Mitsubishi AJ65BT-68TD User Manual

AJ65BT-68TD Thermocouple Temperature Input Module User,s Manual
Mitsubishi Programmable Controller
SAFETY PRECAUTIONS
(Read these precautions before using.)
When using Mitsubishi equipment, thoroughly read this manual and the associated manuals introduced
in this manual. Also pay careful attention to safety and handle the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the CPU module user's manual for a
description of the PLC system safety precautions.
These SAFETY PRECAUTIONS classify the safety precautions into two categories: "DANGER" and
"CAUTION".
DANGER
Procedures which may lead to a dangerous condition and cause death or
serious injury if not carried out properly.
CAUTION
Procedures which may lead to a dangerous condition and cause superficial
to medium injury, or physical damage only, if not carried out properly.
Depending on circumstances, procedures indicated by
CAUTION may also be linked to serious
results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it whenever necessary. Always
forward it to the end user.
[DESIGN PRECAUTIONS]
DANGER
When there are communication errors with the data link, the data of the master module will be held.
Built an interlock circuit into the sequence program that will make sure the system operate safely by using
the communication status information.
CAUTION
Do not bunch the control wires or communication cables with the main circuit or power wires, or them close
to each other.
They should be installed 100 mm (3.9 in.) or more from each other. Not doing so could result in noise that would cause malfunction.
[INSTALLATION PRECAUTIONS]
CAUTION
The module should be used under the environmental conditions listed under the general specifications in
the manual.
Using it under any other environmental conditions could cause problems such as fire, malfunction and
damage to or deterioration of the product.
The module should be fixed securely with a DIN rail or installation screws, and then make sure to tighten it
within the range of the specified torque of the installation screws.
If the screws are loose, it may result in fallout or malfunction.
Tightening the screws too far may cause damages to the screws and/or the module, resulting in fallout or malfunction.
Do not directly touch the module's conductive parts.
Doing so could cause malfunction or trouble in the module.
[WIRING PRECAUTIONS]
CAUTION
Before beginning any installation or wiring work, make sure all phases of the power supply have been
obstructed from the outside.
Failure to completely shut off the power supply phases may cause damages to the module or malfunction.
When turning on the power or operating the module after installation or wiring work, be sure the
module’sterminal covers are correctly attached.
Failure to attach the terminal covers may result in short circuit or failure.
The FG terminals should always be grounded using the class-3 or higher grounding designed specially for
the PLC.
Failure to ground these terminals may cause malfunction.
Use applicable solderless terminals and tighten them with the specified torque. If any solderless spade
terminal is used, it may be disconnected when the terminal screw comes loose, resulting in failure.
When wiring the module, check the rated voltage and terminal layout of the wiring, and make sure the wiring
is done correctly.
Connecting a power supply that differs from the rated voltage or wiring it incorrectly may cause fire or
failure.
Tighten the terminal screws within the range of specified torque.
If the terminal screws are loose, it may result in short circuit or malfunction.
Tightening the terminal screws too far may cause damage to the screws and/or the module, resulting in
short circuit or malfunction.
Be sure there are no foreign substances such as sawdust or wiring debris inside the module.
Such debris could cause fire, failure or malfunction.
[WIRING PRECAUTIONS]
CAUTION
Be sure that the wires or cables connected to the module are stored in the duct or fixed with cramps.
Failure to do so may cause a damage to the module or cables due to dangling, shifting or inadvertent
handling of calbes, or malfunction due to bad cable contacts.
Do not install the control lines together with the communication cables, or bring them close to each other.
Failure to do so may cause malfunctions due to noise.
Do not grab on the cable when removing the communication cable or power cable connected to the module.
When removing the cable, loose the screws on the side that is connected to the module.
Pulling the cable that is still connected to the module may cause a damage to the module or cable, or
malfunction due to bad contacts.
[STARTING AND MAINTENANCE PRECAUTIONS]
CAUTION
Do not touch the terminals while the power is on.
Doing so may cause malfunction.
Make sure to switch all phases of the external power supply off before cleaning or re-tightening screws.
If you do not switch off the external power supply, it will cause failure or malfunction of the module.
If the screws are loose, it may result in fallout, short circuit or malfunction.
Tightening the screws too far may cause damages to the screws and/or the module, resulting in fallout,
short circuit or malfunction.
Do not disassemble or modify the module.
Doing so could cause failure, malfunction injury or fire.
Do not drop or give a strong shock to the module because its case is made of resin.
Doing so may cause a damage to the module.
Make sure to switch all phases of the external power supply off before mounting or removing the module.
If you do not switch off the external power supply, it will cause failure or malfunction of the module.
Mounting/removing the terminal block is limited to 50 times after using a product. (IEC61131-2-compliant)
Before handling the module, always touch grounded metal, etc. to discharge static electricity from the
human body.
Failure to do so can cause the module to fail or malfunction.
[DISPOSAL PRECAUTION]
CAUTION
When disposing of this product, treat it as an industrial waste.
Revisions
* The manual number is noted at the lower left of the back cover.
Print Date *Manual Number Revision
Apr., 1998 SH(NA)-3304-A First printing
Jul., 2005 SH(NA)-3304-B Addition
Conformation to the EMC Directive and Low Voltage Instruction, WARRANTY
Correction
SAFETY PRECAUTIONS, Section 2.2, 5
Dec., 2006 SH(NA)-3304-C Correction
SAFETY PRECAUTIONS, Section 2.1, 3.9.4, 4.3, Chapter 5
Japanese Manual Version SH-3651-E
This manual does not imply guarantee or implementation right for industrial ownership or implementation
of other rights. Mitsubishi Electric Corporation is not responsible for industrial ownership problems caused
by use of the contents of this manual.
© 1998 Mitsubishi Electric Corporation
Introduction
Thank you for purchasing the Mitsubishi Graphic Operation Terminal.
Before using the equipment, please read this manual carefully to develop full familiarity with the functions and
performance of the graphic operation terminal you have purchased, so as to ensure correct use.
Please forward a copy of this manual to the end user.
