Ventilation air must be introduced constantly at a set ratio in an air-conditioning system. The ventilation air introduced is to be
mixed with the return air to adjust the temperature and humidity, supply oxygen, reduce odors, remove tobacco smoke, and to
increase the air cleanliness.
The standard ventilation (outdoor air intake) volume is determined according to the type of application, estimated number of
occupants in the room, room area, and relevant regulations. Systems that accurately facilitate these requirements are required
in buildings.
1. Necessity of Ventilation
The purpose of ventilation is basically divided into “oxygen supply”, “air cleanliness”, “temperature control” and “humidity control”.
Air cleanliness includes eliminating “odors”, “gases”, “dust” and “bacteria”. Ventilation needs are divided into “personal comfort”,
“optimum environment for animals and plants”, and “optimum environment for machinery and constructed materials”.
Ventilation regulations are detailed in a variety of codes and standards applied to mechanical systems in buildings. Energy
efficiency codes also often apply to the design of ventilation systems.
1.1 Room Air Environment in Buildings
In Japan, the “Building Management Law”, a law concerning the sanitary environment in buildings, designates 11 applications
including offices, shops, and schools with a total floor area of 32,300ft2 (3,000m2) or more, as buildings. Law maintenance
and ventilation, water supply, discharge management according to the Environmental Sanitation Management Standards is
obligatory.
The following table gives a specific account of buildings in Tokyo.
(Tokyo Food and Environment Guidance Center Report)
Specic Account of Buildings in Tokyo (March, 2003)
Number of Buildings%
Offices1,46756.7
Shops30922.0
Department Stores632.4
Schools41816.2
Inns1234.8
Theaters863.3
Libraries120.5
Museums110.4
Assembly Halls632.4
Art Museums80.3
Amusement Centers271. 0
Total2,587100.0
Note: Excludes buildings with an expanded oor space of 32,300 to 58,820ft2 (3,000 to 5,000m2) in particular areas.
Results of the air quality measurement public
Percentage Unsuitable Air Quality by Year
inspection and the standard values that were
not met (percentage of unsuitability) for the
approximately 500 buildings examined in 1980
are shown in the chart at the right.
There was a large decrease in high percentages
60
50
40
relative humidity
carbon dioxide
temperature
carbon monoxide
ventilation
floating particles
(tobacco smoke)
of floating particles, but there was almost no
change in temperature and carbon dioxide. The
30
highest percentage of unsuitability in 2006 is
relative humidity with 36%, followed by carbon
dioxide at 28%.
20
10
Percentage of unsuitable air quality (%)
0
76 77 7879 80 8171 73 75
(From reference data in the 2006 edition of the “Water Supply
Division, Dept. of Localized Public Health, Tokyo Metropolitan
Government, Bureau of Public Health”)
In Japan, an Instruction Guideline based on these regulations has been issued, and unified guidance is followed. Part of the
Instruction Guideline regarding ventilation is shown below.
The ventilation air intake must be 33ft (10m) or higher from ground level, and be located at an appropriate distance from the
•
exhaust air outlet. (Neighbouring buildings must also be considered.)
The ventilation air intake volume must be 15 to 18 CFM·occupant. (25 to 30 m3/h·occupant.)
•
An air volume measurement access hole must be installed at an appropriate position to measure the treated air volume of
•
the ventilating device.
Select the position and shape of the supply diffuser and return grille to evenly distribute the ventilation air in the room.
•
1.2 Effect of Air Contamination
Effect of Oxygen (O2) Concentration
Concentration (%)Standards and Effect of Concentration Changes
Approx. 21Standard atmosphere.
20.5
20 - 19
18Industrial Safety and Health Act. (Hypoxia prevention regulations.)
16Normal concentration in exhaled air.
16 - 12
15Flame in combustion devices will extinguish.
12Short term threat to life.
7Fatal
Ventilation air volume standard is a guideline where concentration does not decrease more than 0.5%
from normal value. (The Building Standard Law of Japan)
Oxygen deciency of this amount does not directly endanger life in a normal air pressure, but if there is a
combustion device in the area, the generation of CO will increase rapidly due to incomplete combustion.
Increase in pulse and breathing; resulting in dizziness and headaches.
