Mitsubishi MSH-C18TV-E1, MSH-C24TV-E1, MUH-C18TV-E1, MUH-C24TV-E1 Service Manual

Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
HFC
utilized
R407C
SERVICE MANUAL
Wireless type Model
No. OB279
MSH-C18TV ­MSH-C24TV -
MSH-C18TV ­MSH-C24TV -
E1 E1
(WH)
(WH)
CONTENTS
10. SERVICE FUNCTIONS·····································33
11. TROUBLESHOOTING ······································35
12. DISASSEMBLY INSTRUCTIONS·····················47
13. PARTS LIST······················································53
14. OPTIONAL PARTS···········································58
· MUH-C18TV -
· MUH-C24TV -
1. TECHNICAL CHANGES····································2
2. PART NAMES AND FUNCTIONS······················5
3. SPECIFICATION·················································7
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS························ 9
6. WIRING DIAGRAM···········································11
8. PERFORMANCE CURVES······························15
9. MICROPROCESSOR CONTROL ····················23
E1E1
E1E1
Page 2
1
TECHNICAL CHANGES
MSH-C18SV - MSH-C18TV -
1. Rated voltage has changed to 230V.
2. Remote controller has changed.
• SLEEP MODE function has been removed.
• ECONO COOL operation has added.
• SWING button has been removed, but SWING MODE function has available by VANE CONTROLbutton.
3. Indoor electronic control P.C. board has changed.
MSH-C24TV -
New model
E1
MUH-C18SV - MUH-C18TV -
1. Path of heat exchanger has changed.
2. Temperature of defrosting control has changed. (-3: ➜ -2.7:)
3. Capillary tube has changed. [{3.0 o {1.6 o 750 (2pcs) {3.0 o {1.4 o 600 (2pcs), {3.0 o {2.0 o 500 {3.0 o {2.0 o 850, {3.0 o {2.0 o 350 has removed.]
4. Refrigerant filling capacity has changed. (1.70kg ➜ 1.60kg)
MUH-C24TV -
New model
E1
E1E1
E1E1
2
Page 3
INFORMATION FOR THE AIR CONDITIONER WITH R-407C REFRIGERANT
New Specification Previous Specification
The incompatible lubricant easily separates from refrigerant and makes the layer in the upper inside the suction muffler. The higher position of the returning oil hole enables to return the lubricant of the upper layer to the compressor.
Since refrigerant and lubricant are compatible each other, lubricant returns to the compressor through the lower position returning oil hole.
Compressor
Suction muffler
Returning oil hole
Lubricant
Refrigerant
Compressor
Suction muffler
Returning oil hole
Lubricant and Refrigerant
Compressor
-30 -20 -10 0 10 20
30
40 50 60
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
(MPa[Gauge])
R407C R22
Conversion chart of refrigerant temperature and pressure
Saturated liquid pressure
(:)
This room air conditioner adopts HFC refrigerant (R407C) which will never destroy the ozone layer. Pay attention to following points.
1 Take sufficient care not to allow water and other contaminations to enter the R407C refrigerant during storage and
installation, since it is more susceptible to contaminations than HCFC (R22) refrigerant.
2 Clean refrigerant pipings should be used. 3 Composition change may occur in R407C since it is a mixed refrigerant. When charging, charge liquid refrigerant to
prevent composition change.
4 Be especially careful when managing the tools.
If dust, dirt, or water mixes in the refrigerant cycle, it may cause decrease of performance.
Refrigerant Composition (Ratio)
R32: R125: R134a (23%:25%:52%) Refrigerant handling Chlorine Safety group (ASHRAE) Molecular weight Boiling point (:) Steam pressure [25:](Mpa [Gauge]) Saturated steam density [25:](Kg/K)
Refrigerant
Combustibility ODP w1 GWP w2 Refrigerant charge method Additional charge on leakage Kind Color Smell
Lubricant
w1:Ozone Destruction Parameter : based on CFC11 w2 :Global Warmth Parameter : based on CO
2
New refrigerant
R407C
Non-azeotropic refrigerant
Not included
A1/A1
86.2
-43.6
0.9177
42.5
Non combustible
0
1530
From liquid phase in cylinder
Impossible
Incompatible oil
Non Non
Previous refrigerant
R22
HCFC22 (100%)
Single refrigerant
Included
A1
86.5
-40.8
0.94
44.4
Non combustible
0.055 1700
Gas phase
Possible
Compatible oil
Light yellow
Non
NOTE : The unit of pressure has been changed to MPa on the
international system of units(SI unit system).
The conversion factor is: 1(MPa[Gauge]) =10.2(kgf/
3
ff
[Gauge])
Page 4
1.Tools dedicated for the air conditioner with R407C refrigerant
R407C tools Can R22 tools be used?
Gas leak detector
A gauge manifold with a sight glass is recommended for charging the liquid refregerant.
Hose material have been changed to improve the pressure resistance.
Dedicated for HFC refrigerant.
Description
Provided to prevent the back flow of oil. This adapter enables you to use existing vacuum pumps.
No
No
No
Yes Yes
New
New
Gauge manifold
Charge hose
Torque wrench Flare tool
Vacuum pump adapter
Electronic scale for refrigerant charging
Use the electronic control scale for measuring the R407C.
Electronic scale for refrigerant charging
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder for R407C with siphon
Refrigerant (liquid)
Gage manifold
Outdoor unit
Indoor unit
Union
Liquid pipe Gas pipe
Service port
Stop valve
Charge hose
The following tools are required for R407C refrigerant. Some R22 tools can be substituted for R407C tools. Do not use tools that are used with R22 refrigerant in order to avoid mixing oils.
2.Refrigerant piping
Do not use copper pipes which are broken, deformed or discoloured. In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulfur and oxides, or have no dust/ dirt, shaving particles, oil, moisture or any other contamination.
•If there is a large amount of residual oil inside the piping and joints, deterioration of the refrigerant oil will result.
3.Refrigerant oil
Apply the specific refrigeration oil (accessories) to the flare and the union seat surfaces.
4.Air purge
Use the vacuum pump for air purge to protect environments, and to avoid changing the composition of refrigerant.
5.Additional charge
For additional charging, charge the refrigerant with liquid phase slowly using a gas cylinder. If the refrigerant is charged with gas phase, the composition of refrigerant will change. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. If liquid refrigerant is rapidly charged at once, the compressor may be locked.
NOTE: 1. The R407C is mixed refrigerant which consist of three different kinds of evaporative temperature. As a result, the
R407C occurs the change of composition.
2. Additional refrigerant charge has been changed by change of refrigerant.(R22 ➔ R407C) R22 : <MUH-18 type> 50g/m R407C : <MUH-C18TV> 35g/m
: <MUH-24 type> 65g/m R407C : <MUH-C24TV> 45g/m
4
Page 5
2
1 2 3 4 5 6 7
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller mouting hardware Fixing screw for 3 o 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Felt tape (Used for left or left-rear piping)
1 6 1 2 2 1 1
MSH-C18TV­MSH-C24TV-
E1 E1
8
9
Drain socket Drain cap {33 Drain cap {16
1 6
1 2 1
MUH-C18TV-
E1
MUH-C24TV-
E1
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSH-C18TV ­MSH-C24TV -
(When the grille is open)
E1
E1
Front panel
OUTDOOR UNIT
MUH-C18TV -
ACCESSORIES
Indoor unit
E1
Air inlet
(back and side)
Piping
Drainage hose
Air outlet
Drain outlet
MUH-C24TV -
Air inlet
E1
Air outlet
Outdoor unit
5
Page 6
REMOTE CONTROLLER
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
I FEEL
COOL
HEAT
DRY
PM
CLOCK
AM
RESET CLOCK
Open the front lid.
Signal transmitting section
Operation display section
OPERATE /STOP
(ON /OFF)button
TEMPERATURE buttons
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE CONTROL button
CLOCK SET button
MSH-C18TV ­MSH-C24TV -
E1
E1
6
Page 7
3
Indoor model
Function
Power supply
Capacity Dehumidification Air flow(High) Power outlet Running current Power input Auxiliary heater Power factor Starting current Fan motor current
Model Winding resistance(at20:) Dimensions WOHOD Weight Air direction Sound level (High) Fan speed (High) Fan speed regulator Thermistor RT11(at25:) Thermistor RT12(at25:) Outdoor model Air flow Compressor motor current Fan motor current Model Output Winding resistance(at20:) Model Winding resistance(at20:) Dimensions WOHOD Weight Sound level Fan speed (High) Fan speed regulator Refrigerant filling capacity(R407C) Refrigerating oil (Model) Thermistor
RT61(at0:)
Thermistor
RT63(at0:)
kW
r/h
K /h
A A
W
A(kW)
%
A A
"
mm
kg
dB
rpm
k" k"
K /h
A A
W
"
"
mm
kg
dB
rpm
kg
cc k" k"
MSH-C18TV -
E1
Single phase
230V, 50Hz
756
15
— 98 55
0.25
RA4V27-EF WHT-BLK 183.8 BLK-RED 250.5 1,015O320O190
14
5
42
1,180
3 10 10
MUH-C18TV -
E1
2,196
0.39
PE-36VPEHT
1,600 C-R 1.06 C-S 2.03
RA6V50-OG
WHT-BLK 116.4
BLK-RED 111.0
850o605o290
54 52
828
1
1.60
1,100 (NEO22)
33.18 —
Cooling
5.2
2.4
9.4
2,110
2.46
8.76
Heating
6.0 —
9.7
2,180
2.75
9.06
MSH-C24TV -
E1
Single phase
230V, 50Hz
816
25
83
0.29
RA4V27-EE WHT-BLK 183.3 BLK-RED 250.5 1,015O320O190
14
5
45
1,260
3 10 10
MUH-C24TV -
E1
2,700
0.58
NE-47VMHHT
2,200 C-R 0.67 C-S 2.02
RA6V85-AA
WHT-BLK 62.7 BLK-YLW 30.2
YLW-RED 62.9
870o850o295
71 53
735
2
2.00
1,400 (NEO22)
33.18
33.18
Cooling
6.3
3.0
12.8
2,850
97
2.21
11.93
Heating
7.5 —
13.7
3,020
96
2.48
12.87
Electrical
data
Fan
motor
Special
remarks
Compressor
Electrical
data
Fan
motor
Special
remarks
Capacity
Coefficient of performance(C.O.P)
Capacity
SPECIFICATION
NOTE:Test conditions are based on JIS C 9612.
Cooling : Indoor Dry-bulb temperature 27°C / Wet-bulb temperature 19°C
Outdoor Dry-bulb temperature 35°C / Wet-bulb temperature (24°C)
Heating : Indoor Dry-bulb temperature 20°C / Wet-bulb temperature
Outdoor Dry-bulb temperature 7°C / Wet-bulb temperature 6°C
7
Page 8
4
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
42
SPL(dB(A)) LINE
High
NOTCH
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15.5:
90
80
70
60
50
40
30
20
10
63 125 250 500 1000 2000 4000 8000
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
BAND CENTER FREQUENCIES, Hz
Test conditions, Cooling : Dry-bulb temperature 27: Wet-bulb temperature 19:
APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE
45
SPL(dB(A)) LINE
High
NOTCH
Heating : Dry-bulb temperature 20: Wet-bulb temperature 15.5:
NOISE CRITERIA CURVES
MSH-C18TV-
E1
MSH-C24TV-
E1
MUH-C18TV-
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
90
80
E1
NOTCH
High
SPL(dB(A)) LINE
52
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
MUH-C24TV-
Test conditions, Cooling : Dry-bulb temperature 35: Wet-bulb temperature 24:
Heating : Dry-bulb temperature 7: Wet-bulb temperature 6:
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
OCTAVE BAND SOUND PRESSURE LEVEL, dB re 0.0002 MICRO BAR
8
E1
NOTCH
SPL(dB(A)) LINE
High
90
80
70
60
50
40
30
APPROXIMATE
20
THRESHOLD OF HEARING FOR CONTINUOUS NOISE
10
63 125 250 500 1000 2000 4000 8000
BAND CENTER FREQUENCIES, Hz
53
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
Page 9
5
OUTLINES AND DIMENSIONS
MSH-C18TV ­MSH-C24TV -
INDOOR UNIT
Unit: mm
E1
E1
995
60
40
4holes 1120
150 648 217
Indoor unit
20
320
Wireless remote controller
MUH-C18TV -
OUTDOOR UNIT
Drainage hole [16.2
35
90
248
Air in
58
162
E1
355
350
1015
Air in
20
19
19077550
Power supply cord Lead to right 2m Lead to left 1m
290
Installation plate
Air in
Air out
310
345
450 450
5190
100mm or more
352438
Installation plate
Liquid line [8-0.5m Gas line [12-0.43m
{
Insulation [50 O.D
[28 I.D
Drain hose [16 Insulation [28
100mm or more
500mm or more
254
3 297
Wall hole [75
100mm or more
350mm or more
605
Drainage 3holes [33
292
20
Air out
183
500 850
50
74
157
30
100
Service panel
Liquid refrigerant pipe joint
Refregerant pipe (flared) [6.35
35-
30-
Gas refregerant pipe joint
161
9
Refregerant pipe (flared) [15.88
Page 10
100 10
1000For 10 units or less
200
Outdoor Unit-Necessary surrounding clearance (Concentrated installation)
The upper side must be open.
Outdoor Unit-Necessary surrounding clearance
200
10
10
10
Note:Allow adequate upper clearance
150
500
500
Service space
Front opening
R20
R20
25 max.
