13. PARTS LIST······················································43
14. OPTIONAL PARTS ······················BACK COVER
E1E1
E1E1
E1E1
1
Lubricant
Refrigerant
New refrigerant
R407C
R32: R125: R134a (23%:25%:52%)
Non-azeotropic refrigerant
Not included
A1/A1
86.2
-43.6
0.9177
42.5
Non combustible
0
1530
From liquid phase in cylinder
Impossible
Incompatible oil
Non
Non
Previous refrigerant
R22
HCFC22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055
1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant
Composition (Ratio)
Refrigerant handling
Chlorine
Safety group (ASHRAE)
Molecular weight
Boiling point (:)
Steam pressure [25:](Mpa [Gauge])
Saturated steam density [25:](Kg/K)
Combustibility
ODP w1
GWP w2
Refrigerant charge method
Additional charge on leakage
Kind
Color
Smell
w1:Ozone Destruction Parameter : based on CFC11
w2 :Global Warmth Parameter : based on CO
2
New SpecificationPrevious Specification
The incompatible lubricant easily separates from refrigerant
and makes the layer in the upper inside the suction muffler.
The higher position of the returning oil hole enables to return
the lubricant of the upper layer to the compressor.
Since refrigerant and lubricant are compatible each other,
lubricant returns to the compressor through the lower
position returning oil hole.
Compressor
Suction muffler
Returning oil hole
Lubricant
Refrigerant
Compressor
Suction muffler
Returning oil hole
Lubricant and Refrigerant
Compressor
-30 -20 -10 010 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa[Gauge])
R407C
R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
TECHNICAL CHANGES
INFORMATION FOR THE AIR CONDITIONER WITH R407C REFRIGERANT
This room air conditioner adopts HFC refrigerant (R407C) which never destroy the ozone layer.
Pay attention to following points.
1 Take sufficient care not to allow water and other contaminations to enter the R407C refrigerant during storage and
installation, since it is more susceptible to contaminations than HCFC (R22) refrigerant.
2 Clean refrigerant piping should be used.
3 Composition change may occur in R407C since it is a mixed refrigerant. When charging, charge liquid refrigerant to
prevent composition change.
4 Be especially careful when managing the tools.
If dust, dirt, or water mixes in the refrigerant cycle, it may cause decrease of performance.
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa[Gauge]) =10.2(kgf/ff[Gauge])
2
1.Tools dedicated for the air conditioner with R407C refrigerant
R407C toolsCan R22 tools be used?
Gas leak detector
A gauge manifold with a sight glass is recommended for charging the
liquid refregerant.
Hose material have been changed to improve the pressure
resistance.
Dedicated for HFC refrigerant.
Description
Provided to prevent the back flow of oil. This adapter enables you to use
existing vacuum pumps.
No
No
No
Yes
Yes
New
New
Gauge manifold
Charge hose
Torque wrench
Flare tool
Vacuum pump
adapter
Electronic scale for
refrigerant charging
Use the electronic control scale for measuring the R407C.
The following tools are required for R407C refrigerant. Some R22 tools can be substituted for R407C tools.
Do not use tools that are used with R22 refrigerant in order to avoid mixing oils.
2.Refrigerant piping
Do not use copper pipes which are broken, deformed or discoloured.
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulfur and oxides, or have no dust/ dirt,
shaving particles, oil, moisture or any other contamination.
•If there is a large amount of residual oil inside the piping and joints, deterioration of the refrigerant oil will result.
3.Refrigerant oil
Apply the specific refrigeration oil (accessories) to the flare and the union seat surfaces.
4.Air purge
Use the vacuum pump for air purge to protect environments, and to avoid changing the composition of refrigerant.
5.Additional charge
For additional charging, charge the refrigerant with liquid phase slowly using a gas cylinder. If the refrigerant is charged with
gas phase, the composition of refrigerant will change. In this case, ability of the refrigerating cycle decreases or normal
operation can be impossible.
If liquid refrigerant is rapidly charged at once, the compressor may be locked.
NOTE: 1. The R407C is mixed refrigerant which consist of three different kinds of evaporative temperature. As a result, the
R407C occurs the change of composition.
2. Additional refrigerant charge has been changed by change of refrigerant.(R22 ➔ R407C)
Installation plate
Unit fixing screw
5 o 12mm
Wireless remote
controller
Remote controller
holder
Fixing screw for
3.5 o 16mm (Black)
Battery (AAA) for
remote controller
Drain hose
Drain pipe cover
Knockout cover
Screw for 4 o 10mm
Refrigerating oil
2
2
1
1
2
2
1
1
1
2
1
Q'ty
1
2
3
4
4
5
6
7
8
9
9
0
1
2
PART NAMES AND FUNCTIONS
MCF-C13UV -MCF-C18UV -MCF-C24UV -
INDOOR UNIT
E1E1E1
MUCF-C13UV -
E1
OUTDOOR UNIT
MUCF-C18UV -MUCF-C24UV -
Air inlet
(back and side)
Piping
Drain hose
Air outlet
Drain outlet
OUTDOOR UNIT
E1E1
Air inlet
Piping
Drain hose
Air outlet
Drain outlet
4
MCF-C13UV -MCF-C18UV -MCF-C24UV -
REMOTE CONTROLLER
Signal transmitting section
E1E1E1
Operation display section
OPERATE /STOP
(ON /OFF)button
Open the front lid.
