Mitsubishi Electric MELSERVO-JN, MR-JN-10A, MR-JN-20A1, MR-JN-20A, MR-JN-40A Instruction Manual

...
General-Purpose AC Servo
JN Series
General-Purpose Interface Servo Amplifier
MODEL (Servo Amplifier)
MR-JN-A
MODEL (Servo Motor)
HF-KN HF-KPG1/G5/G7 HG-KRG1/G5/G7
INSTRUCTION MANUAL
D

Safety Instructions

Please read the instructions carefully before using the equipment.
Be sure to read through this Instruction Manual, Installation guide and appended documents carefully before using the equipment. For your protection, do not install, operate, inspect or perform maintenance procedures until you have a full knowledge of the equipment and the safety information and instructions. In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
WARNING
CAUTION
Note that the the instructions of both levels because they are important to personnel safety. What must not be done and what must be done are indicated by the following diagrammatic symbols.
CAUTION level may lead to a serious consequence according to conditions. Please follow
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight injury to personnel or may cause physical damage.
: Indicates what must not be done. For example, "No Fire" is indicated by .
: Indicates what must be done. For example, grounding is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so on are classified into "POINT". After reading this Instruction Manual, always keep it accessible to the operator.
A - 1
1. To prevent electric shock, note the following
WARNING
Before wiring, be sure to turn off the power, wait for 15 minutes or longer, and then make sure that the charge lamp is off to prevent an electric shock. In addition, always confirm if the charge lamp is off or not from the front of the servo amplifier. Ground the servo amplifier and the servo motor securely. Only qualified personnel should attempt wiring and inspection. Wire the servo amplifier and the servo motor after installation is complete to prevent an electric shock. Do not operate the switches with wet hands as it may cause an electric shock. Do not damage, stress excessively, place heavy objects or pinch the cable to prevent an electric shock. To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of the servo amplifier with the protective earth (PE) of the control box. When using an earth-leakage current breaker (RCD), select the type B. To avoid an electric shock, insulate the connections of the power supply terminals.
2. To prevent fire, note the following
CAUTION
Install the servo amplifier, the servo motor and the regenerative option on incombustible material. Installing them directly or close to combustibles may cause a fire. Be sure to connect a magnetic contactor between the power supply and the main circuit power supply (L1/L2) of the servo amplifier, in order to configure a circuit that shuts off the power supply by the magnetic contactor. If a magnetic contactor is not connected, a continuous flow of a large current may cause a fire when the servo amplifier malfunctions. When using a regenerative resistor, configure a circuit that shuts off the power if abnormality is found. Otherwise, the regenerative resistor may overheat, causing a fire due to a regenerative transistor fault. When using a regenerative option, remove the built-in regenerative resistor and its wiring from the servo amplifier. Provide an adequate protection to prevent conductive matters such as screws or metal pieces or combustible matters such as oil from entering the servo amplifier and the servo motor. Always connect a molded-case circuit breaker to the power supply of the servo amplifier.
3. To prevent injury, note the following
CAUTION
Do not apply voltage other than specified in this Instruction Manual to each terminal as it may cause burst, damage, etc. Connect the wires to correct terminals to prevent burst, damage, etc. Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur. The servo amplifier heat sink, the regenerative option, the servo motor can be very hot during power-on and for some time after power-off, and it may result burns or damages to parts (cables, etc.) Take measures, e.g. provide covers, to prevent accidental contact of hands and parts with them. Never touch the rotating parts of the servo motor during operation as it may cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric shock, etc.
(1) Transportation and installation
CAUTION
Carry the products in a suitable way according to their weights. Do not stack the product packages exceeding the maximum number specified on the package. Do not hold the lead of the built-in regenerative resistor, the cables, or the connectors when carrying the servo amplifier. Otherwise, it may drop. Do not hold the cable, the shaft or the encoder when carrying the servo motor. Install the equipment on a weight-bearing place in accordance with this Instruction Manual. Do not get on or place heavy objects on the equipment. Install the equipment in the specified direction. Improper installation causes oil leakage, leading to a fire and malfunction. Leave specified clearances between the servo amplifier and inner wall of the control box or other equipment. Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may occur. Do not install or operate a servo amplifier and a servo motor which are damaged or have any part missing. Do not drop or shock the servo amplifier or the servo motor as they are precision equipment. When storing the equipment, please fulfill the following environmental conditions.
Ambient temperature
Ambient humidity
Ambience Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
Altitude Max. 1000m (3280 ft)
Vibration resistance
Note. For the standard servo motor (without reduction gear.)
Item
Operation [ ] 0 to 55 (non-freezing) 0 to 40 (non-freezing)
Storage [ ] 20 to 65 (non-freezing) 15 to 70 (non-freezing)
Operation
Storage 10%RH to 90%RH (non-condensing)
5%RH to 90%RH (non-condensing)
2
5.9 m/s
, 10 to 55Hz
(directions of X, Y, and Z axes)
Servo amplifier Servo motor
Environmental
10%RH to 80%RH (non-condensing)
HF-KN Series
HF-KP Series (Note)
HG-KR series (Note)
X
Y: 49m/s2
Couple the servo motor to a machine securely. Insecure coupling may cause the servo motor to come off. Be sure to measure the motor vibration level with the servo motor mounted to the machine when checking the vibration level. A great vibration may cause the early damage of a bearing, encoder, brake, and reduction gear. The great vibration may also cause the poor connector connection or bolt looseness. For the gain adjustment at the equipment startup, check the torque waveform and the speed waveform by using a measurement device, and then check that no vibration occurs. If the vibration occurs due to high gain, the vibration may cause the early damage of the servo motor. Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo motor during operation. Never hit the servo motor or shaft, especially when coupling the servo motor to a machine as it may damage the encoder. Do not apply load exceeding the permissible load as it may break the shaft. When the equipment has been stored for an extended period of time, contact your local sales office. When handling the servo amplifier, be careful with the edged parts such as the corners of the servo amplifier.
A - 3
CAUTION
The servo amplifier must be installed in the metal cabinet. When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method). Additionally, disinfect and protect wood from insects before packing products.
(2) Wiring
CAUTION
Before unplugging CNP1 connector from the servo amplifier, disconnect the lead of the built-in regenerative resistor from CNP1 connector first. Wire the equipment correctly and securely. Improper wiring may cause unexpected operation. Do not install a power capacitor, a surge killer or a radio noise filter (optional FR-BIF) between the servo motor and the servo amplifier. Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier and the servo motor. Not doing so may cause unexpected operation. Connect the servo amplifier power output (U/V/W) to the servo motor power input (U/V/W) directly. Do not install a magnetic contactor, etc. between the servo amplifier and the servo motor.
Servo amplifier
U
V
W
Servo motor
U
V
W
Servo amplifier
U
M
W
Servo motor
U
V
W
MV
Do not connect AC power supply directly to the servo motor. Otherwise, a fault may occur. Install a surge absorbing diode on the DC relay designed for control output signal in the specified direction. Improper installation of the surge absorbing diode may cause the servo amplifier to malfunction such that the signals are not output, and emergency stop and other safety circuits are inoperable.
Servo amplifier
DOCOM
Control output signal
DICOM
Sink output
interface
24VDC
RA
Servo amplifier
DOCOM
Control output signal
DICOM
Source output
interface
24VDC
RA
Configure a circuit to turn off EM1 when the main circuit power supply is turned off to prevent an unexpected restart of the servo amplifier.
(3) Test run adjustment
CAUTION
Check and adjust the parameter setting before operation. Improper settings may cause some machines to perform unexpected operation. Never adjust or change the parameter values extremely as it will make operation unstable.
A - 4
(4) Usage
CAUTION
Configure an external emergency stop circuit in order to stop the operation immediately and shut off the power. Do not disassemble or repair the equipment. If an alarm is reset while the operation signal is input to the servo amplifier, the equipment starts suddenly. Be sure that the operation signal is off before resetting the alarm to prevent an accident. Do not modify the equipment. Electromagnetic interference from the servo amplifier may affect the surrounding electronic equipment. Minimize the influence of the electromagnetic interference by using a noise filter, etc. Toxic gases may be generated by burning or disassembling the servo amplifier. Do not burn or disassemble the servo amplifier. Use the servo amplifier with the specified servo motor. The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used for ordinary braking. For such reasons as service life and mechanical structure (e.g. where a ball screw and the servo motor are coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety, install a stopper on the machine side.
(5) Corrective actions
CAUTION
Ensure safety by confirming the power off, etc. before performing corrective actions. Otherwise, it may cause an accident. When it is assumed that a hazardous condition may take place at the occur due to a power failure or a product fault, use a servo motor with an electromagnetic brake or provide an external brake mechanism for the purpose of prevention. Configure the electromagnetic brake operation circuit which interlocks with an external emergency stop switch.
Shut off the servo motor when the Servo-on (SON), the Malfunction (ALM), or the Electromagnetic brake interlock (MBR) are turned OFF.
Servo motor
B
Electromagnetic brake
SON RA
When an alarm occurs, remove its cause. Then, ensure safety and reset the alarm before restarting operation. Provide an adequate protection to prevent unexpected restart after an instantaneous power failure.
Circuit must be opened with the emergency stop switch.
24VDC
A - 5
(6) Storing of servo motor
CAUTION
Note the following points when storing the servo motor for an extended period of time (guideline: three or more months). Be sure to store the servo motor indoors in a clean and dry place. If it is stored in a dusty or damp place, make adequate provision, e.g. cover the whole product. If the insulation resistance of the winding decreases, reexamine the storage method. Though the servo motor is rust-proofed before shipment using paint or rust prevention oil, rust may be produced depending on the storage conditions or storage period. If the servo motor is to be stored for longer than six months, apply rust prevention oil again especially to the machined surfaces of the shaft, etc. Before using the servo motor that has been stored for an extended period of time, hand-turn the servo motor output shaft to confirm that nothing is wrong with the servo motor. (For the servo motor with an electromagnetic brake, turn ON the power supply of the electromagnetic brake, first. Then, release the electromagnetic brake before hand-turn.) When the equipment has been stored for an extended period of time, contact your local sales office.
(7) Maintenance, inspection and parts replacement
CAUTION
Make sure that the emergency stop circuit operates properly such that an operation can be stopped immediately and a power is shut off by the emergency stop switch. It is recommended that the servo amplifier be replaced every 10 years when it is used in general environment.
(8) General instruction
To illustrate details, the equipment in the diagrams of this Instruction Manual may have been drawn without covers and safety guards. When the equipment is operated, the covers and safety guards must be installed as specified. Operation must be performed in accordance with this Instruction Manual.
A - 6

About processing of waste

When you discard converter unit, servo amplifier, servo motor, battery (primary battery), and other option articles, please follow the law of each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not been designed or manufactured to be incorporated in a device or system used in purposes related to human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or under water relays, contact Mitsubishi Electric.
These products have been manufactured under strict quality control. However, when installing the product where major accidents or losses could occur if the product fails, install appropriate backup or failsafe functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If the total number of the following operations exceeds 100,000, the converter unit, servo amplifier (drive unit) and/or converter unit may fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Write to the EEP-ROM due to device changes
Write to the EEP-ROM due to point table changes
Write to the EEP-ROM due to program changes
Write to the EEP-ROM due to data records with drive recorder
Precautions for Choosing the Products
Mitsubishi Electric will not be held liable for damage caused by factors found not to be the cause of Mitsubishi Electric; machine damage or lost profits caused by faults in the Mitsubishi Electric products; damage, secondary damage, accident compensation caused by special factors unpredictable by Mitsubishi Electric; damages to products other than Mitsubishi Electric products; and to other duties.

COMPLIANCE WITH EC DIRECTIVES

Refer to appendix 7 for the compliance with EC directives.

CONFORMANCE WITH UL/CSA STANDARD

Refer to appendix 8 for the conformance with UL/CSA standard.
A - 7
<<About the manuals>>
Relevant manuals
Manual name Manual No.
MELSERVO-JN Series Instructions and Cautions for Safe Use of AC Servos
(Enclosed in servo amplifier.)
QUICK INSTALLATION GUIDE L(NA)03052ENG
MELSERVO Servo Motor Instruction Manual Vol.2 SH(NA)030041ENG
MELSERVO Servo Motor Instruction Manual Vol.3 SH(NA)030113ENG
EMC Installation Guidelines IB(NA)67310
IB(NA)0300157
<<About the wires used for wiring>>
Wiring wires mentioned in this instruction manual are selected based on the ambient temperature of 40 (104
).
<<U.S. customary units>>
U.S. customary units are not shown in this manual. Convert the values if necessary according to the following table.
Quantity SI (metric) unit U.S. customary unit
Mass 1 [kg] 2.2046 [lb] Length 1 [mm] 0.03937 [inch] Torque 1 [N•m] 141.6 [oz•inch] Moment of inertia 1 [(× 10-4 kg•m2)] 5.4675 [oz•inch2] Load (thrust load/axial load) 1 [N] 0.2248 [lbf] Temperature N [°C] × 9/5 + 32 N [°F]
A - 8

Introduction

Introduction
The Mitsubishi Electric MELSERVO-JN series general-purpose AC servo is based on the MELSERVO-J3 series, and retains its high performance, with some limitations in functions. For details of functions, performance and specifications of the MELSERVO-JN series, refer to chapters 1 to 13 and appendices of this Instruction Manual. This section describes the how-to (startup, actual operation, and others) for users who use the MELSERVO-JN series AC servo for the first time.
CAUTION
Unpack the product and check the rating plate to see if the servo motor and servo amplifier are as you ordered.
(1) Servo amplifier
Servo amplifier 1
Servo amplifier power supply connectors for CNP1 and CNP 2 1 each
MELSERVO-JN series
Instructions and Cautions for Safe Use of AC Servos
(2) Servo motor
Servo motor 1
Instructions and Cautions for Safe Use of AC Servos (Motor) 1
The lead of the built-in regenerative resistor is connected between P and C terminals on the servo amplifier power supply connectors (CNP1) of the MR-JN­20A(1)/40A. When taking the servo amplifier out from the shipping box, do not hold the lead of the built-in regenerative resistor.
Packaged product Quantity
1
Packaged product Quantity
- 1 -
Introduction

1. Operation and setting

Operation and settings of the servo amplifier are easily performed only on the display section (3-digit, 7­segment LED) and on the operation section (four pushbuttons and one-touch tuning button) located on the front panel of the servo amplifier.
AUTO
Executes the one-touch tuning.
MODE
Changes the display mode and switches the upper/lower.
SET
Determines the display and data, and clears data.
UP/DOWN
Scrolls the display and data.
(1) One-touch tuning function (refer to section 6.1)
Gain and filter adjustment of the servo is easily made by the AUTO button located on the front panel of the servo amplifier.
(2) Status display, diagnosis, and parameter setting (refer to chapter 5)
The servo amplifier status display (cumulative feedback pulses, servo motor speed, and others), diagnosis (servo operation-ready complete status, external I/O signal ON/OFF, test operation), point table settings and parameter settings can be easily performed by the MODE, SET, UP and DOWN buttons located on the front panel of the servo amplifier.
- 2 -

