Mitsubishi FX3UC-32MT/DSS, FX2NC-32EX-DS, FX3UC-64MT/DSS, FX2NC-16EX-DS, FX2NC-16EYT-DSS Hardware Manual

...
FX3UC (D, DS, DSS) SERIES
Side
B
Side
A
Side
B
JAPANESE ENGLISH
JY997D50501E
PROGRAMMABLE CONTROLLERS
HARDWARE MANUAL
Manual Number JY997D50501
Revision E
Date December 2017
This manual describes the part names, dimensions, mounting, cabling and specifications for the product. This manual is extracted from FX3UC (D,DS,DSS) Series User's Manual - Hardware Edition. Refer to FX3UC Series User's Manual - Hardware Edition details. Before use, read this manual and manuals of relevant products fully to acquire proficiency in the handling and operating the produ ct. Make sure to learn all the product information, safety information, and precautions. And, store this manual in a safe place so that it can be taken out and read whenever necessary. Always forward it to the end user. Registration The company name and the product name to be described in this manual are the registered trad emarks or trademarks of each company.
Effective December 2017 Specifications are subject to change without notice.

Safety Precaution

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
This manual classifies the safety precautions into two categories:
and .
Depending on the cir cumstances, procedures indicated by
It is important to follow all precautions for personal safety.
STARTUP AND MAINTENANCE PRECAUTIONS
Do not touch any terminal while the PLC's power is on.
Before cleaning or retightening terminals, cut off all phases of
may also cause severe injury.
Doing so may cause electric shock or malfunctions.
the power supply externally. Failure to do so may cause electric shock.
© 2013 Mitsubishi Electric Corporation
(Read these precautions before use.)
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight personal injury or physical damage.
STARTUP AND MAINTENANCE PRECAUTIONS
Before modifying or disr upting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.
Do not change the program in the PLC from two or more peripheral equipment devices at the same time. (i.e. from a programming tool and a GOT) Doing so may cause destruction or malfunction of the PLC program.
Use the battery for memory backup correctly in FX3UC Series User's Manual - Hardware Edition.
- Use the battery only for the specified purpose.
- Connect the battery correctly.
- Do not charge, disassemble, heat, put in fire, short-circuit,
connect reversely, weld, swallow or burn the battery, or apply excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or
expose to direct sunlight.
- Do not expose to water, bring near fire or touch liquid
leakage or other contents directly.
- Incorrect handling of the battery may cause heat excessive
generation, bursting, ignition, liquid leakage or deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment.
- When replacing the battery, make sure to use our specified
product (FX3U-32BL).
- When a battery error occurs ("BAT" LED is lit in red), follow the
description in FX
STARTUP AND MAINTENANCE PRECAUTIONS
Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is attached or detached while the PLC's power is on, the data in the memory may be destroyed, or the memory cassette may be damaged.
Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions. For repair, contact your local Mitsubishi Electric representative.
Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause equipment failures or malfunctions.
- Peripheral devices, extension units/blocks, connector
conversion adapter, extension power supply units, special adapters, and FX Series terminal blocks.
- Battery and memory cassettes
Do not use the chemicals for cleaning.
If there is the possibility of touching the PLC inside a control
panel in maintenance, make sure to discharge to avoid the influence of static electricity.
DISPOSAL PRECAUTIONS
Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of your device. When disposing of batteries, separate them from other waste according to local regulations. (For details of the Battery Directive in EU countries, refer to FX3UC Series User's Manual - Hardware Edition.)
TRANSPORTATION AND STORAGE PRECAUTIONS
Before transporting the PLC, turn on the power to the PLC to check that the BAT LED is off, and check the battery life. If the PLC is transported with the BAT LED on or the battery exhausted, the battery-backed data may be unstable during transportation.
3UC
Series User's Manual - Hardware Edition.
TRANSPORTATION AND STORAGE PRECAUTIONS
The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in Section 2.1 by using dedicated packaging boxes and shock-absorbing palettes. Failure to do so may cause failures in the PLC. After transportation, verify operation of the PLC and check for damage of the mounting part, etc.
When transporting lithium batteries, follow required transportation regulations. (For details of the regulated products, refer to FX3UC Series User's Manual - Hardware Edition.)