Open the front lid.
ON/OFF
ON/OFF
TOO
WARM
CLOCK
TOO
WARM
PM
AM
TOO
COOL
PM
AM
TOO
COOL
TEMPERATURE buttons
FAN SPEED CONTROL button
OPERATION SELECT button
RESET button
I FEEL
FAN
MODE
COOL
DRY
FAN
VANE
RESET
5
CLOCK
STOP
START
HR.
MIN.
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
VANE CONTROL button
3
Indoor model
Function
Power supply
Capacity
Dehumidification
Air flow
(High/Med.W/LowW)
Power outlet
Running current
Power input
Auxiliary heater
Power factor
Starting current
Fan motor current
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Air direction
Sound level(High/Med.W/LowW)
Fan speed(High/Med.
W
/LowW)
Fan speed regulator
Thermistor RT11(at25:)
Thermistor RT12(at25:)
Outdoor model
Air flow
(High/LowW)
Compressor motor current
Fan motor current
Model
Output
Winding
resistance(at20:)
Model
Winding
resistance(at20:)
Dimensions WOHOD
Weight
Sound level (High)
Fan speed
(High/LowW)
Fan speed regulator
Refrigerant filling
capacity(R407C)
Refrigerating oil (Model)
The standard data contained in these specifications apply only to the operation of the air conditioner under normal condition.
Operating conditions vary according to the areas where these units are installed. The following information has been provided
to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : ˚C WB
(2) Indoor outlet air wet-bulb temperature : ˚C WB
(3) Outdoor intake air dry-bulb temperature : ˚C DB
(4) Total input : W
The table of Indoor air wet-bulb temperature difference on the left side of the chart on this page shows the difference
between the indoor intake air wet-bulb temperature and the indoor outlet air wet-bulb temperature for your reference at
service.
How to measure the indoor air wet-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air intake.
Cover the thermometers to avoid direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of the room.
5. Press the EMERGENCY OPERATION switch to start the EMERGENCY operation.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
11.4
10.5
9.5
8.6
7.7
6.8
15.7
14.2
12.8
11.5
10.3
9.0
9.9
9.1
8.2
7.5
6.7
5.9
OUTDOOR UNIT
MCF-C13UV- E1
MCF-C18UV- E1
MCF-C24UV- E1
16
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
20253035
0.3
0.4
0.5
0.6
0.7
20253035
0.3
0.4
0.5
0.6
0.7
20253035
6
7
8
9
10
11
230V
230V
230V
230V
Ambient temperature (:)
Ambient humidity(%)
Ambient temperature (:)
Ambient humidity(%)
Ambient temperature (:)
Ambient humidity(%)
Ambient temperature (:)
Ambient humidity(%)
18
506070
32
Outdoor low pressure
50
60
70
Outdoor unit current (A)
18
506070
32
(:)
(%)
Outdoor low pressure
18
506070
32
(%)
Outdoor unit current (A)
6
5
4
3
7
7
6
5
4
3
(kgf/F[Gauge])(MPa[Gauge])
(kgf/F[Gauge])(MPa[Gauge])
(:)
(%)
(:)
(%)
20253035
(:)
8
9
10
11
12
13
14
20253035
0.3
0.4
0.5
0.6
0.7
1520253035
3
4
5
6
7
8
230V
18
506070
32
(:)
(%)
Outdoor low pressure
6
5
4
3
7
(kgf/F[Gauge])(MPa[Gauge])
230V
Ambient temperature (:)
Ambient humidity(%)
Ambient temperature (:)
Ambient humidity(%)
506070
Outdoor unit current (A)
(:)
(%)
COOL operation
1 Both indoor and outdoor units are under the same temperature/humidity condition.
Dry Bulb temperature (˚C)
20
25
30
Relative humidity (%)
50
60
70
2 Air flow should be set at MAX..
3 The unit of pressure has been changed to MPa on the international system of units(SI unit system).
The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
MUCF-C13UV-
E1
E1
E1
MUCF-C18UV-
MUCF-C24UV-
17
PERFORMANCE DATA
COOL operation
MCF-C13UV -: MUCF-C13UV -
CAPACITY:3.55(kW) SHF:0.70 INPUT:1400(W)
INDOOR INDOOR
DB(:)
NOTEQ : Total capacity (kW) SHF : Sensible heat factor DB: Dry-bulb temperature
SHC : Sensible heat capacity (kW) INPUT : Total power input (W)WB: Wet-bulb temperature
QSHC SHF
35404346
INPUTINPUTINPUTINPUT
E1E1
Q
SHC SHF
OUTDOOR DB(:)
Q
SHC SHFQ
SHC SHF
23
9
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
STOP
START
HR.
MIN.
I FEEL
COOL
DRY
PM
CLOCK
AM
RESET
CLOCK
FAN
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
VANE CONTROL button
CLOCK SET button
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
TEMPERATURE buttons
MICROPROCESSOR CONTROL
WIRELESS REMOTE CONTROLLER
MCF-C13UV MCF-C18UV MCF-C24UV -
E1
MUCF-C13UV -
E1
MUCF-C18UV -
E1
MUCF-C24UV -
E1
E1
E1
Once the operation mode are set, the same operation mode
can be repeated by simply turning the OPERATE/STOP
(ON/OFF) button ON.
