Mitsubishi Electric MS12, MS17TN, MSH12, MS15, MSH15TN Installation Manual

Page 1
VG79A008H02
SPLIT-TYPE AIR CONDITIONERS Models
MS12/15/17TN MSH12/15TN
Series
[FLARE CONNECTION TYPE]
ADVANCED AND EVER ADVANCING
INSTALLATION MANUAL
1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY
Please report to your supply authority or obtain their consent before connecting
this equipment to the power supply system. Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR
SAFETY” before installing the air conditioner. Be sure to observe the cautions specified here as they include important items
related to safety. The indications and meanings are as follows.
WARNING
Could lead to death, serious injury, etc.
CAUTION
Could lead to serious injury in particular environments when operated incorrectly.
After reading this manual, be sure to keep it together with the OPERATING
INSTRUCTIONS in a handy place on the customer’s site.
WARNING
Do not install the unit by yourself (customer).
Incomplete installation could cause injury due to fire, electric shock, the unit falling or leakage of water. Consult the dealer from whom you purchased the unit or special installer.
Install the unit securely in a place which can bear the weight of the unit.
When installed in an insufficient strong place, the unit could fall causing injury.
Use the indoor/outdoor unit connecting wire that meets the Standards to
connect the indoor and outdoor units and fix the wire to the terminal block securely so that no external force is conveyed to the connecting section of the terminal block.
Incomplete connection or fixing of the wire could result in a fire.
Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.
It could cause a fire or an electric shock due to defective contact, defective insulation, exceeding the permissible current, etc.
Check that the refrigerant gas do not leak after installation has com-
pleted.
Perform the installation securely referring to the installation manual.
Incomplete installation could cause a personal injury due to fire, electric shock, the unit falling or leakage of water.
Perform electrical work according to the installation manual and be sure
to use an exclusive circuit.
If the capacity of the power circuit is insufficient or there is incomplete electrical work, it could result in a fire or an electric shock.
Attach the electrical cover to the indoor unit and the service panel to the
outdoor unit securely.
If the electrical cover in the indoor unit and/or the service panel in the outdoor unit are not attached securely, it could result in a fire or an electric shock due to dust, water, etc.
Be sure to use the part provided or specified parts for the installation
work.
The use of defective parts could cause an injury due to a fire, an electric shock, the unit falling, leakage of water, etc.
Be sure to cut off the main power in case of setting up the indoor
electronic control P.C. board or wiring works.
It could cause an electric shock.
CAUTION
Ground the unit.
Do not connect the ground to a gas pipe, water pipe, lightning rod or telephone ground. Defective grounding could cause an electric shock.
Do not install the unit in a place where an inflammable gas leaks.
If gas leak and accumulate in the area surrounding the unit, it could cause an explosion.
Install a ground leakage breaker depending on the installation place (Where it is humid).
If a ground leakage breaker is not installed, it could cause an electric shock.
Perform the drainage/piping work securely according to the installation manual.
If there is a defect in the drainage/piping work, water could drop from the unit and household goods could be wet and damaged.
2. SELECTING THE INSTALLATION LOCATION
2-1 INDOOR UNIT
Where airflow is not blocked.
Where cool air spreads over the entire room.
Maximum refrigerant piping length between indoor unit and outdoor unit is 49 ft.
and the difference of height of both units is 25 ft. maximum. Rigid wall without vibration.
Where it is not exposed to direct sunshine.
Where easily drained.
At a distance 3 ft. or more away from your TV and radio (to prevent picture from
being distorted or noise from being generated). In a place as far away as possible from fluorescent and incandescent lights (so
the infrared remote control can operate the air conditioner normally). Where the air filter can be removed and replaced easily.
2-2 OUTDOOR UNIT
Where it is not exposed to strong wind.
Where airflow is good and dustless.
Where it is not exposed to rain and direct sunshine.
Where neighbours are not annoyed by operation sound or hot air.
Where rigid wall or support is available to prevent the increase of operation sound
or vibration. Where there is no risk of combustible gas leakage.
