Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories: and .
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe
injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight
personal injury or physical damage.
Depending on the circumstances, procedures indicated by may also cause severe injury. It is
important to follow all precautions for personal safety. Store this manual in a safe place so that it can be taken
out and read whenever necessary. Always forward it to the end user.
1. DESIGN PRECAUTIONS
Reference
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs
are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control
block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the PLC
are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
98
121
139
172
186
224
245
284
352
Reference
98
121
139
172
186
224
245
284
352
(1)
Safety Precautions
(Read these precautions before use.)
2. INSTALLATION PRECAUTIONS
Reference
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Use the product within the generic environment specifications described in section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S,
SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
• Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
• Install the product securely using a DIN rail or mounting screws.
Terminal blockDIN rail only
Main unit, FX2N Series I/O extension unit/block, FX2N/FX3U Series special
function block, and special adapter
• Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities.
• Make sure to affix the expansion board with tapping screws.
Tightening torque should follow the specifications in the manual.
Loose connections may cause malfunctions.
• When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Be sure to remove the dust proof sheet from the PLC’s ventilation port when installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
• Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely
to their designated connectors.
Loose connections may cause malfunctions.
• Connect the display module, memory cassette, and expansion board securely to their designated connectors.
Loose connections may cause malfunctions.
• Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause device failures or malfunctions.
- Peripheral devices, display modules, expansion boards and special adapters
- Extension units/blocks and FX Series terminal blocks
- Battery and memory cassette
• Connect the memory cassette securely to the appropriate connector.
Loose connections may cause malfunctions.
Installing the cassette in a raised or tilted posture can also cause malfunctions.
DIN rail or direct mounting
98
352
Reference
99
353
3. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
(2)
Reference
99
121
139
172
186
224
245
353
Safety Precautions
(Read these precautions before use.)
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension
units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to section 9.3).
• Connect the AC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX3G Series main unit and FX2N/FX3U Series extension equipment in accordance
with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24”) or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24”) or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
• Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
• Before cleaning or retightening terminals, cut off all phases of the power supply externally.
Failure to do so may cause electric shock.
• Use the battery for memory backup correctly in conformance to this manual.
- Use the battery only for the specified purpose.
- Connect the battery correctly.
- Do not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or burn the battery,
or apply excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or expose to direct sunlight.
- Do not expose to water, bring near fire or touch liquid leakage or other contents directly.
- Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or
deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment.
• Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and
the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
• Do not change the program in the PLC from two or more peripheral equipment devices at the same time. (i.e. from
a programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.
Reference
199
307
385
(3)
Safety Precautions
(Read these precautions before use.)
• Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is
attached or detached while the PLC’s power is on, the data in the memory may be destroyed, or the memory
cassette may be damaged.
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
• Turn off the power to the PLC before connecting or disconnecting any extension cable.
Failure to do so may cause equipment failures or malfunctions.
• Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- Peripheral devices, display module, expansion boards, and special adapters
- Extension units/blocks and FX Series terminal blocks
- Battery and memory cassette
5. DISPOSAL PRECAUTIONS
• Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of
your device.
When disposing of batteries, separate them from other waste according to local regulations.
(For details of the Battery Directive in EU countries, refer to Appendix E)
Reference
199
307
375
385
Reference
199
6. TRANSPORTATION AND STORAGE PRECAUTIONS
• When transporting the FX3G Series PLC incorporating the optional battery, turn on the PLC before shipment,
confirm that the battery mode is set using a parameter and the ALM LED is OFF, and check the battery life.
If the PLC is transported with the ALM LED on or the battery exhausted, the battery-backed data may be unstable
during transportation.
• The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in the general
specifications (section 4.1). Failure to do so may cause failures in the PLC.
After transportation, verify the operations of the PLC.
• When transporting lithium batteries, follow required transportation regulations.
(For details of the regulated products, refer to Appendix D)
Reference
199
385
(4)
FX3G Series Programmable Controllers
User’s Manual - Hardware Edition
FX3G Series Programmable Controllers
User's Manual [Hardware Edition]
Manual numberJY997D31301
Manual revisionJ
Date9/2013
Foreword
This manual contains text, diagrams and explanations which will guide the reader in the correct installation,
safe use and operation of the FX
before attempting to install or use the unit.
And, store this manual in a safe place so that you can take it out and read it whenever necessary. Always
forward it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi
Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of
using the contents noted in this manual.
3G Series Programmable Controllers and should be read and understood
1
FX3G Series Programmable Controllers
User’s Manual - Hardware Edition
Outline Precautions
• This manual provides information for the use of the FX3G Series Programmable Controllers. The manual
has been written to be used by trained and competent personnel. The definition of such a person or
persons is as follows;
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all
associated documentation for the said product. All maintenance should be carried out in accordance
with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices. The operators should also be
familiar with documentation which is connected with the actual operation of the completed equipment.
Note: The term 'completed equipment' refers to a third party constructed device which contains or uses
the product associated with this manual
• This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
• When combining this product with other products, please confirm the standard and the code, or regulations
with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
machine, and apparatus with which a user is using.
• If in doubt at any stage during the installation of the product, always consult a professional electrical
engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
use, please consult the nearest Mitsubishi Electric representative.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you
have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric
representative.
Registration
•Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
• Ethernet is a trademark of Xerox Corporation.
®
•MODBUS
• Phillips is a registered trademark of Phillips Screw Company.
• The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.
is a registered trademark of Schneider Electric SA.
Certification of UL, cUL standards ....................................................................................................... 14
Compliance with EC directive (CE Marking) ........................................................................................ 14
Requirement for Compliance with EMC directive................................................................... 14
Requirement for Compliance with LVD directive.................................................................... 17
Caution for compliance with EC Directive .............................................................................. 18
1. Introduction19
1.1 Introduction of Manuals................................................................................................................. 19
1.1.1 Classification of major components in this manual........................................................................19
1.1.2 Manual organization and position of this manual ..........................................................................21
1.1.3 List of manuals ..............................................................................................................................22
1.2 Generic Names and Abbreviations Used in Manuals.................................................................... 27
Table of Contents
2. Features and Part Names29
2.1 Major Features.............................................................................................................................. 29
2.2 Names and Functions of Parts...................................................................................................... 31
2.2.1 Front Panel.................................................................................................................................... 31
3.1 List of Products and Interpretation of Model Names..................................................................... 34
3.1.1 Main units ...................................................................................................................................... 35
4.6.1 Main units ...................................................................................................................................... 52
6.5 Expansion of Main Unit ................................................................................................................. 76
6.5.1 When adding input/output extension blocks using the 24V DC service power supply of
the main unit.................................................................................................................................. 77
6.5.2 Selection example 1 using the 24V DC service power supply of the main unit............................. 79
6.5.3 Selection example 2 using the 24V DC service power supply of the main unit............................. 80
6.6 Expansion of FX2N Series I/O Powered Extension Unit ............................................................... 81
6.6.1 Quick reference matrix (when only input/output devices are added)............................................. 81
6.6.2 When special extension devices are also added (calculation of current consumption)................. 84
6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)...................................................... 86
... 68
4
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.8 Number of Input/Output (Occupied) Points and Current Consumption......................................... 88
6.8.1 [A] Main units................................................................................................................................. 88
19.2 Installation and Removal........................................................................................................... 309
19.2.1 Installation (when the expansion board/connector conversion adapter is not used together)... 309
19.2.2 Installation (when the expansion board/connector conversion adapter is used together)......... 310
19.3 Summary of Functions .............................................................................................................. 311
19.4 Procedure for Accessing the Menu Screen from the Title Screen ............................................ 312
19.4.1 Title screen ................................................................................................................................ 312
19.4.2 Top screen (time display) .......................................................................................................... 312
19.4.3 Menu screen.............................................................................................................................. 312
19.5 Menu Structure.......................................................................................................................... 313
Revised History ..................................................................................................................... 419
13
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Standards
Certification of UL, cUL standards
FX3G series main units, FX3G series interface adapter, FX3U series special adapters and FX2N input/output
extension units/blocks supporting UL, cUL standards are as follows:
This note does not guarantee that an entire mechanical module produced in accordance with the contents of
this note will comply with the following standards.
Compliance to EMC directive and LVD directive of the entire mechanical module should be checked by the
user / manufacturer. For more details please contact to the local Mitsubishi Electric sales site.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified standards below) and
design analysis (through the creation of a technical construction file) to the European Directive for
Electromagnetic Compatibility (2004/108/EC) when used as directed by the appropriate documentation.
Attention
• This products is designed for use in industrial applications.
Note
• Manufactured by:
Mitsubishi Electric Corporation
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
• Manufactured at:
Mitsubishi Electric Corporation Himeji Works
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
14
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Type :Programmable Controller (Open Type Equipment)
Models :MELSEC FX
from June 1st, 2005FX3U-232ADPFX3U-485ADP
from April 1st, 2007FX3U-232ADP-MBFX3U-485ADP-MB
from December 1st, 2007 FX3U-4AD-PTW-ADPFX3U-4AD-PNK-ADP
from November 1st, 2008
from December 1st, 2008
from March 1st, 2009
from June 1st, 2009FX
from December 1st, 2009
from February 1st, 2012FX3U-ENET-ADP
from September 1st, 2013 FX3G-4EX-BDFX3G-2EYT-BDFX3G-485-BD-RJ
Compliance with all relevant aspects of the standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
15
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Standards
Models :MELSEC FX
from July 1st, 1997
from April 1st, 1998FX2N-48ER-DSFX2N-48ET-DSS
from August 1st, 1998FX2N-48ER-UA1/UL
from August 1st, 2005FX2N-8ER-ES/ULFX2N-8EX-ES/ULFX2N-8EYR-ES/UL
from September 1st, 2010 FX2N-8EYR-S-ES/UL
2N series manufactured
FX2N-ER-ES/UL FX2N-ET-ESS/UL
Where indicates:32,48
FX2N-16EX-ES/ULFX2N-16EYR-ES/ULFX2N-16EYT-ESS/UL
FX2N-8EYT-ESS/UL
For the products above, PLCs manufactured
before March 31st, 2002 are compliant with EN50081-2 (EN61000-6-4) and EN50082-2
from April 1st, 2002 to April 30th, 2006 are compliant with EN50081-2 (EN61000-6-4) and EN61131-2:1994
+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
StandardRemark
EN61000-6-4:2007 - Generic emission standard
Industrial environment
EN50081-2:1993Electromagnetic compatibility
EN50082-2:1995Electromagnetic compatibility
- Generic immunity standard
Industrial environment
EN61131-2:1994Programmable controllers
/A11:1996- Equipment requirements and tests
/A12:2000
EN61131-2:2007Programmable controllers
- Equipment requirements and tests
Compliance with all relevant aspects of the standard.
• Emission-Enclosure port
• Emission-Low voltage AC mains port
• Emission-Telecommunications/network port
Compliance with all relevant aspects of the standard.
• RF immunity
• Fast transients
•ESD
• Conducted
• Power magnetic fields
Compliance with all relevant aspects of the standard.
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• Damped oscillatory wave
Compliance with all relevant aspects of the standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
16
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Requirement for Compliance with LVD directive
The following products have shown compliance through direct testing (of the identified standards below) and
design analysis (through the creation of a technical construction file) to the European Directive for Low
Voltage (2006/95/EC) when used as directed by the appropriate documentation.
Type :Programmable Controller (Open Type Equipment)
Models :MELSEC FX
from November 1st, 2008
from December 1st, 2008
from March 1st, 2009
from December 1st, 2009
StandardRemark
EN61131-2:2007 Programmable controllers
- Equipment requirements and tests
3G series manufactured
FX3G-MT/ES
Where indicates:14,24,40,60
FX3G-MR/ES
Where indicates:14,24,40,60
FX3G-MT/ESS
Where indicates:14,24,40,60
3G-MR/DS
FX
Where indicates:14,24,40,60
The equipment has been assessed as a component for fitting in a suitable
enclosure which meets the requirements of EN61131-2:2007
Standards
Models :MELSEC FX2N series manufactured
from July 1st, 1997
from April 1st, 1998FX2N-48ER-DS
from August 1st, 1998FX2N-48ER-UA1/UL
from August 1st, 2005FX2N-8ER-ES/ULFX2N-8EYR-ES/UL
from September 1st, 2010 FX2N-8EYR-S-ES/UL
FX2N-ER-ES/ULFX2N-ET-ESS/UL
Where indicates:32,48
FX2N-16EYR-ES/UL
For the products above, PLCs manufactured
before March 31st, 2002 are compliant with IEC1010-1
from April 1st, 2002 to April 30th, 2006 are compliant with EN61131-2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
StandardRemark
IEC1010-1:1990 Safety requirements for electrical
/A1:1992 equipment for measurement, control,
and laboratory use
- General requirements
EN61131-2:1994 Programmable controllers
/A11:1996 - Equipment requirements and tests
/A12:2000
EN61131-2:2007 Programmable controllers
- Equipment requirements and tests
The equipment has been assessed as a component for fitting in a
suitable enclosure which meets the requirements of IEC 10101:1990+A1:1992
The equipment has been assessed as a component for fitting in a
suitable enclosure which meets the requirements of EN611312:1994+A11:1996+A12:2000
The equipment has been assessed as a component for fitting in a
suitable enclosure which meets the requirements of EN61131-2:2007
17
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Caution for compliance with EC Directive
1. Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and used within conductive
control boxes. Please use the FX
shielded control boxes. Please secure the control box lid to the control box (for conduction). Installation within
a control box greatly affects the safety of the system and aids in shielding noise from the programmable logic
controller.
2. Caution for Analog Products in use
The analog products have been found to be compliant to the European standards in the aforesaid manual
and directive. However, for the very best performance from what are in fact delicate measuring and controlled
output devices, Mitsubishi Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered carefully. For users of proprietary
cables (integral with sensors or actuators), these users should follow those manufacturers' installation
requirements.
Mitsubishi Electric recommends that shielded cables be used. If NO other EMC protection is provided, users
may experience temporary loss or accuracy between +10% / -10% in very heavy industrial areas.
However, Mitsubishi Electric suggests that if adequate EMC precautions are followed for the users complete
control system.
- Sensitive analog cables should not be laid in the same trunking or cable conduit as high voltage cabling.
Where possible, users should run analog cables separately.
- Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops
are accidentally created.
- When reading analog values, EMC accuracy can be improved by averaging the readings. This can be
achieved either through functions on the analog special adapters/boards/blocks or through a user's
program in the FX
3G Series PLC main unit.
3G Series programmable logic controllers while installed in conductive
Standards
18
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1.Introduction
1 Introduction
1.1 Introduction of Manuals
1
Introduction
This manual explains the procedures for selecting the system components, main unit specifications and
procedures for installing the main unit, specifications for the input/output powered extension units/blocks, and
procedures for adding input/output devices, and procedures for operating the display module etc.
3G PLCs can make various kinds of control in combination with the main unit functions and many extension
FX
devices (expansion board, special adapters and special function blocks).
The detailed explanation of the sequence instructions, communication control, analog control and positioning
control are given in separate manuals.
→ For information on manual organization, refer to Subsection 1.1.2.
1.1Introduction of Manuals
1.1.1Classification of major components in this manual
1) Main unit (Chapter 1 to Chapter 14)
DivisionOutlineReference
Introduction of manuals
Features and part names
Introduction of product
Specifications
Version information
System configuration
Input/output No. and unit No.
assignment
Installation
Power supply wiring
Input wiring
High-speed counter
Output wiring
Examples of wiring for each use
Test operation, adjustment,
maintenance and error check
This chapter contains explanations of the procedures for obtaining the manuals
and the abbreviations.
This chapter contains explanations of the product features and the names and
functions of the parts.
This chapter contains explanations of the structures for model names, extension
products.
This chapter contains explanations of the specifications for power supply and
input/output, external dimensions and terminal block layout.
This chapter contains explanation for upgrading of FX3G PLCs and information for
the application of programming tools.
Procedure for determining whether or not a system configuration is possible.
Extension device current consumption and configuration examples.
Input/output assignment procedure for input/output powered extension units/
blocks, etc., and unit No. assignment procedure for special function blocks.
This chapter contains explanations for the panel layout and the procedures for
installing with DIN rail or screws and how to connect extension devices.
This chapter contains explanations of the procedures for preparing for wiring,
power supply specifications and instructions for wiring.
This chapter contains explanations of the input specifications and instructions for
wiring.
This chapter contains explanations of the procedures for using the high-speed
counter examples of programming.
This chapter contains explanations for the output specifications and instructions
for wiring.
This chapter contains explanations of the procedures for wiring input/output
devices for main uses.
This chapter contains explanations of the procedures for test operation and
adjustment, maintenance and error check items and measures to be taken upon
occurrence of error.
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
Chapter 9
Chapter 10
Chapter 11
Chapter 12
Chapter 13
Chapter 14
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
19
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2) Extension devices (Chapter 15 to Chapter 18)
DivisionOutlineReference
Input/output powered extension
units
Input/output extension blocksChapter 16
Extension power supply unit
(FX3U-1PSU-5V)
Extension products for special
functions, such as analog control
and communication
3) Optional products (Chapter 19 to Chapter 22)
DivisionOutlineReference
Display module
FX Series terminal blocks
Memory cassette
Battery
This chapter contains explanations for the input/output specifications, external
dimensions and terminal layout for each product.
This chapter contains explanations of specifications for the extension power
supply unit and external dimensions.
This chapter contains explanations for the external dimensions and terminal
layout (For details, refer to the manual for each extension device).
This chapter contains explanation of the specifications, external dimensions,
mounting procedures and operating procedures for display modules (FX3G-5DM).
This chapter contains explanations of the procedures for wiring FX-16/32E -TB.
This chapter contains explanations of the specifications for the memory cassette
and the installation procedures.
This chapter contains explanations of the procedures for replacing the battery and
detecting battery voltage drop.
1 Introduction
1.1 Introduction of Manuals
Chapter 15
Chapter 17
Chapter 18
Chapter 19
Chapter 20
Chapter 21
Chapter 22
4) Others (Appendix A to Appendix E)
DivisionOutlineReference
List of special devices
List of instructions
List of discontinued models
Precautions for battery
transportation
Handling of batteries and devices
with Built-in batteries in EU
member states
This chapter contains an explanation list of the special auxiliary relays (M8000 to
M8511) and special data registers (D8000 to D8511)
(For details, refer to the programming manual.)
This chapter contains an explanation list of the basic instructions and applied
instructions
(For details, refer to the programming manual.)
The discontinued MELSEC-F Series PLC models and programming tools
described in this manual.
This chapter contains explanations for transport regulations and guidelines.Appendix D
This chapter contains explanations for the disposal precautions of batteries and
exporting batteries to EU member states.
