(Always read these instructions before using this equipment.)
Before using this product, please read this manual and the relevant manuals introduced in this manual
carefully and pay full attention to safety to handle the product correctly.
The instructions given in this manual are concerned with this product. For the safety instructions of the
programmable controller system, please read the CPU module user's manual.
In this manual, the safety instructions are ranked as "DANGER" and "CAUTION".
DANGER
!
CAUTION
!
Note that the !CAUTION level may lead to a serious consequence according to the circumstances.
Always follow the instructions of both levels because they are important to personal safety.
Please save this manual to make it accessible when required and always forward it to the end user.
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight personal injury or physical damage.
[Design Instructions]
!
DANGER
If a communication error occurs in the data link, the following will occur in the station having the
communication error.
Use the communication status information, and configure an interlock circuit in the sequence
program so that the system will operate safely.
Incorrect outputs and incorrect operations can lead to accidents.
(1) All points of the general-purpose input from this module will turn OFF.
(2) All points of the general-purpose output from this module will turn OFF.
The input/output may turn ON or OFF depending on the module trouble.
Provide a circuit that externally monitors input/output signals that could lead to serious trouble.
A - 1
!
k
CAUTION
Do not bind the control wire or communication cable with the main circuit or power wire, or
place the control wire near these.
Separate by at least 100mm or more.
Failure to observe this could lead to malfunctions caused by noise.
Always connect the master module and CC-Link dedicated cable at the data link terminal block.
If the data link terminal block and general-purpose input/output terminal block are incorrectly
inserted, module trouble could occur.
Data link terminal
bloc
General-purpose input/
output terminal block
[Mounting Instructions]
!
CAUTION
Use this module within the general specification environment described in the manual.
Use in an environment outside the general specification range could lead to electric shocks,
fires, malfunctioning, product damage or deterioration.
Always connect the crimp, press-fit or solder the connector wire connections with the maker-
designated tools, and securely connect the connector to the module.
An incomplete connection could lead to short-circuits or malfunctioning.
Do not directly touch the conductive section of the module.
Failure to observe this could lead to module malfunctioning or trouble.
Securely fix the module with the DIN rail or installation screw. Tighten the installation screw
within the designated torque range.
A loose screw could lead to dropping, short-circuiting or malfunctioning.
If the screw is too tight, dropping or short-circuiting could occur due to screw damage.
Securely mount the connector of each connection cable to the mounting section.
An incomplete connection could lead to malfunctioning caused by an incorrect contact.
A - 2
[Wiring Instructions]
!
CAUTION
Before starting installation or wiring work, be sure to shut off all phases of external power supply
used by the system.
Failure to shut off all phases could lead to electric shocks, product damage or malfunctioning.
Always install the terminal covers enclosed with the product before turning ON the power or
operating the product after installation or wiring work.
Failure to install the terminal cover could lead to electric shocks.
Always ground the FG terminal with Class D grounding (Class 3 grounding) dedicated of the
programmable controller.
Failure to do so could lead to malfunctioning.
Always confirm the product's rated voltage and terminal layout before wiring the module.
Connecting with a power supply other than the rated power supply, or incorrect wiring could
lead to fires or trouble.
Tighten the terminal screws within the specified torque range.
A loose terminal screw could lead to short-circuiting or malfunctioning.
If the terminal screw is too tight, dropping or short-circuiting could occur due to screw damage.
Make sure that foreign matter, such as cutting chips or wire scraps, do not enter the module.
Failure to observe this could lead to fires, trouble or malfunctioning.
The communication cables and power supply cable connected to the module must be placed in
a conduit or fixed with a clamp.
If the cable is not placed in a conduit or fixed with a clamp, the module or cable could be
damaged by the cable variation, movement or unintentional pulling leading to malfunctioning
caused by an improper cable connection.
Do not install the control lines together with the communication cables, or bring them close to
each other. Failure to do so may cause malfunctions due to noise.
Do not remove the communication cable or power supply cable connected to the module by
pulling on the cable section.
If the cable has a connector, hold the connector at the section connected to the module, and
remove.
If the cable does not have a connector, loosen the screws at the section connected to the
module, and remove.
Pulling on the cable while connected to the module could lead to module or cable damage, or
malfunctioning caused by an improper cable connection.
A - 3
[Startup/Maintenance Instructions]
!
CAUTION
When power is ON, do not touch the terminals.
Doing so can cause an electric shock or malfunction.
Before cleaning or tightening the terminal screws and module mounting screws, be sure to shut
off all phases of external power supply used by the system.
Failure to shut off all phases could lead to module trouble or malfunctioning.
Do not touch the connector inside the lid at the front of the module.
Failure to observe this could lead to module trouble or malfunctioning.
Never disassemble or modify the module.
Failure to observe this could lead to trouble, malfunctioning, injuries or fires.
Do not drop or apply any strong impact to the module. Doing so may damage the module.
Before installing or removing the module on the panel, be sure to shut off all phases of external
power supply used by the system.
Failure to shut off all phases could lead to module trouble or malfunctioning.
Do not install/remove the terminal block more than 50 times after the first use of the product.
(IEC 61131-2 compliant)
[Disposal Instructions]
!
