Mitsubishi Electric MUFZ-KJ25VE-E1, MUFZ-KJ25VE-ER1, MUFZ-KJ35VE-E1, MUFZ-KJ35VE-ER1, MUFZ-KJ50VE-E1 Service Manual

...
Page 1
SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ···································3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. NOISE CRITERIA CURVES ······························ 6
5. OUTLINES AND DIMENSIONS ························ 7
7. REFRIGERANT SYSTEM DIAGRAM ············· 10
8. PERFORMANCE CURVES ····························· 12
9. ACTUA TOR CONTROL ··································· 23
10. SERVICE FUNCTIONS ···································· 24
11. TROUBLESHOOTING ····································· 25
12. DISASSEMBLY INSTRUCTIONS ···················· 46
Models
SPLIT-TYPE AIR CONDITIONERS
NOTE: RoHS compliant products have <G> mark on the spec name plate.
HFC
utilized
R410A
No. OBH667
REVISED EDITION-B
OUTDOOR UNIT
Indoor unit service manual MFZ-KJ•VE Series (OBH666)
PARTS CATALOG (OBB667)
MUFZ-KJ25VE
-
E1, ER1
MUFZ-KJ35VE
-
E1, ER1
MUFZ-KJ50VE
-
E1, ER1
MUFZ-KJ25VE MUFZ-KJ35VE
Please void OBH667 REVISED EDITION-A.
Revision B:
MUFZ-KJ25VE -
ER1
, MUFZ-KJ35VE -
ER1
and
MUFZ-KJ50VE -
ER1
have been added.
Page 2
2
<Preparation before the repair service>
Prepare the proper tools. Prepare the proper protectors. Provide adequate ventilation. After stopping the operation of the air conditioner, turn off the power-supply breaker and remove the power plug. Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands. Do not pour water into the electric parts. Do not touch the refrigerant. Do not touch the hot or cold areas in the refrigeration cycle. When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
Use the specifi ed refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
Revision A:
MUFZ-KJ50VE -E1 has been added.
Revision B:
MUFZ-KJ25VE -
ER1
, MUFZ-KJ35VE -
ER1
and MUFZ-KJ50VE -
ER1
have been added.
OBH667B
Page 3
3
MUFZ-KJ25VE -
E1
,
ER1
MUFZ-KJ35VE -
E1
,
ER1
MUFZ-KJ50VE -
E1
,
ER1
1. New model
TECHNICAL CHANGES
1
Air outlet
Drain outlet
Piping
Drain hose
Air inlet
(back and side)
MUFZ-KJ25VE MUFZ-KJ35VE
PART NAMES AND FUNCTIONS
2
ACCESSORIES
Model
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
Drain socket 1
Piping
Air outlet
Drain outlet
Air inlet
(back and side)
Drain hose
MUFZ-KJ50VE
OBH667B
Page 4
4
Outdoor model MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
Power supply Single phase, 230 V, 50 Hz
Capacity Rated frequency (Min.-Max.)
Cooling
kW
2.5 (0.5 - 3.4) 3.5 (0.5 - 3.7) 5.0 (1.6 - 5.7)
Heating 3.4 (1.2 - 4.6) 4.3 (1.2 - 5.5) 6.0 (2.2 - 8.2)
Breaker Capacity A 10 16
Electrical data
Power input 1 (Total)
Cooling
W
540 940 1,410
Heating 770 1,110 1,610
Running current
1
(Total)
Cooling
A
2.7 4.2 6.2
Heating 3.6 5.1 7.1
Power factor
1 (Total)
Cooling
%
87 98
Heating 91 93 98
Starting current
1 (Total) A 3.6 5.1 7.1
Coeffi cient of performance (COP)
1 (Total)
Cooling 4.63 3.72 3.55 Heating 4.42 3.91 3.73
Compressor
Model SNB140FRUMT SNB172FEKMT Output W 950 1,200
Current
1
Cooling
A
2.19 3.69 5.18
Heating 3.16 4.61 5.94
Refrigeration oil (Model) L 0.35 (FV50S) 0.40 (FV50S)
Fan motor
Model RC0J50-CI RC0J60-BC
Current
1
Cooling
A
0.28 0.82
Heating 0.31 0.82 Dimensions W × H × D mm 800 × 550 × 285 840 × 880 × 330 Weight kg 37 55
Special remarks
Dehumidifi cation Cooling L/h 0.6 1.4 2.0
Air fl ow 1
Cooling
Med.
m3/h
1,806 2,748
Low 1,038 1,632
Heating
High 2,016 2,856
Med. 1,710 2,748
Low 1,326 2,274
Sound level
1
Cooling
dB(A)
46 47 49
Heating 51
Fan speed
Cooling
Med.
rpm
810 780
Low 490 480
Heating
High 900 810
Med. 770 780
Low 610 650 Fan speed regulator 3 Refrigerant fi lling capacity (R410A) kg 1.10 1.50
NOTE: Test conditions are based on ISO 5151. Cooling: Indoor Dry-bulb temperature 27°C Wet-bulb temperature 19°C Outdoor Dry-bulb temperature 35°C Heating: Indoor Dry-bulb temperature 20°C Outdoor Dry-bulb temperature 7°C Wet-bulb temperature 6°C Refrigerant piping length (one way): 5 m 1 Measured under rated operating frequency.
SPECIFICATION
3
OBH667B
Page 5
5
Specifi cations and rated conditions of main electric parts
Model
Item
MUFZ-KJ25VE MUFZ-KJ35VE
Smoothing capacitor
(C61, C62) 600 μF/ 620 μF 420 V
Diode module (DB61) 15 A 600 V
Fuse
(F61) T20AL250V
(F701, F801, F901)
T3.15AL250V
Power module
(IC700) 15 A 600 V
(IC932) 8A600V
Expansion valve coil
(LEV) 12 V DC
Reactor (L61) 23 mH
Power factor controller
(IC820) 20A 600V
Circuit protection
(PTC64, PTC65) 33 Ω
Terminal block (TB) 5 P
Relay
(X63) 3 A 250 V
(X64) 20 A 250 V
(X69) 10A 250V
R.V.coil (21S4) 220 - 240 V AC
Specifi cations and rated conditions of main electric parts
Model
Item
MUZ-KJ50VE
Smoothing capacitor
(CB1, CB2, CB3)
560 μF 450 V
Fuse
(F601, F880, F901)
T3.15AL250 V
IGBT module
(IC932) 5 A 600 V
(IC700) 20 A 600 V
Expansion valve coil
(LEV) 12 V DC
Reactor (L) 340 μH Diode module (IC820) 20 A 600 V
Circuit protection
(PTC64, PTC65) 33 Ω
Terminal block (TB1, TB2) 3 P
Relay
(X64) 20 A 250 V (X65) 20 A 250 V
(X69) 10 A 250 V (X601) 3 A 250 V (X602) 3 A 250 V
R.V. coil (21S4) 220 - 240 V AC
OBH667B
Page 6
6
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
46 51
NC-10
MUFZ-KJ25VE
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
COOLING
FUNCTION
SPL(dB(A))
LINE
HEATING
47 51
NC-10
MUFZ-KJ35VE
NOISE CRITERIA CURVES
4
Test conditions Cooling: Dry-bulb temperature 35°C Heating: Dry-bulb temperature 7°C Wet-bulb temperature 6°C
OUTDOOR UNIT
MICROPHONE
1 m
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
NC-10
COOLING
FUNCTION
SPL(dB(A)) LINE
HEATING
49 51
MUFZ-KJ50VE
OBH667B
Page 7
7
10
69
800
302.5 500 Bolt pitch for installation
150
22.3
Handle
550
280
164.5
99.5
170.5
23
Service panel
Service port
285
344.5
44
400
Air in
Air out
Air in
17.5
Bolt pitch for
installation
304~325
40
Liquid refrigerant pipe joint Refrigerant pipe (flared) ø6.35
Gas refrigerant pipe joint Refrigerant pipe (flared) ø9.52
43
35
2 holes 10 X 21
Drain hole ø42
REQUIRED SPACE
350 mm or more
100 mm or more
100 mm or more
*1 100 mm or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
Clear *1
200 mm or
more *2
Unit: mm
MUFZ-KJ25VE MUFZ-KJ35VE
OUTLINES AND DIMENSIONS
5
MUFZ-KJ50VE
417.5
40
42
Drain hole
175
500
330
50
Air in
Air out
2-holes 10 21
360
840
109
81
880
452
Service panel
99.5
164.5 195
35
44
Liquid refrigerant pipe joint Refrigerant pipe (flared)
Ø 6.35
Gas refrigerant pipe joint Refrigerant pipe (flared)
Ø 12.7
350 mm or more
100 mm or more
REQUIRED SPACE
100 mm or more
500 mm
or more *2
*1 500 mm or more when front and sides of the unit are clear
*2 When any 2 sides of left, right and rear of the unit are clear
Clear *1
OBH667B
Page 8
8
WIRING DIAGRAM
6
MUFZ-KJ25VE MUFZ-KJ35VE
OBH667B
Page 9
9
MUFZ-KJ50VE
OBH667B
Page 10
10
Unit: mm
MUFZ-KJ25VE MUFZ-KJ35VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve (with strainar)
Stop valve
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe ø9.52 (with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
R.V. coil heating ON cooling OFF
Strainer #100
LEV
Ambient temperature thermistor RT65
Muffler
Capillary tube ø4.0×ø2.4×240
Outdoor heat exchanger temperature thermistor RT68
Capillary tube ø3.0×ø2.0×210
Muffler
REFRIGERANT SYSTEM DIAGRAM
7
MUFZ-KJ50VE
Outdoor heat exchanger
Flared connection
Defrost thermistor RT61
Discharge temperature thermistor RT62
Flared connection
Stop valve
Stop valve
Capillary tube
ø
4.0
×
ø
2.4×100 Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe ø6.35 (with heat insulator)
LEV
Muffler
R.V. coil heating ON cooling OFF
Muffler
#100
Strainer
#100
Outdoor heat exchanger temperature thermistor RT68
Ambient temperature thermistor RT65
Strainer
#100
OBH667B
Page 11
11
Max. Length A
Max. Height
difference
B
Indoor unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: m Piping size O.D: mm
Max. Length A Max. Height difference B Gas Liquid
MUFZ-KJ25/35 20 12 9.52 6.35 MUFZ-KJ50 30 15 12.7 6.35
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUFZ-KJ25/35 1,100
0 30 60 90 120 150 180 210 240 390
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 10 m 15 m 20 m 25 m 30 m
MUFZ-KJ50 1,500 0 60 160 260 360 460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
OBH667B
Page 12
12
PERFORMANCE CURVES8
The standard specifications apply only to the operation of the air conditioner under normal conditions. Since operating condi­tions vary according to the areas where these units are installed, the following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264 V, 50 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature: °C [WB]
}
Cooling
(2) Indoor outlet air wet-bulb temperature: °C [WB] (3) Outdoor intake air dry-bulb temperature: °C [DB] (4) Total input: W (5) Indoor intake air dry-bulb temperature: °C [DB]
}
Heating(6) Outdoor intake air wet-bulb temperature: °C [WB] (7) Total input: W Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
INDOOR UNIT OUTDOOR UNIT
Wet and dry bulb thermometers FRONT VIEW
Wet and dry bulb thermometers BACK VIEW
Cooling capacity (
at Rated frequency)
0.9
1.0
1.1
1.2
1.3
1.4
1.5
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature(°C)
Capacity correction factors
26
24
20 18
22
Indoor intake air Wet-bulb temperature( )
MUFZ-KJ35VE
MUFZ-KJ25VE
Indoor air Wet-bulb temperature
difference (°C)
8.5
7.9
7.2
6.6
6.0
5.4
4.8
12.9
11.8
10.8
9.8
8.8
7.9
7.0
14.6
13.4
12.2
11.0
9.9
8.9
7.8
MUFZ-KJ50VE
8-1. CAPACITY AND INPUT CURVES
OBH667B
Page 13
13
NOTE: The above broken lines are for the heating operation without any frost and defrost operation.
