Before installation, operation, maintenance or inspection of this product, thoroughly read through and
understand this manual and all of the associated manuals. Also, take care to handle the module properly and
safely.
This manual classifies the safety precautions into two categories: and .
Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe
injury.
Indicates that incorrect handling may cause hazardous conditions, resulting in medium or slight
personal injury or physical damage.
Depending on the circumstances, procedures indicated by may also cause severe injury. It is
important to follow all precautions for personal safety. Store this manual in a safe place so that it can be taken
out and read whenever necessary. Always forward it to the end user.
1. DESIGN PRECAUTIONS
Reference
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs
are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output control
block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the PLC
are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on or
off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to
ensure safe machinery operation in such a case.
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
• Install module so that excessive force will not be applied to peripheral device connectors.
Failure to do so may result in wire damage/breakage or PLC failure.
98
121
139
172
186
224
245
284
352
Reference
98
121
139
172
186
224
245
284
352
(1)
Safety Precautions
(Read these precautions before use.)
2. INSTALLATION PRECAUTIONS
Reference
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Use the product within the generic environment specifications described in section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl2, H2S,
SO2 or NO2), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
• Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
• Install the product securely using a DIN rail or mounting screws.
Terminal blockDIN rail only
Main unit, FX2N Series I/O extension unit/block, FX2N/FX3U Series special
function block, and special adapter
• Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities.
• Make sure to affix the expansion board with tapping screws.
Tightening torque should follow the specifications in the manual.
Loose connections may cause malfunctions.
• When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Be sure to remove the dust proof sheet from the PLC’s ventilation port when installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
• Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely
to their designated connectors.
Loose connections may cause malfunctions.
• Connect the display module, memory cassette, and expansion board securely to their designated connectors.
Loose connections may cause malfunctions.
• Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause device failures or malfunctions.
- Peripheral devices, display modules, expansion boards and special adapters
- Extension units/blocks and FX Series terminal blocks
- Battery and memory cassette
• Connect the memory cassette securely to the appropriate connector.
Loose connections may cause malfunctions.
Installing the cassette in a raised or tilted posture can also cause malfunctions.
DIN rail or direct mounting
98
352
Reference
99
353
3. WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
(2)
Reference
99
121
139
172
186
224
245
353
Safety Precautions
(Read these precautions before use.)
• Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension
units.
Doing so may cause damage to the product.
• Perform class D grounding (grounding resistance: 100 or less) to the grounding terminal on the main unit and
extension units with a wire 2 mm2 or thicker.
Do not use common grounding with heavy electrical systems (refer to section 9.3).
• Connect the AC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
• Do not wire vacant terminals externally.
Doing so may damage the product.
• When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
• Make sure to properly wire the FX3G Series main unit and FX2N/FX3U Series extension equipment in accordance
with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24”) or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
• Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
• Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described in the manual.
- Tightening torque should follow the specifications in the manual.
- Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24”) or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
• Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
• Before cleaning or retightening terminals, cut off all phases of the power supply externally.
Failure to do so may cause electric shock.
• Use the battery for memory backup correctly in conformance to this manual.
- Use the battery only for the specified purpose.
- Connect the battery correctly.
- Do not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or burn the battery,
or apply excessive forces (vibration, impact, drop, etc.) to the battery.
- Do not store or use the battery at high temperatures or expose to direct sunlight.
- Do not expose to water, bring near fire or touch liquid leakage or other contents directly.
- Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or
deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment.
• Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and
the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
• Do not change the program in the PLC from two or more peripheral equipment devices at the same time. (i.e. from
a programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.
Reference
199
307
385
(3)
Safety Precautions
(Read these precautions before use.)
• Turn off the power to the PLC before attaching or detaching the memory cassette. If the memory cassette is
attached or detached while the PLC’s power is on, the data in the memory may be destroyed, or the memory
cassette may be damaged.
• Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
For repair, contact your local Mitsubishi Electric representative.
• Turn off the power to the PLC before connecting or disconnecting any extension cable.
Failure to do so may cause equipment failures or malfunctions.
• Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause equipment failures or malfunctions.
- Peripheral devices, display module, expansion boards, and special adapters
- Extension units/blocks and FX Series terminal blocks
- Battery and memory cassette
5. DISPOSAL PRECAUTIONS
• Please contact a certified electronic waste disposal company for the environmentally safe recycling and disposal of
your device.
When disposing of batteries, separate them from other waste according to local regulations.
