Mitsubishi Electric LGH-250RVXT-E, LGH-200RVXT-E, LGH-150RVXT-E Installation Instructions

Lossnay
Models:
LGH-150RVXT-E LGH-200RVXT-E LGH-250RVXT-E
1509876HC8401
Installation Instructions
Lossnay Energy Recovery Ventilator
MODELS:
LGH-150RVXT-E LGH-200RVXT-E LGH-250RVXT-E
English
Installation Instructions
(For use by dealer/contractor)
Safety precautions ............................................... 1
Outline drawings .................................................. 3
Before installation ................................................ 3
Standard installation examples............................4
Installation method ..............................................4
Function settings ...............................................13
Check points after installation work ................... 22
Trial operation ....................................................22
This product needs to be installed properly in order to ensure maximum functionality as well as safety. Please make sure to read this installation manual before starting the installation.
l Installation must be performed by a dealer or installation contractor. Please note that improper installation may cause malfunction or accident.
“Operating Instructions” and this manual must be handed over to the customer after completing the installation.
Safety precautions
The following signs indicate that death or serious injury may be caused by failure to heed the precautions described below.
WARNING
Do not modify or disassemble.
Do not
disassemble
Prohibition of use in bath or shower room
Connect the
grounding wire.
The instructions
given must be
followed.
(It could cause re, electric shock or injury.)
The Lossnay unit and remote controller should not be installed where it is highly humid, like a bathroom, or other wet place.
(It could cause electric shock or power leakage.)
Connect the product properly to ground.
(Malfunctioning or power leaks can cause electrical
shock.)
Use the specied power supply and voltage.
(Use of incorrect power supply or voltage could cause
re or electric shock.)
Select a place with sufcient strength and install
the main unit securely.
(It could cause injury if it falls.)
The instructions
given must be
followed.
Wiring work must be performed by qualied
professionals, and be implemented safely and securely in accordance with the engineering standards and the extension wiring rules for electrical equipment.
(Poor connection or improper wiring work could cause
electric shock or re.)
Install a power supply isolator at the power supply side as per local electrical regulations. All supply circuits must be disconnected before obtaining
access to the terminal devices. Use the specied
cable size and connect the cables securely to prevent disconnection when they are pulled.
(If there is a defect in the connection, there is a possibility of re.)
Select an adequate place for the opening to introduce outdoor air, where it will not intake the exhaust fumes like combustion gas, or others, and there is no risk of blockage.
(Shortage of fresh air could put the room in a state of
oxygen deciency.)
A duct made of steel must be installed with care not to be connected electrically with metal, wire, stainless steel plate, or others.
(It could cause re when power leakage occurs.)
Eng-1
Safety precautions (continued)
CAUTION
Prohibited
The instructions
given must be
followed.
Do not place a burning appliance in a place where it is exposed directly to the air from the Lossnay unit.
(It could cause an accident as a result of incomplete
combustion.)
Do not use at a place where it is exposed to high
temperatures (40˚C or higher), naked ames, or in
environment with combustible fumes.
(It could cause re.)
Do not use in an environment such as a chemical factory, where hazardous gases such as acidic gases, alkaline gases, organic solvent fumes, paint fumes, or gases containing corrosive components are generated.
(It could malfunction.)
Do not install this product in a place where it is exposed to ultraviolet light.
(UV may damage covering insulation.)
Put on gloves during installation.
(It could cause injury.)
Make sure the power supply isolator is turned off on the power distribution panel when Lossnay is not used for a long period of time after the installation.
(It could cause electric shock, power leakage, or re as a result of deteriorated insulation.)
Always use the specied suspension bolts,
nuts and washers or correctly rated wire / chain hangers.
(Use of hardware with insufcient strength could result in the product dropping.)
The outside ducts must be tilted at a gradient (1/30 or more) down toward the outdoor louvres from Lossnay, and properly insulated.
(The entry of rain water may cause power leakage, re, or damage to household property.)
The instructions
given must be
followed.
The control box cover must be closed after the installation.
(Dust or humidity may cause power leakage or re.)
When connecting external devices (electric heater, damper, lamp, monitoring unit, etc.) using output signals of the Lossnay unit, make sure to install safety equipment for the external devices.
(It could cause re, damage, etc. without safety equipment.)
Select a duct heater in compliance with local and national laws, ordinances, and standards.
Select a duct heater that has obtained the CE mark. Install the duct heater separated from the product
by a distance of 2 m or more.
(Failure to do so may result in re or equipment
damage due to the transmission of residual heat from
the heater.)
This appliance is not intended for use by persons (including children) with reduced physical sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
(This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.)
CAUTION
lWhen using the product where it is exposed to high temperatures
and humidity (40˚C or higher, RH 80% or higher), or where fog occurs frequently, moisture is likely to condense in the core, and
may result in condensation build up in the unit. The product should not be used under such conditions.
lOutdoor air may enter the Lossnay owing to the pressure
difference between indoor and outdoor or external winds even when the product is not operated. It is recommended to install an Electrically operated damper to block the outdoor air.
lIn a cold weather area, an area with strong external winds or
where fog occurs frequently, cold outdoor air, external winds or fog
may be introduced into the product when its operation is stopped. It is recommended to install an Electrically operated damper.
lWhen using the product in an environment where there is a
window, or opening near the outdoor louvre , where insects are likely to gather around the interior or exterior light , take note that
small insects may intrude into the product.
lIn a cold weather area, or others, dewing or freezing could occur
on the main unit, where the duct is connected, or other sections,
depending on the conditions of outdoor air and indoor temperature
and moisture, even if they are within the range of operating conditions. Make sure to conrm the operating conditions and other precautions, and do not use the product if dewing or freezing
is anticipated.