0.8
0.9
1.0
1.1
1.2
1.3
-10-5 0 5 1015202530354045 Outdoor intake air Dry-bulb temperature (°C)
Input correction factors
26
24
22 20 18
Indoor intake air Wet-bulb temperature( )
Indoor air Wet-bulb temperature
difference (°C)
7.2
6.6
6.0
5.4
4.8
4.2
10.8
9.8
8.8
7.9
7.0
6.1
MUFZ-KJ35VE
12.2
11.0
9.9
8.9
7.8
6.8
MUFZ-KJ50VE
MUFZ-KJ25VE
Total input (Cooling :
at Rated frequency
)
Indoor air Dry-bulb temperature
difference (°C)
22.9
21.2
19.4
17.6
15.9
14.1
12.3
10.6
8.8
7.1
MUFZ-KJ25VE
29.0
26.8
24.5
22.3
20.1
17.8
15.6
13.4
11.1
8.9
MUFZ-KJ35VE
28.0
25.9
23.7
21.6
19.4
17.2
15.1
12.9
10.8
8.6
MUFZ-KJ50VE
Outdoor intake air Wet-bulb temperature (°C)
-15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Heating capacity (
at Rated frequency)
Capacity correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
Indoor air Dry-bulb temperature
difference (°C)
22.9
21.2
19.4
17.6
15.9
14.1
12.3
10.6
8.8
7.1
MUFZ-KJ25VE
29.0
26.8
24.5
22.3
20.1
17.8
15.6
13.4
11.1
8.9
MUFZ-KJ35VE
28.0
25.9
23.7
21.6
19.4
17.2
15.1
12.9
10.8
8.6
MUFZ-KJ50VE
Outdoor intake air Wet-bulb temperature (°C)
-15 -10 -5 0 5 10 15
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
Total input (Heating :
at Rated frequency
)
Input correction factor
15
20
26
Indoor intake air Dry-bulb temperature ( )
OBH667B
Page 14
14
8-2. CAPACITY AND INPUT CORRECTION BY OPERATIONAL FREQUENCY OF COMPRESSOR
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
0.5
1.0
1.5
0 50 100
1
2
3
0 50 100
150
0.5
1.0
1.5
2.0
050100
150
1
2
3
0 50 100
150
0.5
1.0
1.5
2.0
050100
150
1
2
3
MUFZ-KJ25VE
MUFZ-KJ35VE
Correction of Coolin g capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operationalfrequency of compressor (Hz)
Input correction factors
Correction of Heating capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heati nginput
The operational frequency of compressor (Hz)
Input correction factors
Correction of Cooling capacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Cooling input
The operational frequency of compressor (Hz)
Input correction factors
Correction of Heati ngcapacity
The operational frequency of compressor (Hz)
Capacity correction factors
Correction of Heati nginput
The operational frequenc y of compressor (Hz)
Input correction factors
Correction of Cooling capacity
Capacity correction factors
Correction of Cooling input
Input correction factors
Correction of Heating capacity
Capacity correction factors
MUFZ-KJ50VE
Correction of Heating input
Capacity correction factors
The operational frequency of compressor (Hz)
The operational frequency of compressor (Hz)
The operational frequency of compressor (H z)
The operational frequency of compressor (Hz)
0 50 100
0.5
1.0
1.5
2.0
0 50 100
0.5
1.0
1.5
2.0
0 50 100 150
0.5
1.0
1.5
2.0
0 50 100 150
0.5
1.0
1.5
2.0
8-3. HOW TO OPERATE FIXED-FREQUENCY OPERATION
<Test run operation>
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5.
After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor varies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on remote controller.
OBH667B
Page 15
15
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
0.9
15 20 25 30 35
0.4
0.5
0.6
0.7
0.8
Ambient temperature(°C) Ambient humidity(%)
15 20 25 30 35
0.3
0.4
0.5
0.6
0.7
0.8
(kgf/cm2[Gauge])(MPa [Gauge])
6
5
4
7
8
9
(kgf/cm2[Gauge])(MPa [Gauge])
4
6
5
7
8
50 60 70
Ambient temperature(°C) Ambient humidity(%)
50 60 70
Ambient temperature(°C) Ambient humidity(%)
Outdoor low pressure
MUFZ-KJ25VE MUFZ-KJ35VE
MUFZ-KJ50VE
(kgf/cm2[Gauge])(MPa [Gauge])
50 60 70
3
5
4
6
7
8
COOL operation
Both indoor and outdoor unit are under the same temperature/
humidity condition.
Operation: TEST RUN OPERATION (Refer to 8-3.)
8-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
Dry-bulb temperature (°C) Relative humidity (%)
20 50 25 60 30 70
NOTE: The unit of pressure has been changed to MPa on the international system of units (SI unit system) The conversion factor is: 1 (MPa [Gauge]) = 10.2 (kgf/cm2 [Gauge])
15 20 25 30 35
1.5
2.0
2.5
3.0
15 20 25 30 35
2.5
3.0
3.5
4.0
4.5
Ambient temperature (°C) Ambient humidity(%)
50 60 70 50 60 70 50 60 70
Outdoor current (A)
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
MUFZ-KJ35VEMUFZ-KJ25VE
Outdoor unit current
15 20 25 30 35
3
4
5
6
7
8
MUFZ-KJ50VE
Ambient temperature (°C) Ambient humidity(%)
Outdoor current (A)
0510
15 20 25
2.5
3.0
3.5
4.0
4.5
0 5 10 15 20 25
4
5
6
7
8
9
0510
15 20 25
4.0
4.5
5.0
5.5
6.0
Ambient temperature (°C)
Outdoor current (A)
MUFZ-KJ35VEMUFZ-KJ25VE
Outdoor unit current
MUFZ-KJ50VE
Ambient temperature (°C)
Outdoor current (A)
Ambient temperature (°C)
Outdoor current (A)
Condition:
Operation: Test run operation (Refer to 8-3.)
HEAT operation
Indoor Outdoor
Dry bulb temperature (°C) 20.0 2 7 15 20.0
Wet bulb temperature (°C) 14.5 1 6 12 14.5
OBH667B
Page 16
16
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ25VE
CAPACITY: 2.5 kW SHF: 0.85 INPUT: 540 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.94 1.97 0.67 432 2.81 1.88 0.67 454 2.70 1.81 0.67 475 2.60 1.74 0.67 497
21 20 3.06 1.68 0.55 454 2.94 1.62 0.55 481 2.85 1.57 0.55 491 2.75 1.51 0.55 513
22 18 2.94 2.09 0.71 432 2.81 2.00 0.71 454 2.70 1.92 0.71 475 2.60 1.85 0.71 497
22 20 3.06 1.81 0.59 454 2.94 1.73 0.59 481 2.85 1.68 0.59 491 2.75 1.62 0.59 513
22 22 3.19 1.50 0.47 470 3.08 1.45 0.47 500 3.00 1.41 0.47 513 2.88 1.35 0.47 535
23 18 2.94 2.20 0.75 432 2.81 2.11 0.75 454 2.70 2.03 0.75 475 2.60 1.95 0.75 497
23 20 3.06 1.93 0.63 454 2.94 1.85 0.63 481 2.85 1.80 0.63 491 2.75 1.73 0.63 513
23 22 3.19 1.63 0.51 470 3.08 1.57 0.51 500 3.00 1.53 0.51 513 2.88 1.47 0.51 535
24 18 2.94 2.32 0.79 432 2.81 2.22 0.79 454 2.70 2.13 0.79 475 2.60 2.05 0.79 497
24 20 3.06 2.05 0.67 454 2.94 1.97 0.67 481 2.85 1.91 0.67 491 2.75 1.84 0.67 513
24 22 3.19 1.75 0.55 470 3.08 1.69 0.55 500 3.00 1.65 0.55 513 2.88 1.58 0.55 535
24 24 3.35 1.44 0.43 491 3.23 1.39 0.43 518 3.15 1.35 0.43 535 3.05 1.31 0.43 562
25 18 2.94 2.44 0.83 432 2.81 2.33 0.83 454 2.70 2.24 0.83 475 2.60 2.16 0.83 497
25 20 3.06 2.17 0.71 454 2.94 2.09 0.71 481 2.85 2.02 0.71 491 2.75 1.95 0.71 513
25 22 3.19 1.88 0.59 470 3.08 1.81 0.59 500 3.00 1.77 0.59 513 2.88 1.70 0.59 535
25 24 3.35 1.57 0.47 491 3.23 1.52 0.47 518 3.15 1.48 0.47 535 3.05 1.43 0.47 562
26 18 2.94 2.56 0.87 432 2.81 2.45 0.87 454 2.70 2.35 0.87 475 2.60 2.26 0.87 497
26 20 3.06 2.30 0.75 454 2.94 2.20 0.75 481 2.85 2.14 0.75 491 2.75 2.06 0.75 513
26 22 3.19 2.01 0.63 470 3.08 1.94 0.63 500 3.00 1.89 0.63 513 2.88 1.81 0.63 535
26 24 3.35 1.71 0.51 491 3.23 1.64 0.51 518 3.15 1.61 0.51 535 3.05 1.56 0.51 562
26 26 3.45 1.35 0.39 518 3.35 1.31 0.39 545 3.30 1.29 0.39 562 3.20 1.25 0.39 578
27 18 2.94 2.67 0.91 432 2.81 2.56 0.91 454 2.70 2.46 0.91 475 2.60 2.37 0.91 497
27 20 3.06 2.42 0.79 454 2.94 2.32 0.79 481 2.85 2.25 0.79 491 2.75 2.17 0.79 513
27 22 3.19 2.14 0.67 470 3.08 2.06 0.67 500 3.00 2.01 0.67 513 2.88 1.93 0.67 535
27 24 3.35 1.84 0.55 491 3.23 1.77 0.55 518 3.15 1.73 0.55 535 3.05 1.68 0.55 562
27 26 3.45 1.48 0.43 518 3.35 1.44 0.43 545 3.30 1.42 0.43 562 3.20 1.38 0.43 578
28 18 2.94 2.79 0.95 432 2.81 2.67 0.95 454 2.70 2.57 0.95 475 2.60 2.47 0.95 497
28 20 3.06 2.54 0.83 454 2.94 2.44 0.83 481 2.85 2.37 0.83 491 2.75 2.28 0.83 513
28 22 3.19 2.26 0.71 470 3.08 2.18 0.71 500 3.00 2.13 0.71 513 2.88 2.04 0.71 535
28 24 3.35 1.98 0.59 491 3.23 1.90 0.59 518 3.15 1.86 0.59 535 3.05 1.80 0.59 562
28 26 3.45 1.62 0.47 518 3.35 1.57 0.47 545 3.30 1.55 0.47 562 3.20 1.50 0.47 578
29 18 2.94 2.91 0.99 432 2.81 2.78 0.99 454 2.70 2.67 0.99 475 2.60 2.57 0.99 497
29 20 3.06 2.66 0.87 454 2.94 2.56 0.87 481 2.85 2.48 0.87 491 2.75 2.39 0.87 513
29 22 3.19 2.39 0.75 470 3.08 2.31 0.75 500 3.00 2.25 0.75 513 2.88 2.16 0.75 535
29 24 3.35 2.11 0.63 491 3.23 2.03 0.63 518 3.15 1.98 0.63 535 3.05 1.92 0.63 562
29 26 3.45 1.76 0.51 518 3.35 1.71 0.51 545 3.30 1.68 0.51 562 3.20 1.63 0.51 578
30 18 2.94 2.94 1.00 432 2.81 2.81 1.00 454 2.70 2.70 1.00 475 2.60 2.60 1.00 497
30 20 3.06 2.79 0.91 454 2.94 2.67 0.91 481 2.85 2.59 0.91 491 2.75 2.50 0.91 513
30 22 3.19 2.52 0.79 470 3.08 2.43 0.79 500 3.00 2.37 0.79 513 2.88 2.27 0.79 535
30 24 3.35 2.24 0.67 491 3.23 2.16 0.67 518 3.15 2.11 0.67 535 3.05 2.04 0.67 562
30 26 3.45 1.90 0.55 518 3.35 1.84 0.55 545 3.30 1.82 0.55 562 3.20 1.76 0.55 578
31 18 2.94 2.94 1.00 432 2.81 2.81 1.00 454 2.70 2.70 1.00 475 2.60 2.60 1.00 497
31 20 3.06 2.91 0.95 454 2.94 2.79 0.95 481 2.85 2.71 0.95 491 2.75 2.61 0.95 513
31 22 3.19 2.65 0.83 470 3.08 2.55 0.83 500 3.00 2.49 0.83 513 2.88 2.39 0.83 535
31 24 3.35 2.38 0.71 491 3.23 2.29 0.71 518 3.15 2.24 0.71 535 3.05 2.17 0.71 562
31 26 3.45 2.04 0.59 518 3.35 1.98 0.59 545 3.30 1.95 0.59 562 3.20 1.89 0.59 578
32 18 2.94 2.94 1.00 432 2.81 2.81 1.00 454 2.70 2.70 1.00 475 2.60 2.60 1.00 497
32 20 3.06 3.03 0.99 454 2.94 2.91 0.99 481 2.85 2.82 0.99 491 2.75 2.72 0.99 513
32 22 3.19 2.77 0.87 470 3.08 2.68 0.87 500 3.00 2.61 0.87 513 2.88 2.50 0.87 535