Standard bolt length
65
Front right piping holes­detail figures
80
17
12
R6
23
33
Side air intake
724295
Outlet guide installation hole
302
Air intake
Air intake
Air outlet
870
185 185
500
330
362
1715
39.5 27.5
Terminal block for indoor and outdoor unit connection
Handle for moving
179 524
441
445
450
468
553
850
40 60524
Service panel
Refrigerant-pipe flared connection [15.88
Refrigerant-pipe flared connection [9.52
Knock out hole for front piping
(refrigerant,drainage and wiring)
42
45
104
33
Bottom piping hole
2-U-shaped notched holes
Drainage hole [33
Drainage hole [33
2-12o23 Oval holes (standard bolt M10)
Handle for moving
A
Handle for moving
138
95
Rear piping hole
Rear fresh air intake
A
Knock out hole for right piping
(refrigerant,drainage and wiring)
60
120
4553
Knock out holes for power line 2-[27
MUH-C24TV-
E1
OUTDOOR UNIT
Unit: mm
10
Page 11
6
WIRING DIAGRAM
MSH-C18TV -
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
POWER SUPPLY CORD ~/N 230V 50Hz
PE
CIRCUIT BREAKER
SYMBOL
C11
DSAR
F11 F12
HIC1
NOTES:
INDOOR FAN CAPACITOR SURGE ABSORBER FUSE (3.15A) THERMAL FUSE (93:) DC/DC CONVERTER
1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
MUH-C18TV -
E1
MODEL WIRING DIAGRAM
TB
L
BRN
3
N
2
NAME
BRN
BLU
BLU
WHT
BRN
DSAR
GRN/YLW
RED
F12
BLU BLU
GRN/YLW
SYMBOL
12V
230V~
IC141
MF MV
NR11
RT11
: Connector
E1
MODEL WIRING DIAGRAM
HIC1
4
52C
3
TRANS
F11
ELECTRONIC CONTROL P.C. BOARD
REMOTE CONTROLLER
SYMBOL
RT12
2
BLU
1
LD1
CN
102
3
DISPLAY P.C. BOARD
HYBRID IC
CN
151
MV
CN201
5
NAME
3 1
CN
101
3
RECEIVER P.C. BOARD
INDOOR FAN MOTOR (INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMISTOR
TB
52C
IC141
NR11
C11
CN
112
CN
121
CN211
4 2 1
CN
111
3
RT12
BRN YLW GRY WHT RED BLK
RT11
NAME INDOOR COIL THERMISTOR TERMINAL BLOCK CONTACTOR
VG79B068H01
MF
OUTDOOR UNIT
12V
230V~
FROM INDOOR UNIT
CONNECTING
SYMBOL
C1
COMPRESSOR CAPACITOR
C65
DSAR
F61
IC881
NOTES:
OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (2A) DC/DC CONVERTER
1.About the indoor side electric wiring refer to the indoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
NAME
TB
3
N
2
: Connector
SR61
SYMBOL
52C
VLT
X62
S
TB
X62
21S4
52C
VLT
C65
CN711
MC
RED RED
1
WHT
2 3
BLK
4
C
R
MF
1
ORN
2
WHT
3
BLK
4
NAME TERMINAL BLOCK R.V. COIL RELAY R.V. COIL COMPRESSOR CONTACTOR
X62
C1
21S4
BLK
NR61
BLK
WHTNO COM
RED BLK
RT61
CN730
RED
BLU
DSAR
GRN/YLW
WHT
WHT
WHT
BLU
SYMBOL
MC
MF NR61 RT61 SR61
CN661 CN721 CN720
1
F61
TAB21
IC881
TRANS
TAB20
DEICER P.C. BOARD
52C
NAME COMPRESOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DEFROST THERMISTOR SOLID STATE RELAY
SG79B966H01
11
Page 12
MSH-C24TV -
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
230V~
POWER SUPPLY CORD ~/N 230V 50Hz
PE
CIRCUIT BREAKER
E1
MODEL WIRING DIAGRAM
TB
3
N
2 L
GRN/YLW
BLU
BRN
RED
BLU
WHT
WHT
F12
1
DSAR
GRN/YLW
BLU BLU
LD1
2 1
102
CN
WHT
CN
151
3
MV
DISPLAY P.C. BOARD
CN201
5
3 1
RECEIVER P.C. BOARD
HIC1
4
52C
3
TRANS
F11
CN
ELECTRONIC CONTROL P.C. BOARD
101
3
REMOTE CONTROLLER
IC141
NR11
C11
CN
112
CN
111
CN
121
CN211
4 2 1
RT12
RT11
3
BRN YLW GRY
MF
WHT RED BLK
SYMBOL
C11
DSAR
F11 F12
HIC1
NOTES:
INDOOR FAN CAPACITOR SURGE ABSORBER FUSE (3.15A) THERMAL FUSE (93;) DC/DC CONVERTER
1.About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
MUH-C24TV -
OUTDOOR UNIT
TB
3
12V
N
2
230V
~
FROM INDOOR UNIT
CONNECTING
GRN/YLW
NOTES:
1.Use copper conductors only (For field wiring).
2.Since the indoor and outdoor unit connecting wires have polarity, connect them according to the numbers (3,N,2).
3.Symbols below indicate. :Terminal block, :Connector
NAME
SYMBOL
IC141
MF
MV NR11 RT11
: Connector
E1
MODEL WIRING DIAGRAM
RT61
CN661
WHT
DSAR
RT63
CN662
SR62 SR61
X62
X52
T61
BLU
WHT WHT
CZ
WHT WHT
BLU
2
1
52C
NAME HYBRID IC INDOOR FAN MOTOR (INNER FUSE) VANE MOTOR VARISTOR ROOM TEMPERATURE THERMISTOR
WHT
C
SYMBOL
BLU
MF
YLW
ORN
WHT
BLK
YLW
BLK
WHT
321
CN711
NR61
A2
RED
12
RED
ORN
X62
COM
X52
COM
52C
6543
DEICER P.C. BOARD
C2
CN721
1 2
21S4
3
NO
TAB52
NO
F61
1 3 5
CN730
BLU
RED
C1
RED
S
MC
BLK
R
A1
SYMBOL
RT12
TB
52C
CZ C1 C2
DSAR
F61
MC
MF NR61 RT61 RT63 SR61 SR62
TB T61 X52 X62
21S4
52C
NAME INDOOR COIL THERMISTOR TERMINAL BLOCK CONTACTOR
VG79B069H01
NAME CZ SURGE ABSORBER COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR SURGE ABSORBER FUSE (3.15A) COMPRESSOR (INNER PROTECTOR) OUTDOOR FAN MOTOR (INNER PROTECTOR) VARISTOR DEFROST THERMISTOR AMBIENT TEMPERATURE THERMISTOR SOLID STATE RELAY SOLID STATE RELAY TERMINAL BLOCK TRANSFORMER CONTACTOR R. V. COIL RELAY R. V. COIL COMPRESSOR CONTACTOR
SG79J155H01
12
Page 13
7
REFRIGERANT SYSTEM DIAGRAM
MSH-C18TV -
Unit:mm
E1
MUH-C18TV -
E1
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Distributor
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Muffler
Stop valve (with service port)
Strainer
Stop valve
4- way valve
Capillary tube
[3.0o[2.0o850
Compressor
Check valve
OUTDOOR UNIT
Strainer
Defrost thermistor RT61
Refrigerant flow in cooling Refrigerant flow in heating
Outdoor heat exchanger
Capillary tube
[3.0o[1.4o600
(2 pcs)
R.V. coil Heating ON Cooling OFF
MSH-C24TV -
INDOOR UNIT
Indoor coil
Indoor heat exchanger
Room temperature thermistor RT11
thermistor RT12
E1
Distributor
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Stop valve
Refrigerant pipe [9.52 (with heat insulator)
Muffler
Stop valve (with service port)
Strainer
4- way valve
Receiver
Strainer
Compressor
Capillary tube [3.0X[2.0X450
Unit:mm
MUH-C24TV -
OUTDOOR UNIT
Outdoor heat exchanger
Defrost thermistor RT61
Ambient tempera­ture thermistor RT63
R.V. coil Heating ON
Cooling OFF Refrigerant flow in cooling Refrigerant flow in heating
E1
13
Page 14
Model
Piping size O.D : mm Length of connecting pipe : m
Refrigerant piping
Max. length : m
A
15
Indoor unit
Gas 0.43
Liquid 0.5
Gas
15.88
Liquid
6.35
9.52
Outdoor unit
Gas 0
Liquid 0
MSH-C18TV - E1 MUH-C18TV - E1
MSH-C24TV - E1 MUH-C24TV - E1
Indoor unit
wMax. Height
difference: 5m
A
Refrigerant Piping Max. Length
w Height difference should be within 5m regardless of which unit, indoor or outdoor position is high.
Outdoor unit
Model
MSH-C18TV -
E1
MUH-C18TV - E1
Refrigerant piping length (one way)
Outdoor unit precharged
1600
15m
280
7m
0
10m
105
MAX. REFRIGERANT PIPING LENGTH
Model
MSH-C24TV -
E1
MUH-C24TV - E1
Refrigerant piping length (one way)
Outdoor unit precharged
2000
15m
360
7m
0
10m
135
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R407C : g)
Calculation : Xg=35g/m (Refrigerant piping length (m)–7)
Calculation : Xg=45g/m (Refrigerant piping length (m)–7)
14
Page 15
8
11.4
7.4
8.3
9.3
10.4
12.5
13.5
8.6
9.8
11.0
12.2
14.9
MSH-C18TV - E1
MSH-C24TV - E1
Wet-and dry-bulb thermometers
Wet-and dry-bulb thermometers
PERFORMANCE CURVES
MSH-C18TV - MUH-C18TV ­MSH-C24TV - MUH-C24TV -
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been pro­vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 264V
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature : °CWB (2) Indoor outlet air wet-bulb temperature : °CWB (3) Outdoor intake air dry-bulb temperature : °CDB (4) Total input: W (5) Indoor intake air dry-bulb temperature : °CDB (6) Outdoor intake air wet-bulb temperature : °CWB (7) Total input : W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the differ-
ence between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
, 50Hz
E1E1 E1E1
Cooling
}
Heating
}
How to measure the indoor air wet-bulb/dry-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
INDOOR UNIT
OUTDOOR UNIT
15
Page 16
31.1
28.7
26.3
24.0
21.6
19.2
16.8
14.4
36.1
33.3
30.5
27.7
25.0
22.2
19.4
16.6
MSH-C18TV - E1
MSH-C24TV - E1
NOTE:The above curves are for the heating operation without any frost and defrosting.
15 20
50
2560 30
70(%)
35(:)
0.3
0.4
0.5
0.6
0.7
18 32
230V
7
6
5
4
3
18 32
230V
15 20
50
25 60
30
70(%)
35(:)
6
7
8
9
10
11
15 20
50
25 60
30
70(%)
35(:)
0.2
0.3
0.4
0.5
0.6
0.7
18
32
230V
7
6
5
4
3
15 20
50
2560 30
70(%)
35(:)
8
9
10
11
12
13
18 32
230V
230V
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
11
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
20 25
Relative humidity(%)
50 60
30 70
22
Air flow should be set at MAX.