Table of Contents
1. OVERVIEW 1-1
1.1 Features............................................................................................................................................................1- 1
2. SYSTEM CONFIGURATION 2-1 to 2-2
2.1 Overall Configuration ........................................................................................................................................ 2- 1
2.2 Applicable CPUs ...............................................................................................................................................2- 2
3. SPECIFICATIONS 3-1 to 3-24
3.1 General Specification........................................................................................................................................ 3- 1
3.2 Performance Specifications .............................................................................................................................. 3- 2
3.3 Temperature/Digital Conversion Characteristics............................................................................................... 3- 4
3.4 Maximum Transmission Distance over the CC-Link System ............................................................................ 3- 4
3.5 Data Link Processing Time. .............................................................................................................................. 3- 5
3.6 Twisted Cable Specifications ............................................................................................................................ 3- 6
3.7 Function List...................................................................................................................................................... 3- 7
3.8 I/O Signals in Respect to the Master Module.................................................................................................... 3- 8
3.8.1 I/O signal list .......................................................................................................................................... 3- 8
3.8.2 I/O signal functions ................................................................................................................................ 3-11
3.8.3 Wire breakage detection........................................................................................................................3-16
3.8.4 Conversion enable/disable designation ................................................................................................. 3-17
3.8.5 Sampling processing/travel average processing designation................................................................ 3-18
3.8.6 Thermocouple type selection................................................................................................................. 3-20
3.8.7 Pt100 cold junction compensation enable/disable designation .............................................................3-21
3.9 Remote Register ............................................................................................................................................... 3-22
3.9.1 Remote register assignment.................................................................................................................. 3-22
3.9.2 High and low limit settings ..................................................................................................................... 3-23
3.9.3 Detected temperature value ..................................................................................................................3-24
3.9.4 Scaling value .........................................................................................................................................3-24
4. SETTING AND PROCEDURE BEFORE OPERATION 4-1 to 4-10
4.1 Procedure before Operation .............................................................................................................................4- 1
4.2 Handling Precautions........................................................................................................................................ 4- 2
4.3 Part Identification and Setting ........................................................................................................................... 4- 3
4.4 Error Compensation by the Offset Value/Gain Value Setting ........................................................................... 4- 5
4.4.1 Initial settings for error compensation.................................................................................................... 4- 6
4.4.2 Error compensation procedure .............................................................................................................. 4- 7
4.5 Station Number Setting..................................................................................................................................... 4- 8
4.6 Orientation of Module Installation .....................................................................................................................4- 8
4.7 Wiring................................................................................................................................................................4- 9
4.7.1 Handling precautions for twisted cables ................................................................................................ 4- 9
4.7.2 Wiring example with CC-Link modules .................................................................................................. 4- 9
4.7.3 Precautions when wiring to a thermocouple .......................................................................................... 4-10
4.7.4 Wiring example with thermocouple........................................................................................................ 4-10
5. PROGRAMMING 5-1 to 5-18
5.1 Programming Procedure................................................................................................................................... 5- 1
5.2 Programming Example of Reading Initial Setting and Detected Temperature Value .......................................5- 2
5.3 Program Eamples when QCPU(Q Mode) Is Used ............................................................................................ 5- 5
5.4 Program Eamples when QCPU Is Used ........................................................................................................... 5-10
5.5 Program Eamples when ACPU/QCPU(A Mode) Is Used (Dedicated Instructions)...........................................5-13
5.6 Program Eamples when ACPU/QCPU(A Mode) Is Used (FROM/TO Instructions)........................................... 5-16
6. TROUBLESHOOTING 6-1 to 6-5
6.1 Cause of Errors and Corrective Actions by LED Indication...............................................................................6- 1
6.2 When Wire Breakage Detection Flag is On ...................................................................................................... 6- 3
6.3 When E2PROM Error Flag is On....................................................................................................................... 6- 3
6.4 When Detected Temperature Value cannot be Read ....................................................................................... 6- 3
6.5 When Detected Temperature Value is Abnormal .............................................................................................6- 3
6.6 When There is a Communication Error between Master Station and AJ65BT-68TD ....................................... 6- 4
APPENDIX A-1 to A-28
Appendix 1 Usual Operation Limits and Superheated Operating Limits.................................................................. A- 1
Appendix 2 Allowable Temperature Differences...................................................................................................... A- 1
Appendix 3 Thermal Electromotive Force Chart ...................................................................................................... A- 2
Appendix 3.1 Standard Thermal Electromotive Force of B............................................................................. A- 2
Appendix 3.2 Standard Thermal Electromotive Force of R............................................................................. A- 6
Appendix 3.3 Standard Thermal Electromotive Force of S............................................................................. A-10
Appendix 3.4 Standard Thermal Electromotive Force of K............................................................................. A-14
Appendix 3.5 Standard Thermal Electromotive Force of E............................................................................. A-18
Appendix 3.6 Standard Thermal Electromotive Force of J..............................................................................A-21
Appendix 3.7 Standard Thermal Electromotive Force of T ............................................................................. A-25
Appendix 4 External Dimensions Diagram............................................................................................................... A-27
About This Manual
The following are manuals related to this product.
Request for the manuals as needed according to the chart below.
Related Manuals
Manual Name
Manual No.
(Type code)
Type AJ61BT11/A1SJ61BT11 CC-Link System Master/Local Module User's Manual
This manual explains about the system configuration, performance specifications, functions, handling, wiring and troubleshooting of AJ61BT11and A1SJ61BT11. (Sold separately)
IB-66721 (13J872)
Type AJ61QBT11/A1SJ61QBT11 CC-Link System Master/Local Module User's Manual
This manual explains about the system configuration, performance specifications, functions, handling, wiring and troubleshooting of AJ61QBT11and A1SJ61QBT11. (Sold separately)
IB-66722 (13J901)
Type QJ61BT11N CC-Link System Master/Local Module User's Manual
Describes the system configuration, performance specifications, functions, handling, wiring and troubleshooting of the QJ61BT11N. (Optionally available)
SH-080394E
(13JR64)
Conformation to the EMC Directive and Low Voltage Instruction
When complying with EMC Directives and Low-Voltage Directives by assembling a Mitsubishi PLC compatible with EMC Directive and Low-Voltage Directives into the user product, refer to Chapter 3 "EMC Directives and Low-Voltage Directives" in the User’s Manual (Hardware) for the CPU module being used.
The CE logo is printed on the rating plate on the main body of the PLC that conforms to the EMC directive and low voltage instruction.
To conform this product to the EMC Directive and Low Voltage Directive, refer to the Section of "CC-Link
Modules" in Chapter 3 "EMC Directive and Low Voltage Directive" of the User's Manual (Hardware) of the
CPU module used.
About Generic Terms and Abbreviations
Unless otherwise specified, this manual uses the following generic terms and abbreviations to
explain the AJ65BT-68TD Thermocouple Input Module. Temperature input module.
Generic Term/
Abbreviation
Description
GX Developer Generic product name for product model names SWnD5C-GPPW, SWnD5C-GPPW-A,
SWnD5C-GPPW-V and SWnD5C-GPPW-VA. n in the model name indicates 4 or more.
ACPU Generic term for A0J2CPU, A0J2HCPU, A1CPU, A2CPU, A2CPU-S1, A3CPU, A1SCPU,
A1SCPUC24-R2, A1SHCPU, A1SJCPU, A1SJCPU-S3, A1SJHCPU, A1NCPU, A2NCPU, A2NCPU-S1, A3NCPU, A3MCPU, A3HCPU, A2SCPU, A2SHCPU, A2ACPU, A2ACPU-S1, A3ACPU, A2UCPU, A2UCPU-S1, A2USCPU, A2USCPU-S1, A2USHCPU-S1, A3UCPU and A4UCPU.
