Mitsubishi MS-07NV - E2 (WH), MS-12NV - E1 (WH), MS-09NV - E2 (WH), MS-12NV - E2 (WH), MS-18NV - E2 (WH) Service Manual

...
This Servise Manual OB206 deals with MS-07/09/12/18/24NV-E1, MU-07/09/12/18/24NV-E1, MS-18NV-E2, and MU-18NV-E2 in OB175 THIRD EDITION issued in June in 1997. Therfore, please refer to OB206, not to OB175 THIRD EDITION, for the above models.
SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
Wireless type Models
No. OB206
MS-07NV ­MS-09NV ­MS-12NV ­MS-18NV ­MS-24NV ­MS-07NV ­MS-09NV ­MS-12NV ­MS-18NV ­MS-24NV ­MS-18NV -
(WH) (WH) (WH) (WH) (WH) (WH) (WH) (WH) (WH) (WH) (WH)
· MU-07NV -
· MU-09NV -
· MU-12NV -
· MU-18NV -
· MU-24NV -
· MU-07NV -
· MU-09NV -
· MU-12NV -
· MU-18NV -
· MU-24NV -
· MU-18NV -
CONTENTS
E1E1
E1E1
E1E1
E1E1
E1E1
E2E2
E2E2
E2E2
E2E2
E2E2
E3E3
MS-18NV ­MS-24NV ­MS-18NV ­MS-24NV ­MS-18NV -
E1 E1 E2 E2 E3
1. TECHNICAL CHANGES····································2
2. PART NAMES AND FUNCTIONS······················3
3. SPECIFICATION·················································6
4. OUTLINES AND DIMENSIONS·························9
5. WIRING DIAGRAM ··········································12
6. REFRIGERANT SYSTEM DIAGRAM··············20
7. PERFORMANCE CURVES······························24
8. MICROPROCESSOR CONTROL ····················27
10. TROUBLESHOOTING······································37
11. DISASSEMBLY INSTRUCTIONS·····················45
12. PARTS LIST······················································53
13. OPTIONAL PARTS···········································61
1
TECHNICAL CHANGES
MS-07NV - MS-07NV -
1. Indoor electronic control P.C. board has changed. However, it is compatible between and models.
2. Auto restart function is added.
MS-09NV - MS-09NV -
1. Indoor electronic control P.C. board has changed. However, it is compatible between and models.
2. Auto restart function is added.
3. Refrigerant filling capacity (R-22) has changed. (900g ➔850g)
MS-12NV - MS-12NV -
1. Indoor electronic control P.C. board has changed. However, it is compatible between and models. Auto restart function is added.
MS-18NV - MS-18NV -
1. Indoor electronic control P.C. board has changed. However, it is compatible between and models.
2. Auto restart function is added.
MS-24NV - MS-24NV -
1. Indoor electronic control P.C. board has changed. However, it is compatible between and models.
2. Auto restart function is added.
E2E1
E2E1
E2E1
E2E1
E2E1
E2E1
E3E2
E3E2
E2E1
E2E1
2
2
PART NAMES AND FUNCTIONS
INDOOR UNIT
MS-07NV - MS-09NV - MS-12NV ­MS-07NV - MS-09NV - MS-12NV -
E1E1E1
E2E2E2
MS-18NV ­MS-24NV ­MS-18NV ­MS-24NV ­MS-18NV -
E1
E1
E2
E2
E3
(When the front panel is open)
MS-07NV - MS-09NV - MS-12NV ­MS-07NV - MS-09NV - MS-12NV -
MS-18NV - MS-24NV -
E1E1
E1E1E1 E2E2E2
MS-18NV - MS-24NV - MS-18NV -
OUTDOOR UNIT
MU-07NV- MU-09NV ­MU-07NV- MU-09NV -
E1E1
E2E2
MS-07NV - MS-09NV - MS-12NV ­MS-07NV - MS-09NV - MS-12NV -
MS-18NV - MS-24NV ­MS-18NV - MS-24NV - MS-18NV -
E3E2E2
E1E1
MU-12NV - MU-18NV ­MU-24NV - MU-12NV ­MU-18NV - MU-24NV ­MU-18NV -
E3
E1E1E1 E2E2E2
E3E2E2
E1E1
E2E1
E2E2
3
MS-07NV - MS-09NV - MS-12NV ­MS-18NV - MS-24NV - MS-18NV -
REMOTE CONTROLLER
E1E1E1
E2E1E1
4
MS-07NV - (Product number 7000001T~) MS-09NV - (Product number 7000001T~) MS-12NV - (Product number 7000001T~) MS-24NV - (Product number 7000001T~) MS-07NV - MS-09NV ­MS-12NV - MS-18NV - (Product number 7000001T~) MS-24NV - MS-18NV -
E1E1
E1E1
E2E2
E2E2
E3E2
5
Capacity
Electrical data
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
Model
Function
Power supply
Coefficient of performance(C.O.P)
Capacity Dehumidification Air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Model Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit Outdoor unit Air direction Sound level (Hi) Fan speed (Hi) Fan speed regulator Refrigerant filling capacity(R-22)
Thermistor
Width Height Depth Width Height Depth
Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit
RT11(at25:) RT12(at25:)
kW
r/h
K /h
A A W
A(kW)
% A A A
W
"
"
"
mm mm mm mm mm mm
kg kg
dB
dB rpm rpm
kg
k"
k"
MS-07NV -
E1
E2
Cooling
2.2
0.8
3.15-3.05 680-710
98-97
2.69-2.59
3.24-3.10
RH-135VGHT
650
C-R 4.17 C-S 5.75
0.65
MS-09NV - E1
Cooling
2.5
1.1
3.60-3.45 780-810
98-98
3.15-2.99
3.21-3.09
RH-145VGHT
700
C-R 4.04 C-S 5.96
0.9
815 275 183 780 540 255
8
32
5
37 44-45 1,100
740-770
4 1
10
10
Single phase,220-240V,50Hz
INDOOR 492 OUTDOOR 1620
10
25
INDOOR 0.17 OUTDOOR 0.29
RC4V19-AA
WHT-BLK292.4 BLK-RED324.6
RA6V23-AB
WHT-BLK268.4 BLK-RED390.8
3
NOTE:Test conditions
6
SPECIFICATION
Cooling : Indoor DB27: / WB19:
Outdoor DB35: / WB24:
Model
Function
Power supply
Capacity
Capacity
Dehumidification Air flow Power outlet Running current Power input Auxiliary heater
Electrical data
Power factor Starting current Compressor motor current Fan motor current
Coefficient of performance(C.O.P)
Model
Compressor
Output Winding resistance(at20:)
Indoor
fan motor
Outdoor
fan motor
Model Winding resistance(at20:) Model Winding resistance(at20:)
Indoor unit
Dimensions
Outdoor unit
Weight
Indoor unit Outdoor unit Air direction Sound level (Hi) Fan speed
Special remarks
(Hi) Fan speed regulator Refrigerant filling capacity(R-22)
Thermistor
NOTE:Test conditions
Cooling : Indoor DB27: / WB19:
Outdoor DB35: / WB24:
Width Height Depth Width Height Depth
Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit
RT11(at25:) RT12(at25:)
MS-09NV - E2
Cooling
Single phase,220-240V,50Hz kW r/h
INDOOR 492 OUTDOOR 1620
K /h
2.5
1.1
A A
W
3.60-3.45 780-810
A(kW)
%
A A
INDOOR 0.17 OUTDOOR 0.29
A
98-98
25
3.15-2.99
3.21-3.09
RH-145VGHT
W
"
"
WHT-BLK268.4 BLK-RED390.8
"
700
C-R 4.04 C-S 5.96
WHT-BLK292.4 BLK-RED324.6
RA6V23-AB
mm mm mm mm mm mm
780 540
255 kg kg
dB
dB rpm rpm
kg
32
37 44-45 1,100
740-770
0.65 k" k"
MS-12NV -
Cooling
3.5
1.6
INDOOR 558 OUTDOOR 2190-2304
10
6.20-6.35
1310-1390
96-91
35
5.66-5.81
INDOOR 0.17 OUTDOOR 0.37
2.67-2.52
RH-231VHAT
1,100
C-R 2.11 C-S 3.97
RC4V19-AA
RA6V40-EC or EE
WHT-BLK130.4 BLK-RED134.6 815 275 183
850 605 290
8
38
5
42 50
1,230
780-820 4 1
0.8 10 10
E1
E2
7
Capacity
Electrical data
Compressor
Indoor
fan motor
Outdoor
fan motor
Dimensions
Weight
Special remarks
Model
Function
Power supply
Coefficient of performance(C.O.P)
Capacity Dehumidification Air flow Power outlet Running current Power input Auxiliary heater Power factor Starting current Compressor motor current Fan motor current
Model Output Winding resistance(at20:) Model Winding resistance(at20:) Model Winding resistance(at20:)
Indoor unit
Outdoor unit
Indoor unit Outdoor unit Air direction Sound level (Hi) Fan speed (Hi) Fan speed regulator Refrigerant filling capacity(R-22)
Thermistor
Width Height Depth Width Height Depth
Indoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Outdoor unit
RT11(at25:) RT12(at25:)
kW
R/h
K /h
A A
W
A(kW)
%
A A A
W
"
"
"
mm mm mm mm mm mm
kg kg
dB
dB rpm rpm
kg k" k"
MS-18NV -
E1 E2 E3
MS-24NV -
E1 E2
Single phase,220-240V,50Hz
WHT-BLK183.8 BLK-RED250.5
1,015
320 190 850 605 290
14
5
4
10 10
Cooling
6.4
3.4
INDOOR 816 OUTDOOR 2286
25
12.9-12.6
2,780-2,900
98-96
59
12.06-11.76
INDOOR 0.29 OUTDOOR 0.55
2.30-2.21
NH-47VMDT
2,200
C-R0.96 C-S 2.07
RA4V27-EC
RA6V60-AA or AB
WHT-BLK81.1 BLK-RED102.2 BLK-YLW 92.2
61
45 53
1,260
860-886
2
2.15
Cooling
5.1
2.5
INDOOR 756 OUTDOOR 2190
15
9.1
1,910-2,010
95-92 51-55
8.46
INDOOR 0.25 OUTDOOR 0.39
2.67-2.54
NH-33VMDT
1,500
C-R1.2 C-S 2.7
RA4V27-EA
RA6V50-OD or OF
WHT-BLK116.4 BLK-RED111
55
42 52
1,180
810-845
1
1.65
NOTE:Test conditions
Cooling : Indoor DB27: / WB19:
Outdoor DB35: / WB24:
8
4
OUTLINES AND DIMENSIONS
MS-07NV - MS-09NV ­MS-07NV - MS-09NV -
INDOOR UNIT
E1E1
E2E2
Unit : mm
MU-07NV - MU-09NV ­MU-07NV - MU-09NV -
OUTDOOR UNIT
E1E1
E2E2
9
MS-12NV - MS-12NV -
INDOOR UNIT
E2E1
Unit : mm
{
MU-12NV - MU-12NV -
OUTDOOR UNIT
E2E1
If the right/left sides or back side is vacant,the front has only to be 50cm unobstructed.