32 24 3.35 2.51 0.75 491 3.23 2.42 0.75 518 3.15 2.36 0.75 535 3.05 2.29 0.75 562
32 26 3.45 2.17 0.63 518 3.35 2.11 0.63 545 3.30 2.08 0.63 562 3.20 2.02 0.63 578
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Page 17
17
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ25VE
CAPACITY: 2.5 kW SHF: 0.85 INPUT: 540 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 2.45 1.64 0.67 529 2.25 1.51 0.67 562 2.08 1.39 0.67 583
21 20 2.58 1.42 0.55 551 2.40 1.32 0.55 578 2.23 1.22 0.55 610
22 18 2.45 1.74 0.71 529 2.25 1.60 0.71 562 2.08 1.47 0.71 583
22 20 2.58 1.52 0.59 551 2.40 1.42 0.59 578 2.23 1.31 0.59 610
22 22 2.73 1.28 0.47 572 2.55 1.20 0.47 605 2.38 1.12 0.47 626
23 18 2.45 1.84 0.75 529 2.25 1.69 0.75 562 2.08 1.56 0.75 583
23 20 2.58 1.62 0.63 551 2.40 1.51 0.63 578 2.23 1.40 0.63 610
23 22 2.73 1.39 0.51 572 2.55 1.30 0.51 605 2.38 1.21 0.51 626
24 18 2.45 1.94 0.79 529 2.25 1.78 0.79 562 2.08 1.64 0.79 583
24 20 2.58 1.73 0.67 551 2.40 1.61 0.67 578 2.23 1.49 0.67 610
24 22 2.73 1.50 0.55 572 2.55 1.40 0.55 605 2.38 1.31 0.55 626
24 24 2.88 1.24 0.43 594 2.70 1.16 0.43 621 2.55 1.10 0.43 648
25 18 2.45 2.03 0.83 529 2.25 1.87 0.83 562 2.08 1.72 0.83 583
25 20 2.58 1.83 0.71 551 2.40 1.70 0.71 578 2.23 1.58 0.71 610
25 22 2.73 1.61 0.59 572 2.55 1.50 0.59 605 2.38 1.40 0.59 626
25 24 2.88 1.35 0.47 594 2.70 1.27 0.47 621 2.55 1.20 0.47 648
26 18 2.45 2.13 0.87 529 2.25 1.96 0.87 562 2.08 1.81 0.87 583
26 20 2.58 1.93 0.75 551 2.40 1.80 0.75 578 2.23 1.67 0.75 610
26 22 2.73 1.72 0.63 572 2.55 1.61 0.63 605 2.38 1.50 0.63 626
26 24 2.88 1.47 0.51 594 2.70 1.38 0.51 621 2.55 1.30 0.51 648
26 26 3.03 1.18 0.39 616 2.85 1.11 0.39 643 2.68 1.04 0.39 670
27 18 2.45 2.23 0.91 529 2.25 2.05 0.91 562 2.08 1.89 0.91 583
27 20 2.58 2.03 0.79 551 2.40 1.90 0.79 578 2.23 1.76 0.79 610
27 22 2.73 1.83 0.67 572 2.55 1.71 0.67 605 2.38 1.59 0.67 626
27 24 2.88 1.58 0.55 594 2.70 1.49 0.55 621 2.55 1.40 0.55 648
27 26 3.03 1.30 0.43 616 2.85 1.23 0.43 643 2.68 1.15 0.43 670
28 18 2.45 2.33 0.95 529 2.25 2.14 0.95 562 2.08 1.97 0.95 583
28 20 2.58 2.14 0.83 551 2.40 1.99 0.83 578 2.23 1.85 0.83 610
28 22 2.73 1.93 0.71 572 2.55 1.81 0.71 605 2.38 1.69 0.71 626
28 24 2.88 1.70 0.59 594 2.70 1.59 0.59 621 2.55 1.50 0.59 648
28 26 3.03 1.42 0.47 616 2.85 1.34 0.47 643 2.68 1.26 0.47 670
29 18 2.45 2.43 0.99 529 2.25 2.23 0.99 562 2.08 2.05 0.99 583
29 20 2.58 2.24 0.87 551 2.40 2.09 0.87 578 2.23 1.94 0.87 610
29 22 2.73 2.04 0.75 572 2.55 1.91 0.75 605 2.38 1.78 0.75 626
29 24 2.88 1.81 0.63 594 2.70 1.70 0.63 621 2.55 1.61 0.63 648
29 26 3.03 1.54 0.51 616 2.85 1.45 0.51 643 2.68 1.36 0.51 670
30 18 2.45 2.45 1.00 529 2.25 2.25 1.00 562 2.08 2.08 1.00 583
30 20 2.58 2.34 0.91 551 2.40 2.18 0.91 578 2.23 2.02 0.91 610
30 22 2.73 2.15 0.79 572 2.55 2.01 0.79 605 2.38 1.88 0.79 626
30 24 2.88 1.93 0.67 594 2.70 1.81 0.67 621 2.55 1.71 0.67 648
30 26 3.03 1.66 0.55 616 2.85 1.57 0.55 643 2.68 1.47 0.55 670
31 18 2.45 2.45 1.00 529 2.25 2.25 1.00 562 2.08 2.08 1.00 583
31 20 2.58 2.45 0.95 551 2.40 2.28 0.95 578 2.23 2.11 0.95 610
31 22 2.73 2.26 0.83 572 2.55 2.12 0.83 605 2.38 1.97 0.83 626
31 24 2.88 2.04 0.71 594 2.70 1.92 0.71 621 2.55 1.81 0.71 648
31 26 3.03 1.78 0.59 616 2.85 1.68 0.59 643 2.68 1.58 0.59 670
32 18 2.45 2.45 1.00 529 2.25 2.25 1.00 562 2.08 2.08 1.00 583
32 20 2.58 2.55 0.99 551 2.40 2.38 0.99 578 2.23 2.20 0.99 610
32 22 2.73 2.37 0.87 572 2.55 2.22 0.87 605 2.38 2.07 0.87 626
32 24 2.88 2.16 0.75 594 2.70 2.03 0.75 621 2.55 1.91 0.75 648
32 26 3.03 1.91 0.63 616 2.85 1.80 0.63 643 2.68 1.69 0.63 670
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Page 18
18
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ35VE
CAPACITY: 3.5 kW SHF: 0.73 INPUT: 940 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.11 2.26 0.55 752 3.94 2.17 0.55 790 3.78 2.08 0.55 827 3.64 2.00 0.55 865
21 20 4.29 1.84 0.43 790 4.11 1.77 0.43 837 3.99 1.72 0.43 855 3.85 1.66 0.43 893
22 18 4.11 2.43 0.59 752 3.94 2.32 0.59 790 3.78 2.23 0.59 827 3.64 2.15 0.59 865
22 20 4.29 2.02 0.47 790 4.11 1.93 0.47 837 3.99 1.88 0.47 855 3.85 1.81 0.47 893
22 22 4.46 1.56 0.35 818 4.31 1.51 0.35 870 4.20 1.47 0.35 893 4.03 1.41 0.35 931
23 18 4.11 2.59 0.63 752 3.94 2.48 0.63 790 3.78 2.38 0.63 827 3.64 2.29 0.63 865
23 20 4.29 2.19 0.51 790 4.11 2.10 0.51 837 3.99 2.03 0.51 855 3.85 1.96 0.51 893
23 22 4.46 1.74 0.39 818 4.31 1.68 0.39 870 4.20 1.64 0.39 893 4.03 1.57 0.39 931
24 18 4.11 2.76 0.67 752 3.94 2.64 0.67 790 3.78 2.53 0.67 827 3.64 2.44 0.67 865
24 20 4.29 2.36 0.55 790 4.11 2.26 0.55 837 3.99 2.19 0.55 855 3.85 2.12 0.55 893
24 22 4.46 1.92 0.43 818 4.31 1.85 0.43 870 4.20 1.81 0.43 893 4.03 1.73 0.43 931
24 24 4.69 1.45 0.31 855 4.52 1.40 0.31 902 4.41 1.37 0.31 931 4.27 1.32 0.31 978
25 18 4.11 2.92 0.71 752 3.94 2.80 0.71 790 3.78 2.68 0.71 827 3.64 2.58 0.71 865
25 20 4.29 2.53 0.59 790 4.11 2.43 0.59 837 3.99 2.35 0.59 855 3.85 2.27 0.59 893
25 22 4.46 2.10 0.47 818 4.31 2.02 0.47 870 4.20 1.97 0.47 893 4.03 1.89 0.47 931
25 24 4.69 1.64 0.35 855 4.52 1.58 0.35 902 4.41 1.54 0.35 931 4.27 1.49 0.35 978
26 18 4.11 3.08 0.75 752 3.94 2.95 0.75 790 3.78 2.84 0.75 827 3.64 2.73 0.75 865
26 20 4.29 2.70 0.63 790 4.11 2.59 0.63 837 3.99 2.51 0.63 855 3.85 2.43 0.63 893
26 22 4.46 2.28 0.51 818 4.31 2.20 0.51 870 4.20 2.14 0.51 893 4.03 2.05 0.51 931
26 24 4.69 1.83 0.39 855 4.52 1.76 0.39 902 4.41 1.72 0.39 931 4.27 1.67 0.39 978
26 26 4.83 1.30 0.27 902 4.69 1.27 0.27 949 4.62 1.25 0.27 978 4.48 1.21 0.27 1006
27 18 4.11 3.25 0.79 752 3.94 3.11 0.79 790 3.78 2.99 0.79 827 3.64 2.88 0.79 865
27 20 4.29 2.87 0.67 790 4.11 2.76 0.67 837 3.99 2.67 0.67 855 3.85 2.58 0.67 893
27 22 4.46 2.45 0.55 818 4.31 2.37 0.55 870 4.20 2.31 0.55 893 4.03 2.21 0.55 931
27 24 4.69 2.02 0.43 855 4.52 1.94 0.43 902 4.41 1.90 0.43 931 4.27 1.84 0.43 978
27 26 4.83 1.50 0.31 902 4.69 1.45 0.31 949 4.62 1.43 0.31 978 4.48 1.39 0.31 1006
28 18 4.11 3.41 0.83 752 3.94 3.27 0.83 790 3.78 3.14 0.83 827 3.64 3.02 0.83 865
28 20 4.29 3.04 0.71 790 4.11 2.92 0.71 837 3.99 2.83 0.71 855 3.85 2.73 0.71 893
28 22 4.46 2.63 0.59 818 4.31 2.54 0.59 870 4.20 2.48 0.59 893 4.03 2.37 0.59 931
28 24 4.69 2.20 0.47 855 4.52 2.12 0.47 902 4.41 2.07 0.47 931 4.27 2.01 0.47 978
28 26 4.83 1.69 0.35 902 4.69 1.64 0.35 949 4.62 1.62 0.35 978 4.48 1.57 0.35 1006
29 18 4.11 3.58 0.87 752 3.94 3.43 0.87 790 3.78 3.29 0.87 827 3.64 3.17 0.87 865
29 20 4.29 3.22 0.75 790 4.11 3.08 0.75 837 3.99 2.99 0.75 855 3.85 2.89 0.75 893
29 22 4.46 2.81 0.63 818 4.31 2.71 0.63 870 4.20 2.65 0.63 893 4.03 2.54 0.63 931
29 24 4.69 2.39 0.51 855 4.52 2.30 0.51 902 4.41 2.25 0.51 931 4.27 2.18 0.51 978
29 26 4.83 1.88 0.39 902 4.69 1.83 0.39 949 4.62 1.80 0.39 978 4.48 1.75 0.39 1006
30 18 4.11 3.74 0.91 752 3.94 3.58 0.91 790 3.78 3.44 0.91 827 3.64 3.31 0.91 865
30 20 4.29 3.39 0.79 790 4.11 3.25 0.79 837 3.99 3.15 0.79 855 3.85 3.04 0.79 893
30 22 4.46 2.99 0.67 818 4.31 2.88 0.67 870 4.20 2.81 0.67 893 4.03 2.70 0.67 931
30 24 4.69 2.58 0.55 855 4.52 2.48 0.55 902 4.41 2.43 0.55 931 4.27 2.35 0.55 978
30 26 4.83 2.08 0.43 902 4.69 2.02 0.43 949 4.62 1.99 0.43 978 4.48 1.93 0.43 1006
31 18 4.11 3.91 0.95 752 3.94 3.74 0.95 790 3.78 3.59 0.95 827 3.64 3.46 0.95 865
31 20 4.29 3.56 0.83 790 4.11 3.41 0.83 837 3.99 3.31 0.83 855 3.85 3.20 0.83 893
31 22 4.46 3.17 0.71 818 4.31 3.06 0.71 870 4.20 2.98 0.71 893 4.03 2.86 0.71 931
31 24 4.69 2.77 0.59 855 4.52 2.66 0.59 902 4.41 2.60 0.59 931 4.27 2.52 0.59 978
31 26 4.83 2.27 0.47 902 4.69 2.20 0.47 949 4.62 2.17 0.47 978 4.48 2.11 0.47 1006
32 18 4.11 4.07 0.99 752 3.94 3.90 0.99 790 3.78 3.74 0.99 827 3.64 3.60 0.99 865
32 20 4.29 3.73 0.87 790 4.11 3.58 0.87 837 3.99 3.47 0.87 855 3.85 3.35 0.87 893
32 22 4.46 3.35 0.75 818 4.31 3.23 0.75 870 4.20 3.15 0.75 893 4.03 3.02 0.75 931
32 24 4.69 2.95 0.63 855 4.52 2.84 0.63 902 4.41 2.78 0.63 931 4.27 2.69 0.63 978
32 26 4.83 2.46 0.51 902 4.69 2.39 0.51 949 4.62 2.36 0.51 978 4.48 2.28 0.51 1006
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Page 19
19
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ35VE
CAPACITY: 3.5 kW SHF: 0.73 INPUT: 940 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 3.43 1.89 0.55 921 3.15 1.73 0.55 978 2.91 1.60 0.55 1015
21 20 3.61 1.55 0.43 959 3.36 1.44 0.43 1006 3.12 1.34 0.43 1062
22 18 3.43 2.02 0.59 921 3.15 1.86 0.59 978 2.91 1.71 0.59 1015
22 20 3.61 1.69 0.47 959 3.36 1.58 0.47 1006 3.12 1.46 0.47 1062
22 22 3.82 1.34 0.35 996 3.57 1.25 0.35 1053 3.33 1.16 0.35 1090
23 18 3.43 2.16 0.63 921 3.15 1.98 0.63 978 2.91 1.83 0.63 1015
23 20 3.61 1.84 0.51 959 3.36 1.71 0.51 1006 3.12 1.59 0.51 1062
23 22 3.82 1.49 0.39 996 3.57 1.39 0.39 1053 3.33 1.30 0.39 1090
24 18 3.43 2.30 0.67 921 3.15 2.11 0.67 978 2.91 1.95 0.67 1015
24 20 3.61 1.98 0.55 959 3.36 1.85 0.55 1006 3.12 1.71 0.55 1062
24 22 3.82 1.64 0.43 996 3.57 1.54 0.43 1053 3.33 1.43 0.43 1090
24 24 4.03 1.25 0.31 1034 3.78 1.17 0.31 1081 3.57 1.11 0.31 1128
25 18 3.43 2.44 0.71 921 3.15 2.24 0.71 978 2.91 2.06 0.71 1015