Appendix A
Appendix B
Appendix C
Appendix E
20
FX3G Series Programmable Controllers
FX -48ER
2N
7245613
0
7245613
0
OUT
IN
L
X5 X7X1X3 X5 X7X1X3 X5 X7
X4 X6
X0
X2 X4 X6X0X2 X4 X6
24+
N
COM
X0
X1
X2
X3
COM4Y4Y5
COM5
Y7COM2Y4Y5Y6Y7 COM3
Y0
Y1
Y2
Y3
COM1
Y0
Y1
Y2
Y3
Y4Y5Y6
Y7
Y0
Y1
Y2Y3Y6
POWER
7245613
0
7245613
0
7245613
0
7245613
0
User's Manual - Hardware Edition
1.1.2Manual organization and position of this manual
This manual describes detail on the hardware, including the system configuration, selection, installation and
wiring. The instructions, communication control, analog control and positioning control are explained in
separate manuals. Refer to the manuals as needed.
FX3G Series
(Main unit)
Built-in functions
Sequence instructions
High-speed counter
Positioning instructions
PID
Additional options
Input/output powered extension
units/blocks
Expansion board, Special adapters
Analog
3U
FX -4AD-ADP
POWER
Communication
24+24-V1+
I1+
COM1
V2+
I2+
COM2
V3+
I3+
COM3
V4+
I4+
COM4
Special function blocks
Analog
As for FX2N Series, refer to individual
manuals.
Options
Display module
Memory cassette
Battery
Manuals supplied with product
Each product comes with the installation manual or
the User's Manual (except the input/output powered
extension units/blocks).
I
nstallation manual
The part names, installation procedures and
specifications are shown.
As for the functions and program examples, refer to
the separate User's Manual -
Edition.
User's manual
The procedures for wiring and installing,
specifications and functions are explained.
To use some products, separate manuals may be
necessary.
Manual for each use (separate volume)
Refer to the manual for each purpose of use.
User's Manual - Hardware Edition
JY997D31301 (Model: FX
Details of analog special function
blocks and analog special adapters
The manuals for FX3G Series will be
available in or after September, 2008.
Details of N:N Network,
parallel link, computer link, nonprotocol communication and
programming communication
The manuals for FX
3G
Series will be
available in or after September, 2008.
Details of wiring, instructions and
operations of positioning functions in
PLC main unit
The manuals for FX
3G
Series will be
available in or after September, 2008.
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
21
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1.1.3List of manuals
FX3G Series PLC main units supplied only with the hardware manual.
For the details of the hardware of FX
For instructions for programming and hardware information on special function devices, refer to the relevant
manuals.
: Indispensable manuals : Manuals necessary for some purposes : Manuals with separate volumes for details
1 Introduction
1.1 Introduction of Manuals
3G Series, refer to this manual.
Manual title
Manuals for PLC main unit
FX3G PLC main unit
Supplied
product
Separate
volume
Programming
Separate
volume
Separate
volume
Separate
volume
Separate
volume
Separate
volume
FX Series terminal block
Supplied
product
Manuals for communication control
Common
Separate
volume
Separate
volume
RS-232C/RS-422/RS-485 communication
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed and FX Series User's
Manual - Data Communication Edition. For the MODBUS communication, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's
Manual - MODBUS Serial Communication Edition.
Supplied
product
Supplied
product
Supplied
product
Supplied
product
with
with
with
with
with
with
FX3G Series
HARDWARE MANUAL
FX3G Series User's Manual
- Hardware Edition
(this manual)
FX3S/FX3G/FX
Series Programming
Manual - Basic & Applied
Instruction Edition
FX CPU Structured
Programming Manual
[Device & Common]
FX CPU Structured
Programming Manual
[Basic & Applied Instruction]
FX CPU Structured
Programming Manual
[Application Functions]
FX INPUT AND
OUTPUT TERMINAL
BLOCKS USER'S GUIDE
FX Series User's Manual Data Communication Edition
FX3S/FX3G/FX
Series User's Manual
- MODBUS Serial
Communication Edition
FX3G-232-BD
Installation Manual
FX3U-232ADP-MB
Installation Manual
FX3U-232ADP
Installation Manual
FX3G-422-BD
Installation Manual
3GC
3GC
/FX3U/FX
/FX3U/FX
3UC
3UC
Manual
number
Extractions of descriptions of input/output
JY997D46001
JY997D31301
JY997D16601
SH-080782
JY997D26001
JY997D34701
JY997D34801
JY992D50401 Procedures for handling FX Series terminal block.-
JY997D16901
JY997D26201
JY997D32001
JY997D26401
JY997D13701
JY997D32101
specifications, wiring and installation of FX3G Series
PLC main unit from FX3G Series User's Manual Hardware Edition.
For the detailed explanation, refer to this manual.
Details of hardware of FX3G Series PLC main unit,
including input/output specifications, wiring,
installation and maintenance.
Details of sequence programming for FX3G Series,
including explanation for basic instructions, applied
instructions and various devices.
Programming methods, specifications, functions, etc.
required to create structured programs.
Devices, parameters, etc. provided in structured
projects of GX Works2.
Sequence instructions provided in structured projects
of GX Works2.
Application functions provided in structured projects
of GX Works2.
Details of N:N Network, parallel link, computer link
and no-protocol communication (RS instructions,
FX2N-232IF).
Details on MODBUS serial communication
in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs.
Procedures for handling the RS-232C communication
expansion board.
Procedures for handling the RS-232C communication
special adapter.
Procedures for handling the RS-232C communication
special adapter.
Procedures for handling the RS-422 communication
expansion board.
Contents
Model name
code
-
09R521
09R517
13JW06
09R925
09R926
09R927
09R715
-
-
-
-
-
22
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Manual title
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Ethernet, CC-Link, CC-Link/LT
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
product
Separate
volume
Supplied
product
Separate
volume
Supplied
product
Separate
volume
Supplied
product
Separate
volume
Supplied
product
Supplied
product
Supplied
product
Separate
volume
Supplied
product
with
with
with
with
with
with
with
with
with
with
with
with
with
FX3G-485-BD
Installation Manual
FX3G-485-BD-RJ
Installation Manual
FX3U-485ADP-MB
Installation Manual
FX3U-485ADP
Installation Manual
FX-485PC-IF
Hardware Manual
FX3U-ENET-ADP
Installation Manual
FX3U-ENET-ADP
User's Manual
FX3U-16CCL-M
Installation Manual
FX3U-16CCL-M
User's Manual
FX2N-16CCL-M
Hardware Manual
FX2N-16CCL-M
User's Manual
FX3U-64CCL
Installation Manual
FX3U-64CCL
User's Manual
2N-32CCL
FX
User's Manual
Remote I/O station, remote
device station and intelligent
device station for CC-Link
FX
2N-64CL-M
User's Manual Hardware Volume
FX2N-64CL-M
User's Manual Detailed Volume
Remote I/O station, remote
device station, power supply
adapter and dedicated power
supply for CC-Link/LT
1 Introduction
1.1 Introduction of Manuals
Manual
number
JY997D32201
JY997D51501
JY997D26301
JY997D13801
JY992D81801
JY997D47401
JY997D45801
JY997D43401
JY997D43601 Details of CC-Link master special function block.09R724
JY992D87801
JY992D87901 Details of CC-Link master special function block.09R710
JY997D29801
JY997D30401
JY992D71701
As for the remote I/O station, remote device station and intelligent
device station for CC-Link, refer to the relevant manuals and related
documents.
JY997D05401
JY997D08501
As for the remote I/O station, remote device station, power supply
adapter and dedicated power supply for CC-Link/LT, refer to the
relevant manuals and related documents.
Procedures for handling the RS-485 communication
expansion board.
Procedures for handling the RS-485 communication
expansion board.
Procedures for handling the RS-485 communication
special adapter.
Procedures for handling the RS-485 communication
special adapter.
Procedures for handling the RS-232C/RS-485
conversion interface.
Procedures for handling the FX3U-ENET-ADP
Ethernet communication special adapter.
When using, refer to FX3U-ENET-ADP User's
Manual.
Details of FX3U-ENET-ADP Ethernet communication
special adapter.
Procedures for handling the CC-Link master special
function block.
When using, refer to FX3U-16CCL-M User's Manual.
Procedures for handling the CC-Link master special
function block.
When using, refer to FX2N-16CCL-M User's Manual.
Procedures for handling the CC-Link Intelligent
device station special function block.
When using, refer to FX3U-64CCL User's Manual.
Details of the CC-Link Intelligent device station
special function block.
Procedures for handling the CC-Link remote device
station special function block.
Procedures for handling the CC-Link/LT master
special function block.
When using, refer to FX
Details.
Details of the CC-Link/LT master special function
block.
Contents
2N-64CL-M User's Manual -
Model name
code
-
-
-
-
-
-
09R725
-
-
-
09R718
09R711
-
-
09R706
-
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
23
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1 Introduction
1.1 Introduction of Manuals
Manual title
Manuals for analog/temperature control
Common
with
with
with
with
with
with
with
with
with
with
with
with
with
with
FX3S/FX3G/FX
Series User's Manual Analog Control Edition
FX3G-2AD-BD
Installation Manual
FX3U-4AD
Installation Manual
FX2N-2AD
User's Guide
FX2N-4AD
User's Guide
FX2N-8AD
User's Manual
FX3U-4AD-ADP
User's Manual
FX3U-4AD-PT-ADP
User's Manual
FX3U-4AD-PTW-ADP
User's Manual
FX2N-4AD-PT
User's Guide
FX3U-4AD-PNK-ADP
User's Manual
FX
3U-4AD-TC-ADP
User's Manual
FX2N-4AD-TC
User's Guide
FX2N-2LC
User's Guide
FX2N-2LC
User's Manual
FX3U-4LC
Installation Manual
FX3U-4LC
User's Manual
Separate
volume
Analog input, temperature input and temperature control
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Separate
volume
Supplied
product
Separate
volume
3GC
/FX3U/FX
3UC
Manual
number
JY997D16701
JY997D33501
JY997D20701
JY992D74701
JY992D65201
JY992D86001
JY997D13901
JY997D14701
JY997D29101
JY992D65601
JY997D29201
JY997D14801
JY992D65501
JY992D85601
JY992D85801
JY997D38901
JY997D39101
Contents
Details of analog special function block (FX3U-4AD,
FX3U-4DA, FX3UC-4AD) and analog special adapter
(FX3U-***-**-ADP)
Procedures for handling the 2-ch analog input
expansion board.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch analog input special
function block.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 2-ch analog input special
function block.
Procedures for handling the 4-ch analog input special
function block.
Procedures for handling the 8-ch analog input special
function block (to be used also for thermocouple
input).
Procedures for handling the 4-ch analog input special
adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch Pt100 temperature
sensor input special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch Pt100 temperature
sensor input special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition
Procedures for handling the 4-ch Pt100 temperature
sensor input special function block.
Procedures for handling the 4-ch Pt1000/Ni1000
temperature sensor input special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch thermocouple input
special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch thermocouple input
special function block.
Procedures for handling the 2-ch temperature control
special function block.
When using, refer to FX2N-2LC User's Manual.
Procedures for handling the 2-ch temperature control
special function block.
Procedures for handling the 4-ch temperature control
special function block.
When using, refer to FX3U-4LC User's Manual.
Procedures for handling the 4-ch temperature control
special function block.
3GC
3GC
3GC
3GC
3GC
3GC
3GC
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
3UC
3UC
3UC
3UC
3UC
3UC
3UC
Model name
code
09R619
-
-
-
-
09R608
-
-
-
-
-
-
-
-
09R607
-
09R625
24
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Manual title
Analog output
When using each product, refer also to the Use's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Analog input/output (mixed)
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
product
Supplied
product
Manuals for positioning control
Common
Separate
volume
Manuals for FX-30P
Supplied
product
Separate
volume
Other manuals
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Input extension
Supplied
product
Output extension
Supplied
product
Variable analog potentiometers
Supplied
product
Connector conversion
Supplied
product
Battery (maintenance option)
Supplied
product
with
with
with
with
with
with
with
with
with
with
with
with
FX3G-1DA-BD
Installation Manual
FX3U-4DA-ADP
User's Manual
FX3U-4DA
Installation Manual
FX2N-2DA
User's Guide
FX3U-3A-ADP
User's Manual
FX2N-5A
User's Manual
FX3S/FX3G/FX
Series User's Manual Positioning Control Edition
FX-30P
Installation Manual
FX-30P
Operation Manual
3G-4EX-BD
FX
User's Manual
FX
3G-2EYT-BD
User's Manual
FX3G-8AV-BD
Installation Manual
FX3G-CNV-ADP
Installation Manual
FX3U-32BL BatteryJY997D14101 Battery life and handling procedures.-
3GC
/FX3U/FX
JY997D33601
JY997D14001
JY997D20801
JY992D74901
JY997D35601
JY997D11401
3UC
JY997D16801
JY997D34201
JY997D34401
JY997D51301
JY997D51401
JY997D33701
JY997D32301
Manual
number
1.1 Introduction of Manuals
Contents
Procedures for handling the 1-ch analog output
expansion board.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch analog output
special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch analog output
special function block.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 2-ch analog output
special function block.
Procedures for handling the 2-ch analog input and 1ch analog output special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch analog input and 1ch analog output special function block.
Details of positioning functions of FX3S/FX3G/
FX3GC/FX3U/FX3UCSeries.
Describes FX-30P specification extracted from the
FX-30P Operation manual.
For details, refer to FX-30P Operation manual.
Describes Handy Programming Panel FX-30P
details.
Procedures for handling the 4 points input expansion
board.
Procedures for handling the 2 points transistor output
expansion board.
Procedures for handling the 8-ch variable analog
potentiometers expansion board.
When using, refer to FX3S/FX3G/FX
Series Programming Manual -Basic & Applied
Instruction Edition.
Procedures for handling the conversion function
expansion adapter for connectors for connecting
communication and analog special adapters.
3GC
3GC
3GC
3GC
3GC
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
3UC
3UC
3UC
3UC
3UC
1 Introduction
Model name
code
-
-
-
-
-
09R616
09R620
-
09R924
-
-
-
-
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
25
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1 Introduction
1.1 Introduction of Manuals
Manual title
Memory cassette
Supplied
product
Display module
Supplied
product
Extension power supply unit
Supplied
product
with
with
with
FX3G-EEPROM-32L
Installation Manual
FX3G-5DM
Installation Manual
FX3U-1PSU-5V
Installation Manual
Manual
number
JY997D32401
JY997D33801
JY997D22501
Contents
Specifications and operating procedures of the
memory cassette.
Procedures for mounting and handling the display
module.
Specifications and operating procedures of the
extension power supply unit.
Model name
code
-
-
-
26
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1.2 Generic Names and Abbreviations Used in Manuals
1.2Generic Names and Abbreviations Used in Manuals
1 Introduction
1
Introduction
Abbreviation/
generic name
PLCs
FX3G SeriesGeneric name for FX3G Series PLCs
FX3U SeriesGeneric name for FX3U Series PLCs
FX2N SeriesGeneric name for FX2N Series PLCs
FX3G PLCs or main unitsAbbreviation of FX3G Series PLC main units
Expansion boards
Special adaptersGeneric name for communication special adapters and analog special adapters
Communication special
adapters
Analog special adapters
Extension devicesGeneric name for FX3U Series special function blocks, FX2N Series extension devices
FX2N Series extension devices
Input/output extension devices
FX2N Series input/output
powered extension units
FX2N Series input/output
extension blocks
FX2N Series input extension
blocks
FX2N Series output extension
blocks
Special function blocksGeneric name for FX3U Series special function blocks, FX2N Series special function blocks
FX3U Series special function
blocks
2N Series special function
FX
blocks
Memory cassettes
Display module
BatteryAbbreviation of model FX3U-32BL battery
FX Series terminal blocks
Extension cables
Input/output cables
Connectors for input/output
CC-Link master
Intelligent device stationsAbbreviation of FX3U-64CCL interface block
Remote device stationsAbbreviation of FX2N-32CCL interface block
Remote I/O stationRemote station that handles bit data only
Peripheral devicesGeneric name for programming software, handy programming panel (HPP) and indicator
Generic name for the following models
FX3G-4EX-BD, FX3G-2EYT-BD, FX3G-232-BD, FX3G-422-BD, FX3G-485-BD, FX3G-485-BD-RJ,
FX3G-2AD-BD, FX3G-1DA-BD, FX3G-8AV-BD
Generic name for the following models
FX3U-232ADP(-MB), FX3U-485ADP(-MB), FX3U-ENET-ADP
Generic name for the following models
FX3U-4AD-ADP, FX3U-4DA-ADP, FX3U-3A-ADP, FX3U-4AD-PT-ADP, FX3U-4AD-PTW-ADP,
FX3U-4AD-PNK-ADP, FX3U-4AD-TC-ADP
Generic name for FX2N Series input/output powered extension units, FX2N Series input/output
extension blocks and FX2N Series special function blocks
Generic name for FX2N Series input/output powered extension units, FX2N Series input/output
extension blocks
Generic name for the following models
FX2N-32ER-ES/UL, FX2N-32ER, FX2N-32ES, FX2N-32ET-ESS/UL, FX2N-32ET, FX2N-48ER,
FX2N-48ER-ES/UL, FX2N-48ET, FX2N-48ET-ESS/UL, FX2N-48ER-UA1/UL, FX2N-48ER-DS,
FX2N-48ET-DSS, FX2N-48ER-D, FX2N-48ET-D
Generic name for the following models
FX2N-8ER-ES/UL, FX2N-8ER
Generic name for the following models
FX2N-16EX-ES/UL, FX2N-16EX, FX2N-16EX-C, FX2N-16EXL-C, FX2N-8EX-ES/UL,
FX2N-8EX-UA1/UL, FX2N-8EX
Generic name for the following models
FX2N-16EYR-ES/UL, FX2N-16EYR, FX2N-16EYT-ESS/UL, FX2N-16EYT, FX2N-16EYS,
FX2N-16EYT-C, FX2N-8EYR-ES/UL, FX2N-8EYR-S-ES/UL, FX2N-8EYT-ESS/UL, FX2N-8EYR,
FX2N-8EYT, FX2N-8EYT-H
Generic name for the following models
FX3U-16CCL-M, FX3U-64CCL, FX3U-4AD, FX3U-4LC, FX3U-4DA
Generic name for the following models
FX3G-EEPROM-32L
Generic name for the following models
FX3G-5DM
Generic name for the following models
FX-16E-TB, FX-32E-TB, FX-16EX-A1-TB, FX-16EYR-TB, FX-16EYS-TB, FX-16EYT-TB,
FX-16EYT-H-TB
Generic name for the following models
FX0N-30EC, FX0N-65EC
Generic name for the following models
FX-16E-500CAB-S, FX-16ECAB, FX-16E-CAB-R, FX-A32E-CAB
150, 300 or 500 is entered in .
