Midea Split Duct Air Conditioner Installation Manual

Page 1
INSTALLATION MANUAL
Split Duct Air Conditioner
Digital Scroll and DC/AC Inverter Commercial Air-conditioner
The Digital Scroll and DC/AC Inverter share the same indoor units.
Thank you very much for purchasing our air conditioner,
Before using your air conditioner, please read this manual carefully and keep it for future reference.
Page 2
The air conditioner must be installed by qualified persons.
When installing the indoor unit or its tubing, please follow this manual as strictly as possible.
When all the installation work is finished, please turn on the power only after a thorough check.
No further announcement if there is any change of this manual caused by product improvement.
Indoor Unit
Enough room for installation and maintenance.
The ceiling is horizontal and it can afford the weight of the indoor unit.
The air inlet and outlet are not impeded and does not affected by outdoor air too much.
The air flow can reach every part of the room.
The connecting pipe and drainpipe can be easily extracted out.
1. INSTALLATION PRECAUTION
2. INSTALLATION PLACE
1
installation manual
NOTE
The installor should illustrate to users how to correctly use and maintain the air-conditioner, as well as remind users to carefully read and keep both Installation Manual and Owner's Manual well.
There is no direct radiation from heat source.
Outdoor Unit
Enough room for installation and maintenance.
The air inlet and outlet are not impeded and does not affected by outdoor air too much.
Dry and well ventilated place.
The supporter is flat and horizontal and can afford the weigh of outdoor unit, without noise and vibration.
The noise and the outlet air will not influence your neighbor.
No combustible gas.
Place convenient for piping and wiring.
Please keep away from the following places, or malfunction may be caused.(if unavoidable, please consult the professionals):
There is mineral oil like the oil of cutting machine.
There is much salty air. (Near the coast)
There is caustic gas such as sulfuric gas. (Near the hotspring.)
Factory where the voltage fluctuate greatly.
In the car or in the cabin.
In the kitchen or a place full of oil steam.
There is strong electromagnetic wave.
There is combustible gas or materials.
There is much evaporating acid or alkaline gas.
Other special areas.
Notes Before Installation
Select the correct carry-in path.
Move this unit as originally packaged as possible.
If the air conditioner is installed on a metal part of the building, it must be electrically insulated according to the relevant standards to electrical appliances.
CONTENTS PAGE
INSTALLATION PRECAUTION..................................................................1
INSTALLATION PLACE............................................................................1
ACCESSORIES........................................................................................2
INTDOOR UNIT INSTALLATION ..............................................................2
INSTALLATION SPACE..........................................................................10
REFRIGERANT PIPE.............................................................................10
DUCT DESIGN.......................................................................................11
INSTALL THE CONNECTING PIPE..........................................................13
REFRIGERANT PIPE CONNECTION........................................................14
CONNECT THE DRAIN PIPE...................................................................15
WIRING.................................................................................................16
CONTROL..............................................................................................17
TROUBLE SHOOTING............................................................................18
INSTALL ELECTRIC THROTTLE PART....................................................19
INSTALL BRANCH PIPE.........................................................................19
TEST OPERATION..................................................................................19
DISPOSALDo not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of esperience and knowledge ,unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Disconnect the power supply before cleaning and maintenance.
CAUTION
Page 3
NOTE
Remark per EMC Directive 89/336/EEC
For to prevent flicker impressions during the start of the compressor (technical process), following installation condi­tions apply.
The power connection for the air conditioner has to be done at the main power distribution.The distribution has to be of a low impedance, normally the required impedance reaches at a 32A fusing point.
No other equipment has to be connected with this power line.
For detailed installation acceptance, please refer to your contract with the power supplier if restrictions do apply for products like washing machines, air conditioners or electrical ovens.
2
installation manual
Please refer to the following figure for the distance measurement between the screw bolts.
Please install with screw bolts.
The handling to the ceiling varies from the constructions, consult the construction personnels for the specific procedures.
The size of the ceiling to be handled.Do keep the ceiling flat. Con­solidate the roof beam for possible vibration.
Cut off the roof beam.
Strengthen the place cut off, and consolidate the roof beam.
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the operation, determine the direction of the pipes to be drawn out. Especially in case there is a ceiling, position the refrigerant pipes, drain pipes, indoor & outdoor lines to the connec­tion places before hanging up the machine.
The installation of hanging screw bolts.
Fig.4-1
Hanging screw bolt s
Ceiling
Timber over the beam
Roof beam
Put the square timber traversely overthe roof beam, then install the hanging screw bolts. (Refer to
Fig.4-1
)
Wooden construction
New concrete bricks
Fig.4-2
Inlaying or embedding the screw bolts (Refer to
Fig.4-2)
Blade shape insertion Slide insertion
Installing Φ10 Hanging Screw Bolts (4 Bolts)
4. INDOOR UNIT INSTALLATION
Cautions on remote controller installation
Never throw or beat the controller.
Before installation, operate the remote controller to determine its location in a reception range.
Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment. (It is necessary to prevent image disturbances or noise interferences.)
Do not install the remote controller in a place exposed to direct sunlight or close to a heatingsource, such as a stove. Note that the positive and negative poles are in right positions when loading batteries.
