in temperature trip functions can only protect the motor from overheating if the motor temperature sensor is
Safety
Instructions
Do not attempt
to
install,
operate,
maintain
or
inspect
the product
until you have read through
this Instruction
Manual
and can use the
Electric
Shock Prevention
WARNING
• Do not open the soft starter enclosure while there is power on the soft starter power terminals.
Fire Prevention
CAUTION
• The soft starter
must be installed
against
a
non-flammable
surface
-
mounting
it in
proximity
of
flammable
material
may result in
a
fire.
Injury Prevention
CAUTION
• The voltage
applied
to
each terminal
must be as specified
in
the Instruction
Manual
-
otherwise
damage
will occur.
equipment correctly. Do not use this product unless you have a full knowledge of the equipment, safety information and instructions and are
qualified to do installations of this nature.
Installation, operation, maintenance and inspection must be performed by qualified personnel. Here, an expert means a person who meets
all the conditions below:
• A person who has proper engineering training. Such training may be available at your local Mitsubishi Electric office. Contact your local
sales office for schedules and locations.
• A person who can access the operating manuals.
• A person who has read and familiarized themselves with the manuals.
In this Instruction Manual, the safety instruction levels are classified into "Warning" and "Caution":
WARNING
Incorrect handling may cause hazardous conditions, resulting in death or severe injury.
CAUTION
Incorrect handling may cause hazardous conditions, resulting in medium or slight injury, or may cause only material damage.
Note that even the CAUTION level may lead to serious consequences under certain conditions. Please follow the instructions of both
levels. They are important for personnel safety.
• Ensure that the power is OFF (MCCB open) before working on the motor or any load connected to the motor. Do not assume that the
power at the motor is OFF while the power to the soft starter is still ON.
NOTE: When wired for inside-delta connection, the six motor terminals remain live even when the motor is off.
• Do not run the soft starter with the cover removed - this increases the risk of access to the exposed terminals and electric shock.
• Even if power is OFF, do not open the soft starter enclosure.
• Before wiring or inspection, the power must be switched OFF.
• This soft starter must be earthed (grounded). Earthing (grounding) must conform to the requirements of national and local safety
regulations and electrical code (NEC section 250, IEC 536 class 1 and other applicable standards).
• Any person who is involved in wiring or inspection of this equipment shall be fully competent to do the work.
• The soft starter must be installed before wiring otherwise there is a risk of electric shock or injury.
• Ensure that cables are not damaged, under excessive stress or pinched anywhere otherwise there is a risk of causing a short circuit or
even electric shock.
• Do not change the cooling fan while power is ON - this is dangerous.
• Do not touch any part of the soft starter or handle the cables with wet hands- this increases the risk of electric shock.
• If the soft starter has become faulty, the soft starter power must be switched OFF. A continuous flow of large current may cause a fire.
• Be sure to perform daily and periodic inspections as specified in the Instruction Manual. If a product is used without regular inspection,
damage or even a fire may occur.
• The cables must be connected to the correct terminals - otherwise damage may occur.
• The connection order of the phases must be correct.
• While power is ON or for some time after it was ON, do not touch the soft starter as it may be extremely hot and could inflict a burn
injury.
wired in and connected to the motor at an appropriate temperature sensing location.
• The effect of electromagnetic interference must be reduced by using a noise filter or by other means. Otherwise nearby electronic
equipment may be affected.
• Before running a soft starter, which had been stored for a long period, inspection and test operation must be performed.
• Static electricity in your body must be discharged before you touch the product.
• Some of the diagrams, drawings and photographs in the Instruction Manual shows the product without a cover or partially open for
explanation. Never operate the product in this manner. The cover(s) must be always re-installed before operating the soft starter.
• Earthing Leakage detection is not active when Inside Delta motor wiring configuration is used.
4 Contents
Transportation
and Installation
CAUTION
• Any person
who is opening
a
package
using a sharp object,
such as a knife and cutter,
must wear gloves
to
prevent
injuries
caused
by
the
Wiring
CAUTION
• The motor
side terminals
(terminals
T1, T2 and T3)
must be connected
correctly.
The soft starter will protect against phase reversal if
Commissioning
CAUTION
• Before
starting
operation,
each configuration
parameter
must be adjusted for the installation and
motor size
. A failure
to do so
may cause
Emergency
Stop CAUTION
• A
n independent hardware
Emergency
Stop must be provided
as a safety measure
to
prevent
hazardous
conditions
to
the machine
and
Maintenance,
inspection
and parts replacement
CAUTION
• Do not carry out a megger
(insulation
resistance)
test on the soft starter
when connected.
It
may cause damage
.
edge of the sharp object.
• The product must be transported in an appropriate method for the weight of the package. Failure to do so may lead to injuries.
• Do not stand or rest heavy objects on the product.
• Do not stack the boxes containing soft starters higher than the number recommended.
• During installation, caution must be taken not to drop the soft starter as doing so may cause injuries and damage to the product.
• The product must be installed against a surface that withstands the weight of the soft starter.
• Do not install the product on a hot surface.
• The mounting orientation of the soft starter must be correct.
• The soft starter must be installed on a strong surface securely with screws so that it will not drop.
• Do not install or operate the soft starter if it is damaged or has parts missing.
• Foreign conductive objects must be prevented from entering the soft starter. That includes screws and metal fragments or flammable
substance such as oil.
• As the soft starter is a precision instrument, do not drop or subject it to impact.
• For the all ranges of the soft starter, the surrounding air temperature must be 0 to +50°C - 0therwise the soft starter may be damaged.
• The ambient humidity specification must be adhered to. Otherwise the soft starter may be damaged. (Refer to par 2.2.2.2 for details.)
• The storage temperature (applicable for a short time, e.g. during transit) specification must be adhered to. Otherwise the soft starter
may be damaged.
• The soft starter must be used indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.) Otherwise the soft starter may
be damaged.
• The soft starter can be used as rated, at an altitude of 1400 m or less above sea level. Higher altitudes require de-rating.
• The soft starter should not be subjected to operational vibration. The soft starter is designed for transportation vibration only. (Refer to
paragraph 2.2.2.7 for details.)
• If halogen-based materials (fluorine, chlorine, bromine, iodine, etc.) infiltrate into a Mitsubishi Electric product, the product will be
damaged. Halogen-based materials are often included in fumigant, which is used to sterilize or disinfest wooden packages. When
packaging, prevent residual fumigant components from being infiltrated into Mitsubishi Electric products, or use an alternative
sterilization or disinfection method (heat disinfection, etc.) for packaging. Sterilization or disinfection of wooden package should also be
performed before packaging the product.
configured to do so. If the soft starter is configured to not check the phase rotation, the motor will rotate inversely – which may, or may
not be a problem in the installation.
• Never connect the motor side terminals (terminals T1, T2 and T3) to the grid power supply. Applying the grid power supply to motor
terminals (T1, T2, T3) will damage the soft starter. The induction motor may be connected to the grid power supply only via a bypass
contactor that is under control of the soft starter.
• Return wires from an Inside Delta motor connection should be connected to the Supply lines on L1, L2, L3 (and NOT on the Bypass
terminals BL1 BL2 BL3)
unexpected behaviour or damage to the motor.
.
equipment in case of soft starter failure (refer paragraph ).
• When the breaker on the soft starter input side trips, the wiring must be checked for fault (short circuit). The cause of the trip must be
identified and removed before turning ON the power on the breaker.
• When a fuse on the soft starter input blows, the wiring and the soft starter needs to be checked for faults. The cause of the blown fuse
must be identified and removed before replacing the fuse and turning on again.
• When a protective function activates, take appropriate corrective action, then reset the soft starter and resume the operation.
Disposal
CAUTION
•When unserviceable, the soft starter should be treated as industrial waste.
5 Contents
AC Alternating Current
BAUD
Bits per second
(relating to the Modbus link)
COM Communication
port on PCs
EMC Electromagnetic Compatibility
FC Function Codes (Modbus)
GPRS General Packet Radio Service
IEC International
Electro
-
technical
Commission
L2 Supply Line Phase 2
MCCB
Moulded Case Circuit Breaker
MFS Motor Frame Size (in kW)
MSC Maximum Starting Current
OC Open Circuit
PC
Personal Computer
PF
Power Factor
PLC Programmable Logic Controller
PTC Positive Temperature Coefficient thermistor
RJ45 Connector standard (
used for Modbus
RTU and TCP
communications on
MEsoftstart
) RMS Root Mean Square
RPM Revolutions per Minute
RS485
Electrical standard for use in serial communications
(used for Modbus
in
MEsoftstart
) RTD Resistance Temperature Detector (e.g. PTC)
RTU / TCP Protocol variants for Modbus (RTU for RS485 serial and TCP
for Ethernet communication)
SC
Short Circuit
SCADA
Supervisory Control and Data Acquisition
SCR Silicon Controlled Rectifier
SICD Software Interface Control Document
TFT Thin Film Transistor (display)
USB Universal Serial Bus
VL-L Voltage Line to
Line
List of Abbreviations
Abbreviation Definition
AC3 Device category for squirrel cage motors
AM Amplitude Modulation
CE Conformité Européenne (for conformity with protection standards of the European Economic Area)
CT Current Transformer
EMI Electromagnetic Interference
GND Ground / Earthing
HMI Human Machine Interface
I/O Input / Output
L1 Supply Line Phase 1
L3 Supply Line Phase 3
MFLC Maximum Full Load Current
MODBUS Communication Protocol originally published by Modicon (now Schneider Electric) in 1979
MOLC Motor Overload Current
MULC Motor Underload Current
6 Contents
TFT
screen
(as shown)
and/or PC Application on Modbus RTU or TCP.
INTRODUCTION
Mitsubishi Electric Europe’s MEsoftstart microprocessor-based advanced digital soft
starter range features bypass control for internal or external bypass and full 3-phase
control. It incorporates both enhanced soft-start and soft-stop characteristics providing
the best solution for a wide range of applications. Its comprehensive motor protection
package guarantees long term reliability while the external bypass connections ensure
flexibility and excellent performance – all in a compact, versatile design.
Two MEsoftstart variants are available namely “Core” and “Pro”:
- Core – Low-cost, simple-to-configure models, using 6 potentiometers each for
start and stop ramp definition and a few slider switches to fully configure the soft
starter. Monitoring and control with PC Application on Modbus RTU.
- Pro – Used for complex applications where more advanced control options are
required. Setting up, Monitoring and Control with full-function local colour touch
This manual contains the Installation and Operating instructions for the
MEsoftstart/I00 and MEsoftstart/I01 Core variants and the MEsoftstart/I01,
MEsoftstart/I02, MEsoftstart/I03 and MEsoftstart/I04 Pro variants of the MEsoftstart
range of Industrial soft starters.
Always read the instructions before connecting and using the equipment.
The correct soft starter model needs to be selected according to the user’s intended application and installation environment.
The selection of the soft starter model can also be driven by a cost compromise between an expensive motor control centre
enclosure / cabinet / panel design / long cables, or a higher rated soft starter model.
The selection of the soft starter model is dependent on the following characteristics of the user’s installation:
1) Motor size and connection type – in general the soft starter current must be greater or equal to the motor full load
current.
2) Typical operating temperature – the soft starter is rated at a nominal operational temperature of 50°C but may be
operated up to 60°C. Implement de-rating of the soft starter maximum current at temperatures above 50°C. The
operating temperature is determined by the environmental factors as well as the soft starter workload.
3) Soft starter workload – The workload is defined in two categories: Normal duty and Heavy duty. This comprises the
typical starting time, the typical number of starts per hour and the running time (if no Bypass Contactor is installed)
a. Typical starting time – the shorter the starting time, the lower the thermal loading on the soft starter. A starting
time of less than 30 seconds is considered normal duty. 30 second-starts and longer, are considered heavy duty.
b. Typical number of starts per hour – frequent starting increases temperature of the heat sink in the soft starter.
Number of starts less than 10 per hour (or 6 minutes or longer between starts) are deemed normal duty. 10 or
more starts per hour (or less than 6 minutes between starts) are considered heavy duty.
c. Bypass contactor installed – if the soft starter is used with an internal or external bypass contactor, the ‘on-time’
of the soft starter is only during starting and stopping – this reduces thermal loading and a smaller soft starter
model may be appropriate. A bypass contactor is recommended for applications where the motor is started and
then runs for a long time before it is stopped. For applications where frequent start-stop cycles are required, a
bypass contactor is not recommended.
4) Altitude above sea-level – the MEsoftstart range of soft starters are designed and tested for operation up to 1400m
above sea level. De-rating of the soft starter maximum and operating currents is needed for operation at higher altitude.
Definition of motor duty applied to MEsoftstart soft starters:
1. Normal duty is defined as no more than 10 starts per hour (> 6 min between starts) and start ramp shorter than 30s.
2. Heavy duty is defined as more than 10 starts per hour (<6 min between starts) or start ramp longer than 30s.
Motor size
The tables below serve as a guideline for selecting the correct model soft starter for the application according to the motor
starting current and type of application. The tables below show the allowable starting current for the listed motor sizes as a
percentage of their maximum normal running current at power factor of 0.8.
A bypass contactor is recommended for applications where the motor runs for a long or continuous periods. A bypass contactor
reduces the current through the soft starter switching elements and can allow the use of a smaller soft starter and increases the
efficiency of the installation.
Applications with short, frequent start and stop ramps should not use a bypass contactor for mechanical life reasons of the
contactor. However, the soft starter needs to be sized correctly to handle the switching current for such heavy duty use.
8 Introduction
Model:
MEsoftstart/I00
Max starting current:
250A Heavy Duty
Model MEsoftstart/I00 soft starter is rated at 100A continuous current and can be used at 240A starting current for normal duty
and at 125A starting current for heavy duty applications and can be ordered with a built-in bypass contactor or can be installed
with an external bypass contactor, or without a bypass contactor. MEsoftstart/I00 can be ordered for voltage ranges from 400Vac
to 690Vac and can be ordered with a built-in bypass contactor or can be installed with an external bypass contactor, or without
a bypass contactor.
Continuous rated current: 100A
Max. starting current: 240A Normal duty
Max starting current: 125A Heavy Duty
Table 1: MEsoftstart/I00 guideline for motor sizes1
Model MEsoftstart/I01 is rated at 200A continuous current and can be used at 480A starting current for normal duty and at
250A starting current for heavy duty applications. MEsoftstart/I01 can be ordered for voltage ranges from 400Vac to 690Vac and
can be ordered with a built-in bypass contactor or can be installed with an external bypass contactor, or without a bypass
contactor.
Model: MEsoftstart/I01
Continuous rated current: 200A
Max. starting current: 480A Normal duty
1
The tables show the allowable starting current for the listed motor sizes as a percentage of their maximum normal running current at
power factor of 0.8 – in the case of motors with heavy duty starting requirements, use only the values from columns marked “Heavy
duty”.
9 Introduction
Model:
MEsoftstart/I03
Table 2: MEsoftstart/I01 guideline for motor sizes1
Model MEsoftstart/I02 is rated at 390A continuous current and can be used at 730A starting current for normal duty and at
390A starting current for heavy duty applications. MEsoftstart/I02 can be ordered for voltage ranges from 400Vac to 690Vac
and can be ordered with a built-in bypass contactor or can be used with an external bypass contactor, or without a bypass
contactor.
Model: MEsoftstart/I02
Continuous rated current: 390A
Max. starting current: 730A Normal duty
Max starting current: 390A Heavy Duty
Table 3: MEsoftstart/I02 guideline for motor sizes1
Model MEsoftstart/I03 is rated at 600A continuous current and can be used at 1440A starting current for normal duty and at
750A starting current for heavy duty applications. MEsoftstart/I03 can be ordered for voltage ranges from 400Vac to 690Vac and
can be ordered with a built-in bypass contactor or can be used with an external bypass contactor, or without a bypass contactor.