(For details of the Battery Directive in EU countries, refer to Appendix E)
Reference
199
307
375
385
Reference
199
6. TRANSPORTATION AND STORAGE PRECAUTIONS
• When transporting the FX3G Series PLC incorporating the optional battery, turn on the PLC before shipment,
confirm that the battery mode is set using a parameter and the ALM LED is OFF, and check the battery life.
If the PLC is transported with the ALM LED on or the battery exhausted, the battery-backed data may be unstable
during transportation.
• The PLC is a precision instrument. During transportation, avoid impacts larger than those specified in the general
specifications (section 4.1). Failure to do so may cause failures in the PLC.
After transportation, verify the operations of the PLC.
• When transporting lithium batteries, follow required transportation regulations.
(For details of the regulated products, refer to Appendix D)
Reference
199
385
(4)
FX3G Series Programmable Controllers
User’s Manual - Hardware Edition
FX3G Series Programmable Controllers
User's Manual [Hardware Edition]
Manual numberJY997D31301
Manual revisionJ
Date9/2013
Foreword
This manual contains text, diagrams and explanations which will guide the reader in the correct installation,
safe use and operation of the FX
before attempting to install or use the unit.
And, store this manual in a safe place so that you can take it out and read it whenever necessary. Always
forward it to the end user.
This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi
Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of
using the contents noted in this manual.
3G Series Programmable Controllers and should be read and understood
1
FX3G Series Programmable Controllers
User’s Manual - Hardware Edition
Outline Precautions
• This manual provides information for the use of the FX3G Series Programmable Controllers. The manual
has been written to be used by trained and competent personnel. The definition of such a person or
persons is as follows;
1) Any engineer who is responsible for the planning, design and construction of automatic equipment
using the product associated with this manual should be of a competent nature, trained and qualified
to the local and national standards required to fulfill that role. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
2) Any commissioning or service engineer must be of a competent nature, trained and qualified to the
local and national standards required to fulfill that job. These engineers should also be trained in the
use and maintenance of the completed product. This includes being completely familiar with all
associated documentation for the said product. All maintenance should be carried out in accordance
with established safety practices.
3) All operators of the completed equipment should be trained to use that product in a safe and
coordinated manner in compliance to established safety practices. The operators should also be
familiar with documentation which is connected with the actual operation of the completed equipment.
Note: The term 'completed equipment' refers to a third party constructed device which contains or uses
the product associated with this manual
• This product has been manufactured as a general-purpose part for general industries, and has not been
designed or manufactured to be incorporated in a device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power, aerospace, medicine
or passenger movement vehicles, consult with Mitsubishi Electric.
• This product has been manufactured under strict quality control. However when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
• When combining this product with other products, please confirm the standard and the code, or regulations
with which the user should follow. Moreover, please confirm the compatibility of this product to the system,
machine, and apparatus with which a user is using.
• If in doubt at any stage during the installation of the product, always consult a professional electrical
engineer who is qualified and trained to the local and national standards. If in doubt about the operation or
use, please consult the nearest Mitsubishi Electric representative.
• Since the examples indicated by this manual, technical bulletin, catalog, etc. are used as a reference,
please use it after confirming the function and safety of the equipment and system. Mitsubishi Electric will
accept no responsibility for actual use of the product based on these illustrative examples.
• This manual content, specification etc. may be changed without a notice for improvement.
• The information in this manual has been carefully checked and is believed to be accurate; however, if you
have noticed a doubtful point, a doubtful error, etc., please contact the nearest Mitsubishi Electric
representative.
Registration
•Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
• Ethernet is a trademark of Xerox Corporation.
®
•MODBUS
• Phillips is a registered trademark of Phillips Screw Company.
• The company name and the product name to be described in this manual are the registered trademarks or
trademarks of each company.
is a registered trademark of Schneider Electric SA.