*Example of dewing condition - Outdoor air: -5˚C or lower, dew-
point temperature at installation place: 10˚C or higher (When the indoor temperature is 22˚C or higher with the relative humidity higher than 50%, or other)
Eng-2
Outline drawings
250
60
Flange
By-pass damper plate
1500
Air exhaust fan (Outside)
Air exhaust fan (Inside)
Ceiling suspension xture (6-15 X 30 oval)
Flange
English
When using φ250 duct
287
58
227
OA EA
(outside air
intake)
750
215
250
255
RA SA
(return air) (supply air)
75090
1980
945.7 945.7
Lossnay cores
By-pass damper plate
50 1450
Model Weight
LGH-150RVXT-E 156 kg LGH-200RVXT-E 159 kg LGH-250RVXT-E 198 kg
Reference for maintenance space
RA air lters OA air lters
Maintenance cover
for fan (470 x 450)
Exhaust
(exhaust air
outlet)
945.7 945.7
Flange
Air supply fan (Inside) Air supply fan (Outside)
Control box
750750115
250
250
424 500
Pipe guide
Supply
Power supply cable opening
116
132
Accessory parts
• Mounting screws 4-8 for duct anges ................. x50
(2 pcs are spare)
560560210
440
φ
242
φ
258
Unit (mm)
1200390
Inspection opening 600 x 600
150 to 250
More than 750
Maintenance cover for
Maintenance space
600
317
- Cores
- Air lters
Before installation
- Accessory parts are in the Lossnay unit (OA duct place) together
with manuals. Please remove all accessory parts before starting installation.
- Damper plate is xed against transportation vibration. Please make
it free before starting installation.
• Duct connecting anges (φ250) ........................... x4
• L shape pieces for 250 x 750 duct anges ........... x8
• Slim-Lossnay connection cable
(gray: two wires) ................................................... x1
- If carrying the product into the building is difcult due to the
product’s size, it is possible to stand the product up like the picture
below.
CAUTION
• Before standing the product up, remove the Lossnay cores and
lters (See page 3 of the operating instructions.)
Eng-3
Standard installation examples
Inspection opening for exhaust fan motors
EA
(exhaust air
outlet)
3 m or more
(recommended)
OA
(outside air
intake)
Downward gradient of duct:
1/30 or more (toward wall side) and provision of distance in table below (to prevent rain water from seeping in)
Deep hood (to prevent rain water from
seeping in)
OA (outside air
intake)
EA (exhaust air
outlet)
Remote controller (optional parts)
Duct
Inspection opening for exhaust fan motors
(600 x 600)
Inspection opening for supply fan motors
Lossnay unit
Anchor bolt (to be provided by user)
Lossnay unit
Inspection opening for supply fan motors
(600 x 600)
Inspection opening for
Lossnay cores, lters and PCB (600 x 600)
Inspection opening
for Lossnay cores, lters and PCB (600 x 600)
Maintenance space
Return air grille (not included)
RA
(return air)
Return air grille (not included)
Supply air grille
(not Included)
SA
(supply air)
Supply air grille
(not included)
EA (exhaust
air outlet)
OA (outside
air intake)
Electrically operated damper (Protection against the intrusion of cold
air while Lossnay is stopped in winter) (To be provided by the customer)
EA (exhaust
air outlet)
OA (outside
air intake)
Lossnay
unit
• In a region where there is risk of freezing in winter, it is recommended to install an Electrically operated damper, or the like, in order to prevent the intrusion of (cold)
outdoor air while Lossnay is stopped.
CAUTION
• Do not install Lossnay unit vertically or on
an incline.
• Do not install Lossnay unit up-side-down.
Installation method
Installing the Lossnay unit
1. Attaching the duct connecting anges
1) 250 x 750 duct anges Use the supplied screws (size:4-8) to x L shape pieces and form 250 x 750 anges to the Lossnay unit.
L shape piece
(Accessory parts)
Mounting screw (size:4-8) (Accessory parts)
2) φ250 duct anges For supply and exhaust path, φ250 duct x 2 can be used. Use the supplied screws (size:4-8) to secure φ250 duct connecting anges to the Lossnay unit.
Mounting screw (size:4-8) (Accessory parts)
Duct connecting ange (Accessory parts)
CAUTION
• Before attaching the duct connecting anges, check that no
foreign matter (scraps of paper, vinyl, etc.) has found its way inside to Lossnay unit.
Eng-4
Installation method (continued)
English
2. Preparing the anchor bolts (M12)
Mount the washers (outer diameter of >24 mm) and nuts onto the
pre-recessed anchor bolts (M12), as shown in the gure below.
Anchor bolt (M12)
Nut
Washer
CAUTION
Nut
[When using (customer-prepared) vibration isolation rubber] When using (customer-prepared) vibration isolation rubber, there
is a possibility of this causing a decrease in strength, so we
recommend the following type of construction.
Anchor bolt (M12)
Nut
Washer Vibration isolation rubber
Nut
USE TWO NUTS
CAUTION
USE TWO NUTS
3. Mounting Lossnay unit
(1) Hang the ceiling suspension xtures on the anchor bolts and
adjust in such a way that Lossnay unit is level.
(2) Tighten up securely using double nuts.