Generic name for the following models
FX2C-I/O-CON, FX2C-I/O-CON-S, FX2C-I/O-CON-SA
Generic name for the following models
FX3U-16CCL-M, FX2N-16CCL-M
Description
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
27
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1 Introduction
1.2 Generic Names and Abbreviations Used in Manuals
Abbreviation/
generic name
Programming toolGeneric name for programming software and handy programming panel (HPP)
Programming softwareGeneric name for GX Works2, GX Developer and FX-PCS/WIN (-E)
GX Works2
GX Developer
FX-PCS/WIN (-E)Abbreviation of programming software packages FX-PCS/WIN and FX-PCS/WIN-E
Handy programming panels
(HPP)
RS-232C/RS-422 converters
RS-232C/RS-485 convertersAbbreviation of FX-485PC-IF
Indicators
GOT1000 SeriesGeneric name for GT16, GT15, GT14, GT11 and GT10
GOT-900 SeriesGeneric name for GOT-A900 Series and GOT-F900 Series
GOT-A900 SeriesGeneric name for GOT-A900 Series
GOT-F900 SeriesGeneric name for GOT-F900 Series
Manuals
FX3G Hardware EditionAbbreviation of FX3G Series User's Manual - Hardware Edition
Programming manual
Data Communication EditionAbbreviation of FX Series User's Manual - Data Communication Edition
MODBUS Serial
Communication Edition
Analog Control EditionAbbreviation of FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Analog Control Edition
Positioning Control EditionAbbreviation of FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - Positioning Control Edition
Abbreviation of programming software packages SW DNC-GXW2-J and SW DNC-GXW2-E
Abbreviation of programming software packages SW D5C-GPPW-J and SW D5C-GPPW-E
Generic name for the following models
FX-30P, FX-20P, FX-20P-E
Generic name for the following models
FX-232AW, FX-232AWC, FX-232AWC-H
Abbreviation of FX3S/FX3G/FX3GC/FX3U/FX3UC Series Programming Manual - Basic & Applied
Instruction Edition
Abbreviation of FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's Manual - MODBUS Serial
Communication Edition
Description
28
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2.Features and Part Names
2.1Major Features
2 Features and Part Names
2.1 Major Features
1
Introduction
2
Features and
Part Names
1. Basic functions
[Up to 256 input/output points]
The total number of inputs and outputs (128
points maximum) directly connected to the PLC
and remote inputs and outputs (128 points
maximum) of the CC-Link can be extended to
256 points.
[Program memory]
The PLC has a 32K-step EEPROM memory.
[Built-in USB port]
The PLC has a built-in USB port for the
programming communication function to enable
high-speed communication at 12Mbps.
[Built-in RUN/STOP switch]
The PLC can be started and stopped with the
built-in switch.
RUN and STOP commands can be given to the
PLC through a general-purpose input terminal or
peripheral device.
[Built-in Variable analog potentiometers]
The PLC has two built-in variable analog
potentiometers available for adjusting the timer
set time.
[Writing during RUN]
The programming software for personal
computer enables you to modify the program
while the PLC is running.
[Built-in clock function]
The PLC has a clock function to control the time.
[Programming tool]
Use a version of a programming tool supporting
3G.
the FX
→ Refer to 5. Version Information and
Peripheral Equipment Connectability in this
manual.
*For peripheral devices not applicable to FX
Series, specify FX1N Series for model selection,
and you can program the sequence.
In this case, use instructions and devices within
the ranges common to FX
selected model of PLC.
3G Series and the
3G
[Remote debugging of program]
Use of programming software (GX Works2, GX
Developer) enables you to remotely transfer
programs and monitor PLC operation through a
modem connected to the RS-232C expansion
board or RS-232C communication special
adapter.
2. Input/output high-speed processing
functions of main unit
[High-speed counter function]
Input terminals of main unit
- Input of open collector transistor output
- 1-phase 60kHz x 4 points + 10kHz x 2 points
- 2-phase 30kHz x 2 points + 5kHz x 1 points
→ Refer to 11. Use of High-speed Counters in
this manual and Programming Manual.
[Pulse catch function]
Signals with short ON width or OFF width can be
captured without a complicated program.
→ Refer to 10. Input Wiring Procedures
in this manual and Programming Manual.
Input terminalSignal ON/OFF width
X000, X001, X003, X00410 s
X002, X00550 s
[Input interruption function]
The PLC can process interruption routines with
higher priority using external signals whose
minimum ON duration or OFF duration is 10 s
(X000, X001, X003 and X004) or 50 s (X002
and X005). (The timer interruption function is
also provided.)
→ Refer to 10. Input Wiring Procedures in
this manual and Programming Manual.
[Pulse width/period measurement function]
(Supported in Ver. 1.10 or later)
The width/period of pulses from input terminals
(X000, X001, X003 and X004) of the main unit
can be measured in units of 10 s.
→ Refer to 10. Input Wiring Procedures and
Programming Manual.
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
29
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2 Features and Part Names
2.1 Major Features
[Pulse output function]
When output terminals in the transistor output
type main unit are used, pulses of up to 100kHz
can be output simultaneously to 3 axes
*1
Y001 and Y002).
*1.2 axes (Y000 and Y001) in 14-point and
24-point type main units
Using a number of instructions programming is
simplified.
→ Refer to Positioning Control Edition.
[Various positioning instructions]
→ Refer to Positioning Control Edition.
InstructionDescription
DSZR
ABS
DRVI
DRVA
PLSV
TBL
Mechanical zero return instruction with DOG
search function
Instruction to read the current value from our
servo amplifier with absolute position (ABS)
detecting function
Positioning (relative positioning) to specify the
movement from the current position
Positioning (absolute positioning) to specify
the target position based on the current
value 0
Instruction to change the pulse train output
frequency
Instruction for positioning based on batch
setting of positioning operation, moving
distance and speed
3. Display functions (display module)
(Supported in Ver. 1.10 or later)
FX3G-5DM Display Module (option) can be
incorporated in the PLC.
[Monitor/test function]
Devices can be monitored and tested by
operating the buttons on the display module.
The button operations can be inhibited by the
user program.
[Other functions]
On the display module, you can set the time,
adjust the contrast and display the PLC version
and error codes.
→ Refer to 19. Display Module (FX3G-5DM) in
this manual.
(Y000,
• MODBUS communication
(Supported in Ver. 1.30 or later)
→ Refer to MODBUS Serial Communication
• Ethernet (Supported in Ver. 2.00 or later)
→ Refer to FX
3U-ENET-ADP User's Manual.
• CC-Link
- Master station (Compatible with CC-Link
Ver. 2.00 and Ver. 1.10):
3U-16CCL-M
FX
- Master station (Compatible with CC-Link
Ver. 1.10):
FX
2N-16CCL-M
- Intelligent device station
FX3U-64CCL
- Remote device station
FX
2N-32CCL
→ Refer to the manual for each product.
• CC-Link/LT
- Master station : FX
2N-64CL-M
- Remote I/O station, Remote device station
→ Refer to the manual for each product.
5. Analog functions
The expansion board, special adapter and
special function block for each analog function
are connected.
→ Refer to Analog Control Edition.
[Kinds of analog functions]
• Voltage/current input
• Voltage/current output
• Temperature sensor input (thermocouple and
platinum resistance thermometer sensor)
• Temperature control
Edition.
4. Communication and network functions
The expansion board, special adapter and
special function block for each communication
function can be connected.
[Kinds of communication functions]
• Programming communication
(RS-232C/RS-422/USB)
• N:N Network
• Parallel link
• Computer link
• Inverter communication
(Supported in Ver. 1.10 or later)
• Non-protocol communication
(Built-in RS-422/RS-232C/RS-485)
→ Refer to Data Communication Edition.
30
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2.2Names and Functions of Parts
2.2.1Front Panel
2 Features and Part Names
2.2 Names and Functions of Parts
1
Introduction
Factory default configuration (standard)
[4][3]
[2]
[1]
[11]
[1] Peripheral device connecting
connector cover
[2] Terminal namesThe signal names for power supply, input and output terminals are shown.
[3] Top cover (S)
(40points, 60points type only)
[4] Top coverMount the expansion board, display module, memory cassette and battery under this
[5] Terminal block coversThe covers can be opened for wiring.
[6] Input display LEDs (red)When an input terminal (X000 or more) is turned on, the corresponding LED lights.
[7] Extension device connecting
connector cover
[8] Operation status display LEDsThe operation status of the PLC can be checked with the LEDs.
[9] Output display LEDs (red)When an output terminal (Y000 or more) is turned on, the corresponding LED lights.
[10] Model name (abbreviation)The model name of the main unit is indicated.
[11] DIN rail mounting hooksThe main unit can be installed on DIN46277 rail (35mm (1.38") wide).
[12] The year and month of productionThe year and month of production of the main unit is indicated.
The peripheral device connector, variable analog potentiometers and RUN/STOP switch
are located under this cover.
Mount the expansion board and memory cassette under this cover.
cover.
Keep the covers closed while the PLC is running (the unit power is on).
Connect the extension cables of input/output powered extension unit/block or special
function block to the extension device connecting connectors under this cover.
FX3U Series extension devices and FX2N Series extension devices can be connected.
The LEDs turn off, light and flash according to the following table.
LED nameDisplay colorDescription
POWGreenOn while power is on the PLC.
RUNGreenOn while the PLC is running.
ERR
ALMRed
Check the nameplate on the right side for the model name.
[10]
→
For details on the year and month of production, refer to Subsection 5.1.2
[12]
→ For details on the operation status, refer to Section 14.5.
RedFlashing when a program error occurs.
RedLights when a CPU error occurs.
[5]
[6]
[7]
[8]
[9]
→ For details on the extension devices, refer to
Chapter 15, Chapter 16, Chapter 17 and Section 18.1.
Lights when the battery voltage drops.
(When the optional battery is used)
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
.
9
Preparation and
Power Supply
Wiring
31
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
When the top covers are open
2 Features and Part Names
2.2 Names and Functions of Parts
[6][5][4]
[3]
[2]
[7]
[8]
[1]
[9][10]
[1] Peripheral device connecting
connector (USB)
[2] Peripheral device connecting
connector (RS-422)
[3] RUN/STOP switchTo stop writing (batch) of the sequence program or operation, set the switch to STOP
[4] Variable analog potentiometersTwo variable analog potentiometers are built in.
[5] Optional equipment connector1Connect the expansion board and memory cassette to the connector.
[6] Optional equipment connector2
(40 points, 60 points type only)
[7] Battery connectorConnect the optional battery to the connector.
[8] Battery holderThis holder accommodates the optional battery.
[9] Optional equipment connecting
screw holes2 (2 places)
(40 points, 60 points type only)
[10] Optional equipment connecting
screw holes1 (2 places)
Connect a programming tool (PC) to program a sequence.
→ For details on applicable peripheral devices, refer to Chapter 5.
Connect a programming tool to program a sequence.
→ For details on applicable peripheral devices, refer to Chapter 5.
(slide it downward).
To start operation (run the machine), set it to RUN (slide it upward).
Upper side : VR1, Lower side : VR2
Connect the expansion board, display module and memory cassette to the connector.
These holes are designed to secure the expansion board and memory cassette with
screws.
These holes are designed to secure the expansion board and memory cassette with
screws.
When the terminal block covers are open
[2]
[1]
[5]
[1] Power supply terminalConnect the power supply to the main unit.
[2] Terminal block mounting
screws
[3] Input (X) terminalsWire switches and sensors to the terminals.
[4] Output (Y) terminalsWire loads (contactors, solenoid valves, etc.) to be driven to the terminals.
[5] Terminal coverA protective terminal cover (refer to the following drawing) is fitted to the lower stage of
If the main unit must be replaced, loosen the screws (slightly loosen the left and right
screws), and the upper part of the terminal block can be removed.
→ For anchoring of the terminal block, refer to Subsection 9.1.2.
each terminal block.
The cover prevents fingers from touching terminals, thereby improving safety.
[3]
[4]
[2]
32
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2.2.2Sides
2 Features and Part Names
2.2 Names and Functions of Parts
1
Introduction
Left side
[1]
[1] Connector conversion adapter
connecting screw holes1 (2 places)
[2] NameplateThe product model name, control number and power supply specifications are shown.
[3] DIN rail mounting grooveThe unit can be installed on DIN46277 rail (35 mm (1.38") wide).
These holes are designed to secure the connector conversion adapter with screws.
Right side
[2]
[3]
→
For details on the manufacturer's serial number, refer to Subsection 5.1.1.
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
33
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
3.1 List of Products and Interpretation of Model Names
3.Introduction of Products
3.1List of Products and Interpretation of Model Names
The following system configuration is classified into product groups A to O in the product introduction sections
given below.
Display module
E
FX3G-5DM
F
Expansion boards
InputOutput
FX3G-4EX-BD
Communication
FX
3G
-232-BD
3G
-422-BD
FX
3G
-485-BD
FX
FX3G-485-BD-RJ
FX
3G
-2EYT-BD
Analog
FX3G-2AD-BD
3G
-1DA-BD
FX
Analog volume
3G
-8AV-BD
FX
Battery
KL
FX3U-32BLFX3G-EEPROM-32L
3 Introduction of Products
Memory cassettes
Special adapters
HC
Analog
FX
3U
-4AD-ADP
3U
-4DA-ADP
FX
3U
-3A-ADP
FX
FX
3U
-4AD-PT-ADP
3U
-4AD-PTW-ADP
FX
3U
-4AD-PNK-ADP
FX
3U
-4AD-TC-ADP
FX
Communication
FX
3U
-232ADP(-MB)
3U
-485ADP(-MB)
FX
3U
-ENET-ADP
FX
Connector
G
conversion
adapter
3G
FX
-CNV-ADP
A
FX3G-14MR/ES
3G
FX
3G
FX
3G
FX
FX3G-14MR/DS
3G
FX
3G
FX
3G
FX
JJ
FX0N-30EC
FX
Input/output powered
B
FX
2N
-
32ER-ES/UL
2N
-48ER-ES/UL
FX
2N
-48ER-UA1/UL
FX
2N
-32ER
FX
2N
-48ER
FX
2N
-32ES
FX
2N
-
32ET-ESS/UL
FX
2N
-48ET-ESS/UL
FX
FX
2N
-32ET
2N
-48ET
FX
extension units
Input/output
FX
FX
FX
FX
2N
-
48ER-DS
2N
-48ER-D
2N
-
48ET-DSS
2N
-48ET-D
D
Main units
Input/output
-24MR/ES
-40MR/ES
-60MR/ES
-24MR/DS
-40MR/DS
-60MR/DS
FX3G-14MT/ES(S)
FX
FX
FX
FX3G-14MT/DS(S)
FX
FX
FX
Extension cables
0N
-65EC
Special function blocks
Analog
3U
-4AD
FX
FX
3U
-4DA
3U
-4LC
FX
2N
-2AD
FX
2N
-2DA
FX
2N
-4AD
FX
2N
-4AD-TC
FX
2N
-4AD-PT
FX
2N
-4DA
FX
2N
-5A
FX
2N
-8AD
FX
2N
-2LC
FX
3G
-24MT/ES(S)
3G
-40MT/ES(S)
3G
-60MT/ES(S)
3G
-24MT/DS(S)
3G
-40MT/DS(S)
3G
-60MT/DS(S)
FX Series terminal blocks can be connected to
connector type units.
Connector conversion adapter
FX
2N
-CNV-BC
Network
FX3U-16CCL-M
3U-64CCL
FX
FX2N-16CCL-M
2N-32CCL
FX
2N-64CL-M
FX
To Network
Input/output extension blocks
InputOutput
FX
2N
-8EX-ES/UL
FX
2N
-8EX
FX
2N
-8EX-UA1/UL
FX
2N
-16EX-ES/UL
FX
2N
-16EX
FX
2N
-16EX-C
FX
2N
-16EXL-C
Input/output
FX
2N
-8ER-ES/UL
FX
2N
-8ER
FX
FX
FX
FX
FX
FX
FX
FX
FX
FX
FX
FX
2N
-8EYR-ES/UL
2N
-8EYR-S-ES/UL
2N
-8EYT-ESS/UL
2N
-8EYR
2N
-8EYT
2N
-8EYT-H
2N
-16EYR-ES/UL
2N
-16EYT-ESS/UL
2N
-16EYR
2N
-16EYT
2N
-16EYT-C
2N
-16EYS
34
Extension power supply unit
I
FX
3U
-1PSU-5V
Power supply unit
O
FX
2N
-20PSU
The configuration is remote I/O for CC-Link.
N
Remote I/O
FX Series terminal block
M
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
3.1.1Main units
The main unit incorporates a CPU, memory, input and output terminals and power supply.
To establish a system, at least one main unit is necessary.
A
FX
3G
Series name
Total number of input
and output points
Model name
AC power supply common to 24V DC sink and source input
*1.Each value inside ( ) indicates the number of occupied points.
M
Main unit
Number of input/output points
Total number
of points
14(16)
14(16)
14(16)
24(32)
24(32)
24(32)
60(64)
60(64)
60(64)
14(16)
14(16)
14(16)
24(32)
24(32)
24(32)
60(64)
60(64)
60(64)
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
*1
Number of
input points
14(16)
14(16)
14(16)
36(40)
36(40)
36(40)
14(16)
14(16)
14(16)
36(40)
36(40)
36(40)
3 Introduction of Products
3.1 List of Products and Interpretation of Model Names
Incorporating power supply, CPU, memory and input/output
Power supply, Input/output type: Connection on terminal block
R/ES : AC power supply/24V DC (sink/source) input/Relay output
T/ES : AC power supply/24V DC (sink/source) input/Transistor (sink) output
T/ESS: AC power supply/24V DC (sink/source) input/Transistor (source) output
R/DS : DC power supply/24V DC (sink/source) input/Relay output
T/DS : DC power supply/24V DC (sink/source) input/Transistor (sink) output
T/DSS: DC power supply/24V DC (sink/source) input/Transistor (source) output
The input/output powered extension unit incorporates a power supply circuit and input and output terminals.
It is designed to add input and output terminals.
B
It can supply power to extension devices connected on the downstream side.