Certification of UL, cUL standards ....................................................................................................... 14
Compliance with EC directive (CE Marking) ........................................................................................ 14
Requirement for Compliance with EMC directive................................................................... 14
Requirement for Compliance with LVD directive.................................................................... 17
Caution for compliance with EC Directive .............................................................................. 18
1. Introduction19
1.1 Introduction of Manuals................................................................................................................. 19
1.1.1 Classification of major components in this manual........................................................................19
1.1.2 Manual organization and position of this manual ..........................................................................21
1.1.3 List of manuals ..............................................................................................................................22
1.2 Generic Names and Abbreviations Used in Manuals.................................................................... 27
Table of Contents
2. Features and Part Names29
2.1 Major Features.............................................................................................................................. 29
2.2 Names and Functions of Parts...................................................................................................... 31
2.2.1 Front Panel.................................................................................................................................... 31
3.1 List of Products and Interpretation of Model Names..................................................................... 34
3.1.1 Main units ...................................................................................................................................... 35
4.6.1 Main units ...................................................................................................................................... 52
6.5 Expansion of Main Unit ................................................................................................................. 76
6.5.1 When adding input/output extension blocks using the 24V DC service power supply of
the main unit.................................................................................................................................. 77
6.5.2 Selection example 1 using the 24V DC service power supply of the main unit............................. 79
6.5.3 Selection example 2 using the 24V DC service power supply of the main unit............................. 80
6.6 Expansion of FX2N Series I/O Powered Extension Unit ............................................................... 81
6.6.1 Quick reference matrix (when only input/output devices are added)............................................. 81
6.6.2 When special extension devices are also added (calculation of current consumption)................. 84
6.7 Expansion of Extension Power Supply Unit (FX3U-1PSU-5V)...................................................... 86
... 68
4
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
6.8 Number of Input/Output (Occupied) Points and Current Consumption......................................... 88
6.8.1 [A] Main units................................................................................................................................. 88
19.2 Installation and Removal........................................................................................................... 309
19.2.1 Installation (when the expansion board/connector conversion adapter is not used together)... 309
19.2.2 Installation (when the expansion board/connector conversion adapter is used together)......... 310
19.3 Summary of Functions .............................................................................................................. 311
19.4 Procedure for Accessing the Menu Screen from the Title Screen ............................................ 312
19.4.1 Title screen ................................................................................................................................ 312
19.4.2 Top screen (time display) .......................................................................................................... 312
19.4.3 Menu screen.............................................................................................................................. 312
19.5 Menu Structure.......................................................................................................................... 313
Revised History ..................................................................................................................... 419
13
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Standards
Certification of UL, cUL standards
FX3G series main units, FX3G series interface adapter, FX3U series special adapters and FX2N input/output
extension units/blocks supporting UL, cUL standards are as follows:
This note does not guarantee that an entire mechanical module produced in accordance with the contents of
this note will comply with the following standards.
Compliance to EMC directive and LVD directive of the entire mechanical module should be checked by the
user / manufacturer. For more details please contact to the local Mitsubishi Electric sales site.
Requirement for Compliance with EMC directive
The following products have shown compliance through direct testing (of the identified standards below) and
design analysis (through the creation of a technical construction file) to the European Directive for
Electromagnetic Compatibility (2004/108/EC) when used as directed by the appropriate documentation.
Attention
• This products is designed for use in industrial applications.
Note
• Manufactured by:
Mitsubishi Electric Corporation
2-7-3 Marunouchi, Chiyoda-ku, Tokyo, 100-8310 Japan
• Manufactured at:
Mitsubishi Electric Corporation Himeji Works
840 Chiyoda-machi, Himeji, Hyogo, 670-8677 Japan
• Authorized Representative in the European Community:
Mitsubishi Electric Europe B.V.
Gothaer Str. 8, 40880 Ratingen, Germany
14
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Type :Programmable Controller (Open Type Equipment)
Models :MELSEC FX
from June 1st, 2005FX3U-232ADPFX3U-485ADP
from April 1st, 2007FX3U-232ADP-MBFX3U-485ADP-MB
from December 1st, 2007 FX3U-4AD-PTW-ADPFX3U-4AD-PNK-ADP
from November 1st, 2008
from December 1st, 2008
from March 1st, 2009
from June 1st, 2009FX
from December 1st, 2009
from February 1st, 2012FX3U-ENET-ADP
from September 1st, 2013 FX3G-4EX-BDFX3G-2EYT-BDFX3G-485-BD-RJ
Compliance with all relevant aspects of the standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
15
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Standards
Models :MELSEC FX
from July 1st, 1997
from April 1st, 1998FX2N-48ER-DSFX2N-48ET-DSS
from August 1st, 1998FX2N-48ER-UA1/UL
from August 1st, 2005FX2N-8ER-ES/ULFX2N-8EX-ES/ULFX2N-8EYR-ES/UL
from September 1st, 2010 FX2N-8EYR-S-ES/UL
2N series manufactured
FX2N-ER-ES/UL FX2N-ET-ESS/UL
Where indicates:32,48
FX2N-16EX-ES/ULFX2N-16EYR-ES/ULFX2N-16EYT-ESS/UL
FX2N-8EYT-ESS/UL
For the products above, PLCs manufactured
before March 31st, 2002 are compliant with EN50081-2 (EN61000-6-4) and EN50082-2
from April 1st, 2002 to April 30th, 2006 are compliant with EN50081-2 (EN61000-6-4) and EN61131-2:1994
+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
StandardRemark
EN61000-6-4:2007 - Generic emission standard
Industrial environment
EN50081-2:1993Electromagnetic compatibility
EN50082-2:1995Electromagnetic compatibility
- Generic immunity standard
Industrial environment
EN61131-2:1994Programmable controllers
/A11:1996- Equipment requirements and tests
/A12:2000
EN61131-2:2007Programmable controllers
- Equipment requirements and tests
Compliance with all relevant aspects of the standard.