Continuous rated current: 600A
Max. starting current: 1440A Normal duty
Max starting current: 750A Heavy Duty
10 Introduction
Table 4: MEsoftstart/I03 guideline for motor sizes1
Model MEsoftstart/I04 is rated at 900A continuous current and can be used at 1600A starting current for normal duty and at
900A starting current for heavy duty applications. MEsoftstart/I04 can be ordered for voltage ranges from 400Vac to 690Vac
and can be used with an external bypass contactor, or without a bypass contactor.
Model: MEsoftstart/I04
Continuous rated current: 900A
Max. starting current: 1600A Normal duty
Max starting current: 900A Heavy Duty
Note: a built-in bypass contactor option is not available with model MEsoftstart/I04.
Table 5: MEsoftstart/I04 guideline for motor sizes1
11 Introduction
Typical operating temperature
The operating temperature is determined by the typical ambient temperature in the immediate vicinity of the soft starter, air
flow through the soft starter and cooling mechanisms that are used, as well as the soft starter workload. Refer par 2.2.3 for a
description of how the cabinet design can also be used to best regulate operating temperature.
De-rate the soft starter starting capacity at 1.4% per °C for higher temperatures above 50°C.
Example of temperature de-rating:
The requirement is for a 75kW 400Vac motor (normal, 3-wire connected) in a heavy duty application, to operate in an
environment where the operating temperature is likely to be 60°C. From Table 2, the motor’s FLC = 136A (at 0.8 power
factor), while the MEsoftstart/I01 model soft starter can provide a maximum starting current of 184% (or 250A) if operated
below 50°C.
These values should be de-rated for operation at 60°C i.e. (60°C - 50°C) * 1.4% = 14%, thus 184% - 14% = 170% (or 231A).
If this is insufficient for the application, then more robust selection for this application may be MEsoftstart/I02 with a derated starting current of 287% - 14% = 273% (or 371A) – see Table 3.
Soft starter workload
Soft starter workload is made up of the starting time, stopping time and number of starts per hour, as well as any run time when
a bypass contactor is not used. If the expected work load is high, a soft starter with a larger current margin should be selected.
If the expected starting time is longer than 30 seconds, a higher rated soft starter should be selected. If the application requires
frequent starts with short running time, select a soft starter from the heavy duty columns.
Figure 1 –Normal and Heavy duty applications as defined by soft starter on-time
12 Introduction
Altitude of installation.
The MEsoftstart range of soft starters are designed and tested at 1400m above sea level. When planning to use the soft starter
at altitudes higher than 1400m the soft starter the guideline is to de-rate at 0.67% per 100m for higher altitudes.
Selection example
1. The application is a fan in a 400V AC3 distribution, which does not require high starting torque. A normal 3-wire
configuration (with bypass) 90kW fan motor is specified, with normal duty starting: Ramp-start of 20s duration,
requiring no more than 200% of the motor’s running current during start-up:
b) Conclusion: our starting current < 480A allowed for normal duty with MEsoftstart/I01
Use soft starter (MEsoftstart/I01).
2. The application is a compressor or conveyor in a 400V AC3 distribution, requiring high starting torque. The same
90kW motor – this time driving a compressor motor – is specified (with bypass), with heavy duty starting: slow
ramp longer than 30s duration and approximately 400% of the motor’s running current during start-up:
a) Calculations:
Here, starting current needed = 400% × 162.4
= 649.6A
b) Conclusion: our starting current >250A allowed for heavy duty with MEsoftstart/I01. Looking at
MEsoftstart/I02, its heavy duty starting current of 390A is also too low, i.e. MEsoftstart/I03 with a heavy
duty starting current of 900A would suffice.
Use soft starter (MEsoftstart/I03).
Checking the Product when unpacking
Unpack the product and check the label on the soft starter to ensure that the model agrees with the order and that the product
is intact. Figure 2 shows product labels for the MEsoftstart/I01 and MEsoftstart/I02 models. From the label can be seen the
rated continuous current of the MEsoftstart soft starter, as well as the maximum starting current for normal duty. The rated
supply voltage is also visible on the label.
Note that the labels in Figure 2 are both labels for MEsoftstart models without built-in bypass contactors. This can be seen
from the grid side and motor side bypass terminal markings on the label.
Recommended motor sizes are shown on the label. These motor sizes are applicable for normal 3-wire installation. Also refer
to the tables in paragraph 1.1.1 for more information about the supported motor sizes.
13 Introduction
Component and Terminal identification
Component and terminals are identified in Figure 3 and Table 6 below. Comparable markings are used on all other models.
14 Introduction
Figure 2 – Product marking
Figure 3 – Soft starter terminal and component identification
15 Introduction
10 Pin
Wiring terminal
connector
3.2.4
TFT touchscreen for monitoring and controlling the soft
j) Busbar 8 / BT1 Bypass contactor supply L1 to motor T1
k) Busbar 10 / BT2 Bypass contactor supply L2 to motor T2
l) Busbar 12 / BT3 Bypass contactor supply L3 to motor T3
m) RJ 45 (x 2)
Two RS485 to MEsoftstart PC App /
Modbus RTU interface
Only on models without
internal bypass
contactor
Only on models without
internal bypass
contactor
Two ports of the same
Modbus port for easy
daisy-chaining
3.2.1
7
n)
o)
(x2)
10 Pin Wiring terminal connector
(X2)
p) TFT touchscreen
Green Wiring terminals on top side
Green Wiring terminals on bottom sideOnly on Pro variants3.2.4
starter
Only on Pro variants6
3.2.5
q) HMI panelPotentiometer HMI panel Only on Core variants5
r) RJ 45TCP to MEsoftstart PC App / Modbus TCP interfaceOnly on Pro variants7.2
s) Earthing studChassis ground
t) Protective coverFinger guard for terminals
u) Warranty label
Do not remove this label. The warranty is void if the
label is removed or damaged
3.2.2
3.2.3
16 Introduction
INSTALLATION INSTRUCTIONS
This chapter explains the installation of the MEsoftstart/I00, MEsoftstart/I01, MEsoftstart/I02, MEsoftstart/I03 and
MEsoftstart/I04 model soft starters. Note that for safety reasons, it is important to install the soft starter in a cabinet or
enclosure where the terminals will not pose a hazard to personnel. This section shows how to safely install the soft starter and
provides guidelines for the selection or design of a suitable motor control centre cabinet / enclosure.
Always read the instructions before installing, connecting and using the equipment.
The peripheral devices that are needed around the soft starter need to be specified before planning the installation of the soft
starter.
The soft starter can be wired to start a normal 3-wire motor or inside-delta on a six-wire motor. The installation and wiring of
the soft starter is similar for the normal and the inside-delta connections, but there may be implications for the enclosure size
and cable length, as well as the selection of external bypass contactor for the different ways of connecting the motor.
Normal Delta 3-wire connection
The diagram below shows the connection diagram for the soft starter with and without built-in bypass contactor, for normal 3wire connection. With this method of connecting the motor, the full motor starting current flows through the soft starter
switching elements during start-up. After start-up and if a built-in or external bypass contactor is used, the full running current
of the motor flows through the contactor. If no bypass contactor is used, the motor’s continuous running current flows through
the soft starter switching elements.
Figure 4 – Soft starter circuit diagram for 3-wire delta motor
With this method of installation, the bypass contactor must be scaled for the full running current of the motor. Only three
cables are needed to run the distance to the motor.
18 Installation Instructions
Inside-delta 6-wire connection
The diagram below shows the connection diagram for the soft starter with and without built-in bypass contactor, for an insidedelta 6-wire connection. With this method of connecting the motor, 58% of the motor’s starting current flows through the soft
starter switching elements during the start-up ramp. After start-up and if a built-in or external bypass contactor is used, 58% of
the running current of the motor flows through the bypass contactor. If no bypass contactor is used, 58% of the motor’s
continuous running current flows through the soft starter switching elements.
Figure 5 – Soft starter circuit diagram for 6-wire inside-delta motor
Ensure to connect the grid-side terminals of the inside-delta motor to the soft starter L1, L2, L3 terminals. Incorrectly
connecting them to the Bypass terminals may damage the soft starter. Refer Figure 19.
Note that for inside delta wiring the Earthing Leakage protection is not active.
19 Installation Instructions
Take special note of the wiring of an inside delta motor when the grid connection on the soft starter is clockwise or anticlockwise. Refer to Figure 6 to understand the difference.
Figure 6 –6-wire Inside-delta wiring for clockwise and anti-clockwise grid rotation
20 Installation Instructions
Soft starter and Peripheral devices
Always check the nameplate information on your motor before designing the peripheral devices
Figure 7 shows the MEsoftstart/I01 Core model soft starter and the associated peripheral devices. The installation for the other
MEsoftstart models will be the same.
Figure 7 – Soft starter circuit diagram with peripheral devices
21 Installation Instructions
2.
Moulded case circuit breaker
The circuit breaker must be selected according to the maximum current of the motor.
3.
The fuses are required to protect the soft starter SCRs against excessive currents. The
4.
5.
Bypass contactor relay circuit
This circuit breaker is a 2A circuit breaker protecting the Soft starter
output signal that
6.
7.
8.
The items in Figure 7 are further described in Table 7 below.
Table 7: Peripheral devices in the soft starter installation
MEsoftstart models without
built-in bypass contactor)
Description
The MEsoftstart soft starter connects to the supply voltage on the top side and to the
motor on the bottom side.
The circuit breaker should ideally be controllable from an Emergency Stop button and
the soft starter Shunt Trip Relay.
fuses should ideally be in line between the circuit breaker and the soft starter and
outside the delta for 6-wire installations. The fuses should be selected as follows for
the different MEsoftstart models:
Model
MEsoftstart/I00
MEsoftstart/I01
MEsoftstart/I02
MEsoftstart/I03
MEsoftstart/I04
Installed to run the motor when at full speed. The ‘BYPASS CONTACTOR’ discrete
output signal (refer Table 13) from the soft starter should be used to control the bypass
contactor. Select the bypass contactor according to the maximum running current of
the motor as indicated on the motor manufacturer’s label. If the motor is wired in an
inside-delta circuit, the bypass contactor may be selected to be 58% of the motor rated
running current.
Refer to Mitsubishi Electric’s non-reversing Magnetic Contactors.
Minimum
Fuse current
160A
315A
500A
900A
1000A
Refer
Figure 3
-
Figure 5
Max I2t
rating
6050
125000
322000
1330000 pc33ud69v900tf
1330000 pc33ud69v1000tf
Recommended
Mersen2 Fuse
pc31ud69v160tf
pc30ud69v315tf
pc31ud69v500tf
30 sec rating
@ 690V
330A
750A
1300A
2890A
3200A
Figure 25
breaker
(Only applicable to
MEsoftstart installations with
external bypass contactor)
Emergency stop
Motor Temperature Sensor The motor temperature sensor is read by the soft starter. The soft starter uses this
Induction motor
activates the external Bypass contactor via a 50/60Hz coil. The contactor coil is
powered from the supply voltage and should be selected according to the supply
voltage
A STOP button that will open the MCCB to disconnect all power to the soft starter and
motor.
reading to protect the motor from overheating.
Configured as a 3-wire motor for normal delta connection or 6-wire for inside delta
wiring.
-
-
-
Capacitors for power factor improvement
Capacitors for power factor improvement must not be connected on the output of the soft starter (between the soft starter and
the motor). If power factor correction is required, add the capacitors on the grid-side of the soft starter.
2
Mersen is a tradename of Mersen S.A. headquarted in France.
22 Installation Instructions
Environmental
Model
Specification
Notes
De-rate above 50
°C at 1.4% per °C
0.67%
per 100 m
Motor control centre cabinet design
A soft starter unit uses semiconductor devices. To ensure reliable operation and long service lifetime for the soft starter, it is
important to operate the soft starter in the ambient environment that complies with the equipment specifications.
When designing or selecting a soft starter cabinet, the structure, size and device layout inside the cabinet should be determined
by considering issues such as:
Safe and easy access for wiring;
Safe and easy access to the HMI for configuring and monitoring;
Heat generation and cooling of the soft starter;
Peripheral devices that need to be in the cabinet and
The operating environment.
Minimum cabinet size
The minimum cabinet size should be decided upon by considering the following:
a) The circuit layout with peripheral devices (refer par 2.1);
b) The installation environment (refer paragraph 2.2.2);
c) Air flow requirements of the soft starter (refer par 2.3.3);
d) Cooling requirements inside the cabinet (refer paragraph 2.2.3);
e) Minimum space required around the soft starter (refer par 2.3.3).
Soft starter installation environment
The following table lists the standard specifications of the soft starter installation environment.
Table 8: Soft starter environmental specification
parameter
Surrounding Air
temperature
Realtive humidity
Storage temperature
Atmosphere
Altitude
Vibration
Using the soft starter in an environment that does not satisfy these conditions, will deteriorate its performance, shorten its life
span and can lead to failure. The following paragraphs contain suggested measures to ensure that the environment complies
with the specification.
0.02g²/Hz from 10 to 50Hz, reducing linearly
on a log-linear plot to 0.0001g²/Hz at 500Hz.
< 85%
-30°C to +70°C
(directions
of X, Y, Z axes)
starter
inside the closed cabinet
Ideally < 50% @ 50° to < 85% @20°C
For the installation at an altitude above 1400m
de-rate the rated current of the soft starter at
Road transport vibration only
23 Installation Instructions
Temperature
For the MEsoftstart range of soft starters, the permissible surrounding air temperature of the soft starter is between -10°C and
+60°C. Always operate the soft starter within this temperature range. Operation outside this range will considerably shorten
the service lives of the semiconductors, parts, capacitors and other electronics. Take the following measures to keep the
surrounding air temperature of the soft starter within the specified range.
(a) Measures against high temperature
o Use a forced ventilation system or similar cooling system. (Refer to par 2.2.3 on page 26.)
o Install the cabinet in an air-conditioned chamber.
o Block direct sunlight.
o Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source.
o Ventilate the area around the cabinet well.
(b) Measures against low temperature
o Provide a space heater in the cabinet.
o Do not power OFF the soft starter. (Keep the motor start signal of the soft starter OFF.)
(c) Sudden temperature changes
o Select an installation place where temperature does not change suddenly.
o Avoid installing the soft starter near the air outlet of an air conditioner.
o If temperature changes are caused by opening/closing of a door, install the soft starter away from the door.
Humidity
Operate the soft starter within the specified ambient air humidity. Too high humidity will pose problems of reduced insulation
and metal corrosion. On the other hand, too low humidity is conducive to the build-up of static electricity and may cause
dielectric breakdown in solid state devices.
(a) Measures against high humidity
o Seal the cabinet and provide it with a hygroscopic agent.
o Provide dry air into the cabinet from outside.
o Provide a space heater in the cabinet.
(b) Measures against low humidity
o Air with proper humidity can be blown into the cabinet from outside. Also, when installing or inspecting the unit,
discharge your body (static electricity) beforehand.
(c) Measures against condensation
Condensation may occur if the cabinet temperature changes suddenly or if the outside air temperature changes suddenly.
Condensation causes faults such as reduced insulation and corrosion.
o Take the measures against high humidity in (a) above.
o Do not power OFF the soft starter.
24 Installation Instructions
Dust, dirt, oil mist
Dust and dirt may cause such faults as poor contacts, reduced insulation and cooling effect due to the moisture-absorbed
accumulated dust and dirt and in-cabinet temperature rise due to a clogged filter. In an atmosphere where conductive powder
floats, dust and dirt may cause such faults as malfunction, deteriorated insulation and short circuit in a short time.
Since oil mist may cause similar conditions, it is necessary to take adequate measures.
Countermeasures:
o Place the soft starter in a totally enclosed cabinet.
o Take measures if the in-cabinet temperature rises. (Refer to paragraph 2.2.2.1)
o Purge air.
o Pump clean air from outside to make the in-cabinet air pressure higher than the outside air pressure.
Corrosive gas, salt damage
If the soft starter is exposed to corrosive gas or to salt (e.g. near the sea), the printed circuit board and components will corrode,
the relays and switches can deteriorate resulting in unreliable contact.
When it is required to operate the soft starter in this environment, take the measures suggested in the paragraph 2.2.2.3.
