Mitsubishi MUCF-GA35VB-E1, MUCF-GA50VB-E1, MUCF-GA60VB-E1 Service Manual

FLOOR AND CEILING TYPE AIR CONDITIONERS
HFC
utilized
R410A
OUTDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision A:
RoHS PARTS LIST has been added. Please void OB383.
No. OB383
REVISED EDITION-A
MUCF-GA35VB ­MUCF-GA50VB ­MUCF-GA60VB -
MUCF-GA50VB
E1
E1
E1
Indoor unit service manual
MCF-GA•VB Series (OB382)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················5
3. SPECIFICATION·················································5
4. NOISE CRITERIA CURVES·······························6
5. OUTLINES AND DIMENSIONS·························7
6. WIRING DIAGRAM ············································8
7. REFRIGERANT SYSTEM DIAGRAM··············10
9. TROUBLESHOOTING······································22
10. DISASSEMBLY INSTRUCTIONS·····················24
11. PARTS LIST······················································31
12. RoHS PARTS LIST···········································34
NOTE:
This service manual describes technical data of the outdoor units. RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant).
Refrigeration
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-51.4
1.557 64
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant Composition (Ratio) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa) Saturated steam density [25:](Kg/K) Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
w1:Ozone Destruction Parameter : based on CFC-11 w2 :Global Warmth Parameter : based on CO
2
Revision A :
• RoHS PARTS LIST has been added.
1
MUCF-A12WV - MUCF-GA35VB -
1. Model name has been changed.
MUCF-A18WV - MUCF-GA50VB -
1. Model name has been changed.
MUCF-A24WV - MUCF-GA60VB -
1. Model name has been changed.
TECHNICAL CHANGES
E1E1
E1E1
E1E1
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners. 1 As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2 Take sufficient care not to allow water and other contaminations to enter the R410Arefrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3 For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4 Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
2
NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).
New Specification Current Specification
The incompatible refrigeration oil easily separates from refrigerant and is in the upper layer inside the suction muffler. Raising position of the oil back hole enables to back the refrigeration oil of the upper layer to flow back to the compressor.
Since refrigerant and refrigerating oil are compatible each, refrigeration oil goes back to the compressor through the lower position oil back hole.
Compressor
Suction muffler
Oil back hole
Refrigeration oil
Refrigerant
Compressor
Suction muffler
Oil back hole
Refrigeration oil /Refrigerant
Compressor
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa [Gauge])
R410A R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
R410A tools
Can R22 tools be used?
Gas leak detector
R410A has high pressures beyond the measurement range of existing gauges. Port diameters have been changed to prevent any other refrigerant from being charged into the unit.
Hose material and cap size have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
6.35 mm and 9.52 mm
Description
Clamp bar hole has been enlarged to reinforce the spring strength in the tool. Provided for flaring work (to be used with R22 flare tool).
Provided to prevent the back flow of oil. This adapter enables you to use vacuum pumps.
It is difficult to measure R410A with a charging cylinder because the refrigerant bubbles due to high pressure and high-speed vaporization
No
No
No
Yes
Yes
New
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool Flare gauge
Vacuum pump adapter
Electronic scale for refrigerant charging
No : Not Substitutable for R410A Yes : Substitutable for R410A
No 12.7 mm and 15.88 mm
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
1.Tools dedicated for the air conditioner with R410A refrigerant
The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools. The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.
3
Electronic scale for refrigerant charging
Outdoor unit
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R410A with siphon
Refrigerant (liquid)
Service port
Gauge manifold valve (for R410A)
Union
Liquid pipe Gas pipe
Stop valve
Indoor unit
Charge hose (for R410A)
R410A
Pipe diameter
mm
6.35
9.52
12.7
15.88
17 22 26 29
Dimension of flare nut
R22
17 22 24 27
2.Refrigerant piping
Wall thickness
Outside diameter
Pipe
mm
For liquid
For gas
6.35
9.52
12.7
15.88
0.8 mm
0.8 mm
0.8 mm
1.0 mm
Heat resisting foam plastic Specific gravity 0.045 Thickness 8 mm
Insulation material
1 Specifications
Use the refrigerant pipes that meet the following specifications.
• Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88). Never use any pipe with a thickness less than 0.8 mm (6.35, 9.52, 12.7), 1.0 mm (15.88), as the pressure resistance is insufficient.
2 Flaring work and flare nut
Flaring work for R410A pipe differs from that for R22 pipe. For details of flaring work, refer to Installation manual “FLARING WORK”.