CAUTION
When disposing of the product, handle it as industrial waste.
A - 4
REVISIONS
*
The instruction manual No. is described on the lower left of the back cover of this instruction manual.
Date of print * Instruction manual No.Revision details
Jul., 1997IB (NA)-66781-AInitial print
Apr., 1999IB (NA)-66781-BComplete review
Sep., 2002IB (NA)-66781-CEquivalent to Japanese version D
Addition of description for use of the QCPU (Q mode)
Addition
Compliance with the EMC/Low Voltage Directive, Section 4.5.1,
Section 5.2.2
Deletion
This manual does not guarantee the implementation of industrial rights or other rights, and does not authorize the
implementation rights. Mitsubishi shall not be held liable for any problems regarding industrial rights that occur through
the use of the contents given in this manual.
Thank you for purchasing the Mitsubishi general-purpose programmable controller MELSEC-A.
Always read through this manual, and fully comprehend the functions and performance of the A Series
programmable controller before starting use to ensure correct usage of this product.
Make sure that this manual is delivered to the final user.
About Manuals ...............................................................................................................................................A- 9
Compliance with the EMC/Low Voltage Directive.........................................................................................A- 9
Using This Manual.........................................................................................................................................A- 10
Generic Terms and Abbreviations ................................................................................................................A- 11
Definitions and Details of Terms...................................................................................................................A- 12
1. OUTLINE1- 1 to 1- 4
1.1 Features ................................................................................................................................................... 1- 2
2. SYSTEM CONFIGURATION2- 1 to 2- 2
2.1 System configuration ............................................................................................................................... 2- 1
2.2 Applicable systems .................................................................................................................................. 2- 2
3. SPECIFICATIONS3- 1 to 3- 26
3.1 General specifications.............................................................................................................................. 3- 1
3.5 List of functions ........................................................................................................................................ 3- 6
3.6 Input/output signals for master module ................................................................................................... 3- 7
3.6.1 List of input/output signals................................................................................................................. 3- 7
3.6.2 Details of input/output signals ........................................................................................................... 3- 8
3.7 R2 buffer memory list .............................................................................................................................. 3- 13
3.8 Transmission delay time ......................................................................................................................... 3- 19
4.5.1 Precautions for handling the CC-Link dedicated cables .................................................................. 4- 8
4.5.2 Connection of the CC-Link dedicated cables ................................................................................... 4- 8
4.5.3 Connection with external device ....................................................................................................... 4- 9
4.6 Checking the module’s state (Hardware test) ........................................................................................ 4- 11
5. PRELIMINARY INFORMATION5- 1 to 5- 46
5.1 System used in this manual ..................................................................................................................... 5- 1
5.7.2 About control data ............................................................................................................................5- 29
5.7.3 Reading the R2 buffer memory........................................................................................................ 5- 40
5.7.4 Writing to the R2 buffer memory...................................................................................................... 5- 43
6. EXCHANGING DATA WITH AN EXTERNAL DEVICE6- 1 to 6- 30
6.1 Matters to understand before transmitting data ...................................................................................... 6- 1
6.2 Matters to know before receiving data .................................................................................................... 6- 5
6.3 Exchanging data using the buffer memory automatic update function .................................................. 6- 9
6.3.1 Transmitting data to an external device .......................................................................................... 6- 9
6.3.2 Receiving data from an external device .......................................................................................... 6- 14
6.4 Exchanging data using the transmission/reception buffer.....................................................................6- 18
6.4.1 Transmitting data to an external device ..........................................................................................6- 18
6.4.2 Receiving data from an external device .......................................................................................... 6- 24
7. USING FRAMES WHEN EXCHANGING DATA7- 1 to 7- 38
7.1 What are frames?..................................................................................................................................... 7- 1
7.2 Transmitting data using frames ............................................................................................................... 7- 2
7.2.1 Transmitting using transmission frame 1 area .................................................................................7- 2
7.2.2 Transmitting using the transmission frame 2 area........................................................................... 7- 4
7.3 Receiving data using frames ................................................................................................................... 7- 6
7.3.1 Reception data ..................................................................................................................................7- 8
7.3.2 Reading the reception data.............................................................................................................. 7- 10
7.4 Transmitting data at the device and status change ............................................................................... 7- 13
8.3 Flow control .............................................................................................................................................. 8- 6
8.4 ASCII-BIN conversion of transmission data ........................................................................................... 8- 10
8.5 RW update function ................................................................................................................................ 8- 12
8.6 Initializing the R2 ..................................................................................................................................... 8- 15
8.7 Clearing the OS reception area ..............................................................................................................8- 16
8.8 Registering and initializing the R2 EEPROM ......................................................................................... 8- 19
8.9 Controlling the RS-232-C signal ............................................................................................................. 8- 22
8.9.1 Correspondence of RS-232-C control signal and remote input/output signal ............................... 8- 22
8.9.2 Precautions for using RS-232-C control signal read/write function ................................................ 8- 23
8.10 Confirming the R2 switch states and software version........................................................................ 8- 24
9. PROGRAM EXAMPLES9- 1 to 9- 48
9.1 Conditions for program examples ........................................................................................................... 9- 1
9.2 Example of program for using buffer memory automatic update function ............................................. 9- 2
9.2.1 When using FROM/TO command with ACPU / QCPU-A (A mode) ...............................................9- 2
9.2.2 When using dedicated commands with ACPU / QCPU-A (A mode) .............................................. 9- 6
9.2.3 When using dedicated commands with QCPU (Q mode) / QnACPU............................................ 9- 11
9.2.4 When using the FROM/TO commands with ACPU / QCPU-A (A mode)
10.1.1 Error code storage area ................................................................................................................10- 1
10.1.2 List of error codes.......................................................................................................................... 10- 2
10.2 Confirming the error with the LED ....................................................................................................... 10- 5
10.3 Examples of trouble in general-purpose input circuit.......................................................................... 10- 7
10.4 Troubleshooting per symptom............................................................................................................. 10- 9
10.5 Troubleshooting when the master station's ERR. LED flashes......................................................... 10- 10
The following manuals are also related to this product.