If the front or right/left sides
are vacant, the top has only
to be 10cm unobstructed.
10
12.7
MS-18NV - MS-24NV -
E1E1
MS-18NV - MS-24NV - MS-18NV -
INDOOR UNIT
995995
6060
E3E2E2
4040
4holes 14holes 111✕2020
150150 648648 217217
Unit : mm
Indoor unitIndoor unit
2020
10151015
320320
1901907757755050
Power supply cordPower supply cord Lead to right 2mLead to right 2m Lead to left 1mLead to left 1m
5656
17.517.5
160160
Wireless remote controllerWireless remote controller
MU-18NV - MU-24NV -
E1E1
MU-18NV - MU-24NV - MU-18NV -
OUTDOOR UNIT
Installation plateInstallation plate
Air inAir in
Air outAir out
E3E2E2
450450
450450
352352438438
55190190
Installation plateInstallation plate
Liquid line Liquid line [[8-0.5m8-0.5m Gas line Gas line [[12-0.43m12-0.43m
{
Insulation Insulation [[50 O.D50 O.D
[ [28 I.D28 I.D
Drain hose Drain hose [[1616 Insulation Insulation [[2828
254254
33 297297
WWall hole all hole [[7575
If the front or right/left sides
are vacant, the top has only
to be 10cm unobstructed.
If the right/left sides or back side is vacant,the front has only to be 50cm unobstructed.
11
5
WIRING DIAGRAM
MS-07NV ­MS-09NV -
INDOOR UNIT
SYMBOL
C11 F12 F11
MF
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
MU-07NV ­MU-09NV -
E1
E1
MODELS WIRING DIAGRAM
❈ ❈
NAME INDOOR FAN CAPACITOR FUSE(93:) FUSE(3.15A) INDOOR FAN MOTOR
E1
E1
MODELS WIRING DIAGRAM
SYMBOL
NR11 RT11 RT12
HIC1
NAME NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR DC/DC CONVERTER
SYMBOL
TB
MV
SR11
52C
TERMINAL BLOCK VANE MOTOR SOLID STATE RELAY CONTACTOR
OUTDOOR UNIT
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
NAME
SYMBOL
MF MC
OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT)
NAME NAME
SYMBOL
TB
F
TERMINAL BLOCK FUSE (2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
12
MS-12NV -
E1
MODEL WIRING DIAGRAM
NAME
SYMBOL
NR11 RT11 RT12
HIC1
VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR DC/DC CONVERTER
NAME NAME
INDOOR UNIT
SYMBOL
C11 F12 F11
MF
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(93:) FUSE(3.15A) INDOOR FAN MOTOR
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
SYMBOL
TB MV
SR11
52C
TERMINAL BLOCK VANE MOTOR SOLID STATE RELAY CONTACTOR
MU-12NV -
E1
MODEL WIRING DIAGRAM
OUTDOOR UNIT
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate. : Terminal block, : Connector
NAME
SYMBOL
MF MC
OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT)
NAME NAME
SYMBOL
TB
F
TERMINAL BLOCK FUSE(2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
13
MS-18NV -
E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
POWER SUPPLY CORD
1~
220-240V 50Hz
MODEL WIRING DIAGRAM
TB
L
BRN
BRN
2
N
BLU
GRN/YLW
WHT
BLK
F12
BRN
DSAR
RECEIVER P.C.BOARD
BLK
BLK
101CN102
GRN/YLW
REMOTE CONTROLLER
2 1
LD1
3 3
BLK
CN
DISPLAY
P.C.BOARD
4
CN201
3 1
CN 151
ELECTRONIC CONTROL P.C BOARD
5
MV
52C
3
F11
IC141
NR11
CN
112
3
CN
121
CN211
C11
4 2 1
CN 111
BRN YLW GRY WHT RED BLK
RT12
MF
RT11
SYMBOL
C11 F12 F11
MF MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(93:) FUSE(3.15A) INDOOR FAN MOTOR VANE MOTOR
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
MU-18NV -
OUTDOOR UNIT
NAME
E1
TO INDOOR UNIT CONNECTING
MODEL WIRING DIAGRAM
TB
2
N
SYMBOL
NR11 RT11 RT12
IC141
GRN / YLW
52C
NAME NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR HYBRID IC CONTACTOR
WHT
BLK
C1
C2
RED
BLK
BLK
WHT
ORN
RED
SYMBOL
MC
S
4 3 2
1
TB
DSAR
C
BLK
WHT
ORN
RED
TERMINAL BLOCK SURGE ABSORBER
R
MF
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
NAME
14
SYMBOL
MF
MC
NAME NAME OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT)
SYMBOL
TB
F
TERMINAL BLOCK FUSE (2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
MS-24NV -
SYMBOL
TB
DSAR
HIC1
SYMBOL
NR11
RT11 RT12
IC141
52C
SYMBOL
C11
F12 F11
MF MV
NAME
NAME NAME INDOOR FAN CAPACITOR FUSE(93¡C) FUSE(3.15A) INDOOR FAN MOTOR VANE MOTOR
VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR HYBRID IC CONTACTOR
TERMINAL BLOCK SURGE ABSORBER DC / DC CONVERTER
6
5
4
3
2
1
78
RED
X1
BLU
F
1
TB2
RED
BLU
BLU
GRY
WHT
TO INDOOR UNIT CONNECTING
REDRED
a
b
TB
2
WHT
52C
1
2
R
C
S
BLK
RED
C1
MC
YLW YLW
BLK
WHT
RED ORN
WHT BLK
ORN
RED
C2
MF
RED
CR
52C
N
RED
GRN/YLW
3
6
26F1
X1
BLU
5
1
3
220-240V
220-240V
SYMBOL
C1 C2 X1
SYMBOL
MF MC
52C
SYMBOL
TB CR
F
NAME
NAME NAME COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR FAN MOTOR RELAY
OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT) COMPRESSOR CONTACTOR
TERMINAL BLOCK SURGE ABSORBER FUSE(2A)
E1
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
POWER SUPPLY CORD ~/N 220-240V 50Hz
CIRCUIT BREAKER
MODEL WIRING DIAGRAM
220-240V~
220-240V~
TB
3
2
BRN
N
BLU
GRN/YLW
RED
WHT
BLU
F12
WHT
1
GRN/YLW
DSAR
RECEIVER P.C.BOARD
REMOTE CONTROLLER
BLU BLU
2 1
WHT
101CN102
3 3
LD1
CN
BLU
CN
151
MV
DISPLAY P.C.BOARD
CN201
5
HIC1
4
52C
3
3 1
ELECTRONIC CONTROL P.C BOARD
TRANS
F11
IC141
NR11
CN
112
CN
121
CN211
C11
4 2 1
CN
111
RT12
3
BRN YLW GRY
MF
WHT RED BLK
RT11
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
MU-24NV -
E1
MODEL WIRING DIAGRAM
OUTDOOR UNIT
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate. : Terminal block, : Connector
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
15
MS-07NV - MS-09NV - MS-12NV -
INDOOR UNIT
TO OUTDOOR UNIT CONNECTING
220-240V~
POWER SUPPLY CORD ~/N 220-240V 50Hz
MODELS WIRING DIAGRAM
TB
L
BRN
BRN
F12
BLU
1
BLU
122
1 2
CN
LD101
5
2
WHT
N
BLU
BLU
GRN/YLW
GUARD
PLATE
GRN/YLW
POWER MONITOR, RECEIVER P.C.BOARD
BLU
CN
151
MV
5
E2E2E2
HIC1
CN201
1
ELECTRONIC CONTROL P.C BOARD
3
52C
4
TRANS
F11
NR11
SR11
C11
CN 112
CN 111
CN 121
3 2 1
CN211
RT12
RT11
BLK GRY YLW BRN WHT RED
1 2 3
MF
4 5 6
3
CIRCUIT BREAKER
SYMBOL
C11
F12 F11
MF
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(93:) FUSE(3.15A) INDOOR FAN MOTOR
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
NAME
MU-07NV - MU-09NV -
OUTDOOR UNIT
TO INDOOR UNIT CONNECTING
MODELS WIRING DIAGRAM
220-240V~
REMOTE CONTROLLER
E2E2
TB
2
N
GRN/YLW
SYMBOL
NR11 RT11 RT12
HIC1
❈❈❈
BLU
NAME NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR DC/DC CONVERTER
WHT
F
C2
WHT
BLU
RED
1 2 3
BLU
WHT BLK
RED
SYMBOL
TB MV
SR11
52C
WHT
MF
TERMINAL BLOCK VANE MOTOR SOLID STATE RELAY CONTACTOR
C
C1
RED
BLK
MC
S
R
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
NAME
16
SYMBOL
MF
MC
NAME NAME OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT)
SYMBOL
TB
F
TERMINAL BLOCK FUSE (2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
MS-18NV -
E2
MODEL WIRING DIAGRAM
INDOOR UNIT
~
SYMBOL
C11 F12 F11
MF MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(93¡C) FUSE(3.15A) INDOOR FAN MOTOR VANE MOTOR
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
NAME
SYMBOL
NR11 RT11 RT12
IC141
52C
NAME NAME VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR HYBRID IC CONTACTOR
SYMBOL
TB
DSAR
HIC1
TERMINAL BLOCK SURGE ABSORBER DC / DC CONVERTER
MU-18NV -
E2
MODEL WIRING DIAGRAM
OUTDOOR UNIT
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
NAME
SYMBOL
MF MC
OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT)
NAME NAME
SYMBOL
TB
F
TERMINAL BLOCK FUSE(2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
17
MS-24NV -
E2
INDOOR UNIT
220-240V~ `
MODEL WIRING DIAGRAM
TB
3
RED
HIC1
IC141
112
CN
RT12
220-240V~
TO OUTDOOR UNIT CONNECTING
POWER SUPPLY CORD ~/N 220-240V 50Hz
CIRCUIT BREAKER
2
GRN/YLW
SYMBOL
C11 F12 F11
MF MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
MU-24NV -
INDOOR FAN CAPACITOR FUSE(93¡C) FUSE(3.15A) INDOOR FAN MOTOR VANE MOTOR
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
E2
OUTDOOR UNIT
TO INDOOR
WHT
BLU
WHT
F12
BLU
BLU
1
GRN/YLW
DSAR
RECEIVER
P.C.BOARD
REMOTE CONTROLLER
2 1
WHT
LD1
CN
CN
102
101
3 3
SYMBOL
N
BLU
BRN
NAME
NR11 RT11 RT12
IC141
52C
MODEL WIRING DIAGRAM
TB
220-240 ~
UNIT
CONNECTING
220-240 ~
2
N
3
GRN/YLW
WHT
RED
CN201
BLU
DISPLAY P.C.BOARD
3 1
CN
ELECTRONIC CONTROL P.C BOARD
151
5
MV
VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR HYBRID IC CONTACTOR
52C
2
BLU
BLU
BLU
RED
TB2
1
F
4
52C
3
NAME NAME
1
RED
78
X1
5
6
A2/b
52C
A1/a
RED
RED
CR
F11
X1
TRANS
C2
3
1
GRY
SYMBOL
DSAR
WHT
26F1
RED
NR11
CN211
C11
TB
TERMINAL BLOCK SURGE ABSORBER
HIC1
RED ORN WHT BLK YLW YLW
DC / DC CONVERTER
RED
1
ORN
2
WHT
3
BLK
4 5 6
BLU
CN
121
CN
111
3
BRN YLW GRY
MF
MF
S
RED
WHT
RED
BLK
RT11
C
MC
R
BLK
C1
4 2 1
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
FAN MOTOR RELAY
X1
TB2
NOTE:1. Use copper conductors only.(For field wiring)
TERMINAL BLOCK
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull
the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate. : Terminal block, : Connector
NAME
18
SYMBOL
MF
MC
52C
26F1
NAME NAME OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT) COMPRESSOR CONTACTOR THERMAL READ SWITCH
SYMBOL
TB
CR
F
TERMINAL BLOCK SURGE ABSORBER FUSE(2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
MS-18NV -
E3
INDOOR UNIT
O OUTDOOR
T UNIT CONNECTING
220-240V~
POWER SUPPLY CORD ~/N 220-240V 50Hz
CIRCUITBREAKER
MODEL WIRING DIAGRAM
TB
L
GRN/YLW
BRN
2
N
BLU
BRN
WHT
BLU
F12
BRN
DSAR
RECEIVER P.C.BOARD
BLU BLU
101
GRN/YLW
REMOTE CONTROLLER
2 1
LD1
CN
3 3
BLU
CN
102
DISPLAY P.C.BOARD
HIC1
4
CN201
3 1
CN
151
ELECTRONIC CONTROL P.C BOARD
5
MV
52C
3
TRANS
F11
IC141
NR11
CN
112
CN
121
CN211
4
C11
2 1
CN 111
RT12
3
BRN YLW GRY WHT
MF RED BLK
RT11
SYMBOL
C11 F12 F11
MF MV
NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.