33
The unit of pressure has been changed to MPa on the international system of units(SI unit system). The conversion factor is : 1(MPa [Gauge]) =10.2(kgf/ff[Gauge])
(kgf/F[Gauge])(MPa[Gauge])
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
(kgf/F[Gauge])(MPa[Gauge])
MUH-C18TV -
MUH-C24TV -
E1
MUH-C18TV -
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
E1
MUH-C24TV -
E1
E1
Outdoor low pressure
Ambient temperature(˚C) Ambient humidity(%)
Outdoor unit current (A)
Ambient temperature(˚C) Ambient humidity(%)
16
Page 17
HEAT operation
5 10152025
12
13
14
15
16
7
21
230V
(:)
Condition indoor:Dry bulb temperature 20.0°C
Wet bulb temperature 14.5°C
MUH-C18TV -
13
E1
Outdoor:Dry bulb temperature 7,15,20°C
Wet bulb temperature 6,12,14.5°C
12
11
10
230V
Outdoor unit current (A)
9
5 10152025
7
21
Ambient temperature(˚C)
MUH-C24TV -
E1
Outdoor unit current (A)
(:)
Ambient temperature(˚C)
17
Page 18
PERFORMANCE DATA COOL operation
MSH-C18TV - : MUH-C18TV - (230V)
CAPACITY : 5.2(KW) SHF : 0.68 INPUT : 2110(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 18 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
6.11
6.37
6.11
6.37
6.63
6.11
6.37
6.63
6.11
6.37
6.63
6.97
6.11
6.37
6.63
6.97
6.11
6.37
6.63
6.97
7.18
6.11
6.37
6.63
6.97
7.18
6.11
6.37
6.63
6.97
7.18
6.11
6.37
6.63
6.97
7.18
6.11
6.37
6.63
6.97
7.18
6.11
6.37
6.63
6.97
7.18
6.11
6.37
6.63
6.97
7.18
21 2725
1688
0.50
3.06 1772
0.38
2.42 1688
0.54
3.30 1772
0.42
2.68 1836
0.30
1.99 1688
0.58
3.54 1772
0.46
2.93 1836
0.34
2.25 1688
0.62
3.79 1772
0.50
3.19 1836
0.38
2.52 1920
0.26
1.81 1688
0.66
4.03 1772
0.54
3.44 1836
0.42
2.78 1920
0.30
2.09 1688
0.70
4.28 1772
0.58
3.69 1836
0.46
3.05 1920
0.34
2.37 2026
0.22
1.58 1688
0.74
4.52 1772
0.62
3.95 1836
0.50
3.32 1920
0.38
2.65 2026
0.26
1.87 1688
0.78
4.77 1772
0.66
4.20 1836
0.54
3.58 1920
0.42
2.93 2026
0.30
2.15 1688
0.82
5.01 1772
0.70
4.46 1836
0.58
3.85 1920
0.46
3.21 2026
0.34
2.44 1688
0.86
5.25 1772
0.74
4.71 1836
0.62
4.11 1920
0.50
3.48 2026
0.38
2.73 1688
0.90
5.50 1772
0.78
4.97 1836
0.66
4.38 1920
0.54
3.76 2026
0.42
3.01 1688
0.94
5.74 1772
0.82
5.22 1836
0.70
4.64 1920
0.58
4.04 2026
0.46
3.30
E1E1
5.85
6.11
5.85
6.11
6.40
5.85
6.11
6.40
5.85
6.11
6.40
6.71
5.85
6.11
6.40
6.71
5.85
6.11
6.40
6.71
6.97
5.85
6.11
6.40
6.71
6.97
5.85
6.11
6.40
6.71
6.97
5.85
6.11
6.40
6.71
6.97
5.85
6.11
6.40
6.71
6.97
5.85
6.11
6.40
6.71
6.97
5.85
6.11
6.40
6.71
6.97
2.93
2.32
3.16
2.57
1.92
3.39
2.81
2.17
3.63
3.06
2.43
1.74
3.86
3.30
2.69
2.01
4.10
3.54
2.94
2.28
1.53
4.33
3.79
3.20
2.55
1.81
4.56
4.03
3.45
2.82
2.09
4.80
4.28
3.71
3.09
2.37
5.03
4.52
3.97
3.35
2.65
5.27
4.77
4.22
3.62
2.93
5.50
5.01
4.48
3.89
3.21
OUTDOOR DB(:)
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.66
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1772 1878 1772 1878 1952 1772 1878 1952 1772 1878 1952 2026 1772 1878 1952 2026 1772 1878 1952 2026 2131 1772 1878 1952 2026 2131 1772 1878 1952 2026 2131 1772 1878 1952 2026 2131 1772 1878 1952 2026 2131 1772 1878 1952 2026 2131 1772 1878 1952 2026 2131
18
5.62
5.93
5.62
5.93
6.24
5.62
5.93
6.24
5.62
5.93
6.24
6.55
5.62
5.93
6.24
6.55
5.62
5.93
6.24
6.55
6.86
5.62
5.93
6.24
6.55
6.86
5.62
5.93
6.24
6.55
6.86
5.62
5.93
6.24
6.55
6.86
5.62
5.93
6.24
6.55
6.86
5.62
5.93
6.24
6.55
6.86
5.62
5.93
6.24
6.55
6.86
2.81
2.25
3.03
2.49
1.87
3.26
2.73
2.12
3.48
2.96
2.37
1.70
3.71
3.20
2.62
1.97
3.93
3.44
2.87
2.23
1.51
4.16
3.68
3.12
2.49
1.78
4.38
3.91
3.37
2.75
2.06
4.61
4.15
3.62
3.01
2.33
4.83
4.39
3.87
3.28
2.61
5.05
4.62
4.12
3.54
2.88
5.28
4.86
4.37
3.80
3.16
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.66
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1857 1920 1857 1920 2005 1857 1920 2005 1857 1920 2005 2089 1857 1920 2005 2089 1857 1920 2005 2089 2194 1857 1920 2005 2089 2194 1857 1920 2005 2089 2194 1857 1920 2005 2089 2194 1857 1920 2005 2089 2194 1857 1920 2005 2089 2194 1857 1920 2005 2089 2194
5.41
5.72
5.41
5.72
5.98
5.41
5.72
5.98
5.41
5.72
5.98
6.34
5.41
5.72
5.98
6.34
5.41
5.72
5.98
6.34
6.66
5.41
5.72
5.98
6.34
6.66
5.41
5.72
5.98
6.34
6.66
5.41
5.72
5.98
6.34
6.66
5.41
5.72
5.98
6.34
6.66
5.41
5.72
5.98
6.34
6.66
5.41
5.72
5.98
6.34
6.66
2.70
2.17
2.92
2.40
1.79
3.14
2.63
2.03
3.35
2.86
2.27
1.65
3.57
3.09
2.51
1.90
3.79
3.32
2.75
2.16
1.46
4.00
3.55
2.99
2.41
1.73
4.22
3.78
3.23
2.66
2.00
4.43
4.00
3.47
2.92
2.26
4.65
4.23
3.71
3.17
2.53
4.87
4.46
3.95
3.43
2.80
5.08
4.69
4.19
3.68
3.06
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.66
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
1941 2005 1941 2005 2089 1941 2005 2089 1941 2005 2089 2194 1941 2005 2089 2194 1941 2005 2089 2194 2258 1941 2005 2089 2194 2258 1941 2005 2089 2194 2258 1941 2005 2089 2194 2258 1941 2005 2089 2194 2258 1941 2005 2089 2194 2258 1941 2005 2089 2194 2258
Page 19
PERFORMANCE DATA COOL operation
2068 2152 2068 2152 2237 2068 2152 2237 2068 2152 2237 2321 2068 2152 2237 2321 2068 2152 2237 2321 2405 2068 2152 2237 2321 2405 2068 2152 2237 2321 2405 2068 2152 2237 2321 2405 2068 2152 2237 2321 2405 2068 2152 2237 2321 2405 2068 2152 2237 2321 2405
E1E1
4.68
4.99
4.68
4.99
5.30
4.68
4.99
5.30
4.68
4.99
5.30
5.62
4.68
4.99
5.30
5.62
4.68
4.99
5.30
5.62
5.93
4.68
4.99
5.30
5.62
5.93
4.68
4.99
5.30
5.62
5.93
4.68
4.99
5.30
5.62
5.93
4.68
4.99
5.30
5.62
5.93
4.68
4.99
5.30
5.62
5.93
4.68
4.99
5.30
5.62
5.93
2.34
1.90
2.53
2.10
1.59
2.71
2.30
1.80
2.90
2.50
2.02
1.49
3.09
2.70
2.23
1.68
3.28
2.90
2.44
1.91
1.30
3.46
3.10
2.65
2.13
1.54
3.65
3.29
2.86
2.36
1.78
3.84
3.49
3.08
2.58
2.02
4.02
3.69
3.29
2.81
2.25
4.21
3.89
3.50
3.03
2.49
4.40
4.09
3.71
3.26
2.73
OUTDOOR DB(:)
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.66
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
2194 2258 2194 2258 2363 2194 2258 2363 2194 2258 2363 2427 2194 2258 2363 2427 2194 2258 2363 2427 2511 2194 2258 2363 2427 2511 2194 2258 2363 2427 2511 2194 2258 2363 2427 2511 2194 2258 2363 2427 2511 2194 2258 2363 2427 2511 2194 2258 2363 2427 2511
19
4.50
4.81
4.50
4.81
5.12
4.50
4.81
5.12
4.50
4.81
5.12
5.46
4.50
4.81
5.12
5.46
4.50
4.81
5.12
5.46
5.75
4.50
4.81
5.12
5.46
5.75
4.50
4.81
5.12
5.46
5.75
4.50
4.81
5.12
5.46
5.75
4.50
4.81
5.12
5.46
5.75
4.50
4.81
5.12
5.46
5.75
4.50
4.81
5.12
5.46
5.75
2.25
1.83
2.43
2.02
1.54
2.61
2.21
1.74
2.79
2.41
1.95
1.42
2.97
2.60
2.15
1.64
3.15
2.79
2.36
1.86
1.26
3.33
2.98
2.56
2.07
1.49
3.51
3.17
2.77
2.29
1.72
3.69
3.37
2.97
2.51
1.95
3.87
3.56
3.18
2.73
2.18
4.05
3.75
3.38
2.95
2.41
4.23
3.94
3.59
3.17
2.64
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.66
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
2237 2321 2237 2321 2405 2237 2321 2405 2237 2321 2405 2479 2237 2321 2405 2479 2237 2321 2405 2479 2564 2237 2321 2405 2479 2564 2237 2321 2405 2479 2564 2237 2321 2405 2479 2564 2237 2321 2405 2479 2564 2237 2321 2405 2479 2564 2237 2321 2405 2479 2564
4.32
4.63
4.32
4.63
4.94
4.32
4.63
4.94
4.32
4.63
4.94
5.30
4.32
4.63
4.94
5.30
4.32
4.63
4.94
5.30
5.56
4.32
4.63
4.94
5.30
5.56
4.32
4.63
4.94
5.30
5.56
4.32
4.63
4.94
5.30
5.56
4.32
4.63
4.94
5.30
5.56
4.32
4.63
4.94
5.30
5.56
4.32
4.63
4.94
5.30
5.56
MSH-C18TV - : MUH-C18TV - (230V)
CAPACITY : 5.2(KW) SHF : 0.68 INPUT : 2110(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 18 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT46Q SHC SHF INPUT
5.10
5.36
5.10
5.36
5.67
5.10
5.36
5.67
5.10
5.36
5.67
5.98
5.10
5.36
5.67
5.98
5.10
5.36
5.67
5.98
6.29
5.10
5.36
5.67
5.98
6.29
5.10
5.36
5.67
5.98
6.29
5.10
5.36
5.67
5.98
6.29
5.10
5.36
5.67
5.98
6.29
5.10
5.36
5.67
5.98
6.29
5.10
5.36
5.67
5.98
6.29
35 4340
0.50
2.55
0.38
2.04
0.54
2.75
0.42
2.25
0.30
1.70
0.58
2.96
0.46
2.46
0.34
1.93
0.62
3.16
0.50
2.68
0.38
2.15
0.26
1.55
0.66
3.36
0.54
2.89
0.42
2.38
0.30
1.79
0.70
3.57
0.58
3.11
0.46
2.61
0.34
2.03
0.22
1.38
0.74
3.77
0.62
3.32
0.50
2.83
0.38
2.27
0.26
1.64
0.78
3.97
0.66
3.53
0.54
3.06
0.42
2.51
0.30
1.89
0.82
4.18
0.70
3.75
0.58
3.29
0.46
2.75
0.34
2.14
0.86
4.38
0.74
3.96
0.62
3.51
0.50
2.99
0.38
2.39
0.90
4.59
0.78
4.18
0.66
3.74
0.54
3.23
0.42
2.64
0.94
4.79
0.82
4.39
0.70
3.97
0.58
3.47
0.46
2.89
2.16
1.76
2.33
1.94
1.48
2.50
2.13
1.68
2.68
2.31
1.88
1.38
2.85
2.50
2.07
1.59
3.02
2.68
2.27
1.80
1.22
3.19
2.87
2.47
2.02
1.45
3.37
3.05
2.67
2.23
1.67
3.54
3.24
2.87
2.44
1.89
3.71
3.42
3.06
2.65
2.11
3.88
3.61
3.26
2.86
2.34
4.06
3.79
3.46
3.08
2.56
0.50
0.38
0.54
0.42
0.30
0.58
0.46
0.34
0.62
0.50
0.38
0.26
0.66
0.54
0.42
0.30
0.70
0.58
0.46
0.34
0.22
0.74
0.62
0.50
0.38
0.26
0.78
0.66
0.54
0.42
0.30
0.82
0.70
0.58
0.46
0.34
0.86
0.74
0.62
0.50
0.38
0.90
0.78
0.66
0.54
0.42
0.94
0.82
0.70
0.58
0.46
2279 2384 2279 2384 2448 2279 2384 2448 2279 2384 2448 2532 2279 2384 2448 2532 2279 2384 2448 2532 2616 2279 2384 2448 2532 2616 2279 2384 2448 2532 2616 2279 2384 2448 2532 2616 2279 2384 2448 2532 2616 2279 2384 2448 2532 2616 2279 2384 2448 2532 2616
Page 20
PERFORMANCE DATA COOL operation
MSH-C24TV - : MUH-C24TV - (230V)
CAPACITY : 6.3(KW) SHF : 0.67 INPUT : 2850(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 18 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT30Q SHC SHF INPUT
7.40
7.72
7.40
7.72
8.03
7.40
7.72
8.03
7.40
7.72
8.03
8.44
7.40
7.72
8.03
8.44
7.40
7.72
8.03
8.44
8.69
7.40
7.72
8.03
8.44
8.69
7.40
7.72
8.03
8.44
8.69
7.40
7.72
8.03
8.44
8.69
7.40
7.72
8.03
8.44
8.69
7.40
7.72
8.03
8.44
8.69
7.40
7.72
8.03
8.44
8.69
21 2725
2280
0.49
3.63 2394
0.37
2.86 2280
0.53