In necessary, order them by quoting the details in the tables below.
Manual Name
Control & Communication Link System Master/Local Module Type AJ61BT11/A1SJ61BT11
User's Manual
Explains the configuration, performance and specifications, functions, handling, wiring and
troubleshooting of the AJ61BT11 and A1SJ61BT11 system.
Control & Communication Link System Master/Local Module Type
AJ61QBT11/A1SJ61QBT11 User's Manual
Explains the configuration, performance and specifications, functions, handling, wiring and
troubleshooting of the AJ61QBT11 and A1SJ61QBT11 system.
CC-Link System Master/Local Module User's Manual QJ61BT11N
Explains the configuration, performance and specifications, functions, handling, wiring and
troubleshooting of the QJ61BT11N system.(Sold separately)
AnSHCPU/AnACPU/AnUCPU/QCPU-A (A mode) Programming Manual QJ61BT11
(Dedicated Instructions)
Explains the configuration, performance and specifications, functions, handling, wiring and
troubleshooting of the QJ61BT11 system.(Sold separately)
(Sold separately)
(Sold separately)
Compliance with the EMC/Low Voltage Directive
Manual Number
(Model Code)
IB-66721
(13J872)
IB-66722
(13J873)
SH-080394E
(13JR64)
IB-66251
(13J742)
When incorporating the Mitsubishi programmable controller into other machinery or
equipment and keeping compliance with the EMC and low voltage directives, refer to
Chapter 3, "EMC Directives and Low Voltage Directives" of the User's Manual
(Hardware) included with the CPU module or base unit used.
The CE logo is printed on the rating plate of the programmable controller, indicating
compliance with the EMC and low voltage directives.
To conform this product to the EMC Directive and Low Voltage Directive, refer to the
Section of "CC-Link Modules" in Chapter 3 "EMC Directive and Low Voltage Directive"
in the User’s Manual (Hardware) of the CPU module used or the programmable
controller CPU supplied with the base unit.
A - 9
Using This Manual
This section "Using this manual" describes the R2 usage in categories of purpose.
Refer to the following details when using this manual.
(1) To find the characteristics of R2 (Section 1.1)
The features are described in section 1.1.
(2) To find the system configuration (Section 2.1)
The configuration of a system using R2 is explained in section 2.1.
(3) To find the master module that can use R2, and the CPU version that can use the
CC-Link dedicated commands (Section 2.2)
The master module that can use R2, and the CPU version that can use the CCLink dedicated commands are explained in section 2.2.
(4) To find the R2 specifications (Chapter 3)
The R2 specifications are described in Chapter 3.
(5) To find the time for transmitting/receiving data with R2 (Sections 3.8, 3.9)
The R2 transmission delay time and transmission/reception time are explained in
sections 3.8 and 3.9.
(6) To find the procedures for operating R2 (Chapter 4)
The procedures for operating the R2, and the methods of checking the module
state are explained in Chapter 4.
(7) To find how to access the R2 buffer memory (Sections 5.6, 5.7)
The methods of accessing the buffer memory are described in sections 5.6 and
5.7.
(8) To exchange data with an external device (Chapter 6)
The methods of exchanging data with an external device are explained in Chapter
6.
(9) To add a frame when exchanging data (Chapter 7)
The details of the frame, and the methods of adding a frame are explained in
Chapter 7.
(10) To find sample programs (Chapter 9)
Sample programs are described in Chapter 9.
(11) When trouble occurs (Chapter 10)
The error code list and troubleshooting are described in Chapter 10.
"How to Use This Manual" is described by purposes of using CSKP.
Refer to the following and use this manual.
A - 10
Generic Terms and Abbreviations
Unless specially noted, the following generic terms and abbreviations are used in this
manual to explain the AJ65BT-R2 type RS-232-C interface module.
Generic term/abbreviationDetails of generic term/abbreviation
R2Abbreviation for AJ65BT-R2 type RS-232-C interface module.
CC-LinkAbbreviation for Control & Communication Link system.
Master moduleGeneric term when using AJ61QBT11, A1SJ61QBT11, AJ61BT11, A1SJ61BT11, QJ61BT11
and QJ61BT11N as the master station.
Remote moduleGeneric term for AJ65BTB - , AJ65BTC - , AJ65BT-64AD, AJ65BT-64DAV and
AJ65BT-64DAI.