3 Introduction of Products
3.1 List of Products and Interpretation of Model Names
FX
2N
Series name
Total number of input
and output points
Model name
AC power supply common to 24V DC sink and source input
Power supply, Input/output type: Connection on terminal block
·R : AC Power supply/24V DC (sink) input/Relay output
·S : AC Power supply/24V DC (sink) input/Triac (SSR) output
·T : AC Power supply/24V DC (sink) input/Transistor (sink) output
·R-ES: AC Power supply/24V DC (sink/source) input/Relay output
Input/output
extension
Number of input/output points
of points
·T-ESS: AC Power supply/24V DC (sink/source) input/Transistor (source) output
·R-UA1: AC Power supply/100V AC input/Relay output
·R-DS: DC Power supply/24V DC (sink/source) input/Relay output
·T-DSS: DC Power supply/24V DC (sink/source) input/Transistor (source) output
·R-D: DC Power supply/24V DC (sink) input/Relay output
·T-D: DC Power supply/24V DC (sink) input/Transistor (sink) output
Number of
input points
Number of
output points
Incorporating power supply and input/output terminals
Classification 1: None: Not compliant with standard
UL:Compliant with standard
Input typeOutput type
Connection
form
36
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
3.1.3Input/output extension blocks
The input/output extension block has built-in input or output terminals to add input or output terminals.
Connect the input/output extension block to the main unit or input/output powered extension unit.
Peripheral device connector [USB]
USB Mini-B connector [USB2.0]
Peripheral device connector [RS-422]
MINI DIN 8Pin
Expansion board connector
FX3U-64CCL CC-Link connection terminal block
Accessing the other station from CC-Link is used.
→ Refer to Subsection 3.2.4.
When FX-232AW or FX-232AWC is used, the communication baud rate is 19,200 bps or less.
→ For details, refer to Subsection 3.2.3.
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
41
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
3.2.1Programming tool
The following programming tools support FX3G Series PLCs.
Model nameDescription
GX Works2
GX Developer
FX-30PFX-30P (From first version) supports FX3G PLCs (Ver. 1.10 or later)
Version 1.07H or later of SW DNC-GXW2-J supports the FX3G.
Version 1.08J or later of SW DNC-GXW2-E supports the FX3G.
Version 8.72A or later of SW D5C-GPPW-J and SW D5C-GPPW-E supports FX3G.
Although the tool earlier than version 8.72A can be used for programming by selecting FX1N(C), restrictions
will be made on programming.
→ For more information, refer to 5. Version Information and Peripheral Equipment Connectability.
3.2.2Communication cables
3 Introduction of Products
3.2 Connector Types and Cables for Program Communication
1
2
3
4
5
Model nameDescription
USB cable
3m
USB cable
RS-232C cable
F2-232CAB-1
F2-232CAB
F2-232CAB-2
FX-232CAB-1
FX-232CAB-2
RS-422 cable
FX-422CAB0
FX-20P-CAB0
*1
1
4
1
1
5
5
2
3
USB A plug USB Mini-B plug
(9’10")
For connection between personal computer and FX3G programming port (USB)
3m
D-SUB 9Pin D-SUB 25Pin
(9’10")
For connection between personal computer and RS-232C/RS-422 converter
3m
D-SUB 25Pin D-SUB 25Pin
(9’10")
For connection between personal computer and RS-232C/RS-422 converter
3m
Half-pitch 14-pin D-SUB 25Pin
(9’10")
For connection between personal computer and RS-232C/RS-422 converter
D-SUB 9Pin D-SUB 9Pin
3m
For connection between personal computer and RS-232C/RS-422 converter FX3G-232-BD,
(9’10")
FX3U-232ADP(-MB)
Half-pitch 14-pin D-SUB 9Pin
3m
For connection between personal computer and RS-232C/RS-422 converter FX3G-232-BD,
(9’10")
FX3U-232ADP(-MB)
D-SUB 25Pin MINI DIN 8Pin
1.5m
For connection between RS-232C/RS-422 converter and FX3G programming port (RS-422),
(4’11")
FX3G-422-BD
1.5m
MINI DIN 8Pin MINI DIN 8Pin
(4’11")
For connection between FX-30P and FX3G programming port (RS-422), FX3G-422-BD
*1.The following USB cables are applicable.
Model nameDescription
MR-J3USBCBL3MUSB cable 3m(9’10")
GT09-C30USB-5PUSB cable to transfer personal computer data (USB A plug) 3m(9’10")
3.2.3Converters and interface
Model nameDescription
RS-232C/RS-422 Converters
RS-232C/RS-422 converter (high-speed type)
Communication speed: Applicable to 9,600 to 115,200 bps .
RS-232C/RS-422 converters
Communication speed: Applicable to 9,600/19,200 bps
42
FX-232AWC-H
FX-232AW
FX-232AWC
*1
*1.When the programming software is not applicable to FX3G, the converter is applicable only to 9,600 or
19,200 bps.
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
3.2 Connector Types and Cables for Program Communication
3.2.4The accessing path to the FX3G from CC-Link
The FX3G connected to the FX3U-64CCL can be accessed via CC-Link from the FX master station (FX3U-
16CCL-M) and Q CPU (Q mode) master/local station when GX Works2 is used.
Accessing permits read, write, verify, device batch monitoring and device test.
The communication path of CC-Link is illustrated as follows.
→ For details, refer to the manual of GX Works2 or GX Developer
1) The path when accessing from the FX
3U-16CCL-M
3 Introduction of Products
1
Introduction
2
Features and
Part Names
PC
(GX Works2)
*1
FX
main unit
CC-Link
3G
FX3U-16CCL-M
FX
3G
main unit
FX
3U-64CCL
2) The path when accessing from the master QCPU (Q mode) station
PC
GX Works2
etc.
*1
CC-Link
QCPU
(Q mode)
Q
master
station
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
FX
3G
main unit
FX3U-64CCL
3) The path when accessing from a local QCPU (Q mode) station
Q
master
station
FX
3G
main unit
FX3U-64CCL
PC
GX Works2
etc.
*1
CC-Link
QCPU
(Q mode)
Q
local
station
QCPU
(Q mode)
*1.Direct connection or connection using the GOT transparent mode.
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
43
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.1 Generic Specifications
4.Specifications, External Dimensions and Terminal
Layout (Main Units)
This Chapter explains the specifications, external dimensions and terminal layout of the main units.
→ For the specifications for the input/output powered extension units, refer to Chapter 15.
→ For the specifications for the input/output extension blocks, refer to Chapter 16.
4.1Generic Specifications
ItemSpecifications
Ambient temperature
Ambient humidity5 to 95%RH (no condensation) when operating
Vibration resistance
Shock resistance*1147m/s2 Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
Noise resistanceBy noise simulator at noise voltage of 1,000Vp-p, noise width of 1 s, rise time of 1ns and period of 30 to 100Hz
Dielectric withstand
voltage
Insulation resistance
Grounding
Working atmosphere Free from corrosive or flammable gas and excessive conductive dust
Working altitude
*1.The criterion is shown in IEC61131-2.
*2.For more information on the dielectric withstand voltage test and the insulation resistance test of the
terminals of each product, refer to the following.
*3.Ground the PLC independently or jointly.
0 to 55 C (32 to 131 F) when operating and -25 to 75 C (-13 to 167 F) when stored
Frequency(Hz)
When installed on
*1
DIN rail
When installed
directly
1.5kV AC for one minute
500V AC for one minute
5M or more by 500V DC megger
Class D grounding (grounding resistance: 100 or less)
<Common grounding with a heavy electrical system is not allowed>
*4
< 2000m
PLC
Other
equipment
10 to 57-0.035
57 to 1504.9-
10 to 57-0.075
57 to 1509.8-
PLC
Acceleration(m/s2)
Between each terminals and ground terminal
Other
equipment
Half amplitude(mm)
*3
PLC
Sweep Count for
X, Y, Z: 10 times
(80 min in each
direction)
*2
→ Refer to Subsection 4.1.1.
→ Refer to Section 9.3.
Other
equipment
44
Independent grounding
Best condition
Shared grounding
Good condition
Common grounding
Not allowed
*4.The PLC cannot be used at a pressure higher than the atmospheric pressure to avoid damage.
FX3G Series Programmable Controllers
4 Specifications, External Dimensions and Terminal Layout (Main Units)
User's Manual - Hardware Edition
4.1.1Dielectric withstand voltage test and insulation resistance test
Perform dielectric withstand voltage test and insulation resistance test at the following voltage between each
terminals and the main unit ground terminal.
4.1 Generic Specifications
1
Introduction
Between terminalsDielectric strength
Terminals of main unit and input/output powered extension unit/block
Between power supply terminal (AC power
supply) and ground terminal
Between power supply terminal (DC power
supply) and ground terminal
Between 24V DC service power supply
connected to input terminal (24V DC) and
ground terminal
Between input terminal (100V AC) and
ground terminal
Between output terminal (relay) and ground
terminal
Between output terminal (transistor) and
ground terminal
Between output terminal (triac) and ground
terminal
Terminals of expansion board, special adapter and special function block
Between terminal of expansion board
(Except FX3G-4EX-BD and FX3G-2EYT-BD)
and ground terminal
Between FX3G-4EX-BD input terminal
(24V DC) and ground terminal
Between FX3G-2EYT-BD output terminal
(transistor) and ground terminal
Between terminal of special adapter and
ground terminal
Special function blockEach manual
1.5kV AC for 1min
500V AC for 1min
1.5kV AC for 1min
500V AC for 1min-
1.5kV AC for 1minOnly input/output powered extension unit/block
Not allowedNot allowed
500V AC for 1min
Insulation
resistance
5M or more
on 500V DC
Megger
5M or more
on 500V DC
Megger
Remarks
-
-
-
Only input/output powered extension unit/block
-
Since the expansion board and the main unit
CPU are not insulated, it is not allowed to
perform the dielectric withstand voltage test and
insulation resistance test between them.
-
-
-
Refer to the manual for each special function
block.
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
45
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4.2Power Supply Specifications
The specifications for the main unit power supply are explained below.
For the power (current) consumed by the special function blocks, refer to this manual or the special function
units/blocks manual.
4.2.1AC Power Supply Type
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.2 Power Supply Specifications
Item
Supply voltage100 to 240V AC
Allowable supply
voltage range
Rated frequency50/60Hz
Allowable
instantaneous power
failure time
Power fuse250V 1A250V 3.15A
Rush current30A max. 5ms or less/100V AC, 50A max. 5ms or less/200V AC
Power consumption
24V DC service power
*2
supply
FX3G-14M /EFX3G-24M /EFX3G-40M /EFX3G-60M /E
85 to 264V AC
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
*1
31W32W37W40W
400mA
*1.This item shows values when all 24V DC service power supplies are used in the maximum
configuration connectable to the main unit, and includes the input current (5 or 7mA per point).
*2.When input/output extension blocks are connected, the 24V DC service power changes the current
consumed by the point (number) of the block connected.
4.2.2DC Power Supply Type
Item
Supply voltage24V DC
Allowable supply
voltage range
Allowable
instantaneous power
failure time
Power fuse125V 2.5A125V 3.15A
Rush current30A max. 1ms or less/24V DC
Power consumption
24V DC service power
supply
*1.There power consumption values are maximum values which include consumption of all expansion
equipment and input current (5 or 7 mA per point).
FX3G-14M /DFX3G-24M /DFX3G-40M /DFX3G-60M /D
20.4 to 28.8V DC
Operation can be continued upon occurrence of instantaneous power failure for 5 ms or less.
*1
19W21W25W29W
Specifications
→ For details on the 24V DC service power supply, refer to Subsection 6.5.
Specifications
-
46
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4.3Input Specifications
The main unit input specifications are explained below.
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.3 Input Specifications
1
Introduction
4.3.124V DC Input (sink/source)
The input numbers in the table indicate the main unit terminal numbers. "X010 or more" means the numbers
from X010 to the largest number that the main unit has.
Standard mode*3 : 0.5 s to several hundred s/instruction
Extension mode*3 : 1.2 s to several hundred s/instruction
128 points or less
128 points or less
128 points or less-
256 points or less
M1536 to M76796144 points-
S1000 to S40953096 points-
Available as analog timers
VR1 : D8030
VR2 : D8031
→
For the writing function during running, refer to Subsection 5.2.5.
(3)Total points
The device numbers are octal.
S0 to S910 points-
T192 to T1998 points0.1 to 3,276.7 sec
T246 to T2494 points0.001 to 32.767 sec
T250 to T2556 points0.1 to 3,276.7 sec
C0 to C1516 pointsCounting from 0 to 32,767
(1) + (2) (3) total number of points is
128 or less.
50
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
ItemPerformance
16 bits up
(EEPROM keep)
Counter
High-speed
counter
Data register
(32 bits when
paired)
Extension
register
Extension file
register
Pointer
NestingFor master controlN0 to N78 pointsFor MC instructions
Constant
*1.The current time of the clock is backed up by the capacitor built-in the PLC. Supply the power to the
PLC for 30 minutes or more to completely charge this large-capacity capacitor.
(The capacitor works for 10 days (atmosphere: 25 C )
The current time can be backed up by the battery when the optional battery is incorporated.
*2.These devices can be changed to the keep (battery backup) type using a parameter when the optional
battery is used.
*3.The standard mode is selected when the program capacity is set to 16000 steps or less using a
parameter.
The extension mode is selected when the program capacity is set to 16001 steps or more using a
parameter.
*4.Supported in Ver. 1.10 or later
32 bits up/down
(For general)
32 bits up/down
(EEPROM keep)
1-phase 1-count input in
both directions
(32 bits up/down)
(EEPROM keep)
1-phase 2-count input in
both directions
(32 bits up/down)
(EEPROM keep)
2-phase 2-count input in
both directions
(32 bits up/down)
(EEPROM keep)
For general (16 bits)D0 to D127128 points-
For EEPROM keep (16 bits)D128 to D1099972 points-
For general*2 (16 bits)
File register
(EEPROM keep)
For special (16 bits)D8000 to D8511512 points-
For index (16 bits)
For general
For EEPROM keep (16 bits)ER0 to ER2399924000 points
For branching of JUMP and
CALL
Input interruption
Timer interruption
Decimal number (K)
Hexadecimal number (H)
Real number (E)
*2
(16 bits)
*4
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.5 Performance Specifications
C16 to C199184 pointsCounting from 0 to 32,767
C200 to C21920 points
C220 to C23415 points
C235 to C245
C246 to C250
C251 to C255
D1100 to D79996900 points-
D1000 to D7999
V0 to V7
Z0 to Z7
R0 to R2399924000 points-
P0 to P20472048 points
I0 to I5
I6 to I8
16bits-32,768 to +32,767
32bits-2,147,483,648 to +2,147,483,647
16bits0 to FFFF
32bits0 to FFFFFFFF
32bits
Counting from -2,147,483,648 to +2,147,483,647
Maximum 7000
points
16 points-
6 points
3 points
128
-1.0 x 2
Decimal-point and exponential notations are possible.
to -1.0 x 2
Counting from -2,147,483,648 to
+2,147,483,647
Can be set as file registers in units of
500 points from D1000 in the program
area (EEPROM) using parameters.
Stored in the EEPROM built-in the main
unit, or stored in the EEPROM in the
memory cassette when the memory
cassette is used.
For CJ instructions and CALL
instructions
-
-126
, 0 , 1.0 x 2
-126
to 1.0 x 2
128
→ For details on the battery, refer to Chapter 22.
→ For the parameter setting method, refer to Chapter 22.
→ For parameter settings, refer to the Programming Manual.
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
51
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4 Specifications, External Dimensions and Terminal Layout (Main Units)
The external dimensions of the main unit are explained.
4.6.1Main units
2- 4.5 mounting holes
SeriesModel nameW: mm (inches)W1: mm (inches)MASS (weight): kg (lbs)
FX3G-14M
FX3G-24M
FX3G-40M
FX3G-60M
W1(mounting hole pitch)
W
FX3G-14MR/ES
FX3G-14MT/ES
FX3G-14MT/ESS
FX3G-14MR/DS
FX3G-14MT/DS
FX3G-14MT/DSS
FX3G-24MR/ES
FX3G-24MT/ES
FX3G-24MT/ESS
FX3G-24MR/DS
FX3G-24MT/DS
FX3G-24MT/DSS
FX3G-40MR/ES
FX3G-40MT/ES
FX
FX
FX3G-40MT/DS
FX3G-40MT/DSS
FX
FX
FX
FX
FX
FX
90(3.55")
82(3.23")(mounting hole pitch)
3G-40MT/ESS
3G-40MR/DS
3G-60MR/ES
3G-60MT/ES
3G-60MT/ESS
3G-60MR/DS
3G-60MT/DS
3G-60MT/DSS
Unit: mm (inches)
86(3.39")
90 (3.55")82 (3.23")0.50 (1.10 lbs)
90 (3.55")82 (3.23")0.55 (1.21lbs)
130 (5.12")122 (4.81")0.70 (1.54 lbs)
175 (6.89")167 (6.58")0.85 (1.87 lbs)
1) Accessories
Dust proof protection sheet
Manual supplied with product
2) Installation
35mm(1.38") wide DIN rail or Direct installation (with screws) (M4 x 2)
8(0.32")
52
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4.7Terminal Layout
The terminal layout in the main unit is shown below.
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.7 Terminal Layout
1
Introduction
4.7.1Interpretation of terminal block layout
Input terminalPower supply terminals
X3S/S X1
X2NLX4X5X6X7X10
X0
FX3G-40MT/ES
0V
24V
24V DC service
power supply
• Indication of Power supply terminals
The AC power supply type has [L] and [N] terminals.
The DC power supply type has [] and [ ] terminals.
For external wiring, make sure to read the power supply wiring described later.
• Indication of 24V DC service power supply
The AC power supply type has [0V] and [24V] terminals, whereas the DC power supply type shows [•]
since the DC power supply type does not have the service power supply.
Do not connect with [•] terminals.
For external wiring, make sure to read the power supply wiring described later.
• Indication of Input terminal
Both AC and DC power supply type have the same input terminals, however, the external input wiring
differs from each other.
For external wiring, make sure to read the input wiring described later.
• Indication of output terminals connected to common terminal
One common terminal covers 1, 2, 3 or 4 output points.
The output numbers (Y) connected to a common terminal are enclosed with heavy partition lines.
For transistor output (source) type, [COM ] is [+V ].
Y2Y0
Y1Y4Y10
COM1 COM2COM0
Y3
Common terminal
(4 points/common
terminal)
X11
X12
Y6
COM3
Y7
Y5Y11
X13
X15
X14
COM4
Output
terminal
X17
X21
X16
X20
Output terminals
connected to COM5
Y12
Y13
X23
X22
Y14
COM5
X25
X24
X26
Y16
Y15
Y17
Partition
X27
[ ·
] Vacant terminal (Do not use.)
→ Refer to Chapter 9.
→ Refer to Chapter 9.
→ Refer to Chapter 10.
