Mitsubishi Electronics MSH-A18ND User Manual

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
SERVICE MANUAL
Wireless type Models
Revision B:
•Remote controller model has been changed.
•RoHS PARTS LIST has been added. Please void OB427 REVISED EDITION-A.
No. OB427
REVISED EDITION-B
MSH-A18ND ­MSH-A24ND -
MSH-A18ND MSH-A24ND
S1
S1
Outdoor unit service manual
MUH-A·ND Series (OB428)
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················2
3. SPECIFICATION·················································4
4. OUTLINES AND DIMENSIONS·························5
5. WIRING DIAGRAM ············································6
6. REFRIGERANT SYSTEM DIAGRAM················7
7. SERVICE FUNCTIONS ······································8
8. TROUBLESHOOTING······································10
10. PARTS LIST······················································20
11. RoHS PARTS LIST···········································23
NOTE:
This service manual describes technical data of the indoor units. RoHS compliant products have <G> mark on the spec name plate. For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant).
TM
Grille
Air inlet
Remote controller
Remote control
receiving section
Air cleaning filter (White bellows type)
Horizontal vane
Vertical vanes
Catechin air filter
(When the grille is opened)
Operation section
Display section
Emergency operation switch
Operation indicator lamp
Remote control
receiving section
Front panel
1 2 3 4 5 6 7 8
Installation plate Installation plate fixing screw 4 o 25 mm Remote controller holder Fixing screw for 3 o 3.5 o 1.6 mm (Black) Battery (AAA) for remote controller Wireless remote controller Air cleaning filter Felt tape (Used for left or left-rear piping)
1 7 1 2 2 1 2 1
MSH-A18ND MSH-A24ND
Revision A:
Parts No. of 10.PARTS LIST has been revised.
Revision B:
•Remote controller model has been changed. (KP0A ➔ KM04A) Both remote controllers can be used as alternative.
•RoHS PARTS LIST has been added.
1
MSH-18TN - MSH-A18ND ­MSH-24TN - MSH-A24ND -
1. Model name has been changed.
2. Grille design has been changed.
3. Unit size has been changed.(W 1,015a o H 320a o D 190a W 1,100a o H 325a o D 258a)
4. Electricity receiving unit has been changed from indoor unit to outdoor unit.
2
TECHNICAL CHANGES
S1S1
S1S1
PART NAMES AND FUNCTIONS
INDOOR UNIT
MSH-A18ND MSH-A24ND
ACCESSORIES
2
REMOTE CONTROLLER
ON/OFF
TOO
COOL
PM
AM
TOO
WARM
ON/OFF
FAN
TOO
WARM
TOO
COOL
VANE
MODE
ECONO COOL
STOP
START
HR.
MIN.
WIDE VANE
LONG
I FEEL
COOL
HEAT
DRY
PM
CLOCK
AM
RESET CLOCK
Open the front lid.
Signal transmitting section
Operation display section
OPERATE /STOP (ON /OFF) button
TEMPERATURE buttons
OPERATION SELECT button
FAN SPEED CONTROL button
OFF-TIMER button
HR. button
MIN. button
(TIME SET button)
ON-TIMER button
RESET button
ECONO COOL button
VANE button
(Horizontal vane button)
CLOCK SET button
LONG button
WIDE VANE button
(Vertical vane button)
Indication of remote controller model is on back.
MSH-A18ND MSH-A24ND
3
3
Indoor model
Function
Power supply
Air flow
(High/Med./Low) Running current Power input Power factor Model Current Winding resistance (at 20:) Dimensions WOHOD Weight Air direction Sound level (High/Med./Low) Fan speed (High/Med./Low) Fan speed regulator Remote controller model
K /h
A W %
A
"
mm
kg
dB
rpm
Single phase
220V, 60Hz
768/642/516
0.28 60 97
RC4N32-AA
0.28
WHT-BLK 205.5 BLK-RED 217.6 1,100O325O258
16
5
42/37/32
1,070/920/780
3
KP0A, KM04A
Cooling
Heating Cooling
954/822/684
1,280/1,130/970
Heating
954/834/726
1,280/1,150/1,020
Single phase
220V, 60Hz
0.37 81 99
RC4V40-AA
0.37
WHT-BLK 138.2 BLK-RED 159.0 1,100O325O258
16
5
47/42/37
3
KP0A, KM04A
Electrical
data
Fan
motor
Special
remarks
Capacity
MSH-A18ND MSH-A24ND
SPECIFICATION
NOTE: Test conditions are based on ISO 5151.
