CITY MULTI® H2I® Y-SERIES HYPER-HEATING INVERTER
SYSTEM DESIGN
1. ELECTRICAL WORK ...........................................................................................................................................H2iSD-2
1-1. General Cautions ....................................................................................................................................... H2iSD-2
1-2. Power Supply for Indoor Unit and Outdoor Unit ......................................................................................... H2iSD-3
3-1. R410A Piping Material ..............................................................................................................................H2iSD-22
4-1. Installation Site Requirements ................................................................................................................. H2iSD-26
4-2. Installation Clearance Space ................................................................................................................... H2iSD-27
4-3. Piping Direction ........................................................................................................................................ H2iSD-29
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
H2iSD-1
®
Y-SERIES
2010 H2i
SYSTEM DESIGN
1. ELECTRICAL WORK
1-1. General Cautions
Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring
regulations, and guidance of each electric power company.
Wiring for control (hereinafter referred to as transmission ) shall be (50mm[1-5/8in] or more) apart from power source
wiring so that it is not influenced by electric noise from power source wiring. (Do not insert transmission and power
source wire in the same conduit.)
Be sure to provide designated grounding work to outdoor unit.
Give some allowance to wiring for electrical part box of indoor and outdoor units, because the box is sometimes removed
at the time of service work.
Never connect 100V, 208~230,460V power source to terminal block of transmission . If connected,electrical parts will
be burnt
Use
multiplecore
out.
2-conductor
cable, the resultant poor transmitting and receiving will cause erroneous operations.
shield cable for transmission . If transmission of different systems are wired with the same
cable
cable
cable
cable
cables
Outdoor
unit
2-conductor shield cable
OKNO
Outdoor
unit
2-conductor shield cable
BC controller
Indoor unit
Remote
controller
Indoor unit
Remote
controller
Outdoor
unit
Outdoor
unit
Multiple-
core cable
Remote
controller
BC controller
controller
Indoor unit
Indoor unit
Remote
H2iSD-2
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
1. ELECTRICAL WORK
1-2. Power Supply for Indoor and Outdoor Units
1-2-1. Electrical Characteristics of the Indoor Units
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
H2iSD-5
2. M-NET CONTROL
2-1. Transmission Cable Length Limitations
®
Y-SERIES
2010 H2i
SYSTEM DESIGN
2-1-1. Using MA Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm
Max. Total M-NET Wiring
Max. length to Outdoor (M-NET cable)
(L1 → 8) <=2km [6,560ft.] 1.25mm2 [AWG16] or thicker
∑
L1+L8, L3+L4, L6, L2+L6+L8, L7 <=200m[656ft.] 1.25mm2 [AWG16] or thicker
Max. length from MA to Indoor a1+a2, a1+a2+a3+a4 <=200m[656ft.] 0.3-1.25 mm
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm
L
8
Group1Group3Group5
OS
(52)
TB3
M2
TB7
M2SM2M1M1 S
2
L
6
L
7
L
(51)
OC
TB3
M2M1M1
TB7
AG-150A
Shielded wire
OC
(54 )
TB7
M1M2
S
TB3
M2M1
Power Supply Unit
PAC-SC51KUA
AB
S
V+V-FG
AB
S
V+V-FG
L
3
IC
(01)
TB5 TB15
M1 M2 12S
a1
AB
a2
MA
IC
(02)
TB15
TB5
12
M1 M2 S
n
OC, OS : Outdoor unit controller; IC: Indoor unit controller; MA: MA remote controller
L
1
M1 M2 S
M1 M2 S
IC
(04)
TB15
TB5
12
a2
L
4
IC
(03)
TB 15
TB5
12
a1
AB
MA
M1 M2 S
M1 M2 S
IC
(05)
TB15
TB5
12
a1
AB
MA
IC
(07)
TB15
TB5
12
2
[AWG16] or thicker
2
[AWG22-16]
2
[AWG18-14]
IC
(06)
TB5
M1 M2 S
a2
a4
AB
MA
TB15
12
a3
2-1-2. Using ME Remote controller
Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission.