Effect of Carbon Monoxide (CO) 10,000 ppm = 1%
Concentration (ppm)
0.01 - 0.2Standard atmosphere.
5Tolerable long-term value.
10
20
50
100
200Light headache in the frontal lobe in 2 to 3 hours.
400Headache in the temporal lobe, nausea in 1 to 2 hours; headache in the back of head in 2.5 to 3 hours.
800Headache, dizziness, nausea, convulsions in 45 minutes. Comatose in 2 hours.
1,600Headache, dizziness in 20 minutes. Death in 2 hours.
3,200Headache, dizziness in 5 to 10 minutes. Death in 30 minutes.
6,400Death in 10 to 15 minutes.
12,800Death in 1 to 3 minutes.
Several 10,000 ppm
(Several %)
The Building Standard Law of Japan, Law for Maintenance of Sanitation in Buildings.
Environmental standard for a 24-hour average.
Considered to be the tolerable short-term value.
Environmental standard for an 8-hour average.
Tolerable concentration for working environment.
(Japan Industrial Sanitation Association)
No effect for 3 hours. Effect noticed after 6 hours.
Headache, illness after 9 hours; harmful for long-term but not fatal.
Level may be found in automobile exhaust.
Effect of Concentration Changes
Approx. 5 ppm is
the annual
average value in
city
environments.
This value may
exceed 100 ppm
near roads, in
tunnels and
parking areas.
U-3
CHAPTER 1 • Ventilation for Healthy Living
Effect of Carbon Dioxide (CO2)
Concentration (%)Effect of Concentration Changes
0.03 (0.04)Standard atmosphere.
0.04 - 0.06City air.
0.07Tolerable concentration when many occupants stay in the space for long time.
0.10
0.15Tolerable concentration used for ventilation calculations.
0.2 - 0.5Relatively poor.
0.5 or moreVery poor.
0.5Long-term safety limits (U.S. Labor Sanitation) ACGIH, regulation of working offices.
2Depth of breathing and inhalation volume increases 30%.
3Work and physical functions deteriorate, increase breathing doubles.
4Normal exhalation concentration.
4 - 5
8
18 or moreFatal
Note: According to Facility Check List published by Kagekuni-sha.
General tolerable concentration.
The “Building Standard Law” of Japan, “Law for Maintenance of Sanitation in Buildings”.
The respiratory center is stimulated; depth and times of breathing increases. Dangerous if inhaled for a
long period. If an O2 deciency also occurs, conditions will rapidly deteriorate and become dangerous.
When inhaled for 10 minutes, breathing difficulties, redness in the face and headaches will occur.
Conditions will worsen when there is also an O2 deciency .
There is no toxic level in
CO2 alone.
However, these
tolerable concentrations
are a guideline of the
contamination estimated
when the physical and
chemical properties of
the air deteriorate in
proportion to the
increase of CO2.
1.3 Effect of Air Contamination in Buildings
Dirtiness of interior
•
New ceilings, walls and ornaments will turn yellow from dust in 1 to 2 years.
2. Ventilation Standards
The legal standards for ventilation differ according to each country. Please follow the standards set by your country. In the U.S.,
ASHRAE revised their standards in 1989 to become more strict.
U-4
CHAPTER 1 • Ventilation for Healthy Living
3. Ventilation Method
3.1 Comparing of Ventilation Methods
There are two main types of ventilation methods.
Centralized Ventilation Method
Mainly used in large buildings, with the ventilation air intake being installed in one machine room. For this method, primary
treatment of the ventilation air, such as energy recovery to the intake air and dust removal, is performed via distribution to the
building by ducts.
Independent Zoned Ventilation Method
Mainly used in small to medium sized buildings, with areas being ventilated using ventilation air intake via independent
ventilation devices. The use of this method has recently increased as independent control is becoming more feasible.
Invoicing for each zone separately is possible, even
in a tenant building.
U-6
CHAPTER 1 • Ventilation for Healthy Living
4. Ventilation Performance
The ventilation performance is largely affected by the installation conditions. Optimum performance may not be achieved
unless the model and usage methods are selected according to the conditions.
Generally, the ventilation performance is expressed by “air volume” and “wind pressure (static pressure)”.
4.1 Air Volume
Air volume equals the volume of air exhausted (or supplied) by the unit in a given period, and is expressed in CFM or m3/hr (hour).