Cooling : Indoor DB27°C WB19°C Heating : Indoor DB20°C WB 15.5°C
Indoor-Outdoor piping length : 5m
Test conditions are based on SSA 356/366. Cooling : Indoor DB29°C WB19°C Heating : Indoor DB21°C
Indoor-Outdoor piping length : 7.5m
Outdoor DB35°C WB(24°C) Outdoor DB 7°C WB 6°C
Outdoor DB46°C WB24°C Outdoor DB 7°C WB 6°C
4
4
258
162
19
58
47
7.5
315
255.547
2.5
98
173
98 173414.5 414.5
5
253
791
56
1068
1100
325
Air out
Air in
Insulation [28
Drain hose [16 (Connected part O.D)
Installation plate
Wall hole [75
Wireless remote controller
Installation plate
Indoor unit
{
Liquid line [ 6.35-0.5m Gas line [ 12-0.43m Insulation [ 50 O.D
[ 32 I.D
{
Liquid line [ 9.52-0.5m Gas line [ 12-0.43m Insulation [ 50 O.D
[ 32 I.D
for MSH-A18ND
for MSH-A24ND
OUTLINES AND DIMENSIONS
MSH-A18ND MSH-A24ND
INDOOR UNIT
Unit: mm
5
5
WIRING DIAGRAM
MSH-A18ND
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220V~
SYMBOL
C11 F11
HIC1
MF
NOTES:
INDOOR FAN CAPACITOR FUSE (3.15A) DC/DC CONVERTER FAN MOTOR (INNER PROTECTOR)
1.About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
TB
3 N 2
RED BLU BRN
NAME
CN 151
GRN/YLW
MV2 MV2 MV1
: Connector
15
SYMBOL
NR11 RT11
CN201
3 2 1
F11
CN 102
TAB12
CN
ELECTRONIC CONTROL P.C. BOARD
101
33
DISPLAY P.C.BOARD
RECEIVER P.C.BOARD
NAME MV1 MV2
VANE MOTOR (HORIZONTAL) VANE MOTOR (VERTICAL) VARISTOR ROOM TEMPERATURE THERMISTOR
HIC1
NR11
SR141
REMOTE CONTROLLER
C11
CN211
SYMBOL
RT12
SR141
TB
CN 112
CN 111
CN 121
3
1 3 4
RT12 RT11
BLK GRY YLW BRN WHT RED
MF
NAME INDOOR COIL THERMISTOR SOLID STATE RELAY TERMINAL BLOCK
MSH-A24ND
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
12V
220V~
SYMBOL
C11 F11
HIC1
MF
MV1
NOTES:
INDOOR FAN CAPACITOR FUSE (3.15A) DC/DC CONVERTER INDOOR FAN MOTOR (INNER PROTECTOR) VANE MOTOR (HORIZONTAL)
1.About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
2.Use copper conductors only. (For field wiring)
3.Symbols below indicate. : Terminal block
TB
3 N 2
RED BLU BRN
GRN/YLW
NAME
MV2
CN
151
MV2
15
MV1
SYMBOL
NR11 RT11 RT12 RT13
: Connector
CN201
3
2 1
TAB12
CN 102
CN
ELECTRONIC CONTROL P.C. BOARD
101
33
DISPLAY P.C.BOARD
RECEIVER P.C.BOARD
NAME NAME
MV2
VANE MOTOR (VERTICAL) VARISTOR ROOM TEMPERATURE THERMIST OR INDOOR COIL THERMISTOR (MAIN) INDOOR COIL THERMISTOR (SUB)
6
HIC1
F11
REMOTE CONTROLLER
NR11
SR141
4 3 2 1
CN112
CN 121
1
C11
3 4
CN211
CN
111
SYMBOL
SR141
TB
RT13
RT12
3
BLK GRY YLW BRN WHT RED
RT11
MF
SOLID STATE RELAY TERMINAL BLOCK
6
Strainer
#50
Strainer
#50
REFRIGERANT SYSTEM DIAGRAM
MSH-A18ND
INDOOR UNIT
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Distributor
Refrigerant pipe [12.7 (with heat insulator)
Flared connection
Flared connection
MSH-A24ND
INDOOR UNIT
Indoor heat exchanger
Indoor coil thermistor RT13(sub)
Room temperature thermistor RT11
Indoor coil thermistor RT12(main)
Distributor
Unit:mm
Refrigerant pipe [15.88 (with heat insulator)
Flared connection
Flared connection
Refrigerant pipe [6.35 (with heat insulator)
Refrigerant pipe [6.35 (with heat insulator)
Refrigerant flow in cooling Refrigerant flow in heating
7
7
No. 1 unit No. 2 unit No. 3 unit No. 4 unit
1 unit operation No modification
– – –
2 units operation
Same as at left
Solder J1
– –
3 units operation
Same as at left Same as at left
Solder J2
4 units operation
Same as at left Same as at left Same as at left
Solder both J1 and J2
SERVICE FUNCTIONS
MSH-A18ND MSH-A24ND
7-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board. The time will be shortened as follows. Set time : 1 minute 1-second Set time : 3 minute 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit of JPG and JPS.)
7-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
NOTE : For modification, take out the batteries and press the OPERATE/STOP(ON/OFF) button 2 or 3 times at first.
After modification, put back the batteries then press the RESET button.
Remote controller model : KM04A
J2
J1
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1. After modification, press the RESET button.
Remote controller model : KP0A
J2
Table 1
J1
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote controller for the indoor unit. The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are set. The setting will be cancelled if the breaker has turned off, or the power supply has shut down. Please conduct the above setting once again after the power has restored.
7-3. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. Auto restart function automatically starts operation in the same mode just before the shutoff of the main power. However if the unit is operated in I FEELCONTROL mode before power failure, the operation is not memorized. In I FEEL CONTROL mode, the operation is decided by the initial room tempera­ture.
8
How to release AUTO RESTART FUNCTION
JR07
IC152
CN151
CN112
CN111
CN121
SW1
IC101
RA102
C11
CN201
CN211
TAB12
1Turn off the main power for the unit. 2Pull out the electronic control P.C. board, the receiver P.C.
board and the display P.C.board. (Refer to 9-2.)
3Solder jumper wire to JR07 on the indoor
electronic control P.C. board. (Refer to 8-6.)
Operation
If the main power has been cut, the operation settings remain.
1 2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
NOTE
The operation settings are memorized when 10 seconds have passed after the remote controller was operated with the
remote controller.
If main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is
cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart. Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current by adding to the system that allows the units to start one by one.