25 20 3.61 2.13 0.59 959 3.36 1.98 0.59 1006 3.12 1.84 0.59 1062
25 22 3.82 1.79 0.47 996 3.57 1.68 0.47 1053 3.33 1.56 0.47 1090
25 24 4.03 1.41 0.35 1034 3.78 1.32 0.35 1081 3.57 1.25 0.35 1128
26 18 3.43 2.57 0.75 921 3.15 2.36 0.75 978 2.91 2.18 0.75 1015
26 20 3.61 2.27 0.63 959 3.36 2.12 0.63 1006 3.12 1.96 0.63 1062
26 22 3.82 1.95 0.51 996 3.57 1.82 0.51 1053 3.33 1.70 0.51 1090
26 24 4.03 1.57 0.39 1034 3.78 1.47 0.39 1081 3.57 1.39 0.39 1128
26 26 4.24 1.14 0.27 1072 3.99 1.08 0.27 1119 3.75 1.01 0.27 1166
27 18 3.43 2.71 0.79 921 3.15 2.49 0.79 978 2.91 2.29 0.79 1015
27 20 3.61 2.42 0.67 959 3.36 2.25 0.67 1006 3.12 2.09 0.67 1062
27 22 3.82 2.10 0.55 996 3.57 1.96 0.55 1053 3.33 1.83 0.55 1090
27 24 4.03 1.73 0.43 1034 3.78 1.63 0.43 1081 3.57 1.54 0.43 1128
27 26 4.24 1.31 0.31 1072 3.99 1.24 0.31 1119 3.75 1.16 0.31 1166
28 18 3.43 2.85 0.83 921 3.15 2.61 0.83 978 2.91 2.41 0.83 1015
28 20 3.61 2.56 0.71 959 3.36 2.39 0.71 1006 3.12 2.21 0.71 1062
28 22 3.82 2.25 0.59 996 3.57 2.11 0.59 1053 3.33 1.96 0.59 1090
28 24 4.03 1.89 0.47 1034 3.78 1.78 0.47 1081 3.57 1.68 0.47 1128
28 26 4.24 1.48 0.35 1072 3.99 1.40 0.35 1119 3.75 1.31 0.35 1166
29 18 3.43 2.98 0.87 921 3.15 2.74 0.87 978 2.91 2.53 0.87 1015
29 20 3.61 2.70 0.75 959 3.36 2.52 0.75 1006 3.12 2.34 0.75 1062
29 22 3.82 2.40 0.63 996 3.57 2.25 0.63 1053 3.33 2.09 0.63 1090
29 24 4.03 2.05 0.51 1034 3.78 1.93 0.51 1081 3.57 1.82 0.51 1128
29 26 4.24 1.65 0.39 1072 3.99 1.56 0.39 1119 3.75 1.46 0.39 1166
30 18 3.43 3.12 0.91 921 3.15 2.87 0.91 978 2.91 2.64 0.91 1015
30 20 3.61 2.85 0.79 959 3.36 2.65 0.79 1006 3.12 2.46 0.79 1062
30 22 3.82 2.56 0.67 996 3.57 2.39 0.67 1053 3.33 2.23 0.67 1090
30 24 4.03 2.21 0.55 1034 3.78 2.08 0.55 1081 3.57 1.96 0.55 1128
30 26 4.24 1.82 0.43 1072 3.99 1.72 0.43 1119 3.75 1.61 0.43 1166
31 18 3.43 3.26 0.95 921 3.15 2.99 0.95 978 2.91 2.76 0.95 1015
31 20 3.61 2.99 0.83 959 3.36 2.79 0.83 1006 3.12 2.59 0.83 1062
31 22 3.82 2.71 0.71 996 3.57 2.53 0.71 1053 3.33 2.36 0.71 1090
31 24 4.03 2.37 0.59 1034 3.78 2.23 0.59 1081 3.57 2.11 0.59 1128
31 26 4.24 1.99 0.47 1072 3.99 1.88 0.47 1119 3.75 1.76 0.47 1166
32 18 3.43 3.40 0.99 921 3.15 3.12 0.99 978 2.91 2.88 0.99 1015
32 20 3.61 3.14 0.87 959 3.36 2.92 0.87 1006 3.12 2.71 0.87 1062
32 22 3.82 2.86 0.75 996 3.57 2.68 0.75 1053 3.33 2.49 0.75 1090
32 24 4.03 2.54 0.63 1034 3.78 2.38 0.63 1081 3.57 2.25 0.63 1128
32 26 4.24 2.16 0.51 1072 3.99 2.03 0.51 1119 3.75 1.91 0.51 1166
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Page 20
20
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ50VE
CAPACITY: 5.0 kW SHF: 0.71 INPUT: 1410 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
21 25 27 30
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 5.88 3.11 0.53 1128 5.63 2.98 0.53 1184 5.40 2.86 0.53 1241 5.20 2.76 0.53 1297
21 20 6.13 2.51 0.41 1184 5.88 2.41 0.41 1255 5.70 2.34 0.41 1283 5.50 2.26 0.41 1340
22 18 5.88 3.35 0.57 1128 5.63 3.21 0.57 1184 5.40 3.08 0.57 1241 5.20 2.96 0.57 1297
22 20 6.13 2.76 0.45 1184 5.88 2.64 0.45 1255 5.70 2.57 0.45 1283 5.50 2.48 0.45 1340
22 22 6.38 2.10 0.33 1227 6.15 2.03 0.33 1304 6.00 1.98 0.33 1340 5.75 1.90 0.33 1396
23 18 5.88 3.58 0.61 1128 5.63 3.43 0.61 1184 5.40 3.29 0.61 1241 5.20 3.17 0.61 1297
23 20 6.13 3.00 0.49 1184 5.88 2.88 0.49 1255 5.70 2.79 0.49 1283 5.50 2.70 0.49 1340
23 22 6.38 2.36 0.37 1227 6.15 2.28 0.37 1304 6.00 2.22 0.37 1340 5.75 2.13 0.37 1396
24 18 5.88 3.82 0.65 1128 5.63 3.66 0.65 1184 5.40 3.51 0.65 1241 5.20 3.38 0.65 1297
24 20 6.13 3.25 0.53 1184 5.88 3.11 0.53 1255 5.70 3.02 0.53 1283 5.50 2.92 0.53 1340
24 22 6.38 2.61 0.41 1227 6.15 2.52 0.41 1304 6.00 2.46 0.41 1340 5.75 2.36 0.41 1396
24 24 6.70 1.94 0.29 1283 6.45 1.87 0.29 1354 6.30 1.83 0.29 1396 6.10 1.77 0.29 1466
25 18 5.88 4.05 0.69 1128 5.63 3.88 0.69 1184 5.40 3.73 0.69 1241 5.20 3.59 0.69 1297
25 20 6.13 3.49 0.57 1184 5.88 3.35 0.57 1255 5.70 3.25 0.57 1283 5.50 3.14 0.57 1340
25 22 6.38 2.87 0.45 1227 6.15 2.77 0.45 1304 6.00 2.70 0.45 1340 5.75 2.59 0.45 1396
25 24 6.70 2.21 0.33 1283 6.45 2.13 0.33 1354 6.30 2.08 0.33 1396 6.10 2.01 0.33 1466
26 18 5.88 4.29 0.73 1128 5.63 4.11 0.73 1184 5.40 3.94 0.73 1241 5.20 3.80 0.73 1297
26 20 6.13 3.74 0.61 1184 5.88 3.58 0.61 1255 5.70 3.48 0.61 1283 5.50 3.36 0.61 1340
26 22 6.38 3.12 0.49 1227 6.15 3.01 0.49 1304 6.00 2.94 0.49 1340 5.75 2.82 0.49 1396
26 24 6.70 2.48 0.37 1283 6.45 2.39 0.37 1354 6.30 2.33 0.37 1396 6.10 2.26 0.37 1466
26 26 6.90 1.73 0.25 1354 6.70 1.68 0.25 1424 6.60 1.65 0.25 1466 6.40 1.60 0.25 1509
27 18 5.88 4.52 0.77 1128 5.63 4.33 0.77 1184 5.40 4.16 0.77 1241 5.20 4.00 0.77 1297
27 20 6.13 3.98 0.65 1184 5.88 3.82 0.65 1255 5.70 3.71 0.65 1283 5.50 3.58 0.65 1340
27 22 6.38 3.38 0.53 1227 6.15 3.26 0.53 1304 6.00 3.18 0.53 1340 5.75 3.05 0.53 1396
27 24 6.70 2.75 0.41 1283 6.45 2.64 0.41 1354 6.30 2.58 0.41 1396 6.10 2.50 0.41 1466
27 26 6.90 2.00 0.29 1354 6.70 1.94 0.29 1424 6.60 1.91 0.29 1466 6.40 1.86 0.29 1509
28 18 5.88 4.76 0.81 1128 5.63 4.56 0.81 1184 5.40 4.37 0.81 1241 5.20 4.21 0.81 1297
28 20 6.13 4.23 0.69 1184 5.88 4.05 0.69 1255 5.70 3.93 0.69 1283 5.50 3.80 0.69 1340
28 22 6.38 3.63 0.57 1227 6.15 3.51 0.57 1304 6.00 3.42 0.57 1340 5.75 3.28 0.57 1396
28 24 6.70 3.02 0.45 1283 6.45 2.90 0.45 1354 6.30 2.84 0.45 1396 6.10 2.75 0.45 1466
28 26 6.90 2.28 0.33 1354 6.70 2.21 0.33 1424 6.60 2.18 0.33 1466 6.40 2.11 0.33 1509
29 18 5.88 4.99 0.85 1128 5.63 4.78 0.85 1184 5.40 4.59 0.85 1241 5.20 4.42 0.85 1297
29 20 6.13 4.47 0.73 1184 5.88 4.29 0.73 1255 5.70 4.16 0.73 1283 5.50 4.02 0.73 1340
29 22 6.38 3.89 0.61 1227 6.15 3.75 0.61 1304 6.00 3.66 0.61 1340 5.75 3.51 0.61 1396
29 24 6.70 3.28 0.49 1283 6.45 3.16 0.49 1354 6.30 3.09 0.49 1396 6.10 2.99 0.49 1466
29 26 6.90 2.55 0.37 1354 6.70 2.48 0.37 1424 6.60 2.44 0.37 1466 6.40 2.37 0.37 1509
30 18 5.88 5.23 0.89 1128 5.63 5.01 0.89 1184 5.40 4.81 0.89 1241 5.20 4.63 0.89 1297
30 20 6.13 4.72 0.77 1184 5.88 4.52 0.77 1255 5.70 4.39 0.77 1283 5.50 4.24 0.77 1340
30 22 6.38 4.14 0.65 1227 6.15 4.00 0.65 1304 6.00 3.90 0.65 1340 5.75 3.74 0.65 1396
30 24 6.70 3.55 0.53 1283 6.45 3.42 0.53 1354 6.30 3.34 0.53 1396 6.10 3.23 0.53 1466
30 26 6.90 2.83 0.41 1354 6.70 2.75 0.41 1424 6.60 2.71 0.41 1466 6.40 2.62 0.41 1509
31 18 5.88 5.46 0.93 1128 5.63 5.23 0.93 1184 5.40 5.02 0.93 1241 5.20 4.84 0.93 1297
31 20 6.13 4.96 0.81 1184 5.88 4.76 0.81 1255 5.70 4.62 0.81 1283 5.50 4.46 0.81 1340
31 22 6.38 4.40 0.69 1227 6.15 4.24 0.69 1304 6.00 4.14 0.69 1340 5.75 3.97 0.69 1396
31 24 6.70 3.82 0.57 1283 6.45 3.68 0.57 1354 6.30 3.59 0.57 1396 6.10 3.48 0.57 1466
31 26 6.90 3.11 0.45 1354 6.70 3.02 0.45 1424 6.60 2.97 0.45 1466 6.40 2.88 0.45 1509
32 18 5.88 5.70 0.97 1128 5.63 5.46 0.97 1184 5.40 5.24 0.97 1241 5.20 5.04 0.97 1297
32 20 6.13 5.21 0.85 1184 5.88 4.99 0.85 1255 5.70 4.84 0.85 1283 5.50 4.68 0.85 1340
32 22 6.38 4.65 0.73 1227 6.15 4.49 0.73 1304 6.00 4.38 0.73 1340 5.75 4.20 0.73 1396
32 24 6.70 4.09 0.61 1283 6.45 3.93 0.61 1354 6.30 3.84 0.61 1396 6.10 3.72 0.61 1466
32 26 6.90 3.38 0.49 1354 6.70 3.28 0.49 1424 6.60 3.23 0.49 1466 6.40 3.14 0.49 1509
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Page 21
21
PERFORMANCE DATA COOL operation at Rated frequency
MUFZ-KJ50VE
CAPACITY: 5.0 kW SHF: 0.71 INPUT: 1410 W
INDOOR
DB (°C)
INDOOR
WB (°C)
OUTDOOR DB (°C)
35 40 46
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT
21 18 4.90 2.60 0.53 1382 4.50 2.39 0.53 1466 4.15 2.20 0.53 1523
21 20 5.15 2.11 0.41 1438 4.80 1.97 0.41 1509 4.45 1.82 0.41 1593
22 18 4.90 2.79 0.57 1382 4.50 2.57 0.57 1466 4.15 2.37 0.57 1523
22 20 5.15 2.32 0.45 1438 4.80 2.16 0.45 1509 4.45 2.00 0.45 1593
22 22 5.45 1.80 0.33 1495 5.10 1.68 0.33 1579 4.75 1.57 0.33 1636
23 18 4.90 2.99 0.61 1382 4.50 2.75 0.61 1466 4.15 2.53 0.61 1523
23 20 5.15 2.52 0.49 1438 4.80 2.35 0.49 1509 4.45 2.18 0.49 1593
23 22 5.45 2.02 0.37 1495 5.10 1.89 0.37 1579 4.75 1.76 0.37 1636
24 18 4.90 3.19 0.65 1382 4.50 2.93 0.65 1466 4.15 2.70 0.65 1523
24 20 5.15 2.73 0.53 1438 4.80 2.54 0.53 1509 4.45 2.36 0.53 1593
24 22 5.45 2.23 0.41 1495 5.10 2.09 0.41 1579 4.75 1.95 0.41 1636
24 24 5.75 1.67 0.29 1551 5.40 1.57 0.29 1621 5.10 1.48 0.29 1692
25 18 4.90 3.38 0.69 1382 4.50 3.11 0.69 1466 4.15 2.86 0.69 1523
25 20 5.15 2.94 0.57 1438 4.80 2.74 0.57 1509 4.45 2.54 0.57 1593
25 22 5.45 2.45 0.45 1495 5.10 2.30 0.45 1579 4.75 2.14 0.45 1636
25 24 5.75 1.90 0.33 1551 5.40 1.78 0.33 1621 5.10 1.68 0.33 1692
26 18 4.90 3.58 0.73 1382 4.50 3.29 0.73 1466 4.15 3.03 0.73 1523
26 20 5.15 3.14 0.61 1438 4.80 2.93 0.61 1509 4.45 2.71 0.61 1593
26 22 5.45 2.67 0.49 1495 5.10 2.50 0.49 1579 4.75 2.33 0.49 1636
26 24 5.75 2.13 0.37 1551 5.40 2.00 0.37 1621 5.10 1.89 0.37 1692
26 26 6.05 1.51 0.25 1607 5.70 1.43 0.25 1678 5.35 1.34 0.25 1748
27 18 4.90 3.77 0.77 1382 4.50 3.47 0.77 1466 4.15 3.20 0.77 1523
27 20 5.15 3.35 0.65 1438 4.80 3.12 0.65 1509 4.45 2.89 0.65 1593