Indoor unit receives the signal with a beep tone.
When the system turns off, 3-minute time delay will operate to
protect system from overload and compressor will not restart
for 3 minutes.
9-1. “I FEEL CONTROL” ( )OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote
controller. OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select “I FEEL CONTROL”( )mode with the OPERA-
TION SELECT button.
(3) The operation mode is determined by the room
temperature at start-up of the operation.
Initial room temperaturemode
more than 25°C
more than 13°C, less than 25°C
COOL mode of
“I FEEL CONTROL”
DRY mode of
“I FEEL CONTROL”
INDOOR UNIT DISPLAY SECTION
Operation Indicator lamp
The operation indicator at the right side of the indoor
unit indicates the operation state.
• The following indication applies regardless of shape of
the indicator.
Operation Indicator
Operation stateIndication
This shows that the
air conditioner is
operating to reach
the target temperature.
Please wait until the
target temperature is
obtained.
This shows that the
room temperature is
approaching the
target temperature.
lighted
not lighted
Difference
between target
temperature
and room
temperature
Approx. 2 :
or more
Approx. 2 :
or less
● Once the mode is fixed, the mode will not change by room
temperature afterwards.
● Under the ON-TIMER ()timer operation, mode is
determined according to the room temperature at the set
time the operation starts.
● When the system is stopped on the remote controller, and
restarted within 2 hours in “I FEEL CONTROL” ( )mode,
the system operates in previous mode automatically
regardless of the room temperature.
Example
Previous operation
COOL mode of
“I FEEL CONTROL”
Restart
COOL mode of
“I FEEL CONTROL”
or COOL mode
● When the system is restarted after 2 hours and more, the
operation mode is determined by the room temperature at
start-up of the operation.
Example
Restart
COOL or DRY mode of
Previous operation
COOL mode of “I FEEL
CONTROL” or COOL
mode
“I FEEL CONTROL” that
is determined by room
temperature at start-up
of the operation.
24
(4) The initial set temperature is decided by the initial room temperature.
Difference between room
temperature and set temperature
during operation.
TOO
COOL
TOO
WARM
Model
COOL mode of
“I FEEL CONTROL”
DRY mode of
“I FEEL CONTROL”
Initial room temperature
26°C or more
25°C to 26°C
more than 13°C, less than 25°C
Initial set temperature
24°C
Initial room temperature
minus 2°C
Initial room temperature
minus 2°C
❈1
❈1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of the room temperature at restart.
The set temperature is calculated by the previous set temperature.
(5) TEMPERATURES buttons
In “I FEEL CONTROL”( ) mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature is controlled by or TOO WARM or TOO COOL buttons when you feel too warm or too cool.
Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
● Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering
the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or
cold. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.
In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
…
To raise the set temperature 1~2 degrees(°C)
…
To lower the set temperature 1~2 degrees(°C)
9-1-1. COOL mode of “I FEEL CONTROL”
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In AUTO the fan speed is as follows.
Initial temperature difference
Room temperature minus set temperature : 2 degrees or more········································High
Room temperature minus set temperature : Between 1 and 2 degrees····························Med.
Room temperature minus set temperature : less than 1 degrees······································Low
2. Coil frost prevention
① Temperature control
When the indoor coil thermistor RT12 reads -1:or below, the coil frost prevention mode starts
immediately. However the coil frost prevention doesn’t work for 5 minutes since the compressor has
started.
The indoor fan operates at the set speed the compressor stops for 5 minutes.
After that, if RT12 still reads below -1: this mode is prolonged until the RT12 reads over -1:.
② Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med..
c. Room temperature is below 26:.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts
from the beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26:. However, when two of the above conditions (b.and c.) are satisfied again. Time accumulation is resumed.
Fan speed
1 deg.
1.7 deg.
2 deg.
4 deg.
25
.
..
.
Operation time chart
Example
Compressor and
Outdoor fan motor
OFF
ON
ON
OFF
Indoor fan motor
ON (continuously at set speed)
9-1-2. DRY mode of “I FEEL CONTROL”
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the temperature.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by room temperature control and time control.
Set temperature is controlled to fall 2: as initial set temperature.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
• When the room temperature is 23: or over:
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
• When the room temperature is under 23:.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
Example
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection (Coil frost
prevention) has the priority.
However, when coil frost prevention works while the compressor is not operating, it’s speed becomes Low.
9-2. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION SELECT button.
(3) Press the TEMPERATURE buttons.
(TOO WARM or TOO COOL button)
The setting range is 16 ~ 31°C
w Indoor fan continues to operate regardless of thermostat’s OFF-ON.
w Coil frost prevention is as same as COOL mode of “I FEEL CONTROL”.
26
1
2
3
4
5
SWING
AUTO
9-3. DRY () OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor
unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION
SELECT button.
(3) The microprocessor reads the room temperature
and determines the set temperature. Set temperature is as shown on the right chart.
Thermostat (SET TEMP.)does not work.
The other operations are same as DRY mode of
“I FEEL CONTROL”.
(4) DRY operation will not function when the room
temperature is 13°C or below.
9-4. FAN () OPERATION
(1) Press the OPERATE/STOP (ON/OFF) button.