INDOOR FAN CAPACITOR FUSE(93¡C) FUSE(3.15A) INDOOR FAN MOTOR VANE MOTOR
2. Use copper conductors only.(For field wiring)
3. Symbols below indicate. : Terminal block, : Connector
MU-12NV - MU-18NV -
OUTDOOR UNIT
TO INDOOR UNIT CONNECTING
NAME
E3E2
SYMBOL
NR11 RT11 RT12
IC141
52C
VARISTOR ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR HYBRID IC CONTACTOR
MODELS WIRING DIAGRAM
220-240V~
TB
2
N
GRN/YLW
NAME NAME
WHT
F
C2
BLU
RED ORN WHT BLU
WHT
1 2 3 4
RED ORN WHT BLK
SYMBOL
TB
DSAR
HIC1
C1
MF
TERMINAL BLOCK SURGE ABSORBER DC / DC CONVERTER
C
RED
MC
S
BLK
R
SYMBOL
COMPRESSOR CAPACITOR
C1
OUTDOOR FAN CAPACITOR
C2
NOTE:1. Use copper conductors only.(For field wiring)
2. “”show the terminals with a lock mechanism, so they cannot be removed when you pull the lead wire. Be sure to pull the wire by pushing the locking lever(projected part) of the terminal with a finger.
3. Symbols below indicate.
: Terminal block, : Connector
NAME
SYMBOL
MF
MC
NAME NAME OUTDOOR FAN MOTOR COMPRESSOR (INNER THERMOSTAT)
SYMBOL
TB
F
TERMINAL BLOCK FUSE(2A)
1.Slide the sleeve.
2.Pull the wire while pushing the locking lever.
19
6
REFRIGERANT SYSTEM DIAGRAM
MS-07NV - MS-09NV ­MS-07NV - MS-09NV -
INDOOR UNIT
Refrigerant pipe [9.52 (Option) (with heat insulator)
Unit:mm
E1E1
E2E2
MU-07NV - MU-09NV ­MU-07NV - MU-09NV -
E1E1
E2E2
OUTDOOR UNIT
Stop valve (with service port)
Indoor heat exchanger
Room temperature thermistor RT11
Indoor coil thermistor RT12
Refrigerant pipe [6.35
(Option) (with heat insulator)
MS-12NV - MS-12NV -
Refrigerant pipe [12.7 (Optional)
INDOOR UNIT
(with heat insulator)
Flared connection
E2E1
Accumulator
Capillary tube [1.6x1200
Outdoor heat exchanger
Compressor
Strainer
Refrigerant flow in cooling
MU-12NV - MU-12NV -
OUTDOOR UNIT
Unit:mm
E2E1
Indoor heat exchanger
Room temperature thermistor RT11
20
Indoor coil thermistor
RT12
Flared connection
Refrigerant pipe [6.35
(Option) (with heat insulator)
Stop valve (with service port)
Stop valve
Compressor
Capillary tube [1.8x800
Outdoor heat exchanger
Strainer
Refrigerant flow in cooling
MS-18NV - MS-18NV ­MS-18NV -
E3
E2E1
MU-18NV - MU-18NV ­MU-18NV -
E3
E2E1
Unit:mm
INDOOR UNIT
Indoor heat exchanger
Distributor
Room temperature thermistor RT11
Indoor coil thermistor
RT12
Refrigerant pipe [15.88 (Option) (with heat insulator)
Stop valve (with service port)
Flared connection
Stop valve
Refrigerant pipe [6.35
(Option)
(with heat insulator)
Accumulator
Capillary tube [2.0X700
Compressor
Refrigerant flow in cooling
OUTDOOR UNIT
Outdoor heat
Strainer
exchanger
MS-24NV - MS-24NV ­INDOOR UNIT
Indoor heat exchanger
Distributor
Room temperature thermistor RT11
Indoor coil thermistor
Refrigerant pipe [15.88 (Option) (with heat insulator)
RT12
Flared connection
Refrigerant pipe [9.52
(Option)
(with heat insulator)
E2E1
Stop valve (with service port)
Stop valve
MU-24NV - MU-24NV -
Accumulator
Capillary tube [1.6X350
Capillary tube [2.0X700
Unit:mm
E2E1
OUTDOOR UNIT
Outdoor heat exchanger
Compressor
Discharge Pressure Regulator
Strainer
Refrigerant flow in cooling
21
Model
Outdoor unit precharged
(up to 7m)
650 900
850 800
1650
2150
Refrigerant piping length (one way)
15m
120
7m
0
10m
45
MS-07NV - E1 MS-07NV - E2 MS-09NV - E1 MS-09NV -
E2
MS-12NV -
E1
MS-12NV -
E2
MS-18NV -
E1
MS-18NV - E2 MS-18NV - E3 MS-24NV - E1 MS-24NV - E2
Model
Refrigerant piping
Max. length : m
A
10
15
Piping size O.D : mm
Length of connecting pipe : m
Indoor unit
0.43
Gas
9.52
12.7
15.88
Liquid
6.35
9.52
Outdoor unit
0
MS-07NV - E1 MS-07NV - E2 MS-09NV - E1 MS-09NV -
E2
MS-12NV -
E1
MS-12NV -
E2
MS-18NV -
E1
MS-18NV - E2 MS-18NV - E3
MS-24NV -
E1
MS-24NV -
E2
MAX. REFRIGERANT PIPING LENGTH
MAX. HEIGHT DIFFERENCE
ADDITIONAL REFRIGERANT CHARGE(R-22 : g)
Calculation : Xg=15g/m(A-7)m
22
EVACUATION PROCEDURES(AIR PURGE)
Connect the refrigerant pipes (both the liquid and gas pipes) between the indoor and the outdoor units.
Remove the service port cap of the stop valve on the side of the outdoor unit gas pipe (The stop valve will not work in its initial state fresh out of the factory (totally closed with cap on)).
When vacuuming
Connect the gage manifold valve and the vacuum pump to the service port of the stop valve on the liquid pipe side of the outdoor unit.
Run the vacuum pump for more than 15 minutes and at this
time confirm that the pressure gage indicates 0.1 Mpa.
Check the vacuum with the gage manifold valve, then close the gage manifold valve, and stop the vacuum pump.
Leave it as is for one or two minutes. Make sure the pointer of the gage manifold valve remains in the same position.
Remove the gage manifold valve quickly from the service port of the stop valve.
After refrigerant pipes are connected and evacuated, fully open all stop valves on gas and liquid pipe sides Operating without fully opening lowers the performance and causes trouble.
Pipe length :
7m maximum No gas charge is needed.
Tighten the cap to the service port to obtain the initial status.
Retighten the cap.
Leak test
Pipe length
exceeding 7m Charge the prescribed amount of gas.
23
7
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions. Since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
PERFORMANCE CURVES
(1) GUARANTEED VOLTAGE
Rated voltage : ±10% (198 ~ 264V
),50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :°CWB (2) Indoor outlet air wet-bulb temperature :°CWB (3) Outdoor intake air dry-bulb temperature :°CDB (4) Total input :W
Indoor air wet-bulb temperature difference on the left side of the chart on next page shows the difference between the indoor intake air wet-bulb temperature and the indoor outlet air wet-bulb temperature for your reference at service.
How to measure the indoor air wet-bulb temperature difference
1. Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.
2. Attach at least 2 sets of dry-bulb thermometers to the outdoor air inlet. Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch to start the EMERGENCYoperation.
6. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
7. 10 minutes later, measure temperature again and check that the temperature does not change.
Cooling
}
24
INDOOR UNIT
OUTDOOR UNIT
8
7
6
5
4
3
E3
OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation
Both indoor and outdoor unit are under the same temperature/humidity condition.
Dry-bulb temperature
Relative humidity(%) 20 25 30 70
Air flow should be set at MAX.