When installing the unit at a high level, be sure to fix the unit legs.
Where it is at least 10 ft. away from the antenna of TV set or radio. (Otherwise,
images would be disturbed or noise would be generated.) Install the unit horizontally.
CAUTION
Avoid the following places for installation where air conditioner trouble is liable to occur.
Where there is too much machine oil.
Salty environment as seaside areas.
Hot-spring areas.
Where sulfide gas exists.
Other special atmospheric areas.
2-3 WIRELESS REMOTE CONTROLLER MOUNTING
Place of mounting
• Where it is easy to operate and easily visible.
• Where children can not touch.
Mounting
Select a position about 4 ft. above the floor, check that signals from the remote controller are surely received by the indoor unit from that position (‘beep’ or ‘beep­beep’ receiving tone sounds). After that, attach remote controller mounting hardware 3 to a pillar or wall and set the wireless remote controller 6.
In rooms where inverter type fluorescent lamps are used, the signal from the wireless remote controller may not be received.
Page 2
I
A
33-7/16
11-7/16
12-7/32
19-11/16
3/4 3/4
3/8
30-3/4
10-1/16
11-7/32
19-11/16
I
A
1
2
C
D
H
E
B
G
F
7
3
4
6
3. INSTALLATION DIAGRAM & ACCESSORIES
5
FLARED CONNECTIONS
This unit has flared connections on both indoor and outdoor sides.
Remove the valve cover of the outdoor unit, then connect the pipe.
Refrigerant pipes are used to connect the indoor and outdoor units.
Limits
Pipe length 49 ft. max.
Height difference 25 ft. max.
No. of bends 10 max.
Refrigerant adjustment ... If pipe length exceeds 25 ft., additional refrigerant
(R-22) charge is required. (The outdoor unit is charged with refrigerant for pipe length up to 25 ft..)
Up to 25 ft. No additional charge is required.
Pipe length
Exceeding 25 ft.
Refrigerant to MS type 0.53 oz each 5 ft.
be added MSH type 2.68 oz each 5 ft.
ACCESSORIES
Check the following parts before installation.
1 Installation plate 1
2 Installation plate fixing screw 4 × 25 mm 6
3 Remote controller mounting hardware 1
4 Fixing screw for 3 3.5 × 16 mm (Black) 2
5 Battery (AAA) for remote controller 2
6 Wireless remote controller 1
7 Felt tape (Used for left or left-rear piping) 1
PART TO BE PROVIDED AT YOUR SITE
Optional extension pipe
A Indoor/outdoor unit connecting wire 1 B Extension pipe 1
C Wall hole sleeve 1 D Wall hole cover 1
Pipe fixing band (The quantity depends
E
on the pipe length.) Fixing screw for E 4 × 20 mm (The
F
quantity depends on the pipe length.)
G Piping tape 1 H Putty 1
Drain hose (or soft PVC. hose,
I
19/32 in. inner dia. or hard PVC pipe VP16)
J Refrigeration oil 1
Additional charge is required.
(Refer to the table below.)
2 to 5
2 to 5
1
10 in. or more
PIPING PREPARATION
1 Table below shows the specifications of pipes commercially available. 2 Ensure that the 2 refrigerant pipes are insulated to prevent condensation. 3 Refrigerant pipe bending radius must be 4 in. or more.
Pipe
Outside diameter
For liquid 1/4 0.0265 5/16
12 type 1/2 0.0285 5/16
For gas
15, 17 type 5/8 0.0315 5/16
Minimum wall thickness is UL1995 33’s reference.
Refrigerant pipes of 10, 16, 23, 33 and 49 ft. are available as optional items.
Be sure to use the insulation of specified thickness. Excessive thickness may cause incorrect installation of the indoor unit and lack of thickness may cause dew drippage.
3-3/16 in. or more
1-3/6 in. or more
Minimum wall thickness
inch inch
Insulation thickness
Insulation
material
Heat resisting foam plastic Specific gravity 0.045
CAUTION
Decide the installation position using mark on the installation plate indicating the indoor unit size as reference.