(2) Select FAN mode with the OPERATION SELECT button.
(3) Select the desired fan speed. When AUTO, it becomes Low.
Only indoor fan operates.
Outdoor unit does not operate.
9-5. AUTO VANE OPERATION
(1) Vane motor drive
This series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are
controlled by pulse signals (approx. 12V, transmitted from indoor microprocessor.)
(2) Each time the VANE CONTROLbutton is pressed, angle of horizontal vane is changed in sequence, from 1, 2, 3, 4, 5,
SWING to AUTO.
(3) Positioning
The vane is once pressed to the vane stopper to confirm the standard position and then set to the desired angle.
Confirming of standard position is performed in case of follows.
(a) When the OPERATE/STOP (ON/OFF) button is pressed (POWER ON/OFF).
(b) When the vane control is changed from AUTO to MANUAL.
(c) When the SWING is finished.
(d) When the test run starts.
(e) When the power supply turns ON.
27
(4) VANE AUTO ( ) mode
4
1
1
1
2
3
4
5
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum
room-temperature distribution.
1.In COOL and DRY operation
Vane angle is fixed to position 1.
2.In FAN operation
Vane angle is fixed to position 4.
(5) Dew prevention
During COOL or DRY operation at position 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the
angle of horizontal vane automatically changes to position 1 for dew prevention.
(6) SWING MODE( )
By selecting SWING mode with the VANE CONTROL button the horizontal vane swings vertically. The remote controller
displays “ “.SWING mode is cancelled when the VANE CONTROL button is pressed once again.
(7) STOP and ON-TIMER standby
When the following cases occur, the vane returns to the closed position.
(a) When the operation is stopped by the remote controller.
(b) When the operation is stopped by the emergency operation.
(c) When the ON-timer is on standby.
9-6. TIMER OPERATION
1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner.
(2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press TIMER CONTROL button to select the operation.
“ON-TIMER” button... AUTO START operation (ON timer)
“OFF-TIMER” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “” or “” mark is flashing.
These marks disappear in 1 minute.
After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
• Apower failure occurs.
•The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with the ON/OFF TIMER buttons.
To cancel the ON timer, press the “ON-TIMER” button.
To cancel the OFF timer, press the “OFF-TIMER” button.
TIMER is cancelled and the display of set time disappears.
28
PROGRAM TIMER
PM
AM
PM
PM
Press once <Cool>
Press once again<Stop>
OPERATION INDICATOR lamp
• The following indication applies
regardless of shape of the indicator.
● The OFF timer and ON timer can be used in combination.
● “” and “” display show the order of the OFF timer and ON timer operation.
➝
(Example 1) The current timer is 8:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
➝
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
9-7. EMERGENCY-TEST OPERATION
In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the
indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote
controller run down. The unit will start and the OPERATION INDICATOR lamp will light.
The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at
High speed and the system is in continuous operation. (The thermostat is ON.)
After 30 minutes of test run operation the system shifts to EMERGENCY COOL MODE with a set temperature of 24°C.
The fan speed shifts to Med. speed.
The coil frost prevention works even in emergency operation.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO () mode.
Emergency operation continues until the EMERGENCY OPERATION switch is pressed again or the unit receives any signal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
EMERGENCY
OPERATION switch
9-8. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed
are memorized by the auto restart P.C. board.
The “AUTO RESTART” function sets to work the moment the power has restored after power failure. Then, the unit will
restart automatically. However if the unit is operated in “I FEELCONTROL” mode, before power failure, the operation is
not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature.
NOTE
:
•The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
•If the main power is turned off or a power failure occurs while AUTO START/ STOP timer is active, the timer setting is
cancelled.
•If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
•To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the
same time.
•When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting
current by adding to the system that allows the units to start one by one.
29
SERVICE FUNCTIONS10
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
–
–
–
2 units operation
Same as at left
Solder J1
–
–
3 units operation
Same as at left
Same as at left
Solder J2
–
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
MCF-C13UV MCF-C18UV MCF-C24UV -
E1
MUCF-C13UV -
E1
MUCF-C18UV -
E1
MUCF-C24UV -
E1
E1
E1
10-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the indoor electronic control P.C. board.
The time will be shortened as follows.(Refer to page 36.)
Set time : 1 minute ➔ 1-second
Set time : 3 minute ➔ 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
10-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor
unit individually by each remote controller, P.C. boards of remote controller must be modified according to the indoor unit
number.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below :
NOTE : For remodelling, take out the batteries
and press the
OPERATE/STOP(ON/OFF)button twice
or 3 times at first.
After finish remodelling, put back the
batteries then press the RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit will only accepts the signal from the remote controller that has been assigned to the indoor unit once they
are set.
The setting will be cancelled if the breaker has turned off, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
10-3. RELEASE OF AUTO RESTART FUNCTION
Solder JHA (refer to page 36) with a jumper line on the indoor electronic control P.C. board.
Remove the auto restart assy from “Connector CN104”.
30
TROUBLESHOOTING11
Insert the negative pole
of the batteries first.
Check if the polarity of
the batteries are correct.
RESET button
MCF-C13UV MCF-C18UV MCF-C24UV -
E1
MUCF-C13UV -
E1
MUCF-C18UV -
E1
MUCF-C24UV -
E1
E1
E1
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
(1) Check the power supply voltage.