Explosive, flammable gases
It is not recommended to install and use the soft starter in an environment where flammable gasses are present. The soft starter
is not explosion proof and it will have to be contained in a certified explosion-proof cabinet If possible, avoid installation in such
environments and install the soft starter in a non-hazardous place.
High altitude
The soft starter may be used at its recommended current rating, at altitudes lower than 1400m above sea-level. For the
installation at an altitude above 1400 m, de-rate the rated current of the soft starter at 0.67% per 100 m.
If it is used at a higher altitude than 2500m above sea level, thin air will reduce the cooling effect and low air pressure will
deteriorate dielectric strength and a higher rated soft starter model should be selected.
Vibration, impact
The soft starter is not designed to withstand periods of high vibration or high impact. The vibration resistance of the soft starter
vibration spectrum is tested at 0.02g²/Hz from 10 to 50Hz, reducing linearly on a log-linear plot to 0.0001g²/Hz at 500Hz for
the directions of X, Y, Z axes. Applying vibration and impacts for a long time may loosen the structures and cause poor contacts
of connectors, even if those vibration and impacts are within the specified values. (Refer to IEC 60068-2-6).
Especially when impacts are applied repeatedly, caution must be taken because such impacts may break the installation feet.
Countermeasures:
o Provide the cabinet with rubber vibration isolators.
o Strengthen the structure to prevent the cabinet from resonance.
o Install the cabinet away from the sources of the vibration.
25 Installation Instructions
Cooling system types for soft starter cabinet
The heat that the soft starter and other equipment (transformers, lamps, resistors, etc.) generates, as well as any incoming
heat (such as direct sunlight) must be dissipated to keep the temperature inside the cabinet lower than the permissible
operating temperature of the soft starter.
When selecting or designing a cabinet for the soft starter, the following cooling considerations (for the cabinet) must be
considered:
The cooling systems are classified as follows in terms of the cooling calculation method.
(a) Cooling by natural heat dissipation from the cabinet surface (totally enclosed type).
(b) Cooling by heatsink (e.g. aluminium fin).
(c) Cooling by ventilation (forced ventilation type, pipe ventilation type).
(d) Cooling by heat exchanger or cooler (e.g. heat pipe, cooler).
Table 9: Cooling systems for soft starter cabinet
Cooling system
Cabinet layout Comment
Natural
cooling
Forced
cooling
Natural ventilation
(enclosed, open type)
Natural ventilation
(totally enclosed type)
Heatsink cooling
Forced ventilation
This system is low in cost and generally used, but the cabinet size
increases as the soft starter capacity increases.This system is for relatively
small capacities.
Being a totally enclosed type, this system is the most appropriate for
hostile environment having dust, dirt, oil mist, etc. The cabinet size
increases depending on the soft starter capacity.
This system has restrictions on the heatsink mounting position and area.
This system is for relatively small capacities.
This system is for general indoor installation. This is appropriate for
cabinet downsizing and cost reduction and often used.
Heat pipe
26 Installation Instructions
This is a totally enclosed for cabinet downsizing
Soft starter installation
Soft starter placement
Placement of the soft starter needs careful planning. The clearance below the soft starter is required for terminal access for
wiring as well as air inlet and the clearance above the soft starter is required for heat dissipation as well as terminal access for
wiring. Consider the following:
a) Install the soft starter securely on a sturdy horizontal or vertical surface with bolts (refer paragraph 2.3.6).
b) Leave enough clearances and take measures to cool the device (refer par 2.3.3).
c) Leave enough clearance to access terminals to wire the soft starter.
d) Avoid places where the soft starter is subjected to direct sunlight, high temperature and high humidity (refer
paragraph 2.2.2).
e) Install the soft starter on a non-flammable wall surface.
f) When encasing multiple soft starters, install them in parallel as a cooling measure (refer paragraph 2.3.4)
g) For heat dissipation and maintenance, keep clearance between the soft starter and the other devices or cabinet
surface.
Installation orientation of the soft starter
The MEsoftstart models without internal bypass contactor may be mounted at any orientation, but the recommended
orientation is upright against a wall or against the cabinet back or side (max. deviation from vertical is 22.5°).
This allows for easy access to the HMI, terminals and with natural air flow from bottom to top as shown in Figure 9.
If a MEsoftstart model with an internal bypass contactor is used, the orientation guidelines in Figure 8 should be adhered to.
27 Installation Instructions
Figure 8 – Mounting orientation
Air flow around the soft starter
Heat is blown up from inside the soft starter by the small built-in fan. Leave space around the soft starter for ample air flow
through the soft starter cabinet. Any equipment placed above the soft starter should be heat resistant.
Figure 9 – Air flow around the soft starter
Arrangement of multiple soft starters
When encasing multiple soft starters in the same cabinet, generally arrange them horizontally as shown in the right Figure 10
(a). When it is inevitable to arrange them vertically to minimize space, take such measures as to provide guides since heat from
the bottom soft starters can increase the temperatures in the top soft starters, causing soft starter overheating.
Figure 10 – Arrangement of multiple soft starters in a single cabinet
When mounting multiple soft starters, take caution not to make the surrounding air temperature of the soft starter higher
than the permissible value by providing ventilation and increasing the cabinet size.
28 Installation Instructions
Arrangement of the ventilation fan and soft starter
Figure 11 – Arrangement of the ventilation fan and soft starter
Heat generated in the soft starter is blown up from the bottom of the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation fan installation after fully considering air flow. (Air passes
through areas of low resistance. Make an airway and airflow plates to expose the soft starter to cool air.)
29 Installation Instructions
Drilling plan for soft starter installation
When drilling mounting holes in a cabinet, take caution not to allow chips and other foreign matter to enter the soft starter.
Figure 12 through Figure 18 below shows the drilling plan for mounting the MEsoftstart soft starter in a cabinet or against a
wall.
MEsoftstart/I00 and MEsoftstart/I01 Drilling plan
Figure 12 – Drilling plan: MEsoftstart/I00 with and without
bypass contactor and MEsoftstart/I01 without bypass
contactor
MEsoftstart/I02 Drilling plan
Figure 13 – Drilling plan: MEsoftstart/I01 with bypass contactor
Figure 14 – Drilling plan: MEsoftstart/I02 without bypass
contactor
30 Installation Instructions
Figure 15 – Drilling plan: MEsoftstart/I02 with bypass contactor
MEsoftstart/I03 Drilling plan
Figure 16 – Drilling plan: MEsoftstart/I03 without
bypass contactor
MEsoftstart/I04 Drilling plan
Figure 17 – Drilling plan: MEsoftstart/I03 with bypass contactor
Figure 18 – Drilling plan: MEsoftstart/I03 without bypass contactor
31 Installation Instructions
WIRING
This chapter identifies the terminals and explains the wiring of the MEsoftstart/I01 and MEsoftstart/I02 models soft starter.
Always read the instructions before installing, connecting and using the equipment.
The soft starter has grid-side and motor-side power terminals, an earthing stud. All variants have Modbus RTU cable
connectors and signal terminals on green wiring terminal blocks (grid input side). The terminals are clearly marked on all
MEsoftstart models.
Terminal identification – Pro variants
All Pro MEsoftstart variants have a Modbus TCP RJ45 terminal (grid input side) and additional signal terminals on green
wiring terminal blocks. Figure 19 shows the terminals/connectors for Pro variant models MEsoftstart/I01 and MEsoftstart/I02
without built-in bypass contactor.
Figure 19 – Soft starter Pro variant terminal identification
33 Wiring
Terminal identification – Core variants
Figure 20 shows the terminals for Core variant models MEsoftstart/I00 and MEsoftstart/I01 without built-in bypass
contactor.
power factor correction capacitors should be fitted between the soft starter
NOTES:
To prevent a malfunction due to noise, route the signal cables 10 cm or more away from the power cables. Also, separate the
main circuit cables at the input side from the main circuit cables at the output side.
After wiring, wire offcuts must not be left in the cabinet. Always keep the soft starter cabinet clean. When drilling mounting
holes in a cabinet etc., take caution not to allow shavings, chips and other foreign matter to enter the soft starter.
Wiring instructions
Power Terminals – Main circuit
Wiring of the Main circuit of the soft starter and the motor is specified in Table 10 and Table 11 and shown in Figure 21.
Table 10: Power terminals wiring
Terminal
symbol
L1,L2,L3 3 phase AC power input.
BL1,BL2,BL3 3 phase AC power to bypass
Terminal name
motor and for models
without built-in bypass
contactor:
contactor.
Terminal function description
Connect these terminals via fuses and MCCB to the three-phase supply
lines. (Refer Figure 7).
Ensure to connect the supply power to the correct terminals as
shown in Figure 21 and Figure 19 or Figure 20
and the motor).
Connect these terminals from the bypass contactor to the soft starter
Connect these terminals to the external bypass contactor. The bypass
contactor should be controlled by the Soft starter Bypass Relay output.
Figure 21 – Power wiring on the soft starter
Note that if bypass terminals are not used, they should be covered for safety. The cable sizes and connection lugs for
the Main circuit are specified in Table 11.
35 Wiring
[Nm]
M6
MEsoftstart
/I03 M12 12 MEsoftstart
/I04 M12 12
Table 11: Power wiring size and tightening torque specification
Inverter model Lug, Nut and Bolt size Tightening torque
Cable size
MEsoftstart/I00
MEsoftstart/I01 M6 6
MEsoftstart/I02
M8
6
8
Select the cable size according to the motor maximum
starting current. Refer to local installation standards
for the site.
Earthing stud
The earthing stud on the soft starter should be connected to the cabinet ground or other low-impedance earthing point using
the guidelines shown in Figure 22. The voltage measuring channels of the soft starter require a system earthing to work correctly.
A lack of proper earthing connection may cause the soft starter to behave erratically.
The Earthing wire should be as short as possible (preferably less than 0.5 m). The earthing stud is an M8 bolt on all MEsoftstart
models. Use the same cable cross section as selected for power wiring in Table 11.
Protective guards over the power terminals
After connecting all the AC cables, and before switching on the grid supply power, fit the protective guards supplied with the
soft starter. Pull the side sections slightly apart to slide over the busbar terminal block until the two front lips and lip on each
side clip in position under the terminal block.
36 Wiring
Figure 22 – Earthing wiring on the soft starter
Figure 23 – Fitting protective guards over terminals
37 Wiring
Wiring terminals on the Pro variants
This section defines the wiring terminals on the full-featured MEsoftstart/I pro range of soft starters.
Wiring terminal X1 (Pro) – Control outputs
The green wiring terminal X1 on the bottom side of the soft starter (refer Figure 19) provides access to the control outputs of
the soft starter.
Table 12: Control output wiring terminals on the Pro models
Terminal
X1-1
X1-2
Terminal name
Ready-Relay
Ready_Relay return
Terminal function description
This output signal from the soft starter will be active when the soft starter is ready to start the motor. It
may be used for a remote device to be able to start the motor. The signal will be inactive when configuring
the soft starter and while the motor is starting, running, stopping or the delay between starts is
implemented.
X1-3
X1-4
X1-5
X1-6
X1-7
X1-8
X1-9
X1-10
Run-Relay
Run_Relay return
Shunt Trip Relay
Shunt Trip Relay return
Phase A
Phase B
Sensor-GND
Not Connected
This output signal from the soft starter will be active when the soft starter is busy starting, running or stopping
the motor. It may be used to monitor the operation of the soft starter.
This output signal from the soft starter will be active whenever an internal stack over current is detected.
These input signals to the soft starter are used to be able to connect a shaft sensor to measure the motor’s
revolutions per minute.
The MEsoftstart soft starter is not delivered with a shaft sensor. A compatible shaft sensor may be ordered
with the soft starter.
-
38 Wiring
Figure 24 – Terminal X1 (Pro) – wiring example
Wiring terminal X2 (Pro) – Temperature Sensors and Contactor control
The green wiring terminal X2 on the bottom side of the soft starter (refer Figure 19) provides access to the terminals where the
external temperature sensors should be connected and where the reversing or bypass contactors can be connected.
Table 13: Temperature sensor input and contactor output terminals on the Pro models
Terminal Terminal name
X2-1
X2-2
X2-3
X2-4
X2-5
X2-6
X2-7
X2-8
X2-9
X2-10
PT-100 (A)
PT-100 (B)
PT-100 (B)
LM35 GND
LM35 Signal
LM35 +24V
Reversing Contactor
Reversing Contactor
Return
Bypass Contactor
Bypass Contactor
Return
Terminal function description
PT-100 3-wire temperature sensor.
Note: MEsoftstart soft starters are not delivered with a temperature sensor as standard. Please include
the optional, compatible temperature sensor when ordering the soft starter.
These terminals provide access to 24V and ground for an LM35-type temperature sensor on the motor.
The soft starter will read the sensor and be able to limit current to the motor when the temperature rises
above the pre-configured maximum for the motor. Refer Figure 7.
Note: MEsoftstart soft starters are not delivered with a temperature sensor as standard. Please include
the optional, compatible temperature sensor when ordering the soft starter.
Note: Future function – not available in MEsoftstart firmware version 2.0 and earlier
Terminals for a reversing contactor that is under the Soft starter control – used for braking a motor for fast
stop.
The firmware version no. can be found at the top of all TFT touchscreen displays (see Figure 39) and/or on
a Modbus master such as the PC App (see Figure 58).
Terminals for an external bypass contactor that is under the Soft starter control.
(* Ensure to configure the soft starter for use with a bypass contactor.)
39 Wiring
Figure 25 – Terminal X2 (Pro) – wiring example
bridged or the soft starter will be
in Maintenance
.
X3-9 Return
Wiring terminal X3 (Pro) – Communications and Control inputs
The green wiring terminal X3 on the top side of the soft starter (refer Figure 19) provides access to the wiring terminals for the
PC Interface and is where the Auto/Maintenance, remote start and reset signals to the soft starter, should be connected.
Table 14: Communication and Control I/O wiring terminals on the Pro models
Terminal
X3-1
X3-2
X3-3
Terminal name
RS-485 A and -B
RS-485 Ground
Terminal function description
Communication port for control expansion. Two wire RS485-A and RS485-B terminals. Functionality to be
defined.
X3-4
X3-5
X3-6
X3-7
X3-8
X3-10
Over Alarm Return
Fault / Incoming Alarm
Fault / Incoming Alarm
Auto / Maintenance
Remote Start
Over Alarm
Return
Output: Motor overload alarm. This output is activated when the measured current is higher than the
frame size or higher than the Motor Overload Current (MOLC) parameter in the configuration.
Output: This is a configurable output and can be set to either be an indication of 3 phase power present
in the soft starter OR a fault detected by the soft starter.
The Fault output is reset when the user presses RESET on the TFT or via the PC interface or remote reset.
Input: Auto / Maintenance. When this signal is active the Soft starter is in ‘Auto’ and control will be
possible from any remote location via RTU, TCP, PLC discrete inputs AND the TFT or Pot HMI on the
box. When this signal is not active the Soft starter is in ‘Maintenance’ and the control will be possible
from local location only i.e. via TFT or Pot HMI.
NOTE that this is a normally-closed switch connection. If not used the terminals must be
This is the return signal for Auto/Maintenance input AND Remote Start input.
Input: When the soft starter is configured for ‘REMOTE’ control, this input will start the soft starter.
This is an input signal to the soft starter and may be used to remotely start the motor from e.g. a PLC
controller. The controller should use the Ready Relay output (refer Table 12 X1-1 and X1-2) to be able
to detect when the soft starter is ready to start the motor.
NOTE that the system must be configured for REMOTE operation (refer paragraph 6.7.1).
Close this contactor to start the motor, open it to Stop the motor.
40 Wiring
Figure 26 – Terminal X3 (Pro) – wiring example
Wiring terminal X4 (Pro) – Control I/O and power
The green wiring terminal X4 on the top side of the soft starter (refer Figure 19) provides access to the wiring terminals for the
PC Interface and is where the Reset, Temperature fault monitoring and external 24V DC may optionally be connected.
Table 15: DC power and Control I/O wiring terminals on the Pro models
Output: This output is set active when the soft starter trips due to a high temperature on internal
heatsinks or on the motor.