Be careful the drain hose is not raised.
10 in. or more
Piping can be directed towards rear, right, downward, left or left-rear directions.
Rear side Right
Rear
Downward
Lock the catch.
Front
Left-rear
Left
MU12TN and MUH12TN
4 in. or more
Air outlet
14 in. or more
4-3/8 × 13/16 slot
4 in. or more
4 in. or more
16 in. or more
Note: If clearance behind the outdoor unit is only 15-3/4 or 20 in., side A must be fully opened.
MU15/17TN and MUH15TN
4 in. or more
4 in. or more
Note: If clearance behind the outdoor unit is only 15-3/4 or 20 in., side A must be fully opened.
20 in. or more
Air outlet
4 in. or more
14 in. or more
4-3/8 × 13/16 slot
Separate the 2 connecting pipes and apply insulation individually.
5/16 in. thickness thermal insulation plastic.
When the piping is to be attached to a wall containing metals (tin plated) or metal netting, use a chemically treated wooden piece 13/16 in. or thicker between the wall and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
(Unit: inch)
Units should be installed by licensed contrac­tor according to local code requirement.
Page 3
4. INDOOR UNIT INSTALLATION
4-1 FIXING OF INSTALLATION PLATE
Find a structural material (such as a stud) in the wall and fix installation plate
horizontally.
Tie a piece of thread to the hole.
3-3/16 in. or more
10 in. or more
Fix the installation plate 1 so that the plumb string stays in this range.
When bolts recessed in the concrete wall are to be utilized, secure the installation plate 1 using 7/16 in. × 13/16 in. · 7/16 in. × 1 in. oval hole (17-3/4 in. mm pitch). If the recessed bolt is too long, change it for a shorter one available in the market.
4-2 WALL HOLE DRILLING
1 Determine the wall hole position. 2 Drill a 3 in. hole so that outside can be lower than inside. 3 Insert the wall hole sleeve C.
Positioning of the holes on the wall
Fixing screw 2 4 × 25 (6 pieces)
Installation plate 1
10 in. or more
Secure the arrow marked hole as much as possible.
Horizontal level can be easily obtained by handing a piece of weight in a piece of thread and matching with a triangle
mark.
4-3 POWER SUPPLY AND INDOOR/OUTDOOR CON-
NECTING WIRE CONNECTION
Power should be taken from an exclusive branched circuit.
Wiring work should be based on applicable technical standards.
Wiring connections should be made following the diagram.
Screws should be tightened so they won’t loosen.
ELECTRICAL SPECIFICATIONS
MODEL MS12TN MS15TN MS17TN
INDOOR UNIT
Power supply (V, PHASE, Hz) 115, 1, 60 115, 1, 60 115, 1, 60
Min. Circuit Ampacity 0.6 0.6 0.7
Fan motor (F.L.A) 0.43 0.43 0.51
OUTDOOR UNIT
Power supply (V, PHASE, Hz) 208/230, 1, 60 208/230, 1, 60 208/230, 1, 60
Max. Fuse size (time delay) (A) 15 20 20
Min. Circuit Ampacity 12 14 15
Fan motor (F.L.A) 0.42 0.52 0.52
Compressor
Control voltage
MODEL MSH12TN MSH15TN
Power supply (V, PHASE, Hz) 115, 1, 60 115, 1, 60
Min. Circuit Ampacity 0.6 0.6
Fan motor (F.L.A) 0.43 0.43
Power supply (V, PHASE, Hz) 208/230, 1, 60 208/230, 1, 60
Max. Fuse size (time delay) (A) 15 20
Min. Circuit Ampacity 14 14
Fan motor (F.L.A) 0.42 0.52
Compressor
Control voltage
(R.L.A) 9.0 10.0 11.0
(L.R.A) 29.0 35.0 38.0
Indoor unit-Remote controller : (Wireless) Indoor unit-Outdoor unit : DC12V (Polar)
ELECTRICAL SPECIFICATIONS
INDOOR UNIT
OUTDOOR UNIT
(R.L.A) 10.0 10.0
(L.R.A) 35.0 35.0
Indoor unit-Remote controller : (Wireless) Indoor unit-Outdoor unit : DC12V (Polar)
4 in. 3-3/16 in.