• Emission-Enclosure port
• Emission-Low voltage AC mains port
• Emission-Telecommunications/network port
Compliance with all relevant aspects of the standard.
• RF immunity
• Fast transients
•ESD
• Conducted
• Power magnetic fields
Compliance with all relevant aspects of the standard.
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• Damped oscillatory wave
Compliance with all relevant aspects of the standard.
EMI
• Radiated Emission
• Conducted Emission
EMS
• Radiated electromagnetic field
• Fast transient burst
• Electrostatic discharge
• High-energy surge
• Voltage drops and interruptions
• Conducted RF
• Power frequency magnetic field
16
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Requirement for Compliance with LVD directive
The following products have shown compliance through direct testing (of the identified standards below) and
design analysis (through the creation of a technical construction file) to the European Directive for Low
Voltage (2006/95/EC) when used as directed by the appropriate documentation.
Type :Programmable Controller (Open Type Equipment)
Models :MELSEC FX
from November 1st, 2008
from December 1st, 2008
from March 1st, 2009
from December 1st, 2009
StandardRemark
EN61131-2:2007 Programmable controllers
- Equipment requirements and tests
3G series manufactured
FX3G-MT/ES
Where indicates:14,24,40,60
FX3G-MR/ES
Where indicates:14,24,40,60
FX3G-MT/ESS
Where indicates:14,24,40,60
3G-MR/DS
FX
Where indicates:14,24,40,60
The equipment has been assessed as a component for fitting in a suitable
enclosure which meets the requirements of EN61131-2:2007
Standards
Models :MELSEC FX2N series manufactured
from July 1st, 1997
from April 1st, 1998FX2N-48ER-DS
from August 1st, 1998FX2N-48ER-UA1/UL
from August 1st, 2005FX2N-8ER-ES/ULFX2N-8EYR-ES/UL
from September 1st, 2010 FX2N-8EYR-S-ES/UL
FX2N-ER-ES/ULFX2N-ET-ESS/UL
Where indicates:32,48
FX2N-16EYR-ES/UL
For the products above, PLCs manufactured
before March 31st, 2002 are compliant with IEC1010-1
from April 1st, 2002 to April 30th, 2006 are compliant with EN61131-2:1994+A11:1996+A12:2000
after May 1st, 2006 are compliant with EN61131-2:2007
StandardRemark
IEC1010-1:1990 Safety requirements for electrical
/A1:1992 equipment for measurement, control,
and laboratory use
- General requirements
EN61131-2:1994 Programmable controllers
/A11:1996 - Equipment requirements and tests
/A12:2000
EN61131-2:2007 Programmable controllers
- Equipment requirements and tests
The equipment has been assessed as a component for fitting in a
suitable enclosure which meets the requirements of IEC 10101:1990+A1:1992
The equipment has been assessed as a component for fitting in a
suitable enclosure which meets the requirements of EN611312:1994+A11:1996+A12:2000
The equipment has been assessed as a component for fitting in a
suitable enclosure which meets the requirements of EN61131-2:2007
17
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Caution for compliance with EC Directive
1. Installation in Enclosure
Programmable logic controllers are open-type devices that must be installed and used within conductive
control boxes. Please use the FX
shielded control boxes. Please secure the control box lid to the control box (for conduction). Installation within
a control box greatly affects the safety of the system and aids in shielding noise from the programmable logic
controller.
2. Caution for Analog Products in use
The analog products have been found to be compliant to the European standards in the aforesaid manual
and directive. However, for the very best performance from what are in fact delicate measuring and controlled
output devices, Mitsubishi Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered carefully. For users of proprietary
cables (integral with sensors or actuators), these users should follow those manufacturers' installation
requirements.