(2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
(2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
(2) Before servicing check that the connector and terminal are connected properly.
(3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discolouration.
(4) When troubleshooting, refer to the flow chart and the check table on page 32.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then re-attach the front lid.
2 Press the RESET button with tip end of ball point
pen or the like, and then use the remote controller.
NOTE1. : If the RESET button is not pressed, the remote controller may not operate correctly.
31
11-2. Instruction of troubleshooting
Operation Indicator
· Flashing of the OPERATION INDICATOR lamp (on the left-hand side)
indicates possible abnormalities.
· The OPERATION INDICATOR lamp (on the left-hand side) is lighting during
normal operation.
•The following indication applies regardless of shape of the indocator.
Flashing
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Indoor unit
doesn't receive
the signal from
remote controller.
OPERATION
INDICATOR
lamp on the indoor
unit is flashing
on and off.
Outdoor unit
operates in
only Test Run
operation.
Outdoor unit
doesn't
operate
even in
Test Run
operation.
Indoor unit
operates, when
the EMERGENCY
OPERATION
switch is pressed.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is pressed.
Check room
temperature
thermistor.
Refer to "Test point
diagram and
voltage" on page 36.
Refer to
D
"Check of
outdoor unit"
on page 35.
Refer to B
"Check of
remote controller
and receiver
P.C. board"
on page 34.
Refer to C
"Check of indoor
electronic control
P.C. board"
on page 35.
2-time flash
Cause: Indoor unit
• Trouble of room
temperature/ indoor
coil thermistor
Check room tempreture thermistor and
indoor coil thermistor
Refer to "Test point
diagram and voltage"
on page 36.
When the remote
controller is
pressed
or when the
EMERGENCY
OPERATION
switch is
pressed,
the fan doesn't
rotate, with
OPERATION
INDICATOR
lamp on.
Refer to A
"Check of
indoor fan
motor" on
page 34.
1. Troubleshooting check table
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
Abnormal
NO.
point
Indication
Symptom
Detect method
Indoor coil
thermistor
1
Room
temperature thermistor
2-time flash
2.5-second OFF
Outdoor unit
does not run.
Detect Indoor coil/room temperature thermistor short or
open circuit.
32
Check point
● Check resistance of thermistor.
● Re-connect connector.
● Check indoor electronic control P.C.board.
2. Trouble criterion of main parts
C
S
R
BLK
RED
WHT
BLKRED ORNYLW BLU BRN
WHT
GRN
YLW
P
MAIN
BLKYLW
RED ORN
WHT
MAIN1
AUX.
MAIN2
P
BLK
RED ORN
WHT
MAIN
AUX.
P
BRN
YLW
PNK
RED
ORN
BLU
ROTOR
BLK
RED
WHT
MAIN
AUX.
P
MCF-C13UV MCF-C18UV MCF-C24UV -
E1
MUCF-C13UV -
E1
MUCF-C18UV -
E1
MUCF-C24UV -
Part name
Room
temperature
thermistor (RT11)
Measure the resistance with a tester.
(Part temperature 10°C ~ 30°C)
Indoor coil
thermistor
(RT12)
Compressor
(MC)
INNER
PROTECTOR
MUCF-C13UV
150 i 5: OPEN
90 i 10: CLOSE
MUCF-C18UV
155 i 5: OPEN
90 i 10: CLOSE
MUCF-C24UV
160 i 5: OPEN
90 i 10: CLOSE
Measure the resistance between the terminals with a tester.
(Part wiring temperature -10°C ~ 40°C)
Terminal
C-R
C-S
Measure the resistance between the terminals with a tester.
(Part wiring temperature10°C ~ 30°C)
Measure the resistance between the terminals with a tester.
(Part wiring temperature -10°C ~ 40°C)
Color of
lead wire
WHT-BLK
BLK-RED
BLK-YLW
MUCF-C13UV
155 ~ 190Ω
364 ~ 446Ω
______
Normal
MUCF-C18UV
102 ~ 126Ω
97 ~ 120Ω
MUCF-C24UV
71 ~ 88Ω
90 ~ 111Ω
81~ 100Ω
Abnormal
Open or
short-circuit
MUCF-C18UV
MUCF-C24UV
Measure the resistance between the terminals with a tester.
(Part wiring temperature10°C ~ 30°C)
NormalAbnormal
RED-PNK/ORN
BRN-YLW/BLU
329
~357
Ω
Open or
short-circuit
: INNER PROTECTOR
P
33
Indoor fan does not operate.
● Re-install the unit away from lights.
● Attach a filter on receiving part.
Switch on the remote controller
Is LCD display on remote
controller visible?
Replace the batteries.(Refer to page 31.)
Remove batteries, then set them back and press
the RESET button. Check if the unit operates with
remote controller.
Does the unit operate with remote controller?
Turn on a radio to AM and press
switch on remote controller.
Is noise heard from radio?Replace the remote controller.
Are there any fluorescent lights
of inverter or rapid-start type
within the range of 1m?
Measure the voltage between receiver P.C.board connector No.2(+)and No.1 when remote controller button is pressed.
Is the voltage approx. 4V DC?
No
(5V DC or 0V DC)
Replace the receiver P.C. board.