250 x 750 duct anges
Room Side
φ250 duct anges
Room Side
Outdoor Side
Heat-insulating material
Outdoor duct
Duct connecting ange
Outdoor Side
Heat-insulating material
Duct
Aluminium tape
Duct
Taping
Aluminium tape
Lossnay
unit
Anchor bolt
(M12)
Nut Washer
Ceiling suspension
xture
Washer Nut
CAUTION
When suspending Lossnay unit from the ceiling, do not handle it in such a way that force will be applied to the control box.
• Install the anchor bolts to ensure the product's weight or
earthquake load. (Correctly rated wire/chain may also be used)
4. Connecting the ducts
(1) Fasten the duct securely to the duct connecting ange, and
wrap aluminium tape (eld supply) around the joints so that
there is no air leakage.
(2) Suspend the ducts from the ceiling so that their weight will not
be applied to the Lossnay unit.
(3) The two outdoor ducts must be covered with heat-insulating
material in order to prevent condensation from forming.
Lossnay
Outdoor duct
Duct connecting ange
unit
CAUTION
• When on-site commissioning is planned, a straight duct
length more than 10xD (D=duct diameter or equivalent) from the source of turbulence like bends, contractions and dampers etc, to the measurement point is recommended for correct measurement. In the United Kingdam, on-site measurment should therefore be measured in accordance with BSRIA guideline (Commissioning Air System. Application procedures for buildings AG3/89.3(2001))
Before attaching the ducts, check that no (debris or any other) foreign matter (scraps of paper, vinyl, etc.) has found its way inside the ducts.
• Do not touch the damper plate inside Lossnay unit when
connecting the ducts. (When the rectangular duct is secured with screws, check that the screws are not collided to the damper plate.)
• If it is expected that the ambient temperature around the place
where the Lossnay unit is installed will be high during the summer air conditioning season, it is recommended that the indoor duct work be covered with insulation material.
• Do not place the auxiliary blower to the exhaust side air
passage.
Do not carry out the following types of duct construction. (Doing so
could cause a drop in the air volume and generate abnormal noises.)
• Extremely
sharp bends
• Multiple bends • Bends right next
to the outlet
• Extreme reduction in
the diameter of the connected ducts
Eng-5
Installation method (continued)
Electrical installation
With this product, the wiring installation method will vary according to
the design of the system. Perform electrical installation to meet local electrical regulations. * Always use double insulated PVC cable for the transmission cables.
* Wiring work must be performed by qualied professionals.
* All supply circuits must be disconnected before obtaining access to
the terminal devices.
Names of components in control box
TM3
TM4
TB5
TM2
LED3
LED1, 2, 4
SW2, SW5
SA1, SA2
TM1
Eng-6
Installation method (continued)
Wire connection diagram ----- Model LGH-150 and 200 RVXT-E
* TM1, TM2, TM3, TM4, TB5 shown in dotted lines are eld work.
* Be sure to connect the ground wire. * A power supply isolator must be installed. * Always use an isolator for the main switch power connection. * Select proper circuit breaker according to the electrical current information in the chart below.
Model LGH-150RVXT-E LGH-200RVXT-E Maximum current when operating [A] 5.6 6.4
Inrush current after power
supply ON [A]
10 ms 12.1 100 ms 6.6
Printed Circuit Board 1
M
3
EXHAUST FAN MOTOR (Inside)
M
2
SUPPLY
FAN MOTOR (Inside)
CN9
CN10
CN119
CN118
TAB2 TAB1
TAB5
LED6
Bypass monitor or Pre-
heater signal output (*1)
Malfunction monitor
output (*1)
Operation monitor
output (*1)
COM
PZ­61DR-E
2nd remote controller
(Max. 2 controllers)
2nd Lossnay unit
(Max. 15 units)
M-NET­transmission cable
Shielded Wire
Volt-free contact
12V or 24VDC Mr .Slim
(non-polar)
(*1) MAX 240 VAC 1 A MIN 220 VAC 100 mA
24 VDC 1 A 5 VDC 100 mA
TM3
7
8
9
10
1
X15
TM4
X14
CN20(GR)
CN26(WH)
CN32(WH)
X13
CN17(RE)
LED3
2
Printed Circuit Board for control
A
TB5
B
S
TM2
1
2
3
LED4 LED2 LED1
SW2
SA2 SA1
SW5
CN21
English
M
4
EXHAUST FAN MOTOR (Outside)
M
1
SUPPLY
FAN MOTOR (Outside)
GM
M1: Motor for supply fan (outside) M2: Motor for supply fan (inside) M3: Motor for exhaust fan (inside) M4: Motor for exhaust fan (outside)
GM: Motor for By-pass damper
TH1: Thermistor for outside air TH2: Thermistor for return air SW2,5: Switch (Function selection)
TM1:
Terminal block (Power supply) TM2: Terminal block (External control input) TM3: Terminal block (Monitor output) TM4: Terminal block (Transmission cable) TB5: Terminal block (M-NET Transmission cable)
Printed Circuit Board 2
CN9
LED6
CN121
CN10
CN7
TAB2
TAB1
REACTOR
Denition of symbols
TAB1, TAB2, (TAB5) TAB3,TAB4 X13: Relay contact X14: Relay contact X15: Relay contact CN5: Connector (Thermistor RA) CN7: Connector (Motor for By-pass damper) CN9: Connector (Fan motor) CN10: Connector (Fan motor) CN17: Connector (Fan speed 1/2/3/4) CN18: Connector CN118: Connector
CN19: Connector
: Connector (Power supply)
: Connector (Reactor)
REACTOR
LINE
FILTER
CN19
CN18
CN5
CN22
TH1(OA)
TH2(RA)
Isolator
(Field supply)
L
N
PE
L
N
POWER SUPPLY
TM1
CN119: Connector CN20: Unused
CN22: Connector (Thermistor OA)
CN26: Connector (
CN32: Connector (Remote control selection) SA1: Address setting rotary switch (tens digit) SA2: Address setting rotary switch (ones digit)
LED1 to LED3: Inspection indicator lamp
LED4, LED6: Power supply indicator lamp
SYMBOL
:
:
By-pass, 0 - 10 VDC Fan speed control
Terminal block
Connector on PCB
)
Eng-7
Installation method (continued)
Wire connection diagram ----- Models LGH-250RVXT-E
* TM1, TM2, TM3, TM4, TB5 shown in dotted lines are eld work.