Max. length via Outdoor (M-NET cable)
Max. Total M-NET Wiring
Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7, L3+L5 <=200m[656ft.] 1.25mm
Max. length from ME to Indoor e1, e2+e3, e4 <=10m[32ft.]*1 0.3-1.25 mm
24VDC to AG-150A n <=50m[164ft.] 0.75-2.0 mm
*1. If the length from ME to Indoor exceed 10m [33ft.], use 1.25 mm
L
8
OS
(52)
TB3
M2
TB7
S
M2
OC, OS : Outdoor unit controller; IC: Indoor unit controller; ME: ME remote controller
H2iSD-6
OC
(51)
TB3
M2M1M1
TB7
M2M1M1
S
Shielded wire
2
L
TB7
M1 M2
L6L7
Power Supply Unit
PAC-SC51KUA
AG-150A
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
L1+L2+L3+L4, L1+L2+L6+L7,L1+L2+L3+L5, L3+L4+L6+L7
∑ (L1 → 8) <=2km [6,560ft.] 1.25mm
2
[AWG16] shielded cable, but the total length should be counted into Max. length via Outdoor.
When 10m [32ft] is exceeded, use cables with
the same specification as transmission cables.
2
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
PE insulated PVC jacketed shielded communication cable
CPEVS :
CVV : PV insulated PVC sheathed control cable
1.25 [AWG16]
1.25 [AWG16]
Max length : 200m [656ft]
SYSTEM DESIGN
2010 H2i
Y-SERIES
2
2
®
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
H2iSD-7
®
Y-SERIES
2010 H2i
SYSTEM DESIGN
2. M-NET CONTROL
2-3. System Conguration Restrictions
2-3-1. Common restrictions for the CITY MULTI system
For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.)
C) 1 LOSSNAY unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 LOSSNAY unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor unit.
E) Maximum 3 System controllers are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the Outdoor unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor unit, if the transmission
power is supplied by the power supply unit PAC-SC51KUA. Details refer to 2-3-3-C.
*System controller connected as described in D) and E) would have a risk that the failure of connected Outdoor
unit would stop power supply to the System controller.
2-3-2. Ensuring proper communication power for M-NET
In order to ensure proper communication among Outdoor unit, Indoor unit, LOSSNAY and Controllers, the transmission
power situation for the M-NET should be observed. In some cases, Transmission booster should be used. Taking the
power consumption index of Indoor unit sized P06-P54 as 1, the equivalent power consumption index and supply
capability index of others are listed at Table 2-3-1 and Table 2-3-2.
Table 2-3-1 The equivalent power consumption by index Indoor units, LOSSNAY, controllers
Indoor, OA unitIndoor unit
Sized P06-P54
Sized P72,
P96
BC controller
CMB
1701/41/23121/2
*RC : Remote Controller
Table 2-3-2 The equivalent power supply capability index of Trans.Booster, Power supply unit, Connector TB3, TB7 of Outdoor unit.
Transmission Booster
PAC-SF46EPA
25
*If PAC-SC51KUA is used to supply power at TB7 side, no power supply need from Outdoor unit at TB7, Connector TB3 itself will therefore have 32.
Not applicable to the PUMY model.
Power supply unit
PAC-SC51KUA
With the equivalent power consumption values in Table 2-3-1 and Table 2-3-2, PAC-SF46EPA can be designed into the airconditioner system to ensure proper system communication according to 2-3-2-A, B, C.
2-3-2-A) Firstly, count from TB3 at TB3 side the total quantity of Indoor units and ME remote controller, Timers and System
controllers.If the total quantity reaches 40, a PAC-SF46EPA should be set.In this case, Indoor unit sized P72, 96 is
counted as 7 Indoor units, but MA remote controller(s), LOSSNAY is NOT counted.
2-3-2-B) Secondly, count from TB7 side to TB3 side the total transmission power consumption index. If the total power consumption
reaches 32, a PAC-SF46EPA should be set.Yet, if a PAC-SC51KUA is used to supply power at TB7 side, count from
index TB3 side only.
2-3-2-C) Thirdly, count from TB7 at TB7 side the total transmission power consumption index, If the total power consumption reaches
6, a PAC-SF46EPA should be set.
System example
2
5
MA RC.LOSSNAY
PAR-21MAA
PAC-YT51CRB
PAR-FA32MA
LGH-RX-E
PZ-41SLB
BM ADAPTER
BAC-HD150
ME Remote Contr.Timers, System Contr.ON/OFF ContrMN Converter.