4.2 Wind Pressure
When a piece of paper is placed in front of a fan then released, the piece of paper will be blown away. The force that blows the
paper away is called wind pressure and is normally expressed in inH2O. Wind pressure is divided into the following three types:
4.2.1 Static Pressure
The force that effects the surroundings when the air is contained such as in an automobile tyre or rubber balloon. For example,
in a water gun, the hydraulic pressure increases when pressed by a piston. If there is a small hole, the water is forced out of
that opening. The pressure of the water is equivalent to air static pressure. The higher the pressure, the farther the water (air)
can be forced out.
4.2.2 Dynamic Pressure
The speed at which air flows; for example, the force at which a hurricane presses against a building.
4.2.3 Total Pressure
The total force that wind has, and is the sum of the static pressure and dynamic pressure.
U-7
CHAPTER 1 • Ventilation for Healthy Living
4.3 Measuring the Air Volume and Static Pressure
Mitsubishi Electric measures the Lossnay’s air volume and static pressure with a device as shown below according to Japan
Industrial Standards (JIS B 8628).
Measuring Device Using Orice (JIS B 8628 Standards)
Chamber
Damper
Smoothing
net
Wind gauge
duct path
Orice
Connection
Supply
Air
(SA)
Test unit
Blower
Pressure
difference before
and after orice
(Air volume
measurement)
Static pressure in chamber
(Static pressure measurement)
A) When measuring the supply air volume (with the orice plate)
Wind gauge
duct path
Smoothing
grid
Orice
Wind dispersing place
Smoothing
Return
Air
(RA)
net
B) When measuring the return air volume (with the orice plate)
Smoothing
grid
Blower
Connection
Test unit
Static pressure in chamber
(Static pressure measurement)
Measurement Method
The unit is operated with the throttle device fully closed. There is no air flow at this time, and the air volume is 0. The maximum
point of the static pressure (Point A, the static pressure at this point is called the totally closed pressure) can be obtained. Next,
the throttle device is gradually opened, the auxiliary fan is operated, and the median points (Points B, C and D) are obtained.
Finally, the throttle device is completely opened, and the auxiliary fan is operated until the static pressure in the chamber reaches 0.
The maximum point of the air volume (Point E, the air volume at this point is called the fully opened air volume) is obtained. The
points are connected as shown below, and are expressed as air volume, static pressure curves (Q-H curve).
U-8
)
Static pressure (
H
Air volume (Q)
CHAPTER 1 • Ventilation for Healthy Living
5. Outdoor Air (ventilation) Load
5.1 How to Calculate Each Approximate Load
5.1 A (US unit)
The ventilation air load can be calculated with the following formula if the required ventilation intake volume “Q CFM” is known:
(Ventilation air load) = γ · QF · (iO - iR)
=
γ [lb/ft3] × S[ft2] × k × n [occupant/ft2] × Vf [CFM / occupant] × (iO - iR): ∆i [Btu/lb]
: Specific air gravity - 0.0749 lb/ft
γ
S : Building’s airconditioned area
k : Thermal coefficient; generally 0.7 - 0.8.
n :
The average population concentration is the inverse of the occupancy area per person. If the number of persons in the
room is unclear, refer to the Floor space per person table below.
Vf : Ventilation air intake volume per occupant
Refer to the Required ventilation air intake volume per occupant table below.
iO : Ventilation air enthalpy - Btu/lb
iR : Indoor enthalpy - Btu/lb
Floor Space per Occupant (ft2)
(According to the Japan Federation of Architects and Building Engineers Associations)
The amount of smoking that could be present in each type of room must be carefully considered when obtaining the
required ventilation volume shown in the table above.
U-9
CHAPTER 1 • Ventilation for Healthy Living
5.1 B (SI unit)
The ventilation air load can be calculated with the following formula if the required ventilation intake volume “Q m3/h” is known:
(Ventilation air load) = γ · QF · (iO - iR)
=
[kg/m3] × S [m2] × k × n [occupant/m2] × Vf [m3/h·occupants] × (iO - iR): ∆i [kJ/kg]
γ
: Specific air gravity - 1.2 kg/m
γ
S : Building’s air-conditioned area
k : Thermal coefficient; generally 0.7 - 0.8.
n :
The average population concentration is the inverse of the occupancy area per occupant. If the number of occupants in the
room is unclear, refer to the Floor space per
Vf : Ventilation air intake volume per
Refer to the Required ventilation air intake volume per
iO : Ventilation air enthalpy - kJ/kg
iR : Indoor enthalpy - kJ/kg
Floor Space per Occupant (m2)
(According to the Japan Federation of Architects and Building Engineers Associations)
The amount of smoking that could be present in each type of room must be carefully considered when obtaining the
required ventilation volume shown in the table above.