3.Refrigerant oil
Apply the special refrigeration oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.
4.Air purge
• Do not discharge the refrigerant into the atmosphere.
Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant
circuit.
• Use the vacuum pump for air purging for the purpose of environmental protection.
5.Additional charge
For additional charging, charge the refrigerant from liquid phase of the gas cylinder. If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigeration cycle decreases or normal operation can be impossible. However, charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.
4
2
Drain hose
Piping
Air inlet
Drain outlet
(back and side)
Air outlet
Outdoor model
Function
Power supply
Capacity Dehumidification Air flow(High) Power outlet Runnning current Power input Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at 20:) Model Winding resistance(at 20:) Dimensions WOHOD Weight Sound level(High) Fan speed(High) Fan speed regulator Refrigerant filling capacity(R410A) Refrigeration oil (Model)
kW
r/h
K /h
A
A W %
A
A
A
W
"
"
mm
kg
dB
rpm
kg cc
MUCF-GA50VB
Cooling
Single phase
230V, 50Hz
4.8
2.4
2,196
15
7.98
1,744
95 37
7.59
0.39
2.65
RN196VHSHT
1,300 C-R 1.80 C-S 3.00
RA6V50-PA WHT-BLK 79.5 BLK-RED 83.0
850o605o290
44 52
825
1
1.45
520 (NEO22)
MUCF-GA60VB
Cooling
Single phase
230V, 50Hz
6.0
3.1
2,322
25
10.62 2,370
97 74
10.07
0.55
2.45
NN29VBAHT
1,900 C-R 0.80 C-S 1.64
RA6V60-MA
WHT-BLK 71
BLK-RED 89
850o605o290
60 53
873
1
1.85
1,200 (NEO22)
Electrical
data
Compressor
Fan
motor
Special
remarks
Coefficient of performance(C.O.P)
Capacity
MUCF-GA35VB
Cooling
Single phase
230V, 50Hz
3.5
1.5
1,914
10
4.89
1,104
98 29
4.58
0.31
3.02
RN135VHSHT
900 C-R 2.79 C-S 3.36
RA6V33-JC
WHT-BLK 215
BLK-RED 307 780o540o255
36 49
825
1
0.75
620
(NEO22)
Piping
Drain hose
Air outlet
Air inlet
Drain outlet
(back and side)
PART NAMES AND FUNCTIONS
MUCF-GA35VB
3
SPECIFICATION
MUCF-GA50VB MUCF-GA60VB
NOTE: Test conditions are based on ISO 5151
Cooling : Indoor DB27°C WB19°C
Outdoor DB35°C WB(24°C)
Indoor-Outdoor piping length : 5m
5
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
53
SPL(dB(A)) LINE
COOLING
FUNCTION
High
FAN SPEED
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
52
SPL(dB(A)) LINE
COOLING
FUNCTION
High
FAN SPEED
OUTDOOR UNIT
MICROPHONE
1m
49
SPL(dB(A)) LINE
COOLING
FUNCTION
High
FAN SPEED
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
NOISE CRITERIA CURVES
NOISE CRITERIA CURVES
MUCF-GA35VB
MUCF-GA50VB
MUCF-GA60VB
6
5
100mm or more
10
0m
m
o
r m
ore
100mm or more
350mm or more
5
0
0
m
m
o
r m
o
re
Drainage 3 holes [33
Air out
Air in
Air in
Service panel
Liquid refrigerant pipe joint
Refregerant pipe (flared) [6.35
Gas refregerant pipe joint
Refregerant pipe (flared) [12.7 (MUCF-GA50VB) [15.88 (MUCF-GA60VB)
35-
30
-
30
100
161
157
74
850
500
183
20
292
605
248
35
350
50
290
310
345
20
355
90
Drainage hole [16.2
320
25
43-
35
-
155
90
104
74
260
10
780
500
122
40
540
320
285
255
Service panel
Gas refrigerant pipe joint Refrigerant pipe (flared) [12.7
Liquid refrigerant pipe joint Refrigerant pipe (flared) [6.35
Air out
Air in
Air in
109
32
110
147
Drainage 3 holes [33
100mm or more
100mm or more
100mm or more
350mm or more
REQUIRED SPACE
400m
m
or m
ore
OUTLINES AND DIMENSIONS