1. Remote controller.. ..................................1
2. Remote controller holder.........................1
3. Mounting screw
(ST2.9x10-C-H)........................................2
4. Alkaline dry battery(AM4)
..................................................................2
Remote controller & Its Frame
For power details of the air conditioner, refer to the rating plate of the product.
For any question contact your local dealer.
Table.3-1
1
1
1
Name of Accessories
Installation manual
KJR-10B Wire controller
Pipe insula­tion material
Adhesive tape for seal
Heat insulation
To connect drain pipe
Q‘ty
4
(This manual)
Outline
Usage
Wire
control the
air-conditioner
Clasp
Network matching wire
1
1
1
Water outlet joint
For drainage
Chucking the joint which connect the drain hose and the outlet of indoor unit
The indoor unit which at the terminal of communication system shouldconnect a impedance between port P and port Q
The following are selectable accessories
3. ACCESSORIES
7.1-16.0
20.0-28.0
2
2
3
Rem ote c ontr oller ho lder
Mou nting screw
Fig.3-1
1
Remote
controller
Page 4
3
installation manual
Overhanging the indoor unit
Overhang the indoor unit onto the hanging screw bolts with block.
Position the indoor unit in a flat level by using the level indicator, unless it may cause leakage.
Screw nut
Overhang part
washer
Hanging screw bolt
Fig.4-5
Fig.4-8
Fig.4-7
Fig.4-6
Install the main body
Installing the dust proof net and canvas air passage
Open the air-in grill Anti-clockwise the bolts as indicated in follow figure sketch.Then pull down the air-in grill.
Take out the air-in grill.
Dismantle the air filter
Clean the air filter (Vacuum cleaner or pure water may be used to clean the air filter. If the dust accumulation is too heavy , please use soft brush and mild detergent to clean it and dry out in cool place).
The air-in side should face down when using water. (See Fig.4-7)
Pipe Connection
The static pressure outside the unit is 200Pa , the length of the air pipe attached is determined by this parameter.
The positioning of ceiling hole and indoor unit and hanging screw bolts
Routine method of installation: the size of installation for indoor unit following Fig.4-9
Please install with Φ10 hanging screw bolts.
Carry out the pipe and line operation in the ceiling after finishing the installation of the main body. While choosing where to start the operation, determine the direction of the position the refrigerant pipes, drain pipes, indoor & outdoor lines and line­controlled lines to the connection places before.
For original concrete bricks
Steel roof beam structre
Fig.4-3
Fig.4-4
Steel bar
Embedding screw bolt
(Pipe hanging and embedding screw bolt)
Use embeding screw bold, crock and stick harmness (refer to
Fig.4-3)
Hanging scr ew b olt
Hanging bolts
Supporting
Install and use directly the supporting angle steel. (refer to
Fig.4-4)
angle steel
The air-in side should face up when using vacuum cleaner. (See Fig.4-8)
Page 5
4
installation manual
Fig.4-9
Fig.4-10
7.1~11.2KW/h
14~16KW/h
Unit: mm
Unit: mm
The positioning of ceiling hole and indoor unit and hanging screw bolts
routine method of installation: the size of installation for indoor unit following the Fig.4--9 and Fig.4-10
1073
64
31
82
339
82
AIR OUTLET
1300
6-Φ5 HOLES FOR AIR OUTLET DUCT CONNECTION
AIR OUTLET DUCT FLANGE
400
AIR INTAKE DUCT FLANGE
4-12*25 OBLONG SUSPENTION BOLT HOLES
AIR INTAKE
4-Φ5 HOLES FOR AIR OUTLET DUCT CONNECTION
400
65
15
37
638
600
17
253
638
14
136
69
90
15
50
800
1148
137
125
11
28
169
691
52
35
136
123
179
15
ELECTRICAL
CONTROL
BOX
PLASTIC COVER
930
135 88
24
46
68
82
82
56
270
420
249
29
72265
75
61
43
189123
642
420
85
856
214
86
800
44
253155
189123
26
255 33
65
REFRIGERANT-PIPE FLANED CONNECTION Φ16(5/8)
REFRIGERANT-PIPE FLANED CONNECTION Φ9.52(3/8)
PLASTIC COVER
ELECTRICAL CONTROL BOX
SAFETY DRAIN CONNECTING PIPE
CONNECTING POINT OF DRAIN PIPE
4-12*25 OBLONG SUSPENTION BOLT HOLES
AIR INTAKE
AIR OUTLET DUCT FLANGE
4-Φ5HOLES FOR AIR INTAKE DUCT CONNECTION
AIR OUTLET
339
75
61
43
189123
REFRIGERANT-PIPE FLANED CONNECTION Φ16(5/8)
REFRIGERANT-PIPE FLANED CONNECTION Φ9.52(3/8)
SAFETY DRAIN CONNECTING PIPE
CONNECTING POINT OF DRAIN PIPE
690
952
Page 6
5
installation manual
Fig.4-12
Fig.4-11
The method of installation: Adopt following method if the air-conditioning’s size of installationsite is limited and the indoor unit can’t put into the installtionsite.
7.1~11.2KW/h
Water Tray
Position A
Position B
11-Screw
Safety Drain Tray
1. The whole unit status show as Fig.4-11
2. Remove the all 11
screw
from fixed Safety Drain Tray, and then take off the tray as figure showed in Fig.5-11.