* Be sure to connect the ground wire. * A power supply isolator must be installed. * Always use an isolator for the main switch power connection. * Select proper circuit breaker according to the electrical current information in the chart below.
Model LGH-250RVXT-E
Maximum current when operating [A] 10.8
Inrush current after power
supply ON [A]
M
EXHAUST FAN MOTOR (Outside)
10 ms 21.8 100 ms 11.9
M
3
EXHAUST FAN MOTOR (Inside)
4
CN9
Top Left Printed Circuit Board
(EA Outside)
TAB2
Top Right Printed
Circuit Board
(EA Inside)
CN9
TAB5
LED6
CN121
TAB1
CN118
TAB2
LED6
CN119
TAB1
(*1)
Bypass monitor or Pre-
heater signal output (*1)
Malfunction monitor
output (*1)
Operation monitor
output (*1)
PZ­61DR-E
2nd remote controller
(Max. 2 controllers)
2nd Lossnay unit
(Max. 15 units)
M-NET­transmission cable
Shielded Wire
12V or
Volt-free
24VDC
contact
Mr .Slim
(non-polar)
MAX 240 VAC 1 A MIN 220 VAC 100 mA
24 VDC 1 A 5 VDC 100 mA
COM
7
8
9
10
1
2
A
B
S
1
2
3
TM3
X15
TM4
TB5
TM2
CN20(GR)
CN26(WH)
CN32(WH)
X14
X13
CN17(RE)
LED3
CN17 (Red)
Printed Circuit Board for Control
CN21
LED4 LED2 LED1
SW2
SA2 SA1
SW5
M
SUPPLY
FAN MOTOR (Inside)
M
1
SUPPLY
FAN MOTOR (Outside)
GM
GM
2
CN10
Bottom Right
Printed Circuit Board
(SA Inside)
CN10
Bottom Left Printed Circuit Board
(SA Outside)
CN7
TAB2
M1: Motor for supply fan (outside) M2: Motor for supply fan (inside) M3: Motor for exhaust fan (inside) M4: Motor for exhaust fan (outside)
GM: Motor for By-pass damper
TH1: Thermistor for outside air TH2: Thermistor for return air SW2, 5
: Switch (Function selection)
TM1:
Terminal block (Power supply) TM2: Terminal block (External control input) TM3: Terminal block (Monitor output) TM4: Terminal block (Transmission cable) TB5: Terminal block (M-NET Transmission cable)
LED6
CN121
TAB2
LED6
TAB1
REACTOR
CN121
TAB1
REACTOR
Denition of symbols
TAB1, TAB2, TAB5 TAB3, TAB4
: Connector (Power supply)
: Connector (Reactor) X13: Relay contact X14: Relay contact X15: Relay contact CN5: Connector (Thermistor RA) CN7: Connector (Motor for By-pass damper) CN9: Connector (Fan motor) CN10: Connector (Fan motor) CN17: Connector (Fan speed 1/2/3/4) CN18: Connector CN118: Connector
CN19: Connector
CN19
CN18
CN5
TH2(RA)
LINE
FILTER
L
N
PE
TM1
CN22
TH1(OA)
Isolator
(Field supply)
POWER SUPPLY
L
N
CN119: Connector CN20: Unused CN21: Connector CN121: Connector
CN22: Connector (Thermistor OA)
CN26: Connector (
By-pass, 0 - 10 VDC Fan speed control
) CN32: Connector (Remote control selection) SA1: Address setting rotary switch (tens digit) SA2: Address setting rotary switch (ones digit)
LED1 to LED3: Inspection indicator lamp
LED4, LED6: Power supply indicator lamp
SYMBOL
:
:
Terminal block
Connector on PCB
Eng-8
Installation method (continued)
English
Connecting the power supply cable
1. Remove the black screws and the control box cover
Control box cover
Black screws
2. Connecting the power supply cable and transmission cable
Pass the Power supply cable through the bush* and connect to the
TM1 terminal block using the round terminals. Connect the ground wire to the ground terminal and secure tightening the bush. (* Use
an item that can rmly secure the cable such as a PG connector.)
The following system conguration can
be created. Connect the necessary parts.
1 When connecting with remote controller (PZ-61DR-E). 2 When interlocked with indoor unit of air conditioner or other
external device including other manufactures.
3 When operating multiple Lossnay units. 4 By-pass monitor or Pre-heater signal output. 5 Malfunction monitor output. 6 Operation monitor output
7 When switching fan speed externally (when a sensor or other
device is connected).