2. Startup

When switching the power on for the first time, follow the startup procedure below.
Visual wiring check
Refer to (1) in this section.
Surrounding environment
check
Check the surrounding environment (cable routing and impurity such as wire offcuts or metallic dust) of the servo amplifier and the servo motor.
Power-on of the control circuit
power supply
Refer to (2) (a) in this section.
I/O signal wiring check during
power-on
Refer to (3) in this section.
Parameter setting
Refer to (4) in this section.
Power-on of the main circuit
power supply
Refer to (2) (a) in this section.
Operation confirmation before
actual operation
One-touch tuning
Refer to (5) in this section.
Refer to (6) in this section.
Actual operation
Stop
Refer to (7) in this section.
When switching the power off, follow (2) (b) in this section.
Introduction
- 3 -
Introduction
(1) Visual wiring check
Before switching on the main circuit and control circuit power supplies, check the following items.
Power supply system wiring
The power supplied to the power input terminals (L1, L2, +24V, 0V) of the servo amplifier should satisfy
the defined specifications. (Refer to section 1.3.)
Connection of servo amplifier and servo motor
The servo motor power supply terminals (U, V, W) of the servo amplifier should match in phase with the
power input terminals (U, V, W) of the servo motor.
Servo amplifier Servo motor
U
V
W
U
V
W
M
The power supplied to the servo amplifier should not be connected to the servo motor power supply
terminals (U, V, W). The connected servo amplifier and servo motor will be damaged.
Servo amplifier
U
1
L
V
L
2
W
Servo motor
U
V
W
M
The earth terminal of the servo motor should be connected to the PE terminal of the servo amplifier.
Servo amplifier Servo motor
M
When regenerative option is used
The built-in regenerative resistor and its wirings should be removed from the servo amplifier.
The regenerative option should be connected to P and C terminals.
A twisted cable should be used. (Refer to section 11.2 (4).)
I/O signal wiring
The power supplied to CN1 connector (DICOM and DOCOM) of the servo amplifier should satisfy the
defined specifications. (Refer to section 1.3.)
SD and DOCOM of CN1 connector should not be shorted.
Servo amplifier
CN1
DOCOM
SD
- 4 -
(2) Power on and off procedures
(a) Power-on
Switch the power on in the following procedure. Always follow this procedure at power-on.
1) Turn off the servo-on (SON).
2) Make sure that command and start signal from the controller are not input.
3) Switch on the control circuit power supply. At power-on, "888" appears instantaneously, but it is not an error. In the position control mode, data is displayed in 2[s] or later after displaying "CL" (cumulative feedback pulses in pulse unit) (initial value), or by pressing the "MODE", "UP" or "DOWN" button.
Displayed contents differ depending on each control mode. Refer to section 5.3 for details.
4) Switch on the main circuit power supply.
(b) Power-off
1) Make sure that command and start signal from the controller are not input.
2) Turn off the servo-on (SON).
3) Switch off the main circuit power supply.
4) Switch off the control circuit power supply.
(3) I/O signal wiring check during the energization
Input signal wiring confirmation
Introduction
On/off status of the input signals of CN1 connector can be checked using the external I/O signal display.
By using this function, input signal wiring can be checked. (Refer to section 5.8.)
Output signal wiring confirmation
Output signals of CN1 connector can be turned on/off forcibly using the DO output. By using this function,
output signal wiring can be checked. (Refer to section 5.9.)
(4) Parameter setting
POINT
Some parameters are made valid when power is switched off, then on after setting. Refer to chapter 4 for details. For the positioning mode, refer to section 13.7.
Set the parameters as necessary, such as selecting the control mode and the regenerative option. In the position control mode, the servo amplifier can be used just by changing the basic setting parameters (parameter No. PA As necessary, set the gain/filter parameters (parameter No. PB ), the extension setting parameters (parameter No. PC For the internal speed control mode and the internal torque control mode, refer to chapter 4.
) mainly.
) and the I/O setting parameters (parameter No. PD ).
- 5 -
Introduction
The following shows the main parameters, which must be changed, among parameter No. PA
.
PA01 Selection of control mode (refer to section 4.1.3)
Select the control mode of the servo amplifier, and whether to enable or not the one-touch tuning function.
Parameter No. PA01
0
Selection of control mode 0: Position control mode 1: Position control mode and internal speed control mode 2: Internal speed control mode 3: Internal speed control mode and in ternal 4: Internal torque control mode 5: Internal torque control mode and position control mode 6: Positioning mode (point table method) 7: Positioning mode (program method)
One-touch tuning function selection 0: Valid 1: Invalid When this parameter is set to "1", the one-touch tuning is ignored.
torque control mode
PA02 Selection of regenerative option (refer to section 4.1.4)
Set this parameter when using the regenerative option.
Parameter No. PA02
0
Selection of regenerative option 00: Regenerative option is not used. For servo amplifier of 100W, regenerative resistor is not used. For servo amplifier of 200 to 400W, built-in regenerative resistor is
used. 02: MR-RB032 03: MR-RB12
PA05 Number of command input pulses per servo motor revolution (refer to section 4.1.6)
Set the number of command input pulses necessary to rotate the servo motor one turn.
When "100 (10000[pulse/rev])" (initial value) is set to parameter No. PA05, the servo motor rotates one turn by inputting 1000 pulses of the command pulse to the servo amplifier. When "0" is set to parameter No. PA05, the servo motor rotates one turn by inputting the command pulse of servo motor resolution to the servo amplifier.
Parameter No. PA05
setting
100 to 500
Command
pulses
0 Servo motor resolution [pulse/rev]
Number of command input pulses necessary to rotate the servo motor one
Parameter No. PA05
FBP conversion
(Note 1)
Value converted to the number of command input pulses per revolution (FBP)
Description
100 pulse/rev]
turn [
Electronic gear
CMX CDV
(Note 2)
Deviation
counter
Servo motor
M
Encoder
Note 1. This process converts the number of pulses required to rotate the servo motor one turn to the value set in parameter No. PA05.
2. Electric gear numerator and denominator can be set by parameters No. PA06 and PA07. (Refer to section 4.1.7.)
- 6 -
Introduction
PA13 Selection of command input pulse form (refer to section 4.1.11)
Select the input form of the pulse train input signal. Command pulses may be input in any of three different forms, for which positive or negative logic can be chosen.
Arrow
or in the table indicates the timing of importing a pulse train. A- and B-phase pulse trains
are imported after being multiplied by 4.
Parameter No. PA13
Selection of command input pulse form
Setting
00
01
02
10
11
12
Pulse train form
Forward rotation pulse train Reverse rotation pulse train
Signed pulse train
Positive logic
A-phase pulse train B-phase pulse train
Forward rotation pulse train Reverse rotation pulse train
Signed pulse train
Negative logic
A-phase pulse train B-phase pulse train
Forward rotation command
PP
NP
PP
NP
PP
NP
PP
NP
PP
NP
PP
NP
H
L
Reverse rotation command
L
H
Pulse train input filter selection
POINT
Setting
0 1Mpps or less 1500kpps or less 2200kpps or less
Command pulse frequency
The noise tolerance can be enhanced by setting parameter No. PA13 to "1 " when the command pulse frequency is 500kpps or less or "2
" when
200kpps or less.
- 7 -
Introduction
PA14 Selection of servo motor rotation direction (refer to section 4.1.12)
Select servo motor rotation direction relative to the input pulse train.
Parameter No. PA14
setting
0 CCW CW
1 CW CCW
When forward rotation pulse is input When reverse rotation pulse is input
Servo motor rotation direction
Forward rotation (CCW)
Reverse rotation (CW)
(5) Operation confirmation before actual operation
Before starting actual operation, perform JOG operation to make sure that the machine operates properly. MR-JN can perform the JOG operation in the test operation mode on the operation section (four pushbuttons). (Refer to section 5.10.)
JOG operation in the test operation
mode
(Servo motor alone)
(a) Confirm that the servo amplifier and servo motor operate properly.
With the servo motor disconnected from the machine, use the test operation mode (JOG operation) at the slowest speed and check whether the servo motor rotates correctly.
Operation by commands from the
controller
(Servo motor and machine are
connected)
(b) Confirm that the servo motor rotates correctly at the slowest speed
under the commands from the controller. Make sure that the servo motor rotates in the following procedure.
1) Switch on the forced stop (EM1) and servo-on (SON). When the servo amplifier is in a servo-on status, the ready (RD) switches on.
2) Switch on the forward rotation stroke end (LSP) and the reverse rotation stroke end (LSN).
3) In the position control mode, when command pulses are input from the controller, the servo motor starts rotating. Give a low speed command at first and check the operation direction, etc. of the servo motor. If the servo motor does not rotate in the intended direction, check the input signal.
4) After checking that the machine operates properly, perform the automatic operation by the program of the controller to check for any problem with the operation.
- 8 -
Introduction
(6) One-touch tuning
Just by pressing the "AUTO" button on the front panel of the servo amplifier during operation, the gain/filter is easily adjusted. (Refer to section 6.1.)
Startup of system
Operation
Rotate the servo motor by a command device, etc. (The one-touch tuning cannot be performed if the servo motor is not operating.)
Shift to the one-touch tuning
mode
Press the "AUTO" button for 3[s] or longer while the servo motor is rotating. The display changes to "
", and the
mode shifts to the one-touch tuning mode.
Selection of the response
mode
Press the "UP" or the "DOWN" button while "
" is displayed to select the response mode. (Refer to (1) in section 6.1.2.)
Execution of the one-touch
tuning
Start the one-touch tuning by pressing the "AUTO" button. The progress of the one-touch tuning is displayed in percentage.
One-touch tuning complete
0% 100%
When the one-touch tuning is completed properly, "
" is displayed and the gain/filter is automatically
adjusted.
POINT
For the fine adjustment after the one-touch tuning, refer to section 6.4.
- 9 -
(7) Stop
In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo motor. Refer to section 3.11 for the servo motor with an electromagnetic brake.
(a) Servo-on (SON) OFF
The base circuit is shut off and the servo motor coasts.
(b) Alarm occurrence
When an alarm occurs, the base circuit is shut off and the dynamic brake activates to stop the servo motor immediately.
(c) Forced stop (EM1) OFF
The base circuit is shut off and the dynamic brake activates to stop the servo motor immediately. Servo forced stop warning alarm (E6.1) occurs.
(d) Forward rotation stroke end (LSP) or reverse rotation stroke end (LSN) OFF
Position control mode: Droop pluses are cleared, and the servo motor shaft is locked. The servo motor can rotate in an opposite direction. Internal speed control mode: The servo motor stops immediately, and the shaft is locked. The servo motor can rotate in an opposite direction.
(e) Simultaneous ON or simultaneous OFF of forward rotation start (ST1) and reverse rotation start (ST2)
In internal speed control mode: The servo motor decelerates to a stop. In positioning mode: The servo motor decelerates to a stop after JOG operation.
(f) Simultaneous ON or simultaneous OFF of forward rotation selection (RS1) and reverse rotation selection
(RS2) (only in the internal torque control) The servo motor coasts.
POINT
The forward rotation stroke end (LSP) and reverse rotation stroke end (LSN) operate as follows. Assigned to the external input signals: depends on the value set in parameter
Not assigned to the external input signals: automatically turns on regardless of
In the internal torque control mode, the forward rotation stroke end (LSP) and reverse rotation stroke end (LSN) become invalid. (Refer to section 3.5.)
No. PD01.
the value set in parameter No. PD01.
Introduction
- 10 -

3. Troubleshooting at startup

Introduction
Never adjust or change the parameter values extremely as it will make operation
CAUTION
unstable.
POINT
You can refer to reasons for servo motor rotation failure, etc. using MR Configurator.
The following faults may occur at startup. If any of such faults occurs, take the corresponding action.
(1) Troubleshooting
No. Step of occurrence Fault Investigation Possible cause Reference
1 Power on
Alarm occurs. Remove cause. Section
Digital output ALM
2 Switch on servo-on
(SON).
Servo motor shaft is
3 Input command
pulse.
(Test operation)
(In the position
Check if the ready (RD) is ON.
control mode)
Check if the electromagnetic
Check the ON/OFF status of the
The 3-digit, 7-segment
LED is not lit.
The 3-digit, 7-segment
LED blinks.
occurs. The 3-digit,
7-segment LED does not
display the alarm.
Alarm occurs. Remove cause. Section
free.
Servo motor does not
rotate.
Not improved even if CN1, CN2
and CN3 connectors are
disconnected.
Improved when CN1 connector is
disconnected.
Improved when CN2 connector is
disconnected.
Improved when CN3 connector is
disconnected.
Check the ON/OFF status of the
output signal on the external I/O
signal display (refer to section
5.8).
Check the followings.
1. Check the display to see if the
servo amplifier is ready to
operate.
2. Check the external I/O signal
display (refer to section 5.8) to
see if the servo-on (SON) is ON.
Check the cumulative command
pulses on the status display or on
MR Configurator.
Check the set value of parameter
No.PA13 (command input pulse
form).
brake interlock (MBR) is ON.
output signal on the external I/O
signal display (refer to section
5.8).
1. Power supply voltage fault
2. Servo amplifier is faulty.
Power supply of CN1 cabling is
shorted.
1. Power supply of encoder
cabling is shorted.
2. Encoder is faulty.
Power supply of CN3 cabling is
shorted.
Wiring mistake.
The polarity of the digital output
circuit diode is not correct.
1. Servo-on (SON) is not input.
(Wiring mistake)
2. The interface power supply
(24VDC) is not supplied.
1. Wiring mistake.
(a) For open collector pulse train
input, 24VDC power is not
supplied to OPC.
(b) LSP and LSN are not on.
(c) Wiring mistake.
The polarity of the digital output
circuit diode is not correct.
2. No pulses are input.
3. Electromagnetic brake operates.
Wiring mistake.
The polarity of the digital output
circuit diode is not correct.
8.2
Section
3.8.2
8.2
Section
5.8
Section
3.8.2
Section
3.11
Section
4.1.11
Section
5.3
Section
3.8.2
- 11 -
Introduction
№ Step of occurrence Fault Investigation Possible cause Reference
3 Input command
pulse.
(Test operation)
(In the position
Check the set value of parameter
control mode)
4 Switch on forward
rotation start (ST1)
or reverse rotation
start (ST2).
(In the internal
speed control
mode)
5 Switch on forward
rotation selection
(RS1) or reverse
rotation selection
Check the ON/OFF status of the
(RS2).
(In the internal
torque control
mode)
Check the internal speed limits 0
Check the forward torque limit
6 Switch on forward
rotation start (ST1)
or reverse rotation
start (ST2).
(In the positioning
mode)
Check the forward torque limit
7 Gain adjustment
(In the position
control mode)
(In the internal
speed control
mode)
(In the positioning
mode)
8 Cyclic operation
(In the position
control mode)
Servo motor rotates in
reverse direction.
Servo motor does not
rotate.
Servo motor does not
rotate.
Servo motor does not
rotate.
Check the values of position data
Rotation ripples (speed
fluctuations) are large at
low speed.
Large load inertia
moment causes the
servo motor shaft to
oscillate side to side.
Position shift occurs. Confirm the cumulative command
Check the cumulative command
pulses on the status display or on
MR Configurator.
No.PA14 (rotation direction
selection).
Check the ON/OFF status of the
input signal on the external I/O
signal display (refer to section
5.8).
Check the internal speed
commands 0 to 7 (parameters No.
PC05 to PC08 and PC31 to
PC34).
Check the forward torque limit
(parameter No. PA11) or reverse
torque limit (parameter No. PA12).
Check the set value of parameter
No.PC12 (internal torque
command).
input signal on the external I/O
signal display (refer to section
5.8).
to 7 (parameters No. PC05 to
PC08 and PC31 to PC34).
(parameter No. PA11) or reverse
torque limit (parameter No. PA12).
Check the ON/OFF status of the
input signal on the external I/O
signal display (refer to section
5.8).
and servo motor speed set in the
point table or program.
(parameter No. PA11) or reverse
torque limit (parameter No. PA12).
Make gain adjustment in the
following procedure.
1. Increase the auto tuning
response level.
2. Repeat acceleration and
deceleration several times to
complete auto tuning.
If the servo motor may be run with
safety, repeat acceleration and
deceleration several times to
complete auto tuning.
pulses, the cumulative feedback
pulses and the actual servo motor
position.
1. Mistake in wiring to controller.
2. Mistake in setting of parameter
No. PA14.
LSP, LSN, ST1 or ST2 is off. Section
Set value is 0. Section
Torque limit level is too low as
compared to the load torque.
Internal torque command is too
low as compared to the load
torque.
RS1 or RS2 is off. Section
Set value is 0. Section
Set value is 0. Section
LSP, LSN, ST1 or ST2 is off. Section
Set value is 0. Chapter
Torque limit level is too low as
compared to the load torque.
Gain adjustment fault Chapter 6
Gain adjustment fault Chapter 6
Pulse counting error, etc. due to
noise.
Section
4.1.12
Section
5.3
5.8
4.3.2
Section
4.1.10
Section
4.3.2
5.8
4.3.2
4.1.10
5.8
13
Section
4.1.10
(2) in this
section
- 12 -
Introduction
(2) How to find the cause of position shift
Servo amplifierController
(a)Output pulse
counter
Q
Servo-on (SON), Stroke end (LSP/LSN) input
Cause A
Cause C
Electronic gear (parameters No. PA06, PA07)
P FBP
FBP conversion
(b)Cumulative command pulses
(c) Cumulative feedback pulses
CMX CDV
C
Servo motor
M
Encoder
Machine
L
(d) Machine stop position M
Cause B
When a position shift occurs, check (a) output pulse counter Q, (b) cumulative command pulses P, (c) cumulative feedback pulses C, and (d) machine stop position M in the above diagram.
Cause A, Cause B and Cause C indicate position shift causes. For example, Cause A indicates that noise entered the wiring between the controller and servo amplifier, causing the command input pulse to be miss­counted.
In a normal status without position shift, there are the following relationships.
1) Q
P (output pulse counter cumulative command pulses)
2) When using the electronic gear CMX (parameter No. PA06)
P
CDV (parameter No. PA07)
Servo motor encoder resolution
FBP (parameter No. PA05) (Note)
C (cumulative command pulses electronic gear cumulative feedback pulses)
Note. When "0" is set to the FBP (parameter No. PA05), the FBP becomes the servo motor encoder resolution.
3) C  Δ
M (cumulative feedback pulses travel per pulse machine position)
Check for a position shift in the following sequence.
1) When Q ≠ P
Noise entered in the pulse train signal wiring between the controller and servo amplifier, causing command input pulses to be miss-counted. (Cause A) Make the following check or take the following measures.
Check the shielding. Run wiring away from the power circuit. Install a data line filter. (Refer to section 11.9 (2) (a).)
POINT
The noise tolerance can be enhanced by setting parameter No. PA13 to "1 " when the command pulse frequency is 500kpps or less or "2 200kpps or less.
" when
- 13 -
2) When P
CMX CDV
Note. When "0" is set to the FBP (parameter No. PA05), the FBP becomes the servo motor encoder resolution.
During the operation, the servo-on (SON), the forward/reverse rotation stroke end (LSP/LSN) was turned off, or the clear (CR) or the reset (RES) was turned on. (Cause C) If a malfunction may occur due to much noise, increase the input filter setting (parameter No. PD19).
3) When C Δ
Mechanical slip occurred between the servo motor and machine. (Cause B)

4. Tough drive function

Servo motor encoder resolution
FBP (parameter No. PA05) (Note)
≠ M
Introduction
≠ C
Since the operation status of devices may be changed by the tough drive
CAUTION
operation, check for any problems before making this function valid.
POINT
For details of the tough drive function, refer to section 7.1.
The tough drive function continues the operation not to stop a machine in such situations when normally an alarm is activated.
Three types of tough drive function can be selected in parameter No. PA04.
Parameter No. PA04
Overload tough drive function selection Set the tough drive function for overload.
Setting
0 1
Vibration tough drive function selection Set the function for vibration suppression.
Setting
0 1
Overload tough drive function
Invalid
Valid
Vibration tough drive function
Invalid
Valid
Instantaneous power failure tough drive function selection Set tough drive function for instantaneous power failure of the main circuit power supply.
Setting
Instantaneous power failure tough drive function 0 1
Invalid
Valid
- 14 -
(1) Overload tough drive function
This function reduces the effective load ratio before an overload alarm occurs to avoid the alarm.
(2) Vibration tough drive function
This function suppresses the machine resonance caused by aging distortion or individual difference of the machine.
(3) Instantaneous power failure tough drive function
This function avoids the instantaneous power failure during operation.
Introduction
- 15 -