U-10
CHAPTER 1 • Ventilation for Healthy Living
See below for Calculation examples of determining ventilation load during both cooling and heating.
5.2 Ventilation Load During Cooling (In an Office Building)
Cooling Load Classications
•
(a)Indoor penetration heat
(b)Indoor generated heat
(c)Reheating load(qRL)
(d)Outdoor air load
(a) Is the heat penetrating the room, and often is 30 to 40% of the entire cooling load?
(b) Is the heat generated in the room?
(c) Is applies only when reheating is necessary?
(d) Is the heat generated when ventilation air is mixed into part of the supply air diffuser volume and introduced into the room?
The ventilation air is introduced to provide ventilation for the room occupants, and is referred to as the ventilating load.
Office Building
Department Store, Shop
Heat generated from walls (qWS)
Heat generated from glass
Accumulated heat load in walls (qSS)
Generated heat from occupants
Generated heat from electrical equipment
Sensible heat (qFS)
Latent heat (qFL)
from direct sunlight (qGS)
from conduction and convection (qGS)
Sensible heat (qHS)
Latent heat (qHL)
Sensible heat (qES)
Latent heat (qEL)
Typical Load Values During Cooling
Load TypeLoad
4.9 W/ft2 (53.0 W/m2)
Occupants2.5 W/ft2 (26.4 W/m2)
Lighting Equipment2.8 W/ft2 (30.0 W/m2)
Total14.6 W/ft2 (157.0 W/m2)
Ventilation air
load 33.8%
4.9 W/ft
(53.0 W/m2)
2
Indoor
generated heat
(occupants, lighting
equipment) 35.9%
5.2 W/ft2 (56.4 W/m2)
Indoor
penetration
heat 30.3%
2
4.4 W/ft
(47.6 W/m2)
2
14.6 W/ft
(157.0 W/m2 )
Ventilation Air Load
Indoor
Generated Heat
Indoor Penetration Heat4.4 W/ft2 (47.6 W/m2)
Conditions: Middle south-facing oor of a typical office building.
Cooling Load Per Unit Area
When the volume of ventilation air per occupants is 15 CFM (25 m3/h), and the number of occupants per 1 ft2 is 0.0186 (1 m2 is
0.2), the cooling load will be approximately 14.6 W/ft2 (157.0 W/m2).
<US unit>
When the load per floor area of 1 ft2 with a ventilation volume of 15 CFM·occupant is calculated with the air conditions detailed
above, the following is obtained:
Ventilation air load = 0.0749 Ib/ft3 (Specific gravity of air) × 0.0186 occupant/ft2 (number of occupants per 1 ft2)
× 15 CFM·occupants (ventilation air volume) × 13.7 Btu/Ib (air enthalpy difference indoor/outdoor) = 0.286 Btu/min·ft2 (4.9 W/ft2)
<SI unit>
When the load per floor area of 1 m2 with a ventilation volume of 25 m3/h·occupant is calculated with the air conditions detailed
above, the following is obtained:
Ventilation air load = 1.2 kg/m3 (Specific gravity of air) × 0.2 occupant/m2 (number of occupants per 1 m2)
× 25 m3/h·occupants (ventilation air volume) × 31.8 kJ/kg (air enthalpy difference indoor/outdoor) = 190.8 kJ/h·m2 (53.0 W/m2)
The Lossnay recuperates approximately 70% of the exhaust air load and saves on approximately 20% of the total load.
U-11
CHAPTER 1 • Ventilation for Healthy Living
Determining Internal Heat Gain
•
When classifying loads, the internal heat gain (indoor generated heat + indoor penetration heat) is the ventilation air load
subtracted from the approximate cooling load when it is assumed that there is no reheating load.