Mitsubishi Electric recommends that shielded cables be used. If NO other EMC protection is provided, users
may experience temporary loss or accuracy between +10% / -10% in very heavy industrial areas.
However, Mitsubishi Electric suggests that if adequate EMC precautions are followed for the users complete
control system.
- Sensitive analog cables should not be laid in the same trunking or cable conduit as high voltage cabling.
Where possible, users should run analog cables separately.
- Good cable shielding should be used. When terminating the shield at Earth - ensure that no earth loops
are accidentally created.
- When reading analog values, EMC accuracy can be improved by averaging the readings. This can be
achieved either through functions on the analog special adapters/boards/blocks or through a user's
program in the FX
3G Series PLC main unit.
3G Series programmable logic controllers while installed in conductive
Standards
18
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1.Introduction
1 Introduction
1.1 Introduction of Manuals
1
Introduction
This manual explains the procedures for selecting the system components, main unit specifications and
procedures for installing the main unit, specifications for the input/output powered extension units/blocks, and
procedures for adding input/output devices, and procedures for operating the display module etc.
3G PLCs can make various kinds of control in combination with the main unit functions and many extension
FX
devices (expansion board, special adapters and special function blocks).
The detailed explanation of the sequence instructions, communication control, analog control and positioning
control are given in separate manuals.
→ For information on manual organization, refer to Subsection 1.1.2.
1.1Introduction of Manuals
1.1.1Classification of major components in this manual
1) Main unit (Chapter 1 to Chapter 14)
DivisionOutlineReference
Introduction of manuals
Features and part names
Introduction of product
Specifications
Version information
System configuration
Input/output No. and unit No.
assignment
Installation
Power supply wiring
Input wiring
High-speed counter
Output wiring
Examples of wiring for each use
Test operation, adjustment,
maintenance and error check
This chapter contains explanations of the procedures for obtaining the manuals
and the abbreviations.
This chapter contains explanations of the product features and the names and
functions of the parts.
This chapter contains explanations of the structures for model names, extension
products.
This chapter contains explanations of the specifications for power supply and
input/output, external dimensions and terminal block layout.
This chapter contains explanation for upgrading of FX3G PLCs and information for
the application of programming tools.
Procedure for determining whether or not a system configuration is possible.
Extension device current consumption and configuration examples.
Input/output assignment procedure for input/output powered extension units/
blocks, etc., and unit No. assignment procedure for special function blocks.
This chapter contains explanations for the panel layout and the procedures for
installing with DIN rail or screws and how to connect extension devices.
This chapter contains explanations of the procedures for preparing for wiring,
power supply specifications and instructions for wiring.
This chapter contains explanations of the input specifications and instructions for
wiring.
This chapter contains explanations of the procedures for using the high-speed
counter examples of programming.
This chapter contains explanations for the output specifications and instructions
for wiring.
This chapter contains explanations of the procedures for wiring input/output
devices for main uses.
This chapter contains explanations of the procedures for test operation and
adjustment, maintenance and error check items and measures to be taken upon
occurrence of error.
Chapter 1
Chapter 2
Chapter 3
Chapter 4
Chapter 5
Chapter 6
Chapter 7
Chapter 8
Chapter 9
Chapter 10
Chapter 11
Chapter 12
Chapter 13
Chapter 14
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
19
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
2) Extension devices (Chapter 15 to Chapter 18)
DivisionOutlineReference
Input/output powered extension
units
Input/output extension blocksChapter 16
Extension power supply unit
(FX3U-1PSU-5V)
Extension products for special
functions, such as analog control
and communication
3) Optional products (Chapter 19 to Chapter 22)
DivisionOutlineReference
Display module
FX Series terminal blocks
Memory cassette
Battery
This chapter contains explanations for the input/output specifications, external
dimensions and terminal layout for each product.
This chapter contains explanations of specifications for the extension power
supply unit and external dimensions.
This chapter contains explanations for the external dimensions and terminal
layout (For details, refer to the manual for each extension device).
This chapter contains explanation of the specifications, external dimensions,
mounting procedures and operating procedures for display modules (FX3G-5DM).
This chapter contains explanations of the procedures for wiring FX-16/32E -TB.
This chapter contains explanations of the specifications for the memory cassette
and the installation procedures.
This chapter contains explanations of the procedures for replacing the battery and
detecting battery voltage drop.