-
-
-
-
Provide 24V DC (1A) on this input to be able to safely configure the soft starter, or update software,
without having the 3 phase power connected.
41 Wiring
Figure 27 – Terminal X4 (Pro) – wiring example
Wiring terminals on the Core variants
This section defines the wiring terminal connectors for the MEsoftstart/I Core variants of Industrial soft starters.
Wiring terminal X1 (Core) – Control outputs
The green wiring terminal X1 on the top side of the soft starter (refer Figure 20) provides access to the control outputs of the
soft starter and is where the external temperature sensors should be connected.
Table 16: Control output and temperature sensor wiring terminals on the Core models
Terminal
X1-1
X1-2
X1-3
X1-4
Terminal name
Ready-Relay
Ready_Relay return
Run/Bypass Relay
Run/Bypass_Relay
Terminal function description
This output signal from the soft starter will be active when the soft starter is ready to start the motor. It
may be used for a remote device to be able to start the motor. The signal will be inactive when configuring
the soft starter and while the motor is starting, running, stopping or the delay between starts is
implemented.
This output signal from the soft starter will be active when the start-ramp is completed and the motor is
running. It may be used to switch power to the motor using a bypass contactor once the motor is running
and to again open the bypass contactor when the soft starter is stopping the motor. Refer Figure 7
X1-5
X1-6
X1-7
X1-8
X1-9
X1-10
Fault Relay
Fault Relay return
Not connected
PT-100 (A)
PT-100 (B)
PT-100 (B)
This output signal from the soft starter will be active whenever an internal stack over current is detected.
-PT-100 3-wire temperature sensor.
Note: MEsoftstart soft starters are not delivered with a temperature sensor as standard. Please include
the optional, compatible temperature sensor when ordering the soft starter.
42 Wiring
Figure 28 – Terminal X1 (Core) – wiring example
Wiring terminal X2 (Core) – Control I/O and power
The green wiring terminal X2 on the top side of the soft starter (refer Figure 20) provides access to the wiring terminals for the
PC Interface and is where the Auto/Maintenance, remote start and reset signals to the soft starter, should be connected.
Table 17: Communication and Control I/O wiring terminals on the Core models
Terminal
Terminal name
Terminal function description
X2-1
X2-2
X2-3
X2-4
X2-5 Auto / Maintenance
X2-6
X2-7
X2-8
External reset-in
External reset-in return
Remote Start/Stop
Remote Start/Stop
Return and Auto /
Maintenance Return
RS-485 A and -B
RS-485 Ground
This is an input signal to the soft starter and may be used to remotely reset the soft starter from e.g. a
PLC controller.
NOTE that the system must be configured for REMOTE operation (refer paragraph 6.7.1), close this
contactor to reset the soft starter, open it to allow the soft starter to continue.
Input: This input will start the soft starter when the switch is closed and stop the soft starter when the
switch is opened.
This is an input signal to the soft starter and may be used to remotely start the motor from e.g. a PLC
controller. The controller should use the Ready Relay output (refer Table 12 X1-1 and X1-2) to be able
to detect when the soft starter is ready to start the motor.
NOTE that the if the system is started with this signal and then stopped from the HMI push-button
or Modbus controller, this switch will first have to be opened and then again closed before the
motor will again start from a remote signal
Input: Auto / Maintenance. When this signal is active the Soft starter is in ‘Auto’ and control will be
possible from any remote location via RTU, TCP, PLC discrete inputs AND the TFT or Pot HMI on the
box. When this signal is not active the Soft starter is in ‘Maintenance’ and the control will be possible
from local location only i.e. via the Potentiometer HMI.
NOTE that this is a normally-closed switch connection. If not used the terminals must be bridged
or the soft starter will be in Maintenance.
Modbus RTU communication port. Two wire RS485-A and RS485-B terminals.
(This port is also available on J2 and J3 RJ45 connectors)
X2-9
X2-10
DC Ground
24V DC
Provide 24V DC (1A) on this input to be able to safely configure the soft starter, or update software,
without having the 3 phase power connected.
43 Wiring
Figure 29 – Terminal X2 (Core) – wiring example
MEsoftstart PC Interface
The MEsoftstart PC interface is available as a two-wire RS485 port plus ground Modbus RTU interface on all MEsoftstart/I models
(MEsoftstart/I00 – MEsoftstart/I04).
On Pro variants of MEsoftstart/I01 – MEsoftstart/I04, the MEsoftstart PC interface is also available on the Modbus TCP interface
(on the Ethernet port).
For the Modbus RTU it is recommended to use the dedicated RS485 to USB cable that is available with the MEsoftstart PC App.
This cable plugs in on the J2 or J3 RJ45 connectors on the soft starter (refer Figure 19) and connects to a USB port on the PC.
Note that drivers for the RS485 to USB converter may need to be installed. For the MEsoftstart dedicated cable, the drivers will
be provided with the cable. Refer par 7.1 for instructions to install the drivers and the application.
The soft starters may be daisy-chained on the RS485 line to enable the PC to configure them one after the other without having
to move the cable. To minimise reflections the RS485 lines need to be terminated with a 120Ω resistor at the far end.
Modbus TCP is available on the Pro variants’ Ethernet RJ45 port on J1 and a standard Ethernet cable may be used between the
soft starter and the PC, SCADA or PLC as required.
44 Wiring
PRECAUTIONS FOR USE OF THE SOFT STARTER
This chapter explains the precautions for use of this product. Always read the instructions before using the equipment.
PRECAUTIONS FOR USE OF THE SOFT STARTER ............................................................................................................... 45
The MEsoftstart/I series soft starter is a highly reliable product, but an incorrect peripheral circuit may shorten the product life
or damage the product. Before starting operation, always recheck the following points:
Refer
Checkpoint
Countermeasure
Checked
The soft starter model is
appropriate for the motor
that will be connected to
it.
There is adequate space
for air-flow around the soft
Terminals are insulated.
The main circuit cable
gauge is adequate.
lines
(L1, L2, L3), Circuit breaker,
Fuses, soft starter and
motor is correct.
contactor is used, the
wiring between the bypass
terminals is correct.
If the soft starter model is not appropriate
for the motor that it is connected to, the
starting current may not be enough and the
motor can overheat.
- Consider a larger model soft starter.
- Consider
delta to the motor.
- Consider adding an external bypass
contactor (for models without built in
contactor) - this may reduce the thermal
load on the soft starter.
- Contact your local distributor for
assistance to find the best solution.
If the air-flow is restricted, the soft starter
will overheat and trip.
Use terminals with insulation sleeves to wire
the power supply and the motor.
Use an appropriate cable gauge to suppress
the voltage drop to 2% or less. If the wiring
distance is long between the soft starter and
motor, the voltage drop in the main circuit
will cause the motor torque to decrease.
Direct application of power to the motorside output terminals (T1, T2, T3) of the soft
starter will damage the soft starter.
Inadvertently connecting the supply lines to
the Bypass terminals will damage the soft
starter
- Confirm that the line voltage is within the
soft starter’s rated voltage range.
-
current.
- Confirm that the fuses that are installed
are according to the specification in Table
7 for the selected soft starter model.
- Confirm that if an external bypass
contactor is used, the contactor is rated
for the operating current of the motor.
Table 1
Table 2
Table 3
Model: MEsoftstart/I03
Continuous
rated
current:
Max.
starting
Max
starting
current:
Table 4Table 4
Table 5
Paragraph 2.3.3
Figure 21
Local standards
Table 7
600A
1440A Normal
duty
750A Heavy
Duty
46 Precautions for use
soft starter and
soft starter
soft
Checkpoint
Countermeasure
- If the phases to or from the bypass
contactor are swapped around, a short
circuit will be caused between phases
when the soft starter closes the bypass.
- Before switch-on, inspect to confirm that
the phases on the bypass contactor are
wired using the same orientation as on
the soft starter.
No wire offcuts or
remnants from drilling
are left in the enclosure.
Wire offcuts can cause failure or
malfunction. Always keep the
enclosure clean.
When drilling mounting holes in a cabinet
etc., take caution not to allow chips and
other foreign matter to enter the
or to remain the the enclosure.
The protective covers are in
place over the Grid and
Motor terminals.
The protective covers should be replaced
once the wiring is done and before applying
power to the soft starter.
Emergency stop is wired to
the circuit breaker and is in
a position where the
operator has easy access.
The emergency stop should remove all
power to the soft starter and the motor and
should be hard wired to the main circuit
breaker to ensure that the operator can
reliably stop the motor in case of an
emergency.
Countermeasures are taken
against EMI.
The input/output (main circuit) of the soft
starter includes high frequency components,
which may interfere with the communication
devices (such as AM radios) used near the
soft starter. In such case, install a noise
filter.
On the soft starter's output
side, there should be no
power factor correction
capacitor, surge suppressor,
or radio noise filter
Such installation will cause the soft starter to
trip or the capacitor and surge suppressor to
be damaged. If any of the above devices are
connected, remove it before power is
applied.
installed.
Refer
Checked
Paragraph 2.3.6
Par 3.2.3
Figure 7
-
Paragraph 2.1.4
No short circuit or ground
fault is present on the soft
starter's output side.
- A short circuit or ground fault on the soft
starter's output side may damage the
starter.
- Fully check the insulation resistance of
the circuit prior to installing the soft
starter. Repeated short circuits caused by
peripheral circuits inadequacy or a
ground fault caused by wiring insulation
inadequacy or reduced motor insulation
resistance may damage the soft starter
module.
- Fully check the phase-to-earthing
(ground) insulation and phase-to-phase
47 Precautions for use
-
Checkpoint
Countermeasure
insulation of the soft starter's output side
before connecting the soft starter.
- This is especially important for an
installation with an existing or old
motor or use in a hostile atmosphere to
make sure to check the motor insulation
resistance.
The voltage applied to the
soft starter I/O signal
circuits is within the
specifications.
Application of a voltage higher than the
permissible voltage to the soft starter I/O
signal circuits or opposite polarity may
damage the I/O devices.
Refer
Paragraph 3.2
Checked
48 Precautions for use
BASIC OPERATION – CORE MODELS
This chapter explains the configuration and the basic operation of the core variants of MEsoftstart Industrial soft starter.
This chapter explains the operation and use of this product. Always read the instructions before using the equipment.
On power-up, the soft starter will be in IDLE mode. The user will be presented with HMI LEDs that indicates that the power is
present and the supply phase is detected.
When 24V power is present this LED will flash at a frequency of 0.5 Hz. When Modbus RTU communication has been
established and the soft starter is under Modbus control this LED will flash at 1 Hz.
LED off
No power
No power on the CPU card in the soft starter.
0.5Hz Flashing
1 Hz Flashing
Modbus not
detected
Power present;
Modbus in
control
The power is present on the CPU card. CPU is not detecting any Modbus
communication.
The power is present on the CPU card. Soft starter is under Modbus control.
Use the Modbus commands to start and stop the motor.
Phase LED
This LED indicates the detected phase of the applied 3-phase power. The configured phase orientation must be
Clockwise. The interpretation of the Phase LED state is described in the table below.
LED state
LED off
LED on
0.5 Hz
flashing
Detected phase
Unknown phase
Correct phase
Phase error
This occurs before AC power is applied and during phase synchronisation
immediately after application of AC power.
The phase rotation is correct.
An incorrect phase rotation is detected.
Description
If the Phase LED is flashing the indication is that the phase rotation of the 3-phase grid connection to the soft starter is incorrect.
Switch off the grid voltage and swap the incoming phases.
The Mode LED should be off at this stage, indicating that the soft starter is in IDLE mode. The operational modes of the
MEsoftstart/I core model is illustrated in the Figure 30 below:
50 Basic operation – Core models
Figure 30 – MEsoftstart/I Core operational modes
The interpretation of the Mode LED state is described in the table below.
flashes.
engaged. The motor shou
ld be running
.
restart delay time.
flashing
starter awaits
further operator intervention. See error LED for more details.
The Mode LED will indicate the operational mode of the soft starter as shown in the table below.
Mode LED
This LED provides feedback regarding the mode of the software. The Mode LED state can be interpreted whenever
the Power LED is flashing.
LED state
LED off
5 Hz Flashing Ramp mode
LED on
1 Hz flashing Delay mode
0.5 Hz
Software mode
Idle mode
Running mode
Error mode
This is the state when 24Vdc is present, but prior to application of the AC
voltage, or
if AC voltage is present but the soft starter is under Modbus control: prior to
a START command.
After a START or STOP command (HMI panel button, Modbus command or
Remote command), while the ramp-up or ramp-down is in progress, the LED
Ramp-up has been completed and if present, bypass contactor has been
After stop or ramp-down is completed, the Soft starter is implementing the
An error condition was detected. All switching elements are off. The soft
Mode description
In the case that the soft starter is in ERROR mode, the Error LED will help to troubleshoot the cause of the fault – refer paragraph
5.4.
Configure the soft starter for the application
The MEsoftstart/I core models are easy to configure, using the guidelines listed below. The configuration options from the HMI
panel are shown in Figure 31.
The switches to the left and right of the START | STOP key can be used to configure the soft starter as listed below:
51 Basic operation – Core models
Switch
Usage
JOG
Potentiometer
Usage
Bypass
Duty
The soft starter can be used with a built-in or external bypass contactor. A bypass contactor is activated once
the motor is running and reduces the current through the soft starter switching elements while the motor is
running. If present, the bypass contactor is controlled from the soft starter and is activated as soon as the motor
is running and de-activated before the stop ramp commences.
If the soft starter is configured for use without a bypass contactor, the running current of the motor passes
through the soft starter for the entire time that the motor is running.
A bypass contactor is recommended for installations where the motor is started a few times a day and run for
long periods between starts.
A bypass contactor does not add much value when the motor is started and then run for short intervals.
For models with built-in contactors this switch should always be in the ‘Bypass’ position.
When the soft starter is installed in a site where the motor requires a long start ramp or more than 10 starts
per hour, this switch should be set to Heavy Duty and the selection criteria in Table 1 to Table 2 for Heavy
Duty should be used to scale the motor size and the soft starter. Heavy duty usage generates more heat
internally to the soft starter and the lifespan of the soft starter will be affected if the soft starter is used in an
application that is not suitable for the duty of the motor.
The switch may be set to Normal Duty when the start ramp time is 30 seconds or less and the starts per hour is
10 or less.
Note that when the switch is changed to ‘Normal’ the ‘Maximum Number of starts per hour’ reverts to 10. This
may be changed using the Modbus interface (or PC Application) to any number of starts per hour up to 10.
When the switch is changed to ‘Heavy’ the ‘Maximum Number of starts per hour’ reverts to 60. This may be
changed using the Modbus interface (or PC Application) to any number of starts per hour up to 60.
The soft starter provides the capability to JOG the motor. This functionality may be used to e.g. align a conveyor
belt with a loading bay. The JOG functionality will allow the user to slowly turn the motor while the START button
is being pressed. The motor will coast to a stop when the START button is released.
JOG will run the motor at the percentage as set by the Start Ramp Starting % potentiometer.
The Motor Full Load Current % should be set correctly for the motor that is being used.
The intention of JOG is to use the functionality for short, infrequent periods. Over-use of the JOG function will
overheat the motor and the soft starter and will activate a temperature trip.
The normal setting for this switch is ‘NORMAL’. In NORMAL the START button will initiate a start ramp to start
and run the motor.
Motor connection
The soft starter allows for motor to be wired in normal 3-wire connection or in 6-wire inside-delta connection.
The inside-delta wiring allows for a lower current that flows through the soft starter and larger motors may be
used with the same size soft starter. Refer to Figure 5 for Inside-Delta connection.
Refer paragraph 2.1.1 and paragraph 2.1.2 to understand the difference between the wiring, to be able to make
the correct selection.
The potentiometers can be used to configure the soft starter as listed below:
Start Ramp Duration The duration of the start ramp can be adjusted from 5 seconds to 30 seconds.
Stop Ramp Duration
The stop ramp may be disabled by setting this dial to zero and the motor will coast to a stop. When a controlled
soft-stop is required, the stop ramp duration may be set up to 30 seconds.