(2) Heat generated from electrical equipment (lighting)
The approximate value of the lighting and power required for a general office with lighting of 300 - 350 Lux, is 1.9 - 2.8 W/ft2
(20 - 30 W/m2).
Heat generated from electrical equipment (lighting) = 30 W/m
Indoor Penetration Heat
•
The heat that penetrates into the building from outside, which can be determined by subtracting the amount of heat generated
by occupants and lighting from the internal heat gain.
During heating, the heat generated by occupants and electrical equipment in the room can be subtracted from the heating load.
If the warming-up time at the start of heating is short, however, the generated heat may be ignored in some cases.
Percentage of Load
air load 41.9%
Indoor heat
loss
Ventilation
load
Ventilation
5.2 W/ft2
(56.0 W/m2)
Indoor heat
loss 58.1%
7.2 W/ft
(77.7 W/m2)
Heat escaping from glass (qGS)
Heat loss from conduction and convection (qGS)
Accumulated heat load in walls (qSS)
Sensible heat (qFS)
Latent heat (qFL)
Ventilation Air Load
Internal Heat7.2 W/ft2 (77.7 W/m2)
2
Conditions: Middle south-facing oor of a typical office building.
Type of LoadLoad
5.2 W/ft2 (56.0 W/m2)
Total12.4 W/ft2 (133.7 W/m2)
12.4 W/ft2
(133.7 W/m2)
Heating Load Per Unit Area
•
When the ventilation air volume per occupant is 15 CFM (25 m3/h), and the number of occupants per 1 ft2 is 0.0186 (1 m2
is 0.2), the heating load will be approximately 12.4 W/ft2 (133.7 W/m2).
Internal Heat Loss
•
In terms of load classification, the internal heat loss is the value of the ventilation air load subtracted from the approximate
heating load.
Internal heat loss = 12.4 W/ft2 – 5.2 W/ft2 = 7.2 W/ft2 (133.7 W/m2 – 56.0 W/m2 = 77.7 W/m2)
Ventilation Load
•
Standard design air conditions in Tokyo
Dry Bulb Temp.
Heating
<US unit>
When the load per 1 ft2 of floor area with a ventilation volume of 15 CFM·occupant is calculated with the air conditions
detailed above, the following is obtained:
Ventilation air load = 0.749 Ib/ft3 × 0.0186 occupants/ft2 × 15 CFM·occupant × 14.4 Btu/Ib = 0.30 Btu/min·ft2 (5.2 W/ft2)
<SI unit>
When the load per 1 m2 of floor area with a ventilation volume of 25 m3/h·occupant is calculated with the air conditions
detailed above, the following is obtained:
Ventilation air load = 1.2 kg/m3 × 0.2 occupants/m2 × 25 m3/h·occupant × 33.5 kJ/kg = 201.0 kJ/h·m2 (56 W/m2)
The Lossnay recuperates approximately 70% of the ventilation load and saves on approximately 30% of the total load.
U-13
CHAPTER 2
Lossnay Construction and Technology
CHAPTER 2 • Lossnay Construction and Technology
1. Construction and Features
Construction
•
Lossnay is constructed so that the exhaust air passage from the
indoor side to the outdoor side (RA → EA) and the ventilation air
passage from the outdoor side to the indoor side (OA → SA) cross.
The Lossnay Core is located at this crosspoint, and recovers the
heat by conduction through the separating medium between these
airflows. This enables the heat loss during exhaust to be greatly
reduced.
* RA : Return Air
EA : Exhaust Air
OA : Outdoor Air
SA : Supply Air
Main Features
(1) Cooling and heating maintenance fees are reduced while ventilating.
(2) The system size of Heating/cooling system and cooling/heating load can be reduced.
(3) Dehumidifying during summer and humidifying during winter is possible.
(4) Comfortable ventilation is possible with the outdoor air can be adjusted to parallel the room temperature.
(5) Sound can be reduced.
SA (Supply air diffuser)
Supply fan
RA (Return air)
Exhaust side lter
Note: The duct inlet and outlet are linear in the
actual product.
Lossnay Core
EA (Exhaust air)
Exhaust fan
OA (Outdoor air)
Intake side lter
2. Lossnay Core Construction and Technology
Simple Construction
•
The Lossnay core is a cross-air passage total energy recovery unit
constructed from specially treated membrane with a corrugated
structure.
