Mitsubishi FX2N-ROM-E1, FX2NC-ROM-CE1 Hardware Manual

FX2N/FX
2NC
FUNCTION EXPANSION MEMORY
HARDWARE MANUAL
JY997D00401A
2N
/FX
2NC
Function Expansion Memor y. It should be read and understood before
attempting to install or use the unit. Further information can be found in the FX
2N
or FX
2NC
series PLC
hardware manuals.
Guidelines for the safety of the user and protection of the FX2N/FX
2NC
Function
Expansion Memory
If in doubt at any stage during the installation of the FX2N/FX
2NC
Function Expansion Memory always consult a professional electrical engineer who is qualified and trained to the local and national standards. If in doubt about the operation or use of the FX
2N
/FX
2NC
Function Expansion Memory please consult the
nearest Mitsubishi Electri c distributor.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation. Mitsubishi Electric will accept no res ponsibili ty for actual use of the product based on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your specific application.
Note’s on the symbology used in this manual
At various times through out this manual certain symbols will be used to highlight points of information which are intended to ensure the user’s personal safety and protect the integrity of the equipment. Whenever any of the following symbols are encountered, its associated note must be read and understood. Each of the symbols used will now be listed with a brief description of its meaning.
Hardware warnings
1) Indicates that the identified danger WILL cause physical and property damage.
2) Indicates that the identified danger could POSSIBLY cause physical and property damage.
Associated Manuals
¤
: Indispensable manual
¡
: Either manual is necessary
1. Product Outline
1.1 Features
FX2N-ROM-E1 and FX
2NC
-ROM-CE1 are optional memories for the FX2N or FX
2NC
Series PLC to add external ROM instruction. In the products, system programs to add external ROM instruction, EXTR (FNC 180), and the EEPROM memory which can be used as a PLC program area are built in.
1.2 Programming Tools Applicable for EXTR (FNC 180) Instruction
Manual nam e Manual numbe r Description
¤
FX
1S
/FX1N/FX2N/FX
2NC
Programming Manual
II
JY992D88101
(sent separately)
Explains the instructions in the FX
1S
/FX1N/
FX
2N
/FX
2NC
Series PLC.
¡
FX
2N
Hardware Manual
JY992D66301
(included with product)
Describes the contents related to the hardware such as specification, wiring and mounting of the FX
2N
Series PLC.
¡
FX
2NC
Hardware Manual
JY992D76401
(included with product)
Describes the contents related to the hardware such as specification, wiring and mounting of the FX
2NC
Series PLC.
Model name Version
GX Developer SW7 or later FX-PCS/WIN-E 3.10 or later FX-10P-E 4.10 or later FX-20P-E (FX-20P-MFXD-E) 5.10 or later
2. Specifications
3. Installation and Operation
• Don’t attach/remove the memory cassette or memory board before turning off the power. Attaching/removing it while the power is on may damage its contents or element.
• Don’t touch the memory cassette or memory board before discharging static from the body of the user. When transporting, make sure to wrap it in a static-free sheet to prevent damaging its contents or element.
3.1 Ins talla tion of FX2N-ROM-E1
1) Turn off the power of the PLC and remove the cover "a)".
2) Install FX
2N
-ROM-E1 "b)" to the port on the main unit.
3) Put back the cover "a)".
3.2 Ins talla tion of FX
2NC
-ROM-CE1
1) Turn off the power of the PLC and remove the cover "a)".
2) Install FX
2NC
-ROM-CE1 "b)" to the port on the main unit.
3) Place cover "c)", included in the memory board product box, onto the PLC.
Model name
FX2N-ROM-E1 function expansion
memory cassette
FX
2NC
Applicable PLC
FX2N PLC version 3.00 or later (Serial number 15**** or later)
FX
2NC
(Serial number 15**** or later)
If installed in PLC earlier than version 3.00, only 16k-step user program memory and clock function can be used.