(kgf/F•G)(MPa•G)
MU-07NV -
220/240V
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
MU-07NV -
50 60
E2E1
(kgf/F•G)(MPa•G)
8
7
6
MU-09NV -
E2E1
220/240V
5
4
Outdoor low pressure
3
Ambient temperature(˚C)Ambient humidity(%)
E2E1
MU-09NV -
E2E1
220V
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
240V
220V
240V
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
25
7
6
5
4
3
2
8
7
6
5
4
3
7
6
5
4
3
2
(kgf/F•G)(MPa•G)
MU-12NV -
E2E1
220/240V
(kgf/F•G)(MPa•G)
MU-18NV -
E3E2E1
220/240V
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
MU-12NV -
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
(kgf/F•G)(MPa•G)
MU-24NV -
E2E1
220V
240V
E2E1
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
MU-18NV -
E3E2E1
220/240V
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
Outdoor low pressure
Ambient temperature(˚C)Ambient humidity(%)
MU-24NV -
26
Outdoor unit current(A)
Ambient temperature(˚C)Ambient humidity(%)
220/240V
E2E1
220V
240V
8
.
MICROPROCESSOR CONTROL
Wireless remote controller
MS-07NV - MS-09NV - MS-12NV ­MS-18NV - MS-24NV - MS-07NV ­MS-09NV - MS-12NV - MS-18NV ­MS-24NV - MS-18NV -
Once the controls are set, the same operation mode can be repeated by simply turning the OPERATE/STOP button ON. Indoor unit receives the signal with a beep tone. When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.
1. “I FEEL CONTROL” ( ) OPERATION
(1) Press OPERATE/STOP button on the remote con-
troller. OPERATION INDICATOR LAMP of the indoor unit will turn on with a beep tone.
(2) Press OPERATION SELECT button to set “I FEEL
CONTROL”( ) .Then a beep tone is heard.
(3) The operation mode is determined by the initial
room temperature at start-up of the operation.
Initial room temperature
more than 25: 13: to 25:
E3E2
mode
COOL mode of
“I FEEL CONTROL“
DRY mode of
“I FEEL CONTROL”
E1E1E1
E2E1E1
E2E2E2
INDOOR UNIT DISPLAY SECTION
Once the mode is fixed, the mode will not change by room temperature afterwards.
Under the ON-TIMER ( ) operation, the mode is determined according to the room temperature as the operation starts.
When the system is stopped with the OPERATE/STOP button on the remote controller, and restarted within 2 hours in “I FEEL CONTROL” ( ) mode, the system operates in previous mode automatically regardless of the room temperature.
Example
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
When the system is restarted after 2 hours, the operation mode is determined by the initial room temperature at start-up of the operation.
Example
Previous operation
COOL mode of “I FEEL CONTROL” or COOL mode
Restart
COOL mode of “I FEEL CONTROL”
Restart
COOL or DRY mode of “I FEEL CONTROL” that determined by initial room temperature at start-up of the operation.
27
Model
COOL mode of
"I FEEL CONTROL"
DRY mode of
"I FEEL CONTROL"
Initial room temperature Initial set temperature
26: or more
26: or less
13: or 25:
24:
Initial room temperature minus 2: Initial room temperature minus 2:
1
(4) The initial set temperature is decided by the initial room temperature.
1 After the system restarts by the remote controller, the system operates with the previous set temperature regardless of
the initial set temperature. The set temperature is calculated by the previous set temperature.
(5) TEMPERATURES buttons
In “I FEEL CONTROL” ( ) mode, set temperature is decided by the microprocessor based on the room temperature.
In addition, set temperature is controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed, the indoor unit receives the signal and emits a beep tone.
Fuzzy control
When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode. In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.
TOO COOL… To raise the set temperature 1~2 degrees(°C)
TOO WARM … To lower the set temperature 1~2 degrees(°C)
28
— COOL mode of “I FEEL CONTROL” —
ON
Compressor and
OFF
ON
OFF
outdoor fan motor
Indoor fan motor
ON
Run continuously in cooling mode
NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL”
There are two types of controls in coil frost prevention.
Temperature control <MS-/0709/12> When the indoor coil thermistor RT12 reads 4°C or below for 5 minutes, the coil frost prevention mode
starts.
<MS-18/24> When the indoor coil thermistor RT12 reads -1°C or below, the coil frost prevention mode starts immediately.
However, the coil frost prevention only works after 5 minutes from the compressor starts. The compressor stops and the indoor fan operates at the set speed for 5 minutes. After that, if RT12still reads below 4°C (MS-07/09/12) or below -1°C (MS-18/24) this mode prolonged until the RT12 reads over 4°C (MS-07/09/12) or -1°C (MS-18/24).
Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes. a. Compressor has been continuously operating. b. Indoor fan speed is Lo or Me. c. Room temperature is below 26°C. When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning. Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds 26°C. However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.
Indoor fan operates at the set speed by FAN SPEED CONTROL button. Followings are the fan speed in AUTO.
Initial temperature difference Room temperature minus set temperature : 2 degrees or more············································Hi Room temperature minus set temperature : 1 degree or more and less than 2 degrees·····Me Room temperature minus set temperature : less than 1 degree···········································Lo
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the temperature and the microprocessor. By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease. The operation of the compressor and indoor fan is as follows.
1. When the room temperature is 23°C or over:
Compressor operates by temperature control and time control.
Set temperature is controlled to fall 2°C as initial set temperature.When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON. Indoor fan and outdoor fan operate in the same cycle as the compressor.
Fan speed
1 deg.
2 deg.
1.66 deg.
4 deg.
2. When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
29
Operation time chart
Example
Thermostat
1st ON
ON
OFF
ON
Indoor fan
ON
Outdoor fan compressor
NOTE Coil frost prevention during DRY mode of “I FEEL CONTROL”
The operation is same as coil frost prevention during COOL mode of “I FEEL CONTROL” excepting the indoor fan is OFF.
During coil frost prevention the outdoor fan speed becomes Lo and the indoor fan is OFF. (Because the coil frost prevention is priority.)
8 min.
ON
OFF
ON
OFF
3 min.
ON
OFF
ON
OFF
1 min.
2. COOL ( ) OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit
turns on with a beep tone. (2) Select COOL mode. (3) Set the TEMPERATURES button.
(TOO WARM or TOO COOL button)
The setting range is 16 ~ 31°C
Indoor fan continues to operate regardless
of thermostat’s OFF-ON
Coil frost prevention is as same as COOL
mode of “I FEEL CONTROL”
3. DRY ( ) OPERATION
(1) Press OPERATE/STOP button.
OPERATION INDICATOR of the indoor unit
turns on with a beep tone. (2) Select DRY mode. (3) The microprocessor reads the room temper-
ature and determines the set temperature.
Set temperature is as shown on the right
chart.
Thermostat (SET TEMP.)does not work.
The other operations are same as DRY
mode of “I FEEL CONTROL”. (4) DRY operation will not function when the
room temperature is 13°C or below. (5) When DRY operation functions, the fan
speed is lower than cool operation.
30
SLEEP
4.FAN( d )OPERATION
(1)Press POWER ON/OFF button. (2)Select FAN mode with the OPERATION SELECT button. (3)Select the desired fan speed.When AUTO,it becomes Lo.
Only indoor fan operates.Outdoor unit does not operate.
5. FAN MOTOR CONTROL
(1) Rotational frequency feedback control
The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the microprocessor to feedback
the rotational frequency. Comparing the current rotational frequency with the target rotational frequency (Hi,Me,Lo,SLEEP), the microprocessor controls SR11 (MS-07/09/12), IC141 (MS-18/24) and adjusts fan motor electric current to make the cur­rent rotational frequency close to the target rotational frequency. With this control, when the fan speed is switched, the rotational frequency changes smoothly.
(2) Fan motor lock-up protection
When the rotational frequency feedback signal has not output for 12 seconds, (or when the microprocessor cannot detect
the signal for 12 seconds) the fan motor is regarded locked-up. Then the electric current to the fan motor is shut off. 3 min­utes later, the electric current is applied to the fan motor again. During the fan motor lock-up, the OPERATION INDICATOR lamp flashes on and off to show the fan motor abnormality. (See page 38.)
6. AUTO VANE OPERATION
(1) Vane motor drive
MS(D)-N series is equipped with a stepping motor for the vane. The rotating direction, speed, and angle of the motor are
controlled by pulse signals (approx. 12V) transmitted from indoor microprocessor.
(2) The auto vane angle changes as follows by pressing the VANE CONTROL ( ) button.
31
(3) Positioning
The vane is once pressed to the vane stopper below to confirm the standard position and then set to the desired angle. The positioning is decided as follows. (a) When the OPERATE/STOP button is pressed. (POWER ON/OFF) (b) When the vane control is changed from AUTO to MANUAL. (c) When the SWING is finished. (d) When the test run starts. (e) When the power supply turns ON.
(4) VANE AUTO ( ) mode
In VANE AUTO mode, the microprocessor automatically determines the vane angle and operation to make the optimum room-temperature distribution.
In COOL and DRY operation
Vane angle is fixed to Angle 1.
In FAN operation
Vane angle is fixed to Angle 4.
(5) Dew prevention
During COOL or DRY operation at Vane Angle 4 or 5 when the compressor cumulative operation time exceeds 1 hour, the vane angle automatically changes to Angle 1 for dew prevention.
(6) SWING MODE ( )
By pressing the SWING button ( ) vane swings vertically. The remote controller displays “ ”. SWING mode is can­celled when the SWING button or VANE CONTROL button ( ) is pressed or the operation stops or changes to other
mode.
7. SLEEP MODE ( )
• When the SLEEP button ( ) is pressed, the indoor fan speed drops and the air flow sound from the indoor unit is decreased.
• The indications of the remote controller are “ ” and “ ”.
• When the FAN SPEED CONTROLbutton ( ) is pressed during the SLEEP mode , the SLEEP mode is released.
32
8. TIMER OPERATION
1. How to set the timer (1) Press OPERATE/STOP button to start the air conditioner. (2) Check that the current time is set correctly. NOTE : Timer operation will not work without setting the current time. Initially “AM0:00” blinks at the current time display
of TIMER MONITOR so set the current time, correctly with CLOCK SET button.
(3) Press TIMER CONTROL button to select the operation.
” button... AUTO START operation (ON timer) “ ” button... AUTO STOP operation (OFF timer)
(4) Press HR. and MIN. button to set the timer. Time setting is 10-minute units.
HR. and MIN. button will work when “ ” or “ ” mark is flashing. These marks disappear in 1 minute. When setting the ON timer, check that OPERATION INDICATOR of the indoor unit lights.
NOTE1 : Be sure to place the remote controller at the position where its signal can reach the air conditioner even during
TIMER operation, or the set time may deviate within the range of about 10 minutes.
