Mitsubishi Electric AE-200A, AE-50E, EW-50E, AE-50A, EW-50A Instruction Manual

...
Contents
Safety precautions ..............................................................................2
1. Parts to be used ...........................................................................4
1-1. Required parts .......................................................................4
1-2. Separately sold parts ............................................................4
1-3. Commercially available parts ................................................4
2. Before use ....................................................................................5
2-1. Introduction ...........................................................................5
2-2. License ..................................................................................5
2-3. Models of units that can be controlled with BACnet
®
............6
2-4. Restrictions and cautions ......................................................6
3. Usage (System configurations) ....................................................7
3-2. Group configurations ...........................................................10
4. Usage (Communication specifications) ...................................... 11
4-1. BACnet
®
specifications ........................................................ 11
4-2. Communication protocol specifications ............................... 11
4-3. Objects ................................................................................12
4-4. Services ..............................................................................14
4-5. Services for each object ......................................................16
5. Usage (Function specifications) .................................................17
5-1. Controller functions and BACnet
®
functions ........................17
5-2. Basic functions ....................................................................19
5-3. Set temperature objects ......................................................25
5-4. “System Forced Off” forced-reset function ..........................25
5-5. Apportioned electricity billing function .................................26
5-6. Alarm Signal ........................................................................ 30
5-7. Event service specifications ................................................31
5-8.
BACnet® information and storage timing/cycle in nonvolatile memory within the AE-200/AE-50/EW-50
.............................33
6.
Usage (AE-200/AE-50/EW-50 BACnet® connection mode)
.........34
6-1.
AE-200/AE-50/EW-50
BACnet® connection mode ...............34
7. Checking installation operations and performing trial run ..........35
7-1. Flow of initial settings ..........................................................35
7-2. Preparatory items for initial settings ....................................37
7-3. Step-1 Initial settings for the air conditioning system ..........38
7-5. Step-3 Initial settings for the BACnet
®
related items ...........41
7-6. Step-4 Trial run of BACnet
®
function ...................................42
7-7. When changing settings or reconfiguring AE-200/AE-50/
EW-50 .................................................................................55
Appendix: Added functions ............................................................... 57
Air Conditioning Control System
Centralized Controller AE-200A/AE-50A/EW-50A AE-200E/AE-50E/EW-50E
Before using the controller, please read this Instruction Book carefully to ensure proper operation. Retain this manual for future reference. BACnet
®
is a registered trademark of ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers, INC.).
Instruction Book
–BACnet® function–
<ORIGINAL>
2
WT07919X04
Safety precautions
►Observe these precautions carefully to ensure safety. ►After reading this manual, pass the manual on to the end user to retain for future
reference.
►The user should keep this manual for future reference and refer to it as necessary. This
manual should be made available to those who repair or relocate the units. Make sure that the manual is passed on to any future air conditioning system user.
: indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
: indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
: addresses practices not related to personal injury, such as product
and/or property damage.
General precautions
Do not install the controller in areas where large amounts of oil, steam, organic solvents, or corrosive gases (such as ammonia, sulfuric compounds, or acids), or areas where acidic/alkaline solutions or special chemical sprays are used frequently. These substances may significantly reduce the performance and corrode the internal parts, resulting in electric shock, malfunction, smoke, or fire.
To reduce the risk of short circuits, current leakage, electric shock, malfunction, smoke, or fire, do not wash the controller with water or any other liquid.
To reduce the risk of electric shock, malfunction, smoke, or fire, do not touch the electrical parts, USB memory, or touch panel with wet fingers.
To reduce the risk of injury or electric shock, before spraying a chemical around the controller, stop the operation and cover the controller.
To reduce the risk of injury, keep children away while installing, inspecting, or repairing the controller.
If you notice any abnormality (e.g., burning smell), stop the operation, turn off the controller, and consult your dealer. Continuing the operation may result in electric shock, malfunction, or fire.
Properly install all required covers to keep moisture and dust out of the controller. Dust accumulation and the presence of water may result in electric shock, smoke, or fire.
To reduce the risk of fire or explosion, do not place flammable materials or use flammable sprays around the controller.
To reduce the risk of electric shock or malfunction, do not touch the touch panel, switches, or buttons with a sharp object.
To avoid injury from broken glass, do not apply excessive force to the glass parts.
3
WT07919X04
To reduce the risk of injury, electric shock, or malfunction, avoid contact with the sharp edges of certain parts.