3. Take off the tray along the direction of the arrow show in Fig.4-12
4. Clean the tray and evaporator.
5. Re-install the unit follow the reverse above orders.
1. Please shut down the unit and cut off power cable before maintain the motor.
2. Don’t heavy pull the foam tray, when dismounting; otherwise the foam tray would break.
CAUTION
Page 7
4 Screw For fixing the reinforced panel
Side view of fan assembly installation state
Front view of fan assembly installation state
Fan assembly should push horizontally to the end (about 18mm), and then take o f f it.
The state after fan assembly is taken off
Fig.4-13
Fig.4-14
Inside of structure
FIiler
Motor Asseembly
Safety Drain Tray
11-Screw For fixing the satety drain tray
Fortified panel
Move 18mm
Move
Scroll
Pothook
4 Bolts For fixing the fan assembly
CA U TION
1. Refer to Fig.4- 1 3, remove all 1 1 bolts from safety drain tra y , and take o f f the safety drain tra y .
2. Refer to Fig.4- 1 3, remove all 4 bolts from reinforced panel, and take o f f the panel.
3. Refer to Fig.4-13, remove all 4 bolts from fan assembly, see Fig.4-14, accor ding to which orders to take off the fan assembly.
4. Refer to Fig.4-14, horizontal pushing the fan assembl y , until it cannot not move any furthe r , and then lift up slightly and take down to remove it.
5. After motor maintenance, reinstall the fan assemblies as per the reverse above orders. And connect the motor with electric control box, as motor with power cable of capacit y .
1. Please shut down the unit and cut o f f power cabl e before maintain the moto r .
2. Before dismount the fan assembl y , you must remove the motor and electric control box, as well a s connective wires between motor and capacity assembl y .
3. Fan subassembly is very heav y , please be carefu l during maintaining, otherwise physical injury would be caused.
maintenance of motor
maintenance of motor: :
6
installation manual
Page 8
12 Screw For fixing the safety drain tray
CAUTION
Fig.4-15
Fig.4-16
14~16kw/h
Water Tray
Position A
Position B
Safety Drain Tray
1. The whole unit status show as Fig.4-15.
2. Remove the all 1 1
screw
from fixed Safety Drain T ra y , and then take o f f the tray as figure showed in Fig.4-16.
3. T ake o f f the tray along the direction of the arrow show in Fig.4-16.
4. Clean the tray and evaporato r .
5. Re-install the unit follow the reverse above orders.
1. Please shut down the unit and cut o f f power cable before maintain the moto r .
2. Don’t heavy pull the foam tra y , when dismounting; otherwise the foam tray would break.
7
installation manual
Page 9
Side view of fan assembly installation state
Front view of fan assembly installation state
Fan assembly should push horizontally to the end (about 18mm), and then take o f f it.
The state after fan assembly is taken off
12-Screw For fixing the satety drain tray
4 Bolts For fixing the fan assembly
Fig.4-18
Fig.4-17
maintenance of motor
Inside of structure
Safety Drain Tray
Motor Assembly
Filter
Move 18mm
Move
Scroll
Pothook
CAUTION
1. Refer to Fig.4-17, remove all 1 1
screw
from safety drain tra y , and take o f f the safety drain tra y .
3. Refer to Fig.4-17, remove all 4 bolts from fan assembly, see Fig.4-18, accor ding to which orders to take off the fan assembly.
3. Refer to Fig.4-18, horizontal pushing the fan assembl y , until it cannot not move any furthe r , and then lift up slightly and take down to remove it.
4. After motor maintenance, reinstall the fan assemblies as per the reverse a bove orders. And connect the motor with electric control box, a s well as motor with power cable of capacity.
1. Please shut down the unit and cut o f f power cable before maintain the moto r .
2. Before dismount the fan assembl y , you must remove the motor and electric control box, as well as connective wires between motor and capacity assembl y .
3. Fan subassembly is very heav y , please be careful during maintaining, otherwise physical injury would be caused.
8
installation manual
Page 10
The method of installation: adopt following method if the air-conditioning’s size of installation site is limited and the indoor unit can’t put into the installation site.
Fig.4-19
Fig.4-20
Fig.4-21
1121
75
343
96
60
4-Φ10 hanging screw (configure on spot)
Connecting point of drain pipe
Air intake
Air outlet
Refrigerant-pipe flared connectionΦ16(5/8)
Refrigerant-pipe flared connectionΦ9.52(3/8)
Air outlet duct flange
4-12*25 oblong suspention bolt holes
Electrical parts box
Entrances and exits for communication lines of indoor and outdoor
Air intake duct flange
20KW/h 25KW/h 28KW/h
378
55
810
69
66
50
936
1275
1443
125 100
43
200
C
B
A
A
screw
cover plate A
cover plate B
Part A of indoor unit
Part B of indoor unit
bolt A
bolt C
470
9
installation manual
Page 11
10
installation manual
Confirm that there is enough room for installation and mainte­nance.
5. INSTALLATION SPACE
Fig.5-2
Fig.5-1
Maintenance roomage
Maintenance roomage
checking orifice
or more
60 0mmX60 0mm
500mm
or more
600mm
checking orifice
Confirm the minimum drain tilt is 1/100 or more
Cover the pipe before connecting to keep rubbish, dust or other impurities out.