CONTENTS

1. FUNCTIONS AND CONFIGURATION 1 - 1 to 1 -12
1.1 Introduction ............................................................................................................................................... 1 - 1
1.2 Function block diagram ............................................................................................................................ 1 - 3
1.3 Servo amplifier standard specifications ................................................................................................... 1 - 6
1.4 Function list .............................................................................................................................................. 1 - 8
1.5 Model code definition .............................................................................................................................. 1 -10
1.6 Combination with servo motor ................................................................................................................ 1 -10
1.7 Parts identification ................................................................................................................................... 1 -11
1.8 Configuration including auxiliary equipment ........................................................................................... 1 -12
2. INSTALLATION 2 - 1 to 2 - 6
2.1 Installation direction and clearances ....................................................................................................... 2 - 2
2.2 Keep out foreign materials ....................................................................................................................... 2 - 3
2.3 Cable stress .............................................................................................................................................. 2 - 4
2.4 Inspection items ....................................................................................................................................... 2 - 4
2.5 Parts having service lives......................................................................................................................... 2 - 5
3. SIGNALS AND WIRING 3 - 1 to 3 -48
3.1 Input power supply circuit ........................................................................................................................ 3 - 2
3.2 I/O signal connection example ................................................................................................................. 3 - 4
3.2.1 Position control mode ........................................................................................................................ 3 - 4
3.2.2 Internal speed control mode ............................................................................................................. 3 - 6
3.2.3 Internal torque control mode ............................................................................................................. 3 - 7
3.3 Explanation of power supply system ....................................................................................................... 3 - 8
3.3.1 Signal explanations ........................................................................................................................... 3 - 8
3.3.2 Power-on sequence .......................................................................................................................... 3 - 8
3.3.3 CNP1 and CNP2 wiring method ...................................................................................................... 3 -10
3.4 Connectors and signal arrangements .................................................................................................... 3 -13
3.5 Signal explanations ................................................................................................................................. 3 -16
3.6 Detailed description of the signals .......................................................................................................... 3 -22
3.6.1 Position control mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -22
3.6.2 Internal speed control mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -25
3.6.3 Internal torque control mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -28
3.6.4 Position/speed control change mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -31
3.6.5 Internal speed/internal torque control change mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -32
3.6.6 Internal torque/position control change mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -33
3.7 Alarm occurrence timing chart ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -34
3.8 Interfaces ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -35
3.8.1 Internal connection diagram ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -35
3.8.2 Detailed description of interfaces ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3
-36
3.8.3 Source I/O interfaces ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -39
3.9 Treatment of cable shield external conductor ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -40
3.10 Connection of servo amplifier and servo motor ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -41
3.10.1 Connection instructions ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -41
3.10.2 Power supply cable wiring diagrams ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -42
- 16 -
3.11 Servo motor with an electromagnetic brake ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -43
3.11.1 Safety precautions ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -43
3.11.2 Setting ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -43
3.11.3 Timing chartsꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -44
3.11.4 Wiring diagrams (HF-KN series • HF-KP
G1/G5/G7 • HG-KR G1/G5/G7 servo motor) ꞏꞏꞏꞏꞏ 3 -46
3.12 Grounding ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 3 -48
4. PARAMETERS 4 - 1 to 4 -54
4.1 Basic setting parameters (No. PA ) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 2
4.1.1 Parameter list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 2
4.1.2 Parameter write inhibit ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 3
4.1.3 Selection of control mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 4
4.1.4 Selection of regenerative option ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 4
4.1.5 Selection of the tough drive function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 5
4.1.6 Number of command input pulses per servo motor revolution ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 6
4.1.7 Electronic gear ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 - 7
4.1.8 Auto tuning ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -11
4.1.9 In-position range ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -12
4.1.10 Torque limit ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -13
4.1.11 Selection of command input pulse form ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -14
4.1.12 Selection of servo motor rotation direction ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -15
4.1.13 Encoder output pulses ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -16
4.2 Gain/filter parameters (No. PB
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -19
4.2.1 Parameter list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -19
4.2.2 Detail list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -21
4.2.3 Position smoothing ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -29
4.3 Extension setting parameters (No. PC
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -30
4.3.1 Parameter list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -30
4.3.2 List of details ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -32
4.3.3 Alarm history clear ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -39
4.3.4 Drive recorder function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -40
4.4 I/O setting parameters (No. PD
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -44
4.4.1 Parameter list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -44
4.4.2 List of details ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -45
4.4.3 Using forward/reverse rotation stroke end to change the stopping pattern ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 4 -54
5. DISPLAY AND OPERATION SECTIONS 5 - 1 to 5 -30
5.1 Overview ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 1
5.2 Display sequence ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 2
5.3 Status display ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 3
5.3.1 Display transition ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 4
5.3.2 Display examples ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 5
5.3.3 Status display list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 7
5.4 Diagnostic mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 - 9
5.5 Alarm mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -11
5.6 Point table mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -13
5.6.1 Point table transition ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -13
5.6.2 Point table mode setting screen sequence ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -14
- 17 -
5.6.3 Operation example ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -15
5.7 Parameter mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -17
5.7.1 Parameter mode transition ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -17
5.7.2 Operation example ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -18
5.8 External I/O signal display ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -20
5.9 Output signal (DO) forced output ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -23
5.10 Test operation mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -24
5.10.1 Mode change .................................................................................................................................. 5 -24
5.10.2 JOG operation ................................................................................................................................ 5 -25
5.10.3 Positioning operation ...................................................................................................................... 5 -26
5.10.4 Motor-less operation....................................................................................................................... 5 -28
5.10.5 Forced tough drive operation ......................................................................................................... 5 -29
5.11 One-touch tuning ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 5 -29
6. GENERAL GAIN ADJUSTMENT 6 - 1 to 6 -18
6.1 One-touch tuning ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 - 1
6.1.1 One-touch tuning procedure ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 - 2
6.1.2 Display transition and operation procedure of the one-touch tuning ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 - 3
6.1.3 Precautions for one-touch tuning ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 - 7
6.2 Gain adjustment methods ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 - 8
6.3 Auto tuning mode 1 ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -10
6.3.1 Overview ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -10
6.3.2 Auto tuning mode 1 basis ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -11
6.3.3 Adjustment procedure by auto tuning ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -12
6.3.4 Response level setting in auto tuning mode 1 ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -13
6.4 2-gain adjustment mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -14
6.5 Manual mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 6 -15
7. SPECIAL ADJUSTMENT FUNCTIONS 7 - 1 to 7 -18
7.1 Tough drive function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 1
7.1.1 Overload tough drive function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 1
7.1.2 Vibration tough drive function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 2
7.1.3 Instantaneous power failure tough drive function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 4
7.2 Machine resonance suppression function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 6
7.2.1 Function block diagram ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 6
7.2.2 Adaptive filter II ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 6
7.2.3 Machine resonance suppression filter ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 8
7.2.4 Advanced vibration suppression control ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 - 9
7.2.5 Low-pass filter ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 -13
7.3 Gain changing function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 -13
7.3.1 Applications ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 -13
7.3.2 Function block diagram ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 -14
7.3.3 Parameters ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 -15
7.3.4 Gain changing procedure ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 7 -17
8. TROUBLESHOOTING 8 - 1 to 8 -30
8.1 Alarms and warning list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 8 - 1
- 18 -
8.2 Remedies for alarms ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 8 - 3
8.3 Remedies for warnings ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 8 -24
9. DIMENSIONS 9 - 1 to 9 - 4
9.1 Servo amplifier ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 9 - 1
9.2 Connector ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 9 - 3
10. CHARACTERISTICS 10- 1 to 10- 6
10.1 Overload protection characteristics ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 1
10.2 Power supply capacity and generated loss ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 2
10.3 Dynamic brake characteristics ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 4
10.3.1 Dynamic brake operation ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 4
10.3.2 The dynamic brake at the load inertia moment ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 5
10.4 Cable flexing life ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 6
10.5 Inrush currents at power-on of main circuit and control circuit ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 10- 6
11. OPTIONS AND PERIPHERAL EQUIPMENT 11- 1 to 11-46
11.1 Cable/connector sets ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11- 1
11.1.1 Combinations of cable/connector sets ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11- 2
11.1.2 Encoder cable/connector sets ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11- 7
11.1.3 Motor power supply cables ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-17
11.1.4 Motor brake cables ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-19
11.2 Regenerative options ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-21
11.3 Junction terminal block MR-TB26A ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-25
11.4 MR Configurator/MR Configurator2 ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-27
11.4.1 About engineering software ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-27
11.4.2 Precautions for using USB communication function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-28
11.5 Selection example of wires ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-29
11.6 Molded-case circuit breakers, fuses, magnetic contactors ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-32
11.7 Power factor improving AC reactor FR-HAL ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-33
11.8 Relays (recommended) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-33
11.9 Noise reduction techniques ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-34
11.10 Earth-leakage current breaker ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-40
11.11 Circuit protector ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-42
11.12 EMC filter (recommended) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-42
11.13 Surge protector (recommended) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-43
11.14 MR-HDP01 manual pulse generatorꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 11-45
12. SERVO MOTOR 12- 1 to 12-48
12.1 Introduction ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 1
12.1.1 Rating plate ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 1
12.1.2 Parts identification ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 1
12.1.3 Electromagnetic brake ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 2
12.1.4 Servo motor shaft shapes ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 4
12.2 Installation ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 5
12.2.1 Installation direction ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 6
- 19 -
12.2.2 Precautions for load remove ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 7
12.2.3 Permissible load for the shaft ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 8
12.2.4 Protection from oil and water ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 8
12.2.5 Cable ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 9
12.2.6 Inspection ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12- 9
12.2.7 Life ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-10
12.2.8 Machine accuracies ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-10
12.3 Connectors used for servo motor wiring ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-11
12.3.1 Selection of connectors ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-11
12.3.2 Wiring connectors (Connector configurations A B C) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-12
12.4 Connector dimensions ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-13
12.5 HF-KN series servo motor ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-15
12.5.1 Model definition ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-15
12.5.2 Standard specifications ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-16
12.5.3 Electromagnetic brake characteristicsꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-18
12.5.4 Servo motors with special shafts ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-19
12.5.5 Connector installation ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-20
12.5.6 Outline drawings ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-21
12.5.7 USA/Canada compliance ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-26
12.6 HF-KP series servo motor (Order accepted until May 31, 2019)ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-27
12.6.1 Model definition ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-27
12.6.2 Specifications ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-28
12.6.3 Electromagnetic brake characteristicsꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-30
12.6.4 Servo motor with a reduction gear ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-31
12.6.5 Connector installation ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-36
12.7 HG-KR series servo motor ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-38
12.7.1 Model definition ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ
ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-38
12.7.2 Standard specifications ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-39
12.7.3 Electromagnetic brake ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-42
12.7.4 Geared servo motors ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-43
12.7.5 Mounting connectors ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 12-47
13. POSITIONING MODE 13- 1 to 13-94
13.1 Selection method of each operation mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13- 1
13.2 Signals ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13- 2
13.2.1 I/O signal connection example ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13- 2
13.2.2 Connectors and signal arrangements ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13- 3
13.2.3 Signal explanations ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13- 4
13.2.4 Detailed description of the signals ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-11
13.3 Automatic operation mode for point table method ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-15
13.3.1 What is automatic operation mode? ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-15
13.3.2 Automatic operation using point table ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-17
13.4 Automatic operation mode for program method ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-28
13.4.1 What is automatic operation mode for program method? ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-28
13.4.2 Programming language ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-29
13.4.3 Basic setting of signals and parameters ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-44
13.4.4 Program operation timing chart ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-45
13.5 Manual operation mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-46
- 20 -
13.5.1 JOG operation ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-46
13.5.2 Manual pulse generator operationꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-47
13.6 Home position return mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-49
13.6.1 Outline of home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-49
13.6.2 Selection of home position return mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-50
13.6.3 Dog type home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-51
13.6.4 Count type home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-54
13.6.5 Data set type home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-56
13.6.6 Stopper type home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-57
13.6.7 Home position ignorance (Servo-on position as home position) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-59
13.6.8 Dog type rear end reference home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-60
13.6.9 Count type front end reference home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-62
13.6.10 Dog cradle type home position return ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-64
13.6.11 Home position return automatic return function ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-66
13.7 Parameters ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-67
13.7.1 Basic setting parameters (No. PA
13.7.2 Gain/filter parameters (No. PB
13.7.3 Extension setting parameters (No. PC
13.7.4 I/O setting parameters (No. PD
13.7.5 Positioning setting parameters (No. PE
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-68
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-73
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-75
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-78
) ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-80
13.8 Point table setting method ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-86
13.9 Program setting method ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-88
13.10 Single-step feed usage in the test operation mode ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ 13-91
APPENDIX App.- 1 to App.-19
App. 1 Parameter list ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ App.- 1 App. 2 Servo motor ID codes ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ App.- 7 App. 3 Signal layout recording paper ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ App.- 7 App. 4 Status display block diagram ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ App.- 8 App. 5 Compliance with global standards ꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏꞏ App.-10
- 21 -
MEMO
- 22 -

1. FUNCTIONS AND CONFIGURATION

1. FUNCTIONS AND CONFIGURATION

1.1 Introduction

The Mitsubishi Electric MELSERVO-JN series general-purpose AC servo is based on the MELSERVO-J3 series, and retains its high performance, with some limitations in functions. It has position control, internal speed control, internal torque control and positioning modes. Further, it can perform operation with the control modes changed, e.g. position/internal speed control, internal speed/internal torque control and internal torque/position control. Hence, it is applicable to a wide range of fields, not only precision positioning and smooth speed control of machine tools and general industrial machines but also line control and tension control. As this new series has the USB serial communication function, a MR Configurator installed personal computer or the like can be used to perform parameter setting, test operation, status display monitoring, gain adjustment, etc. With one-touch tuning and real-time auto tuning, you can easily and automatically adjust the servo gains according to the machine. The servo amplifier has the tough drive function that continues the operation not to stop a machine in such situation when normally an alarm is activated. The MELSERVO-JN series servo motor is equipped with an incremental encoder which has the resolution of 131072 pulses/rev to ensure the positioning with a high accuracy.
(1) Position control mode
Up to 1Mpps high-speed pulse train is used to control the speed and the direction of a servo motor and execute precision positioning of 131072 pulses/rev resolution. The position smoothing function provides a choice of two different modes appropriate for a machine, so a smoother start/stop can be made in response to a sudden position command. A torque limit is imposed on the servo amplifier by the clamp circuit to protect the power transistor in the main circuit from overcurrent due to sudden acceleration/deceleration or overload. This torque limit value can be changed to any value with the parameter.
(2) Internal speed control mode
A parameter-driven internal speed command (max. 8 speeds) is used to control the speed and the direction of a servo motor precisely and smoothly. There are also the acceleration/deceleration time constant setting in response to the speed command and the servo lock function at a stop time.
(3) Internal torque control mode
An internal torque command (0.0% to 100.0%) is used to control the torque output by the servo motor. To prevent unexpected operation under no load, the speed limit function (internal setting) is also available for application to tension control, etc.
1 - 1
1. FUNCTIONS AND CONFIGURATION
(4) Positioning mode
The positioning mode has point table method and program method.
(a) Point table method
The positioning operation can be executed by setting the position data (the target position), the servo motor speed, the acceleration/deceleration time constant, etc. in the point table as if setting them in parameters. This is the most appropriate to configure a simple positioning system or to simplify a system. 7 point tables can be used.
(b) Program method
The positioning operation is performed by creating the positioning data (the target position), the servo motor speed, the acceleration/deceleration time constant, etc. as a program and by executing the program. This is the most appropriate to configure a simple positioning system or to simplify a system. Up to 8 programs can be created. The program capacity is 120 steps as a total of all programs.
1 - 2
1. FUNCTIONS AND CONFIGURATION

1.2 Function block diagram

The function block diagram of this servo motor is shown below.
(1) Position control mode, internal speed control mode, internal torque control mode
Regenerative option
(Note 2) Main
circuit power supply
(Note 2) Control circuit power supply
MCCB
Circuit
protector
MC
Servo amplifier
Diode stack
Fuse
L1
L2
24V
0V
Pulse
input
Relay
Control
circuit
power
supply
Model
position
control
P
(Note 1)
CHARGE
lamp
Base
amplifier
Model speed
control
Regene­rative TR
Voltage
detection
Overcurrent
protection
Virtual
motor
Current
detector
Virtual
encoder
Dynamic
brake
Current
detection
U
V
W
RA
24VDC
CN2
Servo motorC
U
V
W
B1
B
B2
Encoder
M
Electro­magnetic brake
Model position
Actual
position
control
I/F
CN1
D I/O control
Servo-on Command input pulses Start Failure, etc.
Note 1. A built-in regenerative resistor is not provided for the MR-JN-10A(1).
2. For the specification of power supply, refer to section 1.3.
Model speed
Actual
speed
control
Personal
computer
USB
CN3
USB
Model torque
Current
control
1 - 3
1. FUNCTIONS AND CONFIGURATION
(2) Positioning mode (Point table method)
Regenerative option
(Note 2) Main
circuit power supply
(Note 2) Control
circuit power supply
MCCB
Circuit
protector
Servo amplifier
MC
Diode stack
Fuse
L1
L2
24V
0V
Current
control
Speed control
Model adaptive control
Position
control
Position
command
creation
Relay
Control
circuit
power
supply
Position
No.
data
1
1000
2000
2
4000
3
-500
4
1000
5
2000
6
7 1000
P
(Note 1)
CHARGE
lamp
Base
amplifier
Servo motor
speed
1000 80
2000 100
2000 70
2000 60
2000 80
1000 80
1000 80
Regene­rative TR
Voltage
detection
Point table
Acceleration
time
constant
Current
detector
Overcurrent
protection
Deceleration
time
constant
80
100
60
70
80
80
80
Dynamic
brake
Current
detection
Dwell
0
0
500
1000
0
0
0
Auxiliary
function
0
0
1
1
0
0
0
U
V
W
RA
24VDC
CN2
Servo motorC
U
V
W
B1
Electro­magnetic
B
brake
B2
Encoder
M
USB
I/F
Personal
computer
USB
CN3
CN1
D I/O control
Servo-on Start Failure, etc.
Note 1. A built-in regenerative resistor is not provided for the MR-JN-10A(1).
2. For the specification of power supply, refer to section 1.3.
1 - 4
1. FUNCTIONS AND CONFIGURATION
(3) Positioning mode (Program method)
Regenerative option
(Note 2) Main
circuit power supply
(Note 2) Control
circuit power supply
MCCB
Circuit
protector
Servo amplifier
MC
L1
L2
0V
Diode
stack
Relay
Fuse
24V
Current
control
Speed control
Model adaptive control
Position
control
Control
circuit power supply
P
(Note 1)
CHARGE
lamp
Base
amplifier
Regene­rative TR
Voltage
detection
Program
SPN(1000)
STA(200)
STB(300)
MOV(500)
SPN(1000)
MOVA(1000)
MOVA(0)
Current
detector
Overcurrent
protection
Dynamic
brake
Current
detection
U
V
W
RA
24VDC
CN2
Servo motorC
U
V
W
B1
B
B2
Encoder
M
Electro­magnetic brake
Position
command
creation
I/F
CN1
D I/O control
Servo-on Start Failure, etc.
Note 1. A built-in regenerative resistor is not provided for the MR-JN-10A(1).
2. For the specification of power supply, refer to section 1.3.
STOP
USB
CN3
Personal
computer
USB
1 - 5
1. FUNCTIONS AND CONFIGURATION