Consult your dealer for the proper disposal of the controller. Improper disposal will pose a risk of environmental pollution.
Precautions for relocating or repairing the unit
The controller must be repaired or moved only by qualified personnel. Do not disassemble or modify the controller. Improper installation or repair may result in injury, electric shock, or fire.
Additional precautions
To avoid discoloration, do not use benzene, thinner, or chemical rag to clean the controller. When the controller is heavily soiled, wipe the controller with a well-wrung cloth that has been soaked in water with mild detergent, and then wipe off with a dry cloth.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Terms used in this manual
- “Centralized Controller AE-200A/AE-200E” is referred to as “AE-200”.
- “Centralized Controller AE-50A/AE-50E” is referred to as “AE-50”.
- “Centralized Controller EW-50A/EW-50E” is referred to as “EW-50”.
- “PI controller (PAC-YG60MCA)” is referred to as “PI controller”.
- “AI controller (PAC-YG63MCA)” is referred to as “AI controller”.
- “OA Processing Unit (LOSSNAY with heater and humidifier)” is referred to as “OA Processing Unit”.
- “e-Series chiller unit (EAHV, EACV)” is referred to as “Chiller unit”.
4
WT07919X04
1. Parts to be used
1-1. Required parts
Obtain the items listed below from your dealer before using this function.
No. Item Remarks
1
AE-200/AE-50/EW-50 Instruction Book (BACnet
®
function)
This manual
2
“BACnet connection” license for AE-200/AE-50/EW-50
Required for each AE-200/AE-50/EW-50 that connects to BACnet
®
.
3 BACnet
®
Setting Tool Used for configuring BACnet® function for AE-200/AE-50/EW-50.
4
Software update file Used for updating the AE-200/AE-50/EW-50 to the latest version.
The versions of all AE-200/AE-50/EW-50 that connect to BACnet
®
must be the same.
The items listed above are essential to use the BACnet
®
function. For equipment that are required for initial settings and trial runs of the BACnet® function, refer to section 7-2 “Preparatory items for initial settings”. When using the apportioned electricity billing function with the BACnet® function, the parts that are used for the apportioned electricity billing function are also required. For details, refer to the AE-200/AE-50/EW-50 Instruction Book (Apportioned Electricity Billing Function).
1-2. Separately sold parts
None. When using the apportioned electricity billing function with the BACnet® function, the parts that are used for the apportioned electricity billing function are also required. For details, refer to the AE-200/AE-50/EW-50 Instruction Book (Apportioned Electricity Billing Function).
1-3. Commercially available parts
Where necessary, prepare the commercially available parts listed below.
Item Qty Remarks
Communication item
LAN cable As appropriate
Category 5 or above straight cable (Max. 100 m (328 ft))
*1
Switching HUB Required number 100 BASE-TX-compatible
*1 If the LAN cable is to be longer than 100 m, pass this through a switching HUB.
When using the apportioned electricity billing function with the BACnet® function, the parts that are used for the apportioned electricity billing function are also required. For details, refer to the AE-200/AE-50/EW-50 Instruction Book (Apportioned Electricity Billing Function).
5
WT07919X04
2. Before use
This manual explains how to use the AE-200/AE-50/EW-50 BACnet® function. For how to install AE-200/AE-50/EW-50 or how to use the functions other than the BACnet® function, refer to the AE-200/AE-50/EW-50 Installation Manual and Instruction Book. For how to use the BACnet® Setting Tool, refer to the AE-200/AE-50/EW-50 Instruction Book (BACnet® Setting Tool). When using the apportioned electricity billing function with the BACnet® function, refer to the AE-200/AE-50/EW-50 Instruction Book (Apportioned Electricity Billing Function) and the AE-200/AE-50/EW-50 Instruction Book (BACnet® Apportioned Electricity Billing Function Trial Run).
2-1. Introduction
The AE-200/AE-50/EW-50 BACnet® function can be used when connecting AE-200/AE-50/EW-50 to the open network BACnet® that is used for the building management system. The air conditioning units connected to AE-200/AE-50/EW-50 can be monitored and operated not only from the existing web browser or the AE-200/AE-50’s LCD, but also from the building management system using the BACnet® communication protocol.
Note
The explanation of the BACnet® function in this manual is based on the specification of AE-200/AE-50/ EW-50 software version 7.50.