Start Ramp starting %
The Start Ramp may be started between 15% and 60% depending on the load of the motor. Starting the ramp
at too low a percentage will cause heating build-up in the motor without actually turning the motor.
52 Basic operation – Core models
This potentiometer sets the current limit during start
-
up. The current can be limited between 1x and 6x
provide (as specified in
Table
1
for the
MEsoftstart
/I00 and
Table
2 for the
MEsoftstart
/I01).
Stop Ramp ending %
If enabled, the stop ramp may be stopped at between 60% and 15% after which the motor will coast to a stop
if not stopped already.
Current Limit during startup
Motor Full Load current
(600%) the full load current of the motor (within the limits of the soft starter). Refer
Example: For the MEsoftstart/I00 which is a 100A soft starter with starting current of 240A in Normal Duty,
the starting current for a 22kW motor with full load current of 40A at power factor of 0.8, may be limited to a
value between 240A (6x or 600%) and e.g. 80A (2x or 200%)
Note that if the potentiometer is set to a value higher than the soft starter starting current rating for the
selected Duty and selected motor size, the current will be limited to the maximum that the soft starter can
This potentiometer configures the size of the motor. The motor size is configured in relation to the soft starter
continuous current.
Examples:
For the MEsoftstart/I00 which is a 100A continuous current soft starter:
Configure a 22kW motor (with 40A full load current at power factor of 0.8) at 40%.
Configure a 55kW motor (with 99A full load current at power factor of 0.8) at 100%
For the MEsoftstart/I01 which is a 200A continuous current soft starter:
Configure a 75kW motor (with 135A full load current at power factor of 0.8) at 67%.
Configure a 110kW motor (with 199A full load current at power factor of 0.8) at 100%
Additional configuration parameters
In addition to these parameters, the soft starter may be configured via the Modbus RTU interface for:
Table 1
to Table 2.
Motor protection class between 5 and 30 (default is 10).
PT-100 motor temperature sensor to cause a trip on motor temperature more than the maximum allowed temperature.
Maximum motor temperature (applicable if the PT-100 is selected) ([90°C - 175°C] - default is 120°C)
Motor restart temperature (applicable if the PT-100 is selected) ([40°C - 90°C] - default is 60°C)
Number of starts per hour [1 – 10] for Normal Duty (default is 10); unlimited for Heavy duty (default is 60)
Voltage imbalance [0 – 25%]; default is 20%.
Current imbalance [0 – 20%]; default is 10%.
Controlling the soft starter
The MEsoftstart/I Core models are easy to control, from the HMI panel, or from a remote controller via the inputs on the green
I/O terminals, or from a Modbus controller via the Modbus RTU ports on the bottom of the soft starter.
Using the Auto/Maintenance-feature
The MEsoftstart soft starter features an Auto/Maintenance input on the green terminals, which may be used to prevent
inadvertent START / STOP or RESET control of the soft starter from a remote location while e.g. maintenance is in progress.
Note that to be able to use the Auto/Maintenance function, the Maintenance switch must be wired on the soft starter (refer
Table 17). Note that the Auto/Maintenance input on the soft starter must be normally closed (for the soft starter to be in Auto
control to enable control from remote PLC, or any Modbus master, or the TFT panel). The Maintenance switch must open the
53 Basic operation – Core models
Auto/Maintenance input on the soft starter to prevent remote control of the soft starter. When the Auto/Maintenance input is
open, the soft starter will only accept control inputs locally on the soft starter, from the TFT panel.
The Auto/Maintenance feature must never be used in place of a proper safety procedure to ensure the safety of
personnel working on the soft starter or the motor.
Start, Stop or Reset
The user may START, STOP or RESET the motor via the MEsoftstart/I soft starter as shown in Figure 34.
Figure 32 – MEsoftstart/I Core – Start, Stop and Reset control options from the HMI panel
Figure 33 – MEsoftstart/I Core – Start, Stop and Reset control options from the PC Application
54 Basic operation – Core models
Figure 34 – MEsoftstart/I Core – Start, Stop and Reset control options from the green wiring terminals
Note that (when in Auto control) the motor can be started from any of the three control inputs and stopped from any of the
three control inputs.
Example: If the motor is started from a remote controller by closing the switch on the green terminal and then the motor is
stopped by pushing the START/STOP button on the HMI panel, the motor will be stopped and can only be started again from the
remote controller after the switch is opened and then closed again.
If work needs to be done on the motor or the load, ensure that the Main supply is switched off to prevent inadvertent
starting from a remote switch or Modbus Master.
If an error occurs the motor will be stopped and the ERROR LED will be flashing to indicate the cause of the fault - refer paragraph
5.4. Once the cause of the fault is understood and removed, the soft starter will have to be RESET before operation can continue.
RESET can be done from the HMI panel, the Modbus RTU controller or a remote controller on the green terminal.
Jog
The ‘Jog’ functionality is available to slowly crawl a motor and its load to e.g. align a conveyor with a loading bay. Jog can be
configured and controlled from the HMI panel, as shown in Figure 35.
55 Basic operation – Core models
Figure 35 – MEsoftstart/I Core – JOG setup and control
Take care not to over-use the JOG functionality as the motor and the internal switching elements in the soft starter will
overheat quickly if JOG is done for prolonged periods.
Troubleshooting the MEsoftstart/I core variant
No LEDs on
When connected to three phase power the Power LED should be on, and the Phase LED should be either ON or flashing. If neither
of these two LEDs are on the following checks should be done:
i. Measure the incoming three phase supply power on the Grid-side terminals of the soft starter. If there is not supply
power on all three terminals, check the Main Circuit Breaker and contact the installer to find the problem.
ii. If the supply voltage is present on all three phases (measured on all three terminals) and the soft starter is not showing
any LEDs, please contact your distributor for support.
Flashing Phase LED
i. A flashing phase LED indicates that the phase rotation of the 3-phase supply is wrong. Switch off the main circuit breaker
and swap the incoming lines so that Line 1, Line 2, Line 3 is connected to the Power terminals in that order.
56 Basic operation – Core models
a period of more than 60 seconds.
brown
-
out condition was detected.
where ra
mping is halted due to the
current limit being reached
.
Motor temperature
Motor temperature is high and caused the soft starter to trip to protect the
Bypass contactor
The soft starter is configured for a bypass contactor, but the contactor
did not
Mode LED flashing at 0.5Hz
A Mode LED that is flashing at 0.5 Hz indicates that the soft starter is in Error Mode and the ERROR LED will show a flash pattern
as described below. Use this table to determine the cause of the fault.
The Error LED provides feedback on error conditions. When no error condition is detected, this LED will be off.
When an error is detected the LED will repeat a sequence of flashes specific to the error condition. The sequence
will consist of a number of 0.5s-on and 0.5s-off flashes, followed by an off-period of 1.5s.
The table below describes the number of flashes for each error condition.
Flashes Error
2 Motor underload
Description
A motor underload condition (MULC) is detected, with the motor current
falling below a configured percentage e.g. 10% of the rated motor current for
3 Line voltage
4 Frequency
5 Over current (start) Current exceeds the configured current limit during ramp-up.
6 Ramp Up Time
7 Motor overload
Over current
8
(running)
Supply voltage
9
unbalanced
10 Switching element
Internal
11
temperature high
12
too high
13
not present
Over- or under voltage condition detected on the input voltage lines or a
Detected frequency differs from expected frequency by more than 5%.
Total ramp-up time exceeds the limit configured. This includes the periods
The motor protection curve for the configured protection class was violated.
Current exceeds the set current for the motor or soft start limit.
Voltage levels on input lines differ from each other with more than 20%.
Current flow detected in a line where the switching element is switched off, or
no current flow when the switching element or bypass contactor should be
conducting.
Internal temperature of the soft starter is high and caused the soft starter to
trip.
motor.
close (when switching over after the start-ramp is completed).
Phase detection
i. Switch the main supply off.
ii. Measure to ensure that all three phases of the supply voltage is present. Check Circuit breaker and measure continuity
through the fuses on each phase.
iii. Switch main supply on.
iv. Verify that the Phase LED comes on and stays on (not flashing).
v. Confirm that the phase rotation is the same as the configured phase rotation on the PC Application (the default phase
rotation in Clockwise)
vi. Re-try starting the motor.
vii. If this error occurs repeatedly and all other checks are done, contact your distributor.
Motor underload
i.Check the motor and the load. This error typically occurs on e.g. a pump application when the pump is running dry.
57 Basic operation – Core models
ii. Check the Motor size setting (Rated Current% potentiometer) on the HMI panel and confirm that this is correct
according to the manufacturers nameplate. (This setting can also be confirmed on the PC Application).
iii. Adjust the Motor Underload percentage (MULC%) on the PC Application. The default is 10%.
Line voltage
iv. Check the supply voltage levels. Measure all three phases and confirm that the supply voltages are within the limits of
the supply voltage for the soft starter (refer Figure 4).
v. If supply voltage is within limits while the motor is not running, start the motor and monitor the supply voltage while
the motor is running. Measure the supply voltage at the soft starter GRID terminals.
vi. If this error occurs repeatedly and all other checks are done, contact your distributor.
Frequency
i. Check the supply frequency. Measure all three phases and confirm that the supply frequency is within the limits of the
supply frequency for the soft starter (refer 10.1).
ii. If supply frequency is within limits while the motor is not running, start the motor and monitor the supply frequency
while the motor is running. Measure the supply frequency at the soft starter GRID terminals.
iii. If this error occurs repeatedly and all other checks are done, contact your distributor.
Over current (start)
This error occurs during the start ramp.
i. Check the motor nameplate for the full load current specification of the motor and re-check the soft starter continuous
current rating as well as the maximum starting current for the MEsoftstart soft starter.
ii. Confirm that the maximum starting current of the MEsoftstart soft starter for the duty required by the installation, is at
least three times the motor full load current (refer paragraph 1.1.1)
iii. If possible, connect the PC Application to the Modbus RTU connector on the soft starter and read back the configuration
(refer par 82). The PC Application will numerically display the configuration of the soft starter so that it is easy to see
where the problem lies.
iv. Confirm that the ‘Rated Current%’ potentiometer is set correctly for the size of the motor (refer paragraph 5.2 above).
– If the motor size is wrong, the soft starter will apply an incorrect ramp during start-up.
v. Check the setting of the ‘Start current’ potentiometer. Turn this potentiometer up to allow for a higher starting current.
A typical start current is between 400% and 200% of the Motor Full Load current.
vi. Check the Normal/Heavy setting – When Heavy duty is selected, the soft starter will limit the starting current.
vii. Confirm that the Normal / Inside Delta switch setting is correct for the installation – When Inside Delta is selected the
soft starter will limit the current to 58% of the required current for the selected motor size.
viii. Confirm that the Start Ramp starting% is not too high for the configured motor size. 60% may be too high for a small
motor especially when wired as inside delta.
ix. If changing the settings does not fix the problem contact your distributor for advice.
Ramp up Time
A trip on Ramp-Up time is an indication that the motor takes too long to start with the Soft starter configuration.
i. Make the ‘Start Ramp’ longer
58 Basic operation – Core models
ii. Make the ‘Start Current’ higher.
iii. Make the ‘Start%’ higher.
iv. If none of these actions resolve the problem, check the motor nameplate for the full load current specification of the
motor and re-check the soft starter continuous current rating as well as the maximum starting current for the
MEsoftstart soft starter and contact your distributor for advice.
Motor overload
This error is related to the Motor protection class. The default protection class is 10. If this causes an error, confirm that the
motor and wiring is correct and check with the motor manufacturer if the protection class may be changed to 20 or 30 using the
PC Application.
Over current (running)
i. Check the wiring to the motor.
ii. Check that the motor temperature is not too high.
iii. Confirm that there is no overload on the motor.
Supply voltage and current imbalance
i. The default permitted supply voltage imbalance amongst phases is 20% (refer paragraph 5.2.1). Measure the imbalance
and if below 25%, use the MEsoftstart PC app to change the imbalance percentage to 25% if the motor specification
permits that. If more than 20%, contact your plant electrician to check and try to balance phase loading for the plant.
ii. The default phase current imbalance is 10% (refer paragraph 5.2.1). This can be set to 20% maximum using the
MEsoftstart PC application if the motor specification permits it.
Switching element
This error indicates a hardware fault inside the soft starter. Contact your distributor.
Internal temperature high
This error occurs when the temperature inside the soft starter is too high. The soft starter will trip and only allow a restart again
when the soft starter has cooled down to room temperature.
i. The error may occur because of overuse of the JOG function.
ii. A long start-up ramp time on a motor with heavy load will also cause a temperature trip. Configuring the soft starter
for Heavy Duty (refer paragraph 5.3 above) for a lower limit during the start ramp, may cure the problem. Re-confirm
the motor size and starting current for Heavy Duty in
iii. Table 1 or Table 2 above.
iv. If there is no overuse or abnormal load or environmental conditions that may contribute to this issue and the soft starter
repeatedly trips on this error, please contact your distributor for advice.
59 Basic operation – Core models
Motor temperature too high
This error occurs when the temperature on the motor is higher than the ‘Maximum Motor Temperature’ that is configured (refer
paragraph 5.2.1). The soft starter will trip and only allow a restart again when the motor has cooled down to below the configured
‘Motor restart temperature’.
i. The error may occur because of overuse of the JOG function.
ii. Check the motor.
iii. Check the load.
iv. If there is no overuse or abnormal load or environmental conditions that may contribute to this issue and the soft starter
repeatedly trips on this error, please contact your motor supplier for advice.
Bypass contactor not detected
This error occurs where the soft starter is configured for a bypass contactor which is not present or not working as it should.
After the start ramp is completed, the soft starter closes the bypass relay and then switches off the SCRs (in which case the motor
will coast to a stop when it should be running, and will switch on hard when it should be stopping if the bypass contactor is not
in place).
i. This is most probably a configuration error – if the bypass contactor is not present, ensure that the dip switch on the
HMI is in the correct position showing that a bypass contactor is not present.
ii. The error may be due to a wiring problem where the bypass contactor is not being activated when the start ramp is
completed. Refer to Figure 28.
iii. Confirm that the soft starter output is functioning correctly: First configure for no bypass contactor and start the motor.
Measure the Bypass output on the green connector X1. This contactor should be closed when the start ramp is
completed. (Note that this switching of the relay happens in any case – whether configured for bypass or not).
iv. Confirm that the Contactor is functioning correctly and that it does close when an appropriate activation signal is
applied.
v. If the soft starter is malfunctioning, please contact your distributor for support.
No communication on Modbus interface
If a Modbus Master device is connected to the RTU (RS485) Modbus port on the Core variant soft starter, the soft starter should
start communicating when polled for data. The Power LED should start flashing faster at 1Hz (refer paragraph 5.1), indicating
that communication with the Modbus master has been established. The default settings for the RTU Modbus interface is as
specified in paragraph 10.1, with a Modbus address of 1.
i. Check the communication settings on the Modbus master and confirm that they are correct.
ii. If the Modus master is running on a PC, ensure that the correct drivers for the Modbus RTU (to USB) cable is installed
on the PC.
iii. If it is possible that the Modbus settings on the soft starter-side have been changed or tampered with, do the following
to restore factory defaults on the Modbus settings:
a. Switch power off;
b. Unplug all Modbus RTU cables;
60 Basic operation – Core models
c. Press and hold the Reset button for 20 seconds while switching power on. The four LEDs will flash together
once indicating that the factory restore has been completed;
d. Release the reset button;
e. Retry the Modbus communication with the default communication settings and address of 1.
iv. If the Modbus Master is not the MEsoftstart PC application, test the communication first with the MEsoftstart/I Core
variant PC application (refer paragraph 7.1).
v. Replace the cable with a supplied Modbus RTU cable. Install the provided drivers (refer paragraph 7.1.1.1) and test
again with the MEsoftstart/I Core variant PC application
vi. If the interface still does not work, contact your distributor for support.