NOTE2 : Reset the timer in the following cases, or the set time may deviate and other malfunctions may occur.
A power failure occurs.
The circuit breaker functions.
2. CANCEL Timer setting can be cancelled with the TIMER CONTROLbuttons. (“ ” or “ ”)
To cancel the ON timer, press the “ ” button. To cancel the OFF timer, press the “ ” button.
Timer is cancelled and the display of set time disappears.
PROGRAM TIMER
The OFF timer and ON timer can be used in combination.
”and “ ” display shows the order of the OFF timer and ON timer operation.
(Example 1) The current time is 8:00 PM.
The unit turns off at 11:00 PM, and on at 6:00 AM.
(Example 2) The current time is 11:00 AM.
The unit turns on at 5:00 PM, and off at 9:00 PM.
NOTE : TIMER setting will be cancelled by power failure or breaker functioning.
33
9. EMERGENCY-TEST OPERATION
Emergency operation switch
No. 1 unit No. 2 unit No. 3 unit
No. 4 unit
1 unit operation No modification
– –
2 units operation
Same as at left
Replace J10 with J 11
3 units operation
Same as at left Same as at left
Replace J20 with J 21
4 units operation
Same as at left Same as at left Same as at left
Replase J10 with J11
Replase J20 with J21
When the remote controller is missing, or has failed, or when the batteries run down, press the EMERGENCY OPERATION switch on the front of the indoor unit. The unit will start and the OPERATION INDICATOR lamp will light. The first 30 minutes of operation will be the test run operation. This operation is for servicing. The indoor fan runs at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. After 30 minutes of test run operation the system shifts to EMERGENCY COOL MODE with a set temperature of 24°C. The fan shifts to Me speed. This operation continues until the EMERGENCY OPERATION switch is pressed again or any button on the remote con­troller is pressed, and after that normal operation will start. The coil frost prevention circuit operates in this operation. In the test run or Emergency operation, the horizontal vane operates in AUTO mode with a set temperature of 24°C.
NOTE : Do not press the EMERGENCY OPERATION switch during normal operation.
Press once <Cool> Press again <Stop>
9
SERVICE FUNCTIONS
1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronics control P.C. board. The time will be shortened as follows. 3-minute delay : 3-minute 3-second. AUTO START : 1 hour 1-minutes AUTO STOP : 1 hour 1-minutes
Short the connector during the timer mode.
}
2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room. In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be modified according to the number of the indoor unit.
(1) <The reset button can be located on the rear side.>
MS-07NV - MS-09NV - MS-12NV - MS-18NV ­MS-24NV - MS-18NV -
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
The P.C.board has the print “J10” and “J20”.Jumper wires are mounted to each “J10” and “J20”.Replace J20 and J10 with J21 and J11 according to the number of indoor unit as shown in Table 1. After modification,push the reset button near the batteries.
E2E1
NOTE : For remodeling, take out the batteries at first.
After finish remodeling, put back the batteries then push the RESET but­ton.
E1E1E1E1
Table.1
Note : When power supply failure or installation time, Indoor unit will delete memory about its remote controller so when power
supply is restoration again, indoor unit recommend its remote controller by receive signal from remote controller at first.
34
No. 1 unit No. 2 unit No. 3 unit
No. 4 unit
1 unit operation No modification
– –
2 units operation
Same as at left
Cut J1
3 units operation
Same as at left Same as at left
Cut J2
4 units operation
Same as at left Same as at left Same as at left
Cut both J1 and J2
(2)<The reset button can be located on the front side.>
MS-07NV - (Product number 7000001T~) MS-09NV - (Product number 7000001T~) MS-12NV - (Product number 7000001T~) MS-24NV - (Product number 7000001T~) MS-07NV - MS-09NV ­MS-12NV - MS-18NV - (Product number 7000001T~) MS-24NV - MS-18NV -
How to modify the remote controller P.C. board
Remove batteries before modification. The board has a print as shown below :
The P.C.board has the print “J1” and “J2”.Jumper wires are mounted to each “J1” and “J2”.Cut J1 and J2 according to the number of indoor unit as shown in Table 1. After modification,push the reset button.
E1E1
E1E1
E2E2
E2E2
E3E2
NOTE : For remodeling, take out the
batteries at first. After finish remodeling, put back the batteries then push the RESET button.
Table.1
Note : At power supply failure or installation. indoor unit deletes the memory about remote controller. When the power supply
is turned on and indoor unit receives the first signals from the remote controller, the remote controller number is desig­nated as the indoor unit number. Therefore at and after the second time indoor unit accepts the remote controller of the initial setting number.
At setting-error, turn the power supply off to cancel the individual operation, and then turn the power supply on to restart
the setting.
35
C11
52C
CN201
CN112
CN121SW
CN111
IC101
CN211
CN151
JR07
JR06
CN102
CN151
CN112 CN111CN121
CN101
BZ
SW
52C
IC101 RA102
IC141
CN211
C11CN201
2. AUTO RESTART FUNCTION MS-07NV - MS-09NV ­MS-12NV - MS-24NV ­MS-18NV -
When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan speed are memorized by the indoor electronic control P.C.board. The “AUTO RESTART FUNCTION” sets to work the moment power has restored after power failure.Then, the unit will restart automatically. However if the unit is operated in “I FEEL CON­TROL.” mode before power failure, the operation is not memorized. In “I FEEL CONTROL.” mode, the operation is decided by the initial room temperature.
How to set “AUTO RESTART FUNCTION”
1Turn off the main power for the unit. 2Removed the electronic control P.C. board and the display P.C.board.(See page 45 and 47.) 3Cut the RESISTOR JR07 (MS-07/09/12) or JR06(MS-18/24) on the indoor electronic control P.C.board.
E3
MS-07/09/12
E2E2
E2E2
MS-18/24
Operation
1If the main power (220/240V AC) has been cut, the operation settings remain. 2After the power is restored, the unit restarts automatically according to the memory.(However, it takes at least 3 minutes
for the compressor to start running.)
Note:
36
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned off while AUTO START/STOP timer is active, the timer setting is cancelled when auto restart
function works.
If the unit has been off with the remote controller before power failure, the auto restart function does not works as the
power button of the remote controller is off.
To prevent breaker off due to the rush of startting current, systematize other home appliance not to turn on at the same
time.
When more than one air conditioners are connected under the same power system,compressor starting current as large
as that for all the compressors used flows at a time as soon as the units restart automatically. Therefore, the specific counter-measures are required to prevent main voltage drop or the rush of starting current after power failure by providing the system to allow the units to start in regular succession.
10 TROUBLESHOOTING
MS-07NV - MS-09NV - MS-12NV - MS-18NV ­MS-24NV - MS-07NV - MS-09NV - MS-12NV ­MS-18NV - MS-24NV - MS-18NV -
E3E2E2
E1E1E1E1
E2E2E2E1
10-1 Cautions on troubleshooting
10-1-1 Before troubleshooting, check the followings:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
10-1-2 Take care the followings during servicing.
1) Before servicing the air conditioner, be sure to first turn off the remote controller to stop the main unit, and then after confirming the horizontal vane is closed, turn off the breaker.
2) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
3) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
10-1-3 Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality. To make sure, check the abnormality indication for 2 or 3 times before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.
3) When troubleshooting, refer to the flow chart and the check table on page 38.
10-1-4 How to replace batteries
Weak batteries may cause the remote controller malfunction. In this case, the remote controller can not be repaired only by the battery replacement. To operate the remote con­troller normally, discharge the remote controller in the following order. This remote controller has the reset button. After refilling new batteries, press the reset button with tip end of ball point pen or the like, and then use the remote controller.
AA
RESET button
There are two kinds of remote controllers. A type has the RESET button at the back, and B type does it on the front.
BB
RESET button
37
10-2 Instruction of troubleshooting
Start
Indoor unit oper­ates. Outdoor unit doesn’t operate.
Outdoor unit operates in only Test Run opera­tion.
Check room temperature thermistor.
Outdoor unit doesn’t oper­ate even in Test Run operation.
Refer to
D
“Check of outdoor unit” on page 41.
Indoor unit
doesn’t receive the signal from remote
controller.
Refer to
B
”Check of receiver P.C. board” on page
40.
OPERATION INDICATOR lamp on the indoor unit is flashing on and off.
Indoor unit doesn’t receive the signal from remote controller. Also, OPERATION INDI­CATOR lamp doesn’t flash, when the EMER-
2-time flash
GENCY OPERATION switch is pressed.
2.5-second OFF 3-time flash
Refer to “Check of indoor electronic control
2.5-second OFF
P.C. board” on page 41.
Cause:Indoor unit 2-time-Room temperature/Indoor coil thermistor trouble 3-time-Indoor fan motor trouble
Check indoor coil thermistor. Refer to“Test point dia-
Refer to
A
“Check of indoor fan motor” on page 40.
Check room temperature thermistor. Refer to“Test point diagram and volt­age” on page 42~44.
gram and voltage” on page 42~44.
C
10-2-1 troubleshooting check table
Before taking measures make sure that the symptom reappears, for accurate troubleshooting.
Self check table
Abnormal
NO.
1
2
38
point
Indoor coil thermistor
Room tempera­ture ther­mistor
Indoor fan motor
2-time flash
2.5-second OFF
3-time flash
Indication
2.5-second OFF
Symptom
Outdoor unit does not run.
Indoor fan repeats 12 sec­onds ON and 3 minutes OFF. When the indoor fan breaks, the fan keeps stop­ping.
Detect method
Detect Indoor coil/room tem­perature thermistor short or open circuit every 2 seconds during operation.
When rotational frequency feedback signal is not emit during 12-second indoor fan operation
Check thermistor calibration.
Reconnect connector.
Check indoor electronic control P.C.
Disconnect connector CN211 and then
Check indoor electronic control P.C.
Check indoor fan motor.
Reconnect connector.
Check point
board.
check connector CN121 2 - 3 to make sure rotational frequency feedback signal of 1.5V or over exists.
board.