2-2. License
The licenses related to the AE-200/AE-50/EW-50 BACnet® function are as follows.
License name Requirement condition Required number and remarks
“BACnet connection”
Required when using the BACnet
®
function
One license is required for each AE-200/AE-50/EW-50 that connects to BACnet®.
“Charge”
Required when using the apportioned electricity billing function
One license is required for the AE-200 that is used for electricity apportioning and each AE-50/EW-50 that connects to the AE-200.
6
WT07919X04
2-3. Models of units that can be controlled with BACnet
®
The table below shows models that can connect to AE-200/AE-50/EW-50, and models that can be controlled with the BACnet® function.
V: Connectable/Controllable —: Not connectable/Not controllable
Model
Connectable/Not connectable
to AE-200/AE-50/EW-50
Controllable/Not controllable
with BACnet
®
CITY MULTI
S series V V
Y series V V
HP series V V
R2 series V V
WY series V V
WR2 series V V
HVRF series V V
LOSSNAY V
V
(Only when groups are configured.)
OA Processing Unit V
V
(Only when groups are configured.)
Air To Water Booster unit/Air To Water (PWFY) V V
A-control unit (Mr. Slim) An adapter is required. V
K-control unit
Room air conditioner (RAC) An interface is required. V Hot Water Heat Pump unit
(CAHV, CRHV, QAHV)
V
Chiller unit V
DIDO controller (PAC-YG66DCA) V
PI controller (PAC-YG60MCA) V V
AI controller (PAC-YG63MCA) V
2-4. Restrictions and cautions
Restrictions and cautions for AE-200/AE-50/EW-50 BACnet® functions are as follows.
(1) Action to take when an error occurs
Immediately carry out repairs to the problem area when an error related to air conditioning units is detected on the building management system.
(2) Functions
Due to continuing improvement, specifications are subject to change without notice.
(3) Request interval
When sending “ReadProperty” or “WriteProperty” from the building management system to the AE-200/AE-50/EW-50, set the interval to 200 (ms/property) or above.
When sending 10 properties using “ReadPropertyMultiple”, wait for at least 2000 ms (= 200 ms × 10 properties) before sending another request to the AE-200/AE-50/EW-50.
ReadPropertyReadProperty WriteProperty
200 ms
ReadProperty WriteProperty
200 ms 200 ms200 ms
ReadProperty
ReadPropertyMultiple (10 properties)
2000 ms (200 ms × 10 properties)
7
WT07919X04
3. Usage (System configurations)
3-1. Sample system configurations
(1) When controlling 50 or fewer units of equipment and not using an apportioned electricity
billing function
*1 Use a switching HUB to connect to LAN1 and LAN2 (BACnet®). Do not connect LAN1 and LAN2 (BACnet®) to the same HUB. *2 A PC (hereafter referred to as Setting PC) is required to make settings for the AE-200/EW-50 BACnet
®
functions. After making settings, disconnect the Setting PC as well as LAN cables and HUBs used to connect to the Setting PC from the AE-200/EW-50. Refer to section 7 “Checking installation operations and performing trial run” for details.
Setting PC
*2
Outdoor unit
HUB
*1
Outdoor unit
ME remote controller
ME remote controller
Indoor unit
LAN1
Indoor unit
M-NET
LOSSNAY
M-NET
LOSSNAY
BACnet
®
HUB
*1
EW-50
M-NET
HUB
*1
AE-200
or
Building management system
LAN2
8
WT07919X04
(2) When controlling more than 50 units of equipment *3 and not using an apportioned
electricity billing function
*1 Use a switching HUB to connect to LAN1 and LAN2 (BACnet®). Do not connect LAN1 and LAN2 (BACnet®) to the same HUB. *2 A PC (hereafter referred to as Setting PC) is required to make settings for the AE-200/AE-50/EW-50 BACnet
®
functions. After making settings, disconnect the Setting PC from the AE-200/AE-50/EW-50. Refer to section 7 “Checking installation operations and performing trial run” for details.
*3 Up to 50 units of equipment can be connected to and controlled by each AE-200/AE-50/EW-50. If performing centralized control with an
AE-200, up to 3 AE-50/EW-50 can be connected to a single AE-200 (if not using AE-200 M-NET, up to 4 can be connected).
*4 If performing centralized control with an AE-200, because time synchronization from the building management system comes through
the AE-200, then for systems including those that do not have BACnet
®
control functions, configure so that AE-200 is connected to the
BACnet®, by connecting devices to control with BACnet® to the AE-200.