No
(not clear)
Yes
Yes
No
OK
No
Yes
Yes
Yes
No
Replace the indoor
electronic control P.C. board.
No
A
Check of indoor fan motor
Turn OFF power supply.
Check connector (Fan motor) visually.
No
Re-connect the lead
wires.
Are lead wires connected?
Yes
Disconnect lead wires from connector (Fan motor)on indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.4 and then No.3 and No.4 of the fan motor.
Is resistance 0 (short circuit) or ∞ (open circuit)?
Yes ( 0 or ∞ )
Replace the indoor fan motor.
Is soldered point of the connector
correctly soldered?
(others)
Yes
Replace the indoor electronic control
P.C. board.
No
No
Re-solder it.
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check of remote controller and receiver P.C. board
B
w Check if the remote controller is exclusive for this air conditioner.
34
The unit doesn’t operate with the remote controller.
Also, the OPERATION INDICATOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Check of indoor electronic control P.C. board
C
Replace the fuse.
Yes
Is fuse(F11)blown?
Check both “parts side” and
“pattern side” of indoor
electronic control P.C. board
visually.
Be sure to check both fuse
and varistor in any case.
Is varistor(NR11)burnt?
Yes
Replace the varistor.
Compressor and / or outdoor fan motor does not operate.
Check of outdoor unit
D
MUCF-C13UVMUCF-C18UV-
E1
E1
MUCF-C24UV-
No
Trouble of the indoor electronic
control P.C. board.
No
E1
Press EMERGENCY OPERATION
switch. 3-minute time delay works.
Test run operation operates for 30
minutes.
Yes
Check the outdoor fan motor
and compressor.
Yes
Check the continuity of indoor
and outdoor unit connection.
Check voltage to terminal
block of outdoor unit. Is there
230V AC to terminal block
between 2 - N ?
Start
No
Check voltage to terminal
block of indoor unit. Is
there 230V AC to terminal
block between 2 - N ?
No
Replace the indoor electronic control P.C. board.
Start
Press EMERGENCY OPERATION
switch. 3-minute time delay works.
Test run operation operates for 30
minutes.
Check voltage to terminal
block of outdoor unit. Is there
230V AC to terminal block
between 2 - N ?
Yes
Check voltage to terminal
block of outdoor unit. Is
there 230V AC to terminal
block between 3 - N ?
Yes
Check the outdoor wiring
and conductor relay.
No
No
Check voltage to terminal
block of indoor unit. Is there
230V AC to terminal block
between 3 - N ?
Check the continuity of
indoor and outdoor unit
connection.
Check the continuity of indoor
and outdoor unit connection.
Yes
No
Replace the
indoor electronic control
P.C. board.
35
DE00R697B
To the indoor
electronic control
P.C.board CN113
Indoor coil thermistor (RT12)
Room temperature thermistor (RT11)
RT11
EMERGENCY OPERATION switch
TH113
CH313
GILMS
12
0
0
10
20
30
40
10 20 30 40 50 60
Temperature ( C)
Resistance ( )
TEST POINT DIAGRAM AND VOLTAGE
MCF-C13UV MCF-C18UV MCF-C24UV -
E1
E1
E1
Indoor electronic control P.C. board
Fan motor power supply 230V AC (Refer to page 38)
Med.
Low High
87564321
Fuse 250V AC 3.15A
Power supply
input 230V AC
Room temperature
thermistor(RT11)
+
12V DC
–
}
+
5V DC
–
}
JHA (Release of AUTO RESTART FUNCTION.
Refer to page 30.)
CN113
Room temperature thermistor (RT11)
Time short point (Refer to page 30.)
CN112
Indoor coil thermistor (RT12)
36
DISASSEMBLY INSTRUCTIONS12
<"Terminal with lock mechanism" Detaching points>
In the case of terminal with lock mechanism, detach the terminal as shown below.
(1)(2)
1Slide the sleeve.
2Pull the terminal while
pushing the locking
lever.
1Hold the sleeve, and
pull out the terminal
slowly.
12-1. MCF-C13UV -MCF-C18UV -MCF-C24UV -
INDOOR UNIT
OPERATING PROCEDUREPHOTOS
1. Removing the electronic control P. C . board.
(1) Pull out the upper part of the grille.
( Photo 1 )
(2) Remove the screws of the grille.
(3) Remove screws of terminal block cover. (Photo 2)
Remove the terminal block cover and remove the terminal
block.
(4) Remove the screws of the electrical box cover.
(5) Pull out the electronic control P.C. board. (Photo 3)
Photo 3
Photo 1
Photo 2
E1E1E1
Screws
Grille
Electronic control P.C. board
2. Removing the indoor fan motor
(1) Remove the grille. ( Refer to 1(1) (2) )
(2) Remove the screws of pipe support assembly.
(3) Remove the fan casing.(upper).
(4) Disconnect the connector of the indoor fan motor.
(5) Disconnect the ground wire of the fan motor.
(6) Remove the screws of the motor band and remove the
catch.
(7) Take out the sirocco fan and the indoor fan motor.