MUCF-GA35VB
Unit: mm
MUCF-GA50VB MUCF-GA60VB
7
Unit: mm
6
BRN
WHT WHT
POWER SUPPLY 230V 50Hz
~/N
TB1
CIRCUIT BREAKER
PE
BLU
N
GRN/YLW
BRN
L
NO COM
52C
TB2
CONNECTING 12V
INDOOR UNIT
TO
BLK
1
WHT
2
52C
C2
4
WHT
ORN
RED
2 3
1
RED
C1
BLK
BLK
ORN WHT
RED
MF
R
MC
S
C
DSAR
BLU
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Connector
: Terminal block
NOTES:
SYMBOL
C1 C2
DSAR
NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER
SYMBOL
MC MF
TB1,TB2
NAME COMPRESOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK
SYMBOL
52C
NAME
COMPRESSOR CONTACTOR
CIRCUIT BREAKER
POWER SUPPLY ~/N 230V 50Hz
12V
GRN/YLW
TB2
RED
WHT
BLK
WHT BLU
3
2
1
RED
MF
C2
MC
C1
S
R
C
N
2
TO INDOOR UNIT CONNECTING
WHT
BLU
BLK
RED
WHT
52C
TB1
WHT
BLK
52C
PE
L
1
NO
COM
DSAR
BRN
BRN
SYMBOL
TB1,TB2
52C
SYMBOL
MC MF
SYMBOL
C1 C2
DSAR
NAME
NAME NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER
COMPRESSOR(INNER PROTECTOR)
TERMINAL BLOCK COMPRESSOR CONTACTOR
OUTDOOR FAN MOTOR (INNER FUSE)
WIRING DIAGRAM
MUCF-GA35VB
NOTE:1. About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block, : Connector
MUCF-GA50VB
8
MUCF-GA60VB
TB1
RED
MC
~/N 230V 50Hz
POWER SUPPLY
52C
GRN/YLW
PE
N
CIRCUIT BREAKER
X1
NO
L
NO
REDRED
WHT
BLU
ORN
C2
WHT
3 4
BLK
1 2
ORN
COM
BLU
COM
52C
BLK
S
MF
R
C
12V
INDOOR UNIT CONNECTING
TO
X1
1
BLK
BRN
WHT
2
TB2
DSAR
WHT
C1
BLU
BRN
WHT
BRN
BRN
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Connector
: Terminal block
NOTES:
SYMBOL
C1 C2
DSAR
NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER
SYMBOL
MC MF
TB1,TB2
NAME COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) TERMINAL BLOCK
SYMBOL
X1
52C
NAME RELAY COMPRESSOR CONTACTOR
9
7
REFRIGERANT SYSTEM DIAGRAM
MUCF-GA35VB
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Stop valve (with service port)
Stop valve
Unit:mm
Muffler
Outdoor heat exchanger
Compressor
Strainer #100
Capillary tube [3.0x[1.4x550
Refrigerant flow in cooling
MUCF-GA50VB
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Flared connection
Stop valve (with service port)
Stop valve
Capillary tube
[2.5o[0.6o1,000
Oil separator
Compressor
Strainer
#100
Outdoor heat exchanger
Refrigerant pipe[6.35 (with heat insulator)
Capillary tube
[3.0o[1.6o650
Refrigerant flow in cooling
10
MUCF-GA60VB
Refrigerant pipe [15.88 (with heat insulator)
Stop valve (with service port)
Flared connection
Flared connection
Muffler
Unit:mm
Muffler
#100
Outdoor heat exchanger
Compressor
Refrigerant pipe [6.35 (with heat insulator)
Stop valve
Capillary tube [3.0X[2.0X1000
Refrigerant flow in cooling
11
A: Refrigerant piping Max. length 25m
Max. Height
difference *
10m
*Height difference should be within 10m regardless of which unit,
indoor or outdoor position is high.
Indoor unit
Outdoor unit
If pipe length exceeds 7m, additional refrigerant (R410A) charge is required.
Model
MUCF-GA35VB MUCF-GA50VB
MUCF-GA60VB
Refrigerant piping length (one way)
Outdoor unit precharged
750 1,450 1,850
15m
160
20m
260
25m
360
7m
0
10m
60
REFRIGERANT PIPING MAX. LENGTH & MAX. HEIGHT DIFFERENCE
Models
MUCF-GA35VB MUCF-GA50VB MUCF-GA60VB
Refrigerant piping
Max. length : m
A
25
Piping size O.D. : mm
Gas
{12.7
{15.88
Liquid
{6.35
ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Calculation : Xg=20g/m (Refrigerant piping length (m)–7)
12
Loading...