27 22 5.45 2.89 0.53 1495 5.10 2.70 0.53 1579 4.75 2.52 0.53 1636
27 24 5.75 2.36 0.41 1551 5.40 2.21 0.41 1621 5.10 2.09 0.41 1692
27 26 6.05 1.75 0.29 1607 5.70 1.65 0.29 1678 5.35 1.55 0.29 1748
28 18 4.90 3.97 0.81 1382 4.50 3.65 0.81 1466 4.15 3.36 0.81 1523
28 20 5.15 3.55 0.69 1438 4.80 3.31 0.69 1509 4.45 3.07 0.69 1593
28 22 5.45 3.11 0.57 1495 5.10 2.91 0.57 1579 4.75 2.71 0.57 1636
28 24 5.75 2.59 0.45 1551 5.40 2.43 0.45 1621 5.10 2.30 0.45 1692
28 26 6.05 2.00 0.33 1607 5.70 1.88 0.33 1678 5.35 1.77 0.33 1748
29 18 4.90 4.17 0.85 1382 4.50 3.83 0.85 1466 4.15 3.53 0.85 1523
29 20 5.15 3.76 0.73 1438 4.80 3.50 0.73 1509 4.45 3.25 0.73 1593
29 22 5.45 3.32 0.61 1495 5.10 3.11 0.61 1579 4.75 2.90 0.61 1636
29 24 5.75 2.82 0.49 1551 5.40 2.65 0.49 1621 5.10 2.50 0.49 1692
29 26 6.05 2.24 0.37 1607 5.70 2.11 0.37 1678 5.35 1.98 0.37 1748
30 18 4.90 4.36 0.89 1382 4.50 4.01 0.89 1466 4.15 3.69 0.89 1523
30 20 5.15 3.97 0.77 1438 4.80 3.70 0.77 1509 4.45 3.43 0.77 1593
30 22 5.45 3.54 0.65 1495 5.10 3.32 0.65 1579 4.75 3.09 0.65 1636
30 24 5.75 3.05 0.53 1551 5.40 2.86 0.53 1621 5.10 2.70 0.53 1692
30 26 6.05 2.48 0.41 1607 5.70 2.34 0.41 1678 5.35 2.19 0.41 1748
31 18 4.90 4.56 0.93 1382 4.50 4.19 0.93 1466 4.15 3.86 0.93 1523
31 20 5.15 4.17 0.81 1438 4.80 3.89 0.81 1509 4.45 3.60 0.81 1593
31 22 5.45 3.76 0.69 1495 5.10 3.52 0.69 1579 4.75 3.28 0.69 1636
31 24 5.75 3.28 0.57 1551 5.40 3.08 0.57 1621 5.10 2.91 0.57 1692
31 26 6.05 2.72 0.45 1607 5.70 2.57 0.45 1678 5.35 2.41 0.45 1748
32 18 4.90 4.75 0.97 1382 4.50 4.37 0.97 1466 4.15 4.03 0.97 1523
32 20 5.15 4.38 0.85 1438 4.80 4.08 0.85 1509 4.45 3.78 0.85 1593
32 22 5.45 3.98 0.73 1495 5.10 3.72 0.73 1579 4.75 3.47 0.73 1636
32 24 5.75 3.51 0.61 1551 5.40 3.29 0.61 1621 5.10 3.11 0.61 1692
32 26 6.05 2.96 0.49 1607 5.70 2.79 0.49 1678 5.35 2.62 0.49 1748
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
OBH667B
Page 22
22
PERFORMANCE DATA HEAT operation at Rated frequency
MUFZ-KJ25VE
CAPACITY: 3.4 kW INPUT: 770 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.14 501 2.58 601 3.03 678 3.47 732 3.91 778 4.32 801 4.76 816
21 2.04 539 2.45 639 2.89 708 3.30 762 3.74 801 4.15 824 4.57 855
26 1.84 578 2.28 678 2.69 747 3.13 801 3.57 839 3.98 862 4.42 886
MUFZ-KJ35VE
CAPACITY: 4.3 kW INPUT: 1100 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 2.71 715 3.27 858 3.83 968 4.39 1045 4.95 1111 5.46 1144 6.02 1166
21 2.58 770 3.10 913 3.66 1012 4.17 1089 4.73 1144 5.25 1177 5.78 1221
26 2.32 825 2.88 968 3.40 1067 3.96 1144 4.52 1199 5.03 1232 5.59 1265
NOTE: Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
MUFZ-KJ50VE
CAPACITY: 6.0 kW INPUT: 1610 W
INDOOR
DB (°C)
OUTDOOR WB (°C)
-10 -5 0 5 10 15 20
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
15 3.78 1047 4.56 1256 5.34 1417 6.12 1530 6.90 1626 7.62 1674 8.40 1707
21 3.60 1127 4.32 1336 5.10 1481 5.82 1594 6.60 1674 7.32 1723 8.07 1787
26 3.24 1208 4.02 1417 4.74 1562 5.52 1674 6.30 1755 7.02 1803 7.80 1852
NOTE: Q : Total capacity (kW) INPUT : Total power input (W) DB: Dry-bulb temperature WB: Wet-bulb temperature
OBH667B
Page 23
23
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
9-2. R.V. COIL CONTROL
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan motor
Compressor
5 seconds 15 seconds
ON OFF
Compressor
Outdoor fan motor
R.V.coil
ON OFF
ON OFF
<COOL>
5 seconds
<HEAT>
5 seconds
9-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor. [ON] The fan motor turns ON 5 seconds before the compressor starts up. [OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
9-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
Indoor fan
motor
Defrost
heater
Discharge temperature thermistor
Protection
○○
Indoor coil temperature thermistor
Cooling: Coil frost prevention
Heating: High pressure protec­tion
○○
Defrost thermistor Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Heating: Defrosting (Heater)
Outdoor heat exchanger tem­perature thermistor
Cooling: Low ambient tempera­ture operation
○○○
Cooling: High pressure protec­tion
○○○
ACTUATOR CONTROL
9
OBH667B
Page 24
24
SERVICE FUNCTIONS
10
10-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature
<JS> To change the defrost finish temperature, cut/solder the JS wire of the outdoor inverter P.C. board. (Refer to 11-6-1.)
Jumper wire Defrost nish temperature (°C)
JS
Soldered (Initial setting) 5
None (Cut) 10
10-2. PRE-HEAT CONTROL SETTING
PRE-HEAT CONTROL MUFZ-KJ25/35
When moisture gets into the refrigerant cycle, it may interfere the start-up of the compressor at low outside temperature. The pre-heat control prevents this interference. The pre-heat control turns ON when the discharge temperature thermis­tor is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 50 W)
MUFZ-KJ50
Prolonged low load operation, in which the thermostat is OFF for a long time, at low outside temperature (0°C or less) may cause the following troubles. To prevent those troubles, activate the pre-heat control.
1) If moisture gets into the refrigerant cycle and freezes, it may interfer the start-up of the compressor.
2) If liquid refrigerant collects in the compressor, a failure in the compressor may occur.
The pre-heat control turns ON when the compressor temperature is 20°C or below. When the pre-heat control turns ON, the compressor is energized. (About 70 W)
Pre-heat control setting
<JK> ON: To activate the pre-heat control, cut JK wire of the inverter P.C. board. OFF: To deactivate the pre-heat control, solder JK wire of the inverter P.C. board. (Refer to 11-6.1)
NOTE: When the inverter P.C. board is replaced, check the jumper wires, and cut/solder them if necessary.
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
OBH667B
Page 25
25
11-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.
5) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
TROUBLESHOOTING
11
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing on and off before starting serv-
ice work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) Refer to 11-2 and 11-3.
Lead wiring
Housing point
<Incorrect>
<Correct>
MUFZ-KJ25VE MUFZ-KJ35VE MUFZ-KJ50VE
OBH667B
Page 26
26
Outline of the function This air conditioner can memorize the abnormal condition which has occurred once. Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details can be recalled.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks: Either indoor or outdoor unit is abnormal. Beep is emit-
ted at the same timing as the blinking of the left lamp of the OPERATION INDICATOR lamp. 2
Indoor unit is normal. But the outdoor unit might be abnormal because there are some abnor­malities that cannot be recalled with this way. Check if the outdoor unit is abnormal according to the detailed outdoor unit failure mode recall function. (Refer to 11-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply. <Preparation of the remote controller>
While pressing OPERATION SELECT (MODE) button and TEMP
button on the
remote controller at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indicators
on the LCD screen shown in the right fi gure are all displayed. Then release the but- tons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.
1
Judgment of indoor/outdoor abnormality
Before blinking, does the left lamp of the OPERATION INDI­CATOR lamp stay ON for 3 seconds? Stays ON for 3 seconds (without beep): The outdoor unit is abnormal.
The indoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the indoor unit failure mode table. (Refer to indoor unit service manual.) Make sure to check at least two consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 4 Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes (Blinks)
No (OFF)
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
Repeated cycle
Beeps
AMPM AM PM
NOTE: It takes up to 1 minute to indicate the outdoor unit abnormality. Even if the OPERATION INDICATOR lamp is not lighting, keep checking
at least 1 minute or longer.
4 The information regarding whether the connected
outdoor unit is a low-standby-power model or a non-low­standby-power model will also be initialized.
(Default= compatible with a low-standby-power model)
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table. (Refer to 11-2.3) Make sure to check at least two consecutive blinking cycles.
3
OBH667B
Page 27
27
2. Flow chart of the detailed outdoor unit failure mode recall function
2.Blinking pattern when outdoor unit is abnormal:
ON
OFF
No beep
Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5­second interval
No beep Beeps
Repeated cycle
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Does the left lamp of the OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds? Blinks:
The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp of the OPERATION INDICATOR lamp. 2
Yes (Blinks
)
No (OFF)
The outdoor unit might be abnormal. Check if the outdoor unit is abnormal according to the following procedures.
Operational procedure
Make sure that the remote controller is set to the failure mode recall function.