1 Introduction
1.1 Introduction of Manuals
Chapter 15
Chapter 17
Chapter 18
Chapter 19
Chapter 20
Chapter 21
Chapter 22
4) Others (Appendix A to Appendix E)
DivisionOutlineReference
List of special devices
List of instructions
List of discontinued models
Precautions for battery
transportation
Handling of batteries and devices
with Built-in batteries in EU
member states
This chapter contains an explanation list of the special auxiliary relays (M8000 to
M8511) and special data registers (D8000 to D8511)
(For details, refer to the programming manual.)
This chapter contains an explanation list of the basic instructions and applied
instructions
(For details, refer to the programming manual.)
The discontinued MELSEC-F Series PLC models and programming tools
described in this manual.
This chapter contains explanations for transport regulations and guidelines.Appendix D
This chapter contains explanations for the disposal precautions of batteries and
exporting batteries to EU member states.
Appendix A
Appendix B
Appendix C
Appendix E
20
FX3G Series Programmable Controllers
FX -48ER
2N
7245613
0
7245613
0
OUT
IN
L
X5 X7X1X3 X5 X7X1X3 X5 X7
X4 X6
X0
X2 X4 X6X0X2 X4 X6
24+
N
COM
X0
X1
X2
X3
COM4Y4Y5
COM5
Y7COM2Y4Y5Y6Y7 COM3
Y0
Y1
Y2
Y3
COM1
Y0
Y1
Y2
Y3
Y4Y5Y6
Y7
Y0
Y1
Y2Y3Y6
POWER
7245613
0
7245613
0
7245613
0
7245613
0
User's Manual - Hardware Edition
1.1.2Manual organization and position of this manual
This manual describes detail on the hardware, including the system configuration, selection, installation and
wiring. The instructions, communication control, analog control and positioning control are explained in
separate manuals. Refer to the manuals as needed.
FX3G Series
(Main unit)
Built-in functions
Sequence instructions
High-speed counter
Positioning instructions
PID
Additional options
Input/output powered extension
units/blocks
Expansion board, Special adapters
Analog
3U
FX -4AD-ADP
POWER
Communication
24+24-V1+
I1+
COM1
V2+
I2+
COM2
V3+
I3+
COM3
V4+
I4+
COM4
Special function blocks
Analog
As for FX2N Series, refer to individual
manuals.
Options
Display module
Memory cassette
Battery
Manuals supplied with product
Each product comes with the installation manual or
the User's Manual (except the input/output powered
extension units/blocks).
I
nstallation manual
The part names, installation procedures and
specifications are shown.
As for the functions and program examples, refer to
the separate User's Manual -
Edition.
User's manual
The procedures for wiring and installing,
specifications and functions are explained.
To use some products, separate manuals may be
necessary.
Manual for each use (separate volume)
Refer to the manual for each purpose of use.
User's Manual - Hardware Edition
JY997D31301 (Model: FX
Details of analog special function
blocks and analog special adapters
The manuals for FX3G Series will be
available in or after September, 2008.
Details of N:N Network,
parallel link, computer link, nonprotocol communication and
programming communication
The manuals for FX
3G
Series will be
available in or after September, 2008.
Details of wiring, instructions and
operations of positioning functions in
PLC main unit
The manuals for FX
3G
Series will be
available in or after September, 2008.
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
10
Input Wiring
21
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1.1.3List of manuals
FX3G Series PLC main units supplied only with the hardware manual.
For the details of the hardware of FX
For instructions for programming and hardware information on special function devices, refer to the relevant
manuals.
: Indispensable manuals : Manuals necessary for some purposes : Manuals with separate volumes for details
1 Introduction
1.1 Introduction of Manuals
3G Series, refer to this manual.
Manual title
Manuals for PLC main unit
FX3G PLC main unit
Supplied
product
Separate
volume
Programming
Separate
volume
Separate
volume
Separate
volume
Separate
volume
Separate
volume
FX Series terminal block
Supplied
product
Manuals for communication control
Common
Separate
volume
Separate
volume
RS-232C/RS-422/RS-485 communication
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed and FX Series User's
Manual - Data Communication Edition. For the MODBUS communication, refer to the FX3S/FX3G/FX3GC/FX3U/FX3UC Series User's
Manual - MODBUS Serial Communication Edition.