QnACPU Generic term for Q2ACPU, Q2ACPU-S1, Q2ASCPU, Q2ASCPU-S1, Q2ASHCPU,
Q2ASHCPU-S1, Q3ACPU, Q4APU and Q4ARCPU.
QCPU (A mode) Generic term for Q02CPU-A, Q02HCPU-A and Q06HCPU-A.
QCPU (Q mode) Generic term for Q02CPU, Q02HCPU, Q06HCPU, Q12HCPU and Q25HCPU.
Master station Station that controls a data link system.
One station is required for one system.
Local station Station that has a PLC CPU and can communicate with the master station and other local
stations.
Remote I/O station Station that handles only bit unit information. (Input/output from/to external device)
(AJ65BTB1-16D, AJ65SBTB1-16D, etc.)
Remote device station
Station that handles bit unit information and word unit information. (Input/output from/to external device, analog data conversion)
Remote station Generic term for remote I/O station and remote device station. Controlled by the master
station.
Intelligent device station
Station that can perform transient transmission, e.g. AJ65BT-R2. (Local station included)
Master module Generic term for QJ61BT11N, QJ61BT11, AJ61BT11, A1SJ61BT11, AJ61QBT11 and
A1SJ61QBT11 used as the master station.
SB Link special relay (for CC-Link)
Bit unit information that indicates the module operation status or data link status of the master station/local station. Represented as SB for convenience.
SW Link special register (for CC-Link)
16-bit unit information that indicates the module operation status or data link status of the master station/local station. Represented as SW for convenience.
RX Remote input (for CC-Link)
Information input from a remote station to the master station in bit unit. Represented as RX for convenience.
RY Remote output (for CC-Link)
Information output from the master station to a remote station in bit unit. Represented as RY for convenience.
RWw Remote register (write area for CC-Link)
Information output from the master station to a remote device station in 16-bit unit. Represented as RWw for convenience.
RWr Remote register (read area for CC-Link)
Information input from a remote device station to the master station in 16-bit unit. Represented as RWr for convenience.
Packing List
This product consists of the following items.
Product name Quantity
AJ65BT-68TD thermocouple input module 1
AJ65BT-68TD Thermocouple Temperarure Input Module User’s Manual (Hardware) 1
1. OVERVIEW MELSEC-A
1-1
1. OVERVIEW
This user's manual explains the specifications, handling, programming methods, etc. of the AJ65BT­68TD Thermocouple Input Module (hereinafter referred to as AJ65BT-68TD) used as a remote device station for the CC-Link system.
The AJ65BT-68TD is a module that converts the thermocouple input values from outside the PLC to the temperature values or scaling values of 16-bit signed BIN data.
1.1 Features
The following are the features of the AJ65BT-68TD.
(1) Temperature – digital conversion is possible at eight channels in one module
One AJ65BT-68TD module may perform up to eight channels of temperature – digital conversions.
(2) Thermocouples conforming the JIS standard may be used.
Seven types of thermocouples (K, E, J, T, B, R and S) that conform to the JIS standard may be used. Also, a thermocouple may be chosen independently for each channel
(3) Conversion enabling and disabling
Conversion may be enabled or disabled for each individual channel. By disabling the conversion of channels that are not used, generation of unnecessary wire breakage detection flags may be prevented and sampling time may be reduced.
(4) Wire breakage detection is possible
The thermocouple and compensating conductor breakage may be detected for each channel.
(5) Sampling processing and travel average processing may be designated
As a conversion processing method, sampling processing and travel average processing may designated for each channel.
(6) Cold junction compensation is possible using Pt100 temperature-measuring resistor
Since a Pt100 temperature-measuring resistor is connected, cold junction compensation is performed automatically.
(7) Pt100 cold junction compensation enable/disable setting is possible
By disabling the cold junction compensation by the Pt100 temperature-measuring resistor, cold junction compensation may be performed at outside the module. If the cold junction compensation accuracy ±1 °C of the Pt100 temperature-measuring resistor may not be ignored as a tolerance, cold junction compensation accuracy may be increased by installing a high-accuracy ice bus to outside of the module.
(8) Error compensation can be performed by setting the offset/gain value
Error compensation may be performed individually at each channel by setting the offset/gain value. Also, the offset/gain value may be selected to use a user setting value or factory setting value.
2. SYSTEM CONFIGURATION MELSEC-A
2-1
2. SYSTEM CONFIGURATION
System configuration when using the AJ65BT-68TD is explained below.
2.1 Overall Configuration
The overall configuration when using the AJ65BT-68TD is shown below.
4 stations occupied RX/RY 128 points each RWr/RWw 16 points each
Thermocouple
Temperature detection target object
Master/local module for CC-Link (master station) Master/local module for CC-Link (local station)
Twisted cable with shield
(Intelligent device station)
(Remote I/O station)
AJ65BT-68TD (Remote device station)
(Remote device station)
The maximum overall distance for the system is as follows (varies depending on transmission speed setting).
156 kbps : 1200 m (3937 ft.) 5 Mbps : 150 m (492.1 ft.) 625 kbps : 600 m (1968.5 ft.) 10 Mbps : 100 m (328.1 ft.)
2.5 Mbps : 200 m (656.2 ft.)
2. SYSTEM CONFIGURATION MELSEC-A
2-2
2.2 Applicable CPUs
(1) When the master module is AJ61BT11
• A0J2CPU • A0J2HCPU • A1CPU • A2CPU (S1) • A3CPU
• A1NCPU • A2NCPU (S1) • A3NCPU • A3MCPU • A3HCPU
• A2ACPU (S1) • A3ACPU • A2UCPU (S1) • A3UCPU • A4UCPU
A73CPU
• A1SCPU (C24-R2) • A1SJCPU • A2SCPU • A2USCPU (S1)
• Q02CPU-A • Q02HCPU-A • Q06HCPU-A
(2) When the master module is AJ61QBT11
• Q2ACPU (S1) • Q3ACPU • Q4ACPU
• Q2ASCPU (S1) • Q2ASHCPU (S1)
(3) When the master module is A1SJ61BT11
• A1SCPU (C24-R2) • A1SHCPU • A1SJCPU • A1SJHCPU • A2SCPU
• A2SHCPU • A2USCPU (S1) • A2USH-S1
(4) When the master module is A1SJ61QBT11
• Q2ASCPU (S1) • Q2ASHCPU (S1)
3. SPECIFICATIONS MELSEC-A
3-1
3. SPECIFICATIONS
This section explains the AJ65BT-68TD the general specifications, performance specifications, and transmission specifications.