8 When switching By-pass externally.
9 To change fan speed by 0 - 10 VDC input
10
When using the remote/local switching and the ON/OFF input
(level signal)
11
When connecting to the City Multi or Mitsubishi Electric Air-
Conditioner Network System (MELANS).
12
To start/stop Lossnay stand-alone operation without using the
remote control
CAUTION
• When connecting external devices (electric heater, damper,
lamp, monitoring unit, etc.) using output signals of the Lossnay unit, make sure to install safety equipment for the external devices.
(It could cause re, damage, etc. without safety equipment.)
Insert the cutting
Cord clip
Transmission cable
Bush
TM1
Ground wire
PG connector
Power supply cablePower supply cable
CAUTION
• Always separate the power supply cable and transmission
cable by 5 cm or more to prevent malfunctioning of the unit.
• If the length of the stripped Power supply cable is too long,
the conductors may touch and short out.
• Power supply cable size : 1.5 mm
(1) Tighten the ground wire and transmission cables to the
terminal block.
(2) Secure the transmission cables using the cord clips.
Upon completion of the wiring connections, replace the control box
cover.
2
(ø9)or more.
When connecting with remote controller (PZ-61DR-E)
1
* When controlling Lossnay units with MELANS, connect wires
according to 11 .
Securely connect the transmission cable from the remote controller
to 1 and 2 of the input terminal block (TM4). (No polarity)
Wire type: two-core sheathed cable
Wire diameter: 0.3 mm
If there are two remote controllers, connect them in the same way.
• Keep the overall length of the transmission cable between
Lossnay and the remote controller within 200 m.
2
Note
• Do not tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
• Take care not to connect the power supply cable or M-NET
transmission cable.
Number of transmission cables which can be connected to single input terminal is up to 4 wires.
• Single wires such as PVC wires cannot be connected.
Lossnay
Power supply
Up to two remote controllers
Transmission cables
2 1
Remote controller input terminal
Eng-9
Installation method (continued)
When interlocked with indoor unit of air conditioner or
2
other external device including other manufactures
CAUTION
• The connection may vary according to the output signal type
of the external unit.
• Don’t tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
Lossnay
Power supply
TM2
External device
Power supply
Operating switch for external device
When using Mitsubishi Mr. Slim air conditioner with MA Remote controller
Conrm that the pulse input switch (SW2-2) is set to “OFF”. (Factory setting is “OFF”.) (Refer to function settings No. 28 )
Connect the interlocking cable connector side to CN2L on the
circuit board for the Mr. Slim indoor unit, then connect the lead wire side to the 1 and 2 of the input terminal block (TM2) for the Lossnay external controller input. (No polarity)
• Always separate the power supply cable and the Slim-Lossnay
connection cable by 5 cm or more to prevent the unit from malfunctioning.
• The Slim-Lossnay connection cable is 100 mm long. When wiring, extend it as far as necessary.
Lossnay external control input
(TM2)
Maximum 500 m
Slim-Lossnay connection cable
(Accessory parts)
CN2L
Mr. Slim (Indoor unit)
Printed circuit board
Note
• The Lossnay remote controller (PZ-61DR-E) cannot be used
with this system.
• Use MA remote controller of Mr. Slim for switching Lossnay
ON/OFF or the fan speed.
• The ventilation mode is “automatic ventilation”.
• Ensure that all connections are secure and that the appropriate
insulation is provided.
Use extension cable sheathed PVC cable or cable 0.5 mm
1.5 mm2.
2
to
When the external device has an uncharged a-contact signal
• The wiring should be the following picture.
Lossnay external control input
(TM2)
Maximum 500 m
2
to 1.5 mm2 sheathed PVC cable
0.5 mm
External device
Uncharge a-contact
CAUTION
• If an optocoupler or any other type of polar coupler is used at
the uncharged a-contact, connect the positive side to 3 and the negative side to 1.
When operating multiple Lossnay units
3
1) Connect from Lossnay Unit 1 to Lossnay Unit 2, and from Unit 2 to
Unit 3 and so on up to a maximum of 15 units using a transmission
cable. Wire type: two-core sheathed cable Wire diameter: 0.3 mm
2) When it is interlocked with an external device, turn ON the setting
switch (SW5-10) of main Lossnay where the external signal is
input.
Lossnay
Power supply
Lossnay
Power supply
Lossnay
Power supply
MAX 15 units
2
External device
Remote controller (PZ-61DR-E)
Power supply
Operating switch for external device
1 2
SW5
First
21
TM4
TM4
Transmission cable
21
Lossnay
Second Lossnay
3 4 5 6 7 8 9 10
Connect to remote controller
(PZ-61DR-E)
Connect to third Lossnay
ON
ON OFF
When the external device has a charged operating signal of 12 VDC or 24 VDC
[SW2-2] setting vary depending on the types of output signal of
external device.
• Move the pulse input switch [SW2-2] to the ON position.
(Refer to function settings
No. 28 )
• When interlocking with a pulse output device, a pulse width is at least 200 m sec. to turn Lossnay ON, and 10 sec. interval is
necessary to next output.
• The wiring should be the following picture.
Lossnay external control input
(TM2)
Overall connection extension length
(Follow the operation manual for the external equipment.)
2
to 1.5 mm2 sheathed PVC cable
0.5 mm
External device
12 or 24 VDC
Eng-10
CAUTION
Don’t tighten screws of terminal block with a torque larger
than 0.5 Nm. It could damage the PCB.
Note
• Up to four transmission cables can be connected to one input
terminal.