3.92 2394
0.41
3.16 2480
0.29
2.33 2280
0.57
4.22 2394
0.45
3.47 2480
0.33
2.65 2280
0.61
4.52 2394
0.49
3.78 2480
0.37
2.97 2594
0.25
2.11 2280
0.65
4.81 2394
0.53
4.09 2480
0.41
3.29 2594
0.29
2.45 2280
0.69
5.11 2394
0.57
4.40 2480
0.45
3.61 2594
0.33
2.79 2736
0.21
1.83 2280
0.73
5.40 2394
0.61
4.71 2480
0.49
3.94 2594
0.37
3.12 2736
0.25
2.17 2280
0.77
5.70 2394
0.65
5.02 2480
0.53
4.26 2594
0.41
3.46 2736
0.29
2.52 2280
0.81
6.00 2394
0.69
5.33 2480
0.57
4.58 2594
0.45
3.80 2736
0.33
2.87 2280
0.85
6.29 2394
0.73
5.63 2480
0.61
4.90 2594
0.49
4.14 2736
0.37
3.22 2280
0.89
6.59 2394
0.77
5.94 2480
0.65
5.22 2594
0.53
4.47 2736
0.41
3.56 2280
0.93
6.88 2394
0.81
6.25 2480
0.69
5.54 2594
0.57
4.81 2736
0.45
3.91
E1E1
7.09
7.40
7.09
7.40
7.75
7.09
7.40
7.75
7.09
7.40
7.75
8.13
7.09
7.40
7.75
8.13
7.09
7.40
7.75
8.13
8.44
7.09
7.40
7.75
8.13
8.44
7.09
7.40
7.75
8.13
8.44
7.09
7.40
7.75
8.13
8.44
7.09
7.40
7.75
8.13
8.44
7.09
7.40
7.75
8.13
8.44
7.09
7.40
7.75
8.13
8.44
3.47
2.74
3.76
3.04
2.25
4.04
3.33
2.56
4.32
3.63
2.87
2.03
4.61
3.92
3.18
2.36
4.89
4.22
3.49
2.68
1.77
5.17
4.52
3.80
3.01
2.11
5.46
4.81
4.11
3.33
2.45
5.74
5.11
4.42
3.66
2.79
6.02
5.40
4.73
3.98
3.12
6.31
5.70
5.04
4.31
3.46
6.59
6.00
5.35
4.63
3.80
OUTDOOR DB(:)
0.49
0.37
0.53
0.41
0.29
0.57
0.45
0.33
0.61
0.49
0.37
0.25
0.65
0.53
0.41
0.29
0.69
0.57
0.45
0.33
0.21
0.73
0.61
0.49
0.37
0.25
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
2394 2537 2394 2537 2636 2394 2537 2636 2394 2537 2636 2736 2394 2537 2636 2736 2394 2537 2636 2736 2879 2394 2537 2636 2736 2879 2394 2537 2636 2736 2879 2394 2537 2636 2736 2879 2394 2537 2636 2736 2879 2394 2537 2636 2736 2879 2394 2537 2636 2736 2879
20
6.80
7.18
6.80
7.18
7.56
6.80
7.18
7.56
6.80
7.18
7.56
7.94
6.80
7.18
7.56
7.94
6.80
7.18
7.56
7.94
8.32
6.80
7.18
7.56
7.94
8.32
6.80
7.18
7.56
7.94
8.32
6.80
7.18
7.56
7.94
8.32
6.80
7.18
7.56
7.94
8.32
6.80
7.18
7.56
7.94
8.32
6.80
7.18
7.56
7.94
8.32
3.33
2.66
3.61
2.94
2.19
3.88
3.23
2.49
4.15
3.52
2.80
1.98
4.42
3.81
3.10
2.30
4.69
4.09
3.40
2.62
1.75
4.97
4.38
3.70
2.94
2.08
5.24
4.67
4.01
3.25
2.41
5.51
4.96
4.31
3.57
2.74
5.78
5.24
4.61
3.89
3.08
6.06
5.53
4.91
4.21
3.41
6.33
5.82
5.22
4.52
3.74
0.49
0.37
0.53
0.41
0.29
0.57
0.45
0.33
0.61
0.49
0.37
0.25
0.65
0.53
0.41
0.29
0.69
0.57
0.45
0.33
0.21
0.73
0.61
0.49
0.37
0.25
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
2508 2594 2508 2594 2708 2508 2594 2708 2508 2594 2708 2822 2508 2594 2708 2822 2508 2594 2708 2822 2964 2508 2594 2708 2822 2964 2508 2594 2708 2822 2964 2508 2594 2708 2822 2964 2508 2594 2708 2822 2964 2508 2594 2708 2822 2964 2508 2594 2708 2822 2964
6.55
6.93
6.55
6.93
7.25
6.55
6.93
7.25
6.55
6.93
7.25
7.69
6.55
6.93
7.25
7.69
6.55
6.93
7.25
7.69
8.06
6.55
6.93
7.25
7.69
8.06
6.55
6.93
7.25
7.69
8.06
6.55
6.93
7.25
7.69
8.06
6.55
6.93
7.25
7.69
8.06
6.55
6.93
7.25
7.69
8.06
6.55
6.93
7.25
7.69
8.06
3.21
2.56
3.47
2.84
2.10
3.73
3.12
2.39
4.00
3.40
2.68
1.92
4.26
3.67
2.97
2.23
4.52
3.95
3.26
2.54
1.69
4.78
4.23
3.55
2.84
2.02
5.05
4.50
3.84
3.15
2.34
5.31
4.78
4.13
3.46
2.66
5.57
5.06
4.42
3.77
2.98
5.83
5.34
4.71
4.07
3.31
6.09
5.61
5.00
4.38
3.63
0.49
0.37
0.53
0.41
0.29
0.57
0.45
0.33
0.61
0.49
0.37
0.25
0.65
0.53
0.41
0.29
0.69
0.57
0.45
0.33
0.21
0.73
0.61
0.49
0.37
0.25
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
2622 2708 2622 2708 2822 2622 2708 2822 2622 2708 2822 2964 2622 2708 2822 2964 2622 2708 2822 2964 3050 2622 2708 2822 2964 3050 2622 2708 2822 2964 3050 2622 2708 2822 2964 3050 2622 2708 2822 2964 3050 2622 2708 2822 2964 3050 2622 2708 2822 2964 3050
Page 21
PERFORMANCE DATA COOL operation
2793 2907 2793 2907 3021 2793 2907 3021 2793 2907 3021 3135 2793 2907 3021 3135 2793 2907 3021 3135 3249 2793 2907 3021 3135 3249 2793 2907 3021 3135 3249 2793 2907 3021 3135 3249 2793 2907 3021 3135 3249 2793 2907 3021 3135 3249 2793 2907 3021 3135 3249
E1E1
5.67
60.5
5.67
6.05
6.43
5.67
6.05
6.43
5.67
6.05
6.43
6.80
5.67
6.05
6.43
6.80
5.67
6.05
6.43
6.80
7.18
5.67
6.05
6.43
6.80
7.18
5.67
6.05
6.43
6.80
7.18
5.67
6.05
6.43
6.80
7.18
5.67
6.05
6.43
6.80
7.18
5.67
6.05
6.43
6.80
7.18
5.67
6.05
6.43
6.80
7.18
2.78
2.24
3.01
2.48
1.86
3.23
2.72
2.12
3.46
2.96
2.38
1.70
3.69
3.21
2.63
1.97
3.91
3.45
2.89
2.25
1.51
4.14
3.69
3.15
2.52
1.80
4.37
3.93
3.41
2.79
2.08
4.59
4.17
3.66
3.06
2.37
4.82
4.42
3.92
3.33
2.66
5.05
4.66
4.18
3.61
2.94
5.27
4.90
4.43
3.88
3.23
OUTDOOR DB(:)
0.49
0.37
0.53
0.41
0.29
0.57
0.45
0.33
0.61
0.49
0.37
0.25
0.65
0.53
0.41
0.29
0.69
0.57
0.45
0.33
0.21
0.73
0.61
0.49
0.37
0.25
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
2964 3050 2964 3050 3192 2964 3050 3192 2964 3050 3192 3278 2964 3050 3192 3278 2964 3050 3192 3278 3392 2964 3050 3192 3278 3392 2964 3050 3192 3278 3392 2964 3050 3192 3278 3392 2964 3050 3192 3278 3392 2964 3050 3192 3278 3392 2964 3050 3192 3278 3392
21
5.45
5.83
5.45
5.83
6.21
5.45
5.83
6.21
5.45
5.83
6.21
6.62
5.45
5.83
6.21
6.62
5.45
5.83
6.21
6.62
6.96
5.45
5.83
6.21
6.62
6.96
5.45
5.83
6.21
6.62
6.96
5.45
5.83
6.21
6.62
6.96
5.45
5.83
6.21
6.62
6.96
5.45
5.83
6.21
6.62
6.96
5.45
5.83
6.21
6.62
6.96
2.67
2.16
2.89
2.39
1.80
3.11
2.62
2.05
3.32
2.86
2.30
1.65
3.54
3.09
2.54
1.92
3.76
3.32
2.79
2.18
1.46
3.98
3.55
3.04
2.45
1.74
4.20
3.79
3.29
2.71
2.02
4.41
4.02
3.54
2.98
2.30
4.63
4.25
3.79
3.24
2.58
4.85
4.49
4.03
3.51
2.85
5.07
4.72
4.28
3.77
3.13
0.49
0.37
0.53
0.41
0.29
0.57
0.45
0.33
0.61
0.49
0.37
0.25
0.65
0.53
0.41
0.29
0.69
0.57
0.45
0.33
0.21
0.73
0.61
0.49
0.37
0.25
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
3021 3135 3021 3135 3249 3021 3135 3249 3021 3135 3249 3349 3021 3135 3249 3349 3021 3135 3249 3349 3463 3021 3135 3249 3349 3463 3021 3135 3249 3349 3463 3021 3135 3249 3349 3463 3021 3135 3249 3349 3463 3021 3135 3249 3349 3463 3021 3135 3249 3349 3463
5.23
5.61
5.23
5.61
5.99
5.23
5.61
5.99
5.23
5.61
5.99
6.43
5.23
5.61
5.99
6.43
5.23
5.61
5.99
6.43
6.74
5.23
5.61
5.99
6.43
6.74
5.23
5.61
5.99
6.43
6.74
5.23
5.61
5.99
6.43
6.74
5.23
5.61
5.99
6.43
6.74
5.23
5.61
5.99
6.43
6.74
5.23
5.61
5.99
6.43
6.74
MSH-C24TV - : MUH-C24TV - (230V)
CAPACITY : 6.3(KW) SHF : 0.67 INPUT : 2850(W)
INDOOR
DB(:)
NOTE Q : Total capacity (kW) SHF : Sensible heat factor DB : Dry-bulb temperature
INDOOR
WB(:) 21 21 22 22 22 23 23 23 24 24 24 24 25 25 25 25 26 26 26 26 26 27 27 27 27 27 28 28 28 28 28 29 29 29 29 29 30 30 30 30 30 31 31 31 31 31 32 32 32 32 32
18 20 18 20 22 18 20 22 18 20 22 24 18 20 22 24 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26 18 20 22 24 26
SHC : Sensible heat capacity (kW) INPUT : Total power input (W) WB : Wet-bulb temperature
Q SHC SHF INPUT Q SHC SHF INPUT Q SHC SHF INPUT46Q SHC SHF INPUT
6.17
6.49
6.17
6.49
6.87
6.17
6.49
6.87
6.17
6.49
6.87
7.25
6.17
6.49
6.87
7.25
6.17
6.49
6.87
7.25
7.62
6.17
6.49
6.87
7.25
7.62
6.17
6.49
6.87
7.25
7.62
6.17
6.49
6.87
7.25
7.62
6.17
6.49
6.87
7.25
7.62
6.17
6.49
6.87
7.25
7.62
6.17
6.49
6.87
7.25
7.62
35 4340
0.49
3.03
0.37
2.40
0.53
3.27
0.41
2.66
0.29
1.99
0.57
3.52
0.45
2.92
0.33
2.27
0.61
3.77
0.49
3.18
0.37
2.54
0.25
1.81
0.65
4.01
0.53
3.44
0.41
2.82
0.29
2.10
0.69
4.26
0.57
3.70
0.45
3.09
0.33
2.39
0.21
1.60
0.73
4.51
0.61
3.96
0.49
3.36
0.37
2.68
0.25
1.91
0.77
4.75
0.65
4.22
0.53
3.64
0.41
2.97
0.29
2.21
0.81
5.00
0.69
4.48
0.57
3.91
0.45
3.26
0.33
2.52
0.85
5.25
0.73
4.74
0.61
4.19
0.49
3.55
0.37
2.82
0.89
5.49
0.77
5.00
0.65
4.46
0.53
3.84
0.41
3.13
0.93
5.74
0.81
5.26
0.69
4.74
0.57
4.13
0.45
3.43
2.56
2.07
2.77
2.30
1.74
2.98
2.52
1.98
3.19
2.75
2.21
1.61
3.40
2.97
2.45
1.86
3.61
3.20
2.69
2.12
1.42
3.82
3.42
2.93
2.38
1.69
4.03
3.64
3.17
2.63
1.95
4.24
3.87
3.41
2.89
2.22
4.44
4.09
3.65
3.15
2.49
4.65
4.32
3.89
3.41
2.76
4.86
4.54
4.13
3.66
3.03
0.49
0.37
0.53
0.41
0.29
0.57
0.45
0.33
0.61
0.49
0.37
0.25
0.65
0.53
0.41
0.29
0.69
0.57
0.45
0.33
0.21
0.73
0.61
0.49
0.37
0.25
0.77
0.65
0.53
0.41
0.29
0.81
0.69
0.57
0.45
0.33
0.85
0.73
0.61
0.49
0.37
0.89
0.77
0.65
0.53
0.41
0.93
0.81
0.69
0.57
0.45
3078 3221 3078 3221 3306 3078 3221 3306 3078 3221 3306 3420 3078 3221 3306 3420 3078 3221 3306 3420 3534 3078 3221 3306 3420 3534 3078 3221 3306 3420 3534 3078 3221 3306 3420 3534 3078 3221 3306 3420 3534 3078 3221 3306 3420 3534 3078 3221 3306 3420 3534
Page 22
OUTDOOR WB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
CAPACITY : 6.0(KW)
INPUT : 2180(W)
15 21 26
3.78
3.60
3.24
1417
1526
1635
4.56
4.32
4.02
1700 1809 1918
5.34
5.10
4.74
1918 2006 2115
6.12
5.82
5.52
2071 2158 2267
6.90
6.60
6.30
2202 2267 2376
7.62
7.32
7.02
2267 2333 2442
8.40
8.07
7.80
2311 2420 2507
PERFORMANCE DATA HEAT operation
OUTDOOR WB(:)
INDOOR
-10 -5 0 5 10 15 20
DB(:)
Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT
CAPACITY : 7.5(KW)
INPUT : 3020(W)
15 21 26
4.73
4.50
4.05
1963
2114
2265
5.70
5.40
5.03
2356 2507 2658
6.68
6.38
5.93
2658 2778 2929
7.65
7.28
6.90
2869 2990 3141
8.63
8.25
7.88
3050 3141 3292
9.53
9.15
8.78
3141 3231 3382
10.50
10.09
9.75
3201 3352 3473
MSH-C18TV - : MUH-C18TV - (230V)
NOTE Q :Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature
E1E1
MSH-C24TV - : MUH-C24TV - (230V)
NOTE Q :Total capacity (kW) INPUT:Total power input (W) DB : Dry-bulb temperature
E1E1
22
Page 23
9
lighted
not lighted
Approx. 2 : or more
Difference between target temperature and room temperature
Approx. 2 : or less
This shows that the air conditioner is operating to reach the target temperature. Please wait until the target temperature is obtained.