External deviceGeneric term for devices such as ID controller, bar code reader and general-purpose personal
computer, connected to R2 for data communication.
GPPWGeneric term for model names: SWnD5C-GPPW, SWnD5C-GPPW-A, SWnD5C-GPPW-V
and SWnD5C-GPPW-VA. (“n” included in the model name indicates a number “4” or more.)
AnNCPUAbbreviation of A0J2HCPU, A1SCPU, A1SCPUC24-R2, A1SHCPU, A1SJCPU, A1SJCPU-
AnACPUAbbreviation of A2ACPU, A2ACPU-S1, A2ACPUP21/R21, A2ACPUP21/R21-S1,
A3ACPUP21/R21, A3NCPU and A3ACPU
AnUCPUAbbreviation of A2UCPU, A2UCPU-S1, A2USCPU, A2USCPU-S1, A2USHCPU-S1, A3UCPU
and A4UCPU
QnACPUAbbreviation of Q2ACPU, Q2ACPU-S1, Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU,
Q2ASHCPU-S1, Q3ACPU, Q4ACPU and Q4ARCPU
ACPUAbbreviation of AnNCPU, AnACPU and AnUCPU
QCPU (Q mode)Generic term for Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU and Q25HCPU
QCPU-A (A mode)Generic term for Q02CPU-A, Q02HCPU-A and Q06HCPU-A
A - 11
Definitions and Details of Terms
The definitions and details of terms used in this manual are explained below.
(1)
M
H
This indicates the buffer memory address of the master station.
(2)
R2
H
This indicates the buffer memory address of R2.
(3) Master station
The station that controls the remote station, local station and intelligent device
station.
(4) Intelligent device station
Slave station on CC-Link system that can carry out transient transmission with R2,
etc.
(5) Transient transmission
Function that communicates data with a designated station when access is
requested from the programmable controller CPU, etc.
(6) Buffer memory automatic update function
Function that automatically updates the data between the R2 buffer memory and
master stations' automatic update buffer.
(7) Automatic update buffer
Buffer memory in master station used for the buffer memory automatic update
function in respect to R2.
(8) Registration frame
Row of data targeted for the fixed format section of the statement transmitted and
received between the external device and R2.
The registration frames include the default registration frame registered in the R2,
and the user registration frame registered by the user using EEPROM.
(9) Transmission frame 1 area
Buffer memory address
R2
118H to 119H.
With frame transmission that uses the transmission frame 1 area, a frame can be
added each to the head and end of a random data item when transmitting the
data.
(10) Transmission frame 2 area
Buffer memory address
R2
120H to 185H.
With frame transmission that uses the transmission frame 2 area, up to 100
frames can be added when transmitting the data.
A - 12
A
1 OUTLINE
1. OUTLINE
MELSEC-
1
This User's Manual explains the features and specifications of the R2 used as the
intelligent device station of the CC-Link, communication with an external device, and
the special specifications, etc.
R2 can exchange data with an external device, such as an RS-232-C connection type
barcode reader, ID controller or general-purpose personal computer.
When a barcode reader is connected
Programmable controller
Master station
R2
Data reception
Barcode reader
Reading!
1 - 1
A
1 OUTLINE
1.1 Features
MELSEC-
(1) Easy communication by using the buffer memory automatic update
function.
This function automatically updates the buffer memory between the R2 and
master station at the timing set in R2.
With this, a program to read and write between the R2 and master station can be
eliminated. As the data can be read and written with just the FROM/TO
command, the program is simplified.
(This can be used with all CPUs.)
Carried out with sequence program
Programable controller CPU
1)
TO
FROM
4)
Master station
Buffer memory
(Automatic
update
1
buffer )
*
R2
2)
Buffer
memory
3)
*1 The address differs as shown below
for the A Series and Q/QnA Series.
A Series : Bank 2 M 0
Q/QnA Series : M 2000H to 2FFF
Automatically updated
to FFF
H
H
H
1)The data to be stored in the R2 buffer memory is written into the master
station's automatic update buffer.
2)The data is automatically written in at the R2 timing.
3)The data is automatically read at the R2 timing.
4)The corresponding master station's buffer memory is read to the data in the
R2 buffer memory to be read out.
1 - 2
A
1 OUTLINE
MELSEC-
(2) Addition of frame during data transmission/reception with external
device
By adding a frame to the head and end, a statement format matching the
specifications of the external device, such as the barcode reader or ID controller,
can be created and communicated.
The frames include those that are set as the default, and the frames that can be
randomly created by the user (user registration frame).
A random frame can be added!
Random data
Data transmission
R2
Master station
Monitors the status
of RX, RY and RW,
etc.
Random data
Data reception
External device such as barcode reader,
ID controller, general-purpose personal computer
(3) Automatic transmission possible when user-set transmission
conditions are established
When the user-designated transmission conditions (changes in RX, RY, RW,
etc.), are established, data can be automatically transmitted to the external
device.
Head frame
External device such as barcode reader,
ID controller, general-purpose personal computer
R2
Final frame
Random data
Transmit data after conditions
are established!