10-2-2 Trouble criterion of main parts
P
~
BLK
R
MAIN
AUX
RED
S
C
WHT
MAIN
AUX
FUSE
BLK RED WHT
MAIN
AUX
BLK RED WHTORN
P
MAIN
AUX
BLK RED WHT
P
MAIN
AUX
BLKYLW RED WHTORN
P
MAIN
YLW
RED
BLU
ORN
PNK
ROTOR
INNER PROTECTOR
P
Part name
Room temperature thermistor
Indoor coil thermistor
Measure the resistance with a tester. (Part temperature 10°C ~ 30°C)
Normal
8k~ 20k
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
MS-07NV - MS-09NV - MS-12NV - MS-18NV ­MS-24NV - MS-07NV - MS-09NV - MS-12NV ­MS-18NV - MS-24NV - MS-18NV -
E3E2E2
Check method and criterion
Abnormal
Opened or short-circuited
E1E1E1E1 E2E2E2E1
Figure
Compressor
Indoor fan motor
Outdoor fan motor
Normal
09NV
3.56~4.36
5.25~6.44
12NV 18NV
1.86~2.28
3.50~4.29
1.05~1.30
2.38~2.92
0.84~1.04
1.82~2.24
24NV C-R C-S
07NV
3.67~4.50
5.07~6.21
Measure the resistance between the terminals with a tester. (Coil wiring temperature10°C ~ 30°C)
Normal
Motor partSensor part
WHT-BLK BLK-RED
07/09/12NV 280 ~ 303 313 ~ 336
18/24NV 176 ~ 192 240 ~ 261
Measure the voltage Power ON.
BRN-YLW
YLW-GRY
Normal
4.5 ~ 5.5V
(When fan revolved one time)
0V5V0V
(Approx.)
Abnormal
Remain 0V or 5V
Measure the resistance between the terminals with a tester. (Coil wiring temperature –10°C ~ 40°C)
Normal
WHT-BLK
BLK-RED
07/09NV 236 ~ 290 344 ~ 422
12NV 115 ~ 141 118 ~ 146
18NV
102 ~ 126
97.9 ~ 120
BLK-YLW
Abnormal
Opened or
short-circuited
Opened or
short-circuited
24NV
71.5 ~ 87.5
90.1 ~ 111
81.3 ~ 99.5
Abnormal
07NV 09NV
12NV 18NV
Abnormal
Opened or
short-circuited
24NV
Vane motor
Measure the resistance between the terminals with a tester. (Part temperature10°C ~ 30°C)
Normal
07/09/12NV 282 ~ 305
18/24NV 358 ~ 388
Abnormal
Opened or short-circuited
39
A
Check of indoor fan motor
Indoor fan does not operate.
Are lead wires connected?
Reconnect the lead
wires.
Disconnect lead wires from connector CN211 on indoor electronic control P.C. board. Measure resistance between lead wires No.1 and No.4 and then No.1 and No.2(MS-12/18/24)
Check of receiver P.C. board
B
Turn OFF power supply. Check connector CN211 visually.
YesNo
{
No.1 and No.3 and then No.2 and No.3(MS-07/09)
Is resistance 0 (short circuit) or (open circuit)?
Yes ( 0 or )
Repair the indoor fan motor.
Is soldered point normal?
Yes
}
Replace the indoor electronic control P.C. board.
No
(others)
No
Resolder it.
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but does not operate with the remote controller.
Check the model name of remote controller.
Is.LCD display on remote con-
troller visible?
Yes
Remove batteries and then set them back. Check if the unit operates with remote controller.
Does the unit operate with remote
controller?
Yes
OK
No (not clear)
No
Replace batteries.(see page 37.)
Turn on a radio to AM and press switch on remote controller.
Is noise heard from radio?
Yes
Are there any fluorescent lights of inverter or rapid-start type within the range of 1m?
No
Turn ON power supply. Measure the voltage between receiver P.C. board connector No.2
when remote controller button is pressed.
{
indoor electronic control P.C. board connector LD101 No.2 and JPG(MS-07/09)
No
Yes
Replace the remote controller.
Re-install the unit away from lights.
Attach a filter on receiving part.
(+)
and No.1(MS-12/18/24)
}
40
Is the voltage approx. 4V DC?
No(5V or 0V DC)
Replace the receiver.
Yes
Replace the indoor electronic control P.C. board.
Check of indoor electronic control P.C. board
C
The unit doesn’t operate with the remote controller.
Replace the fuse.
Also, the OPERATION INDICA­TOR lamp doesn’t light up by pressing the EMERGENCY OPERATION switch.
Is fuse(F11)blown?
Check both “parts side” and “pattern side” of indoor electronic control P.C.board visually.
Be sure to check both fuse and varis­tor in any case.
Yes
No
1.Pull out power supply cord.
2.Measure voltage between CN201
1
on electronic con­trol P.C. board and on the terminal block with a tester.
Trouble of indoor electronic con­trol P.C. board.
Yes
Is there resistance? (Approx.0)
N
No
Trouble of fuse(F12)
Is varistor(NR11)burnt?
No
07NV
09NV
Yes
Replace the varistor.
12NV
18NV
24NV
D
Check of outdoor unit
Compressor and outdoor fan do not operate.(Only indoor fan operates.)
MS-07NV
MS-24NV
MS-09NV MS-12NV
Start
Start
MS-18NV
Yes
Check the outdoor fan motor and compressor.
Press EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Check voltage to terminal block of outdoor unit. Is there AC220-240V to terminal block between 2 - N ?
No
Press EMERGENCY OPERATION switch. 3-minute time delay works. Test run operation operates for 30 minutes.
Check voltage to terminal block of outdoor unit. Is there AC220-240V to terminal block between 2 - N ?
Yes
CN201
CN201
13
1
2
No
F12
L
Terminal
N
block
F12
L
Terminal
N
block
Check the continuity of
indoor and outdoor unit
connection.
Replace the indoor elec­tronic control P.C.board.
No
Yes
Check the conti-
Check the continu-
nuity of indoor
ity of indoor and
and outdoor unit
outdoor unit con-
connection.
nection.
Check voltage to terminal block of indoor unit. Is there AC220-240V to terminal block between 2 - N ?
Replace the indoor electronic con­trol P.C. board.
No
Check voltage to terminal block of outdoor unit. Is there AC220-240V to terminal block between 3 - N ?
Yes
Check the outdoor wiring and con­ductor relay at first, then check the outdoor fan motor and compressor.
No
Check voltage to terminal block of indoor unit. Is there AC220-240V to terminal block between 3 - N ?
Check the continuity of indoor and outdoor unit connection.
Yes
41
TEST POINT DIAGRAM AND VOLTAGE MS-18NV ­Indoor electronic control P.C. board
E1
Fan motor power supply
}
Fuse AC250V 3.15A
Power supply input AC220-240V
}
JPS
JPG
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
C144
+
C144
--
Indoor coil thermistor (RT12)
Room temperature thermistor (RT11)
Time short mode point
DC5V
}
Emergency operation switch
JPG
--
JP43
+
DC12V
}
42
TEST POINT DIAGRAM AND VOLTAGE MS-07NV - MS-09NV - MS-12NV ­MS-07NV - MS-09NV - MS-12NV ­Indoor electronic control P.C. board
E1E1E1
E2E2E2
Power supply input AC220-240V
}
Varistor(NR11)
CN201 No1
Fuse AC250V 3.15A
Room temperature thermistor
(RT11)
Indoor coil thermistor
(RT12)
Timer short mode point
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
43
TEST POINT DIAGRAM AND VOLTAGE MS-24NV - MS-18NV ­MS-24NV - MS-18NV ­Indoor electronic control P.C. board
E2E1
E3E2
Fan motor power supply
}
Fuse AC250V 3.15A
Power supply input
}
AC220-240V
+
--
C144
C144
}
DC5V
Room temperature thermistor(RT11)
Indoor coil thermistor(RT12)
Timer short mode point
JPG
--
JP45
+
Room temperature thermistor (RT11) Indoor coil thermistor (RT12)
DC12V
}
Emergency operation switch
44
11
DISASSEMBLY INSTRUCTIONS
NOTE:
on the wiring diagram shows the terminals with a lock mechanism, so it cannot be removed when you pull the lead wire Be sure to pull the wire by pushing the locking lever (projected part) of the terminal with a finger.
Slide the sleeve.Pull the wire while pushing
the locking lever.
11-1 MS-07NV - MS-09NV - MS-12NV -
MS-07NV - MS-09NV - MS-12NV ­INDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screws caps of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board and the display P.C. board.
(1) Remove the front panel. (Refer to 1) (2) Remove the screw of the electrical cover.
Remove the electrical cover.
(3) Disconnect the room temperature thermistor and the con-
nector from the indoor coil thermistor.
(4) Remove the terminal cover.
Remove the screw of the terminal block. (5) Remove the cord clamp. (6) Disconnect all the connectors on the electronic control P.C.
board. (7) Remove the screw of the ground wire. (8) Disconnect the white lead wire and the brown lead wire
from 52C relay. (9) Remove the electronic control P.C. board and the display
P.C. board.
E1E1E1
E2E2E2
Photo 1
Photo 2
Front panel
Screws
Room temperature thermistor connector
Ground wire screw
Cord clamp
Terminal block cover
Indoor electronic control P.C.board
Terminal block cover screw
45
OPERATING PROCEDURE PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con­trol P.C. board.
(5) Unhook the catches (both upper and lower), remove the
electrical box.
4. Removing the vane motor
(1) Remove the front panel. (2) Remove the screw of the vane motor, disconnect the con-
nector.
(3) Remove the vane motor.
Photo 3
Catch
Vane motor screw
5. Removing the line flow fan and the indoor fan motor
(1) Remove the front panel. (Refer to 1) (2) Disconnect the connector from the vane motor. (3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly.
(4) Lifting the left side of the heat exchanger, remove the elec-
trical box. (5) Remove the fixture of the fan motor. (6) Remove the hexagon socket set screws. (7) Remove the line flow fan and the fan motor.
Photo 4
Fan motor catches
Vane motor
Fan motor fixture
Drain hose
Indoor coil thermistor
46
11-2 MS-18NV - MS-24NV - MS-18NV -
MS-24NV - MS-18NV -
E3 E2
INDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the front panel
(1) Remove the screws caps at the down of the front panel.
Remove the screws.
(2) Pull the panel down to your side slightly and unhook the
catches at the top.
2. Removing the electronic control P.C. board
(1) Remove the front panel. (Refer to 1) (2) Remove the electriccal cover. (3) Remove the screw, remove the terminal cover. (4) Remove the screw on the terminal block. (5) Unhook the catch of the lamp holder. (6) Remove the receiver holder. (7) Disconnect the connectors and the lead wire from 52C
relay on the electronic control P.C. board and remove the ground and the indoor coil thermistor.
(8) Remove the electronic control P.C. board.
E2 E1E1
Photo 1
Photo 2
Ground
Front panel
Screws
Indoor coil thermistor
Screw
Terminal block screw
Indoor electronic control P.C. board
47
OPERATING PROCEDURE PHOTOS
3. Removing the electrical box
(1) Remove the front panel. (Refer to 1) (2) Remove the electrical cover. (3) Disconnect the connector of the indoor coil thermistor. (4) Disconnect the motor connector (CN211 and CN121) and
the vane motor connector (CN151) on the electronic con­trol P.C. board.