This shows that the room temperature is approaching the target temperature.
Operation stateIndication
Operation Indicator
Operation Indicator lamp
The operation indicator at the right side of the indoor unit indicates the operation state.
• The following indication does not depend on the shape of lamp.
INDOOR UNIT DISPLAY SECTION
Mode
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature
25: or more
23:to 25:
less than 23:
MICROPROCESSOR CONTROL
WIRELESS REMOTE CONTROLLER
Signal transmitting section
Operation display section
OPERATE /STOP (ON /OFF)button
VANE CONTROL button
OPERATION SELECT button
ECONO COOL button
ON/OFF
I FEEL
HEAT
MODE
ECONO COOL
ON/OFF
COOL
DRY
TOO
WARM
TOO
WARM
FAN
VANE
RESET CLOCK
PM
AM
TOO COOL
TOO
COOL
FAN SPEED CONTROL button
STOP
START
HR.
MIN.
TEMPERATURE buttons
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
MSH-C18TV ­MSH-C24TV -
E1
MUH-C18TV -
E1
MUH-C24TV -
E1
E1
Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
9-1. “I FEEL CONTROL” ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button on the remote
controller. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select mode with the OPERATION SELECT button “I
FEEL CONTROL”.
(3) The operation mode is determined by the room tempera-
ture at start-up of the operation.
RESET button
• Once the mode is fixed, the mode does not change by room temperature afterwards.
• Under the ON-TIMER ( ) operation, mode is deter­mined according to the room temperature at the set time the operation starts.
• When the system is stopped on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” ( )
mode, the system operates in previous mode automati­cally regardless of the room temperature.
Example Previous operation
COOL mode of “I FEEL CONTROL”
Restart
COOL mode of “I FEEL CONTROL”
or COOL mode
When the system is restarted after 2 hours and more, the operation mode is determined by the room temperature at start-up of the operation.
Example
Restart
COOL or DRY or
Previous operation
COOL mode of “I FEEL CONTROL”
or COOL mode
HEAT mode of “I FEEL CONTROL” that deter­mined by room tem­perature at start-up of the operation.
23
Page 24
Model
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
HEAT mode of
"I FEEL CONTROL"
Initial room temperature Initial set temperature
26:
26: or more
25: to 26:
less than 23:
23: to 25:
24:
Initial room temperature minus 2: Initial room temperature minus 2:
1
(4) The initial set temperature is decided by the initial room temperature.
Difference between room temperature and set temperature during operation
1deg. 1.7deg.
3deg.
TOO
COOL
TOO
WARM
1 When the system is restarted with the remote controller, the system operates with the previous set temperature regard-
less of room temperature at restart. The set temperature is calculated by the previous set temperature.
(5) TEMPERATURE buttons
In “I FEEL CONTROL” ( ) mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
To raise the set temperature 1~2 degrees(°C)
To lower the set temperature 1~2 degrees(°C)
9-1-1. COOL mode of “I FEEL CONTROL”
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. In AUTO the fan speed is as follows.
Room temperature minus set temperature : 1.7 degrees or more Room temperature minus set temperature : Between 1 and 1.7 degrees Room temperature minus set temperature : less than 1 degree
2. Coil frost prevention
Temperature control
When the indoor coil thermistor RT12 reads 3°C or below, the coil frost prevention mode starts immediately.
However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started. The indoor fan operates at the set speed and the compressor stops for 5 minutes. After that, if RT12 still reads below 3°C this mode prolonged until the RT12 reads over 3°C.
Time control
When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Low or Med..
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the
beginning.
Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again. Time accumulation is resumed.
Initial temperature difference Fan Speed
··························High
················Med.
·····························
24
Low
Page 25
Operation chart
Outdoor fan speed
28: 31:
High
Ambient temperature thermistor RT63 temperature
Low
Example
Compressor
OFF
ON
OFF
ON
Outdoor fan
(continuously at set speed)
Indoor fan
ON
3. Outdoor fan control <MSH-C24TV only>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63. Outdoor fan Low operation : When the outside temperature decreases to 28°C or less.
Until the outside temperature goes to 31°C or more.
Outdoor fan High operation : Until the outside temperature decreases to 28°C or less.
When the outside temperature goes to 31°C or more.
NOTE : If the temperature of RT63 reads from 28: to 31: at the air conditioner starting, outdoor fan speed is High.
9-1-2. DRY mode of “I FEEL CONTROL”
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.
1. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button. However, in AUTO fan operation, fan speed becomes Low.
2. The operation of the compressor and indoor/ outdoor fan
Compressor operates by room temperature control and time control. Set temperature is controlled to fall 2°C from initial room temperature. Indoor fan and outdoor fan operate in the same cycle as the compressor.
•When the room temperature is 23°C or over: When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
When the room temperature is under 23°C. When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Operation time chart
ON
ON
Example
Thermostat
Indoor fan
Outdoor fan Compressor
OFF
OFF
OFF
ON
ON
8 min.
OFF
OFF
ON
ON
3 min.
OFF
OFF
4 min.
OFF
ON
ON
1 min.
3. Coil frost prevention
• The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.
• Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection(Coil frost prevention) has the priority. However, when coil frost prevention works while the compressor is not operating, it’s speed becomes Low.
4. Outdoor fan control <MSH-C24TV only>
Outdoor fan control is as same as one of COOL mode of “I FEEL CONTROL”.
25
Page 26
9-1-3. HEAT mode of “I FEEL CONTROL”
Difference between room temperature and set temperature during operation
1deg. 1.7deg.
4deg.
2deg.
Released
Cold Air Prevention
18: 22:
Fan speed Set speed Very Low or stop
High pressure protection
Released
52: 56:
ON
Outdoor fan
OFF
Outdoor fan speed
12: 14:
High
Ambient temperature thermistor RT63 temperature
Low
1. Indoor fan speed control
(1) In AUTO the fan speed is as follows.
Set temperature minus room temperature: 2 degrees or more ·············································· High Set temperature minus room temperature: Between 1 and 2 degrees··································· Med. Set temperature minus room temperature: less than 1 degree·············································· Low
(2) Cold air prevention control
The fan runs at set speed when the indoor coil thermistor RT12 temperature exceeds 22°C. The fan operates at Very Low when the temperature of indoor coil thermistor RT12 is below 18°C. But the fan stops when the indoor fan operates at Very Low and the room temperature is 15°C or less.
Indoor coil thermistor RT12 temperature
NOTE : If the temperature of RT12 reads from 18°C to 22°C at the air conditioner starting and also after defrosting, this
control works.
(3) Warm air control.
When compressor starts in heating operation or after defrosting, the fan changes the speed due to the indoor coil ther­mistor RT12 temperature to blow out warm air. After releasing of cold air prevention, when the indoor coil thermistor RT12 temperature is 37°C or above, the fan speed shifts to the set speed, and when the fan speed is changed by the remote controller, the fan speed is the set speed. When the indoor coil thermistor RT12 temperature is less than 37°C, the fan speed is controlled by time as below. <Time condition> <Indoor fan speed> less than 2 minutes························Low 2 minutes to 4 minutes···················Med. 4 minutes or more··························High The upper limit of the fan speed is the set speed. If the thermostat turns off, this operation changes to flow soft control.
(4) Flow soft control
After the thermostat turns off, the indoor fan operates at Very Low. NOTE : When the thermostat turns on, the fan operates at the set speed. Due to the cold air prevention control, the fan
does not start at set speed until the indoor coil thermistor RT12 reads 22°C or more.
2. Outdoor fan control <MSH-C24TV only>
Outdoor fan speed is controlled according to the temperature of ambient temperature thermistor RT63. Outdoor fan Low operation : Until the outside temperature decreases to 12°C.
When the outside temperature goes to 14°C or more.
Outdoor fan High operation :When the outside temperature decreases to 12°C or less.
Until the outside temperature goes to 14°C.
3. High pressure protection
During heating operation, the outdoor fan motor is controlled by the temperature of indoor coil thermistor RT12 for excess rise protection of compressor discharge pressure.
Outdoor fan OFF : 56°C Outdoor fan ON : 52°C
Initial temperature difference Fan speed
High pressure protection chart Example
Indoor coil thermistor
RT12 temperature
56˚C
52˚C
Outdoor fan motor turn OFF
Outdoor fan motor turn ON
Outdoor fan motor
NOTE 1 During high pressure protection and for 4 minutes and 15 seconds (MUH-C18TV)/ 10 seconds (MUH-C24TV) after
high pressure protection, defrosting of outdoor heat exchanger is not detected by the defrost thermistor RT61.
OFF
26
ON
ON
OFF
Page 27
4. Defrosting
Defrosting of outdoor heat exchanger is controlled by deicer P.C. board, with detection by the defrost thermistor RT61.
(1) Starting conditions of defrost
When all conditions of a) ~ c) are satisfied, the defrosting operation starts.
a) Under the heat operation, the compressor cumulative operation time exceeds 40 minutes without the defrosting opera-
tion working. b) The defrost thermistor RT61 reads -2.7°C or less (MSH-C18TV) / -2.0°C or less (MSH-C24TV). c) After releasing the high pressure protection 4 minutes and 15 seconds (MSH-C18TV) / 10 seconds (MSH-C24TV) have
elapsed.
(2) Releasing conditions of defrost
When the condition d) or e) is satisfied, the defrosting operation stops.
d) The defrost thermistor RT61 reads 16.3°C or more (MSH-C18TV) / 20.0°C or more (MSH-C24TV). e) The defrosting time exceeds 10 minutes.
(3) Defrosting time chart
Defrost thermistor RT61
20.0: or more (MSH-C24TV)
16.3: or more (MSH-C18TV)
-2.0: or less (MSH-C24TV)
-2.7: or less (MSH-C18TV)
Outdoor 52C contactor(Compressor)
ON
X62 (R.V. coil)
SR61 Outdoor fan
Defrost counter
Indoor fan
OFF
ON OFF
ON OFF
ON OFF
ON
Very Low
OFF
30 sec.
NOTE
15 sec.
30 sec.
5 sec.
(MSH-C24TV)
(MSH-C18TV)
Max 10 min.
Indoor vane
NOTE • When the indoor coil thermistor RT12 reads above 18°C, indoor fan operates at Very Low for 30 seconds.
• When the indoor coil thermistor RT12 reads 18°C or less, the indoor fan stops.
Horizontal Set position
27
Page 28
5. R.V. coil control
Heating · · · · · ON Cooling · · · · · OFF Dry · · · · · · · · OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
(COOL / DRY)
5 sec.
Compressor
R.V. coil
Outdoor fan
ON OFF
ON OFF
ON OFF
9-2. COOL ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select COOL mode with the OPERATION
SELECT button.
(3) Press the TEMPERATURE buttons.
(TOO WARM or TOO COOL button) to select the desired temperature. The setting range is 16 ~ 31°C. Indoor fan continues to operate regardless of
thermostat’s OFF-ON at set speed.
Coil frost prevention is as same as COOL
mode of “I FEEL CONTROL”.
9-3. DRY ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select DRY mode with the OPERATION
SELECT button.
(3) The microprocessor reads the room tempera-
ture and determines the set temperature. Set temperature is as shown on the right chart. Thermostat (SET TEMP.)does not work. The other operations are same as DRY mode of “I FEEL CONTROL”.
(4) DRY operation will not function when the room
temperature is 13°C or below.
(HEAT)
5 sec.
ON OFF
ON OFF
ON OFF
9-4. HEAT ( ) OPERATION
(1) Press OPERATE/STOP (ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone. (2) Select HEAT mode with the OPERATION SELECT button. (3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C. (4) Indoor fan speed control, high pressure protection, defrosting, R.V. coil control are the same as HEAT mode of “I FEEL
CONTROL”.
28
Page 29
9-5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feed back the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (High,Med.,Low), the microprocessor controls IC141 and adjusts fan motor electric current to make the current rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
Rotational frequency
High
Med.
Low
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 minutes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR Indicator lamp flashes on and off to show the fan motor abnormality. (Refer to page 37.)
High
time
9-6. AUTO VANE OPERATION
(1) Vane motor drive
These models are equipped with a stepping motor for the horizontal vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The horizontal vane angle and mode changes as follows by pressing the VANE CONTROL button.
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. Confirming of standard position is performed in case of follows. (a) When the OPERATE/STOP (ON/OFF) button is pressed. (b) When the vane control is changed from AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON.
(4) VANE AUTO ( ) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum room-temperature distribution.
In COOL and DRY operation
Vane angle is fixed to Angle 1.
In HEAT operation
Vane angle is fixed to Angle 4.
29
Page 30
(5) STOP (operation OFF) and ON-TIMER standby.
Released
Cold Air Prevention
24: 28:
Angle 1
Horizontal vane
Set position
When the following cases occur, the horizontal vane returns to the closed position.
(a) When the OPERATE/STOP (ON/OFF) button is pressed (POWER OFF).
(b) When the operation is stopped by the emergency operation.
(c) When the ON-TIMER is on standby.