(4) Two general-purpose input/output points each provided as a
standard
Two points each are provided for the general-purpose input and output so the
synchronous signal with the barcode reader and ID controller, etc., can be
directly input and output without providing a separate remote I/O module.
1 - 3
A
1 OUTLINE
MEMO
MELSEC-
1 - 4
A
2 SYSTEM CONFIGURATION
2. SYSTEM CONFIGURATION
The system configuration for using R2 is shown explained in this section.
2.1 System configuration
The system configuration for using R2 is shown below.
Up to 26 R2 modules can be connected to one master station.
CC-Link master/local station (master station)CC-Link master/local station (local station)
MELSEC-
2
CC-Link dedicated cable
AJ65BT-R2
(Intelligent device station)
RS-232-C cable
Remote I/O station
Remote device station
1-station occupation
RX/RY 32 points each
RWr/RWw 4 points each
Personal computer Bar code reader
External device
2 - 1
A
2 SYSTEM CONFIGURATION
2.2 Applicable systems
The master module of the CC-Link system that can use R2, and the programmable
controller CPU that can use the CC-Link dedicated commands are explained in this
section.
(1) Applicable master modules
The following indicates the master modules that can use the R2.
When using any of the AJ61BT11, A1SJ61BT11, AJ61QBT11 and A1SJ61QBT11,
use the one that has the following number (9707 B or later) in the DATE field of the
rating plate.
The module that does not have "9707 B" in the DATE field cannot use the R2.
MELSEC-
<Large type>
<Compact type>
Date of Function version Date of Function version
manufacture manufacture
(2) Restrictions on use of CC-Link dedicated commands
Depending on the used programmable controller CPU and master module, the
CC-Link dedicated commands may be unusable.
For details of the restrictions, refer to the A Series Master Module User's Manual
(Details) and AnSHCPU/AnACPU/AnUCPU Programming Manual (Dedicated
Instructions).
For program examples using the dedicated commands, refer to Section 9.2.2,
Section 9.2.3, Section 9.3.2 and Section 9.3.3.
2 - 2
A
3 SPECIFICATIONS
3. SPECIFICATIONS
3.1 General specifications
The general specifications of the R2 are shown below.
ItemSpecifications
Working ambient
temperature
Storage ambient
temperature
Working ambient humidity10 to 90%RH, with no dew condensation
Storage ambient humidity10 to 90%RH, with no dew condensation
FrequencyAccelerationAmplitudeNo. of sweeps
10 to 57Hz–0.075mmWhen there is
JIS B 3502,
Vibration resistance
Impact resistance
Working atmosphereNo corrosive gases
Working altitude *
Installation placeInside control panel
Overvoltage category *
Degree of contamination
2
*
3
IEC 61131-2
compliant
JIS B 3502, IEC 61131-2 compliant (147m/s
1
intermittent
vibration
When there is
continuous
vibration
57 to 150Hz
10 to 57Hz–0.035mm
57 to 150Hz
-20 to 75°C
2000m or less
0 to 55
II or less
2 or less
°
C
2
9.8m/s
2
4.9m/s
2
, 3 times each in X, Y and Z directions)
–
–
MELSEC-
3
10 times each in
X, Y and Z
directions
(for 80 minutes)
*1 Indicates to which power distribution section, from the public power distribution network to the in-plant
machine device, the device is assumed to be connected.
Category II applies to a device fed power from a fixed facility.
The withstand surge voltage level for a device with a rating up to 300V is 2500V.
*2 Exponential indicating the degree of conductive matter generated in the environment where device is
used.
In the degree of contamination level 2, only non-conductive contaminants are generated. However,
temporary conductivity could occur due to rare condensation.
*3 Do not use or store the programmable controller in the environment where the pressure is higher than the
atmospheric pressure at sea level. Otherwise, malfunction may result. To use the programmable controller
in high-pressure environment, contact your nearest Mitsubishi representative.
3 - 1
A
3 SPECIFICATIONS
×
×
⋅
3.2 Performance specifications
The R2 performance specifications are shown below.
(1) RS-232-C specifications
ItemSpecifications
Interface specificationsRS-232-C compliant, 1 channel (Refer to section 3.3)
Transmission methodFull duplex communication method
(Select with RS-232-C transmission specification setting switch)
Data format
Error detectionWith parity check (even/odd)/None
(flow control)
Transmission distance15m
OS reception area5120 bytes
Star bit1
Data bit7/8
Parity bit1 (Yes)/0 (No)
Stop bit1/2
DTR/DSR (ER/DR) controlCommunication control
DC1/DC3 control
MELSEC-
(2) Data link specifications
ItemSpecifications
General-purpose input/output
specifications
Transmission pathBus (RS-485)
EEPROM writing life100,000 times
CC-Link station typeIntelligent device station
No. of occupied stations1 station (RX/RY 32 points each, RWw/RWr 4 points each)
Connection cableCC-Link dedicated cable
Withstand voltageOne minute at 500VAC between DC external terminal batch and grounding
Insulation resistance
Noise withstand levelDC type noise voltage 500Vp-p
Module installation screw
Applicable DIN railTH35-7.5Fe, TH35-7.5Al, TH35-15Fe (JIS C 2812 compliant)
External power supply
Tolerable instantaneous
power failure time
Weight0.40kg
Input side: 24VDC (Positive common/negative common shared type) 2 points
Output side : Transistor output (sink type) 12/24VDC 2 points Terminal block (Refer to
section 3.4)
Ω
or more with 500VDC insulation resistance meter between DC external terminal
10M
batch and grounding
μ
With noise width 1
(Tightening torque range 0.78 to 1.18N
s, noise frequency 25 to 60Hz noise simulator
0.7mm
M4
Current consumption: 0.11A
16mm or more screw
24VDC
1ms
m)
3 - 2
A
3 SPECIFICATIONS
3.3 RS-232-C interface specifications
The specifications of the RS-232-C interface for connection with an external device are
shown below.