6. REFRIGERANT PIPE
Gas side
Piping
Capaticyl(KW)
Piping material
Copper special for air conditioner
7.1/8/9/11.2/14/16/20/25/28
Φ16
Φ9.52
Liquid side
Table.6-1
The indoor unit show as
Fig.4-20
Following Fig.4-21 twist-off the screws, along the direction of A get off the cover plate A and cover plate B.
Dismounting bolt A
Dismounting bolt C
Along the direction of B and C divided the part B and part C of indoor unit.
The part A and part B of indoor unit individual put into the positionsite, then install the indoor unit following
the reverse
order of step 2,3,4 and 5.
Maintenance of motor
1
2
3
4
5
As figure dismounting the bolt of bottom,get down the bottom cover plate.
As figure dismounting 6 bolts in the front plate.
Support the fan subassembly from the bottom, then litter up, get down fan subassembly.
After finished maintenance of motor, then install the motor assembly in the reverse order of step 1,2 and 3.
During this process,the indoor unit don’t need dismounted.
1
2
3
4
5
6
Fig.4-12
bolt
motor assembly
bottom cover plate
screw
pothook
scroll
NOTE
During teardown and installation, the scroll was allowed direct
support by hand
Fan subassembly is more weightiness, please take careful
during teardown and installation, and keep from hurt by fan
subassembly.
Page 12
11
installation manual
Air outlet
Air inlet
Canvas tie-in Canvas tie-in
Air dust filter
checking orifice
Isolation booth
Isolation booth
Fig.7-1
Fig.7-3
NOTE
Other assemblies should be prepared on spot except air conditioner main body.
Cover the pipe before connecting to keep rubbish, dust or other impurities out.
As there is no dust filter on the indoor unit, other places which are easy to maintaining such as inhalant duct should be installed with dust filter. (Without dust filter, dust adherent on the air heat exchanger may cause failure and water-leak.
Key points of duct connection
7. DUCT DESIGN
High Static Pressure Type
240
260
280
300
2000
Q(m3/h)
5000
5500 6000
220
200
180
160
140
120
100
80
60
40
20
0
2500 3000 3500 4000 4500
P(Pa)
20KW/h(50hz) 25KW/h(50hz)
Low speed
Midium speed
High speed
Fig.7-2
240
260
280
300
2000
Q(m3/h)
5000 5500 6000
220
200
180
160
140
120
100
80
60
40
20
0
2500 3000 3500 4000 4500
P(Pa)
28KW/h
(50hz)
Low speed
Midium speed
High speed
Fig.7-4
240
260
280
300
1600 1800 2000
220
200
180
160
140
120
100
80
60
40
20
0
800 1000 1200 1400
P(Pa)
7.1/8.0KW/h
(50hz)
Low speed
Midium speed
High speed
Q(m3/h)
240
260
280
300
400
1600 1800 2000
220
200
180
160
140
120
100
80
60
40
20
0
600
800 1000 1200 1400
P(Pa)
9.0KW/h
(50hz)
Low speed
Midium speed
High speed
Fig.7-5
Q(m3/h)
240
260
280
300
400
Q(m3/h)
1600 1800
2000
220
200
180
160
140
120
100
80
60
40
20
0
600
800 1000 1200 1400
P(Pa)
11.2KW/h
(50hz)
Low speed
Midium speed
High speed
2200
Fig.7-6
Page 13
Panel installation
Unload inner frame. Slide the knob, release the buckle from the outside frame hole, then unload the inner frame.
Knob
Outside frame
Inside frame
Buckle
Hang the outside frame on the main body with face down. (4 places at 4 corners). Hang the belt on the hook of the main body.
Main body
Waist-shaped hole
fixed board
Canvas air passage
Ceiling
Outside frame
Fig.7-12
Hook
Fig.7-13
Fig.7-14
Outside frame
Belt
12
installation manual
240
260
280
300
1000
4000 4500
5000
220
200
180
160
140
120
100
80
60
40
20
0
1500
2000 2500 3000 3500
P(Pa)
14KW/h
(50Hz)
Low speed
Midium speed
High speed
5000
240
260
280
300
800
Q(m3/h)
2000 2200
2400
220
200
180
160
140
120
100
80
60
40
20
0
1000
1200 1400 1600 1800
P(Pa)
7.1KW/h
(60Hz)
8.0KW/h
(60Hz)
Low speed
Midium speed
High speed
2600
240
260
280
300
800
Q(m3/h)
2000 2200
2400
220
200
180
160
140
120
100
80
60
40
20
0
1000
1200 1400 1600 1800
P(Pa)
9.0KW/h
(60Hz)
11.2KW/h
(60Hz)
Low speed
Midium speed
High speed
2600
Heating capacity and cooling capacity are tested under the standard allowable min. static pressure; the 71 test static pressure is 25Pa, 80/90/112 test static pressure is 37Pa, 140/160 test static pressure is 50Pa.
Applicable scope of static pressure
50hz
60hz
7.1kW 8.0kW 9.0kW 11.2kW 14kW 16kW 20kW 25kW 28kW
100196Pa
100196Pa
100196Pa
75150Pa
110 ~220Pa
240
260
280
300
1000
Q(m3/h)
4000 4500
5000
220
200
180
160
140
120
100
80
60
40
20
0
1500
2000 2500 3000 3500
P(Pa)
14KW/h
(60Hz)
16KW/h
(60Hz)
Low speed
Midium speed
High speed
5500
Q(m3/h)
Q(m
3
/h)
240
260
280
300
1000
4000 4500
5000
220
200
180
160
140
120
100
80
60
40
20
0
1500
2000 2500 3000 3500
P(Pa)
16KW/h
(50Hz)
Low speed
Midium speed
High speed
5000
Fig.7-7
Fig.7-8
Fig.7-9
Fig.7-10
Fig.7-11
Page 14
Fix the main body and the outside frame with the fix board of waist-shape hole (in two places).