3.1 General Specification
This section explains the AJ65BT-68TD general specifications.
Item Specifications
Ambient operating temperature
0 to 55
°C
Ambient storage temperature -20 to 75 °C
Ambient operating humidity 10 to 90 %RH, Non-condensing
Ambient storage humidity 10 to 90 %RH, Non-condensing
Frequency Acceleration Amplitude No. of sweeps
10 to 57 Hz
0.075 mm
(0.0030 in.)
Vibration resistance 57 to 150 Hz 9.8 m/s2 {1 G}
10 to 57 Hz
0.035 mm
(0.0014 in.)
57 to 150 Hz 4.9 m/s2 {0.5 G}
Shock resistance Conforming to JIS B 3502, IEC 61131-2
(147 m/s
2
{15 G}, 3 times in each of 3 directions X Y Z)
Operating ambience No corrosive gases
Operating elevation 2000 m (6562 ft.) max.
Installation location Control panel
Over voltage category *1 II max.
Pollution level *2 2 max.
*1 : This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*2 : This index indicates the degree to which conductive material is generated in terms of the
environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally.
10 times each in
X, Y, Z directions
(for 80 min.)
Conforming to JIS B 3502, IEC 61131-2
Under intermittent vibration
Under continuous vibration
3. SPECIFICATIONS MELSEC-A
3-2
3.2 Performance Specifications
The performance specifications of the AJ65BT-68TD are shown below.
Item Specifications
Temperature Sensor Input (°C) -200 to 1700
Output
Detected temperature
Scaling value 16-bit signed binary (0 to 2000)
Applicable thermocouples and temperature measurement range accuracy
Cold junction compensation accuracy (°C)
Overall accuracy Depends on *1 calculation expression
Maximum resolution B, R, S : 0.3 °C K, E, J, T : 0.1 °C
Conversion speed (sampling time) [ms/ch]
Absolute maximum input [V] ± 5
Number of analog input points
8 channels + Pt100 connection channel
Thermocouple input to CC-Link transmission : Transformer insulation
Between channels : Transformer insulation
16-bit signed binary (-2000 to 17000 : value to one decimal place multiplied by 10)
± 1.0
45 ms/channel *2
Insulation method
Applicable
thermocouple
type
Temperature measuremen
t range [°C ]
Conversion accuracy
(When ambient operating
temperature is 25 ±5 °C)
Temperature characteristic
(Per 1 °C of ambient operating
temperature change)
B 600 to 1700 ± 2.5 °C ± 0.4 °C
0 to 200 ± 0.4 °C
200 to 1600 ± 0.3 °C
0 to 200 ± 0.4 °C
200 to 1600 ± 0.3 °C
±0.06 °C or ±0.3 % of the measured
temperature, whichever is greater
±0.06 °C or ±0.02 % of the measured
temperature, whichever is greater
±0.06 °C or ±0.3 % of the measured
temperature, whichever is greater
±0.06 °C or ±0.02 % of the measured
temperature, whichever is greater
±0.06 °C or ±0.02 % of the measured
temperature, whichever is greater
±0.06 °C or ±0.3 % of the measured
temperature, whichever is greater
±0.06 °C or ±0.02 % of the measured
temperature, whichever is greater
±0.5 °C or ±0.25 % of the
measured temperature,
whichever is greater
± 2.0 °C
± 2.0 °C
0 to 350
-200 to 0
0 to 750
0 to 800
-200 to 0
-200 to 0
0 to 1200
S
T
J
E
K
R
3. SPECIFICATIONS MELSEC-A
3-3
Item Specifications
CC-Link station type Remote device station
Number of occupied stations 4 Stations : RX/RY 128 points each RWw/RWr 16 points each
Transmission speed/maximum transmission distance
Refer to Section 3.4
Maximum number of connected modules
Connection cable CC-Link dedicated cable
Depends on noise simulator of noise voltage at 500 Vp-p, noise width at 1 ms and noise
frequency at 25 to 60 Hz
Dielectric withstand voltage 500 V AC between DC external terminal batch and ground for 1 minute
10 MΩ or more using insulation resistance meter when 500 V DC between DC external
terminal batch and ground
Connected terminal block 27-point terminal blocks (M3.5 × 7 screws)
Applicable wire size [mm2] 0.75 to 2.00
Applicable solderless terminal RAV 1.25-3.5, RAV 2-3.5 (conforms to JIS C 2805)
Allowable momentary power failure period [ms]
Screws M4 × 0.7 mm × 16 mm or larger (tightening torque range 78 to 118 N · cm {8 to 12 kg · cm})
May be attached using DIN rails
Applicable DIN rail TH35-7.5Fe, TH35-7.5AI, TH35-15Fe (conforms to JIS C 2812 )
External power supply 24V DC (18 to 30V DC)
Internal consumption current [A] 0.081
Mass [kg (lb)] 0.40 (0.88)
*1 Overall accuracy computation method is as follows:
(Overall accuracy) = (Conversion accuracy) + (Temperature characteristics) × (Ambient operating temperature change) + (Cold junction compensation accuracy) The ambient operating temperature change refers to the value that falls outside the range of 25 ±5 °C. Example) The overall accuracy when using thermocouple K, measured temperature 150 °C, ambient operating temperature 35 °C will be: (±0.5 °C) + (±0.06 °C) × (5 °C) + (±1 °C) = ±1.8 °C
*2 Conversion speed is the time required to convert the input temperature to the corresponding digital
value and store it into the remote register. When using multiple channels, the conversion speed becomes "45ms × number of channels that are conversion enabled".
16 modules
1
Noise durability
Insulation resistor
Module installation screw
3. SPECIFICATIONS MELSEC-A
3-4
3.3 Temperature/Digital Conversion Characteristics
Since the thermal electromotive force has a non-linear characteristic, it must undergo the linearize processing before being written in the remote register. An example of detected temperature characteristic in respect to the thermocouple input value is shown below.
(1200 °C) 12000
48828 [ µV ]
(1200 °C)
0
0
(0 °C)
(
0 °C
)
V
The diagram at left is an example of temperature conversion characteristic example under the conditions shown below: Thermocouple used : JIS K type Terminal block temperature : 0 [°C]
T
e
m
p
e
r
a
t
u
r
e
c
o
n
v
e
r
s
i
o
n
v
a
l
u
e
Thermal electromotive force
Thermocouple output characteristic
3.4 Maximum Transmission Distance over the CC-Link System
The maximum transmission distance over the CC-Link system is shown below.
1) Regardless of the setting of the transmission speed, the cable length must be "greater than 2 m (6.6 ft.)" long between a mater or local station, intelligent device station and the adjacent stations.
2) For 5 Mbps and 10 Mbps transmission speeds, the maximum transmission distance will differ according to the cable length between the remote I/O station and remote device station, so exercise caution.