(6) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the cumulative operation time of compressor exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(7) SWING MODE ( )
By selecting SWING mode with the VANE CONTROLbutton, the horizontal vane swings vertically. The remote controller displays “ ”.
(8) Cold air prevention in HEAT operation
When any of the following conditions occurs in HEAT operation, the vane angle changes to Angle 1
automatically to prevent cold air blowing on users.
Compressor is not operating.
Defrosting is performed.
Indoor coil thermistor RT12 reads 24: or below.
Indoor coil thermistor RT12 temperature is raising from 24°C or below, but it does not exceed 28:.
Indoor coil thermistor RT12 temperature
NOTE: If the temperature of RT12 reads from 27: to 28: at the air conditioner starting, this control works.
(9) ECONO COOL ( ) operation (ECONOmical operation)
When the ECONO COOL button is pressed in COOL mode, set temperature is automatically set 2°C higher than that in COOL mode. Also the horizontal vane swings in various cycle according to the temperature of indoor heat exchanger(RT12). SWING operation makes you feel cooler than set temperature. So, even though the set temperature is higher than that in COOL mode, the air conditioner can keep comfort. As a result, energy can be saved. ECONO COOL operation is cancelled when the ECONO COOL button is pressed once again or VANE CONTROL but­ton is pressed or change to other operation mode.
NOTE : ECONO COOL operation not work in COOL mode of “I FEEL CONTROL”.
SWING operation
In swing operation of ECONO COOL operation air flow is initially blew out upward(levelly). According to the temperature of indoor coil thermistor RT12 at starting of this operation, next downward blow time is decided. Then when the downward blow has been finished, next upward blow time is decided. For initial 10 minutes the swing operation is performed in table G~H for quick cooling(but G : RT 12 is 24: or less). Also, after 10 minutes when the difference of set temperature and room temperature is more than 2:, the swing oper­ation is performed in table D~H for more cooling(but D: RT12 is 20: or less). The air conditioner repeats the swing operation in various cycle as follows.
Temperature of indoor
coil thermistor RT12
A B
C
D E F
G
H
15°C or less 15°C to 17°C
17°C to 18°C
18°C to 20°C
20°C to 21°C 21°C to 22°C 22°C to 24°C
more than 24°C
Downward blow time
(sec.)
2 5 8
11 14 17
20 23
Upward(level) blow time
(sec.)
23 20 17 14 11
8
5 2
30
Page 31
9-7. TIMER OPERATION
PM
AM
PM
PM
1. How to set the timer
(1) Press OPERATE/STOP (ON/OFF) button to start the air conditioner. (2) Check that the current time is set correctly.
NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display of
TIME MONITOR, so set the current time correctly with CLOCK SET button.
(3) Press TIMER CONTROL button to select the operation.
“ON-TIMER” button... AUTO START operation (ON timer) “OFF-TIMER” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “ ” or “ ” mark is flashing. These marks disappear in 1 minute. After setting the ON timer, check that OPERATION INDICATOR lamp of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
• Apower failure occurs.
•The circuit breaker functions.
2. Cancel
TIMER setting can be cancelled with the ON/OFF TIMER buttons. To cancel the ON timer, press the “ON-TIMER” button. To cancel the OFF timer, press the “OFF-TIMER” button. TIMER is cancelled and the display of set time disappears.
PROGRAM TIMER
• The OFF timer and ON timer can be used in combination.
• “ ” and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
31
Page 32
EMERGENCY OPERATION switch
Press once <Cool>
Press again <Heat>
Press once again <Stop>
OPERATION INDICATOR lamp
9-8. EMERGENCY-TEST OPERATION
In case of test run operation or emergency operation, use the EMERGENCY OPERATION switch on the front of the indoor unit. Emergency operation is available when the remote controller is missing, has failed or the batteries of remote controller run down. The unit will start and the OPERATION INDICATOR lamp will light. The first 30 minutes of operation is the test run operation. This operation is for servicing. The indoor fan speed runs at High speed and the system is in continuous operation. (The thermostat is ON.) After 30 minutes of test run operation the system shifts to EMERGENCY COOL / HEAT MODE with a set temperature of 24°C. The fan speed shifts to Med. speed. The coil frost prevention works even in emergency operation, and defrosting too.
In the test run or emergency operation, the horizontal vane operates in VANE AUTO ( ) mode. Emergency operation continues until the EMERGENCY OPERATION switch is pressed once or twice or the unit receives any signal from the remote controller. In case of latter normal operation will start.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
32
Page 33
10
Jumper wire
JPC
Defrost interval time changes from 40 minutes to 15 minutes.
MUH-C18TV -
Model Change point
E1
MUH-C24TV -
Jumper wire
JRF
Defrost interval time changes from 40 minutes to 15 minutes.
E1
Model Change point
SERVICE FUNCTIONS
MSH-C18TV ­MSH-C24TV -
E1
MUH-C18TV -
E1
MUH-C24TV -
E1
E1
10-1. COMPULSORY DEFROST MODE FOR SERVICE
By short circuit of the JP607 and R853(MSH-C18TV)/JPG1 and R871(MSH-C24TV) on the outdoor deicer P.C. board,
defrosting mode can be accomplished regardless of the defrost interval restriction. (Refer to page 45 or 46.)
Defrost thermistor RT61 must read below -2.7°C(MSH-C18TV)/ -2.0°C(MSH-C24TV).
10-2. CHANGE IN DEFROST SETTING
MSH-C18TV
<JPC> When the JPC wire of the deicer P.C. board is cut, the defrost interval time will be changed. (Refer to page 45.)
MSH-C24TV
<JRF> When the JRF wire of the deicer P.C. board is cut, the defrost interval time will be changed. (Refer to page 46.)
10-3. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS the electronic control P.C. board. The time will be shortened as follows. Set time : 1 minute 1-second
Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
10-4. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For remodelling, take out the bat-
teries and push the OPERATE/STOP(ON/OFF)button twice or 3 times at first. After finish remodelling, put back the batteries then push the RESET button.
The P.C. board has the print “J1” and “J2”. Solder “J1” and “J2” according to the number of indoor unit as shown in Table 2. After modification, push the RESET button.
33
Page 34
JR06
CN102
CN151
CN112 CN111CN121
CN101
BZ
SW
52C
IC101 RA102
IC141
CN211
C11CN201
Table 1
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
NOTE : At power supply failure or installation, indoor unit deletes the memory about remote controller. When the power supply
is turned on and indoor unit receives the first signals from the remote controller, the remote controller number is desig­nated as the indoor unit number. Therefore at and after the second time indoor unit accepts the remote controller of the initial setting number. At setting - error, turn the power supply off to cancel the individual operation and then turn the power supply on to restart the setting.
10-5. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEELCON­TROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit. 2Pull out the electronic control P.C. board and the
display P.C.board. (Refer to page 47.)
3Cut the RESISTOR JR06 on the indoor electronic
control P.C.board. (Refer to page 44 .)
Operation
1If the main power (230V AC) has been cut, the operation settings remain. 2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
NOTE
The operation settings are memorized when 10 seconds have passed after the remote controller was operated with the
remote controller.
If main power is turned off or a power failure occurs while AUTO START/STOP timer is active ,the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.
34
Page 35
11
Lead wiring
Housing point
Insert the negative pole of the batteries first. Check if the polarity of the batteries are correct.
RESET button
TROUBLESHOOTING
MSH-C18TV - MUH-C18TV ­MSH-C24TV - MUH-C24TV -
E1E1
E1E1
11-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
(1) Check the power supply voltage. (2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care the following during servicing.
(1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after
confirming the horizontal vane is closed, turn off the breaker and / or disconnect the power plug.
(2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
(3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
(4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
3. Troubleshooting procedure
(1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work. (2) Before servicing check that the connector and terminal are connected properly. (3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discolouration. (4) When troubleshooting, refer to the flow chart on page 36 and the check table on page 37.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, replace the batteries to operate the remote controller normally. 1 Remove the front lid and insert batteries.
Then re-attach the front lid.
2 Press the RESET button with tip end of ball point
pen or the like, and then use the remote controller.
NOTE : If the RESET button is not pressed, the remote controller may not operate correctly.
35
Page 36
11-2. Instruction of troubleshooting
Start
Indoor unit operates. Outdoor unit doesn't operate.
Indoor unit doesn't receive the signal from remote controller.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Outdoor unit operates in only Test Run operation.
Outdoor unit doesn't operate even in Test Run operation.
Indoor unit operates, when the EMERGENCY OPERATION switch is pressed.
Indoor unit doesn't operate, when the EMERGENCY OPERATION switch is pressed.
Check room temperature thermistor. Refer to "Test point diagram and voltage" on page 44.
Refer to D "Check of outdoor unit" on page 40 or 41.
Refer to B "Check of remote controller and receiver P.C. board" on page 39.
Flash on and off at 0.5­second interval Cause: Indoor/ Outdoor unit
• Mis-wiring
2-time flash Cause: Indoor unit
• Trouble of room temp­ erature/ indoor coil thermistor
3-time flash Cause: Indoor unit
• Trouble of indoor fan motor
6-time flash Cause: Outdoor unit
• Trouble of thermistor in outdoor unit
Refer to G "How to check mis-wiring and sirial singal error (When outdoor unit doesn't operate)" on page 43. 1
Check room temperature thermistor and indoor coil thermis­tor. Refer to "Test point diagram and voltage" on page 44.
1-time flash Cause: Indoor/ Outdoor unit
• Trouble of serial signal
Refer to A "Check of indoor fan motor" on page 39.
MSH-C24TV only
7-time flash Cause: Outdoor unit
• Trouble of outdoor unit control system
Replace the deicer P.C. board.
1. Check indoor / outdoor connecting wire.
2. Refer to C "Check of indoor electronic control P.C. board" on page 40.
MSH-C24TV only Outdoor unit doesn't stop even if indoor unit stops.
Refer to E "Check of outdoor unit" on page 41.
Refer to H "Check of outdoor thermistor" on page 43.
Indoor unit operates. Outdoor unit doesn't operate normally.
Unit doesn't operate normal operation in COOL or HEAT mode.
Refer to F "Check of R.V. coil" on page 42.
1<The case of the trouble of the serial signal>
When the power is turned off and then turned on again, the indication shows “the trouble of mis­wiring.”
36
Page 37
1. Troubleshooting check table
Operation Indicator
flashing
· Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible abnormalities.
· The OPERATION INDICATOR lamp (on the left-hand side) is lighting during normal operation.
•The following indication does not depend on the shape of lamp.
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting. Self check table
Abnormal
NO.
point
Indication
Symptom
Detect method
Check point
Mis-wiring
1
Serial signal
Indoor coil thermistor
2
Room tempera­ture ther­mistor
Indoor fan
3
motor
0.5-second ON
0.5-second OFF
1-time flash
2.5-second OFF
2-time flash
2.5-second OFF
3-time flash
2.5-second OFF
Outdoor unit does not run.
Outdoor unit does not run.
Indoor fan motor repeats 12 sec­onds ON and 3 minutes OFF. When the indoor fan motor breaks, the fan keeps stopping.
When serial signal stops for 4 to 5 seconds after 1st on of 52C contactor by POWER turning on.
When serial signal from out­door unit stops for 4 to 5 sec­onds.
Detect Indoor coil/room tem­perature thermistor short or open circuit every 8 seconds during operation.
When rotational frequency feedback pulse signal is not emit during 12-second indoor fan operation.
Check wiring (visual check and conductiv­ity check).
Check indoor electronic control P.C.board.
Check deicer P.C. board.
Check electrical parts.
Check resistance of thermistor.
Re-connect connector.
Check indoor electronic control P.C.board.
Disconnect connector CN211 and then
check connector CN121 - to make sure rotational frequency feedback signal of 1.5V or over exists.
Check indoor electronic control P.C.
board.
Check indoor fan motor.
Re-connect connector.
2
3
6-time flash
Outdoor
4
thermistor
2.5-second OFF
MSH-C24TV
only
Outdoor
5
control system
7-time flash
2.5-second OFF
Outdoor unit does not run
Outdoor unit does not run
When the defrost thermistor shorts or opens after the com­pressor start-up.
When nonvolatile memory data cannot be read properly on deicer P.C. board, outdoor unit stops and restarts 3 min­utes later.
37
Check deicer P.C. board.
Check resistance of thermistor.
Re-connect connector.
Replace deicer P.C. board.
Page 38
2. Trouble criterion of main parts
P
~
BLK
R
MAIN
AUX.
RED
S
C
WHT
MAIN
AUX.
BLK
MSH-C18TV
MSH-C24TV
RED
WHTORN
P
P
C
RED ORN WHT
YLW
BLK
MAIN
AUX.1 AUX.2
YLW
RED
BLU
ORN
PNK
ROTOR
:INNER PROTECTOR
P
MAIN
AUX.
FUSE
BLK
RED
WHT
GRY
YLW
BRN
MSH-C18TV - MUH-C18TV ­MSH-C24TV - MUH-C24TV -
Part name
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Defrost
thermistor(RT61) Ambient temperature thermistor(RT63)
Compressor
(MC)
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)
Normal
8k~ 20k
Measure the resistance with a tester. (Part temperature –10°C ~ 40°C)
Normal
5k~ 60k
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
MSH-C18TV C-R C-S
0.93 ~ 1.15
1.79 ~ 2.19
Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)
E1E1
E1E1
Check method and criterion
Abnormal
Open or short-circuit
Abnormal
Open or short-circuit
Normal
MSH-C24TV
0.59 ~ 0.73
1.78 ~ 2.18
Figure
Abnormal
Open or
short-circuit
Indoor fan motor (MF)
Outdoor fan motor (MF)
Normal
Motor partSensor part
WHT-BLK BLK-RED
176 ~ 192 240 ~ 261
Measure the voltage Power ON.
