81 1.00 454 2.70 2.70 1.00 475 2.60 2.60 1.00 497
31 20 3.06 2.91 0.95 454 2.94 2.79 0.95 481 2.85 2.71 0.95 491 2.75 2.61 0.95 513
31 22 3.19 2.65 0.83 470 3.08 2.55 0.83 500 3.00 2.49 0.83 513 2.88 2.39 0.83 535
31 24 3.35 2.38 0.71 491 3.23 2.29 0.71 518 3.15 2.24 0.71 535 3.05 2.17 0.71 562
31 26 3.45 2.04 0.59 518 3.35 1.98 0.59 545 3.30 1.95 0.59 562 3.20 1.89 0.59 578
32 18 2.94 2.94 1.00 432 2.81 2.81 1.00 454 2.70 2.70 1.00 475 2.60 2.60 1.00 497
32 20 3.06 3.03 0.99 454 2.94 2.91 0.99 481 2.85 2.82 0.99 491 2.75 2.72 0.99 513
32 22 3.19 2.77 0.87 470 3.08 2.68 0.87 500 3.00 2.61 0.87 513 2.88 2.50 0.87 535
32 24 3.35 2.51 0.75 491 3.23 2.42 0.75 518 3.15 2.36 0.75 535 3.05 2.29 0.75 562
32 26 3.45 2.17 0.63 518 3.35 2.11 0.63 545 3.30 2.08 0.63 562 3.20 2.02 0.63 578
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Loading...
+ 36 hidden pages