Setting PC
*2
HUB
*1
LAN1
M-NET
BACnet
®
HUB
*1
AE-50/EW-50
HUB
*1
Building management system
HUB
*1
AE-200
*4
/EW-50
Outdoor
unit
LAN2
LAN1
ME remote controller
Outdoor
unit
M-NET
ME remote controller
M-NET
Outdoor
unit
M-NET
Indoor unit
ME remote controller
Outdoor
unit
Indoor unit
M-NET
LAN2
LAN1
ME remote controller
M-NET
M-NET
Indoor unit
AE-50/EW-50
LOSSNAY
Outdoor unit/indoor unit etc.
LAN2
Indoor unit
LAN1
LOSSNAY
M-NET
AE-50/EW-50
LOSSNAY
Outdoor unit/indoor unit etc.
LOSSNAY
LAN2
9
WT07919X04
(3) When using an apportioned electricity billing function
*4
*1 Use a switching HUB to connect to LAN1 and LAN2 (BACnet®). Do not connect LAN1 and LAN2 (BACnet®) to the same HUB. *2 A PC (hereafter referred to as Setting PC) is required to make settings for the AE-50/EW-50 BACnet
®
functions. After making settings, disconnect the Setting PC from the AE-50/EW-50. Refer to section 7 “Checking installation operations and performing trial run” for details.
*3 If using the apportioned electricity billing function, we recommend that instead of using the AE-50/EW-50 built-in Pulse Input (PI), the PI
controller be used for measurement of electric energy. (If AE-50/EW-50 built-in Pulse Input (PI) is used, pulse input will not be possible when the AE-50/EW-50 is stopped, during power outages or during software updates. This could result in discrepancies between the measurements and the actual electric energy consumed.) When using the AE-50/EW-50 built-in Pulse Input (PI), approve the above-mentioned restrictions for the customer and then use.
*4 Up to 50 units of equipment can be connected to and controlled by each AE-50/EW-50. Up to 4 AE-50/EW-50 controllers can be
connected to each AE-200 for billing function.
*5 To use an apportioned electricity billing function and perform date and time synchronization from the building management system, set
the “Time Master/Sub” setting to “Sub” on the AE-200 for billing function and synchronize the time from AE-50/EW-50 connected to BACnet
®
. The “Time Master/Sub” setting can be made on the Initial Setting Tool, Web Browser for Initial Settings, or AE-200/AE-50’s
LCD. (Refer to the AE-200/AE-50/EW-50 Instruction Book (Initial Settings) for settings methods.)
*6 If using the apportioned electricity billing function, connection of M-NET and Pulse Input (PI) to the AE-200 for billing function is
prohibited. Accordingly, the AE-200 for billing functions does not have any BACnet
®
control devices, and BACnet® connection is not
necessary. As a result, BACnet® settings and "BACnet connection" license are not required for the AE-200 for billing function.
*7 If using the apportioned electricity billing function, connection of LAN1 for transfer of power apportioning information is required.
Setting PC
*2
HUB
*1
LAN1
*7
M-NET
BACnet
®
HUB
*1
AE-50/ EW-50
HUB
*1
Building management system
HUB
*1
AE-200
*5 *6
LAN2
LAN1
*7
PI controller
Outdoor
unit
M-NET
ME remote controller
Outdoor
unit
M-NET
ME remote controller
Indoor unit
M-NET
LAN2
LAN1
*7
M-NET
Indoor unit
AE-50/EW-50
Outdoor unit/indoor unit etc.
LAN2
LAN1
*7
LOSSNAY
M-NET
AE-50/EW-50
LOSSNAY
Outdoor unit/indoor unit etc.
LAN2
LAN1 needs to be connected to the AE-200 for billing function. LAN2 (BACnet
®
), M-NET, and Pulse Input (PI) cannot be connected to the AE-200 for
billing function.
Electricity meter
*3
Electricity meter
LAN1
*7
LAN2
AE-50/ EW-50
M-NET
Pulse signal
Electricity meter
*3
Outdoor unit/indoor unit etc.
Pulse signal
Electricity meter
*3
Pulse signal
Electricity meter
*3
Pulse signal
Pulse signal
10
WT07919X04
3-2. Group configurations
The basic functions of the BACnet® function can be performed for each unit group. Multiple indoor units (ICs) in a group can collectively be controlled. The group number is a range of 1 to 50.