Associated manuals

How to obtain manuals
For the necessary product manuals or documents, consult with your local Mitsubishi Electric representative.
Associated manuals
FX3UC (D, DS, DSS) Series PLC (main unit) comes with this document (hardware manu al). For a detailed explanation of the FX3UC Series hardware and information on instructions for PLC programming and special extension unit/block, refer to the relevant documents.
Manual name Manual No. Description
FX3UC Series User's Manual
- Hardware Edition
FX3S/FX3G/FX3GC/ FX3U/FX3UC Series Programming Manual
- Basic & Applied
Instruction Edition
MELSEC-Q/L/F Structured Programming Manual (Fundamentals)
FXCPU Structured Programming Manual [Device & Common]
FXCPU Structured Programming Manual [Basic & Applied Instruction]
FXCPU Structured Programming Manual [Application Functions]
FX Series User’s Manual - Data Communication Edition
3S/FX3G/FX3GC/
FX FX
3U/FX3UC Series
User's Manual
- Analog Control
Edition
3S/FX3G/FX3GC/
FX FX
3U/FX3UC Series
User's Manual
- Positioning Control
Edition
JY997D28701
MODEL CODE:
09R519
JY997D16601
MODEL CODE:
09R517
SH-080782
MODEL CODE:
13JW06
JY997D26001
MODEL CODE:
09R925
JY997D34701
MODEL CODE:
09R926
JY997D34801
MODEL CODE:
09R927
JY997D16901
MODEL CODE:
09R715
JY997D16701
MODEL CODE:
09R619
JY997D16801
MODEL CODE:
09R620
Explains FX3UC Series PLC specification details for I/O, wiring, installation, and maintenance.
Describes PLC programming for basic/ applied instructions STL/ SFC programming and devices.
Programming methods, specifications, functions, etc. required to create structured programs.
Devices, parameters, etc. provided in structured projects of GX Works2.
Sequence instructions provided in structured projects of GX Works2.
Application functions provided in structured projects of GX Works2.
Explains N:N link, parallel link, computer link, no protocol communication by RS instructions/FX2N- 232IF.
Describes specifications for analog control and programming methods for FX3S/FX3G/FX FX
3UC
Explains the specifications for positioning control of FX3S/FX3G/FX FX
3UC
programming procedures
3GC
Series PLC.
3GC
Series and
/FX3U/
/FX3U/

Certification of UL, cUL standards

FX3UC series main units, FX3U series special adapter, extension power supply unit and FX2N/FX2NC series input/output extension blocks supporting UL, cUL standards are as follows:
UL, cUL file number: E95239 Models: MELSEC FX3U(C) series manufactured
Models: MELSEC FX2NC series manufactured
Models: MELSEC FX2N series manufactured
FX3UC-MT/D FX3UC-MT/DSS Where  indicates: 16, 32, 64, 96 FX3UC-16MR/D-T FX3UC-16MR/DS-T FX3U-232ADP(-MB) FX3U-485ADP(-MB) FX3U-CF-ADP FX3U-ENET-ADP FX3U-4AD-ADP FX3U-4DA-ADP FX3U-3A-ADP FX3U-4AD-PT-ADP FX3U-4AD-PTW-ADP FX3U-4AD-PNK-ADP FX3U-4AD-TC-ADP FX3UC-1PS-5V
FX2NC-16EX(-DS) FX2NC-32EX(-DS) FX2NC-16EYT(-DSS) FX2NC-32EYT(-DSS) FX2NC-16EX-T(-DS) FX2NC-16EYR-T(-DS)
FX2N-8ER-ES/UL FX2N-8EX-ES/UL FX2N-8EYR-ES/UL FX2N-8EYR-S-ES/UL FX2N-8EYT-ESS/UL FX2N-8EX-UA1/UL FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL FX2N-16EYS

Compliance with EC directive (CE Marking)

This product complies with EC directive, however, this document does not guarantee that a mechanical system including this product will comply with EC directive. Compliance to EMC directive and LVD directive of the entire mechanical system should be checked by the user / manufacturer. For more details please contact the local Mitsubishi Electric sales site.

