─ 14 ─
(2) Troubleshooting 2: An error code is displayed on the remote controller.
See below for possible remedies when there is an error during test operation and
CHECK
followed by a 4-digit
number is displayed on the remote controller.
Note: The components marked with * are available for GUF-50/100RDH4 types only.
Error code
Error content Cause Remedy
0900 Test run Is the test operation switch of either the
fan, bypass damper, or humidifier solenoid valve* turned ON?
Set the test operation switch (SW1-1, 7,
8*) to OFF.
2600 Drain error Drain water is not properly discharged. The body must be levelly installed.
The drain pipe must be installed with a
gradient of more than 1/100.
Is there a leak from the permeable-film
humidifier*?
• Fix the water leak.
• Replace the humidifier element*.
When no problem is found after checking the above items.
Replace the circuit board.
2601 Disconnected
water sensor connector
Is the CN4D connector firmly connected?
Firmly connect the connector.
Is the relay connector between the
circuit board and water sensor firmly
connected?
Firmly connect the connector.
When no problem is found after checking the above item.
Replace the circuit board.
3602 Damper motor
error
Is the CNL connector firmly connected? Firmly connect the connector.
Is the connector of the damper motor
section firmly connected?
Firmly connect the connector.
Does the damper operate when the
damper motor is running?
Replace the damper motor if it is not work-
ing.
When no problem is found after checking the above items.
Replace the circuit board.
4116 Fan motor error The motor continues to run when the
operation is stopped.
Replace the circuit board.
5101 Indoor temperature
sensor error
• Are the connectors of each thermistor
firmly connected?
• Is each relay connector firmly con-
nected?
• When no problem is found after
checking the above item.
• Firmly connect each connector.
• Firmly connect each connector.
• Replace the circuit board.
5102 Liquid pipe temper-
ature sensor error
5103 Gas pipe tempera-
ture sensor error
5104 Outdoor tempera-
ture sensor error
6600 Indoor unit address
setting error
There are duplicate address settings,
meaning there are indoor units with the
same address.
Check the addresses of devices in the
system.
6602 Communication
error (Transmission
processor H/W
error)
Any of the transmission cables of the
indoor units, Fresh Master, or outdoor
units was wired, or the polarity was
changed with the power ON.
Simultaneously turn OFF the power of the
indoor units, Fresh Master, and the outdoor
units, and then, turn them ON again.
Specified power supply is not used. Check the power supply.
Earth fault in the transmission cable Check the transmission cable wiring and
shielding.
The setting of the outdoor unit is incorrect.
See the service manual of the outdoor unit.
Transmission data was changed due to
noise in the transmission cable line.
Inspect the transmission waveform and
noise in the transmission cable line.
Malfunction of a controller for the device
in which the error occurs.
If the controller is normal, it is a malfunc-
tion of the circuit board.