Insert the scale.
3-3/16 in.
Align scale with the line.
Wall hole
3 in. dia.
(Indoor side)
(Wall hole cross section)
Center of 3 in. diameter.
Wall thickness
One scale
Wall hole sleeve C
Be sure to use wall hole sleeve C to prevent the outdoor connecting wires from contacting with metal part in the wall and to prevent damage by rat in case the wall is hollow.
Wall hole sealing and fixing pipe to wall
Wall hole cover D
Indoor unit
Wall hole
sleeve C
Seal the wall hole gap with putty H.
Fix the pipe to wall with pipe fixing band E.
Cut off the extra length. Pipe fixing
Fixing screw F
Cut with 1 extra scale length.
band E
Note:
If the indoor unit is powered from outdoor unit, a separate circuit breaker is not required but a disconnect switch may be required by local code. If the indoor unit is powered from an independent power supply, a dedicated circuit breaker or maximum fuse size of 15 A must be installed for the indoor unit, and a disconnect switch may also be required. (Refer to the figures on the right.)
1 Remove the front panel (Refer to 7-1) 2 Remove the electrical cover 3 Remove the display panel
Electrical cover
Display panel
Grounding terminal
4 Fix the conduit connector to conduit cover with lock nut,
then secure it against electrical box with screws.
Electrical box
Conduit cover
Connector
Conduit
Lock nut
Page 4
13N
L1
13N
L1
N
L1 L2
12N
L1
12N
L1
N
L1 L2
90°
5. OUTDOOR UNIT INSTALLATION
Conduit cover
Connector
Lock nut
Service panel
Grounding terminal
5-1 POWER SUPPLY AND INDOOR AND OUTDOOR
WIRE CONNECTION
Connect the indoor/outdoor unit connecting wire A from the indoor unit correctly on
the terminal block. For future servicing, give extra length to connecting wire.
Connect wires to the matching numbers of terminals.
Loosen terminal screw.
Lead wire
5-2 GROUNDING
Remove the service panel.
Fix the conduit connector to conduit cover with lock nut then secure it against unit
with screw. Leave some slack in wires to allow easier servicing.
MU12TN and MUH12TN
Lock nut
Service panel
Connector
MU12/15/17TN
Remark:
Indoor unit can also be
powered from an independent power supply [Max. Fuse size (time delay) : 15 A]. In this case these indoor/outdoor connecting wires for indoor power supply are not necessary.
∗∗ A disconnect switch may
be required. Check the local code.
MUH12/15TN
Remark:
Indoor unit can also be
powered from an independent power supply [Max. Fuse size (time delay) : 15 A]. In this case these indoor/ outdoor connecting wires for indoor power supply are not necessary.
∗∗ A disconnect switch may
be required. Check the local code.
Terminal block
DC12 V (Polar)
DC12 V (Polar)
<Connection details>
INDOOR UNIT
Terminal block
Terminal block 2
OUTDOOR UNIT
INDOOR UNIT
Terminal block
Terminal block 2
OUTDOOR UNIT
Grounding terminal
Disconnect switch ∗∗
115V AC 1phase, 60Hz
∗∗
Ground
Grounding terminal
Grounding terminal
Grounding terminal
Terminal block 1
Ground
Power supply 208/230V AC, 1phase 3wires, 60Hz
Disconnect switch
115V AC 1phase, 60Hz
Terminal block 1
Power supply 208/230V AC, 1phase 3wires, 60Hz
Grounding terminal
Conduit cover
MU15/17TN and MUH15TN
CAUTION
Use care so as connecting wires do not contact pipes.
WARNING
Be sure to attach the service panel of the outdoor unit securely. If it is not attached correctly, it could result in a fire or an electric shock due to dust, water, etc.