1.3 Servo amplifier standard specifications

Servo amplifier
MR-JN-
Item
Output
Main circuit power supply
Control circuit power supply
Interface power supply
Control System Sine-wave PWM control, current control system Dynamic brake Built-in
Protective functions
Structure Natural-cooling, open (IP rating: IP20)
Close mounting
Environmental conditions
Mass
Note. 0.2A is the value applicable when all I/O signals are used. The current capacity can be decreased by reducing the number of I/O
points.
Rated voltage 3-phase 170VAC Rated current [A] 1.1 1.6 2.8 1.1 1.6
Voltage/frequency 1-phase 200VAC to 230VAC, 50/60Hz
Rated current [A] 1.5 2.4 4.5 3.0 5.0 Permissible voltage fluctuation Permissible frequency fluctuation Power supply capacity Refer to section 10.2 Inrush current Refer to section 10.5 Voltage 24VDC Rated current [A] 0.5 Permissible voltage fluctuation Power consumption [W] 10 Voltage 24VDC Power supply capacity [A] 0.2 (Note)
In Ambient temperature
Ambient humidity
Ambience
Altitude Max. 1000m (3280 ft) Vibration resistance 5.9 [m/s2], 10 to 55Hz (directions of X, Y and Z axes)
operation
In
storage
In operation
In storage
10A 20A 40A 10A1 20A1
1-phase 100VAC to 120VAC,
1-phase 170VAC to 253VAC 1-phase 85VAC to 132VAC
Within
5%
Within
10%
10%
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic thermal
relay), servo motor overheat protection, encoder error protection, regenerative error
protection, undervoltage, instantaneous power failure protection, overspeed protection,
When mounting the servo amplifiers closely, operate them at the ambient temperature of 0°C
to 45°C or at 75% or less of the effective load ratio.
[°C] 0 to 55 (non-freezing)
[°F] 32 to 131 (non-freezing)
[°C] -20 to 65 (non-freezing)
[°F] -4 to 149 (non-freezing)
Free from corrosive gas, flammable gas, oil mist, dust and dirt
[kg] 0.6 0.6 0.7 0.6 0.6
[lb] 1.32 1.32 1.54 1.32 1.32
excessive error protection
5%RH to 90%RH (non-condensing)
Indoors (no direct sunlight)
50/60Hz
1 - 6
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
MR-JN-
Item
Max. input pulse frequency 1Mpps (for differential receiver), 200kpps (for open collector)
Command pulse multiplying Position control mode
Internal speed control mode
Internal torque Torque command input Parameter setting control mode Speed limit Parameter setting
Command method
Operation mode
Positioning mode
Home position return mode
Other functions
factor (electronic gear)
In-position range setting 0 to 65535pulses (command pulse unit)
Error excessive 3 rotations
Torque limit Parameter setting
Speed command input Parameter setting
Speed control range 1:5000
Speed fluctuation ratio
Torque limit Parameter setting
Operating specification Positioning by specifying the point table No. (7 points)
Position command input Set in point table. One-point feed length setting range: 1[μm] to 999.999[mm]
Speed command input
table
Point
method
System Signed absolute value command system, Incremental value command system
Operating specification
Position command input
Speed command input
Program method
System Signed absolute value command system, signed incremental value command system
Point
table
method
mode
operation
Automatic
Program method Setting by programming language
JOG
mode
Manual
Manual pulse generator
operation
Dog type
Count type
Data set type
Stopper type
Home position ignorance (Servo-on position as home position)
Dog type rear end reference
Count type front end reference
Dog cradle type
One-time positioning operation Automatic continuous positioning operation
10A 20A 40A 10A1 20A1
Electronic gear A/B, A: 1 to 65535, B: 1 to 65535, 1/50
0.01% or less (load fluctuation 0 to 100%) 0% (power fluctuation
S-pattern acceleration/deceleration time constant is set in parameter No. PC03.
S-pattern acceleration/deceleration time constant is also settable by parameter No. PC03.
One-time positioning operation is performed in accordance with position and speed commands.
Varied speed operation (2 to 7 speeds), Automatic continuous positioning operation
JOG operation is performed in accordance with parameter-set speed command by contact
Command pulse multiplication:
Home position return is made starting with Z-phase pulse after passage of proximity dog.
Home position return direction is selectable. Home position shift value is settable.
Home position return is made by counting encoder pulses after contact with proximity dog.
Home position return direction is selectable. Home position shift value is settable.
Home position is settable at any position by manual operation, etc. Home position
Home position return is made by pressing machine part against stroke end.
Home position return direction is selectable. Home position address is settable.
Home position return direction is selectable. Home position shift value is settable.
Home position return is made with respect to the front end of proximity dog.
Home position return direction is selectable. Home position shift value is settable.
Home position return is made with respect to the front end of a proximity dog by the first
Home position return direction is selectable. Home position shift value is settable.
Acceleration/deceleration time constant is set in point table.
Program language (programmed by MR Configurator).
Program capacity: 120 steps
Setting by program language.
One-point feed length setting range:
Servo motor speed, acceleration/deceleration time constant and S-pattern
acceleration/deceleration time constant are set by program language.
Point table number input, position data input system
(2 to 7 points)
input.
Manual feed is made by manual pulse generator.
1, 10 or 100 is selected using parameter.
Home position address is settable.
Automatic at-dog home position return, Automatic stroke return function
Home position address is settable.
Automatic at-dog home position return, Automatic stroke return function
Home position return is made without dog.
address is settable.
Position where servo-on (SON) is switched on is defined as home position.
Home position address is settable.
Home position return is made with respect to the rear end of proximity dog.
Home position address is settable.
Automatic at-dog home position return, Automatic stroke return function
Home position address is settable.
Automatic at-dog home position return, Automatic stroke return function
Z-phase pulse.
Home position address is settable.
Automatic at-dog home position return, Automatic stroke return function
Backlash function, Overtravel prevention using external limit switch
Software stroke limit
A/B 500
10%)
1[μm] to 999.999[mm]
1 - 7
1. FUNCTIONS AND CONFIGURATION

1.4 Function list

The following table lists the functions of this servo. For details of the functions, refer to the reference field.
(Note 1)
Function Description
Position control mode This servo is used as position control servo.
Internal speed control mode This servo is used as internal speed control servo. S
Internal torque control mode This servo is used as internal torque control servo. T
Position/internal speed control change mode Internal speed/internal torque control change mode Internal torque/position control change mode
Positioning mode (Point table method) (Note 2)
Positioning mode (Program method) (Note 2)
Home position return mode (Note 2)
High-resolution encoder
Gain changing function
Advanced vibration suppression control
Adaptive filter II
Low-pass filter
Electronic gear
One-touch tuning
Auto tuning
Position smoothing Smooth acceleration is enabled in response to input pulse. P Section 4.2.3
S-pattern acceleration/ deceleration time constant
Regenerative option
Alarm history clear
Using input device, control can be switched between position control and internal speed control. Using input device, control can be switched between internal speed control and internal torque control. Using input device, control can be switched between internal torque control and position control. Positioning operation is performed by selecting 7 point tables which are set in advance, in accordance with the set value. Select the point table using an external input signal. Positioning operation is performed by selecting a program from 8 programs which are created in advance. Select the program using an external input signal. Dog type, count type, data set type, stopper type, home position ignorance, dog type rear end reference, count type front end reference, dog cradle type The servo motor is equipped with high-resolution encoder of 131072 pulses/rev. Gains can be changed using an input device or gain changing conditions (servo motor speed, etc.) This function suppresses vibration of an arm end or residual vibration. This function sets the filter characteristics automatically by the one-touch tuning to suppress vibration of a mechanical system. This function is effective for suppressing high-frequency resonance which occurs as the servo system response is increased. Input pulses can be multiplied by 1/50 to 500. P Section 4.1.7 Position command can be multiplied by 1/131 to 1000. Electronic gear setting range can be changed by changing the number of virtual pulses per servo motor revolution. The gain of the servo amplifier can be adjusted by the push button on the front panel. This function optimizes the servo gain automatically as load applied to the servo motor shaft changes.
Smooth acceleration and deceleration are enabled.
Regenerative option is used when the built-in regenerative resistor of the servo amplifier does not have sufficient regenerative capability for the regenerative power generated. This function clears alarm history and the number of tough drive performed.
Control
mode
P
P/S Section 3.6.4
S/T Section 3.6.5
T/P Section 3.6.6
CP Section 13.3
CL Section 13.4
CP/CL Section 13.6
P, S, T
CP/CL
P, S
CP/CL
P
CP/CL
P, S
CP/CL
P, S
CP/CL
CP/CL Section 13.7.1 (3)
P, S
CP/CL
P, S
CP/CL
S, T
CP/CL
P, S, T
CP/CL
P, S, T
CP/CL
Reference
Section 3.2.1 Section 3.6.1 Section 3.2.2 Section 3.6.2 Section 3.2.3 Section 3.6.3
Section 7.3
Section 7.2.4
Section 7.2.2
Section 7.2.5
Section 6.1
Section 6.3
Section 4.3.2 Parameter No. PC03 Section 13.7.3 (2) Parameter No. PC03
Section 11.2
Parameter No. PC11
1 - 8
1. FUNCTIONS AND CONFIGURATION
(Note 1)
Function Description
Command pulse selection
Input signal selection
Output signal selection
Torque limit
Speed limit Servo motor speed can be limited by setting a parameter. T
Status display Servo status is shown on the 3-digit, 7-segment LED display
External I/O signal display ON/OFF statuses of external I/O signals are shown on the display.
Output signal (DO) forced output
Test operation mode
MR Configurator
Tough drive function
Limit switch
Software limit (Note2)
Drive recorder function (Note2)
Note 1. P: Position control mode, S: Internal speed control mode, T: Internal torque control mode,
P/S: Position/internal speed control change mode, S/T: Internal speed/internal torque control change mode,
T/P: Internal torque/position control change mode
CP: Positioning mode (Point table method), CL: Positioning mode (Program method)
2. It is supported by servo amplifier with software version B0 or later.
Command input pulse form can be selected from among three different types.
Forward rotation start (ST1), reverse rotation start (ST2), servo-on (SON) and other input device can be assigned to specific pins.
Ready (RD), trouble (ALM) or other output device can be assigned to specific pins.
The torque generated by the servo motor can be limited by setting a parameter.
Output signal can be forced on/off independently of the servo status. Use this function for output signal wiring check, etc. JOG operation, positioning operation, motor-less operation, DO forced output, forced tough drive operation, program operation, and single-step feed. Note that MR Configurator MRZJW3-SETUP221E is necessary for the positioning operation, program operation or single-step feed. The single-step feed is supported by servo amplifier with software version B0 or later, and MR Configurator with software version C4 or later.
Parameter setting, test operation, status display, etc. can be performed using a personal computer.
This function continues the operation not to stop a machine in such situation when normally an alarm is activated. Three types of the tough drive function are available: overload tough drive, vibration tough drive and instantaneous power failure tough drive. However, the overload tough drive is valid only in the position control mode or positioning mode.
The servo motor travel region can be limited using the forward rotation stroke end (LSP)/reverse rotation stroke end (LSN).
The travel region is limited using parameters in terms of address. The function similar to that of a limit switch is limited by parameter. This function records the state transition before and after the alarm occurrence for the predetermined period of time by always monitoring the servo status. The recorded data can be confirmed on the graph display screen by clicking the "Drive recorder display" button on the alarm history display screen of MR Configurator.
Control
P, S, T
P, S, T
P, S, T
P, S, T
P, S, T
P, S, T
P, S, T
P, S, T
Reference
mode
P Section 4.1.11
Parameter
CP/CL
CP/CL
CP/CL
CP/CL
CP/CL
CP/CL
CP/CL
CP/CL Section 13.10
CP/CL
CP/CL
CP/CL Section 13.2.3
CP/CL Section 13.7.5 (4)
CP/CL
No. PD02 to PD14 Parameter No. PD15 to PD18
P, S
Section 3.6.1 (4)
Section 3.6.3 (3) Parameter No. PC05 to PC08, PC31 to PC34
Section 5.3
Section 5.8
Section 5.9
Section 5.10
Section 11.4 Section 13.8 to
13.10
P, S
Section 7.1
P, S Section 3.5
Section 4.3.4
1 - 9
1. FUNCTIONS AND CONFIGURATION

1.5 Model code definition

(1) Rating plate
The following shows an example of the rating plate for explanation of each item.
AC SERVO
MODEL
Note. The year and month when the servo amplifier is manufactured are written down in the serial number of the rating plate.
The year and month of manufacture are indicated by the last one digit of the year and 1 to 9, X(10), Y(11), Z(12).
For September 2009, the serial number is like "SERIAL:
MR-JN-10A
POWER : 100W INPUT : AC200-230V 1.5A 50/60Hz, DC24V 0.5A
OUTPUT: 3PH170V 0-360Hz 1.1A STD.: IEC/EN 61800-5-1 Max. Surrounding Air Temp.: 55°C
IP20
KCC-REI-MEK-TC300A566G51
TOKYO 100-8310, JAPAN MADE IN JAPAN
SER.A45001001
MAN.: IB(NA)0300157
DATE: 2014-05
99 ”.
Serial number (Note) Model Capacity Applicable power supply Rated output current Standard, Manual number Ambient temperature IP rating KC certification number The year and month of manufacture Country of origin
(2) Model
The following explains the description of models. Not all the combination of symbols exists.
Series
Power supply
Symbol
None
1 1-phase 100 to 120VAC
General purpose interface
Rated output
Symbol
10 20 40
Power supply
1-phase 200 to 230VAC
Rated output [kW]
0.1
0.2
0.4
Serial number
Rating plate

1.6 Combination with servo motor

POINT
The HF-KP G1/G5/G7 servo motors have been discontinued in May 2019.
The following table lists combinations of servo amplifiers and servo motors. The following combinations also apply to servo motors with an electromagnetic brake.
Servo amplifier
MR-JN-10A(1) 053 13
MR-JN-20A(1) 23
MR-JN-40A 43
Note. Depending on the servo motor being used, encoder resolution per
servo motor revolution changes as follows. HF-KN HF-KP
HG-KR
series servo motor: 131072pulses/rev
G1/G5/G7 servo motor: 262144pulses/rev
G1/G5/G7 servo motor: 262144pulses/rev (when combined
Servo motors (Note)
HF-KN HF-KPG1/G5/G7 HG-KR G1/G5/G7
with MR-JN-
A servo amplifier)
1 - 10
1. FUNCTIONS AND CONFIGURATION

1.7 Parts identification

Fixed part (2 places)
Name/Application
Serial number
Main circuit power supply connector (CNP1)
Connect the input power supply/built-in regenerative resistor/regenerative option/servo motor/earth.
Charge lamp
Lit to indicate that the main circuit is charged. While this lamp is lit, do not reconnect the cables.
Rating plate
One-touch tuning button (AUTO)
Press this button to perform the one-touch tuning.
Control circuit power supply connector (CNP2)
Connect the control circuit power supply.
Display
The 3-digit, 7-segment LED shows the servo status and alarm number
Operation section
Used to perform status display, diagnosis, alarm, point table and parameter setting operations.
MODE SET
Used to set data. Used to change the mode.
Detailed
explanation
Section 3.1 Section 3.3
Section 1.5
Section 6.1
Section 3.1 Section 3.3
Chapter 5
Chapter 5
Used to change the display or data in each mode.
I/O signal connector (CN1)
Used to connect digital I/O signals.
USB communication connector (CN3)
Connect the personal computer.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section 3.2 Section 3.4
Section 11.4
Section 3.4
Section 11.1
1 - 11
1. FUNCTIONS AND CONFIGURATION

1.8 Configuration including auxiliary equipment

(Note) Main circuit power supply
Molded-case circuit breaker (MCCB)
Magnetic contactor
(MC)
Power factor improving AC reactor (FR-HAL)
Line noise filter (FR-BSF01)
R S
POINT
Equipment other than the servo amplifier and servo motor are optional or
recommended products.
Servo amplifier
P
Regenerative
C
option
U
AUTO
MODE SET
V
W
Circuit protector
24V
0V
(Note) Control circuit power supply
L
1
L
2
Personal
MR Configurator
Note. Refer to section 1.3 for the power supply specification.
computer
Servo motor
Junction terminal block
1 - 12

2. INSTALLATION

2. INSTALLATION
WARNING
CAUTION
Be sure to ground the servo amplifier to prevent electric shocks.
Carry the products in a suitable way according to their weight. Stacking in excess of the limited number of product packages is not allowed. Do not hold the lead of the built-in regenerative resistor, the cables, or the
connectors when carrying the servo amplifier. Otherwise, it may drop.
Install the equipment to incombustibles. Installing it directly or close to
combustibles will lead to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury. Use the equipment within the specified environmental condition range. (For details
of the environmental condition, refer to section 1.3.)
Provide an adequate protection to prevent conductive matters like screws or
combustible matters like oil from entering the servo amplifier.
Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may
occur.
Do not subject the servo amplifier to drop impact or shock loads as they are
precision equipment.
Do not install or operate a faulty servo amplifier. When the product has been stored for an extended period of time, consult
Mitsubishi Electric.
When handling the servo amplifier, be careful about the edged parts such as the
corners of the servo amplifier.
The servo amplifier must be installed in the metal cabinet.
When fumigants that contain halogen materials such as fluorine, chlorine, bromine, and iodine are used for disinfecting and protecting wooden packaging from insects, they cause malfunction when entering our products. Please take necessary precautions to ensure that remaining materials from fumigant do not enter our products, or treat packaging with methods other than fumigation (heat method). Additionally, disinfect and protect wood from insects before packing products.
2 - 1
2. INSTALLATION

2.1 Installation direction and clearances

The equipment must be installed in the specified direction. Otherwise, a fault may
CAUTION
occur.
Leave specified clearances between the servo amplifier and control box inside walls or other equipment. Doing so may cause malfunction to the equipment.
A regenerative resistor is mounted on the back of this servo amplifier. The regenerative resistor causes a temperature rise of 100
relative to the ambient temperature. Fully examine heat dissipation and
installation position before installing the servo amplifier.
(1) Installation of one servo amplifier
10mm or more
Control box
40mm or more Servo amplifier
40mm or more
Wiring allowance
80mm
10mm or more
Control box
Top
Bottom
2 - 2
2. INSTALLATION
(2) Installation of two or more servo amplifiers
POINT
MR-JN series servo amplifier with any capacity can be mounted closely together.
Leave a large clearance between the top of the servo amplifier and the internal surface of the control box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the environmental conditions. When installing the servo amplifiers closely, leave a clearance of 1mm between the adjacent servo amplifiers in consideration of mounting tolerances. In this case, operate the servo amplifiers at the ambient temperature of 0
to 45 or at 75% or less of the
effective load ratio.
30mm or more
Control box
100mm or more
10mm or more
40mm or more
30mm or more
30mm or more
Control box
100mm or more
1mm
40mm or more
Mounting closelyLeaving clearance
1mm
30mm or more
(3) Others
When using heat generating equipment such as the regenerative option, install them with full consideration of heat generation so that the servo amplifier is not affected. Install the servo amplifier on a perpendicular wall in the correct vertical direction.

2.2 Keep out foreign materials

Top
Bottom
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the servo
amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control box or
a cooling fan installed on the ceiling.
(3) When installing the control box in a place where toxic gas, dirt and dust exist, conduct an air purge (force
clean air into the control box from outside to make the internal pressure higher than the external pressure) to prevent such materials from entering the control box.
2 - 3
2. INSTALLATION

2.3 Cable stress

(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight stress
are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake) with
having some slack from the connector connection part of the servo motor to avoid putting stress on the connector connection part. Use the optional encoder cable within the flexing life range. Use the power supply and brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner or
stamped by workers or vehicles.
(4) For installation on a machine where the servo motor moves, the flexing radius should be made as large as
possible. Refer to section 10.4 for the flexing life.