37
Electrical box
Photo 4
Fan casing
(upper)
Indoor fan motor
Terminal block
Motor band
Screws
Fan
casing(upper)
OPERATING PROCEDUREPHOTOS
3. Removing the indoor heat exchanger.
(1) Remove the grille. (Refer to 1(1) (2))
(2) Remove the screws on both sides and in front of the front
panel. (Photo 5)
(3) Remove the screws of the nozzle assembly. (Photo 6)
(4) Remove the electrical box. (Refer to 1)
(5) Remove the indoor fan motor. (Refer to 2)
(6) Remove the screws of the motor support.
(7) Remove the fan casing. (Iower)
(8) Remove the insulation of the drain pan and remove the
screws. (Photo 7)
(9) Remove the screws under the drain pan.(Photo 8)
(10)
Remove the drain pan.
(11)
Remove the indoor heat exchanger.
Photo 5
Screws
Front panel
Photo 6
Nozzle assembly
Screws
Photo 7
Photo 8
Insulation of drain pan and screws
Drain pan
38
Screws
12-2. MUCF-C13UV -
OUTDOOR UNIT
OPERATING PROCEDUREPHOTOS
E1
1. Removing the cabinet
(1) Remove the screws fixing the top panel.
(2) Remove the screw fixing the service panel.
(3) Remove the screws fixing the cabinet.
(4) Remove the screws fixing the front panel and motor sup-
port.
(5) Remove the service panel, and remove the screw from
the insides.
(6) Remove the top panel.
(7) Remove the cabinet.
Photo 3
Screws of
service panel
Screws of
top panel
Service
panel
Photo 1
Screws of front panel and motor support
Screws of cabinet
Photo 2
Screws of
top panel
2. Removing the electrical parts
(1) Remove the service panel and the cabinet.(Refer to 1)
(2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block (TB)
Screws of
cabinet
Photo 4
Outdoor fan capacitor
39
Compressor capacitor
Terminal block
OPERATING PROCEDUREPHOTOS
3. Removing the propeller fan and the outdoor fan
motor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the propeller fan nut.
(3) Remove the propeller fan.
NOTE : Loose the propeller fan in the rotating direction for
removal.
When attaching the propeller fan, align the mark on the
propeller fan and the motor shaft cut section.
Set the propeller fan in position by using the cut on the
shaft and the mark on the propeller fan.
(4) Remove lead clamps and disconnect the outdoor fan motor
lead wires.
(5) Remove screws fixing the fan motor.
(6) Remove the outdoor fan motor.
Photo 5
Set screws for
outdoor fan motor
Propeller fan
Hook
Lead clamps
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover on the compressor.
(5) Disconnect lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
(7) Disconnect the welded part of the discharge pipe.
(8) Disconnect the welded part of the suction pipe.
(9) Remove nuts fixing the compressor.
(10) Remove the compressor.
NOTE
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
2
(0MPa).
Propeller fan nut
Photo 6
Discharge pipe
Glass
terminal
Compressor
Outdoor
fan motor
Suction pipe
40
Compressor
set nuts
Terminal cover
12-3. MUCF-C18UV-MUCF-C24UV-
OUTDOOR UNIT
OPERATING PROCEDUREPHOTOS
E1E1
1. Removing the cabinet
(1) Remove the screws fixing the cabinet.
(2) Remove the screw fixing the service panel.
(3) Remove the service panel, and remove the screw from
the insides.
(4) Remove the cabinet.
Photo 2
Screws
Photo 1
Service
panel
Screw
Screws
2. Removing the electrical parts
(1) Remove the cabinet . (Refer to 1)
(2) Remove the following parts .
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block
•Fan motor relay (X 1)(For MUCF-C24UV)
•Contactor (52 C) (For MUCF-C24UV)
Photo 3
Fan motor
relay
Contactor
Outdoor fan
capacitor
Compressor
capacitor
Terminal block
Fan motor lead
connector
41
OPERATING PROCEDURE
PHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1)
(2) Disconnect the connector to remove the clamp of fan motor
lead wire.
(3) Remove the propeller fan nut and remove the propeller fan.
(4) Remove screws fixing the fan motor.
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1)
(2) Remove the soundproof felt.
(3) Remove the terminal cover on the compressor.
(4) Disconnect lead wires from the glass terminal of the com-
pressor.(Refer to 2)
(5) Recover gas from the refrigerant circuit.
(6) Disconnect the welded part of the discharge pipe.
(7) Disconnect the welded part of the suction pipe.
(8) Remove nuts fixing the compressor.
(9) Remove the compressor.
NOTE
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
VANE MOTOR
INSTALLATION METAL (L)
AIR FILTER
GRILLE
FRONT PANEL ASSEMBLY
DRAIN PAN
FAN CASING (U)
FAN CASING (L)
UNION (GAS)
UNION (GAS)
INSTALLATION METAL (R)
UNION (LIQUID)
UNION (LIQUID)
BACK PANEL
NOZZLE
INDOOR HERT EXCHANGER
VANE
GRILLE CATCH
{12.7
{15.88
{9.52
{6.35
3PCS/SET
1
1
2
1
1
1
2
2
1
1
1
1
1
1
1
3
1
1
2
1
1
1
2
2
1
1
1
1
1
1
1
3
1
1
2
1
1
1
2
2
1
1
1
1
1
1
1
3
E1
MV
MCF-C13UV-
(WH)
E1
MCF-C18UV-
(WH)
E1
MCF-C24UV-
(WH)
MCF-C13UV -(WH)
MCF-C18UV -(WH)
MCF-C24UV -(WH)
E1
E1
E1
13-1. INDOOR UNIT
STRUCTURAL PARTS
1
2
3
4
15
1314
12
11
10
9
8
Part number that is circled is not shown in the illustration.