• Single wires such as PVC wires cannot be connected.
• Only one unit can be set as main Lossnay. The operating
signal and pulse signal of the external device can be connected to main Lossnay only.
• When the external signal is not input, main-unit setting is not
required even for operation of multiple units.
• Connect the power supply cable to each Lossnay unit.
Installation method (continued)
English
By-pass monitor or Pre-heater signal output.
4
By-pass monitor or Pre-heater signal can be selected at SW5-6.
(Refer to function settings No. 58 )
Always check that it is the intended setting.
By-pass monitor SW5-6 OFF
By-pass operation indicator
Max 240 VAC, 1 A 24 VDC, 1 A Min 220 VAC, 100 mA 5 VDC, 100 mA
Pre-heater output SW5-6 ON
Power Supply for heater
Relay
2 m or more
OA
Pre-heater
Power Supply
Lossnay
Power Supply for relay
TM3
7
8
9
10
TM3
7
8
9
10
SA
X13
X13
Max 240 VAC, 1 A 24 VDC, 1 A Min 220 VAC, 100 mA 5 VDC, 100 mA
CAUTION
• Select a duct heater in compliance with local and national
laws, ordinances, and standards.
Select a duct heater that has obtained the CE mark.
• Always select a heater that is equipped with a non-self-
resetting safety device.
Do not directly supply power from the Lossnay unit to the
duct heater.
(Doing so could cause re.)
• Install a circuit breaker for the duct heater in compliance with
all applicable laws, ordinances, and standards.
• Install the duct heater separated from the product by a
distance of 2 m or more.
(Failure to do so may result in equipment damage due to the
transmission of residual heat from the heater.)
• When using a heater without a temperature control function,
select a heater with a capacity that is matched to the air volume.
• Do not use the heater outside the set air volume. (If the heater’s capacity is too larger, this may result in the
heater frequently turning ON/OFF.)
(If the heater’s capacity is too small, this may result an
inability to heat.)
• Ensure that the duct heater and Lossnay are wired and that the Lossnay function settings have been congured, and then
always check operation by trial operation.
• For the duct heater output, see function setting SW5-6.
Malfunction monitor output.
5
TM3
Malfunction indicator
Power Supply
Max 240 VAC, 1 A 24 VDC, 1 A Min 220 VAC, 100 mA 5 VDC, 100 mA
7
8
9
10
X14
Operation monitor output
6
Operation monitor output can be selected to sympathize with exhaust
fan or supply fan at SW 5-2. SW5-2 OFF: Exhaust fan operation monitor output SW5-2 ON: Supply fan operation monitor output
(Refer to function settings No. 57 )
Always check that it is the intended setting.
TM3
Operation indicator
Power Supply
Max 240 VAC, 1 A 24 VDC, 1 A Min 220 VAC, 100 mA 5 VDC, 100 mA
7
8
9
10
X15
To use operation monitor output for a supply after-heater, turn SW2-8 ON, and use the supply fan operation monitor output with delayed operation. (Refer to function settings No. 57 ) For the heater, observe the cautions listed in 4 .
OA
When switching fan speed externally
7
(when a sensor or other equipment is connected)
Lossnay
Power Supply for heater
2 m or more
SA
Relay
Power Supply for relay
TM3
7
8
9
X15
10
Max 240 VAC, 1 A 24 VDC, 1 A Min 220 VAC, 100 mA 5 VDC, 100 mA
Using a eld supply sensor, etc., make connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN17 (Red) as shown by the gure. Lossnay will operate the fan speed following the table below,
regardless of the remote controller setting.
CN17 (Red) Fan speed 1-2 (Brown-Red) 4 1-3 (Brown-Orange) 3 1-4 (Brown-Yellow) 2 1-5 (Brown-Green) 1
nExample “Fan speed 4”
Field supply sensor, etc.
SW1
Remote display adaptor (Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4 Green 5
Not used. Insulate completely.
Max wiring length 10 m
Lossnay control board
CN17
Fan speed selection
Use this in such a way that it ventilates at low fan speed normally, and when the external sensor detects contamination of indoor air,
it changes to high fan speed operation.
Eng-11
Installation method (continued)
When switching By-pass externally.
8
Establish the wire connection by inserting the optional remote display
adaptor (PAC-SA88HA-E) in the connector CN26 (White).
SW1
SW1: By-pass ventilation operation switch
(When closed: For By-pass ventilation operation)
Remote display adaptor (Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4 Green 5
Not used. Insulate completely.
Max wiring length 10 m
Lossnay control board
CN26
Fan speed/ Ventilation mode selection
With SW1 is “ON”, the ventilation mode of Lossnay is changed to the By-pass ventilation regardless of the setting on the remote controller.
* When the outdoor air temperature drops lower than 8˚C, it
changes to the heat exchanger ventilation. (Display of the
remote controller does not change.)
To change fan speed by 0 - 10 VDC input
9
Establish the wire connection by inserting the optional remote display
adaptor (PAC-SA88HA-E) in the connector CN26 (White).
Not used. Insulate completely.
External device
Remote display adaptor (Optional) PAC-SA88HA-E
Brown 1
Red 2
Orange 3
Yellow 4 (0 - 10 VDC) Green 5 (COM)
Max wiring length 10 m
Lossnay control board
CN26
Fan speed/ Ventilation mode selection
To change fan speed by 0 - 10 VDC input, the wiring should be the above picture. Refer to function settings No. 63 for more details.
CAUTION
• Make sure of correct polarity.