2.4 Inspection items

Before starting maintenance and/or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns off. Otherwise, an electric shock may
WARNING
occur. In addition, always confirm from the front of the servo amplifier whether the charge lamp is off or not.
Due to risk of electric shock, only qualified personnel should attempt inspection. For repair and parts replacement, contact your local sales office.
CAUTION
It is recommended to make the following checks periodically.
(1) Check for loose screws. Retighten any loose screws.
(2) Check the cables and the wires for scratches and cracks. Perform periodic inspection according to
operating conditions.
(3) Make sure that the emergency stop circuit operates properly such that an operation can be stopped
immediately and a power is shut off by the emergency stop switch.
Do not perform insulation resistance test on the servo amplifier as damage may result.
Do not disassemble and/or repair the equipment on customer side.
2 - 4
2. INSTALLATION

2.5 Parts having service lives

Service lives of the following parts are listed below. However, the service life varies depending on operating methods and environmental conditions. If any fault is found in the parts, they must be replaced immediately regardless of their service lives. For parts replacement, please contact your local sales office.
Part name Life guideline
Smoothing capacitor 10 years
Relay
Number of power-on and number of forced stop times:
100,000 times
(1) Smoothing capacitor
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly depends on ambient temperature and operating conditions. The capacitor will reach the end of its life in 10 years when operated continuously in an air-conditioned environment (ambient temperature of 40 ˚C or less).
(2) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of their life when the cumulative number of power-on and forced stop times is 100,000, which depends on the power supply capacity.
2 - 5
2. INSTALLATION
MEMO
2 - 6

3. SIGNALS AND WIRING

3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Otherwise, an electric shock may occur. In addition, always confirm
from the front of the servo amplifier whether the charge lamp is off or not.
Ground the servo amplifier and the servo motor securely.
WARNING
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
To avoid an electric shock, insulate the connections of the power supply terminals.
Before unplugging the CNP1 connector from the servo amplifier, disconnect the
lead of the built-in regenerative resistor from the CNP1 connector.
Wire the equipment correctly and securely. Otherwise, the servo motor may
operate unexpected resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the emergency stop and other protective circuits.
CAUTION
Servo amplifier
DOCOM
Control output signal
DICOM
Sink output
interface
24VDC
RA
Servo amplifier
DOCOM
Control output signal
DICOM
Source output
interface
24VDC
RA
Use a noise filter, etc. to minimize the influence of electromagnetic interference,
which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge killer or radio noise filter (FR-BIF option)
with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative resistor,
causing a fire.
Do not modify the equipment.
3 - 1
3. SIGNALS AND WIRING
Connect the servo amplifier power output (U/V/W) to the servo motor power input
(U/V/W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may
cause a malfunction.
Servo amplifier
CAUTION

3.1 Input power supply circuit

Always connect a magnetic contactor (MC) between the main circuit power supply,
and L
power on the servo amplifier's power supply side. If a magnetic contactor (MC) is
not connected, continuous flow of a large current may cause a fire when the servo
amplifier malfunctions.
Use the trouble (ALM) to switch power off. Otherwise, a regenerative transistor
CAUTION
fault or the like may overheat the regenerative resistor, causing a fire.
Before unplugging the CNP1 connector from the servo amplifier, disconnect the
lead of the built-in regenerative resistor from the CNP1 connector. Otherwise, the
lead of the built-in regenerative resistor may break.
For main circuit power supply of servo amplifier, check the model of servo amplifier
and input the correct voltage. If a voltage exceeding the upper limit shown in the
servo amplifier input voltage specification is input, the servo amplifier malfunctions.
Servo motor
U
V
W
1 and L2 of the servo amplifier to configure a circuit that shuts down the
U
V
M
W
Servo amplifier
U
W
Servo motor
U
V
W
MV
3 - 2
3. SIGNALS AND WIRING
Wire the main circuit power supply as shown below so that the servo-on (SON) turns off as soon as alarm occurrence is detected and power is shut off. A molded-case circuit breaker (MCCB) must be used with the input cables of the main circuit power supply.
Trouble
RA
Forced stop (Note 5)
OFF
ON
MC
MC
SK
Servo amplifier
Main circuit power supply 1-phase 200 to 230VAC or 1-phase 100 to 120VAC
MCCB
MC (Note 6)
(Note 1)
Circuit protector
Control circuit power supply 24VDC (Note 7)
Forced stop (Note 5)
(Note 3)
Note 1. The built-in regenerative resistor is provided for MR-JN-20A(1) and MR-JN-40A. (Factory-wired.) When using the regenerative
option, refer to section 11.2.
2. For encoder cable, use of the option cable is recommended. Refer to section 11.1 for selection of the cable.
3. For sink I/O interface.
For source I/O interface, refer to section 3.8.3.
4. Refer to section 3.10.
5. Configure the circuit to shut off the main circuit power supply by an external sequence simultaneously with the forced stop
(EM1) turning OFF.
6. Be sure to use a magnetic contactor (MC) with an operation delay time of 80ms or less. The operation delay time is the time
interval between current being applied to the coil until closure of contacts.
7. Use the enhanced insulation power supply for the control circuit power supply 24VDC. In addition, do not use a power supply
with an output voltage starting time of one second or more.
Servo-on
CNP1
1
L
Built-in regenerative resistor
L2
P
C
CNP2
+24V
0V
EM1
SON
DOCOM
U
V
W
CN2
CN1CN1
DOCOM
DICOM
ALM
(Note 4)
(Note 2)
Encoder cable
24VDC
RA
Servo motor
U
V
W
Trouble
Motor
M
Encoder
(Note 3)
3 - 3
3. SIGNALS AND WIRING

3.2 I/O signal connection example

3.2.1 Position control mode

Programmable controller FX5U
(Note 10, 11)
- MT/ES (Note 13)
Programmable controller power supply
COM0
COM1
COM2
X0(Note 14)
(Note 3, 5)
Forced stop
Servo-on
Reset
Forward rotation
(Note 5)
stroke end Reverse rotation
stroke end
S/S
24V
0V
L
N
Y0
Y4
Y10
X_
X_
2m max. (Note 8)
24VDC
(Note 4, 10)
10m max.
DICOM
OPC
DOCOM
PP
NP
CR
INP 10
RD OP LG SD
EM1
SON
RES
LSP
LSN
Servo amplifier
(Note 7)(Note 7)
CN1 CN1
1 2
13
9 ALM
12 MBR
23
25
15 LA
5
16 LAR 17 LB 18 LBR 19 LZ
20 LZR 11 21
14 LG
Plate
14
Plate
(Note 7)
CN1
8
4
3
6
7
SD
(Note 2)
RA1
RA2
10m max.
Trouble (Note 6)
Electromagnetic brake interlock
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Encoder Z-phase pulse (differential line driver)
(Note 10, 12)
Control common
(Note 15)
(Note 9) MR Configurator
Personal computer
USB cable
(option)
CN3
3 - 4
CNP1
(Note 1)
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of the servo amplifier main
circuit power connector (CNP1) to the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24VDC
The current capacity can be decreased by reducing the number of I/O points. Refer to section 3.8.2 (1) that gives the current
value necessary for the interface.
5. When starting operation, always switch on the forced stop (EM1) or the forward/reverse rotation stroke end (LSP, LSN).
(Normally closed contacts)
6. Trouble (ALM) turns on in normal alarm-free condition. (Normally closed contact) When this signal is switched off (at occurrence
of an alarm), the output of the programmable controller should be stopped by the sequence program.
7. The pins with the same signal name are connected in the servo amplifier.
8. This length applies to the command input pulses in the open collector system. The wirings can be extended up to 10m when
using positioning modules with the differential line driver type.
9. Use MRZJW3-SETUP221E (C4 or later).
10. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.8.3.
11. The assigned signals can be changed using the settings of parameter No. PD03 to PD14.
12. The assigned signals can be changed using the settings of parameter No. PD15 to PD18.
13. Select the number of I/O points of the programmable controllers in accordance with the system.
14. Select it within X0 to X7.
15. When a command cable for connection with the controller side malfunctions due to disconnection or noise, a position mismatch
can occur. To avoid position mismatch, it is recommended that Encoder A-phase pulse and Encoder B-phase pulse be checked.
10% 200mA current for interfaces from the outside. 200mA is the value applicable when all I/O signals are used.
3 - 5
3. SIGNALS AND WIRING

3.2.2 Internal speed control mode

24VDC
(Note 3, 5)
(Note 9, 10, 12)
(Note 8)
MR Configurator
Forced stop
Servo-on
Reset
Speed selection 1 Forward rotation start
Reverse rotation start
Personal computer
(Note 4, 9)
10m max.
USB cable (option)
DICOM
DOCOM
EM1 SON RES
SP1 ST1 ST2
Servo amplifier
(Note 7)
(Note 7)
CN1
CN1
1
13
8 4 3 5 6 7
CN3
Plate
9ALM
10 SA
11 RD
12 MBR
LZ
19 20 LZR 15 LA 16 LAR 17 LB 18 LBR
14 LG 21 OP
SD
(Note 2)
10m max.
2m max.
RA1
RA2
RA3
RA4
Trouble (Note 6)
Speed reached
Ready
Electromagnetic brake interlock
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
Control common
Encoder Z-phase pulse (open collector)
(Note 9, 11)
CNP1
(Note 1)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of the servo amplifier
main circuit power connector (CNP1) to the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24VDC
10% 200mA current for interfaces from the outside. 200mA is the value applicable when all I/O signals are used.
The current capacity can be decreased by reducing the number of I/O points. Refer to section 3.8.2 (1) that gives the current
value necessary for the interface.
5. When starting operation, always switch on the forced stop (EM1). (Normally closed contacts)
6. Trouble (ALM) turns on in normal alarm-free condition. (Normally closed contact)
7. The pins with the same signal name are connected in the servo amplifier.
8. Use MRZJW3-SETUP221E (C4 or later).
9. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.8.3.
10. The assigned signals can be changed using the settings of parameter No. PD02 to PD14.
11. The assigned signals can be changed using the settings of parameter No. PD15 to PD18.
12. The forward rotation stroke end (LSP) and the reverse rotation stroke end (LSN) automatically switch ON if not assigned to the
external input signals.
3 - 6
3. SIGNALS AND WIRING

3.2.3 Internal torque control mode

(Note 3)
Forced stop
(Note 8, 9)
(Note 7) MR Configurator
Servo-on
Reset
Speed selection 1
Forward rotation selection
Reverse rotation selection
Personal computer
24VDC
(Note 4, 8)
10m max.
USB cable (option)
DICOM
DOCOM
EM1
SON
RES SP1 RS1 RS2
Servo amplifier
(Note 6)
(Note 6)
CN1
CN1
1
13
8 4 3 5 7 6
CN3
Plate
9ALM
11 RD
12 MBR
19 LZ 20
LZR 15 LA 16 LAR 17 LB 18 LBR
14 LG 21 OP
SD
2m max.
(Note 2)
RA1
RA2
RA3
10m max.
Control common Encoder Z-phase pulse
(open collector)
Trouble (Note 5)
Ready
Electromagnetic brake interlock
Encoder Z-phase pulse (differential line driver)
Encoder A-phase pulse (differential line driver)
Encoder B-phase pulse (differential line driver)
Control common
(Note 8, 10)
CNP1
(Note 1)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal (terminal marked ) of the servo amplifier main
circuit power connector (CNP1) to the protective earth (PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the emergency stop and other protective circuits.
3. The forced stop switch (normally closed contact) must be installed.
4. Supply 24VDC
10% 200mA current for interfaces from the outside. 200mA is the value applicable when all I/O signals are used.
The current capacity can be decreased by reducing the number of I/O points. Refer to section 3.8.2 (1) that gives the current
value necessary for the interface.
5. Trouble (ALM) turns on in normal alarm-free condition. (Normally closed contact)
6. The pins with the same signal name are connected in the servo amplifier.
7. Use MRZJW3-SETUP221E (C4 or later).
8. This diagram shows sink I/O interface. For source I/O interface, refer to section 3.8.3.
9. The assigned signals can be changed using the settings of parameter No. PD02 to PD14.
10. The assigned signals can be changed using the settings of parameter No. PD15 to PD18.
3 - 7
3. SIGNALS AND WIRING

3.3 Explanation of power supply system

3.3.1 Signal explanations

Abbreviation
L1 L
2
P C
+24V
0V
U V
W
Protective earth (PE)

3.3.2 Power-on sequence

POINT
For the layout of connector, refer to chapter 9 DIMENSIONS.
Connection target
(application)
Main circuit power supply
Built-in regenerative resistor or regenerative option
Control circuit power supply
Servo motor power
Supply the following power supply. MR-JN-10A/20A/40A : 1-phase 200VAC to 230VAC, 50/60Hz MR-JN-10A1/20A1 : 1-phase 100VAC to 120VAC, 50/60Hz
1) MR-JN-10A(1) When using the regenerative option, connect it to P and C. (MR-JN-10A(1) does not provide a built-in regenerative resistor.)
2) MR-JN-20A(1)/40A When using the servo amplifier built-in regenerative resistor, connect the built-in regenerative resistor to P and C. (Factory-wired.) When using a regenerative option,
first, disconnect the wirings to P and C, second, remove the built-in regenerative resistor from the servo amplifier, finally, connect the regenerative option to P and C.
Supply 24VDC power to +24V and 0V.
Connect to the servo motor power supply terminals (U, V, W). Connect the servo amplifier power supply output (U, V, and W) to the servo motor power supply input (U, V, and W) directly. Do not let a magnetic contactor, etc. intervene. Otherwise, it may cause a malfunction. Connect to the earth terminal of the servo motor and to the protective earth (PE) of the control box to perform grounding.
Description
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.1 using the magnetic contactor with the main circuit power supply (single-phase: L
1
, L2). Configure up an external sequence to switch off the magnetic
contactor as soon as an alarm occurs.
2) The servo amplifier can accept the servo-on (SON) about 1 to 2s after the main circuit power supply is switched on. Therefore, when the servo-on (SON) is switched on simultaneously with the main circuit power supply, the base circuit will switch on in about 1 to 2s, and the ready (RD) will switch on in further about 5ms, making the servo amplifier ready to operate. (Refer to paragraph (2) in this section.) If the main circuit power supply is OFF while the servo-on (SON) is ON, the display on the servo amplifier shows the corresponding warning. Switching ON the main circuit power supply discards the warning and the servo amplifier operates normally.
3) When the reset (RES) is switched on, the base circuit is shut off and the servo motor shaft coasts.
3 - 8
3. SIGNALS AND WIRING
(2) Timing chart
Servo-on (SON) accepted
(1 to 2s)
Main circuit Control circuit Power supply
Base circuit
Servo-on (SON)
Reset (RES)
Ready (RD)
Trouble (ALM)
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
No (ON) Yes (OFF)
1s
10ms
10ms5ms
95ms
10ms
10ms5ms
95ms
5ms 10ms
Power-on timing chart
(3) Forced stop
Configure a circuit which interlocks with an external emergency stop switch in order
CAUTION
to stop the operation immediately and shut off the power.
Configure a circuit that shuts off the main circuit power as soon as EM1 is turned off at a forced stop. When EM1 is turned off, the dynamic brake is operated to stop the servo motor immediately. At this time, the display shows the servo forced stop warning (E6.1). During the normal operation, do not use the forced stop (EM1) to alternate stop and run. The service life of the servo amplifier may be shortened. Also, the servo motor rotates simultaneously with the reset of the forced stop if a forward rotation start (ST1) or the reverse rotation start (ST2) is ON, or if a pulse train is input during the forced stop. Be sure to shut off the operation instruction during the forced stop.
Servo amplifier
(Note)
24VDC
Forced stop
DICOM
EM1
Note. For sink I/O interface. For source I/O interface, refer to section 3.8.3.
3 - 9
3. SIGNALS AND WIRING

3.3.3 CNP1 and CNP2 wiring method

POINT
Refer to section 11.5, for the wire sizes used for wiring.
Use the supplied servo amplifier power supply connectors for wiring of CNP1 and CNP2.
(1) Servo amplifier power supply connectors
Servo amplifier
Connector for CNP1
<Applicable cable example> Wire size: 0.2 to 2.5mm Cable finish OD: to 4mm
2
(AWG24 to AWG12)
FKC2,5/ 9-ST-5,08 (Phoenix Contact)
Connector for CNP2 FKCT 2,5/ 2-ST-5,08 (Phoenix Contact)
CNP1
CNP2
CNP1
CNP2
3 - 10
3. SIGNALS AND WIRING
(2) Termination of the wires
(a) Solid wire
The wire can be used just by stripping the sheath.
Sheath
Core
(b) Twisted wire
1) Inserting the wires directly to the terminals Use the wire after stripping the sheath and twisting the core. At this time, take care to avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the core as it may cause a contact fault.
2) Putting the wires together using a ferrule Use a ferrule as follows.
Cut off the exceeding wire from the tip of the ferrule, leaving 0.5mm or less.
When using the ferrule for two wires, plug the wires in a direction in which insulating sleeves do not interfere the adjacent poles.
Approx. 10mm
Cable size Ferrule type
[mm2] AWG For one wire For two wires
1.25/1.5 16 AI 1,5-10 BK AI-TWIN 2 1,5-10 BK
2/2.5 14 AI 2,5-10 BK
Crimp
0.5mm or shorter
Crimping tool Manufacturer
CRIMPFOX ZA 3 Phoenix Contact
Crimp
3 - 11
3. SIGNALS AND WIRING
(3) Connection method
(a) Inserting the wires directly to the terminals
Insert the wire to the very end of the hole while pressing the button by a tool such as a small flat-blade screwdriver.
Button
Tools such as a small flat-blade screwdriver
Twisted wire
(b) Putting the wires together using a ferrule
Insert the wire as the uneven side of the crimped ferrule collar faces the button side.
Ferrule for one wire or solid wire
Ferrule for two wires
Use a ferrule for two wires when inserting two wires into one hole.
3 - 12
3. SIGNALS AND WIRING