Master station
Remote I/O station Remote device station
Remote I/O station Remote device station
Remote I /O station Remote device station
Remote I/O station Remote device station
Local station Standby master station Intelligent device station
Local station Standby master station Intelligent device station
1) 1)2) 2)1)
Maximum transmission distance
Maximum transmission
distance
156 kbps 30 cm (11.8 in.) or more 1200 m (3937 ft.)
625 kpbs 30 cm (11.8 in.) or more 600 m (1968.5 ft.)
2.5 Mpbs 30 cm (11.8 in.) or more 200 m (656.2 ft.)
60 cm (23.6 in.) or more 150 m (492.1 ft.)
30 to 59 cm (11.8 to 23.2 in.) 110 m (360.9 ft.)
1 m (3.3 ft.) or more 100 m (328.1 ft.)
10 Mbps 60 to 99 cm (23.6 to 39 in.) 80 m (262.5 ft.)
30 to 59 cm (11.8 to 23.2 in.) 50 m (164 ft.)
2) 1) Transmission speed
2 m (6.6 ft.) or more 5 Mbps
3. SPECIFICATIONS MELSEC-A
3-5
3.5 Data Link Processing Time
For the AJ65BT-68TD, the data link processing time shown below will be required in order to execute each function. For details on link scan time, refer to the AJ61BT11/A1SJ61BT11 CC-Link System Master/Local Module User's Manual or the AJ61QBT11/A1SJ61QBT11 CC-Link System Master/Local Module User's Manual.
(1) Mater station (RY) Remote device station (RY) processing time
[Expression] SM + LS × 3 + Remote device station processing time (90 ms)
[ms]
AJ65BT-68TD
SM : Master station sequence program scan time LS : Link scan time
(2) Master station (RWw) Remote device station (RWw) processing time
[Expression] SM + LS × 3 + Remote device station processing time (90 ms)
[ms] AJ65BT-68TD SM : Master station sequence program scan time LS : Link scan time
(3) Master station (RX) Remote Device Station (RX) Processing Time
[Expression] SM + LS × 2 + Remote device station processing time (1 ms)
[ms] AJ65BT-68TD SM : Master station sequence program scan time LS : Link scan time
(4) Master station (RWr) Remote Device Station (RWr) Processing Time
[Expression] SM + LS × 2 + Remote device station processing time (1 ms)
[ms] AJ65BT-68TD SM : Master station sequence program scan time LS : Link scan time
POINT
The above are examples of processing time until the control of the output signal to the AJ65BT­68TD from the PLC CPU or until input signals or remote registers are read.
The maximum time that takes for updating the detected temperature read by the PLC CPU is "data link processing time + sampling time."
3. SPECIFICATIONS MELSEC-A
3-6
3.6 Twisted Cable Specifications
The twisted cable specifications and recommended cables for use with the CC-Link is explained below. Also, the performance of the CC-Link may not be guaranteed when using cables other than recommended ones as shown below. The recommended cable names and specifications are shown in the table below.
Item Specification
Type FANC–SB 0.5 mm2 × 3
Contact
Mitsubishi Electric System Service, Inc.
Kurashige Denkou, Inc.
Cable type Twisted shielded cable
Conductor cross-sectional area 0.5 mm2
Conductor resistance (20 °C) 37.8 Ω/km or less
Conductive resistance 10000 MΩ km or more
Dielectric withstand voltage 500 V DC one minute
Static capacity (1 kHz) 60 nF/km or less
Characteristic impedance (1 MHz) 100 ± 15 Ω
Cross-sectional diagram
blue
white yellow
DA
DB DG
Sheath
Shield
Aluminum tape
Ground wire
External dimensions 7 mm (0.28 in.)
Approximate mass 65 kg / km
3. SPECIFICATIONS MELSEC-A
3-7
3.7 Function List
Below is a function list of the AJ65BT-68TD.
Item Description Reference section
Wire breakage detection
Detects wire breakage for the connected thermocouple by channel.
Section 3.8.3
Conversion enable/disable designation
Performs conversion enable/disable settings by channel.
Sampling time may be reduced by disabling the conversion
at channels not in use.
Section 3.8.4
Sampling processing/travel average processing designation
Designates sampling processing or travel average processing by channel.
Section 3.8.5
Thermocouple type selection
The thermocouple type to be used may be set for each channel or in batch.
Section 3.8.6
Pt100 cold junction compensation enable/disable designation
Designates the Pt100 cold junction compensation enable/disable.
By disabling the Pt100 cold junction compensation, a high­accuracy ice bus is set outside of the module to increase the cold junction compensation accuracy.
Section 3.8.7
Measured temperature upper/lower limit value setting
Sets the upper and lower limits of the measured temperature by channel.
Section 3.9.2
Detected temperature storage
A value to one decimal place (16-bit signed binary) will be stored in the remote register.
Section 3.9.3
Scaling value storage
The detected temperature value will be scaled to a value of 0 to 2000 within the upper and lower limits and stored.
Section 3.9.4
Error compensation by offset/gain value setting
Error compensation is performed by setting the offset/gain values.
Section4.4
3. SPECIFICATIONS MELSEC-A
3-8
3.8 I/O Signals in Respect to the Master Module
The assignment of I/O signals and the functions is explained.
3.8.1 I/O signal list
The AJ65BT-68TD uses 128 points for input and 128 points for output in respect to the data for the master module. The I/O signal assignment and the name of each signal are shown in the table below. Device RX indicates an input signal to the master module from the AJ65BT-68TD, and device RY indicates an output signal from the master module to the AJ65BT-68TD.