(5) Remove the screw of the electrical box, remove the electri-
cal box.
4. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel. (2) Remove the electrical box. (3) Unhook the catches on the both sides of the nozzle assem-
bly. (4) Remove the nozzle assembly. (5) Remove the screws of the bearing support. (6) Remove the screw of the heat exchanger unhook the
catch. (7) Lifting the heat exchanger, remove the bearing support. (8) Remove the motor support. (9) Loose the screw fixing the line flow fan, remove the line
flow fan.
)
(
Remove the screws of the motor band, remove the fan
10
motor.
Photo 3
Photo 3
Catch
Heat exchanger
screw
Bearing support screws
screw
screw
Heat exchanger
48
Photo 4
Indoor fan motor
Fan motor screws
Line flow fan Motor band
11-3 MU-07NV - MU-09NV - MU-07NV - MU-09NV -
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
E2E2E1E1
1. Removing the cabinet
(1) Remove screws securing the top panel. (2) Remove the screw securing the service panel. (3) Remove screws securing the cabinet. (4) Remove the service panel,and remove the screw from the
insides. (5) Remove the top panel. (6) Remove the cabinet.
Photo 1
Photo 2
Screw for service panel
Service panel
Screw for top panel
Screws for cabinet
Screw for top panel
2. Removing the propeller fan and the outdoor fan motor
(1) Remove the cabinet.(Refer to 1) (2) Remove the propeller fan nuts. (3) Remove the propeller fan. NOTE:
Loose the propeller fan in the rotating direction for
removal.
When attaching the propeller fan ,align the mark on the propeller fan and the motor shaft cut section. Set the propeller fan in position by using the cut on the shaft and the mark on the propeller fan.
(4) Remove lead clamps and disconnect the outdoor fan motor
lead wires. (5) Remove screws fixing the fan motor. (6) Remove the outdoor fan motor.
Screw for cabinet
Photo 3
Propeller fan
Outdoor fan motor
Set screws for outdoor fan motor
Propeller fan nut
Lead clamps
49
OPERATING PROCEDURE PHOTOS
3. Removing the compressor
(1) Remove the lead clamps. (2) Remove the screws fixing the relay panel. (3) Remove the screw fixing the service port. (4) Remove the terminal cover. (5) Pull out the lead from the compressor terminal. (6) Remove the overcurrent relay. (7) Remove the compressor nuts. (8) Detach the suction pipe welded section and discharge pipe
welded section with a burner.
NOTE
Before using a burner, purge gas from the pipes until the pres­sure gauge shows 0 kg/cm
Use the burner under the condition that gas can be released even when the inner pressure rises by heat.
2
.
Photo 4
Terminal cover
compressor
Discharge pipe
Suction pipe
50
11-4 MU-12NV - MU-18NV - MU-24NV - MU-12NV -
MU-18NV - MU-24NV - MU-18NV -
E3E2E2
OUTDOOR UNIT
OPERATING PROCEDURE PHOTOS
1. Removing the cabinet
(1) Remove the screws of the cabinet. (2) Hold the bottom of the cabinet on the both side to remove
the cabinet.
Photo 1
Service panel
Photo 2
E2E1E1E1
Screws
2. Removing the electrical parts
(1) Remove the service panel and the cabinet. (2) Remove the following parts.
•Compressor capacitor (C1)
•Outdoor fan capacitor (C2)
•Terminal block
Screws
Photo 3
Compressor capacitor
51
OPERATING PROCEDURE
3. Removing the outdoor fan motor
(1) Remove the cabinet. (Refer to 1) (2) Disconnect the connector remove the hooked lead wire
from the fan motor. (3) Remove the propeller nut and remove the propeller. (4) Remove screws securing the fan motor.
Photo 4
PHOTOS
Hook
Connector
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1) (2) Remove the soundproof felt. (3) Remove the terminal cover on the compressor (4) Disconnect lead wires from the glass terminal of the com-
pressor.(Refer to 2) (5) Release gas from the refrigerant circuit. (6) Disconnect the welded part of the discharge pipe. (7) Disconnect the welded part of the suction pipe. (8) Remove nuts fixing the compressor. (9) Remove the compressor.
Propeller fan
Photo 5
Compressor
Soundproof felt
Propeller nut
Discharge pipe
Suction pipe
52
Compressor set nuts
PARTS LIST12
E02 151 620 E02 155 620 E02 151 666 E02 155 666 E02 151 667
1
2
3
INDOOR HEAT EXCHANGER INDOOR HEAT EXCHANGER UNION(GAS) UNION(GAS) UNION(LIQUID)
Symbol
in Wiring
Diagram
Q'ty/unit
1
1
1
1
1 1
RemarksPart No.
NO.
Part Name
MS-07/09NV-
(WH)
E1 E2
MS-12NV­ (WH)
E1 E2
{9.52 {12.7 {6.35
INDOOR UNIT STRUCTURAL PARTS MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH) MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH)
E1
E1
E1
E2
E2
E2
1
5
4
6
Optional part (See page 62.)
2
3
NO.
E02 202 000 E02 158 000
1
E02 160 000 E02 151 010
2
E02 164 100
3
E02 151 234
4
E02 166 234 E02 151 970
5
E02 166 067
6
FRONT PANEL(WH) FRONT PANEL(WH) FRONT PANEL(WH) GRILLE(WH) AIR FILTER BOX(WH) BOX(WH) INSTALLATION PLATE SCREW CAP(WH)
INDOOR UNIT HEAT EXCHANGER MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH) MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH)
E1
E1
E1
E2
E2
E2
Part Name
Symbol
in Wiring
Diagram
1
MS-07NV- E1
(WH)
1
1 2 1
1 2
MS-07NV- E2
3
(WH)
1
1 2
1 1 2
2
MS-09NV- E1
(WH)
1
1 2 1
1 2
Q'ty/unit
MS-09NV- E2
(WH)
1
1 2
1 1 2
MS-12NV- E1
(WH)
1 1 2 1
1 2
MS-12NV- E2
(WH)
1 1 2
1 1 2
RemarksPart No.
1PC/SET
2PCS/SET
53
INDOOR UNIT ELECTRICAL PARTS MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH) MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH)
E1
E1
E1
E2
E2
E2
8
16
7
9
11
10
6
3
5
1
2
Part number that are circled is not shown in the illustration.
Symbol
NO.
E02 166 235
1
E02 166 040
2
E02 141 702
3
E02 151 303
4
E02 151 300
5
E02 151 505
6
E02 151 302
7
E02 151 509
8
E02 151 308
9
E02 151 307
10
E02 197 375
11
E02 202 450
12
E02 204 450 E02 152 395
13
E02 127 382
14
E02 085 385
15
E02 001 504
16
E02 151 468
17
E02 199 520
18
Part Name
NOZZLE(WH) VANE(WH) DRAIN HOSE VANE MOTOR INDOOR FAN MOTOR RUBBER MOUNT LINE FLOW FAN BEARING MOUNT ROOM TEMPERATURE THERMISTOR INDOOR COIL THERMISTOR TERMINAL BLOCK ELECT CONTROL P.C.BOARD ELECT CONTROL P.C.BOARD POWER SUPPLY CORD FUSE VARISTOR SLEEVE BEARING RECEIVER FAN GUARD
in Wiring
Diagram
MV MF
RT11 RT12
TB
F11
NR11
4
MS-07NV-
(WH)
1 1 1 1 1 2 1 1 1 1 1 1
1 1 1 1 1 1
13
Q'ty/unit
E1 E2 E1 E2 E1 E2
MS-09NV-
(WH)
1
1 1 1 1 2 1 1 1 1 1 1
1 1 1 1 1 1
MS-12NV-
(WH)
1
1 1 1 1 2 1 1 1 1 1
1 1 1 1 1 1 1
12
RemarksPart No.
RC4V19 ­2PCS/SET
3.15A
54
OUTDOOR UNIT STRUCTURAL PARTS MU-07NV ­MU-09NV ­MU-07NV ­MU-09NV -
1
E1
E1
E2
E2
2
5
10
8 9
3
Part number that are circled is not shown in the illustration.
NO.
E02 096 232
1
E02 085 297
2
E02 199 521
3
E02 085 245
4
E02 085 630
5
E02 127 900
6
E02 164 900 E02 047 506
7
E02 096 662
8
E02 096 661
9
E02 085 515
10
E02 127 290
11
E02 158 936
12
CABINET TOP PANEL FAN GUARD SERVICE PANEL OUTDOOR HEAT EXCHANGER COMPRESSOR COMPRESSOR COMPRESSOR RUBBER SET STOP VALVE(LIQUID) STOP VALVE(GAS) MOTOR SUPPORT BASE CAPILLARY TUBE
Part Name
Symbol
in Wiring
Diagram
MC MC
4
MU-07NV
1 1 1 1 1
1 3 1 1 1 1 1
Q'ty/unit
E1
-
E2
-
6
MU-09NV MU-07NV MU-09NV
1 1 1 1 1 1
3 1 1 1 1 1
11
7
E1
-
E2
-
RemarksPart No.
RH-145VGHT RH-135VGHT
{ 6.35 { 9.52
{3.0 {1.6 1200
55
E02 085 501 E02 085 301 E02 085 353 E02 002 350 E02 202 374
1 2 3 4 5
PROPELLER FAN OUTDOOR FAN MOTOR COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR TERMINAL BLOCK
Symbol
in Wiring
Diagram
Q'ty/unit
RA6V23­25+/440VAC
1.5+/440VAC
RemarksPart No.
NO.
Part Name
MF
C1 C2 TB
1 1 1 1 1
MU-07NV-
E1 E2
MU-09NV-
E1 E2
OUTDOOR UNIT FUNCTIONAL PARTS AND ELECTRICAL PARTS MU-07NV ­MU-09NV ­MU-07NV ­MU-09NV -
E1
E1
E2
E2
1
2
4
5
3
56
OUTDOOR UNIT STRUCTURAL PARTS MU-12NV ­MU-12NV -
E1
E2
3
16
15
14
2
1
Part number that are circled is not shown in the illustration.
NO.