Normal
BRN-YLW
YLW-GRY
4.5 ~ 5.5V
(When fan revolved one time)
0V➔5V➔0V
(Approx.)
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
Normal
WHT-BLK
BLK-RED BLK-YLW
YLW-RED
MSH-C18TV
102 ~ 126
97 ~ 120
– –
MSH-C24TV
55 ~ 68
– 26 ~ 33 55 ~ 68
Abnormal
Open or
short-circuit
Abnormal
Remain 0V or 5V
Abnormal
Open or
short-circuit
Vane motor (MV)
Measure the resistance between the terminals with a tester. (Part temperature10°C ~ 30°C)
Normal
RED-other one
358 ~ 388
Abnormal
Open or short-circuit
38
Page 39
A
Check of indoor fan motor
Indoor fan motor does not operate.
No
Re-connect the lead wires.
Check of remote controller and receiver P.C. board
B
Are lead wires connected?
Disconnect lead wires from connector CN211 on the indoor electronic control P.C. board. Measure resistance between lead wires No.1 and No.4 and then No.1 and No.2.
Is resistance 0 (short circuit) or (open circuit)?
Repair or replace the indoor fan motor.
Turn OFF the power supply. Check connector CN211 visually.
Yes
Yes ( 0 or ∞ )
Is soldered point normal?
No
Yes
Insert screwdriver into air outlet to rotate indoor fan
motor slowly for 1 revolution or over, and measure voltage No.2(+) and No.3(-) on CN121.
No
(others)
No
Does voltage repeat 0V DC and 5V DC?
Yes
Replace the indoor electronic control P.C. board.
Re-solver it.
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
w Check if the remote controller is exclusive for this air conditioner.
Switch on the remote controller.
Is LCD display on the the remote controller visible?
Yes
Remove the batteries, then set them back and press the RESET button. Check if the unit operates with the remote controller.
Does the unit operate with the remote controller?
Yes
OK
No (not clear)
No
Measure the voltage between receiver P.C. board connector No.2(+) and No.1 when the remote controller button is pressed.
Replace the batteries.(Refer to page 35.)
Turn on a radio to AM and press switch on the remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
No
Yes
Replace the remote controller.
Re-install the unit away from lights.
Attach a filter on receiving part.
Is the voltage approx. 4V DC?
No(5V or 0V DC)
Replace the receiver P.C. board.
39
Yes
Replace the indoor electronic control P.C. board.
Page 40
Check of indoor electronic control P.C. board
Check the both “parts side” and “pattern side” of indoor electronic control P.C. board visually.
Replace the fuse.
Is fuse(F11) blown?
Be sure to check both fuse and varistor in any case.
Replace the fan motor.
Replace the indoor electronic control P.C. board.
Is winding resistance of fan motor 0 "?
Is winding resistance of vane motor 0 "?
No
Yes
Replace the vane motor.
No
Yes
Yes
Is varistor(NR11) burnt?
Replace the varistor.
Yes
Turn OFF the power supply. Remove indoor fan motor connector CN211 and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON the power supply.
No
No
Does the unit operate with the remote controller? Does the OPERATION INDICATOR lamp light up by pressing the EMERGENCY OPERATION switch?
Yes
No
Measure the resistance between CN201
1 on the
indoor electronic control P.C. board and
N on the terminal
block with the tester.
Is resistance approx. 0"?
Replace the fuse (F12).
CN201
1 2
N
F12
1
3
Terminal block
Be sure to check both resistance.
No()
Yes
Turn OFF the power supply.
Turn OFF the power supply.
C
The unit doesn’t operate with the remote controller. Also, the OPERATION INDICATOR lamp doesn’t light up by press­ing the EMERGENCY OPERATION switch.
D
Check of outdoor unit
Compressor and / or outdoor fan motor doesn’t operate.(Only indoor fan operates.) MSH-C18TV
Start
Press the EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Check the voltage to the terminal block of outdoor unit. Is there 230V AC to the terminal block between
2 N
- ?
Check the voltage to the terminal block of indoor unit. Is there 230V AC to the terminal block between
N
2
- ?
No
No
Replace the indoor elec­tronic control P.C. board.
Yes
Yes
Check the continuity of indoor and outdoor unit connection.
40
Check the outdoor deicer P.C. board at first, then check the outdoor fan motor and the compressor.
Page 41
MSH-C24TV
Yes
Is there 5V DC between J101
- J401 on the deicer
P.C. board? Refer to page 46.
Compressor doesn't operate.
Yes
Is there 230V AC between A1-A2 on the compressor contactor(52C)?
Operate the unit in COOL or HEAT mode by pressing the EMERGENCY OPERATION switch. Test run operation operates for 30 minutes.
Outdoor fan motor doesn't operate.
No
Make the connection of wiring correct.
Check the compressor.
Replace the compressor contactor(52C).
Start
Yes
Is there 230V AC between 2/T1 on the compressor contactor(52C) and N on the outdoor terminal block?
Yes
Is there 230V AC between CN730 1-3 on the deicer P.C. board?
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
Yes
No
Is there 230V AC between 1/L1 on the compressor contactor(52C) and N on the outdoor terminal block?
No
No
Make the connection of wiring correct.
Yes
Yes
Is there 230V AC CN711 1-3 or 2-3 on the deicer P.C. board?
No
Make the connection of wiring correct.
Check the outdoor fan motor. Refer to page 38.
Yes
Replace the deicer P.C. board.
Replace the deicer P.C. board.
No
No
Is there 230V AC between CN730 1-3 on the deicer P.C. board?
Is there 5V DC between J101 - J401 on the deicer P.C. board? Refer to page 46.
+
-
+
-
After 30 seconds, does compressor stop?
No
Yes
Is there 230V AC between A1-A2 on the compressor contactor(52C)?
Replace the deicer P.C. board.
Yes
1 Turn OFF the power supply. 2 After 30 seconds, turn ON the power supply again. 3 Operate the unit in COOL or HEAT mode by pressing the
EMERGENCY OPERATION switch for 1 minute or more. 4 Stop it by pressing the EMERGENCY OPERATION switch twice or once.
Ok
No
After 30 seconds, does outdoor fan motor stop?
Replace the deicer P.C. board.
Yes
Ok
No
Is there 230V AC between 2/T1 on the compressor contactor(52C) and N on the outdoor terminal block?
Yes Replace the compressor contactor(52C).
No
Make the connection of wiring correct.
E
Check of outdoor unit
Compressor and/or outdoor fan motor doesn’t stop.
<MSH-C24TV only>
41
Page 42
Check of R.V. coil
F
Unit operates COOL mode even if it is set HEAT mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board. Turn ON the power supply and operate the indoor unit in HEAT mode by pressing the EMERGENCY OPERATION switch.
After 3 minutes, is there 230V AC between CN721 1-3 on the deicer P.C. board?
Yes
Replace the R.V. coil.
No
Replace the deicer P.C. board.
Unit operates HEAT mode even if it is set to COOL mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board. Turn ON the power supply and operate the indoor unit in COOL mode by pressing the EMERGENCY OPERATION switch.
After 3 minutes, is there 230V AC between CN721 1-3 on the deicer P.C. board?
Yes
Replace the deicer P.C. board.
No
Replace the R.V. coil.
42
Page 43
How to check mis-wiring and serial signal error
Measure resistance between CN 661 1 and 2.
Measure resistance between CN 662 3 and 4.
No
Yes
Replace the thermistor.
Defrost thermistor (RT61)
Re-connect CN661 and CN662. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Ambient temperature thermistor (RT63)
Does the resistance of thermistor have the characteristics on page 45 or 46?
No
Yes
Does the unit operate 10 minutes or more?
Replace the deicer P.C.
board.
Ok 3
3 It is thought defective contact of the connector.
Turn OFF the power supply.
<MSH-C24TV only>
G
Outdoor unit doesn’t operate.
Repair wiring.
Is there 20V DC between both ends of R132 when 52C contactor turns ON? ( By tester, the stylus is between 0 ~ 20V. )
1. Turn OFF the power supply.
2. Re-connect in-out connecting wire.
3. Turn ON the power supply.
Yes
1. Turn OFF the power supply and disconnect in-out connecting wire on the indoor side.
2. Short-circuit between indoor terminal block and .
3. Turn ON the power supply and press the EMERGENCY OPERATION switch.
Yes
Start
1. Turn OFF the power supply.
2. Turn ON the power supply.
3. Press the
3 min. later, when 52C contactor turns ON, what self-check result is displayed on OPERATION INDICATOR lamp on the indoor unit? ❈1
Is there mis-wiring, poor contact, or wire disconnection?
EMERGENCY OPERATION
No
No
switch.
Mis-wiring is indicated.(0.5-sec.ON, 0.5-sec.OFF)
3
N
1 Short circuit of JPG and JPS on the
indoor electronic control P.C. board enables self-check to be displayed in 3 seconds.
Serial signal error is indicated. (0.5-sec.ON, 2.5-sec.OFF)
Replace the indoor electronic control P.C. board.
Thermistors in the outdoor unit are abnormal.
W Disconnect the connector CN661 and CN662 from the deicer P.C. board.
3 minutes later, when the EMERGENCY OPERATION switch is pressed and 52C contactor turns ON, is there 230V AC between the
outdoor terminal block - ? ❈2
Is there 5V DC between J8 -J9 (MSH-C18TV) / J401 - J101 (MSH-C24TV) on the deicer P.C. board?(Refer to page 45 or 46.) ❈2
Is there 10V DC between both ends of R601?(Refer to page 45 or 46.) ❈2 (By tester, the stylus is between 5 ~10V)
H
Check of outdoor thermistor
+
Replace the deicer P.C. board.
N
2
Yes
+
Yes
Yes
No
No
(Check the characteristics of each thermistor.)
43
No
Rectify in-out connecting wire.
Check and rectify the fuse and the varistor on the deicer P.C. board.
Rectify in-out connecting wire.
2 While the serial signal error is indicated,
52C contactor alternates ON for about 10 seconds and OFF for 3 minutes. Measure the voltage when 52C contactor is ON.
Page 44
TEST POINT DIAGRAM AND VOLTAGE MSH-C18TV ­MSH-C24TV -
E1 E1
Fan motor CN211
Fuse(F11)250V AC 3.15A
Power supply input 230V AC
}
R132
0~20V DC
Auto restart function Cut the Resistor JR06. (Refer to page 34.)
+
C144
C144
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12) JPS
Timer short mode point
}
JPG
Emergency operation switch
JPG
+
JP41
Resistance(k")
}
12V DC
}
5V DC
P.C.board
44
Page 45
MUH-C18TV -
E1
Outdoor deicer P.C. board
Fan motor CN711 230V AC
}
R.V. coil
230V AC
}
R601 5~10V DC (Refer to page 43.)
}
+
230V AC
}
CN661 Defrost thermistor(RT61) (Refer to page 43.)
}
}
IC881
12V DC
Fuse (F61) 2A/250V
Defrost interval time short pin (JP607, R853) (Refer to page 33.)
+
J9
5V DC
}
J8
(Refer to page
43.)
+
+
}
52C
12V DC
Jumper wire for change in defrost setting (JPC) (See page 33.)
45
Page 46
MUH-C24TV -
Defrost thermistor (RT61)
Ambient temperature thermistor (RT63)
-20 -10 0 10 20 30 40
0
10
20
30
40
50
60
70
80
90
100
Temperature(:)
Resistance(k")
E1
Outdoor deicer P.C. board
CN661 1-2 Defrost ther­mistor (RT61)
(Refer to page 43.)
Defrost interval time short pin(JPG1, R871) (Refer to page 33.)
(Refer to page 41 and 43.)
+
J101
}
5V
DC
J401
Jumper wire for change in defrost setting (JRF) (Refer to page 33.)
CN662 3-4 Ambient tempera­ture thermistor (RT63) (Refer to page 43.)
46
Fan motor CN711
Varistor NR62
R.V. coil
}
230V AC
+
12V DC
}
Fuse(F61)
3.15A / 250V
Varistor NR61
CN7301-3
}
230V AC
(Refer to page 41.)
R601
}
10V DC
+
(Refer to page 43.)
Page 47
12
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector is a terminal
with lock mechanism
1Slide the sleeve. 2Pull the terminal while
pushing the locking lever.
1Hold the sleeve, and pull out the terminal slowly.
In case of terminal with lock mechanism, detach the terminal as shown below. There are two types ( Refer to (1) and (2)) of the terminal with lock mechanism. The terminal with no lock mechanism can be removed by pulling it out. Check the shape of the terminal and work.
<"Terminal with lock mechanism" Detaching points>
Connector
Sleeve
Locking lever
NOTE:
DISASSEMBLY INSTRUCTIONS
12-1. MSH-C18TV - MSH-C24TV -
E1E1
INDOOR UNIT
OPERATING PROCEDURE
1. Removing the front panel
(1) Remove the screw caps at the down of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board, the receiver P.C. board and the display P.C. board
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Remove the screw of the terminal cover. (4) Remove the screw of the terminal block. (5) Unhook the catch of the lamp holder. (6) Remove the receiver holder and the receiver P.C. board. (7) Remove the screw of the ground wire. (8) Disconnect all the connectors and all the lead wires on the
electronic control P.C. board.
(9) Remove the electronic control P.C. board and display P.C.
board.
Photo 1
Photo 2
PHOTOS
Front panel
Screws
47
Lamp holder
Display P.C. board
Receiver P.C. board
Screw of the termi­nal block
Indoor electronic control P.C. board
Receiver holder
Page 48
OPERATING PROCEDURE
PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con­trol P.C. board.
(5) Remove the screw of the electrical box, remove the electri-
cal box.
4. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel. (2) Remove the electrical box. (3) Unhook the catches on the both sides of the nozzle assem-
bly. (4) Remove the nozzle assembly. (5) Remove the screws of the bearing support. (6) Remove the screw of the heat exchanger unhook the
catch. (7) Lifting the heat exchanger, remove the bearing support. (8) Loose the screw fixing the line flow fan, remove the line
flow fan. (9) Remove the screws of the motor band, remove the fan
motor.
Photo 3
Photo 4
Catch
Screw of the heat exchanger
Screw of the bearing support
Screw of the
ground wire
Screw of the electrical box
Heat exchanger
48
Photo 5
Line flow fan
Indoor fan motor
Screws of the motor band
Screw of the motor bands
Page 49
12-2. MUH-C18TV -
E1
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the down of the cabinet on the both side to remove
the cabinet.
Photo 1
Photo 2
Screws
2. Removing the deicer P.C. board
(1) Remove the service panel and the cabinet. (2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
Screws
Service panel
Photo 3
Deicer P.C. board
49
Compressor
Terminal block (TB)
capacitor (C1)
Page 50
OPERATING PROCEDURE PHOTOS
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Disconnect the connector remove the clamp of fan motor
lead wire. (3) Remove the propeller fan nut and remove the propeller fan. (4) Remove screws fixing the fan motor.
Photo 4
Propeller fan
Set screws of the outdoor fan motor
Lead clamps
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor. (4) Remove the electrical assembly.
(Refer to 2) (5) Recover gas from the refrigerant circuit. (6) Disconnect the welded part of the discharge pipe. (7) Disconnect the welded part of the suction pipe. (8) Remove nuts fixing the compressor. (9) Remove the compressor.
Propeller fan nut
Photo 5
Terminal cover
Compressor
Set screws of the outdoor fan motor
Discharge pipe
Outdoor fan motor
Suction pipe
50
Compressor nuts
Page 51
12-3. MUH-C24TV -
E1
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the top panel and the top panel. (2) Remove the screw of the service panel. To remove the
service panel, pull it down toward you and unhook the catches on the both sides.
(3) Remove the screw of the cover panel. To remove the
cover panel.
(4) Remove the screws of the cabinet.
Open the cabinet to a 45-degree angle. Then lift it and unhook the catches to remove.
Photo 1
Cabinet
Photo 2
Screws of the top panel
Top panel
Service panel
Cover panel
2. Removing the deicer P.C. board
(1) Remove the top panel, the service panel and the cover
panel.
(2) Disconnect all the connectors and the terminals on the
deicer P.C. board.
(3) Remove the deicer P.C. board.
3. Removing the propeller fan and the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Remove the propeller fan nut and the propeller fan.
NOTE:Loose the propeller fan in the rotating direction for
removal. When attaching the propeller fan, align the mark on the propeller fan and the motor shaft cut section. Set the propeller fan in position by using the cut on the shaft and the mark on the propeller fan.
(3) Remove the screws and the outdoor fan motor and the
connectors. Remove the outdoor fan motor.
Photo 3
Terminal block
Photo 4
Propeller fan
Propeller fan nut
Screws of the cabinet
Deicer P.C. board
Motor support
Compressor contactor (52C)
Separator support plate
Separator
Valve bed
51
Page 52
OPERATING PROCEDURE PHOTOS
4. Removing the heat exchanger and compressor
(1) Remove the screws of the rear panel. Remove the screws
of the valve bed and the valve bed. (The valve bed is fixed by the catches on the right and left sides. Lift it to remove.) Open the rear panel to the rear to remove.
NOTE :
All panels are fixed by catches, and must be removed by up and down.
(2) Remove the screws of the side panel and the side panel. (3) Remove the screws of the rear guard and the rear guard. (4) Remove the screws of the separator support plate and
the separator support plate.
(5) Remove the screws of the motor support and the motor
support.
(6) Remove the relay panel.
Disconnect the fan motor lead wires.
(7) Remove the soundproof felt. (8) Remove the screws of the separator and the separator. (9) Recover gas from the refrigerant circuit. (10)
Remove the screws of the heat exchanger and the heat exchanger. Detach the welded part of pipe.
(11)
Remove the nuts of the compressor and the compressor.
Detach the welded part of the suction pipe and the dis­charge pipe.
Photo 5
Screws
Rear panel
Side panel
Screws
Rear guard
Photo 6
Heat exchanger
52
Photo 7
Stop valve
Compressor
Page 53
13
Symbol
in Wiring
Diagram
Q'ty/unit
Including 4,5
3PCS/SET
RemarksPart No.
NO.
Part Name
MSH-C18TV-
1 2 3 4 5 6 7
INSTALLATION PLATE BOX(WH) FRONT PANEL ASSEMBLY(WH) GRILLE(WH) SCREW CAP(WH) AIR FILTER LAMP PANEL(WH)
(WH)
E1
1 1 1 1 3 2 1
1 1 1 1 3 2 1
MSH-C24TV-
(WH)
E1
E02 141 970 E02 143 234 E02 138 000 E02 138 010 E02 143 067 E02 141 100 E02 516 007
PARTS LIST
MSH-C18TV - (WH) MSH-C24TV - (WH)
E1
E1
13-1. INDOOR UNIT
STRUCTURAL PARTS
1
2
3
4
5
13-2. INDOOR UNIT
HEAT EXCHANGER
8
Optional parts (See page 58.)
6
910
13-1. INDOOR UNIT STRUCTURAL PARTS
Part number that is circled is not shown in the illustration.
13-2. INDOOR UNIT HEAT EXCHANGER
E02 141 620
8
E02 138 667
9
E02 176 667 E02 138 666
10
INDOOR HEAT EXCHANGER UNION(LIQUID) UNION(LIQUID) UNION(GAS)
53
1 1
1
1
1 1
{6.35 {9.52 {15.88
Page 54
1 2 3 4 5 6 7 8
9
10 11
12 13
14 15
16 17 18
19
20
NO.
E02 141 302 E02 001 504 E02 141 509 E02 408 702 E02 143 235 E02 143 040 E02 138 307 E02 141 303 E02 138 395 E02 320 395 E02 581 375 E02 540 375 E02 138 308 E02 141 468 E02 581 452 E02 582 452 E02 141 300 E02 213 300 E02 001 505 E02 138 329 E02 336 385 E02 127 382 E02 205 381 E02 209 381 E02 138 383 E02 147 383
LINE FLOW FAN SLEEVE BEARING BEARING MOUNT DRAIN HOSE NOZZLE(WH) VANE(WH) INDOOR COIL THERMISTOR VANE MOTOR POWER SUPPLY CORD POWER SUPPLY CORD TERMINAL BLOCK TERMINAL BLOCK ROOM TEMPERATURE THERMISTOR RECEIVER P. C. BOARD ELECTRONIC CONTROL P.C. BOARD ELECTRONIC CONTROL P.C. BOARD INDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR RUBBER MOUNT DISPLAY P.C. BOARD VARISTOR FUSE THERMAL FUSE THERMAL FUSE SURGE ABSORBER SURGE ABSORBER
Part No.
Symbol
in Wiring
Diagram
Part Name
RT12
MV
TB TB
RT11
MF MF
NR11
F11 F12
F12 DSAR DSAR
Q'ty/unit
MSH-C18TV-
1 1 1 1 1 1 1 1 1
1
1 1 1
1
2 1 1 1 1
1
1 1 1 1 1 1 1 1
1
1 1 1
1
1 2 1 1 1
1
1
(WH)
E1
MSH-C24TV-
(WH)
E1
AUTO RESTART AUTO RESTART RA4V27 ­RA4V27 ­2PCS/SET
3.15A 93: 93:
Remarks
MSH-C18TV - (WH)
E02 581 426 E02 527 083
21 22
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
1 1
1 1
MSH-C24TV - (WH)
E1
E1
13-3. INDOOR UNIT
FUNCTIONAL PARTS AND ELECTRICAL PARTS
1
SLEEVE BEARING
2
3
16
15
13-4. ACCESSORY P ARTS
AND REMOTE CONTROLLER
13
21 22
4
14
5
7
12
6
INDOOR COIL THERMISTOR
8
10
9
11
ROOM TEMPERATURE THERMISTOR
13-3. INDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS
Part numbers that are circled are not shown in the illustration.
54
13-4. ACCESSORY PARTS AND REMOTE CONTROLLER
Page 55
MUH-C18TV -
E1
13-5. OUTDOOR UNIT
STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS
1
DEFROST THERMISTOR
18
15
17
16
2
4
Part numbers that are circled are not shown in the illustration.
Part No. Part Name
NO.
E02 140 233
1
E02 141 232
2
E02 141 521
3
E02 643 630
4
E02 141 501
5
E02 139 515
6
E02 138 506
7
E02 516 900
8
E02 277 290
9
E02 624 661
10
E02 621 662
11
E02 141 245
12
E02 444 961
13
E02 277 353
14
E02 144 301
15
E02 540 374
16
E02 643 451
17
E02 440 310
18
E02 004 340
19
E02 339 936
20
E02 624 936 E02 095 382
21
E02 139 490
22
E02 128 383
23
E02 214 642
24
BACK PANEL CABINET GRILLE OUTDOOR HEAT EXCHANGER PROPELLER FAN MOTOR SUPPORT COMPRESSOR RUBBER SET COMPRESSOR BASE STOP VALVE(GAS) STOP VALVE(LIQUID) SERVICE PANEL 4-WAY VALVE COMPRESSOR CAPACITOR OUTDOOR FAN MOTOR TERMINAL BLOCK DEICER P.C. BOARD DEFROST THERMISTOR COMPRESSOR CONTACTOR CAPILLARY TUBE CAPILLARY TUBE FUSE R. V. COIL SURGE ABSORBER CHECK VALVE
653
Symbol
in Wiring
Diagram
MC
C1
MF
TB
RT61
52C
F61
21S4
DSAR
7
MUH-C18TV-
8
Q'ty/unit
1 1 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 1 1
14
13
12
11 10
9
E1
Remarks
4RUBBERS/SET PE-36VPEHT
{15.88 { 6.35
55+/420V AC RA6V50 ­4P
{3.0{1.4600 {3.0{2.0850
250V / 2A
55
Page 56
MUH-C24TV -
E1
13-6. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
28
1
2
3
4
5
6
7
27
10
11 12
26
8
25
24
23
22
2
13
8
9
14
17
15
16
18
19
21
20
56
Page 57
MUH-C24TV -
E1
13-6. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS
AND FUNCTIONAL PARTS
Part numbers that are circled are not shown in the illustration.
Q'ty/unit
MUH-C24TV -
1 1 1 1 1 1 1 3 1 1 1 1 4 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Part No.
NO.
1
E02 214 297
2
E02 578 309
3
E02 644 630
4
E02 214 301
5
E07 214 501
6
E02 214 290
7
E02 214 232
8
E07 001 009
9
E02 527 521
10
E02 444 961
11
E02 529 490
12
E02 529 310
13
E02 138 506
14
E02 517 900
15
E02 644 662
16
E02 644 661
17
E02 214 245
18
E07 001 006
19
E02 540 374
20
E02 138 351
21
E02 128 383
22
E02 010 342
23
E02 082 353
24
E02 644 451
25
E02 214 522
26
E02 605 523
27
E02 214 249
28
E02 527 515
29
E02 127 382
30
E02 214 384
31
E02 644 936
Part Name
TOP PANEL AMBIENT TEMPERATURE THRMISTOR OUTDOOR HEAT EXCHANGER OUTDOOR FAN MOTOR PROPELLER FAN BASE CABINET HANDLE FAN GUARD 4-WAY VALVE R.V. COIL DEFROST THERMISTOR COMPRESSOR RUBBER SET COMPRESSOR STOP VALVE(LIQUID) STOP VALVE(GAS) SERVICE PANEL COVER PANEL TERMINAL BLOCK OUTDOOR FAN CAPACITOR SURGE ABSORBER COMPRESSOR CONTACTOR COMPRESSOR CAPACITOR DEICER P.C. BOARD REAR PANEL REAR GUARD SIDE PANEL MOTOR SUPPORT FUSE CZ SURGE ABSORBER CAPILLARY TUBE
Symbol
in Wiring
Diagram
RT63
MF
21S4 RT61
MC
TB C2
DSAR
52C
C1
F61
CZ
E1
Remarks
RA6V85-
4RUBBERS/SET NE-47VMHHT
{9.52 {15.88
4P
3.0+/440V AC
50+/440V AC
250V/3.15A
{3.0O{2.0O450
57
Page 58
Deodorizing filter (Gray sponge type)
,
Air cleanig filter (White bellows type)
Model
Part No.
MAC-1100FT
MSH-C18TV-
E1
MSH-C24TV-
E1
Model
Part No.
MAC-1600DF
MSH-C18TV-
E1
MSH-C24TV-
E1
MUH-C18TV ­MUH-C24TV -
E1
E1
13-7. ACCESSORY PARTS
1
2
1
2 1
Q'ty/unit
E1
MUH-C24TV-
E1
1 6
[33 [16
NO.
E02 444 704
1
E02 329 704 E02 444 705
2
E02 444 706
14
Part No.
DRAIN SOCKET DRAIN SOCKET DRAIN CAP DRAIN CAP
Part Name
OPTIONAL PARTS
Symbol
in Wiring
Diagram
MUH-C18TV-
14-1. AIR CLEANING FILTER
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
Remarks
14-2. DEODORIZING FILTER
DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odor of pets.
Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.
When the filter color is still dark even after cleaning, replace the filter with a new one.
Replace the filter at least once a year.
DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
58
Page 59
Page 60
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI CHIYODA-KU, TOKYO100-8310, JAPAN
CC
Copyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD Distributed in Feb. 2001. No.OB279 PDF 248 Made in Japan
New publication, effective Feb. 2001 Specifications subject to change without notice.
Loading...