61 Basic operation – Core models
BASIC OPERATION – PRO MODELS
This chapter explains the configuration and the basic operation of the full-featured pro variants Industrial soft starter
This chapter explains the operation and use of this product. Always read the instructions before using the equipment.
BASIC OPERATION – PRO MODELS .................................................................................................................................. 62
PERATIONAL MODES OF THE SOFT STARTER
O
OWER-UP THE SOFT STARTER
P
ETHOD OF VIEWING AND CHANGING CONFIGURATION PARAMETERS
M
ARAMETERS
P
ARAMETER INTER-DEPENDENCIES
P
ASIC OPERATION PROCEDURE - OPERATION FROM
B
ASIC OPERATION PROCEDURE – OPERATION FROM A REMOTE CONTROLLER
On power-up, the soft starter will be in IDLE mode. The user will be presented with a menu to Start the motor or to make the
selection to enter a configuration setup menu where parameters can be viewed and changed.
Figure 36 – Modes of operation of the soft starter
The soft starter can be configured via the TFT screen on the front panel or via the Modbus RTU or TCP interface using a SCADA
system, or with the MEsoftstart PC Interface. This section describes the configuration using the TFT screen. Refer to par 7.1 for
an overview on using the PC Interface.
If the user selects to configure the soft starter, the user is presented with options to select a Factory Default Configuration
(refer Table 18), or to create a User Configuration. In the case of a User Configuration, changes will be saved to the local nonvolatile memory on the soft starter as the ‘CUSTOM’ configuration. The saved configuration (or CUSTOM configuration) then
becomes the active parameter set that will be used whenever START MOTOR is selected.
The user may at any time revert to the pre-set Factory Defaults (refer Table 18). If the current configuration is unknown, the
user may select to start with a Factory Default set of parameters and then make minor changes on that for a custom
configuration.
63 Basic operation – Pro models
Power-up the soft starter
At power-up the soft starter TFT display will present the user with the option to Start the motor (if the current configuration is
known) or to configure the soft starter for the required language, size of the motor and settings for the application. Section 6.4
below explains the parameters that can be changed and how that influences the operation of the soft starter.
Figure 37 – Power-up the soft starter
Method of viewing and changing configuration parameters
Once in the parameter configuration screen the parameter can be viewed, changed and saved or changed and cancelled. The
layout and usage of the PARAMETER screen and the EDIT screen are shown in Figure 38.
Enter the Parameter screen from the CONFIGURE screen (as shown in
Figure 37) Scroll through the parameters by pressing buttons
to go to the next parameter, or
to go to the previous parameter
button goes to the START screen (refer Figure 37)
and saves the configuration changes
button goes to the EDIT screen where the parameter
options can be viewed and changed.
Figure 38 – Viewing and changing parameters
The EDIT screen allows the user to scroll through the options or values
of the parameter using buttons:
Note that when scrolling through the parameter list - the list will wrap
around and start again with the same list.
to go to the next parameter option in the list or in the
case of a numeric parameter, to increment
to go to the previous parameter option in the list or in
the case of a numeric parameter, to decrement
to cancel any changes and go to the PARAMETER
screen
to save the change and go to the PARAMETER screen.
64 Basic operation – Pro models
6.4.1 Basic Setup
– Motor
6.4.2 Basic Setup
– Start Setup
6.4.3 Basic Setup
– Stop Setup
Parameters
This section explains configurable parameters. Parameters can be viewed and changed when the user selects to ‘Configure the soft
starter’ and then selects ‘User Configure’ (refer Figure 37). A menu will be presented allowing the user to configure the soft starter
as shown below.
Table 18: Configurable parameters of the soft starter
Reference Parameter group Parameters Factory Default (where applicable)
Hardware
• Inside Delta = No
• Workload Norm/Heavy = Normal
• Bypass Contactor = Absent
• Motor Size kW (depends on frame size)
• Motor Application = Default
• Phase Rotation = Clockwise
• Protection Class = 10
RPM Sensor Presence = No
• Start Type = Ramp
• Ramp Type = Linear Time
• Ramp Up Time = 10s
Maximum Starting Time = 60s (Normal
Duty) or unlimited (30minutes - Heavy
Duty)
65 Basic operation – Pro models
• Stop Type = Coasting
Ramp Down Time = 10s
6.4.4 Advanced Setup
6.4.5 Temperature Setup
6.4.6 Jog Control Setup
Reference Parameter group Parameters Factory Default (where applicable)
• Kickstart Voltage % = 60%
• Kickstart Period = 0.2s
• Constant Current % = 50%
• Pedestal RampUp % = 20%
• Pedestal RampDown % = 50%
• MSC % = 200%
• MULC % = 80%
• MOLC % = 100%
• Maximum Starts/Hour = 10
• Ramp Start Angle % = 0%
• Alpha Skip Start % = 36%
• Alpha Skip Stop % = 36%
Note that same value for Skip Start and Stop
implies that the Skip is disabled.
• Heatsink Fan Control = No
• Maximum Motor Temp = 120°C
• Heatsink Restart Temp = 40°C
• Motor Restart Temp = 45°C
• Heatsink Fan Start = 40°C
• Motor Temp Selection = PT100
Note: TMotor indicates that the LM35 sensor is
selected.
• Jog Motor Voltage = 0
(Jog disabled)
66 Basic operation – Pro models
6.4.7 Supply Tolerances
6.4.8 General Setup
6.4.9 Communication Setup
Reference Parameter group Parameters Factory Default (where applicable)
• Max Volt Imbalance = 20%
• Max Current Imbalance = 10%
• Nominal Grid Voltage = 400V
Note that changing the nominal grid
voltage requires the installer to ensure
that all connected contactors (Bypass
etc) have their coils updated to the
same voltage level or damage to the
coils will ensue
• User Language = English
• Motor Name = ‘Motor1’
• Local/Remote Mode = Local
• Password Edit = 0 (disabled)
• Fault / Incoming CB = Fault
Basic Setup – Motor Hardware
The parameters that can be configured under this group are:
67 Basic operation – Pro models
• RS485 Baudrate = 115200
• RS485 Parity = Even
• Modbus Slave Address = 1
• TCP/IP Parameters
Own IP address = 192.168.0.15
IP subnet mask = 255.255.255.0
Client IP address = 192.168.0.16
Gateway address = 192.168.0.1
This parameter defaults to Normal
connection. If the Inside Delta option is selected, the soft starter will
Workload Norm/Heavy
Bypass Cont
actor
Default: Absent
(for models without built
-
in bypass; Present for models with built
-
in bypass)
Motor Size kW
The range of motor frame sizes that may be started with the
MEsoftstart
model soft starter is dependent
Check the motor rating plate and ensure that the correct motor size is selected here.
Motor Application
The typical applications for which the soft starter may be used, each has a pre
-
set factory default
Phase Rotation
ParametersDescription - with options or range
Inside Delta Connection
allow a wider range of motor sizes (since the current through each phase will be only 58% of the phase
current for normal delta connection.)
Do not select Inside Delta when the motor is wired for a normal 3-wire motor.
This parameter specifies whether the soft starter will be used for a Normal duty or Heavy duty application.
Normal duty is defined as no more than 10 starts per hour (> 6 minutes between starts) and start ramp
shorter than 30s.
Heavy duty is defined as more than 10 starts per hour (<6 minutes between starts) or a start ramp 30s
or longer.
The implication of the load duty selection is described in paragraph 1.1.1.
This parameter specifies to the soft starter that the user installs an external bypass contactor for a
MEsoftstart model that has no bypass contactor installed.
If an internal bypass contactor is present, this parameter will be default ‘Present’.
Ensure that this parameter is correct since the soft starter will allow for a higher running current when a
bypass contactor can be switched in after the start-up is completed. Setting this parameter incorrectly can
cause damage to the soft starter and will cause unexpected behaviour such that the motor to coast to a
stop once the start ramp is done, when Bypass is configured for but not present.
on the following parameters:
Supply voltage
Inside Delta or Normal 3-wire connection
Load Duty (Normal or Heavy)
Bypass contactor present or not present
Depending on this configuration, motor sizes may be selected as specified in the tables for each MEsoftstart
model in paragraph 1.1.1.
The TFT display guides the user by presenting only the applicable list of motor sizes and by showing the
typical motor full load current at a power factor of 0.8.
The motor size or rated current can be found in the rating plate of the motor.
Once the motor size is selected, the Max Full Load Current (MFLC) is automatically calculated and displayed.
configuration. The supported applications are listed below.
Notes:
i. The user should select an application profile and then adjust parameters as needed. The selected
configuration will be saved as the User configuration, which will be used to run the soft starter.
ii. If the user’s application is not one of the listed applications, Select ‘Pump’ and set the parameters as
required for the user’s installation.
iii. The User configuration can also be modified if further adjustments are needed.
• Default (select this profile to keep the current configuration)
• Fan
• Pump
• High pressure pump
• Compressor
• Conveyor Belt
This parameter specifies the required direction of the incoming Grid Phase rotation. This can be set to
[Clockwise, Anti-clockwise, Don’t care]
Note: If set to either clockwise or anti-clockwise, then the incoming direction of phase rotation must be
in the selected orientation or the motor will not start and the operator will be allowed to either correct
the wiring or change the direction of rotation.
68 Basic operation – Pro models
Protection Class
RPM Sensor Presence
This parameter should be set when a shaft sensor is fitted for the Soft starter to measure motor speed in
Start Type
Ramp Type
Lin/RMS/S
Parameters
Description - with options or range
If set to “Don’t care” the soft starter will allow the motor to start in the direction of the present
direction of rotation of the phases.
If the direction of rotation of the motor is important, the Phase Rotation should not be set to
“Don’t care”. This bypasses the built-in protection that the soft starter provides.
This parameter can take a value of 2, 5, 10, 20 and 30 and represents the tripping class for motor
overload protection.
RPM.
Basic Setup – Start Ramp
Parameters that specify the start-up ramp time for the motor are configured under this group:
Parameters Description - with options or range
This parameter defines the different starting types that may be configured for the motor. They are:
[Ramp-up, Pedestal, Kickstart, Constant Current]
These parameters can be configured in the Advanced Setup (refer paragraph 6.4.4).
Note that this parameter is not used when Start Type is Constant Current
This parameter specifies the Ramp type that will be used during motor start and stop. Options are
[Linear Time, Linear RMS, and S-Curve]. Default is Linear Time. The selected profile will be applied to
the motor during starting and stopping (Ramp, Kickstart or Pedestal)
Adjusting the ramp type is an advanced feature of the soft starter.
Linear RMS:
This setting implies that a linear RMS voltage will be applied to the motor during starting and stopping
(Ramp, Kickstart or Pedestal). Linear RMS is shown in the graphs (the RED line)
Linear Time:
This setting will result in the RMS voltage applied to the motor as shown in the graph (the BLUE line).
S-Curve:
A Ramp type setting of ‘S-Curve’ will result in the RMS voltage that is applied to the motor as shown in
the graph (the BLUE line).
69 Basic operation – Pro models
Ramp Up time
Parameters Description - with options or range
This parameter defines the period during which the motor voltage, ramps-up.
The parameter is adjustable between:
[10 seconds – 60 seconds or the Maximum Ramp up time parameter].
Note: The Ramp-up time is limited when Normal duty is selected.
Note: The Ramp-up time can be extended by the current limiting functionality of the soft starter. In this
case the Ramp-up time will be made up of the total time where the soft starter is ramping-up the
output voltage. This ramp-up process will be cancelled if the Maximum Ramp-up time is exceeded.
Maximum Starting Time
This parameter defines the maximum period during which the motor may attempt to start within. The
parameter is adjustable between:
[10 seconds – 60 seconds] for Normal Duty
[10 seconds – 1800 seconds] for Heavy Duty
This time represents the maximum possible time that the motor could start in, which includes current
limited delays incurred during the motor starting phase. If the motor has not achieved a Running
status by the end of this time, the soft starter shall trip and display a fault.
Note: This parameter cannot be set to a value less than the “Ramp-up time” above.
Ensure to allow enough time to soft-start the motor within the limitation that is set. If the
time is set too short, the soft start ramp will be aborted before reaching running speed.
Basic Setup – Stop Ramp
Parameters that specify how the motor is stopped, are configured under this group:
Parameters
Stop Type This parameter defines the 3 different stopping types that may be configured for the motor. They are:
Description - with options or range
[Coasting, Ramp-down, Pedestal]
These parameters can be configured in the Advanced Setup (refer paragraph6.4.4).
Coasting:
In this mode, the Firing angle of the SCRs are instantly set to zero and the motor is allowed to coast to
a stop.
70 Basic operation – Pro models
Kickstart Period
Constant Current %
Parameters
Description - with options or range
Ramp Down Time In this mode, the Firing angle of the SCRs decreases linearly from the maximum to zero with the Ramp
up time.
This parameter defines the ramp down time [10sec – 30seconds]
Pedestal:
In this mode, the firing angle drops immediately to a predefined pedestal level. It remains at this
pedestal level until it intersects with the slope of a Normal Ramp down of the ramp down stop type.
At that time, it continues linearly down until it reaches the zero value
Pedestal Voltage
This parameter determines the voltage amplitude of the pedestal voltage as a percentage of the
nominal voltage. The parameter is selectable between [5% - 60%]
Advanced Setup
Parameters that specify the motor current are configured under this group:
Parameters
Kickstart Voltage %
Description - with options or range
In this mode, the Firing angle of the SCRs has a brief step function that lasts for a defined period
before returning to zero and then resuming a linear increase to the maximum value with respect to
the Ramp-up time.
This parameter determines the voltage amplitude of the kick-start voltage as a percentage of the
nominal voltage. The parameter is selectable between [5% - 60%].
This parameter is entered as a
percentage of Max Full Load
Current (MFLC) for the selected
motor
This parameter defines the period that the kick-start voltage is present for. The parameter can be set
between [200ms - 2 Seconds].
In this mode, the soft starter will increase the voltage until the specified current is measured and then
maintain the current for the duriation of the maximum start time or until full voltage reached (i.e. the
motor is running).
This parameter specifies the constant current as a percentage of the Motor Full Load Current, that the
soft starter needs to maintain during the starting of the motor.
71 Basic operation – Pro models
Pedestal RampUp %
Pedestal RampDown %
MSC %
motor
.
MULC %
Motor Under Load Current (MULC) is specified as a percentage of MFLC. This parameter can be set
MOLC %
For a 110kW motor on a
MEsoftstart
/I01 the MOLC parameter will be fixed at [100%
-
241%].
Maximum Starts/Hour
This
parameter will limit the starts per hour to protect the motor and the soft starter.
Parameters
Description - with options or range
Pedestal:
In this mode, the firing angle starts with a step jump to a defined level. It remains at this pedestal level
until it intersects with the slope of a Ramp-up Start Type. At that time, it continues linearly until it
reaches the maximum value.
This parameter determines the voltage amplitude of the pedestal voltage as a percentage of the
nominal voltage. The parameter is selectable between [5% - 80%].
This parameter is entered as a
percentage of Max Full Load
Current (MFLC) for the selected
Ramp Start Angle %
In this mode, the firing angle drops immediately to a predefined pedestal level. It remains at this
pedestal level until it intersects with the slope of a Normal Ramp down of the ramp down stop type.
At that time, it continues linearly down until it reaches the zero value.
This parameter determines the voltage amplitude of the pedestal voltage as a percentage of the
nominal voltage. The parameter is selectable between [5% - 60%].
The Maximum Starting Current (MSC) as a percentage of the Motor Full Load Current (MFLC).
Read the label on the load. The maximum starting current should be selected to match the
power requirement of the load (and not just selecting the maximum that the motor can
handle e.g. a 15kW water pump that is powered by a 30kW motor).
between [0% - 100%] and is typically used to cause a trip when e.g. a pump is running dry and the load
is subsequently drastically reduced.
Motor Over Load Current (MOLC) is specified as a percentage of MFLC. The parameter is adjustable
between 100% and 600% or up to the maximum Frame size capacity which is measured as a
percentage of Max Full Load Current (MFLC) for the selected motor as shown above e.g. :
For a 45kW motor on a MEsoftstart/I01, normal connection, no bypass contactor, the MOLC
parameter range will be [100% - 589%].