With the remote controller headed towards the indoor unit, press TEMP
button to adjust the set temperature to 25°C. 1
1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
The outdoor unit is abnormal. Check the blinking pattern, and identify the abnormal point by referring to the outdoor unit failure mode table (11-2.3.). Make sure to check at least two consecutive blinking cycles.
2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures. Turn OFF the power supply and turn it ON again. Press RESET button of the remote controller.
Repair the failure parts.
The outdoor unit is normal.
Release the failure mode recall function accord­ing to the left mentioned procedure.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" (11-2.1.).
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with
the remote controller headed towards the indoor unit. Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 3 Release the failure mode recall function according to "Releasing the failure mode recall function" men-
tioned above.
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
3
The information regarding whether the
connected outdoor unit is a low-standby-
power model or a non-low-standby-power model will also be initialized.
(Default= compatible with a low-standby-
power model)
NOTE: It takes up to 1 minute to indicate the outdoor unit abnormality. Even if the OPERATION INDICATOR lamp is not lighting, keep
checking at least 1 minute or longer.
OBH667B
Page 28
28
3. Outdoor unit failure mode table
Left lamp
of the
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit failure mode
recall function
OFF None (Normal)
—— —
1-time fl ash
2.5 seconds OFF
Indoor/outdoor communication, receiving error
Any signals from the inverter P.C. board cannot be received normally for 3 minutes.
•Refer to 11-5.
How to check miswiring and serial signal error.
○○
Indoor/outdoor communication, receiving error
Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.
•Refer to 11-5.
How to check miswiring and serial signal error.
2-time fl ash
2.5 seconds OFF
Outdoor power system
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect the connectors. Refer to 11-5. "How to check inverter/ compressor". Check the stop valve.
○○
3-time fl ash
2.5 seconds OFF
Discharge temperature thermistor
1-time fl ash every
2.5 seconds
Thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors". Defective the outdoor thermistors can be identifi ed by checking the blinking pattern of LED.
○○
Defrost thermistor
Fin temperature thermistor 3-time fl ash
2.5 seconds OFF
P.C. board temperature thermistor
4-time fl ash
2.5 seconds OFF
Ambient temperature thermistor
2-time fl ash
2.5 seconds OFF
Outdoor heat exchanger temperature thermistor
4-time fl ash
2.5 seconds OFF
Overcurrent 11-time fl ash
2.5 seconds OFF
Large current fl ows into power module (IC700) (KJ25/35)/ IGBT module (IC700) (KJ50).
Reconnect the compressor connector. Refer to 11-5. "How to check inverter/ compressor". Check the stop valve.
Compressor synchronous abnormality (Compressor start-up failure protection)
12-time fl ash
2.5 seconds OFF
Waveform of compressor current is distorted.
Reconnect the compressor connector. Refer to 11-5. "How to check inverter/ compressor".
• —
5-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check the refrigerant circuit and the refrigerant amount. Refer to 11-5. "Check of LEV".
6-time fl ash
2.5 seconds OFF
High pressure
Temperature indoor coil thermistor exceeds 70°C in HEAT mode. Temperature defrost thermistor exceeds 70°C in COOL mode.
Check the refrigerant circuit and the refrigerant amount. Check the stop valve.
7-time fl ash
2.5 seconds OFF
Fin temperature/ P.C. board temperature
7-time fl ash
2.5 seconds OFF
Temperature of fi n temperature thermistor on the inverter P.C. board exceeds 75 ~ 86°C(KJ25/35)/ 75 ~ 80°C (KJ50), or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C (KJ25/35)/ 70 ~ 75°C (KJ50).
Check around the outdoor unit. Check the outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
8-time fl ash
2.5 seconds OFF
Outdoor fan motor
Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan start-up.
Refer to 11-5.
"Check of outdoor fan motor". Refer to 11-5. "Check of inverter P.C. board".
9-time fl ash
2.5 seconds OFF
Nonvolatile memory data 5-time fl ash
2.5 seconds OFF
Nonvolatile memory data cannot be read properly.
Replace the inverter P.C. board.
○○
Power module (IC700) (KJ25/35) IGBT module (IC700) (KJ50).
6-time fl ash
2.5 seconds OFF
The interface short circuit occurs in the output of the power module (IC700)(KJ25/35)/ IGBT module (IC700) (KJ50). The compressor winding shorts circuit.
Refer to 11-5. "How to check inverter/ compressor".
10-time fl ash
2.5 seconds OFF
Discharge temperature
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check the refrigerant circuit and the refrigerant amount.
11-time fl ash
2.5 seconds OFF
Bus-bar voltage (DC) 8-time fl ash
2.5 seconds OFF
Bus-bar voltage of inverter cannot be detected normally.
Refer to 11-5. "How to check inverter/ compressor".
Each phase current of compressor
9-time fl ash
2.5 seconds OFF
Each phase current of compressor cannot be detected normally.
14-time fl ash
2.5 seconds OFF
Stop valve (Closed valve) 14-time fl ash
2.5 seconds OFF
Closed valve is detected by compressor current.
Check the stop valve.
○○
4-way valve/ Pipe temperature
16-time fl ash
2.5 seconds OFF
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Check the 4-way valve. Replace the inverter P.C. board.
NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (11-3.).
OBH667B
Page 29
29
11-3. TROUBLESHOOTING CHECK TABLE
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
1
Outdoor unit does not op­erate.
1-time fl ash every
2.5 seconds
Outdoor power sys­tem
Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.
Reconnect the connector of the compressor. Refer to 11-5. "How to check in­verter/compressor". Check the stop valve.
2
Outdoor thermistors Discharge temperature thermistor, fi n temperature thermistor,
defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera­ture thermistor shorts or opens during compressor running.
Refer to 11-5. "Check of outdoor thermistors".
3
Outdoor control sys­tem
Nonvolatile memory data cannot be read properly.
(POWER lamp of the indoor unit lights up or fl ashes 7-time.)
Replace the inverter P.C. board.
4
6-time fl ash
2.5 seconds OFF
Serial signal The communication fails between the indoor and outdoor unit
for 3 minutes.
Check connection between the in­verter P.C. board and the relay P.C. board. (KJ50) Refer to 11-5. "How to check miswiring and serial signal error.
5
11-time fl ash
2.5 seconds OFF
Stop valve/ Closed valve
Closed valve is detected by compressor current.
Check the stop valve.
6
14-time fl ash
2.5 seconds OFF
Outdoor unit (Other abnormality)
Outdoor unit is defective.
Refer to 11-2.2. "Flow chart of the detailed outdoor unit failure mode recall function".
7
16-time fl ash
2.5 seconds OFF
4-way valve/
Pipe temperature
The 4-way valve does not work properly. The indoor coil thermistor detects an abnormal temperature.
Refer to 11-5. "Check of R.V. coil". Replace the inverter P.C. board.
8
'Outdoor unit stops and restarts 3 minutes later' is repeated.
2-time fl ash
2.5 seconds OFF
Overcurrent protec­tion
Large current fl ows into power module (IC700)(KJ25/35)/ IGBT module (IC700) (KJ50).
Reconnect the connector of the compressor. Refer to 11-5. "How to check in­verter/compressor". Check the stop valve.
9
3-time fl ash
2.5 seconds OFF
Discharge tempera­ture overheat pro­tection
Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.
Check the refrigerant circuit and the refrigerant amount. Refer to 11-5. "Check of LEV".
10
4-time fl ash
2.5 seconds OFF
Fin temperature /P.C. board tem­perature thermistor overheat protection
Temperature of fi n temperature thermistor on the heat sink ex- ceeds 75 ~ 86°C (KJ25/35)/75 ~ 80°C(KJ50) or temperature of P.C. board temperature thermistor on the inverter P.C.board exceeds 72 ~ 85°C(KJ25/35)/70 ~ 75°C(KJ50).
Check around the outdoor unit. Check the outdoor unit air passage. Refer to 11-5. "Check of outdoor fan motor".
11
5-time fl ash
2.5 seconds OFF
High pressure pro­tection
Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost thermistor exceeds 70°C in COOL mode.
Check the refrigerant circuit and the refrigerant amount. Check the stop valve.
12
8-time fl ash
2.5 seconds OFF
Compressor syn­chronous abnormal­ity
The waveform of compressor current is distorted.
Reconnect the connector of the compressor. Refer to 11-5. "How to check in­verter/compressor".
13
10-time fl ash
2.5 seconds OFF
Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds
after outdoor fan start-up.
Refer to 11-5.
"Check of outdoor fan motor. Refer to 11-5. "Check of inverter P.C. board.
14
12-time fl ash
2.5 seconds OFF
Each phase current of compressor
Each phase current of compressor cannot be detected nor­mally.
Refer to 11-5. "How to check in­verter/compressor".
15
13-time fl ash
2.5 seconds OFF
Bus-bar voltage (DC)
Bus-bar voltage of inverter cannot be detected normally. It occurs with following case.
Instantaneous power voltage drop. (Short time power failure) (KJ50) Refer to 11-5.
"Check of power
supply". (KJ50) Refer to 11-5. "How to check in­verter/compressor".
16
Outdoor unit operates.
1-time fl ash
2.5 seconds OFF
Frequency drop by current protection
KJ25/35 When the input current exceeds approximately
10A (KJ25)/10.5A (KJ35), compressor frequency lowers.
The unit is normal, but check the following. Check if the indoor fi lters are clogged. Check if the refrigerant is short. Check if the indoor/outdoor unit air circulation is short cycled.
KJ50 Current from power outlet is nearing breaker ca-
pacity.
17
3-time fl ash
2.5 seconds OFF
Frequency drop by high pressure pro­tection
Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.
Frequency drop by defrosting in COOL mode
Indoor coil thermistor reads 8°C or less in COOL mode, com­pressor frequency lowers.
18
4-time fl ash
2.5 seconds OFF
Frequency drop by discharge tempera­ture protection
Temperature of discharge temperature thermistor exceeds 111°C, compressor frequency lowers.
Check the refrigerant circuit and the refrigerant amount. Refer to 11-5.
"Check of LEV". Refer to 11-5. "Check of outdoor thermistors".
19
5-time fl ash
2.5 seconds OFF
Outside temperature thermistor protec­tion
When the outside temperature thermistor shorts or opens, protective operation without that thermistor is performed.
Refer to 11-5. Check of outdoor thermistors.
OBH667B
Page 30
30
No. Symptom LED indication
Abnormal point/
Condition
Condition Remedy
20
Outdoor unit operates.
7-time fl ash
2.5 seconds OFF
Low discharge tem­perature protection
Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.
Refer to 11-5. "Check of LEV". Check the refrigerant circuit and the refrigerant amount.
21
8-time fl ash
2.5 seconds OFF
MUFZ-KJ25/35
PAM protection PAM: Pulse Ampli­tude Modulation
The overcurrent fl ows into PFC (Power factor correction : IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.
This is not malfunction. PAM pro­tection will be activated in the fol­lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
MUFZ-KJ50
Zero cross detecting circuit
Zero cross signal cannot be detected. It occurs with following cases.
1 Instantaneous power voltage
drop. (Short time power failure)
2 Distortion of primary voltage Refer to 11-5. "Check of power supply".
22
9-time fl ash
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
Check if the connector of the com­pressor is correctly connected. Refer to 11-5. "How to check inverter/compressor".
NOTE: 1. The location of LED is illustrated at the right fi gure. Refer to 11-6.1.
2. LED is lighted during normal operation.
The fl ashing frequency shows the number of times the LED blinks after every 2.5-second OFF. (Example) When the fl ashing frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON LED
Flashing
MUFZ-KJ50VE
LED
Flashing
MUFZ-KJ25/35VE
Inverter P.C. board
OBH667B
Page 31
31
11-4. TROUBLE CRITERION OF MAIN PARTS
MUFZ-KJ25VE MUFZ-KJ35VE
MUFZ-KJ50VE
Part name Check method and criterion Figure
Defrost thermistor (RT61)
Fin temperature thermistor (RT64)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger temperature thermistor (RT68)
Measure the resistance with a tester.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Discharge temperature thermistor (RT62)
Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.
Refer to 11-6. “Test point diagram and voltage”, 1. “Inverter P.C. board”, for the chart of thermistor.
Compressor
Measure the resistance between terminals using a tester. (Temperature: -10 ~ 40°C)
Normal (Ω)
MUFZ-KJ25/35VE MUFZ-KJ50VE
U-V U-W V-W
1.66 ~ 2.26 0.87 ~ 1.18
Outdoor fan motor
Measure the resistance between lead wires using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUFZ-KJ25/35VE MUFZ-KJ50VE
RED – BLK
BLK – WHT
WHT – RED
12 ~ 16 12 ~ 17
R. V. coil (21S4)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Normal (kΩ)
MUFZ-KJ25/35VE MUFZ-KJ50VE
1.41 ~ 2.00 1.19 ~ 1.78
Expansion valve coil (LEV)
Measure the resistance using a tester. (Temperature: -10 ~ 40°C)
Color of lead wire
Normal (Ω)
MUFZ-KJ25/35/50VE
RED – ORN
37 ~ 54
RED – WHT
RED – BLU
RED – YLW
RED
(+12V)
YLW
BLU
WHT
ORN
LEV
W
U
V
WHT
RED BLK
W
U
V
WHT
RED BLK
OBH667B
Page 32
32
11-5. TROUBLESHOOTING FLOW
A How to check inverter/compressor
Refer to 11-5. “Check of compressor operation time”. Does the compressor operate continuously?