PAR-F27MEA
PZ-52SF
PAC-SF44SRA
PAC-YT34STA
AG-150A
TC-24A
PAC-YT40ANRA CMS
GB-24A
4
System Controller
GB-50ADA
6
6
Outdoor unit
Connector TB3 and TB7 total *
32
-MNF-B
Outdoor unit
Connector TB7 only
6
CMS
-MNG-E
Power supply unit
PAC-SC51KUA
H2iSD-8
TB7TB3
ME remote
TB7TB3
Outdoor unit
M-NET
24VDC
CENTRALIZED CONTROLLER AG-150A
Centralized controller
(AG-150A)
Transmission booster (No.2) should be used,
if the total equivalent transmission power consumption reaches 5.
controller
Transmission booster (No.1) should be used,
if the total quantity of Indoor units and ME remote controllers
reaches 40, (Indoor unit sized P72, 96 is counted as 7);
or if the total equivalent transmission power consumption reaches 32.
LOSSNAY
unit
PZ-52SF
N3
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
N1
0201
UP
TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA
220-240V:0.7A ~/N
POWER RATING
50
3.4kgWEIGHT
MADE IN JAPAN
Transmission
booster
PAC-SF46EPA
(No.2)
LOSSNAY
unit
PZ-52SF
Within N4, the total equivalent transmission
power consumption should not exceed 25.
N4
UP
TRANSMISSION BOOSTER
MODEL
PAC-SF46EPA
220-240V:0.7A ~/N
POWER RATING
50
3.4kgWEIGHT
MADE IN JAPAN
Transmission
booster
(No.1)
ME remote
controller
Within N2, conditions 1,2 should be followed.
1.The total quantity of Indoor units and ME remote controller
should not exceed 40.
*Indoor unit sized P72, 96 is counted as 7 units.
2.The total equivalent transmission power consumption
should not exceed 25.
N2
2. M-NET CONTROL
The power to System controller (excluding LMAP03-U) is supplied via M-NET transmission line. M-NET transmission line
at TB7 side is called Central control transmission line while one at TB3 side is called Indoor-Outdoor transmission line.
There are 3 ways to supply power to the System controller .
A) Connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
B) Connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
C) Connecting to TB7 of the Outdoor unit but receiving power from power supply unit PAC-SC51KUA.
Maximum 3 System controllers can be connected to TB3.
If there is more than 1 Outdoor unit, it is necessary to
replace power supply switch connector CN41 with CN40
on one Outdoor unit.
Maximum 3 System controllers can be connected to TB7
and receiving power from the Outdoor unit.
It is necessary to replace power supply switch connector
CN41 with CN40 on one Outdoor unit.
2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit.
2-3-3-B. When connecting to TB7 of the Outdoor unit and receiving power from the Outdoor unit.
2-3-3-C. When connecting to TB7 of the Outdoor unit but receiving power from PAC-SC51KUA.
2-3-3. Ensuring proper power supply to System controller
Outdoor unit
MA remote controller
GroupGroup
Indoor unit
M-NET transmission lines
(transmission lines
for central controller)
When using PAC-SC51KUA to supply transmission
power, the power supply connector CN41 on the Outdoor
units should be kept as it is. It is also a factory setting.
1 PAC-SC51KUA supports maximum 1 AG-150A unit
due to the limited power 24VDC at its TB3.
However, 1 PAC-SC51KUA supplies transmission power
at its TB2 equal to 5 Indoor units, which is referable at
Table 2-3-2.
If PZ-52SF, Timers, System controller, ON/OFF controller
connected to TB7 consume transmission power more
than 5 (Indoor units), Transmission booster
PAC-SF46EPA is needed. PAC-SF46EPA supplies
transmission power equal to 25 Indoor units.
AG-150A*1 is recommended to connect to TB7 because it performs back-up to a number of data.
In an air conditioner system has more than 1 Outdoor units, AG-150A receiving transmission power through TB3 or TB7 on one of the Outdoor units would
have a risk that the connected Outdoor unit failure would stop power supply to AG-150A and disrupt the whole system.
When applying apportioned electric power function, AG-150A is necessary to connected to TB7 and has its own power supply unit PAC-SC51KUA.
Note: Power supply unit PAC-SC51KUA is for AG-150A.
*1: AG-150A is an example model of system controllers.
SYSTEM DESIGN
Y-SERIES
2010 H2i
®
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
H2iSD-9
2. M-NET CONTROL
2-3-4. Power supply to LM adapter LMAP03U
1-phase 208-230V AC power supply is needed.