Signal direction : AJ65BT-68TD Master module Signal direction : Master module AJ65BT-68TD
Device No. Signal name Device No. Signal name
RXn0 CH.1 conversion completion flag RYn0 CH.1 conversion enable flag
RXn1 CH.2 conversion completion flag RYn1 CH.2 conversion enable flag
RXn2 CH.3 conversion completion flag RYn2 CH.3 conversion enable flag
RXn3 CH.4 conversion completion flag RYn3 CH.4 conversion enable flag
RXn4 CH.5 conversion completion flag RYn4 CH.5 conversion enable flag
RXn5 CH.6 conversion completion flag RYn5 CH.6 conversion enable flag
RXn6 CH.7 conversion completion flag RYn6 CH.7 conversion enable flag
RXn7 CH.8 conversion completion flag RYn7 CH.8 conversion enable flag
RXn8 CH.1 wire breakage detection flag RYn8 CH.1 sampling/travel average processing designation flag
RXn9 CH.2 wire breakage detection flag RYn9 CH.2 sampling/travel average processing designation flag
RXnA CH.3 wire breakage detection flag RYnA CH.3 sampling/travel average processing designation flag
RXnB CH.4 wire breakage detection flag RYnB CH.4 sampling/travel average processing designation flag
RXnC CH.5 wire breakage detection flag RYnC CH.5 sampling/travel average processing designation flag
RXnD CH.6 wire breakage detection flag RYnD CH.6 sampling/travel average processing designation flag
RXnE CH.7 wire breakage detection flag RYnE CH.7 sampling/travel average processing designation flag
RXnF CH.8 wire breakage detection flag RYnF CH.8 sampling/travel average processing designation flag
RX (n+1) 0 CH.1 measurement range over flag (lower limit) RY (n+1) 0 CH.1 t ype "K" thermocouple selection flag
RX (n+1) 1 CH.1 measurement range over flag (upper limit) RY (n+1) 1 CH.1 type "E" thermocouple selection flag
RX (n+1) 2 CH.2 measurement range over flag (lower limit) RY (n+1) 2 CH.1 type "J" t hermoc ouple selection flag
RX (n+1) 3 CH.2 measurement range over flag (upper limit) RY (n+1) 3 CH.1 type "T" thermocouple selection flag
RX (n+1) 4 CH.3 measurement range over flag (lower limit) RY (n+1) 4 CH.1 t ype "B" thermocouple selection flag
RX (n+1) 5 CH.3 measurement range over flag (upper limit) RY (n+1) 5 CH.1 type "R" the rmo couple selection flag
RX (n+1) 6 CH.4 measurement range over flag (lower limit) RY (n+1) 6 CH.1 t ype "S" thermocouple selection flag
RX (n+1) 7 CH.4 measurement range over flag (upper limit) RY (n+1) 7 Use pro hibited
RX (n+1) 8 CH.5 measurement range over flag (lower limit) RY (n+1) 8 CH.2 t ype "K" thermocouple selection flag
RX (n+1) 9 CH.5 measurement range over flag (upper limit) RY (n+1) 9 CH.2 type "E" thermocouple selection flag
RX (n+1) A CH.6 measurement range over flag (lower limit) RY (n+1) A CH.2 type "J" t her moc ouple selection flag
RX (n+1) B CH.6 measurement range over flag (upper limit) RY (n+1) B CH.2 type "T" thermoc ouple selection flag
RX (n+1) C CH.7 measurement range over flag (lower limit) RY (n+1) C CH.2 type "B" thermocouple selection flag
RX (n+1) D CH.7 measurement range over flag (upper limit) RY (n+1) D CH.2 type "R" th erm ocouple selection flag
RX (n+1) E CH.8 measurement range over flag (lower limit) RY (n+1) E CH.2 type "S" thermocouple selection flag
RX (n+1) F CH.8 measurement range over flag (upper limit) RY (n+1) F Use pr ohibited
3. SPECIFICATIONS MELSEC-A
3-9
Signal direction : AJ65BT-68TD Master module Signal direction : Master module AJ65BT-68TD
Device No. Signal name Device No. Signal name
RX (n+2) 0 CH.1 write data error flag RY (n+2) 0 CH.3 type "K" thermocouple selection flag
RX (n+2) 1 CH.2 write data error flag RY (n+2) 1 CH.3 type "E" thermocouple selection flag
RX (n+2) 2 CH.3 write data error flag RY (n+2) 2 CH.3 type "J" thermocouple selection flag
RX (n+2) 3 CH.4 write data error flag RY (n+2) 3 CH.3 type "T" thermocouple selection flag
RX (n+2) 4 CH.5 write data error flag RY (n+2) 4 CH.3 type "B" thermocouple selection flag
RX (n+2) 5 CH.6 write data error flag RY (n+2) 5 CH.3 type "R" thermocouple selection flag
RX (n+2) 6 CH.7 write data error flag RY (n+2) 6 CH.3 type "S" thermocouple selection flag
RX (n+2) 7 CH.8 write data error flag RY (n+2) 7 Use prohibited
RX (n+2) 8 E2PROM abnormal flag RY (n+2) 8 CH.4 type "K" thermocouple selection flag
RX (n+2) 9 Test mode flag RY (n+2) 9 CH.4 type "E" thermocouple selection flag
RX (n+2) A RY (n+2) A CH.4 type "J" thermocouple selection flag
RX (n+2) B RY (n+2) B CH.4 type "T" thermocouple selection flag
RX (n+2) C RY (n+2) C CH.4 type "B" thermocouple selection flag
RX (n+2) D RY (n+2) D CH.4 type "R" thermocouple selection flag
RX (n+2) E RY (n+2) E CH.4 type "S" thermocouple selection flag
RX (n+2) F RY (n+2) F Use prohibited
RX (n+3) 0 RY (n+3) 0 CH.5 type "K" thermocouple selection flag
RX (n+3) 1 RY (n+3) 1 CH.5 type "E" thermocouple selection flag
RX (n+3) 2 RY (n+3) 2 CH.5 type "J" thermocouple selection flag
RX (n+3) 3 RY (n+3) 3 CH.5 type "T" thermocouple selection flag
RX (n+3) 4 RY (n+3) 4 CH.5 type "B" thermocouple selection flag
RX (n+3) 5 RY (n+3) 5 CH.5 type "R" thermocouple selection flag
RX (n+3) 6 RY (n+3) 6 CH.5 type "S" thermocouple selection flag
RX (n+3) 7 RY (n+3) 7 Use prohibited
RX (n+3) 8 RY (n+3) 8 CH.6 type "K" thermocouple selection flag
RX (n+3) 9 RY (n+3) 9 CH.6 type "E" thermocouple selection flag
RX (n+3) A RY (n+3) A CH.6 type "J" thermocouple selection flag
RX (n+3) B RY (n+3) B CH.6 type "T" thermocouple selection flag
RX (n+3) C Use prohibited RY (n+3) C CH.6 type "B" thermocouple selection flag
RX (n+3) D RY (n+3) D CH.6 type "R" thermocouple selection flag
RX (n+3) E RY (n+3) E CH.6 type "S" thermocouple selection flag
RX (n+3) F RY (n+3) F Use prohibited
RX (n+4) 0 RY (n+4) 0 CH.7 type "K" thermocouple selection flag
RX (n+4) 1 RY (n+4) 1 CH.7 type "E" thermocouple selection flag
RX (n+4) 2 RY (n+4) 2 CH.7 type "J" thermocouple selection flag
RX (n+4) 3 RY (n+4) 3 CH.7 type "T" thermocouple selection flag
RX (n+4) 4 RY (n+4) 4 CH.7 type "B" thermocouple selection flag
RX (n+4) 5 RY (n+4) 5 CH.7 type "R" thermocouple selection flag
RX (n+4) 6 RY (n+4) 6 CH.7 type "S" thermocouple selection flag
RX (n+4) 7 RY (n+4) 7 Use prohibited
RX (n+4) 8 RY (n+4) 8 CH.8 type "K" thermocouple selection flag
RX (n+4) 9 RY (n+4) 9 CH.8 type "E" thermocouple selection flag
RX (n+4) A RY (n+4) A CH.8 type "J" thermocouple selection flag
RX (n+4) B RY (n+4) B CH.8 type "T" thermocouple selection flag
RX (n+4) C RY (n+4) C CH.8 type "B" thermocouple selection flag
RX (n+4) D RY (n+4) D CH.8 type "R" thermocouple selection flag
RX (n+4) E RY (n+4) E CH.8 type "S" thermocouple selection flag
RX (n+4) F RY (n+4) F Use prohibited
3. SPECIFICATIONS MELSEC-A
3-10