MELSEC-
12345
6
789
The following type of connector
is mounted on the R2 side, so
use a mate connector that
matches this type.
9-pin D-SUB (female) screw-
fixed type
DDK Ltd.
17L-10090-27-D9AC
Pin
No.
Reception carrier
1
detection
2 Reception dataRD(RXD)
3 Transmission dataSD(TXD)
4 Data terminal readyER(DTR)
5 Signal groundSG
6 Data set readyDR(DSR)
7 Transmission request RS(RTS)
8 Transmission enableCS(CTS)
9 Not used––
Name
Signal
abbrev.
CD
Signal direction
external
R2
device
The details of each signal are explained below.
CD.................. The CD signal status can be read with the input signal RXnB.
ER (DTR) ....... When using DTR/DSR control, this is turned ON and OFF according
to the empty size of the OS reception area for storing the received
data.
(The DTR signal turns ON when the RS can receive data.)
When not using DTR/DSR control, the output signal RYnA is followed.
DR (DSR) ...... When using DTR/DSR control, if this is OFF, data will not be
transmitted from R2 to the external device.
Set this to be always ON when the external device is in the reception
enabled state.
When not using DTR/DSR control, the DSR signal status will be
ignored.
RS .................. This follows the
R2 101H setting and output signal RYn9.
CS .................. When the CS signal is OFF, data will not be transmitted from R2 to
the external device.
Set this to be always ON when the external device is in the reception
enabled state.
A standard connection example of the RS-232-C cable is given in section 4.5.2.
3 - 3
A
3 SPECIFICATIONS
3.4 General-purpose input/output specifications
The general-purpose input/output specifications of the R2 are shown below.
(1) General-purpose input specifications
DC input (Positive common/negative common shared type)
R2External connection view
No. of input points2 points
Insulation methodPhoto coupler insulation
Rated input voltage24VDC
Rated input currentApprox. 7mA
Working voltage range19.2 to 28.8VDC (ripple rate within 5%)
Max. No. of simultaneous
input points
ON voltage/ON current14V or more/3.5mA or more
OFF voltage/OFF current 6V or less/1.7mA or less
Input resistance
Response
time
Common method
External connection
method
Applicable wire size
Applicable crimp terminal
OFF ON10ms or less
ON OFF10ms or less
100%
Approx. 3.3k
2 points/common (COM1)
Positive common/negative common shared
type
7-point terminal block (M3.5 screw)
0.75 to 2mm
RAV1.25-3.5, RAV2-3.5 (JIS C 2805
compliant)
Ω
2
MELSEC-
1XC
24VDC
COM1
2
3XD
Terminal
No.
TB1XCTB3XD
TB2COM1TB4NC
Signal
name
Terminal
No.
Internal
Signal
name
circuit
3 - 4
A
3 SPECIFICATIONS
(2) General-purpose output specifications
R2External connection view
No. of output points2 points
Insulation methodPhoto coupler insulation
Rated load voltage12/24VDC
Working load voltage
range
Max. load current0.1A/point 0.2A/common
Max. rush current0.4A 10ms or less
Leakage current at OFF0.1mA or less
Max. voltage drop at ON1.5VDC or less (MAX) 0.1A
Output typeSink type
Response
time
Output section
OFF ON 2ms or less
ON OFF 2ms or less (resistance load)
Voltage10.2 to 28.8VDC (ripple rate within 5%)
externally
supplied
Current
power
Surge killerZener diode
Common method2 points/common (COM2)
External connection
method
Applicable wire size
Applicable crimp terminal
10.2 to 28.8VDC (ripple rate within 5%)
50mA or less (TYP. 24VDC, per common)
Not including external load current.
7-point terminal block (M3.5 screw)
0.75 to 2mm
2
RAV1.25-3.5, RAV2-3.5 (JIS C 2805
compliant)
Transistor output (sink type)
L
5YC
12/24VDC
COM2
6
L
7YD
Terminal
No.
TB5YCTB7YD
TB6COM2
Signal
name
MELSEC-
Terminal
No.
Internal
Signal
name
circuit
3 - 5
A
3 SPECIFICATIONS
3.5 List of functions
FunctionExplanation
Main
function
Auxiliary
functions
Non-procedural
communication
function
Buffer memory
automatic
update
Frame addition
Monitor
transmission
Transmission
cancellation
Forced
reception
complete
Flow control
ASCII-BIN
conversion
RW update
R2 initialization Initializes the R2.Section 8.6
OS reception
area clear
Registration to
RS EEPROM
The R2 functions are shown below.