6. INDOOR/OUTDOOR UNIT CONNECTION FINISHING AND TEST RUN
6-1 FLARING WORK
Main cause of gas leakage is defect in flaring work.
Perform flaring work correctly in the following procedure.
CONNECTING WIRES
• Wire to be AWG22 double insulated, 300 V insulation. Equal to Belden 9407 (for 12 V DC).
• Use copper conductors only.
CAUTION
Be careful not to make mis-wiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to confirm that they do not move.
If the connecting wire is incorrectly connected to the terminal block, the unit does
not operate normally. If a ground is incorrect, it may cause an electric shock.
1
Pipe cutting
• Cut the copper pipe correctly with pipe cutter.
Copper pipe
2
Burrs removal
• Completely remove all burrs from the cut cross section of the pipe.
• Put the end of the copper pipe downward to prevent burrs from dropping in the pipe.
Burr
Good
Copper pipe
Spare reamer
Pipe cutter
No good
Tilted
Uneven Burred
Page 5
AIR INTAKE GRILLE
ELECTRICAL COVER
Fixing screws
Indoor and outdoor connecting wire A
WARNING
Use the indoor/outdoor unit connecting wire that meets the Standards to connect
the indoor and outdoor units and fix the wire to the terminal block securely so that no external force is conveyed to the connecting section of the terminal block. Incomplete connection or fixing of the wire could result in a fire. Attach the electrical cover securely. If it is attached incorrectly, it could result in a
fire or an electric shock due to dust, water, etc.
Connect wires to the matching numbers of terminals.
MS12/15/17TN
Remark:
Indoor unit can also be
powered from an independent power supply [Max. Fuse size (time delay) : 15 A]. In this case these indoor/ outdoor connecting wires for indoor power supply are not necessary.
∗∗ A disconnect switch may
be required. Check the local code.
MSH12/15TN
Remark:
Indoor unit can also be
powered from an independent power supply [Max. Fuse size (time delay) : 15 A]. In this case these indoor/ outdoor connecting wires for indoor power supply are not necessary.
∗∗ A disconnect switch may
be required. Check the local code.
CONNECTING WIRES
• Wire to be AWG22 double insulated, 300 V insulation. Equal to Belden 9407 (for 12 V DC).
• Use copper conductors only.
DC12 V (Polar)
DC12 V (Polar)
Loosen terminal screw.
Terminal block
INDOOR UNIT
Terminal block
12N
L1
Disconnect switch ∗∗
115V AC 1phase, 60Hz
Terminal
12N
Terminal block 2
OUTDOOR UNIT
INDOOR UNIT
Terminal block
13N
13N
Terminal block 2
OUTDOOR UNIT
block 1
L1
L1 L2
Power supply 208/230V AC, 1phase 3wires, 60Hz
L1
Disconnect switch
115V AC 1phase, 60Hz
Terminal block 1
L1
L1 L2
Power supply 208/230V AC, 1phase 3wires, 60Hz
<Connection details>
N
Ground
∗∗
N
Ground
5/8 in.
Lead wire
Grounding terminal
Grounding terminal
Grounding terminal
Grounding terminal
CAUTION
Be careful not to make mis-wiring.
Firmly tighten the terminal screws to prevent them from loosening.
After tightening, pull the wires lightly to confirm that they do not move.
If the connecting wire is incorrectly connected to the terminal block, the unit does
not operate normally. If a ground is incorrect, it may cause an electric shock.
4-4 AUTO RESTART FUNCTION
When the units of these models are shipped from the factory, auto restart function is
set to ON. If you want to know how to release this function, consult the service center. When the indoor unit is controlled with the remote controller, the operation mode, the
set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. The auto restart function sets to work the moment the power has restored after power failure, then, the unit will restart automatically. If the unit is operated in “I FEEL CONTROL” mode before power failure, the operation is not memorized. In “I FEEL CONTROL” mode, the operation is decided by the initial room temperature at (re)start.
Operation
1 If the power of the indoor unit (115V AC) has been cut, the operation settings
remain.