When connecting to the City Multi, Mitsubishi Electric Air-
11
Conditioner Network System (MELANS)
M-NET transmission cable
Shielded wire M-NET transmission cable input terminal block
TB5
S
BA
• One shielded wire is connected to terminal TB5 S on the PCB.
Address setting is required. (Refer to function setting section.)
M-NET transmission cable: Connect any of the City Multi indoor
unit, or Mitsubishi Electric Air­Conditioner Network System (MELANS)
- to the Lossnay.
• Remote Controller
PZ-61DR-E:
Connect to TM4 1, 2 on the PCB. (See Section 1 “When
connecting with Remote Controller (PZ-61DR-E).)
• Securely connect the M-NET transmission cables to TB5 AB.
(No-Polar)
Type: (Shielded wire, CVVS/CPEVS)
Wire diameter: 1.25 mm2 to 2.0 mm2
CAUTION
• Don’t tighten screws on the terminal block with a torque larger
than 0.5 Nm. It may damage the PCB.
• Always use shielded wires only for the M-NET transmission cables, and nish the shield properly.
When interlocking with Mitsubishi M-NET air conditioner
• Incase of PZ-61DR-E
Air
conditioner
MA remote
controller
Air
conditioner
M-NET transmission cable
Lossnay
PZ-61DR-E
When using the remote/local switching and the ON/OFF
10
input (level signal)
Insert the optional remote ON/OFF adaptor (PAC-SE55RA-E) in
CN32 on the Lossnay control PCB.
Remote control
board
SW2
SW1
Relay power supply
Relay circuit
X
Y
Remote ON/OFF adaptor (Optional) PAC-SE55RA-E
Orange 1
X
Red 2
Y
Brown 3
Max wiring length 10 m
Lossnay control board
CN32
SW1: When this is ON, Lossnay cannot turn ON/OFF by the
Remote Controller (PZ-61DR-E).
SW2: When SW1 is ON, Lossnay can be turned ON by setting
SW2 at ON or turned OFF by setting SW2 at OFF.
SW1: Remote/local selector switch SW2: ON/OFF switch X, Y : Relay (Contactor rating DC 1 mA)
When connecting to PZ-61DR-E and MELANS
• Connect the power feeding unit.
(Optional)
Power
supply unit
MELANS
M-NET transmission cable
Lossnay
PZ-61DR-E
* Limit the total length of transmission cables no longer than
500 m. Limit the wiring length between Lossnay and the power
supply unit (Optional) or the outdoor unit no longer than 200 m.
To start/stop Lossnay stand-alone operation without
12
using the remote control
TM1
Isolator
L
N
PE
TM2
Start/stop the unit by a switch connected to TM213.
When turned the unit ON, it operates at fan speed 4 and
automatic ventilation mode. Do not start/stop the unit by turning the power supply to the unit ON/OFF.
Lossnay external control input
Switch
Eng-12
Function settings
English
Address setting is required when connecting to City Multi and MELANS.
Setting the address
Use the following procedure when setting the address for dedicated Lossnay. (The method in determining the addresses will depend on the existing
system. Refer to the appropriate technical documents for details.) (1) Remove the control box cover. (2) Use a at blade screwdriver to turn the address setting switch on
the circuit board.
• SA1 indicates the tens digit and SA2 indicates the ones digit.
• The factory setting is “00”.
SA1 SA2
10s digit 1s digit
Address setting switch
* When the address number has been changed, the data in the
memory is automatically reset.
Changing the function selection switches (SW-2, 5 and 6)
Set the selection switches (SW-2 and 5) to perform the appropriate
function. * All function except “Trial operation” and “Main unit setting” can be
set also from the remote controller (PZ-61DR-E). If the function is switched later using the remote controller, it operates according to
the setting on the remote controller.
Change the function settings from the remote controller PZ-61DR-E.
Please refer to the Instruction book of PZ-61DR-E for how to set the
function settings.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
(SW2)
OFF ON
(SW5)
OFF ON
Trial operation
No. 28 Pulse input setting
No. 63 External fan speed input setting (0 - 10 VDC) No. 6 Indoor negative pressure setting
No. 7 Indoor positive pressure setting
No. 63 External fan speed input setting (0 - 10 VDC) No. 51 Automatic ventilation mode setting
No. 57
Operation monitor output synchronized with exhaust fan or supply fan
No. 61 Fan speed for air volume “High” input No. 62 Fan speed for air volume “Low” input
No. 9 Delay start setting for air conditioner starting
No. 57 Operation monitor output synchronized with exhaust fan or supply fan
No. 13 , No. 14 Exhaust fan setting No. 5 Automatic recovery setting after power interruption No. 1 Filter maintenance and fan power up setting against lter choking
No. 58 By-pass monitor output or Pre-heater output setting
No. 15 Interlock mode setting No. 15 Interlock mode setting No. 14 Exhaust fan setting at OA temperature lower than -15˚C
Main unit setting (refer to page 10)
DIP-SW 6 is to idenify the model for PCB.
When replacing to new PCB, set the same
setting as old one.
(SW6)
SW6-1 SW6-2 SW6-3 SW6-4
LGH-150RVXT-E OFF ON OFF ON LGH-200RVXT-E ON ON OFF ON LGH-250RVXT-E OFF OFF ON ON
* Do not change from factory setting.
If changed,please set as factory setting.