Caution for Compliance with EC directive

Please use the FX3UC (D, DS, DSS) Series programmable controllers while installed in conductive shielded control panels under a general industrial environment.
Programmable controllers are open-type devices that must be installed and used within conductive control panels. Please secure the control panel lid to the control panel (for conduction). Installation within a control panel greatly affects the safety of the system and aids in shielding noise from the programmable controller.
For the control panel, use the product having sufficient strength, fire protectiveness and shielding property to an installation environment.
24 V DC of the power supply must be supplied from the circuit double/reinforced insulated from the main power supply (MAINS).
Caution for compliance with the LVD directive (EN61010-2-201:2013) (*1)
To an external connection port other than AC power supply terminal and AC input/output terminal, connect the circuit separated from a dangerous voltage by a double/reinforced insulation.
Between the commons having the adjacent relay output terminals, if an external power supply is higher than 120 V AC, the insulation is basic. Therefore, when using 120 V AC or higher external power supply and 30 V DC/AC or lower external power supply between the adjacent commons, do not handle 30 V DC/ AC or lower external power supply as a touchable part, (When handling 30 V DC/AC or lower external power supply as a touchable part, add a basic insulation.)
For crimp terminals to be used for the wiring applied with 30 V AC
Front panel
[6]
[8]
[10]
[6]
[6]
[4]
[2]
[9]
[7]
[11]
[5]
[2]
[12]
[14]
[6]
[4]
[15]
[2]
Under side
[5] Display LED
[4]
[13]
[16]
[6]
[6]
[3]
[2]
[4]
[1]
[2]
Green Green
Red Red
Left side Right side
90(3.54")
W
Unit: mm(inches)
74(2.91")
(13)
(0.52")
90(3.54")
Unit: mm(inches)
74(2.92")W
15
(0.60")
W
Unit: mm(inches)
90
74(2.91")
15
(0.60")
or higher, use the products with insulating sleeves.
Cutoff device such as a breaker or a circuit protector should be installed in accordance with the following precautions.
- Use EN60947-1 or EN60947-3 standards.
- Place the cutoff device so that it can be operated easily.
- Specify that the cutoff device is for this equipment.
(*1) For the time of compliance with the LVD directive (EN61010-
2-201:2013), refer to FX3UC Series User's Manual - Hardware Edition.
Caution for Analog Products in use
The analog special adapters have been found to be compliant to the European standards in the aforesaid manual and directive. However, for the very best performance from what are in fact delicate measuring and controlled output device M itsubishi Electric would like to make the following points; As analog devices are sensitive by nature, their use should be considered carefully. For users of proprietary cables (integral with sensors or actuators), these users should follow the manufacturers’ installation requirements. Mitsubishi Electric recommends that shielded cables be used. If no other EMC protection is provided, then users may experience temporary loss of accuracy between +10 %/-10 % in very heavy industrial areas. However, Mitsubishi Electric suggests that when adequate EMC precautions are followed with general good EMC practice for the users complete control system.
- Sensitive analog cables should not be laid next to or bound with
high voltage cabling. Where possible, users should run analog cables separately.
- Good cable shielding should be used. When grounding the
shield - ensure that no loops are accidentally created.
- When reading analog values, EMC induced errors can be
smoothed out by averaging the readings. This can be achieved either through functions on the analog special adapter/block or through the user’s program in the FX3UC Series PLC main unit.

Incorporated Items

Verify that the following product and items are included in the package.
Included Items
Main units
FX3UC-MT/D FX3UC-16MR/D-T
FX3UC-MT/DSS FX3UC-16MR/DS-T
Input/output extension blocks
FX2NC-EX FX2NC-16EX-T
FX2NC-EX-DS
2NC-16EX-T-DS
FX FX2NC-EYT FX
2NC-EYT-DSS 2NC-16EYR-T
FX FX2NC-16EYR-T-DS
Product 1 unit
FX2NC-100MPCB [1 m (3’ 3"), three wire]
FX2NC-100BPCB [1 m (3’ 3"), two wire]
Manuals [Japanese/English]
Product 1 unit
FX2NC-100MPCB [1 m (3’ 3"), three wire]
Manuals [Japanese/English]
Product 1 unit
FX2NC-10BPCB1 [0.1 m (3.93"), double-ended]
Product 1 unit
1 cable
1 cable
1 manual
1 cable
1 manual
1 cable

1. Outline

1.1 Part names

No. Name
[1] Memory cassette dummy cover
[2] Special adapter connecting hooks
[3] Special adapter connector cover
[4] DIN rail mounting hooks
POW LED On while power is on the PLC.
RUN LED On while the PLC is running.
[5]
BAT LED Lights when the battery voltage drops.
ERR LED
[6] FX2NC/FX3UC Extension block connecting hooks
[7] Input LED
[8] Output LED
[9] Input connector (-T indicates terminal block type)
[10] Output connector (-T indicates terminal block type)
[11] Peripheral device connecting connector (RS-422)
[12] RUN/STOP switch
[13] FX2NC/FX3UC Extension block connecting connector cover
[14] Power connector for main unit
[15] Battery cover
Nameplate printing
[16]
is a mark that instructs to use the cable with an
appropriate temperature ratin g (80°C or more) for wiring.
Flashing when a program error occurs.
Lights when a CPU error occurs.