Signal direction : AJ65BT-68TD Master module Signal direction : Master module AJ65BT-68TD
Device No. Signal name Device No. Signal name
RX (n+5) 0 RY (n+ 5) 0 All CH. batch type "K" thermocouple selection flag
RX (n+5) 1 RY (n+ 5) 1 All CH. batch type "E" thermocouple selection flag
RX (n+5) 2 RY (n+ 5) 2 All CH. batch type "J" thermocouple selection flag
RX (n+5) 3 RY (n+ 5) 3 All CH. batch type "T" thermocouple selection flag
RX (n+5) 4 RY (n+ 5) 4 All CH. batch type "B" thermocouple selection flag
RX (n+5) 5 RY (n+ 5) 5 All CH. batch type "R" thermocouple selection flag
RX (n+5) 6 Use pro hibited RY (n+ 5) 6 All CH. batch type "S" thermocouple selection flag
RX (n+5) 7 RY (n+5) 7 Pt100 cold junction compensation disable flag
RX (n+5) 8 RY (n+5) 8
to to Use prohibited
RX (n+7) 6 RY (n+7) 6
RX (n+7) 7 RY (n+7) 7 Offset/gain value selection flag
RX (n+7) 8 Initial data processing request flag RY (n+7) 8 Initial data processing completion flag
RX (n+7) 9 Initial data setting completion flag RY (n+7) 9 Initial data setting request flag
RX (n+7) A Error status flag RY (n+7) A Error reset request flag
RX (n+7) B Remote READY RY (n+7) B
RX (n+7) C RY (n+7) C
to Use prohibited to Use prohibited
RX (n+7) F RY (n+7) F
n : Addresses assigned to the master module by the station number setting.
POINT
Do not turn on the output signals that are prohibited in respect to the remote device from the master module.
If the prohibited signals are output, the PLC system may malfunction.
3. SPECIFICATIONS MELSEC-A
3-11
3.8.2 I/O signal functions
The function of each I/O signal for the AJ65BT-68TD is explained below.
(1) Input signal
Device No. Signal name Description
RXn0 to RXn7
CH.
conversion completion flag
The conversion completion flag turns on when the detected temperature value converted at each channel is stored in the remote register after power on or a hardware reset.
If the travel average processing is running, it will turn on when the detected temperature value is converted and stored in the remote register after the travel average processing has completed. The conv ersion completion flag changes according to the conditions listed below.
When conversion disabled is changed to enabled The temperature detection of the enabled channels will be commenced. After the detected temperature values are stored in the remote register, the conversion completion flag is turned on for the corresponding channel.
When conversion enabled is changed to disabled The conversion completion flag is turned off for the corresponding channel. For the values stored in the remote register, the data immediately prior to the disable setting are retained.
RXn8 to RXnF
CH.
wire
breakage detection flag
For the thermocouple input circuit for all channels, when only a single section of the I/O signal lines including the thermocouple is broken, the wire breakage detection flag is turned on for the corresponding channel.
The detected temperature value when a wire breakage detection flag is turned on will be maintained at the normal value immediately prior to the wire breakage, and then the conversion completion flag will be turned off.
After the wire breakage has been removed, the wire breakage detection flag may be turned off by turning on the error reset request flag.
Also, after the breakage has been fixed, the updating of detected temperatures value will be resumed regardless of whether or not the wire breakage detection flag is reset, and after the first update has been completed the conversion completion flag will turn on once again.
CH.
measurement range over flag
When a detected temperature value that falls outside of the upper and lower limits set in the remote register is detected, the measurement range over flag is turned on for the corresponding channel.
When the detected temperature value returns to inside the range, it is reset (off) automatically.
RX (n+2) 1 to
RX (n+2) 7
CH.
writ e
data error flag
When a value exceeding the specification is written in the write-only area of the remote register (upper and lower limit setting) or when multiple types of thermocouples are selected in the thermocouple selection flag, the write data error is turned on for the corresponding channel.
After the cause of the write data error has been removed, the flag may be turned off by turning on the error reset request flag.
RX (n+2) 8
After power on or a hardware reset, the internal memory (E2PROM for offset/gain value
storage) is checked, and it turns on if there is an error.
At such times, the conversion function will stop.
When this flag turns on, the error reset request flag may not be used to reset (off) because the module itself is malfunctioning (hardware error).
Turns on during test mode.
Turns off when reverted to normal mode.
RX (n+1) 1 to
RX (n+1) F
E
2
PROM
abnormal flag
Test mode flag RX (n+2) 9
3. SPECIFICATIONS MELSEC-A
3-12
Device No. Signal name Description
After power on or a hardware reset, this is turned on because the AJ65BT-68TD
requests the initial data setting .
After the initial data processing is complete (initial data processing request flag RY(n+7)8 is turned on), it turns off.
Turns on when initial data setting request (initial data setting request flag RY(n+7)9 is
turned on) is made.
After the initial data setting request flag is turned off when initial data setting is complete, this also turns off.
RX (n+7) A
Turns on when wire breakage detection flag/write data error flag/E
2
PROM error flag
turns on.
After the cause of the error has been removed, the flag may be reset (off) by turning on the error reset request flag, but since the E
2
PROM error flag cannot be reset, this
flag may also not be reset.
RX (n+7) B
After power on or a hardware reset, this flag turns on when the initial data setting is
complete and the detected temperature value at the conversion-enabled channel has been stored in the remote register.
Will not turn on when all channels are conversion disabled.
It will turn off for two seconds when the offset/gain switch is set to [OFFSET] during test mode or when changed from [GAIN] to [SET].
Used as an interlock for read and write in respect to the master module.
Initial data processing request flag
RX (n+7) 8
Initial data
setting
completion
flag
RX (n+7) 9
Error status flag
Remote READY
3. SPECIFICATIONS MELSEC-A
3-13
(2) Output signal
Device No. Signal name Description
RYn0 to RYn7
CH.
conversion enable flag
It is possible to designate the conversion enabled or disabled for each channel.
By disabling the conversion at channels not in use, generation of unnecessary wire breakage detection flags may be prevented and sampling time may be reduced.
