Miele PW 6163 EL Installation diagram

Installation plan
Washer
en - US
11.11 M.-Nr. 09 284 570 / 01
2
M.-Nr. 09 284 570 / 01
Technical Data Sheet
Washer: Type of heating:
PW 6163 Electric
Legend:
Circled, bold-type abbreviations mean: Connection required
en - US
Abbreviations surrounded by broken circle: Connection optional or required, depending on model
BWS
Miele vapor and
foam discharge
kit
Vapor extractor in component (inner diameter)
4 5/16” [DN 4” sleeve]
110 mm [DN 100 sleeve]
Foam extractor supports in component (outer diameter)
4 5/16” [DN 4”]
110 mm[DN 100]
Liquid condensate is drained from the vapor extractor by a run-off system installed on-site. Optionally, the foam can be drained into the machine discharge through an integrated line.
ISA
Integrated foam
discharge
Connecting line
1 15/16” [DN 2” sleeve]
50 mm [DN 50 sleeve]
Machine housing lead-through (diameter)
2 1/2”
63.5 mm
MSG
Miele booster fan
Standard voltage
1N AC 230 V
1N AC 230 V
Frequency
50 Hz
50 Hz
Rated load
0.03 kW
0.03 kW
Air throughput, max.
150 m³/h
150 m³/h
Pressure differential, max.
170 Pa
170 Pa
Sound output level
60 dB (A)
60 dB (A)
UM
Miele base
Closed-in base
Height
6 11/16”
170 mm
Width
43 11/16”
1,110 mm
Depth
34 1/4”
870 mm
WI
Weighing system
Base with built-in weighing system
Height
6 11/16”
170 mm
Width
43 11/16”
1,110 mm
Depth
34 1/4”
870 mm
No external loads or weights may act on the appliance when using the weighing system.
A temporary or static weight load on the housing can prevent calibration of the measuring cells, with the result that fault­free functioning of the weighing system cannot be guaranteed.
Options/Accessories:
Installationsplan / Installation plan: PW 6163 EL
Datum / Date: 16.03.2011 Seite / Page: 9
Standard voltage (as delivered) *
3 AC 220-240 V
3 AC 220-240 V
Frequency
50 – 60 Hz
50 – 60 Hz
Rated load
18.0 kW
18.0 kW
Fuse rating
3 × 50 A
3 × 50 A
Connection cable (not included)
Cross section, minimum
4 × 10 mm²
4 × 10 mm²
With threaded cable fitting
M 40 x 1.5
M 40 x 1.5 Alternative voltage
reversible
3 AC 208 V
3 AC 208 V
Frequency
60 Hz
60 Hz Rated load
15.3 kW
15.3 kW Fuse rating
3 × 50 A
3 × 50 A
Connection cable (not included)
Cross section, minimum
4 × 10 mm²
4 × 10 mm²
With threaded cable fitting
M 40 x 1.5
M 40 x 1.5
* If power supply includes a stinger leg, please contact Technical Service at USA 1-800-991-9380 CDN 1-800-643-5361
To facilitate electrical safety checks, we recommend connecting the appliance via a wall receptacle that can be switched off at all poles and locked according to IEC 60309 and IEC 60947. If the appliance is hard wired, a mains separator according to IEC 60947 must be installed. The wall receptacle or mains separator must be visible and accessible after the appliance has been installed. For added safety, we recommend installing a residual current device in the power supply. In that case, an AC/DC­sensitive residual current device is required. If required by national regulations, a potential equalization with good contact connection must be provided.
Cold water
(Soft water)
Minimum flow pressure
14.5 psi
100 kPa
Maximum pressure
145.04 psi
1,000
Required volume flow
5.7 gal/min
26 l/min
Max. volume flow in absence of hot and hard water supply.
17.48 gal/min
79.5 l/min
Special variants, in appliances without wash agent dispensers.
Required volume flow
4.4 gal/min
20 l/min
Max. volume flow in absence of hot and hard water
supply.
17.05 gal/min
77.5 l/min
Threaded connector fitting at site as per DIN 44 991 (flat sealing)
1“ external
thread
1“ external
thread
Length of connector hose
4’ 11 1/16”
1,500 mm
(included in delivery: 2 connector hoses + "Y" fitting)
Water requirement, standard connection with hot water connection in 60° program ( average value)
to be provided
to be provided In absence of hot water supply, add sufficient water to
reach required connection value.
In absence of hot water supply, add sufficient water to reach required connection value.
Hot water
(Soft water)
Max. temperature
158 °F
70 °C
Minimum flow pressure
14.5 psi
100 kPa
Maximum pressure
145.04 psi
1,000 kPa
Required volume flow
3.52 gal/min
16 l/min
Special variants, in appliances without wash agent dispensers.