Non-procedural data transmission/reception with external
device such as barcode reader, ID controller, generalpurpose personal computer.
Automatically updates the buffer memory between the R2
and master station at the update timing set in each area of
the R2 buffer memory.
Adds a frame registered for R2 at the head and end of the
transmission data when transmitting data.
Automatically transmits data to the external device when the
user-designated transmission conditions (changes in RX, RY,
RW and status) are established.
After transmission request is issued from the master station
to R2, forcibly cancels the transmission before R2 completes
transmission to external device.
Forcibly completes the reception when reception data from
external device has not reached the reception complete data
size, etc., and reads out the currently received data.
Stops/resumes transmission of data from external device
according to open space in R2 OS reception area.
Stops/resumes transmission of data from R2 according to
requests from external device.
Carries out ASCII-BIN conversion on the
transmitted/received data.
Assigns master station remote register (RW) and R2 side
area to be automatically updated in the buffer memory.
Clears the received data stored in the R2 OS reception area.
Registers a setting value for the R2 buffer memory's specific
application area in the EEPROM, or returns the value
registered in the EEPROM to the R2 default value.
The value for the R2 buffer memory registered in the
EEPROM (including the setting values changed by the user)
is used as an initial value at the time of the R2 startup.
MELSEC-
Relation with
main function
Trans-
mission
Recep-
tion
––Chapter 6
Reference
Section 5.6
Chapter 7
Section 7.4
Section 8.1
Section 8.2
Section 8.3
Section 8.4
Section 8.5
Section 8.7
Section 8.8
RS-232-C
signal control
Reads the status of the RS-232-C interface signal
stored in the R2 buffer memory, and controls the
output.
Section 8.9
: Related, : Not related
3 - 6
A
3 SPECIFICATIONS
MELSEC-
3.6 Input/output signals for master module
The input/output signals (RX/RY) for the R2 master module are explained in this
section.
3.6.1 List of input/output signals
A list of the R2 input/output signals is shown below.
Signal direction Master module R2Signal direction Master module R2
Device No. (input)Signal nameDevice No. (output)Signal name
RXn0Transmission normal completeRYn0Transmission request
RXn1Transmission error completeRYn1Transmission cancel request
RXn2Reception normal read requestRYn2Reception read complete
RXn6OS reception area clear completeRYn6OS reception area clear request
RXn7EEPROM function normal completeRYn7EEPROM function request
RXn8EEPROM function error completeRYn8Use prohibited
RXn9CS (CTS) signalRYn9
RXnADR (DSR) signalRYnA
RXnB
RXnC to RXnDGeneral-purpose external input signalRYnC to RYnDGeneral-purpose external output signal
RXnE to RX(n+1)8 Use prohibitedRYnE to RY(n+1)8Use prohibited
RX(n+1)9Initial data read completeRY(n+1)9Initial data read request
RX(n+1)AError stateRY(n+1)AError reset request
RX(n+1)BRemote station ready
RX(n+1)C to
RX(n+1)D
RX(n+1)EIntelligent device station access completeRY(n+1)EIntelligent device station access request
RX(n+1)FUse prohibitedRY(n+1)FUse prohibited
Signal status
Use prohibited
CD signalRYnBUse prohibited
RY(n+1)B to RY(n+1)D Use prohibited
Signal setting
n: Address assigned to master module with station No. setting.
RS (RST) signal *
ER (DTR) signal *
1
2
*1 The RS signal setting is valid when the "RS signal status designation (
RYn9 ON/OFF (1)". (Refer to section 8.9.)
*2The ER signal setting is invalid when the "Flow control designation (
flow control. (DTR/DSR/ (ER/DR) control) (1)".
Important
Do not designate the RXn0 to RXn8, RXnE to RX(n+1)F, RYn0 to RYn9, RYnB, or RYnE to
RY (N+1)F signals to the following functions.
Monitor target RX/RY for monitor transmission function
Reference RX/RY for registration frame RX/RY/RW reference special character.
Do not output (turn ON) the usage-prohibited signals.
If an output is carried out to a usage-prohibited signal, the programmable controller system
could malfunction.
3 - 7
R2 101H)" is set to "Follow
R2 100H)" is set to "Carry out
A
3 SPECIFICATIONS
t
t
3.6.2 Details of input/output signals
A detailed explanation of the R2 input/output signals is given below.
The lines in the timing chart indicate the following details.
(1) Remote input (RX)
Device No.Signal nameDetails
When transmitting data to an external device connected to R2, after the transmission
data is written into the R2 transmission area, the transmission request (RYn0) is
turned ON.
RXn0
Transmission normal
complete
When the transmission is completed normally, transmission normal complete (RXn0)
turns ON, and if the transmission is completed abnormally, transmission error
complete (RXn1) turns ON.
The transmission request (RYn0) turns OFF when these signals turn ON.
MELSEC-
RXn1
RXn2
RXn3
RXn4
Transmission error
complete
Reception normal
read request
Reception error read
request
Initialization normal
complete
Transmission request (RYn0)
Transmission normal complete
(RXn0)
or Transmission error complete
(RXn1)
R2 transmits contents
of transmission area to
external device.