Hang one side of the fix board of the waist-shaped hole on the hook of the main body.
Tighten the other side of the board with screw to the outside frame.
Cut off the surplus part of the board with pliers.
Bend the top of the broken end.
Install the inner frame on the outside frame (the inverse sequence of unloading the inner frame).
NOTE
When hanging up the outside frame with the fix board of waist-shaped hole and the belt, stick the outside frame tightly to the ceiling and fix it.
Waist-shaped hole fixed board
Outside frame
Hook
Air passage
Fig.7-17
Fig.7-18
Bend
(Reverse side)
Outside frame
Air inlet
Inside frame
Fix the outside frame and the canvas air passage with screws. Screw must be fixed on from the bottom to the top.
Screw
Ceiling
Canvas air passage
Fig.7-15
NOTE
The signal wire of the remote control receiver must be drawn out through the canvas air passage.
Hang up the outside frame until it sticks to the ceiling tightly.
Canvas air passage
Ceiling
Outside frame
Air passage
Main body
Fig.7-16
Install remote controller.
Check whether the height drop between the indoor unit and outdoor unit, the length of refrigerant pipe, and the number of the bends meet the following requirements:
The max height drop and The length of refrigerant pipe deponding on the ouotdoor unit.(If the height drop is more than 10m, you had better put the outdoor unit over above the indoor unit.)
The number bends fewer than 15.
Do not let air, dust, or other impurities fall in the pipe system during the time of installation.
The connecting pipe should not be installed until the indoor and outdoor units have been fixed already.
Keep the connecting pipe dry, and do not let moisture in during installation.
The Procedure of Connecting Pipes Measure the necessary length of the connecting pipe, and make it by the following way.
Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Don,t harm them.
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4rounds with hands before fasten the flare nuts. (Refer to Fig.8-1)
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
The stop valve of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part of stop valve, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before connection.
Expel the air (refer to the “Expel The Air”) after connecting the refrigerant pipe with the indoor unit and the outdoor unit.Then fasten the nuts at the repair-points.
Notices For Benable pipe.
The bending angle should not exceed 90
Bending position is preferably in the bendable pipe. The larger the better it is .
Do not bend the pipe more than three times.
Bend the connecting pipe of small wall thickness.
Cut out a desired concave at the bending part of the insulating pipe.
8. INSTALL THE CONNECTING PIPE
Connect the remote control receiver with the indoor unit signal wires and fix it.
NOTE
13
installation manual
Page 15
Check all the joints with the leak detector or soap water. (See Fig.9-6 as a reference illustration)
Be sure to with insulating materials cover all the exposed parts of the flare pipe joints and refrigerant pipe on the liquid-side and the gas-side. Ensure that there is no gap between them.
Incomplete insulation may cause water condensation.
9.2 Check The Leakage
9.3 Insulation
B A
D
C
Check-point of indoor unit
Check-point of outdoor unit
A. Lo-stop valve B. Hi-stop valve C,D. Joints of the connecting pipe to the indoor unit.
Fig.9-2
9. REFRIGERANT PIPE CONNECTION
9.1 Expel The Air
Bend the pipe with thumb
Make the ends straight
Fig.9-1
Fig.8-3
Fig.8-2
Locate The Pipe
Drill a hole in the wall (suitable just for the size of the wall conduit, 90mm in general), then set on the fittings such as the wall conduit and its cover.
Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by condensation.
Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe all ocation to do no damage to the tubing.
Connect the pipes.
Then, open the stem of stop valves of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit fluently flow.
Be sure of no leakage by checking it with leak detector or soap water.
Cover the joint of the connecting pipe to the indoor unit with the sound proof/insulating sheath (fittings), and bind it well with the tapes to prevent leakage.
Flaring
Cut a pipe with a pipe cutter.
Insert a flare nut into a pipe and flare the pipe.
90
lean crude burr
Then expose the pipe(cover it with tapes after bending).
To prevent collapsing of deforming, please bend the pipe at its biggest radius.
Use bender to get a small radius pipes.
Use the market brass pipe. Be sure to use the same insulating materials when you buy the brass pipe. (More than 9mm thick)
Use frozen oil
Fig.8-1
14
installation manual
A
90+4
_
45+2
_
Outside diameter
A(mm)
Max
8.7 Φ6.4mm
Φ9.5mm
Φ12.7mm
Φ15.9mm
Φ19.1mm
12.4
15.8
19.0
23.3
8.3
12.0
15.4
18.6
22.9
Min
Table.9-1
Fig.9-3
Fig.9-4
Page 16
Install indoor unit drain pipe The outlet has PTI screw bread, Please use sealing materials and pipe sheath (fitting) when connecting PVC pipes.