Building management system
BACnet
®
AE-200/AE-50/EW-50
LAN2
M-NET
* Outdoor units and remote
controllers are omitted in this figure.
Air conditioning equipment
IC
01
Group
No. 1
IC 02
IC 03
IC (Indoor unit)
IC 04
Group
No. 2
IC
05
Unit address
Group number
11
WT07919X04
4. Usage (Communication specifications)
4-1. BACnet® specifications
BACnet® communication specifications are based on ANSI/ASHRAE Standard 135-2010.
4-2. Communication protocol specifications
(1) Overview of protocol
Use BACnet®/IP based on ANSI/ASHRAE Standard 135-2010 on UDP/IP of Ethernet®*.
LAN2 is used to connect BACnet
®
.
Ether header IP header UDP header BVLL header NPCI header APDU
* Ethernet
®
is a registered trademark of Fuji Xerox Co., Ltd.
(2) Ether header
The physical layer is Ethernet® and the specifications are 100BASE-TX.
(3) IP header
A Class C private address is recommended *1. The sub-net mask is 255. 255. 255. 0.
*1 Recommended values (range): [192.168.2.1] to [192.168.254.254]
[192.168.0.0] and [192.168.255.255] should not be used for a LAN2 IP address. An IP address set using LAN1 should not be used as a LAN2 IP address.
LAN1 and LAN2 network addresses must not be the same.
(4) UDP header
47808 (0xBAC0) is recommended for the default UDP port for unicast and broadcast.
(5) BVLL header
BVLC type (1 octet): 0x81 fixed (BVLL for BACnet®/IP) BVLC function (1 octet): 0x0A for unicast
0x0B for broadcast BVLC length (2 octets): Variable (BVLL header (4) + APDU data length) (The above is a typical example. For details, refer to ANSI/ASHRAE Standard 135-2010.)
(6) BACnet® NETWORK NPCI header
Version (1 octet): 0x01 fixed Control (1 octet): 0x04 with response message
0x00 without response message
(The above is a typical example. For details, refer to ANSI/ASHRAE Standard 135-2010.)
(7) APDU for BACnet
®
Data of 1,024 octets and under. (Refer to ANSI/ASHRAE Standard 135-2010 for details.)
12
WT07919X04
4-3. Objects
Support status for objects and for BACnet® functions are listed below.
V: Supported —: Not supported
Object type
*1
Abbreviation
Supported/
Not supported
Object
Access Credential (32)
Access Door (30)
Access Point (33)
Access Rights (34)
Access User (35)
Access Zone (36)
Accumulator (23) AC V
Group Apportioned Electric Energy Interlocked Units Apportioned Electric Energy PIcontroller Electric Energy 1–4 Pulse Input Electric Energy 1–4 Group Apportionment Parameter Interlocked Units Apportionment Parameter
Analog Input (0) AI V
Room Temp [Water Temp] Error Code Detail
Analog Output (1)
Analog Value (2) AV V
Set Temp [Set Water Temp] Set Temp Cool Set Temp Heat Set Temp Auto Set High Limit Setback Temp Set Low Limit Setback Temp
Averaging (18)
Binary Input (3) BI V
On Off State Alarm Signal
*2
Filter Sign [Circulating Water Exchange Sign] M-NET Communication State Night Purge State Thermo On Off State System Alarm Signal
*2
External Heat Source State PIcontroller Alarm Signal
*2
Binary Output (4) BO V On Off Setup
*3
Binary Value (5) BV V
Filter Sign Reset [Circulating Water Exchange Sign Reset] Prohibition On Off
*3
Prohibition Mode Prohibition Filter Sign Reset [Prohibition Circulating Water Exchange Sign Reset] Prohibition Set Temperature Prohibition Fan Speed System Forced Off (individual)/(collective)
*4
BitString Value (39)
Calendar (6) — CharacterString
Value
(40)
Command (7)
Credential Data Input (37)
Date Pattern Value (41)
Date Value (42) — DateTime Pattern
Value
(43)
DateTime Value (44)
Device (8) DEV V Device object of AE-200/AE-50/EW-50
Event Enrollment (9)
Event Log (25)
13
WT07919X04
Object type
*1
Abbreviation
Supported/
Not supported