Remark:
When indoor and outdoor unit are powered in separate circuit even if the power of the outdoor unit (208/230V AC) is cut auto restart function doesn’t work. 2 When three minutes have passed after power was restored, the unit will restart
automatically according to the memory.
Notes:
The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
If the main power is turned off or a power failure occurs while AUTO START/STOP timer is active, the timer setting is cancelled. As these models are equipped with the auto restart function, the air conditioner should start operating at the same time that a power has restored.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliances not to turn on at the same time.
4-5 PIPE FORMING
Place the drain hose below the refrigerant piping.
Make sure that the drain hose is not heaved or snaked.
Do not pull the hose to apply the tape.
When the drain hose passes the room, be sure to wrap insulation material (obtain-
able at a store) around it. Wrap the felt tape 7 around the pipe and the drain hose, then put the pipe in the
back space of the indoor unit.
Liquid pipe
Drain hose
FOR REAR, RIGHT OR DOWNWARD PIPING
Pipe arrangement
Put the refrigerant piping and the drain hose together, then apply piping tape G to them.
Be careful drain hose is not heaved.
Cut off in case of right piping. Cut off in case of downward piping.
Insert the piping and the drain hose into the wall hole sleeve C, and hook the upper
part of the indoor unit on the installation plate 1. Check if the indoor unit is hooked securely on the installation plate 1 by moving the
unit to left and right. Thrust the lower part of the indoor unit into the installation plate 1.
Gas pipe
Felt tape 7
Firmly apply piping tape G from the end.
Page 6
3
Putting nut on
• Remove flare nuts attached to indoor and outdoor units, then put them on pipe having completed burr removal. (not possible to put them on after flaring work)
4
Flaring work
• Perform flaring work using flaring tool as shown below.
Flaring tool
Die
Copper pipe
Outside diameter A
mm inch inch
6.35 1/4 3/32
12.7 1/2 5/32
15.88 5/8 5/32
• Firmly hold copper pipe in a die in the dimension shown in the table above.
5
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the flared section and perform flaring work again.
Smooth all around
Flare nut
Copper pipe
A
Yo r k
Die
Flare nut
Inside is shining without any scratches.
Copper pipe
Connect the gauge manifold valve and the vacuum pump to the service port of the stop valve on the gas pipe side of the outdoor unit.
Run the vacuum pump. (Vacuumize for more than 15 minutes.)
Check the vacuum with the gauge manifold valve, then close the gauge manifold valve and stop the vacuum pump.
Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve remains in the same position. Confirm that the pressure gauge shows –0.101 MPa [Gauge] (–30 in. Hg).
Stop valve
Stop valve
Close
Remove the gauge manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on both sides of gas pipe and liquid pipe. Operating without fully opening lowers the performance and this causes trouble.
Pipe length up to 25 ft. No gas charge is needed.
Hexagonal wrench
Open
Gauge manifold valve
Charge hose
Pipe length exceeding 25 ft. Charge the prescribed amount of gas. (refer to 3)
Liquid pipe
Stop valve
Service port
Vacuum pump
Hexagonal wrench
Gas pipe
Caps
Even length all around
6-2 PIPE CONNECTION
1 Indoor unit connection Connect both liquid pipe and gas pipe to indoor unit.
Apply a thin coat of refrigeration oil J on the seat surface of pipe.
For connection, align the center of both pipe and union, then tighten the first 3 to 4
turns in flare nut by hand. For tightening the union part of the indoor unit side, use the table below as a standard
and tighten the flare nut using two wrenches. Excessive tightening damages the flare section.
Pipe diameter Tightening torque
mm inch ft. · Ib
6.35 1/4 10 to 13
12.7 1/2 36 to 42
15.88 5/8 54 to 58
2 Outdoor unit connection Connect pipes to the pipe joint part of the stop valve in the same method as the indoor unit.
For tightening, use the same tightening torque applied for indoor unit and tighten the
flare nut with torque wrench or spanner.