®
The power supply unit PAC-SC51KUA is not necessary when connecting only the LMAP03U. Yet, make sure to change
the power supply changeover connector CN41 to CN40 on the LM adapter.
2-3-5.
Y-SERIES
2010 H2i
SYSTEM DESIGN
2-3-6.
Power supply to BM ADAPTER
1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.
Yet, make sure to move the power jumper from CN41 to CN40 on the BM ADAPTER.
Power supply to GB-50ADA-A
1-phase 100-240VAC power supply is needed.
The power supply unit PAC-SC51KUA is not necessary.
GB-50ADA-A supplies power through TB3, which equals 6 indoor units. (refer to Table 2-3-2)
H2iSD-10
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
2. M-NET CONTROL
Branch
No. setting
Unit address No. setting
Rotary switch
In order to constitute CITY MULTI in a complete system, switch
operation for setting the unit address No. and connection No. is
required.
À Address No. of outdoor unit, indoor unit and remote controller.
The address No. is set at the address setting board.
In the case of R2 system, it is necessary to set the same No. at the
branch No. switch of indoor unit as that of the BC controller
connected. (When connecting two or more branches, use the lowest
branch No.)
Á Caution for switch operations
 MA remote controller
¥ Be sure to shut off power source before switch setting. If operated with power source on, switch can
not operate properly.
¥ When connecting only one remote controller to one group, it is always the main remote controller.
When connecting two remote controllers to one group, set one remote controller as the main remote controller
and the other as the sub remote controller.
¥ No units with identical unit address shall exist in one whole air conditioner system. If set erroneously,
the system can not operate.
¥ The factory setting is Main .
2-4-1. Switch operation
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
PAR-21MAA
The MA remote controller does not have the switches listed above.
Refer to the installation manual for the function setting.
Setting the dip switches
There are switches on the front of the remote controller. Remote controller Main/Sub and other function settings
are performed using these switches. Ordinarily, only change the Main/Sub setting of SW1.
(The factory settings are all “ON”.)
SW No
1
2
3
SW contents Main
Remote controller
Main/Sub setting
Temperature display
units setting
Cooling/heating display in AUTO mode
ON
Main
Celsius
Yes
OFF
Sub
Fahrenheit
No
Comment
Set one of the two remote controllers at one group to “Main”
When the temperature is displayed in [Fahrenheit], set to “No”.
When you do not want to display “Cooling” and “Heating” in the
Auto mode, set to “No”.
PAC-YT51CRB
4
Intake temperature
display
YesNo
When you do not want to display the intake temperature, set to
“No”.
2-4. Address Setting
SYSTEM DESIGN
Y-SERIES
2010 H2i
®
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
H2iSD-11
2. M-NET CONTROL
2-4-2. Rule of setting address
Unit
Indoor unit
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Address setting
01 ~ 50
52 ~ 99, 100
101 ~ 150
151 ~ 199, 200
NoteExample
The address of outdoor unit + 1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
System remote
controller
ON/OFF remote
controller
000, 201 ~ 250
000, 201 ~ 250
Local remote controller
System controller
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
101
101
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101
101
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101
101100
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101100
LMAP03U
201 ~ 250
1
1
Fixed
Fixed
Group remote
controller
201 ~ 250
The smallest group No. to be managed + 200
For TC-24A, the address is set on the screen.
101
2
Fixed
2
Fixed
Outdoor unit
BC controller
(Main)
52 ~ 99, 100
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
101
BC controller
(Sub)
51 ~ 99, 100
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC and OS are
automatically detected. (Note 2)
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1)
Indoor unit to be connected to the BC controller (Main)
(2)
Indoor unit to be connected to the BC controller (No.1 Sub)
(3)
Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
101
(Note1)
The smallest group No. to be managed is changeable.
The smallest group No. to be managed + 200
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC and OS in one refrigerant circuit system are automatically detected.
OC and OS are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
AG-150A
GB-50ADA
GB-24A
000, 201 ~ 250
101100
00 0
PAC-YG50ECA
000, 201 ~ 250
101100
BAC-HD150
000, 201 ~ 250
101100
Settings are made on the initial screen of AG-150A.
Settings are made with setting tool of BM ADAPTER.
00 0
00 0
®
Y-SERIES
2010 H2i
SYSTEM DESIGN
H2iSD-12
2010 Hyper-heating Y-SERIES SYSTEM DESIGN (Sept. 2010)
Loading...
+ 26 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.