Object
File (10)
Global Group (26)
Group (11)
Integer Value (45)
Large Analog Value (46)
Life Safety Point (21)
Life Safety Zone (22)
Load Control (28)
Loop (12)
Multi-state Input (13) MI V
Error Code Operational Mode State Fan Speed State Air Direction State Ventilation Mode State Air To Water Mode State
Multi-state Output (14) MO V
Operational Mode Setup Fan Speed Setup Air Direction Setup Ventilation Mode Setup Air To Water Mode Setup
Multi-state Value (19)
Network Security (38)
Notification Class (15) CLS V Notification Class
OctetString Value (47) — Positive Integer
Value
(48)
Program (16)
Pulse Converter (24)
Schedule (17)
Structured View (29)
Time Pattern Value (49)
Time Value (50)
Trend Log (20) LOG V
Trend Log Room Temp Trend Log Group Apportioned Electric Energy Trend Log Interlocked Units Apportioned Electric Energy Trend Log PIcontroller Electric Energy 1–4 Trend Log Pulse Input Electric Energy 1–4 Trend Log Group Apportionment parameter Trend Log Interlocked Units Apportionment parameter
Trend Log Multiple (27)
*1 Values within parentheses are “Object_Type” property values. *2 Outputs an error code (4-digit) in Description and Message Text of event notification. *3 Do not use this when “External Input Setting” for AE-200/AE-50/EW-50 is set to “ON/OFF (Level signal)”. “External Input Setting” can
be configured on the Initial Setting Tool, Web Browser for Initial Settings, or AE-200/AE-50’s LCD. (Refer to the AE-200/AE-50/EW-50 Instruction Book (Initial Settings) for settings methods.)
*4 Executes the stop command and remote controller operation prohibition (run/stop) command for air conditioning units.
14
WT07919X04
4-4. Services
The BACnet® service support status is shown below.
V: Supported —: Not supported Initiate request: Provides services Execute request: Receives and uses services
Service Initiate request Execute request
1. Alarm and Event Services
(1) Acknowledge Alarm Service
(2) ConfirmedCOVNotification Service V
(3) ConfirmedEventNotification Service V
(4) GetAlarmSummary Service
(5) GetEnrollmentSummary service
(6) GetEventInformation Service V
(7) LifeSafetyOperation Service
(8) SubscribeCOV Service
*1
V
(9) SubscribeCOVProperty Service
2. File Access Services
(1) AtomicReadFile Service
(2) AtomicWriteFile Service
3. Object Access Services
(1) AddListElement Service V
(2) RemoveListElement Service V
(3) CreateObject Service
(4) DeleteObject Service
(5) ReadProperty Service V
(6) ReadPropertyConditional Service
(7) ReadPropertyMultiple Service V
(8) ReadRange Service V
(9) WriteProperty Service V
(10) WritePropertyMultiple Service V
4. Remote Device Management Services
(1) DeviceCommunicationControl Service
(2) ConfirmedPrivateTransfer Service
(3) ConfirmedTextMessage Service
(4) ReinitializeDevice Service
5. Virtual Terminal Services
(1) VT-Open Service
(2) VT-Close Service
(3) VT-Data Service
6. Security Services
(1) Authenticate Service
(2) Request Key Service
7. Unconfirmed Services
(1) I-Am V V
15
WT07919X04
Service Initiate request Execute request
(2) I-Have V
(3) UnconfirmedCOVNotification Service V
(4) UnconfirmedEventNotification Service V
(5) UnconfirmedPrivateTransfer Service
(6) UnconfirmedTextMessage Service
(7) TimeSynchronization Service V
(8) UTCTimeSynchronization Service
(9) Who-Has V
(10) Who-Is V V
*1 The maximum number of COV notifications which can be registered is 3,150. However, 5 is the maximum number of COV notifications
which can be registered in which Lifetime is not = 0.
16
WT07919X04
4-5. Services for each object
The table below lists the supported services for each object.