INSULATION AND TAPING
1 Cover piping joints with pipe cover. 2 For outdoor unit side, surely insulate every piping including valves. 3 Using piping tape G, apply taping starting from the entry of outdoor unit.
Fix the end of piping tape G with adhesive tape.
When piping has to be arranged through above ceiling, closet or area where the
temperature and humidity are high, wind additional commercially sold insulation for prevention of condensation.
6-3 PURGING PROCEDURES·LEAK TEST
PURGING PROCEDURES
Tighten the cap to the service port to obtain the initial status.
Retighten the cap of the stop valve.
Leak test
Tightening torque
ft. · Ib
Cap for service port 10 to 13
Cap for stop valve 15 to 22
6-4 TEST RUN
MS type
Before performing the test run, recheck any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation. The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test run (continuous operation) for 30 minutes. A thermostat does not work during this time. After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 75 °F in COOL MODE. Perform test run in the following procedure.
PROCEDURE
Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts. 2 Press it once more, and the operation stops.
(The operation mode alternates between 1 and 2 every time the EMERGENCY OPERATION switch is pressed.)
Mode
Operation Indicator lamp
1
COOL
STOP
2
(Light) (Off)
(Off) (Off)
EMERGENCY OPERATION switch
Connect the refrigerant pipes (both liquid pipe and gas pipe) between the indoor and the outdoor unit.
Remove the service port cap of the stop valve on the gas pipe side of the outdoor unit. (The stop valve will not work in it initial state fresh out of the factory (totally closed with cap on).)
Page 7
FOR LEFT OR LEFT-REAR PIPING
Pipe arrangement
Put the refrigerant piping and the drain hose together, then apply felt tape 7 to them.
Be careful drain hose is not heaved.
Felt tape 7
Firmly apply felt tape 7 from the end. (Felt tape 7 overlap width should be 1/3 the tape width.)
REATTACHING DRAIN HOSE
Be sure to reattach the drain hose and the drain cap in case of left or left-rear piping. Otherwise, it could cause drops of water to drip down from the drain hose.
Cut off in case of left piping.
Use a bandage stopper at the end of felt tape 7.
INDOOR UNIT INSTALLATION
Insert the drain hose into the wall hole sleeve C, and hook the upper part of
indoor unit on the installation plate 1. Then, move the unit to the very edge of the left side for putting the piping easily in the back space of the indoor unit.
Installation plate 1
Bead
Set the polystyrene block along the “L” formed bead of the installation plate to hold the unit obliquery.
Connect the refrigerant piping with the extension pipe B.
Thrust the lower part of the indoor unit into the installation plate 1.
The polystyrene block is provided in the packing material.
4-6 DRAIN PIPING
The drain hose should point downward for easy drain flow. (Fig. 1)
Do not make drain piping as shown in Fig. 2 to 5.
Accumulated Downward slope
Do not raise.
drain water
Air
Drain hose
1
Pull out the drain cap at the rear right of the indoor unit.
Drain cap
Hold the convex section at the end and pull the drain cap.
Drain cap
2
Pull out the drain hose at the rear left of the indoor unit.
Hold the claw marked by the arrow and pull out the drain hose forward.
Drain hose
3
Put the drain cap into the section to which the drain hose is to be attached at the rear of the indoor unit.
Insert the screwdriver, etc. (not sharp-edged tool) into the hole at the end of the cap and insert the cap fully into the drain pan.
Water leakage
(Fig. 1) (Fig. 2) (Fig. 3)
Tip of drain hose dipped in water.
Water leakage
(Fig. 4) (Fig. 5)
If the drain hose provided with the indoor unit is too short, connect it with drain
hose I that should be provided at your site. If the extension drain hose has to pass through a room, be sure to wrap it with
commercially sold insulation.
Ditch
Less than 2 in. gap
Water leakage
Waving
Drain hose
Soft hose I.D. 19/32 in. or hard vinyl chloride
Drain cap
4
Insert the drain hose into the section to which the drain hose is to be attached at the rear right of the indoor unit.
Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to the projection of its inserting part at the drain pan.
Drain hose
Page 8
MSH type
Before performing the test run, recheck any wrong wiring.
Wrong wiring prevents normal operation or results in blown fuse disabling operation. The test run can be started by pressing EMERGENCY OPERATION switch. When
the EMERGENCY OPERATION switch is once pressed, the unit will start the test run (continuous operation) for 30 minutes. A thermostat does not work during this time. After 30 minutes the unit will start the EMERGENCY OPERATION at a fixed temperature setting of 75 °F in COOL MODE or HEAT MODE. Perform test run in the following procedure.
PROCEDURE
Press the EMERGENCY OPERATION switch.
1 Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.
If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect the indoor/outdoor connecting wire A for mis-wiring.
2 Press it once more, and the EMERGENCY HEAT MODE starts. 3 Press it once more, and the operation stops.
(The operation mode changes in order of 1 ~ 3 every time the EMERGENCY OPERATION switch is pressed.)
Mode
Operation Indicator lamp
1
COOL
(Light) (Off)
FRONT PANEL REINSTALLATION
1 Before installing the panel, set the horizontal vane to the position as shown in the
figure below.
2 Attach the bottom of the panel under the horizontal vane. 3 Set the top of the panel. 4 Push as the arrow mark on the panel to fix it to the air conditioner.
1 Horizontal vane
Slightly downward
3
4 Push
2
HEAT
2
STOP
3
In starting the heating operation, indoor unit fan may not operate to prevent
blowing cool air. Please wait for a few minutes until the temperature of heat exchanger rises and warm air blows out.
(Off) (Light)
(Off) (Off)
EMERGENCY OPERATION switch
MS type and MSH type
Checking the remote (infrared) signal reception
Press the ON/OFF button on the remote controller and check that an electronic sound is heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.
Checking the auto restart function
After operating the unit with the remote controller, turn off the main power. Then turn it on again and check if the unit operates in the same mode as the mode right before the main power shutoff.
If the indoor unit is operated with the remote controller, both the test run and the emergency operation are released by commands from the remote controller.
Once the compressor stops, the restart preventive device operates so the
compressor will not operate for three minutes to protect the air conditioner.
6-5 EXPLANATION TO THE CUSTOMER
Using the OPERATING INSTRUCTIONS, explain the following to the customer,
how to control temperature, how to remove the air filters, how to remove or put the remote controller in the remote controller mounting hardware, how to clean, precautions for operation, etc. Recommend the customer to read the OPERATING INSTRUCTIONS carefully.
7. FOR MOVEMENT AND MAINTENANCE
7-1 REMOVING AND REINSTALLING THE FRONT PANEL
FRONT PANEL REMOVAL
Horizontal vane
7-2 REMOVING THE INDOOR UNIT
Remove the bottom of the indoor unit from the installation plate.
1 Remove the front panel. (See FRONT PANEL REMOVAL shown above.) 2 Insert flat screwdrivers into the square holes at the left and right bottom of the
indoor unit and push them up; the bottom of the indoor unit goes down and the hooks are released.
Push
Go down
Square hole
7-3 GAS CHARGE
1 Connect gas cylinder to the service port of stop valve (3-way). 2 Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder. 3 Replenish specified amount of the refrigerant, while operating the air conditioner
for cooling.
CAUTION
Never charge liquid refrigerant, such as by inverting the gas cylinder while charging, otherwise troubles may be generated.
To maintain the high pressure of the gas cylinder, warm the gas cylinder with warm water (under 106 °F) during cold season. But never use naked flame or steam.
Refrigerant gas cylinder operating valve
Refrigerant gas cylinder
Indoor
unit
Union
Liquid pipe
Gas pipe
Charge hose
Stop valve
Outdoor
unit
Service port
4 Release the hooks.
1 Remove the screw caps. 2 Remove three screws.
3 Pull the bottom.
Hold this concave section and pull the bottom forward to remove the front panel.
(R-22 gas) Gas charge
HEAD OFFICE: MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
SCALE
Loading...