1.2 External dimensions/weight

Main units (Connector type)
Main units (Terminal block type)
FX2NC input/output extension blocks (Connector type)
Unit: mm(inches)
90(3.54")
(13)
W
(0.52")
FX2NC input/output extension blocks (Terminal block type)
Type Model name
FX3UC-16MT/D(SS)
Main units (Connector type)
Main units (Terminal block type)
FX3UC-32MT/D(SS)
FX3UC-64MT/D(SS)
FX3UC-96MT/D(SS)
FX
74(2.91")
3UC-16MR/D(S)-T
W: mm
(inches)
34.0
(1.34)
34.0
(1.34)
59.7
(2.36)
85.4
(3.37)
34.0
(1.34)
MASS (Weight)
kg (lbs)
Approx. 0.2
(0.44)
Approx. 0.2
(0.44)
Approx. 0.3
(0.66)
Approx. 0.35
(0.77)
Approx. 0.25
(0.55)
Type Model name
FX2NC-16EX(-DS)
Input/output extension blocks (Connector type)
Input/output extension blocks (Terminal block type)
FX2NC-32EX(-DS)
FX2NC-16EYT(-DSS)
FX2NC-32EYT(-DSS)
FX2NC-16EX-T(-DS)
FX2NC-16EYR-T(-DS)

2. General specifications and Installation

For more details, refer to the FX3UC Series User's Manual -
INSTALLATION PRECAUTIONS
Make sure to cut off all phases of the power supply externally before attempting installation or wiring work. Failure to do so may cause electric shock or damage to the product.
INSTALLATION PRECAUTIONS
Use the product within the generic environment specifications described in section 2.1 of this manua l. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S, SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
Do not touch the conductive parts of the product directly. Doing so may cause device failures or malfunctions.
Install the product securely using a DIN rail or mounting screws.
Install the product on a flat surface. If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities.
When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.
Be sure to remove the dust proof sheet from the PLC's ventilation port when installation work is completed. Failure to do so may cause fire, equipment failures or
:
malfunctions.
Connect the extension cables, peripheral device cables, input/ output cables and battery connecting cable securely to their designated connectors. Loose connections may cause malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices. Failure to do so may cause device failures or malfunctions.
- Peripheral devices, extension units/blocks, connector
conversion adapter, extension power supply units, special adapters, and FX Series terminal blocks
- Battery and memory cassettes
W: mm
(inches)
14.6
(0.57)
26.2
(1.03)
14.6
(0.57)
26.2
(1.03)
20.2
(0.57)
24.2
(0.95)
MASS (Weight)
kg (lbs)
Approx. 0.15
(0.33)
Approx. 0.2
(0.44)
Approx. 0.15
(0.33)
Approx. 0.2
(0.44)
Approx. 0.15
(0.33)
Approx. 0.2
(0.44)
Hardware Edition
:
Notes
Configuration without extension cable
FX3UC
Main unit
FX
2NC-16EXFX2NC-16EYT
50 mm (1.97")
A
A
A
A
A
A
2
B
B
4
A
B
C
Main unit
Input extension block
Input extension block
Output extension block
3 Ground
(Green)
1 (Red)
Main unit
2 (Black)
1 (Red) 2 (Black)
The figure below shows the pin numbers of the power connectors.
Two power connectors of each extension block are connected in parallel inside the block. Accordingly, there is no discrimination between the entrance side and the exit side of the power supply. Either (upper or lower) connector can be connected. At shipment from the factory, a resin cover is attached to the lower connector. Connect the upper connector first. Remove the resin cover from the lower connector when performing crossover wiring for the later block. (In case of the FX2NC-EX(-T)-DS, removal of the connector cover is unnecessary.)
Black
Black
Red
Red
Green Ground
Extension block
When a dust proof sheet is supp lied with an extension unit/ block, keep the sheet applied to the ventilation slits during installation and wiring work.
To prevent temperature rise, do not install the PLC on a floor, a ceiling or a vertical surface. Install it horizontally on a wall as shown in section 2.2.
Keep a space of 50 mm (1.97”) or more between the unit main body and another device or structure (section 2.2 part A). Install the unit as far away as possible from high-voltage lines, high­voltage devices and power equipment. Failure to do so may cause fire, equipment failur es or malfunctions.