10. CONNECT THE DRAIN PIPE
15
installation manual
All the stop valves should be opened before test operation. Each air conditioner has two stop valves of different sizes on the side of the outdoor unit which operate as Lo-stop value, respec­tively. (Refer to
Fig.9-6
)
Flare nut
Stopper
Cap
Valve body
Valve stem
Fig.9-6
Fig.9-5
-76 cmHg
Lo-lever
Hi-lever
Charge hose
Charge hose
Vacuum pump
Lo-lever
Manifold valve
Multi-meter
Pressure meter
The necessary filling amount of refrigerant
Refrigerant volume to be added is calculated according to outdoor unit installation manual .Be sure to add refrigerant measuring by a scale. L: The length of the pipe
Please record the quantity added and store it carefully for future maintenance.
Expel the air with a vacuum pump (Refer to
Fig.9-4
) (Please
refer to its manual for the way of using manifold valve)
Loosen and remove the maintenance nuts of stop valves A and B, and connect the charge hose of the manifold valve with the maintenance terminator of stop valve A. (Be sure that stop valves A and B are both closed)
Connect the joint of the charge hose with the vacuum pump.
Open the Lo-lever of the manifold valve completely.
Turn on the vacuum pump. At the beginning of pumping, loosen the maintenance terminator nut of stop valve B a little to check whether the air comes in (the sound of the pump changes, and the indicator of compound meter turns below zero). Then fasten the nut.
When the pumping has finished, close the Lo-lever of the manifold valve completely and turn off the vacuum pump.
When you have pumped for over 15 minutes, please confirm that the indicator of multimeter is on -1.0X105Pa (-76cmHg)
Loosen and remove the quadrangle cover of stop valves A and B to open stop valve A and B completely, then fasten them.
Disassemble the charge hose from the repair-mouth of stop valve A, and fasten the nut.
Torque Tubing size
14.4~17.2N.m
32.7~39.9N.m
49.5~60.3N.m
61.8~75.4N.m
92.7~118.6N.m
Φ6.4mm
Φ9.5mm
Φ12.7mm
Φ15.9mm
Φ19.1mm
Table.9-2
Bend
S shap
Fasten the nut Put the connecting tubing at the proper position, wrench the nuts with hands then fasten it with a wrench. (Refer to
Fig.9-4
Too large torque will harm the bellmouthing and too small will cause leakage. Please determine the torque according to Table.9-2.
The drain pipe of indoor unit must be heat insulated, or it will condense dew, as well as the connections of the indoor unit.
Hard PVC binder must be used for pipe connection, and make sure there is no leakage.
With the connection part to the indoor unit, please be noted not to impose pressure on the side of indoor unit pipes.
When the declivity of the drain pipe downwards is over 1/100, there should not be any win ding.
The total length of the drain pipe when pulled out traversely shall not exceed 20m, when the pipe is over long, a prop stand must be installed to prevent winding.
Refer to the figures on the right for the installation of the pipes.
CAUTION
Fig.10-1
1.5M~2M
Page 17
Attaching wiring
The air conditioner should use separate power supply with rated voltage.
The external power supply to the air conditioner should have ground wiring, which is linked to the ground wiring of the indoor and outdoor unit.
The wiring work should be done by qualified persons according to circuit drawing.
A leakage protector should be installed according to the National Standard concerning electrical appliance.
Be sure to locate the power wiring and the signal wring well to avoid cross-disturbance and their contact with connecting pipe or stop value body.
The wiring attached to this air conditioner is 10m long. Be sure to prolong it with wiring of the same type and proper length if necessary. Generally, do not twist two wiring together unless the joint is soldered well and covered with insulator tape.
Do not turn on the power until you have checked carefully after wiring.
11. WIRING
Capacity(KW)
200/250/280
16/10
2.5(<20 m)-4.0(<50 m)
2.0
0.75(<1200 m)
Circuit breaker/fuse (A)
Indoor unit power wiring (mm
2
)
Indoor/outdoor connecting wiring(mm2)
Ground wiring
Weak electric signal
Power
Phase
1-Phase
220-240V50Hz / 208-230V~60HZ
Frequency and volt
Table.11-1
A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
CAUTION
Fig.11-1
16
installation manual
Communication Wiring Chart
Communication wiring will be different according to the horse­power of air-condictioners. The wiring of 71T1 to 160T1 indoor unit, please refer to Fig.11-1, and Fig.11-2 is the communication wiring for 200T1, 250T1 and 280T1 indoor unit.
The reserved function is indicated in broken line table,users can select it when necessary.
CAUTION
NOTE
The air-conditioners can connect with Central Control Monitor (CCM). Before operation, please wiring correctly and set system address and network address of indoor units.
TO CCM
COMM.BUS
Please use 3-core shielding wire, and ground the shielding layer.
TO INDOOR POWER SUPPLY
220-240V~ 50Hz / 208-230V~60Hz
L
N
YELLOW/GREEN
2
INDOOR UNIT
TO INDOOR&OUTDOOR
COMM.BUS
Fig.11-3
1
Terminal board diagram
Please refer to the indoor unit wiring diagram for the detailed wiring. In accord with the communication wiring,
terminal board wiring is different according to the horsepower of air-condictioners. The wiring of 71T1 to 160T1 indoor unit, please refer to Fig.11-3, and Fig.11-4 is the wiring for 200T1, 250T1 and 280T1 indoor unit.