3.4 Connectors and signal arrangements

POINT For the positioning mode, refer to section 13.2.2. The pin configurations of the connectors are as viewed from the cable connector wiring section. Refer to (2) in this section for CN1 signal assignment.
(1) Signal arrangement
The front view shown below is that of MR-JN-20A(1) or smaller. Refer to chapter 9 DIMENSIONS for the appearances and connector layouts of the other servo amplifiers.
CNP2
1 P N C
OPC
1 N C
SON
LSP
2 N C
EM1
INP
MBR
10
12
CN1
1
2
DICOM
3
4
RES
5
6
CR
7
8
LSN
9
ALM
11
RD
DOCOM
15
LA
17
LB
19
LZ
21
OP
23
PP
25
NP
14
LG
16
LAR
18
LBR
20
LZR
22
PG
24
NG
2613
CN3 (USB connector) Refer to section 11.4.
CN2
2
LG 8
1
P5
4
MRR
3
MR
6
5
10
MDR
9
7
MD
The 3M make connector is shown. When using any other connector, refer to section 11.1.2.
AUTO
MODE
SET
CN3
The frames of the CN1 connector are connected to the PE (earth) terminal in the servo amplifier.
Signal assignments shown above are in the case of position control mode.
3 - 13
3. SIGNALS AND WIRING
(2) CN1 signal assignment
The signal assignment of connector changes with the control mode as indicated below; For the pins which are given parameter No. in the related parameter column, their signals can be changed using those parameters.
Pin No.
1 DICOM
2 OPC OPC/- -/OPC
3 I RES RES RES RES RES RES PD03 PD04
4 I SON SON SON SON SON SON PD05 PD06
5 I CR CR/SP1 SP1 SP1/SP1 SP1 SP1/CR PD07 PD08
6 I LSP LSP/ST1 ST1 ST1/RS2 RS2 RS2/LSP PD09 PD10
7 I LSN LSN/ST2 ST2 ST2/RS1 RS1 RS1/LSN PD11 PD12
8 I EM1 EM1 EM1 EM1 EM1 EM1 PD13 PD14
9 O ALM ALM ALM ALM ALM ALM PD15
10 O INP INP/SA SA SA/- -/INP PD16
11 O RD RD RD RD RD RD PD17
12 O MBR MBR MBR MBR MBR MBR PD18
13 DOCOM DOCOM DOCOM DOCOM DOCOM DOCOM
14 LG LG LG LG LG LG
15 O LA LA LA LA LA LA
16 O LAR LAR LAR LAR LAR LAR
17 O LB LB LB LB LB LB
18 O LBR LBR LBR LBR LBR LBR
19 O LZ LZ LZ LZ LZ LZ
20 O LZR LZR LZR LZR LZR LZR
21 O OP OP OP OP OP OP
22 I PG PG/- -/PG
23 I PP PP/- -/PP PD02
24 I NG NG/- -/NG
25 I NP NP/- -/NP PD02
26
Note 1. I: Input signal, O: Output signal
2. P: Position control mode, S: Internal speed control mode, T: Internal torque control mode,
P/S: Position/internal speed control change mode, S/T: Internal speed/internal torque control change mode,
T/P: Internal torque/position control change mode
(Note 1)
I/O
P P/S S S/T T T/P
(Note 2) I/O signals in control modes
DICOM DICOM DICOM DICOM DICOM
Related
parameter No.
3 - 14
3. SIGNALS AND WIRING
(3) Explanation of abbreviations
Abbreviation Signal name Abbreviation Signal name
SON Servo-on ALM Trouble
RES Reset INP In-position
PC Proportion control SA Speed reached
EM1 Forced stop MBR Electromagnetic brake interlock
CR Clear TLC Limiting torque
ST1 Forward rotation start VLC Limiting speed
ST2 Reverse rotation start WNG Warning
RS1 Forward rotation selection ZSP Zero speed
RS2 Reverse rotation selection MTTR During tough drive
TL1 Internal torque limit selection CDPS During variable gain selection
LSP Forward rotation stroke end OP Encoder Z-phase pulse (open collector)
LSN Reverse rotation stroke end LZ
SP1 Speed selection 1 LZR
SP2 Speed selection 2 LA
SP3 Speed selection 3 LAR
LOP Control change LB
CDP Gain changing LBR
PP
NP OPC Open collector power input
PG DOCOM Digital I/F common
NG LG Control common
RD Ready SD Shield
Forward/reverse rotation pulse train
DICOM Digital I/F power supply input
Encoder Z-phase pulse
(differential line driver)
Encoder A-phase pulse
(differential line driver)
Encoder B-phase pulse
(differential line driver)
3 - 15
3. SIGNALS AND WIRING

3.5 Signal explanations

POINT For the positioning mode, refer to section 13.2.3.
For the I/O interfaces (symbols in I/O division column in the table), refer to section 3.8.2. In the control mode field of the table P : Position control mode, S: Internal speed control mode, T: Internal torque control mode
: Denotes that the signal may be used in the initial setting status.
: Denotes that the signal may be used by setting the corresponding parameter No. PD02 to PD18.
The pin numbers in the connector pin No. column are those in the initial status.
(1) I/O devices
(a) Input devices
Connec-
Device Symbol
Servo-on SON CN1-4 When SON is turned on, the power is supplied to the base circuit and the
Reset RES CN1-3 When RES is turned on for 50ms or longer, an alarm can be reset.
Forward rotation
stroke end
(Note) Input device Operation
1 1
0 1
1 0
0 0
Reverse rotation
stroke end
tor pin
No.
servo amplifier is ready to operate (servo-on).
When SON is turned off, the power to the base circuit is shut off and the
servo motor coasts.
Set parameter No. PD01 to "
(keep terminals connected) automatically in the servo amplifier.
Some alarms cannot be deactivated by the reset (RES). Refer to section
8.1.
Turning RES on in an alarm-free status shuts off the base circuit. The
base circuit is not shut off when "
This device is not designed to make a stop. Do not turn it ON during
operation.
LSP CN1-6 To start operation, turn LSP/LSN on. Turn it off to bring the motor to a
sudden stop and make it servo-locked.
1 " in parameter No. PD20 to make a slow stop.
Set "
(Refer to section 4.4.2.)
LSP LSN
LSN CN1-7 Note. 0: off
1: on
When LSP or LSN turns OFF, stroke limit warning (99.
warning (WNG) turns ON. However, when using WNG, set parameter
No. PD15 to PD18 to make it usable.
In the internal speed control mode, LSP and LSN turns ON automatically
if they are not assigned to the external input signals.
Functions/Applications
4 " to switch this signal on
1 " is set in parameter No. PD20.
CCW
direction
CW
direction
) occurs, and
division
DI-1
DI-1
DI-1
I/O
Control
mode
P S T
3 - 16
3. SIGNALS AND WIRING
Connec-
Device Symbol
Internal
torque limit
selection
Note. 0: off
Forward rotation
start
Reverse rotation
start
If both ST1 and ST2 are switched on or off during operation, the servo
Forward rotation
selection
Reverse rotation
selection
Note. 0: off
TL1
ST1
ST2
RS1
RS2
tor pin
No.
The internal torque limit 2 (parameter No. PC14) becomes valid by turning
TL1 on.
The forward torque limit (parameter No. PA11) and the reverse torque
limit (parameter No. PA12) are always valid.
The smallest torque limit among the valid forward and reverse torque
limits is the actual torque limit value.
(Note)
Input device
TL1
0
1
1: on
Used to start the servo motor in any of the following directions. DI-1
Note. 0: off
(Note) Input device
ST2 ST1
0 0
0 1 CCW
1 0 CW
motor will be decelerated to a stop according to parameter No. PC02
setting and servo-locked.
When "
servo-locked after deceleration to a stop.
Used to select any of the following servo motor torque generation
directions.
Torque is not generated if both RS1 and RS2 are switched ON or OFF
during the operation.
1 1 Stop (servo lock)
1: on
1 " is set in parameter No. PC23, the servo motor is not
(Note) Input device
RS2 RS1
0 0 Torque is not generated.
0 1
1 0
1 1 Torque is not generated.
1: on
Functions/Applications
Comparison between limit
Parameter
No. PC14
Parameter
No. PC14
values
Parameter
No. PA11
>
Parameter
No. PA12
Parameter
No. PA11
<
Parameter
No. PA12
Servo motor starting direction
Stop (servo lock)
Torque generation direction
Forward rotation in driving mode / reverse rotation in regenerative mode
Reverse rotation in driving mode / forward rotation in regenerative mode
Valid torque limit value
Forward
rotation
Parameter
No. PA11
Parameter
No. PA11
Parameter
No. PC14
Reverse
rotation
Parameter
No. PA12
Parameter
No. PA12
Parameter
No. PC14
Control
I/O
division
DI-1
DI-1
mode
P S T
3 - 17
3. SIGNALS AND WIRING
Connec-
Device Symbol
Speed selection 1 SP1
Speed selection 2 SP2
Speed selection 3 SP3
Proportion control PC
Forced stop EM1 CN1-8
Clear CR CN1-5
tor pin
No.
<Internal speed control mode> Used to select the command speed for operation. (Max. 8 speeds)
(Note) Input device
SP3 SP2 SP1
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
Note. 0: off
<Internal torque control mode> Used to select the limit speed for operation. (Max. 8 speeds)
(Note) Input device
SP3 SP2 SP1
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
1 1 0
1 1 1
Note. 0: off
When PC is turned on, the type of the speed loop switches from the proportional integral type to the proportional type. If the servo motor at a stop is rotated even one pulse due to any external factor, it generates torque to compensate for a position shift. When the servo motor shaft is to be locked mechanically after positioning completion (stop), switching on the proportion control (PC) upon positioning completion will suppress the unnecessary torque generated to compensate for a position shift. In case of locking the servo motor shaft for a long time, turn on the internal torque limit selection (TL1) simultaneously with the proportion control (PC). Then, set the internal torque limit 2 (parameter No. PC14) in order to make the torque lower than the rating. When EM1 is turned off (contact between commons is opened), the servo amplifier falls in a forced stop state in which the base circuit is shut off, and the dynamic brake activates. When EM1 is turned on (contact between commons is shorted) in the forced stop state, the state can be reset. When CR is turned on, the droop pulses of the position control counter are cleared on its leading edge. The pulse width should be 10ms or more. The delay amount set in parameter No. PB03 (position command acceleration/deceleration time constant) is also cleared. When parameter No. PD22 is set to " on.
1: on
1: on
Functions/Applications
Speed command
Internal speed command 0 (parameter No. PC05)
Internal speed command 1 (parameter No. PC06)
Internal speed command 2 (parameter No. PC07)
Internal speed command 3 (parameter No. PC08)
Internal speed command 4 (parameter No. PC31)
Internal speed command 5 (parameter No. PC32)
Internal speed command 6 (parameter No. PC33)
Internal speed command 7 (parameter No. PC34)
Speed limit
Internal speed limit 0 (parameter No. PC05)
Internal speed limit 1 (parameter No. PC06)
Internal speed limit 2 (parameter No. PC07)
Internal speed limit 3 (parameter No. PC08)
Internal speed limit 4 (parameter No. PC31)
Internal speed limit 5 (parameter No. PC32)
Internal speed limit 6 (parameter No. PC33)
Internal speed limit 7 (parameter No. PC34)
1 ", the pulses are always cleared while CR is
I/O
division
DI-1
DI-1
DI-1
DI-1
DI-1
DI-1
Control
mode
P S T
3 - 18
3. SIGNALS AND WIRING
Connec-
Device Symbol
Gain changing CDP The values of the load to motor inertia moment ratio and the gains are
Control change LOP <Position/internal speed control change mode>
(Note) LOP Control mode
0 Position
1 Internal speed
Note. 0: off
<Internal speed/internal torque control change mode>
(Note) LOP Control mode
0 Internal speed
1 Internal torque
Note. 0: off
<Internal torque/position control mode>
(Note) LOP Control mode
0 Internal torque
1 Position
Note. 0: off
tor pin
No.
Functions/Applications
changed to the value set in parameter No. PB29 to PB34 by turning CDP
on.
Used to select the control mode in the position/internal speed control
change mode.
1: on
Used to select the control mode in the internal speed/internal torque
control change mode.
1: on
Used to select the control mode in the internal torque/position control
change mode.
1: on
(b) Output devices
Control mode
I/O
division
P S T
Functions/A
pplications.
DI-1
DI-1 Refer to
Connec-
Device Symbol
Trouble ALM CN1-9 ALM turns off when power is switched off or the protective circuit is
Ready RD CN1-11 RD turns on when the servo motor is ready for the operation after turning
In-position INP CN1-10 INP turns on when the number of droop pulses is in the preset in-position
tor pin
No.
Functions/Applications
activated to shut off the base circuit.
When there is no alarm, ALM turns on approximately 1s after power-on.
on the servo-on (SON).
range. The in-position range can be changed using parameter No. PA10.
When the in-position range is increased, may be kept connected during
low-speed rotation.
INP turns on when servo-on turns on.
If parameter No. PA04 is set to "
function is enabled, the INP ON time in the overload tough drive is
delayed. The delay time can be limited by parameter No. PC26.
1" and the overload tough drive
3 - 19
I/O
division
DO-1
DO-1
DO-1
Control
mode
P S T
3. SIGNALS AND WIRING
Connec-
Device Symbol
Speed reached
Limiting speed
Limiting torque
Zero speed
SA CN1-10
VLC
TLC
ZSP
tor pin
No.
Functions/Applications
SA turns on when the servo motor speed has nearly reached the preset speed. When the preset speed is 20r/min or less, SA always turns on. SA does not turn on even when the servo-on (SON) is turned off or the servo motor speed by the external force reaches the preset speed while both the forward rotation start (ST1) and the reverse rotation start (ST2) are off. VLC turns ON when the speed reaches the value limited by any of the internal speed limits 0 to 7 (parameter No. PC05 to PC08, and PC31 to PC34) in the internal torque control mode. VLC turns off when servo-on (SON) turns off.
TLC turns ON when the generated torque reaches the value set to the forward torque limit (parameter No. PA11), the reverse torque limit (parameter No. PA12) or the internal torque limit 2 (parameter No. PC14). ZSP turns on when the servo motor speed is zero speed (50r/min) or less. Zero speed can be changed using parameter No. PC10. Example Zero speed is 50r/min
I/O
division
DO-1
DO-1
DO-1
DO-1
Control
P S T
mode
Electromagnetic brake interlock
Warning
During tough drive
During variable gain selection
MBR
WNG
MTTR
CDPS
Forward rotation direction
Servo motor speed
Reverse rotation direction
Zero speed (ZSP)
ZSP turns on 1) when the servo motor is decelerated to 50r/min, and ZSP turns off 2) when the servo motor is accelerated to 70r/min again. ZSP turns on 3) when the servo motor is decelerated again to 50r/min, and turns off 4) when the servo motor speed has reached -70r/min. The range from the point when the servo motor speed has reached ON level, and ZSP turns on, to the point when it is accelerated again and has reached OFF level is called hysteresis width. Hysteresis width is 20r/min for the MR-JN-A servo amplifier. If parameter No. PA04 is set to " function is enabled, the ZSP ON time in the overload tough drive is delayed. The delay time can be limited by parameter No. PC26. MBR turns off when the servo is switched off or an alarm occurs. At an alarm occurrence, MBR turns off regardless of the base circuit status. When a warning occurs, WNG turns on. When there is no warning, WNG turns off approximately 1s after power­on. If the instantaneous power failure tough drive function selection is enabled, MTTR turns on when the instantaneous tough drive activates. If parameter No. PD20 is set to " overload tough drive activates. CDPS is on during gain changing.
OFF level 70r/min
ON level 50r/min
0r/min
ON level 50r/min
OFF level 70r/min
ON OFF
1)
3)
2)
1" and the overload tough drive
1 ", MTTR also turns on when the
4)
20r/min (Hysteresis width)
Parameter No. PC10
Parameter No. PC10
20r/min (Hysteresis width)
DO-1
DO-1
DO-1
DO-1
3 - 20
3. SIGNALS AND WIRING
(2) Input signals
Control
mode
P S T
(Note)
PP NP PG NG
Connec-
tor pin No.
CN1-23 CN1-25 CN1-22 CN1-24
Functions/Applications
Used to input command pulses.
In the open collector system (max. input frequency 200kpps) Forward rotation pulse train across PP-DOCOM Reverse rotation pulse train across NP-DOCOM In the differential receiver system (max. input frequency 1Mpps) Forward rotation pulse train across PG-PP Reverse rotation pulse train across NG-NP The command input pulse form can be changed using parameter No. PA13.
) and use it at the sink
Signal Symbol
Forward rotation pulse train Reverse rotation pulse train
Note. For the internal speed control mode or the internal torque control mode, PP or NP cannot be assigned to the CN1-23 pin or CN1-
25 pin. When assigning an input device to the CN1-23 pin or CN1-25 pin, supply OPC with 24VDC (
interface. It cannot be used at source interface.
I/O
division
DI-2
(3) Output signals
Control
mode
P S T
Signal Symbol
Encoder Z-phase pulse (Open collector)
Encoder A-phase pulse (Differential line driver) Encoder B-phase pulse (Differential line driver) Encoder Z-phase pulse (Differential line driver)
Connec-
tor pin No.
OP CN1-21 Outputs the zero-point signal of the encoder. One pulse is output per
servo motor revolution. OP turns on when the zero-point position is reached. (Negative logic) The minimum pulse width is about 400 this pulse, set the creep speed to 100r/min. or less.
LA
LAR
LB
LBR
LZ
LZR
CN1-15 CN1-16
CN1-17 CN1-18
CN1-19 CN1-20
Outputs pulses per servo motor revolution set in parameter No. PA15 in the differential line driver type. In CCW rotation of the servo motor, the encoder B-phase pulse lags the encoder A-phase pulse by a phase angle of The relationships between rotation direction and phase difference of the A- and B-phase pulses can be changed using parameter No. PC13.
The same signal as OP is output in the differential line driver type. DO-2
/2.
Functions/Applications
s. For home position return using
I/O
division
DO-2
DO-2
(4) Power supply
Signal Symbol
Digital I/F power supply input
Open collector power input Digital I/F common
Control common LG CN1-14
Shield SD Plate
DICOM CN1-1
OPC CN1-2
DOCOM CN1-13
Connec-
tor pin No.
Functions/Applications
Used to input 24VDC (200mA) for I/O interface. The power supply capacity changes depending on the number of I/O interface points to be used. For a sink interface, connect the positive terminal of the 24VDC external power supply to DICOM. For a source interface, connect the negative terminal of the 24VDC external power supply to DICOM. When inputting a pulse train in the open collector system, supply this terminal with the positive (
Common terminal for input signals such as SON and EM1. Pins are connected internally. Separated from LG. For a sink interface, connect the negative terminal of the 24VDC external power supply to DICOM. For a source interface, connect the positive terminal of the 24VDC external power supply to DICOM. Common terminal for OP.
Connect the external conductor of the shield cable.
) power of 24VDC.
I/O
division
Control
mode
P S T
3 - 21
3. SIGNALS AND WIRING

3.6 Detailed description of the signals

POINT
For the positioning mode, refer to section 13.2.4.