ON : Conversion enabled
.....
wire breakage detection is conducted at the same time
the temperature of the target object is taken.
OFF : Conversion disabled
....
neither temperature taking or wire breakage detection
is conducted.
By setting of conversion enable/disable, the following changes are made.
When conversion is changed from disabled
enabled
Temperature detection of the enabled channel is commenced. After the detected temperature value of the corresponding channel is stored in the remote register, the conversion completion flag of the corresponding channel is turned on.
When the conversion is changed from enabled
disabled.
The conversion completion flag is turned off for the corresponding channel. For the detected temperature value stored in the remote register, the data immediately prior to the disable setting will be retained.
RYn8 to RYnF
CH.
sampling processing/ travel average processing designation
flag
It is possible to designate the sampling processing or travel average processing for each independent channel.
ON : Travel average processing
OFF : Sampling processing
In travel average processing, an average value of four detected temperature value samples that were taken during each sampling time is calculated and stored in the remote register.
When changed from sampling processing
travel average processing
The conversion completion flag for the corresponding channel is turned off. An average value of four detected temperature value samples is calculated, and after it has been stored to the remote register the conversion completion flag of the corresponding channel is turned on.
When changed from travel average processing
sampling processing
The conversion completion flag is turned off for the corresponding channel. After the most recent detected temperature value is stored in the remote register, the conversion completion flag for the corresponding channel is turned on.
Note : This flag is only valid when the initial data processing completion flag (RY (n+7)
8) or initial data setting request flag (RY (n+7) 9) is on.
3. SPECIFICATIONS MELSEC-A
3-14
Device No. Signal name Description
RY (n+1) 0
to
RY (n+1) 6
CH.1 thermocouple selection flag
RY (n+1) 8
to
RY (n+1) E
CH.2 thermocouple selection flag
RY (n+2) 0
to
RY (n+2) 6
CH.3 thermocouple selection flag
RY (n+2) 8
to
RY (n+2) E
CH.4 thermocouple selection flag
RY (n+3) 0
to
RY (n+3) 6
CH.5 thermocouple selection flag
RY (n+3) 8
to
RY (n+3) E
CH.6 thermocouple selection flag
RY (n+4) 0
to
RY (n+4) 6
CH.7 thermocouple selection flag
RY (n+4) 8
to
RY (n+4) E
CH.8 thermocouple selection flag
All CH. batch thermocouple selection flag
All channels are selected to the same thermocouple in batch. This flag takes priority over the thermocouple selection flag for individual channels. The thermocouple selection flag for individual channels may only be used when this flag is off.
Also, when multiple batch thermocouple selection flags are turned on, the write data error flag is turned on and the previously selected thermocouple type is retained.
Refer to the I/O signal list for the correspondence between each signal and thermocouple type.
Note : This flag is only valid when the initial data processing compensation flag
(RY(n+7)8) or initial data setting request flag (RY (n+7) 9) is on.
RY (n+5) 7
The detected temperature value to be stored in the remote register can be selected
from a value that has undergone cold junction compensation by Pt100 temperature­measuring resistor, and a value that has not (the cold junction compensation is performed externally).
ON : Cold contact compensation is not performed by the Pt100 temperature-
measuring resistor.
OFF : Cold contact compensation is performed by the Pt100 temperature-measuring
resistor.
Note : This flag is only valid when the initial data processing compensation flag
(RY(n+7)8) or initial data setting request flag (RY (n+7) 9) is on.
Selects the type of thermocouple to be connected to each channel.
Only the flags appropriate for the thermocouple to be used are turned on.
It is read as the set value when the initial data processing request flag is turned on.
When the flag is off after power on or a hardware reset, the K type is selected.
Also, when multiple thermocouple selection flags are turned on, the write data error flag is turned on and the previously selected thermocouple type is retained.
Refer to the I/O signal list for the correspondence between each signal and thermocouple type.
Note : This flag is only valid when the initial data processing compensation flag
(RY(n+7)8) or initial data setting request flag (RY (n+7) 9) is on.
RY (n+5) 0
to
RY (n+5) 6
Pt100 cold junction compensation disable flag
3. SPECIFICATIONS MELSEC-A
3-15
Device No. Signal name Description
Select whether or not the offset/gain value will be set to "user setting" or "factory
setting."
At the product shipment from factory, the same values for the factory settings are stored in the E
2
PROM for storing the user setting offset/gain values.
ON : Factory setting (Offset-gain, 100.0
Ω (0 °C equivalent) -300 °C)
OFF : User setting
Note : This flag is only valid when the initial data processing compensation flag (RY
(n+7) 8) or initial data setting request flag (RY (n+7) 9) is on.
RY (n+7) 8
Initial data processing completion flag
After power on or hardware reset, the initial data are set in the module by turning this flag on during the initial data processing request .
Used when designating sampling processing/travel average processing designation, selecting offset/gain value, setting upper and lower limits, Pt100 cold junction compensation enable/disable designation or selecting thermocouples.
Turned on when changing the initial values.
Used when designating sampling processing/travel average processing, selecting offset/gain value, setting upper and lower limits, or Pt100 cold junction compensation enable/disable designation.
Error reset request flag
When this flag is turned on, the wire breakage detection flag/write data error flag are reset (turned off), and the error status flags are reset at the same time. However, the E
2
PROM error flag may not be reset (turned off) and therefore the error status flag will
remain on.
n : Address assigned to the master module by the station number setting.
RY (n+7) 7
Offset/gain value selection flag
RY (n+7) 9
Initial data setting request flag
RY (n+7) A
3. SPECIFICATIONS MELSEC-A
3-16
3.8.3 Wire breakage detection
The AJ65BT-68TD detects wire breakage in the thermocouple or compensating conductor used for each channel, and turns on the wire breakage detection flag (RXn8 to RXnF) for the corresponding channel. On the AJ65BT-68TD, the wire breakage detection are performed for channels that are enabled for conversion. The relationships between the wire breakage detection and conversion enable/disable are shown below.
Connection status Conversion enabled/disabled setting Wire breakage detection flag
Conversion enabled
Conversion disabled
Conversion enabled ON
Conversion disabled OFF
Conversion enabled ON
Conversion disabled OFF
POINT
Be sure to set the channels having no thermocouple attached to "conversion disabled." If a channel having no thermocouple attached is set to "conversion enabled," the wire breakage detection flag will turn on.
The channels for which wire breakage detection turned on will retain the normal detected temperature value immediately prior to the breakage detection, and the conversion completion flag for the corresponding channel will turn off. When the detected breakage is fixed, updating of detected temperature value after repair will be resumed and the conversion completion flag will be turned on again.
For thermocouple wiring details, refer to Section 4.7.
+
No breakage
+
Breakage
+
No connection
OFF
Loading...
+ 72 hidden pages