Note: The number of starts per hour is limited to 10 if Normal duty is selected.
This parameter sets the voltage level at which the ramp will begin (to bypass the start-up dead band).
The value can be set between [0 – 35%].
Note that this parameter is not applicable when Pedestal Start type is selected. If Kickstart-start type
is selected, this parameter is applicable immediately after kickstart is completed.
Alpha Skip Start %
Alpha Skip Stop %
These parameters allow the user to configure the soft starter to, during ramping, skip over an area
where the motor displays mechanical resonance (oscillation or vibration) This may be needed in a
small or no-load start-scenario.
The two parameters together define a band between [36% - 100%] where the voltage will jump.
Note:
i. ‘Skip stop’ must at all times be greater than ‘Skip start’. The soft starter configuration menu
will enforce this.
‘Skip start and Skip stop may not be further apart than 15%. Thus the maximum skip-jump
ii.
will be 15%. The soft starter configuration menu will enforce this
If the ‘Skip start’ parameter is equal to the ‘Skip Stop’ parameter, no voltage jump is
iii.
implemented
.
72 Basic operation – Pro models
.
Heatsink Fan Control
Maximum Motor Temp
Heatsink Restart Temp
Motor Restart Temp
Heatsink Fan Start
This parameter defines the temperature at which the heatsink fan must start and keep running. Below
Jog Motor Voltage
Temperature Setup
These parameters specify the temperature limits that will be used by the soft starter to ensure the soft starter and the motor
are operated within safe limits.
Parameters Description - with options or range
This parameter defines if the soft starter fan should be started when temperature becomes too high, or
if the fan should always run during motor start, stop and run.
Options are [Yes, No]. Default is ‘No’ (indicating that the fan will always run while stopping and starting.
This parameter defines the maximum temperature at which the motor may operate. It is specified in
the motor manufacturer’s documentation.
The allowed range for this temperature is dependent on the type of motor sensor that is configured
and installed (refer ‘Motor Temp Selection’ parameter):
‘Motor Temp Selection’ = PT100, this parameter may be set between [90°C - 175°C].
‘Motor Temp Selection’ = TMotor (LM35), this parameter may be set between [90°C - 115°C].
The default value is 115°C.
Important Note:
i. When the motor temperature reaches 110% of this value, a warning will be displayed on
the display unit.
ii. When the temperature reaches 120% the soft starter will trip and a fault will be displayed
on the display unit.
This parameter defines the temperature to where the heatsink must cool down after a trip on
excessive heatsink temperature, before the soft starter is ready for operation again.
This parameter may be set between [30°C - 60°C] The default value is 40°C.
This parameter is applicable when the motor has tripped due to exceeding the “Motor Maximum
Temperature”. The parameter defines the temperature below which a restart may safely be attempted
again.
This parameter may be set between [35°C - 80°C]. The default value is 45°C.
this temperature the Fan will stop running.
This parameter is only applicable when ‘Fan Temperature Control’ is set to ‘Yes’ and may be set
between [35°C - 50°C]. The default is 40°C.
Motor Temp Selection This parameter configures the soft starter for use of the LM35 temperature sensor (option TMotor) or
a PT100 sensor or no integrated motor temperature sensor.
The PT100 sensor is the default selection.
Jog Control Setup
Jog Motor Voltage settings can be changed with the parameter in this group:
Parameters Description - with options or range
The soft starter provides the option to manually ramp-up the motor at a fixed voltage increment. This
is typically used to test an installation or to do mechanical alignment and positioning of conveyor belts.
This parameter defines the percentage of nominal voltage that is applied to the motor when the Jog
function is operated. The parameter is settable between [0, 5%-80%].
0 indicates that the ’JOG’ option is disabled and a value of between 5% and 80% will ensure that the
JOG option is available on the Start screen.
73 Basic operation – Pro models
Max Volt Imbalance
This parameter is the maximum
percentage imbalance that can occur between the lowest and highest
Max Current Imbalance
Parameters
Description
- with options or range
User Language
Currently only English is supported for the HMI of the soft starter.
Motor Name
This is an alpha numeric string of up to 11 characters that may be used to identify the soft starter
Local/Remote Mode
Password Edit
The default Password is 0
– indicating that no password is active. If a password is required, this password
Fault / Incoming CB
This parameter configures the relay output on the green terminal X3
-
6,7 (refer
Figure
26
).
RS485 Baudrate
Parameters Description - with options or range
Supply Tolerances
Parameters that specifies if Torque control should be used during starting and stopping of the motor and related parameters:
Parameters Description - with options or range
measuring phase voltages before a trip will occur. The parameter can be set between [15% - 25%]. The
default is 20%.
Nominal Grid Voltage This value is factory set to the supply voltage for the model of soft starter and will be between 400V,
The current imbalance is monitored while the soft starter in running (and not during Starting and
Stopping). This parameter is the maximum percentage imbalance that can occur between the lowest
and highest measuring phase currents before a trip will occur. The parameter can be set between [5% 20%]. The default is 10%.
525V and 690V.
General Setup
The parameters that can be configured under this group are:
station. Default is “Motor1”.
This parameter determines if the soft starter is controlled locally (either from the TFT display or a
Modbus master such as the MEsoftstart PC Interface) or remotely via external digital control inputs
(e.g. a physical switch or a PLC).
When ‘Remote operation is selected, the TFT display will not activate the “START MOTOR” button, but
instead will indicate that “REMOTE MODE” is active (with REMCTL in yellow to indicate that the remote
device is in control of the soft starter operation).
may be set between 1 – 999999; and then a password will be required for all configuration operations. If
the password is set and then lost, contact your distributor to unlock.
When configured for FAULT relay, this output will be switched whenever a fault occurs
When configured for Incoming CB, the output will be true when power is present at the soft starter.
Communication Setup
General parameters are configured under this group:
Parameters Description - with options or range
74 Basic operation – Pro models
The baud rate on the RS485 port. This parameter is applicable to the MEsoftstart PC Interface as well as
the Modbus RTU interface.
RS485 Parity
Modbus Slave Address
TCP/IP Parameters
Gateway address = 192.168.0.1
Start Type
-> Ramp
-
up Constant Current
Jog
Advanced settings
Pedestal
Kickstart
Max Motor Start
Time (MMST)
Kickstart Voltage
X X Yes X X
Kickstart Period
X X Yes X X
Constant Current %
X Yes X
Pedestal RampUp %
Pedestal RampDown
%
MSC %
MULC %
MOLC %
Maximum
Ramp Start Angle
Alpha Skip Start %
Alpha Skip Stop %
Parameters Description - with options or range
The default parity on the Modbus RS485 port is Even parity. This may be set to Odd parity or No Parity.
The address of the soft starter on the Modbus link. The default address is 1.The address may be set
between [1 – 247].
Entering the setup will allows setting of the IP parameters for the Modbus TCP interface e.g.
Own IP address = 192.168.0.15 Port 502
IP subnet mask = 255.255.255.0
Client IP address = 192.168.0.16
Parameter inter-dependencies
Some parameters are only applicable when certain options are selected. The table below shows how the Start Type Configuration
can be adjusted by changing some of the Advanced setup parameters.
Ramp type
Ramp Up Time
(Limited by
Maximum Motor
Start Time MMST)
S-Curve
Yes (<= MMST)
Yes
X
Yes
Linear RMS
Linear Time
X
Yes
X
Equal to MMST
Yes
X
Fixed at 2s
2 Secs
Starts/Hour (SPH)
NORMAL Duty:
Starts per Hour =< 10, “Ramp Up Time” =< 30Sec and MMST
=< 60.
HEAVY Duty:
Starts per Hour is 1 to 720 and “Ramp Up Time” and MMST,
from 1 to 1800 seconds
Yes
Yes
Yes
X
X
Yes
Yes
X
X
X
X
X
X
Yes
Yes
Yes
NORMAL Duty:
SPH =< 10;
Ramp Up Time =< 60s;
MMST =< 60
As often as
required without
tripping the Soft
starter due to
overload or over
temperature
3
4
X
(Yes1)
(Yes
Yes
2)
Yes
Yes
X
X
X
X
X
X
3
When skip zone is used in conjunction with Pedestal the pedestal percentage should be should be lower than the Skip Start % by at least 4%
4
When skip zone is needed, Skip Start should be less than Skip Stop by at least “0” (i.e. disabled) and at most 15%. When skip zone is not
needed Skip Start and Skip Stop should be set equal (at any percentage between 36% and 100%)
75 Basic operation – Pro models
Basic operation procedure - operation from TFT display panel
This section shows the basic operation of the soft starter when using the TFT display panel. Note that for operation from the
TFT panel, the Modbus Controller (or MEsoftstart PC Application) should not be present and the Soft starter must be in
LOCAL operation mode (refer par 6.4.8).
Understanding the information on the TFT display
The TFT display shows all the information that is required to understand the soft starter operation and do basic fault finding. The
TFT display is small and compact notation is used to identify the parameters. Refer to Figure 39 below to understand the usage
and interpretation of the Parameter display area.
After power-up the Parameter display area cycles between parameter sets. The parameters sets are:
i. Default parameter display,
ii. General parameter display,
iii. Temperature display,
iv. Supply Status display,
v. Voltage and Current measurement display,
vi. Modbus and fan status.
The Default display is shown in Figure 39. The Information / Status area at the bottom indicates that the user may ‘Touch and
Hold’ to stop the cycling and view a single parameter set, or to change to another data set. ‘Touch and Hold’ will stop the
automatic cycling of parameter sets (shown in Figure 40) and will cycle manually between the data sets. After displaying the
Modbus and fan status, the auto-cycling will resume.
76 Basic operation – Pro models
Figure 39 – Understanding the display areas
77 Basic operation – Pro models
Figure 40 – Understanding the data display
Motor starting
Once User Configuration is completed and the configuration accepted, the user will be presented with the Start screen as shown
in Figure 41.
Figure 41 – Power-up the soft starter: Start the Motor
When the START MOTOR button is pressed, the soft starter will start the motor applying the configuration parameters. During
the start of the motor, the voltage as a function of time is displayed on a start progress screen. Note that the screen in Figure 41
shows a Ramp start type. This will depend on the selection as described in paragraph 6.4.2.
78 Basic operation – Pro models
Motor stopping
The motor may be stopped during the motor starting sequence or while it is running, by pressing the STOP MOTOR button.
When the STOP MOTOR button has been pressed, the voltage as a function of time is displayed on a stop progress screen. Note
that the screen in Figure 41 shows a Ramp-down stop type. The display will depend on the selection as described in
paragraph6.4.3.
JOG operation from the operation panel
When a non-zero Jog Voltage has been configured (refer paragraph 6.6.4), the Start screen will appear as shown below:
Figure 42 – Start screen with Jog option enabled
The motor may now be started by pushing the ‘JOG MOTOR’ button. While ‘JOG’ is active, the ‘Alpha’ value will increase
resulting in an increased supply voltage being applied to the motor over a maximum time of 2 seconds. Pushing the ‘JOG
MOTOR’ button again will cause the motor to coast to a stop.
If, while using the ‘JOG MOTOR’ button, the motor starts to exceed a comfortable speed, ‘JOG MOTOR’ can be pushed again
and then pushed again when it is back at a comfortable speed. All motor tripping conditions are monitored during Jog and
excessive running under Jog may sooner or later result in a trip.
Basic operation procedure – operation from a remote controller
This section shows the basic operation of the soft starter when using a remote controller such as a PLC. Note that for operation
from a remote controller, the Soft starter must be in REMOTE operation mode (refer par 6.7.1). The Modbus Controller (or
MEsoftstart PC Application) may or may not be present but will only be able to monitor the soft starter or re-configure the soft
starter when the motor is stopped.
Note that to be able to control the soft starter operation via a remote controller, the remote controller (or remote start button)
must be wired on the soft starter (refer Table 14).
79 Basic operation – Pro models
Configure the soft starter for remote control from the TFT display panel:
Selecting REMOTE operation
Select to Configure Soft starter
Select User Configure
Scroll through using the button until the
‘Operation’ parameter is shown; and Edit the
parameter. Set to ‘Remote’.
Be sure to the change.
Press the button twice to get to the
start screen which should now show that the
Operation Mode is “REMOTE”
Figure 43 – Remote / Local Operation from the TFT display
Start, Stop and Reset the soft starter from a remote controller.
The soft starter may be wired for remote operation and operation may then be controlled by closing the START contactor wired
on X3-9 and X3-10 as shown in Table 14. The soft starter will commence to do the start ramp-up as configured (refer paragraph
6.6.2). When the START contactor is opened, the stop-ramp will commence. After completing the ramp-down, a delay will be
implemented before starting is allowed again.
The delay is calculated to enforce the “Maximum Starts per Hour” that is set as described in par 6.4.4.
In case of a fault, remote Reset may be used to reset the soft starter. The RESET switch should be wired on X4-1 and X4-2 as
shown in Table 15.
Ensure to understand the nature of the problem before using remote reset. Refer paragraph 8.2 for more information.
80 Basic operation – Pro models
Using the Auto/Maintenance-feature
The MEsoftstart soft starter features an Auto/Maintenance input which may be used to prevent inadvertent START / STOP or
RESET control of the soft starter from a remote location while e.g. maintenance is in progress.
Note that to be able to use the Auto/Maintenance function, the Maintenance switch must be wired on the soft starter (refer
Table 14). Note that the Auto/Maintenance input on the soft starter must be normally closed (for the soft starter to be in Auto
control to enable control from remote PLC, or any Modbus master, or the TFT panel). The Maintenance switch must open the
Auto/Maintenance input on the soft starter to prevent remote control of the soft starter. When the Auto/Maintenance input is
open, the soft starter will only accept control inputs locally on the soft starter, from the TFT panel.
The Auto/Maintenance feature must never be used in place of a proper safety procedure to ensure the safety of
personnel working on the soft starter or the motor.
81 Basic operation – Pro models
MESOFTSTART COMMUNICATION INTERFACE
This chapter introduces the MEsoftstart PC App for the MEsoftstart/I PRO variants and MEsoftstart/I Core variants, and
explains how to install and use the software.
This chapter explains the operation and use of this product. Always read the instructions before using the equipment.
MESOFTSTART COMMUNICATION INTERFACE ................................................................................................................ 82
This section describes how to install the MEsoftstart PC App on the user’s computer and how to use the interface to configure,
monitor and control the soft starter.
The MEsoftstart PC App is tested to run on the Windows 10 operating system.
Two versions of PC Application software are available: for the Pro variants and the Core variants - the difference between the
two is shown in the table below.
Table 19: MEsoftstart PC App differences for Pro and Core variants
MEsoftstart/I Pro variants MEsoftstart/I Core variants
Configuration
The MEsoftstart/I Pro variants are full featured soft starters
that are highly configurable.
The PC Application for the Pro variants are designed to make
the complex configuration easy.
The PC Application for the Pro variants provides real-time
monitoring (while the motor is idle, starting, running and
stopping).
The Modbus link (PC Application, PLC or SCADA) allows Start, Stop and Reset control
The MEsoftstart PC application for Pro variants can be used
with Modbus RTU or Modbus TCP.
- Modbus RTU interfaces on the RS485 RJ45 connector
on J2 or J3
- Modbus TCP interfaces on the RJ45 Ethernet port on J1
If the Modbus TCP interface is used, an Ethernet cable may
be used to connect the PC with the soft starter.
The MEsoftstart/I Core variants are easy to use with
configuration via potentiometers and switches.
The PC Application for the Core variants allows the user to
view the configuration (as set by the potentiometers and
switches) and set limited configurable parameters
(refer paragraph 5.2.1).
Monitoring
The PC Application for the Core variants provides monitoring
(while the motor is stopped or running but not while starting
and stopping)
Control
Interface
The MEsoftstart PC application for Core variants is based on
Modbus RTU and interfaces on the RS485 RJ45 connector on
J1 or J2.
Cable
If Modbus RTU is used a special cable is needed that
converts the RS485 on the soft starter to a USB interface on
the laptop.