When data is received from an external device connected to R2 and the transmission
is completed normally, reception normal read request (RXn2) turns ON. If the
transmission is completed abnormally, reception error read request (RXn3) turns ON.
The reception data is stored in the R2 reception area at this time.
The data in the R2 reception area is read out when these signals turn ON, and read
complete (RYn2) turns OFF when the reading is completed.
Reception normal read reques
(RXn2)
or Reception error read reques
(RXn3)
Reception read complete (RYn2)
Reception area is read
with sequence program.
The initialization request (RYn4) is turned ON to initialize R2.
When the R2 is correctly initialized, initialization correct complete (RXn4) turns ON,
and when the process ends abnormally, initialization error complete (RXn5) turns ON.
The initialization request signal (RYn4) turns OFF when these signals turn ON.
RXn5
Initialization error
complete
Initialization request (RYn4)
Initialization normal complete
(RXn4)
or Initialization error complete
(RXn5)
3 - 8
R2 is initialized.
A
3 SPECIFICATIONS
Device No.Signal nameDetails
The OS reception area clear request (RYn6) is turned ON to abort the data in the R2
OS reception area.
When OS reception area clear is completed, the R2 turns the OS reception area clear
complete (RXn6) ON, so the OS reception area clear request (RYn6) will turn OFF.
MELSEC-
RXn6
RXn7
RXn8
RXn9
RXnA
RXnB
RXnC
RXnD
OS reception area
clear complete
EEPROM function
normal complete
EEPROM function
error complete
CS (CTS)
signal
Signal
status
DR (DSR)
signal
CD signal
General-purpose
external input signal
OS reception area
clear request (RYn6)
OS reception area
clear complete (RXn6)
R2 clears the OS
reception area.
When the R2 EEPROM function is executed, after the data is read into the R2 buffer
memory (1C0
H), EEPROM function request (RYn7) turns ON.
When completed normally, EEPROM function normal complete (RXn7) turns ON.
When completed abnormally, EEPROM function error complete (RXn8) turns ON.
When these signals turn ON, EEPROM function request (RYn7) turns OFF.
EEPROM function request (RYn7)
EEPROM function normal complete
(RXn7)
or EEPROM function error complete
(RXn8)
R2 executes
EEPROM function.
This signal indicates the control signal status (CS, DR, CD signal) during RS-232-C
communication with an ON or OFF state.
This signal indicates the status of the R2 general-purpose external input (XC, XD)
status with an ON or OFF state.
RXnC: Corresponds to XC RXnD: corresponds to XD
When writing in the initialization data before executing initialization, the initial data read
request (RY(N+1)9) turns ON, and the initialization data is written to the master station.
At this time, remote station ready (RX(n+1)B) turns OFF.
When the writing is completed, initial data read complete (RX(n+1)9) turns ON, and
the initial data read request (RY(n+1)9) turns OFF.
When these turn OFF, initial data read complete (RX(n+1)9) turns OFF, and remote
station ready (RX(n+1)B) turns ON.
RX(n+1)9
Initial data read
complete
Initial data read request (RY(n+1)9)
Initial data read complete
(RX(n+1)9)
Remote station ready (RX(n+1)B)
3 - 9
R2 writes initialization
data to master station.
A
3 SPECIFICATIONS
Device No.Signal nameDetails
This signal indicates the R2 error state.
If the R2 ERR.LED is lit, the error status (RX(n+1)A) turns ON, and when the
ERR.LED is OFF, the status turns OFF.
When an error occurs, the R2 stores the error code in the error code storage area
R2
1A8H to 1B2H).
(
When the error reset request (RY(n+1)A) is turned ON after remedying the error
cause, the error status (RX(n+1)A) can be turned OFF.
When the initialization error complete (RXn5) is ON, review the R2 initial setting and
turn ON the initialization request (RYn4) again to reinitialize the setting.
RX(n+1)A Error state
When the reinitialization is completed normally and the initialization normal complete
(RXn4) turns ON, the error state (RX(n+1)A) turns OFF.
(When the initialization error complete (RXn5) is ON, turning ON the error reset
request (RY(n+1)A) will not turn OFF the error state (RX(n+1)A).)
Error state (RX(n+1)A)
Any error cause
Error reset request (RY(n+1)A)
MELSEC-
RX(n+1)B Remote station ready
Intelligent device
RX(n+1)E
station access
complete
This signal indicates that the R2 can operate. (Refer to the section for RX(n+1)9.)
ON : The R2 is in the operatable state, and the initial data read request (RY(n+1)9)
is OFF.
OFF : An R2 initialization error occurred (R2 buffer memory setting value error), or
when the initial data read request (RY(n+1)9) is turned ON.
This signal indicates the R2 access complete state in response to the intelligent device
station access request (RY(n+1)E).
If not using dedicated commands and directly reading/writing from the programmable
controller CPU to the master station buffer memory, when accessing to the R2 is
completed, the R2 will turn intelligent device station access complete (RX(n+1)E) ON.
With this signal, the intelligent device station access request (RY(n+1)E) will turn OFF.
Intelligent device station
access request (RY(n+1)E)
Intelligent device station
access complete (RX(n+1)E)
Access to the intelligent
device station
3 - 10
Loading...
+ 234 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.