: Supported
: Settings can be changed on the BACnet
®
Setting Tool. INIT: Provides services (Initiate) EXEC: Receives and executes services (Execute)
Device
Analog Input
Analog Value
Binary Input
Binary Output
Binary Value
Multi-State Input
Multi-State Output
Notification Class
Accumulator
Trend Log
ConfirmedCOVNotification
INIT
EXEC
ConfirmedEventNotification
INIT
EXEC
GetEventInformation
INIT
EXEC
SubscribeCOV
INIT
EXEC
AddListElement
INIT
EXEC
RemoveListElement
INIT
EXEC
ReadProperty
INIT
EXEC
ReadPropertyMultiple
INIT
EXEC
ReadRange
INIT
EXEC
WriteProperty
INIT
EXEC
WritePropertyMultiple
INIT
EXEC
I-Am
INIT
EXEC
I-Have
INIT
EXEC
UnconfirmedCOVNotification
INIT
EXEC
UnconfirmedEventNotification
INIT
EXEC
TimeSynchronization
INIT
EXEC
Who-Has
INIT
EXEC
Who-Is
INIT
EXEC
Object
Service
17
WT07919X04
5. Usage (Function specifications)
The AE-200/AE-50/EW-50 BACnet® function mutually converts communications for air conditioning equipment connected to the AE-200/AE-50/EW-50 and for BACnet® communications.
5-1. Controller functions and BACnet® functions
The table below lists the supported controller functions which can monitor/operate from the web browser or the AE-200/AE-50’s LCD and the BACnet® functions.
V: Supported —: Not supported
Classification Item Controller function BACnet® function Remarks
Monitor/ Operation
On Off Setup V V
On Off State V V
Operational Mode Setup V V
Operational Mode State V V
Fan Speed Setup V V
Fan Speed State V V
Air Direction Setup V V
BACnet
®
does not support “Downblow 20%” and “Auto” settings.
Air Direction State V V
BACnet
®
does not support “Downblow 20%” and “Auto” settings.
Room Temp [Water Temp]
V V
Set Temp [Set Water Temp]
V V
Set Temp Cool V V
Set Temp Heat V V
Set Temp Auto V V
Set High Limit Setback Temp V V
Only AE-200A/AE-50A/EW-50A
Set Low Limit Setback Temp V V
Only AE-200A/AE-50A/EW-50A
Ventilation Mode Setup V V
Ventilation Mode State V V
Air To Water Mode Setup V V
Air To Water Mode State V V
Night Purge Setup V
Night Purge State V V
Prohibition On Off V V
Prohibition Mode V V
Prohibition Filter Sign Reset [Prohibition Circulating Water Exchange Sign Reset]
V V
Prohibition Set Temperature V V
Prohibition Timer V
Prohibition Air Direction V
Prohibition Fan Speed V V
System Forced Off (individual)
V V
System Forced Off (collective)
V V
Thermo On Off State V
*1
V
*2
External Heat Source State V
Output status of indoor unit CN24
18
WT07919X04
Classification Item Controller function BACnet® function Remarks
Alarm monitor
Alarm Signal (Air conditioning unit/PI controller)
V V
Error Code V V
Controllers support 4-digit error codes, and BACnet
®
supports
1- and 4-digit error codes.
System Alarm Signal V V
M-NET Communication State V V
Filter Sign [Circulating Water Exchange Sign]
V V
Filter Sign Reset [Circulating Water Exchange Sign Reset]
V V
Control functions
Command Failure V
High Limit/Low Limit Alarm V
*3
V
Night Setback control V
Schedule control V
Interlock control V
Data management functions
Energy management data/ Trend log
V V
These are collected individually in the body/BACnet
®
, so sometimes the values of these do not coincide.
Group Apportioned Electric Energy
V V
Interlocked Units Apportioned Electric Energy
V V
Group Apportionment Parameter
V V
BACnet
®
function has only
parameters for outdoor units.
Interlocked Units Apportionment Parameter
V V
BACnet
®
function has only
parameters for outdoor units.
PIcontroller Electric Energy (Ch 1–4)
V V
Pulse Input Electric Energy (Metering device 1–4)
V V
Other functions
Unit of temperature setting V V
This setting on the AE-200/AE-50/EW-50 and the one on the BACnet
®
are
different. On the BACnet
®
, only the unit of temperature that is used for BACnet
®
communication can be set.
Cumulative operation time/ FAN operation time
V
Time management V V
BACnet
®
router V
LCD lock V
*1 Supports only Thermo-ON time, Thermo-ON/OFF count.
Thermo-ON/OFF count cannot be monitored from the AE-200/AE-50’s LCD or web browser, but can be checked with the CSV output
function. *2 Supports only Thermo-ON/OFF state. *3 Alarms can occur when the upper and lower limit values are exceeded due to the AI controller (option).
Loading...
+ 42 hidden pages