SIROCCO FAN
FAN MOTOR RUBBER MOUNT
INDOOR FAN MOTOR
INDOOR FAN MOTOR
INDOOR FAN MOTOR
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
RECEIVER P.C. BOARD
INDOOR COIL THERMISTOR
ELECTRONIC CONTROL P.C. BOARD
ELECTRONIC CONTROL P.C. BOARD
ELECTRONIC CONTROL P.C. BOARD
AUTO RESTART ASSEMBLY
SWITCH BOARD
VARISTOR
FUSE
OUTDOOR HEAT EXCHANGER
MOTOR SUPPORT
PROPELLER FAN
CABINET
GRILLE(OUT)
OUTDOOR FAN MOTOR
COMPRESSOR
COMPRESSOR RUBBER SET
BASE
STOP VALVE (GAS)
STOP VALVE (LIQUID)
COMPRESSOR CAPACITOR
OUTDOOR FAN CAPACITOR
TERMINAL BLOCK
FUSE
SERVICE PANEL
BACK PANEL
TOP PANEL
CAPILLARY TUBE
in Wiring
Diagram
MF
MC
C1
C2
TB
F
79108
Q'ty/unit
MUCF-C13UV-
1
1
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
11
E1
Remarks
RA6V33RE231VHSHT
3PCS/SET
{12.7
{6.35
30+ /440V AC
1.5+ /440V AC
3P
250V 2A
{ 3.0X{1.6X600
45
MUCF-C18UV MUCF-C24UV -
E1
E1
13-5. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
21
20
19
18
17
16
15
14
1
13
12
11
10
2
9
8
45 637
46
13-5. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
No.Part No.
1
E02 141 232
2
E02 141 521
3
E02 141 501
E02 140 515
4
E02 139 515
5
E02 138 506
E02 624 900
6
E02 517 900
E02 217 290
7
E02 176 290
8
E02 624 661
E02 627 662
9
E02 625 662
10
E02 141 245
E02 217 630
11
E02 147 630
12
E02 326 384
13
E02 288 343
14
E02 095 382
E02 197 374
15
E02 601 374
E07 056 374
16
E02 010 342
17
E02 138 351
18
E02 082 353
19
E02 229 381
E02 144 301
20
E02 147 301
21
E02 140 233
E02 683 937
22
E02 684 936
Part name
CABINET
GRILLE(OUT)
PROPELLER FAN
MOTOR SUPPORT
MOTOR SUPPORT
COMPRESSOR RUBBER SET
COMPRESSOR
COMPRESSOR
BASE
BASE
STOP VALVE(GAS)
STOP VALVE(LIQUID)
STOP VALVE(LIQUID)
SERVICE PANEL
OUTDOOR HEAT EXCHANGER
OUTDOOR HEAT EXCHANGER
CR SURGE ABSORBER
FAN MOTOR RELAY
FUSE
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
COMPRESSOR CONTACTOR
OUTDOOR FAN CAPACITOR
COMPRESSOR CAPACITOR
THERMOSTAT
OUTDOOR FAN MOTOR
OUTDOOR FAN MOTOR
BACK PANEL
CAPILLARY TUBE
CAPILLARY TUBE
Symbol
in Wiring
Diagram
MC
MC
CR
X1
F
TB
TB
TB2
52C
C2
C1
26F1
MF
MF
MUCF-C18UV-
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
Q'ty/unit
E1
MUCF-C24UV-
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
E1
Remarks
4RUBBERS/SET
PE33VPEHT
NE47VMHHT
{15.88
{6.35
{9.52
2A
3P
4P
3.0+/440VAC
50+/440VAC
RA6V50-OG
RA6V60-AC
{4.0X{2.4X1200
{4.0X{2.4X1100
47
OPTIONAL PARTS14
Remove the air
filter and the
deodorizing
filter together.
Separate the deodorizing
filter (gray sponge type)
from the air filter.
Remove the air
filter and the
air cleaning filter
together.
Separate the air
cleaning filter
(white bellows type)
from the air filter.
14-1. AIR CLEANING FILTER
● If the air cleaning filter is clogged, it may lower the unit’s capacity or cause condensation at the air outlet .
● The air cleaning filter is disposable . The standard usable term is about 4 months . However , if the color of the filter
turns to dark brown , replace soon .
Model
MCF-C13UVMCF-C18UVMCF-C24UV-
E1
E1
E1
Part No.
MAC - 1200 FT
14-2. DEODORIZING FILTER
● Clean the filter every two weeks . When it becomes too dirt , clean it more often .
● Replace the filter with a new one when its color can not be restored even after washing or when the filter becomes dark.
● Standard interval for the filter replacement is about 1 year .
Model
MCF-C13UVMCF-C18UVMCF-C24UV-
E1
E1
E1
Part No.
MAC - 1700 DF
HEAD OFFICE: MITSUBISHI DENKI BLDG.,2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2002 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD
Distributed in Apr. 2002. No.OB299 22
Made in Japan
New publication, effective Apr. 2002
Specifications subject to change without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.