10/10
INDOOR UNI T
XT2 XT3
PQE
OUTDOOR UNI T
CENTRAL CONTROL MONITOR (CCM)
F1、F2、E
COMPUTER
XYE
INDOOR UNI T
XT2 XT3
INDOOR UNI T
XT2 XT3
XYE
PQE PQE
INDOOR UNI T
XT2 XT3
......
Fig.11-2
71/80/90/112/140/160
INDOOR UNI T
PQE
OUTDOOR UNI T
CENTRAL CONTROL MONITOR (CCM)
F1、F2、E
COMPUTER
XYE
INDOOR UNI T
XT2
INDOOR UNI T
XT2
XYE
PQE
INDOOR UNI T
XT2
......
XT2
The Specification of Power
Fig.10-2
Put as deep as possible (about 10mm)
Downward declivity lower than 1/100
VP30
Caution: While connecting the drain pipe, please use the drain pipe con­nect to the secondary water holder simultaneously, for avoiding there are little condensate water deposit in the unit when the machine is running under the high humidity working condition.
XYE
220-240V~50Hz
Page 18
Table.12-1
12. CONTROL
ENC1
POWER_S
0
0
1
2
F
F
3
E
4
D
5
C
6
B
7
A
8
9
Mainboard codes indication label
Fig.12-1
When V4+ outdoor unit set the code to be found address automatically, the new V4+ indoor unit do not need to set the indoor unit address, at this time the V4+ outdoor unit will distribute different addresses for indoor units automatically.
When V4+ outdoor unit set the code to be found address non-automatically, all the indoor units must set the system addresses by remote controller first (For the setting system address of indoor unit which has two or more main boards, it has to separate use the display board connected with ten­core connecting wire to set the address for each mainboard).
The setting of network address is through the communication of indoor and outdoor units, its address is the same as the indoor unit system address, and not need to set separate.
When all indoor units are V4+ series indoor unit, the central controlling of indoor unit can be finished in the outdoor unit, and not need to make central control in the indoor unit, the detail please refers to the V4+ outdoor unit instruction ma­nual;.
For the previous indoor unit’s central control function, can use (X, Y, E) terminal to connect and form the central control group, at this time there is not need to set the network address, and also can use outside setting network module, mainboard (CN20) to form network.
SW1
Difinition
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
SW1
ON
1234
 
1 means factory test mode
0 means auto addressing mode (default setting)
 
1 means DC fan is chosen 0 means AC fan is chosen
00 means DC fanstatic pressure is 0 (reserved)
reserved
J1, J2
Difinition
without jumper fo r auto restart function
"J1"
with jumper f or non-auto restart function
"J1"
J1
J1
J2
Horsepower code
ENC1
Toggle switch
Code
7
Capacity(Horsepower)
11200W(4.0HP)
12500W(5.0HP)
14000W(5.0HP)
For set horsepower
Note: The horsepower has been set before leaving the factory, anyone can’t modify it except the maintenance person.
A
6
5
4
3
2
1
0
8
9
2200W(0.8HP)
2800W(1.0HP)
3600W(1.2HP)
4500W(1.5HP)
5600W(2.0HP)
7100W(2.5HP)
8000W(3.0HP)
9000W(3.2HP)
10000W(4.0HP)
16000W(6.0HP)
TO CCM
COMM.BUS
Please use 3-core shielding wire, and ground the shielding layer.
TO INDOOR POWER SUPPLY
220-240V~ 50Hz
L
N
YELLOW/GREEN
INDOOR UNIT
TO INDOOR&OUTDOOR
COMM.BUS
TO CCM
COMM.BUS
TO NEXT INDOOR UNIT
Fig.11-4
01 means DC fanstatic pressure is 1 (reserved)
10 means DC fanstatic pressure is 2 (reserved)
11 means DC fanstatic pressure is 3 (reserved)
Base on different purposes to set the switch codes on the main boards of indoor unit, Once finish the setting, please cut off the main power, and then switch on the power again. Otherwise, setting functions could not work.
NOTE
200T1: Please dial switch ENC1 to 8 (both system A and B).
250T1: Please dial switch ENC1 to 9 for system A and 8 for system B.
280T1: Please dial switch ENC1 to 9 (both system A and B).
Network Address Setting
ENC1 is used for setting the refrigeration capacity(refer to Table.12-1 for different indoor unit) of the indoor unit.
Horsepower set
XT3
XT2
17
installation manual
TO INDOOR&OUTDOOR
COMM.BUS
Page 19
SW2
ON
1234
SW2
ON
1234 SW2
ON
1234
SW2
ON
1234
SW2
ON
1234 SW2
ON
1234
SW2
ON
1234
SW2
ON
1234
SW 2 Difinition
00 means shutting down the unit to “stop cold air” at 15
00 means the time of stopping TERMAL fan is 4 mintue
13. TROUBLE SHOOTING
18
installation manual
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW5
ON
1 2
SW7
ON
1 2
SW7
ON
1 2
ON
ON
SW5
Difinition
SW7
Difinition
0/1
Difinition
SW6
ON
1 2 3
SW6
ON
1 2 3
SW6
ON
1 2 3
00 means temp. compensation value is 6 under heat mode
1 means old display panel
1 means auto air blow under
auto mode
non-auto mode
reserved
standard configuration
last unit of the network
means 0
means 1
For 200T1 unit, two mainboards in the electric control should set the code ENC1 to 8;
For 250T1 unit, a mainboard in the electric control should set the code ENC1 to 8; the other one should set the code ENC1 to 9;
For 280T1 unit, two mainboards in the electric control should set the code to 9.