Supplied
product
Supplied
product
Supplied
product
Supplied
product
with
with
with
with
with
with
FX3G Series
HARDWARE MANUAL
FX3G Series User's Manual
- Hardware Edition
(this manual)
FX3S/FX3G/FX
Series Programming
Manual - Basic & Applied
Instruction Edition
FX CPU Structured
Programming Manual
[Device & Common]
FX CPU Structured
Programming Manual
[Basic & Applied Instruction]
FX CPU Structured
Programming Manual
[Application Functions]
FX INPUT AND
OUTPUT TERMINAL
BLOCKS USER'S GUIDE
FX Series User's Manual Data Communication Edition
FX3S/FX3G/FX
Series User's Manual
- MODBUS Serial
Communication Edition
FX3G-232-BD
Installation Manual
FX3U-232ADP-MB
Installation Manual
FX3U-232ADP
Installation Manual
FX3G-422-BD
Installation Manual
3GC
3GC
/FX3U/FX
/FX3U/FX
3UC
3UC
Manual
number
Extractions of descriptions of input/output
JY997D46001
JY997D31301
JY997D16601
SH-080782
JY997D26001
JY997D34701
JY997D34801
JY992D50401 Procedures for handling FX Series terminal block.-
JY997D16901
JY997D26201
JY997D32001
JY997D26401
JY997D13701
JY997D32101
specifications, wiring and installation of FX3G Series
PLC main unit from FX3G Series User's Manual Hardware Edition.
For the detailed explanation, refer to this manual.
Details of hardware of FX3G Series PLC main unit,
including input/output specifications, wiring,
installation and maintenance.
Details of sequence programming for FX3G Series,
including explanation for basic instructions, applied
instructions and various devices.
Programming methods, specifications, functions, etc.
required to create structured programs.
Devices, parameters, etc. provided in structured
projects of GX Works2.
Sequence instructions provided in structured projects
of GX Works2.
Application functions provided in structured projects
of GX Works2.
Details of N:N Network, parallel link, computer link
and no-protocol communication (RS instructions,
FX2N-232IF).
Details on MODBUS serial communication
in FX3S/FX3G/FX3GC/FX3U/FX3UC PLCs.
Procedures for handling the RS-232C communication
expansion board.
Procedures for handling the RS-232C communication
special adapter.
Procedures for handling the RS-232C communication
special adapter.
Procedures for handling the RS-422 communication
expansion board.
Contents
Model name
code
-
09R521
09R517
13JW06
09R925
09R926
09R927
09R715
-
-
-
-
-
22
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
Manual title
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Ethernet, CC-Link, CC-Link/LT
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
product
Separate
volume
Supplied
product
Separate
volume
Supplied
product
Separate
volume
Supplied
product
Separate
volume
Supplied
product
Supplied
product
Supplied
product
Separate
volume
Supplied
product
with
with
with
with
with
with
with
with
with
with
with
with
with
FX3G-485-BD
Installation Manual
FX3G-485-BD-RJ
Installation Manual
FX3U-485ADP-MB
Installation Manual
FX3U-485ADP
Installation Manual
FX-485PC-IF
Hardware Manual
FX3U-ENET-ADP
Installation Manual
FX3U-ENET-ADP
User's Manual
FX3U-16CCL-M
Installation Manual
FX3U-16CCL-M
User's Manual
FX2N-16CCL-M
Hardware Manual
FX2N-16CCL-M
User's Manual
FX3U-64CCL
Installation Manual
FX3U-64CCL
User's Manual
2N-32CCL
FX
User's Manual
Remote I/O station, remote
device station and intelligent
device station for CC-Link
FX
2N-64CL-M
User's Manual Hardware Volume
FX2N-64CL-M
User's Manual Detailed Volume
Remote I/O station, remote
device station, power supply
adapter and dedicated power
supply for CC-Link/LT
1 Introduction
1.1 Introduction of Manuals
Manual
number
JY997D32201
JY997D51501
JY997D26301
JY997D13801
JY992D81801
JY997D47401
JY997D45801
JY997D43401
JY997D43601 Details of CC-Link master special function block.09R724
JY992D87801
JY992D87901 Details of CC-Link master special function block.09R710
JY997D29801
JY997D30401
JY992D71701
As for the remote I/O station, remote device station and intelligent
device station for CC-Link, refer to the relevant manuals and related
documents.
JY997D05401
JY997D08501
As for the remote I/O station, remote device station, power supply
adapter and dedicated power supply for CC-Link/LT, refer to the
relevant manuals and related documents.
Procedures for handling the RS-485 communication
expansion board.
Procedures for handling the RS-485 communication
expansion board.
Procedures for handling the RS-485 communication
special adapter.
Procedures for handling the RS-485 communication
special adapter.
Procedures for handling the RS-232C/RS-485
conversion interface.