E02 141 521
1
E02 141 232
2
E02 140 233
3
E02 141 245
4
E02 075 506
5
E02 140 515
6
E02 141 630
7
E02 141 900
8
E02 140 290
9
E02 139 662
10
E02 140 661
11
E02 141 501
12
E02 141 301
13
E02 079 353
14
E02 204 374
15
E02 138 351
16
E02 140 936
17
GRILLE CABINET ASSEMBLY BACK PANEL SERVICE PANEL COMPRESSOR RUBBER SET MOTOR SUPPORT OUTDOOR HEAT EXCHANGER COMPRESSOR BASE STOP VALVE(LOQUID) STOP VALVE(GAS) PROPELLER FAN OUTDOOR FAN MOTOR COMPRESSOR CAPACITOR TEAMINAL BLOCK OUTDOOR FAN CAPACITOR CAPILLARY TUBE
Part Name
12
Symbol
in Wiring
Diagram
MC
MF
C1
TB
C2
6
MU-12NV-
1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1
5
Q'ty/unit
E1
8
MU-12NV-
1 1 1 1 3 1 1 1 1 1 1 1 1 1 1 1 1
7
13
E2
RH-231VHAT
{ 6.35 { 12.7
RA6V40 ­30+/440VAC
3.0MFD/440VAC {3.0{1.8800
4
10
11
9
RemarksPart No.
57
INDOOR UNIT STRUCTURAL PARTS MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH)
E1
E1
E2
E2
E3
1
5
3
Optional parts (See page 62.)
6
2
6
Part number that are circled is not shown in the illustration.
NO.
E02 138 000
1
E02 138 010
2
E02 143 234
3
E02 141 100
4
E02 141 970
5
E02 143 067
6
E02 171 007
7
E02 176 007
FRONT PANEL (WH) GRILLE (WH) BOX (WH) AIR FILTER INSTALLATION PLATE SCREW CAP (WH) LAMP PANEL (WH) LAMP PANEL (WH)
Part Name
INDOOR UNIT HEAT EXCHANGER PARTS MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH)
E1
E1
E2
E2
E3
1
6
Symbol
in Wiring
Diagram
MS-18NV-
(WH)
E1 E2 E3
1 1 1 2 1 3 1
4
Q'ty/unit
MS-24NV-
(WH)
1 1 1 2 1 3
1
E1 E2
RemarksPart No.
1PC/SET
3PCS/SET
NO.
E02 141 620
1
E02 138 667
2
E02 176 667 E02 138 666
3
58
INDOOR HEAT EXCHANGER UNION(LIQUID) UNION(LIQUID) UNION(GAS)
Part Name
Symbol
in Wiring
Diagram
32
Q'ty/unit
MS-18NV -
(WH)
E1 E2 E3
1 1
1
MS-24NV
(WH)
1
1 1
-
E1 E2
RemarksPart No.
{6.35 {9.52 {15.88
INDOOR UNIT ELECTRICAL PARTS MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH)
E1
E1
E2
E2
E3
15
11
10
5
8
3
1
2
Part number that are circled is not shown in the illustration.
Symbol
Part No.
NO.
1
E02 143 235
2
E02 143 040
3
E02 141 702 E02 141 300
4
E02 213 300
5
E02 001 505 E02 138 395
6
E02 147 395 E02 320 395 E02 138 450
7
E02 213 450 E02 197 450
8
E02 141 302
9
E02 141 303
10
E02 138 329
11
E02 141 509 E02 138 375
12
E02 209 375 E02 197 375
13
E02 085 385
14
E02 141 468
15
E02 001 504
16
E02 138 307
17
E02 138 308
18
E02 127 382
19
E02 138 520
Part Name
NOZZLE (WH) VANE (WH) DRAIN HOSE INDOOR FAN MOTOR INDOOR FAN MOTOR RUBBER MOUNT POWER SUPPLY CORD POWER SUPPLY CORD POWER SUPPLY CORD ELECT CONTROL P.C. BOARD ELECT CONTROL P.C. BOARD ELECT CONTROL P.C. BOARD LINE FLOW FAN VANE MOTOR DISPLAY P.C. BOARD BEARING MOUNT TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK VARISTOR RECEIVER P. C. BOARD SLEEVE BEARING INDOOR COIL THERMISTOR ROOM TEMPERATURE THERMIST OR FUSE FAN GUARD
in Wiring
Diagram
MF MF
MV
TB TB TB
NR11
RT12
RT11
F11
9
MS-18NV
(WH)
1 1 1 1
2 1
1
1 1 1 1 1
1 1 1 1 1 1 1
-
6
E1
12
MS-18NV
(WH)
4
16
-
1 1 1 1
2 1
1 1 1 1 1
1 1 1 1 1 1 1 1
5
Q'ty/unit
E2 E3
MS-24NV
17
(WH)
1 1 1
1 2
1
1
1 1 1 1
1
1 1 1 1 1 1 1
E1
-
MS-24NV
(WH)
1 1 1
1 2
1
1
1 1 1 1
1
1 1 1 1 1 1 1
7
E2
-
RA4V27 -EA RA4V27 -EC 2PCS/SET
3.15A
14
Remarks
59
Symbol
in Wiring
Diagram
Q'ty/unit
Remarks
Part No.
NO.
Part Name
E1 E1E2 E3
-- -E2­E02 141 232 E02 141 521 E02 141 245 E02 138 630 E02 147 630 E02 138 515 E02 139 515 E02 138 900 E02 042 900 E02 138 290 E02 176 290 E02 144 301 E02 147 301 E02 141 501 E02 144 353 E02 082 353 E02 138 351 E02 141 374 E02 197 374 E02 209 374 E02 138 936 E02 176 936 E02 138 506 E02 139 662 E02 176 662 E02 150 661 E02 140 233 E02 010 342 E02 229 381 E02 288 343
1 2 3
4
5
6
7
8
9 10 11
12
13 14 15 16
17 18 19 20
CABINET GRILLE SERVICE PANEL OUTDOOR HEAT EXCHANGER OUTDOOR HEAT EXCHANGER MOTOR SUPPORT MOTOR SUPPORT COMPRESSOR COMPRESSOR BASE BASE OUTDOOR FAN MOTOR OUTDOOR FAN MOTOR PROPELLER FAN COMPRESSOR CAPACITOR COMPRESSOR CAPACITOR OUTDOOR FAN CAPACITOR TERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK CAPILLARY TUBE CAPILLARY TUBE COMPRESSOR RUBBER SET STOP VALVE(LIQUID) STOP VALVE(LIQUID) STOP VALVE(GAS) BACK PANEL COMPRESSOR CONTACTOR THERMAL REED SWITCH FAN MOTOR RELAY
MU-18NV
1 1 1 1
1
1
1
1
1 1
1 1
1
4 1
1 1
MU-18NV
1 1 1 1
1
1
1
1
1 1
1
1
1
4 1
1 1
MU-24NV
1 1 1
1
1
1
1
1 1
1 1
1 1 1 4
1 1 1 1
MU-24NV
1 1 1
1
1
1
1
1 1
1 1
1 1 1 4
1 1 1 1 1 1
NH-33VMDT NH-47VMDT
RA6V50 ­RA6V60 -
45+/440V 50+/440V
3.0+/440V
{3.0{2.0700 {3.0{1.6350
{ 6.35 { 9.52 {15.88
MC MC
MF MF
C1 C1 C2 TB TB TB
52C
OUTDOOR UNIT STRUCTURAL PARTS MU-18NV ­MU-24NV ­MU-18NV ­MU-24NV ­MU-18NV -
E1
E1
E2
E2
1
E3
17
11
12
10
4
8
2
Part number that are circled is not shown in the illustration.
60
9
5
14
6
3
15
16
7
ACCESSORY AND REMOTE CONTROLLER PARTS
3m 5m 7m
10m
3m 5m
7m 10m 15m
3m
5m
7m 10m 15m
3m
5m
7m 10m 15m
9.52 (3/8)
12.7 (1/2)
15.88 (5/8)
6.35 (1/4)
9.52 (3/8)
27
31
21
27
MAC-440PI MAC-441PI MAC-442PI MAC-443PI MAC-660PI MAC-661PI MAC-662PI MAC-663PI MAC-664PI MAC-670PI MAC-671PI MAC-672PI MAC-673PI
MAC-674PI MAC-860PIE MAC-861PIE MAC-862PIE MAC-863PIE MAC-864PIE
MS-07NV­MS-09NV­MS-07NV­MS-09NV-
MS-12NV­MS-12NV-
MS-18NV­MS-18NV­MS-18NV-
MS-24NV­MS-24NV-
0
45
0
45
120
0
45
120
0
45
120
Pipe length
Cross-section
Part No.Model
A-Gas B-Liquid
Pipe size O.D mm (in.)
Insulation
DC
Additional refrigerant
charge
R-22 (g)
E1 E1 E2 E2
E1 E2
E1 E2 E3
E1 E2
MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH) MS-18NV - (WH) MS-24NV - (WH) MS-07NV - (WH) MS-09NV - (WH) MS-12NV - (WH) MS-18NV - (WH) MS-24NV - (WH) MS-18NV - (WH)
E1
E1
E1
E1
E1
E2
E2
E2
E2
E2
E3
2
1
Symbol
NO.
Part Name
in Wiring
Diagram
E02 138 426
1
E02 141 083
2
REMOTE CONTROLLER REMOTE CONTROLLER HOLDER
13 OPTIONAL PARTS
1. REFRIGERANT PIPES
The air conditioner has flared connections its indoor and outdoor sides. Please use the optional extension pipe as follows.
Q'ty/unit
MS-07/09/12/18/24NV- MS-18NV - MS-07/09/12/18/24NV-
E1 E3 E2
1 1
(WH)
RemarksPart No.
61
2. AIR CLEANING FILTER
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 3 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
Model MS-07NV - , MS-09NV - , MS-12NV - MS-18NV - , MS-24NV -
E1 E2
E1 E2
E3
E1 E2
E1 E2
E1 E2
Part No. MAC-1000FT MAC-1100FT
3. DEODORIZING FILTER
DEODORIZING FILTER removes ammonia and hydrogen sulphide emitted from tobacco, and odors of pets.
Clean DEODORIZING FILTER every two weeks. If the filter is particularly dirty, clean the filter more often.
For cleaning, soak the filter in warm water for a while, and then wash and rinse it. Dry the filter in the shade thoroughly.
When the filter color is still dark even after cleaning, replace the filter with a new one.
Replace the filter at least once a year.
Model MS-07NV - , MS-09NV - , MS-12NV - MS-18NV - , MS-24NV -
E1 E2
E1 E2
E3
E1 E2
E1 E2
E1 E2
Part No. MAC-1500DF MAC-1600DF
DEODORIZING FILTER and AIR CLEANING FILTER can be attached on either side.
62
HEAD OFFICE MITSUBISHI DENKI BLDG.MARUNOUCHI TOKYO100 TELEX J24532 CABLE MELCO TOKYO
CC
Copyright 1997 MITSUBISHI ELECTRIC ENGINIEERING CO.,LTD Issued in Sep. 1997. No.OB206 646 Printed in Japan
New publication, effective Sep. 1997 Specifications subject to change without notice.
Loading...