Refer to 11-5. “Check of compressor start failure”.
OK.
No
Yes
Refer to 11-5. “Check of compressor winding”. Is the compressor normal?
Replace the compressor.
No
Yes
B Check of open phase
C Check of compressor
With the connector between the compressor and the power module (IC700)(MUFZ-KJ25/35)/ IGBT module (IC700)(MUFZ- KJ50) disconnected, activate the inverter and check if the inverter is normal by measuring the voltage balance between the
terminals.
Output voltage is 50 - 130 V. (The voltage may differ according to the tester.)
<< Operation method>> Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERA-
TION: Refer to 8-3.) <<Measurement point>> At 3 points BLK (U)-WHT (V) BLK (U)-RED (W) WHT(V)-RED (W)
NOTE: 1. Output voltage varies according to power supply voltage.
2. Measure the voltage by analog type tester.
3. During this check, LED of the inverter P.C. board fl ashes 9 times. (Refer to 11-6.1.)
Measure AC voltage between the lead wires at 3 points.
Are the voltages balanced?
Disconnect the connector between the compressor and the power module (IC700)(MUFZ-KJ25/35)/ IGBT module (IC700)(MUFZ-KJ50).
Replace the inverter P.C. board.
Check the voltage between terminals.
Check the compressor.
See 11-5. “Check of compressor”.
No
Yes
See 11-5. “Check of open phase”.
OBH667B
Page 33
33
F Check of compressor start failure
D Check of compressor winding
E Check of compressor operation time
Disconnect the connector between the compressor and the power module (IC700)(MUFZ-KJ25/35)/ IGBT module (IC700)(MUFZ-KJ50), and measure the resistance between the compressor terminals.
<<Measurement point>> At 3 points BLK-WHT BLK-RED WHT-RED <<Judgement>> Refer to 11-4. 0 [Ω] ················Abnormal [short] Infinite [Ω] ·······Abnormal [open] NOTE: Be sure to zero the ohmmeter before measurement.
Measure the resistance between the lead wires at 3 points.
1 Heat the compressor with a drier for about 20 minutes. Do not recover refrigerant gas while heating.
Heating part
Connect the compressor and activate the inverter. Then measure
the time until the inverter stops due to over current. <<Operation method>> Start heating or cooling operation by pressing EMERGENCY OPERATION switch on the indoor unit. (TEST RUN OPERATION: Refer to 8-3.) <<Measurement>> Measure the time from the start of compressor to the stop of compressor due to overcurrent.
Compressor starts
Abnormal (IC700 failure) (Compressor winding short)
Abnormal (Compressor lock out) (Starting defect)
Abnormal (Poor contact) (Inverter P.C. board defect) (Disconnected connector)
Abnormal (Refrigerant circuit defect) (Closed valve)
Normal
0 second
1 second
2 seconds
10 seconds
10 minutes
<<Judgement>>
After the compressor is heated with a drier, does the compressor start? 1
Replace the compressor.
Compressor start failure. Activate pre-heat control. (Refer to 10-2. "PRE-HEAT CONTROL SETTING")
No
Yes
Does the compressor run for 10 seconds or more after it starts?
Check the refrigerant circuit. Check the stop valve.
Yes
No
Confi rm that ~ is normal.
•Electrical circuit check . Contact of the compressor connector . Output voltage of inverter P.C. board and balance of them (See 11-5. ) . Direct current voltage between DB61(+) and (-)(MUFZ-KJ25/35)/ JP715(+)
and JP30(-)(MUFZ-KJ50)on the inverter P.C. board
. Voltage between outdoor terminal block S1-S2
OBH667B
Page 34
34
G Check of outdoor thermistors
Replace the thermistor except RT64. When RT64 is abnormal, replace the inverter P.C. board.
Replace the inverter P.C. board.
No
No
Is the resistance of thermistor normal? (Refer to 11-6.1.)
Reconnect the connector of thermistor. Turn ON the power supply and press EMERGENCY OPERATION switch.
Does the unit operate for 10 minutes or more without showing thermistor abnormality?
OK. (Cause is poor contact.)
Yes
Yes
Disconnect the connector of thermistor in the Inverter P.C. board (see below table), and measure the resistance of thermistor.
MUFZ-KJ25/35
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN641 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN642 pin1 and pin2 Ambient temperature RT65 Between CN643 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN644 pin1 and pin3
MUFZ-KJ50
Thermistor Symbol Connector, Pin No. Board
Defrost RT61 Between CN671 pin1 and pin2
Inverter P.C. board
Discharge temperature RT62 Between CN671 pin3 and pin4 Fin temperature RT64 Between CN673 pin1 and pin2 Ambient temperature RT65 Between CN672 pin1 and pin2 Outdoor heat exchanger temperature RT68 Between CN671 pin5 and pin6
OBH667B
Page 35
35
H Check of R.V. coil
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN721 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the power module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 11-4. In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN602 is connected.
Is there 230 VAC between CN602 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
No
Yes
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates COOL mode even if it is set to HEAT mode.
Is there 230 VAC between CN602 and
on the inverter P.C. board 3 minutes
after the power supply is turned ON?
Yes
No
Replace the inverter P.C. board.
Replace the 4-way valve.
Unit operates HEAT mode even if it is set to COOL mode.
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch twice (HEAT mode).
Disconnect connector between the compressor and the IGBT module (IC700). Turn ON the power supply and press EMERGENCY OPERATION switch once (COOL mode).
MUFZ-KJ25/35
MUFZ-KJ50
OBH667B
Page 36
36
I Check of outdoor fan motor
Is the resistance between each ter­minal of outdoor fan motor normal? (Refer to 11-4.)
Disconnect CN932 from the inverter P.C. board, and turn on the power supply.
Rotate the outdoor fan motor manually and measure the voltage of CN931. Between 1(+) and 5(-) Between 2(+) and 5(-) Between 3(+) and 5(-)
Does the voltage between each terminal become 5 and 0 VDC repeatedly?
Does the outdoor fan motor rotate smoothly?
Replace the outdoor fan motor.
Replace the inverter P.C. board.
Yes
Yes
No
(Fixed to either 5 or 0 VDC)
No
No
Yes
Disconnect the connectors CN931 and CN932 from the inverter P.C. board. Check the connection between the connector CN931 and CN932.
OBH667B
Page 37
37
J Check of power supply
Is there voltage 230 VAC between the indoor terminal block S1 and S2?
No
Yes
Replace the indoor electronic control P.C. board.
Rectify indoor/outdoor connecting wire.
Yes
If light up, OK. If fl ash, refer to 11-3.
Does POWER lamp on the indoor unit light up?
Does LED on the inverter P.C. board light up or fl ash? (Refer to 11-6.1.)
No
Replace the inverter P.C. board.
Is there bus-bar voltage 260 - 370 VDC between DB61 (+) and DB61 (–) (MUFZ-KJ25/35)/325 - 370 VDC between JP715 (+) and JP30 (–) (MUFZ-KJ50) on the inverter P.C. board? (Refer to 11-6.1.)
No
Check the electric parts in main circuit.
Yes
Yes
No
Disconnect the connector between the compressor and the power module (IC700) (MUFZ-KJ25/35)/IGBT module (IC700) (MUFZ-KJ50). Turn ON power supply and press EMERGENCY OPERATION switch.
Inverter P.C. board (Solder side)
DB61
260 - 370 VDC
MUFZ-KJ25/35
325 -370 VDC
JP30
JP715
MUFZ-KJ50
OBH667B
Page 38
38
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit. 1
Expansion valve operates in full-opening direction.
OK
NOTE: After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn it ON again.
2. Press RESET button on the remote controller.
1. Regardless of normal or abnormal condition, a short beep is emitted once the signal is received.
Measure each voltage between connector pins of CN724 on the inverter P.C. board.
1. Pin (-) — Pin (+)
2. Pin (-) — Pin (+)
3. Pin (-) — Pin (+)
4. Pin (-) — Pin (+) Is there about 3 - 5 VAC between each?
NOTE: Measure the voltage by an analog
tester.
Properly fi x the LEV coil to the expansion valve.
Replace the inverter P.C. board.
Replace the LEV coil.
Replace the expansion valve.
Is LEV coil properly fi xed to the expansion valve?
Does the resistance of LEV coil have the characteristics? (Refer to 11-4.)
Do you hear the expansion valve "click, click·······"? Do you feel the expansion valve vibrate on touching it ?
Turn ON the power supply. <Preparation of the remote controller>
While pressing both OPERATION SELECT (MODE) button and TEMP button on the remote controller at the same time, press RESET button. First, release RESET button.
Hold down the other two buttons for another 3 sec-
onds. Make sure that the indicators on the LCD screen shown in the right fi gure are all displayed. Then re- lease the buttons.
Yes
No
No
Yes
No
Yes
No
Yes
K Check of LEV (Expansion valve)
AMPM AM PM
OBH667B
Page 39
39
Check the outdoor fan motor. (Refer to 11-5. .)
Is the fuse (F901) blown on the in­verter P.C. board?
Check the connection of the connectors (CN931, CN932) of the outdoor fan motor. If the connection is poor, make it correct.
Operate the outdoor unit by starting EMERGENCY OPERATION.
Check the LED indication on the in­verter P.C. board. Does the LED fl ash 10 times?
Replace the inverter P.C. board.
Check the corresponding parts following LED indication. (Refer to 11-3.)
Yes
No
Yes (10-time fl ash)
No
L Check of inverter P.C. board
OBH667B
Page 40
40
How to check miswiring and serial signal error
M
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn it ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit.
No
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR lamp on the indoor unit light up? <Confi rmation of the power supply to the indoor unit>
Yes
Correct the wiring.
Is the serial signal error indicated 6 minutes later?
Yes
Is there any miswiring, poor contact or wire dis­connection of the indoor/outdoor connecting wire?
No
Yes
No
A
Is there rated voltage between outdoor terminal block S1 and S2?
Yes
Check for miswiring, broken wires, and loose wire connection between the power supply and outdoor terminal block S1 and between the power supply and outdoor terminal block S2.
Wait for 2 or more minutes after the power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
No
Turn the power supply ON.
When the emergency operation starts, does the rated voltage occur for 2 seconds between indoor terminal block S2 and S3?
Yes
Replace the indoor electronic control P.C. board.
Does the left lamp of the OPERA­TION INDICATOR lamp on the indoor unit blink continuously 6 minutes af­ter the emergency operation starts?
No
Does the outdoor LED light up?
Yes
Does the outdoor LED blink 6 times?
Yes
Confi rm that the thermostat is OFF and wiring is not loose.
No
Does DC (6V or more) occur between indoor terminal block S2 and S3?
Yes
Replace the outdoor inverter P.C. board. 1
No
Turn the power supply OFF. Replace the indoor electronic control P.C. board.
1. Electric charge may remain immediately after the power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board. 1
Yes
No
No
B
MUFZ-KJ25/35
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 11-2.1 to clear the error history. When the error history is being cleared, the connection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
MFZ-KJ25/35VE-
E2,ER2
OBH667B
Page 41
41
MUFZ-KJ50
Turn the power supply OFF.
Is there rated voltage in the power supply?
Yes
No
Check for incorrect indoor-outdoor connecting wiring.
Check the power supply.
Turn OFF inverter-controlled lighting equipment. Turn OFF the power supply and then turn ON again. Press EMERGENCY OPERATION switch.
A
Is serial signal error indicated 6 minutes later?
B
Yes
Reinstall either the unit or the light away from each other. Attach a fi lter on remote control receiving section of the indoor unit.
No
NOTE: Refer to the indoor unit service manual.
Is there rated voltage between outdoor terminal block S1 and S2?
Check for miswiring, broken wires, and loose wire connection between the power supply and outdoor terminal block S1 and between the power supply and
outdoor terminal block S2. Wait for 2 or more minutes after the power supply is turned on. Touch S2 and S3 with tester probes and start the emergency operation.
When the emergency operation starts, does the rated voltage occur for 2 sec­onds between indoor terminal block S2 and S3?
No
Yes
Replace the indoor electronic control P.C. board.
Does the left lamp of the OPERA­TION INDICATOR lamp on the indoor unit blink continuously 6 minutes after the emergency operation starts?
No
Does DC (10 V or more) occur between L68A and L68B on the outdoor relay P.C. board?
Yes
Does the outdoor LED blink 6 times?
Yes
Replace the outdoor relay P.C. board.
1
No
Does DC (more than 0 V) occur between indoor terminal block S2 and S3?
Yes
Replace the outdoor inverter P.C. board.
1
No
Turn the power supply OFF.
Start the emergency operation.
No
Repair has been completed.
Replace the outdoor inverter P.C. board and the outdoor relay P.C. board. 1
1. Electric charge may remain immediately after the power supply is turned OFF. Perform the procedure after 3 minutes.
Replace the outdoor inverter P.C. board and the outdoor relay P.C. board. 1
Turn the power supply ON.
Does the left lamp of the OPERA­TION INDICATOR lamp on the indoor unit blink continuously 6 minutes after the emergency operation starts?
Yes
No
Replace the indoor electronic control P.C. board.