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
53
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4.7.2FX3G-14M
• AC power supply type
S/SNLX1X2X3X4X5X6X7
X0
FX3G-14MR/ES, FX3G-14MT/ES
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.7 Terminal Layout
0V
24V
FX3G-14MT/ESS
0V
24V
Y1Y4
COM1 COM2COM0COM3Y3COM4Y5COM5
Y1Y4
+V1 +V2
+V0
• DC power supply type
S/S X1X2X3X4X5X6X7
X0
FX3G-14MR/DS, FX3G-14MT/DS
Y1Y4
COM1 COM2COM0COM3Y3COM4Y5COM5
3G
-14MT/DSS
FX
Y1Y4
+V1 +V2+V0+V3Y3+V4Y5+V5
4.7.3FX3G-24M
• AC power supply type
S/SNLX1X2X3X4X5X6X7
X0
Y2Y0
Y2Y0
+V3Y3+V4Y5+V5
Y2Y0
Y2Y0
X10
X11
X12
X13
X14
X15
FX3G-24MR/ES, FX3G-24MT/ES
Y2Y0
0V
24V
FX3G-24MT/ESS
0V
24V
Y1Y5
COM1 COM2COM0COM3
Y1Y5
+V1 +V2+V0+V3
Y3
Y4
Y2Y0
Y3
Y4
• DC power supply type
S/S X1X2X3X4X5X6X7
X0
FX3G-24MR/DS, FX3G-24MT/DS
Y2Y0
Y3
Y4
Y2Y0
Y3
Y4
FX
3G
Y1Y5
COM1 COM2COM0COM3
-24MT/DSS
Y1Y5
+V1 +V2+V0+V3
COM4
+V4
X11
X10
Y6Y7Y10
COM4
Y6Y7Y10
+V4
Y6Y7Y10
Y11
Y6Y7Y10
Y11
X13
X12
X14
Y11
Y11
X15
54
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
4.7.4FX3G-40M
• AC power supply type
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.7 Terminal Layout
1
Introduction
X3S/S X1
X2NLX4X5X6X7X10
X0
FX
3G-40
24V
FX
24V
0V
3G-40
0V
MR/ES, FX
Y1Y4Y10
COM1 COM2COM0
MT/ESS
Y1Y4Y10
+V1 +V2+V0
Y2Y0
Y2Y0
3G-40
Y3
Y3
COM3
+V3
• DC power supply type
X3S/S X1
X2 X4X5X6X7X10
X0
FX3G-40MR/DS, FX3G-40MT/DS
Y2Y0
Y1Y4Y10
FX
3G
COM1 COM2COM0
-40MT/DSS
Y1Y4Y10
+V1 +V2+V0
COM3
Y3
Y2Y0
+V3
Y3
X11
X13
X15
X12
X14
MT/ES
Y6
COM4
Y7
Y5Y11
Y6
+V4
Y7
Y5Y11
X11
X13
X15
X12
X14
Y6
COM4
Y7
Y5Y11
Y6
+V4
Y7
Y5Y11
X16
X16
X17
Y12
Y12
X17
Y12
Y12
X20
Y13
Y13
X21
X20
Y13
Y13
X21
X23
X22
Y14
COM5
Y14
+V5
X23
X22
Y14
COM5
Y14
+V5
X24
Y15
Y15
X25
X24
Y15
Y15
X25
Y16
Y16
X26
Y16
Y17
Y16
X26
Y17
Y17
X27
Y17
X27
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
4.7.5FX3G-60M
• AC power supply type
S/S
X1X2X3X4X5X6X7
X0
NL
FX3G-60MR/ES, FX3G-60MT/ES
0V
24V
FX3G-60MT/ESS
0V
24V
• DC power supply type
FX3G-60MR/DS, FX3G-60MT/DS
FX
3G
Y1Y4
COM1 COM2COM0
Y1Y4
+V1 +V2+V0
S/S X1X2X3X4X5X6X7
X0
Y1Y4Y10Y14Y20
COM1 COM2COM0
-60MT/DSS
Y1Y4Y10Y14Y20
+V1 +V2+V0
6
System
Configuration
X11
X13
X15
X17
X21
X23
X25
X27
X31
X33
X35
X37
X41
X43
X10
X12
X14
X16
X20
X22
X24
X26
X30
X32
X34
X36
X40
X42
7
Input/Output
Nos., Unit Nos.
Y2Y0
Y3
Y2Y0
Y3
Y2Y0
Y3
Y2Y0
Y3
Y6
COM3
Y5
Y7
Y6
+V3
COM3
+V3
Y7
Y5
X11
X10
X12
Y6
Y7
Y5Y11
Y6
Y7
Y5Y11
Y12
Y10Y14Y20
COM4
+V4
X13
X14
COM4
+V4
Y13
Y11
Y12
Y10Y14Y20
Y13
Y11
X15
X17
X21
X16
X20
Y12
Y13
Y12
Y13
COM5
+V5
X23
X22
COM5
+V5
Y16
Y15
Y16
X25
X24
Y16
Y15
Y16
Y17
Y17
X26
Y17
Y17
X27
COM6
+V6
X31
X30
COM6
+V6
Y21
Y21
X32
Y21
Y21
Y22
Y22
X33
Y22
Y22
Y23
Y23
X34
Y23
Y23
X35
Y24
COM7
Y24
+V7
X37
X36
Y24
COM7
Y24
+V7
Y25
Y25
X40
Y25
Y25
Y26
Y26
X41
Y26
Y26
Y27
Y27Y15
X42
Y27
Y27Y15
X43
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
55
FX3G Series Programmable Controllers
r
r
User's Manual - Hardware Edition
5 Version Information and Peripheral Equipment Connectability
5.1 Version Information
5.Version Information and Peripheral Equipment
Connectability
5.1Version Information
5.1.1Manufacturer's serial number check method
The year and month of production of the product can be checked on the name plate, and on the front of the
product.
1. Checking the nameplate
The year and month of production of the product can be checked from the manufacturer's serial number S/N
indicated on the label adhered to the right side of the product.
Example nameplate (manufacturer's serial number: 1010001)
PROGRAMMABLE
CONTROLLER
Right side
MITSUBISHI
MODEL
FX3G-40MT/ES
100-240VAC 50/60Hz 37W
OUT:5~30VDC 0.5A
S/N
1010 0 01
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
Actual product nameplate differs
*
from the example shown above.
<Product from January, 2010><Product during December, 2009 or earlier>
9Z000
Month (Example: Dec.):
1 to 9 = January to September,
X = October, Y = November, Z = December
Year (Example: 2009): Last digit of yearYear (Example: 2010): Last two digit of year
1
Control number
011000
Month (Example: Jan.):
1 to 9 = January to September,
X = October, Y = November, Z = Decembe
1
Control number
2. Checking the front of the product
The year and month of production of the product can be checked from the manufacturer's serial number
"LOT" on the front (at the bottom) of the product.
* Products manufactured in and after October 2008 and after.
56
<Product during December, 2009 or earlier>
<Product from January, 2010>
9Z101
Month (Example: Dec.):
1 to 9 = January to September,
X = October, Y = November, Z = December
Year (Example: 2009): Last digit of year
Year (Example: 2010): Last two digit of year
Month (Example: Jan.):
1 to 9 = January to September,
X = October, Y = November, Z = Decembe
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
5.1.2Version check method
The PLC version can be checked by reading the last three digits of device D8001/D8101.
5 Version Information and Peripheral Equipment Connectability
• Supports connection of following expansion boards:
FX3G-2AD-BD, FX3G-1DA-BD, FX3G-8AV-BD
• Supports connection of display module (FX3G-5DM).
• Supports of the inverter communication function.
• Supports of the pulse width measurement function.
• Supports connection of following special adapter:
FX3U-3A-ADP
• Supports the hardware error function of FX3U-4DA-ADP.
• Supports of the MODBUS communication function.
• Supports the following instruction.
ADPRW(FNC276)
• Supports the following instruction.
IVMC(FNC275)
• Supports the following functions of the FX3U-16CCL-M:
- Network parameter
- Accessing the other station from CC-Link
- Remote device station initialization procedure registration
- CC-Link diagnostics
• Supports connection of following special adapter:
3U-ENET-ADP
FX
• Special parameter error (M8489 and D8489) is added.
• Supports the IP address change function of FX3U-ENET-ADP.
• Supports connection of following expansion boards:
FX
3G-4EX-BD, FX3G-2EYT-BD
3G PLC)
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
57
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.2Programming Tool Applicability
5.2.1Applicable versions of programming tool
1. GX Works2
• GX Works2 English version (SW DNC-GXW2-E) is applicable to FX3G PLCs from the following versions.
5.2 Programming Tool Applicability
FX3G PLC version
Before Ver. 1.40
Ver. 2.00Ver. 1.87R or later
Model name
(Media model name is
shown below.)
GX Works2
SW DNC-GXW2-E
• GX Works2 Japanese version (SW DNC-GXW2-J) is applicable to FX
Applicable GX Works2
version
Ver. 1.08J or later
Remarks
-Before Ver. 2.00Ver. 1.62Q or later
3G PLCs from the following
versions.
FX3G PLC version
Before Ver. 1.40
Before Ver. 2.00Ver. 1.56J or later
Ver. 2.00Ver. 1.86Q or later
Model name
(Media model name is
shown below.)
GX Works2
SW DNC-GXW2-J
Applicable GX Works2
version
Ver. 1.07H or later
Remarks
-
The setting of the FX3U-ENET-ADP is supported in
Ver. 1.90U or later.
2. GX Developer
• GX Developer English version (SW D5C-GPPW-E) is applicable to FX3G PLCs from the following
versions.
FX3G PLC version
Before Ver. 1.10
Ver. 1.10Ver. 8.78G or later
Model name
(Media model name is
shown below.)
GX Developer
SW D5C-GPPW-E
• GX Developer Japanese version (SW D5C-GPPW-J) is applicable to FX
versions.
Applicable
GX Developer version
Ver. 8.72A or later
Remarks
-
3G PLCs from the following
Model name
FX3G PLC version
Before Ver. 1.10
Ver. 1.10Ver. 8.76E or later
(Media model name is
shown below.)
GX Developer
SW D5C-GPPW-J
Applicable
GX Developer version
Ver. 8.72A or later
3. FX-30P
FX-30P is applicable to FX3G PLCs from the following version.
FX3G PLC versionModel name
Ver. 1.00FX-30PVer. 1.00 or later
Applicable
FX-30P version
Remarks
-
Remarks
• FX-30P (From first version) supports FX3G PLCs
(Ver. 1.10 or later).
• The IVMC instruction is supported in FX-30P Ver.
1.50 or later.
58
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.2.2In the case of programming tool (version) not applicable
Inapplicable programming tools can be used by selecting an alternative PLC model.
1. Alternative model setting
Model to be programmedModel to be setPriority High Low
FX3G PLCFX3G
*1."FX2N" is selected when the FX-10P(-E) is used.
FX1N
*1
2. Contents of restrictions
• Programming is enabled only for the range of functionality available in the PLC selected as the alternative
model, such as instructions, device ranges and program sizes. When the FX-10P(-E) is used, the range of
functionality is limited to that available in the FX
• Use a programming tool that can select either FX
register capacity, etc.
• The built-in USB port cannot be used for programming communication.
2N PLC.
3G to change parameters, i.e. memory capacity, file
5.2.3Program transfer speed and programming tools
5.2 Programming Tool Applicability
FX2N
*1
FX2
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
1. Built-in USB communication
The FX3G PLC has a built-in USB communication port, and performs program writing, program reading and
monitoring at high speed (12 Mbps) with a personal computer that supports USB.
1) Supported programming tools
GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later)
2) In programming tools not supporting USB
Communication is performed via RS-422 or RS-232C.
2. RS-422/RS-232C communication
The FX3G PLC can write and read programs and perform monitoring at 115.2 kbps through RS-422/RS-232C
communication.
1) 115.2 kbps supported programming tools
GX Works2 (Ver. 1.08J or later), GX Developer (Ver. 8.72A or later), FX-30P (Ver. 1.00 or later)
2) 115.2 kbps supported interfaces
- Standard built-in port (RS-422) or expansion board FX
When the RS-232C/RS-422 converter FX-232AWC-H is connected.
- Expansion board FX
- Special adapter FX
3) In programming tools not supporting 115.2 kbps
Communication is executed at 9,600 or 19,200 bps.
3G-232-BD for RS-232C
3U-232ADP(-MB) for RS-232C
3G-422-BD for RS-422
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
59
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
5 Version Information and Peripheral Equipment Connectability
5.2 Programming Tool Applicability
5.2.4Cautions on connecting peripheral equipment by way of expansion board or special
adapter
When connecting peripheral equipment (programming tool or GOT [CPU direct connection]) by way of the
3G-232-BD, FX3G-422-BD or FX3U-232ADP(-MB), set the connection channel (CH1 or CH2) as follows. If
FX
the connection channel is not specified with the status below, communication error may occur in the
connected peripheral equipment.
→ For details, refer to the Data Communication Edition.
- Set to "K0" the special data register for communication format setting of the channel connecting the
peripheral equipment (CH1: D8400 or D8120, CH2: D8420).
- Set the communication parameter "PLC system [2]" of the channel connecting the peripheral equipment
to "Not set" (as shown in the window below).
5.2.5Cautions on write during RUN
In FX3G PLCs, write during RUN (program changes in the RUN mode) is enabled using the following
programming tools.
→ For the operating procedure of and cautions on write during RUN,
Programming tools supporting write during RUN
• English version
Programming toolVersionRemarks
GX Works2
(SW DNC-GXW2-E)
GX Developer
(SW D5C-GPPW-E)
FX-PCS/WIN-E
*1
*2
*2
Ver. 1.08J or later
Ver. 1.62Q or later
Ver. 2.00A or later
Ver. 5.00A or later
Ver. 8.72A or later
Ver. 8.78G or later
Ver. 3.00 or later
Leave this unchecked.
refer to the manual of the used programming tool.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
earlier than Ver. 1.40.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.40.
Writing in the instruction and device ranges during RUN is supported in FX2N PLCs
Ver. 1.00.
Writing in the instruction and device ranges during RUN is supported in FX1N PLCs
Ver. 1.00.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
earlier than Ver. 1.10.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.10.
Writing in the instruction and device ranges during RUN is supported in FX1N PLCs
Ver. 1.00.
60
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
• Japanese version
Programming toolVersionRemarks
GX Works2
(SW DNC-GXW2-J)
GX Developer
(SW D5C-GPPW-J)
FX-PCS/WIN
*1
*2
*2
*1.Write during RUN is not possible with a SFC program.
*2.Write during RUN is not possible with a list program or a SFC program.
Cautions on write during RUN
Ver. 1.07H or later
Ver. 1.56J or later
Ver. 2.00A or later
Ver. 5.00A or later
Ver. 8.72A or later
Ver. 8.76E or later
Ver. 4.00 or later
5 Version Information and Peripheral Equipment Connectability
5.2 Programming Tool Applicability
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
earlier than Ver. 1.40.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.40.
Writing in the instruction and device ranges during RUN is supported in FX
Ver. 1.00.
Writing in the instruction and device ranges during RUN is supported in FX1N PLCs
Ver. 1.00.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
earlier than Ver. 1.10.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.10.
Writing in the instruction and device ranges during RUN is supported in FX1N PLCs
Ver. 1.00.
2N PLCs
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
ItemCaution
Program memories which can be
written in RUN mode
•GX Works2
Number of
program steps
which can be
written for
circuit change
in RUN mode
Circuit blocks which cannot be written
in RUN mode
Ver. 1.08J or later
•GX Developer
Ver. 8.72A or later
•GX Developer
Ver. 8.70Y or
former
• FX-PCS/WIN(-E)
Built-in EEPROM and optional memory cassette (whose write protect switch is set to OFF)
256 steps or less after edition (addition/deletion) (including NOP
immediately after circuit blocks except final circuit)
127 steps or less after edition (addition/deletion) (including NOP
immediately after circuit blocks except final circuit)
Circuit blocks*1 in which labels P and I are added, deleted or changed in edited circuits
Circuit blocks in which 1-ms timers (T246 to T249 and T256 to T319) are added in edited circuits
Circuit blocks in which the following instructions are included in edited circuits
• Instruction to output high-speed counters C235 to C255 (OUT instruction)
• TBL (FNC152) instruction
*1.Circuit blocks cannot be edited to insert a label as shown below when written during RUN.
Step
0
FNC 04
EI
Added, deleted, or changed
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
Pointer for
interrupt
I001
FNC 06
FEND
Label I is inserted by editing the circuit block
Added, deleted, or changed
FNC 03
IRET
END
61
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
ItemCaution
Avoid write during RUN to a circuit block including the following instructions during execution.
If write during RUN is executed to such a circuit block, the PLC decelerates and stops pulse
output.
Avoid write during RUN to a circuit block including the following instruction during execution.
If write during RUN is executed to such a circuit block, the PLC immediately stops pulse output.
Avoid write during RUN to a circuit block including the following instructions during execution of
communication.
If write during RUN is executed to such a circuit block, the PLC may stop communication after that.
If the PLC stops communication, set the PLC to the STOP mode once, and then set it to the RUN
mode again.
Circuit blocks which cannot be
written in RUN mode
When write during RUN is completed for a circuit including an instruction for falling edge pulse
(LDF, ANDF, or ORF instruction), the instruction for falling edge pulse is not executed without
regard to the ON/OFF status of the target device.
When write during RUN is completed for a circuit including an instruction for falling edge pulse
(PLF instruction), the instruction for falling edge pulse is not executed without regard to the ON/
OFF status of the device that is set as the operation condition.
It is necessary to set to ON the target device or operation condition device once and then set it
to OFF for executing the instruction for falling edge pulse.
• Instructions for rising edge pulse
When write during RUN is completed for a circuit including an instruction for rising edge pulse,
the instruction for rising edge pulse is executed if a target device of the instruction for rising
edge pulse or the operation condition device is ON.
Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse operation type applied
instructions (such as MOVP)
5 Version Information and Peripheral Equipment Connectability
5.2 Programming Tool Applicability
Circuit blocks which require attention
on operation after write during RUN
Others
Contact ON/OFF status
(while write during RUN is executed)
OFFNot executedNot executed
ON
*1 The PLS instruction is not executed.
Writing in RUN mode to circuit blocks including the following instructions results in the following
operation
• MEP instruction (Conversion of operation result to leading edge pulse instruction)
When completing Write during RUN to a circuit including the MEP instruction, the execution
result of the MEP instruction turns ON (conducting state) if the operation result up to the MEP
instruction is ON.
• MEF instruction (Conversion of operation result to trailing edge pulse instruction)
When completing Write during RUN to a circuit including the MEF instruction, the execution
result of the MEF instruction turns OFF (nonconducting state) regardless of the operation result
(ON or OFF) up to the MEF instruction.