The fresh air and exhaust air passages are totally separated
allowing the fresh air to be introduced without mixing with the
exhaust air.
Principle
•
The Lossnay Core uses the heat transfer properties and moisture
permeability of the treated membrane. Total heat (sensible heat
plus latent heat) is transferred from the stale exhaust air to the
ventilation air being introduced into the system when they pass
through the Lossnay.
Treated membrane
•
The cellulose membrane partition plates are treated with special
chemicals so that the Lossnay Core is an appropriate energy
recovery unit for the ventilator.
The membrane has many unique properties:
(1) Incombustible and strong.
(2) Has selective hydroscopicity and moisture permeability that permits the passage of only water vapor (including some
water-soluble gases).
(3) Has gas barrier properties that does not permit gases such as CO
space.
SA
Supply Air
(Fresh heating/cooling air)
Partition
plate
(Treated
membrane)
Spacer plate
(Treated
membrane)
RA
Return Air
(Dirty heating/cooling air)
2 and other pollutants from entering the conditioned
IndoorsOutdoors
EA
Exhaust Air
(Stale air)
OA
Outdoor air
(Fresh air)
U-16
CHAPTER 2 • Lossnay Construction and Technology
Total Energy Recovery Mechanism
•
Sensible Heat and Latent Heat
The heat that enters and leaves in accordance with rising or falling temperatures is called sensible heat. The direct movement of
water vapor molecules or due to the changes in the matter’s physical properties (evaporation, condensation) is called latent heat.
(1) Temperature (Sensible Heat) Recovery
1) Heat conduction and heat passage is performed through a
partition plate from the high temperature to low temperature
side.
2) As shown in the diagram at right, the energy recovery
efficiency is affected by the resistance of the partition plate.
For Lossnay, there is little difference when compared to
materials such as copper or aluminium that also have high
thermal conductivity.
t1
Ra1
Rp
Ra2
t2
Heat Resistance Coefficients
Lossnay PlateCuAl
Ra1101010
Rp10.000360.0006
Ra2101010
Total2120.0003620.0006
(2) Humidity (Latent Heat) Recovery
Water vapor travels through the partition plate from the high
•
humidity to low humidity side via the differential pressure in
the vapor.
High humidity side
Partition plate
Ra1+Ra2»Rp
Low humidity side
Partition plate
U-17
CHAPTER 2 • Lossnay Construction and Technology
3. Total Energy Recovery Efficiency Calculation
The Lossnay Core’s energy recovery efficiency can be considered
using the following three transfer rates:
(1) Temperature (sensible heat) recovery efficiency
(2) Humidity (latent heat) recovery efficiency
(3) Enthalpy (total heat) recovery efficiency
The energy recovery effect can be calculated if two of the above
efficiencies are known.
Each energy efficiency can be calculated with the formulas in the
•
table.
When the supply and exhaust air volumes are equal, the energy
•
recovery efficiencies on the supply and exhaust sides are the
same.
When the supply and exhaust air volumes are not equal, the total
•
energy recovery efficiency is low if the exhaust volume is lower,
and high if the exhaust volume is higher.
ItemFormula
Temperature recovery
efficiency (%)
Enthalpy recovery
efficiency (%)
ηt =
ηi =
tOA - tSA
tOA - tRA
iOA - iSA
iOA - iRA
×100
× 100
SA
Fresh air exhaust
(Fresh heating/cooling air)
RA
Stale air induction
(Dirty heating/cooling air)
η : Efficiency (%)
t : Dry bulb temperature (°F, °C)
i : Enthalpy (Btu/Ib, kJ/kg)
IndoorsOutdoors
EA
Exhaust air
(Stale air)
OA
Fresh air
induction
(Fresh air)
Calculation of Supply Air Condition After Passing Through Lossnay
If the Lossnay energy recovery efficiency and the conditions of the room and outdoor air are known, the conditions of the air
entering the room and the air exhausted outdoors can be determined with the following formulas in the following table.