3.6.1 Position control mode

POINT
The noise tolerance can be enhanced by setting parameter No. PA13 to "1
200kpps or less.
(Refer to section 4.1.11)
(1) Pulse train input
(a) Input pulse waveform selection
Command pulses may be input in any of three different forms, for which positive or negative logic can be chosen. Set the command input pulse form in parameter No. PA13. Refer to section 4.1.11 for details.
(b) Connections and waveforms
1) Open collector system Connect as shown below.
" when the command pulse frequency is 500kpps or less or "2 " when
Servo amplifier
24VDC
(Note)
OPC
DOCOM
PP
NP
SD
Approx.
1.2k
Approx.
1.2k
Note. Pulse train input interface is comprised of a photo coupler.
Therefore, it may be any malfunctions since the current is reduced when connect a
resistance to a pulse train signal line.
The explanation assumes that the input waveform has been set to the negative logic and forward and reverse rotation pulse trains (parameter No. PA13 has been set to "
10 "). Their relationships with
transistor ON/OFF are as follows.
Forward rotation pulse train (transistor)
Reverse rotation pulse train (transistor)
(ON) (ON)
(ON)
(OFF) (OFF)
(OFF)
(OFF)
(ON) (OFF) (ON) (OFF) (ON)
Reverse rotation commandForward rotation command
3 - 22
3. SIGNALS AND WIRING
2) Differential line driver type Connect as shown below.
Note. Pulse train input interface is comprised of a photo coupler.
The explanation assumes that the input waveform has been set to the negative logic and forward and reverse rotation pulse trains (parameter No. PA13 has been set to " The waveforms of PP, PG, NP and NG are based on that of the ground of the differential line driver.
Servo amplifier
Approx.
PP
100
PG
(Note)
NP
NG
SD
Approx. 100
Therefore, it may be any malfunctions since the current is reduced when connect a
resistance to a pulse train signal line.
10 ").
Forward rotation pulse train
PP
PG
Reverse rotation pulse train
NP
NG
Forward rotation command
Reverse rotation command
(2) In-position (INP)
INP turns on when the number of droop pulses in the deviation counter falls within the preset in-position range (parameter No. PA10). INP turns on when low-speed operation is performed with a large value set as the in-position range.
Servo-on (SON)
ON
OFF
Alarm
Droop pulses
In-position (INP)
Yes
No
ON
OFF
In-position range
3 - 23
3. SIGNALS AND WIRING
(3) Ready (RD)
Servo-on (SON)
ON
OFF
Alarm
Ready (RD)
(4) Torque limit
CAUTION
(a) Torque limit and torque
By setting parameter No. PA11 (forward torque limit) or parameter No. PA12 (reverse torque limit), torque is always limited to the maximum value during operation. A relationship between the limit value and servo motor torque is shown below.
Yes
No
10ms or less
ON
OFF
100ms or less
10ms or less
If the torque limit is canceled during servo lock, the servo motor may suddenly rotate according to position deviation in respect to the command position.
When using the torque limit, check that load to motor inertia moment ratio (parameter No. PB06) is set properly. Improper settings may cause an unexpected operation such as an overshoot.
Max. torque
Torque
Forward rotation (CCW) directionReverse rotation (CW) direction
(b) Torque limit value selection
As shown below, the internal torque limit selection (TL1) can be used for selecting the torque limit between the forward torque limit (parameter No. PA11) or the reverse torque limit (parameter No. PA12) and the internal torque limit 2 (parameter No. PC14). However, if the value of parameter No. PA11 or parameter No. PA12 is lower than the limit value selected by TL1, the value of parameter No. PA11 or parameter No. PA12 is made valid.
(Note) Input
device
TL1
0 Parameter No. PA11 Parameter No. PA12
Parameter No. PC14
1
Parameter No. PC14
Note. 0: off
1: on
100
Torque limit value in parameter No. PA12
Limit value status
Parameter No. PA11 Parameter No. PA12 Parameter No. PA11 Parameter No. PA12
0100
Torque limit value in parameter No. PA11
Forward rotation (CCW)
Reverse rotation (CW)
regeneration
Parameter No. PA11 Parameter No. PA12
Parameter No. PC14 Parameter No. PC14
[%]
Validated torque limit values
driving
Reverse rotation (CW)
driving
Forward rotation (CCW)
regeneration
3 - 24
3. SIGNALS AND WIRING
(c) Limiting torque (TLC)
TLC turns on when the servo motor torque reaches the torque limited by the forward torque limit, the reverse torque limit or the internal torque limit 2.

3.6.2 Internal speed control mode

(1) Internal speed command settings
(a) Speed command and speed
The servo motor operates at the speed set in the parameters. Up to 8 speeds can be set to the internal speed command. The following table indicates the rotation direction according to forward rotation start (ST1) and reverse rotation start (ST2) combination.
(Note 1) Input device
ST2 ST1
0 0
0 1 Forward rotation (CCW)
1 0 Reverse rotation (CW)
1 1
Note 1. 0: off
1: on
2. If the torque limit is canceled during servo lock, the servo
motor may suddenly rotate according to position deviation
in respect to the command position.
Connect the wirings as follows when operating in forward or reverse rotation with the internal speed command set to the eighth speed.
(Note 2) Rotation direction
Stop
(Servo lock)
Stop
(Servo lock)
Forward rotation (CCW)
Servo amplifier
Reverse rotation (CW)
ST1 ST2
SP1
(Note 1)
24VDC
Note 1. For sink I/O interface. For source I/O interface, refer to section 3.8.3.
2. Set the input devices by parameter No. PD02 to PD14.
SP2 SP3
DOCOM
DICOM
(Note 2)
3 - 25
3. SIGNALS AND WIRING
POINT
The servo-on (SON) can be set to turn on automatically by parameter No.
PD01 (input signal automatic ON selection 1).
The forward rotation stroke end (LSP) and the reverse rotation stroke end
(LSN) switches as follows:
Assigned to the external input signals: depends on the value set in parameter No. PD01.
Not assigned to the external input signals: automatically turns on regardless of the value set in parameter No. PD01.
If parameter No. PC23 (function selection C-2) is set to " 0 " (initial
value), the servo motor is servo-locked regardless of the deceleration time constant when the zero speed (ZSP) turns on.
(b) Speed selection 1 (SP1) and speed command value
At the initial condition, the speed command values for the internal speed command 0 and 1 can be selected using the speed selection 1 (SP1).
(Note) Input device
SP1
0 Internal speed command 0 (parameter No. PC05)
1 Internal speed command 1 (parameter No. PC06)
Note. 0: off
1: on
Speed command value
By making the speed selection 2 (SP2) and the speed selection 3 (SP3) usable by setting of parameter No.PD02 to PD14, the speed command values for the internal speed commands 0 to 7 can be selected.
(Note) Input device
SP3 SP2 SP1
0 0 0 Internal speed command 0 (parameter No. PC05)
0 0 1 Internal speed command 1 (parameter No. PC06)
0 1 0 Internal speed command 2 (parameter No. PC07)
0 1 1 Internal speed command 3 (parameter No. PC08)
1 0 0 Internal speed command 4 (parameter No. PC31)
1 0 1 Internal speed command 5 (parameter No. PC32)
1 1 0 Internal speed command 6 (parameter No. PC33)
1 1 1 Internal speed command 7 (parameter No. PC34)
Note. 0: off
1: on
Speed command value
The speed may be changed during rotation. In this case, the values set in parameters No. PC01 and PC02 are used for acceleration/deceleration.
When the speed has been specified under any internal speed command, it does not vary due to the ambient temperature.
3 - 26
3. SIGNALS AND WIRING
(2) Speed reached (SA)
SA turns on when the servo motor speed has nearly reached the speed set to the internal speed command.
Internal speed
Set speed selection
Forward rotation/ reverse rotation start (ST1/ST2)
Servo motor speed
ON OFF
Internal speed
command 1
command 2
(3) Torque limit
As in section 3.6.1 (4).
Speed reached (SA)
ON OFF
3 - 27
)
3. SIGNALS AND WIRING

3.6.3 Internal torque control mode

(1) Internal torque command settings
Torque is controlled by the internal torque command set in parameter No. PC12. If the internal torque command is small, the torque may vary when the actual speed reaches the speed limit value. In such case, increase the speed limit value. The following table indicates the torque generation directions determined by the forward rotation selection (RS1) and the reverse rotation selection (RS2) when the internal torque command (parameter No. PC12) is used.
(Note) Input device Rotation direction
RS2 RS1
Internal torque command (parameter No. PC12)
0.1 to 100.0% 0.0%
Forward rotation (CCW)
0
0 1
1 0
1 1 Torque is not generated.
Note. 0: off
1: on
Torque is not generated.
0
CCW (reverse rotation in driving
mode/forward rotation in
regenerative mode)
CW (forward rotation in driving
mode/reverse rotation in
regenerative mode)
Torque is not
generated.
Generally, make connection as shown below.
Servo amplifier
RS1
(Note)
24VDC
RS2
DOCOM
DICOM
Note. For sink I/O interface. For source I/O interface, refer to section 3.8.3.
The following shows the effect of the low-pass filter on the internal torque command.
Forward rotation/reverse rotation selection
(RS1/RS2)
Torque
ON OFF
Internal torque command (parameter No. PC12)
Internal torque command after filtered
Reverse rotation (CW)
Torque command time constant (parameter No. PC04
(2) Torque limit
By setting parameter No. PA11 (forward torque limit) or parameter No. PA12 (reverse torque limit), torque is always limited to the maximum value during operation. A relationship between limit value and servo motor torque is as in section 3.6.1 (4).
3 - 28
3. SIGNALS AND WIRING
(3) Speed limit
(a) Speed limit value and speed
The speed is limited to the values set in parameters No. PC05 to PC08 and PC31 to PC34 (Internal speed limit 0 to 7).
When the servo motor speed reaches the speed limit value, the internal torque control may become unstable. Make the set value more than 100r/min greater than the desired speed limit value.
The following table indicates the limit direction according to forward rotation selection (RS1) and reverse rotation selection (RS2) combination.
(Note) Input device
RS1 RS2
1 0 Forward rotation (CCW)
0 1 Reverse rotation (CW)
Note. 0: off
1: on
Speed limit direction
Forward rotation (CCW)
Reverse rotation (CW)
Connect the wirings as follows when setting the internal speed limit to the eighth speed.
Servo amplifier
RS1 RS2
SP1
(Note 1)
24VDC
SP2 SP3
DOCOM
DICOM
(Note 2)
Note 1. For sink I/O interface. For source I/O interface, refer to section 3.8.3.
POINT
2. Set the input devices by parameter No. PD02 to PD14.
The servo-on (SON), the forward rotation stroke end (LSP), and the reverse
rotation stroke end (LSN) can be set to turn on automatically by parameter No. PD01 (input signal automatic ON selection 1).
3 - 29
3. SIGNALS AND WIRING
(b) Speed selection 1 (SP1) and speed limit values
At the initial condition, the speed limit values for the internal speed limits 0 and 1 can be selected using the speed selection 1 (SP1).
(Note) Input device
SP1
0 Internal speed limit 0 (parameter No. PC05)
1 Internal speed limit 1 (parameter No. PC06)
Note. 0: off
1: on
Speed limit value
By making the speed selection 2 (SP2) and the speed selection 3 (SP3) usable by setting parameter No.PD02 to PD14, the speed limit values for the internal speed limit 0 to 7 can be selected.
(Note) Input device
SP3 SP2 SP1
0
0 0 1 Internal speed limit 1 (parameter No. PC06)
0 1 0 Internal speed limit 2 (parameter No. PC07)
0 1 1 Internal speed limit 3 (parameter No. PC08)
1 0 0 Internal speed limit 4 (parameter No. PC31)
1 0 1 Internal speed limit 5 (parameter No. PC32)
1 1 0 Internal speed limit 6 (parameter No. PC33)
1 1 1 Internal speed limit 7 (parameter No. PC34)
Note. 0: off
1: on
0 0
Internal speed limit 0 (parameter No. PC05)
When the speed is limited by the internal speed limits 0 to 7, the speed does not vary with the ambient temperature.
(c) Limiting speed (VLC)
VLC turns on when the servo motor speed reaches the speed limited by the internal speed limits 0 to 7.
Speed limit value
3 - 30
3. SIGNALS AND WIRING

3.6.4 Position/speed control change mode

Set parameter No. PA01 to "
1 " to switch to the position/internal speed control change mode.
(1) Control change (LOP)
By using the control change (LOP), control mode can be switched between the position control and the internal speed control modes from an external contact. Relationships between LOP and control modes are indicated below.
(Note) LOP Control mode
0 Position control mode
1 Internal speed control mode
Note. 0: off
1: on
The control mode may be switched in the zero speed status. To ensure safety, switch the control mode after the servo motor has stopped. When the control mode is switched to the internal speed control mode from the position control mode, droop pulses are cleared. Even if the speed is decreased to the zero speed or below after switching LOP, the control mode cannot be switched. A change timing chart is shown below.
Servo motor speed
Position
control mode
Zero speed level
Internal speed
control mode
Position
control mode
Zero speed (ZSP)
Control change (LOP)
Note. When ZSP is not on, control cannot be changed if LOP is switched on-off.
If ZSP switches on after that, control cannot be changed.
ON
OFF
ON
OFF
(2) Torque limit in position control mode
As in section 3.6.1 (4).
(3) Speed setting in internal speed control mode
As in section 3.6.2 (1).
(4) Speed reached (SA)
As in section 3.6.2 (2).
(Note)
(Note)
3 - 31
3. SIGNALS AND WIRING

3.6.5 Internal speed/internal torque control change mode

Set No. PA01 to "
3 " to switch to the internal speed/internal torque control change mode.
(1) Control change (LOP)
By using the control change (LOP), the control mode can be switched between the internal speed control and the internal torque control mode from an external contact. Relationships between LOP and control modes are indicated below.
(Note) LOP Servo control mode
0 Internal speed control mode
1 Internal torque control mode
Note. 0: off
1: on
The control mode may be changed at any time. A change timing chart is shown below.
Internal speed
control mode
Control change (LOP)
Internal torque command (parameter No. PC12)
Servo motor speed
Internal speed
control mode
ON
OFF
Internal torque
control mode
Note. When the start (ST1, ST2) is switched off as soon as the mode is changed to internal speed control,
the servo motor comes to a stop according to the deceleration time constant.
(2) Speed setting in internal speed control mode
As in section 3.6.2 (1).
(3) Torque limit in internal speed control mode
As in section 3.6.1 (4).
(4) Speed limit in internal torque control mode
As in section 3.6.3 (3).
(5) Internal torque control setting in internal torque control mode
As in section 3.6.3 (1).
(6) Torque limit in internal torque control mode
As in section 3.6.3 (2).
(Note)
3 - 32
3. SIGNALS AND WIRING

3.6.6 Internal torque/position control change mode

Set parameter No. PA01 to "
5 " to switch to the internal torque/position control change mode.
(1) Control change (LOP)
By using the control change (LOP), the control mode can be switched between the internal torque control and the position control modes from an external contact. Relationships between LOP and control modes are indicated below.
(Note) LOP Servo control mode
0 Internal torque control mode
1 Position control mode
Note. 0: off
1: on
The control mode may be switched in the zero speed status. To ensure safety, switch the control mode after the servo motor has stopped. When the control mode is switched to the internal torque control mode from the position control mode, droop pulses are cleared. Even if the speed is decreased to the zero speed or below after switching LOP, the control mode cannot be switched. A change timing chart is shown below.
Internal torque
control mode
Position
control mode
Servo motor speed
Position
control mode
Zero speed level
Internal torque command (parameter No. PC12)
Zero speed (ZSP)
Control change (LOP)
ON
OFF
ON
OFF
(2) Speed limit in internal torque control mode
As in section 3.6.3 (3).
(3) Internal torque control setting in internal torque control mode
As in section 3.6.3 (1).
(4) Torque limit in internal torque control mode
As in section 3.6.3 (2).
(5) Torque limit in position control mode
As in section 3.6.1 (4).
3 - 33
3. SIGNALS AND WIRING

3.7 Alarm occurrence timing chart

When an alarm has occurred, remove its cause, make sure that the operation signal is not being input, ensure safety, and reset the alarm before restarting
CAUTION
operation.
As soon as an alarm occurs, turn off servo-on (SON) and power off.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a stop. Switch off the main circuit power supply in the external sequence. To reset the alarm, switch the control circuit power supply from off to on, press the " SET " button on the current alarm screen, or turn the reset (RES) from off to on. However, the alarm cannot be reset unless its cause is removed.
(Note 1) Main circuit
Base circuit
Dynamic brake
Servo-on (SON)
Ready (RD)
Trouble (ALM)
Reset (RES)
Note 1. Shut off the main circuit power as soon as an alarm occurs.
2. Changes depending on the operating status.
ON
OFF
ON
OFF
Valid
Invalid
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Brake operation
1s
Alarm occurs.
Remove cause of trouble.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent (32. overload 1 (50. ) or overload 2 (51. ) alarm after its occurrence, without removing its cause, the servo amplifier and servo motor may become faulty due to temperature rise. Securely remove the cause of the alarm and also allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative (30.
) alarm after its occurrence, the regenerative resistor will generate heat, resulting in an accident.
(3) Instantaneous power failure
If power failure has occurred in the control circuit power supply, undervoltage (10.1) occurs when the power is recovered.
(4) In-position control mode
Once an alarm occurs, the servo motor command rejects the command pulse. When resuming the operation after resetting the alarm, make a home position return.
50ms or more
Power off
Brake operation
15 to 60ms or more (Note 2)
Power on
),
3 - 34
3. SIGNALS AND WIRING

3.8 Interfaces

3.8.1 Internal connection diagram

(Note
3)
(Note 2, 4)
24VDC
USB
(Note 1)
PST SON SON SON RES RES RES 3 EM1 EM1 EM1 8
LSP ST1 6
LSN ST2 7
CR 5
SP1
OPC 2
DOCOM PP 23 PG 22 NP 25 NG 24
(Note 1)
PST
CP/CL
SON MD0 EM1
ST1
RS2
ST2
RS1
DI0
SP1
OPC
DICOM
DI1
DOG
CP/CL
VBUS 1
D-
D+
GND
CN1
Approx. 5.6k
4
Approx. 5.6k
1
13
Approx. 100
Approx. 100 Approx. 1.2k
CN3
2 3 5
Approx. 1.2k
Servo amplifier
<Isolated>
(Note 1)
PS
CN1
ALM ALM
9
INP
10
11
RD
RD
12
MBRSAMBR MBR
(Note 1)
CN1 P S T
15 16 17 18 19 20 21 14
CN2 P S T
7 8 3 4 2
CNP1
LA
LAR
LB
LBR
LZ
LZR
OP LG
(Note 1)
MD
MDR
MR
MRR
LG
T
ALM
RD
CP/CL
ALM
INP
RD
MBR
CP/CL
CP/CL
E
RA
(Note
3)
RA
Differential line driver output (35mA or less)
Open collector output
Servo motor
Encoder
M
Note 1. P: Position control mode, S: Internal speed control mode, T: Internal torque control mode
CP: Positioning mode (Point table method) CL: Positioning mode (Program method)
2. This diagram is for the open collector pulse train input. When inputting the differential line driver pulse train in the position control mode, make the following connection.
DOC 46
24VDC
OPC 2
DICOM
DOCOM
1
13 PP 23 PG 22 NP 25
NG 24
3. For sink I/O interface. For source I/O interface, refer to section 3.8.3.
4. When assigning the input device to the CN1-23 pin or CN1-25 pin in the internal speed control mode, internal torque control mode, or positioning mode, use it at sink input interface. It cannot be used at source input interface. For the positioning mode, the input devices (DI1, DOG) are assigned to the initial values.
3 - 35
A
3. SIGNALS AND WIRING

3.8.2 Detailed description of interfaces

This section provides the details of the I/O signal interfaces (refer to the I/O division in the table) given in section 3.5. Refer to this section and make connection with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor. The following figure is for sink input. Refer to section
3.8.3 for source input.
For transistor
Approx. 5mA
TR
CES 1.0V
V
100
I
CEO
Switch
24VDC 10% 200mA
Servo amplifier
SON,
Approx. 5.6k
etc.
DICOM
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Install a diode (D) for an inductive load, or install an inrush current suppressing resistor (R) for a lamp load. (Rated current: 40mA or less, maximum current: 50mA or less, inrush current: 100mA or less) A maximum of 2.6V voltage drop occurs in the servo amplifier. The following figure is for the sink output. Refer to section 3.8.3 for the source output.
Servo amplifier
If polarity of diode is reversed, servo
ALM, etc.
DOCOM
(Note) 24VDC 10% 200mA
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high
voltage (maximum of 26.4V) from external source.
Load
amplifier will fail.
3 - 36
3. SIGNALS AND WIRING
(3) Pulse train input interface DI-2
Give a pulse train signal in the open collector system or differential line driver type.
(a) Open collector system
1) Interface
Servo amplifier
Max. input pulse frequency 200kpps
Approx. 1.2k
(Note)
24VDC
2m or less
OPC
PP, NP
DOCOM
SD
Note. Pulse train input interface is comprised of a photo coupler.
Therefore, it may be any malfunctions since the current is reduced when connect a
resistance to a pulse train signal line.
2) Input pulse condition
tHL
PP
NP
0.9
0.1
tc
tc tLH
tF
tLH=tHL<0.2 s tc>2 s tF>3 s
(b) Differential line driver type
1) Interface
Servo amplifier
Max. input pulse
10m or less
(Note)
Am26LS31 or equivalent
VOH: 2.5V
OL
: 0.5V
V
Note. Pulse train input interface is comprised of a photo coupler.
Therefore, it may be any malfunctions since the current is reduced when connect a
resistance to a pulse train signal line.
frequency 1Mpps
PP(NP)
Approx. 100
PG(NG)
SD
3 - 37
3. SIGNALS AND WIRING
2) Input pulse condition
PP PG
0.9
0.1
tHL
tc
tLH=tHL<0.1 s tc>0.35 s tF>3 s
NP NG
(4) Encoder output pulse DO-2
(a) Open collector system
Interface Max. output current: 35mA
Servo amplifier
OP
LG
SD
tc tLH
tF
Servo amplifier
OP
LG
SD
5 to 24VDC
Photocoupler
(b) Differential line driver type
1) Interface Max. output current: 35mA
Servo amplifier Servo amplifier
LA (LB, LZ)
LAR (LBR, LZR)
LG
SD
Am26LS32 or equivalent
150
LA (LB, LZ)
LAR (LBR, LZR)
SD
100
High-speed photocoupler
3 - 38
A
3. SIGNALS AND WIRING
2) Output pulse
Servo motor CCW rotation
LA
LAR
LB
LBR
LZ
LZR
OP
T
/2
400 s or more
Time cycle (T) is determined by the settings of parameter No.PA15 and PC13.