It is recommended to use the cable that is supplied to
ensure that the supported buffer size of the converter is
adequate.
- MEsoftstart/I Pro PC Interface Application
(supports RTU and TCP)
- If using Modbus RTU, the Driver for Modbus Interface is
83 MEsoftstart PC Interface Application
Download the following version
- MEsoftstart/I Core PC Interface Application
(supports only RTU)
- Driver for Modbus Interface
Installing the MEsoftstart PC App on a PC or laptop
The installation instruction for both PC applications, is the same. Ensure to download the correct zip folder for the MEsoftstart/I
Pro variant or the MEsoftstart/I Core variant.
Copy the files to the PC or laptop
Copy the MEsoftstart installation files can be downloaded from the Mitsubishi Electric Europe website (they can also be obtained
from your distributor) to the hard drive of the PC or laptop that will be used for the MEsoftstart configuration and monitoring.
For the Core variant, and, if Modbus RTU is to be used for the Pro variant as well, a cable with RS485 to USB converter will be
used. The drivers for the Modbus interface cable also need to be downloaded. If Modbus TCP will be used, the drivers are not
required. Open the folder where the files are copied. The folder should look like Figure 44 :
Figure 44 – MEsoftstart Installation files on the user PC or Laptop
Run the PC application
Open the folder MEsoftstart/I Pro PC Interface Application or MEsoftstart/I Core PC Interface Application and double click on
the ‘.exe’ file to run the program.
Figure 45 – MEsoftstart PC App files on the user PC or Laptop
84 MEsoftstart PC Interface Application
The MEsoftstart PC App should run and the home screen should be visible (refer Figure 46).
Figure 46 –Home screen with Modbus RTU setup selected
Once the MEsoftstart PC App is running, the Information screen can be accessed by clicking the _icon. The Information
screen shows the software version and the supported MEsoftstart models.
85 MEsoftstart PC Interface Application
Figure 47 –Information screen
Modbus RTU – Test to see if a driver is required for the Modbus-USB cable
If Modbus TCP is being used, this step may be omitted.
Ensure that the Connection Setup-> Type is on ‘Serial’ to be able to view the serial Modbus RTU setup parameters. Click on the
down arrow of the “Available COM Ports” drop-down box and make a note of all the COM ports listed.
Connect the computer to the MEsoftstart soft starter – using the cable provided.
i. For the Pro variants: Ensure to connect to J2 or J3 on the bottom (motor-side) of the MEsoftstart enclosure.
ii. For the Core variants: Ensure to connect to J1 or J2 on the top (grid supply-side) of the MEsoftstart enclosure
If the wires are long or communication quality is a problem ensure to use a terminating resistor on the other connector on the
last soft starter in line (if they are daisy-chained) – refer paragraph 0.
Note: If the computer is connected to the internet and offers to find a driver for the new hardware, wait for it to complete the
procedure. You may also point the computer to the driver in the “MEsoftstart Installation files\Driver for Modbus interface”
folder (refer Figure 44).
If nothing happens or once the new driver installation is completed, click on the “Refresh COM ports” button and confirm that a
new COM port was added to the drop-down list of “Available COM Ports”.
Figure 48 – MEsoftstart PC Application detects the COM port of the Modbus-USB cable
If the new COM port is not automatically detected, close the MEsoftstart/I PC Interface Application, remove the Modbus-USB
cable. Install the provided driver, reconnect the Modbus-USB cable and start the MEsoftstart PC App again.
86 MEsoftstart PC Interface Application
Modbus TCP
If the Core variant is used or the Pro variant with Modbus RTU is being used, this step may be omitted.
Ensure that the Connection Setup-> Type is on ‘TCP’ to be able to view the serial Modbus TCP setup parameters. Ensure that the
IP Address is correct and the Port is 502. The PC or laptop should be set for a static IP address.
Connect the computer to the MEsoftstart soft starter using a normal Ethernet cable. Ensure to connect to J1 on top of (grid side
of) the MEsoftstart enclosure.
Figure 49 – MEsoftstart PC Application setup for Modbus TCP connection
Connecting to the soft starter
When the MEsoftstart/I PC Interface Application is running and the Ethernet cable or Modbus-USB cable is connected to a
MEsoftstart soft starter that is powered-up, the “Connect” button can be clicked, to connect the computer to the soft starter.
87 MEsoftstart PC Interface Application
Figure 50 – MEsoftstart PC App on RTU Modbus waiting for communication from soft starter
If the MEsoftstart PC App is not connecting to the soft starter, it may be that the Modbus communication parameters or the
Modbus Slave Address of the soft starter have been modified on the soft starter.
For the Pro variants: Refer paragraph 6.4.9 for information on how to check the TCP and RTU Modbus communication
parameters and RTU address on the soft starter using the TFT display.
For the Core variants: Refer paragraph 5.4.16.
Once the communication parameters and RTU address on the soft starter and the MEsoftstart PC App are the same, try
connecting to the soft starter again.
When first connected to the soft starter, the Start screen will be shown (refer Figure 51 for Pro variant Start screen).
Figure 51 –PC Application for Pro variant - Start screen
88 MEsoftstart PC Interface Application
On the Pro variants:
Once the MEsoftstart PC App (or other Modbus controller) is connected, the soft starter TFT display will not accept command
inputs (other than to toggle through the Parameter Display Area options). This will be clear to the user with the yellow text
“TCPCTL” being displayed in the top right side of the TFT display – refer Figure 39.
To return control to the TFT display on the soft starter, close the PC application or disconnect the Modbus cable. After a delay
of about 10 seconds, the TFT display will allow user inputs again.
Note that after power-up, the soft starter will only service the Modbus port once the configuration has been accepted on the
TFT display. If the MEsoftstart PC App shows that it has the communication port open but is not receiving data from the soft
starter (refer Figure 50), check the TFT display on the soft starter and accept the configuration. Once this is done, the soft starter
should commence Modbus communication and the Start screen (Figure 51) should be visible.
On the Core variants:
Once connected the MEsoftstart/I Core variant Mode LED will flash faster (1Hz) to indicate that Modbus monitoring and Control
is possible. Limited configuration is also possible (refer paragraph 5.2.1
Do not attempt to immediately start the motor – first view the configuration and confirm that the settings are correct
for the user’s installation.
Configuring start and stop behaviour using the MEsoftstart PC App
On the Core variant:
Configuration is mostly done on the Potentiometer HMI – refer paragraph 5.2 above. The configuration that the soft starter
reads from the HMI inputs may be viewed on the MEsoftstart/I Core PC Interface Application. In addition, advanced settings may
be configured from the PC Application. Figure 52 shows a typical configuration screen for the Core model. Note how the ‘Rampup time’, ‘Maximum Starting Current Percentage’, ‘Rated Current’ etc. values are displayed but the fields are inactive for editing
since these parameters are set on the potentiometers on the HMI panel.
Figure 52 –PC Application for Core variant - Configuration screen
89 MEsoftstart PC Interface Application
On the Pro variant:
The parameters that may be configured via the MEsoftstart PC App are the same parameters which are available for
configuration via the TFT display.
From the Start screen select to “Edit Configuration”. The Configure screen will be shown with the “Basic Setup” parameters (refer
Figure 53). Note that every time the MEsoftstart PC App connects to the soft starter, the current soft starter configuration is
uploaded from the soft starter so that the PC Application configuration and the soft starter configuration will be the same.
When changes are made on the MEsoftstart PC App configuration screen, the configuration parameters are different
from the actual configuration on the soft starter. The PC configuration and the actual soft starter configuration will
only be the same again after a successful “Download” to the soft starter or when “Current Configuration” is selected
to again upload from the soft starter (overwriting changes that were made on the Configure screen).
Note that all the parameters that are available on the configuration screen are the same as those that are listed for the TFT
display configuration (refer Table 18). In addition, the MEsoftstart PC App shows the model of the connected soft starter and a
theoretical representation of what the configured start and stop ramps will look like.
Select the “Advanced Setup” to view more detail parameters (refer Figure 53). Note that the “Kickstart Setup” parameters will
only become available for editing once “Start Type – Kickstart” is selected. Similarly, the “Constant Current Setup” parameters
are visible, but only available for editing when the “Start Type – Constant Current” is selected. The “Pedestal Setup” parameters
are visible, but only available when the “Start Type – Pedestal” is selected.
Also take note of the parameter inter-dependencies as listed in paragraph 6.5. The PC Application will indicate which parameters
are not applicable for the configured scenario, by making the parameters inactive (grey).
90 MEsoftstart PC Interface Application
When the configuration is acceptable, the user should select “Download” to save the configuration to the soft starter followed
by “Back” to return to the Start screen. There is an optional password when downloading a new configuration to the soft
starter. This is to prevent unauthorised changes to the soft starter. If the password is not in use the value ‘0’ will allow the
91 MEsoftstart PC Interface Application
Figure 53 –Configure screen
‘download’ action to continue. If the password was activated on the soft starter, the correct password will be required to
download the configuration to the soft starter. Refer paragraph 6.4.8 for more information on the password.
The user may at any time revert to “Factory default” parameter set, or to the “Current Configuration” on the soft starter, or
may load “From File” a previously saved configuration. (Refer Figure 54).
Note that the default “File Path” where the configuration files are saved can be changed from the Home screen (refer Figure 46).
Configuring limits and tolerances using the MEsoftstart PC App
On the Core and the Pro variants:
The soft starter implements protection against over temperature on the motor and on the soft starter heat sinks, as well as
supply voltage and current unbalance. These parameters should not usually be changed, but are available to the advanced user
to adjust.
Note that the soft starter can control the internal fan to run whenever the motor is running. Or to start running when the heatsink
temperatures are above a limit – “Heatsink Fan Start Temperature”.
92 MEsoftstart PC Interface Application
Figure 54 –Configure screen buttons
Temperatures, when the soft starter will trip to protect the motor or the switching electronics inside the soft starter, can also be
adjusted.
Figure 55 –Configure screen - limits and tolerances
Configuring general parameters and communication settings
On the Core and the Pro variants:
Just like on the TFT display, the MEsoftstart PC App may be used to configure general parameters and communication settings
for the Modbus interface. Refer Figure 56 for an overview of what can be changed on these screens.
Figure 56 –Configure screen – general parameters and communication settings
93 MEsoftstart PC Interface Application
Configuring for the JOG option using the MEsoftstart PC App
On the Core variant: JOG is controlled from the HMI panel (refer paragraph5.3.3)
On the Pro variant:
Just like on the TFT display the soft starter may be configured using the MEsoftstart PC App to “JOG” the motor at a fixed voltage
for testing or calibration purposes.
Once a configuration with a greater-than-zero “JOG Motor Voltage Percentage” is downloaded to the soft starter, JOG mode is
available on the soft starter and from the PC application. If JOG mode is no longer needed, set the “JOG Motor Voltage Percentage” back to zero again. The JOG buttons on the PC application and the TFT display will be removed.
Change the password and view the firmware revisions
On the Pro variant:
If required, a password can be set to protect against accidental or unauthorised changing of the configuration. Note that when
the password is set via the PC Application or on the TFT, it will be required for each configuration change. If the password is lost,
the distributor will have to be contacted to recover the functionality.
On the Core and the Pro variants:
The embedded firmware revisions can be viewed via the PC Application. Refer Figure 58
94 MEsoftstart PC Interface Application
Figure 57 –Configure screen – JOG mode
Figure 58 –Configure screen –password and revisions
Controlling the soft starter using the MEsoftstart PC App
On the Core variant – refer paragraph 5.3.2
On the Core and the Pro variants:
The MEsoftstart PC App may be used to control the soft starter. From the Start screen, use the “START” button to start the
motor. View the progress of the start-ramp on the Start screen or the TFT display. Press the ‘Stop’ button and watch the stop
ramp (if configured) and the implementation of the delay before start is again allowed.
95 MEsoftstart PC Interface Application
Figure 59 – MEsoftstart PC Application Control screen
Resetting the soft starter using the MEsoftstart PC Application
On the Core variant – refer paragraph 5.3.2
On the Core and the Pro variants:
Whenever a fault is detected by the soft starter, the soft starter will require a RESET before operation is possible again.
Investigate the cause of the fault, fix the issue and “Reset” the soft starter using the button on the screen.
96 MEsoftstart PC Interface Application
Figure 60 – MEsoftstart PC Application Fault screen
97 MEsoftstart PC Interface Application
MEsoftstart Modbus interfaces
The MEsoftstart PC App and any SCADA system, both use the same MODBUS protocol and either is the Modbus Master when
connected to the soft starter. The SCADA uses a subset of the total register definition. Some of the registers will only be used by
the PC Application (note: these register values will not be shown in the final SCADA SICD document).
Note:
The MEsoftstart Core variant supports only Modbus RTU using RS485 using connectors J1 and J2.
The MEsoftstart Pro variant supports two Modbus interfaces:
- Modbus RTU on RS485 using connectors J2 and J3
- Modbus TCP on Ethernet using connector J1 (Pro variants only)
Please request the Modbus Software Interface Control Document from your local distributor.
The following general guidelines apply:
- The PC Application and the SCADA system may not be simultaneously present on the Modbus RTU RS-485 data bus due to
bus conflict issues. Two Modbus devices may be present – one on the Modbus TCP port and one on the Modbus RTU port.
The device that connects first, will be the Master and will be in control of the soft starter. The Master will be able to start,
stop and reset the soft starter. The other Modbus device will only be able to monitor the status and progress sent by the
soft starter.
- The Modbus Master can to connect to the soft starter (via MODBUS messages) when the soft starter is in any state (Stopped,
Starting, Stopping or Running) and request status updates as well as read the soft starter’s present configuration.
- The soft starter configuration may only be updated by the Modbus Master when the soft starter is in the Stopped state. On
receipt of a new configuration, the soft starter checks the password and then performs a validity check on the received
parameters and responds either with errors, or with a positive response. A single configuration parameter compliance
failure, will result in the whole configuration will be discarded (refer paragraph 6.5).
- The Modbus Master may send regular status request messages beginning when the soft starter is in Stopped mode. The
Modbus Master will then be in control of the soft starter and will remain in control, provided that a continuous regular
message is sent from the Master to the Soft starter. While the Modbus Master is in control of the soft starter the TFT display
will indicate this with the words “TCPCTL” or “RTUCTL”, depending on if the TCP Modbus master is in control, or the RTU
Modbus master.
- If a second Modbus device is also present and monitoring, the TFT display will indicate “TCP” or “RTU” next to the control
indication – refer Figure 39.
- If the soft starter does not receive messages from the Modbus Master for a period longer than 10 seconds, control will
revert to the other Modbus device present or to the soft starter TFT display if no other Modbus device is present. The
Modbus Master is required to ensure that it gets regular status updates from the soft starter at a recommended rate of
once per second to keep itself appraised of the most up-to-date status of the soft starter.
- The soft starter is not able to distinguish when under Modbus control, whether it is the PC Application or a SCADA control
system that is the Modbus Master.
- The soft starter Modbus interface does not support Modbus Broadcast mode or Silent mode.
- The RS-485 RTU Modbus communication interface is default set to 115200 BAUD, 1 Start, 1 Stop, and Even Parity (with the
possibility of No Parity and Odd Parity available). This is reconfigurable from the Modbus Master and from the TFT display.
98 MEsoftstart PC Interface Application
At present the following Modbus function codes (FCs) are supported:
The soft starter RTU address can be configured from 1 to 247.
Any write action either to Configuration registers, or the Control Command register, that receives a positive response back from
the soft starter, may be interpreted by the Modbus Master as confirmation that the configuration data is correct and will be
saved in the soft starter, or that the command will be put into effect. An error response must be interpreted as the opposite.
Updates to individual configuration parameters should be done by sending the full complement of configuration parameters.
99 MEsoftstart PC Interface Application
PROTECTIVE FUNCTIONS & TROUBLESHOOTING (PRO)
This chapter explains the protection functions that are implemented in the PRO variants of the soft starter. For
troubleshooting on the Core variant refer to paragraph 5.4.
This chapter explains the operation and use of this product. Always read the instructions before using the equipment.