Required volume flow
4.4 gal/min
20 l/min
Threaded connector fitting at site as per DIN 44 991 (flat sealing)
¾" external thread
¾" external thread
Length of connection hose
4’ 11 1/16”
1,500 mm
(included in delivery: 1 connector hose)
Water requirement, standard connection with hot water connection in 60° program ( average value)
to be provided
to be provided
If no hot water supply, connect the hose to the cold water supply!
Machine connections:
Installationsplan / Installation plan: PW 6163 EL
Datum / Date: 16.03.2011 Seite / Page: 10
Cold water
(Hard water)
Minimum flow pressure
14.5 psi
100 kPa
Maximum pressure
145.04 psi
1,000 kPa
Required volume flow
7.03 gal/min
32 l/min
Threaded connector fitting at site as per DIN 44 991 (flat sealing)
1“ external
thread
1“ external
thread
Length of connection hose
4’ 11 1/16”
1,500 mm
(included in delivery: 2 connector hoses + "Y" fitting)
Water requirement, standard connection with hot water connection in 60° program ( average value)
to be provided
to be provided
If no hard water supply, connect the hose to the cold water supply!
Cold water
Liquid dispensing
(Option)
Minimum flow pressure
14.5 psi
100 kPa
Maximum pressure
145.04 psi
1,000 kPa
Required volume flow
1.21 gal/min
5.5 l/min
Threaded connector fitting at site as per DIN 44 991 (flat sealing)
¾" external thread
¾" external thread
Length of connector hose
4’ 11 1/16”
1,500 mm
(included in delivery: 1 connector hose)
Drainage, version
with dump valve
Max. temperature
203°F
95 °C
Drainage supports in machine (outside diameter)
2 15/16” [DN
70]
75 mm [DN 70]
On-site drain (inner diameter)
2 15/16” [DN
70 sleeve]
75 mm [DN 70 sleeve]
Max. transient throughput
43.99 gal/min
200 l/min
Vented drainage required. Drain manifolds serving several machines must be of sufficient cross-section.
Venting the
machine
Machine side fittings for Miele vapor and foam discharge kit .
Machine vent
On-site vapor and machine vent line for connection of Miele vapor and foam discharge kit or Miele booster fan.
Potential
equalization
Externally threaded supports
3/8” x 1 3/8”
10 × 35 mm
with shims and nuts
10 M
10 M
If necessary, equipotential bonding with good galvanic contact must be created , in compliance with all applicable national installation specifications.
Anchorage
fittings (supplied)
without plinth
4 × wood screws DIN 571 (Ø × length)
1/2” x 3 9/16”
12 × 90 mm
4 × screw anchors (Ø × length)
5/8” x 3 1/8”
16 × 80 mm
Machine must be secured!
Floating floor fastening material to be provided on site .
Miele Base / Base with built-in weighing system
4 × wood screws DIN 571 (Ø × length)
1/2” x 3 9/16”
12 × 90 mm
4 × screw anchors (Ø × length)
5/8” x 3 1/8”
16 × 80 mm
Machine must be secured!
Floating floor fastening material to be provided on site .
MEL
Installationsplan / Installation plan: PW 6163 EL
Datum / Date: 16.03.2011 Seite / Page: 11
Machine data
Width
45 13/16”
1,164 mm
Depth
42 1/8”
1,070 mm
Height
67 5/8”
1,718 mm
Housing width
43 11/16”
1,110 mm
Housing depth
34 1/4”
870 mm
Housing height
67 1/8”
1,705 mm
Width loading opening (clear width)
42 15/16”
1,090 mm
Width of wall cutout (clear width)
45 1/4”
1,150 mm
Height of wall cutout (clear height)
67 15/16”
1,725 mm
Height of wall cutout with base (clear height)
74 5/8”
1,895 mm
Recommended lateral interval between units
23 5/8”
600 mm
Minimum lateral separation possible
11 13/16”
300 mm
When the minimum separation is chosen this may cause
customer service additional work when performing maintenance and repairs Complete technical installation is then to be checked on-site and modified as necessary.
Net weight
1400 lbs
634 kg
Max. floor loading in operation.
7.479 N
7.479 N
Max static loading
6.769 N
6.769 N
Max dynamic loading
710 N
710 N
Max. drum rotation frequency
16.3 Hz
16.3 Hz
Average heat dissipation in the installation room
(depending on room temperature and selected program)
to be provided
to be provided
Installation should only be carried out by authorized installers and must comply with local and national building codes. Observe installation instructions when installing this machine. Alteration rights reserved.
Installationsplan / Installation plan: PW 6163 EL
Datum / Date: 16.03.2011 Seite / Page: 12
Loading...