2.1 Generic specifications [Main unit]

Item Specification
Ambient temperature
Ambient humidity
Vibration resistance (*1)
Shock resistanc (*1)
Noise resistance
Dielectric withstand voltage
Insulation resistance
Grounding
Working atmosphere
Working altitude
Installation location
Overvoltage category
Pollution degree
(*1) The criterion is shown in IEC61131-2.
2) For common grounding, refer to section 3.2.
(
*
(*3) The PLC cannot be used at a pressure higher than the
(
4) The programmable controller is assumed to be installed in an
*
0 to 55 °C (32 to 131 °F) when operating and -25 to 75 °C (-13 to 167 °F) when stored
5 to 95 %RH (no condensation) when operating
Accel-
Fre-
eration
quency
(Hz)
(m/s2)
When
10 to 57 - 0.035 installed on DIN rail
(147 m/s2 Acceleration, Action time: 11 ms, 3 times by half-sine pulse in each direction X, Y, and Z)
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1 μs, rise time of 1ns and period of 30 to 100 Hz
500 V AC for one minute
5 M or higher by 500 V DC insulation resistance tester
Class D grounding (grounding resistance: 100 Ω or less) <Common grounding with a heavy electrical system is not allowed.> (*2)
Free from corrosive or flammable gas and excessive conductive dusts
<2000 m (*3)
Inside a control panel (*4)
ΙΙ or less
2 or less
atmospheric pressure to avoid damage.
environment equivalent to indoor.
57 to
4.9 -
150
Between batch of all terminals and ground terminal
Half
ampli-
tude
(mm)
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)

2.2 Installation Location

Install the PLC in an environment conforming to the generic specifications (section 2.1), installation precauti ons and notes.
For more details, refer to FX3UC Series User's Manual -
Installation location in enclosure
Space in enclosure
Extension devices can be connected on the left and right sides of the PLC main unit. If you intend to add extension devices in the future, keep extra space on the left and right sides open.
Configuration with extension cable
A
A
equipment
A
-4AD-ADP
3U
FX
FX3UC
A
FX2N-10PG
Other
equipment
Main unit
A
A
2NC-16EX
FX
FX0N-65EC FX0N-30EC
equipment
A
Other
FX2N-CNV-BC
A
-CNV-IF
2NC
FX
Other
50 mm
(1.97")
Hardware Edition.

2.3 Procedures for installing to and detaching from DIN rail

The main unit can be installed on a DIN46277 rail [35 mm (1.38”) wide]. For detail, refer to the following manual.
Refer to FX3UC Series User's Manual - Hardware Edition.

2.3.1 Installing methods

1) Turn the power supply OFF.
2) Push the DIN rail mounting hooks
of all connected units/blocks as
shown in the figure on the right .
1
A
3) Align the upper side of the DIN
rail mounting groove with the DIN rail ( in the figure on the right).
4) While pressing the main unit
onto the DIN rail, lock the DIN rail mounting hooks as shown in the figure below .
1

2.3.2 Removal methods

1) Turn the power supply OFF.
2) Disconnect all connected
cables including the power cable and I/O cable.
3) Insert a flathead screwdriver to
the DIN rail mounting hook ( in the figure on the right).
4) Lever the screwdriver slightly
toward direction , to pull out the DIN rail mounting hooks, allowing them to come off the
DIN rail.
5) Remove the main unit from the
DIN rail ( in the figure on the right).
6) Push the DIN rail mounting
hooks as shown in the figure on the right .
3
2
1

2.4 Connection of power supply connector

Use the dedicated built-in power connector to supply power to the main unit.
The power should be supplied to the main unit, FX2NC Series I/O extension blocks and FX2NC/FX3UC Series special extension blocks. Some (FX2NC-EX(-T)) of FX2NC Series I/O extension blocks require power cable types B and C shown on the right, while others (FX2NC-EX(-T)-DS) do not require them. For details, refer to FX3UC Series User's Manual - Hardware Edition.
When connecting two or more extension blocks which require power cables "B" and "C" shown on the right, perform crossover wiring between the extension blocks using two (upper and lower) power connectors.