Yes
Replace the outdoor inverter P.C. board and the outdoor relay P.C. board. 1
Yes
A
B Turn the power supply ON.
No
Was the indoor unit ever connected to the Multi (MXZ) series and operated (turned on)?
The connection information to the Multi series is stored in the indoor unit. Refer to “Deleting the memorized abnormal condition” described in 11-2.1 to clear the error history. When the error history is being cleared, the connection information also will be initialized. The indoor unit will be compatible with a low-standby-power model after initialization.
OK
Yes
No
OBH667B
Page 42
42
N Electromagnetic noise enters into TV sets or radios
Yes
Is the unit earthed?
No
Earth the unit.
Yes
Is the distance between the antennas and the indoor unit within 3 m, or is the distance between the antennas and the outdoor unit within 3 m?
No
Extend the distance between the antennas and the indoor unit, and/or the antennas and the outdoor unit.
Is the distance between the TV sets or radios and the indoor unit within 1 m, or is the distance between the TV sets or radios and the outdoor unit within 3 m?
Yes
Extend the distance between the TV sets and/or radios and the indoor unit, or the TV sets or radios and the outdoor unit.
Are the antennas damaged? Is the coaxial cable damaged? Is there any poor contact in the anten­na wiring?
Yes
No
No
Replace or repair the antenna. Replace or repair the coaxial cable.
Is the indoor/outdoor connecting wire of the air conditioner and the wiring of the antennas close?
Yes
Extend the distance between the indoor/outdoor connecting wire of the air conditioner and the wir­ing of the antennas.
No
Even if all of the above conditions are fulfi lled, the electromagnetic noise may enter, depending on the electric fi eld strength or the installation condition (combination of specifi c conditions such as antennas or wiring). Check the following before asking for service.
1. Devices affected by the electromagnetic noise TV sets, radios (FM/AM broadcast, shortwave)
2. Channel, frequency, broadcast station affected by the electromagnetic noise
3. Channel, frequency, broadcast station unaffected by the electromagnetic noise
4. Layout of: indoor/outdoor unit of the air conditioner, indoor/outdoor wiring, earth wire, antennas, wiring from antennas, receiver
5. Electric fi eld intensity of the broadcast station affected by the electromagnetic noise
6. Presence or absence of amplifi er such as booster
7. Operation condition of air conditioner when the electromagnetic noise enters in
1) Turn OFF the power supply once, and then turn ON the power supply. In this situation, check for the electromagnetic noise.
2) Within 3 minutes after turning ON the power supply, press OPERATE/STOP (ON/OFF) button on the remote controller for power ON, and check for the electromagnetic noise.
3) After a short time (3 minutes later after turning ON), the outdoor unit starts running. During operation, check for the electromagnetic noise.
4) Press OPERATE/STOP (ON/OFF) button on the remote controller for power OFF, when the outdoor unit stops but the indoor/outdoor communication still runs on. In this situation, check for the electromagnetic noise.
OBH667B
Page 43
43
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 10 20 30 40 50 60 70 80 90 100 110 120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
1. Inverter P.C. board
MUFZ-KJ25VE MUFZ-KJ35VE
11-6. TEST POINT DIAGRAM AND VOLTAGE
Fin temperature
thermistor/RT64
(CN642)
Ambient temperature
thermistor/RT65
(CN643)
Discharge temperature
thermistor/RT62
(CN641)
Defrost thermistor
/RT61(CN641)
DB61 260 - 370 VDC
Front side of unit
230 VAC
Smoothing capacitor (C62)
Output to drive compressor (LDU, LDV, LDW)
(+)
(-)
Fuse (F701) T3.15AL250V
Smoothing capacitor (C61)
Fuse (F901) T3.15AL250V
R.V.coil (CN721) 230 VAC
Jumper wire for changing defrost setting (JS)
Signal of outdoor
fan motor (CN931)
230 VAC
Outdoor heat exchanger
temperature thermistor
/RT68 (CN644)
Jumper wire for pre-heat control setting (JK)
Fuse (F801) T3.15AL250V
Back side of unit
LEV connector
(CN724)
Output to drive outdoor fan motor (CN932)
LED
OBH667B
Page 44
44
MUFZ-KJ50VE
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature( )
Defrost thermistor(RT61) Ambient temperature thermistor(RT65) Outdoor heat exchanger temperature thermistor(RT68)
Temperature( )
Discharge temperature thermistor(RT62)
0 102030405060708090100110120
0
100
200
300
400
500
600
700
0 1020304050607080
0
20
40
60
80
100
120
140
160
180
200
Temperature( )
Fin temperature thermistor(RT64)
Resistance(k )
Resistance(k )
Resistance(k )
Fin temperature thermistor/RT64 (CN673)
Ambient temperature thermistor/RT65 (CN672)
Discharge temperature thermistor/RT62 (CN671)
Defrost thermistor /RT61 (CN671)
Output to drive outdoor fan motor (CN932)
Outdoor heat exchanger temperature thermistor /RT68 (CN671)
Fuse (F901) T3.15AL250V
Fuse (F880) T3.15AL250V
LEV connector (CN724)
Jumper wire for changing defrost setting (JS)
Jumper wire for pre-heat control setting (JK)
Fuse (F601) T3.15AL250V
Signal of out­door fan motor (CN931)
R.V. coil (CN602) 230VAC
325 - 370 VDC
JP715 (+)
JP30 (-)
LED
Heater (CN601) 230VAC
To relay P.C. board CN680 (CN681)
OBH667B
Page 45
45
2. Relay P.C. board
MUFZ-KJ50VE
To inverter P.C. board CN681 (CN680)
CN60
L68B(-)
L68A(+)
10 VDC
OBH667B
Page 46
46
12-1. MUFZ-KJ25VE MUFZ-KJ35VE
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screw fixing the service panel. (2) Pull down the service panel and remove it. (3) Disconnect the power supply and indoor/outdoor con-
necting wire. (4) Remove the screws fixing the top panel. (5) Remove the top panel. (6) Remove the screws fixing the cabinet. (7) Remove the cabinet. (8) Remove the screws fixing the back panel. (9) Remove the back panel.
Photo 1
Photo 2
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector has the
locking mechanism.
Slide the sleeve. Pull the terminal while pushing the locking lever.
Hold the sleeve, and pull out the terminal slowly.
Connector
Sleeve
Locking lever
Back panel
Service
panel
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the service panel
Direction to remove
Screws of the cabinet
Hooks
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below. There are two types (refer to (1) and (2)) of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
DISASSEMBLY INSTRUCTIONS
12
Screw of the
cabinet
Screws of the back panel
Screws of the terminal block support and the back panel
OBH667B
Page 47
47
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors:
<Inverter P.C. board>
CN721 (R.V. coil) CN931, CN932 (Fan motor) CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector (CN61). (4) Remove the screws fixing the heat sink support and the sep-
arator.
(5) Remove the fixing screws of the terminal block support and
the back panel.
(6) Remove the inverter assembly. (7) Remove the screw of the earth wire and screw of the termi-
nal block support.
(8) Remove the heat sink support from the P.C. board support. (9) Remove the screw of the inverter P.C. board and remove the
inverter P.C. board from the P.C. board support.
Photo 3
Photo 4 (Inverter assembly)
Photo 5
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN721 (R.V. coil)
(3) Remove the R.V. coil.
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN641 (Defrost thermistor and discharge temperature ther-
mistor) CN643 (Ambient temperature thermistor) CN644 (Outdoor heat exchanger temperature thermistor)
(3) Pull out the discharge temperature thermistor from its holder. (4) Pull out the defrost thermistor from its holder. (Photo 6) (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (Photo 6)
(6) Pull out the ambient temperature thermistor from its holder.
Discharge temperature thermistor
Screw of the R.V. coil
Heat sink
Screw of the earth wire
Screw of the
Terminal block support
47
Screw of the inverter P.C. board
Heat sink support
P.C. board support
Terminal block support
Screws of the heat sink support and the separator
Screws of the terminal block support and the back panel
OBH667B
Page 48
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connectors: <Inverter P.C. board>
CN931, CN932 (Fan motor) (3) Remove the propeller nut. (4) Remove the propeller. (5) Remove the screws fixing the fan motor. (6) Remove the fan motor.
Photo 6
Photo 7
Photo 8
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to 1.) (2) Remove the inverter assembly. (Refer to 2.) (3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(4) Detach the brazed part of the suction and the discharge pipe
connected with compressor. (5) Remove the nuts of compressor legs. (6) Remove the compressor. (7) Detach the brazed part of pipes connected with 4-way valve.
48
Propeller nut
Screws of the outdoor fan motor
Propeller
Photo 9
Brazed parts of 4-way valve
Suction pipe brazed part
Discharge pipe brazed part
Defrost thermistor
Outdoor heat exchanger tempera­ture thermistor
Ambient temperature thermistor
OBH667B
Page 49
49
12-2. MUFZ-KJ50VE
NOTE: Turn OFF power supply before disassembly.
OPERATING PROCEDURE
PHOTOS
1. Removing the cabinet
(1) Remove the screws of the service panel. (2) Remove the screws of the top panel. (3) Remove the screw of the valve cover. (4) Remove the service panel. (5) Remove the top panel. (6) Remove the valve cover. (7) Disconnect the power supply and indoor/outdoor connect-
ing wire. (8) Remove the screws of the cabinet. (9) Remove the cabinet. (10)
Remove the screws of the back panel.
(11)
Remove the back panel.
Photo 2
Photo 1
Screws of the cabinet
Screws of the top panel
Screws of the cabinet
Screws of the top panel
Screw of the back panel
Screws of the cabinet
Screws of the service panel
Screw of the valve cover
Screws of the cabinet
Screws of the back panel
OBH667B
Page 50
50
OPERATING PROCEDURE
PHOTOS
2. Removing the inverter assembly, inverter P.C. board and relay P.C. board
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following con-
nectors: <Inverter P.C. board> CN602 (R.V. coil) CN931, CN932 (Fan motor) CN671 (Defrost thermistor, discharge temperature thermistor
and outdoor heat exchanger temperature thermistor) CN672 (Ambient temperature thermistor) CN724 (LEV)
(3) Remove the compressor connector. (4) Remove the screws fixing the relay panel. (5) Remove the relay panel. (6) Remove the earth wires and the lead wires of the inverter P.C.
board. (7) Remove the screws of the P.B. support. (8) Remove the inverter P.C. board from the relay panel. (9) Disconnect the following connectors:
<Relay P.C. board> CN60 (Terminal block) CN680 (Inverter P.C. board) TAB65 (Inverter P.C. board) TB71
(10)
Remove the screws fixing the P.B. holder.
(11)
Remove the relay P.C. board from the P.B. holder.
Photo 3
Photo 4
3. Removing R.V. coil
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the following connector: <Inverter P.C. board>
CN602 (R.V. coil)
(3) Remove the R.V. coil.
Screws of the P.B. support
Screws of the relay panel
Inverter P.C. board
Earth wires
Screw of the P.B. holder
Screws of the P.B. support
Brazed parts of 4-way valve
Screw of the R.V. coil
Screw of the relay panel
Relay P.C board
OBH667B
Page 51
51
OPERATING PROCEDURE PHOTOS
4. Removing the discharge temperature thermistor, defrost thermistor, outdoor heat exchanger tempera­ture thermistor and ambient temperature thermistor
(1) Remove the cabinet and panels. (Refer to 1.) (2) Disconnect the lead wire to the reactor and the following
connectors: <Inverter P.C. board>
CN671 (Defrost thermistor, discharge temperature thermis-
tor and outdoor heart exchanger temperature ther­mistor)
CN672 (Ambient temperature thermistor)
(3) Pull out the discharge temperature thermistor from its hold-
er. (Photo 7) (4) Pull out the defrost thermistor from its holder. (5) Pull out the outdoor heat exchanger temperature thermistor
from its holder. (6) Pull out the ambient temperature thermistor from its holder.
Photo 5
Photo 6
Photo 7
5. Removing outdoor fan motor
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.)
(2) Disconnect the following connectors:
<Inverter P.C. board>
CN931 and CN932 (Fan motor)
(3) Remove the propeller. (4) Remove the screws fixing the fan motor. (5) Remove the fan motor.
6. Removing the compressor and 4-way valve
(1)
Remove the top panel, cabinet and service panel. (Refer to 1.) (2) Remove the back panel. (Refer to 1.) (3) Remove the inverter assembly. (Refer to 2.) (4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure gauge
shows 0 kg/cm2 (0 MPa).
(5) Detach the brazed part of the suction and the discharge
pipe connected with compressor. (6) Remove the compressor nuts. (7) Remove the compressor. (8) Detach the brazed parts of 4-way valve and pipe. (Photo 4)
Screws of the outdoor fan motor
Outdoor heat exchanger temperature thermistor
Ambient temperature thermistor
Defrost thermistor
Brazed part of the discharge pipe
Brazed part of the suction pipe
Discharge temperature
thermistor
OBH667B
Page 52
© Copyright 2013 MITSUBISHI ELECTRIC CORPORATION Distributed in Jan. 2014. No. OBH667 REVISED EDITION-B Distributed in Oct. 2013. No. OBH667 REVISED EDITION-A Distributed in Jun. 2013. No. OBH667 Made in Japan
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
New publication, effective Jan. 2014 Specifications are subject to change without notice.
Loading...