Built-in functions
System memory
Equipped with functions K10 to K13 of the EXTR (FNC 180) instruction
• K10: I nverter operation monitoring
• K11: Inverter operation control
• K12: Read of inverter parameter
• K13: Write of inverter parameter
User program memory
• Memory capacity: 16k steps (can be set to 2k, 4k or 8k steps also)
• Memory type: EEPROM
• Allowable number of write: Approx. 10k times (memory protect switch provided)
Clock function
Not provided (clock is built in PLC)
Year 1980 to 2079
Year display in 2 or 4 digit s
Monthly difference of
72
4
5
6
1
3
0
1611
15
14
17
10
12
13
14
17
1510
12
13
72
4
5
6
1
3
0
1611
OUT
IN
L
24+
X1
X3
7
Y1
Y3
COM2
Y5
Y7
CO
Y13
COM4
Y1
Y0
Y2
Y4
Y6
Y12
Y14
N
a)
FX2N main unit
Memory protect sw it ch
b)
FX
2N C
Memory protect switch
b)
c)
a)
1) PLC FX
2N
,FX
2NC
(version 3.00 or later)
RS-485 communication module [FX
2N
]
FX
2N
-485-BD
FX0N-485ADP + FX2N-CNV-BD [FX
2NC
]
FX
0N
-485ADP
S500 (with RS-485 communication function) E500 PU (RS-485) connector
2) Inverter
A500 PU connector
3) 10 BASE-T cable
4) Twisted pair cable A500
Optional connection
Termination resistors are needed on both ends of 1) and 2).
. .
.
FR-A5NR
2N
1) PLC FX
2N
,FX
2NC
(version 3.00 or later)
RS-485 communication module [FX
2N
]
FX
2N
-485-BD
FX0N-485ADP + FX2N-CNV-BD [FX
2NC
]
FX
0N
-485ADP
S500 (with RS-485 communication function) E500 PU (RS-485) connector
2) Inverter
A500 PU connector
3) 10 BASE-T cable
4) Twisted pair cable A500
Optional connection
Termination resistors are needed on both ends of 1) and 2).
. .
.
FR-A5NR
/FX
2N
or FX
2NC
Function
2NC
series PLC
2. Specifications
Model name
Applicable PLC
System memory
Built-in functions
User program memory
Clock function
FX2N-ROM-E1 function expansion
memory cassette
FX2N PLC version 3.00 or later (Serial number 15**** or later)
If installed in PLC earlier than version 3.00, only 16k-step user program memory and clock function can be used.
Equipped with functions K10 to K13 of the EXTR (FNC 180) instruction
• K10: I nverter operation monitoring
• K11: Inverter operation control
• K12: Read of inverter parameter
• K13: Write of inverter parameter
• Memory capacity: 16k steps (can be set to 2k, 4k or 8k steps also)
• Memory type: EEPROM
• Allowable number of write: Approx. 10k times (memory protect switch provided)
Not provided (clock is built in PLC)
2NC
FX
-ROM-CE1 functio n expansion memory board
2NC
FX
PLC version 3.00 or later
(Serial number 15**** or later)
• Year 1980 to 2079
• Year display in 2 or 4 digit s
• Monthly difference of ±45 sec. (at 25°C)
3. Installation and Operation
• Don’t attach/remove the memory cassette or memory board before turning off the power. Attaching/removing it while the power is on may damage its contents or element.
• Don’t touch the memory cassette or memory board before discharging static from the body of the user. When transporting, make sure to wrap it in a static-free sheet to prevent damaging its contents or element.
3.1 Ins talla tion of FX2N-ROM-E1
a)
X3
X1
24+
N
L
Y2
Y1
Y0
b)
Memory protect sw it ch
72
6
17
5
1611
4
1510
3
14
13
1
12
0
72
6
17
IN
5
1611
4
15
3
14
13
1
12
7
0
10
Y1
OUT
Y14 COM4
Y13
Y12
CO
Y7
Y6
Y5
Y4
COM2
Y3
3.3 Operation
The program error may flash when used for the first time because the EEPROM (user program memory) is not initialized. In the personal computer or FX-20P (off-line mode), transfer and write a p rogram in that status. In the FX-10P or FX-20P (online mode), execute all NOP write to erase the contents.
After writing a program, make sure to verify.
Set the memory protect switch to OFF bef ore writing a prog r am. Duri ng normal operat ion, it is reco mmende d to set it to ON to prevent erroneous write.
When installed in the FX
2N
or FX
the 16k-step EEPROM and clock function can be used.
2N
If installed in the FX
or FX
2NC
function can be used.
4. Inverter Communication Function
• When handling the PLC or inverter, follow the notices indicated in each manual which is included with the main unit in order to avoid electric shock, fire, a damage or an accident.
• Make sure to perform class D grounding of the ground terminal of communication equipment for the PLC together w ith that of th e PLC m ain uni t. Ground the shie ld of a sh ielded c able at one point on the PLC. Do not, however, ground at t he same point as high v oltage line. If grounding is imperfect, effects of noise or surge induction takes place, and it may cause a communication error or erroneous operation.