3.8.3 Source I/O interfaces

In this servo amplifier, source type I/O interfaces can be used. In this case, all DI-1 input signals and DO-1 output signals are of source type. Perform wiring according to the following interfaces.
(1) Digital input interface DI-1
Servo amplifier
SON,
Approx. 5.6k
etc.
Switch
Approx. 5mA
V
CES 1.0V
100
I
CEO
24VDC 10% 200mA
(2) Digital output interface DO-1
A maximum of 2.6V voltage drop occurs in the servo amplifier.
Servo amplifier
ALM, etc.
DOCOM
(Note)
Note. If the voltage drop (maximum of 2.6V) interferes with the relay operation, apply high voltage
(maximum of 26.4V) from external source.
Load
24 VDC ± 10% 200 mA
DICOM
If polarity of diode is reversed, servo amplifier will fail.
3 - 39
3. SIGNALS AND WIRING

3.9 Treatment of cable shield external conductor

In the case of the CN1 and CN2 connectors, securely connect the shielded external conductor of the cable to the ground plate as shown in this section and fix it to the connector shell.
SheathExternal conductor
Strip the sheath.
(1) For CN1 connector (3M connector)
Ground plate
Screw
Screw
Cable
Core
External conductor
Pull back the external conductor to cover the sheath.
Sheath
(2) For CN2 connector (3M or Molex connector)
Ground plate
Cable
Screw
3 - 40
3. SIGNALS AND WIRING

3.10 Connection of servo amplifier and servo motor

Connect the servo amplifier power output (U/V/W) to the servo motor power input
CAUTION
(U/V/W) directly. Do not connect a magnetic contactor and others between them. Otherwise, it may cause a malfunction.

3.10.1 Connection instructions

WARNING
To avoid an electric shock, insulate the connections of the power supply terminals.
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier and servo motor. Not doing so may cause unexpected operation.
Do not connect AC power supply directly to the servo motor. Otherwise, a fault
CAUTION
may occur.
Do not use the 24VDC interface and control circuit power supplies for the electromagnetic brake. Always use the power supply designed exclusively for the electromagnetic brake. Otherwise, a fault may occur.
POINT
Refer to section 11.1 for the selection of the encoder cable.
This section indicates the connection of the servo motor power supply (U, V, W). Use of the optional cable or the connector set is recommended for connection between the servo amplifier and the servo motor. Refer to section 11.1 for details of the options.
For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal of the servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo
amplifier
PE terminal
Servo motor
3 - 41
3. SIGNALS AND WIRING

3.10.2 Power supply cable wiring diagrams

(1) HF-KN series
HF-KP G1/G5/G7 HG-KR G1/G5/G7 servo motor
(a) When cable length is 10m or less
Servo amplifier
(b) When cable length exceeds 10m
When the cable length exceeds 10m, fabricate an extension cable as shown below. In this case, the motor power supply cable should be within 2m long. Refer to section 11.5 for the wire used for the extension cable.
Servo amplifier
CNP1
U
V
W
CNP1
U V
W
50m or less
Extension cable
10m or less
MR-PWS1CBL M-A1-L MR-PWS1CBL M-A2-L MR-PWS1CBL M-A1-H MR-PWS1CBL M-A2-H
AWG 19(red) AWG 19(white) AWG 19(black) AWG 19(green/yellow)
MR-PWS1CBL2M-A1-L MR-PWS1CBL2M-A2-L MR-PWS1CBL2M-A1-H MR-PWS1CBL2M-A2-H MR-PWS2CBL03M-A1-L MR-PWS2CBL03M-A2-L
AWG 19(red) AWG 19(white) AWG 19(black) AWG 19(green/yellow)
Servo motor
W
2m or less
U V
M
Servo motor
U V
M
W
(Note) a) Relay connector for extension cable
Note. Use of the following connectors is recommended when ingress protection (IP65) is necessary.
(Note) b) Relay connector for motor power supply cable
Relay connector
a) Relay connector for extension cable
b) Relay connector for motor power supply cable
Connector: RM15WTPZ-4P(71) Cord clamp: JR13WCC-5(72) (Hirose Electric)
Connector: RM15WTJZ-4S(81) Cord clamp: JR13WCC-8(72) (Hirose Electric)
Description IP rating
IP65
Numeral changes depending on the cable OD.
IP65
Numeral changes depending on the cable OD.
3 - 42
3. SIGNALS AND WIRING

3.11 Servo motor with an electromagnetic brake

3.11.1 Safety precautions

Configure an electromagnetic brake operation circuit which interlocks with an external emergency stop switch.
CAUTION
Shut off the servo motor when Servo-on (SON), Malfunction (ALM), or Electromagnetic brake interlock (MBR) are turned OFF.
Servo motor
B
Electromagnetic brake
SON RA
Circuit must be opened with the emergency stop switch.
24VDC
The electromagnetic brake is provided for holding purpose and must not be used for ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake operates properly.
Do not use the 24VDC interface and control circuit power supplies for the electromagnetic brake. Always use the power supply designed exclusively for the electromagnetic brake. Otherwise, a fault may occur.
POINT
Refer to chapter 12 for specifications such as the power supply capacity and operation delay time of the electromagnetic brake.
Switch off the servo-on (SON) after the servo motor has stopped.
Refer to (3) in section 12.1.3 for the selection of the surge absorbers for the electromagnetic brake.
Note the following when the servo motor with an electromagnetic brake is used.
1) Always assign the electromagnetic brake interlock (MBR) to CN1-12 pin by parameter No. PD18. (MBR is assigned to CN1-12 pin by default.)
2) The electromagnetic brake operates when the power (24VDC) turns off.
3) While the reset (RES) is on, the base circuit is shut off. When using the servo motor with a vertical shaft, use the electromagnetic brake interlock (MBR).

3.11.2 Setting

(1) Set "
05 " to parameter No. PD18 to assign the electromagnetic brake interlock (MBR) to CN1-12 pin.
(2) Using parameter No. PC09 (electromagnetic brake sequence output), set a time delay (Tb) at servo-off
from electromagnetic brake operation to base circuit shut-off as in the timing chart shown in section
3.11.3 (1).
3 - 43
3. SIGNALS AND WIRING

3.11.3 Timing charts

(1) Servo-on (SON) command (from controller) ON/OFF
Tb [ms] after the servo-on (SON) signal is switched off, the servo lock is released and the servo motor coasts. If the electromagnetic brake is made valid in the servo lock status, the brake life may be shorter. Therefore, when using the electromagnetic brake in a vertical lift application or the like, set Tb to about the same as the electromagnetic brake operation delay time to prevent a drop.
Servo motor speed
Base circuit
Electromagnetic brake interlock (MBR)
Servo-on (SON)
Position command (Note 4)
Electromagnetic brake
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. Electromagnetic brake is released after delaying for the release delay time of electromagnetic brake and operation time of
external circuit relay. For the release delay time of electromagnetic brake, refer to section 12.5.3, 12.6.3.
3. Give a position command after the electromagnetic brake is released.
4. For the position control mode.
0 r/min
ON
OFF
(Note 1) ON
OFF
ON
OFF
0 r/min
Release
Activate
(95ms)
(95ms)
(Note 3)
Release delay time and external relay (Note 2)
Coasting
Tb
Electromagnetic brake sequence output (parameter No. PC09)
Electromagnetic brake operation delay time
(2) Forced stop (EM1) ON/OFF
Deceleration starts after the forced stop (EM1) turns OFF. (Note 2)
Dynamic brake
Dynamic brake
Servo motor speed
Base circuit
Electromagnetic brake interlock (MBR)
ON
OFF
(Note 1) ON
OFF
(10ms)
Tb
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake sequence
output (parameter No. PC09)
Electromagnetic brake operation delay time
Electromagnetic brake release
(210ms)
(210ms)
Forced stop (EM1)
Invalid (ON)
Valid (OFF)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. The operation differs from the timing chart of MR-J3-
A servo amplifier.
3 - 44
3. SIGNALS AND WIRING
(3) Alarm occurrence
Dynamic brake
Dynamic brake
Servo motor speed
(10ms)
Base circuit (Note 1)
Electromagnetic brake interlock (MBR)
Trouble (ALM)
Note 1. Electromagnetic brake sequence output (parameter No. PC09) is invalid.
2. ON: Electromagnetic brake is not activated.
(Note 2)
OFF: Electromagnetic brake is activated.
ON
OFF
ON
OFF
No (ON)
Yes (OFF)
Electromagnetic brake
Electromagnetic brake
Electromagnetic brake operation delay time
(4) Both main and control circuit power supplies off
(10ms)
Servo motor speed
(Note 1)
Base circuit
10 to 60ms
ON
OFF
Dynamic brake
Dynamic brake Electromagnetic brake
Electromagnetic brake
Electromagnetic brake interlock (MBR)
Trouble (ALM)
Main circuit
Control circuit
Note 1. Changes with the operating status.
(Note 2)
ON
OFF
No (ON)
Yes (OFF)
power supply
2. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
ON
OFF
Electromagnetic brake operation delay time
3 - 45
3. SIGNALS AND WIRING
(5) Only main circuit power supply off (control circuit power supply remains on)
Deceleration starts after the trouble (ALM) turns OFF. (Note 2)
Dynamic brake
Dynamic brake Electromagnetic brake
Electromagnetic brake
Servo motor speed
(10ms)
Base circuit
Electromagnetic brake interlock (MBR)
Trouble (ALM)
Main circuit power supply
ON
OFF
ON
(Note 1)
OFF
No (ON)
Yes (OFF)
ON
OFF
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. The operation differs from the timing chart of MR-J3-
3.11.4 Wiring diagrams (HF-KN series
(1) When cable length is 10m or less
24VDC power supply for electromagnetic brake
(Note 3)
Electromagnetic
brake interlock
(MBR)
Electromagnetic brake sequence output (parameter No. PC09)
Electromagnetic brake operation delay time
10 to 60ms
A servo amplifier.
HF-KP G1/G5/G7 HG-KR G1/G5/G7 servo motor)
10m or less
MR-BKS1CBL M-A1-L MR-BKS1CBL M-A2-L
Trouble
(ALM)
(Note 5) RA
(Note 1)
MR-BKS1CBL M-A1 -H MR-BKS1CBL M- A2-H
AWG20
U
AWG20
Servo motor
(Note 2)
B1
B
B2
Note 1. Connect a surge absorber as close to the servo motor as possible.
2. There is no polarity in electromagnetic brake terminals (B1 and B2).
3. When using a servo motor with an electromagnetic brake, always assign the electromagnetic brake
interlock (MBR) to CN1-12 pin by parameter No. PD18.
4. Do not use the 24VDC interface power supply for the electromagnetic brake.
5. Switch off the circuit interlocking with the emergency stop switch.
When fabricating the motor brake cable MR-BKS1CBL
M-H, refer to section 11.1.4.
3 - 46
3. SIGNALS AND WIRING
(2) When cable length exceeds 10m
When the cable length exceeds 10m, fabricate an extension cable as shown below on the customer side. In this case, the motor brake cable should be within 2m long. Refer to section 11.5 for the wire used for the extension cable.
2m or less
MR-BKS1CBL2M-A1-L MR-BKS1CBL2M-A2-L MR-BKS1CBL2M-A1-H MR-BKS1CBL2M-A2-H MR-BKS2CBL03M-A1-L MR-BKS2CBL03M-A2-L
U
AWG20
AWG20
Servo motor
(Note 3)
B1
B
B2
(Note 5)
24VDC power supply for
electromagnetic brake
(Note 4)
Electromagnetic
brake interlock
(MBR)
50m or less
Extension cable (To be fabricated)
Trouble
(ALM)
(Note 6)
RA
(Note 1)
Note 1. Connect a surge absorber as close to the servo motor as possible.
Relay connector
a) Relay connector for extension cable
b) Relay connector for motor brake cable
(Note 2) a) Relay connector for extension cable
2. Use of the following connectors is recommended when ingress protection (IP65) is necessary.
Description
CM10-CR2P­(DDK)
(DDK)
3. There is no polarity in electromagnetic brake terminals (B1 and B2).
4. When using a servo motor with an electromagnetic brake, always assign the electromagnetic brake interlock (MBR)
to CN1-12 pin by parameter No. PD18.
5. Do not use the 24VDC interface power supply for the electromagnetic brake.
6. Switch off the circuit interlocking with the emergency stop switch.
Wire size: S, M, L
Wire size: S, M, L
(Note 2) b) Relay connector for motor brake cable
IP65
IP65CM10-SP2S-
IP rating
3 - 47
x
3. SIGNALS AND WIRING

3.12 Grounding

Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth (PE) terminal
WARNING
(terminal marked
) of the servo amplifier with the protective earth (PE) of the
control box.
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always ground. To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB(NA)67310).
Control bo
(Note) Main circuit power supply
MCCB
Line filter
(Note) Control circuit power supply
Circuit protector
MC
Servo amplifier
L
1
L2
+24V
0V
CN1
logiccontroller
Programmable
Servo motor
CN2
Encoder
U
V
W
Ensure to connect it to PE terminal of the servo amplifier. Do not connect it directly to the protective earth of the control panel.
U
M
V W
Outer
Protective earth (PE)
box
Note. For the specification of power supply, refer to section 1.3.
3 - 48

4. PARAMETERS

4. PARAMETERS
Never make a drastic adjustment or change to the parameter values, as doing so will make the operation unstable. Do not change the parameter settings as described below. Doing so may cause an
CAUTION
In this servo amplifier, the parameters are classified into the following groups on a function basis.
Parameter group Main description
Basic setting parameters
(No. PA
Gain/filter parameters
(No. PB
Extension setting parameters
(No. PC
I/O setting parameters
(No. PD
Positioning setting parameters
(No. PE
When using this servo in the position control mode, mainly setting the basic setting parameters (No. PA ) allows the setting of the basic parameters at the time of introduction.
)
)
)
)
)
unexpected condition, such as failing to start up the servo amplifier.
Changing the values of the parameters for manufacturer setting. Setting out-of-range values. Changing the fixed values in the digits of a parameter.
POINT For the positioning mode, refer to section 13.7. Positioning mode is supported by servo amplifier with software version B0 or later.
Make basic setting with these parameters when using this servo amplifier in the position control
mode.
Use these parameters when making gain adjustment manually.
Use these parameters mainly when using this servo amplifier in the internal speed control mode or
in the internal torque control mode.
Use these parameters when changing the I/O signals of the servo amplifier.
Use these parameters only for the positioning mode.
(Refer to section 13.7.5.)
4 - 1
4. PARAMETERS
4.1 Basic setting parameters (No. PA
)
POINT For any parameter whose symbol is preceded by *, set the parameter value and switch power off once, then switch it on again to make that parameter setting valid.
Never change parameters for manufacturer setting.

4.1.1 Parameter list

No. Symbol Name
PA01 *STY Control mode 000h
PA02 *REG Regenerative option 000h
PA03
PA04 *AOP1 Tough drive function selection 000h
PA05 *FBP Number of command input pulses per revolution
PA06 CMX
PA07 CDV
PA08 ATU Auto tuning mode 001h
PA09 RSP Auto tuning response 6
PA10 INP In-position range
PA11 TLP Forward torque limit 100 %
PA12 TLN Reverse torque limit 100 %
PA13 *PLSS Command input pulse form 000h
PA14 *POL Rotation direction selection 0
PA15 *ENR Encoder output pulses 4000 pulse/rev
PA16 *ENR2 Encoder output pulse electronic gear 0
PA17 For manufacturer setting 000h
PA18 000h
PA19 *BLK Parameter write inhibit 00Eh
For manufacturer setting 000h
Electronic gear numerator
(Command input pulse multiplying factor numerator)
Electronic gear denominator
(Command input pulse multiplying factor denominator)
Initial
value
100
1
1
100 Refer to
Unit
100
pulse/rev
section
4.1.9.
Control mode
Internal
Position
speed
Internal
torque
4 - 2
4. PARAMETERS

4.1.2 Parameter write inhibit

Parameter
No. Symbol Name Position
PA19 *BLK Parameter write inhibit 00Eh
Initial
value
Setting
range
Refer to
the text.
Unit
Control mode
Internal
speed
POINT This parameter is made valid when power is switched off, then on after setting.
In the factory setting, this servo amplifier allows to change all the setting parameters. With the setting of parameter No. PA19, writing can be disabled to prevent accidental changes. The following table indicates the parameters which are enabled for reference and writing by the setting of parameter No. PA19. Operation can be performed for the parameters marked
.
Positioning
setting parameters No. PE
Parameter No. PA19
setting
000h
00Ah
00Bh
00Ch
00Eh
(initial value)
10Bh
10Ch
10Eh
Setting
operation
Reference
Writing
Reference
Writing
Reference
Writing
Reference
Writing
Reference
Writing
Reference
Writing
Reference
Writing
Reference
Writing
Basic setting
parameters No. PA
Parameter No.
PA19 only
Parameter No.
PA19 only
Parameter No.
PA19 only
Parameter No.
PA19 only
Parameter No.
PA19 only
Gain/Filter
parameters
No. PB
Extension setting
parameters No. PC
I/O setting
parameters
No. PD
Internal
torque
4 - 3
Loading...