For the same indoor unit, every mainboard must be differ­ent indoor unit addresses and network addresses.
When using central controller to control the indoor unit, please pay attention to the address setting, as the 220T1, 250T1 and 280T1 units have two or more mainboards. We suggest setting the neighbor address for the mainboards in the same indoor unit. When using a central controller for controlling, mainboards in the same unit must be opened and closed at the same time, for avoiding the unexpected incident.
Table.13-1
NO. Type Contents
LED Lamp flash
Remarks
The evaporator sensor check point is abnoma or room temp. sensor is abnormal.
Indoor/outdoor unit communication is abnormal.
Condenser sensor check point is abnormal or outdoor temp. sensor is abnomal
Water level switch is abnormal
Mode conflict
Run lamp flashes at 2.5Hz.
The timer lamp flashes at
2.5Hz.
All the indoor alarm lamps flash at 0.5Hz.
Alarm lamp flashes at 2.5Hz.
Defrost lamp flashes at
2.5Hz.
After the malfunctions disappear, it restores automatically.
After the malfunctions disappear, it restores automatically.
After the malfunctions disappear, it restores automatically.
If the malfunctions can’t be solved in three min. all the indoor alarm lamps flash at 0.5Hz.Turn off the power to restore.
When the indoor unit turns to heating mode or is turned off, the alarm will disappear.
1
2
3
4
5
Malfun­ction
Malfun­ction
Malfun­ction
Malfun­ction
Alarm
7
6
Alarm
EPPROM error
The indoor unit without an add­ress when it is first time electri­fied
Malfun­ction
Defrost lamp flashes at
0.5Hz.
After the malfunctions disappear, it restores automatically.
Timer lamp and run lamp flash at 2.5Hz together.
After the malfunctions disappear, it restores automatically.
SW6 Difinition
CAUTION
Please adjust the code ENC1 to the suitable position (both system A and B should be adjusted for 200T1, 250T1 and 280T1 indoor unit).
01 means shutting down the unit to “stop cold air” at 20
10 means shutting down the unit to “stop cold air” at 24
11 means shutting down the unit to “stop cold air” at 26
01 means the time of stopping TERMAL fan is 8 mintue
10 means the time of stopping TERMAL fan is 12 mintue
11 means the time of stopping TERMAL fan is 16 mintue
01 means temp. compensation value is 2 under heat mode
10 means temp. compensation value is 4 under heat mode
11 means temp. compensation value is 8 under heat mode
0 means new display panel
0 means auto air blow under
Page 20
Please refer to the following figures to install.
14. INSTALL ELECTRIC THROTTLE PART
Connective Pipe 1
Connective Pipe 2
Fig.13-1
Fig.14-1
PRE-DEF indicator(cooling and heating type) or fan only indicator(cooling only type)
Infrared signal receiver
Operation lamp
Timer indicator
Alarm indicator
Temporary button
installation manual
Branch Part should be installed in horizontal mode or vertical mode.
15. INSTALL BRANCH PIPE
A
B
Install horizontally
Install vertically
Main pipe is vertical to horizontal plane
Fig.15-1
Fig.15-2
Fig.15-3
16. TEST OPERATION
The test operation must be carried out after the entire installation has been completed.
Please confirm the following points before the test operation:
The indoor unit and outdoor unit are installed properly.
Tubing and wiring are correctly completed.
The refrigerant pipe system is leakage-checked.
The drainage is unimpeded.
The heating insulation works well.
The ground wiring is connected correctly.
The length of the tubing and the added stow capacity of the refriger­ant have been recorded.
The power voltage fits the rated voltage of the air conditioner.
There is no obstacle at the outlet and inlet of the outdoor and indoor and indoor units
The gas-side and liqid-side stop vaule are both opened.
The air conditioner is pre-heated by turning on the power.
19
Low-pressure pipe
Hi-pressure pipe
Electric throttle part
Liquid branch pipe
Φ9.5
Φ9.5
Φ15.9
Φ15.9
Gas branch pipe
10m
Φ25.4
Φ12.7
According to the user’s requirement, install the remote controller frame where the remote controller’s signal can reach the indoor unit smoothly.
Test operation Set the air conditioner under the mode of “COOLING”with the remote controller, and check the following points per the “Owner’s Manual” If there is any malfunction, please resolve it through chapter “Troubles And Causes ”in the “Owner’sManual”.
The indoor unit
Whether the switch on the remote controller works well.
Whether the buttons on the remote controller works well.
Whether the air flow louver moves normally.
Whether the room temperature is adjusted well.
Whether the indicator lights normally.
Whether the temporary buttons works well.
Whether the drainage is normal.
Protection function will delay the startup of compressor for 3 minutes in case the unit is turned on immediately after power on or restarted after shutdown.
CAUTION
Whether there is vibration or abnormal noise during operation.
Whether the air conditioner heats well in the case of the HEATING/COOLING type.
The outdoor unit
Whether there is vibration or abnormal noise during operation.
Whether the generated wind, noise, or condensed water by the air conditioner have influenced your neighborhood.
Whether any of the refrigerant is leaked.
Loading...