Eng-13
Function settings (continued)
No Function
Filter maintenance and fan power up setting
*1
against lter choking
2 Lossnay core maintenance indicator setting N/A Available - - - - - - 0 N/A
Automatic recovery setting after power interruption
5
6 Indoor negative pressure setting
7 Indoor positive pressure setting
Max. fan speed setting during the rst 30 minutes
8
9 Delay start setting for air conditioner starting
Exhaust fan setting during air conditioner defrosting
13
Exhaust fan setting at OA temperature lower
14
than -15 ˚C
15 Interlock mode setting
28 Pulse input setting
Night-purge setting 1)
*30
Air volume
Night-purge setting 2)
*31
Outdoor and indoor temperature gap
Night-purge setting 3)
*32
Threshold of outdoor temperature
Night-purge setting 4)
*33
Time span for memorizing
*34 Input priority setting
36 Outdoor temperature display setting N/A Available - - - - - - 0 N/A
37 Indoor temperature display setting N/A Available - - - - - - 0 N/A 38 Calculated supply air temperature display setting N/A Available - - - - - - 0 N/A
Temperature exchange efciency setting (10 digit)
39
40 Temperature exchange efciency setting (1 digit) Setting Data 0 to 9 --> 1 digit of temperature exchange efciency 0 to 9 0 N/A *41 Outdoor temperature correction Setting Data 0 to 14 --> Outdoor temperature correction -7 ˚C to 7 ˚C 7 N/A *42 Indoor temperature correction Setting Data 0 to 14 --> Room temperature correction -7 ˚C to 7 ˚C 7 N/A
*51 Automatic ventilation mode setting
Automatic ventilation mode setting 1)
*52
Outdoor and indoor temperature gap
Automatic ventilation mode setting 2)
*53
The lowest outdoor temperature setting
Automatic ventilation mode setting 3)
*54
The lowest indoor temperature setting *55 Supply fan power up setting N/A 1 level up 2 level up 3 level up 4 level up - - - 0 N/A *56 Exhaust fan power up setting N/A 1 level up 2 level up 3 level up 4 level up - - - 0 N/A
Operation monitor output synchronized with
57
exhaust fan or supply fan
By-pass monitor output or Pre-heater output set-
58
ting
Pre-heater setting 1)
*59
ON temperature
Pre-heater setting 2)
*60
OFF interval
*61 Fan speed for air volume “High” input
*62 Fan speed for air volume “Low” input
*63 External fan speed input setting (0 - 10 VDC)
100 Initialization - Initialize - - - - - - 0 N/A
This table shows the summary of function settings. Please refer to the following pages for more details.
The functions indicated with * are newly added or modied from Lossnay LGH-RX The functions indicated with “N/A” in the “DIP-SW No.” column are available only when using with remote controller PZ-61DR-E.
0 1 2 3 4 5 6 7
Indicator
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Setting Data 0 to 15 --> The lowest outdoor temperature for Night-purge 15 ˚C to 30 ˚C 2 N/A
Main unit
input priority
Setting Data 0 to 9 --> 10 digit of temperature exchange efciency 0 to 9 7 N/A
Dip-SW
priority
Setting Data 0 to 7 --> Temperature gap 0 ˚C to 7 ˚C 0 N/A
Setting Data 0 to 15 --> Lowest outdoor temperature 10 ˚C to 25 ˚C 6 N/A
Setting Data 0 to 15 --> Lowest indoor temperature 15 ˚C to 30 ˚C 1 N/A
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
Dip-SW
priority
available Fan power up N/A
Stop when the power is On
N/A Available - - - - - - 0 N/A
ON/OFF interlock
Non-pulse
Fan speed 1 Fan speed 2 Fan speed 3 Fan speed 4
N/A
0 ˚C 1 ˚C 2 ˚C 3 ˚C 4 ˚C 5 ˚C 6 ˚C 7 ˚C 5 N/A
24 hrs 48 hrs 72 hrs - - - - - 0 N/A
Individual
input priority
Pattern A Pattern B
EA fan
monitor
output
By-pass
monitor
output
0 ˚C -1 ˚C -2 ˚C -3 ˚C -4 ˚C -5 ˚C -6 ˚C -7 ˚C 0 N/A
1 hr 2 hrs 3 hrs 4 hrs 5 hrs - - - 0 N/A
Fan speed 4Fan speed
Fan speed 2Fan speed
Indicator N/A Fan power up N/A
Start when the power is On
Supply 1
N/A
N/A
N/A 15 min 30 min - - - - 0 5-1
Stop No change - - - - - 0 5-3
Stop
input
N/A Pattern X Pattern Y Pattern Z - - - 0
down
Exhaust 1
down
Fan speed
1 or 2
ON inter-
lock
Pulse
input
- - - - - - 0 N/A
SA fan
monitor
output
Operation
monitor
output for
Pre-heater
3
1
-E series.
5
Setting Data
Indicator available Fan power up available
Return to the
state before interruption
Supply 2
down
Exhaust 2
down
No change - - - - 0
OFF inter-
lock
- - - - - 0 2-2
Free
setting
SA fan
monitor
with delay
operation
- - - - - 0 5-6
- - - - - 0 2-9
- - - - - 0 2-10
- - - - 0 5-5
- - - - 0 5-4
- - - - 0 2-4
- - - - 0 2-5
External
input given
priority
- - - - 0 2-7
- - - - 0
- - - 0
- - - 0 N/A
Factory
setting
DIP-SW
No.
5-3 5-9
5-7 5-8
2-8
5-2
2-3 2-6
Eng-14
Loading...
+ 33 hidden pages