When the operation result up to the MEF instruction is set to ON once and then set to OFF, the
execution result of the MEF instruction turns ON (conducting state)
Operation result up to MEP/MEF instructionMEP instructionMEF instruction
OFF
ONON (conducting)
• When writing during RUN with GX Works2 Ver. 1.08J or later, GX Developer Ver. 8.72A or
later, the program is as follows.
When the number of program steps is reduced by deletion of contacts, coils and applied
instructions, the program capacity becomes smaller by as many as the reduced number of
steps.
• Errors cannot be detected in write during RUN even in a circuit which causes errors.
Errors are detected after the PLC is stopped once, and then run again.
Instruction for
rising edge pulse
Executed
OFF (nonconduct-
*1
ing)
Instruction for
falling edge pulse
Not executed
OFF (nonconduct-
ing)
OFF (nonconduct-
ing)
62
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
5 Version Information and Peripheral Equipment Connectability
5.3Use of (Built-in USB) Programming Port
Make sure to set the contents described in this section when executing circuit monitor, device registration
monitor, program reading/writing, etc. in the FX
Works2, GX Developer Ver. 8.72A or later. For GX Developer is prior to Ver. 8.72A, communication using the
(built-in USB) programming port is not available.
5.3.1Installation of USB driver
It is necessary to install the USB driver to execute USB communication using the (built-in USB) programming
port.
For the USB driver installation method and procedure, refer to the following manual.
5.3.2Setting in GX Developer
3G PLC using the (built-in USB) programming port and GX
→ GX Works2 Version 1 Operating Manual (Common)
→ GX Developer Version 8 Operating Manual (Startup)
5.3 Use of (Built-in USB) Programming Port
1
Introduction
2
Features and
Part Names
3
Product
Introduction
1. Select [Online] [Transfer setup...] to open the "Transfer setup" dialog box.
2. Double-click [Serial USB] in [PC side I/F] to open the "PC side I/F Serial setting" dialog box.
3. Select "USB (Built-in port)".
Double-click it.
Select "USB (Built-in port)"
4. Click the [OK] button to finish the setting.
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
63
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
A
User's Manual - Hardware Edition
5.4 Cautions on using transparent function by way of USB in GOT1000 Series
5 Version Information and Peripheral Equipment Connectability
5.4Cautions on using transparent function by way of USB in GOT1000
Series
When monitoring circuits, device registration, etc. or reading/writing programs in an FX3G PLC from GX
Developer Ver.8.22Y or later using the transparent function by way of USB in the GOT1000 Series, make
sure to execute the following setting.
If the following setting is not provided, a communication error occurs.
GX Developer Ver.8.21X or former
When using transparent function by way of
USB in GOT1000 Series
When using transparent function by way of
RS-232 in GOT1000 Series
When directly connecting GX Developer to
PLC
Not supported (not available)Setting shown below is required.
Set "COM port" and "Transmission speed"
on "PC side I/F Serial setting" dialog box.
*1.GX Developer Ver.8.72A or later supports the FX
3G Series.
GX Developer Ver8.22Y or later
Select "RS-232C" in setting shown below,
and set "COM port" and "Transmission
speed".
Setting in GX Developer (Ver. 8.22Y or later)
1. Select [Online] [Transfer setup...] to open the "Transfer setup" dialog box.
2. Double-click [Serial] in [PC side I/F] to open the "PC side I/F Serial setting" dialog box.
3. Select "USB (GOT Transparent mode)".
Double-click it.
*1
display screen is the example of Ver.8.72A.
4. Click the [OK] button to finish the setting.
Select "USB (GOT
transparent mode)"
64
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
5.5 Cautions on using transparent port (2-port) function of GOT-F900 Series
5 Version Information and Peripheral Equipment Connectability
5.5Cautions on using transparent port (2-port) function of GOT-F900
Series
When monitoring circuits, device registration, etc. in an FX3G PLC from GX Developer Ver. 8.72A or later
using the transparent (2-port) function in the GOT-F900 Series, make sure to execute the following setting.
If the following setting is not provided, write to PLC, read from PLC, verify with PLC, etc. operate normally, but
monitoring (ladder monitor, entry data monitor, etc.) cannot be normally executed.
GX Developer Ver. 8.12N or earlier GX Developer Ver. 8.22Y or later GX Developer Ver. 8.72A or later
When directly
connecting GX Developer
to PLC
When using transparent
function in GOT-F900
Series
Set "COM port" and "Transmission
speed" on "PC side I/F Serial
setting" dialog box.
Setting shown below is not required.
Setting in GX Developer (Ver. 8.22Y or later)
Select "RS-232C" on "PC side I/F
Serial setting" dialog box, and set
"COM port" and "Transmission
speed."
Setting shown below is not
required.
Select "RS-232C" on "PC side I/F
Serial setting" dialog box, and set
"COM port" and "Transmission
speed."
Select "RS-232C" on "PC side I/F
Serial setting" dialog box, and
execute setting shown below.
1
Introduction
2
Features and
Part Names
3
Product
Introduction
1. Select [Online] [Transfer setup...] to open the "Transfer Setup" dialog box.
2. Double-click [PLC module] in [PLC side I/F] to open the [PLC side I/F Detailed setting of PLC
module] dialog box.
3. Put a check mark to the check box [via GOT-F900 transparent mode] as shown below
Double-click it.
Put a check mark to the
check box "via GOT-F900
transparent mode."
A display screen is the example of Ver. 8.72A.
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
4. Click the [OK] button to finish the setting.
65
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
5 Version Information and Peripheral Equipment Connectability
User's Manual - Hardware Edition
5.6Other Peripheral Equipment Applicability
5.6.1Other Peripheral Equipment Applicability
Model nameApplicabilityRemarks
Standard monitor OS, communication driver and option OS which support the FX3G PLC
are required.
For details, refer to the GOT manual.
This series is subject to the following restrictions when connected using unsupported
standard monitor OS, communication driver or option OS.
5.6 Other Peripheral Equipment Applicability
GOT1000 SeriesApplicable
F940WGOTNot available
F940GOT F940 Handy GOT Not available
F930GOT(-K)Not available
F920GOT(-K)Not available
ET-940Not available
FX-10DM(-SET0)Not available
FX-10DUNot available
Contents of restrictions
• Programming is enabled only in the function ranges such as instructions, device ranges
and program sizes available in the FX1N and FX1NC PLCs.
• The list editor function for MELSEC-FX is not available. When using the list editor
function for MELSEC-FX, upgrade the standard monitor OS, communication driver and
option OS to the version compatible with the FX3G PLC.
Check the applicability of other items in the GOT manual.
The following restriction applies when connected.
Contents of restrictions
Programming is enabled only in the function ranges such as instructions, device ranges
and program sizes available in the FX1N and FX1NC PLCs.
For applicable models, refer to the GOT manual.
For connection using the 2-port interface function*1, refer to Section 5.5.
The following restriction applies when connected.
Contents of restrictions
Programming is enabled only in the function ranges such as instructions, device ranges
and program sizes available in the FX1N and FX1NC PLCs.
For supported models and device ranges, refer to the FX-10DM USER'S MANUAL
(JY992D86401).
The following restriction applies when connected.
Contents of restrictions
It is limited to the device range and function range supported by the highest class model
(FX
1N or FX2N) applicable in the product version.
For supported models and device ranges, refer to the FX-10DU-E/FX-20DU-E User's
Manual (JY992D54801).
*1.The F940GOT and ET-940 whose version is former than Ver. 1.10 do not support the transparent (2-
port) function of the GX Developer.
66
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.Examination of System Configuration
6.1Configuration of a Whole System
The configuration of a whole system is shown below as an example.
Configuration of whole system
Expansion board/Special adapters/Memory cassette
1
Display module/Connector conversion adapter
Memory cassette
Special
adapters
Expansion board
Connector conversion
adapter
*1
Display module
Main unit
FX3G-40MT/ES
X000 to X027
Determination of number of
extension devices to be connected
2
to main unit
Input extension
FX
X030 to X047
6 Examination of System Configuration
6.1 Configuration of a Whole System
Extension devices for
2N/FX3U Series
FX
Output
block
2N-16EX
extension block
FX2N-16EYT
-
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
Determination of number of devices to be connected to extension unit/
4
extension power supply unit
FX2N input/output powered
extension unit
Extension power supply unit
FX
FX Series terminal block
6
*3
2N-32ER-ES/UL
X050 to X067
Y040 to Y057
Refer to Chapter 19.
Y000 to Y017
Selection of extension cable
3
Extension devices for FX2N/FX3U Series
*4
Input extension
FX2N-16EX-C FX2N-16CCL-M
X070 to X107
block
*2
function block
Special
Unit No.0
Range of devices powered from
The range of devices powered from
the FX
extension unit or the extension
When CC-Link is used
5
Y020 to Y037
main unit
Refer to this chapter.
2N input/output powered
power supply unit
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
*1.The connector conversion adapter is required to use a special adapter.
*2.Included in the number of units connectable to the main unit when the input extension block (including
2N-8ER-ES/UL and FX2N-8ER) is used and the extension power supply unit is located on the
the FX
upstream side.
*3.When using an input/output extension unit, select a power supply type that is the same as the main
unit.
*4.Available when the main unit is the AC power supply type.
The connection positions and number of expansion boards, connector conversion adapter and memory
cassette configuration vary depending on the number of points in main units. For details, refer to the
description below.
• In the case of the main units (40/60 point type)
Connector conversion adapter
BD1 1st position
BD1 2nd position
BD2 1st position
BD2 2nd position
Model name
Expansion board
(Except for the FX3G-4EX-BD,
FX3G-2EYT-BD, FX3G-8AV-BD)
*1.Can be connected in either position only one device can be at one time.
*2.The memory cassette cannot be connected when the display module is connected to the BD (1st
position).
*3.The display module cannot be connected when the memory cassette is connected to the BD (1st
position).
Available connection position
BD (1st position)BD (2nd position)
-
*1*1*2
*1*1*3
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
69
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.2Rules of System Configuration
The system configuration must meet the following four requirements.
1Number of input/output points
The total number of input and output points should be 256 or less in the whole system.
→ For details, refer to 6.3 Number of Input/Output Points and Maximum Number of Input/Output
Number of input/output points on whole systemUp to 256 points
1. Number of input/output points (including input/output occupied points)Up to 128 points
6 Examination of System Configuration
6.2 Rules of System Configuration
Points.
· Expansion board
· Special adapter
Remote I/O station Remote I/O station Remote I/O station Remote I/O station
2. Number of remote I/O pointsUp to 128 points
Remote I/O station Remote I/O station Remote I/O station Remote I/O station
Main unit
Input/output
extension
unit/block
CC-Link/LT
CC-Link system
Special
function
block
CC-Link/LT
master
CC-Link master
2Number of connected special extension devices
The figure below shows the number of connectable expansion boards, special adapters, extension
power supply units
ADP) is required as the expansion board when special adapters are connected.
→ For details, refer to 6.4 Number of Connected Extension Devices (Including Extension Cable).
•FX
3G Main units (40/60 point type)
Special
adapter
(analog)
*1
and special function blocks. The connector conversion adapter (FX3G-CNV-
Special adapter
(communication)
Expansion
board
Main unit
40/60 point type
Input/output
powered
extension unit
Extension
power supply
unit
*1
function block
Special
70
Up to 2 unitsUp to 2 unitsUp to 2 unitsOnly 1 unitUp to 2 units
3G Main units (14/24 point type)
•FX
Special
adapter
(analog)
Special adapter
(communication)
Expansion
board
Only 1 unitOnly 1 unitOnly 1 unitOnly 1 unitUp to 2 units
Main unit
14/24 point type
*1.Available when the main unit is the AC power supply type.
Input/output
powered
extension unit
Extension
power supply
unit
*1
Up to 8 units
Special
function block
Up to 8 units
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6 Examination of System Configuration
6.2 Rules of System Configuration
3Connection restriction and calculation of current consumption
The number of points and number of units connected are restricted by the number of extension
blocks connected to the main unit.
The built-in power supply of the input/output powered extension unit and extension power supply
unit supplies the power to a unit/block/board extended to the corresponding unit. The built-in power
supply refers to the 24V DC service power supply, 5V DC power supply and internal 24V DC power
supply. The consumed power varies depending on the type of extended unit/block/board.
Special
adapter
Power supply
from main unit
Expansion
board
Main unit
Extension block
(some blocks can
be connected)
Power supply
from main unit
Input/output
powered
extension
unit
Extension block
(some blocks can
be connected)
Power supply from
input/output powered
extension unit
Extension
power supply
unit
Extension block
(some blocks can
be connected)
Power supply from
extension power
supply unit
*1
1
Introduction
2
Features and
Part Names
3
Product
Introduction
Refer to Section 6.4.
*1.When connecting an input extension block on the downstream side of an extension power supply unit,
supply the power to the input extension block from the nearest main unit on the upstream side, or from
an input/output powered extension unit on the upstream side of the extension power supply unit.
The extension power supply unit is available only when the main unit is a AC power supply type.
In the example above, the input/output powered extension unit supplies the power to extension
blocks.
→ For details, refer to 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V).
Refer to Section 6.5.Refer to Section 6.6.Refer to Section 6.7.
→ For details, refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit.
4Other restrictions
• Restrictions in the use of the FX3G-422-BD
- When connecting a device (such as GOT) which consumes an internal 5V DC to each of the RS-422
port built in the main unit and the FX
If both devices are used continuously, their life may be shortened due to heat generation.
<Configuration example 1>
RS-422 port built-in main unit + GT1020LBL (5V DC type)
3G-422-BD + GT1020LBL (5V DC type)
FX
Avoid continuous use of two GT1020LBL (5V DC type) units.
- When connecting a device (such as GOT) which consumes an internal 5V DC to each of two FX
BD units connected to the (40-point/60-point type) main unit, avoid continuous use of either device.
If both devices are used continuously, their life may be shortened due to heat generation.
→ For details, refer to 6.5 Expansion of Main Unit.
3G-422-BD at the same time, avoid continuous use of either device.
3G-422-
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
<Configuration example 2>
When connecting the 40-point type main unit and two FX
3G-422-BD + GT1020LBL (5V DC type)
FX
3G-422-BD + GT1020LBL (5V DC type)
FX
Avoid continuous use of two GT1020LBL (5V DC type) units.
- It is not allowable to connect a device (such as GOT) which consumes an internal 5V DC to each of the
RS-422 port in the (40-point/60-point type) main unit and two FX
the same time.
• Restrictions in the use of an input/output powered extension unit
When using an input/output extension unit, select a power supply type that is the same as the main unit.
3G-422-BD units
3G-422-BD units (3 channels in total) at
71
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
6 Examination of System Configuration
6.3Number of Input/Output Points and Maximum Number of Input/Output
Points
6.3.1Calculation of number of input/output points
To obtain the total number of input/output points, count the input/output points of input/output powered
extension units/blocks and the input/output occupied points of special function blocks.
The number of remote I/O points on CC-Link network must be excluded.
1Total the number of input/output points on the main unit and the number of
those on the input/output powered extension units/blocks.
To obtain the total number of input/output points, count the input points (X000 and more) and output
points (Y000 and more) of the main unit and input/output powered extension units/blocks.
The number of input/output points of each type of device is shown on the list below.
→ The list of numbers of input/output points is shown in Section 6.8.
2Count the input/output points of the remote I/O stations connected on FX2N-
64CL-M network.
Add the number of remote I/O points to the number of input/output points from the main unit and
input/output powered extension units/blocks calculated in the above step.
→ For the remote I/O point calculation method, refer to the FX2N-64CL-M manual.
3Count the number of input/output occupied points of special function blocks.
The number of occupied input/output points per unit is 8.
The number of occupied input/output points of each type of device can be obtained by the following
formula or from the list shown below.
→ For a list of occupied input/output points, refer to Section 6.8.
Number of special function
blocks
units
Number of special function
blocks
Observe the following instructions when using the following products.
•FX
3U-16CCL-M (CC-Link master)
Only one FX3U-16CCL-M unit can be connected to a single PLC main unit.
This master cannot be used together with FX
•FX
2N-16CCL-M (CC-Link master)
When more than one master station is connected, a remote I/O station cannot be connected to the 2nd and
following master stations.
This master cannot be used together with FX
•FX3U-64CCL
Only one FX3U-64CCL unit can be connected to a single PLC main unit.
Number of points per unit
8 points
Each special function block
used for FROM/TO instructions
occupies eight input or output
points.
2N-16CCL-M.
3U-16CCL-M.
Number of occupied
input/output points
Total number of
=
occupied input/
output points
points
72
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
4Calculate the total number of input/output points.
Total the number of points counted in Steps 1, 2 and 3, and check that it does not exceed 128
points (maximum number of input/output points).
Maximum number of
input/output points
Number of input/output points
6 Examination of System Configuration
Number of input/output occupied
points
1
Introduction
2
Features and
Part Names
128 points
Maximum number of
points controllable on
system
(A) : Number of input/output points of main unit
(B) : Number of input/output points of input/
output powered extension units
(C) : Number of input/output points of input/
output extension blocks
(A)(B)(C)
+
Total number of input/output points of input/
output powered extension units and input/output
extension blocks
++
(D)
(D) : Number of remote I/O points of FX
(E) : Number of special function blocks
(E) units
+
Each special function unit/block
used for FROM/TO instructions
occupies eight input or output
points.
2N
-64CL-M
5When CC-Link master is used, count the remote I/O points.
When CC-Link is used, the total number of input/output points of the remote I/O stations connected
on the network and the number of input/output points calculated in the previous step are 256 or
less.
3U-16CCL-M, FX2N-16CCL-M (CC-Link master)
1. FX
Calculate the number of remote I/O points connected on the network in the following step.
8 points
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
73
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.3 Number of Input/Output Points and Maximum Number of Input/Output Points
6 Examination of System Configuration
6.3.2Maximum number of input/output points when CC-Link master is used
1. Calculation of maximum number of input/output points
When CC-Link master block is used, the following maximum number of input/output points can be connected.
Maximum number of
input/output points
Number of input/
output points
Number of input/output
occupied points
CC-Link remote I/O
256 points
Maximum number
of points
controllable on
system
(A) : Number of input/output points of main unit
(B) : Number of input/output points of input/output
powered extension units
(C) : Number of input/output points of input/output
extension blocks
(A)(B)(C)(D)
Total number of
input/output points
For details, refer to Subsection 6.3.1.
(E) units
Number of points occupied
by special function blocks
(D) : Number of remote I/O points of FX
(E) : Number of input/output points occupied by special function blocks
(F) : Number of remote I/O stations (units) connected to CC-Link
master
8
points
(F) stations
Total number of points obtained by formula
++
"number of remote I/O stations 32 points"
(The number is multiplied by 32 points
regardless of the number of remote I/O
points.)