• The signal cables must not be laid near or bundled with the main circuit lines, high voltage power cables or load carrying wires. Otherwise effects of noise or surge induction are likely to take place, and it may cause a communication error or erroneous operation. Keep a safe distance of more than 100mm (3.94") from these wires.
4.1 Outline of Functions and System Configuration
When using K10 to K13 of the EXTR (FNC 180) instruction, operation monitor ing, control value write or parameter monitoring and change in the A500/E500/S500 (with RS-485 communication function) Series MITSUBISHI TRA NSISTORIZED INVERTER can be pe rform e d . The details of programming and setting can be found in the Programming Manual
Total extension distance PLC Using interface Extension distance
2N
FX
2NC
FX
Connecting with one inverter
FX2N-485-BD Maximum 50m (164')
2N
FX
-CNV-BD + FX
FX0N-485ADP
1S
/FX1N/
1) Turn off the power of the PLC and remove the cover "a)".
2N
2) Install FX
-ROM-E1 "b)" to the port on the main unit.
3) Put back the cover "a)".
3.2 Ins talla tion of FX
2N
2NC
or FX
Series PLC to add
Memory protect switch
1) Turn off the power of the PLC and remove the cover "a)".
2) Install FX
3) Place cover "c)", included in the memory board product box, onto the PLC.
2NC
-ROM-CE1 "b)" to the port on the main unit.
2NC
-ROM-CE1
FX2N main unit
c)
b)
a)
FX
2N C
main unit
memory board
±
45 sec. (at 25°C)
3.3 Operation
The program error may flash when used for the first time because the EEPROM (user program memory) is not initialized. In the personal computer or FX-20P (off-line mode), transfer and write a p rogram in that status. In the FX-10P or FX-20P (online mode), execute all NOP write to erase the contents.
After writing a program, make sure to verify.
Set the memory protect switch to OFF bef ore writing a prog r am. Duri ng normal operat ion, it is reco mmende d to set it to ON to prevent erroneous write.
When installed in the FX
2N
or FX
2NC
Series PLC version 3.00 or later, the EXTR (FNC 180) instruction and the 16k-step EEPROM and clock function can be used. If installed in the FX
2N
or FX
2NC
Series PLC earlier than version 3.00, only the 16k-step EEPROM and clock
function can be used.
4. Inverter Communication Function
• When handling the PLC or inverter, follow the notices indicated in each manual which is included with the main unit in order to avoid electric shock, fire, a damage or an accident.
• Make sure to perform class D grounding of the ground terminal of communication equipment for the PLC together w ith that of th e PLC m ain uni t. Ground the shie ld of a sh ielded c able at one point on the PLC. Do not, however, ground at t he same point as high v oltage line. If grounding is imperfect, effects of noise or surge induction takes place, and it may cause a communication error or erroneous operation.
• The signal cables must not be laid near or bundled with the main circuit lines, high voltage power cables or load carrying wires. Otherwise effects of noise or surge induction are likely to take place, and it may cause a communication error or erroneous operation. Keep a safe distance of more than 100mm (3.94") from these wires.
4.1 Outline of Functions and System Configuration
When using K10 to K13 of the EXTR (FNC 180) instruction, operation monitor ing, control value write or parameter monitoring and change in the A500/E500/S500 (with RS-485 communication function) Series MITSUBISHI TRA NSISTORIZED INVERTER can be pe rform e d . The details of programming and setting can be found in the Programming Manual
II
, JY992D88101.
Total extension distance
Connecting with one inverter
PLC Using interface Extension distance
FX
2N
FX2N-485-BD Maximum 50m (164') FX
2N
-CNV-BD + FX0N-485ADP Maximum 500m (1640')
FX
2NC
FX0N-485ADP
1) PLC FX
2N
,FX
2NC
(version 3.00 or later)
RS-485 communication module [FX
2N
]
FX
2N
-485-BD
FX0N-485ADP + FX2N-CNV-BD [FX
2NC
]
FX
0N
-485ADP
S500 (with RS-485 communication function) E500 PU (RS-485) connector
2) Inverter
A500 PU connector
3) 10 BASE-T cable
4) Twisted pair cable A500
Optional connection
Termination resistors are needed on both ends of 1) and 2).
. .
.
FR-A5NR