Procedures for handling the FX3U-ENET-ADP
Ethernet communication special adapter.
When using, refer to FX3U-ENET-ADP User's
Manual.
Details of FX3U-ENET-ADP Ethernet communication
special adapter.
Procedures for handling the CC-Link master special
function block.
When using, refer to FX3U-16CCL-M User's Manual.
Procedures for handling the CC-Link master special
function block.
When using, refer to FX2N-16CCL-M User's Manual.
Procedures for handling the CC-Link Intelligent
device station special function block.
When using, refer to FX3U-64CCL User's Manual.
Details of the CC-Link Intelligent device station
special function block.
Procedures for handling the CC-Link remote device
station special function block.
Procedures for handling the CC-Link/LT master
special function block.
When using, refer to FX
Details.
Details of the CC-Link/LT master special function
block.
Contents
2N-64CL-M User's Manual -
Model name
code
-
-
-
-
-
-
09R725
-
-
-
09R718
09R711
-
-
09R706
-
1
Introduction
2
Features and
Part Names
3
Product
Introduction
4
Specifications
5
Version and
Peripheral
Devices
6
System
Configuration
7
Input/Output
Nos., Unit Nos.
8
Installation
9
Preparation and
Power Supply
Wiring
23
10
Input Wiring
FX3G Series Programmable Controllers
User's Manual - Hardware Edition
1 Introduction
1.1 Introduction of Manuals
Manual title
Manuals for analog/temperature control
Common
with
with
with
with
with
with
with
with
with
with
with
with
with
with
FX3S/FX3G/FX
Series User's Manual Analog Control Edition
FX3G-2AD-BD
Installation Manual
FX3U-4AD
Installation Manual
FX2N-2AD
User's Guide
FX2N-4AD
User's Guide
FX2N-8AD
User's Manual
FX3U-4AD-ADP
User's Manual
FX3U-4AD-PT-ADP
User's Manual
FX3U-4AD-PTW-ADP
User's Manual
FX2N-4AD-PT
User's Guide
FX3U-4AD-PNK-ADP
User's Manual
FX
3U-4AD-TC-ADP
User's Manual
FX2N-4AD-TC
User's Guide
FX2N-2LC
User's Guide
FX2N-2LC
User's Manual
FX3U-4LC
Installation Manual
FX3U-4LC
User's Manual
Separate
volume
Analog input, temperature input and temperature control
When using each product, refer also to the User's Manual - Hardware Edition for the PLC main unit to be installed.
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Supplied
product
Separate
volume
Supplied
product
Separate
volume
3GC
/FX3U/FX
3UC
Manual
number
JY997D16701
JY997D33501
JY997D20701
JY992D74701
JY992D65201
JY992D86001
JY997D13901
JY997D14701
JY997D29101
JY992D65601
JY997D29201
JY997D14801
JY992D65501
JY992D85601
JY992D85801
JY997D38901
JY997D39101
Contents
Details of analog special function block (FX3U-4AD,
FX3U-4DA, FX3UC-4AD) and analog special adapter
(FX3U-***-**-ADP)
Procedures for handling the 2-ch analog input
expansion board.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch analog input special
function block.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 2-ch analog input special
function block.
Procedures for handling the 4-ch analog input special
function block.
Procedures for handling the 8-ch analog input special
function block (to be used also for thermocouple
input).
Procedures for handling the 4-ch analog input special
adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch Pt100 temperature
sensor input special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch Pt100 temperature
sensor input special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition
Procedures for handling the 4-ch Pt100 temperature
sensor input special function block.
Procedures for handling the 4-ch Pt1000/Ni1000
temperature sensor input special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch thermocouple input
special adapter.
When using, refer to FX3S/FX3G/FX
Series User's Manual - Analog Control Edition.
Procedures for handling the 4-ch thermocouple input
special function block.
Procedures for handling the 2-ch temperature control
special function block.
When using, refer to FX2N-2LC User's Manual.
Procedures for handling the 2-ch temperature control
special function block.
Procedures for handling the 4-ch temperature control
special function block.
When using, refer to FX3U-4LC User's Manual.
Procedures for handling the 4-ch temperature control
special function block.
3GC
3GC
3GC
3GC
3GC
3GC
3GC
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
/FX3U/FX
3UC
3UC
3UC
3UC
3UC
3UC
3UC
Model name
code
09R619
-
-
-
-
09R608
-
-
-
-
-
-
-
-
09R607
-
09R625
24
Loading...
+ 398 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.