2N
-64CL-M
32
points
128
points
*1.The number of CC-Link points is calculated by the formula "32 points number of stations" even when
remote I/O stations having less than 32 points are used.
For details, refer to the manual of the CC-Link master block used.
2. Procedures for calculating number of input/output points based on example of system
configuration
For the main unit, input/output powered extension units/blocks and CC-Link remote I/O stations, the number
of input/output points and the total number of points are restricted.
X000 to X027
Main unit
Y000 to Y017
24/16=40
points
X030 to X047
Input/output
powered
extension unit
Y020 to Y037
16/16=32
points
X050 to X067
Input
extension
block
-
16/0=16
points
X070 to X077
Input
extension
block
-
8/0=8 points
-
Special
function block
-
8 points8 points
-
FX3U-16CCL-M
-
*1
CC-Link network
Remote I/O
(32 points)
Number of input/output points occupied by
special function blocks(16 points)
0 points
Number of input/output points
(96 points)
Number of input/output points (excluding remote I/O points on
CC-Link) + Number of input/output occupied points
Up to 128 points
11296
Number of
remaining
points
256 points or less in total
Number of
remaining
points
Remote I/O
(32 points)
160
Number of CC-Link input/output points
Remote I/O
(32 points)
32 points 3 units = 96 points
128 points or less in total
256 points128
74
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.4 Number of Connected Extension Devices (Including Extension Cable)
6 Examination of System Configuration
6.4Number of Connected Extension Devices (Including Extension Cable)
6.4.1Number of connectable expansion boards and special adapters
1
Introduction
The number of connectable expansion boards and special adapters varies depending on the number of points
in the main unit. The connector conversion adapter (FX
→ For assignment of communication channels, refer to Section 7.3.
• In the case of Main units (40/60 point type)
Use of expansion board
When expansion board is not used0
When expansion board is used
Number of connectable
expansion boards
Communication expansion board
3G-4EX-BD, FX3G-2EYT-BD,
FX
1 unit
FX3G-8AV-BD
Analog expansion board
2 units
*1.Only one FX3G-4EX-BD, FX3G-2EYT-BD and FX3G-8AV-BD can be connected to a single PLC main unit.
*2.Only one FX3U-ENET-ADP can be connected to a single PLC main unit.
• In the case of Main units (14/24 point type)
Use of expansion board
When expansion board is not used01 unit1 unit
When expansion board is used1 unitCannot be connected.Cannot be connected.
Number of connectable
expansion boards
6.4.2Input/output powered extension units
2
Features and
3G
-CNV-ADP) is required to connect the special adapter.
Number of connectable special adapters of each type
Communication
special adapters
*2
2 units
1 unit2 units
*2
2 units
*1
Cannot be connected.Cannot be connected.
Number of connectable special adapters of each type
Communication
special adapters
Analog special adapters
Analog
special adapters
2 units
1 unit
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
Up to 2 input/output powered extension units can be connected in one system.
6.4.3Extension Power Supply Unit
Only one extension power supply unit (FX3U-1PSU-5V) unit can be connected to a single PLC main unit.
Available when the main unit is the AC power supply type.
6.4.4Special function blocks
Up to 8 special function units/blocks can be connected in one system.
When connecting the following products, take into consideration the combination, number of units/blocks and
connecting order.
TypeLimitations
FX3U-16CCL
FX2N-16CCL-M
FX3U-64CCL• Only one FX3U-64CCL unit can be connected to a single PLC main unit.
FX2N-2AD
FX2N-2DA
• Only one FX3U-16CCL-M unit can be connected to a single PLC main unit.
• This master cannot be used together with FX2N-16CCL-M.
• When some units are used, a remote I/O station cannot be connected to the second and following master stations.
• This master cannot be used together with FX3U-16CCL-M.
When any of these products is connected to a FX2N Series input/output powered extension unit, the current
consumption is restricted.
The total current consumption of FX2N-2AD and FX2N-2DA must be the following value or less.
-FX2N-32E : 190mA or less
-FX2N-48E : 300mA or less
6.4.5Extension cable
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
One extension cable can be used in a system.
The FX
•FX
•FX
2N-CNV-BC is required when the extension block is connected.
0N-65EC(650mm(25.59"))
0N-30EC(300mm(11.81"))
75
10
Input Wiring
FX3G Series Programmable Controllers
6 Examination of System Configuration
User's Manual - Hardware Edition
6.5Expansion of Main Unit
The extendibility of the main unit varies depending on the power supply type (AC power supply type or DC
power supply type). Select proper extension devices in accordance with the power supply type of the main
unit used.
In the case of AC power type main unit
The allowable extension to the AC power supply type main unit varies depending on used extension blocks
as described below.
1. When connecting only the input/output extension block
Input/output extension blocks of up to 32 points can be connected.
However, when the extension power supply unit (FX3U-1PSU-5V) is used and the main unit is the nearest
upstream unit to the extension power supply unit, make sure that the number of points including the input
extension block (including the FX
does not exceed 32.
2. When connecting the input/output extension block and special function block
2N-8ER-ES/UL and FX2N-8ER) extended to the extension power supply unit
6.5 Expansion of Main Unit
Input/output extension blocks of up to 16 points can be connected.
However, when the extension power supply unit (FX3U-1PSU-5V) is used and the main unit is the nearest
upstream unit to the extension power supply unit, make sure that the number of points including the input
extension block (including the FX
does not exceed 16.
Only 1 special function block can be connected.
2N-8ER-ES/UL and FX2N-8ER) extended to the extension power supply unit
3. When connecting only the special function block
Up to 2 special function blocks can be connected.
When extension of the above points 1 to 3 is carried out and further extension is required, determine whether
extension is possible using one of the following methods:
• Using the 24V DC service power supply (400mA) of the main unit
• Using an input/output powered extension unit
• Using an extension power supply unit
For details, refer to the following.
→ Refer to 6.5.1 When adding input/output extension blocks using the 24V DC service power supply
of the main unit.
→ Refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit.
→ Refer to 6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V).
76
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6 Examination of System Configuration
In the case of DC power type main unit
The allowable extension to the DC power supply type main unit varies depending on used extension blocks
as described below.
1. When connecting only the input/output extension block
Input/output extension blocks of up to 32 points can be connected.
2. When connecting the input/output extension block and special function block
Input/output extension blocks of up to 16 points can be connected.
Only 1 special function block can be connected.
3. When connecting only the special function block
Up to 2 special function blocks can be connected.
6.5 Expansion of Main Unit
1
Introduction
2
Features and
Part Names
3
Product
Introduction
When extension of the above points 1 to 3 is carried out and further extension is required, determine whether
extension is possible using one of the following methods:
For details, refer to the following.
→ Refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit.
6.5.1When adding input/output extension blocks using the 24V DC service power supply
of the main unit
When extension is prohibited in the AC power supply type main unit due to restrictions in connection
described above, it is possible to add extension blocks using the 24V DC service power supply of the main
unit.
For adding extension blocks using the 24V DC service power supply, it is necessary to examine again
whether extension is possible for all of extension blocks selected in the preceding subsection and extension
blocks to be selected in this subsection.
Note that only up to two network-related special function blocks can be connected including extension to the
main unit.
1Confirm the priority of all extension blocks to be connected to the main unit.
The priority is set to each extension block to be connected, and required to judge the possibility of
extension to the main unit. The priority is determined by the extension block type without regard to
the connection position.
3U
When the extension power supply unit (FX
the extension power supply unit is the main unit, the priority should be considered also for input
2N
extension blocks (including the FX
-8ER-ES/UL and FX2N-8ER) extended to the extension power
supply unit.
-1PSU-5V) is used and the nearest upstream unit to
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
<Priority>
Priority LowPriority High
Special function
block
Output extension
>>>
block
Priority 2Priority 3Priority 1Priority 4
FX2N-8ER-ES/UL
2N
-8ER
FX
Input extension
block
2Judge whether extension to the main unit is possible.
Judge the possibility of extension to the main unit for all extension blocks in turn, starting from the
extension block having the highest priority confirmed in step 1. Consider that 16 input/output points
2N
are provided in each of the FX
ity over 8 input points. For judgment about the possibility of extension to the main unit, refer to the
Section 6.5.
-8ER-ES/UL and FX2N-8ER. Eight output points have higher prior-
77
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6 Examination of System Configuration
6.5 Expansion of Main Unit
3Check whether extension from the 24V DC service power supply is possible.
Check using the quick reference matrix shown below whether the number of points whose extension is judged as impossible in step 2 can be added using the 24V DC service power supply.
A special function block is handled in the same way as 16 output points.
Output
(Example)
Number of
100016
added points
250508
150
400 300 200 10000
08162432
Number of added points
Example: When 8 input points and 8 output points are connected, the current of the 24V DC service
power supply becomes 150mA or less.
Input
4Confirm the current capacity of the 24V DC service power supply from the
value shown in the quick reference matrix.
This remaining power supply capacity (current) can be used as a power supply for external loads
(such as sensors), special adapters and special function blocks by the user.
→ For the current capacity of a special adapter,
refer to the manual for each special adapter.
→ For the current capacity of a special function block,
refer to Subsection 6.8.3.
If it is not possible to connect input/output extension blocks even using the 24V DC service power
supply of the main unit, consider adding an input/output powered extension unit to the system.
→ Refer to 6.6 Expansion of FX2N Series I/O Powered Extension Unit.
78
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6 Examination of System Configuration
6.5 Expansion of Main Unit
6.5.2Selection example 1 using the 24V DC service power supply of the main unit
This subsection explains an example in which 8 input points and 16 output points are added to the following
system configuration using the 24V DC service power supply of the main unit.
<Example of configuration>
Main unit
Input extension
block
8 points
Special function
block
FX
3U
-64CCL
Output extension
block
8 points
Output extension
block
16 points
Input extension
block
8 points
1
Introduction
2
Features and
Part Names
(Special function block 1unit + Input/output 16 points)
Range extendible to main unit
Extension blocks to be added
(Input 8 points + Output 16 points)
1Confirm the priority of all extension blocks to be connected to the main unit.
The priority is determined by the extension block type without regard to the connection position
from the main unit as shown below.
<Priority>
Main unit
Input extension
block
8 points
Priority 3
Special function
block
FX
3U
-64CCL
Priority 1
Output extension
block
8 points
Priority 2
Output extension
block
16 points
Input extension
block
8 points
Priority 3
2Judge whether extension to the main unit is possible.
Judge the possibility of extension to the main unit for all extension blocks in turn, starting from a
block having the highest priority confirmed in step 1.
In this example, due to the restriction "one special extension block and 16 points in input/output
3U
extension block", the only FX
-64CCL (priority 1) and 16 points of the output extension block (pri-
ority 2) can be connected to the main unit.
3Check whether extension from the 24V DC service power supply is possible.
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
Check using the quick reference matrix whether 16 input points and 8 output points whose extension is judged as impossible in step 2 can be added.
Output
Number of
After 16 input points and 8 output points are connected, the remaining current of the 24V DC service power
supply is 50mA or less. Accordingly, it is possible to add 16 input points and 8 output points.
The remaining power supply capacity (50mA) can be used as a power supply for external loads (such as
sensors)
100016
added points
250508
150
400 300 200 10000
08162432
Number of added points
Input
, special adapters and special function blocks by the user.
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
79
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6 Examination of System Configuration
6.5 Expansion of Main Unit
6.5.3Selection example 2 using the 24V DC service power supply of the main unit
This subsection explains an example in which FX2N-2AD and 8 output points are added to the following
system configuration using the 24V DC service power supply of the main unit.
<Example of configuration>
Main unit
Input extension
block
8 points
Special function
block
FX
3U
-64CCL
Output extension
block
8 points
Special function
block
FX
2N
-2AD
Output extension
block
8 points
(Special function block 1unit + Input/output 16 points)
Range extendible to main unit
Extension blocks to be added
(Special function block 1unit + output
8 points)
1Confirm the priority of all extension blocks to be connected to the main unit.
The priority is determined by the extension block type without regard to the connection position
from the main unit as shown below.
<Priority>
Main unit
Input extension
block
8 points
Priority 3
Special function
block
FX
3U
-64CCL
Priority 1
Output extension
block
8 points
Priority 2
Special function
block
FX
2N
-2AD
Priority 1
Output extension
block
8 points
Priority 2
2Judge whether extension to the main unit is possible.
Judge the possibility of extension to the main unit for all extension blocks in turn, starting from a
block having the highest priority confirmed in step 1.
3U
In this example, due to the restriction "two special function blocks", only the FX
2N
1) and FX
-2AD (priority 1) can be connected to the main unit.
-64CCL (priority
3Check whether extension from the 24V DC service power supply is possible.
Check using the quick reference matrix whether 8 input points and 16 output points whose extension is judged as impossible in step 2 can be added.
Output
Number of
After 8 input points and 16 output points are connected, the remaining current of the 24V DC service power
supply is 50mA or less. Accordingly, it is possible to add 8 input points and 16 output points.
100016
added points
250508
150
400 300 200 10000
08162432
Number of added points
Input
80
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.6 Expansion of FX2N Series I/O Powered Extension Unit
6 Examination of System Configuration
6.6Expansion of FX2N Series I/O Powered Extension Unit
When extension is not possible due to the main unit connection restrictions described in the preceding section
and extension of input/output is required, select the input/output powered extension unit.
Since input/output powered extension units have built-in input/output terminals, reexamine the input/output
devices connected to the main unit to ensure the required number of points.
Range to be covered
by main unit
Range exceeding power supply capacity
1
Introduction
2
Features and
Part Names
Before
selection
After
selection
Determine whether extension devices can be connected to the input/output powered extension unit by the
following method.
• When only input/output extension devices are added, use the quick reference matrix.
• When also special extension devices are added, calculate the current consumption to ensure that the total
current to be consumed by the added extension devices can be supplied by the built-in power supply.
→ Refer to 6.6.2 When special extension devices are also added (calculation of current consumption).
Main unit
Main unit
Input/output
extension
block
Input/output
extension
block
→ Refer to 6.6.1 Quick reference matrix (when only input/output devices are added).
Special
function block
Special
function block
Input extension
block
(16 points)
Input/output powered
extension unit
(32 points)
Output extension
block (16 points)
Replaced with input/output
powered extension unit
Special
function block
Special
function block
6.6.1Quick reference matrix (when only input/output devices are added)
In the following quick reference matrix, the value at the intersection of the number of input points to be added
(horizontal axis) with the number of output points to be added (vertical axis) indicates the remaining power
supply capacity.
1Select the input/output extension block (number of points) to be connected
to the main unit.
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
Check that the number of input/output points can be added.
3U
When connecting the FX
upstream unit to the FX
-1PSU-5V extension power supply unit to a system where the nearest
3U
-1PSU-5V is an input/output powered extension unit, include the current
consumption by the input extension blocks (including FX
3U
to the FX
-1PSU-5V when calculating the total current consumption of the input/output powered
extension unit.
1. AC power supply/DC input type
1) FX2N-32ER, FX2N-32ET, FX2N-32ES
FX2N-32ER-ES/UL, FX2N-32ET-ESS/UL
AC power supply
DC input type
FX2N
-32E
(Example) When a 16-input and 0-output point extension block is connected to FX
current of the 24V DC service power supply becomes 150mA or less.
Output
Number of
added points
2524
10050016
175 12575258
0
250 200 150 10050
08162432
Number of added points
(Example)
2N
-8ER-ES/UL and FX2N-8ER) connected
Input
2N-32ER-ES/UL, the
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
81
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2) FX2N-48ER, FX2N-48ET
2N-48ER-ES/UL, FX2N-48ET-ESS/UL
FX
6 Examination of System Configuration
6.6 Expansion of FX2N Series I/O Powered Extension Unit
AC power supply
DC input type
FX2N-48E
Output
Number of
added points
(Example) When a 32-input and 16-output point extension block is connected to FX
current of 24V DC service power supply becomes 110mA or less.
2. DC power supply/DC input type
1) FX2N-48ER-D, FX2N-48ET-D
2N-48ER-DS, FX2N-48ET-DSS
FX
(24V DC service power supply is not provided.)
DC power supply
DC input type
FX2N-48E-D
(Example) When adding 32 inputs to FX
Output
48
40
32
24
Number of
added points
16
8
0
1048
853540
160 110 60 1032
235 185 135853524
310 260 210 160 110601016
385 335 285 235 185 13585358
460 410 360 310 260 210 160 110600
0816243240485664
−
0816243240485664
2N-48ER-DS, a maximum of 24 outputs are expandable
(Example)
Number of added points
(Example)
Number of added points
Input
Input
2N-48ER-ES/UL, the
3. AC power supply/AC input type
1) FX2N-48ER-UA1/UL
(24V DC service power supply is not provided.)
AC power supply
DC input type
FX2N-48ER-UA1/UL
(Example) When adding 24 inputs to FX
Output
48
40
32
24
Number of
added points
16
8
0
(Example)
0816243240485664
Number of added points
2N-48ER-UA1/UL, a maximum of 32 outputs are expandable
Input
82
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.6 Expansion of FX2N Series I/O Powered Extension Unit
6 Examination of System Configuration
2Check the current capacity of the 24V DC service power supply based on the
value shown in the quick reference matrix.
1. In the case of AC power supply/DC input type
The remaining power supply capacity (current) can be used as a power supply to loads (sensors or the like).
When special adapters and special function units/blocks are connected by external wiring, it is necessary to
consider whether they can be covered by the remaining power supply capacity.
2. In the case of DC power supply/DC input type
24V DC service power supply is not provided.
1
Introduction
2
Features and
Part Names
3. In the case of AC power supply/AC input type
24V DC service power supply is not provided.
3When the power supply capacity is insufficient, connect another input/output
powered extension unit.
When two input/output powered extension units or more are connected, calculate the power supply
capacities of the input/output extension blocks and special function blocks connected to them, and
check the capacity.
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
83
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.6 Expansion of FX2N Series I/O Powered Extension Unit
6 Examination of System Configuration
6.6.2When special extension devices are also added (calculation of current
consumption)
1Select an input/output powered extension unit.
→ For the data on the number of input/output occupied points and current consumption of each type,
refer to Section 6.8.
Capacity of built-in power supply
5V DC power
supply [mA]
Power supply
classification
Classification
Number of
connected units
Type
Number of input/
output points
[points]
1 -11 -2
1
With built-in
power
supply
B1
Input/output
powered
extension unit
Example of entry FX
-FX2N-
2N-48ER-ES/UL48690460
2Enter the specifications for the products to be added.
Enter the data for the input/output extension blocks and special function blocks to be connected to
the input/output powered extension unit, and calculate the current.
→ For data on the number of input/output occupied points and current consumption of each type,
refer to Section 6.8.