Supply SideExhaust Side
TemperaturetSA = tOA - (tOA - tRA) × ηttEA = tRA + (tOA - tRA) × ηt
A chart that shows the properties of humid air is called a psychrometric chart. The psychrometric chart can be used to find the
(1) Dry bulb temperature, (2) Wet bulb temperature, (3) Absolute humidity, (4) Relative humidity, (5) Dew point and (6) Enthalpy
(total heat) of a certain air condition. If two of these values are known, the other values can be found with the chart. Now air
conditions will change when it is heated, cooled, humidified or dehumidified can also be seen easily on the chart.
(1) Dry Bulb Temperature t (°F, °C)
Generally referred to as standard temperature, the DB
temperature is obtained by using a dry bulb thermometer
(conventional thermometer).
Temperature (°F,°C)
(2) Wet Bulb Temperature t’ (°F, °C)
When a dry bulb thermometer is wrapped in a piece of wet
gauze and an ample air ow (3 m/s or more) is applied, the
heat from the air and evaporating water vapor applied to the
wet bulb will balance at an equal state and the wet bulb
temperature is obtained.
Wet bulb temperature
(dew point) t’ (°F, °C)
(3) Absolute Humidity x (Ib/Ib’, kg/kg’)
Weight (Ib, kg) of the water vapor that corresponds to the
weight (Ib’, kg’) of the dry air in the humid air.
(4) Relative Humidity ϕ (%)
Ratio of the water vapor pressure Pw in the humid air and the
water vapor pressure Pws in the saturated air at the same
temperature. Relative humidity is obtained with the following
formula:
ϕR = PW/PWS × 100
(5) Dew Point t” (°F, °C)
Water content in the air will start to condense when air is
cooled and the dry bulb temperature at that condition is the
dew point.
(6) Enthalpy i (Btu/Ib, kJ/kg)
Physical matter has a set heat when it is at a certain
temperature and state. The retained heat is called the
enthalpy, with dry air at 32 °F (0 °C) being set at 0.
Relative humidity ϕ (%)
The dew point t” of the air at point A is the temperature
of the point at the same absolute humidity as point A
on the saturation curve.
t”
Parallel to absolute
temperature scale line
t” °F, °C dew point
Absolute humidity x (Ib/Ib’, kg/kg’)
A
Enthalpy i (Btu/Ib, kJ/kg)
U-19
CHAPTER 2 • Lossnay Construction and Technology
5. Lossnay Energy Recovery Calculation
The following diagram shows the various air conditions when ventilation air is introduced through the Lossnay Core. If a
conventional sensible energy recovery unit is used alone and is assumed to have the same energy recovery efficiency as
Lossnay, the condition of the air supplied to the room is expressed by Point A in the figure. Point A shows that the air is very
humid in summer and very dry in winter.
The air supplied to the room with Lossnay is indicated by Point S in the figure. The air is precooled and dehumidified in the
summer, and preheated and humidified in the winter before it is introduced to the room.
iOA
AO
iSA
Enthalpy (Btu/Ib, kJ/kg)
iOA
Outdoor air
iRA
iSA
Ventilation load
Lossnay Core energy recovery
O
tOAtSA
condition in
winter
Enthalpy (Btu/Ib, kJ/kg)
Dry bulb temperature (°F, °C)
i
RA
S
A
Ventilation load
Lossnay Core energy recovery
R
Supply air condition of
the Lossnay
Room air condition in winter
tRAtRA
Room air
condition
S
R
in summer
t
SAtOA
Supply air condition of
the Lossnay
The quantity of heat recovered by using the Lossnay Core can be calculated with the formula below:
under standard conditions 75 (Ib/ft3)
Q = Treated air volume (CFM)
t = Temperature (°F)
x = Absolute humidity (Ib/Ib’)
i = Enthalpy (Btu/Ib)
η = Energy recovery efficiency (%)
<SI unit>
γ = Specic weight of the air
under standard conditions 1.2 (kg/m3)
Q = Treated air volume (m3/h)
t = Temperature (°C)
x = Absolute humidity (kg/kg’)
i = Enthalpy (kJ/kg)
η = Energy recovery efficiency (%)
Outdoor air condition
in summer
XOA
XSA
XRA
Absolute humidity
(Ib/Ib’, kg/kg’)
XRA
XSA
XOA
OA : Outdoor air
RA : Return air
SA : Supply air
U-20
OA : Outdoor air
RA : Return air
SA : Supply air
CHAPTER 3
General Technical Considerations
Loading...
+ 75 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.