Calculation of current consumption
of built-in power supply
5V DC power
supply [mA]
2
Power supply
classification
Enter the
products
connected to
the input/
output powered
extension unit
Classification
B2
Input/output
extension
*1
block
C
Special
function
unit/block
Number of
connected
units
-
*2
8
Type
FX2N--
FX2N--
FX2N--
FX2N--
2N--
FX
FX2N--
FX2N--
FX2N--
FX2N/FX3U-
FX2N/FX3U-
FX2N/FX3U-
FX2N/FX3U-
FX
2N/FX3U-
2N/FX3U-
FX
FX
2N/FX3U-
FX2N/FX3U-
Number of input/
output points
[points]
24V DC service
power supply
[mA]
1 -3
24V DC power
supply [mA]
84
2 -12 -22 -3
Calculate the totals
*1.When connecting the FX
3U-1PSU-5V extension power supply unit to a system where the nearest
upstream unit to the FX3U-1PSU-5V is input/output powered extension unit, also enter the current
consumption and number of occupied I/O points for the input extension blocks (including FX
ES/UL and FX
2N-8ER) that are connected to the FX3U-1PSU-5V.
2N-8ER-
*2.A maximum of 8 special function blocks are connectable, including the main unit and extension power
supply unit.
FX3G Series Programmable Controllers
A
A
A
A
User's Manual - Hardware Edition
3Determine whether FX2N-2AD and FX
Determine the number of analog special function blocks (FX2N-2AD and FX2N-2DA) to be connected to the input/output powered extension unit by the following method.
• When connecting to FX2N-32E
Analog special function block
6 Examination of System Configuration
6.6 Expansion of FX2N Series I/O Powered Extension Unit
2N
-2DA can be added.
Total current
consumption
1
Introduction
2
Features and
Part Names
FX2N-2AD
50mA
• When connecting to FX
FX2N-2AD
50mA
units
Analog special function block
units
+
+
FX2N-2DA
85mA
2N-48E
FX2N-2DA
85mA
units
units
=
=
mA
Total current
consumption
mA
190m
300m
4Determine whether the devices can be added to the input/output powered
extension unit.
Calculate the current to confirm whether the selected extension devices can be connected.
1. Calculate the current consumption of the built-in 24V DC power supply (24V DC service
power supply).
The value obtained by this calculation (when the value is positive) indicates the remaining capacity of 24V DC
service power supply, and the capacity can be used for external loads.
Capacity of 24V DC
power supply
Input/output powered
extension unit
1 -3
mA
Current consumption
Total of current consumed by
extension devices
2 -3
-
mA
Calculation result
=
mA
0m
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
2. Calculate the current consumption of the built-in 5V DC power supply.
Capacity of 5V DC
power supply
Input/output powered
extension unit
1 -2
mA
If the calculation results for the current consumption of the 24V DC power supply and 5V DC power supply
are negative values, the current consumption exceeds the capacity of the built-in power supply.
Reconfigure the system, adding input/output powered extension units or extension power supply units.
Current consumption
Total of current consumed by
extension devices
2 -2
-
mA
Calculation result
=
mA
0m
85
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
6 Examination of System Configuration
6.7Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
Select the extension power supply unit for adding special function blocks when extension is prohibited in the
AC power supply type main unit due to restrictions in connection described in Section 6.5.
1Enter the current supply specification of the extension power supply unit.
The output current of the extension power supply unit is proportional to the ambient temperature as
shown by the derating curve below. Enter the output current value, based on this derating curve.
Also verify that the number of occupied input/output points from input/output extension block(s)
connected to the extension power supply unit is less than 32.
Output current [A]
1.0
0.8
0.3
0.2
Derating curve
24V DC
0
Ambient temperature [°C]
5V DC
5540
Capacity of built-in power supply
5V DC power
supply [mA]
3 -1
Power supply for
internal 24V DC
[mA]
3 -2
3
Power supply
classification
With built-in
power supply
Classification
D1
Extension
power supply
unit
Number of
connected
units
-FX3U-1PSU-5V32
Type
2Enter the specifications for the products to be added.
Enter the data on the input/output extension blocks and special function units/blocks to be connected to the input/output powered extension unit, and calculate the current.
→ For the data on the number of input/output occupied points and current consumption of each type,
refer to Section 6.8.
Capacity of built-in power supply
5V DC power
supply [mA]
Power supply for
internal 24V DC
[mA]
Power supply
classification
Enter the
products
connected to
the extension
power supply
unit
Classification
B2
Input/output
extension
*2
block
C
Special
function
unit/block
Number of
connected
units
-
*3
8
Type
FX2N--
FX2N--
FX2N--
FX2N--
FX2N/FX3U--
FX2N/FX3U--
FX2N/FX3U--
2N/FX3U--
FX
FX
2N/FX3U--
2N/FX3U--
FX
FX
2N/FX3U--
FX2N/FX3U--
Connectable I/O
occupied points
[points]
3 -3
Number of
I/O occupied
points
{points]
*1
86
4
Calculate the totals
4 -14 -24 -3
FX3G Series Programmable Controllers
A
A
User's Manual - Hardware Edition
*1.Input/output occupied points by special function blocks are excluded.
*2.For the input extension block (including the FX
calculate the current consumption of the internal 24V DC. Include the input extension block in
calculation for the nearest main unit or input/output powered extension unit located on the upstream
side to the extension power supply unit.
→ When the main unit is on the upstream side, refer to Subsection 6.5.1 and Subsection 6.5.2.
→ When the input/output powered extension unit is on the upstream side, refer to Subsection 6.6.1
*3.A maximum of 8 special function units/blocks are connectable, including the main unit and the input/
output powered extension unit.
6 Examination of System Configuration
6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)
2N-8ER-ES/UL and FX2N-8ER), it is not necessary to
and Subsection 6.6.2.
1
Introduction
2
Features and
Part Names
3Determine whether the devices can be added to the extension power supply
unit.
Calculate the current to confirm whether the selected extension devices can be connected.
1. Calculate the current consumption of the built-in 5V DC power supply.
Capacity of 5V DC
power supply
Extension power
supply unit
3 -1
mA
Current consumption
Total of current consumed
by extension devices
4 -1
-
mA
2. Calculate the available current supply from the internal 24V DC power supply.
Power supply
capacity for internal
24V DC
Extension power
supply unit
3 -24 -2
Current consumption
Total of current consumed
by extension devices
-
mAmA
3. Calculate the available input/output occupied points (excluding the occupied input/output
by special function blocks).
Calculation result
=
Calculation result
=
mA
mA
0m
0m
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
Connectable I/O
occupied points
Extension power
supply unit
3 -3
points
If the calculation result for the 5V DC power supply is a negative value, the current consumption exceeds the
power supply capacity.
If the calculation result for the internal 24V DC is a negative value, the current consumption exceeds the
power supply capacity.
If the calculation result for the number of occupied input/output points is a negative value, the available
number of input/output points is exceeded.
Reconfigure the system with an input/output powered extension unit.
Number of I/O
occupied points
Total of I/O occupied points
by extension devices
4 -3
-
points
Calculation result
points
0points=
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
87
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.8 Number of Input/Output (Occupied) Points and Current Consumption
6 Examination of System Configuration
6.8Number of Input/Output (Occupied) Points and Current Consumption
The following tables show the number of input/output points or the number of input/output occupied points for
each type of device, along with the power supply type and current consumption values needed for selecting a
product.
• Number of input/output points or input/output occupied points on each type of device
• Output current of 24V DC service power supply of main units
• Output current of 5V DC power supply and 24V DC service power supply of input/output powered
extension units
• Current consumed by input/output extension blocks and special function blocks
The current consumption is determined differently in the following cases.
• In the input/output powered extension unit, 5V DC and internal 24V DC are supplied via extension cables.
It is necessary to calculate the current consumption. Subtract the current consumption of the internal 24V
DC from the 24V DC service power supply.
• The special function units/blocks connected to the AC power supply type main unit or to the 24V DC
service power supply terminal of the input/output powered extension unit consume the external 24V DC.
Include the current in the calculation of current consumption.
When the terminal is connected with an external power supply, the current is not included in the calculation
of current consumption.
6.8.1[A] Main units
A
No.Type
AC power supply type
FX3G-14MR/ES
FX3G-14MT/ES
FX3G-14MT/ESS
FX3G-24MR/ES
FX3G-24MT/ESS
FX3G-40MR/ES
FX3G-40MT/ESS
FX3G-60MR/ES
FX3G-60MT/ESS
A1
*1.Each number inside ( ) indicates the number of occupied points.
DC power supply type
FX3G-14MR/DS
FX
3G-14MT/DS
FX3G-14MT/DSS
FX3G-24MR/DS
FX3G-24MT/DSS
FX3G-40MR/DS
FX3G-40MT/DSS
FX3G-60MR/DS
FX3G-60MT/DSS
Use numbers inside ( ) when calculating the total number of input/output points.
Input/outputOutput current (mA)
Number of input/
output points
[points]
*1
14(16)
*1
24(32)
4024/16FX3G-40MT/ES
*1
60(64)
*1
14(16)
*1
24(32)
4024/16FX3G-40MT/DS
*1
60(64)
Input/output
[points]
8/6(8)
14(16)/10(16)FX3G-24MT/ES
36(40)/24FX3G-60MT/ES
8/6(8)
14(16)/10(16)FX3G-24MT/DS
36(40)/24FX3G-60MT/DS
24V DC service power supply
400
-
88
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.8 Number of Input/Output (Occupied) Points and Current Consumption
*1.Four inputs and four outputs are occupied as unused numbers.
Number of input/
output points
*1
16
8
16100
8
16150
[points]
Current consumed (mA)
5V DCInternal 24V DC
-62.5
-
-
5V DC power supply
690
50FX2N-8EX
75
24V DC service
power supply
250
460
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
89
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.8.3[C] Special function devices
6 Examination of System Configuration
6.8 Number of Input/Output (Occupied) Points and Current Consumption
C
No.Type
FX3U-4AD8110090
FX2N-2AD820
FX2N-4AD830055
FX2N-8AD850080
FX2N-4AD-PT 830050
FX2N-4AD-TC 830050
FX3U-4DA81200160
FX2N-2DA830
C1
FX2N-4DA8300200
FX2N-5A870090
FX3U-4LC8160050
FX2N-2LC870055
FX3U-16CCL-M
FX3U-64CCL800220
FX2N-16CCL-M
FX2N-32CCL8130050
FX2N-64CL-M
Number of input/
occupied output
points
*1
8
*1
8
*2
8
5V DCInternal 24V DCExternal 24V DC
00240
00150
190
Current consumed (mA)
*3
50
*3
85
Supplied from power supply for
*1.The following number of points is added according to the products connected to the network.
Number of remote I/O stations 32 points
*2.The following number of points is added according to the products connected to the network.
Total number of input/output points of remote I/O stations
*3.When analog special function blocks (FX
powered extension unit (FX
2N-32E or FX2N-48E ), the following limitation must be taken into
2N-2AD and FX2N-2DA) are connected to an input/output
consideration. (When the blocks are connected to the main unit, this limitation is not applied.)
The total current consumption of the analog special function blocks (FX
2N-2AD and FX2N-2DA) should
be less than the following current values.
- Total current consumption of blocks connected to FX2N-32E : 190 mA or less
- Total current consumption of blocks connected to FX
2N-48E : 300 mA or less
0
0
CC-Link/LT
6.8.4[D] Extension Power Supply Unit
Number of input/
occupied output
points
90
D
No.Type
FX
D1
3U-1PSU-5V-1000300
*1.The ambient temperature restricts the output current. For details, refer to the derating curve in Section
6.7.
Current consumed (mA)
5V DC power supplyInternal 24V DC
*1
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
7 Assignment of Input/Output Numbers and Unit Numbers
7.1 Assignment of Input/Output Numbers (X/Y)
7.Assignment of Input/Output Numbers and Unit Numbers
7.1Assignment of Input/Output Numbers (X/Y)
If input/output powered extension units/blocks have been connected when the power is turned on, the main
unit automatically assigns the input/output numbers (X/Y) (octal) to the units/blocks.
Therefore, it is unnecessary to specify the input/output numbers with parameters.
Accordingly, it is not necessary to specify input/output numbers using parameters.
It is necessary to assign input and output numbers in the following special function blocks.
2N-64CL-M
•FX
7.1.1Concept of assigning
1
Introduction
2
Features and
Part Names
3
Product
Introduction
When the power is turned on, input/output numbers (X/Y) are assigned in accordance with the following rules.
In the FX
For details on assignment, refer to the FX
2N-64CL-M, input/output numbers are assigned to connected remote input/output stations.
2N-64CL-M manual.
1. Input/output numbers (X/Y) are octal.
Octal numbers are assigned as input/output numbers (X/Y) as shown below.
- X000 to X007, X010 to X017, X020 to X027......, X070 to X077, X100 to X107...
- Y000 to Y007, Y010 to Y017, Y020 to Y027......, Y070 to Y077, Y100 to Y107...
2. Unused numbers
Note that unused numbers (which cause the difference between the number of occupied points and the
number of effective points) are generated when the following products are used.
- Main units (FX
- input/output extension blocks (FX
3G-14M , FX3G-24M , FX3G-60M )
2N-8ER-ES/UL, FX2N-8ER)
3. Numbers for added input/output unit/block
To an added input/output powered extension unit/block, input numbers and output numbers following the
input numbers and output numbers given to the preceding device are assigned.
The last digit of the assigned numbers must begin with 0.
When the input/output powered extension unit is connected to the main unit, input/output numbers are
assigned as follows.
• In the case of FX
X000 to X007
3G-14M• In the case of FX3G-24M
(X016,X017: Unused numbers)
X010 to X027
X000 to X015
X020 to X037
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
Main unit
FX3G-14MT/ES
Y000 to Y005
(Y006,Y007: Unused numbers)
• In the case of FX
X000 to X027
Main unit
FX
3G
-40MT/ES
Y000 to Y017
Input/output powered
extension unit
Y010 to Y027
3G-40M• In the case of FX3G-60M
X030 to X047
Input/output powered
Y020 to Y037
FX
2N
-32ER
extension unit
FX
2N
-32ER
Main unit
FX
3G
-24MT/ES
Y000 to Y011
(Y012 to Y017: Unused numbers)
(X044 to X047: Unused numbers)
X000 to X043
Main unit
FX
3G
-60MT/ES
Y000 to Y027
Input/output powered
extension unit
FX
2N
-32ER
Y020 to Y037
X050 to X067
Input/output powered
extension unit
2N
-32ER
FX
Y030 to Y047
91
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
7.1.2Example of assigning
An example of assignment of input/output numbers (X/Y) is shown below.
1. Example of configuration
7 Assignment of Input/Output Numbers and Unit Numbers
7.1 Assignment of Input/Output Numbers (X/Y)
Special adapter
FX
3U
-4AD-ADP
Connector
conversion
adapter
3G
-CNV-ADP
FX
Input/output
powered
extension unit
2N
-32ET
FX
Main unit
FX
3G
-24MT/ES
Input
extension
block
2N
-8EX
FX
Input/output
extension block
2N
-8ER
FX
Special function
block
2N
-16CCL-M
FX
2. Assignment of input/output numbers
Input/output numbers are assigned to the above example configuration as shown below.
(X024 to X027:
Unused numbers)
X020 to X023
Input/output
Special function
extension block
2N
FX
-8ER
FX
Y020 to Y023
(Y024 to Y027:
Unused numbers)
-
block
2N
-16CCL-M
-
--
Special adapter
3U
-4AD-ADP
FX
Connector
conversion
adapter
FX
3G
-CNV-ADP
(X016, X017:
Unused numbers)
X000 to X015
Main unit
3G
-24MT/ES
FX
Y000 to Y011
(Y012 to Y017:
Unused numbers)
X030 to X047
Input/output
powered
extension unit
FX
2N
-32ET
X050 to X057
Input
extension
block
FX
2N
-8EX
Y030 to Y047
7.1.3Application of I/O number label
The input/output powered extension units/blocks come with an I/O number label.
Apply the I/O number label to spaces on the enclosure (see the following figure) so that the input/output
numbers can be identified.
For X050
92
For Y040
FX3G Series Programmable Controllers
7 Assignment of Input/Output Numbers and Unit Numbers
User's Manual - Hardware Edition
7.2Unit Numbers of Special Function Blocks
7.2.1Concept of assigning
7.2 Unit Numbers of Special Function Blocks
1
Introduction
When power is turned on, the main unit (CPU) automatically assigns the numbers 0 to 7 to special function
blocks starting from the one closest to the main unit.
Unit numbers are not given to input/output powered extension units/blocks.
1. Special function blocks connected to main unit
The numbers 0 to 7 are assigned to the special function blocks starting from the one closest to the main unit.
2. Products to which unit numbers are not assigned
• Input/output powered extension units: FX2N-32ER, FX2N-48ET, etc.
• Input/output extension blocks: FX
• Connector conversion adapter: FX
• Expansion boards: FX
• Special adapters: FX
• Extension power supply unit: FX
7.2.2Example of assigning
Unit numbers are assigned to the special function blocks in the following configuration.
→ For assignment of input/output numbers, refer to Section 7.1.
1. Example of configuration
Special adapter
FX
3U
-4AD-ADP
Connector
conversion
adapter
3G
-CNV-ADP
FX
Main unit
FX
3G
-24MT/ES
2N-16EX, FX2N-16EYR, etc.
3G-CNV-ADP, FX2N-CNV-BC
3G-232-BD, etc.
3U-232ADP(-MB), FX3U-4AD-ADP, etc.
3U-1PSU-5V
Input
extension
block
2N
FX
-8EX
Special function
block
2N
-16CCL-M
FX
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
Input/output
powered
extension unit
2N
-32ET
FX
Special
function
3U
FX
block
-64CCL
2. Assignment of Unit No.
Unit numbers are assigned to the special function blocks in the above configuration as shown below.
Unit No.
No.0
Special adapter
FX
3U
-4AD-ADP
Connector
conversion
adapter
FX
3G
-CNV-ADP
Input/output
powered
extension unit
FX
2N
-32ET
FX
Unit No.
No.1
function
FX
Main unit
3G
-24MT/ES
Special
block
3U
-64CCL
Input
extension
block
2N
-8EX
FX
Special function
block
2N
-16CCL-M
FX
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
93
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
7.2.3Application of unit number labels
The special function units/blocks come with unit number labels.
Apply the unit number labels to spaces on the enclosure (see the following figure) so that the unit numbers
can be identified.
Y818D33101
No.0
No.1
No.2
No.3
No.4
7 Assignment of Input/Output Numbers and Unit Numbers
7.2 Unit Numbers of Special Function Blocks
No.5
No.6
No.7
No.0
94
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.